Variable frequency drive (HVAC) · BACnet points list

Danfoss VLT HVAC Drive FC 102 with BACnet/IP MCA 125 BACnet points list

Updated 28 October 2026

Short answer

The MCA 125 is a plug-in option that puts a VLT HVAC Drive FC 102 on BACnet IP. It publishes the drive's I/O, speed, power, alarm words and control bits as fixed objects, plus 30 user-mappable custom AV objects (AV:102 to AV:131) set in parameter 8-77. Many objects only respond when the matching I/O option (MCB 101/109/113/114/115) or a CBM license is present.

This page lists 250 BACnet objects for the Danfoss VLT HVAC Drive FC 102 with BACnet/IP MCA 125 — 132 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Danfoss’s own free documentation, linked below.

Manufacturer
Danfoss
Model
VLT HVAC Drive FC 102 with BACnet/IP MCA 125
Equipment
Variable frequency drive (HVAC)
Equipment type
VFDs & pumps
BACnet objects
250 (132 writable)
Transport
BACnet IP
Firmware
FC 102 software 9.7x; MCA 125 software 3.05 (custom objects need 3.05 or later)
Default device instance
1
Also known as
FC 102, FC102, VLT HVAC Drive, MCA 125, MCA125, 134B1586, VLT BACnet/IP
Source document
VLT BACnet/IP MCA 125 Programming Guide (VLT HVAC Drive FC 102, VLT AQUA Drive FC 202) · AU361182716349en-000201 (130R0673) · rev. 2025-12
Download CSV 250 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Danfoss VLT HVAC Drive FC 102 with BACnet/IP MCA 125

Integration in brief

Give the drive a unique instance in 8-70 and an IP address in 12-0*, then write BV:1 RUN/STOP command and AV:1 Input reference 1 (%). Read BV:4 RUN/STOP monitor, BV:5 OK/FAULT monitor and AV:0/AV:5/AV:6 for speed, current and power, and use BV:3 to reset trips. Set 8-03/8-04 so the drive goes to a known state if the BMS stops writing.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1RUN/STOP commandStart/stop from the BMSCommand
AV 1Input reference 1Speed reference in %; writes also restart the 8-03 timeoutCommand
BV 3Fault reset commandReset a tripped driveWrite
BV 4RUN/STOP monitorRunning statusRead
BV 6HAND/AUTO referenceShows if the drive is in HandRead
AV 0Speed act valueActual speed feedbackRead
AV 5Motor currentMotor ampsRead
AV 6PowerDrive power in kWRead
BV 5OK/FAULT monitorAny active drive faultRead
AV 61Alarm word 1Alarm detail for troubleshootingRead

Heartbeat & communication loss

Parameter 8-03 Control Timeout Time (0.5-18000 s, factory 60.0 s) restarts on every write to any AO, AV 1/2/31, BV 1/2/25/26/27 or MSV 1. If the BMS stops writing for longer than that, the drive raises alarm 17 Ctrl.word TO and does whatever 8-04 Control Timeout Function selects (factory Off; options include stop and trip or max speed). 8-05 End-of-Timeout Function (factory Resume setup) sets what happens when writes resume. Danfoss suggests about 3 writes per timeout window.

Sensors & values from the BMS

The BMS can write the PID feedback to AV:31 Bus feedback 1 (parameter 8-94) and the PID setpoint to AV:30 Setpoint 1 (parameter 20-21). Writing AV:31 also restarts the control timeout.

Network setup

Watch out for

Danfoss VLT HVAC Drive FC 102 with BACnet/IP MCA 125 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

