- Home
- BACnet points lists
- FläktGroup
- ISYteq controller for eCO Top / eCO Side compact AHUs
Air handling unit controller (compact AHU) · BACnet points list
FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs BACnet points list
Updated 12 November 2026
The ISYteq controller in eCO Top / eCO Side units has BACnet built in, on RS-485 (MS/TP) or Ethernet (BACnet IP). The object list covers external setpoints from the BMS, temperature, humidity, air quality, pressure and flow sensors, coil, fan and damper outputs, setpoints and offsets, sensor and equipment fault flags, collective alarms, unit and control mode multistates and schedules. Most points are read-only; setpoints, enables and mode selections are R/W.
This page lists 495 BACnet objects for the FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs — 50 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from FläktGroup’s own free documentation, linked below.
- Manufacturer
- FläktGroup
- Model
- ISYteq controller for eCO Top / eCO Side compact AHUs
- Equipment
- Air handling unit controller (compact AHU)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 495 (50 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- ISYteq, eCO Top, eCO Side, eCO SEC, ISYteq eCO, DC_10484GB, Flakt eCO BACnet
Reference only, provided as-is: verify against FläktGroup’s current documentation and the live device before use. Not official FläktGroup information. Terms of use.
BMS integration notes: FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs
Set Protocol to MS/TP on the RS-485 channel (or use Ethernet port 1 for BACnet IP), set name and device instance in the HMI, then command the unit with MV 3939011 Unit Operation Mode and the temperature setpoint, and read temperatures, fan outputs and the collective alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 3939011 | Unit Operation Mode | Unit mode command: 1 Automatic, 3 Low, 4 High speed... | Write |
| AV 3030071 | Temperature Control Setpoint | Temperature setpoint, 5-45 °C | Write |
| AI 3030042 | Temperature Control External Setpoint | External temperature setpoint from the BMS, °C | Write |
| MV 3939091 | Unit Operation Mode Actual | Actual unit operation mode | Write |
| AI 106011 | Supply Air Temperature Sensor | Supply air temperature, °C | Read |
| AI 206011 | Extract Air Temperature Sensor | Extract air temperature, °C | Read |
| AI 306011 | Outdoor Air Temperature Sensor | Outdoor air temperature, °C | Read |
| AO 101011 | Supply Air Fan 1 Output | Supply fan output, % | Read |
| BO 3939031 | Alarm Collective A | Collective A alarm | Read |
| BO 3939041 | Alarm Collective B | Collective B alarm | Read |
Enable & remote start
MV 3939011 Unit Operation Mode (R/W) selects Automatic, Room Frost Protection, Low/High Speed, Free Profile 1/2 or Night Purge. BV 3030081 / 3131081 / 3232081 let temperature, humidity or air quality control enable the unit.
Sensors & values from the BMS
The AI external setpoint objects (temperature 3030042, relative 3030043, humidity 3131042, air quality 3232042, fan flow/pressure/manual 133022-24 and 233022-24, outdoor air amount 2929011) are R/W inputs the BMS can write.
Network setup
- MS/TP: HMI /Configuration/Network/RS485, choose channel 1 (A1/B1) or 2 (A2/B2), set Protocol = MS/TP, MAC, baud, BC net, MaxMaster, MaxInfoFrames.
- BACnet IP: Ethernet port 1 (X23).
- Name and device instance: HMI /Configuration/Network/BACnet/General; EDE export button on the same page. Admin login needed.
Watch out for
- The same instance number is used by several object types; map by type and instance.
- Check BMS_List.xlsm on the controller SD card for the object list of the installed software version.
FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 3030042 | Temperature Control External Setpoint | Range 5.0-45.0 | °C | Write | |
| AI | 3030043 | Temperature Control External Relative Setpoint | Range -10.0-10.0 | ΔK | Write | |
| AI | 3131042 | Humidity Control External Setpoint | Range 0.0-100.0 | % | Write | |
| AI | 3232042 | Air Quality Control External Setpoint | Range 0.0-3000.0 | ppm | Write | |
| AI | 133022 | Supply Air Fan Control Volume Flow External Setpoint | Range 0-100000 | m³/h | Write | |
| AI | 133023 | Supply Air Fan Control Pressure External Setpoint | Range 0-500 | Pa | Write | |
| AI | 133024 | Supply Air Fan Control Manual External Setpoint | Range 0.0-100.0 | % | Write | |
| AI | 233022 | Extract Air Fan Control Volume Flow External Setpoint | Range 0-100000 | m³/h | Write | |
| AI | 233023 | Extract Air Fan Control Pressure External Setpoint | Range 0-500 | Pa | Write | |
| AI | 233024 | Extract Air Fan Control Manual External Setpoint | Range 0.0-100.0 | % | Write | |
| AI | 2929011 | Damper Control Outdoor Air Amount External Setpoint | Range 0.0-100.0 | % | Write | |
| AImin | 106011 | Supply Air Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 106031 | Supply Air Fan Nozzle Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 106041 | Supply Air Heater 1 Inlet Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 106051 | Supply Air Heater 1 Outlet Temperature Sensor | Range 5.0-200.0 | °C | Read | |
| AI | 106061 | Supply Air Heater 2 Inlet Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 106071 | Supply Air Heater 2 Outlet Temperature Sensor | Range 5.0-200.0 | °C | Read | |
| AI | 106081 | Supply Air Cooler 1 Inlet Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 106091 | Supply Air Cooler 1 Outlet Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 106101 | Supply Air Cooler 2 Inlet Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 106111 | Supply Air Cooler 2 Outlet Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 106141 | Supply Air Reheater 1 Inlet Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 106151 | Supply Air Reheater 1 Outlet Temperature Sensor | Range 5.0-200.0 | °C | Read | |
| AImin | 206011 | Extract Air Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 206071 | Extract Air Fan Nozzle Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AImin | 306011 | Outdoor Air Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 306021 | Outdoor Air Filter Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 306031 | Outdoor Air Preheater 1 Inlet Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 306041 | Outdoor Air Preheater 1 Outlet Temperature Sensor | Range 5.0-200.0 | °C | Read | |
| AI | 406011 | Exhaust Air Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 706011 | Room Air Temperature Sensor 1 | Range -50.0-200.0 | °C | Read | |
| AI | 706021 | Room Air Temperature Sensor 2 | Range -50.0-200.0 | °C | Read | |
| AI | 706031 | Room Air Temperature Sensor 3 | Range -50.0-200.0 | °C | Read | |
| AI | 706041 | Room Air Temperature Sensor 4 | Range -50.0-200.0 | °C | Read | |
| AI | 806011 | Energy Recovery System 1 Inlet Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 806021 | Energy Recovery System 1 Outlet Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 806031 | Supply Air Temperature Sensor Behind Energy Recovery System | Range -50.0-200.0 | °C | Read | |
| AI | 806041 | Exhaust Air Temperature Sensor Behind Energy Recovery System | Range -50.0-200.0 | °C | Read | |
| AI | 806051 | Energy Recovery System Icing Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 2006011 | Outdoor Air External Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 2106011 | Evaporator 1 Temperature Sensor | Range -50.0-200.0 | °C | Read | |
| AI | 107011 | Supply Humidity Sensor | Range 0.0-100.0 | % | Read | |
| AI | 207011 | Extract Air Humidity Sensor | Range 0.0-100.0 | % | Read | |
| AI | 307011 | Outdoor Air Humidity Sensor | Range 0.0-100.0 | % | Read | |
| AI | 407011 | Exhaust Air Humidity Sensor | Range 0.0-100.0 | % | Read | |
| AI | 707011 | Room Air Humidity Sensor 1 | Range 0.0-100.0 | % | Read | |
| AI | 707021 | Room Air Humidity Sensor 2 | Range 0.0-100.0 | % | Read | |
| AI | 707031 | Room Air Humidity Sensor 3 | Range 0.0-100.0 | % | Read | |
| AI | 707041 | Room Air Humidity Sensor 4 | Range 0.0-100.0 | % | Read | |
| AI | 2007011 | Outdoor Air External Humidity Sensor | Range 0.0-100.0 | % | Read | |
| AI | 208011 | Extract Air Quality Sensor | Range 0.0-3276.7 | ppm | Read | |
| AI | 308011 | Outdoor Air Quality Sensor | Range 0.0-3276.7 | ppm | Read | |
| AI | 708011 | Room Air Quality Sensor 1 | Range 0.0-3276.7 | ppm | Read | |
| AI | 708021 | Room Air Quality Sensor 2 | Range 0.0-3276.7 | ppm | Read | |
| AI | 708031 | Room Air Quality Sensor 3 | Range 0.0-3276.7 | ppm | Read | |
| AI | 708041 | Room Air Quality Sensor 4 | Range 0.0-3276.7 | ppm | Read | |
| AI | 109011 | Supply Air Filter Pressure Sensor 1 | Range -10-250 | Pa | Read | |
| AI | 109021 | Supply Air Filter Pressure Sensor 2 | Range -10-250 | Pa | Read | |
| AI | 109031 | Supply Air Nozzle Pressure Sensor | Range -10-5000 | Pa | Read | |
| AI | 109041 | Supply Air Duct Pressure Sensor | Range -10-500 | Pa | Read | |
| AI | 209011 | Extract Air Filter Pressure 1 Sensor | Range -10-250 | Pa | Read | |
| AI | 209021 | Extract Air Filter Pressure 2 Sensor | Range -10-250 | Pa | Read | |
| AI | 209031 | Extract Air Duct Pressure Sensor | Range -10-500 | Pa | Read | |
| AI | 209041 | Extract Air Nozzle Pressure Sensor | Range -10-5000 | Pa | Read | |
| AI | 309011 | Outdoor Air Filter Pressure 1 Sensor | Range -10-250 | Pa | Read | |
