Air handling unit controller (Climatix) · BACnet points list

FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V2.xx BACnet points list

Updated 12 November 2026

Short answer

eQ air handling units use a Siemens Climatix POL6xx controller; a plug-in Climatix BACnet IP (POL908) or MS/TP (POL904) module exposes the eQ Fläkt V2.xx application. The list covers temperatures, pressures, flows, fan data, coil and heat-recovery output signals, setpoints and PID parameters, alarm inputs and values, operating mode and status multistates, schedules and calendars.

This page lists 584 BACnet objects for the FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V2.xx — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from FläktGroup’s own free documentation, linked below.

Manufacturer
FläktGroup
Model
eQ AHU controls (Climatix), application eQ Fläkt AHU V2.xx
Equipment
Air handling unit controller (Climatix)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
584 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
eQ, eQ Flakt V2, eQ Fläkt AHU V2.xx, Climatix eQ, DC_10159GB, POL908, POL904
Source document
eQ Controls - Climatix BACnet communication module, Installation and maintenance instruction (BACnet objects of eQ Fläkt V2.xx) · DC_10159GB 20180823_R0 · rev. 2018-08-23
Download CSV 584 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against FläktGroup’s current documentation and the live device before use. Not official FläktGroup information. Terms of use.

BMS integration notes: FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V2.xx

Integration in brief

Fit a Climatix BACnet IP (POL908) or MS/TP (POL904) module, set its network parameters on the controller and export the EDE file. Command the unit with the BMS time-switch-program objects (OpModeBmsTimeStSwtch or the steps/temperature variant) and the bus setpoint, then read operating mode, status, temperatures, fan signals and the alarm-class objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 8442OpModeBmsTimeStSwtchBMS operating command: 0 Auto, 1 Off, 2-4 stage 1-3Read
AV 1884ExtSetpointSpvCOMTemperature setpoint written over the bus, °CRead
MV 6080ActOpModeActual operating mode (off, comfort, economy...)Read
MV 32321ActOpStaActual operation status / stop reasonRead
AI 45150SupplyTmpSupply air temperatureRead
AI 28256ReturnAirTmpExtract air temperatureRead
AI 53218OutTmpOutdoor air temperatureRead
AO 59037SplyFanVarPosSupply fan output signal, 0-100 %Read
MV 42640AlmCl1Critical (A) alarm class activeRead
MV 38643AlmCl2Low (B) alarm class activeRead

Enable & remote start

The document gives no access column. OpModeBmsTimeStSwtch (steps) and OpModeBmsTimeStTmpSwtch (steps/temperature) are the BMS time-switch-program commands (0 = Auto follows the unit's own program); which one applies depends on the unit's control mode.

Sensors & values from the BMS

ExtSetpointSpvCOM (AV 1884) is the external setpoint value from communication; the AI ExtSetpointSpv is the hard-wired external setpoint input.

Network setup

Watch out for

FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V2.xx BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

