Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP) BACnet points list
Updated 6 November 2026
Vacon 100 family drives (now Danfoss) have BACnet MS/TP on the RS-485 terminals and BACnet IP on the Ethernet port, both built in. The object list is Binary Values for drive status, run/stop, direction, reset, stop modes and fieldbus control-word bits, and Analog Values for monitors, the speed reference (% of nominal), limits, ramps, process data, AnyParam access and the fixed control/status words.
This page lists 71 BACnet objects for the Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP) — 30 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Danfoss’s own free documentation, linked below.
- Manufacturer
- Danfoss
- Model
- Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP)
- Equipment
- Variable frequency drive (HVAC)
- Equipment type
- VFDs & pumps
- BACnet objects
- 71 (30 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 0 = use the number read from the drive (shown in the monitor menu)
- Also known as
- Vacon 100, Vacon 100 FLOW, Vacon 100 HVAC, Vacon 100 BACnet, DPD00091, AN361179477697
Reference only, provided as-is: verify against Danfoss’s current documentation and the live device before use. Not official Danfoss information. Terms of use.
BMS integration notes: Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP)
Select the BACnet protocol on RS-485 (M5.8) or Ethernet (M5.9), set the MS/TP MAC address, baud rate and instance (P5.8.3.1) or the IP settings and P5.9.3.1.3 Protocol in use = 1, and make Fieldbus the remote control place (P3.2.1). Then command BV 15 run/stop (or AV 36 control word) and AV 24 speed reference, and read BV 1, AV 1 and the fault points.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 15 | Run/Stop CMD | Run/stop command (1 = run) | Command |
| AV 24 | Speed Reference | Speed reference, % of nominal speed | Command |
| BV 17 | Reset Fault | Resets the active fault | Command |
| BV 1 | Run/Stop State | Running status | Read |
| AV 1 | Output Frequency | Output frequency, Hz | Read |
| AV 5 | Motor Current | Motor current, A | Read |
| AV 3 | Load (power) | Motor shaft power, % | Read |
| BV 3 | Fault State | Any active drive fault | Read |
| AV 23 | Active Fault Code | Which fault is active | Read |
Enable & remote start
Make Fieldbus the remote control place (Main Menu > Parameters > Start/Stop Setup > P3.2.1 Rem. Ctrl. Place) and choose the fieldbus as the reference source (M3.3). The manual's quick test writes AV 36 control word 0 then 1 to start, AV 24 = 50 for 50 % speed, and 0 to stop.
Heartbeat & communication loss
MS/TP: P5.8.3.1.5 Communication time-out (0-65535 s, default 10, 0 = off) raises a communication error if the drive is sole master for that long. BACnet IP: P5.9.3.1.2 Communication time-out (default 0 = not used) is the longest allowed gap between UDP packets from the master; losing the Ethernet link faults at once even with 0.
Network setup
- MS/TP: P5.8.3.1.1 baud rate (1 = 9600 default, 2 = 19200, 3 = 38400, 4 = 76800), P5.8.3.1.2 autobauding, P5.8.3.1.3 MAC address 1-127 (default 1).
- P5.8.3.1.4 / P5.9.3.1.1 Instance number: 0 (default) uses a number read from the drive, shown in the monitor menu; any other value is used as is.
- BACnet IP: P5.9.1.1 IP address mode (default 1 = DHCP with AutoIP; 0 = fixed, default 192.168.0.10); P5.9.3.1.3 Protocol in use = 1 turns BACnet IP on.
- BACnet IP: P5.9.3.1.4-6 set a BBMD IP, port and time to live for foreign-device registration.
- Terminate the first and last drive on the MS/TP segment.
- PICS lists DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM-B, DM-DDB-B and DM-DOB-B; the drive is a B-ASC.
Watch out for
- BV 15 run/stop only works when the fieldbus is the active control place.
- Process data objects depend on the drive application; check the application manual before mapping them.
