Easy BACnet
  1. Home
  2. BACnet points lists
  3. CAREL
  4. k.air air handling unit controller

Air handling unit controller · BACnet points list

CAREL k.air air handling unit controller BACnet points list

Updated 12 November 2026

Short answer

k.air is CAREL's ready-made air handling unit controller. Its manual has a supervisor variable table with a Modbus address and a BACnet object for every variable: about 4,350 objects covering BMS commands, setpoints, every sensor and output (with its configuration), fan, humidifier, compressor and heat recovery data, and one alarm BV per alarm. Most of the list is configuration; an integrator normally maps a small part of it.

This page lists 4350 BACnet objects for the CAREL k.air air handling unit controller — 2473 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CAREL’s own free documentation, linked below.

Manufacturer
CAREL
Model
k.air air handling unit controller
Equipment
Air handling unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
4350 (2473 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
k.air, kair, k.air large, k.air mini, CAREL k.air, +030220981, CAREL AHU controller
Source document
k.air - Air handling unit controller, user manual (11. Supervisor variable table) · +030220981 · rev. rel. 1.8 - 2026-06-25
Download CSV 4350 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CAREL’s current documentation and the live device before use. Not official CAREL information. Terms of use.

BMS integration notes: CAREL k.air air handling unit controller

Integration in brief

Enable BMS on/off with BV 234, then switch the unit with BV 2 and select summer or winter with BV 4. Write the comfort temperature setpoints (AV 2585 winter, AV 2584 summer) if the BMS owns them. Read the unit status (PIV 3645), the supply, return and room temperatures, and the generic alarm BV 902; BV 1 resets alarms. Configure the BMS offline alarm (PIV 2898/2899) if the BMS should be supervised.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 234Scheduler_OnOffUnit.BMS_OnOff_EnMust be on for the BMS on/off command to workWrite
BV 2Scheduler_OnOffUnit.BMS_OnOffUnit on/off command from the BMSWrite
BV 4SummerWinter_BMSSummer/winter command (0 = summer, 1 = winter)Write
AV 2585UnitSetP.TempSetP.Winter.ComfortWinter comfort temperature setpointWrite
AV 2584UnitSetP.TempSetP.Summer.ComfortSummer comfort temperature setpointWrite
BV 1AlarmsMng.AlrmResByBmsAlarm resetWrite
PIV 3645SchedStatusActive status: 0 off, 1 economy, 2 pre-comfort, 3 comfortRead
AV 3435SupplyTemp.Val_Hw_RSupply air temperature (probe reading)Read
AV 3442RetTemp.Val_RReturn air temperatureRead
BV 902GlobalAlrm_Dout.Val_WGeneric alarm activeRead

Enable & remote start

The unit can be switched by keypad/th-Tune, BMS, digital input and scheduler; any enabled source set to off stops it. BMS on/off works only when BV 234 (enable on/off request by BMS) is on; BV 2 then turns the unit on or off.

Heartbeat & communication loss

PIV 2898 selects BMS offline handling (0 disabled, 1 warning only, 2 alarm, 3 alarm with timeout) and PIV 2899 sets the timeout, 120 s by default. BV 1347 shows the BMS offline alarm.

Network setup

Watch out for

CAREL k.air air handling unit controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