584 of 584 shown
Type
Show
FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V2.xx BACnet Points List
DescriptionStates
AI115AuxTmpAuxiliary temperature°CRead
AI28023BalPrsPressure balancingPaRead
AI23945CoilWtrTmpCombi coil 1 wtr temperature°CRead
AI10582ExFilterExtract air filter sensorPaRead
AI40895ExhaustTmpExhaust air temperature°CRead
AI32361ExhFan_DCLCurrentSupply fan DCL Current (SW 2.52+)ARead
AI9232ExhFan_DCLVoltageSupply fan DCL Voltage (SW 2.52+)VRead
AI41627ExhFan_FanSpeedExhaust fan speed (SW 2.52+)rpmRead
AI58193ExhFan_MaxSpeedExhaust fan max speed (SW 2.52+)rpmRead
AI12204ExhFan_ModTempExhaust fan mod temperature (SW 2.52+)°CRead
AI11254ExhFan_MotTempExhaust fan mot temperature (SW 2.52+)°CRead
AI6069ExhFan_OpTimeExhaust fan - Operating time (SW 2.52+)Read
AI8243ExhFan_OpTimeHHExhaust fan - Operating time, hours (SW 2.52+)hRead
AI36707ExhFan_OpTimeMMExhaust fan - Operating time, minutes (SW 2.52+)minRead
AI2311ExhFan_PCBTempExhaust fan PCB temperature (SW 2.52+)°CRead
AI42634ExhFan_PowerExhaust fan Power (SW 2.52+)WRead
AI48207ExhFanExtSpvExhaust fan external setpointPa or l/s depending on fan control type.Read
AI19767ExPreFilterExtract air pre-filter sensorPaRead
AI4854ExtraFrstTmpExtra heating frost temperature°CRead
AI20915ExtraSupplyTmpSupply air temperature 2°CRead
AI12205ExtSetpointSpvExternal setpoint°CRead
AI39125HrecFrstPrsHeat recovery frost pressurePaRead
AI50488HrecInTakePrsHeat exchanger pressure dropPaRead
AI44798HrecSupplyTmpHeat recovery supply air temp°CRead
AI12446HrecWtrTmpHeat recovery water temperature°CRead
AI50341HtgFrstTmpHeating frost temperature°CRead
AI45222OutHumOutdoor air relative humidity%RHRead
AImin53218OutTmpOutdoor air temperature°CRead
AI49723OutTmpWallOutdoor wall temperature sensor°CRead
AImin28256ReturnAirTmpExtract air temperature°CRead
AI38593ReturnFlowExhaust air flowl/sRead
AI39576ReturnPrsExhaust air pressurePaRead
AI37799RoomHumRoom relative humidity%RHRead
AI60643RoomTmpRoom temperature°CRead
AI51635RoomTmp2Room temperature 2°CRead
AI56927SplyFan_DCLCurrentSupply fan DCL Current (SW 2.52+)ARead
AI33830SplyFan_DCLVoltageSupply fan DCL Voltage (SW 2.52+)VRead
AI48513SplyFan_FanSpeedSupply fan speed (SW 2.52+)rpmRead
AI64587SplyFan_MaxSpeedSupply fan max speed (SW 2.52+)rpmRead
AI28696SplyFan_ModTempSupply fan mod temperature (SW 2.52+)°CRead
AI29762SplyFan_MotTempSupply fan mot temperature (SW 2.52+)°CRead
AI8364SplyFan_OpTimeSupply fan - Operating time (SW 2.52+)Read
AI16169SplyFan_OpTimeHHSupply fan - Operating time, hours (SW 2.52+)hRead
AI36985SplyFan_OpTimeMMSupply fan - Operating time, minutes (SW 2.52+)minRead
AI22195SplyFan_PCBTempSupply fan PCB temperature (SW 2.52+)°CRead
AI39978SplyFan_PowerSupply fan Power (SW 2.52+)WRead
AI30575SplyFanExtSpvSupply fan external setpointPa or l/s depending on fan control type.Read
AI59395SplyFilterOutdoor air filter sensorPaRead
AI44474SplyPreFilterOutdoor air pre-filter sensorPaRead
AI9497SupplyFlowSupply air flowl/sRead
AI53018SupplyHumSupply air relative humidity%RHRead
AI20400SupplyPrsSupply air pressurePaRead
AImin45150SupplyTmpSupply air temperature (values column printed 0=Ok / 1=Alarm)Read
AO22813AuxOutputAuxiliary analog output fan0-100%Read
AO57034BalanceCntrlPosPressure balancing extract damper controller output signal%Read
AO38455BalCtlrSplyPosMixing outdoor damper controller output signal%Read
AO45643CoolingPmpVarPosCooling 1 pump output signal0-100%Read
AO30925CoolingPosCooling output signal0-100%Read
AO37442ElectricalHtgPosElectrical heating output signal0-100%Read
AO40119ExhFanVarPosExhaust fan output signal0-100%Read
AO59738ExtraClgPmpVarPosExtra cooling pump output signal0-100%Read
AO60283ExtraClgPosExtra cooling output signal0-100%Read
AO45777ExtraElHtgPosExtra electrical heating output signal0-100%Read
AO166ExtraHtgPmpVarPosExtra heating pump output signal0-100%Read
AO46994ExtraHtgPosExtra heating output signal0-100%Read
AO34442HeatingPmpVarPosHeating pump output signal0-100%Read
AO26209HeatingPosHeating output signal0-100%Read
AO49662HrecDampPosHeat recovery damper output signal0-100%Read
AO29755HrecPmpVarPosHeat recovery pump output signal0-100%Read
AO5922HrecPosHeat recovery output signal0-100%Read
AO39618HumidityCtrlPosHumidifier output signal0-100%Read
AO23338ReCoolingPosReCooler cooling output signal%Read
AO17798ReHeatingPosReCooler heating output signal%Read
AOmin59037SplyFanVarPosSupply fan output signal0-100%Read
AV2735ActCascSpvClgActual supply cooling setpoint (when use of cascade control)°CRead
AV50248ActCascSpvDehActual supply dehumidification setpoint for humidification%RHRead
AV28804ActCascSpvHtgActual supply heating setpoint (when use of cascade control)°CRead
AV58111ActCascSpvHumActual supply humidification setpoint%RHRead
AV52988ActCtrlValActual controlled temperature°CRead
AV38385ActCtrlValHumActual controlled humidification%RHRead
AV30105ActMainSpvClgActual cooling setpoint, Main (depending on actual control mode)°CRead
AV47998ActMainSpvDehActual dehumidification setpoint for humidification%RHRead
AV4018ActMainSpvHtgActual heating setpoint, Main (depending on actual control mode)°CRead
AV40393ActMainSpvHumActual humidification setpoint%RHRead
AV3315ActvClgRecDevActivate cooling recovery - Temperature differenceKRead
AV21855AirQCmpCtrLoopKpAir quality compensation - Proportional factor (SW 2.62+)Read
AV21857AirQCmpCtrLoopTDAir quality compensation - Differential factor (SW 2.62+)sRead
AV21856AirQCmpCtrLoopTIAir quality compensation - Integral factor (SW 2.62+)sRead
AV10236AirQCmpPrValActual air quality compensation0-100%Read
AV22649AirQSpvAir quality setpointppmRead
AV3737AirQualityAir qualityppmRead
AV1899AlmAckBtnCOMAlarm Ack button - Value comm. (SW 2.62+)Read0=Off; 1=On
AV2429BalCtlrSplyLowLimitBalance control - Min pressure outdoor damperPaRead
AV31736BalDmpMaxTmBalance control - Max timesRead
AV5939BalDmpTmBalance control - Force damper at start timesRead
AV49991BalMaxDevBalance control - Max pressure deviationPaRead
AV28570BalPrsLowLmtBalance control - Min pressure extract damper%Read
AV22141BalPrsSpBalance control - Pressure setpointPaRead
AV228BlkClgRecDevBlock cooling recovery - Temperature differenceKRead
AV33121BlkHtgRecDevBlock heat recovery - Temperature differenceKRead
AV44092BoostClgSpvBoost cooling setpoint°CRead
AV27113BoostHtgSpvBoost heating setpoint°CRead
AV3510BoostPreStrtTmBoost pre-start timeminRead
AV13266BoostRmSpvBoost room temperature setpoint°CRead
AV17241CalibrationActvTmCalibration - Time delaysRead
AV34380CalibrationExhFanStartCalibration - Q-min exhaust fan startl/sRead
AV46866CalibrationExhFanStopCalibration - Q-min exhaust fan stopl/sRead
AV32048CalibrationMaxDevCalibration - Maximum deviationl/sRead
AV38555CalibrationQCalibration Ql/sRead
AV38027CalibrationQExhCalibration Q Exhaustl/sRead
AV59099CalibrationQRedCalibration - Reduce Q%Read
AV54865CalibrationQRtCalibration Q Extractl/sRead
AV48462CalibrationStoPmaxCalibration - P-max pressure heat exchangerPaRead
AV17936CalibrationStoPminCalibration - P-min pressure heat exchangerPaRead
AV52218CalibrationStoQmaxCalibration - Q-max flow heat exchangerl/sRead
AV12452CalibrationStoQminCalibration - Q-min flow heat exchangerl/sRead
AV57930CascFlowLmtMaxDevLmtDraught heating max deviation°CRead
AV27342CascFlowLmtMinDevLmtDraught cooling max deviation°CRead
AV40280CG_EM24_1ActPowerEnergy actual powerWRead
AV36000CG_EM24_1AvePowerEnergy save powerWRead