- BV 18-22 stop modes and BV 23/24 BusCtrl/BusRef are commandable control-word bits; leave them alone unless needed.
Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BV | 0 | Ready State | Indicates whether the drive is ready or not | Read | Inactive/Active: Not Ready/Ready | |
| BVmin | 1 | Run/Stop State | Indicates whether the drive is running or stopped | Read | Inactive/Active: Stop/Run | |
| BV | 2 | Fwd/Rev State | Indicates the rotation direction of the motor | Read | Inactive/Active: Fwd/Rev | |
| BVmin | 3 | Fault State | Indicates if a fault is active | Read | Inactive/Active: OK/Fault | |
| BV | 4 | Alarm State | Indicates if an alarm is active | Read | Inactive/Active: OK/Alarm | |
| BV | 5 | At Setpoint | Ref. Frequency reached | Read | Inactive/Active: False/True | |
| BV | 6 | At Zero Speed | Motor Running at zero speed | Read | Inactive/Active: False/True | |
| BV | 7 | fb_ProcessdataOut_01 Bit_0 | ProcessDataOut1 bit 0 | Read | Inactive/Active: 0/1 | |
| BV | 8 | fb_ProcessdataOut_01 Bit_1 | ProcessDataOut1 bit 1 | Read | Inactive/Active: 0/1 | |
| BV | 9 | fb_ProcessdataOut_01 Bit_2 | ProcessDataOut1 bit 2 | Read | Inactive/Active: 0/1 | |
| BV | 10 | fb_ProcessdataOut_01 Bit_3 | ProcessDataOut1 bit 3 | Read | Inactive/Active: 0/1 | |
| BV | 11 | fb_ProcessdataOut_01 Bit_4 | ProcessDataOut1 bit 4 | Read | Inactive/Active: 0/1 | |
| BV | 12 | fb_ProcessdataOut_01 Bit_5 | ProcessDataOut1 bit 5 | Read | Inactive/Active: 0/1 | |
| BV | 13 | fb_ProcessdataOut_01 Bit_6 | ProcessDataOut1 bit 6 | Read | Inactive/Active: 0/1 | |
| BV | 14 | fb_ProcessdataOut_01 Bit_7 | ProcessDataOut1 bit 7 | Read | Inactive/Active: 0/1 | |
| BVmin | 15 | Run/Stop CMD | Command to start drive (FB control is active) | Command | Inactive/Active: Stop/Run | |
| BV | 16 | Fwd/Rev CMD | Command to run forward/ reverse | Command | Inactive/Active: Fwd/Rev | |
| BVmin | 17 | Reset Fault | Command to reset Active Fault from drive | Command | Inactive/Active: 0/Reset | |
| BV | 18 | Stop By Coast | Stop Drive by coast | Command | Inactive/Active: 0/1 | |
| BV | 19 | Stop By Ramp | Stop Drive by ramp | Command | Inactive/Active: 0/1 | |
| BV | 20 | Quick Stop | Quick Stop | Command | Inactive/Active: 0/1 | |
| BV | 21 | Zero Ramp | Stop by zero ramp | Command | Inactive/Active: 0/1 | |
| BV | 22 | Hold Ramp | Hold ramp | Command | Inactive/Active: 0/1 | |
| BV | 23 | BusCtrl | Activate Bus control | Command | Inactive/Active: 0/1 | |
| BV | 24 | BusRef | Activate Bus reference | Command | Inactive/Active: 0/1 | |
| BV | 25 | fb_control_word Bit_10 | fb_control_word bit 10 | Command | Inactive/Active: 0/1 | |
| BV | 26 | fb_control_word Bit_11 | fb_control_word bit 11 | Command | Inactive/Active: 0/1 | |
| BV | 27 | fb_control_word Bit_12 | fb_control_word bit 12 | Command | Inactive/Active: 0/1 | |
| BV | 28 | fb_control_word Bit_13 | fb_control_word bit 13 | Command | Inactive/Active: 0/1 | |
| BV | 29 | fb_control_word Bit_14 | fb_control_word bit 14 | Command | Inactive/Active: 0/1 | |