250 of 250 shown
Type
Multi-state
Access
Show
Danfoss VLT HVAC Drive FC 102 with BACnet/IP MCA 125 BACnet Points List
DescriptionStates
AI0Analog input 53Maps to drive parameter 1662%Read
AI1Analog input 54Maps to drive parameter 1664%Read
AI2Analog in X30/11Maps to drive parameter 1675; needs MCB 101%Read
AI3Analog in X30/12Maps to drive parameter 1676; needs MCB 101%Read
AI4Analog in X42/1Maps to drive parameter 1830; needs MCB 109VRead
AI5Analog in X42/3Maps to drive parameter 1831; needs MCB 109VRead
AI6Analog in X42/5Maps to drive parameter 1832; needs MCB 109VRead
AI7Analog input X48/2Maps to drive parameter 1836; needs MCB 114%Read
AI8Analog input X48/4Maps to drive parameter 1837; needs MCB 114°CRead
AI9Analog input X48/7Maps to drive parameter 1838; needs MCB 114°CRead
AI10Analog input X48/10Maps to drive parameter 1839; needs MCB 114°CRead
AI11Analog input X49/1Maps to drive parameter 1840; needs MCB 115V/A/TRead
AI12Analog input X49/3Maps to drive parameter 1841; needs MCB 115V/A/TRead
AI13Analog input X49/5Maps to drive parameter 1842; needs MCB 115V/A/TRead
AI14Pressure sensor 1Maps to drive parameter 3126PascalRead
AI15Pressure sensor 2Maps to drive parameter 3127PascalRead
AI16Pressure sensor 3Maps to drive parameter 3128PascalRead
AI17Pressure sensor 4Maps to drive parameter 3129PascalRead
AO0Terminal 42 output bus controlMaps to drive parameter 653%Command
AO1Pulse out #27 bus controlMaps to drive parameter 593%Command
AO2Pulse out #29 bus controlMaps to drive parameter 595%Command
AO3Terminal X30/8 output bus controlMaps to drive parameter 663; needs MCB 101%Command
AO4Analog output X42/7Maps to drive parameter 2643; needs MCB 109VCommand
AO5Analog output X42/9Maps to drive parameter 2653; needs MCB 109VCommand
AO6Analog output X42/11Maps to drive parameter 2663; needs MCB 109VCommand
AO7Analog output X49/7Maps to drive parameter 3644; needs MCB 115VCommand
AO8Analog output X49/9Maps to drive parameter 3654; needs MCB 115VCommand
AO9Analog output X49/11Maps to drive parameter 3664; needs MCB 115VCommand
AO10Analog output X45/1Maps to drive parameter 1678; needs MCB 113VRead
AO11Analog output X45/3Maps to drive parameter 1679; needs MCB 113VRead
AVmin0Speed act valueMaps to drive parameter 1682%Read
AVmin1Input reference 1Maps to drive parameter 1682%Command
AV2Input reference 2Maps to drive parameter 1682%Command
AV3Output speed%Read
AV4PID feedback%Read
AVmin5Motor currentMaps to drive parameter 1614AmpsRead
AVmin6PowerMaps to drive parameter 1610KWRead
AV15Motor thermalMaps to drive parameter 1618%Read
AV21Operating hoursMaps to drive parameter 1500HoursRead
AV22Running hoursMaps to drive parameter 1501HoursRead
AV23kWh counterMaps to drive parameter 1502kWhRead
AV24Motor voltageMaps to drive parameter 1612VRead
AV25FrequencyMaps to drive parameter 1613HzRead
AV26TorqueMaps to drive parameter 1622%Read
AV27DC link voltageMaps to drive parameter 1630VRead
AV28Heatsink temp.Maps to drive parameter 1634°CRead
AV29Inverter thermalMaps to drive parameter 1635%Read
AV30Setpoint 1Maps to drive parameter 2021%Write
AV31Bus feedback 1Maps to drive parameter 894%Write
AV58Sensorless readoutMaps to drive parameter 1850Read
AV59PID outputMaps to drive parameter 1658%Read
AV60PID setpointMaps to drive parameter 1659Same as feedback unitRead
AVmin61Alarm word 1Maps to drive parameter 1690Read
AV62Alarm word 2Maps to drive parameter 1691Read
AV63Alarm word 3Maps to drive parameter 1697Read
AV65External referenceMaps to drive parameter 1650Read
AV66Warning word 1Maps to drive parameter 1692Read
AV67Warning word 2Maps to drive parameter 1693Read
AV68Warning word 3Maps to drive parameter 1698Read
AV70Feedback [unit]Maps to drive parameter 1652Same as feedback unitRead
AV71AirPressure To Air Flow 2Maps to drive parameter 1857M2/HRead
AV74Ext. status wordMaps to drive parameter 1694Read
AV75Ext. status word 2Maps to drive parameter 1695Read
AV80Below level threshold [0]Maps to drive parameter 3121[0]PascalWrite
AV81Below level threshold [1]Maps to drive parameter 3121[1]PascalWrite
AV82Below level threshold [2]Maps to drive parameter 3121[2]PascalWrite