AV49048CG_EM24_1OpHoursEnergy operating hourshRead
AV19610CG_EM24_1ParEnergyEnergy partialkWhRead
AV61249CG_EM24_1TotEnergyEnergy totalkWhRead
AV875ClgPmpActiveHourCooling pump - Operating hours (SW 2.56+)hRead
AV21849ClgReClgCtrLoopKpReCooler cooling controller - Proportional factor (SW 2.62+)Read
AV21851ClgReClgCtrLoopTDReCooler cooling controller - Differential factor (SW 2.62+)sRead
AV21850ClgReClgCtrLoopTIReCooler cooling controller - Integral factor (SW 2.62+)sRead
AV21807CoolingCtrLoopKpCooling - Proportional factor (SW 2.62+)Read
AV21809CoolingCtrLoopTDCooling - Differential factor (SW 2.62+)sRead
AV21808CoolingCtrLoopTICooling - Integral factor (SW 2.62+)sRead
AV16471CoolingOffTmpCooling 1 disable by outdoor temperature°CRead
AV18421CounterFlowExchangerX1Counter flow heat exchanger - X1°CRead
AV30614CounterFlowExchangerX2Counter flow heat exchanger - X2°CRead
AV29892CounterFlowExchangerY1Counter flow heat exchanger - Y1%Read
AV17575CounterFlowExchangerY2Counter flow heat exchanger - Y2%Read
AV21825CRecDamperCtrLoopKpMixing damper cooling recovery controller - Proportional factor (SW 2.62+)Read
AV21827CRecDamperCtrLoopTDMixing damper cooling recovery controller - Differential factor (SW 2.62+)sRead
AV21826CRecDamperCtrLoopTIMixing damper cooling recovery controller - Integral factor (SW 2.62+)sRead
AV33908CrecDampRecMixing damper cooling recovery output signal%Read
AV28660DeFrstMxSpdHeat exchanger defrost max output signal°CRead
AV21939DehumidificationCtrLoopKpDehumidification - Proportional factor (SW 2.62+)Read
AV21941DehumidificationCtrLoopTDDehumidification - Differential factor (SW 2.62+)sRead
AV21940DehumidificationCtrLoopTIDehumidification - Integral factor (SW 2.62+)sRead
AV18150DehumidificationPrValActual dehumidification value0-100%Read
AV21292DewpointSupply dew point°CRead
AV41175DewpointDzDew point - Neutral zone°CRead
AV876ExClgPmpActiveHourExtra cooling pump - Operating hours (SW 2.56+)hRead
AV45194ExFilterPreAlmExtract air filter Pre-alarmPaRead
AV871ExhFanActiveHourExhaust fan - Operating hours (SW 2.56+)hRead
AV33255ExhFanActSpvActual exhaust fan setpointl/sRead
AV59694ExhFanActValActual exhaust fan valueRead
AV52288ExhFanCurrentDanfoss / OJ-DV Exhaust fan current (SW 2.52+)ARead
AV56254ExhFanDevAlmMaxDevExhaust fan - Maximum deviation (flow control)%, Pa or l/s depending on configurationRead
AV54886ExhFanDevAlmMaxDevPrsExhaust fan - Maximum deviation (pressure control)PaRead
AV58855ExhFanDevAlmMinLmtExhaust fan - Minimum limit (flow control)Read
AV48357ExhFanDevAlmMinLmtPrsExhaust fan - Minimum limit (pressure control)PaRead
AV7102ExhFanEnergyDanfoss exhaust fan Energy (SW 2.52+)kWhRead
AV14530ExhFanMotorVoltDanfoss / OJ-DV Exhaust fan motor voltage (SW 2.52+)VRead
AV36017ExhFanOpDaysDanfoss / OJ-DV Exhaust fan - Operating days (SW 2.52+)daysRead
AV27013ExhFanOpHrsDanfoss / OJ-DV Exhaust fan - Operating hours (SW 2.52+)hRead
AV49021ExhFanOpMinutesDanfoss / OJ-DV Exhaust fan - Operating minutes (SW 2.52+)minRead
AV65306ExhFanOutFreqDanfoss / OJ-DV Exhaust fan frequency (SW 2.52+)HzRead
AV42046ExhFanPowerDanfoss / OJ-DV Exhaust fan power (SW 2.52+)kWRead
AV55707ExhFanPrcOutDanfoss / OJ-DV Exhaust fan output signal (SW 2.52+)%Read
AV55889ExhFanSpeedDanfoss / OJ-DV Exhaust fan speed (SW 2.52+)rpmRead
AV2525ExhFanSpvMaxForceExhaust fan max force setpoint%, Pa or l/s depending on configurationRead
AV45030ExhFanSpvSt1SpvExhaust fan step 1 setpoint%, Pa or l/s depending on configurationRead
AV13370ExhFanSpvSt2SpvExhaust fan step 2 setpoint%, Pa or l/s depending on configurationRead
AV17038ExhFanSpvSt3SpvExhaust fan step 3 setpoint%, Pa or l/s depending on configurationRead
AV1908ExhOJEngyCOMOJ-DV Exhaust fan energy (SW 2.52+)kWhRead
AV874ExHtgPmpActiveHourExtra heating pump - Operating hours (SW 2.56+)hRead
AV23230ExPreFilterPreAlmExtract air pre-filter Pre-alarmPaRead
AV4853ExtControlDlyOfTmExt ctrl off delayhRead
AV21813ExtCoolingCtrLoopKpExtra cooling - Proportional factor (SW 2.62+)Read
AV21815ExtCoolingCtrLoopTDExtra cooling - Differential factor (SW 2.62+)sRead
AV21814ExtCoolingCtrLoopTIExtra cooling - Integral factor (SW 2.62+)sRead
AV21810ExtHeatingCtrLoopKpExtra heating - Proportional factor (SW 2.62+)Read
AV21812ExtHeatingCtrLoopTDExtra heating - Differential factor (SW 2.62+)sRead
AV21811ExtHeatingCtrLoopTIExtra heating - Integral factor (SW 2.62+)sRead
AV54677ExtraClgOffTmpExtra cooling off temperature°CRead
AV4625ExtraHtgFrstSpvExtra heating frost protection setpoint°CRead
AV60579ExtraHtgFrstSpvStByExtra heating frost protection setpoint stand-by°CRead
AV27620ExtraHtgPreHtgX1Extra heating, pre-heating - X10 - 100%Read
AV23431ExtraHtgPreHtgX2Extra heating, pre-heating - X2°CRead
AV22741ExtraHtgPreHtgY1Extra heating, pre-heating - Y1°CRead
AV26806ExtraHtgPreHtgY2Extra heating, pre-heating - Y20 - 100%Read
AV58349ExtraSpvExtra Sequence setpoint°CRead
AV13916ExtraSpv2Extra setpoint 2 (SW 2.42+)°CRead
AV21837ExtrPrsBalCtrLoopKpExtract air pressure balance controller - Proportional factor (SW 2.62+)Read
AV21839ExtrPrsBalCtrLoopTDExtract air pressure balance controller - Differential factor (SW 2.62+)sRead
AV21838ExtrPrsBalCtrLoopTIExtract air pressure balance controller - Integral factor (SW 2.62+)sRead
AV1886ExtSetpExhFanCOMExhaust fan external setpoint - Value comm. (SW 2.62+)Pa or l/s depending on fan control type.Read
AVmin1884ExtSetpointSpvCOMExternal setpoint - Value comm. (SW 2.62+)°CRead
AV1885ExtSetpSplyFanCOMSupply fan external setpoint - Value comm. (SW 2.62+)Pa or l/s depending on fan control type.Read
AV21864FanClgCtrLoopKpFan cooling - Proportional factor (SW 2.62+)Read
AV21866FanClgCtrLoopTDFan cooling - Differential factor (SW 2.62+)sRead
AV21865FanClgCtrLoopTIFan cooling - Integral factor (SW 2.62+)sRead
AV58670FanClgPrValActual fan cooling value0-100%Read
AV54041FanCmpClgDzFan compensation - Cooling neutral zone°CRead
AV41346FanCmpHtgDzFan compensation - Heating neutral zone°CRead
AV21933FanCmpHumCtrLoopKpFan compensation (humidification) - Proportional factor (SW 2.62+)Read
AV21935FanCmpHumCtrLoopTDFan compensation (humidification) - Differential factor (SW 2.62+)sRead
AV21934FanCmpHumCtrLoopTIFan compensation (humidification) - Integral factor (SW 2.62+)sRead
AV15399FanCmpHumPrValActual fan compensation humidification0-100%Read
AV21858FanCmpTmpCtrLoopKpFan compensation (temp) - Proportional factor (SW 2.62+)Read
AV21860FanCmpTmpCtrLoopTDFan compensation (temp) - Differential factor (SW 2.62+)sRead
AV21859FanCmpTmpCtrLoopTIFan compensation (temp) - Integral factor (SW 2.62+)sRead
AV9430FanCmpTmpPrValActual fan compensation temperature0-100%Read
AV59241FanCmpTmpSpvFan compensation - Temperature setpoint°CRead
AV21861FanHtgCtrLoopKpFan heating - Proportional factor (SW 2.62+)Read
AV21863FanHtgCtrLoopTDFan heating - Differential factor (SW 2.62+)sRead
AV21862FanHtgCtrLoopTIFan heating - Integral factor (SW 2.62+)sRead
AV49915FanHtgPrValActual fan heating value0-100%Read
AV21801HeatingCtrLoopKpHeating - Proportional factor (SW 2.62+)Read
AV21803HeatingCtrLoopTDHeating - Differential factor (SW 2.62+)sRead
AV21802HeatingCtrLoopTIHeating - Integral factor (SW 2.62+)sRead
AV35635HeatingFrstSpvHeating frost protection setpoint°CRead
AV12781HeatingFrstSpvStByHeating frost protection setpoint stand-by°CRead
AV23412HeatingPreHtgX1Heating Pre-heating - X10 - 100%Read
AV27415HeatingPreHtgX2Heating Pre-heating - X2°CRead
AV26693HeatingPreHtgY1Heating Pre-heating - Y1°CRead