| AI | 309021 | Outdoor Air Filter Pressure Sensor 2 | Range -10-250 | Pa | Read | |
| AI | 309031 | Outdoor Air Bypass Pressure Sensor | Range -10-500 | Pa | Read | |
| AI | 409011 | Exhaust Air Bypass Pressure Sensor | Range -10-500 | Pa | Read | |
| AI | 809011 | Energy Recovery System Pressure Sensor | Range -10-500 | Pa | Read | |
| AI | 104011 | Supply Air Heater 1 Valve Feedback | Range -5-5 | % | Read | |
| AI | 104021 | Supply Air Heater 2 Valve Feedback | Range -5-5 | % | Read | |
| AI | 104031 | Supply Air Cooler Valve 1 Feedback | Range -5-5 | % | Read | |
| AI | 104041 | Supply Air Cooler Valve 2 Feedback | Range -5-5 | % | Read | |
| AI | 104061 | Supply Air Reheater 1 Valve Feedback | Range -5-5 | % | Read | |
| AI | 304011 | Outdoor Air Preheater 1 Valve Feedback | Range -5-5 | % | Read | |
| AI | 804011 | Energy Recovery System Valve 1 Feedback | Range -5-5 | % | Read | |
| AI | 102011 | Supply Air Damper 1 Feedback | Range -5-5 | % | Read | |
| AI | 202011 | Extract Air Damper 1 Feedback | Range -5-5 | % | Read | |
| AI | 302011 | Outdoor Air Damper 1 Feedback | Range -5-5 | % | Read | |
| AI | 302021 | Outdoor Air Bypass Damper Feedback | Range -5-5 | % | Read | |
| AI | 402011 | Exhaust Air Damper 1 Feedback | Range -5-5 | % | Read | |
| AI | 402021 | Exhaust Air Bypass Damper Feedback | Range -5-5 | % | Read | |
| AI | 602011 | Recirculation Air Damper 1 Feedback | Range -5-5 | % | Read | |
| AI | 4102011 | Smoke Bypass Damper Feedback | Range -5-5 | % | Read | |
| AO | 112031 | Supply Air Electric Heater 1 Output | Range 0-100 | % | Read | |
| AO | 112021 | Supply Air Electric Reheater 1 Output | Range 0-100 | % | Read | |
| AO | 312011 | Outdoor Air Electric Preheater 1 Output | Range 0-100 | % | Read | |
| AO | 2128041 | DX Mitsubishi Inverter Stage 1 Output | Range 0-100 | % | Read | |
| AO | 2128051 | DX Mitsubishi Inverter Stage 2 Output | Range 0-100 | % | Read | |
| AO | 2128061 | DX Daikin Inverter Stage 1 Output | Range 0-100 | % | Read | |
| AO | 2128071 | DX Daikin Inverter Stage 2 Output | Range 0-100 | % | Read | |
| AO | 103011 | Supply Air Heater 1 Pump Output | Range 0-100 | % | Read | |
| AO | 103021 | Supply Air Heater 2 Pump Output | Range 0-100 | % | Read | |
| AO | 103031 | Supply Air Cooler Pump 1 Output | Range 0-100 | % | Read | |
| AO | 103041 | Supply Air Cooler Pump 2 Output | Range 0-100 | % | Read | |
| AO | 103061 | Supply Air Reheater 1 Pump Output | Range 0-100 | % | Read | |
| AO | 303011 | Outdoor Air Preheater 1 Pump Output | Range 0-100 | % | Read | |
| AO | 803011 | Energy Recovery System 1 Pump Output | Range 0-100 | % | Read | |
| AO | 104011 | Supply Air Heater 1 Valve Output | Range 0-100 | % | Read | |
| AO | 104021 | Supply Air Heater 2 Valve Output | Range 0-100 | % | Read | |
| AO | 104031 | Supply Air Cooler Valve 1 Output | Range 0-100 | % | Read | |
| AO | 104041 | Supply Air Cooler Valve 2 Output | Range 0-100 | % | Read | |
| AO | 104061 | Supply Air Reheater 1 Valve Output | Range 0-100 | % | Read | |
| AO | 304011 | Outdoor Air Preheater 1 Valve Output | Range 0-100 | % | Read | |
| AO | 804011 | Energy Recovery System Valve 1 Output | Range 0-100 | % | Read | |
| AO | 805011 | Energy Recovery System 1 Motor Output | Range 0.0-100.0 | % | Read | |
| AOmin | 101011 | Supply Air Fan 1 Output | Range 0.0-100.0 | % | Read | |
| AO | 101021 | Supply Air Fan 2 Output | Range 0.0-100.0 | % | Read | |
| AO | 101031 | Supply Air Fan 3 Output | Range 0.0-100.0 | % | Read | |
| AO | 101041 | Supply Air Fan 4 Output | Range 0.0-100.0 | % | Read | |
| AO | 101051 | Supply Air Fan 5 Output | Range 0.0-100.0 | % | Read | |
| AO | 101061 | Supply Air Fan 6 Output | Range 0.0-100.0 | % | Read | |
| AO | 101071 | Supply Air Fan 7 Output | Range 0.0-100.0 | % | Read | |
| AO | 101081 | Supply Air Fan 8 Output | Range 0.0-100.0 | % | Read | |
| AO | 201011 | Extract Air Fan 1 Output | Range 0.0-100.0 | % | Read | |
| AO | 201021 | Extract Air Fan 2 Output | Range 0.0-100.0 | % | Read | |
| AO | 201031 | Extract Air Fan 3 Output | Range 0.0-100.0 | % | Read | |
| AO | 201041 | Extract Air Fan 4 Output | Range 0.0-100.0 | % | Read | |
| AO | 201051 | Extract Air Fan 5 Output | Range 0.0-100.0 | % | Read | |
| AO | 201061 | Extract Air Fan 6 Output | Range 0.0-100.0 | % | Read | |
| AO | 201071 | Extract Air Fan 7 Output | Range 0.0-100.0 | % | Read | |
| AO | 201081 | Extract Air Fan 8 Output | Range 0.0-100.0 | % | Read | |
| AO | 102011 | Supply Air Damper 1 Output | Range 0-100 | % | Read | |
| AO | 202011 | Extract Air Damper 1 Output | Range 0-100 | % | Read | |
| AO | 302011 | Outdoor Air Damper 1 Output | Range 0-100 | % | Read | |
| AO | 302021 | Outdoor Air Bypass Damper Output | Range 0-100 | % | Read | |
| AO | 402011 | Exhaust Air Damper 1 Output | Range 0-100 | % | Read | |
| AO | 402021 | Exhaust Air Bypass Damper Output | Range 0-100 | % | Read | |
| AO | 602011 | Recirculation Air Damper 1 Output | Range 0-100 | % | Read | |
| AO | 4102011 | Smoke Bypass Damper Output | Range 0-100 | % | Read | |
| AO | 4101011 | Smoke Extraction Fan 1 Output | Range 0.0-100.0 | % | Read | |
| AO | 4101021 | Smoke Extraction Fan 2 Output | Range 0.0-100.0 | % | Read | |
| AO | 4101031 | Smoke Extraction Fan 3 Output | Range 0.0-100.0 | % | Read | |
| AV | 3030031 | Temperature Control Heating Setpoint | Range 5.0-45.0 | °C | Write | |
| AV | 3030041 | Temperature Control Cooling Setpoint | Range 5.0-45.0 | °C | Write | |
| AV | 3030051 | Temperature Control Heating Offset Setpoint | Range -10.0-0.0 | ΔK | Write | |
| AV | 3030061 | Temperature Control Cooling Offset Setpoint | Range 0.0-10.0 | ΔK | Write | |
| AVmin | 3030071 | Temperature Control Setpoint | Range 5.0-45.0 | °C | Write | |
| AV | 3030081 | Temperature Control Relative Setpoint | Range -5.0-5.0 | ΔK | Write | |
| AV | 3131031 | Humidity Control Humidification Setpoint | Range 0.0-100.0 | % | Write | |
| AV | 3131041 | Humidity Control Dehumidification Setpoint | Range 0.0-100.0 | % | Write | |
| AV | 3131051 | Humidity Control Humidification Offset Setpoint | Range 0.0-10.0 | % | Write | |
| AV | 3131061 | Humidity Control Dehumidification Offset Setpoint | Range 0.0-10.0 | % | Write | |
| AV | 3131071 | Humidity Setpoint | Range 0.0-100.0 | % | Write | |
| AV | 3232071 | Air Quality Setpoint | Range 0-3000 | ppm | Write | |
| AV | 133012 | Supply Air Fan Volume Flow Setpoint | Range 0-100000 | m³/h | Write | |
| AV | 133013 | Supply Air Fan Pressure Setpoint | Range 0-1000 | Pa | Write | |
| AV | 133014 | Supply Air Fan Manual Setpoint | Range 0.0-100.0 | % | Write | |
| AV | 133024 | Supply Air Fan Control Offset Setpoint | Range -100.0-100.0 | % | Write | |
| AV | 133025 | Supply Air Fan Control Factor Setpoint | Range 0-5 | Write | ||
| AV | 133034 | Supply Air Fan Control Offset Absolut Setpoint | Range 0.00-655.35 | m³/h | Write | |
| AV | 233012 | Extract Air Fan Volume Flow Setpoint | Range 0-100000 | m³/h | Write | |
| AV | 233013 | Extract Air Fan Pressure Setpoint | Range 0-1000 | Pa | Write | |
| AV | 233014 | Extract Air Fan Setpoint | Range 0.0-100.0 | % | Write | |
| AV | 233024 | Extract Air Fan Control Offset Setpoint | Range -100.0-100.0 | % | Write | |
| AV | 233025 | Extract Air Fan Control Factor Setpoint | Range 0-5 | Write | ||
| AV | 233034 | Extract Air Fan Control Offset Absolut Setpoint | Range 0.00-655.35 | m³/h | Write | |
| AV | 2929011 | Damper Control Outdoor Air Amount Setpoint | Range 0-100 | % | Write | |
| AV | 106011 | Supply Air Temperature Control Value | Range -50.0-200.0 | °C | Read | |
| AV | 206011 | Extract Air Temperature Control Value | Range -50.0-200.0 | °C | Read | |
| AV | 306011 | Outdoor Air Temperature Control Value | Range -50.0-200.0 | °C | Read | |
| AV | 706011 | Room Air Temperature Control Value | Range -50.0-200.0 | °C | Read | |
| AV | 2006011 | Outdoor Air external Temperature Control Value | Range -50.0-200.0 | °C | Read | |
| AV | 3030231 | Temperature Control Value | Range n/a | °C | Read | |
| AV | 3030011 | Temperature Control Heating Setpoint Control Value | Range 5.0-45.0 | °C | Read | |
| AV | 3030012 | Temperature Control Heating Active Setpoint Control Value | Range 5.0-45.0 | °C | Read | |
| AV | 3030021 | Temperature Control Cooling Setpoint Control Value | Range 5.0-45.0 | °C | Read | |
| AV | 3030022 | Temperature Control Cooling Active Setpoint Control Value | Range 5.0-45.0 | °C | Read | |
| AV | 3030072 | Temperature Control Cascade Heating Setpoint | Range 10.0 to 45.0 | °C | Read | |
| AV | 3030232 | Temperature Control Cascade Control Value | Range n/a | °C | Read | |
| AV | 3030073 | Temperature Control Base Setpoint | Range 5.0-45.0 | °C | Read | |
| AV | 3030171 | Temperature Control Supply Air Minimum Relative Setpoint | Range -10.0-0.0 | ΔK | Read | |
| AV | 3030181 | Temperature Control Supply Air Maximum Relative Setpoint | Range 0.0-10.0 | ΔK | Read | |
| AV | 3030191 | Temperature Control Supply Air Minimum Absolute Setpoint | Range 10.0 to 45.0 | °C | Read | |
| AV | 3030201 | Temperature Control Supply Air Maximum Absolute Setpoint | Range 10.0 to 45.0 | °C | Read | |
| AV | 107022 | Supply Air Humidity Absolute Control Value | Range 0.0-20.0 | g/kg | Read | |
| AV | 207022 | Extract Air Humidity Absolute Control Value | Range 0.0-20.0 | g/kg | Read | |
