Easy BACnet
  1. Home
  2. BACnet points lists
  3. Danfoss
  4. iC7 Series drives with BACnet/IP (OS7BI) or BACnet MS/TP (OS7BN)

Variable frequency drive · BACnet points list

Danfoss iC7 Series drives with BACnet/IP (OS7BI) or BACnet MS/TP (OS7BN) BACnet points list

Updated 7 November 2026

Short answer

Danfoss iC7 drives talk BACnet/IP over the X1/X2 Ethernet ports with the OS7BI option, or BACnet MS/TP with the OS7BN option. Both operating guides print the same fixed object list: I/O values for the integrated and general-purpose I/O, run/stop and speed reference, drive measurements and hour/energy counters, PID and multi-zone setpoints, fixed-speed pump (MPC) data, and the fieldbus control and status word bits.

This page lists 141 BACnet objects for the Danfoss iC7 Series drives with BACnet/IP (OS7BI) or BACnet MS/TP (OS7BN) — 54 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Danfoss’s own free documentation, linked below.

Manufacturer
Danfoss
Model
iC7 Series drives with BACnet/IP (OS7BI) or BACnet MS/TP (OS7BN)
Equipment
Variable frequency drive
Equipment type
VFDs & pumps
BACnet objects
141 (54 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
1
Also known as
iC7-Automation, iC7-Hybrid, OS7BI, OS7BN, iC7 BACnet/IP, iC7 BACnet MSTP, 136R0460, 136R0437
Source document
iC7 Series BACnet/IP Operating Guide (BACnet/IP OS7BI) · AQ548636302177en-010101 (136R0460) · rev. 2026.04
Download CSV 141 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Danfoss’s current documentation and the live device before use. Not official Danfoss information. Terms of use.

BMS integration notes: Danfoss iC7 Series drives with BACnet/IP (OS7BI) or BACnet MS/TP (OS7BN)

Integration in brief

Set Control Place Selection to Advanced Control/Fieldbus Control and the fieldbus reference and start sources to Fieldbus (parameter group 5.5), then write BV 1 RUN/STOP Command and AV 1 Fieldbus Speed Reference 1. Read Running (BV 33), Motor Speed (AV 3), current and power, and the Trip/Warning flags with Fault Status Word 1 for alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1RUN/STOP CommandRun/stop command (1 = run)Write
AV 1Fieldbus Speed Reference 1 (Input Reference 1)Speed reference, %Write
AV 30Multi Zone Reference 1 (Setpoint 1)Setpoint 1 when the drive runs its own PIDWrite
BV 33RunningRunning statusRead
AV 3Motor Speed (Motor Actual Speed)Actual motor speed, %Write
AV 5Motor CurrentMotor current, ARead
AV 6Output PowerOutput power, kWRead
BV 22TripDrive trippedRead
BV 21WarningActive warningRead
AV 61Fault Status Word 1Fault code wordRead

Enable & remote start

Parameter group 5.5 Control Places: Control Place Selection (5.5.2.1, also AV 49) must be Advanced Control or Fieldbus Control, with Fieldbus Speed Reference Source and the Advanced Start/Stop/Coast inputs set to Fieldbus.

Heartbeat & communication loss

BACnet Connection Timeout (10.3.7.2.14, default 60 s, 10-18000 s) watches the fieldbus data. The response (10.3.7.2.16) can be set to info, warning, warning with a switch to the alternative control place (10.3.7.2.15), or fault (ramp then coast, or coast).

