Short answer

The ISYteq controller in eCO Top / eCO Side units has BACnet built in, on RS-485 (MS/TP) or Ethernet (BACnet IP). The object list covers external setpoints from the BMS, temperature, humidity, air quality, pressure and flow sensors, coil, fan and damper outputs, setpoints and offsets, sensor and equipment fault flags, collective alarms, unit and control mode multistates and schedules. Most points are read-only; setpoints, enables and mode selections are R/W.

This page lists 495 BACnet objects for the FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs — 50 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from FläktGroup’s own free documentation, linked below.

Manufacturer
FläktGroup
Model
ISYteq controller for eCO Top / eCO Side compact AHUs
Equipment
Air handling unit controller (compact AHU)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
495 (50 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
ISYteq, eCO Top, eCO Side, eCO SEC, ISYteq eCO, DC_10484GB, Flakt eCO BACnet
Source document
BACnet ISYteq for eCO Top and eCO Side - datasheet (BACnet register, ISYteq) · DC_10484GB 20200812_R0 · rev. 2020-08-12
Download CSV 495 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against FläktGroup’s current documentation and the live device before use. Not official FläktGroup information. Terms of use.

BMS integration notes: FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs

Integration in brief

Set Protocol to MS/TP on the RS-485 channel (or use Ethernet port 1 for BACnet IP), set name and device instance in the HMI, then command the unit with MV 3939011 Unit Operation Mode and the temperature setpoint, and read temperatures, fan outputs and the collective alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 3939011Unit Operation ModeUnit mode command: 1 Automatic, 3 Low, 4 High speed...Write
AV 3030071Temperature Control SetpointTemperature setpoint, 5-45 °CWrite
AI 3030042Temperature Control External SetpointExternal temperature setpoint from the BMS, °CWrite
MV 3939091Unit Operation Mode ActualActual unit operation modeWrite
AI 106011Supply Air Temperature SensorSupply air temperature, °CRead
AI 206011Extract Air Temperature SensorExtract air temperature, °CRead
AI 306011Outdoor Air Temperature SensorOutdoor air temperature, °CRead
AO 101011Supply Air Fan 1 OutputSupply fan output, %Read
BO 3939031Alarm Collective ACollective A alarmRead
BO 3939041Alarm Collective BCollective B alarmRead

Enable & remote start

MV 3939011 Unit Operation Mode (R/W) selects Automatic, Room Frost Protection, Low/High Speed, Free Profile 1/2 or Night Purge. BV 3030081 / 3131081 / 3232081 let temperature, humidity or air quality control enable the unit.

Sensors & values from the BMS

The AI external setpoint objects (temperature 3030042, relative 3030043, humidity 3131042, air quality 3232042, fan flow/pressure/manual 133022-24 and 233022-24, outdoor air amount 2929011) are R/W inputs the BMS can write.