| AV | 307022 | Outdoor Air Humidity Absolute Control Value | Range 0.0-20.0 | g/kg | Read | |
| AV | 707021 | Room Air Humidity 1 Absolute Value | Range 0.0-20.0 | g/kg | Read | |
| AV | 707022 | Room Air Humidity 2 Absolute Value | Range 0.0-20.0 | g/kg | Read | |
| AV | 707023 | Room Air Humidity 3 Absolute Value | Range 0.0-20.0 | g/kg | Read | |
| AV | 707024 | Room Air Humidity 4 Absolute Value | Range 0.0-20.0 | g/kg | Read | |
| AV | 707025 | Room Air Humidity Absolute Control Value | Range 0.0-20.0 | g/kg | Read | |
| AV | 2007022 | Outdoor Air External Humidity Absolute Control Value | Range 0.0-20.0 | g/kg | Read | |
| AV | 107011 | Supply Air Humidity Relative Control Value | Range -50.0-200.0 | % | Read | |
| AV | 207011 | Extract Air Humidity Relative Control Value | Range -50.0-200.0 | % | Read | |
| AV | 307011 | Outdoor Air Humidity Relative Control Value | Range -50.0-200.0 | % | Read | |
| AV | 707011 | Room Air Humidity Relative Control Value | Range -50.0-200.0 | % | Read | |
| AV | 2007011 | Outdoor Air External Humidity Relative Control Value | Range -50.0-200.0 | % | Read | |
| AV | 3131011 | Humidity Control Humidification Setpoint Control Value | Range 0.0-100.0 | % | Read | |
| AV | 3131021 | Humidity Control Dehumidification Setpoint Control Value | Range 0.0-100.0 | % | Read | |
| AV | 3131231 | Humidity Control Value | Range n/a | % | Read | |
| AV | 3131072 | Humidity Control Cascade Humidification Setpoint | Range 0.0-100.0 | % | Read | |
| AV | 3131232 | Humidity Control Cascade Control Value | Range n/a | % | Read | |
| AV | 3131171 | Humidity Control Supply Air Minimum Relative Setpoint | Range 0.0-100.0 | % | Read | |
| AV | 3131181 | Humidity Control Supply Air Maximum Relative Setpoint | Range 0.0-100.0 | % | Read | |
| AV | 3131191 | Humidity Control Supply Air Minimum Absolute Setpoint | Range 0-20 | g/kg | Read | |
| AV | 3131201 | Humidity Control Supply Air Maximum Absolute Setpoint | Range 0-20 | g/kg | Read | |
| AV | 208011 | Extract Air Quality Control Value | Range 0.0-3000.0 | Ppm | Read | |
| AV | 708011 | Room Air Quality Control Value | Range 0.0-3000.0 | ppm | Read | |
| AV | 3232011 | Air Quality Control Setpoint Control Value | Range 0-2500 | ppm | Read | |
| AV | 3232231 | Air Quality Control Value | Range 0-5000 | Ppm | Read | |
| AV | 3939021 | Unit On Operating Hours | Range 0-65535 | h | Read | |
| AV | 3939081 | Order Number | Range 0-65535 | Read | ||
| AV | 3939151 | Temperature Control Room frost protection Hysterisis Setpoint | Range 0.0-20.0 | ΔK | Read | |
| AV | 4010011 | Specific Fan Power | Range 0-65535 | Wh/m³ | Read | |
| AV | 133015 | Supply Air Fan Control Volume Flow Setpoint Control Value | Range 0-100000 | m³/h | Read | |
| AV | 133016 | Supply Air Fan Control Pressure Setpoint Control Value | Range 0-1000 | Pa | Read | |
| AV | 133017 | Supply Air Fan Control Manual Setpoint Control Value | Range 0.0-100.0 | % | Read | |
| AV | 133031 | Supply Air Fan Calculated Volume Flow | Range -327680-327670 | m³/h | Read | |
| AV | 233015 | Extract Air Fan Control Volume Flow Setpoint Control Value | Range 0-100000 | m³/h | Read | |
| AV | 233016 | Extract Air Fan Control Pressure Setpoint Control Value | Range 0-5000 | Pa | Read | |
| AV | 233017 | Extract Air Fan Control Manual Setpoint Control Value | Range 0.0-100.0 | % | Read | |
| AV | 233031 | Extract Air Fan Calculated Volume Flow | Range -327680-327670 | m³/h | Read | |
| AV | 112031 | Supply Air Electric Heater 1 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 112021 | Supply Air Electric Reheater 1 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 312011 | Outdoor Air Electric Preheater 1 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 2128021 | DX Condensing Unit Stage 1 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 2128031 | DX Condensing Unit Stage 2 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 2128041 | DX Mitsubishi Inverter Stage 1 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 2128051 | DX Mitsubishi Inverter Stage 2 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 2128061 | DX Daikin Inverter Stage 1 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 2128071 | DX Daikin Inverter Stage 2 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 103013 | Supply Air Heater 1 Pump Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 103023 | Supply Air Heater 2 Pump Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 103033 | Supply Air Cooler Pump 1 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 103043 | Supply Air Cooler Pump 2 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 103063 | Supply Air Reheater 1 Pump Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 303013 | Outdoor Air Preheater 1 Pump Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 803013 | Energy Recovery System Pump 1 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 805013 | Energy Recovery System 1 Motor Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 101011 | Supply Air Fan 1 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 101021 | Supply Air Fan 2 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 101031 | Supply Air Fan 3 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 101041 | Supply Air Fan 4 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 101051 | Supply Air Fan 5 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 101061 | Supply Air Fan 6 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 101071 | Supply Air Fan 7 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 101081 | Supply Air Fan 8 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 201011 | Extract Air Fan 1 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 201021 | Extract Air Fan 2 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 201031 | Extract Air Fan 3 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 201041 | Extract Air Fan 4 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 201051 | Extract Air Fan 5 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 201061 | Extract Air Fan 6 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 201071 | Extract Air Fan 7 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 201081 | Extract Air Fan 8 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 4101011 | Smoke Extraction Fan 1 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 4101021 | Smoke Extraction Fan 2 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 4101031 | Smoke Extraction Fan 3 Operating Hours | Range 0-2147483647 | h | Read | |
| AV | 4101012 | Smoke Extraction Fan 1 Standstill Days | Range 0-100 | d | Read | |
| AV | 4101022 | Smoke Extraction Fan 2 Standstill Days | Range 0-100 | d | Read | |
| AV | 4101032 | Smoke Extraction Fan 3 Standstill Days | Range 0-100 | d | Read | |
| BI | 112021 | Supply Air Electric Reheater 1 Fault | Read | Inactive=Fault; Active=Ok | ||
| BI | 112031 | Supply Air Electric Heater 1 Fault | Read | Inactive=Fault; Active=Ok | ||
| BI | 312011 | Outdoor Air Electric Preheater 1 Fault | Read | Inactive=Fault; Active=Ok | ||
| BI | 2128021 | DX Condensing Unit Stage 1 Fault | Read | Inactive=Fault; Active=Ok | ||
| BI | 2128031 | DX Condensing Unit Stage 2 Fault | Read | Inactive=Fault; Active=Ok | ||
| BI | 2128041 | DX Mitsubishi Inverter Stage 1 Fault | Read | Inactive=Fault; Active=Ok | ||
| BI | 2128043 | DX Mitsubishi Inverter Stage 1 Pre defrost Input | Read | Inactive=Off; Active=On | ||
| BI | 2128042 | DX Mitsubishi Inverter Stage 1 Defrost Input | Read | Inactive=Off; Active=On | ||
| BI | 2128051 | DX Mitsubishi Inverter Stage 2 Fault | Read | Inactive=Fault; Active=Ok | ||
| BI | 2128053 | DX Mitsubishi Inverter Stage 2 Pre defrost Input | Read | Inactive=Off; Active=On | ||
| BI | 2128052 | DX Mitsubishi Inverter Stage 2 Defrost Input | Read | Inactive=Off; Active=On | ||
| BI | 2128061 | DX Daikin Inverter Stage 1 Fault | Read | Inactive=Fault; Active=Ok | ||
| BI | 2128062 | DX Daikin Inverter Stage 1 Defrost Input | Read | Inactive=Off; Active=On | ||
| BI | 2128071 | DX Daikin Inverter Stage 2 Fault | Read | Inactive=Off; Active=On | ||
| BI | 2128072 | DX Daikin Inverter Stage 2 Defrost Input | Read | Inactive=Off; Active=On | ||
| BI | 103011 | Supply Air Heater 1 Pump Motor protection | Read | Inactive=Fault; Active=Ok | ||
| BI | 103021 | Supply Air Heater 2 Pump Motor protection | Read | Inactive=Fault; Active=Ok | ||
| BI | 103031 | Supply Air Cooler Pump 1 Motor protection | Read | Inactive=Fault; Active=Ok | ||
| BI | 103041 | Supply Air Cooler Pump 2 Motor protection | Read | Inactive=Fault; Active=Ok | ||
| BI | 103061 | Supply Air Reheater 1 Pump Motor protection | Read | Inactive=Fault; Active=Ok | ||
| BI | 303011 | Outdoor Air Preheater 1 Pump Motorprotection | Read | Inactive=Fault; Active=Ok | ||
| BI | 803011 | Energy Recovery System 1 Pump Motor protection | Read | Inactive=Fault; Active=Ok | ||
| BI | 805012 | Energy Recovery System 1 Motor Rotation Guard Input | Read | Inactive=Off; Active=On | ||
| BI | 805011 | Energy Recovery System 1 Motor Motor protection | Read | Inactive=Fault; Active=Ok | ||
| BOmin | 3939031 | Alarm Collective A | Read | Inactive=Off; Active=On | ||
| BOmin | 3939041 | Alarm Collective B | Read | Inactive=Off; Active=On | ||
| BO | 3939011 | Alarm New A | Read | Inactive=Off; Active=On | ||