Network setup

Watch out for

Danfoss iC7 Series drives with BACnet/IP (OS7BI) or BACnet MS/TP (OS7BN) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

141 of 141 shown
Type
Access
Show
Danfoss iC7 Series drives with BACnet/IP (OS7BI) or BACnet MS/TP (OS7BN) BACnet Points List
DescriptionStates
AI20Analog Input (T33)Parameter 1611 (9.3.4 [101])%Read
AI21Analog Input (T34)Parameter 1612 (9.3.5 [101])%Read
AI22Analog Input (T2)Parameter 1620 (9.3.3 [201])%Read
AI23Analog Input (T3)Parameter 1621 (9.3.4 [201])%Read
AI24Temperature Input (T34)Parameter 1616 (9.3.6 [101])°CRead
AI25Temperature Input 1 (T2)Parameter 4966 (9.3.6 [201])°CRead
AI26Temperature Input 2 (T3)Parameter 4967 (9.3.7 [201])°CRead
AO0Analog Output 1 (T31)Parameter 1613 (9.3.3 [101])%Write
AO3Analog Output (T4)Parameter 1622 (9.3.5 [201])%Write
AVmin1Fieldbus Speed Reference 1 (Input Reference 1)Parameter 1611 (9.3.4 [101])%Write
AVmin3Motor Speed (Motor Actual Speed)Parameter 1612 (9.3.5 [101])%Write
AVmin5Motor CurrentParameter 1620 (9.3.3 [201])ARead
AVmin6Output PowerParameter 1621 (9.3.4 [201])kWRead
AV7Fieldbus Process ReferenceParameter 1616 (9.3.6 [101])%Read
AV15Motor Thermal Overload (ETR)Parameter 2951 (4.1.16)%Read
AV16Line-To-Line Voltage (RMS)Parameter 9040 (1.1.2)VRead
AV17L1-L2 Line Voltage (RMS)Parameter 9048 (1.1.3)VRead
AV18L2-L3 Line Voltage (RMS)Parameter 9049 (1.1.4)VRead
AV19L3-L1 Line Voltage (RMS)Parameter 9050 (1.1.5)VRead
AV20Control Unit On TimeParameter 2000 (6.5.1)hRead
AV21Power Unit On TimeParameter 2001 (6.5.2)hRead
AV22Active Running HoursParameter 2009 (6.5.9)hRead
AV23Energy ConsumptionParameter 2002 (6.5.3)kWhRead
AV24Motor VoltageParameter 9005 (4.1.6)VRead
AV25Output FrequencyParameter 9015 (5.8.1.3)HzRead
AV26TorqueParameter 1708 (4.1.12)%Read
AV27DC Link VoltageParameter 9044 (2.1.3)VRead
AV28Heat Sink TemperatureParameter 2950 (2.1.15)°CRead
AVmin30Multi Zone Reference 1 (Setpoint 1)Parameter 6383 (5.10.8.1)%Write
AV32Feedback 1Parameter 6080 (5.10.1.6)%Read
AV35Multi Zone Reference 2 (Setpoint 2)Parameter 6384 (5.10.8.2)%Write
AV37Feedback 2Parameter 6085 (5.10.1.7)%Read
AV40Multi Zone Reference 3 (Setpoint 3)Parameter 6285 (5.10.8.3)%Write
AV42Feedback 3Parameter 6104 (5.10.1.8)%Read
AV47Control Unit TemperatureParameter 2952 (6.1.1.3)°CRead
AV49Control Place SelectionParameter 114 (5.5.2.1)Write
AV51Occurrence NumberParameter 1610 (6.1.1.1)Read
AV52PID Start SpeedParameter 6056 (5.10.3.24)HzWrite
AV53On Reference BandwidthParameter 6050 (5.10.2.1)%Write
AV54PID Proportional GainParameter 6065 (5.10.5.1)Write
AV55PID Integral TimeParameter 6058 (5.10.5.2)sWrite
AV56PID Derivative TimeParameter 6068 (5.10.5.5)sWrite
AV57PID Derivative GainParameter 6069 (5.10.5.6)Write
AV59Process Controller output (PID Output)Parameter 6075 (5.10.1.2)%Write
AV60ReservedParameter 6092 (5.10.1.3)Read
AVmin61Fault Status Word 1Parameter 6203 (5.1.5)Read
AV66Warning WordParameter 6205 (5.1.8)Read
