Variable frequency drive (water / pump) · BACnet points list
Danfoss VLT AQUA Drive FC 202 with BACnet/IP MCA 125 BACnet points list
Updated 28 October 2026
Same MCA 125 BACnet IP option as the FC 102, but on the AQUA (pump) drive. Besides the shared drive objects it adds pump-specific status points such as deragging, sleep mode, dry pump, no flow, end of curve, pipe fill and a pump status string. Objects for absent I/O options or a missing CBM license will not return useful data.
This page lists 250 BACnet objects for the Danfoss VLT AQUA Drive FC 202 with BACnet/IP MCA 125 — 117 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Danfoss’s own free documentation, linked below.
- Manufacturer
- Danfoss
- Model
- VLT AQUA Drive FC 202 with BACnet/IP MCA 125
- Equipment
- Variable frequency drive (water / pump)
- Equipment type
- VFDs & pumps
- BACnet objects
- 250 (117 writable)
- Transport
- BACnet IP
- Firmware
- FC 202 software 5.8x; MCA 125 software 3.05 (custom objects need 3.05 or later)
- Default device instance
- 1
- Also known as
- FC 202, FC202, VLT AQUA Drive, MCA 125, MCA125, 134B1586, VLT BACnet/IP
BMS integration notes: Danfoss VLT AQUA Drive FC 202 with BACnet/IP MCA 125
Give the drive a unique instance in 8-70 and an IP address in 12-0*, then write BV:1 RUN/STOP command and AV:1 Input reference 1 (%). Read BV:4, BV:5 and AV:0/AV:5/AV:6 for status, speed, current and power, plus pump points such as BV:49 No flow and BV:50 Dry pump. Use BV:3 to reset trips and set 8-03/8-04 so the drive goes to a known state if the BMS stops writing.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | RUN/STOP command | Start/stop from the BMS | Command |
| AV 1 | Input reference 1 | Speed reference in %; writes also restart the 8-03 timeout | Command |
| BV 3 | Fault reset command | Reset a tripped drive | Write |
| BV 4 | RUN/STOP monitor | Running status | Read |
| BV 6 | HAND/AUTO reference | Shows if the drive is in Hand | Read |
| AV 0 | Speed act value | Actual speed feedback | Read |
| AV 5 | Motor current | Motor amps | Read |
| AV 6 | Power | Drive power in kW | Read |
| BV 5 | OK/FAULT monitor | Any active drive fault | Read |
| AV 61 | Alarm word 1 | Alarm detail for troubleshooting | Read |
Heartbeat & communication loss
Parameter 8-03 Control Timeout Time (0.5-18000 s, factory 60.0 s) restarts on every write to any AO, AV 1/2/31, BV 1/2/25/26/27 or MSV 1. If the BMS stops writing for longer than that, the drive raises alarm 17 Ctrl.word TO and does whatever 8-04 Control Timeout Function selects (factory Off; options include stop and trip or max speed). 8-05 End-of-Timeout Function (factory Resume setup) sets what happens when writes resume. Danfoss suggests about 3 writes per timeout window.
Sensors & values from the BMS
The BMS can write the PID feedback to AV:31 Bus feedback 1 (parameter 8-94) and the PID setpoint to AV:30 Setpoint 1 (parameter 20-21). Writing AV:31 also restarts the control timeout.
Network setup
- Device instance is parameter 8-70 (factory 1, range 0-4194302); the MCA 125 DIP switches override it unless they are all On or all Off.
- IP address: 12-00 selects Manual, DHCP or BOOTP; manual addresses go in 12-01 to 12-03 and need a power cycle.
- BACnet UDP port is 12-72 (factory 47808).
- Foreign-device registration: BBMD address 12-75 (0.0.0.0 disables), port 12-76, re-register interval 12-77.
- 8-74 sends I-Am at power-up only (factory) or about once a minute; 8-75 holds the reinitialize password (default admin).
Watch out for
- The MCA 125 shares the 8-7* BACnet parameters with the built-in MS/TP port, so connect the drive to only one BACnet network.
- The guide does not say which drive parameters (control site, control word source, reference source) must be set for bus control; check the drive programming guide.
- Many objects need an option card (MCB 101/109/113/114/115, MCO) or a CBM license and are dead without it.
- AV:102-AV:131 are blank until parameter 8-77 maps a drive parameter; unmapped ones are out of service or 'Not Configured'.