| BO | 3939021 | Alarm New B | Read | Inactive=Off; Active=On | ||
| BO | 3939161 | Heating Request | Read | Inactive=Off; Active=On | ||
| BO | 3939171 | Cooling Request | Read | Inactive=Off; Active=On | ||
| BO | 4141011 | Fire Alarm Indication | Read | Inactive=Ok; Active=Fault | ||
| BO | 112021 | Supply Air Electric Reheater 1 On | Read | Inactive=Off; Active=On | ||
| BO | 112031 | Supply Air Electric Heater 1 On | Read | Inactive=Off; Active=On | ||
| BO | 312011 | Outdoor Air Electric Preheater 1 On | Read | Inactive=Off; Active=On | ||
| BO | 2128021 | DX Condensing Unit Stage 1 On | Read | Inactive=Off; Active=On | ||
| BO | 2128031 | DX Condensing Unit Stage 2 On | Read | Inactive=Off; Active=On | ||
| BO | 2128041 | DX Mitsubishi Inverter Stage 1 On | Read | Inactive=Off; Active=On | ||
| BO | 2128042 | DX Mitsubishi Inverter Stage 1 Heating Output | Read | Inactive=Off; Active=On | ||
| BO | 2128051 | DX Mitsubishi Inverter Stage 2 On | Read | Inactive=Off; Active=On | ||
| BO | 2128052 | DX Mitsubishi Inverter Stage 2 Heating Output | Read | Inactive=Off; Active=On | ||
| BO | 2128061 | DX Daikin Inverter Stage 1 On | Read | Inactive=Off; Active=On | ||
| BO | 2128062 | DX Daikin Inverter Stage 1 Heating Output | Read | Inactive=Off; Active=On | ||
| BO | 2128071 | DX Daikin Inverter Stage 2 On | Read | Inactive=Off; Active=On | ||
| BO | 2128072 | DX Daikin Inverter Stage 2 Heating Output | Read | Inactive=Off; Active=On | ||
| BO | 103011 | Supply Air Heater 1 Pump On | Read | Inactive=Off; Active=On | ||
| BO | 103021 | Supply Air Heater 2 Pump On | Read | Inactive=Off; Active=On | ||
| BO | 103031 | Supply Air Cooler 1 Pump On | Read | Inactive=Off; Active=On | ||
| BO | 103041 | Supply Air Cooler 2 Pump On | Read | Inactive=Off; Active=On | ||
| BO | 103061 | Supply Air Reheater 1 Pump On | Read | Inactive=Off; Active=On | ||
| BO | 303011 | Outdoor Air Preheater 1 Pump On | Read | Inactive=Off; Active=On | ||
| BO | 803011 | Energy Recovery System 1 Pump On | Read | Inactive=Off; Active=On | ||
| BO | 104011 | Supply Air Heater 1 Valve Open | Read | Inactive=Off; Active=On | ||
| BO | 104012 | Supply Air Heater 1 Valve Close | Read | Inactive=Off; Active=On | ||
| BO | 104021 | Supply Air Heater 2 Valve Open | Read | Inactive=Off; Active=On | ||
| BO | 104022 | Supply Air Heater 2 Valve Close | Read | Inactive=Off; Active=On | ||
| BO | 104031 | Supply Air Cooler Valve 1 Open | Read | Inactive=Off; Active=On | ||
| BO | 104032 | Supply Air Cooler Valve 1 Close | Read | Inactive=Off; Active=On | ||
| BO | 104041 | Supply Air Cooler Valve 2 Open | Read | Inactive=Off; Active=On | ||
| BO | 104042 | Supply Air Cooler Valve 2 Close | Read | Inactive=Off; Active=On | ||
| BO | 104061 | Supply Air Reheater 1 Valve Open | Read | Inactive=Off; Active=On | ||
| BO | 104062 | Supply Air Reheater 1 Valve Close | Read | Inactive=Off; Active=On | ||
| BO | 304011 | Outdoor Air Preheater 1 Valve Open | Read | Inactive=Off; Active=On | ||
| BO | 304012 | Outdoor Air Preheater 1 Valve Close | Read | Inactive=Off; Active=On | ||
| BO | 804011 | Energy Recovery System 1 Valve Open | Read | Inactive=Off; Active=On | ||
| BO | 804012 | Energy Recovery System 1 Valve Close | Read | Inactive=Off; Active=On | ||
| BO | 805011 | Energy Recovery System 1 Motor On | Read | Inactive=Off; Active=On | ||
| BO | 101011 | Supply Air Fan 1 On | Read | Inactive=Off; Active=On | ||
| BO | 101021 | Supply Air Fan 2 On | Read | Inactive=Off; Active=On | ||
| BO | 101031 | Supply Air Fan 3 On | Read | Inactive=Off; Active=On | ||
| BO | 101041 | Supply Air Fan 4 On | Read | Inactive=Off; Active=On | ||
| BO | 101051 | Supply Air Fan 5 On | Read | Inactive=Off; Active=On | ||
| BO | 101061 | Supply Air Fan 6 On | Read | Inactive=Off; Active=On | ||
| BO | 101071 | Supply Air Fan 7 On | Read | Inactive=Off; Active=On | ||
| BO | 101081 | Supply Air Fan 8 On | Read | Inactive=Off; Active=On | ||
| BO | 201011 | Extract Air Fan 1 On | Read | Inactive=Off; Active=On | ||
| BO | 201021 | Extract Air Fan 2 On | Read | Inactive=Off; Active=On | ||
| BO | 201031 | Extract Air Fan 3 On | Read | Inactive=Off; Active=On | ||
| BO | 201041 | Extract Air Fan 4 On | Read | Inactive=Off; Active=On | ||
| BO | 201051 | Extract Air Fan 5 On | Read | Inactive=Off; Active=On | ||
| BO | 201061 | Extract Air Fan 6 On | Read | Inactive=Off; Active=On | ||
| BO | 201071 | Extract Air Fan 7 On Digital Output | Read | Inactive=Off; Active=On | ||
| BO | 201081 | Extract Air Fan 8 On | Read | Inactive=Off; Active=On | ||
| BO | 102011 | Supply Air Damper 1 Open | Read | Inactive=Off; Active=On | ||
| BO | 102012 | Supply Air Damper 1 Close | Read | Inactive=Off; Active=On | ||
| BO | 202011 | Extract Air Damper 1 Open | Read | Inactive=Off; Active=On | ||
| BO | 202012 | Extract Air Damper 1 Close | Read | Inactive=Off; Active=On | ||
| BO | 302011 | Outdoor Air Damper 1 Open | Read | Inactive=Off; Active=On | ||
| BO | 302012 | Outdoor Air Damper 1 Close | Read | Inactive=Off; Active=On | ||
| BO | 302021 | Outdoor Air Bypass Damper Open | Read | Inactive=Off; Active=On | ||
| BO | 302022 | Outdoor Air Bypass Damper Close | Read | Inactive=Off; Active=On | ||
| BO | 402011 | Exhaust Air Damper 1 Open | Read | Inactive=Off; Active=On | ||
| BO | 402012 | Exhaust Air Damper 1 Close | Read | Inactive=Off; Active=On | ||
| BO | 402021 | Exhaust Air Bypass Damper Open | Read | Inactive=Off; Active=On | ||
| BO | 402022 | Exhaust Air Bypass Damper Close | Read | Inactive=Off; Active=On | ||
| BO | 602011 | Recirculation Air Damper 1 Open | Read | Inactive=Off; Active=On | ||
| BO | 602012 | Recirculation Air Damper 1 Close | Read | Inactive=Off; Active=On | ||
| BO | 4102011 | Smoke Bypass Damper Open | Read | Inactive=Off; Active=On | ||
| BO | 4102012 | Smoke Bypass Damper Close | Read | Inactive=Off; Active=On | ||
| BO | 4101011 | Smoke Extraction Fan 1 On | Read | Inactive=Off; Active=On | ||
| BO | 4101021 | Smoke Extraction Fan 2 On | Read | Inactive=Off; Active=On | ||
| BO | 4101031 | Smoke Extraction Fan 3 On | Read | Inactive=Off; Active=On | ||
| BV | 3030081 | Unit Enable Via Temperature Control | Write | Inactive=Off; Active=On | ||
| BV | 3030111 | Temperature Control Relative Setpoint | Write | Inactive=Off; Active=On | ||
| BV | 3131081 | Unit Enable Via Humidity Control | Write | Inactive=Off; Active=On | ||
| BV | 3131101 | Humidity Control Enable | Write | Inactive=Off; Active=On | ||
| BV | 3232081 | Unit Enable Via Air Quality Control | Write | Inactive=Off; Active=On | ||
| BV | 3232101 | Air Quality Control Enable | Write | Inactive=Off; Active=On | ||
| BV | 106011 | Supply Air Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 106031 | Supply Air Fan Nozzle Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 106041 | Supply Air Heater 1 Inlet Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 106051 | Supply Air Heater 1 Outlet Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 106061 | Supply Air Heater 2 Inlet Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 106071 | Supply Air Heater 2 Outlet Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 106081 | Supply Air Cooler 1 Inlet Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 106091 | Supply Air Cooler 1 Outlet Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 106101 | Supply Air Cooler 2 Inlet Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 106111 | Supply Air Cooler 2 Outlet Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 106141 | Supply Air Reheater 1 Inlet Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 106151 | Supply Air Reheater 1 Outlet Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 206011 | Extract Air Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 206071 | Extract Air Fan Nozzle Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 306011 | Outdoor Air Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 306021 | Outdoor Air Filter Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 306031 | Outdoor Air Preheater 1 Inlet Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 306041 | Outdoor Air Preheater 1 Outlet Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 406011 | Exhaust Air Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 706011 | Room Air Temperature Sensor 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 706021 | Room Air Temperature Sensor 2 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 706031 | Room Air Temperature Sensor 3 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 706041 | Room Air Temperature Sensor 4 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 806011 | Energy Recovery System 1 Inlet Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 806021 | Energy Recovery System 1 Outlet Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 806031 | Supply Air Temperature Sensor Behind Energy Recovery System Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 806041 | Exhaust Air Temperature Sensor Behind Energy Recovery System Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 806051 | Energy Recovery System Icing Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 2006011 | Outdoor Air External Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 2106011 | Evaporator 1 Temperature Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 107011 | Supply Humidity Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 