AV70FeedbackParameter 6090 (5.10.1.4)%Read
AV71Converted Signal 1Parameter 6700m³/hRead
AV72Converted SignalParameter 6701m³/hWrite
AV77Converted Signal 3Parameter 6702m³/hRead
AV153MPC StatusParameter 5367 (5.31.2.1.1)Read
AV154Number of Fixed-Speed Pumps RunningParameter 5331 (5.31.2.1.2)Read
AV155Fixed-Speed Pump 1 StatusParameter 5340 (5.31.2.1.3)Read
AV156Fixed-Speed Pump 2 StatusParameter 5341 (5.31.2.1.4)Read
AV157Fixed-Speed Pump 3 StatusParameter 5342 (5.31.2.1.5)Read
AV158Fixed-Speed Pump 4 StatusParameter 5343 (5.31.2.1.6)Read
AV159Fixed-Speed Pump 5 StatusParameter 5344 (5.31.2.1.7)Read
AV163Fixed-Speed Pump 1 Running HoursParameter 5350 (5.31.2.1.8)hWrite
AV164Fixed-Speed Pump 2 Running HoursParameter 5351 (5.31.2.1.9)hWrite
AV165Fixed-Speed Pump 3 Running HoursParameter 5352 (5.31.2.1.10)hWrite
AV166Fixed-Speed Pump 4 Running HoursParameter 5353 (5.31.2.1.11)hWrite
AV167Fixed-Speed Pump 5 Running HoursParameter 5354 (5.31.2.1.12)hWrite
AV171Fixed-Speed Pump 1 Number of StartsParameter 5357 (5.31.2.1.13)Read
AV172Fixed-Speed Pump 2 Number of StartsParameter 5358 (5.31.2.1.14)Read
AV173Fixed-Speed Pump 3 Number of StartsParameter 5359 (5.31.2.1.15)Read
AV174Fixed-Speed Pump 4 Number of StartsParameter 5360 (5.31.2.1.16)Read
AV175Fixed-Speed Pump 5 Number of StartsParameter 5361 (5.31.2.1.17)Read
BI0Digital input Term 13Parameter 1614 (9.3.1 [101])Read
BI1Digital input Term 14Parameter 1614 (9.3.1 [101])Read
BI2Digital input Term 15Parameter 1614 (9.3.1 [101])Read
BI3Digital input Term 16Parameter 1614 (9.3.1 [101])Read
BI4Digital input Term 17Parameter 1614 (9.3.1 [101])Read
BI5Digital input Term 18Parameter 1614 (9.3.1 [101])Read
BI7Digital input 1 (T11)Parameter 1614 (9.3.1 [201])Read
BI8Digital input 1 (T12)Parameter 1614 (9.3.1 [201])Read
BI9Digital input 1 (T13)Parameter 1614 (9.3.1 [201])Read
BO0Digital Output Term 15Parameter 1615 (9.3.2 [101])Write
BO1Digital Output Term 15Parameter 1615 (9.3.2 [101])Write
BO2Digital Output 1 (T7)Parameter 1615 (9.3.2 [201])Write
BO3Digital Output 2 (T8)Parameter 1615 (9.3.2 [201])Write
BO4Relay Output 1 (T5)Parameter 1615 (9.3.2 [101])Write
BO5Relay Output 2 (T6)Parameter 1615 (9.3.2 [101])Write
BO6Relay Output 1 X101Parameter 4909 (9.3.1 [201])Write
BO7Relay Output 2 X102Parameter 4909 (9.3.1 [201])Write
BO8Relay Output 3 X103Parameter 4909 (9.3.1 [201])Write
BVmin1RUN/STOP CommandParameter 1335 (5.27.1.42)Write
BV3Fault ResetParameter 1307 (5.27.1.50)Read
BV5READY/FAULT MonitorParameter 1307 (5.27.1.50)Read
BV6LOCAL/REMOTEParameter 1307 (5.27.1.50)Read
BVmin21WarningParameter 1307 (5.27.1.50)Read
BVmin22TripParameter 1307 (5.27.1.50)Read
BV24CoastingParameter 1335 (5.27.1.42)Write
BV25Reversing (CW/CCW)Parameter 1335 (5.27.1.42)Write
BV31Speed = referenceParameter 1307 (5.27.1.50)Read
BV32Bus controlParameter 1307 (5.27.1.50)Read
BVmin33RunningParameter 1307 (5.27.1.50)Read
BV34Ramp 1/Ramp 2Parameter 1335 (5.27.1.42)Write