4350 of 4350 shown
Type
AnalogBinary
Access
Show
CAREL k.air air handling unit controller BACnet Points List
DescriptionStates
BVmin1AlarmsMng.AlrmResByBmsAlarm reset by BMS; Modbus CS001Write
BVmin2Scheduler_OnOffUnit.BMS_OnOffOn/off request by BMS; Modbus CS002Write
BVmin4SummerWinter_BMSSummer/Winter mode by BMS (FALSE: Summer; TRUE: Winter); Modbus CS004Write
BV5Scheduler_OnOffUnit.BMS_UnitProfile_EnEnable the unit profile from BMS; Modbus CS005Write
BV6Scheduler_Cfg.Prg[0].Event[0].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS006Write
BV7Scheduler_Cfg.Prg[0].Event[1].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS007Write
BV8Scheduler_Cfg.Prg[0].Event[2].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS008Write
BV9Scheduler_Cfg.Prg[0].Event[3].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS009Write
BV10Scheduler_Cfg.Prg[0].Event[4].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS010Write
BV11Scheduler_Cfg.Prg[0].Event[5].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS011Write
BV12Scheduler_Cfg.Prg[0].Event[6].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS012Write
BV13Scheduler_Cfg.Prg[0].Event[7].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS013Write
BV14Scheduler_Cfg.Prg[0].Event[8].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS014Write
BV15Scheduler_Cfg.Prg[0].Event[9].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS015Write
BV16Scheduler_Cfg.Prg[1].Event[0].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS016Write
BV17Scheduler_Cfg.Prg[1].Event[1].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS017Write
BV18Scheduler_Cfg.Prg[1].Event[2].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS018Write
BV19Scheduler_Cfg.Prg[1].Event[3].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS019Write
BV20Scheduler_Cfg.Prg[1].Event[4].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS020Write
BV21Scheduler_Cfg.Prg[1].Event[5].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS021Write
BV22Scheduler_Cfg.Prg[1].Event[6].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS022Write
BV23Scheduler_Cfg.Prg[1].Event[7].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS023Write
BV24Scheduler_Cfg.Prg[1].Event[8].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS024Write
BV25Scheduler_Cfg.Prg[1].Event[9].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS025Write
BV26Scheduler_Cfg.Prg[2].Event[0].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS026Write
BV27Scheduler_Cfg.Prg[2].Event[1].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS027Write
BV28Scheduler_Cfg.Prg[2].Event[2].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS028Write
BV29Scheduler_Cfg.Prg[2].Event[3].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS029Write
BV30Scheduler_Cfg.Prg[2].Event[4].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS030Write
BV31Scheduler_Cfg.Prg[2].Event[5].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS031Write
BV32Scheduler_Cfg.Prg[2].Event[6].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS032Write
BV33Scheduler_Cfg.Prg[2].Event[7].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS033Write
BV34Scheduler_Cfg.Prg[2].Event[8].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS034Write
BV35Scheduler_Cfg.Prg[2].Event[9].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS035Write
BV36Scheduler_Cfg.Prg[3].Event[0].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS036Write
BV37Scheduler_Cfg.Prg[3].Event[1].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS037Write
BV38Scheduler_Cfg.Prg[3].Event[2].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS038Write
BV39Scheduler_Cfg.Prg[3].Event[3].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS039Write
BV40Scheduler_Cfg.Prg[3].Event[4].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS040Write
BV41Scheduler_Cfg.Prg[3].Event[5].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS041Write
BV42Scheduler_Cfg.Prg[3].Event[6].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS042Write
BV43Scheduler_Cfg.Prg[3].Event[7].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS043Write
BV44Scheduler_Cfg.Prg[3].Event[8].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS044Write
BV45Scheduler_Cfg.Prg[3].Event[9].EnabledScheduler: configuration - Program - Event - Enable event; Modbus CS045Write
BV46Scheduler_Cfg.SDays[0].EnabledScheduler: configuration - Special day - Enabled; Modbus CS046Write
BV47Scheduler_Cfg.SDays[1].EnabledScheduler: configuration - Special day - Enabled; Modbus CS047Write
BV48Scheduler_Cfg.SDays[2].EnabledScheduler: configuration - Special day - Enabled; Modbus CS048Write
BV49Scheduler_Cfg.SDays[3].EnabledScheduler: configuration - Special day - Enabled; Modbus CS049Write
BV50Scheduler_Cfg.SDays[4].EnabledScheduler: configuration - Special day - Enabled; Modbus CS050Write
BV51Scheduler_Cfg.SDays[5].EnabledScheduler: configuration - Special day - Enabled; Modbus CS051Write
BV52Scheduler_Cfg.SDays[6].EnabledScheduler: configuration - Special day - Enabled; Modbus CS052Write
BV53Scheduler_Cfg.SDays[7].EnabledScheduler: configuration - Special day - Enabled; Modbus CS053Write
BV54Scheduler_Cfg.SDays[8].EnabledScheduler: configuration - Special day - Enabled; Modbus CS054Write
BV55Scheduler_Cfg.SDays[9].EnabledScheduler: configuration - Special day - Enabled; Modbus CS055Write
BV56Scheduler_Cfg.SDays[10].EnabledScheduler: configuration - Special day - Enabled; Modbus CS056Write
BV57Scheduler_Cfg.SDays[11].EnabledScheduler: configuration - Special day - Enabled; Modbus CS057Write
BV58Scheduler_Cfg.SDays[12].EnabledScheduler: configuration - Special day - Enabled; Modbus CS058Write
BV59Scheduler_Cfg.SDays[13].EnabledScheduler: configuration - Special day - Enabled; Modbus CS059Write
BV60Scheduler_Cfg.SDays[14].EnabledScheduler: configuration - Special day - Enabled; Modbus CS060Write
BV61Scheduler_Cfg.Vac[0].EnabledScheduler: configuration - Vacation period - Enabled; Modbus CS061Write
BV62Scheduler_Cfg.Vac[1].EnabledScheduler: configuration - Vacation period - Enabled; Modbus CS062Write
BV63Scheduler_Cfg.Vac[2].EnabledScheduler: configuration - Vacation period - Enabled; Modbus CS063Write
BV65SupplyAirFlwSw.LogicDin_RWSupply air flow switch - Logic digital input; Modbus CS065Write
BV66RetAirFlwSw.LogicDin_RWReturn air flow switch - Logic digital input; Modbus CS066Write
BV67AirFlwSw.LogicDin_RWAir flow switch - Logic digital input; Modbus CS067Write
BV68AFreezeSw.LogicDin_RWAntifreeze switch - Logic digital input; Modbus CS068Write
BV69RemOnOff.LogicDin_RWRemote On/Off - Logic digital input; Modbus CS069Write
BV70SupplyFanOvld_1.LogicDin_RWSupply fan overload 1 - Logic digital input; Modbus CS070Write
BV71RetFanOvld_1.LogicDin_RWReturn fan overload 1 - Logic digital input; Modbus CS071Write
BV72SupplyFanOvld_2.LogicDin_RWSupply fan overload 2 - Logic digital input; Modbus CS072Write
BV73RetFanOvld_2.LogicDin_RWReturn fan overload 2 - Logic digital input; Modbus CS073Write
BV74SupplyFanInvAlrm.LogicDin_RWSupply inverter alarm - Logic digital input; Modbus CS074Write
BV75RetFanInvAlrm.LogicDin_RWReturn inverter alarm - Logic digital input; Modbus CS075Write
BV76FansOvld.LogicDin_RWFans overload - Logic digital input; Modbus CS076Write
BV77CompOvld.LogicDin_RWCompressor overload - Logic digital input; Modbus CS077Write
BV78HiPSw.LogicDin_RWHigh discharge pressure switch - Logic digital input; Modbus CS078Write
BV79LowPSw.LogicDin_RWLow suction pressure switch - Logic digital input; Modbus CS079Write
BV80RecoveryOvld.LogicDin_RWThermal wheel overload - Logic digital input; Modbus CS080Write
BV81SrsAlrm.LogicDin_RWSerious alarm - Logic digital input; Modbus CS081Write
BV82GenAlrm.LogicDin_RWGeneric alarm - Logic digital input; Modbus CS082Write
BV83GenWarning.LogicDin_RWGeneric warning - Logic digital input; Modbus CS083Write
BV84FiltAlrm.LogicDin_RWFilters alarm - Logic digital input; Modbus CS084Write
BV85SupplyFiltAlrm_1.LogicDin_RWSupply filter alarm 1 - Logic digital input; Modbus CS085Write
BV86SupplyFiltAlrm_2.LogicDin_RWSupply filter alarm 2 - Logic digital input; Modbus CS086Write
BV87RetFiltAlrm.LogicDin_RWReturn filter alarm - Logic digital input; Modbus CS087Write
BV88HumAlrm.LogicDin_RWHumidifier alarm - Logic digital input; Modbus CS088Write
BV89MainCoilPmp1_Ovld.LogicDin_RWMain coil pump 1 overload - Logic digital input; Modbus CS089Write
BV90MainCoilPmp2_Ovld.LogicDin_RWMain coil pump 2 overload - Logic digital input; Modbus CS090Write
BV91ReHeatCoilPmp1_Ovld.LogicDin_RWReHeat coil pump 1 overload - Logic digital input; Modbus CS091Write
BV92ReHeatCoilPmp2_Ovld.LogicDin_RWReHeat coil pump 2 overload - Logic digital input; Modbus CS092Write
BV93PreHeatCoilPmp1_Ovld.LogicDin_RWPreHeat coil pump 1 overload - Logic digital input; Modbus CS093Write
BV94PreHeatCoilPmp2_Ovld.LogicDin_RWPreHeat coil pump 2 overload - Logic digital input; Modbus CS094Write
BV95OA_CoilPmp1_Ovld.LogicDin_RWOutdoor air pre-treatment coil pump 1 overload - Logic digital input; Modbus CS095Write
BV96OA_CoilPmp2_Ovld.LogicDin_RWOutdoor air pre-treatment coil pump 2 overload - Logic digital input; Modbus CS096Write
BV97FreshAirDampSw.LogicDin_RWFresh air damper switch - Logic digital input; Modbus CS097Write
BV98SupplyDamperSw.LogicDin_RWSupply damper switch - Logic digital input; Modbus CS098Write
BV99RetDampSw.LogicDin_RWReturn damper switch - Logic digital input; Modbus CS099Write
BV100MainCoilFlwSw.LogicDin_RWMain coil flow switch - Logic digital input; Modbus CS100Write
BV101PreHeatCoilFlwSw.LogicDin_RWPre-heating coil flow switch - Logic digital input; Modbus CS101Write
BV102ReHeatCoilFlwSw.LogicDin_RWPost-Heating coil flow switch - Logic digital input; Modbus CS102Write
BV103OA_CoilFlwSw.LogicDin_RWOutdoor air pre-treatment coil flow switch - Logic digital input; Modbus CS103Write
BV104RecoveryClogged.LogicDin_RWRecovery clogged - Logic digital input; Modbus CS104Write
BV105ReHeatAlrm.LogicDin_RWRe-heating alarm - Logic digital input; Modbus CS105Write
BV106PreHeatAlrm.LogicDin_RWPre-heating alarm - Logic digital input; Modbus CS106Write
BV107MainHeatCoilAlrm.LogicDin_RWMain coil alarm - Logic digital input; Modbus CS107Write
BV108OA_CoilAlrm.LogicDin_RWOutdoor air pre-treatment-Heat alarm - Logic digital input; Modbus CS108Write
BV109DoorSw.LogicDin_RWDoor Switch - Logic digital input; Modbus CS109Write
BV110FireSmokeAlrm.LogicDin_RWFire/Smoke alarm - Logic digital input; Modbus CS110Write
BV111FiremanOverrideSw.LogicDin_RWFireman override switch - Logic digital input; Modbus CS111Write
BV112SummerWinterModeByDin.LogicDin_RWSummer/Winter mode by digital input - Logic; Modbus CS112Write
BV113Din_SetP.LogicDin_RWSetpoint by digital input - Logic digital input; Modbus CS113Write
BV114Eco_Mode.LogicDin_RWEco mode - Logic digital input; Modbus CS114Write
BV115PreComf_Mode.LogicDin_RWPrecomfort mode - Logic digital input; Modbus CS115Write
BV116Comf_Mode.LogicDin_RWComfort mode - Logic digital input; Modbus CS116Write
BV117AuxDin_1.LogicDin_RWAuxiliary digital input 1 - Logic digital input; Modbus CS117Write
BV118AuxDin_2.LogicDin_RWAuxiliary digital input 2 - Logic digital input; Modbus CS118Write
BV119AuxDin_3.LogicDin_RWAuxiliary digital input 3 - Logic digital input; Modbus CS119Write
BV120AuxDin_4.LogicDin_RWAuxiliary digital input 4 - Logic digital input; Modbus CS120Write
BV121DfrHeatExch_Din.LogicDin_RWHeat exchanger defrost by Din - Logic digital input; Modbus CS121Write
BV122BypassDamp_Dout.LogicDout_RWBypass damper - Logic digital output; Modbus CS122Write
BV123BypassDamp_Open.LogicDout_RWBypass damper floating (open) - Logic digital output; Modbus CS123Write
BV124BypassDamp_Close.LogicDout_RWBypass damper floating (close) - Logic digital output; Modbus CS124Write
BV125FreshAirDamp_Dout.LogicDout_RWFresh air damper - Logic digital output; Modbus CS125Write
BV126ExhAirDamp_Dout.LogicDout_RWExhaust air damper - Logic digital output; Modbus CS126Write
BV127MixingDamp_Dout.LogicDout_RWMixing damper - Logic digital output; Modbus CS127Write
BV128SupplyAirDamp_Dout.LogicDout_RWSupply air damper - Logic digital output; Modbus CS128Write
BV129RetAirDamp_Dout.LogicDout_RWReturn air damper - Logic digital output; Modbus CS129Write
BV130MixingDamp_Open.LogicDout_RWMixing damper floating (OPEN) - Logic digital output; Modbus CS130Write
BV131MixingDamp_Close.LogicDout_RWMixing damper floating (CLOSE) - Logic digital output; Modbus CS131Write
BV132SupplyFan_Dout.LogicDout_RWSupply fan - Logic digital output; Modbus CS132Write
BV133RetFan_Dout.LogicDout_RWReturn fan - Logic digital output; Modbus CS133Write
BV134SupplyFan2_Dout.LogicDout_RWSupply fan 2 - Logic digital output; Modbus CS134Write
BV135RetFan2_Dout.LogicDout_RWReturn fan 2 - Logic digital output; Modbus CS135Write
BV136Comp_Dout.LogicDout_RWCompressor - Logic digital output; Modbus CS136Write
BV137RevVlv.LogicDout_RWReverse valve - Logic digital output; Modbus CS137Write
BV138UnitOnOff_Dout.LogicDout_RWUnit status (On/Off ) - Logic digital output; Modbus CS138Write
BV140GlobalAlrm_Dout.LogicDout_RWGeneric alarm info - Logic digital output; Modbus CS140Write
BV141LightAlrm_Dout.LogicDout_RWLight alarm info - Logic digital output; Modbus CS141Write
BV142SrsAlrm_Dout.LogicDout_RWSerious alarm info - Logic digital output; Modbus CS142Write
BV143Humidifier.LogicDout_RWHumidifier - Logic digital output; Modbus CS143Write
BV144AuxOut1_Dout.LogicDout_RWAuxiliary output 1 - Logic digital output; Modbus CS144Write
BV145AuxOut2_Dout.LogicDout_RWAuxiliary output 2 - Logic digital output; Modbus CS145Write
BV146AuxOut3_Dout.LogicDout_RWAuxiliary output 3 - Logic digital output; Modbus CS146Write
BV147AuxOut4_Dout.LogicDout_RWAuxiliary output 4 - Logic digital output; Modbus CS147Write
BV148MainVlv_Open.LogicDout_RWMain floating valve open - Logic digital output; Modbus CS148Write
BV149PreHeatVlv_Open.LogicDout_RWPre-heating floating valve open - Logic digital output; Modbus CS149Write
BV150ReHeatVlv_Open.LogicDout_RWRe-Heating floating valve open - Logic digital output; Modbus CS150Write
BV151MainVlv_Close.LogicDout_RWMain floating valve close - Logic digital output; Modbus CS151Write
BV152PreHeatVlv_Close.LogicDout_RWPre-heating floating valve close - Logic digital output; Modbus CS152Write
BV153ReHeatVlv_Close.LogicDout_RWRe-Heating floating valve close - Logic digital output; Modbus CS153Write
BV154MainCoil_Step1.LogicDout_RWMain step 1 - Logic digital output; Modbus CS154Write
BV155MainCoil_Step2.LogicDout_RWMain step 2 - Logic digital output; Modbus CS155Write
BV156MainCoil_Step3.LogicDout_RWMain step 3 - Logic digital output; Modbus CS156Write
BV157MainCoil_Step4.LogicDout_RWMain step 4 - Logic digital output; Modbus CS157Write
BV158ReHeatCoil_Step1.LogicDout_RWPostheat heater 1 - Logic digital output; Modbus CS158Write
BV159ReHeatCoil_Step2.LogicDout_RWPostheat heater 2 - Logic digital output; Modbus CS159Write
BV160ReHeatCoil_Step3.LogicDout_RWPostheat heater 3 - Logic digital output; Modbus CS160Write
BV161ReHeatCoil_Step4.LogicDout_RWPostheat heater 4 - Logic digital output; Modbus CS161Write
BV162PreHeatCoil_Step1.LogicDout_RWPreheat heater 1 - Logic digital output; Modbus CS162Write
BV163PreHeatCoil_Step2.LogicDout_RWPreheat heater 2 - Logic digital output; Modbus CS163Write
BV164PreHeatCoil_Step3.LogicDout_RWPreheat heater 3 - Logic digital output; Modbus CS164Write
BV165PreHeatCoil_Step4.LogicDout_RWPreheat heater 4 - Logic digital output; Modbus CS165Write
BV166OA_Coil_Step1.LogicDout_RWOutdoor air pre-treatment heater 1 - Logic digital output; Modbus CS166Write
BV167OA_Coil_Step2.LogicDout_RWOutdoor air pre-treatment heater 2 - Logic digital output; Modbus CS167Write
BV168OA_Coil_Step3.LogicDout_RWOutdoor air pre-treatment heater 3 - Logic digital output; Modbus CS168Write
BV169OA_Coil_Step4.LogicDout_RWOutdoor air pre-treatment heater 4 - Logic digital output; Modbus CS169Write
BV170PreHeatPmp_1.LogicDout_RWPre-Heating pump 1 - Logic digital output; Modbus CS170Write
BV171PreHeatPmp_2.LogicDout_RWPre-Heating pump 2 - Logic digital output; Modbus CS171Write
BV172MainCoilPmp_1.LogicDout_RWMain pump 1 - Logic digital output; Modbus CS172Write
BV173MainCoilPmp_2.LogicDout_RWMain pump 2 - Logic digital output; Modbus CS173Write
BV174ReHeatPmp_1.LogicDout_RWRe-Heating pump 1 - Logic digital output; Modbus CS174Write
BV175ReHeatPmp_2.LogicDout_RWRe-Heating pump 2 - Logic digital output; Modbus CS175Write
BV176OA_CoilPmp_1.LogicDout_RWOutdoor air pre-treatment -Heating pump 1 - Logic digital output; Modbus CS176Write
BV177OA_CoilPmp_2.LogicDout_RWOutdoor air pre-treatment -Heating pump 2 - Logic digital output; Modbus CS177Write
BV178FiltAlrm_Dout.LogicDout_RWFilters alarm - Logic digital output; Modbus CS178Write
BV179Recovery_Dout.LogicDout_RWRecovery - Logic digital output; Modbus CS179Write
BV180IEC_Hum_Dout.LogicDout_RWIEC humidifer - Logic digital output; Modbus CS180Write
BV181SummerWinter_UISummer/Winter mode by Keyboard (FALSE: Summer; TRUE: Winter); Modbus CS181Write
BV182Scheduler_OnOffUnit.PartyMode_StartParty mode: start command; Modbus CS182Write
BV183VarToShow.LogicModbus CS183Write
BV184FreshAirDampEnManFresh air damper manual mode enable; Modbus CS184Write
BV185MixDampEnManMixing damper manual mode enable; Modbus CS185Write
BV186ExhAirDampEnManExhaust air damper manual mode enable; Modbus CS186Write
BV187BypassDampEnManBypass damper manual mode enable; Modbus CS187Write
BV188SupplyFanEnManSupply fan manual mode enable; Modbus CS188Write
BV189RetFanEnManReturn fan manual mode enable; Modbus CS189Write
BV190PreHeatCoilEnManPre heating coil manual mode enable; Modbus CS190Write
BV191MainCoilEnManMain coil manual mode enable; Modbus CS191Write
BV192ReHeatCoilEnManPost heating coil manual mode enable; Modbus CS192Write
BV193CompEnManCompressor manual mode enable; Modbus CS193Write
BV194HumEnManHumidifier manual mode enable; Modbus CS194Write
BV195En_SetPCompEnable setpoint compensation by external temperature; Modbus CS195Write
BV196Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[0].EnabledEvent - Enable event; Modbus CS196Write
BV197Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[1].EnabledEvent - Enable event; Modbus CS197Write
BV198Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[2].EnabledEvent - Enable event; Modbus CS198Write
BV199Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[3].EnabledEvent - Enable event; Modbus CS199Write
BV200Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[4].EnabledEvent - Enable event; Modbus CS200Write
BV201Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[5].EnabledEvent - Enable event; Modbus CS201Write
BV202Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[6].EnabledEvent - Enable event; Modbus CS202Write
BV203Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[7].EnabledEvent - Enable event; Modbus CS203Write
BV204Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[8].EnabledEvent - Enable event; Modbus CS204Write
BV205Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[9].EnabledEvent - Enable event; Modbus CS205Write
BV206Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[0].EnabledVacation period - Enabled; Modbus CS206Write
BV207Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[1].EnabledVacation period - Enabled; Modbus CS207Write
BV208Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[2].EnabledVacation period - Enabled; Modbus CS208Write
BV209Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[0].EnabledSpecial day - Enabled; Modbus CS209Write
BV210Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[1].EnabledSpecial day - Enabled; Modbus CS210Write
BV211Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[2].EnabledSpecial day - Enabled; Modbus CS211Write
BV212Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[3].EnabledSpecial day - Enabled; Modbus CS212Write
BV213Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[4].EnabledSpecial day - Enabled; Modbus CS213Write
BV214Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[5].EnabledSpecial day - Enabled; Modbus CS214Write
BV215Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[6].EnabledSpecial day - Enabled; Modbus CS215Write
BV216Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[7].EnabledSpecial day - Enabled; Modbus CS216Write
BV217Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[8].EnabledSpecial day - Enabled; Modbus CS217Write
BV218Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[9].EnabledSpecial day - Enabled; Modbus CS218Write
BV219Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[10].EnabledSpecial day - Enabled; Modbus CS219Write
BV220Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[11].EnabledSpecial day - Enabled; Modbus CS220Write
BV221Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[12].EnabledSpecial day - Enabled; Modbus CS221Write
BV222Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[13].EnabledSpecial day - Enabled; Modbus CS222Write
BV223Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[14].EnabledSpecial day - Enabled; Modbus CS223Write
BV224Scheduler_OnOffUnit.En_PartyModeEnable Party mode from c.pCO; Modbus CS224Write
BV225En_RetFanEnable return fan; Modbus CS225Write
BV226En_DehumRegEnable dehumidification regulation; Modbus CS226Write
BV227Dehum_En_KWaterDWPDehumidification: enable kwater dew point calculation; Modbus CS227Write
BV228En_WarmUpEnable warm up procedure during start up state; Modbus CS228Write
BV229En_AfreezeOffStateEnable antifreeze during off state; Modbus CS229Write
BV230RegPrbErrModeFALSE=forced off; TRUE=manual activation; Modbus CS230Write
BV231StateMachine.En_RegPrbErr_UnitOffEnabling of the regulation probe error status during the off state; Modbus CS231Write
BV232En_THTNEnable th-Tune management; Modbus CS232Write
BVmin234Scheduler_OnOffUnit.BMS_OnOff_EnEnable on/off request by BMS; Modbus CS234Write
BV236En_VDIEnable VDI management; Modbus CS236Write
BV237En_VDI_HiSatHumStartUpVDI high saturation humidity startup enabled; Modbus CS237Write
BV238RetFanPrefRunDirPreferred running direction (FALSE: left; TRUE: right) for fan; Modbus CS238Write
BV239RetFan_En_EmergFunctEnable emergency function (FALSE: Inactive; TRUE: Active; ) for Ebmpapst fan; Modbus CS239Write
BV245En_Fan_CO2_RegEnable air quality regulation for fans; Modbus CS245Write
BV246En_FanTempLimEnable fan temperature limit regulation; Modbus CS246Write
BV247En_FC_FH_FanRegEnable fan regulation in case of FreeCooling/FreeHeating; Modbus CS247Write
BV248En_NightMinVentEnable night minimum ventilation; Modbus CS248Write
BV249NightVentPriorityPriority between minimum ventilation and night free cooling (FALSE: minimum ...; Modbus CS249Write
BV250Antifreeze.DisLowSupplyTempAlrmDisable Low supply temperature alarm; Modbus CS250Write
BV251Regulation.EnCompNightVentEnable compressor during night ventilation; Modbus CS251Write
BV252Humisonic.ManDrain_HUMSManual drain request: FALSE=no request; TRUE=request to drain; Modbus CS252Write
BV253Humisonic.DevSettings_HUMS.HrsCountResParameters for device configuration - Hours counter reset request; Modbus CS253Write
BV254SupplyFanPrefRunDirPreferred running direction (FALSE: left; TRUE: right) for fan; Modbus CS254Write
BV255SupplyFan_En_EmergFunctSettings of the emergency function - Enable emergency function (FALSE: ...; Modbus CS255Write
BV261AuxReg1_Cfg.DOut_ErrorValueAuxiliary Regulation 1 - Dout: Error value; Modbus CS261Write
BV262AuxReg1_Cfg.EnableSel_ManualEnAuxiliary Regulation 1 - Enable selection: Manual enabling; Modbus CS262Write
BV263AuxReg1_Cfg.En_ComfortRegAuxiliary Regulation 1 - Enable comfort auxiliary regulation; Modbus CS263Write
BV264AuxReg1_Cfg.ReverseModeAuxiliary Regulation 1 - Reverse mode; Modbus CS264Write
BV266AuxReg1_Cfg.ManModeEnAuxiliary Regulation 1 - Manual mode enabled; Modbus CS266Write
BV267AuxReg1_Cfg.DOut_ManModeValAuxiliary Regulation 1 - Dout: Manual mode value; Modbus CS267Write
BV268AuxReg2_Cfg.DOut_ErrorValueAuxiliary Regulation 2 - Dout: Error value; Modbus CS268Write
BV269AuxReg2_Cfg.EnableSel_ManualEnAuxiliary Regulation 2 - Enable selection: Manual enabling; Modbus CS269Write
BV270AuxReg2_Cfg.En_ComfortRegAuxiliary Regulation 2 - Enable comfort auxiliary regulation; Modbus CS270Write
BV271AuxReg2_Cfg.ReverseModeAuxiliary Regulation 2 - Reverse mode; Modbus CS271Write
BV273AuxReg2_Cfg.ManModeEnAuxiliary Regulation 2 - Manual mode enabled; Modbus CS273Write
BV274AuxReg2_Cfg.DOut_ManModeValAuxiliary Regulation 2 - Dout: Manual mode value; Modbus CS274Write
BV275AuxReg3_Cfg.DOut_ErrorValueAuxiliary Regulation 3 - Dout: Error value; Modbus CS275Write
BV276AuxReg3_Cfg.EnableSel_ManualEnAuxiliary Regulation 3 - Enable selection: Manual enabling; Modbus CS276Write
BV277AuxReg3_Cfg.En_ComfortRegAuxiliary Regulation 3 - Enable comfort auxiliary regulation; Modbus CS277Write
BV278AuxReg3_Cfg.ReverseModeAuxiliary Regulation 3 - Reverse mode; Modbus CS278Write
BV280AuxReg3_Cfg.ManModeEnAuxiliary Regulation 3 - Manual mode enabled; Modbus CS280Write
BV281AuxReg3_Cfg.DOut_ManModeValAuxiliary Regulation 3 - Dout: Manual mode value; Modbus CS281Write
BV282AuxReg4_Cfg.DOut_ErrorValueAuxiliary Regulation 4 - Dout: Error value; Modbus CS282Write
BV283AuxReg4_Cfg.EnableSel_ManualEnAuxiliary Regulation 4 - Enable selection: Manual enabling; Modbus CS283Write
BV284AuxReg4_Cfg.En_ComfortRegAuxiliary Regulation 4 - Enable comfort auxiliary regulation; Modbus CS284Write
BV285AuxReg4_Cfg.ReverseModeAuxiliary Regulation 4 - Reverse mode; Modbus CS285Write
BV287AuxReg4_Cfg.ManModeEnAuxiliary Regulation 4 - Manual mode enabled; Modbus CS287Write
BV288AuxReg4_Cfg.DOut_ManModeValAuxiliary Regulation 4 - Dout: Manual mode value; Modbus CS288Write
BV289En_Damp_CO2_RegEnable air quality regulation for fresh air OR mixing damper; Modbus CS289Write
BV290En_FC_FH_DampRegEnable dampers regulation in case of FreeCooling/FreeHeating; Modbus CS290Write
BV291CompTypCompressor type (FALSE: ON/OFF; TRUE: BLDC); Modbus CS291Write
BV292En_EVD_Emb_1Enable EVD emb management; Modbus CS292Write
BV293Coils.MainCoil_PmpFlwChk_EnAntiLockCooling/Heating coil pumps enable antilock function; Modbus CS293Write
BV294Coils.PreHeatCoil_PmpFlwChk_EnAntiLockPreHeating coil pumps enable antilock function; Modbus CS294Write
BV295Coils.ReHeatCoil_PmpFlwChk_EnAntiLockRe Heating coil pumps enable antilock function; Modbus CS295Write
BV296VDI_Conf[0].EnabledEnable of the VDI function; Modbus CS296Write
BV297VDI_Conf[0].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS297Write
BV298VDI_Conf[1].EnabledEnable of the VDI function; Modbus CS298Write
BV299VDI_Conf[1].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS299Write
BV300VDI_Conf[2].EnabledEnable of the VDI function; Modbus CS300Write
BV301VDI_Conf[2].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS301Write
BV302VDI_Conf[3].EnabledEnable of the VDI function; Modbus CS302Write
BV303VDI_Conf[3].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS303Write
BV304VDI_Conf[4].EnabledEnable of the VDI function; Modbus CS304Write
BV305VDI_Conf[4].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS305Write
BV306VDI_Conf[5].EnabledEnable of the VDI function; Modbus CS306Write
BV307VDI_Conf[5].ResCmdReset timings after the inspection; Modbus CS307Write
BV308VDI_Conf[6].EnabledEnable of the VDI function; Modbus CS308Write
BV309VDI_Conf[6].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS309Write
BV310VDI_Conf[7].EnabledEnable of the VDI function; Modbus CS310Write
BV311VDI_Conf[7].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS311Write
BV312VDI_Conf[8].EnabledEnable of the VDI function; Modbus CS312Write
BV313VDI_Conf[8].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS313Write
BV314VDI_Conf[9].EnabledEnable of the VDI function; Modbus CS314Write
BV315VDI_Conf[9].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS315Write
BV316VDI_Conf[10].EnabledEnable of the VDI function; Modbus CS316Write
BV317VDI_Conf[10].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS317Write
BV318VDI_Conf[11].EnabledEnable of the VDI function; Modbus CS318Write
BV319VDI_Conf[11].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS319Write
BV320VDI_Conf[12].EnabledEnable of the VDI function; Modbus CS320Write
BV321VDI_Conf[12].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS321Write
BV322VDI_Conf[13].EnabledEnable of the VDI function; Modbus CS322Write
BV323VDI_Conf[13].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS323Write
BV324VDI_Conf[14].EnabledEnable of the VDI function; Modbus CS324Write
BV325VDI_Conf[14].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS325Write
BV326VDI_Conf[15].EnabledEnable of the VDI function; Modbus CS326Write
BV327VDI_Conf[15].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS327Write
BV328VDI_Conf[16].EnabledEnable of the VDI function; Modbus CS328Write
BV329VDI_Conf[16].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS329Write
BV330VDI_Conf[17].EnabledEnable of the VDI function; Modbus CS330Write
BV331VDI_Conf[17].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS331Write
BV332VDI_Conf[18].EnabledEnable of the VDI function; Modbus CS332Write
BV333VDI_Conf[18].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS333Write
BV334VDI_Conf[19].EnabledEnable of the VDI function; Modbus CS334Write
BV335VDI_Conf[19].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS335Write
BV336VDI_Conf[20].EnabledEnable of the VDI function; Modbus CS336Write
BV337VDI_Conf[20].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS337Write
BV338VDI_Conf[21].EnabledEnable of the VDI function; Modbus CS338Write
BV339VDI_Conf[21].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS339Write
BV340VDI_Conf[22].EnabledEnable of the VDI function; Modbus CS340Write
BV341VDI_Conf[22].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS341Write
BV342VDI_Conf[23].EnabledEnable of the VDI function; Modbus CS342Write
BV343VDI_Conf[23].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS343Write
BV344VDI_Conf[24].EnabledEnable of the VDI function; Modbus CS344Write
BV345VDI_Conf[24].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS345Write
BV346VDI_Conf[25].EnabledEnable of the VDI function; Modbus CS346Write
BV347VDI_Conf[25].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS347Write
BV348VDI_Conf[26].EnabledEnable of the VDI function; Modbus CS348Write
BV349VDI_Conf[26].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS349Write
BV350VDI_Conf[27].EnabledEnable of the VDI function; Modbus CS350Write
BV351VDI_Conf[27].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS351Write
BV352VDI_Conf[28].EnabledEnable of the VDI function; Modbus CS352Write
BV353VDI_Conf[28].AlrmTypReset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS353Write
BV354VDI_Conf[0].ResCmdReset timings after the inspection; Modbus CS354Write
BV355VDI_Conf[1].ResCmdReset timings after the inspection; Modbus CS355Write
BV356VDI_Conf[2].ResCmdReset timings after the inspection; Modbus CS356Write
BV357VDI_Conf[3].ResCmdReset timings after the inspection; Modbus CS357Write
BV358VDI_Conf[4].ResCmdReset timings after the inspection; Modbus CS358Write
BV359VDI_Conf[6].ResCmdReset timings after the inspection; Modbus CS359Write
BV360VDI_Conf[7].ResCmdReset timings after the inspection; Modbus CS360Write
BV361VDI_Conf[8].ResCmdReset timings after the inspection; Modbus CS361Write
BV362VDI_Conf[9].ResCmdReset timings after the inspection; Modbus CS362Write
BV363VDI_Conf[10].ResCmdReset timings after the inspection; Modbus CS363Write
BV364VDI_Conf[11].ResCmdReset timings after the inspection; Modbus CS364Write
BV365VDI_Conf[12].ResCmdReset timings after the inspection; Modbus CS365Write
BV366VDI_Conf[13].ResCmdReset timings after the inspection; Modbus CS366Write
BV367VDI_Conf[14].ResCmdReset timings after the inspection; Modbus CS367Write
BV368VDI_Conf[15].ResCmdReset timings after the inspection; Modbus CS368Write
BV369VDI_Conf[16].ResCmdReset timings after the inspection; Modbus CS369Write
BV370VDI_Conf[17].ResCmdReset timings after the inspection; Modbus CS370Write
BV371VDI_Conf[18].ResCmdReset timings after the inspection; Modbus CS371Write
BV372VDI_Conf[19].ResCmdReset timings after the inspection; Modbus CS372Write
BV373VDI_Conf[20].ResCmdReset timings after the inspection; Modbus CS373Write
BV374VDI_Conf[21].ResCmdReset timings after the inspection; Modbus CS374Write
BV375VDI_Conf[22].ResCmdReset timings after the inspection; Modbus CS375Write
BV376VDI_Conf[23].ResCmdReset timings after the inspection; Modbus CS376Write
BV377VDI_Conf[24].ResCmdReset timings after the inspection; Modbus CS377Write
BV378VDI_Conf[25].ResCmdReset timings after the inspection; Modbus CS378Write
BV379VDI_Conf[26].ResCmdReset timings after the inspection; Modbus CS379Write
BV380VDI_Conf[27].ResCmdReset timings after the inspection; Modbus CS380Write
BV381VDI_Conf[28].ResCmdReset timings after the inspection; Modbus CS381Write
BV382GeneralMng.En_BuzzEnable of Buzzer; Modbus CS382Write
BV383En_LiqSolVlvEnable liquid solenoid valve; Modbus CS384Write
BV384EVD_Emb_Circ.EEV_ManPositEnEEV enable manual position; Modbus CS385Write
BV385Data_EVD_Emb_1.EVD.System.DC_SupplyEn.ValEVD parameters - System configuration - DC power supply enabling; Modbus CS386Write
BV386Data_EVD_Emb_1.EVD.EEV_Config.ExtraOpEn.ValEVD parameters - Valve configuration - EEV opening position synchronization; Modbus CS387Write
BV387Data_EVD_Emb_1.EVD.EEV_Config.ExtraClosEn.ValEVD parameters - Valve configuration - EEV closing position synchronization; Modbus CS388Write
BV388BLDC_compressor.MiscMng_PWRP1.Mng_SerNoCtrl_EnSerial number control enable; Modbus CS389Write
BV389BLDC_compressor.CurrCompCfg_PWRP1.HR22_0_SpeedProfStartModeCurr compressor configuration (Powerplus) - Speed profile start mode (0= ...; Modbus CS390Write
BV390BLDC_compressor.CurrCompCfg_PWRP1.HR22_1_SpeedProfStartModeCurr compressor configuration (Powerplus) - Speed profile start mode (0=-; ...; Modbus CS391Write
BV391BLDC_compressor.CurrCompCfg_PWRP1.HR76_0_DisPhLossDetectCurr compressor configuration (Powerplus) - Disable phase loss algorithm (0=enabled; 1=disabled); Modbus CS392Write
BV392BLDC_compressor.CurrCompCfg_PWRP1.HR76_3_EnOvldThProtRetentionCurr compressor configuration (Powerplus) - Thermal Overload Retention Enable; Modbus CS393Write
BV393BLDC_compressor.MiscMng_PWRP1.MngCstm_SaveCustomCfgSave custom config. command; Modbus CS394Write
BV394BLDC_compressor.AlrmResetMng_PWRP1.Al01_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS395Write
BV395BLDC_compressor.AlrmResetMng_PWRP1.Al02_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS396Write
BV396BLDC_compressor.AlrmResetMng_PWRP1.Al03_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS397Write
BV397BLDC_compressor.AlrmResetMng_PWRP1.Al04_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS398Write
BV398BLDC_compressor.AlrmResetMng_PWRP1.Al05_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS399Write
BV399BLDC_compressor.AlrmResetMng_PWRP1.Al06_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS400Write
BV400BLDC_compressor.AlrmResetMng_PWRP1.Al07_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS401Write
BV401BLDC_compressor.AlrmResetMng_PWRP1.Al08_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS402Write
BV402BLDC_compressor.AlrmResetMng_PWRP1.Al09_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS403Write
BV403BLDC_compressor.AlrmResetMng_PWRP1.Al10_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS404Write
BV404BLDC_compressor.AlrmResetMng_PWRP1.Al11_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS405Write
BV405BLDC_compressor.AlrmResetMng_PWRP1.Al12_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS406Write
BV406BLDC_compressor.AlrmResetMng_PWRP1.Al13_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS407Write
BV407BLDC_compressor.AlrmResetMng_PWRP1.Al14_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS408Write
BV408BLDC_compressor.AlrmResetMng_PWRP1.Al15_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS409Write
BV409BLDC_compressor.AlrmResetMng_PWRP1.Al16_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS410Write
BV410BLDC_compressor.AlrmResetMng_PWRP1.Al17_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS411Write
BV411BLDC_compressor.AlrmResetMng_PWRP1.Al18_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS412Write
BV412BLDC_compressor.AlrmResetMng_PWRP1.Al19_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS413Write
BV413BLDC_compressor.AlrmResetMng_PWRP1.Al20_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS414Write
BV414BLDC_compressor.AlrmResetMng_PWRP1.Al21_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS415Write
BV415BLDC_compressor.AlrmResetMng_PWRP1.Al22_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS416Write
BV416BLDC_compressor.AlrmResetMng_PWRP1.Al23_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS417Write
BV417BLDC_compressor.AlrmResetMng_PWRP1.Al24_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS418Write
BV418BLDC_compressor.AlrmResetMng_PWRP1.Al25_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS419Write
BV419BLDC_compressor.AlrmResetMng_PWRP1.Al26_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS420Write
BV420BLDC_compressor.AlrmResetMng_PWRP1.Al27_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS421Write
BV421BLDC_compressor.AlrmResetMng_PWRP1.Al28_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS422Write
BV422BLDC_compressor.AlrmResetMng_PWRP1.Al99_uMotorResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS423Write
BV423BLDC_compressor.AlrmResetMng_PWRP1.Al101_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS424Write
BV424BLDC_compressor.AlrmResetMng_PWRP1.Al102_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS425Write
BV425BLDC_compressor.AlrmResetMng_PWRP1.Al103_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS426Write
BV426BLDC_compressor.AlrmResetMng_PWRP1.Al104_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS427Write
BV427BLDC_compressor.AlrmResetMng_PWRP1.Al105_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS428Write
BV428BLDC_compressor.AlrmResetMng_PWRP1.Al106_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS429Write
BV429BLDC_compressor.AlrmResetMng_PWRP1.Al107_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS430Write
BV430BLDC_compressor.AlrmResetMng_PWRP1.Al108_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS431Write
BV431BLDC_compressor.AlrmResetMng_PWRP1.Al109_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS432Write
BV432BLDC_compressor.AlrmResetMng_PWRP1.Al110_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS433Write
BV433BLDC_compressor.AlrmResetMng_PWRP1.Al111_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS434Write
BV434BLDC_compressor.AlrmResetMng_PWRP1.Al112_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS435Write
BV435BLDC_compressor.AlrmResetMng_PWRP1.Al113_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS436Write
BV436BLDC_compressor.AlrmResetMng_PWRP1.Al114_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS437Write
BV437BLDC_compressor.AlrmResetMng_PWRP1.Al115_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS438Write
BV438BLDC_compressor.AlrmResetMng_PWRP1.Al116_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS439Write
BV439BLDC_compressor.AlrmResetMng_PWRP1.Al201_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS440Write
BV440BLDC_compressor.AlrmResetMng_PWRP1.Al202_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS441Write
BV441BLDC_compressor.AlrmResetMng_PWRP1.Al203_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS442Write
BV442BLDC_compressor.AlrmResetMng_PWRP1.Al204_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS443Write
BV443BLDC_compressor.AlrmResetMng_PWRP1.Al205_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS444Write
BV444BLDC_compressor.AlrmResetMng_PWRP1.Al206_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS445Write
BV445BLDC_compressor.AlrmResetMng_PWRP1.Al207_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS446Write
BV446BLDC_compressor.AlrmResetMng_PWRP1.Al208_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS447Write
BV447BLDC_compressor.AlrmResetMng_PWRP1.Al209_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS448Write
BV448BLDC_compressor.AlrmResetMng_PWRP1.Al210_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS449Write
BV449BLDC_compressor.AlrmResetMng_PWRP1.Al211_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS450Write
BV450BLDC_compressor.AlrmResetMng_PWRP1.Al212_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS451Write
BV451BLDC_compressor.AlrmResetMng_PWRP1.Al213_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS452Write
BV452BLDC_compressor.AlrmResetMng_PWRP1.Al214_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS453Write
BV453BLDC_compressor.AlrmResetMng_PWRP1.Al215_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS454Write
BV454BLDC_compressor.AlrmResetMng_PWRP1.Al216_uSafeResetTypReset type: 0=Manual - 1=Semiautomatic; Modbus CS455Write
BV455BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_EnEqualBPVlvBLDC envelope configuration - By-pass equalization solenoid valve enable; Modbus CS456Write
BV456BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_EnMopLowCompRatioBLDC envelope configuration - Enable MOP control in low compression ...; Modbus CS457Write
BV457BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_EnSpeedUpModeBLDC envelope configuration - Speed up mode enable to control ...; Modbus CS458Write
BV458BLDC_compressor.AlrmResetMng_BLDC_1.ResetTyp_BLDC_AlrmReset type: 0= Manual - 1= Semiautomatic; Modbus CS459Write
BV4011SanificationDevice.LogicDout_RWSanification device - Logic; Modbus CS460Write
BV3957En_SanificationDeviceEnable sanification device; Modbus CS461Write
BV4035PurgeCmdPurge command ( 0: NO, 1: START); Modbus CS462Write
BV4036SanificationDeviceOvld.LogicDin_RWSanification deivce overload switch - Logic; Modbus CS463Write
BV4037SanificationDeviceOvld.Enable_WSanification deivce overload switch - Enable input; Modbus CS464Write
BV4025En_OilRecovEnable BLDC oil recovery function; Modbus CS465Write
BV4288CstPrbCfg.Temp1FactOpCustom serial probe - Factor Operator - Temp1; Modbus CS466Write
BV4289CstPrbCfg.Temp2FactOpCustom serial probe - Factor Operator – Temp2; Modbus CS467Write
BV4290CstPrbCfg.Hum1FactOpCustom serial probe - Factor Operator - Hum1; Modbus CS468Write
BV4291CstPrbCfg.Hum2FactOpCustom serial probe - Factor Operator – Hum2; Modbus CS469Write
BV4292CstPrbCfg.Press1FactOpCustom serial probe - Factor Operator - Press1; Modbus CS470Write
BV4293CstPrbCfg.Press2FactOpCustom serial probe - Factor Operator – Press2; Modbus CS471Write
BV4294CstPrbCfg.Flow1FactOpCustom serial probe - Factor Operator - Flow1; Modbus CS472Write
BV4295CstPrbCfg.Flow2FactOpCustom serial probe - Factor Operator – Flow2; Modbus CS473Write
BV4342HumiSteamMng.Man_UEY.EnManHumiSteam - Manual management - Enable manual management; Modbus CS474Write
BV4343HumiSteamMng.Man_UEY.PreCleaningHumiSteam - Manual management - Manual pre cleaning; Modbus CS475Write
BV4344HumiSteamMng.Man_UEY.DrnHumiSteam - Manual management - Manual drain; Modbus CS476Write
BV4345HumiSteamMng.ResWorkHrs_UEYHumiSteam - Reset working hours; Modbus CS477Write
BV4367MainCoilCoolHeat_Din.LogicDin_RWMain coil cool/heat - digital input - Logic; Modbus CS478Write
BV4369En_FanTempRegEnable fan temperature regulation; Modbus CS479Write
BV4447GenericDin1.LogicDin_RWGeneric Din1 - digital input - Logic; Modbus CS480Write
BV4454GenericDin2.LogicDin_RWGeneric Din2 - digital input - Logic; Modbus CS481Write
BV4461GenericDin3.LogicDin_RWGeneric Din3 - digital input - Logic; Modbus CS482Write
BV4468GenericDin4.LogicDin_RWGeneric Din4 - digital input - Logic; Modbus CS483Write
BV4475GenericDin5.LogicDin_RWGeneric Din5 - digital input - Logic; Modbus CS484Write
BV4499IEC_EnManIEC: manual mode enable; Modbus CS485Write
BV4504BMS_Reg_DigitalPrbMap[1]BMS registers - Digital map – 1; Modbus CS486Write
BV4505BMS_Reg_DigitalPrbMap[2]BMS registers - Digital map – 2; Modbus CS487Write
BV4506BMS_Reg_DigitalPrbMap[3]BMS registers - Digital map – 3; Modbus CS488Write
BV4507BMS_Reg_DigitalPrbMap[4]BMS registers - Digital map – 4; Modbus CS489Write
BV4508BMS_Reg_DigitalPrbMap[5]BMS registers - Digital map – 5; Modbus CS490Write
BV4514OA_Vlv_Open.LogicDout_RWOutdoor air pre-treatment floating valve open - Logic; Modbus CS491Write
BV4515OA_Vlv_Close.LogicDout_RWOutdoor air pre-treatment floating valve close - Logic; Modbus CS492Write
BV4516OA_CoilEnManOutdoor air pre-treatment coil manual mode enable; Modbus CS493Write
BV459MainCoil_CoolHeatModeCooling/Heating coil working mode; Modbus DI001Read
BV461SupplyTemp.Enable_WSupply temperature - Enable input; Modbus DI003Read
BV462SupplyTemp.Configured_RSupply temperature - Analog input configured; Modbus DI004Read
BV463SupplyTemp.PrbOk_RSupply temperature - Probe working correctly; Modbus DI005Read
BV464SupplyTemp.Alrm_RSupply temperature - Alarm probe broken or disconnected; Modbus DI006Read
BV465SupplyHum.Enable_WSupply humidity - Enable input; Modbus DI007Read
BV466SupplyHum.Configured_RSupply humidity - Analog input configured; Modbus DI008Read
BV467SupplyHum.PrbOk_RSupply humidity - Probe working correctly; Modbus DI009Read
BV468SupplyHum.Alrm_RSupply humidity - Alarm probe broken or disconnected; Modbus DI010Read
BV469RetTemp.Enable_WReturn temperature - Enable input; Modbus DI011Read
BV470RetTemp.Configured_RReturn temperature - Analog input configured; Modbus DI012Read
BV471RetTemp.PrbOk_RReturn temperature - Probe working correctly; Modbus DI013Read
BV472RetTemp.Alrm_RReturn temperature - Alarm probe broken or disconnected; Modbus DI014Read
BV473RetHum.Enable_WReturn humidity - Enable input; Modbus DI015Read
BV474RetHum.Configured_RReturn humidity - Analog input configured; Modbus DI016Read
BV475RetHum.PrbOk_RReturn humidity - Probe working correctly; Modbus DI017Read
BV476RetHum.Alrm_RReturn humidity - Alarm probe broken or disconnected; Modbus DI018Read
BV477RoomTemp.Enable_WRoom temperature - Enable input; Modbus DI019Read
BV478RoomTemp.Configured_RRoom temperature - Analog input configured; Modbus DI020Read
BV479RoomTemp.PrbOk_RRoom temperature - Probe working correctly; Modbus DI021Read
BV480RoomTemp.Alrm_RRoom temperature - Alarm probe broken or disconnected; Modbus DI022Read
BV481RoomHum.Enable_WRoom humidity - Enable input; Modbus DI023Read
BV482RoomHum.Configured_RRoom humidity - Analog input configured; Modbus DI024Read
BV483RoomHum.PrbOk_RRoom humidity - Probe working correctly; Modbus DI025Read
BV484RoomHum.Alrm_RRoom humidity - Alarm probe broken or disconnected; Modbus DI026Read
BV485ExtTemp.Enable_WFresh air temperature - Enable input; Modbus DI027Read
BV487ExtTemp.PrbOk_RFresh air temperature - Probe working correctly; Modbus DI029Read
BV488ExtTemp.Alrm_RFresh air temperature - Alarm probe broken or disconnected; Modbus DI030Read
BV489ExtHum.Enable_WFresh air humidity - Enable input; Modbus DI031Read
BV490ExtHum.Configured_RFresh air humidity - Analog input configured; Modbus DI032Read
BV491ExtHum.PrbOk_RFresh air humidity - Probe working correctly; Modbus DI033Read
BV492ExtHum.Alrm_RFresh air humidity - Alarm probe broken or disconnected; Modbus DI034Read
BV493ExhTemp.Enable_WExhaust temperature - Enable input; Modbus DI035Read
BV494ExhTemp.Configured_RExhaust temperature - Analog input configured; Modbus DI036Read
BV495ExhTemp.PrbOk_RExhaust temperature - Probe working correctly; Modbus DI037Read
BV496ExhTemp.Alrm_RExhaust temperature - Alarm probe broken or disconnected; Modbus DI038Read
BV497ExhHum.Enable_WExhaust humidity - Enable input; Modbus DI039Read
BV498ExhHum.Configured_RExhaust humidity - Analog input configured; Modbus DI040Read
BV499ExhHum.PrbOk_RExhaust humidity - Probe working correctly; Modbus DI041Read
BV500ExhHum.Alrm_RExhaust humidity - Alarm probe broken or disconnected; Modbus DI042Read
BV501AFreezeTemp.Enable_WAntifreeze temperature - Enable input; Modbus DI043Read
BV502AFreezeTemp.Configured_RAntifreeze temperature - Analog input configured; Modbus DI044Read
BV503AFreezeTemp.PrbOk_RAntifreeze temperature - Probe working correctly; Modbus DI045Read
BV504AFreezeTemp.Alrm_RAntifreeze temperature - Alarm probe broken or disconnected; Modbus DI046Read
BV505SatTemp.Enable_WSaturation temperature - Enable input; Modbus DI047Read
BV507SatTemp.PrbOk_RSaturation temperature - Probe working correctly; Modbus DI049Read
BV508SatTemp.Alrm_RSaturation temperature - Alarm probe broken or disconnected; Modbus DI050Read
BV509SatHum.Enable_WSaturation humidity - Enable input; Modbus DI051Read
BV510SatHum.Configured_RSaturation humidity - Analog input configured; Modbus DI052Read
BV511SatHum.PrbOk_RSaturation humidity - Probe working correctly; Modbus DI053Read
BV512SatHum.Alrm_RSaturation humidity - Alarm probe broken or disconnected; Modbus DI054Read
BV513OA_Temp.Enable_WOutdoor air pre-treatment temperature - Enable input; Modbus DI055Read
BV514OA_Temp.Configured_ROutdoor air pre-treatment temperature - Analog input configured; Modbus DI056Read
BV515OA_Temp.PrbOk_ROutdoor air pre-treatment temperature - Probe working correctly; Modbus DI057Read
BV516OA_Temp.Alrm_ROutdoor air pre-treatment temperature - Alarm probe broken or disconnected; Modbus DI058Read
BV517SupplyAirP.Enable_WSupply air pressure - Enable input; Modbus DI059Read
BV518SupplyAirP.Configured_RSupply air pressure - Analog input configured; Modbus DI060Read
BV519SupplyAirP.PrbOk_RSupply air pressure - Probe working correctly; Modbus DI061Read
BV520SupplyAirP.Alrm_RSupply air pressure - Alarm probe broken or disconnected; Modbus DI062Read
BV521RetAirP.Enable_WReturn air pressure - Enable input; Modbus DI063Read
BV522RetAirP.Configured_RReturn air pressure - Analog input configured; Modbus DI064Read
BV523RetAirP.PrbOk_RReturn air pressure - Probe working correctly; Modbus DI065Read
BV524RetAirP.Alrm_RReturn air pressure - Alarm probe broken or disconnected; Modbus DI066Read
BV525AirQuality_CO2.Enable_WCO2 sensor - Enable input; Modbus DI067Read
BV526AirQuality_CO2.Configured_RCO2 sensor - Analog input configured; Modbus DI068Read
BV527AirQuality_CO2.PrbOk_RCO2 sensor - Probe working correctly; Modbus DI069Read
BV528AirQuality_CO2.Alrm_RCO2 sensor - Alarm probe broken or disconnected; Modbus DI070Read
BV529AirQuality_VOC.Enable_WVOC sensor - Enable input; Modbus DI071Read
BV530AirQuality_VOC.Configured_RVOC sensor - Analog input configured; Modbus DI072Read
BV531AirQuality_VOC.PrbOk_RVOC sensor - Probe working correctly; Modbus DI073Read
BV532AirQuality_VOC.Alrm_RVOC sensor - Alarm probe broken or disconnected; Modbus DI074Read
BV533DscgP.Enable_WDischarge pressure - Enable input; Modbus DI075Read
BV534DscgP.Configured_RDischarge pressure - Analog input configured; Modbus DI076Read
BV535DscgP.PrbOk_RDischarge pressure - Probe working correctly; Modbus DI077Read
BV536DscgP.Alrm_RDischarge pressure - Alarm probe broken or disconnected; Modbus DI078Read
BV537DscgT.Enable_WDischarge temperature - Enable input; Modbus DI079Read
BV538DscgT.Configured_RDischarge temperature - Analog input configured; Modbus DI080Read
BV539DscgT.PrbOk_RDischarge temperature - Probe working correctly; Modbus DI081Read
BV540DscgT.Alrm_RDischarge temperature - Alarm probe broken or disconnected; Modbus DI082Read
BV541SuctP.Enable_WSuction pressure - Enable input; Modbus DI083Read
BV542SuctP.Configured_RSuction pressure - Analog input configured; Modbus DI084Read
BV543SuctP.PrbOk_RSuction pressure - Probe working correctly; Modbus DI085Read
BV544SuctP.Alrm_RSuction pressure - Alarm probe broken or disconnected; Modbus DI086Read
BV545SuctT.Enable_WSuction temperature - Enable input; Modbus DI087Read
BV546SuctT.Configured_RSuction temperature - Analog input configured; Modbus DI088Read
BV547SuctT.PrbOk_RSuction temperature - Probe working correctly; Modbus DI089Read
BV548SuctT.Alrm_RSuction temperature - Alarm probe broken or disconnected; Modbus DI090Read
BV549OA_CoilWaterTemp.Enable_WOutdoor air pre-treatment coil water temperature - Enable input; Modbus DI091Read
BV550OA_CoilWaterTemp.Configured_ROutdoor air pre-treatment coil water temperature - Analog input configured; Modbus DI092Read
BV551OA_CoilWaterTemp.PrbOk_ROutdoor air pre-treatment coil water temperature - Probe working correctly; Modbus DI093Read
BV552OA_CoilWaterTemp.Alrm_ROutdoor air pre-treatment coil water temperature - Alarm probe broken ...; Modbus DI094Read
BV553PreHeatCoilWaterTemp.Enable_WPreheat coil water temperature - Enable input; Modbus DI095Read
BV554PreHeatCoilWaterTemp.Configured_RPreheat coil water temperature - Analog input configured; Modbus DI096Read
BV555PreHeatCoilWaterTemp.PrbOk_RPreheat coil water temperature - Probe working correctly; Modbus DI097Read
BV556PreHeatCoilWaterTemp.Alrm_RPreheat coil water temperature - Alarm probe broken or disconnected; Modbus DI098Read
BV557MainCoilWaterTemp.Enable_WMain coil water temperature - Enable input; Modbus DI099Read
BV558MainCoilWaterTemp.Configured_RMain coil water temperature - Analog input configured; Modbus DI100Read