207011 | Extract Air Humidity Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 307011 | Outdoor Air Humidity Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 407011 | Exhaust Air Humidity Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 707011 | Room Air Humidity Sensor 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 707021 | Room Air Humidity Sensor 2 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 707031 | Room Air Humidity Sensor 3 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 707041 | Room Air Humidity Sensor 4 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 2007011 | Outdoor Air External Humidity Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 208011 | Extract Air Quality Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 308011 | Outdoor Air Quality Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 708011 | Room Air Quality Sensor 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 708021 | Room Air Quality Sensor 2 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 708031 | Room Air Quality Sensor 3 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 708041 | Room Air Quality Sensor 4 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 109011 | Supply Air Filter Pressure Sensor 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 109021 | Supply Air Filter Pressure Sensor 2 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 109031 | Supply Air Nozzle Pressure Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 109041 | Supply Air Duct Pressure Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 209011 | Extract Air Filter Pressure Sensor 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 209021 | Extract Air Filter Pressure Sensor 2 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 209031 | Extract Air Duct Pressure Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 209041 | Extract Air Nozzle Pressure Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 309011 | Outdoor Air Filter Pressure Sensor 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 309021 | Outdoor Air Filter Pressure Sensor 2 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 309031 | Outdoor Air Bypass Pressure Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 409011 | Exhaust Air Bypass Pressure Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 809011 | Energy Recovery System Pressure Sensor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 3939161 | Unit On | Read | Inactive=Off; Active=On | ||
| BV | 830031 | Energy Recovery System Control Anti Icing Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 3939171 | Warmup Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 3030012 | Value Monitoring Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 3030013 | Value Tripping with Acknowledge Monitoring Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 3030011 | Value Monitoring Tripping Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 4141012 | Fire Alarm Fault | Read | Inactive=Ok; Active=Alarm | ||
| BV | 112021 | Supply Air Electric Reheater 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 112031 | Supply Air Electric Heater 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 312011 | Outdoor Air Electric Preheater 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 2128021 | DX Condensing Unit Stage 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 2128031 | DX Condensing Unit Stage 2 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 2128041 | DX Mitsubishi Inverter Stage 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 2128051 | DX Mitsubishi Inverter Stage 2 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 2128061 | DX Daikin Inverter Stage 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 2128071 | DX Daikin Inverter Stage 2 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 2128011 | DX Freeze Protection Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 110012 | Supply Air Heater 1 Frost Protection Air Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 110022 | Supply Air Heater 2 Frost Protection Air Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 310011 | Outdoor Air Preheater 1 Frost Protection Air Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 110031 | Supply Air Reheater 1 Frost Protection Air Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 103011 | Supply Air Heater 1 Pump Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 103021 | Supply Air Heater 2 Pump Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 103031 | Supply Air Cooler Pump 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 103041 | Supply Air Cooler Pump 2 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 103061 | Supply Air Reheater 1 Pump Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 303011 | Outdoor Air Preheater 1 Pump Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 803011 | Energy Recovery System Pump 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 104011 | Supply Air Heater 1 Valve Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 104021 | Supply Air Heater 2 Valve Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 104031 | Supply Air Cooler Valve 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 104041 | Supply Air Cooler Valve 2 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 104061 | Supply Air Reheater 1 Valve Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 304011 | Outdoor Air Preheater 1 Valve Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 804011 | Energy Recovery System 1 Valve Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 805011 | Energy Recovery System 1 Motor Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 805012 | Energy Recovery System 1 Motor Rotation Monitoring Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 101011 | Supply Air Fan 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 101021 | Supply Air Fan 2 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 101031 | Supply Air Fan 3 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 101041 | Supply Air Fan 4 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 101051 | Supply Air Fan 5 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 101061 | Supply Air Fan 6 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 101071 | Supply Air Fan 7 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 101081 | Supply Air Fan 8 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 201011 | Extract Air Fan 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 201021 | Extract Air Fan 2 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 201031 | Extract Air Fan 3 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 201041 | Extract Air Fan 4 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 201051 | Extract Air Fan 5 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 201061 | Extract Air Fan 6 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 201071 | Extract Air Fan 7 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 201081 | Extract Air Fan 8 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 102011 | Supply Air Damper 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 202011 | Extract Air Damper 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 302011 | Outdoor Air Damper 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 302021 | Outdoor Air Bypass Damper Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 402011 | Exhaust Air Damper 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 402021 | Exhaust Air Bypass Damper Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 602011 | Recirculation Air Damper 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 4102011 | Smoke Bypass Damper Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 4101011 | Smoke Extraction Fan 1 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 4101021 | Smoke Extraction Fan 2 Fault | Read | Inactive=Ok; Active=Fault | ||
| BV | 4101031 | Smoke Extraction Fan 3 Fault | Read | Inactive=Ok; Active=Fault | ||
| MV | 3030011 | Temperature Control Type | Write | 1=None; 2=Supply Air; 3=Extract; 4=Room Air; 5=Extract Cascade; 6=Room Cascade; 7=Outdoor Air Curve | ||
| MV | 3030012 | Temperature Control Mode | Write | 1=Automatic; 2=Heating; 3=Cooling; 4=Night Purge | ||
| MV | 3131011 | Humidity Control Type | Write | 1=None; 2=Supply Air; 3=Extract Air; 4=Room Air; 5=Extract Air Cascade; 6=Room Air Cascade | ||
| MV | 3131012 | Humidity Control Mode | Write | 1=Automatic; 2=Heating; 3=Cooling | ||
| MV | 3232011 | Air Quality Control Type | Write | 1=None; 2=Extract Air; 3=Room Air | ||
| MV | 3232012 | Air Quality Control Mode | Write | 1=Passive; 2=Active; 3=Passive/Active; 4=Active/Passive | ||
| MVmin | 3939011 | Unit Operation Mode | Write | 1=Automatic; 2=Room Frost Protection; 3=Low Speed; 4=High Speed; 5=Free Profile 1; 6=Free Profile 2; 7=Night Purge | ||
| MVmin | 3939091 | Unit Operation Mode Actual | Write | 1=Room Frost Protection; 2=Low Speed; 3=High Speed; 4=Free Profile 1; 5=Free Profile 2; 6=Night Purge; 7=Boost | ||
| SCH | 3903011 | Pump Kick SO | Read | |||
| SCH | 3904011 | Valve Lime Kick SO | Read | |||
| SCH | 3939011 | Unit Operation Mode SO | Read | |||
| SCH | 3939181 | Change Over SO | Read | |||
| SCH | 4139011 | Smoke Bypass Damper Exercise SO | Read |
No points match these filters.