AV83Below level threshold [3]Maps to drive parameter 3121[3]PascalWrite
AV84Above level threshold [0]Maps to drive parameter 3122[0]PascalWrite
AV85Above level threshold [1]Maps to drive parameter 3122[1]PascalWrite
AV86Above level threshold [2]Maps to drive parameter 3122[2]PascalWrite
AV87Above level threshold [3]Maps to drive parameter 3122[3]PascalWrite
AV88On delay time [0]Maps to drive parameter 3123[0]Sec.Write
AV89On delay time [1]Maps to drive parameter 3123[1]Sec.Write
AV90On delay time [2]Maps to drive parameter 3123[2]Sec.Write
AV91On delay time [3]Maps to drive parameter 3123[3]Sec.Write
AV92Reset delay time [0]Maps to drive parameter 3124[0]Sec.Write
AV93Reset delay time [1]Maps to drive parameter 3124[1]Sec.Write
AV94Reset delay Time [2]Maps to drive parameter 3124[2]Sec.Write
AV95Reset delay time [3]Maps to drive parameter 3124[3]Sec.Write
AV96CBM Stator [%]Maps to drive parameter 4590; needs CBM license%Read
AV97CBM Load [%]Maps to drive parameter 4591; needs CBM license%Read
AV98CBM Sensor 1 [%]Maps to drive parameter 4592; needs CBM license%Read
AV99CBM Sensor 2 [%]Maps to drive parameter 4594; needs CBM license%Read
AV100CBM Sensor 3 [%]Maps to drive parameter 4596; needs CBM license%Read
AV101CBM Sensor 4 [%]Maps to drive parameter 4598; needs CBM license%Read
AV102Custom objectMaps to drive parameter 877[0]User definedWrite
AV103Custom objectMaps to drive parameter 877[1]User definedWrite
AV104Custom objectMaps to drive parameter 877[2]User definedWrite
AV105Custom objectMaps to drive parameter 877[3]User definedWrite
AV106Custom objectMaps to drive parameter 877[4]User definedWrite
AV107Custom objectMaps to drive parameter 877[5]User definedWrite
AV108Custom objectMaps to drive parameter 877[6]User definedWrite
AV109Custom objectMaps to drive parameter 877[7]User definedWrite
AV110Custom objectMaps to drive parameter 877[8]User definedWrite
AV111Custom objectMaps to drive parameter 877[9]User definedWrite
AV112Custom objectMaps to drive parameter 877[10]User definedWrite
AV113Custom objectMaps to drive parameter 877[11]User definedWrite
AV114Custom objectMaps to drive parameter 877[12]User definedWrite
AV115Custom objectMaps to drive parameter 877[13]User definedWrite
AV116Custom objectMaps to drive parameter 877[14]User definedWrite
AV117Custom objectMaps to drive parameter 877[15]User definedWrite
AV118Custom objectMaps to drive parameter 877[16]User definedWrite
AV119Custom objectMaps to drive parameter 877[17]User definedWrite
AV120Custom objectMaps to drive parameter 877[18]User definedWrite
AV121Custom objectMaps to drive parameter 877[19]User definedWrite
AV122Custom objectMaps to drive parameter 877[20]User definedWrite
AV123Custom objectMaps to drive parameter 877[21]User definedWrite
AV124Custom objectMaps to drive parameter 877[22]User definedWrite
AV125Custom objectMaps to drive parameter 877[23]User definedWrite
AV126Custom objectMaps to drive parameter 877[24]User definedWrite
AV127Custom objectMaps to drive parameter 877[25]User definedWrite
AV128Custom objectMaps to drive parameter 877[26]User definedWrite
AV129Custom objectMaps to drive parameter 877[27]User definedWrite
AV130Custom objectMaps to drive parameter 877[28]User definedWrite
AV131Custom objectMaps to drive parameter 877[29]User definedWrite
AV132Freeze fault log for downloadWrite
AV133Amount of faultsRead
AV134Fault indexWrite
AV135Fault numberMaps to drive parameter 4330/1530Read
AV136Fault subcodeMaps to drive parameter 4331/1531Read
AV137Fault timeMaps to drive parameter 4332/1532Read
AV138Fault dateMaps to drive parameter 4333/1533Read
AV142Fault speedMaps to drive parameter 4338/1538Read
AV143Fault durationMaps to drive parameter 4339Read
AV144Fault ext. refMaps to drive parameter 4340/4040Read
AV145Fault frequencyMaps to drive parameter 4341/4041Read
AV146Fault currentMaps to drive parameter 4342/4042Read
AV147Fault voltageMaps to drive parameter 4343/4043Read
AV148Fault DC link voltageMaps to drive parameter 4344/4044Read
AV149Fault control wordMaps to drive parameter 4345/4045Read
AV150Fault status wordMaps to drive parameter 4346/4046Read
AV151Fault torqueMaps to drive parameter 4347/4047Read