| BV | 30 | fb_control_word Bit_15 | fb_control_word bit 15 | Command | Inactive/Active: 0/1 | |
| AV | 0 | Frequency Setpoint | Frequency Setpoint | Hz | Read | |
| AVmin | 1 | Output Frequency | Output Frequency | Hz | Read | |
| AV | 2 | Motor Speed | Motor Speed | rpm | Read | |
| AVmin | 3 | Load (power) | Motor shaft power | % | Read | |
| AV | 4 | Kilowatt Hours total | Total energy counter | kWh | Read | |
| AVmin | 5 | Motor Current | Motor Current | A | Read | |
| AV | 6 | DC link Voltage | DC link Voltage | V | Read | |
| AV | 7 | Motor Voltage | Motor Voltage | V | Read | |
| AV | 8 | Unit Temperature | Heatsink Temperature | °C | Read | |
| AV | 9 | Motor Torque | Torque, % of motor nominal | % | Read | |
| AV | 10 | Operating Days | Operating days (resettable) | days | Read | |
| AV | 11 | Operating Hours | Operating hours (resettable) | h | Read | |
| AV | 12 | Kilowatt Hours | Energy counter (resettable) | kWh | Read | |
| AV | 13 | Torque Reference | Torque Reference | % | Read | |
| AV | 14 | Temperature Rise | Calculated motor temperature, 100 % = nominal | % | Read | |
| AV | 15 | fb_ProcessdataOut_01 | Process data out 1, application specific | Read | ||
| AV | 16 | fb_ProcessdataOut_02 | Process data out 2, application specific | Read | ||
| AV | 17 | fb_ProcessdataOut_03 | Process data out 3, application specific | Read | ||
| AV | 18 | fb_ProcessdataOut_04 | Process data out 4, application specific | Read | ||
| AV | 19 | fb_ProcessdataOut_05 | Process data out 5, application specific | Read | ||
| AV | 20 | fb_ProcessdataOut_06 | Process data out 6, application specific | Read | ||
| AV | 21 | fb_ProcessdataOut_07 | Process data out 7, application specific | Read | ||
| AV | 22 | fb_ProcessdataOut_08 | Process data out 8, application specific | Read | ||
| AVmin | 23 | Active Fault Code | Active Fault Code | Read | ||
| AVmin | 24 | Speed Reference | Speed reference, % of nominal speed | % | Command | |
| AV | 25 | Current Limit | Current Limit | A | Write | |
| AV | 26 | Min Frequency | Minimum Frequency | Hz | Write | |
| AV | 27 | Maximum Frequency | Maximum Frequency | Hz | Write | |
| AV | 28 | Accel Time | Acceleration Time | s | Write | |
| AV | 29 | Decel Time | Deceleration Time | s | Write | |
| AV | 30 | fb_ProcessdataIn_01 | Process data in 1, application specific | Command | ||
| AV | 31 | fb_ProcessdataIn_02 | Process data in 2, application specific | Command | ||
| AV | 32 | fb_ProcessdataIn_03 | Process data in 3, application specific | Command | ||
| AV | 33 | fb_ProcessdataIn_04 | Process data in 4, application specific | Command | ||
| AV | 34 | AnyParam ID | Parameter ID used by AV35 (0-65535) | Write | ||
| AV | 35 | AnyParam Value | Value of the parameter set in AV34 | Write | ||
| AV | 36 | Fb_Control_Word Lo16 | Fixed control word, bits 0-15 | Command | ||
| AV | 37 | Fb_Control_Word Hi16 | Fixed control word, bits 16-31 | Command | ||
| AV | 38 | Fb_Status_Word Lo16 | Fixed status word, bits 0-15 | Read | ||
| AV | 39 | Fb_Status_Word Hi16 | Fixed status word, bits 16-31 | Read |
No points match these filters.