Object ID lookup: FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs point IDs by name
AI3030042Temperature Control External SetpointAI3030043Temperature Control External Relative SetpointAI3131042Humidity Control External SetpointAI3232042Air Quality Control External SetpointAI133022Supply Air Fan Control Volume Flow External SetpointAI133023Supply Air Fan Control Pressure External SetpointAI133024Supply Air Fan Control Manual External SetpointAI233022Extract Air Fan Control Volume Flow External SetpointAI233023Extract Air Fan Control Pressure External SetpointAI233024Extract Air Fan Control Manual External SetpointAI2929011Damper Control Outdoor Air Amount External SetpointAI106011Supply Air Temperature SensorAI106031Supply Air Fan Nozzle Temperature SensorAI106041Supply Air Heater 1 Inlet Temperature SensorAI106051Supply Air Heater 1 Outlet Temperature SensorAI106061Supply Air Heater 2 Inlet Temperature SensorAI106071Supply Air Heater 2 Outlet Temperature SensorAI106081Supply Air Cooler 1 Inlet Temperature SensorAI106091Supply Air Cooler 1 Outlet Temperature SensorAI106101Supply Air Cooler 2 Inlet Temperature SensorAI106111Supply Air Cooler 2 Outlet Temperature SensorAI106141Supply Air Reheater 1 Inlet Temperature SensorAI106151Supply Air Reheater 1 Outlet Temperature SensorAI206011Extract Air Temperature SensorAI206071Extract Air Fan Nozzle Temperature SensorAI306011Outdoor Air Temperature SensorAI306021Outdoor Air Filter Temperature SensorAI306031Outdoor Air Preheater 1 Inlet Temperature SensorAI306041Outdoor Air Preheater 1 Outlet Temperature SensorAI406011Exhaust Air Temperature SensorAI706011Room Air Temperature Sensor 1AI706021Room Air Temperature Sensor 2AI706031Room Air Temperature Sensor 3AI706041Room Air Temperature Sensor 4AI806011Energy Recovery System 1 Inlet Temperature SensorAI806021Energy Recovery System 1 Outlet Temperature SensorAI806031Supply Air Temperature Sensor Behind Energy Recovery SystemAI806041Exhaust Air Temperature Sensor Behind Energy Recovery SystemAI806051Energy Recovery System Icing Temperature SensorAI2006011Outdoor Air External Temperature SensorAI2106011Evaporator 1 Temperature SensorAI107011Supply Humidity SensorAI207011Extract Air Humidity SensorAI307011Outdoor Air Humidity SensorAI407011Exhaust Air Humidity SensorAI707011Room Air Humidity Sensor 1AI707021Room Air Humidity Sensor 2AI707031Room Air Humidity Sensor 3AI707041Room Air Humidity Sensor 4AI2007011Outdoor Air External Humidity SensorAI208011Extract Air Quality SensorAI308011Outdoor Air Quality SensorAI708011Room Air Quality Sensor 1AI708021Room Air Quality Sensor 2AI708031Room Air Quality Sensor 3AI708041Room Air Quality Sensor 4AI109011Supply Air Filter Pressure Sensor 1AI109021Supply Air Filter Pressure Sensor 2AI109031Supply Air Nozzle Pressure SensorAI109041Supply Air Duct Pressure SensorAI209011Extract Air Filter Pressure 1 SensorAI209021Extract Air Filter Pressure 2 SensorAI209031Extract Air Duct Pressure SensorAI209041Extract Air Nozzle Pressure SensorAI309011Outdoor Air Filter Pressure 1 SensorAI309021Outdoor Air Filter Pressure Sensor 2AI309031Outdoor Air Bypass Pressure SensorAI409011Exhaust Air Bypass Pressure SensorAI809011Energy Recovery System Pressure SensorAI104011Supply Air Heater 1 Valve FeedbackAI104021Supply Air Heater 2 Valve FeedbackAI104031Supply Air Cooler Valve 1 FeedbackAI104041Supply Air Cooler Valve 2 FeedbackAI104061Supply Air Reheater 1 Valve FeedbackAI304011Outdoor Air Preheater 1 Valve FeedbackAI804011Energy Recovery System Valve 1 FeedbackAI102011Supply Air Damper 1 FeedbackAI202011Extract Air Damper 1 FeedbackAI302011Outdoor Air Damper 1 FeedbackAI302021Outdoor Air Bypass Damper FeedbackAI402011Exhaust Air Damper 1 FeedbackAI402021Exhaust Air Bypass Damper FeedbackAI602011Recirculation Air Damper 1 FeedbackAI4102011Smoke Bypass Damper FeedbackAO112031Supply Air Electric Heater 1 OutputAO112021Supply Air Electric Reheater 1 OutputAO312011Outdoor Air Electric Preheater 1 OutputAO2128041DX Mitsubishi Inverter Stage 1 OutputAO2128051DX Mitsubishi Inverter Stage 2 OutputAO2128061DX Daikin Inverter Stage 1 OutputAO2128071DX Daikin Inverter Stage 2 OutputAO103011Supply Air Heater 1 Pump OutputAO103021Supply Air Heater 2 Pump OutputAO103031Supply Air Cooler Pump 1 OutputAO103041Supply Air Cooler Pump 2 OutputAO103061Supply Air Reheater 1 Pump OutputAO303011Outdoor Air Preheater 1 Pump OutputAO803011Energy Recovery System 1 Pump OutputAO104011Supply Air Heater 1 Valve OutputAO104021Supply Air Heater 2 Valve OutputAO104031Supply Air Cooler Valve 1 OutputAO104041Supply Air Cooler Valve 2 OutputAO104061Supply Air Reheater 1 Valve OutputAO304011Outdoor Air Preheater 1 Valve OutputAO804011Energy Recovery System Valve 1 OutputAO805011Energy Recovery System 1 Motor OutputAO101011Supply Air Fan 1 OutputAO101021Supply Air Fan 2 OutputAO101031Supply Air Fan 3 OutputAO101041Supply Air Fan 4 OutputAO101051Supply Air Fan 5 OutputAO101061Supply Air Fan 6 OutputAO101071Supply Air Fan 7 OutputAO101081Supply Air Fan 8 OutputAO201011Extract Air Fan 1 OutputAO201021Extract Air Fan 2 OutputAO201031Extract Air Fan 3 OutputAO201041Extract Air Fan 4 OutputAO201051Extract Air Fan 5 OutputAO201061Extract Air Fan 6 OutputAO201071Extract Air Fan 7 OutputAO201081Extract Air Fan 8 OutputAO102011Supply Air Damper 1 OutputAO202011Extract Air Damper 1 OutputAO302011Outdoor Air Damper 1 OutputAO302021Outdoor Air Bypass Damper OutputAO402011Exhaust Air Damper 1 OutputAO402021Exhaust Air Bypass Damper OutputAO602011Recirculation Air Damper 1 OutputAO4102011Smoke Bypass Damper OutputAO4101011Smoke Extraction Fan 1 OutputAO4101021Smoke Extraction Fan 2 OutputAO4101031Smoke Extraction Fan 3 OutputAV3030031Temperature Control Heating SetpointAV3030041Temperature Control Cooling SetpointAV3030051Temperature Control Heating Offset SetpointAV3030061Temperature Control Cooling Offset SetpointAV3030071Temperature Control SetpointAV3030081Temperature Control Relative SetpointAV3131031Humidity Control Humidification SetpointAV3131041Humidity Control Dehumidification SetpointAV3131051Humidity Control Humidification Offset SetpointAV3131061Humidity Control Dehumidification Offset SetpointAV3131071Humidity SetpointAV3232071Air Quality SetpointAV133012Supply Air Fan Volume Flow SetpointAV133013Supply Air Fan Pressure SetpointAV133014Supply Air Fan Manual SetpointAV133024Supply Air Fan Control Offset SetpointAV133025Supply Air Fan Control Factor SetpointAV133034Supply Air Fan Control Offset Absolut SetpointAV233012Extract Air Fan Volume Flow SetpointAV233013Extract Air Fan Pressure SetpointAV233014Extract Air Fan SetpointAV233024Extract Air Fan Control Offset SetpointAV233025Extract Air Fan Control Factor SetpointAV233034Extract Air Fan Control Offset Absolut SetpointAV2929011Damper Control Outdoor Air Amount SetpointAV106011Supply Air Temperature Control ValueAV206011Extract Air Temperature Control ValueAV306011Outdoor Air Temperature Control ValueAV706011Room Air Temperature Control ValueAV2006011Outdoor Air external Temperature Control ValueAV3030231Temperature Control ValueAV3030011Temperature Control Heating Setpoint Control ValueAV3030012Temperature Control Heating Active Setpoint Control ValueAV3030021Temperature Control Cooling Setpoint Control ValueAV3030022Temperature Control Cooling Active Setpoint Control ValueAV3030072Temperature Control Cascade Heating SetpointAV3030232Temperature Control Cascade Control ValueAV3030073Temperature Control Base SetpointAV3030171Temperature Control Supply Air Minimum Relative SetpointAV3030181Temperature Control Supply Air Maximum Relative SetpointAV3030191Temperature Control Supply Air Minimum Absolute SetpointAV3030201Temperature Control Supply Air Maximum Absolute SetpointAV107022Supply Air Humidity Absolute Control ValueAV207022Extract Air Humidity Absolute Control ValueAV307022Outdoor Air Humidity Absolute Control ValueAV707021Room Air Humidity 1 Absolute ValueAV707022Room Air Humidity 2 Absolute ValueAV707023Room Air Humidity 3 Absolute ValueAV707024Room Air Humidity 4 Absolute ValueAV707025Room Air Humidity Absolute Control ValueAV2007022Outdoor Air External Humidity Absolute Control ValueAV107011Supply Air Humidity Relative Control ValueAV207011Extract Air Humidity Relative Control ValueAV307011Outdoor Air Humidity Relative Control ValueAV707011Room Air Humidity Relative Control ValueAV2007011Outdoor Air External Humidity Relative Control ValueAV3131011Humidity Control Humidification Setpoint Control ValueAV3131021Humidity Control Dehumidification Setpoint Control ValueAV3131231Humidity Control ValueAV3131072Humidity Control Cascade Humidification SetpointAV3131232Humidity Control Cascade Control ValueAV3131171Humidity Control