BV560MainCoilWaterTemp.Alrm_RMain coil water temperature - Alarm probe broken or disconnected; Modbus DI102Read
BV561ReHeatCoilWaterTemp.Enable_WPostheat coil water temperature - Enable input; Modbus DI103Read
BV562ReHeatCoilWaterTemp.Configured_RPostheat coil water temperature - Analog input configured; Modbus DI104Read
BV563ReHeatCoilWaterTemp.PrbOk_RPostheat coil water temperature - Probe working correctly; Modbus DI105Read
BV564ReHeatCoilWaterTemp.Alrm_RPostheat coil water temperature - Alarm probe broken or disconnected; Modbus DI106Read
BV565AuxPrb_1.Enable_WAuxiliary probe 1 - Enable input; Modbus DI107Read
BV566AuxPrb_1.Configured_RAuxiliary probe 1 - Analog input configured; Modbus DI108Read
BV567AuxPrb_1.PrbOk_RAuxiliary probe 1 - Probe working correctly; Modbus DI109Read
BV568AuxPrb_1.Alrm_RAuxiliary probe 1 - Alarm probe broken or disconnected; Modbus DI110Read
BV569AuxPrb_2.Enable_WAuxiliary probe 2 - Enable input; Modbus DI111Read
BV570AuxPrb_2.Configured_RAuxiliary probe 2 - Analog input configured; Modbus DI112Read
BV571AuxPrb_2.PrbOk_RAuxiliary probe 2 - Probe working correctly; Modbus DI113Read
BV572AuxPrb_2.Alrm_RAuxiliary probe 2 - Alarm probe broken or disconnected; Modbus DI114Read
BV573AuxPrb_3.Enable_WAuxiliary probe 3 - Enable input; Modbus DI115Read
BV574AuxPrb_3.Configured_RAuxiliary probe 3 - Analog input configured; Modbus DI116Read
BV575AuxPrb_3.PrbOk_RAuxiliary probe 3 - Probe working correctly; Modbus DI117Read
BV576AuxPrb_3.Alrm_RAuxiliary probe 3 - Alarm probe broken or disconnected; Modbus DI118Read
BV577AuxPrb_4.Enable_WAuxiliary probe 4 - Enable input; Modbus DI119Read
BV578AuxPrb_4.Configured_RAuxiliary probe 4 - Analog input configured; Modbus DI120Read
BV579AuxPrb_4.PrbOk_RAuxiliary probe 4 - Probe working correctly; Modbus DI121Read
BV580AuxPrb_4.Alrm_RAuxiliary probe 4 - Alarm probe broken or disconnected; Modbus DI122Read
BV581Ain_SetP.Enable_WSetpoint by AIN - Enable input; Modbus DI123Read
BV582Ain_SetP.Configured_RSetpoint by AIN - Analog input configured; Modbus DI124Read
BV583Ain_SetP.PrbOk_RSetpoint by AIN - Probe working correctly; Modbus DI125Read
BV584Ain_SetP.Alrm_RSetpoint by AIN - Alarm probe broken or disconnected; Modbus DI126Read
BV585SupplyRecoveryTemp.Enable_WSupply recovery temperature - Enable input; Modbus DI127Read
BV586SupplyRecoveryTemp.Configured_RSupply recovery temperature - Analog input configured; Modbus DI128Read
BV587SupplyRecoveryTemp.PrbOk_RSupply recovery temperature - Probe working correctly; Modbus DI129Read
BV588SupplyRecoveryTemp.Alrm_RSupply recovery temperature - Alarm probe broken or disconnected; Modbus DI130Read
BV589RetRecoveryTemp.Enable_WReturn recovery temperature - Enable input; Modbus DI131Read
BV590RetRecoveryTemp.Configured_RReturn recovery temperature - Analog input configured; Modbus DI132Read
BV591RetRecoveryTemp.PrbOk_RReturn recovery temperature - Probe working correctly; Modbus DI133Read
BV592RetRecoveryTemp.Alrm_RReturn recovery temperature - Alarm probe broken or disconnected; Modbus DI134Read
BV593HepaFilt_1.Enable_WHepa filter 1 - Enable input; Modbus DI135Read
BV594HepaFilt_1.Configured_RHepa filter 1 - Analog input configured; Modbus DI136Read
BV595HepaFilt_1.PrbOk_RHepa filter 1 - Probe working correctly; Modbus DI137Read
BV596HepaFilt_1.Alrm_RHepa filter 1 - Alarm probe broken or disconnected; Modbus DI138Read
BV597HepaFilt_2.Enable_WHepa filter 2 - Enable input; Modbus DI139Read
BV598HepaFilt_2.Configured_RHepa filter 2 - Analog input configured; Modbus DI140Read
BV599HepaFilt_2.PrbOk_RHepa filter 2 - Probe working correctly; Modbus DI141Read
BV600HepaFilt_2.Alrm_RHepa filter 2 - Alarm probe broken or disconnected; Modbus DI142Read
BV601SupplyAirFlwSw.Val_Hw_RSupply air flow switch - Value reads from board; Modbus DI143Read
BV602SupplyAirFlwSw.Enable_WSupply air flow switch - Enable input; Modbus DI144Read
BV603SupplyAirFlwSw.Configured_RSupply air flow switch - Digital input configured; Modbus DI145Read
BV604SupplyAirFlwSw.Val_RSupply air flow switch; Modbus DI146Read
BV605RetAirFlwSw.Val_Hw_RReturn air flow switch - Value reads from board; Modbus DI147Read
BV606RetAirFlwSw.Enable_WReturn air flow switch - Enable input; Modbus DI148Read
BV607RetAirFlwSw.Configured_RReturn air flow switch - Digital input configured; Modbus DI149Read
BV608RetAirFlwSw.Val_RReturn air flow switch; Modbus DI150Read
BV609AirFlwSw.Val_Hw_RAir flow switch - Value reads from board; Modbus DI151Read
BV610AirFlwSw.Enable_WAir flow switch - Enable input; Modbus DI152Read
BV611AirFlwSw.Configured_RAir flow switch - Digital input configured; Modbus DI153Read
BV612AirFlwSw.Val_RAir flow switch; Modbus DI154Read
BV613AFreezeSw.Val_Hw_RAntifreeze switch - Value reads from board; Modbus DI155Read
BV614AFreezeSw.Enable_WAntifreeze switch - Enable input; Modbus DI156Read
BV615AFreezeSw.Configured_RAntifreeze switch - Digital input configured; Modbus DI157Read
BV616AFreezeSw.Val_RAntifreeze switch; Modbus DI158Read
BV617RemOnOff.Val_Hw_RRemote On/Off - Value reads from board; Modbus DI159Read
BV618RemOnOff.Enable_WRemote On/Off - Enable input; Modbus DI160Read
BV619RemOnOff.Configured_RRemote On/Off - Digital input configured; Modbus DI161Read
BV620RemOnOff.Val_RRemote On/Off; Modbus DI162Read
BV621SupplyFanOvld_1.Val_Hw_RSupply fan overload 1 - Value reads from board; Modbus DI163Read
BV622SupplyFanOvld_1.Enable_WSupply fan overload 1 - Enable input; Modbus DI164Read
BV623SupplyFanOvld_1.Configured_RSupply fan overload 1 - Digital input configured; Modbus DI165Read
BV624SupplyFanOvld_1.Val_RSupply fan overload 1; Modbus DI166Read
BV625RetFanOvld_1.Val_Hw_RReturn fan overload 1 - Value reads from board; Modbus DI167Read
BV626RetFanOvld_1.Enable_WReturn fan overload 1 - Enable input; Modbus DI168Read
BV627RetFanOvld_1.Configured_RReturn fan overload 1 - Digital input configured; Modbus DI169Read
BV628RetFanOvld_1.Val_RReturn fan overload 1; Modbus DI170Read
BV629SupplyFanOvld_2.Val_Hw_RSupply fan overload 2 - Value reads from board; Modbus DI171Read
BV630SupplyFanOvld_2.Enable_WSupply fan overload 2 - Enable input; Modbus DI172Read
BV631SupplyFanOvld_2.Configured_RSupply fan overload 2 - Digital input configured; Modbus DI173Read
BV632SupplyFanOvld_2.Val_RSupply fan overload 2; Modbus DI174Read
BV633RetFanOvld_2.Val_Hw_RReturn fan overload 2 - Value reads from board; Modbus DI175Read
BV634RetFanOvld_2.Enable_WReturn fan overload 2 - Enable input; Modbus DI176Read
BV635RetFanOvld_2.Configured_RReturn fan overload 2 - Digital input configured; Modbus DI177Read
BV636RetFanOvld_2.Val_RReturn fan overload 2; Modbus DI178Read
BV637SupplyFanInvAlrm.Val_Hw_RSupply inverter alarm - Value reads from board; Modbus DI179Read
BV638SupplyFanInvAlrm.Enable_WSupply inverter alarm - Enable input; Modbus DI180Read
BV639SupplyFanInvAlrm.Configured_RSupply inverter alarm - Digital input configured; Modbus DI181Read
BV640SupplyFanInvAlrm.Val_RSupply inverter alarm; Modbus DI182Read
BV641RetFanInvAlrm.Val_Hw_RReturn inverter alarm - Value reads from board; Modbus DI183Read
BV642RetFanInvAlrm.Enable_WReturn inverter alarm - Enable input; Modbus DI184Read
BV643RetFanInvAlrm.Configured_RReturn inverter alarm - Digital input configured; Modbus DI185Read
BV644RetFanInvAlrm.Val_RReturn inverter alarm; Modbus DI186Read
BV645FansOvld.Val_Hw_RFans overload - Value reads from board; Modbus DI187Read
BV646FansOvld.Enable_WFans overload - Enable input; Modbus DI188Read
BV647FansOvld.Configured_RFans overload - Digital input configured; Modbus DI189Read
BV648FansOvld.Val_RFans overload; Modbus DI190Read
BV649CompOvld.Val_Hw_RCompressor overload - Value reads from board; Modbus DI191Read
BV650CompOvld.Enable_WCompressor overload - Enable input; Modbus DI192Read
BV651CompOvld.Configured_RCompressor overload - Digital input configured; Modbus DI193Read
BV652CompOvld.Val_RCompressor overload; Modbus DI194Read
BV653HiPSw.Val_Hw_RHigh discharge pressure switch - Value reads from board; Modbus DI195Read
BV654HiPSw.Enable_WHigh discharge pressure switch - Enable input; Modbus DI196Read
BV655HiPSw.Configured_RHigh discharge pressure switch - Digital input configured; Modbus DI197Read
BV656HiPSw.Val_RHigh discharge pressure switch; Modbus DI198Read
BV657LowPSw.Val_Hw_RLow suction pressure switch - Value reads from board; Modbus DI199Read
BV658LowPSw.Enable_WLow suction pressure switch - Enable input; Modbus DI200Read
BV659LowPSw.Configured_RLow suction pressure switch - Digital input configured; Modbus DI201Read
BV660LowPSw.Val_RLow suction pressure switch; Modbus DI202Read
BV661RecoveryOvld.Val_Hw_RThermal wheel overload - Value reads from board; Modbus DI203Read
BV662RecoveryOvld.Enable_WThermal wheel overload - Enable input; Modbus DI204Read
BV663RecoveryOvld.Configured_RThermal wheel overload - Digital input configured; Modbus DI205Read
BV664RecoveryOvld.Val_RThermal wheel overload; Modbus DI206Read
BV665SrsAlrm.Val_Hw_RSerious alarm - Value reads from board; Modbus DI207Read
BV666SrsAlrm.Enable_WSerious alarm - Enable input; Modbus DI208Read
BV667SrsAlrm.Configured_RSerious alarm - Digital input configured; Modbus DI209Read
BV668SrsAlrm.Val_RSerious alarm; Modbus DI210Read
BV669GenAlrm.Val_Hw_RGeneric alarm - Value reads from board; Modbus DI211Read
BV670GenAlrm.Enable_WGeneric alarm - Enable input; Modbus DI212Read
BV671GenAlrm.Configured_RGeneric alarm - Digital input configured; Modbus DI213Read
BV672GenAlrm.Val_RGeneric alarm; Modbus DI214Read
BV673GenWarning.Val_Hw_RGeneric warning - Value reads from board; Modbus DI215Read
BV674GenWarning.Enable_WGeneric warning - Enable input; Modbus DI216Read
BV675GenWarning.Configured_RGeneric warning - Digital input configured; Modbus DI217Read
BV676GenWarning.Val_RGeneric warning; Modbus DI218Read
BV677FiltAlrm.Val_Hw_RFilters alarm - Value reads from board; Modbus DI219Read
BV678FiltAlrm.Enable_WFilters alarm - Enable input; Modbus DI220Read
BV679FiltAlrm.Configured_RFilters alarm - Digital input configured; Modbus DI221Read
BV680FiltAlrm.Val_RFilters alarm; Modbus DI222Read
BV681SupplyFiltAlrm_1.Val_Hw_RSupply filter alarm 1 - Value reads from board; Modbus DI223Read
BV682SupplyFiltAlrm_1.Enable_WSupply filter alarm 1 - Enable input; Modbus DI224Read
BV683SupplyFiltAlrm_1.Configured_RSupply filter alarm 1 - Digital input configured; Modbus DI225Read
BV684SupplyFiltAlrm_1.Val_RSupply filter alarm 1; Modbus DI226Read
BV685SupplyFiltAlrm_2.Val_Hw_RSupply filter alarm 2 - Value reads from board; Modbus DI227Read
BV686SupplyFiltAlrm_2.Enable_WSupply filter alarm 2 - Enable input; Modbus DI228Read
BV687SupplyFiltAlrm_2.Configured_RSupply filter alarm 2 - Digital input configured; Modbus DI229Read
BV688SupplyFiltAlrm_2.Val_RSupply filter alarm 2; Modbus DI230Read
BV689RetFiltAlrm.Val_Hw_RReturn filter alarm - Value reads from board; Modbus DI231Read
BV690RetFiltAlrm.Enable_WReturn filter alarm - Enable input; Modbus DI232Read
BV691RetFiltAlrm.Configured_RReturn filter alarm - Digital input configured; Modbus DI233Read
BV692RetFiltAlrm.Val_RReturn filter alarm; Modbus DI234Read
BV693HumAlrm.Val_Hw_RHumidifier alarm - Value reads from board; Modbus DI235Read
BV694HumAlrm.Enable_WHumidifier alarm - Enable input; Modbus DI236Read
BV695HumAlrm.Configured_RHumidifier alarm - Digital input configured; Modbus DI237Read
BV696HumAlrm.Val_RHumidifier alarm; Modbus DI238Read
BV697MainCoilPmp1_Ovld.Val_Hw_RMain coil pump 1 overload - Value reads from board; Modbus DI239Read
BV698MainCoilPmp1_Ovld.Enable_WMain coil pump 1 overload - Enable input; Modbus DI240Read
BV699MainCoilPmp1_Ovld.Configured_RMain coil pump 1 overload - Digital input configured; Modbus DI241Read
BV700MainCoilPmp1_Ovld.Val_RMain coil pump 1 overload; Modbus DI242Read
BV701MainCoilPmp2_Ovld.Val_Hw_RMain coil pump 2 overload - Value reads from board; Modbus DI243Read
BV702MainCoilPmp2_Ovld.Enable_WMain coil pump 2 overload - Enable input; Modbus DI244Read
BV703MainCoilPmp2_Ovld.Configured_RMain coil pump 2 overload - Digital input configured; Modbus DI245Read
BV704MainCoilPmp2_Ovld.Val_RMain coil pump 2 overload; Modbus DI246Read
BV705ReHeatCoilPmp1_Ovld.Val_Hw_RReHeat coil pump 1 overload - Value reads from board; Modbus DI247Read
BV706ReHeatCoilPmp1_Ovld.Enable_WReHeat coil pump 1 overload - Enable input; Modbus DI248Read
BV707ReHeatCoilPmp1_Ovld.Configured_RReHeat coil pump 1 overload - Digital input configured; Modbus DI249Read
BV708ReHeatCoilPmp1_Ovld.Val_RReHeat coil pump 1 overload; Modbus DI250Read
BV709ReHeatCoilPmp2_Ovld.Val_Hw_RReHeat coil pump 2 overload - Value reads from board; Modbus DI251Read
BV710ReHeatCoilPmp2_Ovld.Enable_WReHeat coil pump 2 overload - Enable input; Modbus DI252Read
BV711ReHeatCoilPmp2_Ovld.Configured_RReHeat coil pump 2 overload - Digital input configured; Modbus DI253Read
BV712ReHeatCoilPmp2_Ovld.Val_RReHeat coil pump 2 overload; Modbus DI254Read
BV713PreHeatCoilPmp1_Ovld.Val_Hw_RPreHeat coil pump 1 overload - Value reads from board; Modbus DI255Read
BV714PreHeatCoilPmp1_Ovld.Enable_WPreHeat coil pump 1 overload - Enable input; Modbus DI256Read
BV715PreHeatCoilPmp1_Ovld.Configured_RPreHeat coil pump 1 overload - Digital input configured; Modbus DI257Read
BV716PreHeatCoilPmp1_Ovld.Val_RPreHeat coil pump 1 overload; Modbus DI258Read
BV717PreHeatCoilPmp2_Ovld.Val_Hw_RPreHeat coil pump 2 overload - Value reads from board; Modbus DI259Read
BV718PreHeatCoilPmp2_Ovld.Enable_WPreHeat coil pump 2 overload - Enable input; Modbus DI260Read
BV719PreHeatCoilPmp2_Ovld.Configured_RPreHeat coil pump 2 overload - Digital input configured; Modbus DI261Read
BV720PreHeatCoilPmp2_Ovld.Val_RPreHeat coil pump 2 overload; Modbus DI262Read
BV721OA_CoilPmp1_Ovld.Val_Hw_ROutdoor air pre-treatment coil pump 1 overload - Value reads ...; Modbus DI263Read
BV722OA_CoilPmp1_Ovld.Enable_WOutdoor air pre-treatment coil pump 1 overload - Enable input; Modbus DI264Read
BV723OA_CoilPmp1_Ovld.Configured_ROutdoor air pre-treatment coil pump 1 overload - Digital input configured; Modbus DI265Read
BV724OA_CoilPmp1_Ovld.Val_ROutdoor air pre-treatment coil pump 2 overload - Value reads ...; Modbus DI266Read
BV725OA_CoilPmp2_Ovld.Val_Hw_ROutdoor air pre-treatment coil pump 2 overload - Value reads ...; Modbus DI267Read
BV726OA_CoilPmp2_Ovld.Enable_WOutdoor air pre-treatment coil pump 2 overload - Enable input; Modbus DI268Read
BV727OA_CoilPmp2_Ovld.Configured_ROutdoor air pre-treatment coil pump 2 overload - Digital input configured; Modbus DI269Read
BV728OA_CoilPmp2_Ovld.Val_ROutdoor air pre-treatment coil pump 2 overload; Modbus DI270Read
BV729FreshAirDampSw.Val_Hw_RFresh air damper switch - Value reads from board; Modbus DI271Read
BV730FreshAirDampSw.Enable_WFresh air damper switch - Enable input; Modbus DI272Read
BV731FreshAirDampSw.Configured_RFresh air damper switch - Digital input configured; Modbus DI273Read
BV732FreshAirDampSw.Val_RFresh air damper switch; Modbus DI274Read
BV733SupplyDamperSw.Val_Hw_RSupply damper switch - Value reads from board; Modbus DI275Read
BV734SupplyDamperSw.Enable_WSupply damper switch - Enable input; Modbus DI276Read
BV735SupplyDamperSw.Configured_RSupply damper switch - Digital input configured; Modbus DI277Read
BV736SupplyDamperSw.Val_RSupply damper switch; Modbus DI278Read
BV737RetDampSw.Val_Hw_RReturn damper switch - Value reads from board; Modbus DI279Read
BV738RetDampSw.Enable_WReturn damper switch - Enable input; Modbus DI280Read
BV739RetDampSw.Configured_RReturn damper switch - Digital input configured; Modbus DI281Read
BV740RetDampSw.Val_RReturn damper switch; Modbus DI282Read
BV741MainCoilFlwSw.Val_Hw_RMain coil flow switch - Value reads from board; Modbus DI283Read
BV742MainCoilFlwSw.Enable_WMain coil flow switch - Enable input; Modbus DI284Read
BV743MainCoilFlwSw.Configured_RMain coil flow switch - Digital input configured; Modbus DI285Read
BV744MainCoilFlwSw.Val_RMain coil flow switch; Modbus DI286Read
BV745PreHeatCoilFlwSw.Val_Hw_RPre-heating coil flow switch - Value reads from board; Modbus DI287Read
BV746PreHeatCoilFlwSw.Enable_WPre-heating coil flow switch - Enable input; Modbus DI288Read
BV747PreHeatCoilFlwSw.Configured_RPre-heating coil flow switch - Digital input configured; Modbus DI289Read
BV748PreHeatCoilFlwSw.Val_RPre-heating coil flow switch; Modbus DI290Read
BV749ReHeatCoilFlwSw.Val_Hw_RPost-Heating coil flow switch - Value reads from board; Modbus DI291Read
BV750ReHeatCoilFlwSw.Enable_WPost-Heating coil flow switch - Enable input; Modbus DI292Read
BV751ReHeatCoilFlwSw.Configured_RPost-Heating coil flow switch - Digital input configured; Modbus DI293Read
BV752ReHeatCoilFlwSw.Val_RPost-Heating coil flow switch; Modbus DI294Read
BV753OA_CoilFlwSw.Val_Hw_ROutdoor air pre-treatment coil flow switch - Value reads from board; Modbus DI295Read
BV754OA_CoilFlwSw.Enable_WOutdoor air pre-treatment coil flow switch - Enable input; Modbus DI296Read
BV755OA_CoilFlwSw.Configured_ROutdoor air pre-treatment coil flow switch - Digital input configured; Modbus DI297Read
BV756OA_CoilFlwSw.Val_ROutdoor air pre-treatment coil flow switch; Modbus DI298Read
BV757RecoveryClogged.Val_Hw_RRecovery clogged - Value reads from board; Modbus DI299Read
BV758RecoveryClogged.Enable_WRecovery clogged - Enable input; Modbus DI300Read
BV759RecoveryClogged.Configured_RRecovery clogged - Digital input configured; Modbus DI301Read
BV760RecoveryClogged.Val_RRecovery clogged; Modbus DI302Read
BV761ReHeatAlrm.Val_Hw_RRe-heating alarm - Value reads from board; Modbus DI303Read
BV762ReHeatAlrm.Enable_WRe-heating alarm - Enable input; Modbus DI304Read
BV763ReHeatAlrm.Configured_RRe-heating alarm - Digital input configured; Modbus DI305Read
BV764ReHeatAlrm.Val_RRe-heating alarm; Modbus DI306Read
BV765PreHeatAlrm.Val_Hw_RPre-heating alarm - Value reads from board; Modbus DI307Read
BV766PreHeatAlrm.Enable_WPre-heating alarm - Enable input; Modbus DI308Read
BV767PreHeatAlrm.Configured_RPre-heating alarm - Digital input configured; Modbus DI309Read
BV768PreHeatAlrm.Val_RPre-heating alarm; Modbus DI310Read
BV769MainHeatCoilAlrm.Val_Hw_RMain coil alarm - Value reads from board; Modbus DI311Read
BV770MainHeatCoilAlrm.Enable_WMain coil alarm - Enable input; Modbus DI312Read
BV771MainHeatCoilAlrm.Configured_RMain coil alarm - Digital input configured; Modbus DI313Read
BV772MainHeatCoilAlrm.Val_RMain coil alarm; Modbus DI314Read
BV773OA_CoilAlrm.Val_Hw_ROutdoor air pre-treatment alarm - Value reads from board; Modbus DI315Read
BV774OA_CoilAlrm.Enable_WOutdoor air pre-treatment alarm - Enable input; Modbus DI316Read
BV775OA_CoilAlrm.Configured_ROutdoor air pre-treatment alarm - Digital input configured; Modbus DI317Read
BV776OA_CoilAlrm.Val_ROutdoor air pre-treatment alarm; Modbus DI318Read
BV777DoorSw.Val_Hw_RDoor Switch - Value reads from board; Modbus DI319Read
BV778DoorSw.Enable_WDoor Switch - Enable input; Modbus DI320Read
BV779DoorSw.Configured_RDoor Switch - Digital input configured; Modbus DI321Read
BV780DoorSw.Val_RDoor Switch; Modbus DI322Read
BV781FireSmokeAlrm.Val_Hw_RFire/Smoke alarm - Value reads from board; Modbus DI323Read
BV782FireSmokeAlrm.Enable_WFire/Smoke alarm - Enable input; Modbus DI324Read
BV783FireSmokeAlrm.Configured_RFire/Smoke alarm - Digital input configured; Modbus DI325Read
BV784FireSmokeAlrm.Val_RFire/Smoke alarm; Modbus DI326Read
BV785FiremanOverrideSw.Val_Hw_RFireman override switch - Value reads from board; Modbus DI327Read
BV786FiremanOverrideSw.Enable_WFireman override switch - Enable input; Modbus DI328Read
BV787FiremanOverrideSw.Configured_RFireman override switch - Digital input configured; Modbus DI329Read
BV788FiremanOverrideSw.Val_RFireman override switch; Modbus DI330Read
BV789SummerWinterModeByDin.Val_Hw_RSummer/Winter mode by digital input - Value reads from board; Modbus DI331Read
BV790SummerWinterModeByDin.Enable_WSummer/Winter mode by digital input - Enable input; Modbus DI332Read
BV791SummerWinterModeByDin.Configured_RSummer/Winter mode by digital input - Configured; Modbus DI333Read
BV792SummerWinterModeByDin.Val_RSummer/Winter mode by digital input; Modbus DI334Read
BV793Din_SetP.Val_Hw_RSetpoint by digital input - Value reads from board; Modbus DI335Read
BV794Din_SetP.Enable_WSetpoint by digital input - Enable input; Modbus DI336Read
BV795Din_SetP.Configured_RSetpoint by digital input - Digital input configured; Modbus DI337Read
BV796Din_SetP.Val_RSetpoint by digital input; Modbus DI338Read
BV797Eco_Mode.Val_Hw_REco mode - Value reads from board; Modbus DI339Read
BV798Eco_Mode.Enable_WEco mode - Enable input; Modbus DI340Read
BV799Eco_Mode.Configured_REco mode - Digital input configured; Modbus DI341Read
BV800Eco_Mode.Val_REco mode; Modbus DI342Read
BV801PreComf_Mode.Val_Hw_RPrecomfort mode - Value reads from board; Modbus DI343Read
BV802PreComf_Mode.Enable_WPrecomfort mode - Enable input; Modbus DI344Read
BV803PreComf_Mode.Configured_RPrecomfort mode - Digital input configured; Modbus DI345Read
BV804PreComf_Mode.Val_RPrecomfort mode; Modbus DI346Read
BV805Comf_Mode.Val_Hw_RComfort mode - Value reads from board; Modbus DI347Read
BV806Comf_Mode.Enable_WComfort mode - Enable input; Modbus DI348Read
BV807Comf_Mode.Configured_RComfort mode - Digital input configured; Modbus DI349Read
BV808Comf_Mode.Val_RComfort mode; Modbus DI350Read
BV809AuxDin_1.Val_Hw_RAuxiliary digital input 1 - Value reads from board; Modbus DI351Read
BV810AuxDin_1.Enable_WAuxiliary digital input 1 - Enable input; Modbus DI352Read
BV811AuxDin_1.Configured_RAuxiliary digital input 1 - Digital input configured; Modbus DI353Read
BV812AuxDin_1.Val_RAuxiliary digital input 1; Modbus DI354Read
BV813AuxDin_2.Val_Hw_RAuxiliary digital input 2 - Value reads from board; Modbus DI355Read
BV814AuxDin_2.Enable_WAuxiliary digital input 2 - Enable input; Modbus DI356Read
BV815AuxDin_2.Configured_RAuxiliary digital input 2 - Digital input configured; Modbus DI357Read
BV816AuxDin_2.Val_RAuxiliary digital input 2; Modbus DI358Read
BV817AuxDin_3.Val_Hw_RAuxiliary digital input 3 - Value reads from board; Modbus DI359Read
BV818AuxDin_3.Enable_WAuxiliary digital input 3 - Enable input; Modbus DI360Read
BV819AuxDin_3.Configured_RAuxiliary digital input 3 - Digital input configured; Modbus DI361Read
BV820AuxDin_3.Val_RAuxiliary digital input 3; Modbus DI362Read
BV821AuxDin_4.Val_Hw_RAuxiliary digital input 4 - Value reads from board; Modbus DI363Read
BV822AuxDin_4.Enable_WAuxiliary digital input 4 - Enable input; Modbus DI364Read
BV823AuxDin_4.Configured_RAuxiliary digital input 4 - Digital input configured; Modbus DI365Read
BV824AuxDin_4.Val_RAuxiliary digital input 4; Modbus DI366Read
BV825DfrHeatExch_Din.Val_Hw_RHeat exchanger defrost by Din - Value reads from board; Modbus DI367Read
BV826DfrHeatExch_Din.Enable_WHeat exchanger defrost by Din - Enable input; Modbus DI368Read
BV827DfrHeatExch_Din.Configured_RHeat exchanger defrost by Din - Digital input configured; Modbus DI369Read
BV828DfrHeatExch_Din.Val_RHeat exchanger defrost by Din; Modbus DI370Read
BV830BypassDamp_Dout.Val_WBypass damper; Modbus DI372Read
BV831BypassDamp_Dout.Enable_WBypass damper - Enable output; Modbus DI373Read
BV832BypassDamp_Dout.Configured_RBypass damper - Output configurated; Modbus DI374Read
BV833BypassDamp_Open.Val_Hw_RBypass damper floating (open) - Hardware value writes from board; Modbus DI375Read
BV834BypassDamp_Open.Val_WBypass damper floating (open); Modbus DI376Read
BV835BypassDamp_Open.Enable_WBypass damper floating (open) - Enable output; Modbus DI377Read
BV836BypassDamp_Open.Configured_RBypass damper floating (open) - Output configurated; Modbus DI378Read
BV837BypassDamp_Close.Val_Hw_RBypass damper floating (close) - Hardware value writes from board; Modbus DI379Read
BV838BypassDamp_Close.Val_WBypass damper floating (close); Modbus DI380Read
BV839BypassDamp_Close.Enable_WBypass damper floating (close) - Enable output; Modbus DI381Read
BV840BypassDamp_Close.Configured_RBypass damper floating (close) - Output configurated; Modbus DI382Read
BV841FreshAirDamp_Dout.Val_Hw_RFresh air damper - Hardware value writes from board; Modbus DI383Read
BV843FreshAirDamp_Dout.Enable_WFresh air damper - Enable output; Modbus DI385Read
BV844FreshAirDamp_Dout.Configured_RFresh air damper - Output configurated; Modbus DI386Read
BV846ExhAirDamp_Dout.Val_WExhaust air damper; Modbus DI388Read
BV847ExhAirDamp_Dout.Enable_WExhaust air damper - Enable output; Modbus DI389Read
BV848ExhAirDamp_Dout.Configured_RExhaust air damper - Output configurated; Modbus DI390Read
BV850MixingDamp_Dout.Val_WMixing damper; Modbus DI392Read
BV851MixingDamp_Dout.Enable_WMixing damper - Enable output; Modbus DI393Read
BV852MixingDamp_Dout.Configured_RMixing damper - Output configurated; Modbus DI394Read
BV853SupplyAirDamp_Dout.Val_Hw_RSupply air damper - Hardware value writes from board; Modbus DI395Read
BV854SupplyAirDamp_Dout.Val_WSupply air damper; Modbus DI396Read
BV855SupplyAirDamp_Dout.Enable_WSupply air damper - Enable output; Modbus DI397Read
BV856SupplyAirDamp_Dout.Configured_RSupply air damper - Output configurated; Modbus DI398Read
BV857RetAirDamp_Dout.Val_Hw_RReturn air damper - Hardware value writes from board; Modbus DI399Read
BV858RetAirDamp_Dout.Val_WReturn air damper; Modbus DI400Read
BV859RetAirDamp_Dout.Enable_WReturn air damper - Enable output; Modbus DI401Read
BV860RetAirDamp_Dout.Configured_RReturn air damper - Output configurated; Modbus DI402Read
BV861MixingDamp_Open.Val_Hw_RMixing damper floating (OPEN) - Hardware value writes from board; Modbus DI403Read
BV862MixingDamp_Open.Val_WMixing damper floating (OPEN); Modbus DI404Read
BV863MixingDamp_Open.Enable_WMixing damper floating (OPEN) - Enable output; Modbus DI405Read
BV864MixingDamp_Open.Configured_RMixing damper floating (OPEN) - Output configurated; Modbus DI406Read
BV865MixingDamp_Close.Val_Hw_RMixing damper floating (CLOSE) - Hardware value writes from board; Modbus DI407Read
BV866MixingDamp_Close.Val_WMixing damper floating (CLOSE); Modbus DI408Read
BV867MixingDamp_Close.Enable_WMixing damper floating (CLOSE) - Enable output; Modbus DI409Read
BV868MixingDamp_Close.Configured_RMixing damper floating (CLOSE) - Output configurated; Modbus DI410Read
BV870SupplyFan_Dout.Val_WSupply fan; Modbus DI412Read
BV871SupplyFan_Dout.Enable_WSupply fan - Enable output; Modbus DI413Read
BV872SupplyFan_Dout.Configured_RSupply fan - Output configurated; Modbus DI414Read
BV874RetFan_Dout.Val_WReturn fan; Modbus DI416Read
BV875RetFan_Dout.Enable_WReturn fan - Enable output; Modbus DI417Read
BV876RetFan_Dout.Configured_RReturn fan - Output configurated; Modbus DI418Read
BV877SupplyFan2_Dout.Val_Hw_RSupply fan 2 - Hardware value writes from board; Modbus DI419Read
BV878SupplyFan2_Dout.Val_WSupply fan 2; Modbus DI420Read
BV879SupplyFan2_Dout.Enable_WSupply fan 2 - Enable output; Modbus DI421Read
BV880SupplyFan2_Dout.Configured_RSupply fan 2 - Output configurated; Modbus DI422Read
BV881RetFan2_Dout.Val_Hw_RReturn fan 2 - Hardware value writes from board; Modbus DI423Read
BV882RetFan2_Dout.Val_WReturn fan 2; Modbus DI424Read
BV883RetFan2_Dout.Enable_WReturn fan 2 - Enable output; Modbus DI425Read
BV884RetFan2_Dout.Configured_RReturn fan 2 - Output configurated; Modbus DI426Read
BV886Comp_Dout.Val_WCompressor; Modbus DI428Read
BV887Comp_Dout.Enable_WCompressor - Enable output; Modbus DI429Read
BV888Comp_Dout.Configured_RCompressor - Output configurated; Modbus DI430Read
BV889RevVlv.Val_Hw_RReverse valve - Hardware value writes from board; Modbus DI431Read
BV890RevVlv.Val_WReverse valve; Modbus DI432Read
BV891RevVlv.Enable_WReverse valve - Enable output; Modbus DI433Read
BV892RevVlv.Configured_RReverse valve - Output configurated; Modbus DI434Read
BV893UnitOnOff_Dout.Val_Hw_RUnit status (On/Off ) - Hardware value writes from board; Modbus DI435Read
BV894UnitOnOff_Dout.Val_WUnit status (On/Off ); Modbus DI436Read
BV895UnitOnOff_Dout.Enable_WUnit status (On/Off ) - Enable output; Modbus DI437Read
BV896UnitOnOff_Dout.Configured_RUnit status (On/Off ) - Output configurated; Modbus DI438Read
BV897CoolHeat_Dout.Val_Hw_RCool/Heat status - Hardware value writes from board; Modbus DI439Read
BV898CoolHeat_Dout.Val_WCool/Heat status; Modbus DI440Read
BV899CoolHeat_Dout.Enable_WCool/Heat status - Enable output; Modbus DI441Read
BV900CoolHeat_Dout.Configured_RCool/Heat status - Output configurated; Modbus DI442Read
BV901GlobalAlrm_Dout.Val_Hw_RGeneric alarm info - Hardware value writes from board; Modbus DI443Read
BVmin902GlobalAlrm_Dout.Val_WGeneric alarm info; Modbus DI444Read
BV903GlobalAlrm_Dout.Enable_WGeneric alarm info - Enable output; Modbus DI445Read
BV904GlobalAlrm_Dout.Configured_RGeneric alarm info - Output configurated; Modbus DI446Read
BV905LightAlrm_Dout.Val_Hw_RLight alarm info - Hardware value writes from board; Modbus DI447Read
BV906LightAlrm_Dout.Val_WLight alarm info; Modbus DI448Read
BV907LightAlrm_Dout.Enable_WLight alarm info - Enable output; Modbus DI449Read
BV908LightAlrm_Dout.Configured_RLight alarm info - Output configurated; Modbus DI450Read
BV909SrsAlrm_Dout.Val_Hw_RSerious alarm info - Hardware value writes from board; Modbus DI451Read
BV910SrsAlrm_Dout.Val_WSerious alarm info; Modbus DI452Read
BV911SrsAlrm_Dout.Enable_WSerious alarm info - Enable output; Modbus DI453Read
BV912SrsAlrm_Dout.Configured_RSerious alarm info - Output configurated; Modbus DI454Read
BV913Humidifier.Val_Hw_RHumidifier - Hardware value writes from board; Modbus DI455Read
BV914Humidifier.Val_WHumidifier; Modbus DI456Read
BV915Humidifier.Enable_WHumidifier - Enable output; Modbus DI457Read
BV916Humidifier.Configured_RHumidifier - Output configurated; Modbus DI458Read
BV917AuxOut1_Dout.Val_Hw_RAuxiliary output 1 - Hardware value writes from board; Modbus DI459Read
BV919AuxOut1_Dout.Enable_WAuxiliary output 1 - Enable output; Modbus DI461Read
BV920AuxOut1_Dout.Configured_RAuxiliary output 1 - Output configurated; Modbus DI462Read
BV921AuxOut2_Dout.Val_Hw_RAuxiliary output 2 - Hardware value writes from board; Modbus DI463Read
BV923AuxOut2_Dout.Enable_WAuxiliary output 2 - Enable output; Modbus DI465Read
BV924AuxOut2_Dout.Configured_RAuxiliary output 2 - Output configurated; Modbus DI466Read
BV925AuxOut3_Dout.Val_Hw_RAuxiliary output 3 - Hardware value writes from board; Modbus DI467Read
BV927AuxOut3_Dout.Enable_WAuxiliary output 3 - Enable output; Modbus DI469Read
BV928AuxOut3_Dout.Configured_RAuxiliary output 3 - Output configurated; Modbus DI470Read
BV929AuxOut4_Dout.Val_Hw_RAuxiliary output 4 - Hardware value writes from board; Modbus DI471Read
BV931AuxOut4_Dout.Enable_WAuxiliary output 4 - Enable output; Modbus DI473Read
BV932AuxOut4_Dout.Configured_RAuxiliary output 4 - Output configurated; Modbus DI474Read
BV933MainVlv_Open.Val_Hw_RMain floating valve open - Hardware value writes from board; Modbus DI475Read
BV934MainVlv_Open.Val_WMain floating valve open; Modbus DI476Read
BV935MainVlv_Open.Enable_WMain floating valve open - Enable output; Modbus DI477Read
BV936MainVlv_Open.Configured_RMain floating valve open - Output configurated; Modbus DI478Read
BV937PreHeatVlv_Open.Val_Hw_RPre-heating floating valve open - Hardware value writes from board; Modbus DI479Read
BV938PreHeatVlv_Open.Val_WPre-heating floating valve open; Modbus DI480Read
BV939PreHeatVlv_Open.Enable_WPre-heating floating valve open - Enable output; Modbus DI481Read
BV940PreHeatVlv_Open.Configured_RPre-heating floating valve open - Output configurated; Modbus DI482Read
BV941ReHeatVlv_Open.Val_Hw_RRe-Heating floating valve open - Hardware value writes from board; Modbus DI483Read
BV942ReHeatVlv_Open.Val_WRe-Heating floating valve open; Modbus DI484Read
BV943ReHeatVlv_Open.Enable_WRe-Heating floating valve open - Enable output; Modbus DI485Read
BV944ReHeatVlv_Open.Configured_RRe-Heating floating valve open - Output configurated; Modbus DI486Read
BV945MainVlv_Close.Val_Hw_RMain floating valve close - Hardware value writes from board; Modbus DI487Read
BV946MainVlv_Close.Val_WMain floating valve close; Modbus DI488Read
BV947MainVlv_Close.Enable_WMain floating valve close - Enable output; Modbus DI489Read
BV948MainVlv_Close.Configured_RMain floating valve close - Output configurated; Modbus DI490Read
BV949PreHeatVlv_Close.Val_Hw_RPre-heating floating valve close - Hardware value writes from board; Modbus DI491Read
BV950PreHeatVlv_Close.Val_WPre-heating floating valve close; Modbus DI492Read
BV951PreHeatVlv_Close.Enable_WPre-heating floating valve close - Enable output; Modbus DI493Read
BV952PreHeatVlv_Close.Configured_RPre-heating floating valve close - Output configurated; Modbus DI494Read
BV953ReHeatVlv_Close.Val_Hw_RRe-Heating floating valve close - Hardware value writes from board; Modbus DI495Read
BV954ReHeatVlv_Close.Val_WRe-Heating floating valve close; Modbus DI496Read
BV955ReHeatVlv_Close.Enable_WRe-Heating floating valve close - Enable output; Modbus DI497Read
BV956ReHeatVlv_Close.Configured_RRe-Heating floating valve close - Output configurated; Modbus DI498Read
BV957MainCoil_Step1.Val_Hw_RMain step 1 - Hardware value writes from board; Modbus DI499Read
BV958MainCoil_Step1.Val_WMain step 1; Modbus DI500Read
BV959MainCoil_Step1.Enable_WMain step 1 - Enable output; Modbus DI501Read
BV960MainCoil_Step1.Configured_RMain step 1 - Output configurated; Modbus DI502Read
BV961MainCoil_Step2.Val_Hw_RMain step 2 - Hardware value writes from board; Modbus DI503Read
BV962MainCoil_Step2.Val_WMain step 2; Modbus DI504Read
BV963MainCoil_Step2.Enable_WMain step 2 - Enable output; Modbus DI505Read
BV964MainCoil_Step2.Configured_RMain step 2 - Output configurated; Modbus DI506Read
BV965MainCoil_Step3.Val_Hw_RMain step 3 - Hardware value writes from board; Modbus DI507Read
BV966MainCoil_Step3.Val_WMain step 3; Modbus DI508Read
BV967MainCoil_Step3.Enable_WMain step 3 - Enable output; Modbus DI509Read
BV968MainCoil_Step3.Configured_RMain step 3 - Output configurated; Modbus DI510Read
BV969MainCoil_Step4.Val_Hw_RMain step 4 - Hardware value writes from board; Modbus DI511Read
BV970MainCoil_Step4.Val_WMain step 4; Modbus DI512Read
BV971MainCoil_Step4.Enable_WMain step 4 - Enable output; Modbus DI513Read
BV972MainCoil_Step4.Configured_RMain step 4 - Output configurated; Modbus DI514Read
BV973ReHeatCoil_Step1.Val_Hw_RPostheat heater 1 - Hardware value writes from board; Modbus DI515Read
BV974ReHeatCoil_Step1.Val_WPostheat heater 1; Modbus DI516Read
BV975ReHeatCoil_Step1.Enable_WPostheat heater 1 - Enable output; Modbus DI517Read
BV976ReHeatCoil_Step1.Configured_RPostheat heater 1 - Output configurated; Modbus DI518Read
BV977ReHeatCoil_Step2.Val_Hw_RPostheat heater 2 - Hardware value writes from board; Modbus DI519Read
BV978ReHeatCoil_Step2.Val_WPostheat heater 2; Modbus DI520Read
BV979ReHeatCoil_Step2.Enable_WPostheat heater 2 - Enable output; Modbus DI521Read
BV980ReHeatCoil_Step2.Configured_RPostheat heater 2 - Output configurated; Modbus DI522Read
BV981ReHeatCoil_Step3.Val_Hw_RPostheat heater 3 - Hardware value writes from board; Modbus DI523Read
BV982ReHeatCoil_Step3.Val_WPostheat heater 3; Modbus DI524Read
BV983ReHeatCoil_Step3.Enable_WPostheat heater 3 - Enable output; Modbus DI525Read
BV984ReHeatCoil_Step3.Configured_RPostheat heater 3 - Output configurated; Modbus DI526Read
BV985ReHeatCoil_Step4.Val_Hw_RPostheat heater 4 - Hardware value writes from board; Modbus DI527Read
BV986ReHeatCoil_Step4.Val_WPostheat heater 4; Modbus DI528Read
BV987ReHeatCoil_Step4.Enable_WPostheat heater 4 - Enable output; Modbus DI529Read
BV988ReHeatCoil_Step4.Configured_RPostheat heater 4 - Output configurated; Modbus DI530Read
BV989PreHeatCoil_Step1.Val_Hw_RPreheat heater 1 - Hardware value writes from board; Modbus DI531Read
BV990PreHeatCoil_Step1.Val_WPreheat heater 1; Modbus DI532Read
BV991PreHeatCoil_Step1.Enable_WPreheat heater 1 - Enable output; Modbus DI533Read
BV992PreHeatCoil_Step1.Configured_RPreheat heater 1 - Output configurated; Modbus DI534Read
BV993PreHeatCoil_Step2.Val_Hw_RPreheat heater 2 - Hardware value writes from board; Modbus DI535Read
BV994PreHeatCoil_Step2.Val_WPreheat heater 2; Modbus DI536Read
BV995PreHeatCoil_Step2.Enable_WPreheat heater 2 - Enable output; Modbus DI537Read
BV996PreHeatCoil_Step2.Configured_RPreheat heater 2 - Output configurated; Modbus DI538Read
BV997PreHeatCoil_Step3.Val_Hw_RPreheat heater 3 - Hardware value writes from board; Modbus DI539Read
BV998PreHeatCoil_Step3.Val_WPreheat heater 3; Modbus DI540Read
BV999PreHeatCoil_Step3.Enable_WPreheat heater 3 - Enable output; Modbus DI541Read
BV1000PreHeatCoil_Step3.Configured_RPreheat heater 3 - Output configurated; Modbus DI542Read
BV1001PreHeatCoil_Step4.Val_Hw_RPreheat heater 4 - Hardware value writes from board; Modbus DI543Read
BV1002PreHeatCoil_Step4.Val_WPreheat heater 4; Modbus DI544Read
BV1003PreHeatCoil_Step4.Enable_WPreheat heater 4 - Enable output; Modbus DI545Read
BV1004PreHeatCoil_Step4.Configured_RPreheat heater 4 - Output configurated; Modbus DI546Read
BV1005OA_Coil_Step1.Val_Hw_ROutdoor air pre-treatment heater 1 - Hardware value writes from board; Modbus DI547Read
BV1006OA_Coil_Step1.Val_WOutdoor air pre-treatment heater 1; Modbus DI548Read
BV1007OA_Coil_Step1.Enable_WOutdoor air pre-treatment heater 1 - Enable output; Modbus DI549Read
BV1008OA_Coil_Step1.Configured_ROutdoor air pre-treatment heater 1 - Output configurated; Modbus DI550Read
BV1009OA_Coil_Step2.Val_Hw_ROutdoor air pre-treatment heater 2 - Hardware value writes from board; Modbus DI551Read
BV1010OA_Coil_Step2.Val_WOutdoor air pre-treatment heater 2; Modbus DI552Read
BV1011OA_Coil_Step2.Enable_WOutdoor air pre-treatment heater 2 - Enable output; Modbus DI553Read
BV1012OA_Coil_Step2.Configured_ROutdoor air pre-treatment heater 2 - Output configurated; Modbus DI554Read
BV1013OA_Coil_Step3.Val_Hw_ROutdoor air pre-treatment heater 3 - Hardware value writes from board; Modbus DI555Read
BV1014OA_Coil_Step3.Val_WOutdoor air pre-treatment heater 3; Modbus DI556Read
BV1015OA_Coil_Step3.Enable_WOutdoor air pre-treatment heater 3 - Enable output; Modbus DI557Read
BV1016OA_Coil_Step3.Configured_ROutdoor air pre-treatment heater 3 - Output configurated; Modbus DI558Read
BV1017OA_Coil_Step4.Val_Hw_ROutdoor air pre-treatment heater 4 - Hardware value writes from board; Modbus DI559Read
BV1018OA_Coil_Step4.Val_WOutdoor air pre-treatment heater 4; Modbus DI560Read
BV1019OA_Coil_Step4.Enable_WOutdoor air pre-treatment heater 4 - Enable output; Modbus DI561Read
BV1020OA_Coil_Step4.Configured_ROutdoor air pre-treatment heater 4 - Output configurated; Modbus DI562Read
BV1021PreHeatPmp_1.Val_Hw_RPre-Heating pump 1 - Hardware value writes from board; Modbus DI563Read
BV1022PreHeatPmp_1.Val_WPre-Heating pump 1; Modbus DI564Read
BV1023PreHeatPmp_1.Enable_WPre-Heating pump 1 - Enable output; Modbus DI565Read
BV1024PreHeatPmp_1.Configured_RPre-Heating pump 1 - Output configurated; Modbus DI566Read
BV1025PreHeatPmp_2.Val_Hw_RPre-Heating pump 2 - Hardware value writes from board; Modbus DI567Read
BV1026PreHeatPmp_2.Val_WPre-Heating pump 2; Modbus DI568Read
BV1027PreHeatPmp_2.Enable_WPre-Heating pump 2 - Enable output; Modbus DI569Read
BV1028PreHeatPmp_2.Configured_RPre-Heating pump 2 - Output configurated; Modbus DI570Read
BV1029MainCoilPmp_1.Val_Hw_RMain pump 1 - Hardware value writes from board; Modbus DI571Read
BV1030MainCoilPmp_1.Val_WMain pump 1; Modbus DI572Read
BV1031MainCoilPmp_1.Enable_WMain pump 1 - Enable output; Modbus DI573Read
BV1032MainCoilPmp_1.Configured_RMain pump 1 - Output configurated; Modbus DI574Read
BV1033MainCoilPmp_2.Val_Hw_RMain pump 2 - Hardware value writes from board; Modbus DI575Read
BV1034MainCoilPmp_2.Val_WMain pump 2; Modbus DI576Read
BV1035MainCoilPmp_2.Enable_WMain pump 2 - Enable output; Modbus DI577Read
BV1036MainCoilPmp_2.Configured_RMain pump 2 - Output configurated; Modbus DI578Read
BV1037ReHeatPmp_1.Val_Hw_RRe-Heating pump 1 - Hardware value writes from board; Modbus DI579Read
BV1038ReHeatPmp_1.Val_WRe-Heating pump 1; Modbus DI580Read
BV1039ReHeatPmp_1.Enable_WRe-Heating pump 1 - Enable output; Modbus DI581Read
BV1040ReHeatPmp_1.Configured_RRe-Heating pump 1 - Output configurated; Modbus DI582Read
BV1041ReHeatPmp_2.Val_Hw_RRe-Heating pump 2 - Hardware value writes from board; Modbus DI583Read
BV1042ReHeatPmp_2.Val_WRe-Heating pump 2; Modbus DI584Read
BV1043ReHeatPmp_2.Enable_WRe-Heating pump 2 - Enable output; Modbus DI585Read
BV1044ReHeatPmp_2.Configured_RRe-Heating pump 2 - Output configurated; Modbus DI586Read
BV1045OA_CoilPmp_1.Val_Hw_ROutdoor air pre-treatment-Heating pump 1 - Hardware value writes from board; Modbus DI587Read
BV1046OA_CoilPmp_1.Val_WOutdoor air pre-treatment-Heating pump 1; Modbus DI588Read
BV1047OA_CoilPmp_1.Enable_WOutdoor air pre-treatment-Heating pump 1 - Enable output; Modbus DI589Read
BV1048OA_CoilPmp_1.Configured_ROutdoor air pre-treatment-Heating pump 1 - Output configurated; Modbus DI590Read
BV1049OA_CoilPmp_2.Val_Hw_ROutdoor air pre-treatment-Heating pump 2 - Hardware value writes from board; Modbus DI591Read
BV1050OA_CoilPmp_2.Val_WOutdoor air pre-treatment-Heating pump 2; Modbus DI592Read
BV1051OA_CoilPmp_2.Enable_WOutdoor air pre-treatment-Heating pump 2 - Enable output; Modbus DI593Read
BV1052OA_CoilPmp_2.Configured_ROutdoor air pre-treatment-Heating pump 2 - Output configurated; Modbus DI594Read
BV1053FiltAlrm_Dout.Val_Hw_RFilters alarm - Hardware value writes from board; Modbus DI595Read
BV1054FiltAlrm_Dout.Val_WFilters alarm; Modbus DI596Read
BV1055FiltAlrm_Dout.Enable_WFilters alarm - Enable output; Modbus DI597Read
BV1056FiltAlrm_Dout.Configured_RFilters alarm - Output configurated; Modbus DI598Read
BV1057Recovery_Dout.Val_Hw_RRecovery - Hardware value writes from board; Modbus DI599Read
BV1058Recovery_Dout.Val_WRecovery; Modbus DI600Read
BV1059Recovery_Dout.Enable_WRecovery - Enable output; Modbus DI601Read
BV1060Recovery_Dout.Configured_RRecovery - Output configurated; Modbus DI602Read
BV1061IEC_Hum_Dout.Val_Hw_RIEC humidifer - Hardware value writes from board; Modbus DI603Read
BV1062IEC_Hum_Dout.Val_WIEC humidifer; Modbus DI604Read
BV1063IEC_Hum_Dout.Enable_WIEC humidifer - Enable output; Modbus DI605Read
BV1064IEC_Hum_Dout.Configured_RIEC humidifer - Output configurated; Modbus DI606Read
BV1065SupplyFan_Aout.Enable_WSupply fan - Enable output; Modbus DI607Read
BV1066SupplyFan_Aout.Configured_RSupply fan - Analog output configured; Modbus DI608Read
BV1067RetFan_Aout.Enable_WReturn fan - Enable output; Modbus DI609Read
BV1068RetFan_Aout.Configured_RReturn fan - Analog output configured; Modbus DI610Read
BV1069BypassDamp_Aout.Enable_WBypass damper - Enable output; Modbus DI611Read
BV1070BypassDamp_Aout.Configured_RBypass damper - Analog output configured; Modbus DI612Read
BV1071MixingDamp_Aout.Enable_WMixing damper - Enable output; Modbus DI613Read
BV1072MixingDamp_Aout.Configured_RMixing damper - Analog output configured; Modbus DI614Read
BV1073FreshAirDamp_Aout.Enable_WFresh air damper - Enable output; Modbus DI615Read
BV1074FreshAirDamp_Aout.Configured_RFresh air damper - Analog output configured; Modbus DI616Read
BV1075ReHeatCoil_Aout.Enable_WReheat heater - Enable output; Modbus DI617Read
BV1076ReHeatCoil_Aout.Configured_RReheat heater - Analog output configured; Modbus DI618Read
BV1077PreHeatCoil_Aout.Enable_WPre-Heating heater - Enable output; Modbus DI619Read
BV1078PreHeatCoil_Aout.Configured_RPre-Heating heater - Analog output configured; Modbus DI620Read
BV1079OA_Coil_Aout.Enable_WOutdoor air pre-treatment heater - Enable output; Modbus DI621Read
BV1080OA_Coil_Aout.Configured_ROutdoor air pre-treatment heater - Analog output configured; Modbus DI622Read
BV1081MainCoil_Aout.Enable_WMain coil valve - Enable output; Modbus DI623Read
BV1082MainCoil_Aout.Configured_RMain coil valve - Analog output configured; Modbus DI624Read
BV1083ThrmlWheel_Aout.Enable_WThermal wheel - Enable output; Modbus DI625Read
BV1084ThrmlWheel_Aout.Configured_RThermal wheel - Analog output configured; Modbus DI626Read
BV1085Humidifier_Aout.Enable_WHumidifier - Enable output; Modbus DI627Read
BV1086Humidifier_Aout.Configured_RHumidifier - Analog output configured; Modbus DI628Read
BV1087ExhAirDamp_Aout.Enable_WExhaust air damper - Enable output; Modbus DI629Read
BV1088ExhAirDamp_Aout.Configured_RExhaust air damper - Analog output configured; Modbus DI630Read
BV1089AuxAout_1.Enable_WAuxiliary output 1 - Enable output; Modbus DI631Read
BV1090AuxAout_1.Configured_RAuxiliary output 1 - Analog output configured; Modbus DI632Read
BV1091AuxAout_2.Enable_WAuxiliary output 2 - Enable output; Modbus DI633Read
BV1092AuxAout_2.Configured_RAuxiliary output 2 - Analog output configured; Modbus DI634Read
BV1093AuxAout_3.Enable_WAuxiliary output 3 - Enable output; Modbus DI635Read
BV1094AuxAout_3.Configured_RAuxiliary output 3 - Analog output configured; Modbus DI636Read
BV1095AuxAout_4.Enable_WAuxiliary output 4 - Enable output; Modbus DI637Read
BV1096AuxAout_4.Configured_RAuxiliary output 4 - Analog output configured; Modbus DI638Read
BV1097IEC_Aout.Enable_WIEC - Enable output; Modbus DI639Read
BV1098IEC_Aout.Configured_RIEC - Analog output configured; Modbus DI640Read
BV1099Recovery_Aout.Enable_WRecovery pump - Enable output; Modbus DI641Read
BV1100Recovery_Aout.Configured_RRecovery pump - Analog output configured; Modbus DI642Read
BV1101SupplyAirDamp_Aout.Enable_WSupply air damper - Enable output; Modbus DI643Read
BV1102SupplyAirDamp_Aout.Configured_RSupply air damper - Analog output configured; Modbus DI644Read
BV1103RetAirDamp_Aout.Enable_WReturn air damper - Enable output; Modbus DI645Read
BV1104RetAirDamp_Aout.Configured_RReturn air damper - Analog output configured; Modbus DI646Read
BV1115Scheduler_OnOffUnit.FB_SchedulerMngK_1.StatusChkModbus DI657Read
BV1116Scheduler_OnOffUnit.FB_SchedulerMngK_1.VacChkModbus DI658Read
BV1117Scheduler_OnOffUnit.FB_SchedulerMngK_1.SDayChkModbus DI659Read
BV1152GeneralMng.WizardCustomModbus DI694Read
BV1153Scheduler_OnOffUnit.FB_SchedulerMskMng_1.CfgErr_SCHEDModbus DI695Read
BV1157GenericHumidifier.ModulHum_IO_CfgWarnModbus DI699Read
BV1164AuxiliaryRegulation.AuxReg1_Info.InputCheckCfgErrAuxiliary regulation 1: Informations - Input check configuration error; Modbus DI706Read
BV1165AuxiliaryRegulation.AuxReg1_Info.OutputCheckCfgErrAuxiliary regulation 1: Informations - Output check configuration error; Modbus DI707Read
BV1166AuxiliaryRegulation.AuxReg1_Info.DOutAuxiliary regulation 1: Informations - Dout configured; Modbus DI708Read
BV1167AuxiliaryRegulation.AuxReg1_Info.EnableCheckCfgErrAuxiliary regulation 1: Informations - Enable check configuration error; Modbus DI709Read
BV1168AuxiliaryRegulation.AuxReg2_Info.InputCheckCfgErrAuxiliary regulation 2: Informations - Input check configuration error; Modbus DI710Read
BV1169AuxiliaryRegulation.AuxReg2_Info.OutputCheckCfgErrAuxiliary regulation 2: Informations - Output check configuration error; Modbus DI711Read
BV1170AuxiliaryRegulation.AuxReg2_Info.DOutAuxiliary regulation 2: Informations - Dout configured; Modbus DI712Read
BV1171AuxiliaryRegulation.AuxReg2_Info.EnableCheckCfgErrAuxiliary regulation 2: Informations - Enable check configuration error; Modbus DI713Read
BV1172AuxiliaryRegulation.AuxReg3_Info.InputCheckCfgErrAuxiliary regulation 3: Informations - Input check configuration error; Modbus DI714Read
BV1173AuxiliaryRegulation.AuxReg3_Info.OutputCheckCfgErrAuxiliary regulation 3: Informations - Output check configuration error; Modbus DI715Read
BV1174AuxiliaryRegulation.AuxReg3_Info.DOutAuxiliary regulation 3: Informations - Dout configured; Modbus DI716Read
BV1175AuxiliaryRegulation.AuxReg3_Info.EnableCheckCfgErrAuxiliary regulation 3: Informations - Enable check configuration error; Modbus DI717Read
BV1176AuxiliaryRegulation.AuxReg4_Info.InputCheckCfgErrAuxiliary regulation 4: Informations - Input check configuration error; Modbus DI718Read
BV1177AuxiliaryRegulation.AuxReg4_Info.OutputCheckCfgErrAuxiliary regulation 4: Informations - Output check configuration error; Modbus DI719Read
BV1178AuxiliaryRegulation.AuxReg4_Info.DOutAuxiliary regulation 4: Informations - Dout configured; Modbus DI720Read
BV1179AuxiliaryRegulation.AuxReg4_Info.EnableCheckCfgErrAuxiliary regulation 4: Informations - Enable check configuration error; Modbus DI721Read
BV1180Comp_OnOff.OnOffComp_IO_CfgWarnModbus DI722Read
BV1181BLDC_compressor.BLDC_Comp_IO_CfgWarnModbus DI723Read
BV1182cpCOmini_HighEndc.pCOmini high end version present; Modbus DI724Read
BV1183GeneralMng.DHCP_State_1Automatically generated; Modbus DI725Read
BV1184BLDC_compressor.Info_PWRP1.StatusReg_Bit_15Inverter Power Plus Info - Status register bit 15; Modbus DI726Read
BV1185BLDC_compressor.Info_PWRP1.StatusReg_Bit_14Inverter Power Plus Info - Status register bit 14; Modbus DI727Read
BV1186BLDC_compressor.Info_PWRP1.StatusReg_Bit_13Inverter Power Plus Info - Status register bit 13; Modbus DI728Read
BV1187BLDC_compressor.Info_PWRP1.StatusReg_Bit_12Inverter Power Plus Info - Status register bit 12; Modbus DI729Read
BV1188BLDC_compressor.Info_PWRP1.StatusReg_DriveTrippedInverter Power Plus Info - Drive in alarm; Modbus DI730Read
BV1189BLDC_compressor.Info_PWRP1.StatusReg_Bit_10Inverter Power Plus Info - Status register bit 10; Modbus DI731Read
BV1190BLDC_compressor.Info_PWRP1.StatusReg_MainSupplyLossedInverter Power Plus Info - Power supply status: 0=OK; 1=loss ...; Modbus DI732Read
BV1191BLDC_compressor.Info_PWRP1.StatusReg_MotorOverloadInverter Power Plus Info - Motor overload; Modbus DI733Read
BV1192BLDC_compressor.Info_PWRP1.StatusReg_DriveInAutotuneInverter Power Plus Info - Autotune running; Modbus DI734Read
BV1193BLDC_compressor.Info_PWRP1.StatusReg_Bit_06Inverter Power Plus Info - Status register bit 06; Modbus DI735Read
BV1194BLDC_compressor.Info_PWRP1.StatusReg_SwitchingFreqDeratingONInverter Power Plus Info - Switching frequency derating ON; Modbus DI736Read
BV1195BLDC_compressor.Info_PWRP1.StatusReg_FanONInverter Power Plus Info - Fan ON; Modbus DI737Read
BV1196BLDC_compressor.Info_PWRP1.StatusReg_UnderVoltageInverter Power Plus Info - Under voltage; Modbus DI738Read
BV1197BLDC_compressor.Info_PWRP1.StatusReg_MotorPTC_OverHeatInverter Power Plus Info - Motor PTC overheating; Modbus DI739Read
BV1198BLDC_compressor.Info_PWRP1.StatusReg_RelayConfigONInverter Power Plus Info - Relay config. ON; Modbus DI740Read
BV1199BLDC_compressor.Info_PWRP1.StatusReg_DriveInhibitInverter Power Plus Info - Safety input status (STO); 0=drive ...; Modbus DI741Read
BV1200BLDC_compressor.Info_PWRP1.SpeedReg_Bit_15Inverter Power Plus Info - Speed register bit 15; Modbus DI742Read
BV1201BLDC_compressor.Info_PWRP1.SpeedReg_Bit_14Inverter Power Plus Info - Speed register bit 14; Modbus DI743Read
BV1202BLDC_compressor.Info_PWRP1.SpeedReg_Bit_13Inverter Power Plus Info - Speed register bit 13; Modbus DI744Read
BV1203BLDC_compressor.Info_PWRP1.SpeedReg_Bit_12Inverter Power Plus Info - Speed register bit 12; Modbus DI745Read
BV1204BLDC_compressor.Info_PWRP1.SpeedReg_Bit_11Inverter Power Plus Info - Speed register bit 11; Modbus DI746Read
BV1205BLDC_compressor.Info_PWRP1.SpeedReg_Bit_10Inverter Power Plus Info - Speed register bit 10; Modbus DI747Read
BV1206BLDC_compressor.Info_PWRP1.SpeedReg_Bit_09Inverter Power Plus Info - Speed register bit 09; Modbus DI748Read
BV1207BLDC_compressor.Info_PWRP1.SpeedReg_Bit_08Inverter Power Plus Info - Speed register bit 08; Modbus DI749Read
BV1208BLDC_compressor.Info_PWRP1.SpeedReg_Bit_07Inverter Power Plus Info - Speed register bit 07; Modbus DI750Read
BV1209BLDC_compressor.Info_PWRP1.SpeedReg_Bit_06Inverter Power Plus Info - Speed register bit 06; Modbus DI751Read
BV1210BLDC_compressor.Info_PWRP1.SpeedReg_Bit_05Inverter Power Plus Info - Speed register bit 05; Modbus DI752Read
BV1211BLDC_compressor.Info_PWRP1.SpeedReg_Bit_04Inverter Power Plus Info - Speed register bit 04; Modbus DI753Read
BV1212BLDC_compressor.Info_PWRP1.SpeedReg_Bit_03Inverter Power Plus Info - Speed register bit 03; Modbus DI754Read
BV1213BLDC_compressor.Info_PWRP1.SpeedReg_Bit_02Inverter Power Plus Info - Speed register bit 02; Modbus DI755Read
BV1214BLDC_compressor.Info_PWRP1.SpeedReg_Bit_01Inverter Power Plus Info - Speed register bit 01; Modbus DI756Read
BV1215BLDC_compressor.Info_PWRP1.SpeedReg_Bit_00Inverter Power Plus Info - Speed register bit 00; Modbus DI757Read
BV1216BLDC_compressor.Info_PWRP1.Mng_CheckVI_NotOKInverter Power Plus Info - Reserved; Modbus DI758Read
BV1217BLDC_compressor.Info_PWRP1.Mng_LoadDefFailInverter Power Plus Info - Reserved; Modbus DI759Read
BV1218BLDC_compressor.Info_PWRP1.Info_PSD_400VInverter Power Plus Info - Main supply as three phases; Modbus DI760Read
BV1219BLDC_compressor.Info_PWRP1.Mng_MotSelect_400VInverter Power Plus Info - Three-phase inverter required for compressor; Modbus DI761Read
BV1220BLDC_compressor.MiscMng_PWRP1.MngCstm_SaveCustomCfgInProgressCustom cofiguration data saving in progress; Modbus DI762Read
BV1221BLDC_compressor.PwrpOnline_BLDC1Inverter is online; Modbus DI763Read
BV1222Info_BLDC1.Mng_TestModeBLDC informations - Managing test mode; Modbus DI764Read
BV1223Info_BLDC1.Info_SIAM_90rpsZoneBLDC informations - Working zone 1c - max speed 90 ...; Modbus DI765Read
BV1224Info_BLDC1.UI_EqualizationStatusBLDC informations - Show pressure equalization status (blinking); Modbus DI766Read
