  4. Vacon NX OPT-CJ BACnet MS/TP option board

Variable frequency drive (BACnet option board) · BACnet points list

Danfoss Vacon NX OPT-CJ BACnet MS/TP option board BACnet points list

Updated 4 November 2026

Short answer

OPT-CJ adds BACnet MS/TP to Vacon NX drives (now Danfoss Drives). The object list is Binary Values for drive status, run/stop, direction and fault reset, and Analog Values for speed reference, frequency, current, power, energy, fault code, limits, ramps and raw fieldbus process data and control/status words.

This page lists 71 BACnet objects for the Danfoss Vacon NX OPT-CJ BACnet MS/TP option board — 30 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Danfoss’s own free documentation, linked below.

Manufacturer
Danfoss
Model
Vacon NX OPT-CJ BACnet MS/TP option board
Equipment
Variable frequency drive (BACnet option board)
Equipment type
VFDs & pumps
BACnet objects
71 (30 writable)
Transport
BACnet MS/TP
Firmware
Option board software OPTCJ_10522 (AV 34-39 from OPTCJ_10522V009)
Default device instance
0 = use the unique number read from the drive (shown in the monitor menu)
Also known as
OPT-CJ, OPTCJ, NXOPTCJ, Vacon NX BACnet, Vacon NXS, Vacon NXP, Vacon NXL, DPD00901
Source document
Vacon NX OPT-CJ BACnet Option Board User Manual · DPD00901A (Danfoss BC361182944770en-000101) · rev. 19.01.2012
Download CSV 71 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Danfoss’s current documentation and the live device before use. Not official Danfoss information. Terms of use.

BMS integration notes: Danfoss Vacon NX OPT-CJ BACnet MS/TP option board

Integration in brief

Install the board in slot D or E, set MAC address, baud rate, instance number and communication time-out in menu M7, and make Fieldbus the active control place. Then command BV 15 run/stop and AV 24 speed reference, and read BV 1, AV 1 and the fault points.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 15Run/Stop CMDRun/stop command (1 = run)Command
AV 24Speed ReferenceSpeed reference, % of nominal speedCommand
BV 17Reset FaultResets the active faultCommand
BV 1Run/Stop StateRunning statusRead
AV 1Output FrequencyOutput frequency, HzRead
AV 5Motor CurrentMotor current, ARead
AV 3Load (power)Motor shaft power, %Read
BV 3Fault StateAny active drive faultRead
AV 23Active Fault CodeWhich fault is activeRead

Enable & remote start

Select Fieldbus as the active control place on the drive (see the Vacon NX user manual); BV 15 run/stop, BV 16 direction and AV 24 speed reference only work then.

Heartbeat & communication loss

Parameter Comm. time-out (P7.x.1.4, 10-60 s in 10 s steps, default 10 s, 0 = off) raises a fieldbus fault if communication stops. The drive reaction is set by P2.7.22 Response to fieldbus fault: 0 no response, 1 warning, 2 fault with ramp stop, 3 fault with coast stop.

Network setup

Watch out for

Danfoss Vacon NX OPT-CJ BACnet MS/TP option board BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