Supply Air Minimum Relative SetpointAV3131181Humidity Control Supply Air Maximum Relative SetpointAV3131191Humidity Control Supply Air Minimum Absolute SetpointAV3131201Humidity Control Supply Air Maximum Absolute SetpointAV208011Extract Air Quality Control ValueAV708011Room Air Quality Control ValueAV3232011Air Quality Control Setpoint Control ValueAV3232231Air Quality Control ValueAV3939021Unit On Operating HoursAV3939081Order NumberAV3939151Temperature Control Room frost protection Hysterisis SetpointAV4010011Specific Fan PowerAV133015Supply Air Fan Control Volume Flow Setpoint Control ValueAV133016Supply Air Fan Control Pressure Setpoint Control ValueAV133017Supply Air Fan Control Manual Setpoint Control ValueAV133031Supply Air Fan Calculated Volume FlowAV233015Extract Air Fan Control Volume Flow Setpoint Control ValueAV233016Extract Air Fan Control Pressure Setpoint Control ValueAV233017Extract Air Fan Control Manual Setpoint Control ValueAV233031Extract Air Fan Calculated Volume FlowAV112031Supply Air Electric Heater 1 Operating HoursAV112021Supply Air Electric Reheater 1 Operating HoursAV312011Outdoor Air Electric Preheater 1 Operating HoursAV2128021DX Condensing Unit Stage 1 Operating HoursAV2128031DX Condensing Unit Stage 2 Operating HoursAV2128041DX Mitsubishi Inverter Stage 1 Operating HoursAV2128051DX Mitsubishi Inverter Stage 2 Operating HoursAV2128061DX Daikin Inverter Stage 1 Operating HoursAV2128071DX Daikin Inverter Stage 2 Operating HoursAV103013Supply Air Heater 1 Pump Operating HoursAV103023Supply Air Heater 2 Pump Operating HoursAV103033Supply Air Cooler Pump 1 Operating HoursAV103043Supply Air Cooler Pump 2 Operating HoursAV103063Supply Air Reheater 1 Pump Operating HoursAV303013Outdoor Air Preheater 1 Pump Operating HoursAV803013Energy Recovery System Pump 1 Operating HoursAV805013Energy Recovery System 1 Motor Operating HoursAV101011Supply Air Fan 1 Operating HoursAV101021Supply Air Fan 2 Operating HoursAV101031Supply Air Fan 3 Operating HoursAV101041Supply Air Fan 4 Operating HoursAV101051Supply Air Fan 5 Operating HoursAV101061Supply Air Fan 6 Operating HoursAV101071Supply Air Fan 7 Operating HoursAV101081Supply Air Fan 8 Operating HoursAV201011Extract Air Fan 1 Operating HoursAV201021Extract Air Fan 2 Operating HoursAV201031Extract Air Fan 3 Operating HoursAV201041Extract Air Fan 4 Operating HoursAV201051Extract Air Fan 5 Operating HoursAV201061Extract Air Fan 6 Operating HoursAV201071Extract Air Fan 7 Operating HoursAV201081Extract Air Fan 8 Operating HoursAV4101011Smoke Extraction Fan 1 Operating HoursAV4101021Smoke Extraction Fan 2 Operating HoursAV4101031Smoke Extraction Fan 3 Operating HoursAV4101012Smoke Extraction Fan 1 Standstill DaysAV4101022Smoke Extraction Fan 2 Standstill DaysAV4101032Smoke Extraction Fan 3 Standstill DaysBI112021Supply Air Electric Reheater 1 FaultBI112031Supply Air Electric Heater 1 FaultBI312011Outdoor Air Electric Preheater 1 FaultBI2128021DX Condensing Unit Stage 1 FaultBI2128031DX Condensing Unit Stage 2 FaultBI2128041DX Mitsubishi Inverter Stage 1 FaultBI2128043DX Mitsubishi Inverter Stage 1 Pre defrost InputBI2128042DX Mitsubishi Inverter Stage 1 Defrost InputBI2128051DX Mitsubishi Inverter Stage 2 FaultBI2128053DX Mitsubishi Inverter Stage 2 Pre defrost InputBI2128052DX Mitsubishi Inverter Stage 2 Defrost InputBI2128061DX Daikin Inverter Stage 1 FaultBI2128062DX Daikin Inverter Stage 1 Defrost InputBI2128071DX Daikin Inverter Stage 2 FaultBI2128072DX Daikin Inverter Stage 2 Defrost InputBI103011Supply Air Heater 1 Pump Motor protectionBI103021Supply Air Heater 2 Pump Motor protectionBI103031Supply Air Cooler Pump 1 Motor protectionBI103041Supply Air Cooler Pump 2 Motor protectionBI103061Supply Air Reheater 1 Pump Motor protectionBI303011Outdoor Air Preheater 1 Pump MotorprotectionBI803011Energy Recovery System 1 Pump Motor protectionBI805012Energy Recovery System 1 Motor Rotation Guard InputBI805011Energy Recovery System 1 Motor Motor protectionBO3939031Alarm Collective ABO3939041Alarm Collective BBO3939011Alarm New ABO3939021Alarm New BBO3939161Heating RequestBO3939171Cooling RequestBO4141011Fire Alarm IndicationBO112021Supply Air Electric Reheater 1 OnBO112031Supply Air Electric Heater 1 OnBO312011Outdoor Air Electric Preheater 1 OnBO2128021DX Condensing Unit Stage 1 OnBO2128031DX Condensing Unit Stage 2 OnBO2128041DX Mitsubishi Inverter Stage 1 OnBO2128042DX Mitsubishi Inverter Stage 1 Heating OutputBO2128051DX Mitsubishi Inverter Stage 2 OnBO2128052DX Mitsubishi Inverter Stage 2 Heating OutputBO2128061DX Daikin Inverter Stage 1 OnBO2128062DX Daikin Inverter Stage 1 Heating OutputBO2128071DX Daikin Inverter Stage 2 OnBO2128072DX Daikin Inverter Stage 2 Heating OutputBO103011Supply Air Heater 1 Pump OnBO103021Supply Air Heater 2 Pump OnBO103031Supply Air Cooler 1 Pump OnBO103041Supply Air Cooler 2 Pump OnBO103061Supply Air Reheater 1 Pump OnBO303011Outdoor Air Preheater 1 Pump OnBO803011Energy Recovery System 1 Pump OnBO104011Supply Air Heater 1 Valve OpenBO104012Supply Air Heater 1 Valve CloseBO104021Supply Air Heater 2 Valve OpenBO104022Supply Air Heater 2 Valve CloseBO104031Supply Air Cooler Valve 1 OpenBO104032Supply Air Cooler Valve 1 CloseBO104041Supply Air Cooler Valve 2 OpenBO104042Supply Air Cooler Valve 2 CloseBO104061Supply Air Reheater 1 Valve OpenBO104062Supply Air Reheater 1 Valve CloseBO304011Outdoor Air Preheater 1 Valve OpenBO304012Outdoor Air Preheater 1 Valve CloseBO804011Energy Recovery System 1 Valve OpenBO804012Energy Recovery System 1 Valve CloseBO805011Energy Recovery System 1 Motor OnBO101011Supply Air Fan 1 OnBO101021Supply Air Fan 2 OnBO101031Supply Air Fan 3 OnBO101041Supply Air Fan 4 OnBO101051Supply Air Fan 5 OnBO101061Supply Air Fan 6 OnBO101071Supply Air Fan 7 OnBO101081Supply Air Fan 8 OnBO201011Extract Air Fan 1 OnBO201021Extract Air Fan 2 OnBO201031Extract Air Fan 3 OnBO201041Extract Air Fan 4 OnBO201051Extract Air Fan 5 OnBO201061Extract Air Fan 6 OnBO201071Extract Air Fan 7 On Digital OutputBO201081Extract Air Fan 8 OnBO102011Supply Air Damper 1 OpenBO102012Supply Air Damper 1 CloseBO202011Extract Air Damper 1 OpenBO202012Extract Air Damper 1 CloseBO302011Outdoor Air Damper 1 OpenBO302012Outdoor Air Damper 1 CloseBO302021Outdoor Air Bypass Damper OpenBO302022Outdoor Air Bypass Damper CloseBO402011Exhaust Air Damper 1 OpenBO402012Exhaust Air Damper 1 CloseBO402021Exhaust Air Bypass Damper OpenBO402022Exhaust Air Bypass Damper CloseBO602011Recirculation Air Damper 1 OpenBO602012Recirculation Air Damper 1 CloseBO4102011Smoke Bypass Damper OpenBO4102012Smoke Bypass Damper CloseBO4101011Smoke Extraction Fan 1 OnBO4101021Smoke Extraction Fan 2 OnBO4101031Smoke Extraction Fan 3 OnBV3030081Unit Enable Via Temperature ControlBV3030111Temperature Control Relative SetpointBV3131081Unit Enable Via Humidity ControlBV3131101Humidity Control EnableBV3232081Unit Enable Via Air Quality ControlBV3232101Air Quality Control EnableBV106011Supply Air Temperature Sensor FaultBV106031Supply Air Fan Nozzle Temperature Sensor FaultBV106041Supply Air Heater 1 Inlet Temperature Sensor FaultBV106051Supply Air Heater 1 Outlet Temperature Sensor FaultBV106061Supply Air Heater 2 Inlet Temperature Sensor FaultBV106071Supply Air Heater 2 Outlet Temperature Sensor FaultBV106081Supply Air Cooler 1 Inlet Temperature Sensor FaultBV106091Supply Air Cooler 1 Outlet Temperature Sensor FaultBV106101Supply Air Cooler 2 Inlet Temperature Sensor FaultBV106111Supply Air Cooler 2 Outlet Temperature Sensor FaultBV106141Supply Air Reheater 1 Inlet Temperature Sensor FaultBV106151Supply Air Reheater 1 Outlet Temperature Sensor FaultBV206011Extract Air Temperature Sensor FaultBV206071Extract Air Fan Nozzle Temperature Sensor FaultBV306011Outdoor Air Temperature Sensor FaultBV306021Outdoor Air Filter Temperature Sensor FaultBV306031Outdoor Air Preheater 1 Inlet Temperature Sensor FaultBV306041Outdoor Air Preheater 1 Outlet Temperature Sensor FaultBV406011Exhaust Air Temperature Sensor FaultBV706011Room Air Temperature Sensor 1 FaultBV706021Room Air Temperature Sensor 2 FaultBV706031Room Air Temperature Sensor 3 FaultBV706041Room Air Temperature Sensor 4 FaultBV806011Energy Recovery System 1 Inlet Temperature Sensor FaultBV806021Energy Recovery System 1 Outlet Temperature Sensor FaultBV806031Supply Air Temperature Sensor Behind Energy Recovery System FaultBV806041Exhaust Air Temperature Sensor Behind Energy Recovery System FaultBV806051Energy Recovery System Icing Temperature Sensor FaultBV2006011Outdoor Air External Temperature Sensor FaultBV2106011Evaporator 1 Temperature Sensor FaultBV107011Supply Humidity Sensor FaultBV207011Extract Air Humidity Sensor FaultBV307011Outdoor Air Humidity Sensor