AV152Fault CBM valueMaps to drive parameter 4348/4048Read
AV153Fault CBM thresholdMaps to drive parameter 4349/4049Read
BI0Digital input term 33Maps to drive parameter 1660, bit 0ReadOn/Off
BI1Digital input term 32Maps to drive parameter 1660, bit 1ReadOn/Off
BI2Digital input term 29Maps to drive parameter 1660, bit 2ReadOn/Off
BI3Digital input term 27Maps to drive parameter 1660, bit 3ReadOn/Off
BI4Digital input term 19Maps to drive parameter 1660, bit 4ReadOn/Off
BI5Digital input term 18Maps to drive parameter 1660, bit 5ReadOn/Off
BI6Digital input term 37Maps to drive parameter 1660, bit 6ReadOn/Off
BI7Digital input GPIO term X30/4Maps to drive parameter 1660, bit 7; needs MCB 101ReadOn/Off
BI8Digital input GPIO term X30/3Maps to drive parameter 1660, bit 8; needs MCB 101ReadOn/Off
BI9Digital input GPIO term X30/2Maps to drive parameter 1660, bit 9; needs MCB 101ReadOn/Off
BI10Digital input ext. relay card X46/13Maps to drive parameter 1660, bit 10; needs MCB 113ReadOn/Off
BI11Digital input ext. relay card X46/11Maps to drive parameter 1660, bit 11; needs MCB 113ReadOn/Off
BI12Digital input ext. relay card X46/09Maps to drive parameter 1660, bit 12; needs MCB 113ReadOn/Off
BI13Digital input ext. relay card X46/07Maps to drive parameter 1660, bit 13; needs MCB 113ReadOn/Off
BI14Digital input ext. relay card X46/05Maps to drive parameter 1660, bit 14; needs MCB 113ReadOn/Off
BI15Digital input ext. relay card X46/03Maps to drive parameter 1660, bit 15; needs MCB 113ReadOn/Off
BI16Digital input ext. relay card X46/01Maps to drive parameter 1660, bit 16; needs MCB 113ReadOn/Off
BO0Digital output term 27Maps to drive parameter 5-90, bit 0CommandOn/Off
BO1Digital output term 29Maps to drive parameter 5-90, bit 1CommandOn/Off
BO2GPIO output term X30/6Maps to drive parameter 5-90, bit 2; needs MCB 101CommandOn/Off
BO3GPIO output term X30/7Maps to drive parameter 5-90, bit 3; needs MCB 101CommandOn/Off
BO4Relay 1Maps to drive parameter 5-90, bit 4CommandOn/Off
BO5Relay 2Maps to drive parameter 5-90, bit 5CommandOn/Off
BO6Option B relay 1 outputMaps to drive parameter 5-90, bit 6; needs MCB 105CommandOn/Off
BO7Option B relay 2 outputMaps to drive parameter 5-90, bit 7; needs MCB 105CommandOn/Off
BO8Option B relay 3 outputMaps to drive parameter 5-90, bit 8; needs MCB 105CommandOn/Off
BO9Digital input programmable op. term X49/7Maps to drive parameter 5-90, bit 24; needs MCB 115CommandOn/Off
BO10Digital input programmable op. term X49/9Maps to drive parameter 5-90, bit 25; needs MCB 115CommandOn/Off
BO11Digital input programmable op. term X49/11Maps to drive parameter 5-90, bit 26; needs MCB 115CommandOn/Off
BO12Extended relay card 1 outputMaps to drive parameter 16-71, bit 4; needs MCB 113CommandOn/Off
BO13Extended relay card 2 outputMaps to drive parameter 16-71, bit 3; needs MCB 113CommandOn/Off
BO14Extended relay card 3 outputMaps to drive parameter 16-71, bit 2; needs MCB 113CommandOn/Off
BO15Extended relay card 4 outputMaps to drive parameter 16-71, bit 7; needs MCB 113CommandOn/Off
BVmin1RUN/STOP commandMaps to drive parameter CTW=047c + bit 15Command
BV2REF 1/REF 2 selectMaps to drive parameter Note 1Command
BVmin3Fault reset commandMaps to drive parameter CTW bit 7Write
BVmin4RUN/STOP monitorMaps to drive parameter STW bit 1Read
BVmin5OK/FAULT monitorMaps to drive parameter STW bits 3, 6, and 7Read
BVmin6HAND/AUTO referenceMaps to drive parameter 16-95 bit 1Read
BV21WarningMaps to drive parameter STW bit 7Read
BV22TripMaps to drive parameter STW bit 3Read
BV23TriplockMaps to drive parameter STW bit 6Read
BV24CoastingMaps to drive parameter CTW bit 3Command
BV25CW/CCWMaps to drive parameter CTW bit 15Command
BV26JogMaps to drive parameter CTW bit 8Command
BV27ResetMaps to drive parameter CTW bit 7Command
BV28Reset KWh counterMaps to drive parameter 1506Command
BV29Reset running hours counterMaps to drive parameter 1507Write
BV30ReverseMaps to drive parameter CTW bit 15Write
BV31Speed = referenceMaps to drive parameter STW bit 8Read
BV32Bus controlMaps to drive parameter STW bit 9Read
BV33RunningMaps to drive parameter STW bit 11Read