Object ID lookup: Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal point IDs by name
BV0Ready StateBV1Run/Stop StateBV2Fwd/Rev StateBV3Fault StateBV4Alarm StateBV5At SetpointBV6At Zero SpeedBV7fb_ProcessdataOut_01 Bit_0BV8fb_ProcessdataOut_01 Bit_1BV9fb_ProcessdataOut_01 Bit_2BV10fb_ProcessdataOut_01 Bit_3BV11fb_ProcessdataOut_01 Bit_4BV12fb_ProcessdataOut_01 Bit_5BV13fb_ProcessdataOut_01 Bit_6BV14fb_ProcessdataOut_01 Bit_7BV15Run/Stop CMDBV16Fwd/Rev CMDBV17Reset FaultBV18Stop By CoastBV19Stop By RampBV20Quick StopBV21Zero RampBV22Hold RampBV23BusCtrlBV24BusRefBV25fb_control_word Bit_10BV26fb_control_word Bit_11BV27fb_control_word Bit_12BV28fb_control_word Bit_13BV29fb_control_word Bit_14BV30fb_control_word Bit_15AV0Frequency SetpointAV1Output FrequencyAV2Motor SpeedAV3Load (power)AV4Kilowatt Hours totalAV5Motor CurrentAV6DC link VoltageAV7Motor VoltageAV8Unit TemperatureAV9Motor TorqueAV10Operating DaysAV11Operating HoursAV12Kilowatt HoursAV13Torque ReferenceAV14Temperature RiseAV15fb_ProcessdataOut_01AV16fb_ProcessdataOut_02AV17fb_ProcessdataOut_03AV18fb_ProcessdataOut_04AV19fb_ProcessdataOut_05AV20fb_ProcessdataOut_06AV21fb_ProcessdataOut_07AV22fb_ProcessdataOut_08AV23Active Fault CodeAV24Speed ReferenceAV25Current LimitAV26Min FrequencyAV27Maximum FrequencyAV28Accel TimeAV29Decel TimeAV30fb_ProcessdataIn_01AV31fb_ProcessdataIn_02AV32fb_ProcessdataIn_03AV33fb_ProcessdataIn_04AV34AnyParam IDAV35AnyParam ValueAV36Fb_Control_Word Lo16AV37Fb_Control_Word Hi16AV38Fb_Status_Word Lo16AV39Fb_Status_Word Hi16
Integration notes
- From the Vacon 100 Internal BACnet Installation Manual DPD00091B (Danfoss AN361179477697en-000101), Tables 14-15 (PDF pp32-34).
- Fieldbus must be the remote control place (P3.2.1 Rem. Ctrl. Place) for BV 15 and AV 24 to take effect.
- BV 7-14 and AV 15-22 / AV 30-33 are process data whose meaning depends on the application.
- AV 36/AV 37 are IEEE-754 floats; binary coding works only for values without decimals.
- The control word (AV 36) uses bit 0 start/stop, bit 1 direction, bit 2 fault reset; the status word (AV 38) bit 0 ready, 1 run, 2 direction, 3 fault, 4 alarm, 5 at reference, 6 zero speed.
- High and low limits of the objects come from the drive application.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP)
How many BACnet points does the Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP) have?
This list has 71 BACnet objects: 40 analog values, 31 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP) BACnet points are writable?
30 of the 71 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP) BACnet documentation?
The source is Vacon 100 AC drives, Internal BACnet Installation Manual (DPD00091B (AN361179477697en-000101)), revision 2013-06-04, published free by Danfoss at https://assets.danfoss.com/documents/277119/AN361179477697en-000101.pdf.
What are the minimum BACnet points to integrate the Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP)?