BV1225Info_BLDC1.UI_LowDeltaPBLDC informations - Show low pressure difference condition; Modbus DI767Read
BV1226Info_BLDC1.EnvTyp_SiamCompBLDC informations - Envelope Type: Siam compressor; Modbus DI768Read
BV1227SPV_Warning_ConfigWarning: SPV Configuration error; Modbus DI769Read
BV1228SPV_Warning_LicenseWarning: SPV License not compatible; Modbus DI770Read
BV1229Al_NOT_USED.ActiveAlarm to make the alarms list compatible with mask - ...; Modbus DI1000Read
BV1230Al_SupplyTemp.ActiveSupply temperature probe alarm - Alarm status; Modbus DI1001Read
BV1231Al_SupplyHum.ActiveSupply humidity probe alarm - Alarm status; Modbus DI1002Read
BV1232Al_RetTemp.ActiveReturn temperature probe alarm - Alarm status; Modbus DI1003Read
BV1233Al_RetHum.ActiveReturn humidity probe alarm - Alarm status; Modbus DI1004Read
BV1234Al_RoomTemp.ActiveRoom temperature probe alarm - Alarm status; Modbus DI1005Read
BV1235Al_RoomHum.ActiveRoom humidity probe alarm - Alarm status; Modbus DI1006Read
BV1236Al_ExtTemp.ActiveFresh air temperature probe alarm - Alarm status; Modbus DI1007Read
BV1237Al_ExtHum.ActiveFresh air humidity probe alarm - Alarm status; Modbus DI1008Read
BV1238Al_ExhTemp.ActiveExhaust temperature probe alarm - Alarm status; Modbus DI1009Read
BV1239Al_ExhHum.ActiveExhaust humidity probe alarm - Alarm status; Modbus DI1010Read
BV1240Al_AFreezeTemp.ActiveAntifreeze temperature probe alarm - Alarm status; Modbus DI1011Read
BV1241Al_SatTemp.ActiveSaturation temperature probe alarm - Alarm status; Modbus DI1012Read
BV1242Al_SatHum.ActiveSaturation humidity probe alarm - Alarm status; Modbus DI1013Read
BV1243Al_OutdoorAirTemp.ActiveOutdoor air pre-treatment temperature probe alarm- Alarm status; Modbus DI1014Read
BV1244Al_SupplyAirP.ActiveSupply air pressure probe alarm - Alarm status; Modbus DI1015Read
BV1245Al_RetAirP.ActiveReturn air pressure probe alarm - Alarm status; Modbus DI1016Read
BV1246Al_AirQuality_CO2.ActiveCO2 sensor probe alarm - Alarm status; Modbus DI1017Read
BV1247Al_AirQuality_VOC.ActiveVOC sensor probe alarm - Alarm status; Modbus DI1018Read
BV1248Al_DscgP.ActiveDischarge pressure probe alarm - Alarm status; Modbus DI1019Read
BV1249Al_DscgT.ActiveDischarge temperature probe alarm - Alarm status; Modbus DI1020Read
BV1250Al_SuctP.ActiveSuction pressure probe alarm - Alarm status; Modbus DI1021Read
BV1251Al_SuctT.ActiveSuction temperature probe alarm - Alarm status; Modbus DI1022Read
BV1252Al_OA_CoilWaterTemp.ActiveOutdoor air pre-treatment coil water temperature probe alarm - Alarm status; Modbus DI1023Read
BV1253Al_PreHeatCoilWaterTemp.ActivePreheat coil water temperature probe alarm - Alarm status; Modbus DI1024Read
BV1254Al_MainCoilWaterTemp.ActiveMain coil water temperature probe alarm - Alarm status; Modbus DI1025Read
BV1255Al_ReHeatCoilWaterTemp.ActiveRe heat coil water temperature probe alarm - Alarm status; Modbus DI1026Read
BV1256Al_AuxPrb_1.ActiveAuxiliary probe 1 probe alarm - Alarm status; Modbus DI1027Read
BV1257Al_AuxPrb_2.ActiveAuxiliary probe 2 probe alarm - Alarm status; Modbus DI1028Read
BV1258Al_AuxPrb_3.ActiveAuxiliary probe 3 probe alarm - Alarm status; Modbus DI1029Read
BV1259Al_AuxPrb_4.ActiveAuxiliary probe 4 probe alarm - Alarm status; Modbus DI1030Read
BV1260Al_Ain_SetP.ActiveSetpoint by AIN probe alarm - Alarm status; Modbus DI1031Read
BV1261Al_SupplyRecoveryTemp.ActiveSupply recovery temperature probe alarm - Alarm status; Modbus DI1032Read
BV1262Al_RetRecoveryTemp.ActiveReturn recovery temperature probe alarm - Alarm status; Modbus DI1033Read
BV1263Al_HepaFilt_1.ActiveHepa filter 1 probe alarm - Alarm status; Modbus DI1034Read
BV1264Al_HepaFilt_2.ActiveHepa filter 2 probe alarm - Alarm status; Modbus DI1035Read
BV1265Al_GenericAlrmByDin.ActiveGeneric alarm from digital input - Alarm status; Modbus DI1036Read
BV1266Al_MainHeat_Ovld.ActiveMain coil alarm - Alarm status; Modbus DI1037Read
BV1267Al_SupplyFanOvld.ActiveSupply fan overload - Alarm status; Modbus DI1038Read
BV1268Al_RetFanOvld.ActiveReturn fan overload - Alarm status; Modbus DI1039Read
BV1269Al_FansOvld.ActiveFans overload - Alarm status; Modbus DI1040Read
BV1270Al_CompOvld.ActiveCompressor overload - Alarm status; Modbus DI1041Read
BV1271Al_HiP_Sw.ActiveHigh discharge pressure switch - Alarm status; Modbus DI1042Read
BV1272Al_LowP_Sw.ActiveLow suction pressure switch - Alarm status; Modbus DI1043Read
BV1273Al_SupplyAirFlwSw.ActiveSupply air flow switch alarm - Alarm status; Modbus DI1044Read
BV1274Al_RetAirFlwSw.ActiveReturn air flow switch alarm - Alarm status; Modbus DI1045Read
BV1275Al_AirFlwSw.ActiveAir flow switch alarm - Alarm status; Modbus DI1046Read
BV1276Al_AFreeze.ActiveAntifreeze alarm - Alarm status; Modbus DI1047Read
BV1277Al_LowSH_EVD_Emb.ActiveEVD - Low SH - Alarm status; Modbus DI1048Read
BV1278Al_EEV_MotErr.ActiveEVD - Motor error - Alarm status; Modbus DI1049Read
BV1279Al_SettingOutOfBound_EVD_Emb.ActiveEVD - Setting out of bound - Alarm status; Modbus DI1050Read
BV1280Al_RangeErr_EVD_Emb.ActiveEVD - Settings range error - Alarm status; Modbus DI1051Read
BV1281Al_InvOffline.ActiveInverter - Offline - Alarm status; Modbus DI1052Read
BV1282Al_Inv01_OverA.ActiveInverter - Drive overcurrent (01) - Alarm status; Modbus DI1053Read
BV1283Al_Inv02_MotOvld.ActiveInverter - Motor overload (02) - Alarm status; Modbus DI1054Read
BV1284Al_Inv03_DC_BusOverV.ActiveInverter - DC Bus overvoltage (03) - Alarm status; Modbus DI1055Read
BV1285Al_Inv04_DC_BusUnderV.ActiveInverter - DC bus undervoltage (04) - Alarm status; Modbus DI1056Read
BV1286Al_Inv05_OverTemp.ActiveInverter - Drive overtemperature (05) - Alarm status; Modbus DI1057Read
BV1287Al_Inv06_DrvUnderTemp.ActiveInverter - Drive undertemperature (06) - Alarm status; Modbus DI1058Read
BV1288Al_Inv07_HW_OverA.ActiveInverter - HW overcurrent HW(07) - Alarm status; Modbus DI1059Read
BV1289Al_Inv08_MotOverTemp.ActiveInverter - PTC motor overtemperature (08) - Alarm status; Modbus DI1060Read
BV1290Al_Inv09_OutputFault.ActiveInverter - IGBT module error (09) - Alarm status; Modbus DI1061Read
BV1291Al_Inv10_FlashDataErr.ActiveInverter - CPU error (10) - Alarm status; Modbus DI1062Read
BV1292Al_Inv11_ParamDef.ActiveInverter - Parameter default (11) - Alarm status; Modbus DI1063Read
BV1293Al_Inv12_DC_RippTooLarge.ActiveInverter - DC bus ripple (12) - Alarm status; Modbus DI1064Read
BV1294Al_Inv13_MB_CommFault.ActiveInverter - Data communication fault (13) - Alarm status; Modbus DI1065Read
BV1295Al_Inv14_DrvThermistorFault.ActiveInverter - Drive thermistor fault (14) - Alarm status; Modbus DI1066Read
BV1296Al_Inv15_AutotuneFault.ActiveInverter - Autotuning fault (15) - Alarm status; Modbus DI1067Read
BV1297Al_Inv16_DrvDis.ActiveInverter - Drive disabled (16) - Alarm status; Modbus DI1068Read
BV1298Al_Inv17_MotPhaseFault.ActiveInverter - Motor phase fault (17) - Alarm status; Modbus DI1069Read
BV1299Al_Inv18_FanFault.ActiveInverter - Internal fan fault (18) - Alarm status; Modbus DI1070Read
BV1300Al_Inv19_SpeedFault.ActiveInverter - Speed fault (19) - Alarm status; Modbus DI1071Read
BV1301Al_Inv20_PFC_Failure.ActiveInverter - PFC module error (20) - Alarm status; Modbus DI1072Read
BV1302Al_Inv21_PFC_OverVolt.ActiveInverter - PFC overvoltage (21) - Alarm status; Modbus DI1073Read
BV1303Al_Inv22_PFC_UnderVolt.ActiveInverter - PFC undervoltage (22) - Alarm status; Modbus DI1074Read
BV1304Al_Inv23_STO_Survey1.ActiveInverter - STO detection error (23) - Alarm status; Modbus DI1075Read
BV1305Al_Inv24_STO_Survey2.ActiveInverter - STO detection error (24) - Alarm status; Modbus DI1076Read
BV1306Al_Inv25_GroundFault.ActiveInverter - Ground fault (25) - Alarm status; Modbus DI1077Read
BV1307Al_Inv26_ADC_ConvSync.ActiveInverter - ADC conversion sync fault (26) - Alarm status; Modbus DI1078Read
BV1308Al_Inv27_HW_Sync.ActiveInverter - HW sync fault (27) - Alarm status; Modbus DI1079Read
BV1309Al_Inv28_DrvOvrld.ActiveInverter - Drive overload (28) - Alarm status; Modbus DI1080Read
BV1310Al_Inv29_uCSafe_DriveStop.ActiveInverter - Drive overtemperature (HW) (29) - Alarm status; Modbus DI1081Read
BV1311Al_Inv99_UnexpectedStop.ActiveInverter - Unexpected stop (99) - Alarm status; Modbus DI1082Read
BV1312Al_StartFail_BLDC1.ActiveBLDC - Starting failure - Alarm status; Modbus DI1083Read
BV1313Al_SwPrototype.ActivePrototype software - Alarm status; Modbus DI1084Read
BV1314Al_retain.ActiveHigh number of retain memory writings - Alarm status; Modbus DI1085Read
BV1315Al_Err_retain_write.ActiveError in retain memory writings - Alarm status; Modbus DI1086Read
BV1316Al_Offline_THTN.Activeth-Tune offline - Alarm status; Modbus DI1087Read
BV1317Al_LowSupplyTemp.ActiveLow supply temperature - Alarm status; Modbus DI1088Read
BV1318Warn_MainCoilTOutOfRange.ActiveMain coil water temperature out of range warning - Alarm status; Modbus DI1090Read
BV1319Al_SupplyAirFlwSwWarn.ActiveSupply air flow warning - Alarm status; Modbus DI1091Read
BV1320Al_RetAirFlwSwWarn.ActiveReturn air flow warning - Alarm status; Modbus DI1092Read
BV1321Al_AirFlwSwWarn.ActiveAir flow warning - Alarm status; Modbus DI1093Read
BV1322Warn_AFreezeWarn.ActiveAntifreeze warning - Alarm status; Modbus DI1094Read
BV1323Al_HumAlrm.ActiveHumidifier alarm - Alarm status; Modbus DI1095Read
BV1324Al_WrkHrs_Hum.ActiveWarning - Humidifier maintenance required - Alarm status; Modbus DI1096Read
BV1325Al_WrkHrs_SupplyFan.ActiveWarning - Supply fan maintenance required - Alarm status; Modbus DI1097Read
BV1326Al_WrkHrs_ReturnFan.ActiveWarning - Return fan maintenance required - Alarm status; Modbus DI1098Read
BV1327Al_WrkHrs_ThrmlWheel.ActiveWarning - Thermal wheel maintenance required - Alarm status; Modbus DI1099Read
BV1328Al_WrkHrs_DirtyFilt.ActiveWarning - Filters maintenance required - Alarm status; Modbus DI1100Read
BV1329Al_DirtyFiltByDin.ActiveCommon - Dirty filters alarm - Alarm status; Modbus DI1101Read
BV1330Al_WrkHrs_Comp.ActiveWarning - Compressor maintenance required - Alarm status; Modbus DI1102Read
BV1331Al_HiRatioP_BLDC.ActiveCompressor envelope - High compression ratio - Alarm status; Modbus DI1103Read
BV1332Al_DscgHiP_BLDC.ActiveCompressor envelope - High discharge pressure - Alarm status; Modbus DI1104Read
BV1333Al_HiCurr_BLDC.ActiveCompressor envelope - High motor current - Alarm status; Modbus DI1105Read
BV1334Al_SuctHiP_BLDC.ActiveCompressor envelope - High suction pressure - Alarm status; Modbus DI1106Read
BV1335Al_LowRatioP_BLDC.ActiveCompressor envelope - Low compression ratio - Alarm status; Modbus DI1107Read
BV1336Al_LowDeltaP_BLDC.ActiveCompressor envelope - Low differential pressure - Alarm status; Modbus DI1108Read
BV1337Al_LowDscgP_BLDC.ActiveCompressor envelope - Low discharge pressure - Alarm status; Modbus DI1109Read
BV1338Al_LowSuctP_BLDC.ActiveCompressor envelope - Low suction pressure - Alarm status; Modbus DI1110Read
BV1339Al_HiDscgTemp_BLDC.ActiveCompressor envelope - High discharge temperature - Alarm status; Modbus DI1111Read
BV1340Al_LOP_EVD_Emb.ActiveEVD - LOP - Alarm status; Modbus DI1112Read
BV1341Al_MOP_EVD_Emb.ActiveEVD - MOP - Alarm status; Modbus DI1113Read
BV1342Al_HiCondTemp_EVD_Emb.ActiveEVD - High condensing temperature - Alarm status; Modbus DI1114Read
BV1343Al_LowSuctTemp_EVD_Emb.ActiveEVD - Low suction temperature - Alarm status; Modbus DI1115Read
BV1344Al_EmergClos_EVD_Emb.ActiveEVD - Emergency closing - Alarm status; Modbus DI1116Read
BV1345Al_DisStartDp_BLDC.ActiveBLDC - Delta pressure greater than the allowable at startup ...; Modbus DI1117Read
BV1346Al_ThTune_ClkBrd.Activeth-Tune clock not working - Alarm status; Modbus DI1118Read
BV1347Al_BMS_Offline.ActiveBMS offline - Alarm status; Modbus DI1121Read
BV1348Al_Selftuning_EVD_Emb.ActiveEVD - Selftuning alarm - Alarm status; Modbus DI1122Read
BV1349Al_Offline_Humisonic.ActiveHumisonic - Offline - Alarm status; Modbus DI1123Read
BV1350Al_HiHum_Humisonic.ActiveHumisonic - High humidity - Alarm status; Modbus DI1124Read
BV1351Al_LowHum_Humisonic.ActiveHumisonic - Low humidity - Alarm status; Modbus DI1125Read
BV1352Al_NoProd_Humisonic.ActiveHumisonic - No production - Alarm status; Modbus DI1126Read
BV1353Al_FaultyDrn_Humisonic.ActiveHumisonic - Faulty drain - Alarm status; Modbus DI1127Read
BV1354Al_Wmissing_Humisonic.ActiveHumisonic - Missing water - Alarm status; Modbus DI1128Read
BV1355Al_ExtSignal_Humisonic.ActiveHumisonic - External signal not correctly connected - Alarm status; Modbus DI1129Read
BV1356Al_Functest_Humisonic.ActiveHumisonic - Functional test not executed - Alarm status; Modbus DI1130Read
BV1357Al_Autotest_Humisonic.ActiveHumisonic - Autotest failure - Alarm status; Modbus DI1131Read
BV1358Al_EEPROM_Err_Humisonic.ActiveHumisonic - EEPROM error - Alarm status; Modbus DI1132Read
BV1359Al_Offline_EBM_SupplyFan.ActiveEBM supply fan - Offline - Alarm status; Modbus DI1133Read
BV1360Al_Generic_EBM_SupplyFan.ActiveEBM supply fan 1 - Generic alarm; Modbus DI1134Read
BV1385Al_Offline_EBM_RetFan.ActiveEBM return fan - Offline - Alarm status; Modbus DI1159Read
BV1361Al_Offline_EBM_SupplyFan2.ActiveEBM supply fan 2 - Offline; Modbus DI1135Read
BV1362Al_Generic_EBM_SupplyFan2.ActiveEBM supply fan 2 - Generic alarm; Modbus DI1136Read
BV1363Al_Offline_EBM_SupplyFan3.ActiveEBM supply fan 3 - Offline; Modbus DI1137Read
BV1364Al_Generic_EBM_SupplyFan3.ActiveEBM supply fan 3 - Generic alarm; Modbus DI1138Read
BV1365Al_Offline_EBM_SupplyFan4.ActiveEBM supply fan 4 - Offline; Modbus DI1139Read
BV1366Al_Generic_EBM_SupplyFan4.ActiveEBM supply fan 4 - Generic alarm; Modbus DI1140Read
BV1367Al_NOT_USED_138.ActiveAlarm NOT USED 138; Modbus DI1141Read
BV1368Al_NOT_USED_139.ActiveAlarm NOT USED 139; Modbus DI1142Read
BV1369Al_NOT_USED_140.ActiveAlarm NOT USED 140; Modbus DI1143Read
BV1370Al_NOT_USED_141.ActiveAlarm NOT USED 141; Modbus DI1144Read
BV1371Al_NOT_USED_142.ActiveAlarm NOT USED 142; Modbus DI1145Read
BV1372Al_NOT_USED_143.ActiveAlarm NOT USED 143; Modbus DI1146Read
BV1373Al_NOT_USED_144.ActiveAlarm NOT USED 144; Modbus DI1147Read
BV1374Al_NOT_USED_145.ActiveAlarm NOT USED 145; Modbus DI1148Read
BV1375Al_NOT_USED_146.ActiveAlarm NOT USED 146; Modbus DI1149Read
BV1376Al_NOT_USED_147.ActiveAlarm NOT USED 147; Modbus DI1150Read
BV1377Al_NOT_USED_148.ActiveAlarm NOT USED 148; Modbus DI1151Read
BV1378Al_NOT_USED_149.ActiveAlarm NOT USED 149; Modbus DI1152Read
BV1379Al_NOT_USED_150.ActiveAlarm NOT USED 150; Modbus DI1153Read
BV1380Al_NOT_USED_151.ActiveAlarm NOT USED 151; Modbus DI1154Read
BV1381Al_NOT_USED_152.ActiveAlarm NOT USED 152; Modbus DI1155Read
BV1382Al_NOT_USED_153.ActiveAlarm NOT USED 153; Modbus DI1156Read
BV1383Al_NOT_USED_154.ActiveAlarm NOT USED 154; Modbus DI1157Read
BV1384Al_NOT_USED_155.ActiveAlarm NOT USED 155; Modbus DI1158Read
BV1386Al_Generic_EBM_RetFan.ActiveEBM return fan 1 - Generic alarm; Modbus DI1160Read
BV1387Al_Offline_EBM_RetFan2.ActiveEBM return fan 2 - Offline; Modbus DI1161Read
BV1388Al_Generic_EBM_RetFan2.ActiveEBM return fan 2 - Generic alarm; Modbus DI1162Read
BV1389Al_Offline_EBM_RetFan3.ActiveEBM return fan 3 - Offline; Modbus DI1163Read
BV1390Al_Generic_EBM_RetFan3.ActiveEBM return fan 3 - Generic alarm; Modbus DI1164Read
BV1391Al_Offline_EBM_RetFan4.ActiveEBM return fan 4 - Offline; Modbus DI1165Read
BV1392Al_Generic_EBM_RetFan4.ActiveEBM return fan 4 - Generic alarm; Modbus DI1166Read
BV1393Al_NOT_USED_164.ActiveAlarm NOT USED 164; Modbus DI1167Read
BV1394Al_NOT_USED_165.ActiveAlarm NOT USED 165; Modbus DI1168Read
BV1395Al_NOT_USED_166.ActiveAlarm NOT USED 166; Modbus DI1169Read
BV1396Al_NOT_USED_167.ActiveAlarm NOT USED 167; Modbus DI1170Read
BV1397Al_NOT_USED_168.ActiveAlarm NOT USED 168; Modbus DI1171Read
BV1398Al_NOT_USED_169.ActiveAlarm NOT USED 169; Modbus DI1172Read
BV1399Al_NOT_USED_170.ActiveAlarm NOT USED 170; Modbus DI1173Read
BV1400Al_NOT_USED_171.ActiveAlarm NOT USED 171; Modbus DI1174Read
BV1401Al_NOT_USED_172.ActiveAlarm NOT USED 172; Modbus DI1175Read
BV1402Al_NOT_USED_173.ActiveAlarm NOT USED 173; Modbus DI1176Read
BV1403Al_NOT_USED_174.ActiveAlarm NOT USED 174; Modbus DI1177Read
BV1404Al_NOT_USED_175.ActiveAlarm NOT USED 175; Modbus DI1178Read
BV1405Al_NOT_USED_176.ActiveAlarm NOT USED 176; Modbus DI1179Read
BV1406Al_NOT_USED_177.ActiveAlarm NOT USED 177; Modbus DI1180Read
BV1407Al_NOT_USED_178.ActiveAlarm NOT USED 178; Modbus DI1181Read
BV1408Al_NOT_USED_179.ActiveAlarm NOT USED 179; Modbus DI1182Read
BV1409Al_NOT_USED_180.ActiveAlarm NOT USED 180; Modbus DI1183Read
BV1410Al_NOT_USED_181.ActiveAlarm NOT USED 181; Modbus DI1184Read
BV1411Al_WrkHrs_ModulHum.ActiveWarning - Modulating humidifier maintenance required - Alarm status; Modbus DI1185Read
BV1412Al_RecoveryOvld.ActiveThermal wheel overload - Alarm status; Modbus DI1186Read
BV1413Al_Offline_ZA_SupplyFan.ActiveZA supply fan - Offline - Alarm status; Modbus DI1187Read
BV1414Al_Generic_ZA_SupplyFan.ActiveZA supply fan 1 - Generic alarm; Modbus DI1188Read
BV1415Al_Offline_ZA_SupplyFan2.ActiveZA supply fan 2 - Offline; Modbus DI1189Read
BV1416Al_Generic_ZA_SupplyFan2.ActiveZA supply fan 2 - Generic alarm; Modbus DI1190Read
BV1417Al_Offline_ZA_SupplyFan3.ActiveZA supply fan 3 - Offline; Modbus DI1191Read
BV1418Al_Generic_ZA_SupplyFan3.ActiveZA supply fan 3 - Generic alarm; Modbus DI1192Read
BV1419Al_Offline_ZA_SupplyFan4.ActiveZA supply fan 4 - Offline; Modbus DI1193Read
BV1420Al_Generic_ZA_SupplyFan4.ActiveZA supply fan 4 - Generic alarm; Modbus DI1194Read
BV1421Al_FwIncompatible_ZA_SupplyFan.ActiveZA supply fan 1 - Firmware incompatible; Modbus DI1195Read
BV1422Al_FwIncompatible_ZA_SupplyFan2.ActiveZA supply fan 2 - Firmware incompatible; Modbus DI1196Read
BV1423Al_FwIncompatible_ZA_SupplyFan3.ActiveZA supply fan 3 - Firmware incompatible; Modbus DI1197Read
BV1424Al_FwIncompatible_ZA_SupplyFan4.ActiveZA supply fan 4 - Firmware incompatible; Modbus DI1198Read
BV1426Al_Generic_ZA_RetFan.ActiveZA return fan 1 - Generic alarm; Modbus DI1200Read
BV1427Al_Offline_ZA_RetFan2.ActiveZA return fan 2 - Offline; Modbus DI1201Read
BV1428Al_Generic_ZA_RetFan2.ActiveZA return fan 2 - Generic alarm; Modbus DI1202Read
BV1429Al_Offline_ZA_RetFan3.ActiveZA return fan 3 - Offline; Modbus DI1203Read
BV1430Al_Generic_ZA_RetFan3.ActiveZA return fan 3 - Generic alarm; Modbus DI1204Read
BV1431Al_Offline_ZA_RetFan4.ActiveZA return fan 4 - Offline; Modbus DI1205Read
BV1432Al_Generic_ZA_RetFan4.ActiveZA return fan 4 - Generic alarm; Modbus DI1206Read
BV1433Al_FwIncompatible_ZA_RetFan.ActiveZA return fan 1 - Firmware incompatible; Modbus DI1207Read
BV1434Al_FwIncompatible_ZA_RetFan2.ActiveZA return fan 2 - Firmware incompatible; Modbus DI1208Read
BV1435Al_FwIncompatible_ZA_RetFan3.ActiveZA return fan 3 - Firmware incompatible; Modbus DI1209Read
BV1436Al_FwIncompatible_ZA_RetFan4.ActiveZA return fan 4 - Firmware incompatible; Modbus DI1210Read
BV1436Al_PeakCurrent_ZA_RetFan.ActiveZA return fan - Peak current - Alarm status; Modbus DI1210Read
BV1437Al_ErrCfgB2P.ActiveIO - Configuration error - Alarm status; Modbus DI1211Read
BV1438Al_HighSupplyTemp.ActiveHigh supply temperature - Alarm status; Modbus DI1212Read
BV1439Al_VDI_HygieneInspection_0_0.ActiveAlarm VDI - Hygiene Inspection - Alarm status; Modbus DI1213Read
BV1440Al_VDI_OutdoorAirInlets_1_1.ActiveAlarm VDI - Check for contamination, damage and corrosion - ...; Modbus DI1214Read
BV1441Al_VDI_Dehum_3_1.ActiveAlarm VDI - Check for contamination, damage and corrosion - ...; Modbus DI1215Read
BV1442Al_VDI_Dehum_3_2.ActiveAlarm VDI - Function check drain and syphon - Alarm status; Modbus DI1216Read
BV1443Al_VDI_Dehum_3_3.ActiveAlarm VDI - Clean wet cooler, mist collector and condensate ...; Modbus DI1217Read
BV1444Al_VDI_AHUHousing_4_1.ActiveAlarm VDI - Check for contamination, damage and corrosion on ...; Modbus DI1218Read
BV1445Al_VDI_AHUHousing_4_2.ActiveAlarm VDI - Check for water precipitation - Alarm status; Modbus DI1219Read
BV1446Al_VDI_AHUHousing_4_3.ActiveAlarm VDI - Check empty housings for contamination, damage, and ...; Modbus DI1220Read
BV1447Al_VDI_AirHumWithNoClearW_6_2_1.ActiveAlarm VDI - Check for contamination, damage, microbial growth and ...; Modbus DI1221Read
BV1448Al_VDI_AirHumWithNoClearW_6_2_2.ActiveAlarm VDI - Check condensate precipitation in the humidifier chamber ...; Modbus DI1222Read
BV1449Al_VDI_AirHumWithNoClearW_6_2_3.ActiveAlarm VDI - Check vapour distribution system for deposit - ...; Modbus DI1223Read
BV1450Al_VDI_AirHumWithNoClearW_6_2_4.ActiveAlarm VDI - Check spray nozzle for deposits - Alarm status; Modbus DI1224Read
BV1451Al_VDI_AirHumWithNoClearW_6_2_5.ActiveAlarm VDI - Check drain - Alarm status; Modbus DI1225Read
BV1452Al_VDI_AirHumWithNoClearW_6_2_6.ActiveAlarm VDI - Determine number of CFU in the humidifier ...; Modbus DI1226Read
BV1453Al_VDI_AirHumWithNoClearW_6_2_7.ActiveAlarm VDI - Function check control valve - Alarm status; Modbus DI1227Read
BV1454Al_VDI_AirHumWithNoClearW_6_2_8.ActiveAlarm VDI - Check humidity limiter - Alarm status; Modbus DI1228Read
BV1455Al_VDI_AirFilt_8_1.ActiveAlarm VDI - Check for unacceptable contamination and damage (leakage) ...; Modbus DI1229Read
BV1456Al_VDI_AirFilt_8_2.ActiveAlarm VDI - Check differential pressure - Alarm status; Modbus DI1230Read
BV1457Al_VDI_AirFilt_8_3.ActiveAlarm VDI - Maximum interval until first filter stage is ...; Modbus DI1231Read
BV1458Al_VDI_AirFilt_8_4.ActiveAlarm VDI - Maximum interval until second filter stage is ...; Modbus DI1232Read
BV1459Al_VDI_AirDuct_9_1.ActiveAlarm VDI - Check accessible duct section for damage - ...; Modbus DI1233Read
BV1460Al_VDI_AirDuct_9_2.ActiveAlarm VDI - Check two or three representative locations on ...; Modbus DI1234Read
BV1461Al_VDI_Silencers_11_1.ActiveAlarm VDI - Check silencers for contamination. Damage, and corrosion ...; Modbus DI1235Read
BV1462Al_VDI_Fan_12_1.ActiveAlarm VDI - Check for contamination, damage, and corrosion - ...; Modbus DI1236Read
BV1463Al_VDI_HeatExch_13_1.ActiveAlarm VDI - Visual inspection of air-to-air plate or cross ...; Modbus DI1237Read
BV1464Al_VDI_HeatExch_13_2.ActiveAlarm VDI - Visual inspection of air-to-air rotary heat exchanger ...; Modbus DI1238Read
BV1465Al_VDI_HeatExch_13_4.ActiveAlarm VDI - Heaters: Check for contamination damage, corrosion and ...; Modbus DI1239Read
BV1466Al_VDI_HeatExch_13_5.ActiveAlarm VDI - Coolers: Check tube bundles, mist collectors and ...; Modbus DI1240Read
BV1467Al_VDI_HeatExch_13_6.ActiveAlarm VDI - Function-check drain and syphon - Alarm status; Modbus DI1241Read
BV1468Al_VDI_SupplyHum.ActiveAlarm VDI - Supply humidity probe is needed - Alarm status; Modbus DI1242Read
BV1469Al_DoorSw.ActiveAlarm - Door open - Alarm status; Modbus DI1243Read
BV1470Al_FireSmoke.ActiveAlarm - Fire/Smoke - Alarm status; Modbus DI1244Read
BV1471Al_SrsAlrmByDin.ActiveSerious alarm from digital input - Alarm status; Modbus DI1245Read
BV1472Al_GenericWarnByDin.ActiveGeneric warning from digital input - Alarm status; Modbus DI1246Read
BV1473Al_Sup1_DirtyFiltByDin.ActiveSupply - Dirty filter alarm - Alarm status; Modbus DI1247Read
BV1474Al_Sup2_DirtyFiltByDin.ActiveSupply 2 - Dirty filter alarm - Alarm status; Modbus DI1248Read
BV1475Al_Ret_DirtyFiltByDin.ActiveReturn - Dirty filter alarm - Alarm status; Modbus DI1249Read
BV1476Al_HEPA_Filt1.ActiveHEPA Filter 1 alarm - Alarm status; Modbus DI1250Read
BV1477Al_HEPA_Filt2.ActiveHEPA Filter 2 alarm - Alarm status; Modbus DI1251Read
BV1478Al_MainCoilPmp1_Ovld.ActiveMain coil pump 1 overload - Alarm status; Modbus DI1252Read
BV1479Al_MainCoilPmp2_Ovld.ActiveMain coil pump 2 overload - Alarm status; Modbus DI1253Read
BV1480Al_ReHeatCoilPmp1_Ovld.ActiveRe heat coil pump 1 overload - Alarm status; Modbus DI1254Read
BV1481Al_ReHeatCoilPmp2_Ovld.ActiveRe heat coil pump 2 overload - Alarm status; Modbus DI1255Read
BV1482Al_PreHeatCoilPmp1_Ovld.ActivePre heat coil pump 1 overload - Alarm status; Modbus DI1256Read
BV1483Al_PreHeatCoilPmp2_Ovld.ActivePre heat coil pump 2 overload - Alarm status; Modbus DI1257Read
BV1484Al_MainCoilFlwSw.ActiveMain coil flow switch alarm - Alarm status; Modbus DI1258Read
BV1485Al_ReHeatCoilFlwSw.ActiveRe heat coil flow switch alarm - Alarm status; Modbus DI1259Read
BV1486Al_PreHeatCoilFlwSw.ActivePre heat coil flow switch alarm - Alarm status; Modbus DI1260Read
BV1487Al_RecoveryClogged.ActiveRecovery clogged alarm - Alarm status; Modbus DI1261Read
BV1488Al_ReHeat_Ovld.ActiveRe heat coil alarm - Alarm status; Modbus DI1262Read
BV1489Al_PreHeat_Ovld.ActivePre heat coil alarm - Alarm status; Modbus DI1263Read
BV1490Al_uChiller_Alrm.ActiveAlarm - uChiller - Alarm status; Modbus DI1264Read
BV1491Al_uChiller_Offline.ActiveAlarm - uChiller offline - Alarm status; Modbus DI1265Read
BV1492Al_WrkHrs_MainCoilPmp1.ActiveWarning - Main coil pump 1 maintenance required - Alarm status; Modbus DI1266Read
BV1493Al_WrkHrs_MainCoilPmp2.ActiveWarning - Main coil pump 2 maintenance required - Alarm status; Modbus DI1267Read
BV1494Al_WrkHrs_MainCoilAout.ActiveWarning - Main coil analog output maintenance required - Alarm status; Modbus DI1268Read
BV1495Al_WrkHrs_MainCoilStep1.ActiveWarning - Main coil step 1 maintenance required - Alarm status; Modbus DI1269Read
BV1496Al_WrkHrs_MainCoilStep2.ActiveWarning - Main coil step 2 maintenance required - Alarm status; Modbus DI1270Read
BV1497Al_WrkHrs_MainCoilStep3.ActiveWarning - Main coil step 3 maintenance required - Alarm status; Modbus DI1271Read
BV1498Al_WrkHrs_MainCoilStep4.ActiveWarning - Main coil step 4 maintenance required - Alarm status; Modbus DI1272Read
BV1499Al_WrkHrs_PreHeatCoilPmp1.ActiveWarning - Pre-heating coil pump 1 maintenance required - Alarm status; Modbus DI1273Read
BV1500Al_WrkHrs_PreHeatCoilPmp2.ActiveWarning - Pre-heating coil pump 2 maintenance required - Alarm status; Modbus DI1274Read
BV1501Al_WrkHrs_PreHeatCoilAout.ActiveWarning - Pre-heating coil analog output maintenance required - Alarm status; Modbus DI1275Read
BV1502Al_WrkHrs_PreHeatCoilStep1.ActiveWarning - Pre-heating coil step 1 maintenance required - Alarm status; Modbus DI1276Read
BV1503Al_WrkHrs_PreHeatCoilStep2.ActiveWarning - Pre-heating coil step 2 maintenance required - Alarm status; Modbus DI1277Read
BV1504Al_WrkHrs_PreHeatCoilStep3.ActiveWarning - Pre-heating coil step 3 maintenance required - Alarm status; Modbus DI1278Read
BV1505Al_WrkHrs_PreHeatCoilStep4.ActiveWarning - Pre-heating coil step 4 maintenance required - Alarm status; Modbus DI1279Read
BV1506Al_WrkHrs_ReHeatCoilStep4.ActiveWarning - Re-heating coil step 4 maintenance required - Alarm status; Modbus DI1280Read
BV1507Al_WrkHrs_ReHeatCoilPmp1.ActiveWarning - Re-heating coil pump 1 maintenance required - Alarm status; Modbus DI1281Read
BV1508Al_WrkHrs_ReHeatCoilPmp2.ActiveWarning - Re-heating coil pump 2 maintenance required - Alarm status; Modbus DI1282Read
BV1509Al_WrkHrs_ReHeatCoilAout.ActiveWarning - Re-heating coil analog output maintenance required - Alarm status; Modbus DI1283Read
BV1510Al_WrkHrs_ReHeatCoilStep1.ActiveWarning - Re-heating coil step 1 maintenance required - Alarm status; Modbus DI1284Read
BV1511Al_WrkHrs_ReHeatCoilStep2.ActiveWarning - Re-heating coil step 2 maintenance required - Alarm status; Modbus DI1285Read
BV1512Al_WrkHrs_ReHeatCoilStep3.ActiveWarning - Re-heating coil step 3 maintenance required - Alarm status; Modbus DI1286Read
BV1513Al_WrkHrs_AuxDout.ActiveWarning - Auxiliary digital output maintenance required - Alarm status; Modbus DI1287Read
BV1514Al_WrkHrs_AuxAout.ActiveWarning - Auxiliary analogue output maintenance required - Alarm status; Modbus DI1288Read
BV1515Al_WrkHrs_IEC.ActiveWarning - IEC maintenance required - Alarm status; Modbus DI1289Read
BV1516Al_WrkHrs_Unit.ActiveWarning - Unit maintenance required - Alarm status; Modbus DI1290Read
BV1517Al_Humifog.ActiveAlarm - Humifog alarms present - Alarm status; Modbus DI1291Read
BV1518Al_IEC_Humifog.ActiveAlarm - IEC Humifog alarms present - Alarm status; Modbus DI1292Read
BV1519Al_Humifog_Offline.ActiveAlarm - Humifog offline - Alarm status; Modbus DI1293Read
BV1520Al_IEC_Humifog_Offline.ActiveAlarm - IEC Humifog offline - Alarm status; Modbus DI1294Read
BV1522Al_EEV_HWCompatErr.ActiveAlarm - EEV Hardware compatibility error - Alarm status; Modbus DI1296Read
BV1523Al_PGDx_Offline.ActiveWarning - pGDx Offline - Alarm status; Modbus DI1297Read
BV3934Al_cpCOe_1_Offline.ActiveAlarm - c.pCOe n.1 Offline - Alarm status; Modbus DI1298Read
BV3935Al_cpCOe_2_Offline.ActiveAlarm - c.pCOe n.2 Offline - Alarm status; Modbus DI1299Read
BV3936Al_cpCOe_3_Offline.ActiveAlarm - c.pCOe n.3 Offline - Alarm status; Modbus DI1300Read
BV3937Al_cpCOe_4_Offline.ActiveAlarm - c.pCOe n.4 Offline - Alarm status; Modbus DI1301Read
BV3932Warn_PreHeatCoilTOutOfRange.ActivePreheating coil water temperature out of range warning - Alarm status; Modbus DI1302Read
BV3933Warn_ReHeatCoilTOutOfRange.ActiveReheating coil water temperature out of range warning - Alarm status; Modbus DI1303Read
BV3941MainCoil_FloatVlvMain Coil type: floating valve; Modbus DI1304Read
BV3942Coils.PreHeatCoil_FloatVlvPreHeat coil type: floating valve; Modbus DI1305Read
BV3943Coils.ReHeatCoil_FloatVlvReHeat coil type: floating valve; Modbus DI1306Read
BV3944MainVlv_ReadyToGoMain Coil: floating valve ready to go( FALSE: Pre-positioning in ...; Modbus DI1307Read
BV3945PreHeatVlv_ReadyToGoPreHeat Coil: floating valve ready to go( FALSE: Pre-positioning in ...; Modbus DI1308Read
BV3946ReHeatVlv_ReadyToGoReHeat Coil: floating valve ready to go( FALSE: Pre-positioning in ...; Modbus DI1309Read
BV3951AirQuality_PM10.Alrm_RAir quality: PM 10 - Alarm probe broken or disconnected; Modbus DI1310Read
BV3981AirQuality_PM10.Configured_RAir quality: PM 10 - Configured; Modbus DI1311Read
BV3982AirQuality_PM10.Enable_WAir quality: PM 10 - Enable input; Modbus DI1312Read
BV3986AirQuality_PM10.PrbOk_RAir quality: PM 10 - Probe working correctly; Modbus DI1313Read
BV3990AirQuality_PM25.Alrm_RAir quality: PM 2.5 - Alarm probe broken or disconnected; Modbus DI1314Read
BV3995AirQuality_PM25.Configured_RAir quality: PM 2.5 - Configured; Modbus DI1315Read
BV3996AirQuality_PM25.Enable_WAir quality: PM 2.5 - Enable input; Modbus DI1316Read
BV4000AirQuality_PM25.PrbOk_RAir quality: PM 2.5 - Probe working correctly; Modbus DI1317Read
BV4007SanificationDevice.Val_WSanification device; Modbus DI1318Read
BV4008SanificationDevice.Val_Hw_RSanification device - Hardware value writes from board; Modbus DI1319Read
BV4012SanificationDevice.Enable_WSanification device - Enable output; Modbus DI1320Read
BV4013SanificationDevice.Configured_RSanification device - Configurated; Modbus DI1321Read
BV3968Al_AirQuality_PM10.ActivePM10 probe alarm - Alarm status; Modbus DI1322Read
BV3969Al_AirQuality_PM25.ActivePM2.5 probe alarm - Alarm status; Modbus DI1323Read
BV3958Sanification.SanificationDevice_IO_CfgWarnModbus DI1324Read
BV3960Regulation.QualityAirDevNotSelModbus DI1325Read
BV3970Al_SanificationWarn.ActiveAlarm - Sanification device - Alarm status; Modbus DI1326Read
BV3971Al_WrkHrs_SanificationDevice.ActiveWarning - Sanification device maintenance required - Alarm status; Modbus DI1327Read
BV4038PurgeOnPurge is on; Modbus DI1328Read
BV4039SanificationDeviceOvld.Val_Hw_RSanification deivce overload switch - Value reads from board; Modbus DI1329Read
BV4040SanificationDeviceOvld.Configured_RSanification deivce overload switch - Configured; Modbus DI1330Read
BV4041SanificationDeviceOvld.Val_RSanification deivce overload switch; Modbus DI1331Read
BV4042FC_ActFreecooling activated; Modbus DI1332Read
BV4043FH_ActFreeheating activated; Modbus DI1333Read
BV4071Al_WrkHrs_SupplyFan_2.ActiveWarning - Supply fan 2 maintenance required; Modbus DI1334Read
BV4072Al_WrkHrs_SupplyFan_3.ActiveWarning - Supply fan 3 maintenance required; Modbus DI1335Read
BV4073Al_WrkHrs_SupplyFan_4.ActiveWarning - Supply fan 4 maintenance required; Modbus DI1336Read
BV4074Al_WrkHrs_ReturnFan_2.ActiveWarning - Return 2 fan maintenance required; Modbus DI1337Read
BV4075Al_WrkHrs_ReturnFan_3.ActiveWarning - Return 3 fan maintenance required; Modbus DI1338Read
BV4076Al_WrkHrs_ReturnFan_4.ActiveWarning - Return 4 fan maintenance required; Modbus DI1339Read
BV4286SupplyFan_FireSmokeAlrm_ActSupply Fans active during Fire/Smoke alarm; Modbus DI1340Read
BV4287RetFan_FireSmokeAlrm_ActReturn Fans active during Fire/Smoke alarm; Modbus DI1341Read
BV4330Al_SupplyFanInv.ActiveAlarm - Supply fan inverter feedback - Alarm status; Modbus DI1342Read
BV4331Al_RetFanInv.ActiveAlarm - Return fan inverter feedback - Alarm status; Modbus DI1343Read
BV4332Al_SupplyDampSw.ActiveAlarm - Supply damper feedback - Alarm status; Modbus DI1344Read
BV4333Al_RetDampSw.ActiveAlarm - Return damper feedback - Alarm status; Modbus DI1345Read
BV4334Al_FreshAirDampSw.ActiveAlarm - Fresh air damper feedback - Alarm status; Modbus DI1346Read
BV4335Al_ExhAirDampSw.ActiveAlarm - Exhaust air damper feedback - Alarm status; Modbus DI1347Read
BV4336Al_MixAirDampSw.ActiveAlarm - Mixing air damper feedback - Alarm status; Modbus DI1348Read
BV4337Al_HumiSteam_Offline.ActiveHumiSteam - Offline alarm - Alarm status; Modbus DI1349Read
BV4338Al_HumiSteam_Generic.ActiveHumiSteam - Generic alarm - Alarm status; Modbus DI1350Read
BV4362SummerWinterSummer/Winter mode (FALSE:Summer, TRUE:Winter); Modbus DI1351Read
BV4363MainCoil_CoolHeatMain coil cooling/heating; Modbus DI1352Read
BV4364MainCoilCoolHeat_Din.Configured_RMain coil cool/heat - digital input - Configured; Modbus DI1353Read
BV4365MainCoilCoolHeat_Din.Enable_WMain coil cool/heat - digital input - Enable input; Modbus DI1354Read
BV4366MainCoilCoolHeat_Din.Val_RMain coil cool/heat - digital input; Modbus DI1355Read
BV4368HumDehum_ModeHumidification/Dehumidification (FALSE: humidification; TRUE: dehumidification); Modbus DI1356Read
BV4377GenericAin1.Enable_WGeneric Ain1 - Enable input; Modbus DI1357Read
BV4378GenericAin1.Configured_RGeneric Ain1 - Configured; Modbus DI1358Read
BV4379GenericAin1.PrbOk_RGeneric Ain1 - Probe working correctly; Modbus DI1359Read
BV4380GenericAin1.Alrm_RGeneric Ain1 - Alarm probe broken or disconnected; Modbus DI1360Read
BV4391GenericAin2.Enable_WGeneric Ain2 - Enable input; Modbus DI1361Read
BV4392GenericAin2.Configured_RGeneric Ain2 - Configured; Modbus DI1362Read
BV4393GenericAin2.PrbOk_RGeneric Ain2 - Probe working correctly; Modbus DI1363Read
BV4394GenericAin2.Alrm_RGeneric Ain2 - Alarm probe broken or disconnected; Modbus DI1364Read
BV4405GenericAin3.Enable_WGeneric Ain3 - Enable input; Modbus DI1365Read
BV4406GenericAin3.Configured_RGeneric Ain3 - Configured; Modbus DI1366Read
BV4407GenericAin3.PrbOk_RGeneric Ain3 - Probe working correctly; Modbus DI1367Read
BV4408GenericAin3.Alrm_RGeneric Ain3 - Alarm probe broken or disconnected; Modbus DI1368Read
BV4419GenericAin4.Enable_WGeneric Ain4 - Enable input; Modbus DI1369Read
BV4420GenericAin4.Configured_RGeneric Ain4 - Configured; Modbus DI1370Read
BV4421GenericAin4.PrbOk_RGeneric Ain4 - Probe working correctly; Modbus DI1371Read
BV4422GenericAin4.Alrm_RGeneric Ain4 - Alarm probe broken or disconnected; Modbus DI1372Read
BV4433GenericAin5.Enable_WGeneric Ain5 - Enable input; Modbus DI1373Read
BV4434GenericAin5.Configured_RGeneric Ain5 - Configured; Modbus DI1374Read
BV4435GenericAin5.PrbOk_RGeneric Ain5 - Probe working correctly; Modbus DI1375Read
BV4436GenericAin5.Alrm_RGeneric Ain5 - Alarm probe broken or disconnected; Modbus DI1376Read
BV4448GenericDin1.Val_Hw_RGeneric Din1 - digital input - Value reads from board; Modbus DI1377Read
BV4449GenericDin1.Enable_WGeneric Din1 - digital input - Enable input; Modbus DI1378Read
BV4450GenericDin1.Configured_RGeneric Din1 - digital input - Configured; Modbus DI1379Read
BV4451GenericDin1.Val_RGeneric Din1 - digital input; Modbus DI1380Read
BV4455GenericDin2.Val_Hw_RGeneric Din2 - digital input - Value reads from board; Modbus DI1381Read
BV4456GenericDin2.Enable_WGeneric Din2 - digital input - Enable input; Modbus DI1382Read
BV4457GenericDin2.Configured_RGeneric Din2 - digital input - Configured; Modbus DI1383Read
BV4458GenericDin2.Val_RGeneric Din2 - digital input; Modbus DI1384Read
BV4462GenericDin3.Val_Hw_RGeneric Din3 - digital input - Value reads from board; Modbus DI1385Read
BV4463GenericDin3.Enable_WGeneric Din3 - digital input - Enable input; Modbus DI1386Read
BV4464GenericDin3.Configured_RGeneric Din3 - digital input - Configured; Modbus DI1387Read
BV4465GenericDin3.Val_RGeneric Din3 - digital input; Modbus DI1388Read
BV4469GenericDin4.Val_Hw_RGeneric Din4 - digital input - Value reads from board; Modbus DI1389Read
BV4470GenericDin4.Enable_WGeneric Din4 - digital input - Enable input; Modbus DI1390Read
BV4471GenericDin4.Configured_RGeneric Din4 - digital input - Configured; Modbus DI1391Read
BV4472GenericDin4.Val_RGeneric Din4 - digital input; Modbus DI1392Read
BV4476GenericDin5.Val_Hw_RGeneric Din5 - digital input - Value reads from board; Modbus DI1393Read
BV4477GenericDin5.Enable_WGeneric Din5 - digital input - Enable input; Modbus DI1394Read
BV4478GenericDin5.Configured_RGeneric Din5 - digital input - Configured; Modbus DI1395Read
BV4479GenericDin5.Val_RGeneric Din5 - digital input; Modbus DI1396Read
BV4487Al_GenericAin1.ActiveGeneric Ain1 probe alarm - Alarm status; Modbus DI1397Read
BV4488Al_GenericAin2.ActiveGeneric Ain2 probe alarm - Alarm status; Modbus DI1398Read
BV4489Al_GenericAin3.ActiveGeneric Ain3 probe alarm - Alarm status; Modbus DI1399Read
BV4490Al_GenericAin4.ActiveGeneric Ain4 probe alarm - Alarm status; Modbus DI1400Read
BV4491Al_GenericAin5.ActiveGeneric Ain5 probe alarm - Alarm status; Modbus DI1401Read
BV4492Al_GenericDin1.ActiveAlarm - Generic Din 1 - Alarm status; Modbus DI1402Read
BV4493Al_GenericDin2.ActiveAlarm - Generic Din 2 - Alarm status; Modbus DI1403Read
BV4494Al_GenericDin3.ActiveAlarm - Generic Din 3 - Alarm status; Modbus DI1404Read
BV4495Al_GenericDin4.ActiveAlarm - Generic Din 4 - Alarm status; Modbus DI1405Read
BV4496Al_GenericDin5.ActiveAlarm - Generic Din 5 - Alarm status; Modbus DI1406Read
BV4517OA_Vlv_Open.Val_Hw_ROutdoor air pre-treatment floating valve open - Hardware value writes ...; Modbus DI1407Read
BV4518OA_Vlv_Open.Val_WOutdoor air pre-treatment floating valve open; Modbus DI1408Read
BV4519OA_Vlv_Open.Enable_WOutdoor air pre-treatment floating valve open - Enable output; Modbus DI1409Read
BV4520OA_Vlv_Open.Configured_ROutdoor air pre-treatment floating valve open - Configurated; Modbus DI1410Read
BV4521OA_Vlv_Close.Val_Hw_ROutdoor air pre-treatment floating valve close - Hardware value writes ...; Modbus DI1411Read
BV4522OA_Vlv_Close.Val_WOutdoor air pre-treatment floating valve close; Modbus DI1412Read
BV4523OA_Vlv_Close.Enable_WOutdoor air pre-treatment floating valve close - Enable output; Modbus DI1413Read
BV4524OA_Vlv_Close.Configured_ROutdoor air pre-treatment floating valve close - Configurated; Modbus DI1414Read
BV4525OA_Coil_EnabledEnable outdoor air pre-treatment coil; Modbus DI1415Read
BV4526Al_WrkHrs_OA_CoilAout.ActiveWarning - Outdoor air pre-treatment coil analog output maintenance required ...; Modbus DI1416Read
BV4527Al_WrkHrs_OA_CoilStep1.ActiveWarning - Outdoor air pre-treatment coil step 1 maintenance required ...; Modbus DI1417Read
BV4528Al_WrkHrs_OA_CoilStep2.ActiveWarning - Outdoor air pre-treatment coil step 2 maintenance required ...; Modbus DI1418Read
BV4529Al_WrkHrs_OA_CoilStep3.ActiveWarning - Outdoor air pre-treatment coil step 3 maintenance required ...; Modbus DI1419Read
BV4530Al_WrkHrs_OA_CoilStep4.ActiveWarning - Outdoor air pre-treatment coil step 4 maintenance required ...; Modbus DI1420Read
BV4531Warn_OA_CoilTOutOfRange.ActiveOutdoor air pre-treatment coil water temperature out of range warning ...; Modbus DI1421Read
BV4532Coils.OA_Coil_FloatVlvOutdoor air pre-treatment coil type: floating valve; Modbus DI1422Read
BV4533OA_Vlv_ReadyToGoOutdoor air pre-treatment Coil: floating valve ready to go( FALSE: ...; Modbus DI1423Read
PIV1524Scheduler_OnOffUnit.BMS_UnitProfileBMS unit profile; Modbus HR001Write
PIV1525Scheduler_Cfg.Prg[0].Event[0].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR002Write
PIV1526Scheduler_Cfg.Prg[0].Event[0].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR003Write
PIV1527Scheduler_Cfg.Prg[0].Event[0].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR004Write
PIV1528Scheduler_Cfg.Prg[0].Event[1].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR005Write
PIV1529Scheduler_Cfg.Prg[0].Event[1].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR006Write
PIV1530Scheduler_Cfg.Prg[0].Event[1].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR007Write
PIV1531Scheduler_Cfg.Prg[0].Event[2].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR008Write
PIV1532Scheduler_Cfg.Prg[0].Event[2].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR009Write
PIV1533Scheduler_Cfg.Prg[0].Event[2].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR010Write
PIV1534Scheduler_Cfg.Prg[0].Event[3].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR011Write
PIV1535Scheduler_Cfg.Prg[0].Event[3].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR012Write
PIV1536Scheduler_Cfg.Prg[0].Event[3].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR013Write
PIV1537Scheduler_Cfg.Prg[0].Event[4].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR014Write
PIV1538Scheduler_Cfg.Prg[0].Event[4].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR015Write
PIV1539Scheduler_Cfg.Prg[0].Event[4].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR016Write
PIV1540Scheduler_Cfg.Prg[0].Event[5].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR017Write
PIV1541Scheduler_Cfg.Prg[0].Event[5].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR018Write
PIV1542Scheduler_Cfg.Prg[0].Event[5].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR019Write
PIV1543Scheduler_Cfg.Prg[0].Event[6].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR020Write
PIV1544Scheduler_Cfg.Prg[0].Event[6].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR021Write
PIV1545Scheduler_Cfg.Prg[0].Event[6].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR022Write
PIV1546Scheduler_Cfg.Prg[0].Event[7].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR023Write
PIV1547Scheduler_Cfg.Prg[0].Event[7].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR024Write
PIV1548Scheduler_Cfg.Prg[0].Event[7].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR025Write
PIV1549Scheduler_Cfg.Prg[0].Event[8].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR026Write
PIV1550Scheduler_Cfg.Prg[0].Event[8].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR027Write
PIV1551Scheduler_Cfg.Prg[0].Event[8].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR028Write
PIV1552Scheduler_Cfg.Prg[0].Event[9].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR029Write
PIV1553Scheduler_Cfg.Prg[0].Event[9].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR030Write
PIV1554Scheduler_Cfg.Prg[0].Event[9].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR031Write
PIV1555Scheduler_Cfg.Prg[1].Event[0].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR032Write
PIV1556Scheduler_Cfg.Prg[1].Event[0].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR033Write
PIV1557Scheduler_Cfg.Prg[1].Event[0].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR034Write
PIV1558Scheduler_Cfg.Prg[1].Event[1].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR035Write
PIV1559Scheduler_Cfg.Prg[1].Event[1].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR036Write
PIV1560Scheduler_Cfg.Prg[1].Event[1].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR037Write
PIV1561Scheduler_Cfg.Prg[1].Event[2].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR038Write
PIV1562Scheduler_Cfg.Prg[1].Event[2].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR039Write
PIV1563Scheduler_Cfg.Prg[1].Event[2].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR040Write
PIV1564Scheduler_Cfg.Prg[1].Event[3].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR041Write
PIV1565Scheduler_Cfg.Prg[1].Event[3].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR042Write
PIV1566Scheduler_Cfg.Prg[1].Event[3].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR043Write
PIV1567Scheduler_Cfg.Prg[1].Event[4].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR044Write
PIV1568Scheduler_Cfg.Prg[1].Event[4].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR045Write
PIV1569Scheduler_Cfg.Prg[1].Event[4].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Eco-; Modbus HR046Write
PIV1570Scheduler_Cfg.Prg[1].Event[5].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR047Write
PIV1571Scheduler_Cfg.Prg[1].Event[5].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR048Write
PIV1572Scheduler_Cfg.Prg[1].Event[5].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR049Write
PIV1573Scheduler_Cfg.Prg[1].Event[6].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR050Write
PIV1574Scheduler_Cfg.Prg[1].Event[6].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR051Write
PIV1575Scheduler_Cfg.Prg[1].Event[6].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR052Write
PIV1576Scheduler_Cfg.Prg[1].Event[7].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR053Write
PIV1577Scheduler_Cfg.Prg[1].Event[7].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR054Write
PIV1578Scheduler_Cfg.Prg[1].Event[7].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR055Write
PIV1579Scheduler_Cfg.Prg[1].Event[8].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR056Write
PIV1580Scheduler_Cfg.Prg[1].Event[8].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR057Write
PIV1581Scheduler_Cfg.Prg[1].Event[8].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR058Write
PIV1582Scheduler_Cfg.Prg[1].Event[9].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR059Write
PIV1583Scheduler_Cfg.Prg[1].Event[9].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR060Write
PIV1584Scheduler_Cfg.Prg[1].Event[9].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR061Write
PIV1585Scheduler_Cfg.Prg[2].Event[0].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR062Write
PIV1586Scheduler_Cfg.Prg[2].Event[0].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR063Write
PIV1587Scheduler_Cfg.Prg[2].Event[0].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR064Write
PIV1588Scheduler_Cfg.Prg[2].Event[1].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR065Write
PIV1589Scheduler_Cfg.Prg[2].Event[1].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR066Write
PIV1590Scheduler_Cfg.Prg[2].Event[1].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR067Write
PIV1591Scheduler_Cfg.Prg[2].Event[2].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR068Write
PIV1592Scheduler_Cfg.Prg[2].Event[2].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR069Write
PIV1593Scheduler_Cfg.Prg[2].Event[2].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR070Write
PIV1594Scheduler_Cfg.Prg[2].Event[3].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR071Write
PIV1595Scheduler_Cfg.Prg[2].Event[3].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR072Write
PIV1596Scheduler_Cfg.Prg[2].Event[3].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR073Write
PIV1597Scheduler_Cfg.Prg[2].Event[4].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR074Write
PIV1598Scheduler_Cfg.Prg[2].Event[4].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR075Write
PIV1599Scheduler_Cfg.Prg[2].Event[4].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR076Write
PIV1600Scheduler_Cfg.Prg[2].Event[5].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR077Write
PIV1601Scheduler_Cfg.Prg[2].Event[5].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR078Write
PIV1602Scheduler_Cfg.Prg[2].Event[5].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR079Write
PIV1603Scheduler_Cfg.Prg[2].Event[6].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR080Write
PIV1604Scheduler_Cfg.Prg[2].Event[6].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR081Write
PIV1605Scheduler_Cfg.Prg[2].Event[6].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR082Write
PIV1606Scheduler_Cfg.Prg[2].Event[7].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR083Write
PIV1607Scheduler_Cfg.Prg[2].Event[7].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR084Write
PIV1608Scheduler_Cfg.Prg[2].Event[7].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR085Write
PIV1609Scheduler_Cfg.Prg[2].Event[8].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR086Write
PIV1610Scheduler_Cfg.Prg[2].Event[8].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR087Write
PIV1611Scheduler_Cfg.Prg[2].Event[8].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR088Write
PIV1612Scheduler_Cfg.Prg[2].Event[9].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR089Write
PIV1613Scheduler_Cfg.Prg[2].Event[9].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR090Write
PIV1614Scheduler_Cfg.Prg[2].Event[9].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR091Write
PIV1615Scheduler_Cfg.Prg[3].Event[0].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR092Write
PIV1616Scheduler_Cfg.Prg[3].Event[0].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR093Write
PIV1617Scheduler_Cfg.Prg[3].Event[0].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR094Write
PIV1618Scheduler_Cfg.Prg[3].Event[1].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR095Write
PIV1619Scheduler_Cfg.Prg[3].Event[1].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR096Write
PIV1620Scheduler_Cfg.Prg[3].Event[1].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR097Write
PIV1621Scheduler_Cfg.Prg[3].Event[2].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR098Write
PIV1622Scheduler_Cfg.Prg[3].Event[2].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR099Write
PIV1623Scheduler_Cfg.Prg[3].Event[2].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR100Write
PIV1624Scheduler_Cfg.Prg[3].Event[3].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR101Write
PIV1625Scheduler_Cfg.Prg[3].Event[3].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR102Write
PIV1626Scheduler_Cfg.Prg[3].Event[3].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR103Write
PIV1627Scheduler_Cfg.Prg[3].Event[4].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR104Write
PIV1628Scheduler_Cfg.Prg[3].Event[4].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR105Write
PIV1629Scheduler_Cfg.Prg[3].Event[4].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR106Write
PIV1630Scheduler_Cfg.Prg[3].Event[5].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR107Write
PIV1631Scheduler_Cfg.Prg[3].Event[5].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR108Write
PIV1632Scheduler_Cfg.Prg[3].Event[5].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR109Write
PIV1633Scheduler_Cfg.Prg[3].Event[6].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR110Write
PIV1634Scheduler_Cfg.Prg[3].Event[6].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR111Write
PIV1635Scheduler_Cfg.Prg[3].Event[6].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR112Write
PIV1636Scheduler_Cfg.Prg[3].Event[7].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR113Write
PIV1637Scheduler_Cfg.Prg[3].Event[7].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR114Write
PIV1638Scheduler_Cfg.Prg[3].Event[7].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR115Write
PIV1639Scheduler_Cfg.Prg[3].Event[8].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR116Write
PIV1640Scheduler_Cfg.Prg[3].Event[8].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR117Write
PIV1641Scheduler_Cfg.Prg[3].Event[8].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR118Write
PIV1642Scheduler_Cfg.Prg[3].Event[9].HoursScheduler: configuration - Program - Event - Start hours event; Modbus HR119Write
PIV1643Scheduler_Cfg.Prg[3].Event[9].MinsScheduler: configuration - Program - Event - Start minutes event; Modbus HR120Write
PIV1644Scheduler_Cfg.Prg[3].Event[9].ModeScheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR121Write
PIV1651Scheduler_Cfg.SDays[2].DayScheduler: configuration - Special day - Day; Modbus HR128Write
PIV1652Scheduler_Cfg.SDays[2].ModeScheduler: configuration - Special day - Mode; Modbus HR129Write
PIV1653Scheduler_Cfg.SDays[2].MonthScheduler: configuration - Special day - Month; Modbus HR130Write
PIV1654Scheduler_Cfg.SDays[3].DayScheduler: configuration - Special day - Day; Modbus HR131Write
PIV1655Scheduler_Cfg.SDays[3].ModeScheduler: configuration - Special day - Mode; Modbus HR132Write
PIV1656Scheduler_Cfg.SDays[3].MonthScheduler: configuration - Special day - Month; Modbus HR133Write
PIV1657Scheduler_Cfg.SDays[4].DayScheduler: configuration - Special day - Day; Modbus HR134Write
PIV1658Scheduler_Cfg.SDays[4].ModeScheduler: configuration - Special day - Mode; Modbus HR135Write
PIV1659Scheduler_Cfg.SDays[4].MonthScheduler: configuration - Special day - Month; Modbus HR136Write
PIV1660Scheduler_Cfg.SDays[5].DayScheduler: configuration - Special day - Day; Modbus HR137Write
PIV1661Scheduler_Cfg.SDays[5].ModeScheduler: configuration - Special day - Mode; Modbus HR138Write
PIV1662Scheduler_Cfg.SDays[5].MonthScheduler: configuration - Special day - Month; Modbus HR139Write
