Variable frequency drive (HVAC) · BACnet points list

Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP) BACnet points list

Updated 6 November 2026

Short answer

Vacon 100 family drives (now Danfoss) have BACnet MS/TP on the RS-485 terminals and BACnet IP on the Ethernet port, both built in. The object list is Binary Values for drive status, run/stop, direction, reset, stop modes and fieldbus control-word bits, and Analog Values for monitors, the speed reference (% of nominal), limits, ramps, process data, AnyParam access and the fixed control/status words.

This page lists 71 BACnet objects for the Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP) — 30 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Danfoss’s own free documentation, linked below.

Manufacturer
Danfoss
Model
Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP)
Equipment
Variable frequency drive (HVAC)
Equipment type
VFDs & pumps
BACnet objects
71 (30 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
0 = use the number read from the drive (shown in the monitor menu)
Also known as
Vacon 100, Vacon 100 FLOW, Vacon 100 HVAC, Vacon 100 BACnet, DPD00091, AN361179477697
Source document
Vacon 100 AC drives, Internal BACnet Installation Manual · DPD00091B (AN361179477697en-000101) · rev. 2013-06-04
Download CSV 71 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Danfoss’s current documentation and the live device before use. Not official Danfoss information. Terms of use.

BMS integration notes: Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP)

Integration in brief

Select the BACnet protocol on RS-485 (M5.8) or Ethernet (M5.9), set the MS/TP MAC address, baud rate and instance (P5.8.3.1) or the IP settings and P5.9.3.1.3 Protocol in use = 1, and make Fieldbus the remote control place (P3.2.1). Then command BV 15 run/stop (or AV 36 control word) and AV 24 speed reference, and read BV 1, AV 1 and the fault points.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 15Run/Stop CMDRun/stop command (1 = run)Command
AV 24Speed ReferenceSpeed reference, % of nominal speedCommand
BV 17Reset FaultResets the active faultCommand
BV 1Run/Stop StateRunning statusRead
AV 1Output FrequencyOutput frequency, HzRead
AV 5Motor CurrentMotor current, ARead
AV 3Load (power)Motor shaft power, %Read
BV 3Fault StateAny active drive faultRead
AV 23Active Fault CodeWhich fault is activeRead

Enable & remote start

Make Fieldbus the remote control place (Main Menu > Parameters > Start/Stop Setup > P3.2.1 Rem. Ctrl. Place) and choose the fieldbus as the reference source (M3.3). The manual's quick test writes AV 36 control word 0 then 1 to start, AV 24 = 50 for 50 % speed, and 0 to stop.

Heartbeat & communication loss

MS/TP: P5.8.3.1.5 Communication time-out (0-65535 s, default 10, 0 = off) raises a communication error if the drive is sole master for that long. BACnet IP: P5.9.3.1.2 Communication time-out (default 0 = not used) is the longest allowed gap between UDP packets from the master; losing the Ethernet link faults at once even with 0.