BV41Sleep Mode StatusRead
BV44Interlock StatusRead
BV47End of CurveRead
BV49No FlowRead
BV50Dry RunRead
BV62Fieldbus Status word 1, bit 14Parameter 1307 (5.27.1.50)Read
BV63Fieldbus Status word 1, bit 15Parameter 1307 (5.27.1.50)Read
BV64Fieldbus Status word 2, bit 0Parameter 1344 (5.27.1.90)Read
BV65Fieldbus Status word 2, bit 1Parameter 1344 (5.27.1.90)Read
BV66Fieldbus Status word 2, bit 2Parameter 1344 (5.27.1.90)Read
BV67Fieldbus Status word 2, bit 3Parameter 1344 (5.27.1.90)Read
BV68Fieldbus Status word 2, bit 4Parameter 1344 (5.27.1.90)Read
BV69Fieldbus Status word 2, bit 5Parameter 1344 (5.27.1.90)Read
BV70Fieldbus Status word 2, bit 6Parameter 1344 (5.27.1.90)Read
BV71Fieldbus Status word 2, bit 7Parameter 1344 (5.27.1.90)Read
BV72Fieldbus Status word 2, bit 8Parameter 1344 (5.27.1.90)Read
BV73Fieldbus Status word 2, bit 9Parameter 1344 (5.27.1.90)Read
BV74Fieldbus Status word 2, bit 10Parameter 1344 (5.27.1.90)Read
BV75Fieldbus Status word 2, bit 11Parameter 1344 (5.27.1.90)Read
BV76Fieldbus Status word 2, bit 12Parameter 1344 (5.27.1.90)Read
BV77Fieldbus Status word 2, bit 13Parameter 1344 (5.27.1.90)Read
BV78Fieldbus Status word 2, bit 14Parameter 1344 (5.27.1.90)Read
BV79Fieldbus Status word 2, bit 15Parameter 1344 (5.27.1.90)Read
BV80Fieldbus Control Word 1, bit 12Parameter 1335 (5.27.1.42)Write
BV81Fieldbus Control Word 1, bit 13Parameter 1335 (5.27.1.42)Write
BV82Fieldbus Control Word 1, bit 14Parameter 1335 (5.27.1.42)Write
BV83Fieldbus Control Word 1, bit 15Parameter 1335 (5.27.1.42)Write
BV84Fieldbus Control Word 2, bit 0Parameter 1347 (5.27.1.89)Write
BV85Fieldbus Control Word 2, bit 1Parameter 1347 (5.27.1.89)Write
BV86Fieldbus Control Word 2, bit 2Parameter 1347 (5.27.1.89)Write
BV87Fieldbus Control Word 2, bit 3Parameter 1347 (5.27.1.89)Write
BV88Fieldbus Control Word 2, bit 4Parameter 1347 (5.27.1.89)Write
BV89Fieldbus Control Word 2, bit 5Parameter 1347 (5.27.1.89)Write
BV90Fieldbus Control Word 2, bit 6Parameter 1347 (5.27.1.89)Write
BV91Fieldbus Control Word 2, bit 7Parameter 1347 (5.27.1.89)Write
BV92Fieldbus Control Word 2, bit 8Parameter 1347 (5.27.1.89)Write
BV93Fieldbus Control Word 2, bit 9Parameter 1347 (5.27.1.89)Write
BV94Fieldbus Control Word 2, bit 10Parameter 1347 (5.27.1.89)Write
BV95Fieldbus Control Word 2, bit 11Parameter 1347 (5.27.1.89)Write
BV96Fieldbus Control Word 2, bit 12Parameter 1347 (5.27.1.89)Write
BV97Fieldbus Control Word 2, bit 13Parameter 1347 (5.27.1.89)Write
BV98Fieldbus Control Word 2, bit 14Parameter 1347 (5.27.1.89)Write
BV99Fieldbus Control Word 2, bit 15Parameter 1347 (5.27.1.89)Write
Object ID lookup: Danfoss iC7 Series drives with BACnet/IP or BACnet MS/TP point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the iC7 Series drives with BACnet/IP (OS7BI) or BACnet MS/TP (OS7BN) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Danfoss iC7 Series drives with BACnet/IP (OS7BI) or BACnet MS/TP (OS7BN)