- Warning 34 Fieldbus fault is suppressed for 60 s after power-up; 12-78 can flag a duplicate device instance.
- The timeout trigger table also lists AV 36 and AV 41, which do not appear in the object tables.
Danfoss VLT AQUA Drive FC 202 with BACnet/IP MCA 125 BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | Analog input 53 | Maps to drive parameter 1662 | % | Read | |
| AI | 1 | Analog input 54 | Maps to drive parameter 1664 | % | Read | |
| AI | 2 | Analog in X30/11 | Maps to drive parameter 1675; needs MCB 101 | % | Read | |
| AI | 3 | Analog in X30/12 | Maps to drive parameter 1676; needs MCB 101 | % | Read | |
| AI | 4 | Analog in X42/1 | Maps to drive parameter 1830; needs MCB 109 | V | Read | |
| AI | 5 | Analog in X42/3 | Maps to drive parameter 1831; needs MCB 109 | V | Read | |
| AI | 6 | Analog in X42/5 | Maps to drive parameter 1832; needs MCB 109 | V | Read | |
| AI | 7 | Analog input X48/2 | Maps to drive parameter 1836; needs MCB 114 | % | Read | |
| AI | 8 | Analog input X48/4 | Maps to drive parameter 1837; needs MCB 114 | °C | Read | |
| AI | 9 | Analog input X48/7 | Maps to drive parameter 1838; needs MCB 114 | °C | Read | |
| AI | 10 | Analog input X48/10 | Maps to drive parameter 1839; needs MCB 114 | °C | Read | |
| AI | 11 | Analog input X49/1 | Maps to drive parameter 1840; needs MCB 115 | V/A/T | Read | |
| AI | 12 | Analog input X49/3 | Maps to drive parameter 1841; needs MCB 115 | V/A/T | Read | |
| AI | 13 | Analog input X49/5 | Maps to drive parameter 1842; needs MCB 115 | V/A/T | Read | |
| AO | 0 | Terminal 42 output bus control | Maps to drive parameter 653 | % | Command | |
| AO | 1 | Pulse out #27 bus control | Maps to drive parameter 593 | % | Command | |
| AO | 2 | Pulse out #29 bus control | Maps to drive parameter 595 | % | Command | |
| AO | 3 | Terminal X30/8 output bus control | Maps to drive parameter 663; needs MCB 101 | % | Command | |
| AO | 4 | Analog output X42/7 | Maps to drive parameter 2643; needs MCB 109 | V | Command | |
| AO | 5 | Analog output X42/9 | Maps to drive parameter 2653; needs MCB 109 | V | Command | |
| AO | 6 | Analog output X42/11 | Maps to drive parameter 2663; needs MCB 109 | V | Command | |
| AO | 7 | Analog output X49/7 | Maps to drive parameter 3644; needs MCB 115 | V | Command | |
| AO | 8 | Analog output X49/9 | Maps to drive parameter 3654; needs MCB 115 | V | Command | |
| AO | 9 | Analog output X49/11 | Maps to drive parameter 3664; needs MCB 115 | V | Command | |
| AO | 10 | Analog output X45/1 | Maps to drive parameter 1678; needs MCB 113 | V | Read | |
| AO | 11 | Analog output X45/3 | Maps to drive parameter 1679; needs MCB 113 | V | Read | |
| AVmin | 0 | Speed act value | Maps to drive parameter 1682 | % | Read | |
| AVmin | 1 | Input reference 1 | Maps to drive parameter 1682 | % | Command | |
| AV | 2 | Input reference 2 | Maps to drive parameter 1682 | % | Command | |
| AV | 3 | Output speed | % | Read | ||
| AV | 4 | PID feedback | % | Read | ||
| AVmin | 5 | Motor current | Maps to drive parameter 1614 | Amps | Read | |
| AVmin | 6 | Power | Maps to drive parameter 1610 | KW | Read | |
| AV | 15 | Motor thermal | Maps to drive parameter 1618 | % | Read | |
| AV | 21 | Operating hours | Maps to drive parameter 1500 | Hours | Read | |
| AV | 22 | Running hours | Maps to drive parameter 1501 | Hours | Read | |
| AV | 23 | kWh counter | Maps to drive parameter 1502 | kWh | Read | |
| AV | 24 | Motor voltage | Maps to drive parameter 1612 | V | Read | |
| AV | 25 | Frequency | Maps to drive parameter 1613 | Hz | Read | |
| AV | 26 | Torque | Maps to drive parameter 1622 | % | Read | |