Start with BV 15 Run/Stop CMD (Run/stop command (1 = run)); AV 24 Speed Reference (Speed reference, % of nominal speed); BV 17 Reset Fault (Resets the active fault); BV 1 Run/Stop State (Running status); AV 1 Output Frequency (Output frequency, Hz); AV 5 Motor Current (Motor current, A); AV 3 Load (power) (Motor shaft power, %); BV 3 Fault State (Any active drive fault); AV 23 Active Fault Code (Which fault is active).
How do I enable BMS control of the Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP)?
Make Fieldbus the remote control place (Main Menu > Parameters > Start/Stop Setup > P3.2.1 Rem. Ctrl. Place) and choose the fieldbus as the reference source (M3.3). The manual's quick test writes AV 36 control word 0 then 1 to start, AV 24 = 50 for 50 % speed, and 0 to stop.
Does the Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP) need a BACnet heartbeat or have a communication timeout?
MS/TP: P5.8.3.1.5 Communication time-out (0-65535 s, default 10, 0 = off) raises a communication error if the drive is sole master for that long. BACnet IP: P5.9.3.1.2 Communication time-out (default 0 = not used) is the longest allowed gap between UDP packets from the master; losing the Ethernet link faults at once even with 0.
How do I check these points on the real Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Danfoss BACnet points lists
- Variable frequency drive
Danfoss iC7 Series drives with BACnet/IP (OS7BI) or BACnet MS/TP (OS7BN)
Danfoss iC7 Series drives fitted with the BACnet/IP (OS7BI) or BACnet MS/TP (OS7BN) fieldbus option.
Also known as: iC7-Automation, iC7-Hybrid, OS7BI, OS7BN, iC7 BACnet/IP, iC7 BACnet MSTP, 136R0460, 136R0437 - Digital valve actuator (AB-QM pressure independent valves)
Danfoss NovoCon S / M / L / XL digital actuator
Danfoss NovoCon S, M, L and XL digital actuators on AB-QM pressure independent control valves, including NovoCon S with the ChangeOver6 valve.
Also known as: NovoCon, NovoCon S, NovoCon M, NovoCon L, NovoCon XL, AB-QM NovoCon, NovoCon ChangeOver6, AI368140926963 - Thermal energy meter (BACnet MS/TP plug-in module)
Danfoss SonoMeter 40 BACnet MS/TP module
Danfoss SonoMeter 40 ultrasonic heat/cooling energy meters fitted with the BACnet MS/TP module.
Also known as: SonoMeter 40, SonoMeter, Sonometer 40 BACnet, Danfoss BACnet MS/TP base module, AQ404134831215 - Variable frequency drive (BACnet option board)
Danfoss Vacon NX OPT-CJ BACnet MS/TP option board
Vacon NXS, NXP and NXL AC drives fitted with the OPT-CJ BACnet MS/TP option board (slot D or E).
Also known as: OPT-CJ, OPTCJ, NXOPTCJ, Vacon NX BACnet, Vacon NXS, Vacon NXP, Vacon NXL, DPD00901 - Variable frequency drive (water / pump)
Danfoss VLT AQUA Drive FC 202 with BACnet/IP MCA 125
Danfoss VLT AQUA Drive FC 202 fitted with the MCA 125 BACnet/IP option card.
Also known as: FC 202, FC202, VLT AQUA Drive, MCA 125, MCA125, 134B1586, VLT BACnet/IP - Variable frequency drive (HVAC)
Danfoss VLT HVAC Drive FC 102 with BACnet/IP MCA 125
Danfoss VLT HVAC Drive FC 102 fitted with the MCA 125 BACnet/IP option card.
Also known as: FC 102, FC102, VLT HVAC Drive, MCA 125, MCA125, 134B1586, VLT BACnet/IP
Source: Vacon 100 AC drives, Internal BACnet Installation Manual · DPD00091B (AN361179477697en-000101) · rev. 2013-06-04. Object names, instances and units are reproduced as published; descriptions are our own.