Network setup

Watch out for

FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

495 of 495 shown
Type
Multi-stateOther
Access
Show
FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs BACnet Points List
DescriptionStates
AImin3030042Temperature Control External SetpointRange 5.0-45.0°CWrite
AI3030043Temperature Control External Relative SetpointRange -10.0-10.0ΔKWrite
AI3131042Humidity Control External SetpointRange 0.0-100.0%Write
AI3232042Air Quality Control External SetpointRange 0.0-3000.0ppmWrite
AI133022Supply Air Fan Control Volume Flow External SetpointRange 0-100000m³/hWrite
AI133023Supply Air Fan Control Pressure External SetpointRange 0-500PaWrite
AI133024Supply Air Fan Control Manual External SetpointRange 0.0-100.0%Write
AI233022Extract Air Fan Control Volume Flow External SetpointRange 0-100000m³/hWrite
AI233023Extract Air Fan Control Pressure External SetpointRange 0-500PaWrite
AI233024Extract Air Fan Control Manual External SetpointRange 0.0-100.0%Write
AI2929011Damper Control Outdoor Air Amount External SetpointRange 0.0-100.0%Write
AImin106011Supply Air Temperature SensorRange -50.0-200.0°CRead
AI106031Supply Air Fan Nozzle Temperature SensorRange -50.0-200.0°CRead
AI106041Supply Air Heater 1 Inlet Temperature SensorRange -50.0-200.0°CRead
AI106051Supply Air Heater 1 Outlet Temperature SensorRange 5.0-200.0°CRead
AI106061Supply Air Heater 2 Inlet Temperature SensorRange -50.0-200.0°CRead
AI106071Supply Air Heater 2 Outlet Temperature SensorRange 5.0-200.0°CRead
AI106081Supply Air Cooler 1 Inlet Temperature SensorRange -50.0-200.0°CRead
AI106091Supply Air Cooler 1 Outlet Temperature SensorRange -50.0-200.0°CRead
AI106101Supply Air Cooler 2 Inlet Temperature SensorRange -50.0-200.0°CRead
AI106111Supply Air Cooler 2 Outlet Temperature SensorRange -50.0-200.0°CRead
AI106141Supply Air Reheater 1 Inlet Temperature SensorRange -50.0-200.0°CRead
AI106151Supply Air Reheater 1 Outlet Temperature SensorRange 5.0-200.0°CRead
AImin206011Extract Air Temperature SensorRange -50.0-200.0°CRead
AI206071Extract Air Fan Nozzle Temperature SensorRange -50.0-200.0°CRead
AImin306011Outdoor Air Temperature SensorRange -50.0-200.0°CRead
AI306021Outdoor Air Filter Temperature SensorRange -50.0-200.0°CRead
AI306031Outdoor Air Preheater 1 Inlet Temperature SensorRange -50.0-200.0°CRead
AI306041Outdoor Air Preheater 1 Outlet Temperature SensorRange 5.0-200.0°CRead
AI406011Exhaust Air Temperature SensorRange -50.0-200.0°CRead
AI706011Room Air Temperature Sensor 1Range -50.0-200.0°CRead
AI706021Room Air Temperature Sensor 2Range -50.0-200.0°CRead
AI706031Room Air Temperature Sensor 3Range -50.0-200.0°CRead
AI706041Room Air Temperature Sensor 4Range -50.0-200.0°CRead
AI806011Energy Recovery System 1 Inlet Temperature SensorRange -50.0-200.0°CRead
AI806021Energy Recovery System 1 Outlet Temperature SensorRange -50.0-200.0°CRead
AI806031Supply Air Temperature Sensor Behind Energy Recovery SystemRange -50.0-200.0°CRead
AI806041Exhaust Air Temperature Sensor Behind Energy Recovery SystemRange -50.0-200.0°CRead
AI806051Energy Recovery System Icing Temperature SensorRange -50.0-200.0°CRead
AI2006011Outdoor Air External Temperature SensorRange -50.0-200.0°CRead
AI2106011Evaporator 1 Temperature SensorRange -50.0-200.0°CRead
AI107011Supply Humidity SensorRange 0.0-100.0%Read
AI207011Extract Air Humidity SensorRange 0.0-100.0%Read
AI307011Outdoor Air Humidity SensorRange 0.0-100.0%Read
AI407011Exhaust Air Humidity SensorRange 0.0-100.0%Read
AI707011Room Air Humidity Sensor 1Range 0.0-100.0%Read
AI707021Room Air Humidity Sensor 2Range 0.0-100.0%Read
AI707031Room Air Humidity Sensor 3Range 0.0-100.0%Read
AI707041Room Air Humidity Sensor 4Range 0.0-100.0%Read
AI2007011Outdoor Air External Humidity SensorRange 0.0-100.0%Read
AI208011Extract Air Quality SensorRange 0.0-3276.7ppmRead
AI308011Outdoor Air Quality SensorRange 0.0-3276.7ppmRead
AI708011Room Air Quality Sensor 1Range 0.0-3276.7ppmRead
AI708021Room Air Quality Sensor 2Range 0.0-3276.7ppmRead
AI708031Room Air Quality Sensor 3Range 0.0-3276.7ppmRead
AI708041Room Air Quality Sensor 4Range 0.0-3276.7ppmRead
AI109011Supply Air Filter Pressure Sensor 1Range -10-250PaRead
AI109021Supply Air Filter Pressure Sensor 2Range -10-250PaRead
AI109031Supply Air Nozzle Pressure SensorRange -10-5000PaRead
AI109041Supply Air Duct Pressure SensorRange -10-500PaRead
AI209011Extract Air Filter Pressure 1 SensorRange -10-250PaRead
AI209021Extract Air Filter Pressure 2 SensorRange -10-250PaRead
AI209031Extract Air Duct Pressure SensorRange -10-500PaRead
AI209041Extract Air Nozzle Pressure SensorRange -10-5000PaRead
AI309011Outdoor Air Filter Pressure 1 SensorRange -10-250PaRead
AI309021Outdoor Air Filter Pressure Sensor 2Range -10-250PaRead
AI309031Outdoor Air Bypass Pressure SensorRange -10-500PaRead
AI409011Exhaust Air Bypass Pressure SensorRange -10-500PaRead
AI809011Energy Recovery System Pressure SensorRange -10-500PaRead
AI104011Supply Air Heater 1 Valve FeedbackRange -5-5%Read
AI104021Supply Air Heater 2 Valve FeedbackRange -5-5%Read
AI104031Supply Air Cooler Valve 1 FeedbackRange -5-5%Read
AI104041Supply Air Cooler Valve 2 FeedbackRange -5-5%Read
AI104061Supply Air Reheater 1 Valve FeedbackRange -5-5%Read
AI304011Outdoor Air Preheater 1 Valve FeedbackRange -5-5%Read
AI804011Energy Recovery System Valve 1 FeedbackRange -5-5%Read
AI102011Supply Air Damper 1 FeedbackRange -5-5%Read
AI202011Extract Air Damper 1 FeedbackRange -5-5%Read
AI302011Outdoor Air Damper 1 FeedbackRange -5-5%Read
AI302021Outdoor Air Bypass Damper FeedbackRange -5-5%Read
AI402011Exhaust Air Damper 1 FeedbackRange -5-5%Read
AI402021Exhaust Air Bypass Damper FeedbackRange -5-5%Read
AI602011Recirculation Air Damper 1 FeedbackRange -5-5%Read