BV34Ramp 1/Ramp 2Maps to drive parameter CTW bit 9Command
BV35ECB test modeMaps to drive parameter 3110 bit 0; needs MCO 104Read
BV36ECB drive modeMaps to drive parameter 3110 bit 1; needs MCO 104Read
BV37ECB auto. bypass enableMaps to drive parameter 3110 bit 2; needs MCO 104Read
BV38ECB bypass modeMaps to drive parameter 3110 bit 3; needs MCO 104Read
BV54CBM motor overload warningMaps to drive parameter 1698 bits 18, 19, 28, 29, 30, orRead
BV55CBM motor overload alarmMaps to drive parameter 1697 bits 25, 30, or 31; needs CBMRead
BV56CBM sensor warningMaps to drive parameter 1698 bits 20 to 27; needs CBM licenseRead
BV57CBM sensor alarmMaps to drive parameter 1697 bits 26 to 29; needs CBM licenseRead
MV0Smart logic controller stateMaps to drive parameter 1638Read
MV1Active setupMaps to drive parameter CTW bit 13 and 14Command
MV3Configuration modeMaps to drive parameter 100Write
MV4Pressure sensor 1 cmp statesMaps to drive parameter 3130Read
MV5Pressure sensor 2 cmp statesMaps to drive parameter 3130Read
MV6Pressure sensor 3 cmp statesMaps to drive parameter 3130Read
MV7Pressure sensor 4 cmp statesMaps to drive parameter 3130Read
MV8CBM stator windingMaps to drive parameter 45-01 [0]; needs CBM licenseRead
MV9CBM load envelopeMaps to drive parameter 45-01 [1]; needs CBM licenseRead
MV10CBM sensor 1Maps to drive parameter 45-01 [2]; needs CBM licenseRead
MV11CBM sensor 2Maps to drive parameter 45-01 [3]; needs CBM licenseRead
MV12CBM sensor 3Maps to drive parameter 45-01 [4]; needs CBM licenseRead
MV13CBM sensor 4Maps to drive parameter 45-01 [5]; needs CBM licenseRead
NC0Warning notifierProvided by the MCA 125 option itselfWrite
NC1Trip notifierProvided by the MCA 125 option itselfWrite
NC3Triplock notifierProvided by the MCA 125 option itselfWrite
NC100NC 100Provided by the MCA 125 option itselfWrite
NC200NC 200Provided by the MCA 125 option itselfWrite
NC300NC 300Provided by the MCA 125 option itselfWrite
NC400NC 400Provided by the MCA 125 option itselfWrite
TL0Trend log 0Write
TL1Trend log 1Write
TL2Trend log 2Write
TL3Trend log 3Write
TL4Trend log 4Write
TL5Trend log 5Write
TL6Trend log 6Write
LO0Drive close loopMaps to drive parameter 2093, 2094, 2095Write
Other0Event enrollment 0Provided by the MCA 125 option itselfWrite
Other1Event enrollment 1Provided by the MCA 125 option itselfWrite
Other2Event enrollment 2Provided by the MCA 125 option itselfWrite
Other3Event enrollment 3Provided by the MCA 125 option itselfWrite
Other4Event enrollment 4Provided by the MCA 125 option itselfWrite
Other5Event enrollment 5Provided by the MCA 125 option itselfWrite
Other6Event enrollment 6Provided by the MCA 125 option itselfWrite
Other7Event enrollment 7Provided by the MCA 125 option itselfWrite
Other8Event enrollment 8Provided by the MCA 125 option itselfWrite
Other9Event enrollment 9Provided by the MCA 125 option itselfWrite
Other10Event enrollment 10Provided by the MCA 125 option itselfWrite
Other11Event enrollment 11Provided by the MCA 125 option itselfWrite
Other12Event enrollment 12Provided by the MCA 125 option itselfWrite
Other13Event enrollment 13Provided by the MCA 125 option itselfWrite
SCH0Drive schedule 0Provided by the MCA 125 option itselfWrite
SCH1Drive schedule 1Provided by the MCA 125 option itselfWrite
SCH2Drive schedule 2Provided by the MCA 125 option itselfWrite
SCH3Drive schedule 3Provided by the MCA 125 option itselfWrite
SCH4Drive schedule 4Provided by the MCA 125 option itselfWrite
SCH5Drive schedule 5Provided by the MCA 125 option itselfWrite
CAL0Exception calendarProvided by the MCA 125 option itselfWrite
CAL1Exception calendarProvided by the MCA 125 option itselfWrite
CAL2Exception calendarProvided by the MCA 125 option itselfWrite
CAL3Exception calendarProvided by the MCA 125 option itselfWrite
CAL4Exception calendarProvided by the MCA 125 option itselfWrite
CAL5Exception calendarProvided by the MCA 125 option itselfWrite
Other0Event logProvided by the MCA 125 option itselfRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VLT HVAC Drive FC 102 with BACnet/IP MCA 125 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Danfoss VLT HVAC Drive FC 102 with BACnet/IP MCA 125