PIV1663Scheduler_Cfg.SDays[6].DayScheduler: configuration - Special day - Day; Modbus HR140Write
PIV1664Scheduler_Cfg.SDays[6].ModeScheduler: configuration - Special day - Mode; Modbus HR141Write
PIV1665Scheduler_Cfg.SDays[6].MonthScheduler: configuration - Special day - Month; Modbus HR142Write
PIV1666Scheduler_Cfg.SDays[7].DayScheduler: configuration - Special day - Day; Modbus HR143Write
PIV1667Scheduler_Cfg.SDays[7].ModeScheduler: configuration - Special day - Mode; Modbus HR144Write
PIV1668Scheduler_Cfg.SDays[7].MonthScheduler: configuration - Special day - Month; Modbus HR145Write
PIV1669Scheduler_Cfg.SDays[8].DayScheduler: configuration - Special day - Day; Modbus HR146Write
PIV1670Scheduler_Cfg.SDays[8].ModeScheduler: configuration - Special day - Mode; Modbus HR147Write
PIV1671Scheduler_Cfg.SDays[8].MonthScheduler: configuration - Special day - Month; Modbus HR148Write
PIV1672Scheduler_Cfg.SDays[9].DayScheduler: configuration - Special day - Day; Modbus HR149Write
PIV1673Scheduler_Cfg.SDays[9].ModeScheduler: configuration - Special day - Mode; Modbus HR150Write
PIV1674Scheduler_Cfg.SDays[9].MonthScheduler: configuration - Special day - Month; Modbus HR151Write
PIV1675Scheduler_Cfg.SDays[10].DayScheduler: configuration - Special day - Day; Modbus HR152Write
PIV1676Scheduler_Cfg.SDays[10].ModeScheduler: configuration - Special day - Mode; Modbus HR153Write
PIV1677Scheduler_Cfg.SDays[10].MonthScheduler: configuration - Special day - Month; Modbus HR154Write
PIV1678Scheduler_Cfg.SDays[11].DayScheduler: configuration - Special day - Day; Modbus HR155Write
PIV1679Scheduler_Cfg.SDays[11].ModeScheduler: configuration - Special day - Mode; Modbus HR156Write
PIV1680Scheduler_Cfg.SDays[11].MonthScheduler: configuration - Special day - Month; Modbus HR157Write
PIV1681Scheduler_Cfg.SDays[12].DayScheduler: configuration - Special day - Day; Modbus HR158Write
PIV1682Scheduler_Cfg.SDays[12].ModeScheduler: configuration - Special day - Mode; Modbus HR159Write
PIV1683Scheduler_Cfg.SDays[12].MonthScheduler: configuration - Special day - Month; Modbus HR160Write
PIV1684Scheduler_Cfg.SDays[13].DayScheduler: configuration - Special day - Day; Modbus HR161Write
PIV1685Scheduler_Cfg.SDays[13].ModeScheduler: configuration - Special day - Mode; Modbus HR162Write
PIV1686Scheduler_Cfg.SDays[13].MonthScheduler: configuration - Special day - Month; Modbus HR163Write
PIV1687Scheduler_Cfg.SDays[14].DayScheduler: configuration - Special day - Day; Modbus HR164Write
PIV1688Scheduler_Cfg.SDays[14].ModeScheduler: configuration - Special day - Mode; Modbus HR165Write
PIV1689Scheduler_Cfg.SDays[14].MonthScheduler: configuration - Special day - Month; Modbus HR166Write
PIV1690Scheduler_Cfg.Vac[0].EndDayScheduler: configuration - Vacation period - End day; Modbus HR167Write
PIV1691Scheduler_Cfg.Vac[0].EndMonthScheduler: configuration - Vacation period - End month; Modbus HR168Write
PIV1692Scheduler_Cfg.Vac[0].ModeScheduler: configuration - Vacation period - Mode; Modbus HR169Write
PIV1693Scheduler_Cfg.Vac[0].StartDayScheduler: configuration - Vacation period - Start day; Modbus HR170Write
PIV1694Scheduler_Cfg.Vac[0].StartMonthScheduler: configuration - Vacation period - Start month; Modbus HR171Write
PIV1695Scheduler_Cfg.Vac[1].EndDayScheduler: configuration - Vacation period - End day; Modbus HR172Write
PIV1696Scheduler_Cfg.Vac[1].EndMonthScheduler: configuration - Vacation period - End month; Modbus HR173Write
PIV1697Scheduler_Cfg.Vac[1].ModeScheduler: configuration - Vacation period - Mode; Modbus HR174Write
PIV1698Scheduler_Cfg.Vac[1].StartDayScheduler: configuration - Vacation period - Start day; Modbus HR175Write
PIV1699Scheduler_Cfg.Vac[1].StartMonthScheduler: configuration - Vacation period - Start month; Modbus HR176Write
PIV1700Scheduler_Cfg.Vac[2].EndDayScheduler: configuration - Vacation period - End day; Modbus HR177Write
PIV1701Scheduler_Cfg.Vac[2].EndMonthScheduler: configuration - Vacation period - End month; Modbus HR178Write
PIV1702Scheduler_Cfg.Vac[2].ModeScheduler: configuration - Vacation period - Mode; Modbus HR179Write
PIV1703Scheduler_Cfg.Vac[2].StartDayScheduler: configuration - Vacation period - Start day; Modbus HR180Write
PIV1704Scheduler_Cfg.Vac[2].StartMonthScheduler: configuration - Vacation period - Start month; Modbus HR181Write
PIV1705Scheduler_Cfg.WkDays[0]Scheduler: configuration - Week day; Modbus HR182Write
PIV1706Scheduler_Cfg.WkDays[1]Scheduler: configuration - Week day; Modbus HR183Write
PIV1707Scheduler_Cfg.WkDays[2]Scheduler: configuration - Week day; Modbus HR184Write
PIV1708Scheduler_Cfg.WkDays[3]Scheduler: configuration - Week day; Modbus HR185Write
PIV1709Scheduler_Cfg.WkDays[4]Scheduler: configuration - Week day; Modbus HR186Write
PIV1710Scheduler_Cfg.WkDays[5]Scheduler: configuration - Week day; Modbus HR187Write
PIV1711Scheduler_Cfg.WkDays[6]Scheduler: configuration - Week day; Modbus HR188Write
PIV1712GeneralMng.RTC_BMS.DayBMS real time clock; Modbus HR189Write
PIV1713GeneralMng.RTC_BMS.MonthBMS real time clock; Modbus HR190Write
PIV1714GeneralMng.RTC_BMS.YearBMS real time clock; Modbus HR191Write
AV1715CoilRegOffsetOffset to switch on the el heater and pump; Modbus HR192 (garbled row)Write
PIV1716SupplyTemp.Board_RWSupply temperature - Board selected; Modbus HR193Write
PIV1717SupplyTemp.Ch_Id_RWSupply temperature - Channel id selected; Modbus HR194Write
PIV1718SupplyTemp.Ch_Type_RWSupply temperature - Type probe used; Modbus HR195Write
AV1719SupplyTemp.MinVal_RWSupply temperature - Minimum value analog input; Modbus HR196Write
AV1720SupplyTemp.MaxVal_RWSupply temperature - Maximum value analog input; Modbus HR197Write
AV1721SupplyTemp.Offset_RWSupply temperature - Offset analog input; Modbus HR198Write
PIV1722SupplyTemp.ChFilter_RWSupply temperature - Filter channel; Modbus HR199Write
PIV1723SupplyHum.Board_RWSupply humidity - Board selected; Modbus HR200Write
PIV1724SupplyHum.Ch_Id_RWSupply humidity - Channel id selected; Modbus HR201Write
PIV1725SupplyHum.Ch_Type_RWSupply humidity - Type probe used; Modbus HR202Write
AV1726SupplyHum.MinVal_RWSupply humidity - Minimum value analog input; Modbus HR203Write
AV1727SupplyHum.MaxVal_RWSupply humidity - Maximum value analog input; Modbus HR204Write
AV1728SupplyHum.Offset_RWSupply humidity - Offset analog input; Modbus HR205Write
PIV1729SupplyHum.ChFilter_RWSupply humidity - Filter channel; Modbus HR206Write
PIV1730RetTemp.Board_RWReturn temperature - Board selected; Modbus HR207Write
PIV1731RetTemp.Ch_Id_RWReturn temperature - Channel id selected; Modbus HR208Write
PIV1732RetTemp.Ch_Type_RWReturn temperature - Type probe used; Modbus HR209Write
AV1733RetTemp.MinVal_RWReturn temperature - Minimum value analog input; Modbus HR210Write
AV1734RetTemp.MaxVal_RWReturn temperature - Maximum value analog input; Modbus HR211Write
AV1735RetTemp.Offset_RWReturn temperature - Offset analog input; Modbus HR212Write
PIV1736RetTemp.ChFilter_RWReturn temperature - Filter channel; Modbus HR213Write
PIV1737RetHum.Board_RWReturn humidity - Board selected; Modbus HR214Write
PIV1738RetHum.Ch_Id_RWReturn humidity - Channel id selected; Modbus HR215Write
PIV1739RetHum.Ch_Type_RWReturn humidity - Type probe used; Modbus HR216Write
AV1740RetHum.MinVal_RWReturn humidity - Minimum value analog input; Modbus HR217Write
AV1741RetHum.MaxVal_RWReturn humidity - Maximum value analog input; Modbus HR218Write
AV1742RetHum.Offset_RWReturn humidity - Offset analog input; Modbus HR219Write
PIV1743RetHum.ChFilter_RWReturn humidity - Filter channel; Modbus HR220Write
PIV1744RoomTemp.Board_RWRoom temperature - Board selected; Modbus HR221Write
PIV1745RoomTemp.Ch_Id_RWRoom temperature - Channel id selected; Modbus HR222Write
PIV1746RoomTemp.Ch_Type_RWRoom temperature - Type probe used; Modbus HR223Write
AV1747RoomTemp.MinVal_RWRoom temperature - Minimum value analog input; Modbus HR224Write
AV1748RoomTemp.MaxVal_RWRoom temperature - Maximum value analog input; Modbus HR225Write
AV1749RoomTemp.Offset_RWRoom temperature - Offset analog input; Modbus HR226Write
PIV1750RoomTemp.ChFilter_RWRoom temperature - Filter channel; Modbus HR227Write
PIV1751RoomHum.Board_RWRoom humidity - Board selected; Modbus HR228Write
PIV1752RoomHum.Ch_Id_RWRoom humidity - Channel id selected; Modbus HR229Write
PIV1753RoomHum.Ch_Type_RWRoom humidity - Type probe used; Modbus HR230Write
AV1754RoomHum.MinVal_RWRoom humidity - Minimum value analog input; Modbus HR231Write
AV1755RoomHum.MaxVal_RWRoom humidity - Maximum value analog input; Modbus HR232Write
AV1756RoomHum.Offset_RWRoom humidity - Offset analog input; Modbus HR233Write
PIV1757RoomHum.ChFilter_RWRoom humidity - Filter channel; Modbus HR234Write
PIV1758ExtTemp.Board_RWFresh air temperature - Board selected; Modbus HR235Write
PIV1759ExtTemp.Ch_Id_RWFresh air temperature - Channel id selected; Modbus HR236Write
PIV1760ExtTemp.Ch_Type_RWFresh air temperature - Type probe used; Modbus HR237Write
AV1761ExtTemp.MinVal_RWFresh air temperature - Minimum value analog input; Modbus HR238Write
AV1762ExtTemp.MaxVal_RWFresh air temperature - Maximum value analog input; Modbus HR239Write
AV1763ExtTemp.Offset_RWFresh air temperature - Offset analog input; Modbus HR240Write
PIV1764ExtTemp.ChFilter_RWFresh air temperature - Filter channel; Modbus HR241Write
PIV1765ExtHum.Board_RWFresh air humidity - Board selected; Modbus HR242Write
PIV1766ExtHum.Ch_Id_RWFresh air humidity - Channel id selected; Modbus HR243Write
PIV1767ExtHum.Ch_Type_RWFresh air humidity - Type probe used; Modbus HR244Write
AV1768ExtHum.MinVal_RWFresh air humidity - Minimum value analog input; Modbus HR245Write
AV1769ExtHum.MaxVal_RWFresh air humidity - Maximum value analog input; Modbus HR246Write
AV1770ExtHum.Offset_RWFresh air humidity - Offset analog input; Modbus HR247Write
PIV1771ExtHum.ChFilter_RWFresh air humidity - Filter channel; Modbus HR248Write
PIV1772ExhTemp.Board_RWExhaust temperature - Board selected; Modbus HR249Write
PIV1773ExhTemp.Ch_Id_RWExhaust temperature - Channel id selected; Modbus HR250Write
PIV1774ExhTemp.Ch_Type_RWExhaust temperature - Type probe used; Modbus HR251Write
AV1775ExhTemp.MinVal_RWExhaust temperature - Minimum value analog input; Modbus HR252Write
AV1776ExhTemp.MaxVal_RWExhaust temperature - Maximum value analog input; Modbus HR253Write
AV1777ExhTemp.Offset_RWExhaust temperature - Offset analog input; Modbus HR254Write
PIV1778ExhTemp.ChFilter_RWExhaust temperature - Filter channel; Modbus HR255Write
PIV1779ExhHum.Board_RWExhaust humidity - Board selected; Modbus HR256Write
PIV1780ExhHum.Ch_Id_RWExhaust humidity - Channel id selected; Modbus HR257Write
PIV1781ExhHum.Ch_Type_RWExhaust humidity - Type probe used; Modbus HR258Write
AV1782ExhHum.MinVal_RWExhaust humidity - Minimum value analog input; Modbus HR259Write
AV1783ExhHum.MaxVal_RWExhaust humidity - Maximum value analog input; Modbus HR260Write
AV1784ExhHum.Offset_RWExhaust humidity - Offset analog input; Modbus HR261Write
PIV1785ExhHum.ChFilter_RWExhaust humidity - Filter channel; Modbus HR262Write
PIV1786AFreezeTemp.Board_RWAntifreeze temperature - Board selected; Modbus HR263Write
PIV1787AFreezeTemp.Ch_Id_RWAntifreeze temperature - Channel id selected; Modbus HR264Write
PIV1788AFreezeTemp.Ch_Type_RWAntifreeze temperature - Type probe used; Modbus HR265Write
AV1789AFreezeTemp.MinVal_RWAntifreeze temperature - Minimum value analog input; Modbus HR266Write
AV1790AFreezeTemp.MaxVal_RWAntifreeze temperature - Maximum value analog input; Modbus HR267Write
AV1791AFreezeTemp.Offset_RWAntifreeze temperature - Offset analog input; Modbus HR268Write
PIV1792AFreezeTemp.ChFilter_RWAntifreeze temperature - Filter channel; Modbus HR269Write
PIV1793SatTemp.Board_RWSaturation temperature - Board selected; Modbus HR270Write
PIV1794SatTemp.Ch_Id_RWSaturation temperature - Channel id selected; Modbus HR271Write
PIV1795SatTemp.Ch_Type_RWSaturation temperature - Type probe used; Modbus HR272Write
AV1796SatTemp.MinVal_RWSaturation temperature - Minimum value analog input; Modbus HR273Write
AV1797SatTemp.MaxVal_RWSaturation temperature - Maximum value analog input; Modbus HR274Write
AV1798SatTemp.Offset_RWSaturation temperature - Offset analog input; Modbus HR275Write
PIV1799SatTemp.ChFilter_RWSaturation temperature - Filter channel; Modbus HR276Write
PIV1800SatHum.Board_RWSaturation humidity - Board selected; Modbus HR277Write
PIV1801SatHum.Ch_Id_RWSaturation humidity - Channel id selected; Modbus HR278Write
PIV1802SatHum.Ch_Type_RWSaturation humidity - Type probe used; Modbus HR279Write
AV1803SatHum.MinVal_RWSaturation humidity - Minimum value analog input; Modbus HR280Write
AV1804SatHum.MaxVal_RWSaturation humidity - Maximum value analog input; Modbus HR281Write
AV1805SatHum.Offset_RWSaturation humidity - Offset analog input; Modbus HR282Write
PIV1806SatHum.ChFilter_RWSaturation humidity - Filter channel; Modbus HR283Write
PIV1807OA_Temp.Board_RWOutdoor air pre-treatment temperature - Board selected; Modbus HR284Write
PIV1808OA_Temp.Ch_Id_RWOutdoor air pre-treatment temperature - Channel id selected; Modbus HR285Write
PIV1809OA_Temp.Ch_Type_RWOutdoor air pre-treatment temperature - Type probe used; Modbus HR286Write
AV1810OA_Temp.MinVal_RWOutdoor air pre-treatment temperature - Minimum value analog input; Modbus HR287Write
AV1811OA_Temp.MaxVal_RWOutdoor air pre-treatment temperature - Maximum value analog input; Modbus HR288Write
AV1812OA_Temp.Offset_RWOutdoor air pre-treatment temperature - Offset analog input; Modbus HR289Write
PIV1813OA_Temp.ChFilter_RWOutdoor air pre-treatment temperature - Filter channel; Modbus HR290Write
PIV1814SupplyAirP.Board_RWSupply air pressure - Board selected; Modbus HR291Write
PIV1815SupplyAirP.Ch_Id_RWSupply air pressure - Channel id selected; Modbus HR292Write
PIV1816SupplyAirP.Ch_Type_RWSupply air pressure - Type probe used; Modbus HR293Write
AV1817SupplyAirP.MinVal_RWSupply air pressure - Minimum value analog input; Modbus HR294Write
AV1818SupplyAirP.MaxVal_RWSupply air pressure - Maximum value analog input; Modbus HR295Write
AV1819SupplyAirP.Offset_RWSupply air pressure - Offset analog input; Modbus HR296Write
PIV1820SupplyAirP.ChFilter_RWSupply air pressure - Filter channel; Modbus HR297Write
PIV1821RetAirP.Board_RWReturn air pressure - Board selected; Modbus HR298Write
PIV1822RetAirP.Ch_Id_RWReturn air pressure - Channel id selected; Modbus HR299Write
PIV1823RetAirP.Ch_Type_RWReturn air pressure - Type probe used; Modbus HR300Write
AV1824RetAirP.MinVal_RWReturn air pressure - Minimum value analog input; Modbus HR301Write
AV1825RetAirP.MaxVal_RWReturn air pressure - Maximum value analog input; Modbus HR302Write
AV1826RetAirP.Offset_RWReturn air pressure - Offset analog input; Modbus HR303Write
PIV1827RetAirP.ChFilter_RWReturn air pressure - Filter channel; Modbus HR304Write
PIV1828AirQuality_CO2.Board_RWCO2 sensor - Board selected; Modbus HR305Write
PIV1829AirQuality_CO2.Ch_Id_RWCO2 sensor - Channel id selected; Modbus HR306Write
PIV1830AirQuality_CO2.Ch_Type_RWCO2 sensor - Type probe used; Modbus HR307Write
AV1831AirQuality_CO2.MinVal_RWCO2 sensor - Minimum value analog input; Modbus HR308Write
AV1832AirQuality_CO2.MaxVal_RWCO2 sensor - Maximum value analog input; Modbus HR309Write
AV1833AirQuality_CO2.Offset_RWCO2 sensor - Offset analog input; Modbus HR310Write
PIV1834AirQuality_CO2.ChFilter_RWCO2 sensor - Filter channel; Modbus HR311Write
PIV1835AirQuality_VOC.Board_RWVOC sensor - Board selected; Modbus HR312Write
PIV1836AirQuality_VOC.Ch_Id_RWVOC sensor - Channel id selected; Modbus HR313Write
PIV1837AirQuality_VOC.Ch_Type_RWVOC sensor - Type probe used; Modbus HR314Write
AV1838AirQuality_VOC.MinVal_RWVOC sensor - Minimum value analog input; Modbus HR315Write
AV1839AirQuality_VOC.MaxVal_RWVOC sensor - Maximum value analog input; Modbus HR316Write
AV1840AirQuality_VOC.Offset_RWVOC sensor - Offset analog input; Modbus HR317Write
PIV1841AirQuality_VOC.ChFilter_RWVOC sensor - Filter channel; Modbus HR318Write
PIV1842DscgP.Board_RWDischarge pressure - Board selected; Modbus HR319Write
PIV1843DscgP.Ch_Id_RWDischarge pressure - Channel id selected; Modbus HR320Write
PIV1844DscgP.Ch_Type_RWDischarge pressure - Type probe used; Modbus HR321Write
AV1845DscgP.MinVal_RWDischarge pressure - Minimum value analog input; Modbus HR322Write
AV1846DscgP.MaxVal_RWDischarge pressure - Maximum value analog input; Modbus HR323Write
AV1847DscgP.Offset_RWDischarge pressure - Offset analog input; Modbus HR324Write
PIV1848DscgP.ChFilter_RWDischarge pressure - Filter channel; Modbus HR325Write
PIV1849DscgT.Board_RWDischarge temperature - Board selected; Modbus HR326Write
PIV1850DscgT.Ch_Id_RWDischarge temperature - Channel id selected; Modbus HR327Write
PIV1851DscgT.Ch_Type_RWDischarge temperature - Type probe used; Modbus HR328Write
AV1852DscgT.MinVal_RWDischarge temperature - Minimum value analog input; Modbus HR329Write
AV1853DscgT.MaxVal_RWDischarge temperature - Maximum value analog input; Modbus HR330Write
AV1854DscgT.Offset_RWDischarge temperature - Offset analog input; Modbus HR331Write
PIV1855DscgT.ChFilter_RWDischarge temperature - Filter channel; Modbus HR332Write
PIV1856SuctP.Board_RWSuction pressure - Board selected; Modbus HR333Write
PIV1857SuctP.Ch_Id_RWSuction pressure - Channel id selected; Modbus HR334Write
PIV1858SuctP.Ch_Type_RWSuction pressure - Type probe used; Modbus HR335Write
AV1859SuctP.MinVal_RWSuction pressure - Minimum value analog input; Modbus HR336Write
AV1860SuctP.MaxVal_RWSuction pressure - Maximum value analog input; Modbus HR337Write
AV1861SuctP.Offset_RWSuction pressure - Offset analog input; Modbus HR338Write
PIV1862SuctP.ChFilter_RWSuction pressure - Filter channel; Modbus HR339Write
PIV1863SuctT.Board_RWSuction temperature - Board selected; Modbus HR340Write
PIV1864SuctT.Ch_Id_RWSuction temperature - Channel id selected; Modbus HR341Write
PIV1865SuctT.Ch_Type_RWSuction temperature - Type probe used; Modbus HR342Write
AV1866SuctT.MinVal_RWSuction temperature - Minimum value analog input; Modbus HR343Write
AV1867SuctT.MaxVal_RWSuction temperature - Maximum value analog input; Modbus HR344Write
AV1868SuctT.Offset_RWSuction temperature - Offset analog input; Modbus HR345Write
PIV1869SuctT.ChFilter_RWSuction temperature - Filter channel; Modbus HR346Write
PIV1870OA_CoilWaterTemp.Board_RWOutdoor air pre-treatment coil water temperature - Board selected; Modbus HR347Write
PIV1871OA_CoilWaterTemp.Ch_Id_RWOutdoor air pre-treatment coil water temperature - Channel id selected; Modbus HR348Write
PIV1872OA_CoilWaterTemp.Ch_Type_RWOutdoor air pre-treatment coil water temperature - Type probe used; Modbus HR349Write
AV1873OA_CoilWaterTemp.MinVal_RWOutdoor air pre-treatment coil water temperature - Minimum value analog input; Modbus HR350Write
AV1874OA_CoilWaterTemp.MaxVal_RWOutdoor air pre-treatment coil water temperature - Maximum value analog; Modbus HR351Write
AV1875OA_CoilWaterTemp.Offset_RWOutdoor air pre-treatment coil water temperature - Offset analog input; Modbus HR352Write
PIV1876OA_CoilWaterTemp.ChFilter_RWOutdoor air pre-treatment coil water temperature - Filter channel; Modbus HR353Write
PIV1877PreHeatCoilWaterTemp.Board_RWPreheat coil water temperature - Board selected; Modbus HR354Write
PIV1878PreHeatCoilWaterTemp.Ch_Id_RWPreheat coil water temperature - Channel id selected; Modbus HR355Write
PIV1879PreHeatCoilWaterTemp.Ch_Type_RWPreheat coil water temperature - Type probe used; Modbus HR356Write
AV1880PreHeatCoilWaterTemp.MinVal_RWPreheat coil water temperature - Minimum value analog input; Modbus HR357Write
AV1881PreHeatCoilWaterTemp.MaxVal_RWPreheat coil water temperature - Maximum value analog input; Modbus HR358Write
AV1882PreHeatCoilWaterTemp.Offset_RWPreheat coil water temperature - Offset analog input; Modbus HR359Write
PIV1883PreHeatCoilWaterTemp.ChFilter_RWPreheat coil water temperature - Filter channel; Modbus HR360Write
PIV1884MainCoilWaterTemp.Board_RWMain coil water temperature - Board selected; Modbus HR361Write
PIV1885MainCoilWaterTemp.Ch_Id_RWMain coil water temperature - Channel id selected; Modbus HR362Write
PIV1886MainCoilWaterTemp.Ch_Type_RWMain coil water temperature - Type probe used; Modbus HR363Write
AV1887MainCoilWaterTemp.MinVal_RWMain coil water temperature - Minimum value analog input; Modbus HR364Write
AV1888MainCoilWaterTemp.MaxVal_RWMain coil water temperature - Maximum value analog input; Modbus HR365Write
AV1889MainCoilWaterTemp.Offset_RWMain coil water temperature - Offset analog input; Modbus HR366Write
PIV1890MainCoilWaterTemp.ChFilter_RWMain coil water temperature - Filter channel; Modbus HR367Write
PIV1891ReHeatCoilWaterTemp.Board_RWPostheat coil water temperature - Board selected; Modbus HR368Write
PIV1892ReHeatCoilWaterTemp.Ch_Id_RWPostheat coil water temperature - Channel id selected; Modbus HR369Write
PIV1893ReHeatCoilWaterTemp.Ch_Type_RWPostheat coil water temperature - Type probe used; Modbus HR370Write
AV1894ReHeatCoilWaterTemp.MinVal_RWPostheat coil water temperature - Minimum value analog input; Modbus HR371Write
AV1895ReHeatCoilWaterTemp.MaxVal_RWPostheat coil water temperature - Maximum value analog input; Modbus HR372Write
AV1896ReHeatCoilWaterTemp.Offset_RWPostheat coil water temperature - Offset analog input; Modbus HR373Write
PIV1897ReHeatCoilWaterTemp.ChFilter_RWPostheat coil water temperature - Filter channel; Modbus HR374Write
PIV1898AuxPrb_1.Board_RWAuxiliary probe 1 - Board selected; Modbus HR375Write
PIV1899AuxPrb_1.Ch_Id_RWAuxiliary probe 1 - Channel id selected; Modbus HR376Write
PIV1900AuxPrb_1.Ch_Type_RWAuxiliary probe 1 - Type probe used; Modbus HR377Write
AV1901AuxPrb_1.MinVal_RWAuxiliary probe 1 - Minimum value analog input; Modbus HR378Write
AV1902AuxPrb_1.MaxVal_RWAuxiliary probe 1 - Maximum value analog input; Modbus HR379Write
AV1903AuxPrb_1.Offset_RWAuxiliary probe 1 - Offset analog input; Modbus HR380Write
PIV1904AuxPrb_1.ChFilter_RWAuxiliary probe 1 - Filter channel; Modbus HR381Write
PIV1905AuxPrb_2.Board_RWAuxiliary probe 2 - Board selected; Modbus HR382Write
PIV1906AuxPrb_2.Ch_Id_RWAuxiliary probe 2 - Channel id selected; Modbus HR383Write
PIV1907AuxPrb_2.Ch_Type_RWAuxiliary probe 2 - Type probe used; Modbus HR384Write
AV1908AuxPrb_2.MinVal_RWAuxiliary probe 2 - Minimum value analog input; Modbus HR385Write
AV1909AuxPrb_2.MaxVal_RWAuxiliary probe 2 - Maximum value analog input; Modbus HR386Write
AV1910AuxPrb_2.Offset_RWAuxiliary probe 2 - Offset analog input; Modbus HR387Write
PIV1911AuxPrb_2.ChFilter_RWAuxiliary probe 2 - Filter channel; Modbus HR388Write
PIV1912AuxPrb_3.Board_RWAuxiliary probe 3 - Board selected; Modbus HR389Write
PIV1913AuxPrb_3.Ch_Id_RWAuxiliary probe 3 - Channel id selected; Modbus HR390Write
PIV1914AuxPrb_3.Ch_Type_RWAuxiliary probe 3 - Type probe used; Modbus HR391Write
AV1915AuxPrb_3.MinVal_RWAuxiliary probe 3 - Minimum value analog input; Modbus HR392Write
AV1916AuxPrb_3.MaxVal_RWAuxiliary probe 3 - Maximum value analog input; Modbus HR393Write
AV1917AuxPrb_3.Offset_RWAuxiliary probe 3 - Offset analog input; Modbus HR394Write
PIV1918AuxPrb_3.ChFilter_RWAuxiliary probe 3 - Filter channel; Modbus HR395Write
PIV1919AuxPrb_4.Board_RWAuxiliary probe 4 - Board selected; Modbus HR396Write
PIV1920AuxPrb_4.Ch_Id_RWAuxiliary probe 4 - Channel id selected; Modbus HR397Write
PIV1921AuxPrb_4.Ch_Type_RWAuxiliary probe 4 - Type probe used; Modbus HR398Write
AV1922AuxPrb_4.MinVal_RWAuxiliary probe 4 - Minimum value analog input; Modbus HR399Write
AV1923AuxPrb_4.MaxVal_RWAuxiliary probe 4 - Maximum value analog input; Modbus HR400Write
AV1924AuxPrb_4.Offset_RWAuxiliary probe 4 - Offset analog input; Modbus HR401Write
PIV1925AuxPrb_4.ChFilter_RWAuxiliary probe 4 - Filter channel; Modbus HR402Write
PIV1926Ain_SetP.Board_RWSetpoint by AIN - Board selected; Modbus HR403Write
PIV1927Ain_SetP.Ch_Id_RWSetpoint by AIN - Channel id selected; Modbus HR404Write
PIV1928Ain_SetP.Ch_Type_RWSetpoint by AIN - Type probe used; Modbus HR405Write
AV1929Ain_SetP.MinVal_RWSetpoint by AIN - Minimum value analog input; Modbus HR406Write
AV1930Ain_SetP.MaxVal_RWSetpoint by AIN - Maximum value analog input; Modbus HR407Write
AV1931Ain_SetP.Offset_RWSetpoint by AIN - Offset analog input; Modbus HR408Write
PIV1932Ain_SetP.ChFilter_RWSetpoint by AIN - Filter channel; Modbus HR409Write
PIV1933SupplyRecoveryTemp.Board_RWSupply recovery temperature - Board selected; Modbus HR410Write
PIV1934SupplyRecoveryTemp.Ch_Id_RWSupply recovery temperature - Channel id selected; Modbus HR411Write
PIV1935SupplyRecoveryTemp.Ch_Type_RWSupply recovery temperature - Type probe used; Modbus HR412Write
AV1936SupplyRecoveryTemp.MinVal_RWSupply recovery temperature - Minimum value analog input; Modbus HR413Write
AV1937SupplyRecoveryTemp.MaxVal_RWSupply recovery temperature - Maximum value analog input; Modbus HR414Write
AV1938SupplyRecoveryTemp.Offset_RWSupply recovery temperature - Offset analog input; Modbus HR415Write
PIV1939SupplyRecoveryTemp.ChFilter_RWSupply recovery temperature - Filter channel; Modbus HR416Write
PIV1940RetRecoveryTemp.Board_RWReturn recovery temperature - Board selected; Modbus HR417Write
PIV1941RetRecoveryTemp.Ch_Id_RWReturn recovery temperature - Channel id selected; Modbus HR418Write
PIV1942RetRecoveryTemp.Ch_Type_RWReturn recovery temperature - Type probe used; Modbus HR419Write
AV1943RetRecoveryTemp.MinVal_RWReturn recovery temperature - Minimum value analog input; Modbus HR420Write
AV1944RetRecoveryTemp.MaxVal_RWReturn recovery temperature - Maximum value analog input; Modbus HR421Write
AV1945RetRecoveryTemp.Offset_RWReturn recovery temperature - Offset analog input; Modbus HR422Write
PIV1946RetRecoveryTemp.ChFilter_RWReturn recovery temperature - Filter channel; Modbus HR423Write
PIV1947HepaFilt_1.Board_RWHepa filter 1 - Board selected; Modbus HR424Write
PIV1948HepaFilt_1.Ch_Id_RWHepa filter 1 - Channel id selected; Modbus HR425Write
PIV1949HepaFilt_1.Ch_Type_RWHepa filter 1 - Type probe used; Modbus HR426Write
AV1950HepaFilt_1.MinVal_RWHepa filter 1 - Minimum value analog input; Modbus HR427Write
AV1951HepaFilt_1.MaxVal_RWHepa filter 1 - Maximum value analog input; Modbus HR428Write
AV1952HepaFilt_1.Offset_RWHepa filter 1 - Offset analog input; Modbus HR429Write
PIV1953HepaFilt_1.ChFilter_RWHepa filter 1 - Filter channel; Modbus HR430Write
PIV1954HepaFilt_2.Board_RWHepa filter 2 - Board selected; Modbus HR431Write
PIV1955HepaFilt_2.Ch_Id_RWHepa filter 2 - Channel id selected; Modbus HR432Write
PIV1956HepaFilt_2.Ch_Type_RWHepa filter 2 - Type probe used; Modbus HR433Write
AV1957HepaFilt_2.MinVal_RWHepa filter 2 - Minimum value analog input; Modbus HR434Write
AV1958HepaFilt_2.MaxVal_RWHepa filter 2 - Maximum value analog input; Modbus HR435Write
AV1959HepaFilt_2.Offset_RWHepa filter 2 - Offset analog input; Modbus HR436Write
PIV1960HepaFilt_2.ChFilter_RWHepa filter 2 - Filter channel; Modbus HR437Write
PIV1961SupplyAirFlwSw.Board_RWSupply air flow switch - Board selected; Modbus HR438Write
PIV1962SupplyAirFlwSw.Ch_Id_RWSupply air flow switch - Channel id selected; Modbus HR439Write
PIV1963RetAirFlwSw.Board_RWReturn air flow switch - Board selected; Modbus HR440Write
PIV1964RetAirFlwSw.Ch_Id_RWReturn air flow switch - Channel id selected; Modbus HR441Write
PIV1965AirFlwSw.Board_RWAir flow switch - Board selected; Modbus HR442Write
PIV1966AirFlwSw.Ch_Id_RWAir flow switch - Channel id selected; Modbus HR443Write
PIV1967AFreezeSw.Board_RWAntifreeze switch - Board selected; Modbus HR444Write
PIV1968AFreezeSw.Ch_Id_RWAntifreeze switch - Channel id selected; Modbus HR445Write
PIV1969RemOnOff.Board_RWRemote On/Off - Board selected; Modbus HR446Write
PIV1970RemOnOff.Ch_Id_RWRemote On/Off - Channel id selected; Modbus HR447Write
PIV1971SupplyFanOvld_1.Board_RWSupply fan overload 1 - Board selected; Modbus HR448Write
PIV1972SupplyFanOvld_1.Ch_Id_RWSupply fan overload 1 - Channel id selected; Modbus HR449Write
PIV1973RetFanOvld_1.Board_RWReturn fan overload 1 - Board selected; Modbus HR450Write
PIV1974RetFanOvld_1.Ch_Id_RWReturn fan overload 1 - Channel id selected; Modbus HR451Write
PIV1975SupplyFanOvld_2.Board_RWSupply fan overload 2 - Board selected; Modbus HR452Write
PIV1976SupplyFanOvld_2.Ch_Id_RWSupply fan overload 2 - Channel id selected; Modbus HR453Write
PIV1977RetFanOvld_2.Board_RWReturn fan overload 2 - Board selected; Modbus HR454Write
PIV1978RetFanOvld_2.Ch_Id_RWReturn fan overload 2 - Channel id selected; Modbus HR455Write
PIV1979SupplyFanInvAlrm.Board_RWSupply inverter alarm - Board selected; Modbus HR456Write
PIV1980SupplyFanInvAlrm.Ch_Id_RWSupply inverter alarm - Channel id selected; Modbus HR457Write
PIV1981RetFanInvAlrm.Board_RWReturn inverter alarm - Board selected; Modbus HR458Write
PIV1982RetFanInvAlrm.Ch_Id_RWReturn inverter alarm - Channel id selected; Modbus HR459Write
PIV1983FansOvld.Board_RWFans overload - Board selected; Modbus HR460Write
PIV1984FansOvld.Ch_Id_RWFans overload - Channel id selected; Modbus HR461Write
PIV1985CompOvld.Board_RWCompressor overload - Board selected; Modbus HR462Write
PIV1986CompOvld.Ch_Id_RWCompressor overload - Channel id selected; Modbus HR463Write
PIV1987HiPSw.Board_RWHigh discharge pressure switch - Board selected; Modbus HR464Write
PIV1988HiPSw.Ch_Id_RWHigh discharge pressure switch - Channel id selected; Modbus HR465Write
PIV1989LowPSw.Board_RWLow suction pressure switch - Board selected; Modbus HR466Write
PIV1990LowPSw.Ch_Id_RWLow suction pressure switch - Channel id selected; Modbus HR467Write
PIV1991RecoveryOvld.Board_RWThermal wheel overload - Board selected; Modbus HR468Write
PIV1992RecoveryOvld.Ch_Id_RWThermal wheel overload - Channel id selected; Modbus HR469Write
PIV1993SrsAlrm.Board_RWSerious alarm - Board selected; Modbus HR470Write
PIV1994SrsAlrm.Ch_Id_RWSerious alarm - Channel id selected; Modbus HR471Write
PIV1995GenAlrm.Board_RWGeneric alarm - Board selected; Modbus HR472Write
PIV1996GenAlrm.Ch_Id_RWGeneric alarm - Channel id selected; Modbus HR473Write
PIV1997GenWarning.Board_RWGeneric warning - Board selected; Modbus HR474Write
PIV1998GenWarning.Ch_Id_RWGeneric warning - Channel id selected; Modbus HR475Write
PIV1999FiltAlrm.Board_RWFilters alarm - Board selected; Modbus HR476Write
PIV2000FiltAlrm.Ch_Id_RWFilters alarm - Channel id selected; Modbus HR477Write
PIV2001SupplyFiltAlrm_1.Board_RWSupply filter alarm 1 - Board selected; Modbus HR478Write
PIV2002SupplyFiltAlrm_1.Ch_Id_RWSupply filter alarm 1 - Channel id selected; Modbus HR479Write
PIV2003SupplyFiltAlrm_2.Board_RWSupply filter alarm 2 - Board selected; Modbus HR480Write
PIV2004SupplyFiltAlrm_2.Ch_Id_RWSupply filter alarm 2 - Channel id selected; Modbus HR481Write
PIV2005RetFiltAlrm.Board_RWReturn filter alarm - Board selected; Modbus HR482Write
PIV2006RetFiltAlrm.Ch_Id_RWReturn filter alarm - Channel id selected; Modbus HR483Write
PIV2007HumAlrm.Board_RWHumidifier alarm - Board selected; Modbus HR484Write
PIV2008HumAlrm.Ch_Id_RWHumidifier alarm - Channel id selected; Modbus HR485Write
PIV2009MainCoilPmp1_Ovld.Board_RWMain coil pump 1 overload - Board selected; Modbus HR486Write
PIV2010MainCoilPmp1_Ovld.Ch_Id_RWMain coil pump 1 overload - Channel id selected; Modbus HR487Write
PIV2011MainCoilPmp2_Ovld.Board_RWMain coil pump 2 overload - Board selected; Modbus HR488Write
PIV2012MainCoilPmp2_Ovld.Ch_Id_RWMain coil pump 2 overload - Channel id selected; Modbus HR489Write
PIV2013ReHeatCoilPmp1_Ovld.Board_RWReHeat coil pump 1 overload - Board selected; Modbus HR490Write
PIV2014ReHeatCoilPmp1_Ovld.Ch_Id_RWReHeat coil pump 1 overload - Channel id selected; Modbus HR491Write
PIV2015ReHeatCoilPmp2_Ovld.Board_RWReHeat coil pump 2 overload - Board selected; Modbus HR492Write
PIV2016ReHeatCoilPmp2_Ovld.Ch_Id_RWReHeat coil pump 2 overload - Channel id selected; Modbus HR493Write
PIV2017PreHeatCoilPmp1_Ovld.Board_RWPreHeat coil pump 1 overload - Board selected; Modbus HR494Write
PIV2018PreHeatCoilPmp1_Ovld.Ch_Id_RWPreHeat coil pump 1 overload - Channel id selected; Modbus HR495Write
PIV2019PreHeatCoilPmp2_Ovld.Board_RWPreHeat coil pump 2 overload - Board selected; Modbus HR496Write
PIV2020PreHeatCoilPmp2_Ovld.Ch_Id_RWPreHeat coil pump 2 overload - Channel id selected; Modbus HR497Write
PIV2021OA_CoilPmp1_Ovld.Board_RWOutdoor air pre-treatment coil pump 1 overload - Board selected; Modbus HR498Write
PIV2022OA_CoilPmp1_Ovld.Ch_Id_RWOutdoor air pre-treatment coil pump 1 overload - Channel id selected; Modbus HR499Write
PIV2023OA_CoilPmp2_Ovld.Board_RWOutdoor air pre-treatment coil pump 2 overload - Board selected; Modbus HR500Write
PIV2024OA_CoilPmp2_Ovld.Ch_Id_RWOutdoor air pre-treatment coil pump 2 overload - Channel id selected; Modbus HR501Write
PIV2025FreshAirDampSw.Board_RWFresh air damper switch - Board selected; Modbus HR502Write
PIV2026FreshAirDampSw.Ch_Id_RWFresh air damper switch - Channel id selected; Modbus HR503Write
PIV2027SupplyDamperSw.Board_RWSupply damper switch - Board selected; Modbus HR504Write
PIV2028SupplyDamperSw.Ch_Id_RWSupply damper switch - Channel id selected; Modbus HR505Write
PIV2029RetDampSw.Board_RWReturn damper switch - Board selected; Modbus HR506Write
PIV2030RetDampSw.Ch_Id_RWReturn damper switch - Channel id selected; Modbus HR507Write
PIV2031MainCoilFlwSw.Board_RWMain coil flow switch - Board selected; Modbus HR508Write
PIV2032MainCoilFlwSw.Ch_Id_RWMain coil flow switch - Channel id selected; Modbus HR509Write
PIV2033PreHeatCoilFlwSw.Board_RWPre-heating coil flow switch - Board selected; Modbus HR510Write
PIV2034PreHeatCoilFlwSw.Ch_Id_RWPre-heating coil flow switch - Channel id selected; Modbus HR511Write
PIV2035ReHeatCoilFlwSw.Board_RWPost-Heating coil flow switch - Board selected; Modbus HR512Write
PIV2036ReHeatCoilFlwSw.Ch_Id_RWPost-Heating coil flow switch - Channel id selected; Modbus HR513Write
PIV2037OA_CoilFlwSw.Board_RWOutdoor air pre-treatment coil flow switch - Board selected; Modbus HR514Write
PIV2038OA_CoilFlwSw.Ch_Id_RWOutdoor air pre-treatment coil flow switch - Channel id selected; Modbus HR515Write
PIV2039RecoveryClogged.Board_RWRecovery clogged - Board selected; Modbus HR516Write
PIV2040RecoveryClogged.Ch_Id_RWRecovery clogged - Channel id selected; Modbus HR517Write
PIV2041ReHeatAlrm.Board_RWRe-heating alarm - Board selected; Modbus HR518Write
PIV2042ReHeatAlrm.Ch_Id_RWRe-heating alarm - Channel id selected; Modbus HR519Write
PIV2043PreHeatAlrm.Board_RWPre-heating alarm - Board selected; Modbus HR520Write
PIV2044PreHeatAlrm.Ch_Id_RWPre-heating alarm - Channel id selected; Modbus HR521Write
PIV2045MainHeatCoilAlrm.Board_RWMain coil alarm - Board selected; Modbus HR522Write
PIV2046MainHeatCoilAlrm.Ch_Id_RWMain coil alarm - Channel id selected; Modbus HR523Write
PIV2047OA_CoilAlrm.Board_RWOutdoor air pre-treatment -Heat alarm - Board selected; Modbus HR524Write
PIV2048OA_CoilAlrm.Ch_Id_RWOutdoor air pre-treatment -Heat alarm - Channel id selected; Modbus HR525Write
PIV2049DoorSw.Board_RWDoor Switch - Board selected; Modbus HR526Write
PIV2050DoorSw.Ch_Id_RWDoor Switch - Channel id selected; Modbus HR527Write
PIV2051FireSmokeAlrm.Board_RWFire/Smoke alarm - Board selected; Modbus HR528Write
PIV2052FireSmokeAlrm.Ch_Id_RWFire/Smoke alarm - Channel id selected; Modbus HR529Write
PIV2053FiremanOverrideSw.Board_RWFireman override switch - Board selected; Modbus HR530Write
PIV2054FiremanOverrideSw.Ch_Id_RWFireman override switch - Channel id selected; Modbus HR531Write
PIV2055SummerWinterModeByDin.Board_RWSummer/Winter mode by digital input - Board selected; Modbus HR532Write
PIV2056SummerWinterModeByDin.Ch_Id_RWSummer/Winter mode by digital input - Channel id selected; Modbus HR533Write
PIV2057Din_SetP.Board_RWSetpoint by digital input - Board selected; Modbus HR534Write
PIV2058Din_SetP.Ch_Id_RWSetpoint by digital input - Channel id selected; Modbus HR535Write
PIV2059Eco_Mode.Board_RWEco mode - Board selected; Modbus HR536Write
PIV2060Eco_Mode.Ch_Id_RWEco mode - Channel id selected; Modbus HR537Write
PIV2061PreComf_Mode.Board_RWPrecomfort mode - Board selected; Modbus HR538Write
PIV2062PreComf_Mode.Ch_Id_RWPrecomfort mode - Channel id selected; Modbus HR539Write
PIV2063Comf_Mode.Board_RWComfort mode - Board selected; Modbus HR540Write
PIV2064Comf_Mode.Ch_Id_RWComfort mode - Channel id selected; Modbus HR541Write
PIV2065AuxDin_1.Board_RWAuxiliary digital input 1 - Board selected; Modbus HR542Write
PIV2066AuxDin_1.Ch_Id_RWAuxiliary digital input 1 - Channel id selected; Modbus HR543Write
PIV2067AuxDin_2.Board_RWAuxiliary digital input 2 - Board selected; Modbus HR544Write
PIV2068AuxDin_2.Ch_Id_RWAuxiliary digital input 2 - Channel id selected; Modbus HR545Write
PIV2069AuxDin_3.Board_RWAuxiliary digital input 3 - Board selected; Modbus HR546Write
PIV2070AuxDin_3.Ch_Id_RWAuxiliary digital input 3 - Channel id selected; Modbus HR547Write
PIV2071AuxDin_4.Board_RWAuxiliary digital input 4 - Board selected; Modbus HR548Write
PIV2072AuxDin_4.Ch_Id_RWAuxiliary digital input 4 - Channel id selected; Modbus HR549Write
PIV2073DfrHeatExch_Din.Board_RWHeat exchanger defrost by Din - Board selected; Modbus HR550Write
PIV2074DfrHeatExch_Din.Ch_Id_RWHeat exchanger defrost by Din - Channel id selected; Modbus HR551Write
PIV2075BypassDamp_Dout.Board_RWBypass damper - Board selected; Modbus HR552Write
PIV2076BypassDamp_Dout.Ch_Id_RWBypass damper - Channel id selected; Modbus HR553Write
PIV2077BypassDamp_Dout.T_On_RWBypass damper - Time on cycle relay; Modbus HR554Write
PIV2078BypassDamp_Dout.T_Off_RWBypass damper - Time off cycle releay; Modbus HR555Write
PIV2079BypassDamp_Dout.Ch_Type_RWBypass damper - Digital output type; Modbus HR556Write
PIV2080BypassDamp_Open.Board_RWBypass damper floating (open) - Board selected; Modbus HR557Write
PIV2081BypassDamp_Open.Ch_Id_RWBypass damper floating (open) - Channel id selected; Modbus HR558Write
PIV2082BypassDamp_Open.T_On_RWBypass damper floating (open) - Time on cycle relay; Modbus HR559Write
PIV2083BypassDamp_Open.T_Off_RWBypass damper floating (open) - Time off cycle releay; Modbus HR560Write
PIV2084BypassDamp_Open.Ch_Type_RWBypass damper floating (open) - Digital output type; Modbus HR561Write
PIV2085BypassDamp_Close.Board_RWBypass damper floating (close) - Board selected; Modbus HR562Write
PIV2086BypassDamp_Close.Ch_Id_RWBypass damper floating (close) - Channel id selected; Modbus HR563Write
PIV2087BypassDamp_Close.T_On_RWBypass damper floating (close) - Time on cycle relay; Modbus HR564Write
PIV2088BypassDamp_Close.T_Off_RWBypass damper floating (close) - Time off cycle releay; Modbus HR565Write
PIV2089BypassDamp_Close.Ch_Type_RWBypass damper floating (close) - Digital output type; Modbus HR566Write
PIV2090FreshAirDamp_Dout.Board_RWFresh air damper - Board selected; Modbus HR567Write
PIV2091FreshAirDamp_Dout.Ch_Id_RWFresh air damper - Channel id selected; Modbus HR568Write
PIV2092FreshAirDamp_Dout.T_On_RWFresh air damper - Time on cycle relay; Modbus HR569Write
PIV2093FreshAirDamp_Dout.T_Off_RWFresh air damper - Time off cycle releay; Modbus HR570Write
PIV2094FreshAirDamp_Dout.Ch_Type_RWFresh air damper - Digital output type; Modbus HR571Write
PIV2095ExhAirDamp_Dout.Board_RWExhaust air damper - Board selected; Modbus HR572Write
PIV2096ExhAirDamp_Dout.Ch_Id_RWExhaust air damper - Channel id selected; Modbus HR573Write
PIV2097ExhAirDamp_Dout.T_On_RWExhaust air damper - Time on cycle relay; Modbus HR574Write
PIV2098ExhAirDamp_Dout.T_Off_RWExhaust air damper - Time off cycle releay; Modbus HR575Write
PIV2099ExhAirDamp_Dout.Ch_Type_RWExhaust air damper - Digital output type; Modbus HR576Write
PIV2100MixingDamp_Dout.Board_RWMixing damper - Board selected; Modbus HR577Write
PIV2101MixingDamp_Dout.Ch_Id_RWMixing damper - Channel id selected; Modbus HR578Write
PIV2102MixingDamp_Dout.T_On_RWMixing damper - Time on cycle relay; Modbus HR579Write
PIV2103MixingDamp_Dout.T_Off_RWMixing damper - Time off cycle releay; Modbus HR580Write
PIV2104MixingDamp_Dout.Ch_Type_RWMixing damper - Digital output type; Modbus HR581Write
PIV2105SupplyAirDamp_Dout.Board_RWSupply air damper - Board selected; Modbus HR582Write
PIV2106SupplyAirDamp_Dout.Ch_Id_RWSupply air damper - Channel id selected; Modbus HR583Write
PIV2107SupplyAirDamp_Dout.T_On_RWSupply air damper - Time on cycle relay; Modbus HR584Write
PIV2108SupplyAirDamp_Dout.T_Off_RWSupply air damper - Time off cycle releay; Modbus HR585Write
PIV2109SupplyAirDamp_Dout.Ch_Type_RWSupply air damper - Digital output type; Modbus HR586Write
PIV2110RetAirDamp_Dout.Board_RWReturn air damper - Board selected; Modbus HR587Write
PIV2111RetAirDamp_Dout.Ch_Id_RWReturn air damper - Channel id selected; Modbus HR588Write
PIV2112RetAirDamp_Dout.T_On_RWReturn air damper - Time on cycle relay; Modbus HR589Write
PIV2113RetAirDamp_Dout.T_Off_RWReturn air damper - Time off cycle releay; Modbus HR590Write
PIV2114RetAirDamp_Dout.Ch_Type_RWReturn air damper - Digital output type; Modbus HR591Write
PIV2115MixingDamp_Open.Board_RWMixing damper floating (OPEN) - Board selected; Modbus HR592Write
PIV2116MixingDamp_Open.Ch_Id_RWMixing damper floating (OPEN) - Channel id selected; Modbus HR593Write
PIV2117MixingDamp_Open.T_On_RWMixing damper floating (OPEN) - Time on cycle relay; Modbus HR594Write
PIV2118MixingDamp_Open.T_Off_RWMixing damper floating (OPEN) - Time off cycle releay; Modbus HR595Write
PIV2119MixingDamp_Open.Ch_Type_RWMixing damper floating (OPEN) - Digital output type; Modbus HR596Write
PIV2120MixingDamp_Close.Board_RWMixing damper floating (CLOSE) - Board selected; Modbus HR597Write
PIV2121MixingDamp_Close.Ch_Id_RWMixing damper floating (CLOSE) - Channel id selected; Modbus HR598Write
PIV2122MixingDamp_Close.T_On_RWMixing damper floating (CLOSE) - Time on cycle relay; Modbus HR599Write
PIV2123MixingDamp_Close.T_Off_RWMixing damper floating (CLOSE) - Time off cycle releay; Modbus HR600Write
PIV2124MixingDamp_Close.Ch_Type_RWMixing damper floating (CLOSE) - Digital output type; Modbus HR601Write
PIV2125SupplyFan_Dout.Board_RWSupply fan - Board selected; Modbus HR602Write
PIV2126SupplyFan_Dout.Ch_Id_RWSupply fan - Channel id selected; Modbus HR603Write
PIV2127SupplyFan_Dout.T_On_RWSupply fan - Time on cycle relay; Modbus HR604Write
PIV2128SupplyFan_Dout.T_Off_RWSupply fan - Time off cycle releay; Modbus HR605Write
PIV2129SupplyFan_Dout.Ch_Type_RWSupply fan - Digital output type; Modbus HR606Write
PIV2130RetFan_Dout.Board_RWReturn fan - Board selected; Modbus HR607Write
PIV2131RetFan_Dout.Ch_Id_RWReturn fan - Channel id selected; Modbus HR608Write
PIV2132RetFan_Dout.T_On_RWReturn fan - Time on cycle relay; Modbus HR609Write
PIV2133RetFan_Dout.T_Off_RWReturn fan - Time off cycle releay; Modbus HR610Write
PIV2134RetFan_Dout.Ch_Type_RWReturn fan - Digital output type; Modbus HR611Write
PIV2135SupplyFan2_Dout.Board_RWSupply fan 2 - Board selected; Modbus HR612Write
PIV2136SupplyFan2_Dout.Ch_Id_RWSupply fan 2 - Channel id selected; Modbus HR613Write
PIV2137SupplyFan2_Dout.T_On_RWSupply fan 2 - Time on cycle relay; Modbus HR614Write
PIV2138SupplyFan2_Dout.T_Off_RWSupply fan 2 - Time off cycle releay; Modbus HR615Write
PIV2139SupplyFan2_Dout.Ch_Type_RWSupply fan 2 - Digital output type; Modbus HR616Write
PIV2140RetFan2_Dout.Board_RWReturn fan 2 - Board selected; Modbus HR617Write
PIV2141RetFan2_Dout.Ch_Id_RWReturn fan 2 - Channel id selected; Modbus HR618Write
PIV2142RetFan2_Dout.T_On_RWReturn fan 2 - Time on cycle relay; Modbus HR619Write
PIV2143RetFan2_Dout.T_Off_RWReturn fan 2 - Time off cycle releay; Modbus HR620Write
PIV2144RetFan2_Dout.Ch_Type_RWReturn fan 2 - Digital output type; Modbus HR621Write
PIV2145Comp_Dout.Board_RWCompressor - Board selected; Modbus HR622Write
PIV2146Comp_Dout.Ch_Id_RWCompressor - Channel id selected; Modbus HR623Write
PIV2147Comp_Dout.T_On_RWCompressor - Time on cycle relay; Modbus HR624Write
PIV2148Comp_Dout.T_Off_RWCompressor - Time off cycle releay; Modbus HR625Write
PIV2149Comp_Dout.Ch_Type_RWCompressor - Digital output type; Modbus HR626Write
PIV2150RevVlv.Board_RWReverse valve - Board selected; Modbus HR627Write
PIV2151RevVlv.Ch_Id_RWReverse valve - Channel id selected; Modbus HR628Write
PIV2152RevVlv.T_On_RWReverse valve - Time on cycle relay; Modbus HR629Write
PIV2153RevVlv.T_Off_RWReverse valve - Time off cycle releay; Modbus HR630Write
PIV2154RevVlv.Ch_Type_RWReverse valve - Digital output type; Modbus HR631Write
PIV2155UnitOnOff_Dout.Board_RWUnit status (On/Off) - Board selected; Modbus HR632Write
PIV2156UnitOnOff_Dout.Ch_Id_RWUnit status (On/Off ) - Channel id selected; Modbus HR633Write
PIV2157UnitOnOff_Dout.T_On_RWUnit status (On/Off ) - Time on cycle relay; Modbus HR634Write
PIV2158UnitOnOff_Dout.T_Off_RWUnit status (On/Off ) - Time off cycle releay; Modbus HR635Write
PIV2159UnitOnOff_Dout.Ch_Type_RWUnit status (On/Off ) - Digital output type; Modbus HR636Write
PIV2160CoolHeat_Dout.Board_RWCool/Heat status - Board selected; Modbus HR637Write
PIV2161CoolHeat_Dout.Ch_Id_RWCool/Heat status - Channel id selected; Modbus HR638Write
PIV2162CoolHeat_Dout.T_On_RWCool/Heat status - Time on cycle relay; Modbus HR639Write
PIV2163CoolHeat_Dout.T_Off_RWCool/Heat status - Time off cycle releay; Modbus HR640Write
PIV2164CoolHeat_Dout.Ch_Type_RWCool/Heat status - Digital output type; Modbus HR641Write
PIV2167GlobalAlrm_Dout.T_On_RWGeneric alarm info - Time on cycle relay; Modbus HR644Write
PIV2168GlobalAlrm_Dout.T_Off_RWGeneric alarm info - Time off cycle releay; Modbus HR645Write
PIV2169GlobalAlrm_Dout.Ch_Type_RWGeneric alarm info - Digital output type; Modbus HR646Write
PIV2170LightAlrm_Dout.Board_RWLight alarm info - Board selected; Modbus HR647Write
PIV2171LightAlrm_Dout.Ch_Id_RWLight alarm info - Channel id selected; Modbus HR648Write
PIV2172LightAlrm_Dout.T_On_RWLight alarm info - Time on cycle relay; Modbus HR649Write
PIV2173LightAlrm_Dout.T_Off_RWLight alarm info - Time off cycle releay; Modbus HR650Write
PIV2174LightAlrm_Dout.Ch_Type_RWLight alarm info - Digital output type; Modbus HR651Write
PIV2175SrsAlrm_Dout.Board_RWSerious alarm info - Board selected; Modbus HR652Write
PIV2176SrsAlrm_Dout.Ch_Id_RWSerious alarm info - Channel id selected; Modbus HR653Write
PIV2177SrsAlrm_Dout.T_On_RWSerious alarm info - Time on cycle relay; Modbus HR654Write
PIV2178SrsAlrm_Dout.T_Off_RWSerious alarm info - Time off cycle releay; Modbus HR655Write
PIV2179SrsAlrm_Dout.Ch_Type_RWSerious alarm info - Digital output type; Modbus HR656Write
PIV2180Humidifier.Board_RWHumidifier - Board selected; Modbus HR657Write
PIV2181Humidifier.Ch_Id_RWHumidifier - Channel id selected; Modbus HR658Write
PIV2182Humidifier.T_On_RWHumidifier - Time on cycle relay; Modbus HR659Write
PIV2183Humidifier.T_Off_RWHumidifier - Time off cycle releay; Modbus HR660Write
PIV2184Humidifier.Ch_Type_RWHumidifier - Digital output type; Modbus HR661Write
PIV2185AuxOut1_Dout.Board_RWAuxiliary output 1 - Board selected; Modbus HR662Write
PIV2186AuxOut1_Dout.Ch_Id_RWAuxiliary output 1 - Channel id selected; Modbus HR663Write
PIV2187AuxOut1_Dout.T_On_RWAuxiliary output 1 - Time on cycle relay; Modbus HR664Write
PIV2188AuxOut1_Dout.T_Off_RWAuxiliary output 1 - Time off cycle releay; Modbus HR665Write
PIV2189AuxOut1_Dout.Ch_Type_RWAuxiliary output 1 - Digital output type; Modbus HR666Write
PIV2190AuxOut2_Dout.Board_RWAuxiliary output 2 - Board selected; Modbus HR667Write
PIV2191AuxOut2_Dout.Ch_Id_RWAuxiliary output 2 - Channel id selected; Modbus HR668Write
PIV2192AuxOut2_Dout.T_On_RWAuxiliary output 2 - Time on cycle relay; Modbus HR669Write
PIV2193AuxOut2_Dout.T_Off_RWAuxiliary output 2 - Time off cycle releay; Modbus HR670Write
PIV2194AuxOut2_Dout.Ch_Type_RWAuxiliary output 2 - Digital output type; Modbus HR671Write
PIV2195AuxOut3_Dout.Board_RWAuxiliary output 3 - Board selected; Modbus HR672Write
PIV2196AuxOut3_Dout.Ch_Id_RWAuxiliary output 3 - Channel id selected; Modbus HR673Write
PIV2197AuxOut3_Dout.T_On_RWAuxiliary output 3 - Time on cycle relay; Modbus HR674Write
PIV2198AuxOut3_Dout.T_Off_RWAuxiliary output 3 - Time off cycle releay; Modbus HR675Write
PIV2199AuxOut3_Dout.Ch_Type_RWAuxiliary output 3 - Digital output type; Modbus HR676Write
PIV2200AuxOut4_Dout.Board_RWAuxiliary output 4 - Board selected; Modbus HR677Write
PIV2201AuxOut4_Dout.Ch_Id_RWAuxiliary output 4 - Channel id selected; Modbus HR678Write
PIV2202AuxOut4_Dout.T_On_RWAuxiliary output 4 - Time on cycle relay; Modbus HR679Write
PIV2203AuxOut4_Dout.T_Off_RWAuxiliary output 4 - Time off cycle releay; Modbus HR680Write
PIV2204AuxOut4_Dout.Ch_Type_RWAuxiliary output 4 - Digital output type; Modbus HR681Write
PIV2205MainVlv_Open.Board_RWMain floating valve open - Board selected; Modbus HR682Write
PIV2206MainVlv_Open.Ch_Id_RWMain floating valve open - Channel id selected; Modbus HR683Write
PIV2207MainVlv_Open.T_On_RWMain floating valve open - Time on cycle relay; Modbus HR684Write
PIV2208MainVlv_Open.T_Off_RWMain floating valve open - Time off cycle releay; Modbus HR685Write
PIV2209MainVlv_Open.Ch_Type_RWMain floating valve open - Digital output type; Modbus HR686Write
PIV2210PreHeatVlv_Open.Board_RWPre-heating floating valve open - Board selected; Modbus HR687Write
PIV2211PreHeatVlv_Open.Ch_Id_RWPre-heating floating valve open - Channel id selected; Modbus HR688Write
PIV2212PreHeatVlv_Open.T_On_RWPre-heating floating valve open - Time on cycle relay; Modbus HR689Write
PIV2213PreHeatVlv_Open.T_Off_RWPre-heating floating valve open - Time off cycle releay; Modbus HR690Write
PIV2214PreHeatVlv_Open.Ch_Type_RWPre-heating floating valve open - Digital output type; Modbus HR691Write
PIV2215ReHeatVlv_Open.Board_RWRe-Heating floating valve open - Board selected; Modbus HR692Write
PIV2216ReHeatVlv_Open.Ch_Id_RWRe-Heating floating valve open - Channel id selected; Modbus HR693Write
PIV2217ReHeatVlv_Open.T_On_RWRe-Heating floating valve open - Time on cycle relay; Modbus HR694Write
PIV2218ReHeatVlv_Open.T_Off_RWRe-Heating floating valve open - Time off cycle releay; Modbus HR695Write
PIV2219ReHeatVlv_Open.Ch_Type_RWRe-Heating floating valve open - Digital output type; Modbus HR696Write
PIV2220MainVlv_Close.Board_RWMain floating valve close - Board selected; Modbus HR697Write
PIV2221MainVlv_Close.Ch_Id_RWMain floating valve close - Channel id selected; Modbus HR698Write
PIV2222MainVlv_Close.T_On_RWMain floating valve close - Time on cycle relay; Modbus HR699Write
PIV2223MainVlv_Close.T_Off_RWMain floating valve close - Time off cycle releay; Modbus HR700Write
PIV2224MainVlv_Close.Ch_Type_RWMain floating valve close - Digital output type; Modbus HR701Write
PIV2225PreHeatVlv_Close.Board_RWPre-heating floating valve close - Board selected; Modbus HR702Write
PIV2226PreHeatVlv_Close.Ch_Id_RWPre-heating floating valve close - Channel id selected; Modbus HR703Write
PIV2227PreHeatVlv_Close.T_On_RWPre-heating floating valve close - Time on cycle relay; Modbus HR704Write
PIV2228PreHeatVlv_Close.T_Off_RWPre-heating floating valve close - Time off cycle releay; Modbus HR705Write
PIV2229PreHeatVlv_Close.Ch_Type_RWPre-heating floating valve close - Digital output type; Modbus HR706Write
PIV2230ReHeatVlv_Close.Board_RWRe-Heating floating valve close - Board selected; Modbus HR707Write
PIV2231ReHeatVlv_Close.Ch_Id_RWRe-Heating floating valve close - Channel id selected; Modbus HR708Write
PIV2232ReHeatVlv_Close.T_On_RWRe-Heating floating valve close - Time on cycle relay; Modbus HR709Write
PIV2233ReHeatVlv_Close.T_Off_RWRe-Heating floating valve close - Time off cycle releay; Modbus HR710Write
PIV2234ReHeatVlv_Close.Ch_Type_RWRe-Heating floating valve close - Digital output type; Modbus HR711Write
PIV2235MainCoil_Step1.Board_RWMain step 1 - Board selected; Modbus HR712Write
PIV2236MainCoil_Step1.Ch_Id_RWMain step 1 - Channel id selected; Modbus HR713Write
PIV2237MainCoil_Step1.T_On_RWMain step 1 - Time on cycle relay; Modbus HR714Write
PIV2238MainCoil_Step1.T_Off_RWMain step 1 - Time off cycle releay; Modbus HR715Write
PIV2239MainCoil_Step1.Ch_Type_RWMain step 1 - Digital output type; Modbus HR716Write
PIV2240MainCoil_Step2.Board_RWMain step 2 - Board selected; Modbus HR717Write
PIV2241MainCoil_Step2.Ch_Id_RWMain step 2 - Channel id selected; Modbus HR718Write
PIV2242MainCoil_Step2.T_On_RWMain step 2 - Time on cycle relay; Modbus HR719Write
PIV2243MainCoil_Step2.T_Off_RWMain step 2 - Time off cycle releay; Modbus HR720Write
PIV2244MainCoil_Step2.Ch_Type_RWMain step 2 - Digital output type; Modbus HR721Write
PIV2245MainCoil_Step3.Board_RWMain step 3 - Board selected; Modbus HR722Write
PIV2246MainCoil_Step3.Ch_Id_RWMain step 3 - Channel id selected; Modbus HR723Write
PIV2247MainCoil_Step3.T_On_RWMain step 3 - Time on cycle relay; Modbus HR724Write
PIV2248MainCoil_Step3.T_Off_RWMain step 3 - Time off cycle releay; Modbus HR725Write
PIV2249MainCoil_Step3.Ch_Type_RWMain step 3 - Digital output type; Modbus HR726Write
PIV2250MainCoil_Step4.Board_RWMain step 4 - Board selected; Modbus HR727Write
PIV2251MainCoil_Step4.Ch_Id_RWMain step 4 - Channel id selected; Modbus HR728Write
PIV2252MainCoil_Step4.T_On_RWMain step 4 - Time on cycle relay; Modbus HR729Write
PIV2253MainCoil_Step4.T_Off_RWMain step 4 - Time off cycle releay; Modbus HR730Write
PIV2254MainCoil_Step4.Ch_Type_RWMain step 4 - Digital output type; Modbus HR731Write
PIV2255ReHeatCoil_Step1.Board_RWPostheat heater 1 - Board selected; Modbus HR732Write
PIV2256ReHeatCoil_Step1.Ch_Id_RWPostheat heater 1 - Channel id selected; Modbus HR733Write