AI4102011Smoke Bypass Damper FeedbackRange -5-5%Read
AO112031Supply Air Electric Heater 1 OutputRange 0-100%Read
AO112021Supply Air Electric Reheater 1 OutputRange 0-100%Read
AO312011Outdoor Air Electric Preheater 1 OutputRange 0-100%Read
AO2128041DX Mitsubishi Inverter Stage 1 OutputRange 0-100%Read
AO2128051DX Mitsubishi Inverter Stage 2 OutputRange 0-100%Read
AO2128061DX Daikin Inverter Stage 1 OutputRange 0-100%Read
AO2128071DX Daikin Inverter Stage 2 OutputRange 0-100%Read
AO103011Supply Air Heater 1 Pump OutputRange 0-100%Read
AO103021Supply Air Heater 2 Pump OutputRange 0-100%Read
AO103031Supply Air Cooler Pump 1 OutputRange 0-100%Read
AO103041Supply Air Cooler Pump 2 OutputRange 0-100%Read
AO103061Supply Air Reheater 1 Pump OutputRange 0-100%Read
AO303011Outdoor Air Preheater 1 Pump OutputRange 0-100%Read
AO803011Energy Recovery System 1 Pump OutputRange 0-100%Read
AO104011Supply Air Heater 1 Valve OutputRange 0-100%Read
AO104021Supply Air Heater 2 Valve OutputRange 0-100%Read
AO104031Supply Air Cooler Valve 1 OutputRange 0-100%Read
AO104041Supply Air Cooler Valve 2 OutputRange 0-100%Read
AO104061Supply Air Reheater 1 Valve OutputRange 0-100%Read
AO304011Outdoor Air Preheater 1 Valve OutputRange 0-100%Read
AO804011Energy Recovery System Valve 1 OutputRange 0-100%Read
AO805011Energy Recovery System 1 Motor OutputRange 0.0-100.0%Read
AOmin101011Supply Air Fan 1 OutputRange 0.0-100.0%Read
AO101021Supply Air Fan 2 OutputRange 0.0-100.0%Read
AO101031Supply Air Fan 3 OutputRange 0.0-100.0%Read
AO101041Supply Air Fan 4 OutputRange 0.0-100.0%Read
AO101051Supply Air Fan 5 OutputRange 0.0-100.0%Read
AO101061Supply Air Fan 6 OutputRange 0.0-100.0%Read
AO101071Supply Air Fan 7 OutputRange 0.0-100.0%Read
AO101081Supply Air Fan 8 OutputRange 0.0-100.0%Read
AO201011Extract Air Fan 1 OutputRange 0.0-100.0%Read
AO201021Extract Air Fan 2 OutputRange 0.0-100.0%Read
AO201031Extract Air Fan 3 OutputRange 0.0-100.0%Read
AO201041Extract Air Fan 4 OutputRange 0.0-100.0%Read
AO201051Extract Air Fan 5 OutputRange 0.0-100.0%Read
AO201061Extract Air Fan 6 OutputRange 0.0-100.0%Read
AO201071Extract Air Fan 7 OutputRange 0.0-100.0%Read
AO201081Extract Air Fan 8 OutputRange 0.0-100.0%Read
AO102011Supply Air Damper 1 OutputRange 0-100%Read
AO202011Extract Air Damper 1 OutputRange 0-100%Read
AO302011Outdoor Air Damper 1 OutputRange 0-100%Read
AO302021Outdoor Air Bypass Damper OutputRange 0-100%Read
AO402011Exhaust Air Damper 1 OutputRange 0-100%Read
AO402021Exhaust Air Bypass Damper OutputRange 0-100%Read
AO602011Recirculation Air Damper 1 OutputRange 0-100%Read
AO4102011Smoke Bypass Damper OutputRange 0-100%Read
AO4101011Smoke Extraction Fan 1 OutputRange 0.0-100.0%Read
AO4101021Smoke Extraction Fan 2 OutputRange 0.0-100.0%Read
AO4101031Smoke Extraction Fan 3 OutputRange 0.0-100.0%Read
AV3030031Temperature Control Heating SetpointRange 5.0-45.0°CWrite
AV3030041Temperature Control Cooling SetpointRange 5.0-45.0°CWrite
AV3030051Temperature Control Heating Offset SetpointRange -10.0-0.0ΔKWrite
AV3030061Temperature Control Cooling Offset SetpointRange 0.0-10.0ΔKWrite
AVmin3030071Temperature Control SetpointRange 5.0-45.0°CWrite
AV3030081Temperature Control Relative SetpointRange -5.0-5.0ΔKWrite
AV3131031Humidity Control Humidification SetpointRange 0.0-100.0%Write
AV3131041Humidity Control Dehumidification SetpointRange 0.0-100.0%Write
AV3131051Humidity Control Humidification Offset SetpointRange 0.0-10.0%Write
AV3131061Humidity Control Dehumidification Offset SetpointRange 0.0-10.0%Write
AV3131071Humidity SetpointRange 0.0-100.0%Write
AV3232071Air Quality SetpointRange 0-3000ppmWrite
AV133012Supply Air Fan Volume Flow SetpointRange 0-100000m³/hWrite
AV133013Supply Air Fan Pressure SetpointRange 0-1000PaWrite
AV133014Supply Air Fan Manual SetpointRange 0.0-100.0%Write
AV133024Supply Air Fan Control Offset SetpointRange -100.0-100.0%Write
AV133025Supply Air Fan Control Factor SetpointRange 0-5Write
AV133034Supply Air Fan Control Offset Absolut SetpointRange 0.00-655.35m³/hWrite
AV233012Extract Air Fan Volume Flow SetpointRange 0-100000m³/hWrite
AV233013Extract Air Fan Pressure SetpointRange 0-1000PaWrite
AV233014Extract Air Fan SetpointRange 0.0-100.0%Write
AV233024Extract Air Fan Control Offset SetpointRange -100.0-100.0%Write
AV233025Extract Air Fan Control Factor SetpointRange 0-5Write
AV233034Extract Air Fan Control Offset Absolut SetpointRange 0.00-655.35m³/hWrite
AV2929011Damper Control Outdoor Air Amount SetpointRange 0-100%Write
AV106011Supply Air Temperature Control ValueRange -50.0-200.0°CRead
AV206011Extract Air Temperature Control ValueRange -50.0-200.0°CRead
AV306011Outdoor Air Temperature Control ValueRange -50.0-200.0°CRead
AV706011Room Air Temperature Control ValueRange -50.0-200.0°CRead
AV2006011Outdoor Air external Temperature Control ValueRange -50.0-200.0°CRead
AV3030231Temperature Control ValueRange n/a°CRead
AV3030011Temperature Control Heating Setpoint Control ValueRange 5.0-45.0°CRead
AV3030012Temperature Control Heating Active Setpoint Control ValueRange 5.0-45.0°CRead
AV3030021Temperature Control Cooling Setpoint Control ValueRange 5.0-45.0°CRead
AV3030022Temperature Control Cooling Active Setpoint Control ValueRange 5.0-45.0°CRead
AV3030072Temperature Control Cascade Heating SetpointRange 10.0 to 45.0°CRead
AV3030232Temperature Control Cascade Control ValueRange n/a°CRead
AV3030073Temperature Control Base SetpointRange 5.0-45.0°CRead
AV3030171Temperature Control Supply Air Minimum Relative SetpointRange -10.0-0.0ΔKRead
AV3030181Temperature Control Supply Air Maximum Relative SetpointRange 0.0-10.0ΔKRead
AV3030191Temperature Control Supply Air Minimum Absolute SetpointRange 10.0 to 45.0°CRead