AV22566HeatingPreHtgY2Heating Pre-heating - Y20 - 100%Read
AV21819HRecCtrLoopKpHeat recovery - Proportional factor (SW 2.62+)Read
AV21821HrecCtrLoopTDHeat recovery - Differential factor (SW 2.62+)sRead
AV21820HrecCtrLoopTIHeat recovery - Integral factor (SW 2.62+)sRead
AV21822HRecDamperCtrLoopKpMixing damper controller - Proportional factor (SW 2.62+)Read
AV21824HRecDamperCtrLoopTDMixing damper controller - Differential factor (SW 2.62+)sRead
AV21823HRecDamperCtrLoopTIMixing damper controller - Integral factor (SW 2.62+)sRead
AV1577HrecDampminFrshAirMixing damper - Min fresh air0-100%Read
AV21211HrecDampRecHeat recovery damper recovery value0-100%Read
AV46606HrecDmpPosCtlrPrValMixing damper output signal0-100%Read
AV28958HrecDmpPosHrecX1Mixing - mixing damper - heat recovery X1%Read
AV16765HrecDmpPosHrecX2Mixing - mixing damper - heat recovery X2%Read
AV16943HrecDmpPosHrecY1Mixing - mixing damper - heat recovery Y1%Read
AV29260HrecDmpPosHrecY2Mixing - mixing damper - heat recovery Y2%Read
AV14531HrecDmpPosQminOutMixing damper - Q min outl/sRead
AV39790HrecDmpPosSplyX1Mixing - outdoor damper X1%Read
AV43789HrecDmpPosSplyX2Mixing - outdoor damper X2%Read
AV43103HrecDmpPosSplyY1Mixing - outdoor damper Y1%Read
AV38972HrecDmpPosSplyY2Mixing - outdoor damper Y2%Read
AV48520HrecDmpPosStrtupTmMixing damper - Start up timesRead
AV17247HrecEffEffHeat recovery efficiency%Read
AV21831HRecFrstCtrLoopKpHeat recovery frost protection - Proportional factor (SW 2.62+)Read
AV21833HRecFrstCtrLoopTDHeat recovery frost protection - Differential factor (SW 2.62+)sRead
AV21832HRecFrstCtrLoopTIHeat recovery frost protection - Integral factor (SW 2.62+)sRead
AV15072HRecFrstMinTmHeat exchanger - Frost min timeminRead
AV51620HrecFrstSpvHeat exchanger frost protection setpoint°CRead
AV872HRecPmpActiveHourHeat exchanger pump - Operating hours (SW 2.56+)hRead
AV21828HRecPrsFrstCtrLoopKpHeat recovery frost protection pressure - Proportional factor (SW 2.62+)Read
AV21830HRecPrsFrstCtrLoopTDHeat recovery frost protection pressure - Differential factor (SW 2.62+)sRead
AV21829HRecPrsFrstCtrLoopTIHeat recovery frost protection pressure - Integral factor (SW 2.62+)sRead
AV2152HrecPrsFrstSpvHeat recovery frost setpoint st1°CRead
AV55606HrecPrsFrstSpvStByHeat recovery frost setpoint st2°CRead
AV873HtgPmpActiveHourHeating pump - Operating hours (SW 2.56+)hRead
AV21852HtgReClgCtrLoopKpReCooler heating controller - Proportional factor (SW 2.62+)Read
AV21854HtgReClgCtrLoopTDReCooler heating controller - Differential factor (SW 2.62+)sRead
AV21853HtgReClgCtrLoopTIReCooler heating controller - Integral factor (SW 2.62+)sRead
AV21936HumidityCtrLoopKpHumidification - Proportional factor (SW 2.62+)Read
AV21938HumidityCtrLoopTDHumidification - Differential factor (SW 2.62+)sRead
AV21937HumidityCtrLoopTIHumidification - Integral factor (SW 2.62+)sRead
AV57438HumMaxCtlrMaxSpvSupply humidification max setpoint (pure room/extract control)%RH or g/kg depending on configurationRead
AV21930HumMaxCtrLoopKpHumidification max - Proportional factor (SW 2.62+)Read
AV21932HumMaxCtrLoopTDHumidification max - Differential factor (SW 2.62+)sRead
AV21931HumMaxCtrLoopTIHumidification max - Integral factor (SW 2.62+)sRead
AV51005HumidityCtrlPmpVarPosHumidifier pump output signal0-100%Read
AV61029HumSpvAbsDzAbsolute humidity - Neutral zone%RH or g/kg depending on configurationRead
AV20105HumSpvAbsSpvAbsolute humidity - Setpoint%RH or g/kg depending on configurationRead
AV62747HumSpvAbsSpvDehumAbsolute humidity - Dehumidification setpoint%RH or g/kg depending on configurationRead
AV22791HumSpvAbsSpvHumAbsolute humidity - Humidification setpoint%RH or g/kg depending on configurationRead
AV37532HumSpvRelDzRelative humidity - Neutral zone%RH or g/kg depending on configurationRead
AV2194HumSpvRelSpvRelative humidity - Setpoint%RH or g/kg depending on configurationRead
AV11342HumSpvRelSpvDehumRelative humidity - Dehumidification setpoint%RH or g/kg depending on configurationRead
AV10627HumSpvRelSpvHumRelative humidity - Humidification setpoint%RH or g/kg depending on configurationRead
AV31024IBC_ACVoltHeat recovery - VariMax supply AC voltage (SW 2.62+)VRead
AV14728IBC_AxlSpdHeat recovery - Actual axle speed (SW 2.62+)rpmRead
AV56282IBC_MaxAxlSpdHeat recovery - Maximum axle speed (SW 2.62+)rpmRead
AV5584IBC_PrgVerIOCHeat recovery - Program version IOC (SW 2.62+)Read
AV55901IBC_PrgVerMPCHeat recovery - Program version MPC (SW 2.62+)Read
AV41063IBC_RefSpdHeat recovery - Reference speed (SW 2.62+)rpmRead
AV27990IBC_RotorSpdHeat recovery - Actual rotor speed (SW 2.62+)rpmRead
AV60933IBC_UnitTempHeat recovery - Unit temperature (SW 2.62+)°CRead
AV45225IBC_VariMaxModHeat recovery - VariMax model (SW 2.62+)Reads 25 for VariMax25 etc.Read
AV24572MinV1CircReCoolerReCooler - Minimum value 1 circuit (SW 2.42+)%Read
AV45358MinV2CircReCoolerReCooler - Minimum value 2 circuits (SW 2.42+)%Read
AV7039MinV3CircReCoolerReCooler - Minimum value 3 circuits (SW 2.42+)%Read
AV4465NightCoolMinOutTmpNight free cooling - Min outdoor temperature°CRead
AV1475NightCoolOnDiffNight free cooling - Delta°CRead
AV17755NightCoolRmHysNight free cooling - Hysteresis°CRead
AV7412NightCoolRmSpvNight free cooling room setpoint°CRead
AV57226OutEnthOutdoor air enthalpykJ/kgRead
AV16390OutHumAbsOutdoor air humidity absoluteg/kgRead
AV1887OutHumCOMOutdoor air relative humidity - Value comm. (SW 2.62+)0 - 100 %RHRead
AV1882OutTmpCOMOutdoor air temperature - Value comm. (SW 2.62+)°CRead
AV1883OutTmpWallCOMOutdoor temperature wall sensor - Value comm. (SW 2.62+)°CRead
AV61369RmEnthRoom enthalpykJ/kgRead
AV17315RmHumAbsRoom humidity absoluteg/kgRead
AV39703RmHumDevAlmMaxDevMax deviation room hum%RHRead
AV1888RoomHumCOMRoom relative humidity - Value comm. (SW 2.62+)0 - 100 %RHRead
AV1881RoomTmp2COMRoom temperature 2 - Value comm. (SW 2.62+)°CRead
AV61586RtRmTmpDevAlmMaxDevExtract/Room temperature - Maximum deviation°CRead
AV52945SFPThe current SFP value of the unit (SW 2.58+)kW/(m3/s)Read
AV24823SlaveOffsetSlave offsetl/sRead
AV29558SplyEnthSupply air enthalpykJ/kgRead
AV870SplyFanActiveHourSupply fan - Operating hours (SW 2.56+)HRead
AV46589SplyFanActSpvActual supply fan setpointl/sRead
AV56628SplyFanActValActual sply fan valueRead
AV21928SplyFanCmdStSupply fan cmdRead0=Auto; 1=Off; 2=Stage1; 3=Stage2; 4=Stage3
AV15012SplyFanCurrentDanfoss / OJ-DV Supply fan current (SW 2.52+)ARead
AV57203SplyFanDevAlmMaxDevSupply fan - Maximum deviation (flow control)%, Pa or l/s depending on configurationRead
AV27310SplyFanDevAlmMaxDevPrsSupply fan - Maximum deviation (pressure control)PaRead
AV57642SplyFanDevAlmMinLmtSupply fan - Minimum limit (flow control)Read
AV45SplyFanDevAlmMinLmtPrsSupply fan - Minimum limit (pressure control)PaRead
AV30980SplyFanEnergyDanfoss Supply fan Energy (SW 2.52+)kWhRead
AV15375SplyFanMotorVoltDanfoss / OJ-DV Supply fan motor voltage (SW 2.52+)VRead
AV60939SplyFanOpDaysDanfoss / OJ-DV Supply fan - Operating days (SW 2.52+)DaysRead
AV40024SplyFanOpHrsDanfoss / OJ-DV Supply fan - Operating hours (SW 2.52+)HRead
AV48048SplyFanOpMinutesDanfoss / OJ-DV Supply fan - Operating minutes (SW 2.52+)MinRead
AV2558SplyFanOutFreqDanfoss / OJ-DV Supply fan frequency (SW 2.52+)HzRead
AV20963SplyFanPowerDanfoss / OJ-DV Supply fan power (SW 2.52+)kWRead
AV47905SplyFanPrcOutDanfoss / OJ-DV Supply fan output signal (SW 2.52+)%Read
AV12172SplyFanSpeedDanfoss / OJ-DV Supply fan speed (SW 2.52+)rpmRead