PIV2257ReHeatCoil_Step1.T_On_RWPostheat heater 1 - Time on cycle relay; Modbus HR734Write
PIV2258ReHeatCoil_Step1.T_Off_RWPostheat heater 1 - Time off cycle releay; Modbus HR735Write
PIV2259ReHeatCoil_Step1.Ch_Type_RWPostheat heater 1 - Digital output type; Modbus HR736Write
PIV2260ReHeatCoil_Step2.Board_RWPostheat heater 2 - Board selected; Modbus HR737Write
PIV2261ReHeatCoil_Step2.Ch_Id_RWPostheat heater 2 - Channel id selected; Modbus HR738Write
PIV2262ReHeatCoil_Step2.T_On_RWPostheat heater 2 - Time on cycle relay; Modbus HR739Write
PIV2263ReHeatCoil_Step2.T_Off_RWPostheat heater 2 - Time off cycle releay; Modbus HR740Write
PIV2264ReHeatCoil_Step2.Ch_Type_RWPostheat heater 2 - Digital output type; Modbus HR741Write
PIV2265ReHeatCoil_Step3.Board_RWPostheat heater 3 - Board selected; Modbus HR742Write
PIV2266ReHeatCoil_Step3.Ch_Id_RWPostheat heater 3 - Channel id selected; Modbus HR743Write
PIV2267ReHeatCoil_Step3.T_On_RWPostheat heater 3 - Time on cycle relay; Modbus HR744Write
PIV2268ReHeatCoil_Step3.T_Off_RWPostheat heater 3 - Time off cycle releay; Modbus HR745Write
PIV2269ReHeatCoil_Step3.Ch_Type_RWPostheat heater 3 - Digital output type; Modbus HR746Write
PIV2270ReHeatCoil_Step4.Board_RWPostheat heater 4 - Board selected; Modbus HR747Write
PIV2271ReHeatCoil_Step4.Ch_Id_RWPostheat heater 4 - Channel id selected; Modbus HR748Write
PIV2272ReHeatCoil_Step4.T_On_RWPostheat heater 4 - Time on cycle relay; Modbus HR749Write
PIV2273ReHeatCoil_Step4.T_Off_RWPostheat heater 4 - Time off cycle releay; Modbus HR750Write
PIV2274ReHeatCoil_Step4.Ch_Type_RWPostheat heater 4 - Digital output type; Modbus HR751Write
PIV2275PreHeatCoil_Step1.Board_RWPreheat heater 1 - Board selected; Modbus HR752Write
PIV2276PreHeatCoil_Step1.Ch_Id_RWPreheat heater 1 - Channel id selected; Modbus HR753Write
PIV2277PreHeatCoil_Step1.T_On_RWPreheat heater 1 - Time on cycle relay; Modbus HR754Write
PIV2278PreHeatCoil_Step1.T_Off_RWPreheat heater 1 - Time off cycle releay; Modbus HR755Write
PIV2279PreHeatCoil_Step1.Ch_Type_RWPreheat heater 1 - Digital output type; Modbus HR756Write
PIV2280PreHeatCoil_Step2.Board_RWPreheat heater 2 - Board selected; Modbus HR757Write
PIV2281PreHeatCoil_Step2.Ch_Id_RWPreheat heater 2 - Channel id selected; Modbus HR758Write
PIV2282PreHeatCoil_Step2.T_On_RWPreheat heater 2 - Time on cycle relay; Modbus HR759Write
PIV2283PreHeatCoil_Step2.T_Off_RWPreheat heater 2 - Time off cycle releay; Modbus HR760Write
PIV2284PreHeatCoil_Step2.Ch_Type_RWPreheat heater 2 - Digital output type; Modbus HR761Write
PIV2285PreHeatCoil_Step3.Board_RWPreheat heater 3 - Board selected; Modbus HR762Write
PIV2286PreHeatCoil_Step3.Ch_Id_RWPreheat heater 3 - Channel id selected; Modbus HR763Write
PIV2287PreHeatCoil_Step3.T_On_RWPreheat heater 3 - Time on cycle relay; Modbus HR764Write
PIV2288PreHeatCoil_Step3.T_Off_RWPreheat heater 3 - Time off cycle releay; Modbus HR765Write
PIV2289PreHeatCoil_Step3.Ch_Type_RWPreheat heater 3 - Digital output type; Modbus HR766Write
PIV2290PreHeatCoil_Step4.Board_RWPreheat heater 4 - Board selected; Modbus HR767Write
PIV2291PreHeatCoil_Step4.Ch_Id_RWPreheat heater 4 - Channel id selected; Modbus HR768Write
PIV2292PreHeatCoil_Step4.T_On_RWPreheat heater 4 - Time on cycle relay; Modbus HR769Write
PIV2293PreHeatCoil_Step4.T_Off_RWPreheat heater 4 - Time off cycle releay; Modbus HR770Write
PIV2294PreHeatCoil_Step4.Ch_Type_RWPreheat heater 4 - Digital output type; Modbus HR771Write
PIV2295OA_Coil_Step1.Board_RWOutdoor air pre-treatment heater 1 - Board selected; Modbus HR772Write
PIV2296OA_Coil_Step1.Ch_Id_RWOutdoor air pre-treatment heater 1 - Channel id selected; Modbus HR773Write
PIV2297OA_Coil_Step1.T_On_RWOutdoor air pre-treatment heater 1 - Time on cycle relay; Modbus HR774Write
PIV2298OA_Coil_Step1.T_Off_RWOutdoor air pre-treatment heater 1 - Time off cycle relay; Modbus HR775Write
PIV2299OA_Coil_Step1.Ch_Type_RWOutdoor air pre-treatment heater 1 - Digital output type; Modbus HR776Write
PIV2300OA_Coil_Step2.Board_RWOutdoor air pre-treatment heater 2 - Board selected; Modbus HR777Write
PIV2301OA_Coil_Step2.Ch_Id_RWOutdoor air pre-treatment heater 2 - Channel id selected; Modbus HR778Write
PIV2302OA_Coil_Step2.T_On_RWOutdoor air pre-treatment heater 2 - Time on cycle relay; Modbus HR779Write
PIV2303OA_Coil_Step2.T_Off_RWOutdoor air pre-treatment heater 2 - Time off cycle relay; Modbus HR780Write
PIV2304OA_Coil_Step2.Ch_Type_RWOutdoor air pre-treatment heater 2 - Digital output type; Modbus HR781Write
PIV2305OA_Coil_Step3.Board_RWOutdoor air pre-treatment heater 3 - Board selected; Modbus HR782Write
PIV2306OA_Coil_Step3.Ch_Id_RWOutdoor air pre-treatment heater 3 - Channel id selected; Modbus HR783Write
PIV2307OA_Coil_Step3.T_On_RWOutdoor air pre-treatment heater 3 - Time on cycle relay; Modbus HR784Write
PIV2308OA_Coil_Step3.T_Off_RWOutdoor air pre-treatment heater 3 - Time off cycle relay; Modbus HR785Write
PIV2309OA_Coil_Step3.Ch_Type_RWOutdoor air pre-treatment heater 3 - Digital output type; Modbus HR786Write
PIV2310OA_Coil_Step4.Board_RWOutdoor air pre-treatment heater 4 - Board selected; Modbus HR787Write
PIV2311OA_Coil_Step4.Ch_Id_RWOutdoor air pre-treatment heater 4 - Channel id selected; Modbus HR788Write
PIV2312OA_Coil_Step4.T_On_RWOutdoor air pre-treatment heater 4 - Time on cycle relay; Modbus HR789Write
PIV2313OA_Coil_Step4.T_Off_RWOutdoor air pre-treatment heater 4 - Time off cycle relay; Modbus HR790Write
PIV2314OA_Coil_Step4.Ch_Type_RWOutdoor air pre-treatment heater 4 - Digital output type; Modbus HR791Write
PIV2315PreHeatPmp_1.Board_RWPre-Heating pump 1 - Board selected; Modbus HR792Write
PIV2316PreHeatPmp_1.Ch_Id_RWPre-Heating pump 1 - Channel id selected; Modbus HR793Write
PIV2317PreHeatPmp_1.T_On_RWPre-Heating pump 1 - Time on cycle relay; Modbus HR794Write
PIV2318PreHeatPmp_1.T_Off_RWPre-Heating pump 1 - Time off cycle releay; Modbus HR795Write
PIV2319PreHeatPmp_1.Ch_Type_RWPre-Heating pump 1 - Digital output type; Modbus HR796Write
PIV2320PreHeatPmp_2.Board_RWPre-Heating pump 2 - Board selected; Modbus HR797Write
PIV2321PreHeatPmp_2.Ch_Id_RWPre-Heating pump 2 - Channel id selected; Modbus HR798Write
PIV2322PreHeatPmp_2.T_On_RWPre-Heating pump 2 - Time on cycle relay; Modbus HR799Write
PIV2323PreHeatPmp_2.T_Off_RWPre-Heating pump 2 - Time off cycle releay; Modbus HR800Write
PIV2324PreHeatPmp_2.Ch_Type_RWPre-Heating pump 2 - Digital output type; Modbus HR801Write
PIV2325MainCoilPmp_1.Board_RWMain pump 1 - Board selected; Modbus HR802Write
PIV2326MainCoilPmp_1.Ch_Id_RWMain pump 1 - Channel id selected; Modbus HR803Write
PIV2327MainCoilPmp_1.T_On_RWMain pump 1 - Time on cycle relay; Modbus HR804Write
PIV2328MainCoilPmp_1.T_Off_RWMain pump 1 - Time off cycle releay; Modbus HR805Write
PIV2329MainCoilPmp_1.Ch_Type_RWMain pump 1 - Digital output type; Modbus HR806Write
PIV2330MainCoilPmp_2.Board_RWMain pump 2 - Board selected; Modbus HR807Write
PIV2331MainCoilPmp_2.Ch_Id_RWMain pump 2 - Channel id selected; Modbus HR808Write
PIV2332MainCoilPmp_2.T_On_RWMain pump 2 - Time on cycle relay; Modbus HR809Write
PIV2333MainCoilPmp_2.T_Off_RWMain pump 2 - Time off cycle releay; Modbus HR810Write
PIV2334MainCoilPmp_2.Ch_Type_RWMain pump 2 - Digital output type; Modbus HR811Write
PIV2335ReHeatPmp_1.Board_RWRe-Heating pump 1 - Board selected; Modbus HR812Write
PIV2336ReHeatPmp_1.Ch_Id_RWRe-Heating pump 1 - Channel id selected; Modbus HR813Write
PIV2337ReHeatPmp_1.T_On_RWRe-Heating pump 1 - Time on cycle relay; Modbus HR814Write
PIV2338ReHeatPmp_1.T_Off_RWRe-Heating pump 1 - Time off cycle releay; Modbus HR815Write
PIV2339ReHeatPmp_1.Ch_Type_RWRe-Heating pump 1 - Digital output type; Modbus HR816Write
PIV2340ReHeatPmp_2.Board_RWRe-Heating pump 2 - Board selected; Modbus HR817Write
PIV2341ReHeatPmp_2.Ch_Id_RWRe-Heating pump 2 - Channel id selected; Modbus HR818Write
PIV2342ReHeatPmp_2.T_On_RWRe-Heating pump 2 - Time on cycle relay; Modbus HR819Write
PIV2343ReHeatPmp_2.T_Off_RWRe-Heating pump 2 - Time off cycle releay; Modbus HR820Write
PIV2344ReHeatPmp_2.Ch_Type_RWRe-Heating pump 2 - Digital output type; Modbus HR821Write
PIV2345OA_CoilPmp_1.Board_RWOutdoor air pre-treatment -Heating pump 1 - Board selected; Modbus HR822Write
PIV2346OA_CoilPmp_1.Ch_Id_RWOutdoor air pre-treatment -Heating pump 1 - Channel id selected; Modbus HR823Write
PIV2347OA_CoilPmp_1.T_On_RWOutdoor air pre-treatment -Heating pump 1 - Time on cycle relay; Modbus HR824Write
PIV2348OA_CoilPmp_1.T_Off_RWOutdoor air pre-treatment -Heating pump 1 - Time off cycle releay; Modbus HR825Write
PIV2349OA_CoilPmp_1.Ch_Type_RWOutdoor air pre-treatment -Heating pump 1 - Digital output type; Modbus HR826Write
PIV2350OA_CoilPmp_2.Board_RWOutdoor air pre-treatment -Heating pump 2 - Board selected; Modbus HR827Write
PIV2351OA_CoilPmp_2.Ch_Id_RWOutdoor air pre-treatment -Heating pump 2 - Channel id selected; Modbus HR828Write
PIV2352OA_CoilPmp_2.T_On_RWOutdoor air pre-treatment -Heating pump 2 - Time on cycle relay; Modbus HR829Write
PIV2353OA_CoilPmp_2.T_Off_RWOutdoor air pre-treatment -Heating pump 2 - Time off cycle releay; Modbus HR830Write
PIV2354OA_CoilPmp_2.Ch_Type_RWOutdoor air pre-treatment -Heating pump 2 - Digital output type; Modbus HR831Write
PIV2355FiltAlrm_Dout.Board_RWFilters alarm - Board selected; Modbus HR832Write
PIV2356FiltAlrm_Dout.Ch_Id_RWFilters alarm - Channel id selected; Modbus HR833Write
PIV2357FiltAlrm_Dout.T_On_RWFilters alarm - Time on cycle relay; Modbus HR834Write
PIV2358FiltAlrm_Dout.T_Off_RWFilters alarm - Time off cycle releay; Modbus HR835Write
PIV2359FiltAlrm_Dout.Ch_Type_RWFilters alarm - Digital output type; Modbus HR836Write
PIV2360Recovery_Dout.Board_RWRecovery - Board selected; Modbus HR837Write
PIV2361Recovery_Dout.Ch_Id_RWRecovery - Channel id selected; Modbus HR838Write
PIV2362Recovery_Dout.T_On_RWRecovery - Time on cycle relay; Modbus HR839Write
PIV2363Recovery_Dout.T_Off_RWRecovery - Time off cycle releay; Modbus HR840Write
PIV2364Recovery_Dout.Ch_Type_RWRecovery - Digital output type; Modbus HR841Write
PIV2365IEC_Hum_Dout.Board_RWIEC humidifer - Board selected; Modbus HR842Write
PIV2366IEC_Hum_Dout.Ch_Id_RWIEC humidifer - Channel id selected; Modbus HR843Write
PIV2367IEC_Hum_Dout.T_On_RWIEC humidifer - Time on cycle relay; Modbus HR844Write
PIV2368IEC_Hum_Dout.T_Off_RWIEC humidifer - Time off cycle releay; Modbus HR845Write
PIV2369IEC_Hum_Dout.Ch_Type_RWIEC humidifer - Digital output type; Modbus HR846Write
PIV2370SupplyFan_Aout.Board_RWSupply fan - Board selected; Modbus HR847Write
PIV2371SupplyFan_Aout.Ch_Id_RWSupply fan - Channel id selected; Modbus HR848Write
AV2372SupplyFan_Aout.MinOut_RWSupply fan - Minimum signal analog output; Modbus HR849Write
AV2373SupplyFan_Aout.MaxOut_RWSupply fan - Maximum signal analog output; Modbus HR850Write
AV2374SupplyFan_Aout.PulseWidth_RWSupply fan - Pulse width setting; Modbus HR851Write
PIV2375SupplyFan_Aout.Ch_Type_RWSupply fan - Analog output type; Modbus HR852Write
PIV2376RetFan_Aout.Board_RWReturn fan - Board selected; Modbus HR853Write
PIV2377RetFan_Aout.Ch_Id_RWReturn fan - Channel id selected; Modbus HR854Write
AV2378RetFan_Aout.MinOut_RWReturn fan - Minimum signal analog output; Modbus HR855Write
AV2379RetFan_Aout.MaxOut_RWReturn fan - Maximum signal analog output; Modbus HR856Write
AV2380RetFan_Aout.PulseWidth_RWReturn fan - Pulse width setting; Modbus HR857Write
PIV2381RetFan_Aout.Ch_Type_RWReturn fan - Analog output type; Modbus HR858Write
PIV2382BypassDamp_Aout.Board_RWBypass damper - Board selected; Modbus HR859Write
PIV2383BypassDamp_Aout.Ch_Id_RWBypass damper - Channel id selected; Modbus HR860Write
AV2384BypassDamp_Aout.MinOut_RWBypass damper - Minimum signal analog output; Modbus HR861Write
AV2385BypassDamp_Aout.MaxOut_RWBypass damper - Maximum signal analog output; Modbus HR862Write
AV2386BypassDamp_Aout.PulseWidth_RWBypass damper - Pulse width setting; Modbus HR863Write
PIV2387BypassDamp_Aout.Ch_Type_RWBypass damper - Analog output type; Modbus HR864Write
PIV2388MixingDamp_Aout.Board_RWMixing damper - Board selected; Modbus HR865Write
PIV2389MixingDamp_Aout.Ch_Id_RWMixing damper - Channel id selected; Modbus HR866Write
AV2390MixingDamp_Aout.MinOut_RWMixing damper - Minimum signal analog output; Modbus HR867Write
AV2391MixingDamp_Aout.MaxOut_RWMixing damper - Maximum signal analog output; Modbus HR868Write
AV2392MixingDamp_Aout.PulseWidth_RWMixing damper - Pulse width setting; Modbus HR869Write
PIV2393MixingDamp_Aout.Ch_Type_RWMixing damper - Analog output type; Modbus HR870Write
PIV2394FreshAirDamp_Aout.Board_RWFresh air damper - Board selected; Modbus HR871Write
PIV2395FreshAirDamp_Aout.Ch_Id_RWFresh air damper - Channel id selected; Modbus HR872Write
AV2396FreshAirDamp_Aout.MinOut_RWFresh air damper - Minimum signal analog output; Modbus HR873Write
AV2397FreshAirDamp_Aout.MaxOut_RWFresh air damper - Maximum signal analog output; Modbus HR874Write
AV2398FreshAirDamp_Aout.PulseWidth_RWFresh air damper - Pulse width setting; Modbus HR875Write
PIV2399FreshAirDamp_Aout.Ch_Type_RWFresh air damper - Analog output type; Modbus HR876Write
PIV2400ReHeatCoil_Aout.Board_RWReheat heater - Board selected; Modbus HR877Write
PIV2401ReHeatCoil_Aout.Ch_Id_RWReheat heater - Channel id selected; Modbus HR878Write
AV2402ReHeatCoil_Aout.MinOut_RWReheat heater - Minimum signal analog output; Modbus HR879Write
AV2403ReHeatCoil_Aout.MaxOut_RWReheat heater - Maximum signal analog output; Modbus HR880Write
AV2404ReHeatCoil_Aout.PulseWidth_RWReheat heater - Pulse width setting; Modbus HR881Write
PIV2405ReHeatCoil_Aout.Ch_Type_RWReheat heater - Analog output type; Modbus HR882Write
PIV2406PreHeatCoil_Aout.Board_RWPre-Heating heater - Board selected; Modbus HR883Write
PIV2407PreHeatCoil_Aout.Ch_Id_RWPre-Heating heater - Channel id selected; Modbus HR884Write
AV2408PreHeatCoil_Aout.MinOut_RWPre-Heating heater - Minimum signal analog output; Modbus HR885Write
AV2409PreHeatCoil_Aout.MaxOut_RWPre-Heating heater - Maximum signal analog output; Modbus HR886Write
AV2410PreHeatCoil_Aout.PulseWidth_RWPre-Heating heater - Pulse width setting; Modbus HR887Write
PIV2411PreHeatCoil_Aout.Ch_Type_RWPre-Heating heater - Analog output type; Modbus HR888Write
PIV2412OA_Coil_Aout.Board_RWOutdoor air pre-treatment heater - Board selected; Modbus HR889Write
PIV2413OA_Coil_Aout.Ch_Id_RWOutdoor air pre-treatment heater - Channel id selected; Modbus HR890Write
AV2414OA_Coil_Aout.MinOut_RWOutdoor air pre-treatment heater - Minimum signal analog output; Modbus HR891Write
AV2415OA_Coil_Aout.MaxOut_RWOutdoor air pre-treatment heater - Maximum signal analog output; Modbus HR892Write
AV2416OA_Coil_Aout.PulseWi-dth_RWOutdoor air pre-treatment heater - Pulse width setting; Modbus HR893Write
PIV2417OA_Coil_Aout.Ch_Type_RWOutdoor air pre-treatment heater - Analog output type; Modbus HR894Write
PIV2418MainCoil_Aout.Board_RWMain coil valve - Board selected; Modbus HR895Write
PIV2419MainCoil_Aout.Ch_Id_RWMain coil valve - Channel id selected; Modbus HR896Write
AV2420MainCoil_Aout.MinOut_RWMain coil valve - Minimum signal analog output; Modbus HR897Write
AV2421MainCoil_Aout.MaxOut_RWMain coil valve - Maximum signal analog output; Modbus HR898Write
AV2422MainCoil_Aout.PulseWidth_RWMain coil valve - Pulse width setting; Modbus HR899Write
PIV2423MainCoil_Aout.Ch_Type_RWMain coil valve - Analog output type; Modbus HR900Write
PIV2424ThrmlWheel_Aout.Board_RWThermal wheel - Board selected; Modbus HR901Write
PIV2425ThrmlWheel_Aout.Ch_Id_RWThermal wheel - Channel id selected; Modbus HR902Write
AV2426ThrmlWheel_Aout.MinOut_RWThermal wheel - Minimum signal analog output; Modbus HR903Write
AV2427ThrmlWheel_Aout.MaxOut_RWThermal wheel - Maximum signal analog output; Modbus HR904Write
AV2428ThrmlWheel_Aout.PulseWidth_RWThermal wheel - Pulse width setting; Modbus HR905Write
PIV2429ThrmlWheel_Aout.Ch_Type_RWThermal wheel - Analog output type; Modbus HR906Write
PIV2430Humidifier_Aout.Board_RWHumidifier - Board selected; Modbus HR907Write
PIV2431Humidifier_Aout.Ch_Id_RWHumidifier - Channel id selected; Modbus HR908Write
AV2432Humidifier_Aout.MinOut_RWHumidifier - Minimum signal analog output; Modbus HR909Write
AV2433Humidifier_Aout.MaxOut_RWHumidifier - Maximum signal analog output; Modbus HR910Write
AV2434Humidifier_Aout.PulseWidth_RWHumidifier - Pulse width setting; Modbus HR911Write
PIV2435Humidifier_Aout.Ch_Type_RWHumidifier - Analog output type; Modbus HR912Write
PIV2436ExhAirDamp_Aout.Board_RWExhaust air damper - Board selected; Modbus HR913Write
PIV2437ExhAirDamp_Aout.Ch_Id_RWExhaust air damper - Channel id selected; Modbus HR914Write
AV2438ExhAirDamp_Aout.MinOut_RWExhaust air damper - Minimum signal analog output; Modbus HR915Write
AV2439ExhAirDamp_Aout.MaxOut_RWExhaust air damper - Maximum signal analog output; Modbus HR916Write
AV2440ExhAirDamp_Aout.PulseWidth_RWExhaust air damper - Pulse width setting; Modbus HR917Write
PIV2441ExhAirDamp_Aout.Ch_Type_RWExhaust air damper - Analog output type; Modbus HR918Write
PIV2442AuxAout_1.Board_RWAuxiliary output 1 - Board selected; Modbus HR919Write
PIV2443AuxAout_1.Ch_Id_RWAuxiliary output 1 - Channel id selected; Modbus HR920Write
AV2444AuxAout_1.MinOut_RWAuxiliary output 1 - Minimum signal analog output; Modbus HR921Write
AV2445AuxAout_1.MaxOut_RWAuxiliary output 1 - Maximum signal analog output; Modbus HR922Write
AV2446AuxAout_1.PulseWidth_RWAuxiliary output 1 - Pulse width setting; Modbus HR923Write
PIV2447AuxAout_1.Ch_Type_RWAuxiliary output 1 - Analog output type; Modbus HR924Write
PIV2448AuxAout_2.Board_RWAuxiliary output 2 - Board selected; Modbus HR925Write
PIV2449AuxAout_2.Ch_Id_RWAuxiliary output 2 - Channel id selected; Modbus HR926Write
AV2450AuxAout_2.MinOut_RWAuxiliary output 2 - Minimum signal analog output; Modbus HR927Write
AV2451AuxAout_2.MaxOut_RWAuxiliary output 2 - Maximum signal analog output; Modbus HR928Write
AV2452AuxAout_2.PulseWidth_RWAuxiliary output 2 - Pulse width setting; Modbus HR929Write
PIV2453AuxAout_2.Ch_Type_RWAuxiliary output 2 - Analog output type; Modbus HR930Write
PIV2454AuxAout_3.Board_RWAuxiliary output 3 - Board selected; Modbus HR931Write
PIV2455AuxAout_3.Ch_Id_RWAuxiliary output 3 - Channel id selected; Modbus HR932Write
AV2456AuxAout_3.MinOut_RWAuxiliary output 3 - Minimum signal analog output; Modbus HR933Write
AV2457AuxAout_3.MaxOut_RWAuxiliary output 3 - Maximum signal analog output; Modbus HR934Write
AV2458AuxAout_3.PulseWidth_RWAuxiliary output 3 - Pulse width setting; Modbus HR935Write
PIV2459AuxAout_3.Ch_Type_RWAuxiliary output 3 - Analog output type; Modbus HR936Write
PIV2460AuxAout_4.Board_RWAuxiliary output 4 - Board selected; Modbus HR937Write
PIV2461AuxAout_4.Ch_Id_RWAuxiliary output 4 - Channel id selected; Modbus HR938Write
AV2462AuxAout_4.MinOut_RWAuxiliary output 4 - Minimum signal analog output; Modbus HR939Write
AV2463AuxAout_4.MaxOut_RWAuxiliary output 4 - Maximum signal analog output; Modbus HR940Write
AV2464AuxAout_4.PulseWidth_RWAuxiliary output 4 - Pulse width setting; Modbus HR941Write
PIV2465AuxAout_4.Ch_Type_RWAuxiliary output 4 - Analog output type; Modbus HR942Write
PIV2466IEC_Aout.Board_RWIEC - Board selected; Modbus HR943Write
PIV2467IEC_Aout.Ch_Id_RWIEC - Channel id selected; Modbus HR944Write
AV2468IEC_Aout.MinOut_RWIEC - Minimum signal analog output; Modbus HR945Write
AV2469IEC_Aout.MaxOut_RWIEC - Maximum signal analog output; Modbus HR946Write
AV2470IEC_Aout.PulseWidth_RWIEC - Pulse width setting; Modbus HR947Write
PIV2471IEC_Aout.Ch_Type_RWIEC - Analog output type; Modbus HR948Write
PIV2472Recovery_Aout.Board_RWRecovery pump - Board selected; Modbus HR949Write
PIV2473Recovery_Aout.Ch_Id_RWRecovery pump - Channel id selected; Modbus HR950Write
AV2474Recovery_Aout.MinOut_RWRecovery pump - Minimum signal analog output; Modbus HR951Write
AV2475Recovery_Aout.MaxOut_RWRecovery pump - Maximum signal analog output; Modbus HR952Write
AV2476Recovery_Aout.PulseWidth_RWRecovery pump - Pulse width setting; Modbus HR953Write
PIV2477Recovery_Aout.Ch_Type_RWRecovery pump - Analog output type; Modbus HR954Write
PIV2478SupplyAirDamp_Aout.Board_RWSupply air damper - Board selected; Modbus HR955Write
PIV2479SupplyAirDamp_Aout.Ch_Id_RWSupply air damper - Channel id selected; Modbus HR956Write
AV2480SupplyAirDamp_Aout.MinOut_RWSupply air damper - Minimum signal analog output; Modbus HR957Write
AV2481SupplyAirDamp_Aout.MaxOut_RWSupply air damper - Maximum signal analog output; Modbus HR958Write
AV2482SupplyAirDamp_Aout.PulseWidth_RWSupply air damper - Pulse width setting; Modbus HR959Write
PIV2483SupplyAirDamp_Aout.Ch_Type_RWSupply air damper - Analog output type; Modbus HR960Write
PIV2484RetAirDamp_Aout.Board_RWReturn air damper - Board selected; Modbus HR961Write
PIV2485RetAirDamp_Aout.Ch_Id_RWReturn air damper - Channel id selected; Modbus HR962Write
AV2486RetAirDamp_Aout.MinOut_RWReturn air damper - Minimum signal analog output; Modbus HR963Write
AV2487RetAirDamp_Aout.MaxOut_RWReturn air damper - Maximum signal analog output; Modbus HR964Write
AV2488RetAirDamp_Aout.PulseWidth_RWReturn air damper - Pulse width setting; Modbus HR965Write
PIV2489RetAirDamp_Aout.Ch_Type_RWReturn air damper - Analog output type; Modbus HR966Write
AV2493CurrTempSetPCurrent temperature setpoint; Modbus HR970Write
AV2496CurrSupplyAirFlwSetPCurrent supply air flow setpoint; 32-bit (2 Modbus registers); Modbus HR971Write
AV2497CurrAirQuality_CO2_SetPCurrent air quality CO2 setpoint; Modbus HR973Write
AV2498CurrSupplyStaticP_SetPCurrent supply static pressure setpoint; Modbus HR974Write
AV2499CurrRetAirFlwSetPCurrent return air flow setpoint; 32-bit (2 Modbus registers); Modbus HR975Write
AV2500CurrRetStaticP_SetPCurrent return static pressure setpoint; Modbus HR977Write
IV2501STD_UOM_ZONE_UIUnit of measure for user interface; 32-bit (2 Modbus registers); Modbus HR978Write
AV2502AuxReg1_Cfg.SetPAuxiliary Regulation 1 - Regulation setpoint; Modbus HR980Write
AV2503CurrHumSetPCurrent humidity setpoint; Modbus HR981Write
PIV2504CoolHeat_Chg_DTCooling/Heating change delay time; Modbus HR982Write
PIV2505VarToShow.Ch_TypeModbus HR983Write
AV2506ObjMsk.Min_StaticPressHigh/low limit alarm with hysteresis - Minimum value static pressure; Modbus HR984Write
AV2507ObjMsk.Min_AirQualHigh/low limit alarm with hysteresis - Minimum value air quality; Modbus HR985Write
AV2508ObjMsk.Min_RfrgPressHigh/low limit alarm with hysteresis - Minimum value refrigerant pressure; Modbus HR986Write
AV2509ObjMsk.Min_FlowRateHigh/low limit alarm with hysteresis - Minimum flow rate; Modbus HR987Write
AV2510ObjMsk.Min_AirFlowHigh/low limit alarm with hysteresis - Minimum value air flow; Modbus HR988Write
AV2511ObjMsk.Min_TempHigh/low limit alarm with hysteresis - Minimum value temperature; Modbus HR989Write
AV2512ObjMsk.Min_AoutHigh/low limit alarm with hysteresis - Minimum value AOUT; Modbus HR990Write
AV2513ObjMsk.Min_HumHigh/low limit alarm with hysteresis - Minimum value humidity; Modbus HR991Write
AV2514ObjMsk.Min_GenericHigh/low limit alarm with hysteresis - Minimum value generic; Modbus HR992Write
AV2515ObjMsk.Min_PercentHigh/low limit alarm with hysteresis - Minimum value percent; Modbus HR993Write
AV2516ObjMsk.Max_StaticPressHigh/low limit alarm with hysteresis - Maximum value static pressure; Modbus HR994Write
AV2517ObjMsk.Max_AirQualHigh/low limit alarm with hysteresis - Maximum value air quality; Modbus HR995Write
AV2518ObjMsk.Max_RfrgPressHigh/low limit alarm with hysteresis - Maximum value refrigerant pressure; Modbus HR996Write
AV2519ObjMsk.Max_FlowRateHigh/low limit alarm with hysteresis - Maximum flow rate; Modbus HR997Write
AV2520ObjMsk.Max_AirFlowHigh/low limit alarm with hysteresis - Maximum air flow; Modbus HR998Write
AV2521ObjMsk.Max_HumHigh/low limit alarm with hysteresis - Maxmimum value humidity; Modbus HR999Write
AV2522ObjMsk.Max_TempHigh/low limit alarm with hysteresis - Maximum value temperature; Modbus HR1000Write
AV2523ObjMsk.Max_AoutHigh/low limit alarm with hysteresis - Maximum value AOUT; Modbus HR1001Write
AV2524ObjMsk.Max_GenericHigh/low limit alarm with hysteresis - Maximum value generic; Modbus HR1002Write
AV2525ObjMsk.Max_PercentHigh/low limit alarm with hysteresis - Maximum value percent; Modbus HR1003Write
AV2526ObjMsk.ValOffsetRfrgPressHigh/low limit alarm with hysteresis - Offset value refrigerant pressure; Modbus HR1004Write
AV2527ObjMsk.ValOffsetFlowRateHigh/low limit alarm with hysteresis - Offset value flow rate; Modbus HR1005Write
AV2528ObjMsk.ValOffsetAirFLowHigh/low limit alarm with hysteresis - Offset value air flow; Modbus HR1006Write
AV2529ObjMsk.ValOffsetHumHigh/low limit alarm with hysteresis - Offset value humidity; Modbus HR1007Write
AV2530ObjMsk.ValOffsetTempHigh/low limit alarm with hysteresis - Offset value temperature; Modbus HR1008Write
AV2531ObjMsk.ValOffsetPercentHigh/low limit alarm with hysteresis - Offset value percent; Modbus HR1009Write
AV2532ObjMsk.ValOffsetAirQualHigh/low limit alarm with hysteresis - Offset value air quality; Modbus HR1010Write
AV2533ObjMsk.ValOffsetStaticPressHigh/low limit alarm with hysteresis - Offset value static pressure; Modbus HR1011Write
AV2534ObjMsk.ValOffsetGenericHigh/low limit alarm with hysteresis - Offset value generic probe; Modbus HR1012Write
PIV2535VarToShow.ChFilterModbus HR1013Write
PIV2536GeneralMng.WizardTypeWizard type ( 0: skip, 1: Pre-Loaded, 2: Custom); Modbus HR1014Write
PIV2537GeneralMng.DriveTypDrive type (0: Internal public volume; 1: USB pendrive); Modbus HR1015Write
IV2538GeneralMng.PreLoadConfNumber32-bit (2 Modbus registers); Modbus HR1016Write
IV2539GeneralMng.ExpCfg_Char032-bit (2 Modbus registers); Modbus HR1018Write
IV2540GeneralMng.ExpCfg_Char132-bit (2 Modbus registers); Modbus HR1020Write
IV2541GeneralMng.ExpCfg_Char232-bit (2 Modbus registers); Modbus HR1022Write
IV2542GeneralMng.ExpCfg_Char332-bit (2 Modbus registers); Modbus HR1024Write
IV2543GeneralMng.ExpCfg_Char432-bit (2 Modbus registers); Modbus HR1026Write
IV2544GeneralMng.ExpCfg_Char532-bit (2 Modbus registers); Modbus HR1028Write
IV2545GeneralMng.ExpCfg_Char632-bit (2 Modbus registers); Modbus HR1030Write
IV2546GeneralMng.ExpCfg_Char732-bit (2 Modbus registers); Modbus HR1032Write
IV2547GeneralMng.ExpCfg_Char832-bit (2 Modbus registers); Modbus HR1034Write
IV2548GeneralMng.ExpCfg_Char932-bit (2 Modbus registers); Modbus HR1036Write
IV2549GeneralMng.ExpCfg_Char1032-bit (2 Modbus registers); Modbus HR1038Write
BV2550GeneralMng.WizardConfirmModbus HR1040Write
AV2551FreshAirDampManModeValFresh air damper manual mode value; Modbus HR1041Write
PIV2552FreshAirDampManModeVal_OnOffFor mask usage; Modbus HR1042Write
AV2553MixDampManModeValMixing damper manual mode value; Modbus HR1043Write
PIV2554MixDampManModeVal_OnOffFor mask usage; Modbus HR1044Write
AV2555ExhAirDampManModeValExhaust air damper manual mode value; Modbus HR1045Write
PIV2556ExhAirDampManModeVal_OnOffFor mask usage; Modbus HR1046Write
AV2557BypassDampManModeValBypaas damper manual mode value; Modbus HR1047Write
PIV2558BypassDampManModeVal_OnOffFor mask usage; Modbus HR1048Write
PIV2559SupplyFanManModeVal_3SpeedFor mask usage; Modbus HR1049Write
AV2560SupplyFanManModeValSupply fan manual mode value; Modbus HR1050Write
PIV2561SupplyFanManModeVal_OnOffFor mask usage; Modbus HR1051Write
PIV2562RetFanManModeVal_3SpeedFor mask usage; Modbus HR1052Write
AV2563RetFanManModeValReturn fan manual mode value; Modbus HR1053Write
PIV2564RetFanManModeVal_OnOffFor mask usage; Modbus HR1054Write
AV2565PreHeatCoilManModeValPre heating coil manual mode value; Modbus HR1055Write
AV2566MainCoilManModeValMain coil manual mode value; Modbus HR1056Write
AV2567ReHeatCoilManModeValPost heating coil manual mode value; Modbus HR1057Write
AV2568CompManModeValCompressor manual mode value; Modbus HR1058Write
PIV2569CompManModeVal_USINTFor mask usage; Modbus HR1059Write
AV2570HumManModeValHumidifier manual mode value; Modbus HR1060Write
AV2571ThermWhlManModeValThermal wheel manual mode value; Modbus HR1061Write
AV2578UnitSetP.TempSetP.Summer.PreComfortUnit setpoints - Temperature setpoint - Summer - Pre-comfort; Modbus HR1068Write
AV2579UnitSetP.TempSetP.Winter.PreComfortUnit setpoints - Temperature setpoint - Winter - Pre-comfort; Modbus HR1069Write
AVmin2584UnitSetP.TempSetP.Summer.ComfortUnit setpoints - Temperature setpoint - Summer - Comfort; Modbus HR1074Write
AVmin2585UnitSetP.TempSetP.Winter.ComfortUnit setpoints - Temperature setpoint - Winter - Comfort; Modbus HR1075Write
AV2586TempSetP_MinValTemperature setpoint - minimum value; Modbus HR1076Write
AV2587TempSetP_MaxValTemperature setpoint - maximum value; Modbus HR1077Write
AV2626UnitSetP.SupplyStaticP_SetP.EconomyUnit setpoints - Supply static pressure - Economy; Modbus HR1116Write
AV2629UnitSetP.SupplyStaticP_SetP.PreComfortUnit setpoints - Supply static pressure - Pre-comfort; Modbus HR1119Write
AV2632UnitSetP.SupplyStaticP_SetP.ComfortUnit setpoints - Supply static pressure - Comfort; Modbus HR1122Write
AV2633SupplyStaticPressSetP_MinValSupply static pressure setpoint - minimum value; Modbus HR1123Write
AV2634SupplyStaticPressSetP_MaxValSupply static pressure setpoint - maximum value; Modbus HR1124Write
PIV2635UnitSetP.SupplyAirFlwSetP.EconomyUnit setpoints - Supply air flow - Economy; 32-bit (2 ...; Modbus HR1125Write
PIV2637UnitSetP.SupplyAirFlwSetP.PreComfortUnit setpoints - Supply air flow - Pre-comfort; 32-bit (2 ...; Modbus HR1127Write
PIV2639UnitSetP.SupplyAirFlwSetP.ComfortUnit setpoints - Supply air flow - Comfort; 32-bit (2 ...; Modbus HR1129Write
PIV2641SupplyAirFlwSetP_MinValSupply air flow setpoint - minimum value; 32-bit (2 Modbus registers); Modbus HR1131Write
PIV2643SupplyAirFlwSetP_MaxValSupply air flow setpoint - maximum value; 32-bit (2 Modbus registers); Modbus HR1133Write
AV2645UnitSetP.AirQuality_CO2_SetP.EconomyUnit setpoints - Air quality CO2 - Economy; Modbus HR1135Write
AV2647UnitSetP.AirQuality_CO2_SetP.PreComfortUnit setpoints - Air quality CO2 - Pre-comfort; Modbus HR1137Write
AV2650UnitSetP.AirQuality_CO2_SetP.ComfortUnit setpoints - Air quality CO2 - Comfort; Modbus HR1140Write
AV2651AirQualityCO2SetP_MinValAir quality CO2 setpoint - minimum value; Modbus HR1141Write
AV2652AirQualityCO2SetP_MaxValAir quality CO2 setpoint - maximum value; Modbus HR1142Write
AV2653UnitSetP.RetStaticP_SetP.EconomyUnit setpoints - Return static pressure - Economy; Modbus HR1143Write
AV2656UnitSetP.RetStaticP_SetP.PreComfortUnit setpoints - Return static pressure - Pre-comfort; Modbus HR1146Write
AV2659UnitSetP.RetStaticP_SetP.ComfortUnit setpoints - Return static pressure - Comfort; Modbus HR1149Write
AV2660RetStaticPressSetP_MinValReturn static pressure setpoint - minimum value; Modbus HR1150Write
AV2661RetStaticPressSetP_MaxValReturn static pressure setpoint - maximum value; Modbus HR1151Write
PIV2662UnitSetP.RetAirFlwSetP.EconomyUnit setpoints - Return air flow - Economy; Modbus HR1152Write
PIV2664UnitSetP.RetAirFlwSetP.PreComfortUnit setpoints - Return air flow - Pre-comfort; 32-bit (2 ...; Modbus HR1154Write
PIV2666UnitSetP.RetAirFlwSetP.ComfortUnit setpoints - Return air flow - Comfort; 32-bit (2 ...; Modbus HR1156Write
PIV2668RetAirFlwSetP_MinValReturn air flow setpoint - minimum value; 32-bit (2 Modbus registers); Modbus HR1158Write
PIV2670RetAirFlwSetP_MaxValReturn air flow setpoint - maximum value; 32-bit (2 Modbus registers); Modbus HR1160Write
AV2672UnitSetP.HumSetP.Summer.EconomyUnit setpoints - Humidity - Summer - Economy; Modbus HR1162Write
AV2673UnitSetP.HumSetP.Winter.EconomyUnit setpoints - Humidity - Winter - Economy; Modbus HR1163Write
AV2677UnitSetP.HumSetP.Summer.PreComfortUnit setpoints - Humidity - Summer - Pre-comfort; Modbus HR1167Write
AV2678UnitSetP.HumSetP.Winter.PreComfortUnit setpoints - Humidity - Winter - Pre-comfort; Modbus HR1168Write
AV2683UnitSetP.HumSetP.Summer.ComfortUnit setpoints - Humidity - Summer - Comfort; Modbus HR1173Write
AV2684UnitSetP.HumSetP.Winter.ComfortUnit setpoints - Humidity - Winter - Comfort; Modbus HR1174Write
AV2685HumSetP_MinValHumidity setpoint - minimum value; Modbus HR1175Write
AV2686HumSetP_MaxValHumidity setpoint - maximum value; Modbus HR1176Write
AV2689Regulation.SummerExtTempCompensThrshSummer: external temperature compensation delta; Modbus HR1179Write
AV2690Regulation.SummerExtTempCompensDeltaSummer: external temperature compensation delta; Modbus HR1180Write
AV2691Regulation.SummerMaxCompensOffsetSummer: maximum compensation offset; Modbus HR1181Write
AV2692Regulation.WinterExtTempCompensThrshWinter: external temperature compensation threshold; Modbus HR1182Write
AV2693Regulation.WinterExtTempCompensDeltaWinter: external temperature compensation delta; Modbus HR1183Write
AV2694Regulation.WinterMaxCompensOffsetWinter: maximum compensation offset; Modbus HR1184Write
IV2695Scheduler_OnOffUnit.FB_SchedulerMskMng_1.PrgNr32-bit (2 Modbus registers); Modbus HR1185Write
PIV2696Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[0].HoursEvent - Start hours event; Modbus HR1187Write
PIV2697Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[0].MinsEvent - Start minutes event; Modbus HR1188Write
PIV2698Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[0].ModeEvent - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1189Write
PIV2699Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[1].HoursEvent - Start hours event; Modbus HR1190Write
PIV2700Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[1].MinsEvent - Start minutes event; Modbus HR1191Write
PIV2701Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[1].ModeEvent - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1192Write
PIV2702Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[2].HoursEvent - Start hours event; Modbus HR1193Write
PIV2703Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[2].MinsEvent - Start minutes event; Modbus HR1194Write
PIV2704Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[2].ModeEvent - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1195Write
PIV2705Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[3].HoursEvent - Start hours event; Modbus HR1196Write
PIV2706Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[3].MinsEvent - Start minutes event; Modbus HR1197Write
PIV2707Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[3].ModeEvent - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1198Write
PIV2708Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[4].HoursEvent - Start hours event; Modbus HR1199Write
PIV2709Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[4].MinsEvent - Start minutes event; Modbus HR1200Write
PIV2710Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[4].ModeEvent - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1201Write
PIV2711Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[5].HoursEvent - Start hours event; Modbus HR1202Write
PIV2712Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[5].MinsEvent - Start minutes event; Modbus HR1203Write
PIV2713Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[5].ModeEvent - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1204Write
PIV2714Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[6].HoursEvent - Start hours event; Modbus HR1205Write
PIV2715Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[6].MinsEvent - Start minutes event; Modbus HR1206Write
PIV2716Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[6].ModeEvent - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1207Write
PIV2717Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[7].HoursEvent - Start hours event; Modbus HR1208Write
PIV2718Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[7].MinsEvent - Start minutes event; Modbus HR1209Write
PIV2719Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[7].ModeEvent - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1210Write
PIV2720Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[8].HoursEvent - Start hours event; Modbus HR1211Write
PIV2721Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[8].MinsEvent - Start minutes event; Modbus HR1212Write
PIV2722Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[8].ModeEvent - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1213Write
PIV2723Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[9].HoursEvent - Start hours event; Modbus HR1214Write
PIV2724Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[9].MinsEvent - Start minutes event; Modbus HR1215Write
PIV2725Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[9].ModeEvent - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1216Write
PIV2726Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SaveDataModbus HR1217Write
IV2727Scheduler_OnOffUnit.FB_SchedulerMskMng_1.CopyTo_Prg32-bit (2 Modbus registers); Modbus HR1218Write
PIV2728Scheduler_OnOffUnit.FB_SchedulerMskMng_1.En_PrgCopyModbus HR1220Write
PIV2729Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[0]Monday program; Modbus HR1221Write
PIV2730Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[1]Tuesday program; Modbus HR1222Write
PIV2731Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[2]Wednesday program; Modbus HR1223Write
PIV2732Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[3]Thursday program; Modbus HR1224Write
PIV2733Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[4]Friday program; Modbus HR1225Write
PIV2734Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[5]Saturday program; Modbus HR1226Write
PIV2735Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[6]Sunday program; Modbus HR1227Write
PIV2736Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SaveData_DaysPrgModbus HR1228Write
PIV2737Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[0].StartDayVacation period - Start day; Modbus HR1229Write
PIV2738Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[0].StartMonthVacation period - Start month; Modbus HR1230Write
PIV2739Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[0].EndDayVacation period - End day; Modbus HR1231Write
PIV2740Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[0].EndMonthVacation period - End month; Modbus HR1232Write
PIV2741Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[0].ModeVacation period - Mode; Modbus HR1233Write
PIV2742Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[1].StartDayVacation period - Start day; Modbus HR1234Write
PIV2743Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[1].StartMonthVacation period - Start month; Modbus HR1235Write
PIV2744Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[1].EndDayVacation period - End day; Modbus HR1236Write
PIV2745Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[1].EndMonthVacation period - End month; Modbus HR1237Write
PIV2746Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[1].ModeVacation period - Mode; Modbus HR1238Write
PIV2747Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[2].StartDayVacation period - Start day; Modbus HR1239Write
PIV2748Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[2].StartMonthVacation period - Start month; Modbus HR1240Write
PIV2749Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[2].EndDayVacation period - End day; Modbus HR1241Write
PIV2750Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[2].EndMonthVacation period - End month; Modbus HR1242Write
PIV2751Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[2].ModeVacation period - Mode; Modbus HR1243Write
PIV2752Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SaveData_VacationsPrgModbus HR1244Write
PIV2753Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[0].DaySpecial day - Day; Modbus HR1245Write
PIV2754Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[0].MonthSpecial day - Month; Modbus HR1246Write
PIV2755Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[0].ModeSpecial day - Mode; Modbus HR1247Write
PIV2756Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[1].DaySpecial day - Day; Modbus HR1248Write
PIV2757Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[1].MonthSpecial day - Month; Modbus HR1249Write
PIV2758Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[1].ModeSpecial day - Mode; Modbus HR1250Write
PIV2759Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[2].DaySpecial day - Day; Modbus HR1251Write
PIV2760Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[2].MonthSpecial day - Month; Modbus HR1252Write
PIV2761Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[2].ModeSpecial day - Mode; Modbus HR1253Write
PIV2762Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[3].DaySpecial day - Day; Modbus HR1254Write
PIV2763Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[3].MonthSpecial day - Month; Modbus HR1255Write
PIV2764Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[3].ModeSpecial day - Mode; Modbus HR1256Write
PIV2765Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[4].DaySpecial day - Day; Modbus HR1257Write
PIV2766Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[4].MonthSpecial day - Month; Modbus HR1258Write
PIV2767Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[4].ModeSpecial day - Mode; Modbus HR1259Write
PIV2768Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[5].DaySpecial day - Day; Modbus HR1260Write
PIV2769Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[5].MonthSpecial day - Month; Modbus HR1261Write
PIV2770Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[5].ModeSpecial day - Mode; Modbus HR1262Write
PIV2771Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[6].DaySpecial day - Day; Modbus HR1263Write
PIV2772Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[6].MonthSpecial day - Month; Modbus HR1264Write
PIV2773Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[6].ModeSpecial day - Mode; Modbus HR1265Write
PIV2774Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[7].DaySpecial day - Day; Modbus HR1266Write
PIV2775Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[7].MonthSpecial day - Month; Modbus HR1267Write
PIV2776Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[7].ModeSpecial day - Mode; Modbus HR1268Write
PIV2777Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[8].DaySpecial day - Day; Modbus HR1269Write
PIV2778Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[8].MonthSpecial day - Month; Modbus HR1270Write
PIV2779Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[8].ModeSpecial day - Mode; Modbus HR1271Write
PIV2780Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[9].DaySpecial day - Day; Modbus HR1272Write
PIV2781Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[9].MonthSpecial day - Month; Modbus HR1273Write
PIV2782Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[9].ModeSpecial day - Mode; Modbus HR1274Write
PIV2783Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[10].DaySpecial day - Day; Modbus HR1275Write
PIV2784Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[10].MonthSpecial day - Month; Modbus HR1276Write
PIV2785Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[10].ModeSpecial day - Mode; Modbus HR1277Write
PIV2786Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[11].DaySpecial day - Day; Modbus HR1278Write
PIV2787Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[11].MonthSpecial day - Month; Modbus HR1279Write
PIV2788Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[11].ModeSpecial day - Mode; Modbus HR1280Write
PIV2789Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[12].DaySpecial day - Day; Modbus HR1281Write
PIV2790Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[12].MonthSpecial day - Month; Modbus HR1282Write
PIV2791Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[12].ModeSpecial day - Mode; Modbus HR1283Write
PIV2792Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[13].DaySpecial day - Day; Modbus HR1284Write
PIV2793Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[13].MonthSpecial day - Month; Modbus HR1285Write
PIV2794Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[13].ModeSpecial day - Mode; Modbus HR1286Write
PIV2795Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[14].DaySpecial day - Day; Modbus HR1287Write
PIV2796Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[14].MonthSpecial day - Month; Modbus HR1288Write
PIV2797Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[14].ModeSpecial day - Mode; Modbus HR1289Write
PIV2798Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SaveData_SpecDaysModbus HR1290Write
PIV2799Scheduler_OnOffUnit.PartyMode_DTParty mode duration; Modbus HR1291Write
PIV2800FanTypFans type (0: On/Off; 1: 3 speeds; 2: Modulating; 3: ...; Modbus HR1292Write
PIV2801HeatExchgTypHeating exchanger type; Modbus HR1293Write
PIV2802HumTypHumidifier type (0:None;1:Isothermal;2:Adiabatic;3:Humisonic;4:Humifog; 5:HumiSteam); Modbus HR1294Write
PIV2803IEC_TypIEC type (0: None; 1: OnOff; 2: Modulating; 3: Humisonic); Modbus HR1295Write
PIV2804PreHeatCoil_TypPreHeating coil type; Modbus HR1296Write
PIV2805MainCoil_TypMain coil type; Modbus HR1297Write
PIV2806ReHeatCoil_TypPostHeating coil type; Modbus HR1298Write
PIV2807FreshAirDampTypFresh air damper type (0: On/Off; 1: Modulating); Modbus HR1299Write
PIV2808ExhAirDampTypExhaust air damper type (0: On/Off; 1: Modulating); Modbus HR1300Write
PIV2809MixingAirDampTypMixing air damper type (0: On/Off; 1: Modulating); Modbus HR1301Write
PIV2810SupplyAirDampTypSupply air damper type (0: On/Off; 1: Modulating); Modbus HR1302Write
PIV2811RetAirDampTypReturn air damper type (0: On/Off; 1: Modulating); Modbus HR1303Write
PIV2812BypassDampTypBypass damper type (0: On/Off; 1: Modulating); Modbus HR1304Write
PIV2813Filters_CfgFilters configuration; Modbus HR1305Write
PIV2814HEPA_Filt_CfgHEPA Filter configuration (0: None; 1: Filt 1; Filt 1 ...; Modbus HR1306Write
PIV2815RegTypRegulation type (0: Supply only; 1:Return only; 2: Room only; ...; Modbus HR1307Write
AV2816Regulation.SetP_Offs_KpRegulation set point offset: proportional gain; Modbus HR1308Write
PIV2817Regulation.SetP_Offs_TiRegulation set point offset: integral time; Modbus HR1309Write
PIV2818UnitHumDehumMode_CfgUnit humidification/dehumidification mode configuration (0: Fixed by season; 1: Automatic ...; Modbus HR1310Write
PIV2819UnitCoolHeatMode_CfgUnit cooling heating mode configuration; Modbus HR1311Write
AV2820Regulation.SummerExtTempThrshSummer external temperature threshold; Modbus HR1312Write
AV2821Regulation.WinterExtTempThrshWinter external temperature threshold; Modbus HR1313Write
AV2822Coil_SummerThrshSummer coil water temperature threshold; Modbus HR1314Write
AV2823Coil_WinterThrshWinter coil water temperature threshold; Modbus HR1315Write
PIV2824Coil_WaterT_OutOfRange_DTMain coil: water temperature out of range warning delay time; Modbus HR1316Write
PIV2825Coil_WaterT_CfgCoil water temperature: action configuration; Modbus HR1317Write
PIV2826HumDehum_CtrlPrbHumidification/Dehumidification: Control probe (0: Supply; 1: Return; 2: Room); Modbus HR1318Write
PIV2827HumDehum_CtrlTypHumidification/Dehumidification: Control type (0: Relative; 1: Absolute); Modbus HR1319Write
PIV2828Dehum_RegTypDehumidification: Regulation type (0: DewPoint; 1: Request); Modbus HR1320Write
AV2829HumDehum_RegBandHumidification/Dehumidification: Regulation band; Modbus HR1321Write
PIV2830HumDehum_RegChgDTHumidification/Dehumidification: Regulation change delay time; Modbus HR1322Write
AV2831Regulation.FC_DeltaT_ActFreecooling activation delta; Modbus HR1323Write
AV2832Regulation.FH_DeltaT_ActFreeheating activation delta; Modbus HR1324Write
AV2833FC_PID_Params.KpFree cooling PID parameters - Proportional gain; Modbus HR1325Write
PIV2834FC_PID_Params.TiFree cooling PID parameters - Integral time; Modbus HR1326Write
AV2835FH_PID_Params.KpFree heating PID parameters - Proportional gain; Modbus HR1327Write
PIV2836FH_PID_Params.TiFree heating PID parameters - Integral time; Modbus HR1328Write
AV2837StateMachine.LowWarmUpThrshExtTempLow external temperature threshold for the activation of warm up procedure; Modbus HR1329Write
PIV2838StateMachine.StartUpFanActDTSettable delay between return and supply fan activation (seconds). To ...; Modbus HR1330Write
PIV2839StateMachine.WarmUpDTWarm up delay time; Modbus HR1331Write
PIV2840StateMachine.WarmUpFanActDTWarm up fan activation delay time; Modbus HR1332Write
PIV2841SupplyFanWarmUpReq_3SpeedFor mask usage; Modbus HR1333Write
AV2842SupplyFanWarmUpReqSupply fan request for automatic warm up; Modbus HR1334Write
PIV2843SupplyFanWarmUpReq_OnOffFor mask usage; Modbus HR1335Write
PIV2844RetFanWarmUpReq_3SpeedFor mask usage; Modbus HR1336Write
AV2845RetFanWarmUpReqReturn fan request for automatic warm up; Modbus HR1337Write
PIV2846RetFanWarmUpReq_OnOffFor mask usage; Modbus HR1338Write
AV2847PreHeatCoilWarmUpReqPreHeating coil warm up request; Modbus HR1339Write
AV2848MainCoilWarmUpReqMain coil warm up request; Modbus HR1340Write
AV2849ReHeatCoilWarmUpReqPostHeating coil warm up request; Modbus HR1341Write
AV2850ByPassDampWarmUpReqBypass damper warm up request; Modbus HR1342Write
AV2851ThermWhlWarmUpReqThermal wheel warm up request; Modbus HR1343Write
PIV2852BypassDampWarmUpReq_OnOffFor mask usage; Modbus HR1344Write
PIV2853SupplyFanSwitchOnReq_3SpeedFor mask usage; Modbus HR1345Write
AV2854SupplyFanSwitchOnReqSupply fan request for automatic switch on when warm up ...; Modbus HR1346Write
PIV2855SupplyFanSwitchOnReq_OnOffFor mask usage; Modbus HR1347Write
PIV2856AFreezeTypAntifreeze type (0: NONE; 1: Ext.Temp.; 2: AFreeze Temp.; 3: DigitalInput); Modbus HR1348Write
AV2857Antifreeze.AfreezeTempThrshAntifreeze temperature threshold; Modbus HR1349Write
AV2858Antifreeze.AFreezeEndingDeltaAntifreeze ending delta; Modbus HR1350Write
PIV2859Antifreeze.AFreezeWarnDTAnti freeze warning delay time; Modbus HR1351Write
PIV2860Antifreeze.Al_AFreezeDTAntifreeze alarm delay time; Modbus HR1352Write
AV2861Antifreeze.PrevAFreezeTempThrshPrevent antifreeze threshold; Modbus HR1353Write
AV2862LowSupplyTempThrshLow supply temperature threshold; Modbus HR1354Write
PIV2863LowTempAlrmDT_StartUpLow supply temperature alarm delay time at start up; Modbus HR1355Write
PIV2864LowTempAlrmDT_RunLow supply temperature alarm delay time at unit in run mode; Modbus HR1356Write
AV2865HighSupplyTempThrshHigh supply temperature threshold; Modbus HR1357Write
PIV2866HighTempAlrmDT_StartUpHigh supply temperature alarm delay time at start up; Modbus HR1358Write
PIV2867HighTempAlrmDT_RunHigh supply temperature alarm delay time at unit in run mode; Modbus HR1359Write
AV2868LowHighSupplyT_KpLow supply temp: proportional part; Modbus HR1360Write
PIV2869LowHighSupplyT_TiLow supply temp: integral time; Modbus HR1361Write
AV2870RegPrbErrFreshAirDampReqFresh air damper request in case of regulation probe error: modulating; Modbus HR1362Write
PIV2871RegPrbErrFreshAirDampReq_OnOffFresh air damper request in case of regulation probe error: on/off; Modbus HR1363Write
AV2872RegPrbErrByPassDampReqBypass damper request in case of regulation probe error: modulating; Modbus HR1364Write
AV2873RegPrbErrThermWhlReqThermal wheel request in case of regulation probe error: modulating; Modbus HR1365Write
PIV2874RegPrbErrByPassDampReq_OnOffBypass damper request in case of regulation probe error: on/off; Modbus HR1366Write
AV2875RegPrbErrMixDampReqMixing damper request in case of regulation probe error; Modbus HR1367Write
PIV2876RegPrbErrMixDampReq_OnOffMixing damper request in case of regulation probe error; Modbus HR1368Write
AV2877RegPrbErrExhDampReqExhaust damper request in case of regulation probe error; Modbus HR1369Write
PIV2878RegPrbErrExhDampReq_OnOffExhaust damper request in case of regulation probe error; Modbus HR1370Write
AV2879RegPrbErrSupplyAirDampReqSupply damper request in case of regulation probe error; Modbus HR1371Write
PIV2880RegPrbErrSupplyAirDampReq_OnOffSupply damper request in case of regulation probe error; Modbus HR1372Write
AV2881RegPrbErrRetAirDampReqReturn damper request in case of regulation probe error; Modbus HR1373Write
PIV2882RegPrbErrRetAirDampReq_OnOffReturn damper request in case of regulation probe error; Modbus HR1374Write
AV2883RegPrbErrMainCoilReqMain coil request in case of regulation probe error; Modbus HR1375Write
AV2884RegPrbErrPreHeatCoilReqPreHeating coil request in case of regulation probe error; Modbus HR1376Write
AV2885RegPrbErrReHeatCoilReqPostHeating coil request in case of regulation probe error; Modbus HR1377Write
PIV2886RegPrbErrSupplyFanReq_3SpeedSupply fan speed request in case of regulation probe error; Modbus HR1378Write
AV2887RegPrbErrSupplyFanReqSupply fan speed request in case of regulation probe error; Modbus HR1379Write
PIV2888RegPrbErrSupplyFanReq_OnOffSupply fan speed request in case of regulation probe error; Modbus HR1380Write
PIV2889RegPrbErrRetFanReq_3SpeedSupply fan speed request in case of regulation probe error; Modbus HR1381Write
AV2890RegPrbErrRetFanReqReturn fan speed request in case of regulation probe error; Modbus HR1382Write
PIV2891RegPrbErrRetFanReq_OnOffSupply fan speed request in case of regulation probe error; Modbus HR1383Write
AV2892RegPrbErrCompReqCompressor request in case of regulation probe error: BLDC; Modbus HR1384Write
PIV2893RegPrbErrCompReq_OnOffCompressor request in case of regulation probe error: On/off; Modbus HR1385Write