AV3030201Temperature Control Supply Air Maximum Absolute SetpointRange 10.0 to 45.0°CRead
AV107022Supply Air Humidity Absolute Control ValueRange 0.0-20.0g/kgRead
AV207022Extract Air Humidity Absolute Control ValueRange 0.0-20.0g/kgRead
AV307022Outdoor Air Humidity Absolute Control ValueRange 0.0-20.0g/kgRead
AV707021Room Air Humidity 1 Absolute ValueRange 0.0-20.0g/kgRead
AV707022Room Air Humidity 2 Absolute ValueRange 0.0-20.0g/kgRead
AV707023Room Air Humidity 3 Absolute ValueRange 0.0-20.0g/kgRead
AV707024Room Air Humidity 4 Absolute ValueRange 0.0-20.0g/kgRead
AV707025Room Air Humidity Absolute Control ValueRange 0.0-20.0g/kgRead
AV2007022Outdoor Air External Humidity Absolute Control ValueRange 0.0-20.0g/kgRead
AV107011Supply Air Humidity Relative Control ValueRange -50.0-200.0%Read
AV207011Extract Air Humidity Relative Control ValueRange -50.0-200.0%Read
AV307011Outdoor Air Humidity Relative Control ValueRange -50.0-200.0%Read
AV707011Room Air Humidity Relative Control ValueRange -50.0-200.0%Read
AV2007011Outdoor Air External Humidity Relative Control ValueRange -50.0-200.0%Read
AV3131011Humidity Control Humidification Setpoint Control ValueRange 0.0-100.0%Read
AV3131021Humidity Control Dehumidification Setpoint Control ValueRange 0.0-100.0%Read
AV3131231Humidity Control ValueRange n/a%Read
AV3131072Humidity Control Cascade Humidification SetpointRange 0.0-100.0%Read
AV3131232Humidity Control Cascade Control ValueRange n/a%Read
AV3131171Humidity Control Supply Air Minimum Relative SetpointRange 0.0-100.0%Read
AV3131181Humidity Control Supply Air Maximum Relative SetpointRange 0.0-100.0%Read
AV3131191Humidity Control Supply Air Minimum Absolute SetpointRange 0-20g/kgRead
AV3131201Humidity Control Supply Air Maximum Absolute SetpointRange 0-20g/kgRead
AV208011Extract Air Quality Control ValueRange 0.0-3000.0PpmRead
AV708011Room Air Quality Control ValueRange 0.0-3000.0ppmRead
AV3232011Air Quality Control Setpoint Control ValueRange 0-2500ppmRead
AV3232231Air Quality Control ValueRange 0-5000PpmRead
AV3939021Unit On Operating HoursRange 0-65535hRead
AV3939081Order NumberRange 0-65535Read
AV3939151Temperature Control Room frost protection Hysterisis SetpointRange 0.0-20.0ΔKRead
AV4010011Specific Fan PowerRange 0-65535Wh/m³Read
AV133015Supply Air Fan Control Volume Flow Setpoint Control ValueRange 0-100000m³/hRead
AV133016Supply Air Fan Control Pressure Setpoint Control ValueRange 0-1000PaRead
AV133017Supply Air Fan Control Manual Setpoint Control ValueRange 0.0-100.0%Read
AV133031Supply Air Fan Calculated Volume FlowRange -327680-327670m³/hRead
AV233015Extract Air Fan Control Volume Flow Setpoint Control ValueRange 0-100000m³/hRead
AV233016Extract Air Fan Control Pressure Setpoint Control ValueRange 0-5000PaRead
AV233017Extract Air Fan Control Manual Setpoint Control ValueRange 0.0-100.0%Read
AV233031Extract Air Fan Calculated Volume FlowRange -327680-327670m³/hRead
AV112031Supply Air Electric Heater 1 Operating HoursRange 0-2147483647hRead
AV112021Supply Air Electric Reheater 1 Operating HoursRange 0-2147483647hRead
AV312011Outdoor Air Electric Preheater 1 Operating HoursRange 0-2147483647hRead
AV2128021DX Condensing Unit Stage 1 Operating HoursRange 0-2147483647hRead
AV2128031DX Condensing Unit Stage 2 Operating HoursRange 0-2147483647hRead
AV2128041DX Mitsubishi Inverter Stage 1 Operating HoursRange 0-2147483647hRead
AV2128051DX Mitsubishi Inverter Stage 2 Operating HoursRange 0-2147483647hRead
AV2128061DX Daikin Inverter Stage 1 Operating HoursRange 0-2147483647hRead
AV2128071DX Daikin Inverter Stage 2 Operating HoursRange 0-2147483647hRead
AV103013Supply Air Heater 1 Pump Operating HoursRange 0-2147483647hRead
AV103023Supply Air Heater 2 Pump Operating HoursRange 0-2147483647hRead
AV103033Supply Air Cooler Pump 1 Operating HoursRange 0-2147483647hRead
AV103043Supply Air Cooler Pump 2 Operating HoursRange 0-2147483647hRead
AV103063Supply Air Reheater 1 Pump Operating HoursRange 0-2147483647hRead
AV303013Outdoor Air Preheater 1 Pump Operating HoursRange 0-2147483647hRead
AV803013Energy Recovery System Pump 1 Operating HoursRange 0-2147483647hRead
AV805013Energy Recovery System 1 Motor Operating HoursRange 0-2147483647hRead
AV101011Supply Air Fan 1 Operating HoursRange 0-2147483647hRead
AV101021Supply Air Fan 2 Operating HoursRange 0-2147483647hRead
AV101031Supply Air Fan 3 Operating HoursRange 0-2147483647hRead
AV101041Supply Air Fan 4 Operating HoursRange 0-2147483647hRead
AV101051Supply Air Fan 5 Operating HoursRange 0-2147483647hRead
AV101061Supply Air Fan 6 Operating HoursRange 0-2147483647hRead
AV101071Supply Air Fan 7 Operating HoursRange 0-2147483647hRead
AV101081Supply Air Fan 8 Operating HoursRange 0-2147483647hRead
AV201011Extract Air Fan 1 Operating HoursRange 0-2147483647hRead
AV201021Extract Air Fan 2 Operating HoursRange 0-2147483647hRead
AV201031Extract Air Fan 3 Operating HoursRange 0-2147483647hRead
AV201041Extract Air Fan 4 Operating HoursRange 0-2147483647hRead
AV201051Extract Air Fan 5 Operating HoursRange 0-2147483647hRead
AV201061Extract Air Fan 6 Operating HoursRange 0-2147483647hRead
AV201071Extract Air Fan 7 Operating HoursRange 0-2147483647hRead
AV201081Extract Air Fan 8 Operating HoursRange 0-2147483647hRead
AV4101011Smoke Extraction Fan 1 Operating HoursRange 0-2147483647hRead
AV4101021Smoke Extraction Fan 2 Operating HoursRange 0-2147483647hRead
AV4101031Smoke Extraction Fan 3 Operating HoursRange 0-2147483647hRead
AV4101012Smoke Extraction Fan 1 Standstill DaysRange 0-100dRead
AV4101022Smoke Extraction Fan 2 Standstill DaysRange 0-100dRead
AV4101032Smoke Extraction Fan 3 Standstill DaysRange 0-100dRead
BI112021Supply Air Electric Reheater 1 FaultReadInactive=Fault; Active=Ok
BI112031Supply Air Electric Heater 1 FaultReadInactive=Fault; Active=Ok