How many BACnet points does the Danfoss iC7 Series drives with BACnet/IP (OS7BI) or BACnet MS/TP (OS7BN) have?

This list has 141 BACnet objects: 7 analog inputs, 2 analog outputs, 59 analog values, 9 binary inputs, 9 binary outputs, 55 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Danfoss iC7 Series drives with BACnet/IP (OS7BI) or BACnet MS/TP (OS7BN) BACnet points are writable?

54 of the 141 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Danfoss iC7 Series drives with BACnet/IP (OS7BI) or BACnet MS/TP (OS7BN) BACnet documentation?

The source is iC7 Series BACnet/IP Operating Guide (BACnet/IP OS7BI) (AQ548636302177en-010101 (136R0460)), revision 2026.04, published free by Danfoss at https://assets.danfoss.com/documents/585354/AQ548636302177en-010101.pdf.

What are the minimum BACnet points to integrate the Danfoss iC7 Series drives with BACnet/IP (OS7BI) or BACnet MS/TP (OS7BN)?

Start with BV 1 RUN/STOP Command (Run/stop command (1 = run)); AV 1 Fieldbus Speed Reference 1 (Input Reference 1) (Speed reference, %); AV 30 Multi Zone Reference 1 (Setpoint 1) (Setpoint 1 when the drive runs its own PID); BV 33 Running (Running status); AV 3 Motor Speed (Motor Actual Speed) (Actual motor speed, %); AV 5 Motor Current (Motor current, A); AV 6 Output Power (Output power, kW); BV 22 Trip (Drive tripped); BV 21 Warning (Active warning); AV 61 Fault Status Word 1 (Fault code word).

How do I enable BMS control of the Danfoss iC7 Series drives with BACnet/IP (OS7BI) or BACnet MS/TP (OS7BN)?

Parameter group 5.5 Control Places: Control Place Selection (5.5.2.1, also AV 49) must be Advanced Control or Fieldbus Control, with Fieldbus Speed Reference Source and the Advanced Start/Stop/Coast inputs set to Fieldbus.

Does the Danfoss iC7 Series drives with BACnet/IP (OS7BI) or BACnet MS/TP (OS7BN) need a BACnet heartbeat or have a communication timeout?

BACnet Connection Timeout (10.3.7.2.14, default 60 s, 10-18000 s) watches the fieldbus data. The response (10.3.7.2.16) can be set to info, warning, warning with a switch to the alternative control place (10.3.7.2.15), or fault (ramp then coast, or coast).

How do I check these points on the real iC7 Series drives with BACnet/IP (OS7BI) or BACnet MS/TP (OS7BN)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Danfoss BACnet points lists

Source: iC7 Series BACnet/IP Operating Guide (BACnet/IP OS7BI) · AQ548636302177en-010101 (136R0460) · rev. 2026.04. Object names, instances and units are reproduced as published; descriptions are our own.