| AV | 27 | DC link voltage | Maps to drive parameter 1630 | V | Read | |
| AV | 28 | Heatsink temp. | Maps to drive parameter 1634 | °C | Read | |
| AV | 29 | Inverter thermal | Maps to drive parameter 1635 | % | Read | |
| AV | 30 | Setpoint 1 | Maps to drive parameter 2021 | % | Write | |
| AV | 31 | Bus feedback 1 | Maps to drive parameter 894 | % | Write | |
| AV | 58 | Sensorless readout | Maps to drive parameter 1850 | Read | ||
| AV | 59 | PID output | Maps to drive parameter 1658 | % | Read | |
| AV | 60 | PID setpoint | Maps to drive parameter 1659 | Same as feedback unit | Read | |
| AVmin | 61 | Alarm word 1 | Maps to drive parameter 1690 | Read | ||
| AV | 62 | Alarm word 2 | Maps to drive parameter 1691 | Read | ||
| AV | 63 | Alarm word 3 | Maps to drive parameter 1697 | Read | ||
| AV | 65 | External reference | Maps to drive parameter 1650 | Read | ||
| AV | 66 | Warning word 1 | Maps to drive parameter 1692 | Read | ||
| AV | 67 | Warning word 2 | Maps to drive parameter 1693 | Read | ||
| AV | 68 | Warning word 3 | Maps to drive parameter 1698 | Read | ||
| AV | 70 | Feedback [unit] | Maps to drive parameter 1652 | Same as feedback unit | Read | |
| AV | 72 | Flow | Maps to drive parameter 2969 | M2/H | Read | |
| AV | 73 | Cascade % of total capacity | Maps to drive parameter 2792; needs MCO 102 | % | Read | |
| AV | 74 | Ext. status word | Maps to drive parameter 1694 | Read | ||
| AV | 75 | Ext. status word 2 | Maps to drive parameter 1695 | Read | ||
| AV | 96 | CBM Stator [%] | Maps to drive parameter 4590; needs CBM license | % | Read | |
| AV | 97 | CBM Load [%] | Maps to drive parameter 4591; needs CBM license | % | Read | |
| AV | 98 | CBM Sensor 1 [%] | Maps to drive parameter 4592; needs CBM license | % | Read | |
| AV | 99 | CBM Sensor 2 [%] | Maps to drive parameter 4594; needs CBM license | % | Read | |
| AV | 100 | CBM Sensor 3 [%] | Maps to drive parameter 4596; needs CBM license | % | Read | |
| AV | 101 | CBM Sensor 4 [%] | Maps to drive parameter 4598; needs CBM license | % | Read | |
| AV | 102 | Custom object | Maps to drive parameter 877[0] | User defined | Write | |
| AV | 103 | Custom object | Maps to drive parameter 877[1] | User defined | Write | |
| AV | 104 | Custom object | Maps to drive parameter 877[2] | User defined | Write | |
| AV | 105 | Custom object | Maps to drive parameter 877[3] | User defined | Write | |
| AV | 106 | Custom object | Maps to drive parameter 877[4] | User defined | Write | |
| AV | 107 | Custom object | Maps to drive parameter 877[5] | User defined | Write | |
| AV | 108 | Custom object | Maps to drive parameter 877[6] | User defined | Write | |
| AV | 109 | Custom object | Maps to drive parameter 877[7] | User defined | Write | |
| AV | 110 | Custom object | Maps to drive parameter 877[8] | User defined | Write | |
| AV | 111 | Custom object | Maps to drive parameter 877[9] | User defined | Write | |
| AV | 112 | Custom object | Maps to drive parameter 877[10] | User defined | Write | |
| AV | 113 | Custom object | Maps to drive parameter 877[11] | User defined | Write | |
| AV | 114 | Custom object | Maps to drive parameter 877[12] | User defined | Write | |
| AV | 115 | Custom object | Maps to drive parameter 877[13] | User defined | Write | |
| AV | 116 | Custom object | Maps to drive parameter 877[14] | User defined | Write | |
| AV | 117 | Custom object | Maps to drive parameter 877[15] | User defined | Write | |
| AV | 118 | Custom object | Maps to drive parameter 877[16] | User defined | Write | |
| AV | 119 | Custom object | Maps to drive parameter 877[17] | User defined | Write | |