AV25092SplyFanSpvMaxForceSupply fan max force setpoint%, Pa or l/s depending on configurationRead
AV52572SplyFanSpvSt1SpvSupply fan step 1 setpoint%, Pa or l/s depending on configurationRead
AV22144SplyFanSpvSt2SpvSupply fan step 2 setpoint%, Pa or l/s depending on configurationRead
AV8244SplyFanSpvSt3SpvSupply fan step 3 setpoint%, Pa or l/s depending on configurationRead
AV32127SplyFilterPreAlmOutdoor air filter Pre-alarmPaRead
AV13958SplyHumAbsSupply air humidity absoluteg/kgRead
AV22230SplyHumDevAlmMaxDevMax deviation supply humg/kg %RH or g/kg depending on configurationRead
AV1907SplyOJEngyCOMOJ-DV Supply fan energy (SW 2.52+)kWhRead
AV53804SplyPreFilterPreAlmOutdoor air pre-filter Pre-alarmPaRead
AV21840SplyPrsBalCtrLoopKpSupply air pressure balance controller - Proportional factor (SW 2.62+)Read
AV21842SplyPrsBalCtrLoopTDSupply air pressure balance controller - Differential factor (SW 2.62+)sRead
AV21841SplyPrsBalCtrLoopTISupply air pressure balance controller - Integral factor (SW 2.62+)sRead
AV9756SplyTmpDevAlmMaxDevSupply temperature - Maximum deviation°CRead
AV14143StrtUpModeDelayReCReCooler - Start-up mode (SW 2.42+)sRead
AV8596SuCmpFanPrValActual summer compensation fan0-100%Read
AV34417SuCmpTmpDtaSummer compensation temperature deltaKRead
AV3420SuCmpTmpEndSummer compensation end - Outdoor air temperature setpoint (SW 2.42+)°CRead
AV41033SuCmpTmpPrValActual summer comp temperature°CRead
AV41719SuCmpTmpStartSummer compensation start - Outdoor air temperature setpoint (SW 2.42+)°CRead
AV24338SuWiSwtchCheckOutTmpDampdDamped temperatureRead
AV7989SwtchSplyCmpSummer/winter supply compensation°CRead
AV21843TmpMaxCtrLoopKpTemp max - Proportional factor (SW 2.62+)Read
AV21845TmpMaxCtrLoopTDTemp max - Differential factor (SW 2.62+)sRead
AV21844TmpMaxCtrLoopTITemp max - Integral factor (SW 2.62+)sRead
AV21846TmpMinCtrLoopKpTemp min - Proportional factor (SW 2.62+)Read
AV21848TmpMinCtrLoopTDTemp min - Differential factor (SW 2.62+)sRead
AV21847TmpMinCtrLoopTITemp min - Integral factor (SW 2.62+)sRead
AV2907TmpMinMaxCtlrMaxSpvSupply temperature max setpoint (Pure room/extract control)°CRead
AV13640TmpMinMaxCtlrMinSpvSupply temperature min setpoint (Pure room/extract control)°CRead
AV65251TmpSpvCoDzComfort temperature deadz°CRead
AV55992TmpSpvCoSpvComfort temperature setpoint°CRead
AV8970TmpSpvCoSpvClgComfort cooling setpoint°CRead
AV22817TmpSpvCoSpvHtgComfort heating setpoint°CRead
AV17839WiCmpTmpPrValActual winter comp temperature°CRead
AV34422WiCmpTmpStartWinter compensation start - Outdoor air temperature setpoint (SW 2.42+)°CRead
BI22605AuxAlmAuxiliary alarmRead0=Ok; 1=Alarm
BI21522AuxInpAuxiliary inputRead0=0; 1=1
BI45154ClgAlmCooling DX alarmRead0=Ok; 1=Alarm
BI40242ClgPmpAlmCooling pump alarmRead0=Ok; 1=Alarm
BI43526CoolingFBFbValCooling DX feedbackRead0=Ok; 1=Alarm
BI51912CoolingPmpCmdFBFbValCooling pump feedbackRead0=Ok; 1=Alarm
BI27338DamperExhFBFbValExhaust air damper feedbackRead0=Ok; 1=Alarm
BI6336DamperSplyFBFbValOutdoor air damper feedbackRead0=Ok; 1=Alarm
BI4964ElHtgAlmElectrical heating alarmRead0=Ok; 1=Alarm
BI9864EmergencyStopEmergency stop inputRead0=Off; 1=On
BI1897EmergencyStopCOMEmergency Stop input - Value comm.Read0=Off; 1=On
BI55865ExhFanAlmExhaust fan alarmRead0=Ok; 1=Alarm
BI32844ExhFanFBFbValExhaust fan feedbackRead0=Ok; 1=Alarm
BI45320ExhFilterAlmExtract filter alarmRead0=Ok; 1=Alarm
BI8711ExhPreFilterAlmExtract pre-filter DI alarmRead0=Ok; 1=Alarm
BI1903ExtAlm1COMExternal alarm 1 - Value comm.Read0=Ok; 1=Alarm
BI1904ExtAlm2COMExternal alarm 2 - Value comm.Read0=Ok; 1=Alarm
BI11643ExtCtrl1External control input 1Read0=Off; 1=On
BI1895ExtCtrl1COMExternal control input 1 - Value comm.Read0=Off; 1=On
BI7448ExtCtrl2External control input 2Read0=Off; 1=On
BI1896ExtCtrl2COMExternal control input 2 - Value comm.Read0=Off; 1=On
BI48824ExtraClgAlmExtra cooling DX alarmRead0=Ok; 1=Alarm
BI47898ExtraClgFBFbValExtra cooling DX feedbackRead0=Ok; 1=Alarm
BI31967ExtraClgPmpAlmExtra cooling pump alarmRead0=Ok; 1=Alarm
BI54719ExtraClgPmpCmdFBFbValExtra cooling pump feedbackRead0=Ok; 1=Alarm
BI23132ExtraElHtgAlmExtra electrical heating alarmRead0=Ok; 1=Alarm
BI34361ExtraFrstDtctrExtra heating frost monitorRead0=Ok; 1=Alarm
BI23306ExtraHtgPmpAlmExtra heating pump alarmRead0=Ok; 1=Alarm
BI13329ExtraHtgPmpCmdFBFbValExtra heating pump feedbackRead0=Ok; 1=Alarm
BI8558FanAlmFan alarmRead0=Ok; 1=Alarm
BI13699FilterAlmFilter alarmRead0=Ok; 1=Alarm
BI28514FireAlmFire alarm alarmRead0=Ok; 1=Alarm
BI59736FireAlm2Fire alarm 2 alarmRead0=Ok; 1=Alarm
BI1901FireAlm2COMFire alarm input 2 - Value comm. (SW 2.62+)Read0=Ok; 1=Alarm
BI63865FireAlm3Fire alarm 3 alarmRead0=Ok; 1=Alarm
BI1902FireAlm3COMFire alarm input 3 - Value comm. (SW 2.62+)Read0=Ok; 1=Alarm
BI1900FireAlmCOMFire alarm - Value comm. (SW 2.62+)Read0=Ok; 1=Alarm
BI53169FireDamperFdbkClsdFire damper closedRead0=Ok; 1=Alarm
BI3118FireDamperFdbkOpnFire damper openedRead0=Ok; 1=Alarm
BI44469FireDamperNoMoveFire damper no moveRead0=Ok; 1=Alarm
BI15639HeatingPmpCmdFBFbValHeating pump feedbackRead0=Ok; 1=Alarm
BI62931HRecAlmHeat recovery alarmRead0=Ok; 1=Alarm
BI61487HRecFdbkAlmHeat exchanger feedback alarmRead0=Ok; 1=Alarm
BI31092HrecFrstDtctrHeat recovery frost monitorRead0=Ok; 1=Alarm
BI18003HRecPmpAlmHeat recovery pump alarmRead0=Ok; 1=Alarm
BI34557HrecPmpCmdFBFbValHeat recovery pump feedbackRead0=Ok; 1=Alarm
BI21294HtgFrstDtctrHeating frost monitorRead0=Ok; 1=Alarm
BI47847HtgPmpAlmHeating pump alarmRead0=Ok; 1=Alarm
BI14608HumidityCtrlCmdFBFbValHumidifier feedbackRead0=Ok; 1=Alarm
BI24144HumidityCtrlPmpCmdFBFbValHumidifier pump feedbackRead0=Ok; 1=Alarm
BI3706HumPmpAlmHumidifier pump alarmRead0=Ok; 1=Alarm
BI28757SplyFanAlmSupply fan alarmRead0=Ok; 1=Alarm
BI64102SplyFanFBFbValSupply fan feedback alarmRead0=Ok; 1=Alarm
BI34066SplyFilterAlmOutdoor filter alarmRead0=Ok; 1=Alarm
BI55258SplyPreFilterAlmOutdoor pre-filter DI alarmRead0=Ok; 1=Alarm
BI26679SuWiSwtchSummer/Winter changeover inputRead0=Winter; 1=Summer
BI1898SuWiSwtchCOMSummer/Winter changeover input - Value comm. (SW 2.62+)Read0=Winter; 1=Summer
BO5714AlmOutHighAlarm output 1Read0=Normal; 1=Alarm
BO8035AlmOutLowAlarm output 2Read0=Normal; 1=Alarm
BO5163AuxOpModeIndAuxiliary operation mode outputRead0=Off; 1=On
BO22528AuxTspOutputAuxiliary time switch program outputRead0=Off; 1=On
BO10276CoolingPmpCmdOnOffCooling pump commandRead0=Off; 1=On
BO43251DamperExhOnOffExhaust air damper commandRead0=Off; 1=On
BO6170DamperSplyOnOffOutdoor air damper commandRead0=Off; 1=On
BO63601ExtraClgPmpCmdOnOffExtra cooling pump commandRead0=Off; 1=On
BO31944ExtraHtgPmpCmdOnOffExtra heating pump commandRead0=Off; 1=On
BO12328FireDamperCmdFire damper commandRead0=Off; 1=On
BO10264HeatingPmpCmdOnOffHeating pump commandRead0=Off; 1=On
BO3016HrecOnOffHeat recovery on/offRead0=Off; 1=On
BO59969HrecPmpCmdOnOffHeat recovery (pump) commandRead0=Off; 1=On
BO18044HumidityCtrlCmdOnOffHumidifier commandRead0=Off; 1=On
BO49625HumidityCtrlPmpCmdOnOffHumidifier pump commandRead0=Off; 1=On
BV20016ActvClgRecPrValCooling recoveryRead0=Passive; 1=Active
BV27019BlkClgRecPrValBlock cooling recoveryRead0=Inactive; 1=Active
BV32783BlkHtgRecPrValBlock heat recoveryRead0=Inactive; 1=Active
BV12464CalibrationAlmCalibration alarmRead0=Ok; 1=Alarm
BV49897CgEm24ModbusAlmCG-EM24 com alarmRead0=Ok; 1=Alarm
BV60516CommTestCommunication test pulseRead0=0; 1=1
BV9543DefrostActvReCoolerReCooler - Defrosting activatedRead0=Inactive; 1=Active
BV48629EconetAlmEconet alarmRead0=Ok; 1=Alarm