71 of 71 shown
Type
AnalogBinary
Access
Show
Danfoss Vacon NX OPT-CJ BACnet MS/TP option board BACnet Points List
DescriptionStates
BV0Ready StateDrive readyRead0=Not Ready, 1=Ready
BVmin1Run/Stop StateDrive runningRead0=Stop, 1=Run
BV2Fwd/Rev StateMotor rotation directionRead0=Fwd, 1=Rev
BVmin3Fault StateFault activeRead0=OK, 1=Fault
BV4Warning StateWarning activeRead0=OK, 1=Warning
BV5At SetpointReference frequency reachedRead0=False, 1=True
BV6At Zero SpeedMotor running at zero speedRead0=False, 1=True
BV7General 0Application-specific bit of the General Status WordRead0/1
BV8General 1Application-specific bit of the General Status WordRead0/1
BV9General 2Application-specific bit of the General Status WordRead0/1
BV10General 3Application-specific bit of the General Status WordRead0/1
BV11General 4Application-specific bit of the General Status WordRead0/1
BV12General 5Application-specific bit of the General Status WordRead0/1
BV13General 6Application-specific bit of the General Status WordRead0/1
BV14General 7Application-specific bit of the General Status WordRead0/1
BVmin15Run/Stop CMDStart/stop command (fieldbus control active)Command0=Stop, 1=Run
BV16Fwd/Rev CMDDirection command (fieldbus control active)Command0=Fwd, 1=Rev
BVmin17Reset FaultReset the active faultCommand0, 1=Reset
BV18FBFixedControlWord Bit_3Application-specific bit of the Fixed Control WordCommand0/1
BV19FBFixedControlWord Bit_4Application-specific bit of the Fixed Control WordCommand0/1
BV20FBFixedControlWord Bit_5Application-specific bit of the Fixed Control WordCommand0/1
BV21FBFixedControlWord Bit_6Application-specific bit of the Fixed Control WordCommand0/1
BV22FBFixedControlWord Bit_7Application-specific bit of the Fixed Control WordCommand0/1
BV23FBFixedControlWord Bit_8Application-specific bit of the Fixed Control WordCommand0/1
BV24FBFixedControlWord Bit_9Application-specific bit of the Fixed Control WordCommand0/1
BV25FBFixedControlWord Bit_10Application-specific bit of the Fixed Control WordCommand0/1
BV26FBFixedControlWord Bit_11Application-specific bit of the Fixed Control WordCommand0/1
BV27FBFixedControlWord Bit_12Application-specific bit of the Fixed Control WordCommand0/1
BV28FBFixedControlWord Bit_13Application-specific bit of the Fixed Control WordCommand0/1
BV29FBFixedControlWord Bit_14Application-specific bit of the Fixed Control WordCommand0/1
BV30FBFixedControlWord Bit_15Application-specific bit of the Fixed Control WordCommand0/1
AV0Frequency SetpointFrequency setpointHzRead
AVmin1Output FrequencyOutput frequencyHzRead
AV2Motor SpeedMotor speedrpmRead
AVmin3Load (power)Motor shaft power%Read
AV4Kilowatt Hours totalTotal energy counterkWhRead
AVmin5Motor CurrentMotor currentARead
AV6DC link VoltageDC link voltageVRead
AV7Motor VoltageMotor voltageVRead
AV8Unit TemperatureHeatsink temperature (not on NXL)°CRead
AV9Motor TorqueTorque, % of motor nominal%Read
AV10Operating DaysOperating days (resettable)daysRead
AV11Operating HoursOperating hours (resettable)hRead
AV12Kilowatt HoursEnergy counter (resettable)kWhRead
AV13Torque ReferenceTorque reference (not on NXL)%Read
AV14Temperature RiseCalculated motor temperature, 100 % = nominal (not on NXL)%Read
AV15FBProcessDataOut1Application-specific process data outRead
AV16FBProcessDataOut2Application-specific process data outRead
AV17FBProcessDataOut3Application-specific process data outRead
AV18FBProcessDataOut4Application-specific process data outRead
AV19FBProcessDataOut5Application-specific process data outRead
AV20FBProcessDataOut6Application-specific process data outRead
AV21FBProcessDataOut7Application-specific process data outRead
AV22FBProcessDataOut8Application-specific process data outRead
AVmin23Active Fault CodeActive fault codeRead
AVmin24Speed ReferenceSpeed reference, % of nominal speed%Command
AV25Current LimitCurrent limitAWrite
AV26Min FrequencyMinimum frequencyHzWrite
AV27Maximum FrequencyMaximum frequencyHzWrite
AV28Accel TimeAcceleration timesWrite
AV29Decel TimeDeceleration timesWrite
AV30FBProcessDataIN 1Application-specific process data inCommand
AV31FBProcessDataIN 2Application-specific process data inCommand
AV32FBProcessDataIN 3Application-specific process data inCommand
AV33FBProcessDataIN 4Application-specific process data inCommand
AV34AnyParam IDParameter ID to access through AV 35Write
AV35AnyParam ValueValue of the parameter selected in AV 34Write
AV36FBFixedControlWord PDI 0Fixed control word (B0 run, B1 direction, B2 fault reset)Command
AV37FBGeneralControlWord PDI 1General control word (application specific)Command
AV38FBFixedStatusWord PDO 0Fixed status word (B0 ready, B1 run, B3 fault, B4 warning...)Read
AV39FBGeneralStatusWord PDO 1General status word (application specific)Read
Object ID lookup: Danfoss Vacon NX OPT-CJ BACnet MS/TP option board point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Vacon NX OPT-CJ BACnet MS/TP option board and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Danfoss Vacon NX OPT-CJ BACnet MS/TP option board

How many BACnet points does the Danfoss Vacon NX OPT-CJ BACnet MS/TP option board have?

This list has 71 BACnet objects: 40 analog values, 31 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Danfoss Vacon NX OPT-CJ BACnet MS/TP option board BACnet points are writable?

30 of the 71 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Danfoss Vacon NX OPT-CJ BACnet MS/TP option board BACnet documentation?

The source is Vacon NX OPT-CJ BACnet Option Board User Manual (DPD00901A (Danfoss BC361182944770en-000101)), revision 19.01.2012, published free by Danfoss at https://assets.danfoss.com/documents/latest/270807/BC361182944770en-000101.pdf.

What are the minimum BACnet points to integrate the Danfoss Vacon NX OPT-CJ BACnet MS/TP option board?

Start with BV 15 Run/Stop CMD (Run/stop command (1 = run)); AV 24 Speed Reference (Speed reference, % of nominal speed); BV 17 Reset Fault (Resets the active fault); BV 1 Run/Stop State (Running status); AV 1 Output Frequency (Output frequency, Hz); AV 5 Motor Current (Motor current, A); AV 3 Load (power) (Motor shaft power, %); BV 3 Fault State (Any active drive fault); AV 23 Active Fault Code (Which fault is active).

How do I enable BMS control of the Danfoss Vacon NX OPT-CJ BACnet MS/TP option board?

Select Fieldbus as the active control place on the drive (see the Vacon NX user manual); BV 15 run/stop, BV 16 direction and AV 24 speed reference only work then.

Does the Danfoss Vacon NX OPT-CJ BACnet MS/TP option board need a BACnet heartbeat or have a communication timeout?

Parameter Comm. time-out (P7.x.1.4, 10-60 s in 10 s steps, default 10 s, 0 = off) raises a fieldbus fault if communication stops. The drive reaction is set by P2.7.22 Response to fieldbus fault: 0 no response, 1 warning, 2 fault with ramp stop, 3 fault with coast stop.

How do I check these points on the real Vacon NX OPT-CJ BACnet MS/TP option board?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.