| AV | 120 | Custom object | Maps to drive parameter 877[18] | User defined | Write | |
| AV | 121 | Custom object | Maps to drive parameter 877[19] | User defined | Write | |
| AV | 122 | Custom object | Maps to drive parameter 877[20] | User defined | Write | |
| AV | 123 | Custom object | Maps to drive parameter 877[21] | User defined | Write | |
| AV | 124 | Custom object | Maps to drive parameter 877[22] | User defined | Write | |
| AV | 125 | Custom object | Maps to drive parameter 877[23] | User defined | Write | |
| AV | 126 | Custom object | Maps to drive parameter 877[24] | User defined | Write | |
| AV | 127 | Custom object | Maps to drive parameter 877[25] | User defined | Write | |
| AV | 128 | Custom object | Maps to drive parameter 877[26] | User defined | Write | |
| AV | 129 | Custom object | Maps to drive parameter 877[27] | User defined | Write | |
| AV | 130 | Custom object | Maps to drive parameter 877[28] | User defined | Write | |
| AV | 131 | Custom object | Maps to drive parameter 877[29] | User defined | Write | |
| AV | 132 | Freeze fault log for download | Write | |||
| AV | 133 | Amount of faults | Read | |||
| AV | 134 | Fault index | Write | |||
| AV | 135 | Fault number | Maps to drive parameter 4330/1530 | Read | ||
| AV | 136 | Fault subcode | Maps to drive parameter 4331/1531 | Read | ||
| AV | 137 | Fault time | Maps to drive parameter 4332/1532 | Read | ||
| AV | 138 | Fault date | Maps to drive parameter 4333/1533 | Read | ||
| AV | 139 | Fault setpoint | Maps to drive parameter 4334/1534 | Read | ||
| AV | 140 | Fault feedback | Maps to drive parameter 4335/1535 | Read | ||
| AV | 141 | Fault demand | Maps to drive parameter 4336/1536 | Read | ||
| AV | 142 | Fault speed | Maps to drive parameter 4338/1538 | Read | ||
| AV | 143 | Fault duration | Maps to drive parameter 4339 | Read | ||
| AV | 144 | Fault ext. ref | Maps to drive parameter 4340/4040 | Read | ||
| AV | 145 | Fault frequency | Maps to drive parameter 4341/4041 | Read | ||
| AV | 146 | Fault current | Maps to drive parameter 4342/4042 | Read | ||
| AV | 147 | Fault voltage | Maps to drive parameter 4343/4043 | Read | ||
| AV | 148 | Fault DC link voltage | Maps to drive parameter 4344/4044 | Read | ||
| AV | 149 | Fault control word | Maps to drive parameter 4345/4045 | Read | ||
| AV | 150 | Fault status word | Maps to drive parameter 4346/4046 | Read | ||
| AV | 151 | Fault torque | Maps to drive parameter 4347/4047 | Read | ||
| AV | 152 | Fault CBM value | Maps to drive parameter 4348/4048 | Read | ||
| AV | 153 | Fault CBM threshold | Maps to drive parameter 4349/4049 | Read | ||
| BI | 0 | Digital input term 33 | Maps to drive parameter 1660, bit 0 | Read | On/Off | |
| BI | 1 | Digital input term 32 | Maps to drive parameter 1660, bit 1 | Read | On/Off | |
| BI | 2 | Digital input term 29 | Maps to drive parameter 1660, bit 2 | Read | On/Off | |
| BI | 3 | Digital input term 27 | Maps to drive parameter 1660, bit 3 | Read | On/Off | |
| BI | 4 | Digital input term 19 | Maps to drive parameter 1660, bit 4 | Read | On/Off | |
| BI | 5 | Digital input term 18 | Maps to drive parameter 1660, bit 5 | Read | On/Off | |
| BI | 6 | Digital input term 37 | Maps to drive parameter 1660, bit 6 | Read | On/Off | |
| BI | 7 | Digital input GPIO term X30/4 | Maps to drive parameter 1660, bit 7; needs MCB 101 | Read | On/Off | |
| BI | 8 | Digital input GPIO term X30/3 | Maps to drive parameter 1660, bit 8; needs MCB 101 | Read | On/Off | |
| BI | 9 | Digital input GPIO term X30/2 | Maps to drive parameter 1660, bit 9; needs MCB 101 | Read | On/Off | |
