Fire / smoke damper controller with airflow measurement · BACnet points list

FläktGroup OPTIVENT UltraSafe USFA control unit BACnet points list

Updated 12 November 2026

Short answer

The UltraSafe USFA control unit runs a fire/smoke damper with an ultrasonic airflow sensor and an optional duct smoke detector. Its BACnet objects report damper position, current and test results, airflow, temperature and smoke detector values, accept a flow setpoint, manual override, damper test start, external alarm and interlock commands and an alarm reset, and include status bitstrings, trend logs, a PI loop and notification classes.

This page lists 74 BACnet objects for the FläktGroup OPTIVENT UltraSafe USFA control unit — 24 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from FläktGroup’s own free documentation, linked below.

Manufacturer
FläktGroup
Model
OPTIVENT UltraSafe USFA control unit
Equipment
Fire / smoke damper controller with airflow measurement
Equipment type
Thermostats, sensors & meters
BACnet objects
74 (24 writable)
Transport
—
Firmware
Not stated
Also known as
UltraSafe USFA, USFA, OPTIVENT UltraSafe, Ultrasafe, DC_10786GB, Flakt UltraSafe BACnet
Source document
OPTIVENT UltraSafe USFA Control Unit BACnet Objects · DC_10786GB 20231115_R0 · rev. 2023-11-15
Download CSV 74 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against FläktGroup’s current documentation and the live device before use. Not official FläktGroup information. Terms of use.

BMS integration notes: FläktGroup OPTIVENT UltraSafe USFA control unit

Integration in brief

Read the machine state, damper position, airflow and the fire, fault and service alarm bits. If the BMS sets airflow, set BV 8 to Bus and write AV 2; BV 2 starts a damper test and BV 1 resets alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 2Volume flow setpointRelative airflow setpoint, %Write
BV 8Air flow setpoint sourceActive = Bus: BMS supplies the flow setpointWrite
BV 2Damper testStart a damper testWrite
BV 1Alarm & Event resetReset alarms and eventsWrite
MI 1Machine stateUnit state (normal, damper test, fault, interlock)Read
AI 11Damper positionDamper position, %Read
AI 23Volume flow relativeRelative airflow, %Read
MI 2Smoke detector stateSmoke detector state incl. fire alarmRead
BI 4Damper failureDamper failureRead
BI 1Service alarmService alarm activeRead

Sensors & values from the BMS

BV 8 Air flow setpoint source selects Analog (analog input 1) or Bus; on Bus the BMS writes AV 2 Volume flow setpoint.

Watch out for

FläktGroup OPTIVENT UltraSafe USFA control unit BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