BV14622EconetModbusAlmEconet com alarmRead0=Ok; 1=Alarm
BV19549ExhFanBrkChopFltWarnOJ-DV exhaust fan break chopper fault warning (SW 2.52+)Read0=Ok; 1=Alarm
BV45653ExhFanComErMOCAlmOJ-DV exhaust fan com. error MOC alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV31724ExhFanDevAlmAlmExh fan deviationRead0=Passive; 1=Active
BV851ExhFanDevInAlarmExhaust fan deviation - AlarmRead0=Ok; 1=Alarm
BV42595ExhFanEEPromWarnOJ-DV exhaust fan EEPROM error warning (SW 2.52+)Read0=Ok; 1=Alarm
BV20714ExhFanExt24VOverloadOJ-DV exhaust fan ext.24V supply overload (SW 2.52+)Read0=Ok; 1=Alarm
BV35044ExhFanIHiAlmOJ-DV exhaust fan I HI alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV48716ExhFanInpPhaseWarnOJ-DV exhaust fan input phase error (SW 2.52+)Read0=Ok; 1=Alarm
BV12014ExhFanIntHWAlmOJ-DV exhaust fan internal HW fault alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV11735ExhFanIntStopAlmOJ-DV exhaust fan internal stop alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV61771ExhFanLimitWarnOJ-DV exhaust fan limit warning (SW 2.52+)Read0=Ok; 1=Alarm
BV2305ExhFanModbusAlmExhaust fan com alarmRead0=Ok; 1=Alarm
BV28131ExhFanMotorPhaseAlmOJ-DV exhaust fan motor phase error alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV18566ExhFanRotBlkWarnOJ-DV exhaust fan rotor blocked error (SW 2.52+)Read0=Ok; 1=Alarm
BV3591ExhFanRotDirAlmOJ-DV exhaust fan rotor direction alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV3294ExhFanTmpHiWarnOJ-DV exhaust fan temperature high warning (SW 2.52+)Read0=Ok; 1=Alarm
BV34793ExhFanWarnOJ-DV exhaust fan warning (SW 2.52+)Read0=Ok; 1=Alarm
BV22371ExhFanVHiAlmOJ-DV exhaust fan V HI alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV63996ExhFanVLoAlmOJ-DV exhaust fan V LO alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV49301ExhFanVRippleWarnOJ-DV exhaust fan V ripple warning (SW 2.52+)Read0=Ok; 1=Alarm
BV36120FanOpHrsAlmFan operating hours alarmRead0=Ok; 1=Alarm
BV11442HRecModbusAlmHeat exchanger com alarmRead0=Ok; 1=Alarm
BV32740IBC_CleanHeat recovery - Purging (SW 2.62+)Read62 0=Off; 1=On
BV64099IBC_RotMonHeat recovery - Rotor monitor (SW 2.62+)Read0=Off; 1=On
BV4939IBC_TrippHeat recovery - Tripped control unit (SW 2.62+)Read0=Normal; 1=Alarm
BV24032ManualModeManual modeRead0=Auto; 1=Manual
BV57614MBCommAlmModbus communication alarmRead0=Ok; 1=Alarm
BV57971ReCoolerCirc1AlmReCooler circuit 1 alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV31151ReCoolerCirc2AlmReCooler circuit 2 alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV3867ReCoolerCirc3AlmReCooler circuit 3 alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV43898ReCoolerCompAlmReCooler compressor alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV22662ReCoolerDiffPrsAlmReCooler diff.pressure alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV23528ReCoolerDischaPrbAlmReCooler discharge probe error alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV51749ReCoolerDischaTmpAlmReCooler discharge temp alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV14095ReCoolerEEVAlmReCooler EEV error alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV58255ReCoolerHighEnvlAlmReCooler high envelope alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV27958ReCoolerLowEnvlAlmReCooler low envelope alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV51788ReCoolerLowSupHeatAlmReCooler low super heat alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV42357ReCoolerMaxPrsAlmReCooler max pressure alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV11761ReCoolerMinPrsAlmReCooler min pressure alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV51899ReCoolerRotorAlmReCooler rotor alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV42594ReCoolerSucPrbAlmReCooler suction probe error alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV64374ReCoolerVFDAlmReCooler VFD alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV56902ReCoolerVFDOffLineAlmReCooler VFD offline alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV5243RevClgModbusAlmReCooler alarmRead0=Ok; 1=Alarm
BV21718RmHumDevAlmAlmRoom air humidity deviationRead0=Passive; 1=Active
BV7373RtRmTmpDevAlmAlmExtract/Room air temperature deviationRead0=Passive; 1=Active
BV4286RtTmpFireAlmExtract air temperature fire alarmRead0=Ok; 1=Alarm
BV20345SplyFanBrkChopFltWarnOJ-DV supply fan break chopper fault warning (SW 2.52+)Read0=Ok; 1=Alarm
BV30320SplyFanComErMOCAlmOJ-DV supply fan com. error MOC alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV6486SplyFanDevAlmAlmSupply fan deviationRead0=Passive; 1=Active
BV850SplyFanDevInAlarmSupply fan deviation - AlarmRead0=Ok; 1=Alarm
BV11239SplyFanEEPromWarnOJ-DV supply fan EEPROM error warning (SW 2.52+)Read0=Ok; 1=Alarm
BV21454SplyFanExt24VOverloadOJ-DV supply fan ext.24V supply overload (SW 2.52+)Read0=Ok; 1=Alarm
BV59998SplyFanIHiAlmOJ-DV supply fan I HI alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV644SplyFanInpPhaseWarnOJ-DV supply fan input phase error (SW 2.52+)Read0=Ok; 1=Alarm
BV17719SplyFanIntHWAlmOJ-DV supply fan internal HW fault alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV41043SplyFanIntStopAlmOJ-DV supply fan internal stop alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV62854SplyFanLimitWarnOJ-DV supply fan limit warning (SW 2.52+)Read0=Ok; 1=Alarm
BV45899SplyFanModbusAlmSupply fan com alarmRead0=Ok; 1=Alarm
BV50100SplyFanMotorPhaseAlmOJ-DV supply fan motor phase error alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV50434SplyFanRotBlkWarnOJ-DV supply fan rotor blocked error (SW 2.52+)Read0=Ok; 1=Alarm
BV2762SplyFanRotDirAlmOJ-DV supply fan rotor direction alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV2067SplyFanTmpHiWarnOJ-DV supply fan temperature high warning (SW 2.52+)Read0=Ok; 1=Alarm
BV64963SplyFanWarnOJ-DV supply fan warning (SW 2.52+)Read0=Ok; 1=Alarm
BV13785SplyFanVHiAlmOJ-DV supply fan V HI alarm (SW 2.52+)Read0=Ok; 1=Alarm
BV39750SplyFanVLoAlmOJ-DV supply fan V LO alarm (SW 2.52+)Read0=0; 1=1
BV1200SplyFanVRippleWarnOJ-DV supply fan V ripple warning (SW 2.52+)Read0=Ok; 1=Alarm
BV57113SplyHumDevAlmAlmSupply air humidity deviationRead0=Passive; 1=Active
BV38175SplyTmpDevAlmAlmSupply air temperature deviationRead0=Passive; 1=Active
BV44098SplyTmpFireAlmSupply air temperature fire alarmRead0=Ok; 1=Alarm
BV9042TWCtrlrTwin Wheel controller alarmRead0=Ok; 1=Alarm
BV61922ZoneCtrlrZone controllerRead0=Ok; 1=Alarm
CAL29758CalendarAuxCalendar auxRead0=Date; 1=Range; 2=Wday; 3=Inv
CAL38114CalendarExCalendar exceptionRead0=Date; 1=Range; 2=Wday; 3=In
CAL51936CalendarOffCalendar fix offRead0=Date; 1=Range; 2=Wday; 3=In
MO30094CoolingCmdDxStCooling DX commandRead0=Auto; 1=Off; 2=St1; 3=St2; 4=St3
MO11590ElectricalHtgCmdStStElectrical heating commandRead0=Auto; 1=Off; 2=St1; 3=St2; 4=St3
MO14719ExhFanCmdStExhaust fan commandRead0=Auto; 1=Off; 2=St1; 3=St2; 4=St3
MO27550ExtraClgCmdDxStExtra cooling DX commandRead0=Auto; 1=Off; 2=St1; 3=St2; 4=St3
MO30897ExtraElHtgCmdStStExtra electrical heating commandRead0=Auto; 1=Off; 2=St1; 3=St2; 4=St3
MV39130AckAlmPlsAlarm acknowledgeRead0=Off; 1=On
MV28561ActCtrlModeActual temperature control modeRead0=Room; 1=Return; 2=Supply
MV25131ActCtrlModeHumActual humidification control modeRead0=Room; 1=Return; 2=Supply
MV28279ActFanStepActual fan stepRead0=Off; 1=Stage1; 2=Stage2; 3=Stage3