| BI | 10 | Digital input ext. relay card X46/13 | Maps to drive parameter 1660, bit 10; needs MCB 113 | Read | On/Off | |
| BI | 11 | Digital input ext. relay card X46/11 | Maps to drive parameter 1660, bit 11; needs MCB 113 | Read | On/Off | |
| BI | 12 | Digital input ext. relay card X46/09 | Maps to drive parameter 1660, bit 12; needs MCB 113 | Read | On/Off | |
| BI | 13 | Digital input ext. relay card X46/07 | Maps to drive parameter 1660, bit 13; needs MCB 113 | Read | On/Off | |
| BI | 14 | Digital input ext. relay card X46/05 | Maps to drive parameter 1660, bit 14; needs MCB 113 | Read | On/Off | |
| BI | 15 | Digital input ext. relay card X46/03 | Maps to drive parameter 1660, bit 15; needs MCB 113 | Read | On/Off | |
| BI | 16 | Digital input ext. relay card X46/01 | Maps to drive parameter 1660, bit 16; needs MCB 113 | Read | On/Off | |
| BO | 0 | Digital output term 27 | Maps to drive parameter 5-90, bit 0 | Command | On/Off | |
| BO | 1 | Digital output term 29 | Maps to drive parameter 5-90, bit 1 | Command | On/Off | |
| BO | 2 | GPIO output term X30/6 | Maps to drive parameter 5-90, bit 2; needs MCB 101 | Command | On/Off | |
| BO | 3 | GPIO output term X30/7 | Maps to drive parameter 5-90, bit 3; needs MCB 101 | Command | On/Off | |
| BO | 4 | Relay 1 | Maps to drive parameter 5-90, bit 4 | Command | On/Off | |
| BO | 5 | Relay 2 | Maps to drive parameter 5-90, bit 5 | Command | On/Off | |
| BO | 6 | Option B relay 1 output | Maps to drive parameter 5-90, bit 6; needs MCB 105 | Command | On/Off | |
| BO | 7 | Option B relay 2 output | Maps to drive parameter 5-90, bit 7; needs MCB 105 | Command | On/Off | |
| BO | 8 | Option B relay 3 output | Maps to drive parameter 5-90, bit 8; needs MCB 105 | Command | On/Off | |
| BO | 9 | Digital input programmable op. term X49/7 | Maps to drive parameter 5-90, bit 24; needs MCB 115 | Command | On/Off | |
| BO | 10 | Digital input programmable op. term X49/9 | Maps to drive parameter 5-90, bit 25; needs MCB 115 | Command | On/Off | |
| BO | 11 | Digital input programmable op. term X49/11 | Maps to drive parameter 5-90, bit 26; needs MCB 115 | Command | On/Off | |
| BO | 12 | Extended relay card 1 output | Maps to drive parameter 16-71, bit 4; needs MCB 113 | Command | On/Off | |
| BO | 13 | Extended relay card 2 output | Maps to drive parameter 16-71, bit 3; needs MCB 113 | Command | On/Off | |
| BO | 14 | Extended relay card 3 output | Maps to drive parameter 16-71, bit 2; needs MCB 113 | Command | On/Off | |
| BO | 15 | Extended relay card 4 output | Maps to drive parameter 16-71, bit 7; needs MCB 113 | Command | On/Off | |
| BVmin | 1 | RUN/STOP command | Maps to drive parameter CTW=047c + bit 15 | Command | ||
| BV | 2 | REF 1/REF 2 select | Maps to drive parameter Note 1 | Command | ||
| BVmin | 3 | Fault reset command | Maps to drive parameter CTW bit 7 | Write | ||
| BVmin | 4 | RUN/STOP monitor | Maps to drive parameter STW bit 1 | Read | ||
| BVmin | 5 | OK/FAULT monitor | Maps to drive parameter STW bits 3, 6, and 7 | Read | ||
| BVmin | 6 | HAND/AUTO reference | Maps to drive parameter 16-95 bit 1 | Read | ||
| BV | 21 | Warning | Maps to drive parameter STW bit 7 | Read | ||
| BV | 22 | Trip | Maps to drive parameter STW bit 3 | Read | ||
| BV | 23 | Triplock | Maps to drive parameter STW bit 6 | Read | ||
| BV | 24 | Coasting | Maps to drive parameter CTW bit 3 | Command | ||
| BV | 25 | CW/CCW | Maps to drive parameter CTW bit 15 | Command | ||
| BV | 26 | Jog | Maps to drive parameter CTW bit 8 | Command | ||
| BV | 27 | Reset | Maps to drive parameter CTW bit 7 | Command | ||