BI312011Outdoor Air Electric Preheater 1 FaultReadInactive=Fault; Active=Ok
BI2128021DX Condensing Unit Stage 1 FaultReadInactive=Fault; Active=Ok
BI2128031DX Condensing Unit Stage 2 FaultReadInactive=Fault; Active=Ok
BI2128041DX Mitsubishi Inverter Stage 1 FaultReadInactive=Fault; Active=Ok
BI2128043DX Mitsubishi Inverter Stage 1 Pre defrost InputReadInactive=Off; Active=On
BI2128042DX Mitsubishi Inverter Stage 1 Defrost InputReadInactive=Off; Active=On
BI2128051DX Mitsubishi Inverter Stage 2 FaultReadInactive=Fault; Active=Ok
BI2128053DX Mitsubishi Inverter Stage 2 Pre defrost InputReadInactive=Off; Active=On
BI2128052DX Mitsubishi Inverter Stage 2 Defrost InputReadInactive=Off; Active=On
BI2128061DX Daikin Inverter Stage 1 FaultReadInactive=Fault; Active=Ok
BI2128062DX Daikin Inverter Stage 1 Defrost InputReadInactive=Off; Active=On
BI2128071DX Daikin Inverter Stage 2 FaultReadInactive=Off; Active=On
BI2128072DX Daikin Inverter Stage 2 Defrost InputReadInactive=Off; Active=On
BI103011Supply Air Heater 1 Pump Motor protectionReadInactive=Fault; Active=Ok
BI103021Supply Air Heater 2 Pump Motor protectionReadInactive=Fault; Active=Ok
BI103031Supply Air Cooler Pump 1 Motor protectionReadInactive=Fault; Active=Ok
BI103041Supply Air Cooler Pump 2 Motor protectionReadInactive=Fault; Active=Ok
BI103061Supply Air Reheater 1 Pump Motor protectionReadInactive=Fault; Active=Ok
BI303011Outdoor Air Preheater 1 Pump MotorprotectionReadInactive=Fault; Active=Ok
BI803011Energy Recovery System 1 Pump Motor protectionReadInactive=Fault; Active=Ok
BI805012Energy Recovery System 1 Motor Rotation Guard InputReadInactive=Off; Active=On
BI805011Energy Recovery System 1 Motor Motor protectionReadInactive=Fault; Active=Ok
BOmin3939031Alarm Collective AReadInactive=Off; Active=On
BOmin3939041Alarm Collective BReadInactive=Off; Active=On
BO3939011Alarm New AReadInactive=Off; Active=On
BO3939021Alarm New BReadInactive=Off; Active=On
BO3939161Heating RequestReadInactive=Off; Active=On
BO3939171Cooling RequestReadInactive=Off; Active=On
BO4141011Fire Alarm IndicationReadInactive=Ok; Active=Fault
BO112021Supply Air Electric Reheater 1 OnReadInactive=Off; Active=On
BO112031Supply Air Electric Heater 1 OnReadInactive=Off; Active=On
BO312011Outdoor Air Electric Preheater 1 OnReadInactive=Off; Active=On
BO2128021DX Condensing Unit Stage 1 OnReadInactive=Off; Active=On
BO2128031DX Condensing Unit Stage 2 OnReadInactive=Off; Active=On
BO2128041DX Mitsubishi Inverter Stage 1 OnReadInactive=Off; Active=On
BO2128042DX Mitsubishi Inverter Stage 1 Heating OutputReadInactive=Off; Active=On
BO2128051DX Mitsubishi Inverter Stage 2 OnReadInactive=Off; Active=On
BO2128052DX Mitsubishi Inverter Stage 2 Heating OutputReadInactive=Off; Active=On
BO2128061DX Daikin Inverter Stage 1 OnReadInactive=Off; Active=On
BO2128062DX Daikin Inverter Stage 1 Heating OutputReadInactive=Off; Active=On
BO2128071DX Daikin Inverter Stage 2 OnReadInactive=Off; Active=On
BO2128072DX Daikin Inverter Stage 2 Heating OutputReadInactive=Off; Active=On
BO103011Supply Air Heater 1 Pump OnReadInactive=Off; Active=On
BO103021Supply Air Heater 2 Pump OnReadInactive=Off; Active=On
BO103031Supply Air Cooler 1 Pump OnReadInactive=Off; Active=On
BO103041Supply Air Cooler 2 Pump OnReadInactive=Off; Active=On
BO103061Supply Air Reheater 1 Pump OnReadInactive=Off; Active=On
BO303011Outdoor Air Preheater 1 Pump OnReadInactive=Off; Active=On
BO803011Energy Recovery System 1 Pump OnReadInactive=Off; Active=On
BO104011Supply Air Heater 1 Valve OpenReadInactive=Off; Active=On
BO104012Supply Air Heater 1 Valve CloseReadInactive=Off; Active=On
BO104021Supply Air Heater 2 Valve OpenReadInactive=Off; Active=On
BO104022Supply Air Heater 2 Valve CloseReadInactive=Off; Active=On
BO104031Supply Air Cooler Valve 1 OpenReadInactive=Off; Active=On
BO104032Supply Air Cooler Valve 1 CloseReadInactive=Off; Active=On
BO104041Supply Air Cooler Valve 2 OpenReadInactive=Off; Active=On
BO104042Supply Air Cooler Valve 2 CloseReadInactive=Off; Active=On
BO104061Supply Air Reheater 1 Valve OpenReadInactive=Off; Active=On
BO104062Supply Air Reheater 1 Valve CloseReadInactive=Off; Active=On
BO304011Outdoor Air Preheater 1 Valve OpenReadInactive=Off; Active=On
BO304012Outdoor Air Preheater 1 Valve CloseReadInactive=Off; Active=On
BO804011Energy Recovery System 1 Valve OpenReadInactive=Off; Active=On
BO804012Energy Recovery System 1 Valve CloseReadInactive=Off; Active=On
BO805011Energy Recovery System 1 Motor OnReadInactive=Off; Active=On
BO101011Supply Air Fan 1 OnReadInactive=Off; Active=On
BO101021Supply Air Fan 2 OnReadInactive=Off; Active=On
BO101031Supply Air Fan 3 OnReadInactive=Off; Active=On
BO101041Supply Air Fan 4 OnReadInactive=Off; Active=On
BO101051Supply Air Fan 5 OnReadInactive=Off; Active=On
BO101061Supply Air Fan 6 OnReadInactive=Off; Active=On
BO101071Supply Air Fan 7 OnReadInactive=Off; Active=On
BO101081Supply Air Fan 8 OnReadInactive=Off; Active=On
BO201011Extract Air Fan 1 OnReadInactive=Off; Active=On
BO201021Extract Air Fan 2 OnReadInactive=Off; Active=On
BO201031Extract Air Fan 3 OnReadInactive=Off; Active=On
BO201041Extract Air Fan 4 OnReadInactive=Off; Active=On
BO201051Extract Air Fan 5 OnReadInactive=Off; Active=On
BO201061Extract Air Fan 6 OnReadInactive=Off; Active=On
BO201071Extract Air Fan 7 On Digital OutputReadInactive=Off; Active=On
BO201081Extract Air Fan 8 OnReadInactive=Off; Active=On
BO102011Supply Air Damper 1 OpenReadInactive=Off; Active=On
BO102012Supply Air Damper 1 CloseReadInactive=Off; Active=On
BO202011Extract Air Damper 1 OpenReadInactive=Off; Active=On
BO202012Extract Air Damper 1 CloseReadInactive=Off; Active=On
BO302011Outdoor Air Damper 1 OpenReadInactive=Off; Active=On