MVmin6080ActOpModeActual operating modeRead0=Off; 1=On/Comfort; 2=Economy; 3=Na; 4=Osstp; 5=Nightcooling; 6=Unoccupied (Temperature start); 7=Nightkick (Test temperature); 8=Firedamper test; 9=Fire; 10=Stop; 11=Overrun; 12=Startup
MVmin32321ActOpStaActual operation statusRead0=Nu; 1=Configuration error; 2=SUF; 3=Fire alarm activated; 4=MsgCl0; 5=Emergency Stop; 6=MsgCl1; 7=Fire damper test activated; 8=Manual operation; 9=ExtC; 10=BMS; 11=Time scheduling program; 12=Boost; 13=Night heating/Night cooling
MV19801ActvClgRecKvalActivate cooling recovery - KValRead0=Lower; 1=Higher
MV46769AlmCl0Alarm class Danger alarm (A) statusRead0=Normal; 1=Alarm
MVmin42640AlmCl1Alarm class Critical alarm (A) statusRead0=Normal; 1=Alarm
MVmin38643AlmCl2Alarm class Low alarm (B) statusRead0=Normal; 1=Alarm
MV34514AlmCl3Alarm class Warning alarm (C) statusRead0=Normal; 1=Alarm
MV48172AuxiliaryBmsTimeAuxSwtchAux BMS TSP outputRead0=Auto; 1=Off; 2=On
MV44050AuxiliaryTspCopyAuxPlsAuxiliaryTspCopyAux.PlsRead0=Auto; 1=Off; 2=On
MV39893BlkClgRecKvalBlock cooling recovery - KValRead0=Lower; 1=Higher
MV40828BlkHtgRecKvalBlock heat recovery - KValRead0=Lower; 1=Higher
MV53050CG_EM24_1ResetParPlsEnergy meter reset partialRead0=Passive; 1=Active
MV1708CommTestEnEnable communication testRead0=No; 1=Yes
MV3329CounterFlowExchOffsetBoostCounter flow heat exchanger - Offset boostRead0=Low Boost; 1=Normal Boost; 2=High Boost
MV30051DPTSnsrModbusAlmDPT sensor com alarmRead0=Ok; 1=Alarm
MV50595EconetActOpModeEconet operation modeRead0=Stop; 1=Alarm; 2=Idle; 3=Startup; 4=Heatrec; 5=Cooling; 6=Coolrec; 7=Manual
MV43819ExhEngUnitExhaust fan engineering unitRead0=%; 1=Pa; 2=l/s; 3=m³/h
MV18848ExhFanActAlmExhaust fan alarm (SW 2.52+)Read0=Nu; 1=MOvrVlt.; 2=MUndrVlt.; 3=DClinkUndrVlt; 4=DClinkOvrVlt; 5=IntElectr; 6=Locked; 7=HallSnsr; 8=Ovrh
MV39335ExhFanActWarnExhaust fan warning (SW 2.52+)Read0=Nu; 1=OpenCircutInp; 2=ActSpdLowLlim; 3=BrkOp; 4=DCLlinkVlt; 5=ElectrTmp; 6=MtrTmp; 7=OutpStgTmp; 8=Mes
MV30799ExtControlActModeActual operation mode external controlRead0=Auto; 1=Off; 2=Stage1; 3=Stage2; 4=Stage3
MV28852ExtControlStepExternal control fan stepRead0=Auto; 1=Off; 2=1Step; 3=2Step; 4=3Step
MV24454ExtraHtgPreHtgactvPre htg 2 stateRead
MV9703FireDamper1OperationFire damper 1 modeRead
MV24347FireDamperStateFire damper stateRead0=NotDefined; 1=Closed; 2=Moving; 3=Opened
MV64867FireDamperTestStrtHMIPlsFire damper testRead0=Passive; 1=Active
MV55722HeatingPreHtgactvHeating Pre-heating stateRead
MV13725HumEngUnitHumidity engineering unitRead0=%r.H.; 1=g/kg
MV55390IBC_AlmHeat recovery - Error code (SW 2.62+)Read1=Normal; 2=Internal error; 3=Internal error; 4=Motor temp; 5=Low temp; 6=Overheat; 7=Low voltage; 8=High voltage; 9=Many surge events; 10=Rotation monitor alarm; 11=Rotating at upstart; 12=Motor current high; 13=Overload (fast); 14=Overload; 15=Insufficient load; 16=Error in motor control; 17=Short Circuit; 18=Phase imbalance; 19=Phase 1 Missing; 20=Phase 2 Missing; 21=Phase 3 Missing; 22=Impedance high; 23=Impedance low; 24=Internal error
MV38318IBC_OpModeHeat recovery - Operation mode (SW 2.62+)Read1=Low speed DIP switch ON; 2=High speed DIP switch ON; 3=Manual speed; 4=Control signal; 5=No operation, cleaning; OFF; 6=No operation, cleaning ON; 7=Cleaning ON
MV59996MECHactvCooling recovery activatedRead0=Off; 1=On
MV43500Nbr_CircReCoolerReCooler number of circuits (SW 2.42+)Read0=NotUsed; 1=eQKR008; 2=eQKR011; 3=eQKR018; 4=eQKR023; 5=eQKR032; 6=eQKR041; 7=eQKR050; 8=eQKR072
MV6316NightUnoccCoolingModeCooling coil (night cooling)Read0=Inactive; 1=Active
MV17477NightUnoccHeatingModeHeating coil (night heating)Read0=Inactive; 1=Active
MV31604OpModeAutoManStSwtchManual operation (steps)Read0=Auto; 1=Off; 2=Stage1; 3=Stage2; 4=Stage3
MV60288OpModeAutoManStTmpSwtchManual operation (steps/ temperature)Read0=Auto; 1=Off; 2=Eco St1; 3=Comf St1; 4=Eco St2; 5=Comf St2; 6=Eco St3; 7=Comf St3
MVmin8442OpModeBmsTimeStSwtchBMS TSP stepsRead0=Auto; 1=Off; 2=Stage 1; 3=Stage 2; 4=Stage 3
MV32040OpModeBmsTimeStTmpSwtchBMS TSP steps/temperatureRead0=Auto; 1=Off; 2=Eco St1; 3=ComfSt1; 4=Eco St2; 5=Comf St2; 6=EcoSt3; 7=Comf St3
MV33544OpModeTspCopyUnitPlsOpModeTspCopyUnit.PlsRead
MV41090OpStaReCoolerReCooler operation statusRead0=Stop; 1=Running Full; 2=Defrost; 3=In Alarm; 4=Heating; 5=Cooling; 6=Mandatory OFF; 7=Stand By; 8=Start Up
MV57729OpStaReCooler1ReCooler circuit 1 operation status (SW 2.52+)Read0=Stand By; 1=Init; 2=Unit running; 3=Defrost; 4=Rev. cycle defrost; 5=Exh. Coil low temp; 6=Start phase; 7=Pressure diff. limit; 8=Start delay; 9=Alarm; 10=Compressor shut off; 11=Cool/Heat mode select; 12=Heater run; 13=Alarm unit 1; 14=Alarm unit 2; 15=Alarm unit 3; 16=Defrost ramp up; 17=Check refrigerator charge; 18=Quick start
MV53730OpStaReCooler2ReCooler circuit 2 operation status (SW 2.52+)Read0=Stand By; 1=Init; 2=Unit running; 3=Defrost; 4=Rev. cycle defrost; 5=Exh. Coil low temp; 6=Start phase; 7=Pressure diff. limit; 8=Start delay; 9=Alarm; 10=Compressor shut off; 11=Cool/Heat mode select; 12=Heater run; 13=Alarm unit 1; 14=Alarm unit 2; 15=Alarm unit 3; 16=Defrost ramp up; 17=Check refrigerator charge; 18=Quick start
MV49603OpStaReCooler3ReCooler circuit 3 operation status (SW 2.52+)Read0=Stand By; 1=Init; 2=Unit running; 3=Defrost; 4=Rev. cycle defrost; 5=Exh. Coil low temp; 6=Start phase; 7=Pressure diff. limit; 8=Start delay; 9=Alarm; 10=Compressor shut off; 11=Cool/Heat mode select; 12=Heater run; 13=Alarm unit 1; 14=Alarm unit 2; 15=Alarm unit 3; 16=Defrost ramp up; 17=Check refrigerator charge; 18=Quick start
MV46288PressuresFilterChPlsFilters changed, pre-alarm acknowledgeRead0=Passive; 1=Active
MV64493SeqHumEngUnitHumidification engineering unitRead0=%r.H.; 1=g/kg
MV53317SnsrModbusAlmSensors com alarmRead0=Ok; 1=Alarm
MV54155SplyEngUnitSupply fan engineering unitRead0=%; 1=Pa; 2=l/s; 3=m³/h
MV32186SplyFanActAlmSupply fan alarm (SW 2.52+)Read0=Nu; 1=MOvrVlt.; 2=MUndrVlt.; 3=DClinkUndrVlt; 4=DClinkOvrVlt; 5=IntElectr; 6=Locked; 7=HallSnsr; 8=Ovrh
MV62832SplyFanActWarnSupply fan warning (SW 2.52+)Read0=Nu; 1=OpenCircutInp; 2=ActSpdLowLlim; 3=BrkOp; 4=DCLlinkVlt; 5=ElectrTmp; 6=MtrTmp; 7=OutpStgTmp; 8=Mes
MV24616SuWiSwtchCheckStateSummer/Winter modeRead
MV52222TimeSchedAuxAux TSP outputRead
MV12316TimeSchedStActual time switch program (steps)Read0=Off; 1=Stage1; 2=Stage2; 3=Stage3
MV596TimeSchedStTmpActual time switch program (steps/ temperature)Read0=Auto; 1=Off; 2=Eco St1; 3=Comf St1; 4=Eco St2; 5=Comf St2; 6=Eco St3; 7=Comf St3
PIV15816ExhFanAlmWarnDanfoss / OJ-DV Exhaust fan alarm warning (SW 2.52+)Read
PIV4384IBC_NbrOfDrpConHeat recovery - Number of dropped Modbus connections (SW 2.62+)Read
PIV62302IBC_NbrOfFaultyPacketsHeat recovery - Number of faulty Modbus packets (SW 2.62+)Read
PIV29945IBC_NbrOfOKPacketsHeat recovery - Number of OK Modbus packets (SW 2.62+)Read
PIV31030IBC_TmActiveFltErHeat recovery - Time with active error (SW 2.62+)hRead
PIV30070IBC_TotOpTimeUnitHeat recovery - Total operation time for the control unit (SW 2.62+)hRead
PIV52012SplyFanAlmWarnDanfoss/OJ-DV Supply fan alarm warning (SW 2.52+)Read
SCH55253ScheduleAuxSchedule aux outputRead
SCH31059ScheduleStSchedule stepsRead
SCH32703ScheduleStTmpSchedule steps/tmpRead
Object ID lookup: FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V2.xx point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the eQ AHU controls (Climatix), application eQ Fläkt AHU V2.xx and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V2.xx