| BV | 28 | Reset KWh counter | Maps to drive parameter 1506 | Command | ||
| BV | 29 | Reset running hours counter | Maps to drive parameter 1507 | Write | ||
| BV | 30 | Reverse | Maps to drive parameter CTW bit 15 | Write | ||
| BV | 31 | Speed = reference | Maps to drive parameter STW bit 8 | Read | ||
| BV | 32 | Bus control | Maps to drive parameter STW bit 9 | Read | ||
| BV | 33 | Running | Maps to drive parameter STW bit 11 | Read | ||
| BV | 34 | Ramp 1/Ramp 2 | Maps to drive parameter CTW bit 9 | Command | ||
| BV | 35 | ECB test mode | Maps to drive parameter 3110 bit 0; needs MCO 104 | Read | ||
| BV | 36 | ECB drive mode | Maps to drive parameter 3110 bit 1; needs MCO 104 | Read | ||
| BV | 37 | ECB auto. bypass enable | Maps to drive parameter 3110 bit 2; needs MCO 104 | Read | ||
| BV | 38 | ECB bypass mode | Maps to drive parameter 3110 bit 3; needs MCO 104 | Read | ||
| BV | 39 | Deragging status | Maps to drive parameter 1694 bit 23 | Read | ||
| BV | 40 | Pre/post lube | Maps to drive parameter 1699 bit 3 | Read | ||
| BV | 41 | Sleep mode status | Maps to drive parameter 1695 bit 21 | Read | ||
| BV | 42 | Sleep mode command | Maps to drive parameter 592 bit 0 | Write | ||
| BV | 43 | Pipe filling | Maps to drive parameter 1695 bit 23 | Read | ||
| BV | 44 | External interlock | Maps to drive parameter 0592 bit 1 | Read | ||
| BV | 45 | Latched pump derag | Maps to drive parameter 0592 bit 2 | Read | ||
| BV | 46 | Flow confirmation | Maps to drive parameter 0592 bit 3 | Read | ||
| BV | 47 | End of curve | Maps to drive parameter 1691 bit7 || 1693 bit 7 | Read | ||
| BV | 48 | Broken belt | Maps to drive parameter 1691 bit 8 || 1693 bit 8 | Read | ||
| BV | 49 | No flow | Maps to drive parameter 1691 bit 5 || 1693 bit 5 | Read | ||
| BV | 50 | Dry pump | Maps to drive parameter 1691 bit 6 || 1693 bit 6 | Read | ||
| BV | 51 | User defined alerts | Maps to drive parameter 1699 bit 4 | Read | ||
| BV | 52 | Emergency mode (fire mode) active | Maps to drive parameter 1695 bit 25 | Read | ||
| BV | 53 | Emergency mode (fire mode) was active | Maps to drive parameter 1693 bit 3 | Read | ||
| BV | 54 | CBM motor overload warning | Maps to drive parameter 1698 bits 18, 19, 28, 29, 30, or | Read | ||
| BV | 55 | CBM motor overload alarm | Maps to drive parameter 1697 bits 25, 30, or 31; needs CBM | Read | ||
| BV | 56 | CBM sensor warning | Maps to drive parameter 1698 bits 20 to 27; needs CBM license | Read | ||
| BV | 57 | CBM sensor alarm | Maps to drive parameter 1697 bits 26 to 29; needs CBM license | Read | ||
| MV | 0 | Smart logic controller state | Maps to drive parameter 1638 | Read | ||
| MV | 1 | Active setup | Maps to drive parameter CTW bit 13 and 14 | Command | ||
| MV | 3 | Configuration mode | Maps to drive parameter 100 | Write | ||
| MV | 4 | Pressure sensor 1 cmp states | Maps to drive parameter 3130 | Read | ||
| MV | 5 | Pressure sensor 2 cmp states | Maps to drive parameter 3130 | Read | ||
| MV | 6 | Pressure sensor 3 cmp states | Maps to drive parameter 3130 | Read | ||
| MV | 7 | Pressure sensor 4 cmp states | Maps to drive parameter 3130 | Read | ||
| MV | 8 | CBM stator winding | Maps to drive parameter 45-01 [0]; needs CBM license | Read | ||
| MV | 9 | CBM load envelope | Maps to drive parameter 45-01 [1]; needs CBM license | Read | ||
| MV | 10 | CBM sensor 1 | Maps to drive parameter 45-01 [2]; needs CBM license | Read | ||
| MV | 11 | CBM sensor 2 | Maps to drive parameter 45-01 [3]; needs CBM license | Read | ||
| MV | 12 | CBM sensor 3 | Maps to drive parameter 45-01 [4]; needs CBM license | Read | ||