BO302012Outdoor Air Damper 1 CloseReadInactive=Off; Active=On
BO302021Outdoor Air Bypass Damper OpenReadInactive=Off; Active=On
BO302022Outdoor Air Bypass Damper CloseReadInactive=Off; Active=On
BO402011Exhaust Air Damper 1 OpenReadInactive=Off; Active=On
BO402012Exhaust Air Damper 1 CloseReadInactive=Off; Active=On
BO402021Exhaust Air Bypass Damper OpenReadInactive=Off; Active=On
BO402022Exhaust Air Bypass Damper CloseReadInactive=Off; Active=On
BO602011Recirculation Air Damper 1 OpenReadInactive=Off; Active=On
BO602012Recirculation Air Damper 1 CloseReadInactive=Off; Active=On
BO4102011Smoke Bypass Damper OpenReadInactive=Off; Active=On
BO4102012Smoke Bypass Damper CloseReadInactive=Off; Active=On
BO4101011Smoke Extraction Fan 1 OnReadInactive=Off; Active=On
BO4101021Smoke Extraction Fan 2 OnReadInactive=Off; Active=On
BO4101031Smoke Extraction Fan 3 OnReadInactive=Off; Active=On
BV3030081Unit Enable Via Temperature ControlWriteInactive=Off; Active=On
BV3030111Temperature Control Relative SetpointWriteInactive=Off; Active=On
BV3131081Unit Enable Via Humidity ControlWriteInactive=Off; Active=On
BV3131101Humidity Control EnableWriteInactive=Off; Active=On
BV3232081Unit Enable Via Air Quality ControlWriteInactive=Off; Active=On
BV3232101Air Quality Control EnableWriteInactive=Off; Active=On
BV106011Supply Air Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV106031Supply Air Fan Nozzle Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV106041Supply Air Heater 1 Inlet Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV106051Supply Air Heater 1 Outlet Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV106061Supply Air Heater 2 Inlet Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV106071Supply Air Heater 2 Outlet Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV106081Supply Air Cooler 1 Inlet Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV106091Supply Air Cooler 1 Outlet Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV106101Supply Air Cooler 2 Inlet Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV106111Supply Air Cooler 2 Outlet Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV106141Supply Air Reheater 1 Inlet Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV106151Supply Air Reheater 1 Outlet Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV206011Extract Air Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV206071Extract Air Fan Nozzle Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV306011Outdoor Air Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV306021Outdoor Air Filter Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV306031Outdoor Air Preheater 1 Inlet Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV306041Outdoor Air Preheater 1 Outlet Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV406011Exhaust Air Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV706011Room Air Temperature Sensor 1 FaultReadInactive=Ok; Active=Fault
BV706021Room Air Temperature Sensor 2 FaultReadInactive=Ok; Active=Fault
BV706031Room Air Temperature Sensor 3 FaultReadInactive=Ok; Active=Fault
BV706041Room Air Temperature Sensor 4 FaultReadInactive=Ok; Active=Fault
BV806011Energy Recovery System 1 Inlet Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV806021Energy Recovery System 1 Outlet Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV806031Supply Air Temperature Sensor Behind Energy Recovery System FaultReadInactive=Ok; Active=Fault
BV806041Exhaust Air Temperature Sensor Behind Energy Recovery System FaultReadInactive=Ok; Active=Fault
BV806051Energy Recovery System Icing Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV2006011Outdoor Air External Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV2106011Evaporator 1 Temperature Sensor FaultReadInactive=Ok; Active=Fault
BV107011Supply Humidity Sensor FaultReadInactive=Ok; Active=Fault
BV207011Extract Air Humidity Sensor FaultReadInactive=Ok; Active=Fault
BV307011Outdoor Air Humidity Sensor FaultReadInactive=Ok; Active=Fault
BV407011Exhaust Air Humidity Sensor FaultReadInactive=Ok; Active=Fault
BV707011Room Air Humidity Sensor 1 FaultReadInactive=Ok; Active=Fault
BV707021Room Air Humidity Sensor 2 FaultReadInactive=Ok; Active=Fault
BV707031Room Air Humidity Sensor 3 FaultReadInactive=Ok; Active=Fault
BV707041Room Air Humidity Sensor 4 FaultReadInactive=Ok; Active=Fault
BV2007011Outdoor Air External Humidity Sensor FaultReadInactive=Ok; Active=Fault
BV208011Extract Air Quality Sensor FaultReadInactive=Ok; Active=Fault
BV308011Outdoor Air Quality Sensor FaultReadInactive=Ok; Active=Fault
BV708011Room Air Quality Sensor 1 FaultReadInactive=Ok; Active=Fault
BV708021Room Air Quality Sensor 2 FaultReadInactive=Ok; Active=Fault
BV708031Room Air Quality Sensor 3 FaultReadInactive=Ok; Active=Fault
BV708041Room Air Quality Sensor 4 FaultReadInactive=Ok; Active=Fault
BV109011Supply Air Filter Pressure Sensor 1 FaultReadInactive=Ok; Active=Fault
BV109021Supply Air Filter Pressure Sensor 2 FaultReadInactive=Ok; Active=Fault
BV109031Supply Air Nozzle Pressure Sensor FaultReadInactive=Ok; Active=Fault
BV109041Supply Air Duct Pressure Sensor FaultReadInactive=Ok; Active=Fault
BV209011Extract Air Filter Pressure Sensor 1 FaultReadInactive=Ok; Active=Fault
BV209021Extract Air Filter Pressure Sensor 2 FaultReadInactive=Ok; Active=Fault
BV209031Extract Air Duct Pressure Sensor FaultReadInactive=Ok; Active=Fault
BV209041Extract Air Nozzle Pressure Sensor FaultReadInactive=Ok; Active=Fault
BV309011Outdoor Air Filter Pressure Sensor 1 FaultReadInactive=Ok; Active=Fault
BV309021Outdoor Air Filter Pressure Sensor 2 FaultReadInactive=Ok; Active=Fault
BV309031Outdoor Air Bypass Pressure Sensor FaultReadInactive=Ok; Active=Fault