How many BACnet points does the Danfoss VLT HVAC Drive FC 102 with BACnet/IP MCA 125 have?

This list has 250 BACnet objects: 18 analog inputs, 12 analog outputs, 104 analog values, 17 binary inputs, 16 binary outputs, 28 binary values, 6 calendars, 1 loop, 7 notification classs, 6 schedules, 13 multi-state values, 7 trend logs, 15 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Danfoss VLT HVAC Drive FC 102 with BACnet/IP MCA 125 BACnet points are writable?

132 of the 250 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Danfoss VLT HVAC Drive FC 102 with BACnet/IP MCA 125 BACnet documentation?

The source is VLT BACnet/IP MCA 125 Programming Guide (VLT HVAC Drive FC 102, VLT AQUA Drive FC 202) (AU361182716349en-000201 (130R0673)), revision 2025-12, published free by Danfoss at https://assets.danfoss.com/documents/562086/AU361182716349en-000201.pdf.

What are the minimum BACnet points to integrate the Danfoss VLT HVAC Drive FC 102 with BACnet/IP MCA 125?

Start with BV 1 RUN/STOP command (Start/stop from the BMS); AV 1 Input reference 1 (Speed reference in %; writes also restart the 8-03 timeout); BV 3 Fault reset command (Reset a tripped drive); BV 4 RUN/STOP monitor (Running status); BV 6 HAND/AUTO reference (Shows if the drive is in Hand); AV 0 Speed act value (Actual speed feedback); AV 5 Motor current (Motor amps); AV 6 Power (Drive power in kW); BV 5 OK/FAULT monitor (Any active drive fault); AV 61 Alarm word 1 (Alarm detail for troubleshooting).

Does the Danfoss VLT HVAC Drive FC 102 with BACnet/IP MCA 125 need a BACnet heartbeat or have a communication timeout?

Parameter 8-03 Control Timeout Time (0.5-18000 s, factory 60.0 s) restarts on every write to any AO, AV 1/2/31, BV 1/2/25/26/27 or MSV 1. If the BMS stops writing for longer than that, the drive raises alarm 17 Ctrl.word TO and does whatever 8-04 Control Timeout Function selects (factory Off; options include stop and trip or max speed). 8-05 End-of-Timeout Function (factory Resume setup) sets what happens when writes resume. Danfoss suggests about 3 writes per timeout window.

Can the BMS supply sensor values to the Danfoss VLT HVAC Drive FC 102 with BACnet/IP MCA 125?

The BMS can write the PID feedback to AV:31 Bus feedback 1 (parameter 8-94) and the PID setpoint to AV:30 Setpoint 1 (parameter 20-21). Writing AV:31 also restarts the control timeout.

How do I check these points on the real VLT HVAC Drive FC 102 with BACnet/IP MCA 125?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Danfoss BACnet points lists

Source: VLT BACnet/IP MCA 125 Programming Guide (VLT HVAC Drive FC 102, VLT AQUA Drive FC 202) · AU361182716349en-000201 (130R0673) · rev. 2025-12. Object names, instances and units are reproduced as published; descriptions are our own.