How many BACnet points does the FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V2.xx have?

This list has 584 BACnet objects: 53 analog inputs, 21 analog outputs, 282 analog values, 57 binary inputs, 15 binary outputs, 82 binary values, 3 calendars, 5 multi-state outputs, 3 schedules, 56 multi-state values, 7 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V2.xx BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V2.xx BACnet documentation?

The source is eQ Controls - Climatix BACnet communication module, Installation and maintenance instruction (BACnet objects of eQ Fläkt V2.xx) (DC_10159GB 20180823_R0), revision 2018-08-23, published free by FläktGroup at https://www.flaktgroup.com/api/v1/Documents/129344/Download.

What are the minimum BACnet points to integrate the FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V2.xx?

Start with MV 8442 OpModeBmsTimeStSwtch (BMS operating command: 0 Auto, 1 Off, 2-4 stage 1-3); AV 1884 ExtSetpointSpvCOM (Temperature setpoint written over the bus, °C); MV 6080 ActOpMode (Actual operating mode (off, comfort, economy...)); MV 32321 ActOpSta (Actual operation status / stop reason); AI 45150 SupplyTmp (Supply air temperature); AI 28256 ReturnAirTmp (Extract air temperature); AI 53218 OutTmp (Outdoor air temperature); AO 59037 SplyFanVarPos (Supply fan output signal, 0-100 %); MV 42640 AlmCl1 (Critical (A) alarm class active); MV 38643 AlmCl2 (Low (B) alarm class active).

How do I enable BMS control of the FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V2.xx?

The document gives no access column. OpModeBmsTimeStSwtch (steps) and OpModeBmsTimeStTmpSwtch (steps/temperature) are the BMS time-switch-program commands (0 = Auto follows the unit's own program); which one applies depends on the unit's control mode.

Can the BMS supply sensor values to the FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V2.xx?

ExtSetpointSpvCOM (AV 1884) is the external setpoint value from communication; the AI ExtSetpointSpv is the hard-wired external setpoint input.

How do I check these points on the real eQ AHU controls (Climatix), application eQ Fläkt AHU V2.xx?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More FläktGroup BACnet points lists

Source: eQ Controls - Climatix BACnet communication module, Installation and maintenance instruction (BACnet objects of eQ Fläkt V2.xx) · DC_10159GB 20180823_R0 · rev. 2018-08-23. Object names, instances and units are reproduced as published; descriptions are our own.