BV409011Exhaust Air Bypass Pressure Sensor FaultReadInactive=Ok; Active=Fault
BV809011Energy Recovery System Pressure Sensor FaultReadInactive=Ok; Active=Fault
BV3939161Unit OnReadInactive=Off; Active=On
BV830031Energy Recovery System Control Anti Icing FaultReadInactive=Ok; Active=Fault
BV3939171Warmup FaultReadInactive=Ok; Active=Fault
BV3030012Value Monitoring FaultReadInactive=Ok; Active=Fault
BV3030013Value Tripping with Acknowledge Monitoring FaultReadInactive=Ok; Active=Fault
BV3030011Value Monitoring Tripping FaultReadInactive=Ok; Active=Fault
BV4141012Fire Alarm FaultReadInactive=Ok; Active=Alarm
BV112021Supply Air Electric Reheater 1 FaultReadInactive=Ok; Active=Fault
BV112031Supply Air Electric Heater 1 FaultReadInactive=Ok; Active=Fault
BV312011Outdoor Air Electric Preheater 1 FaultReadInactive=Ok; Active=Fault
BV2128021DX Condensing Unit Stage 1 FaultReadInactive=Ok; Active=Fault
BV2128031DX Condensing Unit Stage 2 FaultReadInactive=Ok; Active=Fault
BV2128041DX Mitsubishi Inverter Stage 1 FaultReadInactive=Ok; Active=Fault
BV2128051DX Mitsubishi Inverter Stage 2 FaultReadInactive=Ok; Active=Fault
BV2128061DX Daikin Inverter Stage 1 FaultReadInactive=Ok; Active=Fault
BV2128071DX Daikin Inverter Stage 2 FaultReadInactive=Ok; Active=Fault
BV2128011DX Freeze Protection FaultReadInactive=Ok; Active=Fault
BV110012Supply Air Heater 1 Frost Protection Air FaultReadInactive=Ok; Active=Fault
BV110022Supply Air Heater 2 Frost Protection Air FaultReadInactive=Ok; Active=Fault
BV310011Outdoor Air Preheater 1 Frost Protection Air FaultReadInactive=Ok; Active=Fault
BV110031Supply Air Reheater 1 Frost Protection Air FaultReadInactive=Ok; Active=Fault
BV103011Supply Air Heater 1 Pump FaultReadInactive=Ok; Active=Fault
BV103021Supply Air Heater 2 Pump FaultReadInactive=Ok; Active=Fault
BV103031Supply Air Cooler Pump 1 FaultReadInactive=Ok; Active=Fault
BV103041Supply Air Cooler Pump 2 FaultReadInactive=Ok; Active=Fault
BV103061Supply Air Reheater 1 Pump FaultReadInactive=Ok; Active=Fault
BV303011Outdoor Air Preheater 1 Pump FaultReadInactive=Ok; Active=Fault
BV803011Energy Recovery System Pump 1 FaultReadInactive=Ok; Active=Fault
BV104011Supply Air Heater 1 Valve FaultReadInactive=Ok; Active=Fault
BV104021Supply Air Heater 2 Valve FaultReadInactive=Ok; Active=Fault
BV104031Supply Air Cooler Valve 1 FaultReadInactive=Ok; Active=Fault
BV104041Supply Air Cooler Valve 2 FaultReadInactive=Ok; Active=Fault
BV104061Supply Air Reheater 1 Valve FaultReadInactive=Ok; Active=Fault
BV304011Outdoor Air Preheater 1 Valve FaultReadInactive=Ok; Active=Fault
BV804011Energy Recovery System 1 Valve FaultReadInactive=Ok; Active=Fault
BV805011Energy Recovery System 1 Motor FaultReadInactive=Ok; Active=Fault
BV805012Energy Recovery System 1 Motor Rotation Monitoring FaultReadInactive=Ok; Active=Fault
BV101011Supply Air Fan 1 FaultReadInactive=Ok; Active=Fault
BV101021Supply Air Fan 2 FaultReadInactive=Ok; Active=Fault
BV101031Supply Air Fan 3 FaultReadInactive=Ok; Active=Fault
BV101041Supply Air Fan 4 FaultReadInactive=Ok; Active=Fault
BV101051Supply Air Fan 5 FaultReadInactive=Ok; Active=Fault
BV101061Supply Air Fan 6 FaultReadInactive=Ok; Active=Fault
BV101071Supply Air Fan 7 FaultReadInactive=Ok; Active=Fault
BV101081Supply Air Fan 8 FaultReadInactive=Ok; Active=Fault
BV201011Extract Air Fan 1 FaultReadInactive=Ok; Active=Fault
BV201021Extract Air Fan 2 FaultReadInactive=Ok; Active=Fault
BV201031Extract Air Fan 3 FaultReadInactive=Ok; Active=Fault
BV201041Extract Air Fan 4 FaultReadInactive=Ok; Active=Fault
BV201051Extract Air Fan 5 FaultReadInactive=Ok; Active=Fault
BV201061Extract Air Fan 6 FaultReadInactive=Ok; Active=Fault
BV201071Extract Air Fan 7 FaultReadInactive=Ok; Active=Fault
BV201081Extract Air Fan 8 FaultReadInactive=Ok; Active=Fault
BV102011Supply Air Damper 1 FaultReadInactive=Ok; Active=Fault
BV202011Extract Air Damper 1 FaultReadInactive=Ok; Active=Fault
BV302011Outdoor Air Damper 1 FaultReadInactive=Ok; Active=Fault
BV302021Outdoor Air Bypass Damper FaultReadInactive=Ok; Active=Fault
BV402011Exhaust Air Damper 1 FaultReadInactive=Ok; Active=Fault
BV402021Exhaust Air Bypass Damper FaultReadInactive=Ok; Active=Fault
BV602011Recirculation Air Damper 1 FaultReadInactive=Ok; Active=Fault
BV4102011Smoke Bypass Damper FaultReadInactive=Ok; Active=Fault
BV4101011Smoke Extraction Fan 1 FaultReadInactive=Ok; Active=Fault
BV4101021Smoke Extraction Fan 2 FaultReadInactive=Ok; Active=Fault
BV4101031Smoke Extraction Fan 3 FaultReadInactive=Ok; Active=Fault
MV3030011Temperature Control TypeWrite1=None; 2=Supply Air; 3=Extract; 4=Room Air; 5=Extract Cascade; 6=Room Cascade; 7=Outdoor Air Curve
MV3030012Temperature Control ModeWrite1=Automatic; 2=Heating; 3=Cooling; 4=Night Purge
MV3131011Humidity Control TypeWrite1=None; 2=Supply Air; 3=Extract Air; 4=Room Air; 5=Extract Air Cascade; 6=Room Air Cascade
MV3131012Humidity Control ModeWrite1=Automatic; 2=Heating; 3=Cooling
MV3232011Air Quality Control TypeWrite1=None; 2=Extract Air; 3=Room Air
MV3232012Air Quality Control ModeWrite1=Passive; 2=Active; 3=Passive/Active; 4=Active/Passive
MVmin3939011Unit Operation ModeWrite1=Automatic; 2=Room Frost Protection; 3=Low Speed; 4=High Speed; 5=Free Profile 1; 6=Free Profile 2; 7=Night Purge
MVmin3939091Unit Operation Mode ActualWrite1=Room Frost Protection; 2=Low Speed; 3=High Speed; 4=Free Profile 1; 5=Free Profile 2; 6=Night Purge; 7=Boost
SCH3903011Pump Kick SORead
SCH3904011Valve Lime Kick SORead
SCH3939011Unit Operation Mode SORead
SCH3939181Change Over SORead
SCH4139011Smoke Bypass Damper Exercise SORead
Object ID lookup: FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ISYteq controller for eCO Top / eCO Side compact AHUs and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs

How many BACnet points does the FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs have?

This list has 495 BACnet objects: 84 analog inputs, 49 analog outputs, 120 analog values, 24 binary inputs, 77 binary outputs, 128 binary values, 5 schedules, 8 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs BACnet points are writable?

50 of the 495 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs BACnet documentation?

The source is BACnet ISYteq for eCO Top and eCO Side - datasheet (BACnet register, ISYteq) (DC_10484GB 20200812_R0), revision 2020-08-12, published free by FläktGroup at https://www.flaktgroup.com/api/v1/Documents/1076733/Download.

What are the minimum BACnet points to integrate the FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs?

Start with MV 3939011 Unit Operation Mode (Unit mode command: 1 Automatic, 3 Low, 4 High speed); AV 3030071 Temperature Control Setpoint (Temperature setpoint, 5-45 °C); AI 3030042 Temperature Control External Setpoint (External temperature setpoint from the BMS, °C); MV 3939091 Unit Operation Mode Actual (Actual unit operation mode); AI 106011 Supply Air Temperature Sensor (Supply air temperature, °C); AI 206011 Extract Air Temperature Sensor (Extract air temperature, °C); AI 306011 Outdoor Air Temperature Sensor (Outdoor air temperature, °C); AO 101011 Supply Air Fan 1 Output (Supply fan output, %); BO 3939031 Alarm Collective A (Collective A alarm); BO 3939041 Alarm Collective B (Collective B alarm).

How do I enable BMS control of the FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs?

MV 3939011 Unit Operation Mode (R/W) selects Automatic, Room Frost Protection, Low/High Speed, Free Profile 1/2 or Night Purge. BV 3030081 / 3131081 / 3232081 let temperature, humidity or air quality control enable the unit.

Can the BMS supply sensor values to the FläktGroup ISYteq controller for eCO Top / eCO Side compact AHUs?

The AI external setpoint objects (temperature 3030042, relative 3030043, humidity 3131042, air quality 3232042, fan flow/pressure/manual 133022-24 and 233022-24, outdoor air amount 2929011) are R/W inputs the BMS can write.