AV2894RegPrbErrHumReqHumidification request in case of regulation probe error; Modbus HR1386Write
AV2895RegPrbErr_IECReqIEC: request in case of regulation probe error; Modbus HR1387Write
PIV2897AuxRegTypAuxiliary regulation type; Modbus HR1389Write
PIV2898BMS_Offline_MngTypBMS Offline alarm management (0: Disabled; 1: Only Warning; 2: ...; Modbus HR1390Write
PIV2899BMS_Offline_Alrm_TimeoutBMS Offline alarm timeout [s]; Modbus HR1391Write
PIV2900MaskMng.ValA_Selection_PGDXpGDx: Main variable selection; Modbus HR1392Write
PIV2901MaskMng.ValB_Selection_PGDXpGDx: Second variable selection; Modbus HR1393Write
PIV2902GeneralMng.SetWipeMemSet wipe memory; Modbus HR1394Write
PIV2903WrkHrs_Unit.WrkHrs_ThrshUnit - Working hours threshold (1000hrs); Modbus HR1395Write
PIV2904WrkHrs_Unit.WrkHrs_ResUnit - Working hours reset; Modbus HR1396Write
PIV2905WrkHrs_SupplyFan.WrkHrs_ThrshSupply Fan - Working hours threshold (1000hrs); Modbus HR1397Write
PIV2906WrkHrs_SupplyFan.WrkHrs_ResSupply Fan - Working hours reset; Modbus HR1398Write
PIV2907WrkHrs_ReturnFan.WrkHrs_ThrshReturn Fan - Working hours threshold (1000hrs); Modbus HR1399Write
PIV2908WrkHrs_ReturnFan.WrkHrs_ResReturn Fan - Working hours reset; Modbus HR1400Write
PIV2909WrkHrs_DirtyFilt.WrkHrs_ThrshDirty filters - Working hours threshold (1000hrs); Modbus HR1401Write
PIV2910WrkHrs_DirtyFilt.WrkHrs_ResDirty filters - Working hours reset; Modbus HR1402Write
PIV2911WrkHrs_ThrmlWheel.WrkHrs_ThrshThermal wheel - Working hours threshold (1000hrs); Modbus HR1403Write
PIV2912WrkHrs_ThrmlWheel.WrkHrs_ResThermal wheel - Working hours reset; Modbus HR1404Write
PIV2913WrkHrs_Comp.WrkHrs_ThrshCompressor - Working hours threshold (1000hrs); Modbus HR1405Write
PIV2914WrkHrs_Comp.WrkHrs_ResCompressor - Working hours reset; Modbus HR1406Write
PIV2915WrkHrs_IEC.WrkHrs_ThrshIEC - Working hours threshold (1000hrs); Modbus HR1407Write
PIV2916WrkHrs_IEC.WrkHrs_ResIEC - Working hours reset; Modbus HR1408Write
PIV2917WrkHrs_Humidifier.WrkHrs_ThrshHumidifier - Working hours threshold (1000hrs); Modbus HR1409Write
PIV2918WrkHrs_Humidifier.WrkHrs_ResHumidifier - Working hours reset; Modbus HR1410Write
PIV2919WrkHrs_AuxDout.WrkHrs_ThrshAuxiliary digital output - Working hours threshold (1000hrs); Modbus HR1411Write
PIV2920WrkHrs_AuxDout.WrkHrs_ResAuxiliary digital output - Working hours reset; Modbus HR1412Write
PIV2921WrkHrs_AuxAout.WrkHrs_ThrshAuxiliary analogue output - Working hours threshold (1000hrs); Modbus HR1413Write
PIV2922WrkHrs_AuxAout.WrkHrs_ResAuxiliary analogue output - Working hours reset; Modbus HR1414Write
PIV2923WrkHrs_MainCoilPmp1.WrkHrs_ThrshMain coil pump 1 - Working hours threshold (1000hrs); Modbus HR1415Write
PIV2924WrkHrs_MainCoilPmp1.WrkHrs_ResMain coil pump 1 - Working hours reset; Modbus HR1416Write
PIV2925WrkHrs_MainCoilPmp2.WrkHrs_ThrshMain coil pump 2 - Working hours threshold (1000hrs); Modbus HR1417Write
PIV2926WrkHrs_MainCoilPmp2.WrkHrs_ResMain coil pump 2 - Working hours reset; Modbus HR1418Write
PIV2927WrkHrs_MainCoilAout.WrkHrs_ThrshMain coil analog output - Working hours threshold (1000hrs); Modbus HR1419Write
PIV2928WrkHrs_MainCoilAout.WrkHrs_ResMain coil analog output - Working hours reset; Modbus HR1420Write
PIV2929WrkHrs_MainCoilStep1.WrkHrs_ThrshMain coil step 1 - Working hours threshold (1000hrs); Modbus HR1421Write
PIV2930WrkHrs_MainCoilStep1.WrkHrs_ResMain coil step 1 - Working hours reset; Modbus HR1422Write
PIV2931WrkHrs_MainCoilStep2.WrkHrs_ThrshMain coil step 2 - Working hours threshold (1000hrs); Modbus HR1423Write
PIV2932WrkHrs_MainCoilStep2.WrkHrs_ResMain coil step 2 - Working hours reset; Modbus HR1424Write
PIV2933WrkHrs_MainCoilStep3.WrkHrs_ThrshMain coil step 3 - Working hours threshold (1000hrs); Modbus HR1425Write
PIV2934WrkHrs_MainCoilStep3.WrkHrs_ResMain coil step 3 - Working hours reset; Modbus HR1426Write
PIV2935WrkHrs_MainCoilStep4.WrkHrs_ThrshMain coil step 4 - Working hours threshold (1000hrs); Modbus HR1427Write
PIV2936WrkHrs_MainCoilStep4.WrkHrs_ResMain coil step 4 - Working hours reset; Modbus HR1428Write
PIV2937WrkHrs_PreHeatCoilPmp1.WrkHrs_ThrshPre-heat coil pump 1 - Working hours threshold (1000hrs); Modbus HR1429Write
PIV2938WrkHrs_PreHeatCoilPmp1.WrkHrs_ResPre-heat coil pump 1 - Working hours reset; Modbus HR1430Write
PIV2939WrkHrs_PreHeatCoilPmp2.WrkHrs_ThrshPre-heat coil pump 2 - Working hours threshold (1000hrs); Modbus HR1431Write
PIV2940WrkHrs_PreHeatCoilPmp2.WrkHrs_ResPre-heat coil pump 2 - Working hours reset; Modbus HR1432Write
PIV2941WrkHrs_PreHeatCoilAout.WrkHrs_ThrshPre-heat coil analog output - Working hours threshold (1000hrs); Modbus HR1433Write
PIV2942WrkHrs_PreHeatCoilAout.WrkHrs_ResPre-heat coil analog output - Working hours reset; Modbus HR1434Write
PIV2943WrkHrs_PreHeatCoilStep1.WrkHrs_ThrshPre-heat coil step 1 - Working hours threshold (1000hrs); Modbus HR1435Write
PIV2944WrkHrs_PreHeatCoilStep1.WrkHrs_ResPre-heat coil step 1 - Working hours reset; Modbus HR1436Write
PIV2945WrkHrs_PreHeatCoilStep2.WrkHrs_ThrshPre-heat coil step 2 - Working hours threshold (1000hrs); Modbus HR1437Write
PIV2946WrkHrs_PreHeatCoilStep2.WrkHrs_ResPre-heat coil step 2 - Working hours reset; Modbus HR1438Write
PIV2947WrkHrs_PreHeatCoilStep3.WrkHrs_ThrshPre-heat coil step 3 - Working hours threshold (1000hrs); Modbus HR1439Write
PIV2948WrkHrs_PreHeatCoilStep3.WrkHrs_ResPre-heat coil step 3 - Working hours reset; Modbus HR1440Write
PIV2949WrkHrs_PreHeatCoilStep4.WrkHrs_ThrshPre-heat coil step 4 - Working hours threshold (1000hrs); Modbus HR1441Write
PIV2950WrkHrs_PreHeatCoilStep4.WrkHrs_ResPre-heat coil step 4 - Working hours reset; Modbus HR1442Write
PIV2951WrkHrs_ReHeatCoilPmp1.WrkHrs_ThrshRe-heat coil pump 1 - Working hours threshold (1000hrs); Modbus HR1443Write
PIV2952WrkHrs_ReHeatCoilPmp1.WrkHrs_ResRe-heat coil pump 1 - Working hours reset; Modbus HR1444Write
PIV2953WrkHrs_ReHeatCoilPmp2.WrkHrs_ThrshRe-heat coil pump 2 - Working hours threshold (1000hrs); Modbus HR1445Write
PIV2954WrkHrs_ReHeatCoilPmp2.WrkHrs_ResRe-heat coil pump 2 - Working hours reset; Modbus HR1446Write
PIV2955WrkHrs_ReHeatCoilAout.WrkHrs_ThrshRe-heat coil analog output - Working hours threshold (1000hrs); Modbus HR1447Write
PIV2956WrkHrs_ReHeatCoilAout.WrkHrs_ResRe-heat coil analog output - Working hours reset; Modbus HR1448Write
PIV2957WrkHrs_ReHeatCoilStep1.WrkHrs_ThrshRe-heat coil step 1 - Working hours threshold (1000hrs); Modbus HR1449Write
PIV2958WrkHrs_ReHeatCoilStep1.WrkHrs_ResRe-heat coil step 1 - Working hours reset; Modbus HR1450Write
PIV2959WrkHrs_ReHeatCoilStep2.WrkHrs_ThrshRe-heat coil step 2 - Working hours threshold (1000hrs); Modbus HR1451Write
PIV2960WrkHrs_ReHeatCoilStep2.WrkHrs_ResRe-heat coil step 2 - Working hours reset; Modbus HR1452Write
PIV2961WrkHrs_ReHeatCoilStep3.WrkHrs_ThrshRe-heat coil step 3 - Working hours threshold (1000hrs); Modbus HR1453Write
PIV2962WrkHrs_ReHeatCoilStep3.WrkHrs_ResRe-heat coil step 3 - Working hours reset; Modbus HR1454Write
PIV2963WrkHrs_ReHeatCoilStep4.WrkHrs_ThrshRe-heat coil step 4 - Working hours threshold (1000hrs); Modbus HR1455Write
PIV2964WrkHrs_ReHeatCoilStep4.WrkHrs_ResRe-heat coil step 4 - Working hours reset; Modbus HR1456Write
PIV2965WorkingHrs.WrkHrs_ResTotCntReset total working hours counter of all devices; Modbus HR1457Write
AV2966Regulation.BypassDampHeatRecovDelta_CoolHeat recovery delta for bypass damp in cooling mode; Modbus HR1458Write
AV2967Regulation.BypassDampHeatRecovDelta_HeatHeat recovery delta for bypass damp in heating mode; Modbus HR1459Write
AV2968HeatExchg_PID_Params.KpHeat exchanger PID parameters - Proportional gain; Modbus HR1460Write
PIV2969HeatExchg_PID_Params.TiHeat exchanger PID parameters - Integral time; Modbus HR1461Write
AV2970Defrost.BypassDamp_MinOpThrshBypass damper: minimum opening threshold; Modbus HR1462Write
AV2971Defrost.BypassDamp_MaxOpThrshBypass damper: maximum opening threshold; Modbus HR1463Write
PIV2972Defrost.MinT_BetweenDfr_HeatExchgMinimum time between heat exchanger defrost; 32-bit (2 Modbus registers); Modbus HR1464Write
PIV2973Defrost.MaxDfrDuration_HeatExchgMaximum defrost heat exchanger duration; 32-bit (2 Modbus registers); Modbus HR1466Write
AV2974Defrost.ExhTempThrshExhaust temperature threshold for defrost; Modbus HR1468Write
AV2975HeatExchanger.DeltaHeatExchgEfficiencyStratification correction factor of the room temperature; Modbus HR1469Write
AV2976Fans.AirP_PrbErr_RetFanReqReturn fan request in case of air pressure probe error; Modbus HR1470Write
AV2977Fans_regulation.RetFanOffsetReqReturn fan offset request; Modbus HR1471Write
PIV2978RetFanRampUpTTime in [s]for a positive change for return fan; Modbus HR1472Write
PIV2979RetFanRampDwnTTime in [s] for a negative change of set value ...; Modbus HR1473Write
IV2980RetFan_EmergencySet_rpmReturn Fan ebmpapst - speed in emergency in rpm; 32-bit ...; Modbus HR1474Write
PIV2981RetFan_EmergLagTTime in ms before entering in emergency mode for Ebmpapst ...; Modbus HR1476Write
PIV2985RetFan_SerDevCfg_TimeoutReturn Fan - Serial interface settings - Frame timeout (ms); ...; 32-bit; Modbus HR1481Write
PIV2986RetFan_SerDevCfg_CmdDTReturn Fan - Serial interface settings - Command delay time ...; 32-bit; Modbus HR1483Write
PIV2989ZiehlAbegg_ReturnFan.SerialInterface_ZA_1.SerDevCfg.DevAddrZA1 Return - Serial interface parameters - Fan Network address; ...; 32-bit; Modbus HR1487Write
PIV2992FanRegTypFan regulation type (0: Static pressure; 1: Air flow; 2: ...; Modbus HR1491Write
AV2993FansAirQuality_PID_Params.KpAir Quality - Fans PID parameters - Proportional gain; Modbus HR1492Write
PIV2994FansAirQuality_PID_Params.TiAir Quality - Fans PID parameters - Integral time; Modbus HR1493Write
PIV2995AirFlwSwTypAir flow switch check type: 0=none; 1=common; 2=supply onlu; 3=supply+return; Modbus HR1494Write
PIV2996AirFlw_ChkTypAir flow check type; Modbus HR1495Write
PIV2997StateMachine.RetryNoAirFlwAlrmNumber of retry after return or supply air flow switch ...; Modbus HR1496Write
PIV2998AirFlwSwDTTimeout for air flow switch detection (seconds); Modbus HR1497Write
PIV2999Fans.AirFlwSwRunAlrmDTAir flow switch alarm delay time in running mode (s); Modbus HR1498Write
AV3000AirFlw_ChkPThrshAir flow check pressure threshold; Modbus HR1499Write
PIV3001StateMachine.FanPostVentilationTFan post ventilation time; Modbus HR1500Write
PIV3002NightMinVent_StartHourNight minimum ventilation: starting hour; Modbus HR1501Write
PIV3003NightMinVent_StartMinNight minimum ventilation: starting minutes; Modbus HR1502Write
PIV3004NightMinVent_EndHourNight minimum ventilation: ending hour; Modbus HR1503Write
PIV3005NightMinVent_EndMinNight minimum ventilation: ending minutes; Modbus HR1504Write
AV3006Fans_regulation.NightMinVent_MaxReqNight minimum ventilation request; Modbus HR1505Write
AV3007Fans_regulation.AirFlw_K_FactorFan K factor for air flow calculations; Modbus HR1506Write
AV3008Fans_regulation.FanFixSpeed_ReqFan fixed speed request; Modbus HR1507Write
PIV3009Fans_regulation.FansThreeSpeedFixSpeedReq(0 = SPEED1; 1= SPEED2; 2= SPEED 3) Three speed ...; Modbus HR1508Write
AV3010FansThreeSpeed1Three speed fan limit 1; Modbus HR1509Write
AV3011FansThreeSpeed2Three speed fan limit 2; Modbus HR1510Write
AV3012FansThreeSpeed3Three speed fan limit 3; Modbus HR1511Write
AV3013Fans_regulation.AirQualityFanMinReqFan air quality minimum request; Modbus HR1512Write
AV3014FanTempReg_PID_Params.KpFan temperature regulation PID parameters - Proportional gain; Modbus HR1513Write
PIV3015FanTempReg_PID_Params.TiFan temperature regulation PID parameters - Integral time; Modbus HR1514Write
AV3016Fans_regulation.SupplyFan_PID_Params.KpProportional gain; Modbus HR1515Write
PIV3017Fans_regulation.SupplyFan_PID_Params.TiIntegral time; Modbus HR1516Write
AV3018Fans_regulation.SupplyFan_PID_Params.DeadBandDead band; Modbus HR1517Write
AV3019Fans_regulation.SupplyAirFlwDeadbandSupply air flow deadband; Modbus HR1518Write
PIV3020CompMinOnTCompressor minumum On time; Modbus HR1519Write
PIV3021CompMinOffTCompressor minumum Off time; Modbus HR1520Write
PIV3022CompMinOnOnSameTCompressor minumum time between two start; Modbus HR1521Write
PIV3023AlarmsMng.LowSuctP_Sw_AlrmStartUpDTLow suction pressure alarm delay time at start up; Modbus HR1522Write
PIV3024AlarmsMng.LowSuctP_Sw_AlrmRunDTLow suction pressure alarm delay time at running time; Modbus HR1523Write
PIV3025LowSuctP_Alrm_CntMaxLow suction pressure alarm: counter max; Modbus HR1524Write
PIV3026LowSuctP_Alrm_TimeValueLow suction pressure alarm: time value; Modbus HR1525Write
AV3027Defrost.DfrStartThrshEvaporator defrost start threshold; Modbus HR1526Write
AV3028Defrost.DfrEndThrshEvaporator defrost end threshold; Modbus HR1527Write
AV3029Defrost.DfrDeltaBypassDampDefrost delta bypass damper; Modbus HR1528Write
PIV3030Defrost.DfrStartDTEvaporator defrost start delay time; Modbus HR1529Write
PIV3031Defrost.DfrT_StopCompDefrost time for stop compressor; Modbus HR1530Write
PIV3032DfrMinTDefrost minimum time; Modbus HR1531Write
PIV3033DfrMaxTDefrost maximum time; Modbus HR1532Write
PIV3034DfrIntervalTTime between two defrost; Modbus HR1533Write
PIV3035DfrDripTDefrost dripping time; Modbus HR1534Write
PIV3036DfrPostDripTPost-dripping time [s]; Modbus HR1535Write
AV3037RevVlvSpeedRpsBLDC minimum speed in defrost; Modbus HR1536Write
AV3038RevVlvDeltaPReverse valve delta P; Modbus HR1537Write
PIV3039Defrost.DfrBeforeChgOverDTDefrost: delay time before change over; Modbus HR1538Write
PIV3040Defrost.DfrAfterChgOverDTDefrost: delay time after change over; Modbus HR1539Write
PIV3041FansDfrReq_3SpeedFans request during evaporator defrost; Modbus HR1540Write
AV3042FansDfrReqFans request during evaporator defrost; Modbus HR1541Write
PIV3043FansDfrReq_OnOffFans request during evaporator defrost; Modbus HR1542Write
PIV3044FansDfrDrippingReq_3SpeedFans request during evaporator defrost: dripping; Modbus HR1543Write
AV3045FansDfrDrippingReqFans request during evaporator defrost: dripping; Modbus HR1544Write
PIV3046FansDfrDrippingReq_OnOffFans request during evaporator defrost: dripping; Modbus HR1545Write
PIV3047FansDfrPostDrippingReq_3SpeedFans request during evaporator defrost: post dripping; Modbus HR1546Write
AV3048FansDfrPostDrippingReqFans request during evaporator defrost: post dripping; Modbus HR1547Write
PIV3049FansDfrPostDrippingReq_OnOffFans request during evaporator defrost: post dripping; Modbus HR1548Write
AV3050HumDehumReg.Hum_PID.KpHumidification PID parameters - Proportional gain; Modbus HR1549Write
PIV3051HumDehumReg.Hum_PID.TiHumidification PID parameters - Integral time; Modbus HR1550Write
PIV3052HumDehumReg.Hum_PID.TdHumidification PID parameters - Derivative time; Modbus HR1551Write
AV3053Hum_MaxLim_ThrshHumidifier: Max humidity threshold; Modbus HR1552Write
AV3054Hum_MaxLim_KpHumidifier: Max humidity proportional part; Modbus HR1553Write
PIV3055Hum_MaxLim_TiHumidifier: Max humidity integral time; Modbus HR1554Write
AV3056Hum_MinTemp_KpHumidifier: Min temperature proportional part (Only adiabatic hum); Modbus HR1555Write
PIV3057Hum_MinTemp_TiHumidifier: Min temperature integral time (Only adiabatic hum); Modbus HR1556Write
IV3058Humisonic.DevSettings_HUMS.WashingTimeSet.DTBetweenWashParameters for device configuration - Timings for washing operations - ...; Modbus HR1557Write
IV3059Humisonic.DevSettings_HUMS.WashingTimeSet.DTInactivWashParameters for device configuration - Timings for washing operations - ...; Modbus HR1558Write
IV3060Humisonic.DevSettings_HUMS.WashingTimeSet.WashTimeParameters for device configuration - Timings for washing operations - ...; Modbus HR1559Write
PIV3061AlarmsMng.DirtyFiltAlrmDTDelay time for dirty filter by DIN; 32-bit (2 Modbus registers); Modbus HR1560Write
AV3062HEPA_Filter_AlrmThrshHEPA filter alarm threshold; Modbus HR1562Write
AV3063Fans.AirP_PrbErr_SupplyFanReqSupply fan request in case of air pressure probe error; Modbus HR1563Write
AV3064AFreezeFansMinSpeedMinimum fan speed during antifreeze; Modbus HR1564Write
PIV3065SupplyFanRampUpTTime in [s]for a positive change for Supply fan; Modbus HR1565Write
PIV3066SupplyFanRampDwnTTime in [s] for a negative change of set value ...; Modbus HR1566Write
IV3067SupplyFan_EmergencySet_rpmFan speed in emergency in rpm; 32-bit (2 Modbus registers); Modbus HR1567Write
PIV3068SupplyFan_EmergLagTTime in ms before entering in emergency mode for Ebmpapst fan; Modbus HR1569Write
PIV3069Ebmpapst_SupplyFan.SerInterfaceSet_EBM_1.CfgProtocol.DevAddrEBM1 Supply - Serial interface settings - Network address for ...; 32-bit; Modbus HR1570Write
PIV3072SupplyFan_SerDevCfg_TimeoutSupply Fan - Serial interface settings - Frame timeout (ms); ...; 32-bit; Modbus HR1574Write
PIV3073SupplyFan_SerDevCfg_CmdDTSupply Fan - Serial interface settings - Command delay time ...; 32-bit; Modbus HR1576Write
PIV3076ZiehlAbegg_SupplyFan.SerialInterface_ZA_1.SerDevCfg.DevAddrZA1 Supply - Serial interface parameters - Fan Network address; ...; 32-bit; Modbus HR1580Write
PIV3079AuxReg1_Cfg.InputSelAuxiliary Regulation 1 - Input selection; Modbus HR1584Write
PIV3080AuxReg1_Cfg.OutputSelAuxiliary Regulation 1 - Output selection; Modbus HR1585Write
AV3081AuxReg1_Cfg.Modul_ErrorValueAuxiliary Regulation 1 - Modulating: Error value; Modbus HR1586Write
PIV3082AuxReg1_Cfg.EnableSelAuxiliary Regulation 1 - Enable selection; Modbus HR1587Write
PIV3083AuxReg1_Cfg.SetPSelAuxiliary Regulation 1 - Setpoint selection; Modbus HR1588Write
AV3084AuxReg1_Cfg.Modul_LowLimAuxiliary Regulation 1 - Modulating: Low limit; Modbus HR1589Write
AV3085AuxReg1_Cfg.DOut_DiffAuxiliary Regulation 1 - Dout: Differential; Modbus HR1590Write
AV3086AuxReg1_Cfg.Modul_HighLimAuxiliary Regulation 1 - Modulating: High limit; Modbus HR1591Write
AV3087AuxReg1_Cfg.Modul_KpAuxiliary Regulation 1 - Modulating: Kp; Modbus HR1592Write
PIV3088AuxReg1_Cfg.Modul_TiAuxiliary Regulation 1 - Modulating: Integral time; Modbus HR1593Write
PIV3089AuxReg1_Cfg.Modul_TdAuxiliary Regulation 1 - Modulating: Derivative time; Modbus HR1594Write
AV3090AuxReg1_Cfg.Modul_DeadBandAuxiliary Regulation 1 - Modulating: Dead Band; Modbus HR1595Write
AV3091AuxReg1_Cfg.Modul_ManModeValAuxiliary Regulation 1 - Modulating: Manual mode value; Modbus HR1596Write
PIV3092AuxReg2_Cfg.InputSelAuxiliary Regulation 2 - Input selection; Modbus HR1597Write
PIV3093AuxReg2_Cfg.OutputSelAuxiliary Regulation 2 - Output selection; Modbus HR1598Write
AV3094AuxReg2_Cfg.Modul_ErrorValueAuxiliary Regulation 2 - Modulating: Error value; Modbus HR1599Write
PIV3095AuxReg2_Cfg.EnableSelAuxiliary Regulation 2 - Enable selection; Modbus HR1600Write
PIV3096AuxReg2_Cfg.SetPSelAuxiliary Regulation 2 - Setpoint selection; Modbus HR1601Write
AV3097AuxReg2_Cfg.SetPAuxiliary Regulation 2 - Regulation setpoint; Modbus HR1602Write
AV3098AuxReg2_Cfg.Modul_LowLimAuxiliary Regulation 2 - Modulating: Low limit; Modbus HR1603Write
AV3099AuxReg2_Cfg.DOut_DiffAuxiliary Regulation 2 - Dout: Differential; Modbus HR1604Write
AV3100AuxReg2_Cfg.Modul_HighLimAuxiliary Regulation 2 - Modulating: High limit; Modbus HR1605Write
AV3101AuxReg2_Cfg.Modul_KpAuxiliary Regulation 2 - Modulating: Kp; Modbus HR1606Write
PIV3102AuxReg2_Cfg.Modul_TiAuxiliary Regulation 2 - Modulating: Integral time; Modbus HR1607Write
PIV3103AuxReg2_Cfg.Modul_TdAuxiliary Regulation 2 - Modulating: Derivative time; Modbus HR1608Write
AV3104AuxReg2_Cfg.Modul_DeadBandAuxiliary Regulation 2 - Modulating: Dead Band; Modbus HR1609Write
AV3105AuxReg2_Cfg.Modul_ManModeValAuxiliary Regulation 2 - Modulating: Manual mode value; Modbus HR1610Write
PIV3106AuxReg3_Cfg.InputSelAuxiliary Regulation 3 - Input selection; Modbus HR1611Write
PIV3107AuxReg3_Cfg.OutputSelAuxiliary Regulation 3 - Output selection; Modbus HR1612Write
AV3108AuxReg3_Cfg.Modul_ErrorValueAuxiliary Regulation 3 - Modulating: Error value; Modbus HR1613Write
PIV3109AuxReg3_Cfg.EnableSelAuxiliary Regulation 3 - Enable selection; Modbus HR1614Write
PIV3110AuxReg3_Cfg.SetPSelAuxiliary Regulation 3 - Setpoint selection; Modbus HR1615Write
AV3111AuxReg3_Cfg.SetPAuxiliary Regulation 3 - Regulation setpoint; Modbus HR1616Write
AV3112AuxReg3_Cfg.Modul_LowLimAuxiliary Regulation 3 - Modulating: Low limit; Modbus HR1617Write
AV3113AuxReg3_Cfg.DOut_DiffAuxiliary Regulation 3 - Dout: Differential; Modbus HR1618Write
AV3114AuxReg3_Cfg.Modul_HighLimAuxiliary Regulation 3 - Modulating: High limit; Modbus HR1619Write
AV3115AuxReg3_Cfg.Modul_KpAuxiliary Regulation 3 - Modulating: Kp; Modbus HR1620Write
PIV3116AuxReg3_Cfg.Modul_TiAuxiliary Regulation 3 - Modulating: Integral time; Modbus HR1621Write
PIV3117AuxReg3_Cfg.Modul_TdAuxiliary Regulation 3 - Modulating: Derivative time; Modbus HR1622Write
AV3118AuxReg3_Cfg.Modul_DeadBandAuxiliary Regulation 3 - Modulating: Dead Band; Modbus HR1623Write
AV3119AuxReg3_Cfg.Modul_ManModeValAuxiliary Regulation 3 - Modulating: Manual mode value; Modbus HR1624Write
PIV3120AuxReg4_Cfg.InputSelAuxiliary Regulation 4 - Input selection; Modbus HR1625Write
PIV3121AuxReg4_Cfg.OutputSelAuxiliary Regulation 4 - Output selection; Modbus HR1626Write
AV3122AuxReg4_Cfg.Modul_ErrorValueAuxiliary Regulation 4 - Modulating: Error value; Modbus HR1627Write
PIV3123AuxReg4_Cfg.EnableSelAuxiliary Regulation 4 - Enable selection; Modbus HR1628Write
PIV3124AuxReg4_Cfg.SetPSelAuxiliary Regulation 4 - Setpoint selection; Modbus HR1629Write
AV3125AuxReg4_Cfg.SetPAuxiliary Regulation 4 - Regulation setpoint; Modbus HR1630Write
AV3126AuxReg4_Cfg.Modul_LowLimAuxiliary Regulation 4 - Modulating: Low limit; Modbus HR1631Write
AV3127AuxReg4_Cfg.DOut_DiffAuxiliary Regulation 4 - Dout: Differential; Modbus HR1632Write
AV3128AuxReg4_Cfg.Modul_HighLimAuxiliary Regulation 4 - Modulating: High limit; Modbus HR1633Write
AV3129AuxReg4_Cfg.Modul_KpAuxiliary Regulation 4 - Modulating: Kp; Modbus HR1634Write
PIV3130AuxReg4_Cfg.Modul_TiAuxiliary Regulation 4 - Modulating: Integral time; Modbus HR1635Write
PIV3131AuxReg4_Cfg.Modul_TdAuxiliary Regulation 4 - Modulating: Derivative time; Modbus HR1636Write
AV3132AuxReg4_Cfg.Modul_DeadBandAuxiliary Regulation 4 - Modulating: Dead Band; Modbus HR1637Write
AV3133AuxReg4_Cfg.Modul_ManModeValAuxiliary Regulation 4 - Modulating: Manual mode value; Modbus HR1638Write
PIV3134DampOpTDamper opening time; Modbus HR1639Write
AV3135DampAirQuality_PID_Params.KpAir Quality - Dampers PID parameters - Proportional gain; Modbus HR1640Write
PIV3136DampAirQuality_PID_Params.TiAir Quality - Dampers PID parameters - Integral time; Modbus HR1641Write
AV3137FreshAirDamp_MinValFresh air damper - Minimum regulation value; Modbus HR1642Write
AV3138FreshAirDamp_MaxValFresh air damper - Maximum regulation value; Modbus HR1643Write
AV3139MixAirDamp_MinValMixing air damper - Minimum regulation value; Modbus HR1644Write
AV3140MixAirDamp_MaxValMixing air damper - Maximum regulation value; Modbus HR1645Write
AV3141IEC_PID_Params.KpIEC: PID parameters - Proportional gain; Modbus HR1646Write
PIV3142IEC_PID_Params.TiIEC: PID parameters - Integral time; Modbus HR1647Write
AV3143IEC_RetHumActThrshIEC: Return humidity activation threshold; Modbus HR1648Write
AV3144IEC_RetHumActDiffIEC: Return humidity activation differential; Modbus HR1649Write
AV3145Regulation.IEC_ExhHumLim_ThrshIEC: Exhaust humidity limit threshold; Modbus HR1650Write
AV3146Regulation.IEC_ExhHumLim_KpIEC: Exhaust humidity limit proportional gain; Modbus HR1651Write
PIV3147Regulation.IEC_ExhHumLim_TiIEC: Exhaust humidity limit integral time; Modbus HR1652Write
AV3148Regulation.IEC_FreshAirDamp_MaxLimIEC: Fresh air damper maximum limitation; Modbus HR1653Write
PIV3149MainCoil_CfgMain coil configuration; Modbus HR1654Write
PIV3150MainCoil_StpNMain coil steps number; Modbus HR1655Write
AV3151CoolCoil_PID_Params.KpCooling coil PID parameters - Proportional gain; Modbus HR1656Write
PIV3152CoolCoil_PID_Params.TiCooling coil PID parameters - Integral time; Modbus HR1657Write
AV3153HeatCoil_PID_Params.KpHeating coil PID parameters - Proportional gain; Modbus HR1658Write
PIV3154HeatCoil_PID_Params.TiHeating coil PID parameters - Integral time; Modbus HR1659Write
AV3155HumDehumReg.DeHum_PID.KpDehumidification PID parameters - Proportional gain; Modbus HR1660Write
PIV3156HumDehumReg.DeHum_PID.TiDehumidification PID parameters - Integral time; Modbus HR1661Write
PIV3157HumDehumReg.DeHum_PID.TdDehumidification PID parameters - Derivative time; Modbus HR1662Write
AV3158HumDehumReg.Dehum_MaxDeltaMaximum dehumidification offset; Modbus HR1663Write
AV3159AFreezeHeatCoilReqHeating coil request during antifreeze off status; Modbus HR1664Write
AV3160AFreezeCoolCoilReqCooling coil request during antifreeze off status; Modbus HR1665Write
PIV3161MainCoil_PmpNoCooling/Heating coil pumps number; Modbus HR1666Write
PIV3162Coils.MainCoil_PmpFlwChk_StartupTCooling/Heating coil pumps flow check startup delay; Modbus HR1667Write
PIV3163Coils.MainCoil_PmpFlwChk_RunTCooling/Heating coil pumps flow check run delay; Modbus HR1668Write
PIV3164Coils.MainCoil_PmpRotTCooling/Heating coil pumps rotation time; Modbus HR1669Write
PIV3165PreHeatCoil_StpNPreHeating coil steps number; Modbus HR1670Write
AV3166PreHeatCoil_PID_Params.KpPre heating PID parameters - Proportional gain; Modbus HR1671Write
PIV3167PreHeatCoil_PID_Params.TiPre heating PID parameters - Integral time; Modbus HR1672Write
AV3168AFreezePreHeatCoilReqPreHeating coil request during antifreeze off status; Modbus HR1673Write
PIV3169PreHeatCoil_PmpNoPreHeating coil pumps number; Modbus HR1674Write
PIV3170Coils.PreHeatCoil_PmpFlwChk_StartupTPreHeating coil pumps flow check startup delay; Modbus HR1675Write
PIV3171Coils.PreHeatCoil_PmpFlwChk_RunTPreHeating coil pumps flow check run delay; Modbus HR1676Write
PIV3172Coils.PreHeatCoil_PmpRotTPreHeating coil pumps rotation time; Modbus HR1677Write
PIV3173ReHeatCoil_StpNPostHeating coil steps number; Modbus HR1678Write
AV3174ReHeatCoil_PID_Params.KpPost heating PID parameters - Proportional gain; Modbus HR1679Write
PIV3175ReHeatCoil_PID_Params.TiPost heating PID parameters - Integral time; Modbus HR1680Write
AV3176AFreezeReHeatCoilReqPostHeating coil request during antifreeze off status; Modbus HR1681Write
PIV3177ReHeatCoil_PmpNoPost Heating coil pumps number; Modbus HR1682Write
PIV3178Coils.ReHeatCoil_PmpFlwChk_StartupTRe Heating coil pumps flow check startup delay; Modbus HR1683Write
PIV3179Coils.ReHeatCoil_PmpFlwChk_RunTReHeating coil pumps flow check run delay; Modbus HR1684Write
PIV3180Coils.ReHeatCoil_PmpRotTRe Heating coil pumps rotation time; Modbus HR1685Write
PIV3181VDI_InactivityStartUp_DelayVDI Inactivity startup activation delay; Modbus HR1686Write
PIV3182VDI_InactStartUp_DurationVDI Inactivity startup duration; Modbus HR1687Write
AV3183VDI_HiSatHumThrshVDI high saturation humidity threshold; Modbus HR1688Write
AV3184VDI_HiSatHumDiffVDI high saturation humidity differential; Modbus HR1689Write
PIV3185VDI_TypVDI Type: 0: Standard; 1: Custom; Modbus HR1690Write
PIV3186VDI_Conf[0].MonthSelMonth selection variable; Modbus HR1691Write
PIV3187VDI_Conf[1].MonthSelMonth selection variable; Modbus HR1692Write
PIV3188VDI_Conf[2].MonthSelMonth selection variable; Modbus HR1693Write
PIV3189VDI_Conf[3].MonthSelMonth selection variable; Modbus HR1694Write
PIV3190VDI_Conf[4].MonthSelMonth selection variable; Modbus HR1695Write
PIV3191VDI_Conf[5].MonthSelMonth selection variable; Modbus HR1696Write
PIV3192VDI_Conf[6].MonthSelMonth selection variable; Modbus HR1697Write
PIV3193VDI_Conf[7].MonthSelMonth selection variable; Modbus HR1698Write
PIV3194VDI_Conf[8].MonthSelMonth selection variable; Modbus HR1699Write
PIV3195VDI_Conf[9].MonthSelMonth selection variable; Modbus HR1700Write
PIV3196VDI_Conf[10].MonthSelMonth selection variable; Modbus HR1701Write
PIV3197VDI_Conf[11].MonthSelMonth selection variable; Modbus HR1702Write
PIV3198VDI_Conf[12].MonthSelMonth selection variable; Modbus HR1703Write
PIV3199VDI_Conf[13].MonthSelMonth selection variable; Modbus HR1704Write
PIV3200VDI_Conf[14].MonthSelMonth selection variable; Modbus HR1705Write
PIV3201VDI_Conf[15].MonthSelMonth selection variable; Modbus HR1706Write
PIV3202VDI_Conf[16].MonthSelMonth selection variable; Modbus HR1707Write
PIV3203VDI_Conf[17].MonthSelMonth selection variable; Modbus HR1708Write
PIV3204VDI_Conf[18].MonthSelMonth selection variable; Modbus HR1709Write
PIV3205VDI_Conf[19].MonthSelMonth selection variable; Modbus HR1710Write
PIV3206VDI_Conf[20].MonthSelMonth selection variable; Modbus HR1711Write
PIV3207VDI_Conf[21].MonthSelMonth selection variable; Modbus HR1712Write
PIV3208VDI_Conf[22].MonthSelMonth selection variable; Modbus HR1713Write
PIV3209VDI_Conf[23].MonthSelMonth selection variable; Modbus HR1714Write
PIV3210VDI_Conf[24].MonthSelMonth selection variable; Modbus HR1715Write
PIV3211VDI_Conf[25].MonthSelMonth selection variable; Modbus HR1716Write
PIV3212VDI_Conf[26].MonthSelMonth selection variable; Modbus HR1717Write
PIV3213VDI_Conf[27].MonthSelMonth selection variable; Modbus HR1718Write
PIV3214VDI_Conf[28].MonthSelMonth selection variable; Modbus HR1719Write
IV3215GeneralMng.DateFormatDate format (0: DD/MM/YY; 1: MM/DD/YY; 2: YY/MM/DD); Modbus HR1720Write
PIV3216GeneralMng.RTC_BMS.HourBMS real time clock; Modbus HR1721Write
PIV3217GeneralMng.RTC_BMS.MinuteBMS real time clock; Modbus HR1722Write
PIV3218PwdUserUser password; Modbus HR1723Write
PIV3219PwdServiceService password; Modbus HR1724Write
PIV3220PwdManufManufacturer password; Modbus HR1725Write
PIV3221GeneralMng.SPV_AddrBMS address; Modbus HR1727Write
PIV3222GeneralMng.SPV_TimeoutBMS timeout; Modbus HR1728Write
PIV3223GeneralMng.BMS_Baudrate_mskBMS baudrate (0=9600; 1=19200; 2=38400); Modbus HR1729Write
PIV3224GeneralMng.BMS_ParityBMS parity; Modbus HR1730Write
PIV3225GeneralMng.BMS_StopBitBMS stopbit; Modbus HR1731Write
PIV3226GeneralMng.FB_Baudrate_mskFor mask usage; Modbus HR1732Write
PIV3227GeneralMng.FB_ParityFieldbus parity; Modbus HR1733Write
PIV3228GeneralMng.FB_StopBitFieldbus stopbit; Modbus HR1734Write
PIV3229BLDC_compressor.MiscMng_BLDC1.Mng_PwrpAddrPowerPlus address; 32-bit (2 Modbus registers); Modbus HR1735Write
PIV3230uChiller_mng.DevAddr_uChDevice address; Modbus HR1737Write
PIV3231IEC.IEC_HUMFOG_DevAddrDevice address; 32-bit (2 Modbus registers); Modbus HR1738Write
PIV3232Humisonic.DevAddr_HUMSDevice address; 32-bit (2 Modbus registers); Modbus HR1740Write
PIV3233Humisonic.Timeout_HUMS32-bit (2 Modbus registers); Modbus timeout for Humisonic (delete after Humisonic library update); Modbus HR1742Write
PIV3234Humisonic.CmdDelay_HUMS32-bit (2 Modbus registers); Modbus command delay for Humisonic (delete after Humisonic library update); Modbus HR1744Write
PIV3235HumifogMng.HUMFOG_DevAddrDevice address; 32-bit (2 Modbus registers); Modbus HR1746Write
PIV3236Scheduler_OnOffUnit.SerDevCfg_THTN.DevAddrSerial device configuration - Device address; 32-bit (2 Modbus registers); Modbus HR1748Write
PIV3237GeneralMng.StationAdr7seg number; 32-bit (2 Modbus registers); Modbus HR1750Write
IV3238Data_EVD_Emb_1.Superparameters.EEVtype.ValSuperparameters - Valve; Modbus HR1752Write
IV3239Data_EVD_Emb_1.EVD.Regulation.GasTyp.ValEVD parameters - Regulation parameters configuration - Refrigerant; Modbus HR1753Write
AV3240EVD_Emb_Circ.EEV_SH_SetP_CoolSuperheat setpoint: cooling mode; Modbus HR1754Write
AV3241EVD_Emb_Circ.EEV_SH_SetP_HeatSuperheat setpoint: heating mode; Modbus HR1755Write
IV3242EVD_Emb_Circ.EEV_StartOpRatio_CoolEEV start opening ratio: cooling mode; Modbus HR1756Write
IV3243EVD_Emb_Circ.EEV_StartOpRatio_HeatEEV start opening ratio: heating mode; Modbus HR1757Write
IV3244Data_EVD_Emb_1.EVD.Regulation.SH_WaitDT.ValEVD parameters - Regulation parameters configuration - Regulation starting delay; Modbus HR1758Write
IV3245Data_EVD_Emb_1.EVD.Regulation.StandByEEV_OpPos.ValEVD parameters - Regulation parameters configuration - Standby valve opening ...; Modbus HR1759Write
AV3246EVD_Emb_Circ.EEV_PID_Kp_CoolEEV Proportional gain: cooling mode; Modbus HR1760Write
AV3247EVD_Emb_Circ.EEV_PID_Ti_CoolEEV Integral time: cooling mode; Modbus HR1761Write
AV3248EVD_Emb_Circ.EEV_PID_Td_CoolEEV Integral time: cooling mode; Modbus HR1762Write
AV3249EVD_Emb_Circ.EEV_PID_Kp_HeatEEV Proportional gain: heating mode; Modbus HR1763Write
AV3250EVD_Emb_Circ.EEV_PID_Ti_HeatEEV Integral time: heating mode; Modbus HR1764Write
AV3251EVD_Emb_Circ.EEV_PID_Td_HeatEEV Integral time: cooling mode; Modbus HR1765Write
IV3252Data_EVD_Emb_1.EVD.Regulation.LowSH_AlrmDT.ValEVD parameters - Regulation parameters configuration - LowSH (low superheat) ...; Modbus HR1766Write
AV3253EVD_Emb_Circ.EEV_LowSH_Thrsh_CoolEEV Low superheat threshold: cooling mode; Modbus HR1767Write
AV3254EVD_Emb_Circ.EEV_LowSH_Ti_CoolEEV Low superheat integral time: cooling mode; Modbus HR1768Write
AV3255EVD_Emb_Circ.EEV_LowSH_Thrsh_HeatEEV Low superheat threshold: heating mode; Modbus HR1769Write
AV3256EVD_Emb_Circ.EEV_LowSH_Ti_HeatEEV Low superheat integral time: heating mode; Modbus HR1770Write
IV3257Data_EVD_Emb_1.EVD.Regulation.LOP_AlrmDT.ValEVD parameters - Regulation parameters configuration - LOP (low evaporating ...; Modbus HR1771Write
AV3258EVD_Emb_Circ.EEV_LOP_Thrsh_CoolEEV LOP threshold: cooling mode; Modbus HR1772Write
AV3259EVD_Emb_Circ.EEV_LOP_Ti_CoolEEV LOP integral time: cooling mode; Modbus HR1773Write
AV3260EVD_Emb_Circ.EEV_LOP_Thrsh_HeatEEV LOP threshold: heating mode; Modbus HR1774Write
AV3261EVD_Emb_Circ.EEV_LOP_Ti_HeatEEV LOP integral time: heating mode; Modbus HR1775Write
IV3262Data_EVD_Emb_1.EVD.Regulation.MOP_AlrmDT.ValEVD parameters - Regulation parameters configuration - MOP (high evaporating ...; Modbus HR1776Write
AV3263EVD_Emb_Circ.EEV_MOP_Thrsh_CoolEEV MOP threshold: cooling mode; Modbus HR1777Write
AV3264EVD_Emb_Circ.EEV_MOP_Ti_CoolEEV MOP integral time: cooling mode; Modbus HR1778Write
AV3265EVD_Emb_Circ.EEV_MOP_Thrsh_HeatEEV MOP threshold: heating mode; Modbus HR1779Write
AV3266EVD_Emb_Circ.EEV_MOP_Ti_HeatEEV MOP integral time: heating mode; Modbus HR1780Write
IV3267EVD_Emb_Circ.EEV_ManPositStepsEEV manual poition steps; Modbus HR1781Write
AV3268Data_EVD_Emb_1.EVD.Regulation.LowSuctAlrmThrsh.ValEVD parameters - Regulation parameters configuration - Low suction temperature ...; Modbus HR1782Write
IV3269Data_EVD_Emb_1.EVD.Regulation.LowSuctAlrmDT.ValEVD parameters - Regulation parameters configuration - Low suction temperature ...; Modbus HR1783Write
IV3270Data_EVD_Emb_1.EVD.EEV_Config.RegMinPos.ValEVD parameters - Valve configuration - EEV minimum steps; Modbus HR1784Write
IV3271Data_EVD_Emb_1.EVD.EEV_Config.RegMaxPos.ValEVD parameters - Valve configuration - EEV maximum steps; Modbus HR1785Write
IV3272Data_EVD_Emb_1.EVD.EEV_Config.FullClosSteps.ValEVD parameters - Valve configuration - EEV closing steps; Modbus HR1786Write
IV3273Data_EVD_Emb_1.EVD.EEV_Config.MoveRate.ValEVD parameters - Valve configuration - EEV step rate; Modbus HR1787Write
IV3274Data_EVD_Emb_1.EVD.EEV_Config.FastClosMoveRate.ValEVD parameters - Valve configuration - EEV: emergency EEV closing speed; Modbus HR1788Write
IV3275Data_EVD_Emb_1.EVD.EEV_Config.MoveDuty.ValEVD parameters - Valve configuration - EEV duty cycle; Modbus HR1789Write
PIV3276BLDC_compressor.MiscMng_BLDC1.Mng_PwrpMotTypCompressor model (PowerPlus); Modbus HR1790Write
PIV3277BLDC_compressor.MiscMng_BLDC1.Mng_CompTypCompressor model; Modbus HR1791Write
PIV3278BLDC_compressor.MiscMng_PWRP1.Mng_DriveTypDrive type; Modbus HR1792Write
IV3279BLDC_compressor.MiscMng_PWRP1.Mng_WriteDefaultWrite default request; Modbus HR1793Write
PIV3280BLDC_compressor.CurrCompCfg_PWRP1.HR29_DataCommTimeoutCurr compressor configuration (Powerplus) - Data communication fault timeout; Modbus HR1794Write
AV3281BLDC_compressor.CurrCompCfg_PWRP1.HR07_MinOutFreqCurr compressor configuration (Powerplus) - Min output frequency; Modbus HR1795Write
AV3282BLDC_compressor.CurrCompCfg_PWRP1.HR06_MaxOutFreqCurr compressor configuration (Powerplus) - Max output frequency; Modbus HR1796Write
AV3283BLDC_compressor.CurrCompCfg_PWRP1.HR10_SkipFreqSetPCurr compressor configuration (Powerplus) - Skip frequency: set 1; Modbus HR1797Write
AV3284BLDC_compressor.CurrCompCfg_PWRP1.HR11_SkipFreqBandCurr compressor configuration (Powerplus) - Skip frequency: band 1; Modbus HR1798Write
AV3285BLDC_compressor.CurrCompCfg_PWRP1.HR67_SkipFreqSetP_2Curr compressor configuration (Powerplus) - Skip frequency setpoint 2; Modbus HR1799Write
AV3286BLDC_compressor.CurrCompCfg_PWRP1.HR68_SkipFreqBand_2Curr compressor configuration (Powerplus) - Skip frequency band 2; Modbus HR1800Write
AV3287BLDC_compressor.CurrCompCfg_PWRP1.HR69_SkipFreqSetp_3Curr compressor configuration (Powerplus) - Skip frequency setpoint 3; Modbus HR1801Write
AV3288BLDC_compressor.CurrCompCfg_PWRP1.HR70_SkipFreqBand_3Curr compressor configuration (Powerplus) - Skip frequency band 3; Modbus HR1802Write
PIV3289BLDC_compressor.CurrCompCfg_PWRP1.HR24_SwitchingFreqCurr compressor configuration (Powerplus) - Switching frequency; Modbus HR1803Write
PIV3290BLDC_compressor.CurrCompCfg_PWRP1.HR25_SwitchingFreqDeratingCurr compressor configuration (Powerplus) - Switching frequency derating; Modbus HR1804Write
PIV3291BLDC_compressor.CurrCompCfg_PWRP1.HR27_MotOvTempAlrmPTC_EnCurr compressor configuration (Powerplus) - Motor overtemperature alarm (PTC) enable; Modbus HR1805Write
PIV3292BLDC_compressor.CurrCompCfg_PWRP1.HR28_MotOvTempAlrmPTC_DelayCurr compressor configuration (Powerplus) - Motor overtemperature alarm delay; Modbus HR1806Write
PIV3293BLDC_compressor.CurrCompCfg_PWRP1.HR08_EnRevSpeedCurr compressor configuration (Powerplus) - Reverse speed enable; Modbus HR1807Write
PIV3294BLDC_compressor.CurrCompCfg_PWRP1.HR09_SpeedDeratingModeCurr compressor configuration (Powerplus) - Speed derating mode; Modbus HR1808Write
PIV3295BLDC_compressor.CurrCompCfg_PWRP1.HR33_StopModeCurr compressor configuration (Powerplus) - Stop mode; Modbus HR1809Write
PIV3296BLDC_compressor.CurrCompCfg_PWRP1.HR34_FlyingRestartCurr compressor configuration (Powerplus) - Flying restart; Modbus HR1810Write
PIV3297BLDC_compressor.CurrCompCfg_PWRP1.HR26_RelayCfgCurr compressor configuration (Powerplus) - Relay configuration; Modbus HR1811Write
PIV3298BLDC_compressor.MiscMng_PWRP1.Mng_MotPolesMotor pole pairs; Modbus HR1812Write
PIV3299BLDC_compressor.CurrCompCfg_PWRP1.HR00_MotCtrlModeCurr compressor configuration (Powerplus) - Motor control mode; Modbus HR1813Write
AV3300BLDC_compressor.CurrCompCfg_PWRP1.HR01_MotBaseFreqCurr compressor configuration (Powerplus) - Motor base frequency; Modbus HR1814Write
PIV3301BLDC_compressor.CurrCompCfg_PWRP1.HR02_MotBaseVCurr compressor configuration (Powerplus) - Motor base voltage; Modbus HR1815Write
AV3302BLDC_compressor.CurrCompCfg_PWRP1.HR03_MotRatedACurr compressor configuration (Powerplus) - Motor rated current; Modbus HR1816Write
PIV3303BLDC_compressor.CurrCompCfg_PWRP1.HR04_MotPwrFactorCurr compressor configuration (Powerplus) - Motor power factor; Modbus HR1817Write
AV3304BLDC_compressor.CurrCompCfg_PWRP1.HR05_MaxOutCurrentCurr compressor configuration (Powerplus) - Max output current; Modbus HR1818Write
AV3305BLDC_compressor.CurrCompCfg_PWRP1.HR12_SpeedProfileFreq1Curr compressor configuration (Powerplus) - Speed profile: frequency 1; Modbus HR1819Write
AV3306BLDC_compressor.CurrCompCfg_PWRP1.HR13_SpeedProfileFreq2Curr compressor configuration (Powerplus) - Speed profile: frequency 2; Modbus HR1820Write
AV3307BLDC_compressor.CurrCompCfg_PWRP1.HR14_SpeedProfileFreq3Curr compressor configuration (Powerplus) - Speed profile: frequency 3; Modbus HR1821Write
AV3308BLDC_compressor.CurrCompCfg_PWRP1.HR15_SpeedProfileAcceleration1Curr compressor configuration (Powerplus) - Speed profile: acceleration 1 [Hz/s]; Modbus HR1822Write
AV3309BLDC_compressor.CurrCompCfg_PWRP1.HR16_SpeedProfileAcceleration2Curr compressor configuration (Powerplus) - Speed profile: acceleration 2 [Hz/s]; Modbus HR1823Write
AV3310BLDC_compressor.CurrCompCfg_PWRP1.HR17_SpeedProfileAcceleration3Curr compressor configuration (Powerplus) - Speed profile: acceleration 3 [Hz/s]; Modbus HR1824Write
AV3311BLDC_compressor.CurrCompCfg_PWRP1.HR18_SpeedProfileAcceleration4Curr compressor configuration (Powerplus) - Speed profile: acceleration 4 [Hz/s]; Modbus HR1825Write
PIV3312BLDC_compressor.CurrCompCfg_PWRP1.HR19_SpeedProfileDelay1Curr compressor configuration (Powerplus) - Speed profile: delay 1; Modbus HR1826Write
PIV3313BLDC_compressor.CurrCompCfg_PWRP1.HR20_SpeedProfileDelay2Curr compressor configuration (Powerplus) - Speed profile: delay 2; Modbus HR1827Write
PIV3314BLDC_compressor.CurrCompCfg_PWRP1.HR21_SpeedProfileDelay3Curr compressor configuration (Powerplus) - Speed profile: delay 3; Modbus HR1828Write
AV3315BLDC_compressor.CurrCompCfg_PWRP1.HR23_SpeedProfileDecelerationCurr compressor configuration (Powerplus) - Speed profile: deceleration [Hz/s]; Modbus HR1829Write
AV3316BLDC_compressor.CurrCompCfg_PWRP1.HR35_V_F_BoostVCurr compressor configuration (Powerplus) - V/f boost voltage; Modbus HR1830Write
AV3317BLDC_compressor.CurrCompCfg_PWRP1.HR36_V_F_FreqAdjCurr compressor configuration (Powerplus) - V/f frequency adjustment; Modbus HR1831Write
AV3318BLDC_compressor.CurrCompCfg_PWRP1.HR37_V_F_VAdjCurr compressor configuration (Powerplus) - V/f voltage adjustment; Modbus HR1832Write
AV3319BLDC_compressor.CurrCompCfg_PWRP1.HR45_MotMagnetizingCurrentCurr compressor configuration (Powerplus) - Motor magnetizing current; Modbus HR1833Write
PIV3320BLDC_compressor.CurrCompCfg_PWRP1.HR46_StatorResistanceCurr compressor configuration (Powerplus) - Stator resistance [mohm]; Modbus HR1834Write
PIV3321BLDC_compressor.CurrCompCfg_PWRP1.HR47_RotorResistanceCurr compressor configuration (Powerplus) - Rotor resistance [mohm]; Modbus HR1835Write
AV3322BLDC_compressor.CurrCompCfg_PWRP1.HR48_StatorInductanceLdCurr compressor configuration (Powerplus) - Stator inductance Ld [mH]; Modbus HR1836Write
PIV3323BLDC_compressor.CurrCompCfg_PWRP1.HR49_LeakageFactorCurr compressor configuration (Powerplus) - Leakage factor; Modbus HR1837Write
AV3324BLDC_compressor.CurrCompCfg_PWRP1.HR50_LqInductanceCurr compressor configuration (Powerplus) - Stator inductance Lq [mH]; Modbus HR1838Write
AV3325BLDC_compressor.CurrCompCfg_PWRP1.HR55_SpeedLoopKpCurr compressor configuration (Powerplus) - Speed loop Kp; Modbus HR1839Write
PIV3326BLDC_compressor.CurrCompCfg_PWRP1.HR56_SpeedLoopTiCurr compressor configuration (Powerplus) - Speed loop Ti; Modbus HR1840Write
PIV3327BLDC_compressor.CurrCompCfg_PWRP1.HR51_MagnetizingTimeCurr compressor configuration (Powerplus) - Magnetizing time; Modbus HR1841Write
AV3328BLDC_compressor.CurrCompCfg_PWRP1.HR57_StartingCurrentCurr compressor configuration (Powerplus) - Starting current; Modbus HR1842Write
AV3329BLDC_compressor.CurrCompCfg_PWRP1.HR58_StartingAFreqCurr compressor configuration (Powerplus) - Frequency for starting current; Modbus HR1843Write
PIV3330BLDC_compressor.CurrCompCfg_PWRP1.CrankCaseHeaterModeCurr compressor configuration (Powerplus) - Crank-case heater mode (0=Strategy mng; ...; Modbus HR1844Write
AV3331BLDC_compressor.CurrCompCfg_PWRP1.HR65_CrankCaseHeaterCurrentCurr compressor configuration (Powerplus) - Crank-case heater current; Modbus HR1845Write
PIV3332BLDC_compressor.CurrCompCfg_PWRP1.HR66_STOResetStrategyCurr compressor configuration (Powerplus) - Safety torque off alarm autoreset ...; Modbus HR1846Write
AV3333BLDC_compressor.CurrCompCfg_PWRP1.HR77_InductSaturFactorCurr compressor configuration (Powerplus) - Inductance saturation factor; Modbus HR1847Write
IV3334BLDC_compressor.AlrmResetMng_PWRP1.RetryThrsMaximum semiautomatic alarm reset retry number; 32-bit (2 Modbus registers); Modbus HR1848Write
PIV3335BLDC_compressor.AlrmResetMng_PWRP1.TimeThrsTime threshold for semiautomatic reset; 32-bit (2 Modbus registers); Modbus HR1850Write
PIV3336BLDC_compressor.MiscMng_BLDC1.Mng_ModbusTimeout32-bit (2 Modbus registers); Modbus communication timeout [ms]; Modbus HR1852Write
PIV3337BLDC_compressor.MiscMng_BLDC1.Mng_ModbusCmdDelay32-bit (2 Modbus registers); Modbus command delay [ms]; Modbus HR1854Write
AV3338BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_MaxDeltaPBLDC envelope configuration - Max. permitted Delta P to start ...; Modbus HR1856Write
IV3339BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_EVDEqualMaxTBLDC envelope configuration - Maximum time of EVD propening to ...; Modbus HR1857Write
IV3340BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_EVDEqualPreopenBLDC envelope configuration - Preopening of EVD in case of ...; Modbus HR1858Write
AV3341BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_DeltaPVariationBLDC envelope configuration - Min. variation of Delta P to ...; Modbus HR1859Write
IV3342BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_DeltaPDelayBLDC envelope configuration - Delay to check increasing DeltaP to ...; Modbus HR1860Write
IV3343BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_RestartDelayBLDC envelope configuration - Restart delay after a start failure; Modbus HR1861Write
IV3344BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_AttemptsBLDC envelope configuration - Max Number of starting attempts; Modbus HR1862Write
AV3345BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_StartUpSpeedBLDC envelope configuration - Start up speed; Modbus HR1863Write
AV3347BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_MinSpeedRpsCustomBLDC envelope configuration - Min speed custom (rps); Modbus HR1865Write
AV3348BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_MaxDescendSpeedRateBLDC envelope configuration - Max. decrease speed rate (in regulation) [rps/s]; Modbus HR1866Write
AV3349BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_MaxRisingSpeedRateBLDC envelope configuration - Max. increase speed rate (in regulation) [rps/s]; Modbus HR1867Write
AV3350BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_SwitchOffSpeedRateBLDC envelope configuration - Decrease max speed rate (= max ...; Modbus HR1868Write
AV3351BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_MaxSlowdownSpeedRateBLDC envelope configuration - Decrease speed rate (to come back ...; Modbus HR1869Write
AV3352BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_MinSpeedControlledBLDC envelope configuration - Min speed permitted to control compressor ...; Modbus HR1870Write
IV3353BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_EnvOutMaxTBLDC envelope configuration - Out of envelop alarm delay time; Modbus HR1871Write
IV3354BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_LowDeltaPAlrmDelayBLDC envelope configuration - Low Delta P alarm delay; Modbus HR1872Write
AV3355BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_SuctTSaturationThrshZone1b1cBLDC envelope configuration - Suction sat.temp. threshold from zone 1b ...; Modbus HR1873Write
IV3356BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_MaxSpeedZone1cBLDC envelope configuration - Max Speed in rps for Zone ...; Modbus HR1874Write
AV3357BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempCtrlThrshZone1aBLDC envelope configuration - Discharge gas temperature control threshold for ...; Modbus HR1875Write
AV3358BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempAlrmThrshZone1aBLDC envelope configuration - Discharge gas limit temperature for Zone ...; Modbus HR1876Write
AV3359BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempCtrlThrshBLDC envelope configuration - Discharge gas temperature control threshold (SIAM ...; Modbus HR1877Write
AV3360BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempAlrmThrshBLDC envelope configuration - Discharge gas limit temperature (SIAM Scroll ...; Modbus HR1878Write
AV3361BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempLimDistanceBLDC envelope configuration - Action distance from High Temperature limit ...; Modbus HR1879Write
IV3362BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempPauseBLDC envelope configuration - Pause between speed reductions when discharge ...; Modbus HR1880Write
AV3363BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempSpeedReductionBLDC envelope configuration - Speed Reduction percentage when discharge temp ...; Modbus HR1881Write
AV3364CstEvapMinTempCustom minimum evaporating temperature; Modbus HR1882Write
AV3365CstCondMaxTempCustom maximum temperature condensing; Modbus HR1883Write
IV3366BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_SubTypeRegModeBLDC envelope configuration - Regol. Evd SubType: 0=null; 1=SSH; 2=DSH; ...; Modbus HR1884Write
AV3367BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DscgTempNTCTBLDC envelope configuration - Time constant of discharge temp sensor; Modbus HR1885Write
AV3368BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DscgSHSetPBLDC envelope configuration - SetPoint of Discharge SH (sent to EVD); Modbus HR1886Write
AV3369BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DTDscgSHRegOnBLDC envelope configuration - Setpoint offset for Discharge Super Heat ...; Modbus HR1887Write
AV3370BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DTDscgSHHystBLDC envelope configuration - Hysteresys for Discharge Super Heat regulation deactivation; Modbus HR1888Write
AV3371BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DscgTempSetPBLDC envelope configuration - SetPoint of Discharge Temp (sent to EVD); Modbus HR1889Write
AV3372BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DTDLTRegOnBLDC envelope configuration - Setpoint offset for Discharge Limit Temp. ...; Modbus HR1890Write
AV3373BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DTDLTHystBLDC envelope configuration - Hysteresys for Discharge Limit Temp. regulation deactivation; Modbus HR1891Write
IV3374BLDC_compressor.AlrmResetMng_BLDC_1.RetryThrsMaximum semiautomatic alarm reset retry number; 32-bit (2 Modbus registers); Modbus HR1892Write
PIV3375BLDC_compressor.AlrmResetMng_BLDC_1.TimeThrsTime threshold for semiautomatic reset; 32-bit (2 Modbus registers); Modbus HR1894Write
AV3376SupplyFanMinValSupply fan: Minimum regulation value; Modbus HR1896Write
AV3377SupplyFanMaxValSupply fan: Maximum regulation value; Modbus HR1897Write
AV3378RetFanMinValReturn fan: Minimum regulation value; Modbus HR1898Write
AV3379RetFanMaxValReturn fan: Maximum regulation value; Modbus HR1899Write
PIV3380GeneralMng.pGDx_MACAddress1PGDx Browser - MAC Address Last Four Digit - Part ...; Modbus HR1900Write
PIV3381GeneralMng.pGDx_MACAddress2PGDx Browser - MAC Address Last Four Digit - Part ...; Modbus HR1901Write
PIV3382GeneralMng.pGDx_MACAddress3PGDx Browser - MAC Address Last Four Digit - Part ...; Modbus HR1902Write
PIV3383GeneralMng.pGDx_MACAddress4PGDx Browser - MAC Address Last Four Digit - Part ...; Modbus HR1903Write
PIV3384BMS_LineBMS Line (0=None; 1=Modbus; 2=BACnet); Modbus HR1904Write
PIV3385BMS2_LineBMS2 Line (0=None; 1=Modbus; 2=BACnet); Modbus HR1905Write
PIV3386ETH_LineEthernet Line (0=None; 1=Modbus); Modbus HR1906Write
PIV3387ETH2_LineEthernet 2 Line (0=None; 1=BACnet); Modbus HR1907Write
PIV3388GeneralMng.BACnet_IDBACnet Device Instance (and Station address in MSTP); 32-bit (2 ...; Modbus HR1908Write
PIV3389GeneralMng.BACnet_TimeoutBACnet timeout; Modbus HR1910Write
PIV3390GeneralMng.BMS2_Baudrate_mskBMS baudrate (0=9600; 1=19200; 2=38400); Modbus HR1911Write
PIV3391GeneralMng.BMS2_ParityBMS 2 parity; Modbus HR1912Write
PIV3392GeneralMng.BMS2_StopBitBMS 2 stopbit; Modbus HR1913Write
PIV3940CoilVlv_OpenTimeCoil floating valve: Opening duration total time(from0% to100%); Modbus HR1914Write
PIV265AuxReg1_Cfg.CoolHeatModeAuxiliary Regulation 1 - Cooling/Heating mode; Modbus HR1915Write
PIV272AuxReg2_Cfg.CoolHeatModeAuxiliary Regulation 2 - Cooling/Heating mode; Modbus HR1916Write
PIV279AuxReg3_Cfg.CoolHeatModeAuxiliary Regulation 3 - Cooling/Heating mode; Modbus HR1917Write
PIV286AuxReg4_Cfg.CoolHeatModeAuxiliary Regulation 4 - Cooling/Heating mode; Modbus HR1918Write
PIV3950HumDehumStartReg_DTHumidification/Dehumidification: start regulation delay time; Modbus HR1919Write
PIV3952AirQuality_PM10.Board_RWAir quality: PM 10 - Board selected; Modbus HR1920Write
PIV3978AirQuality_PM10.Ch_Id_RWAir quality: PM 10 - Channel id selected; Modbus HR1921Write
PIV3979AirQuality_PM10.Ch_Type_RWAir quality: PM 10 - Type probe used; Modbus HR1922Write
PIV3980AirQuality_PM10.ChFilter_RWAir quality: PM 10 - Filter channel; Modbus HR1923Write
AV3983AirQuality_PM10.MaxVal_RWAir quality: PM 10 - Maximum value; Modbus HR1924Write
AV3984AirQuality_PM10.MinVal_RWAir quality: PM 10 - Minimum value; Modbus HR1925Write
AV3985AirQuality_PM10.Offset_RWAir quality: PM 10 - Offset; Modbus HR1926Write
PIV3991AirQuality_PM25.Board_RWAir quality: PM 2.5 - Board selected; Modbus HR1927Write
PIV3992AirQuality_PM25.Ch_Id_RWAir quality: PM 2.5 - Channel id selected; Modbus HR1928Write
PIV3993AirQuality_PM25.Ch_Type_RWAir quality: PM 2.5 - Type probe used; Modbus HR1929Write
PIV3994AirQuality_PM25.ChFilter_RWAir quality: PM 2.5 - Filter channel; Modbus HR1930Write
AV3997AirQuality_PM25.MaxVal_RWAir quality: PM 2.5 - Maximum value; Modbus HR1931Write
AV3998AirQuality_PM25.MinVal_RWAir quality: PM 2.5 - Minimum value; Modbus HR1932Write
AV3999AirQuality_PM25.Offset_RWAir quality: PM 2.5 - Offset; Modbus HR1933Write