Network setup

Watch out for

Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

71 of 71 shown
Type
AnalogBinary
Access
Show
Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP) BACnet Points List
DescriptionStates
BV0Ready StateIndicates whether the drive is ready or notReadInactive/Active: Not Ready/Ready
BVmin1Run/Stop StateIndicates whether the drive is running or stoppedReadInactive/Active: Stop/Run
BV2Fwd/Rev StateIndicates the rotation direction of the motorReadInactive/Active: Fwd/Rev
BVmin3Fault StateIndicates if a fault is activeReadInactive/Active: OK/Fault
BV4Alarm StateIndicates if an alarm is activeReadInactive/Active: OK/Alarm
BV5At SetpointRef. Frequency reachedReadInactive/Active: False/True
BV6At Zero SpeedMotor Running at zero speedReadInactive/Active: False/True
BV7fb_ProcessdataOut_01 Bit_0ProcessDataOut1 bit 0ReadInactive/Active: 0/1
BV8fb_ProcessdataOut_01 Bit_1ProcessDataOut1 bit 1ReadInactive/Active: 0/1
BV9fb_ProcessdataOut_01 Bit_2ProcessDataOut1 bit 2ReadInactive/Active: 0/1
BV10fb_ProcessdataOut_01 Bit_3ProcessDataOut1 bit 3ReadInactive/Active: 0/1
BV11fb_ProcessdataOut_01 Bit_4ProcessDataOut1 bit 4ReadInactive/Active: 0/1
BV12fb_ProcessdataOut_01 Bit_5ProcessDataOut1 bit 5ReadInactive/Active: 0/1
BV13fb_ProcessdataOut_01 Bit_6ProcessDataOut1 bit 6ReadInactive/Active: 0/1
BV14fb_ProcessdataOut_01 Bit_7ProcessDataOut1 bit 7ReadInactive/Active: 0/1
BVmin15Run/Stop CMDCommand to start drive (FB control is active)CommandInactive/Active: Stop/Run
BV16Fwd/Rev CMDCommand to run forward/ reverseCommandInactive/Active: Fwd/Rev
BVmin17Reset FaultCommand to reset Active Fault from driveCommandInactive/Active: 0/Reset
BV18Stop By CoastStop Drive by coastCommandInactive/Active: 0/1
BV19Stop By RampStop Drive by rampCommandInactive/Active: 0/1
BV20Quick StopQuick StopCommandInactive/Active: 0/1
BV21Zero RampStop by zero rampCommandInactive/Active: 0/1
BV22Hold RampHold rampCommandInactive/Active: 0/1
BV23BusCtrlActivate Bus controlCommandInactive/Active: 0/1
BV24BusRefActivate Bus referenceCommandInactive/Active: 0/1
BV25fb_control_word Bit_10fb_control_word bit 10CommandInactive/Active: 0/1
BV26fb_control_word Bit_11fb_control_word bit 11CommandInactive/Active: 0/1
BV27fb_control_word Bit_12fb_control_word bit 12CommandInactive/Active: 0/1
BV28fb_control_word Bit_13fb_control_word bit 13CommandInactive/Active: 0/1
BV29fb_control_word Bit_14fb_control_word bit 14CommandInactive/Active: 0/1
BV30fb_control_word Bit_15fb_control_word bit 15CommandInactive/Active: 0/1
AV0Frequency SetpointFrequency SetpointHzRead
AVmin1Output FrequencyOutput FrequencyHzRead
AV2Motor SpeedMotor SpeedrpmRead
AVmin3Load (power)Motor shaft power%Read
AV4Kilowatt Hours totalTotal energy counterkWhRead
AVmin5Motor CurrentMotor CurrentARead
AV6DC link VoltageDC link VoltageVRead
AV7Motor VoltageMotor VoltageVRead
AV8Unit TemperatureHeatsink Temperature°CRead
AV9Motor TorqueTorque, % of motor nominal%Read
AV10Operating DaysOperating days (resettable)daysRead
AV11Operating HoursOperating hours (resettable)hRead
AV12Kilowatt HoursEnergy counter (resettable)kWhRead
AV13Torque ReferenceTorque Reference%Read
AV14Temperature RiseCalculated motor temperature, 100 % = nominal%Read
AV15fb_ProcessdataOut_01Process data out 1, application specificRead
AV16fb_ProcessdataOut_02Process data out 2, application specificRead
AV17fb_ProcessdataOut_03Process data out 3, application specificRead
AV18fb_ProcessdataOut_04Process data out 4, application specificRead
AV19fb_ProcessdataOut_05Process data out 5, application specificRead
AV20fb_ProcessdataOut_06Process data out 6, application specificRead
AV21fb_ProcessdataOut_07Process data out 7, application specificRead
AV22fb_ProcessdataOut_08Process data out 8, application specificRead
AVmin23Active Fault CodeActive Fault CodeRead
AVmin24Speed ReferenceSpeed reference, % of nominal speed%Command
AV25Current LimitCurrent LimitAWrite
AV26Min FrequencyMinimum FrequencyHzWrite
AV27Maximum FrequencyMaximum FrequencyHzWrite
AV28Accel TimeAcceleration TimesWrite
AV29Decel TimeDeceleration TimesWrite
AV30fb_ProcessdataIn_01Process data in 1, application specificCommand
AV31fb_ProcessdataIn_02Process data in 2, application specificCommand
AV32fb_ProcessdataIn_03Process data in 3, application specificCommand
AV33fb_ProcessdataIn_04Process data in 4, application specificCommand
AV34AnyParam IDParameter ID used by AV35 (0-65535)Write
AV35AnyParam ValueValue of the parameter set in AV34Write
AV36Fb_Control_Word Lo16Fixed control word, bits 0-15Command
AV37Fb_Control_Word Hi16Fixed control word, bits 16-31Command
AV38Fb_Status_Word Lo16Fixed status word, bits 0-15Read
AV39Fb_Status_Word Hi16Fixed status word, bits 16-31Read
Object ID lookup: Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP)

How many BACnet points does the Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP) have?

This list has 71 BACnet objects: 40 analog values, 31 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP) BACnet points are writable?

30 of the 71 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP) BACnet documentation?

The source is Vacon 100 AC drives, Internal BACnet Installation Manual (DPD00091B (AN361179477697en-000101)), revision 2013-06-04, published free by Danfoss at https://assets.danfoss.com/documents/277119/AN361179477697en-000101.pdf.

What are the minimum BACnet points to integrate the Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP)?

Start with BV 15 Run/Stop CMD (Run/stop command (1 = run)); AV 24 Speed Reference (Speed reference, % of nominal speed); BV 17 Reset Fault (Resets the active fault); BV 1 Run/Stop State (Running status); AV 1 Output Frequency (Output frequency, Hz); AV 5 Motor Current (Motor current, A); AV 3 Load (power) (Motor shaft power, %); BV 3 Fault State (Any active drive fault); AV 23 Active Fault Code (Which fault is active).

How do I enable BMS control of the Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP)?

Make Fieldbus the remote control place (Main Menu > Parameters > Start/Stop Setup > P3.2.1 Rem. Ctrl. Place) and choose the fieldbus as the reference source (M3.3). The manual's quick test writes AV 36 control word 0 then 1 to start, AV 24 = 50 for 50 % speed, and 0 to stop.

Does the Danfoss Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP) need a BACnet heartbeat or have a communication timeout?

MS/TP: P5.8.3.1.5 Communication time-out (0-65535 s, default 10, 0 = off) raises a communication error if the drive is sole master for that long. BACnet IP: P5.9.3.1.2 Communication time-out (default 0 = not used) is the longest allowed gap between UDP packets from the master; losing the Ethernet link faults at once even with 0.

How do I check these points on the real Vacon 100 / 100 FLOW / 100 HVAC internal BACnet (MS/TP and IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Danfoss BACnet points lists

Source: Vacon 100 AC drives, Internal BACnet Installation Manual · DPD00091B (AN361179477697en-000101) · rev. 2013-06-04. Object names, instances and units are reproduced as published; descriptions are our own.