| MV | 13 | CBM sensor 4 | Maps to drive parameter 45-01 [5]; needs CBM license | Read | ||
| NC | 0 | Warning notifier | Provided by the MCA 125 option itself | Write | ||
| NC | 1 | Trip notifier | Provided by the MCA 125 option itself | Write | ||
| NC | 3 | Triplock notifier | Provided by the MCA 125 option itself | Write | ||
| NC | 100 | NC 100 | Provided by the MCA 125 option itself | Write | ||
| NC | 200 | NC 200 | Provided by the MCA 125 option itself | Write | ||
| NC | 300 | NC 300 | Provided by the MCA 125 option itself | Write | ||
| NC | 400 | NC 400 | Provided by the MCA 125 option itself | Write | ||
| TL | 0 | Trend log 0 | Write | |||
| TL | 1 | Trend log 1 | Write | |||
| TL | 2 | Trend log 2 | Write | |||
| TL | 3 | Trend log 3 | Write | |||
| TL | 4 | Trend log 4 | Write | |||
| TL | 5 | Trend log 5 | Write | |||
| TL | 6 | Trend log 6 | Write | |||
| LO | 0 | Drive close loop | Maps to drive parameter 2093, 2094, 2095 | Write | ||
| Other | 0 | Event enrollment 0 | Provided by the MCA 125 option itself | Write | ||
| Other | 1 | Event enrollment 1 | Provided by the MCA 125 option itself | Write | ||
| Other | 2 | Event enrollment 2 | Provided by the MCA 125 option itself | Write | ||
| Other | 3 | Event enrollment 3 | Provided by the MCA 125 option itself | Write | ||
| Other | 4 | Event enrollment 4 | Provided by the MCA 125 option itself | Write | ||
| Other | 5 | Event enrollment 5 | Provided by the MCA 125 option itself | Write | ||
| Other | 6 | Event enrollment 6 | Provided by the MCA 125 option itself | Write | ||
| Other | 7 | Event enrollment 7 | Provided by the MCA 125 option itself | Write | ||
| Other | 8 | Event enrollment 8 | Provided by the MCA 125 option itself | Write | ||
| Other | 9 | Event enrollment 9 | Provided by the MCA 125 option itself | Write | ||
| Other | 10 | Event enrollment 10 | Provided by the MCA 125 option itself | Write | ||
| Other | 11 | Event enrollment 11 | Provided by the MCA 125 option itself | Write | ||
| Other | 12 | Event enrollment 12 | Provided by the MCA 125 option itself | Write | ||
| Other | 13 | Event enrollment 13 | Provided by the MCA 125 option itself | Write | ||
| CSV | 1 | Pump status | Provided by the MCA 125 option itself | Read | ||
| SCH | 0 | Drive schedule 0 | Provided by the MCA 125 option itself | Write | ||
| SCH | 1 | Drive schedule 1 | Provided by the MCA 125 option itself | Write | ||
| SCH | 2 | Drive schedule 2 | Provided by the MCA 125 option itself | Write | ||
| SCH | 3 | Drive schedule 3 | Provided by the MCA 125 option itself | Write | ||
| SCH | 4 | Drive schedule 4 | Provided by the MCA 125 option itself | Write | ||
| SCH | 5 | Drive schedule 5 | Provided by the MCA 125 option itself | Write | ||
| CAL | 0 | Exception calendar | Provided by the MCA 125 option itself | Write | ||
| CAL | 1 | Exception calendar | Provided by the MCA 125 option itself | Write | ||
| CAL | 2 | Exception calendar | Provided by the MCA 125 option itself | Write | ||
| CAL | 3 | Exception calendar | Provided by the MCA 125 option itself | Write | ||
| CAL | 4 | Exception calendar | Provided by the MCA 125 option itself | Write | ||
| CAL | 5 | Exception calendar | Provided by the MCA 125 option itself | Write | ||
| Other | 0 | Event log | Provided by the MCA 125 option itself | Read |
No points match these filters.
Integration notes
- Device instance comes from parameter 8-70 (default 1) unless the MCA 125 DIP switches set it.
- Points marked 'needs MCB/MCO ...' only work when that option is installed.
- CBM (condition-based monitoring) objects need a CBM license in the drive.