74 of 74 shown
Type
Access
Show
FläktGroup OPTIVENT UltraSafe USFA control unit BACnet Points List
DescriptionStates
AI1Air duct sizeNominal duct size, 0-315Read
AI2Air duct size effectiveEffective duct size, 0-315Read
AI3Analog output 1Analog output 1 value, 0-10.00Read
AI4Analog output 2Analog output 2 value, 0-10.00Read
AI5Damper currentDamper current, 0-2500Read
AI6Damper current open AVGAverage opening current on last damper testRead
AI8Damper current open maximumPeak opening current on last damper testRead
AI10Damper driving signalActuator control voltage, 0-10.00 (close <6 V, open >6 V)Read
AImin11Damper positionRelative damper position, 0.1-100.0Read
AI12Damper time closeClosing time on last damper testRead
AI14Damper time openOpening time on last damper testRead
AI16Damper voltageDamper position feedback signal, 0-10000Read
AI17Smoke detector currentSmoke detector current, 0-520.0Read
AI18Smoke detector voltageSmoke detector voltage, 0-10000Read
AI19TemperatureAir temperature, -35.0 to 70.0Read
AI22Volume flow absoluteAbsolute air volume flowRead
AImin23Volume flow relativeRelative air volume flow, 0.1-100.0Read
AI24Setpoint via analog input 1Analog input 1 value, 0-10000Read
AI25PI control active valuePI controller output, relativeRead
AI26PI control active setpointPI controller relative flow setpointRead
AV1Analog output 2 overrideOutput 2 value when its function is Not usedWrite
AVmin2Volume flow setpointRelative air volume flow setpoint, 0.1-100.0Write
AV7Damper min. driving signalDamper minimum control voltageWrite
AV8Damper close timeoutDamper closing timeoutWrite
AV9Damper open timeoutDamper opening timeoutWrite
AV17Smoke detector fire thresholdSmoke detector fire alarm thresholdWrite
AV18Smoke detector service thresholdService alarm threshold (Custom detector type)Write
AV21Volume flow attenuationFlow monitoring value filteringWrite
AV22Volume flow betweenIntermediate air volume flowWrite
AV23Volume flow maximumMaximum air volume flowWrite
AV24Volume flow minimumMinimum air volume flowWrite
AV25Volume flow nominalNominal air volume flowRead
BImin1Service alarmService alarmReadInactive=inactive; Active=active
BI2Damper test activeDamper test runningReadInactive=inactive; Active=active
BI3Damper test failureDamper test failedReadInactive=inactive; Active=active
BImin4Damper failureDamper failureReadInactive=inactive; Active=active
BVmin1Alarm & Event resetResets alarms and eventsWriteInactive=inactive; Active=active
BVmin2Damper testStarts a damper testWriteInactive=inactive; Active=start
BV3External AlarmExternal alarm triggerWriteInactive=inactive; Active=active
BV4External InterlockExternal interlock triggerWriteInactive=inactive; Active=active
BV5UltraSonic zero-calibrationStarts ultrasonic zero calibrationWriteInactive=inactive; Active=start
BV6UltraSonic factory-resetStarts ultrasonic sensor factory resetWriteInactive=inactive; Active=reset
BV7External fire damper control systemAn external fire control system is usedWriteInactive=inactive; Active=active
BVmin8Air flow setpoint sourceFlow setpoint sourceWriteInactive=Analog; Active=Bus
BV17Smoke detectorSmoke detector activationWriteInactive=enable; Active=disable
BV18Smoke detector sourceSmoke detector signal typeWriteInactive=voltage; Active=current
Other0Digital input statesBitString Value: Digital input states (bits DI 1-3)Read
Other1Digital output statesBitString Value: Digital output states (bit field)Read
Other2UltraSonic statesBitString Value: Ultrasonic sensor state bitsRead
Other3Event statesBitString Value: Unit event bits (32)Read
Other4Fire alarm statesBitString Value: Fire signal source bits: bus, DI, smoke detector, motor fuseRead
Other5Fault statesBitString Value: Fault bitsRead
Other6Service alarm statesBitString Value: Service alarm bitsRead
Other7Interlock statesBitString Value: Interlock source bits: DI, busRead
Other8Damper test start conditionBitString Value: Damper test trigger source bitsRead
MImin1Machine stateUnit operating stateRead1=Initialization; 2=Waiting for zero-calibration; 3=Zero-calibration active; 4=Normal operation; 5=Damper test initial opening; 6=Damper test closing by spring-force; 7=Damper test final opening; 8=Fault; 9=Interlock
MImin2Smoke detector stateSmoke detector stateRead1=normal operation; 2=not configured; 3=service alarm; 4=fire alarm; 5=short circuit; 6=open loop
MI3UltraSonic calibrationSensor calibration statusRead1=inactive; 2=sensor need calibration; 3=calibration active
MV1Override controlManual damper overrideWrite1=No override control; 2=Open; 3=Close; 4=Vmin; 5=Vbtw; 6=Vmax
MV4Damper test resultResult of the last damper testWrite1=Not performed; 2=Successful; 3=Open limit switch failure (initialization); 4=Closed limit switch failure; 5=Open limit switch failure; 6=Open & closed limit switch failure; 7=Damper test interrupted; 8=Damper test in progress
IV1UltraSonic version majorUltrasonic sensor firmware, majorRead
IV2UltraSonic version minorUltrasonic sensor firmware, minorRead
TL1Damper time close logTrend log: Closing time after each successful testRead
TL2Damper time open logTrend log: Opening time after each successful testRead
TL3Damper current open AVG logTrend log: Average opening current after each successful testRead
TL4Damper current open maximum logTrend log: Maximum opening current after each successful testRead
TL5Volume flow setpoint logTrend log: Volume flow setpointRead
TL6Volume flow setpoint via AI 1 logTrend log: Flow setpoint from analog input 1Read
LO0Damper PI controlDamper PI control loopWrite
NC10NC-10 - Danger notification (Life Safety)Danger to lifeRead
NC30NC-30 - Alarm tripping notificationSystem failure / immediate attentionRead
NC50NC-50 - Maintenance notificationMaintenance indicationRead
NC80NC-80 - Operating notificationOperating notificationsRead
NC90NC-90 - Damper testDamper test notificationsRead
Object ID lookup: FläktGroup OPTIVENT UltraSafe USFA control unit point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the OPTIVENT UltraSafe USFA control unit and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the FläktGroup OPTIVENT UltraSafe USFA control unit

How many BACnet points does the FläktGroup OPTIVENT UltraSafe USFA control unit have?

This list has 74 BACnet objects: 20 analog inputs, 12 analog values, 4 binary inputs, 10 binary values, 1 loop, 3 multi-state inputs, 5 notification classs, 2 multi-state values, 6 trend logs, 2 integer values, 9 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which FläktGroup OPTIVENT UltraSafe USFA control unit BACnet points are writable?

24 of the 74 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official FläktGroup OPTIVENT UltraSafe USFA control unit BACnet documentation?

The source is OPTIVENT UltraSafe USFA Control Unit BACnet Objects (DC_10786GB 20231115_R0), revision 2023-11-15, published free by FläktGroup at https://www.flaktgroup.com/api/v1/Documents/1359816/Download.

What are the minimum BACnet points to integrate the FläktGroup OPTIVENT UltraSafe USFA control unit?

Start with AV 2 Volume flow setpoint (Relative airflow setpoint, %); BV 8 Air flow setpoint source (Active = Bus: BMS supplies the flow setpoint); BV 2 Damper test (Start a damper test); BV 1 Alarm & Event reset (Reset alarms and events); MI 1 Machine state (Unit state (normal, damper test, fault, interlock)); AI 11 Damper position (Damper position, %); AI 23 Volume flow relative (Relative airflow, %); MI 2 Smoke detector state (Smoke detector state incl. fire alarm); BI 4 Damper failure (Damper failure); BI 1 Service alarm (Service alarm active).

Can the BMS supply sensor values to the FläktGroup OPTIVENT UltraSafe USFA control unit?

BV 8 Air flow setpoint source selects Analog (analog input 1) or Bus; on Bus the BMS writes AV 2 Volume flow setpoint.

How do I check these points on the real OPTIVENT UltraSafe USFA control unit?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More FläktGroup BACnet points lists

Source: OPTIVENT UltraSafe USFA Control Unit BACnet Objects · DC_10786GB 20231115_R0 · rev. 2023-11-15. Object names, instances and units are reproduced as published; descriptions are our own.