FaultBV407011Exhaust Air Humidity Sensor FaultBV707011Room Air Humidity Sensor 1 FaultBV707021Room Air Humidity Sensor 2 FaultBV707031Room Air Humidity Sensor 3 FaultBV707041Room Air Humidity Sensor 4 FaultBV2007011Outdoor Air External Humidity Sensor FaultBV208011Extract Air Quality Sensor FaultBV308011Outdoor Air Quality Sensor FaultBV708011Room Air Quality Sensor 1 FaultBV708021Room Air Quality Sensor 2 FaultBV708031Room Air Quality Sensor 3 FaultBV708041Room Air Quality Sensor 4 FaultBV109011Supply Air Filter Pressure Sensor 1 FaultBV109021Supply Air Filter Pressure Sensor 2 FaultBV109031Supply Air Nozzle Pressure Sensor FaultBV109041Supply Air Duct Pressure Sensor FaultBV209011Extract Air Filter Pressure Sensor 1 FaultBV209021Extract Air Filter Pressure Sensor 2 FaultBV209031Extract Air Duct Pressure Sensor FaultBV209041Extract Air Nozzle Pressure Sensor FaultBV309011Outdoor Air Filter Pressure Sensor 1 FaultBV309021Outdoor Air Filter Pressure Sensor 2 FaultBV309031Outdoor Air Bypass Pressure Sensor FaultBV409011Exhaust Air Bypass Pressure Sensor FaultBV809011Energy Recovery System Pressure Sensor FaultBV3939161Unit OnBV830031Energy Recovery System Control Anti Icing FaultBV3939171Warmup FaultBV3030012Value Monitoring FaultBV3030013Value Tripping with Acknowledge Monitoring FaultBV3030011Value Monitoring Tripping FaultBV4141012Fire Alarm FaultBV112021Supply Air Electric Reheater 1 FaultBV112031Supply Air Electric Heater 1 FaultBV312011Outdoor Air Electric Preheater 1 FaultBV2128021DX Condensing Unit Stage 1 FaultBV2128031DX Condensing Unit Stage 2 FaultBV2128041DX Mitsubishi Inverter Stage 1 FaultBV2128051DX Mitsubishi Inverter Stage 2 FaultBV2128061DX Daikin Inverter Stage 1 FaultBV2128071DX Daikin Inverter Stage 2 FaultBV2128011DX Freeze Protection FaultBV110012Supply Air Heater 1 Frost Protection Air FaultBV110022Supply Air Heater 2 Frost Protection Air FaultBV310011Outdoor Air Preheater 1 Frost Protection Air FaultBV110031Supply Air Reheater 1 Frost Protection Air FaultBV103011Supply Air Heater 1 Pump FaultBV103021Supply Air Heater 2 Pump FaultBV103031Supply Air Cooler Pump 1 FaultBV103041Supply Air Cooler Pump 2 FaultBV103061Supply Air Reheater 1 Pump FaultBV303011Outdoor Air Preheater 1 Pump FaultBV803011Energy Recovery System Pump 1 FaultBV104011Supply Air Heater 1 Valve FaultBV104021Supply Air Heater 2 Valve FaultBV104031Supply Air Cooler Valve 1 FaultBV104041Supply Air Cooler Valve 2 FaultBV104061Supply Air Reheater 1 Valve FaultBV304011Outdoor Air Preheater 1 Valve FaultBV804011Energy Recovery System 1 Valve FaultBV805011Energy Recovery System 1 Motor FaultBV805012Energy Recovery System 1 Motor Rotation Monitoring FaultBV101011Supply Air Fan 1 FaultBV101021Supply Air Fan 2 FaultBV101031Supply Air Fan 3 FaultBV101041Supply Air Fan 4 FaultBV101051Supply Air Fan 5 FaultBV101061Supply Air Fan 6 FaultBV101071Supply Air Fan 7 FaultBV101081Supply Air Fan 8 FaultBV201011Extract Air Fan 1 FaultBV201021Extract Air Fan 2 FaultBV201031Extract Air Fan 3 FaultBV201041Extract Air Fan 4 FaultBV201051Extract Air Fan 5 FaultBV201061Extract Air Fan 6 FaultBV201071Extract Air Fan 7 FaultBV201081Extract Air Fan 8 FaultBV102011Supply Air Damper 1 FaultBV202011Extract Air Damper 1 FaultBV302011Outdoor Air Damper 1 FaultBV302021Outdoor Air Bypass Damper FaultBV402011Exhaust Air Damper 1 FaultBV402021Exhaust Air Bypass Damper FaultBV602011Recirculation Air Damper 1 FaultBV4102011Smoke Bypass Damper FaultBV4101011Smoke Extraction Fan 1 FaultBV4101021Smoke Extraction Fan 2 FaultBV4101031Smoke Extraction Fan 3 FaultMV3030011Temperature Control TypeMV3030012Temperature Control ModeMV3131011Humidity Control TypeMV3131012Humidity Control ModeMV3232011Air Quality Control TypeMV3232012Air Quality Control ModeMV3939011Unit Operation ModeMV3939091Unit Operation Mode ActualSCH3903011Pump Kick SOSCH3904011Valve Lime Kick SOSCH3939011Unit Operation Mode SOSCH3939181Change Over SOSCH4139011Smoke Bypass Damper Exercise SO
Integration notes
- The 210 Trend Log objects in the guide's TRENDLOG table are not listed as points.
- Instance numbers repeat across object types (e.g. AI 106011 sensor, AV 106011 control value, BV 106011 sensor fault); always use type plus instance.
- The AI table includes R/W external setpoint objects (e.g. AI 3030042) as printed.
- Objects can be added or removed as the software evolves; the exact list for a unit is in BMS_List.xlsm and the EDE file in the servdoc folder on the controller SD card.
- Descriptions give the printed value range; units as printed (ΔK = temperature difference).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ISYteq controller for eCO Top / eCO Side compact AHUs and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs
How many BACnet points does the FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs have?
This list has 495 BACnet objects: 84 analog inputs, 49 analog outputs, 120 analog values, 24 binary inputs, 77 binary outputs, 128 binary values, 5 schedules, 8 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs BACnet points are writable?
50 of the 495 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs BACnet documentation?
The source is BACnet ISYteq for eCO Top and eCO Side - datasheet (BACnet register, ISYteq) (DC_10484GB 20200812_R0), revision 2020-08-12, published free by FläktGroup at https://www.flaktgroup.com/api/v1/Documents/1076733/Download.
What are the minimum BACnet points to integrate the FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs?
Start with MV 3939011 Unit Operation Mode (Unit mode command: 1 Automatic, 3 Low, 4 High speed); AV 3030071 Temperature Control Setpoint (Temperature setpoint, 5-45 °C); AI 3030042 Temperature Control External Setpoint (External temperature setpoint from the BMS, °C); MV 3939091 Unit Operation Mode Actual (Actual unit operation mode); AI 106011 Supply Air Temperature Sensor (Supply air temperature, °C); AI 206011 Extract Air Temperature Sensor (Extract air temperature, °C); AI 306011 Outdoor Air Temperature Sensor (Outdoor air temperature, °C); AO 101011 Supply Air Fan 1 Output (Supply fan output, %); BO 3939031 Alarm Collective A (Collective A alarm); BO 3939041 Alarm Collective B (Collective B alarm).
How do I enable BMS control of the FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs?
MV 3939011 Unit Operation Mode (R/W) selects Automatic, Room Frost Protection, Low/High Speed, Free Profile 1/2 or Night Purge. BV 3030081 / 3131081 / 3232081 let temperature, humidity or air quality control enable the unit.
Can the BMS supply sensor values to the FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs?
The AI external setpoint objects (temperature 3030042, relative 3030043, humidity 3131042, air quality 3232042, fan flow/pressure/manual 133022-24 and 233022-24, outdoor air amount 2929011) are R/W inputs the BMS can write.
How do I check these points on the real ISYteq controller for eCO Top / eCO Side compact AHUs?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More FläktGroup BACnet points lists
- Air handling unit controller (Climatix)
FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V2.xx
FläktGroup eQ air handling units with Siemens Climatix POL6xx controls running the eQ Fläkt AHU application V2.xx.
Also known as: eQ, eQ Flakt V2, eQ Fläkt AHU V2.xx, Climatix eQ, DC_10159GB, POL908, POL904 - Air handling unit controller (Climatix)
FläktGroup eQ AHU controls (Climatix), application eQ Fläkt AHU V3.xx
FläktGroup eQ air handling units with Siemens Climatix POL6xx controls running the eQ Fläkt AHU application V3.xx.
Also known as: eQ, eQ Flakt V3, eQ Fläkt AHU V3.xx, Climatix eQ, DC_10159GB, POL908, POL904 - Air handling unit controller
FläktGroup ISYteq 4.0 AHU controls (SW 1.3.0.2)
FläktGroup air handling units controlled by ISYteq 4.0, software version 1.3.0.2.
Also known as: ISYteq 4.0, ISYteq 4, Flakt ISYteq BMS list, DC_10838, BMS Communication list 1.3.0.2 - Fire / smoke damper controller with airflow measurement
FläktGroup OPTIVENT UltraSafe USFA control unit
FläktGroup OPTIVENT UltraSafe USFA control units for fire and smoke dampers with ultrasonic airflow measurement.
Also known as: UltraSafe USFA, USFA, OPTIVENT UltraSafe, Ultrasafe, DC_10786GB, Flakt UltraSafe BACnet - Air handling unit controller (Carel uPC3)
FläktGroup vQ Stream unit with Carel uPC3 controller
FläktGroup vQ Stream ventilation units controlled by a Carel uPC3 controller.
Also known as: vQ Stream, vQ Stream uPC3, Flakt vQ Stream BMS list, Carel uPC3 vQ Stream
Source: BACnet ISYteq for eCO Top and eCO Side - datasheet (BACnet register, ISYteq) · DC_10484GB 20200812_R0 · rev. 2020-08-12. Object names, instances and units are reproduced as published; descriptions are our own.