- AV:102-AV:131 are custom objects; their names and units follow the drive parameters mapped in 8-77.
- This file lists objects the guide marks for FC 202 or for both drive series; FC 102-only objects (pressure sensor AI/AV set) are left out.
- MV:4-MV:7 (pressure sensor compare states) carry no drive-series mark in the guide, so they are kept, but their related sensor objects are FC 102-only.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VLT AQUA Drive FC 202 with BACnet/IP MCA 125 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Danfoss VLT AQUA Drive FC 202 with BACnet/IP MCA 125
How many BACnet points does the Danfoss VLT AQUA Drive FC 202 with BACnet/IP MCA 125 have?
This list has 250 BACnet objects: 14 analog inputs, 12 analog outputs, 92 analog values, 17 binary inputs, 16 binary outputs, 43 binary values, 6 calendars, 1 loop, 7 notification classs, 6 schedules, 13 multi-state values, 7 trend logs, 1 characterstring value, 15 others. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Danfoss VLT AQUA Drive FC 202 with BACnet/IP MCA 125 BACnet points are writable?
117 of the 250 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Danfoss VLT AQUA Drive FC 202 with BACnet/IP MCA 125 BACnet documentation?
The source is VLT BACnet/IP MCA 125 Programming Guide (VLT HVAC Drive FC 102, VLT AQUA Drive FC 202) (AU361182716349en-000201 (130R0673)), revision 2025-12, published free by Danfoss at https://assets.danfoss.com/documents/562086/AU361182716349en-000201.pdf.
What are the minimum BACnet points to integrate the Danfoss VLT AQUA Drive FC 202 with BACnet/IP MCA 125?
Start with BV 1 RUN/STOP command (Start/stop from the BMS); AV 1 Input reference 1 (Speed reference in %; writes also restart the 8-03 timeout); BV 3 Fault reset command (Reset a tripped drive); BV 4 RUN/STOP monitor (Running status); BV 6 HAND/AUTO reference (Shows if the drive is in Hand); AV 0 Speed act value (Actual speed feedback); AV 5 Motor current (Motor amps); AV 6 Power (Drive power in kW); BV 5 OK/FAULT monitor (Any active drive fault); AV 61 Alarm word 1 (Alarm detail for troubleshooting).
Does the Danfoss VLT AQUA Drive FC 202 with BACnet/IP MCA 125 need a BACnet heartbeat or have a communication timeout?
Parameter 8-03 Control Timeout Time (0.5-18000 s, factory 60.0 s) restarts on every write to any AO, AV 1/2/31, BV 1/2/25/26/27 or MSV 1. If the BMS stops writing for longer than that, the drive raises alarm 17 Ctrl.word TO and does whatever 8-04 Control Timeout Function selects (factory Off; options include stop and trip or max speed). 8-05 End-of-Timeout Function (factory Resume setup) sets what happens when writes resume. Danfoss suggests about 3 writes per timeout window.
Can the BMS supply sensor values to the Danfoss VLT AQUA Drive FC 202 with BACnet/IP MCA 125?
The BMS can write the PID feedback to AV:31 Bus feedback 1 (parameter 8-94) and the PID setpoint to AV:30 Setpoint 1 (parameter 20-21). Writing AV:31 also restarts the control timeout.
How do I check these points on the real VLT AQUA Drive FC 202 with BACnet/IP MCA 125?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Danfoss BACnet points lists
- Thermal energy meter (BACnet MS/TP plug-in module)
Danfoss SonoMeter 40 BACnet MS/TP module
Danfoss SonoMeter 40 ultrasonic heat/cooling energy meters fitted with the BACnet MS/TP module.
Also known as: SonoMeter 40, SonoMeter, Sonometer 40 BACnet, Danfoss BACnet MS/TP base module, AQ404134831215 - Variable frequency drive (HVAC)
Danfoss VLT HVAC Drive FC 102 with BACnet/IP MCA 125
Danfoss VLT HVAC Drive FC 102 fitted with the MCA 125 BACnet/IP option card.
Also known as: FC 102, FC102, VLT HVAC Drive, MCA 125, MCA125, 134B1586, VLT BACnet/IP
Source: VLT BACnet/IP MCA 125 Programming Guide (VLT HVAC Drive FC 102, VLT AQUA Drive FC 202) · AU361182716349en-000201 (130R0673) · rev. 2025-12. Object names, instances and units are reproduced as published; descriptions are our own.