PIV4004SanificationDevice.Board_RWSanification device - Board selected; Modbus HR1934Write
PIV4005SanificationDevice.Ch_Id_RWSanification device - Channel id selected; Modbus HR1935Write
PIV4006SanificationDevice.Ch_Type_RWSanification device - Digital output type; Modbus HR1936Write
PIV4009SanificationDevice.T_On_RWSanification device - Time on cycle relay; Modbus HR1937Write
PIV4010SanificationDevice.T_Off_RWSanification device - Time off cycle releay; Modbus HR1938Write
AV3954FansAirQualityVOC_PID_Params.KpAir Quality VOC - Fans PID parameters - Proportional gain; Modbus HR1939Write
PIV3953FansAirQualityVOC_PID_Params.TiAir Quality VOC - Fans PID parameters - Integral time; Modbus HR1940Write
AV3955DampAirQualityVOC_PID_Params.KpAir Quality VOC - Dampers PID parameters - Proportional gain; Modbus HR1941Write
PIV3956DampAirQualityVOC_PID_Params.TiAir Quality VOC - Dampers PID parameters - Integral time; Modbus HR1942Write
PIV3959QualitySignalQuality signal used (0: NONE, 1:CO2; 2: VOC;3:CO2 + VOC); Modbus HR1943Write
PIV3961ModeSanDevOffByBmsOrSchedMode sanification during off by BMS or scheduler (0: OFF,1:ON,2:Blink); Modbus HR1944Write
PIV3962SanificationDeviceTimeOnSanification device time on; Modbus HR1945Write
PIV3963SanificationDeviceTimeOffSanification device time off; Modbus HR1946Write
PIV3965WrkHrs_SanificationDevice.WrkHrs_ThrshSanification device - Working hours threshold (1000hrs); Modbus HR1947Write
PIV3967WrkHrs_SanificationDevice.WrkHrs_ResSanification device - Working hours reset; Modbus HR1948Write
PIV3972PurgeTimePurge time; Modbus HR1949Write
PIV3973PurgeModePurge mode (0:NO AUTO, 1:FIXED TIME, 2:DAILY SCHED, 3: FIXED+DAILY SCHED); Modbus HR1950Write
PIV3974PurgeHourPurge start time - Hour; Modbus HR1951Write
PIV3975PurgeMinutePurge start time - Minute; Modbus HR1952Write
AV3976BLDC_compressor.Speed_MaxSpeedRpsCustom_CoolingMaximum speed in cooling mode; Modbus HR1953Write
AV3977BLDC_compressor.Speed_MaxSpeedRpsCustom_HeatingMaximum speed in heating mode; Modbus HR1954Write
PIV4044SanificationDeviceOvld.Board_RWSanification deivce overload switch - Board selected; Modbus HR1955Write
PIV4045SanificationDeviceOvld.Ch_Id_RWSanification deivce overload switch - Channel id selected; Modbus HR1956Write
AV4014CurrAirQuality_VOC_SetPCurrent air quality VOC setpoint; Modbus HR1957Write
AV4023AirQualityVOCSetP_MaxValAir quality VOC setpoint - maximum value; Modbus HR1958Write
AV4022AirQualityVOCSetP_MinValAir quality VOC setpoint - minimum value; Modbus HR1959Write
AV4021UnitSetP.AirQuality_VOC_SetP.ComfortUnit setpoints - Air quality VOC - Comfort; Modbus HR1960Write
AV4015UnitSetP.AirQuality_VOC_SetP.EconomyUnit setpoints - Air quality VOC - Economy; Modbus HR1963Write
AV4018UnitSetP.AirQuality_VOC_SetP.PreComfortUnit setpoints - Air quality VOC - Pre-comfort; Modbus HR1966Write
PIV4024DfrEnActionsDefrost enabled actions (0=None, 1=Only phase 1, 2=Only phase 2, ...; Modbus HR1967Write
AV4026OilRecov_CompMinSpeedThrshOil recovery minimun compressor speed for activation; Modbus HR1968Write
AV4027OilRecov_FrcCompSpeedOil recovery compressor speed in which the compressor is forced; Modbus HR1969Write
PIV4028OilRecov_FrcSpeedTOil recovery duration in which the compressor speed is forced; Modbus HR1970Write
PIV4029OilRecov_WaitTOil recovery time before activation in which the compressor can ...; Modbus HR1971Write
AV4046EVD_Emb_Circ.EEV_PID_Kp_Cool_DfrEEV Proportional gain: cooling mode (Defrost); Modbus HR1972Write
AV4047EVD_Emb_Circ.EEV_PID_Kp_Heat_DfrEEV Proportional gain: heating mode (Defrost); Modbus HR1973Write
AV4048EVD_Emb_Circ.EEV_PID_Td_Cool_DfrEEV Integral time: cooling mode (Defrost); Modbus HR1974Write
AV4049EVD_Emb_Circ.EEV_PID_Td_Heat_DfrEEV Integral time: cooling mode (Defrost); Modbus HR1975Write
AV4050EVD_Emb_Circ.EEV_PID_Ti_Cool_DfrEEV Integral time: cooling mode (Defrost); Modbus HR1976Write
AV4051EVD_Emb_Circ.EEV_PID_Ti_Heat_DfrEEV Integral time: heating mode (Defrost); Modbus HR1977Write
PIV4030FC_FH_TypFree cooling/Free heating selection type (0=Temperature, 1=Enthalpy); Modbus HR1978Write
AV4031Regulation.FC_DeltaEnth_ActFreecooling activation delta enthalpy; Modbus HR1979Write
AV4032Regulation.FH_DeltaEnth_ActFreeheating activation delta enthalpy; Modbus HR1980Write
IV4052GeneralMng.pGDx_HostName_ASCII[1]PGDx - hostname prefix ASCII; Modbus HR1981Write
IV4053GeneralMng.pGDx_HostName_ASCII[2]PGDx - hostname prefix ASCII; Modbus HR1982Write
IV4054GeneralMng.pGDx_HostName_ASCII[3]PGDx - hostname prefix ASCII; Modbus HR1983Write
IV4055GeneralMng.pGDx_HostName_ASCII[4]PGDx - hostname prefix ASCII; Modbus HR1984Write
IV4056GeneralMng.pGDx_HostName_ASCII[5]PGDx - hostname prefix ASCII; Modbus HR1985Write
IV4057GeneralMng.pGDx_HostName_ASCII[6]PGDx - hostname prefix ASCII; Modbus HR1986Write
PIV4058FanNrFan number enabled via Bus; Modbus HR1987Write
PIV4059Ebmpapst_SupplyFan.SerInterfaceSet_EBM_2.CfgProtocol.DevAddrEBM2 Supply - Serial interface settings - Network address for ...; 32-bit; Modbus HR1988Write
PIV4060Ebmpapst_SupplyFan.SerInterfaceSet_EBM_3.CfgProtocol.DevAddrEBM3 Supply - Serial interface settings - Network address for ...; 32-bit; Modbus HR1990Write
PIV4061Ebmpapst_SupplyFan.SerInterfaceSet_EBM_4.CfgProtocol.DevAddrEBM4 Supply - Serial interface settings - Network address for ...; 32-bit; Modbus HR1992Write
PIV4062Ebmpapst_ReturnFan.SerInterfaceSet_EBM_2.CfgProtocol.DevAddrEBM2 Return - Serial interface settings - Network address for ...; 32-bit; Modbus HR1994Write
PIV4063Ebmpapst_ReturnFan.SerInterfaceSet_EBM_3.CfgProtocol.DevAddrEBM3 Return - Serial interface settings - Network address for ...; 32-bit; Modbus HR1996Write
PIV4064Ebmp3pst_ReturnFan.SerInterfaceSet_EBM_4.CfgProtocol.DevAddrEBM4 Return - Serial interface settings - Network address for ...; 32-bit; Modbus HR1998Write
PIV4065ZiehlAbegg_SupplyFan.SerialInterfa-ce_ZA_2.SerDevCfg.DevAddrZA2 Supply - Serial interface parameters - Fan Network address; ...; 32-bit; Modbus HR2000Write
PIV4066ZiehlAbegg_SupplyFan.SerialInterfa-ce_ZA_3.SerDevCfg.DevAddrZA3 Supply - Serial interface parameters - Fan Network address; ...; 32-bit; Modbus HR2002Write
PIV4067ZiehlAbegg_SupplyFan.SerialInterfa-ce_ZA_4.SerDevCfg.DevAddrZA4 Supply - Serial interface parameters - Fan Network address; ...; 32-bit; Modbus HR2004Write
PIV4068ZiehlAbegg_ReturnFan.SerialInterfa-ce_ZA_2.SerDevCfg.DevAddrZA2 Return - Serial interface parameters - Fan Network address; ...; 32-bit; Modbus HR2006Write
PIV4069ZiehlAbegg_ReturnFan.SerialInterfa-ce_ZA_3.SerDevCfg.DevAddrZA3 Return - Serial interface parameters - Fan Network address; ...; 32-bit; Modbus HR2008Write
PIV4070ZiehlAbegg_ReturnFan.SerialInterfa-ce_ZA_4.SerDevCfg.DevAddrZA4 Return - Serial interface parameters - Fan Network address; ...; 32-bit; Modbus HR2010Write
PIV4255WrkHrs_SupplyFan_2.WrkHrs_ThrshSupply Fan 2- Working hours threshold (1000hrs); Modbus HR2012Write
PIV4256WrkHrs_SupplyFan_2.WrkHrs_ResSupply Fan 2- Working hours reset; Modbus HR2013Write
PIV4257WrkHrs_SupplyFan_3.WrkHrs_ThrshSupply Fan 3- Working hours threshold (1000hrs); Modbus HR2014Write
PIV4258WrkHrs_SupplyFan_3.WrkHrs_ResSupply Fan 3- Working hours reset; Modbus HR2015Write
PIV4259WrkHrs_SupplyFan_4.WrkHrs_ThrshSupply Fan 4- Working hours threshold (1000hrs); Modbus HR2016Write
PIV4260WrkHrs_SupplyFan_4.WrkHrs_ResSupply Fan 4- Working hours reset; Modbus HR2017Write
PIV4261WrkHrs_ReturnFan_2.WrkHrs_ThrshReturn Fan 2- Working hours threshold (1000hrs); Modbus HR2018Write
PIV4262WrkHrs_ReturnFan_2.WrkHrs_ResReturn Fan 2- Working hours reset; Modbus HR2019Write
PIV4263WrkHrs_ReturnFan_3.WrkHrs_ThrshReturn Fan 3- Working hours threshold (1000hrs); Modbus HR2020Write
PIV4264WrkHrs_ReturnFan_3.WrkHrs_ResReturn Fan 3- Working hours reset; Modbus HR2021Write
PIV4265WrkHrs_ReturnFan_4.WrkHrs_ThrshReturn Fan 4- Working hours threshold (1000hrs); Modbus HR2022Write
PIV4266WrkHrs_ReturnFan_4.WrkHrs_ResReturn Fan 4- Working hours reset; Modbus HR2023Write
PIV4285FireSmokeMngTypFire Smoke management (0=Stop fans - 1=Only supply fans - ...; Modbus HR2024Write
PIV4296IOs.CstSerPrb_DevAddr[1]Custom serial probe 1 - device address; 32-bit (2 Modbus registers); Modbus HR2025Write
PIV4297IOs.CstSerPrb_DevAddr[2]Custom serial probe 2 - device address; 32-bit (2 Modbus registers); Modbus HR2027Write
PIV4298IOs.CstSerPrb_DevAddr[3]Custom serial probe 3 - device address; 32-bit (2 Modbus registers); Modbus HR2029Write
PIV4299IOs.CstSerPrb_DevAddr[4]Custom serial probe 4 - device address; 32-bit (2 Modbus registers); Modbus HR2031Write
PIV4300IOs.CstSerPrb_DevAddr[5]Custom serial probe 5 - device address; 32-bit (2 Modbus registers); Modbus HR2033Write
PIV4301CstPrbCfg.Temp1AdrCustom serial probe - Serial address - Temp1; Modbus HR2035Write
PIV4302CstPrbCfg.Temp2AdrCustom serial probe - Serial address – Temp2; Modbus HR2036Write
PIV4303CstPrbCfg.Hum1AdrCustom serial probe - Serial address - Hum1; Modbus HR2037Write
PIV4304CstPrbCfg.Hum2AdrCustom serial probe - Serial address – Hum2; Modbus HR2038Write
PIV4305CstPrbCfg.Press1AdrCustom serial probe - Serial address - Press1; Modbus HR2039Write
PIV4306CstPrbCfg.Press2AdrCustom serial probe - Serial address – Press2; Modbus HR2040Write
PIV4307CstPrbCfg.Flow1AdrCustom serial probe - Serial address - Flow1; Modbus HR2041Write
PIV4308CstPrbCfg.Flow2AdrCustom serial probe - Serial address – Flow2; Modbus HR2042Write
IV4309CstPrbCfg.Temp1FactCustom serial probe - Factor - Temp1; Modbus HR2043Write
IV4310CstPrbCfg.Temp2FactCustom serial probe - Factor – Temp2; Modbus HR2044Write
IV4311CstPrbCfg.Hum1FactCustom serial probe - Factor - Hum1; Modbus HR2045Write
IV4312CstPrbCfg.Hum2FactCustom serial probe - Factor – Hum2; Modbus HR2046Write
IV4313CstPrbCfg.Press1FactCustom serial probe - Factor - Press1; Modbus HR2047Write
IV4314CstPrbCfg.Press2FactCustom serial probe - Factor – Press2; Modbus HR2048Write
IV4315CstPrbCfg.Flow1FactCustom serial probe - Factor - Flow1; Modbus HR2049Write
IV4316CstPrbCfg.Flow2FactCustom serial probe - Factor – Flow2; Modbus HR2050Write
AV4317CstPrbCfg.TempAlmMinCustom serial probe - Temp. minimum value limit for trigger ...; 32-bit; Modbus HR2051Write
AV4318CstPrbCfg.TempAlmMaxCustom serial probe - Temp. maximum value limit for trigger ...; 32-bit; Modbus HR2053Write
AV4319CstPrbCfg.HumAlmMinCustom serial probe - Press. minimum value limit for trigger ...; 32-bit; Modbus HR2055Write
AV4320CstPrbCfg.HumAlmMaxCustom serial probe - Press. maximum value limit for trigger ...; 32-bit; Modbus HR2057Write
AV4321CstPrbCfg.PressAlmMinCustom serial probe - Press. minimum value limit for trigger ...; 32-bit; Modbus HR2059Write
AV4322CstPrbCfg.PressAlmMaxCustom serial probe - Press. maximum value limit for trigger ...; 32-bit; Modbus HR2061Write
AV4323CstPrbCfg.FlowAlmMinCustom serial probe - Flow minimum value limit for trigger ...; 32-bit; Modbus HR2063Write
AV4324CstPrbCfg.FlowAlmMaxCustom serial probe - Flow maximum value limit for trigger ...; 32-bit; Modbus HR2065Write
PIV4325CstPrbCfg.TimeoutCustom serial probe - Modbus - Timeout; Modbus HR2067Write
PIV4326CstPrbCfg.CmdDelayCustom serial probe - Modbus - Cmd delay; Modbus HR2068Write
PIV4327IAQ_PrbCfg.VOC_sensibilityIAQ configuration - VOC sensibility (0=disabled,1=low,2=medium,3=high); Modbus HR2069Write
PIV4328IAQ_PrbCfg.TimeoutIAQ configuration - Modbus - Timeout; Modbus HR2070Write
PIV4329IAQ_PrbCfg.CmdDelayIAQ configuration - Modbus - Cmd delay; Modbus HR2071Write
PIV4339HumiSteamMng.DevAddr_UEYHumiSteam - Device address; 32-bit (2 Modbus registers); Modbus HR2072Write
PIV4340HumiSteamMng.Timeout_UEYHumiSteam - Modbus timeout for UEY; 32-bit (2 Modbus registers); Modbus HR2074Write
PIV4341HumiSteamMng.CmdDelay_UEYHumiSteam - Modbus command delay for UEY; 32-bit (2 Modbus registers); Modbus HR2076Write
PIV4352SummerWinterDTSummer/Winter mode change delay time; Modbus HR2078Write
PIV4353SummerWinterSelSummer/Winter selection type; Modbus HR2079Write
AV4354CoolHeat_Chg_OffsetCooling/Heating change offset; 32-bit (2 Modbus registers); Modbus HR2080Write
PIV4355MainCoilCoolHeat_Din.Board_RWMain coil cool/heat - digital input - Board selected; Modbus HR2082Write
PIV4356MainCoilCoolHeat_Din.Ch_Id_RWMain coil cool/heat - digital input - Channel id selected; Modbus HR2083Write
PIV4357UnitAutoModeCfgUnit automatic mode configuration (0: Standard; 1: Energy saving); Modbus HR2084Write
PIV4358SummerEndDaySummer season ending day; Modbus HR2085Write
PIV4359SummerEndMonthSummer season ending month; Modbus HR2086Write
PIV4360SummerStartDaySummer season starting day; Modbus HR2087Write
PIV4361SummerStartMonthSummer season starting month; Modbus HR2088Write
AV4374Fans_regulation.RetFan_PID_Params.DeadBandReturn fan - PID parameters - Dead band; 32-bit (2 ...; Modbus HR2089Write
AV4375Fans_regulation.RetFan_PID_Params.KpReturn fan - PID parameters - Proportional gain; 32-bit (2 ...; Modbus HR2091Write
PIV4376Fans_regulation.RetFan_PID_Params.TiReturn fan - PID parameters - Integral time; Modbus HR2093Write
PIV4381GenericAin1.Board_RWGeneric Ain1 - Board selected; Modbus HR2094Write
PIV4382GenericAin1.Ch_Id_RWGeneric Ain1 - Channel id selected; Modbus HR2095Write
PIV4383GenericAin1.Ch_Type_RWGeneric Ain1 - Type probe used; Modbus HR2096Write
AV4384GenericAin1.MinVal_RWGeneric Ain1 - Minimum value; Modbus HR2097Write
AV4385GenericAin1.MaxVal_RWGeneric Ain1 - Maximum value; Modbus HR2098Write
AV4386GenericAin1.Offset_RWGeneric Ain1 - Offset; Modbus HR2099Write
PIV4387GenericAin1.ChFilter_RWGeneric Ain1 - Filter channel; Modbus HR2100Write
PIV4395GenericAin2.Board_RWGeneric Ain2 - Board selected; Modbus HR2101Write
PIV4396GenericAin2.Ch_Id_RWGeneric Ain2 - Channel id selected; Modbus HR2102Write
PIV4397GenericAin2.Ch_Type_RWGeneric Ain2 - Type probe used; Modbus HR2103Write
AV4398GenericAin2.MinVal_RWGeneric Ain2 - Minimum value; Modbus HR2104Write
AV4399GenericAin2.MaxVal_RWGeneric Ain2 - Maximum value; Modbus HR2105Write
AV4400GenericAin2.Offset_RWGeneric Ain2 - Offset; Modbus HR2106Write
PIV4401GenericAin2.ChFilter_RWGeneric Ain2 - Filter channel; Modbus HR2107Write
PIV4409GenericAin3.Board_RWGeneric Ain3 - Board selected; Modbus HR2108Write
PIV4410GenericAin3.Ch_Id_RWGeneric Ain3 - Channel id selected; Modbus HR2109Write
PIV4411GenericAin3.Ch_Type_RWGeneric Ain3 - Type probe used; Modbus HR2110Write
AV4412GenericAin3.MinVal_RWGeneric Ain3 - Minimum value; Modbus HR2111Write
AV4413GenericAin3.MaxVal_RWGeneric Ain3 - Maximum value; Modbus HR2112Write
AV4414GenericAin3.Offset_RWGeneric Ain3 - Offset; Modbus HR2113Write
PIV4415GenericAin3.ChFilter_RWGeneric Ain3 - Filter channel; Modbus HR2114Write
PIV4423GenericAin4.Board_RWGeneric Ain4 - Board selected; Modbus HR2115Write
PIV4424GenericAin4.Ch_Id_RWGeneric Ain4 - Channel id selected; Modbus HR2116Write
PIV4425GenericAin4.Ch_Type_RWGeneric Ain4 - Type probe used; Modbus HR2117Write
AV4426GenericAin4.MinVal_RWGeneric Ain4 - Minimum value; Modbus HR2118Write
AV4427GenericAin4.MaxVal_RWGeneric Ain4 - Maximum value; Modbus HR2119Write
AV4428GenericAin4.Offset_RWGeneric Ain4 - Offset; Modbus HR2120Write
PIV4429GenericAin4.ChFilter_RWGeneric Ain4 - Filter channel; Modbus HR2121Write
PIV4437GenericAin5.Board_RWGeneric Ain5 - Board selected; Modbus HR2122Write
PIV4438GenericAin5.Ch_Id_RWGeneric Ain5 - Channel id selected; Modbus HR2123Write
PIV4439GenericAin5.Ch_Type_RWGeneric Ain5 - Type probe used; Modbus HR2124Write
AV4440GenericAin5.MinVal_RWGeneric Ain5 - Minimum value; Modbus HR2125Write
AV4441GenericAin5.MaxVal_RWGeneric Ain5 - Maximum value; Modbus HR2126Write
AV4442GenericAin5.Offset_RWGeneric Ain5 - Offset; Modbus HR2127Write
PIV4443GenericAin5.ChFilter_RWGeneric Ain5 - Filter channel; Modbus HR2128Write
PIV4452GenericDin1.Board_RWGeneric Din1 - digital input - Board selected; Modbus HR2129Write
PIV4453GenericDin1.Ch_Id_RWGeneric Din1 - digital input - Channel id selected; Modbus HR2130Write
PIV4459GenericDin2.Board_RWGeneric Din2 - digital input - Board selected; Modbus HR2131Write
PIV4460GenericDin2.Ch_Id_RWGeneric Din2 - digital input - Channel id selected; Modbus HR2132Write
PIV4466GenericDin3.Board_RWGeneric Din3 - digital input - Board selected; Modbus HR2133Write
PIV4467GenericDin3.Ch_Id_RWGeneric Din3 - digital input - Channel id selected; Modbus HR2134Write
PIV4473GenericDin4.Board_RWGeneric Din4 - digital input - Board selected; Modbus HR2135Write
PIV4474GenericDin4.Ch_Id_RWGeneric Din4 - digital input - Channel id selected; Modbus HR2136Write
PIV4480GenericDin5.Board_RWGeneric Din5 - digital input - Board selected; Modbus HR2137Write
PIV4481GenericDin5.Ch_Id_RWGeneric Din5 - digital input - Channel id selected; Modbus HR2138Write
PIV4482GenericDin1_Alrm_MngTypGeneric Ain1 - alarm management (0: Disabled; 1: Only Warning; ...; Modbus HR2139Write
PIV4483GenericDin2_Alrm_MngTypGeneric Ain2 - alarm management (0: Disabled; 1: Only Warning; ...; Modbus HR2140Write
PIV4484GenericDin3_Alrm_MngTypGeneric Ain3 - alarm management (0: Disabled; 1: Only Warning; ...; Modbus HR2141Write
PIV4485GenericDin4_Alrm_MngTypGeneric Ain4 - alarm management (0: Disabled; 1: Only Warning; ...; Modbus HR2142Write
PIV4486GenericDin5_Alrm_MngTypGeneric Ain5 - alarm management (0: Disabled; 1: Only Warning; ...; Modbus HR2143Write
AV4497Regulation.FC_ExtTempLimitFree cooling external temperature; Modbus HR2144Write
AV4498Regulation.FH_ExtTempLimitFree heating external temperature limit; Modbus HR2145Write
AV4500IEC_ManModeValIEC: manual mode value; Modbus HR2146Write
AV4501Regulation.FanTempReg_KpRegulation fans speed: proportional gain; Modbus HR2147Write
PIV4502Regulation.FanTempReg_TdRegulation fans speed: derivative time; Modbus HR2148Write
AV4503Fans_regulation.RetAirFlw_K_FactorReturn fan - K factor for air flow calculations; Modbus HR2149Write
AV4509BMS_Reg_AnalogPrbMap[1]BMS registers - Analog map - 1; Modbus HR2150Write
AV4510BMS_Reg_AnalogPrbMap[2]BMS registers - Analog map – 2; Modbus HR2151Write
AV4511BMS_Reg_AnalogPrbMap[3]BMS registers - Analog map – 3; Modbus HR2152Write
AV4512BMS_Reg_AnalogPrbMap[4]BMS registers - Analog map – 4; Modbus HR2153Write
AV4513BMS_Reg_AnalogPrbMap[5]BMS registers - Analog map – 5; Modbus HR2154Write
PIV4534OA_Vlv_Open.Board_RWOutdoor air pre-treatment floating valve open - Board selected; Modbus HR2155Write
PIV4535OA_Vlv_Open.Ch_Id_RWOutdoor air pre-treatment floating valve open - Channel id selected; Modbus HR2156Write
PIV4536OA_Vlv_Open.T_On_RWOutdoor air pre-treatment floating valve open - Time on cycle relay; Modbus HR2157Write
PIV4537OA_Vlv_Open.T_Off_RWOutdoor air pre-treatment floating valve open - Time off cycle releay; Modbus HR2158Write
PIV4538OA_Vlv_Open.Ch_Type_RWOutdoor air pre-treatment floating valve open - Digital output type; Modbus HR2159Write
PIV4539OA_Vlv_Close.Board_RWOutdoor air pre-treatment floating valve close - Board selected; Modbus HR2160Write
PIV4540OA_Vlv_Close.Ch_Id_RWOutdoor air pre-treatment floating valve close - Channel id selected; Modbus HR2161Write
PIV4541OA_Vlv_Close.T_On_RWOutdoor air pre-treatment floating valve close - Time on cycle relay; Modbus HR2162Write
PIV4542OA_Vlv_Close.T_Off_RWOutdoor air pre-treatment floating valve close - Time off cycle releay; Modbus HR2163Write
PIV4543OA_Vlv_Close.Ch_Type_RWOutdoor air pre-treatment floating valve close - Digital output type; Modbus HR2164Write
AV4544OA_CoilManModeValOutdoor air pre-treatment coil manual mode value; Modbus HR2165Write
PIV4545OA_Coil_TypOutdoor air pre-treatment coil type; Modbus HR2166Write
AV4546OA_CoilWarmUpReqOutdoor air pre-treatment coil warm up request; Modbus HR2167Write
AV4547RegPrbErrOA_CoilReqOutdoor air pre-treatment coil request in case of regulation probe error; Modbus HR2168Write
PIV4548WrkHrs_OA_CoilAout.WrkHrs_ThrshOutdoor air pre-treatment coil analog output - Working hours threshold (1000hrs); Modbus HR2169Write
PIV4549WrkHrs_OA_CoilAout.WrkHrs_ResOutdoor air pre-treatment coil analog output - Working hours reset; Modbus HR2170Write
PIV4550WrkHrs_OA_CoilStep1.WrkHrs_ThrshOutdoor air pre-treatment coil step 1 - Working hours threshold (1000hrs); Modbus HR2171Write
PIV4551WrkHrs_OA_CoilStep1.WrkHrs_ResOutdoor air pre-treatment coil step 1 - Working hours reset; Modbus HR2172Write
PIV4552WrkHrs_OA_CoilStep2.WrkHrs_ThrshOutdoor air pre-treatment coil step 2 - Working hours threshold (1000hrs); Modbus HR2173Write
PIV4553WrkHrs_OA_CoilStep2.WrkHrs_ResOutdoor air pre-treatment coil step 2 - Working hours reset; Modbus HR2174Write
PIV4554WrkHrs_OA_CoilStep3.WrkHrs_ThrshOutdoor air pre-treatment coil step 3 - Working hours threshold (1000hrs); Modbus HR2175Write
PIV4555WrkHrs_OA_CoilStep3.WrkHrs_ResOutdoor air pre-treatment coil step 3 - Working hours reset; Modbus HR2176Write
PIV4556WrkHrs_OA_CoilStep4.WrkHrs_ThrshOutdoor air pre-treatment coil step 4 - Working hours threshold (1000hrs); Modbus HR2177Write
PIV4557WrkHrs_OA_CoilStep4.WrkHrs_ResOutdoor air pre-treatment coil step 4 - Working hours reset; Modbus HR2178Write
PIV4558OA_Coil_StpNOutdoor air pre-treatment coil steps number; Modbus HR2179Write
AV4559OA_Coil_PID_Params.KpOutdoor air pre-treatment coil PID parameters - Proportional gain; Modbus HR2180Write
PIV4560OA_Coil_PID_Params.TiOutdoor air pre-treatment coil PID parameters - Integral time; Modbus HR2181Write
PIV4561AFreezeOA_CoilReqOutdoor air pre-treatment coil request during antifreeze off status; Modbus HR2182Write
PIV4575OA_RegTypOA regulation type (0:OA probe;1: Supply only; 2:Return only; 3: ...; Modbus HR2183Write
AV4576OA_CoilTempSetPOutdoor air pre-treatment - temperature setpoint; Modbus HR2184Write
PIV4577OA_CoilActModeOutdoor air pre-treatment coil - PID enable (0=Always,1=Only DX defrost); Modbus HR2185 (printed as PI4577)Write
PIV3393VDI_Conf[0].MonthMonth before the required inspection; Modbus IR001Read
PIV3394VDI_Conf[1].MonthMonth before the required inspection; Modbus IR002Read
PIV3395VDI_Conf[2].MonthMonth before the required inspection; Modbus IR003Read
PIV3396VDI_Conf[3].MonthMonth before the required inspection; Modbus IR004Read
PIV3397VDI_Conf[4].MonthMonth before the required inspection; Modbus IR005Read
PIV3398VDI_Conf[5].MonthMonth before the required inspection; Modbus IR006Read
PIV3399VDI_Conf[6].MonthMonth before the required inspection; Modbus IR007Read
PIV3400VDI_Conf[7].MonthMonth before the required inspection; Modbus IR008Read
PIV3401VDI_Conf[8].MonthMonth before the required inspection; Modbus IR009Read
PIV3402VDI_Conf[9].MonthMonth before the required inspection; Modbus IR010Read
PIV3403VDI_Conf[10].MonthMonth before the required inspection; Modbus IR011Read
PIV3404VDI_Conf[11].MonthMonth before the required inspection; Modbus IR012Read
PIV3405VDI_Conf[12].MonthMonth before the required inspection; Modbus IR013Read
PIV3406VDI_Conf[13].MonthMonth before the required inspection; Modbus IR014Read
PIV3407VDI_Conf[14].MonthMonth before the required inspection; Modbus IR015Read
PIV3408VDI_Conf[15].MonthMonth before the required inspection; Modbus IR016Read
PIV3409VDI_Conf[16].MonthMonth before the required inspection; Modbus IR017Read
PIV3410VDI_Conf[17].MonthMonth before the required inspection; Modbus IR018Read
PIV3411VDI_Conf[18].MonthMonth before the required inspection; Modbus IR019Read
PIV3412VDI_Conf[19].MonthMonth before the required inspection; Modbus IR020Read
PIV3413VDI_Conf[20].MonthMonth before the required inspection; Modbus IR021Read
PIV3414VDI_Conf[21].MonthMonth before the required inspection; Modbus IR022Read
PIV3415VDI_Conf[22].MonthMonth before the required inspection; Modbus IR023Read
PIV3416VDI_Conf[23].MonthMonth before the required inspection; Modbus IR024Read
PIV3417VDI_Conf[24].MonthMonth before the required inspection; Modbus IR025Read
PIV3418VDI_Conf[25].MonthMonth before the required inspection; Modbus IR026Read
PIV3419VDI_Conf[26].MonthMonth before the required inspection; Modbus IR027Read
PIV3420VDI_Conf[27].MonthMonth before the required inspection; Modbus IR028Read
PIV3421VDI_Conf[28].MonthMonth before the required inspection; Modbus IR029Read
PIV3434SupplyTemp.Uom_WSupply temperature - Uom analog input; Modbus IR042Read
AVmin3435SupplyTemp.Val_Hw_RSupply temperature - Value reads from board; Modbus IR043Read
PIV3437SupplyHum.Uom_WSupply humidity - Uom analog input; Modbus IR045Read
AV3438SupplyHum.Val_Hw_RSupply humidity - Value reads from board; Modbus IR046Read
AV3439SupplyHum.Val_RSupply humidity; Modbus IR047Read
PIV3440RetTemp.Uom_WReturn temperature - Uom analog input; Modbus IR048Read
AV3441RetTemp.Val_Hw_RReturn temperature - Value reads from board; Modbus IR049Read
AVmin3442RetTemp.Val_RReturn temperature; Modbus IR050Read
PIV3443RetHum.Uom_WReturn humidity - Uom analog input; Modbus IR051Read
AV3444RetHum.Val_Hw_RReturn humidity - Value reads from board; Modbus IR052Read
AV3445RetHum.Val_RReturn humidity; Modbus IR053Read
PIV3446RoomTemp.Uom_WRoom temperature - Uom analog input; Modbus IR054Read
AV3447RoomTemp.Val_Hw_RRoom temperature - Value reads from board; Modbus IR055Read
AV3448RoomTemp.Val_RRoom temperature; Modbus IR056Read
PIV3449RoomHum.Uom_WRoom humidity - Uom analog input; Modbus IR057Read
AV3450RoomHum.Val_Hw_RRoom humidity - Value reads from board; Modbus IR058Read
AV3451RoomHum.Val_RRoom humidity; Modbus IR059Read
PIV3452ExtTemp.Uom_WFresh air temperature - Uom analog input; Modbus IR060Read
AV3453ExtTemp.Val_Hw_RFresh air temperature - Value reads from board; Modbus IR061Read
PIV3455ExtHum.Uom_WFresh air humidity - Uom analog input; Modbus IR063Read
AV3456ExtHum.Val_Hw_RFresh air humidity - Value reads from board; Modbus IR064Read
AV3457ExtHum.Val_RFresh air humidity; Modbus IR065Read
PIV3458ExhTemp.Uom_WExhaust temperature - Uom analog input; Modbus IR066Read
AV3459ExhTemp.Val_Hw_RExhaust temperature - Value reads from board; Modbus IR067Read
AV3460ExhTemp.Val_RExhaust temperature; Modbus IR068Read
PIV3461ExhHum.Uom_WExhaust humidity - Uom analog input; Modbus IR069Read
AV3462ExhHum.Val_Hw_RExhaust humidity - Value reads from board; Modbus IR070Read
AV3463ExhHum.Val_RExhaust humidity; Modbus IR071Read
PIV3464AFreezeTemp.Uom_WAntifreeze temperature - Uom analog input; Modbus IR072Read
AV3465AFreezeTemp.Val_Hw_RAntifreeze temperature - Value reads from board; Modbus IR073Read
AV3466AFreezeTemp.Val_RAntifreeze temperature; Modbus IR074Read
PIV3467SatTemp.Uom_WSaturation temperature - Uom analog input; Modbus IR075Read
AV3468SatTemp.Val_Hw_RSaturation temperature - Value reads from board; Modbus IR076Read
PIV3470SatHum.Uom_WSaturation humidity - Uom analog input; Modbus IR078Read
AV3471SatHum.Val_Hw_RSaturation humidity - Value reads from board; Modbus IR079Read
AV3472SatHum.Val_RSaturation humidity; Modbus IR080Read
PIV3473OA_Temp.Uom_WOutdoor air pre-treatment temperature - Uom analog input; Modbus IR081Read
AV3474OA_Temp.Val_Hw_ROutdoor air pre-treatment temperature - Value reads from board; Modbus IR082Read
AV3475OA_Temp.Val_ROutdoor air pre-treatment temperature; Modbus IR083Read
PIV3476SupplyAirP.Uom_WSupply air pressure - Uom analog input; Modbus IR084Read
AV3477SupplyAirP.Val_Hw_RSupply air pressure - Value reads from board; Modbus IR085Read
PIV3479RetAirP.Uom_WReturn air pressure - Uom analog input; Modbus IR087Read
AV3480RetAirP.Val_Hw_RReturn air pressure - Value reads from board; Modbus IR088Read
PIV3482AirQuality_CO2.Uom_WCO2 sensor - Uom analog input; Modbus IR090Read
AV3483AirQuality_CO2.Val_Hw_RCO2 sensor - Value reads from board; Modbus IR091Read
PIV3485AirQuality_VOC.Uom_WVOC sensor - Uom analog input; Modbus IR093Read
AV3486AirQuality_VOC.Val_Hw_RVOC sensor - Value reads from board; Modbus IR094Read
AV3487AirQuality_VOC.Val_RVOC sensor; Modbus IR095Read
PIV3488DscgP.Uom_WDischarge pressure - Uom analog input; Modbus IR096Read
AV3489DscgP.Val_Hw_RDischarge pressure - Value reads from board; Modbus IR097Read
PIV3491DscgT.Uom_WDischarge temperature - Uom analog input; Modbus IR099Read
AV3492DscgT.Val_Hw_RDischarge temperature - Value reads from board; Modbus IR100Read
PIV3494SuctP.Uom_WSuction pressure - Uom analog input; Modbus IR102Read
AV3495SuctP.Val_Hw_RSuction pressure - Value reads from board; Modbus IR103Read
PIV3497SuctT.Uom_WSuction temperature - Uom analog input; Modbus IR105Read
AV3498SuctT.Val_Hw_RSuction temperature - Value reads from board; Modbus IR106Read
PIV3500OA_CoilWaterTemp.Uom_WOutdoor air pre-treatment coil water temperature - Uom analog input; Modbus IR108Read
AV3501OA_CoilWaterTemp.Val_Hw_ROutdoor air pre-treatment coil water temperature - Value reads from board; Modbus IR109Read
AV3502OA_CoilWaterTemp.Val_ROutdoor air pre-treatment coil water temperature; Modbus IR110Read
PIV3503PreHeatCoilWaterTemp.Uom_WPreheat coil water temperature - Uom analog input; Modbus IR111Read
AV3504PreHeatCoilWaterTemp.Val_Hw_RPreheat coil water temperature - Value reads from board; Modbus IR112Read
AV3505PreHeatCoilWaterTemp.Val_RPreheat coil water temperature; Modbus IR113Read
PIV3506MainCoilWaterTemp.Uom_WMain coil water temperature - Uom analog input; Modbus IR114Read
AV3507MainCoilWaterTemp.Val_Hw_RMain coil water temperature - Value reads from board; Modbus IR115Read
AV3508MainCoilWaterTemp.Val_RMain coil water temperature; Modbus IR116Read
PIV3509ReHeatCoilWaterTemp.Uom_WPostheat coil water temperature - Uom analog input; Modbus IR117Read
AV3510ReHeatCoilWaterTemp.Val_Hw_RPostheat coil water temperature - Value reads from board; Modbus IR118Read
AV3511ReHeatCoilWaterTemp.Val_RPostheat coil water temperature; Modbus IR119Read
PIV3512AuxPrb_1.Uom_WAuxiliary probe 1 - Uom analog input; Modbus IR120Read
AV3513AuxPrb_1.Val_Hw_RAuxiliary probe 1 - Value reads from board; Modbus IR121Read
AV3514AuxPrb_1.Val_RAuxiliary probe 1; Modbus IR122Read
PIV3515AuxPrb_2.Uom_WAuxiliary probe 2 - Uom analog input; Modbus IR123Read
AV3516AuxPrb_2.Val_Hw_RAuxiliary probe 2 - Value reads from board; Modbus IR124Read
AV3517AuxPrb_2.Val_RAuxiliary probe 2; Modbus IR125Read
PIV3518AuxPrb_3.Uom_WAuxiliary probe 3 - Uom analog input; Modbus IR126Read
AV3519AuxPrb_3.Val_Hw_RAuxiliary probe 3 - Value reads from board; Modbus IR127Read
AV3520AuxPrb_3.Val_RAuxiliary probe 3; Modbus IR128Read
PIV3521AuxPrb_4.Uom_WAuxiliary probe 4 - Uom analog input; Modbus IR129Read
AV3522AuxPrb_4.Val_Hw_RAuxiliary probe 4 - Value reads from board; Modbus IR130Read
AV3523AuxPrb_4.Val_RAuxiliary probe 4; Modbus IR131Read
PIV3524Ain_SetP.Uom_WSetpoint by AIN - Uom analog input; Modbus IR132Read
AV3525Ain_SetP.Val_Hw_RSetpoint by AIN - Value reads from board; Modbus IR133Read
AV3526Ain_SetP.Val_RSetpoint by AIN; Modbus IR134Read
PIV3527SupplyRecoveryTemp.Uom_WSupply recovery temperature - Uom analog input; Modbus IR135Read
AV3528SupplyRecoveryTemp.Val_Hw_RSupply recovery temperature - Value reads from board; Modbus IR136Read
AV3529SupplyRecoveryTemp.Val_RSupply recovery temperature; Modbus IR137Read
PIV3530RetRecoveryTemp.Uom_WReturn recovery temperature - Uom analog input; Modbus IR138Read
AV3531RetRecoveryTemp.Val_Hw_RReturn recovery temperature - Value reads from board; Modbus IR139Read
AV3532RetRecoveryTemp.Val_RReturn recovery temperature; Modbus IR140Read
PIV3533HepaFilt_1.Uom_WHepa filter 1 - Uom analog input; Modbus IR141Read
AV3534HepaFilt_1.Val_Hw_RHepa filter 1 - Value reads from board; Modbus IR142Read
AV3535HepaFilt_1.Val_RHepa filter 1; Modbus IR143Read
PIV3536HepaFilt_2.Uom_WHepa filter 2 - Uom analog input; Modbus IR144Read
AV3537HepaFilt_2.Val_Hw_RHepa filter 2 - Value reads from board; Modbus IR145Read
AV3538HepaFilt_2.Val_RHepa filter 2; Modbus IR146Read
AV3540SupplyFan_Aout.Val_Hw_RSupply fan - Hardware value writes from board; Modbus IR148Read
AV3542RetFan_Aout.Val_Hw_RReturn fan - Hardware value writes from board; Modbus IR150Read
AV3544BypassDamp_Aout.Val_Hw_RBypass damper - Hardware value writes from board; Modbus IR152Read
AV3546MixingDamp_Aout.Val_Hw_RMixing damper - Hardware value writes from board; Modbus IR154Read
AV3548FreshAirDamp_Aout.Val_Hw_RFresh air damper - Hardware value writes from board; Modbus IR156Read
AV3549ReHeatCoil_Aout.Val_WReheat heater; Modbus IR157Read
AV3550ReHeatCoil_Aout.Val_Hw_RReheat heater - Hardware value writes from board; Modbus IR158Read
AV3551PreHeatCoil_Aout.Val_WPre-Heating heater; Modbus IR159Read
AV3552PreHeatCoil_Aout.Val_Hw_RPre-Heating heater - Hardware value writes from board; Modbus IR160Read
AV3553OA_Coil_Aout.Val_WOutdoor air pre-treatment heater; Modbus IR161Read
AV3554OA_Coil_Aout.Val_Hw_ROutdoor air pre-treatment heater - Hardware value writes from board; Modbus IR162Read
AV3555MainCoil_Aout.Val_WMain coil valve; Modbus IR163Read
AV3556MainCoil_Aout.Val_Hw_RMain coil valve - Hardware value writes from board; Modbus IR164Read
AV3558ThrmlWheel_Aout.Val_Hw_RThermal wheel - Hardware value writes from board; Modbus IR166Read
AV3559Humidifier_Aout.Val_WHumidifier; Modbus IR167Read
AV3560Humidifier_Aout.Val_Hw_RHumidifier - Hardware value writes from board; Modbus IR168Read
AV3562ExhAirDamp_Aout.Val_Hw_RExhaust air damper - Hardware value writes from board; Modbus IR170Read
AV3564AuxAout_1.Val_Hw_RAuxiliary output 1 - Hardware value writes from board; Modbus IR172Read
AV3566AuxAout_2.Val_Hw_RAuxiliary output 2 - Hardware value writes from board; Modbus IR174Read
AV3568AuxAout_3.Val_Hw_RAuxiliary output 3 - Hardware value writes from board; Modbus IR176Read
AV3570AuxAout_4.Val_Hw_RAuxiliary output 4 - Hardware value writes from board; Modbus IR178Read
AV3571IEC_Aout.Val_WIEC; Modbus IR179Read
AV3572IEC_Aout.Val_Hw_RIEC - Hardware value writes from board; Modbus IR180Read
AV3573Recovery_Aout.Val_WRecovery pump; Modbus IR181Read
AV3574Recovery_Aout.Val_Hw_RRecovery pump - Hardware value writes from board; Modbus IR182Read
AV3575SupplyAirDamp_Aout.Val_WSupply air damper; Modbus IR183Read
AV3576SupplyAirDamp_Aout.Val_Hw_RSupply air damper - Hardware value writes from board; Modbus IR184Read
AV3577RetAirDamp_Aout.Val_WReturn air damper; Modbus IR185Read
AV3578RetAirDamp_Aout.Val_Hw_RReturn air damper - Hardware value writes from board; Modbus IR186Read
PIV3579AlarmsMng.AlrmHourAlarm timestamp to which alarm index refers, hour; Modbus IR187Read
PIV3580AlarmsMng.AlrmMinuteAlarm timestamp to which alarm index refers, minute; Modbus IR188Read
PIV3581AlarmsMng.AlrmDayAlarm timestamp to which alarm index refers, day; Modbus IR189Read
PIV3582AlarmsMng.AlrmMonthAlarm timestamp to which alarm index refers, month; Modbus IR190Read
PIV3583AlarmsMng.AlrmYearAlarm timestamp to which alarm index refers, year; Modbus IR191Read
PIV3584AlarmsMng.AlrmLogHourAlarm log. timestamp to which alarm log. index refers, hour; Modbus IR192Read
PIV3585AlarmsMng.AlrmLogMinuteAlarm log. timestamp to which alarm log. index refers, minute; Modbus IR193Read
PIV3586AlarmsMng.AlrmLogDayAlarm log. timestamp to which alarm log. index refers, day; Modbus IR194Read
PIV3587AlarmsMng.AlrmLogMonthAlarm log. timestamp to which alarm log. index refers, month; Modbus IR195Read
PIV3588AlarmsMng.AlrmLogYearAlarm log. timestamp to which alarm log. index refers, year; Modbus IR196Read
IV3589AlarmsMng.ErrParamExpAlrms32-bit (2 Modbus registers); Modbus IR197Read
IV3590Scheduler_OnOffUnit.OnOffByKeb_SecLeftSeconds left before switching on/ff by keyboard; Modbus IR199Read
PIV3591Scheduler_OnOffUnit.PartyMode_CntDwnParty mode countdown; 32-bit (2 Modbus registers); Modbus IR200Read
PIV3592Dampers.DampersStatus0: Off; 1: Startup; 2: On; 3: Shutdown;; Modbus IR202Read
AV3593MaskMng.HeatExchgReqModbus IR203Read
PIV3594MaskMng.HeatExchgStatusSynHeat exchanger status (0: recovery; 1: freecooling; 2: freeheating; 3: ...; Modbus IR204Read
AV3595HeatExchanger.HeatExchgEfficiencyHeat exchanger efficiency (see comment on the algorithm for the formula); Modbus IR205Read
AV3596RetAirFlwValReturn air flw value; Modbus IR206Read
AV3597AirFlwValInput probe air flow; Modbus IR207Read
AV3598SupplyFanReqSupply fan request; Modbus IR208Read
PIV3599ComStatus_Supply_EBM_1Communication status of supply ebm fan (0:Online; 1:Offline; 2:Invalid packet; ...; Modbus IR209Read
PIV3600SupplyFanActPercentage of activation of ebmpapst supply fan; Modbus IR210Read
AV3601RetFanReqReturn fan request; Modbus IR211Read
PIV3602ComStatus_Return_EBM_1Communication status of return ebm fan (0:Online; 1:Offline; 2:Invalid packet; ...; Modbus IR212Read
PIV3603RetFanActPercentage of activation of ebmpapst return fan; Modbus IR213Read
AV3604Fans_regulation.RetFan_AirQuality_SetPOffsReturn fan - Air quality setpoint offset; Modbus IR214Read
AV3605Fans_regulation.SupplyFan_AirQuality_SetPOffsSupply fan - Air quality setpoint offset; Modbus IR215Read
AV3606AirQuality_Damps_RegReqAir Quality - Dampers regulation request; Modbus IR216Read
AV3607AirQuality_Fans_RegReqAir Quality - Fans regulation request; Modbus IR217Read
AV3608SupplyTempRegSetPSupply temperature regulation set point; Modbus IR218Read
AV3609PreHeatCoilRegReqPre-heating request from PID Seq; Modbus IR219Read
AV3610PreHeatCoilReqPre-heating request; Modbus IR220Read
AV3611Coils.ModulMainCoilReqCooling/Heating coil request; Modbus IR221Read
AV3612ReHeatCoilRegReqPost-heating request from PID Seq; Modbus IR222Read
AV3613ReHeatCoilReqPost-heating request; Modbus IR223Read
AV3614CondTempCondensing temperature; Modbus IR224Read
IV3615MaskMng.CompStatusMskModbus IR225Read
IV3616MaskMng.CompOnOffCntDwnOnOff compressor countdown; 32-bit (2 Modbus registers); Modbus IR226Read
AV3617CompReqCompressor request; Modbus IR228Read
AV3618Data_EVD_Emb_1.EVD.Variables.SH_EvapTemp.ValEVD parameters - Status variables - Evaporation temperature; Modbus IR229Read
AV3619Data_EVD_Emb_1.EVD.Variables.CondTemp.ValEVD parameters - Status variables - Condensing temperature; Modbus IR230Read
IV3620MaskMng.BLDC_CompStatusFor mask usage; Modbus IR231Read
IV3621MaskMng.BLDC_CompCntDwnFor mask usage; 32-bit (2 Modbus registers); Modbus IR232Read
AV3622BLDC_PwrReqBLDC power request; Modbus IR234Read
AV3623MaskMng.BLDC_CompPerc_ScaledBLDC Compressore run request scaled with the custom maximum limit; Modbus IR235Read
IV3624BLDC_compressor.EnvZone0=Null;1=OK;2=Max.comp.rat;3=Max.dsc.P.;4=Curr.limit;5=Max. suct.P.;6=Min.comp.rat;7=Min.DeltaP;8=Min.dsc.P.;9=Min.suct.P.; Modbus IR236Read
IV3625BLDCtoEVD.RegSubTypBLDC to EVD parameters - EVD regulation subtype; Modbus IR237Read
IV3626MaskMng.EEV_StatusFor mask usage; Modbus IR238Read
AV3627Data_EVD_Emb_1.EVD.Variables.SH.ValEVD parameters - Status variables - Superheat; Modbus IR239Read
AV3628BLDC_compressor.Info_PWRP1.Info_RotorSpeed_rpsInverter Power Plus Info - Current rotor speed [rps]; Modbus IR240Read
AV3629Data_EVD_Emb_1.EVD.Variables.EEV_PosPercent.ValEVD parameters - Status variables - Valve opening; Modbus IR241Read
IV3630MaskMng.CompEnvCntDwnModbus IR242Read
IV3631Data_EVD_Emb_1.EVD.Variables.EEV_PosSteps.ValEVD parameters - Status variables - Valve position; Modbus IR243Read
AV3632MaskMng.EEVSetFor mask usage; Modbus IR244Read
AV3633Data_EVD_Emb_1.EVD.Variables.DscgSH.ValEVD parameters - Status variables - Discharge superheat; Modbus IR245Read
AV3634HumDehumReg.HumDehum_RegHum_RelHumidification/Dehumidification: Relative humidity variable; Modbus IR246Read
AV3635HumDehumReg.HumDehum_RegHum_AbsHumidification/Dehumidification: Absolute humidity variable; Modbus IR247Read
AV3636HumDehumReg.HumDehum_SetP_AbsHumidification/Dehumidification: Absolute setpoint; Modbus IR248Read
AV3637HumRegReqHumidification request from PID Seq; Modbus IR249Read
AV3638DehumRegReqDehumidification request; Modbus IR250Read
AV3639Dehum_DewPointSetPDew point set point for dehumidification; Modbus IR251Read
AV3640AuxiliaryRegulation.AuxReg1_Info.RegValAuxiliary regulation 1: Informations - Regulation value; Modbus IR252Read
AV3641AuxiliaryRegulation.AuxReg2_Info.RegValAuxiliary regulation 2: Informations - Regulation value; Modbus IR253Read
AV3642AuxiliaryRegulation.AuxReg3_Info.RegValAuxiliary regulation 3: Informations - Regulation value; Modbus IR254Read
AV3643AuxiliaryRegulation.AuxReg4_Info.RegValAuxiliary regulation 4: Informations - Regulation value; Modbus IR255Read
PIV3644Scheduler_OnOffUnit.SchedSrcScheduler source (DIN, Party mode, SPV, cpCO, th-Tune); Modbus IR256Read
PIVmin3645SchedStatusUnit status currently active: 0=Off; 1=Economy; 2=Pre-comfort; 3=Comfort; Modbus IR257Read
AV3646KWater_MB.HR18_ExtTKWater modbus variables - External temperature; Modbus IR258Read
AV3647KWater_MB.HR21_TCircKAirKWater modbus variables - KAir circuit temperature; Modbus IR259Read
PIV3648kWater_UnitStatusUnit status kwater; Modbus IR260Read
AV3649HumifogMng.HUMFOG_PwrReqPower request; Modbus IR261Read
AV3650HumifogMng.HUMFOG_ActualProdActual production of rack (kg/h-lb/h); Modbus IR262Read
PIV3651HumifogMng.HUMFOG_HoursWorskPump running hour humifog; 32-bit (2 Modbus registers); Modbus IR263Read
IV3652HumifogMng.HUMFOG_UnitStatusMachine status; Modbus IR265Read
AV3653IEC_ReqIEC: request; Modbus IR266Read
AV3654IEC.IEC_HUMFOG_ActualProdActual production of rack (kg/h-lb/h); Modbus IR267Read
PIV3655IEC.IEC_HUMFOG_HoursWorksPump running hour humifog; 32-bit (2 Modbus registers); Modbus IR268Read
IV3656IEC.IEC_HUMFOG_UnitStatusMachine status; Modbus IR270Read
AV3657uChiller_mng.Info_uCh.BLDC_rps_Circ1Split an int value into digits - rps bldc circ1 ...; Modbus IR271Read
IV3658uChiller_mng.Info_uCh.EEV_PosPerc_Circ1Split an int value into digits - Opn1 - EEV ...; Modbus IR272Read
AV3659uChiller_mng.Info_uCh.DscgPCirc1Split an int value into digits - dSP1-Discharge press. probe ...; Modbus IR273Read
AV3660uChiller_mng.Info_uCh.SuctPCirc1Split an int value into digits - ScP1-Suction press. of circ.1; Modbus IR274Read
IV3661uChiller_mng.UnitStatus_uChUnitstatus(0=OffByDI; 1=OffByKeyb; 2=OffBySched; 3=OffByBMS; 4=OffByChgOvr; 5=OffByAl; 6=Dfr; 7=StdBy; 14=FCOn; 15=CoolOn; ...; Modbus IR275Read
AV3662uChiller_mng.Info_uCh.BLDC_rps_Circ2Split an int value into digits - rps bldc circ2 ...; Modbus IR276Read
PIV3663GeneralMng.CurrVer.XCurrent version of the application according to standard - X ...; Modbus IR277Read
PIV3664GeneralMng.CurrVer.YCurrent version of the application according to standard - Y ...; Modbus IR278Read
PIV3665GeneralMng.CurrVer.ZCurrent version of the application according to standard - Z ...; Modbus IR279Read
PIV3666GeneralMng.CurrVer.DCurrent version of the application according to standard - D ...; Modbus IR280Read
PIV3667GeneralMng.OsVersion[1]Application version; 32-bit (2 Modbus registers); Modbus IR281Read
PIV3668GeneralMng.OsVersion[2]Application version; 32-bit (2 Modbus registers); Modbus IR283Read
PIV3669GeneralMng.OsVersion[3]Application version; 32-bit (2 Modbus registers); Modbus IR285Read
PIV3670GeneralMng.BoardTyp[1]Type of board (12 = c.pCO, 13 = uPC, 14 ...; 32-bit; Modbus IR287Read
PIV3671GeneralMng.BoardTyp[2]Type of board (12 = c.pCO, 13 = uPC, 14 ...; 32-bit; Modbus IR289Read
PIV3672VarToShow.IdxChNameModbus IR291Read
PIV3673VarToShow.BoardModbus IR292Read
PIV3674VarToShow.Ch_IdModbus IR293Read
AV3675ObjMsk.ValStaticPressHigh/low limit alarm with hysteresis - Value static pressure; Modbus IR294Read
AV3676ObjMsk.ValAirQualHigh/low limit alarm with hysteresis - Value air quality; Modbus IR295Read
AV3677ObjMsk.ValRfrgPressHigh/low limit alarm with hysteresis - Value refrigerant pressure; Modbus IR296Read
AV3678ObjMsk.ValFlowRateHigh/low limit alarm with hysteresis - Value flow rate; Modbus IR297Read
AV3679ObjMsk.ValAirFlowHigh/low limit alarm with hysteresis - Value air flow; Modbus IR298Read
AV3680ObjMsk.ValTempHigh/low limit alarm with hysteresis - Value temperature; Modbus IR299Read
AV3681ObjMsk.ValHumHigh/low limit alarm with hysteresis - Value humidity; Modbus IR300Read
AV3682ObjMsk.ValAoutHigh/low limit alarm with hysteresis - Value analog output; Modbus IR301Read
AV3683ObjMsk.ValGenericHigh/low limit alarm with hysteresis - Value generic probe; Modbus IR302Read
AV3684ObjMsk.ValPercentHigh/low limit alarm with hysteresis - Value percent probe; Modbus IR303Read
PIV3685SupplyFan_MainMaskUsed only for main mask; Modbus IR304Read
PIV3686MaskMng.RetFan_MainMaskUsed only for main mask; Modbus IR305Read
PIV3687HourActual hour; Modbus IR306Read
PIV3688MinuteActual minute; Modbus IR307Read
PIV3689Scheduler_OnOffUnit.UnitStatusUnit status; Modbus IR308Read
PIV3690Ebmpapst_SupplyFan.InfoSpeed_EBM_1.CurrSpeedCurrent speed in [rpm] of the fan for Ebmpapst fan; Modbus IR309Read
PIV3691Ebmpapst_SupplyFan.ElectrInfo_EBM_1.DC_Link_VDC link voltage for Ebmpapst fan; Modbus IR310Read
PIV3692Ebmpapst_SupplyFan.ElectrInfo_EBM_1.DC_Link_ADC link current for Ebmpapst fan; Modbus IR311Read
PIV3693Ebmpapst_SupplyFan.ElectrInfo_EBM_1.CurrPowerCurrent power in [W] for Ebmpapst fan; Modbus IR312Read
PIV3694Ebmpapst_SupplyFan.ElectrInfo_EBM_1.ElectrTempInternal circuit temperature for Ebmpapst fan; Modbus IR313Read
PIV3695Ebmpapst_SupplyFan.MotStatus_EBM_1.IR_MotStatusMotor status input register; Modbus IR314Read
PIV3696Ebmpapst_SupplyFan.Warn_EBM_1.IR_WarnWarining input register (Bitfield); Modbus IR315Read
PIV3697Ebmpapst_SupplyFan.InfoSpeed_EBM_1.MaxSpeedMaximum admissible speed: all read or speed in [rpm] settings ...; Modbus IR316Read
PIV3698Ebmpapst_SupplyFan.CntWorkHrsBkp_EBM_1Working hour counter for Ebmpapst fan; Modbus IR317Read
PIV3699Ebmpapst_ReturnFan.InfoSpeed_EBM_1.CurrSpeedCurrent speed in [rpm] of the fan for Ebmpapst fan; Modbus IR318Read
PIV3700Ebmpapst_ReturnFan.ElectrInfo_EBM_1.DC_Link_VDC link voltage for Ebmpapst fan; Modbus IR319Read
PIV3701Ebmpapst_ReturnFan.ElectrInfo_EBM_1.DC_Link_ADC link current for Ebmpapst fan; Modbus IR320Read
PIV3702Ebmpapst_ReturnFan.ElectrInfo_EBM_1.CurrPowerCurrent power in [W] for Ebmpapst fan; Modbus IR321Read
PIV3703Ebmpapst_ReturnFan.ElectrInfo_EBM_1.ElectrTempInternal circuit temperature for Ebmpapst fan; Modbus IR322Read
PIV3704Ebmpapst_ReturnFan.MotStatus_EBM_1.IR_MotStatusMotor status input register; Modbus IR323Read
PIV3705Ebmpapst_ReturnFan.Warn_EBM_1.IR_WarnWarining input register (Bitfield); Modbus IR324Read
PIV3706Ebmpapst_ReturnFan.InfoSpeed_EBM_1.MaxSpeedMaximum admissible speed: all read or speed in [rpm] settings ...; Modbus IR325Read
PIV3707Ebmpapst_ReturnFan.CntWorkHrsBkp_EBM_1Working hour counter for Ebmpapst fan; Modbus IR326Read
PIV3708ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_1.CurrSpeed_rpmFan speed informations - Actual speed [rpm] of the Zhiel-Abegg fan; Modbus IR327Read
PIV3709ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.DC_LinkVFan electrical informations - DC link voltage (V); Modbus IR328Read
PIV3710ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.LineVFan electrical informations - Supply voltage (peak voltage); Modbus IR329Read
PIV3711ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_1.MaxSpeed_rpmFan speed informations - Maximum set speed; Modbus IR330Read
PIV3712ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_1.MinSpeed_rpmFan speed informations - Minimum set speed; Modbus IR331Read
PIV3713ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.MotPwrFan electrical informations - Motor input power (W); Modbus IR332Read
AV3714ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.ElectronicTempFan electrical informations - Electronics temperature (°C); Modbus IR333Read
AV3715ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.IGBT_tempFan electrical informations - IGBT temperature (°C); Modbus IR334Read
AV3716ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.MCU_TempFan electrical informations - MCU temperature; Modbus IR335Read
AV3717ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.MotTempFan electrical informations - Motr temperature (°C); Modbus IR336Read
PIV3718FanAlrm_ZA_SupplyFan.ErrStatusFan alarms - Error status defines errors currently detected; Modbus IR337Read
PIV3719ZiehlAbegg_SupplyFan.FanStatus_ZA_1.WorkingStatusFan status (working mode, errors) - Working status defines current ...; Modbus IR338Read
PIV3720ZiehlAbegg_SupplyFan.FanStatus_ZA_1.WorkStatusCodeFan status (working mode, errors) - Working status code; Modbus IR339Read
PIV3721ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_1.CurrSpeed_rpmFan speed informations - Actual speed [rpm] of the Zhiel-Abegg fan; Modbus IR340Read
PIV3722ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.DC_LinkVFan electrical informations - DC link voltage (V); Modbus IR341Read
PIV3723ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.LineVFan electrical informations - Supply voltage (peak voltage); Modbus IR342Read
PIV3724ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_1.MaxSpeed_rpmFan speed informations - Maximum set speed; Modbus IR343Read
PIV3725ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_1.MinSpeed_rpmFan speed informations - Minimum set speed; Modbus IR344Read
PIV3726ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.MotPwrFan electrical informations - Motor input power (W); Modbus IR345Read
AV3727ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.ElectronicTempFan electrical informations - Electronics temperature (°C); Modbus IR346Read
AV3728ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.IGBT_tempFan electrical informations - IGBT temperature (°C); Modbus IR347Read
AV3729ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.MCU_TempFan electrical informations - MCU temperature; Modbus IR348Read
AV3730ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.MotTempFan electrical informations - Motr temperature (°C); Modbus IR349Read
PIV3731FanAlrm_ZA_RetFan.ErrStatusFan alarms - Error status defines errors currently detected; Modbus IR350Read
PIV3732ZiehlAbegg_ReturnFan.FanStatus_ZA_1.WorkingStatusFan status (working mode, errors) - Working status defines current ...; Modbus IR351Read
PIV3733ZiehlAbegg_ReturnFan.FanStatus_ZA_1.WorkStatusCodeFan status (working mode, errors) - Working status code; Modbus IR352Read
PIV3734Humisonic.DevInfo_HUMS.FwRel_HDevice info - Firmware release (high part); Modbus IR353Read
PIV3735Humisonic.DevInfo_HUMS.FwRel_LDevice info - Firmware release (low part); Modbus IR354Read
IV3736Humisonic.DevInfo_HUMS.UnitHrsCountDevice info - Working hours of the unit; Modbus IR355Read
IV3737Humisonic.Humisonic_2_1.FwVars.CtrlStateLists of variables of the device not managed by default; Modbus IR356Read
PIV3738Humisonic.AlrmCode_HUMSAlarm code read from device; Modbus IR357Read
PIV3739GeneralMng.DayActual day; Modbus IR358Read
PIV3740GeneralMng.MonthActual month; Modbus IR359Read
PIV3741GeneralMng.YearActual year; Modbus IR360Read
PIV3742GeneralMng.RTC.HourcpCO real time clock; Modbus IR361Read
PIV3743GeneralMng.RTC.MinutecpCO real time clock; Modbus IR362Read
PIV3744GeneralMng.RTC.SecondcpCO real time clock; Modbus IR363Read
PIV3745GeneralMng.LastOnDaySaving of last day before blackout; Modbus IR364Read
PIV3746GeneralMng.LastOnMonthSaving of last month before blackout; Modbus IR365Read
PIV3747GeneralMng.LastOnYearSaving of last year before blackout; Modbus IR366Read
PIV3748GeneralMng.LastOnHourSaving of last hour before blackout; Modbus IR367Read
PIV3749GeneralMng.LastOnMinuteSaving of last minute before blackout; Modbus IR368Read
PIV3750GeneralMng.LastOnSecondSaving of last second before blackout; Modbus IR369Read
PIV3751GeneralMng.OffDaysNumber of days since the last blackout; Modbus IR370Read
PIV3752GeneralMng.OffHoursNumber of hours since the last blackout; Modbus IR371Read
PIV3753GeneralMng.OffMinutesNumbers of minutes since the last blackout; Modbus IR372Read
PIV3754GeneralMng.FB_PollTLast polling loop time (ms); 32-bit (2 Modbus registers); Modbus IR373Read
PIV3755GeneralMng.FB_PollLoopNoNumber of Polling loops; 32-bit (2 Modbus registers); Modbus IR375Read
PIV3756MemWritingsNoAbsolute number of writings in retain memory during the entire ...; 32-bit; Modbus IR377Read
PIV3757GeneralMng.PrgCycleMsProgram speed in ms; Modbus IR379Read
AV3758GeneralMng.CyclesPerSecondProgram speed in CyclePerSecond; Modbus IR380Read
IV3759GeneralMng.ErrParamWizardError communication for Import/Export blocks; 32-bit (2 Modbus registers); Modbus IR381Read
PIV3760GeneralMng.DayOfWeekDay of week; Modbus IR383Read
PIV3761Scheduler_OnOffUnit.FB_SchedulerMskMng_1.PrgsSchedMsgModbus IR384Read
PIV3762WrkHrs_Unit.WrkHrsUnit - Working hours; 32-bit (2 Modbus registers); Modbus IR385Read
PIV3763WrkHrs_Unit.WrkHrs_LeftUnit - Working hours left to the maintenance; 32-bit (2 ...; Modbus IR387Read
PIV3764WrkHrs_SupplyFan.WrkHrsSupply Fan - Working hours; 32-bit (2 Modbus registers); Modbus IR389Read
PIV3765WrkHrs_SupplyFan.WrkHrs_LeftSupply Fan - Working hours left to the maintenance; 32-bit ...; Modbus IR391Read
PIV3766WrkHrs_ReturnFan.WrkHrsReturn Fan - Working hours; 32-bit (2 Modbus registers); Modbus IR393Read
PIV3767WrkHrs_ReturnFan.WrkHrs_LeftReturn Fan - Working hours left to the maintenance; 32-bit ...; Modbus IR395Read
PIV3768WrkHrs_DirtyFilt.WrkHrsDirty filters - Working hours; 32-bit (2 Modbus registers); Modbus IR397Read
PIV3769WrkHrs_DirtyFilt.WrkHrs_LeftDirty filters - Working hours left to the maintenance; 32-bit ...; Modbus IR399Read
PIV3770WrkHrs_ThrmlWheel.WrkHrsThermal wheel - Working hours; 32-bit (2 Modbus registers); Modbus IR401Read
PIV3771WrkHrs_ThrmlWheel.WrkHrs_LeftThermal wheel - Working hours left to the maintenance; 32-bit ...; Modbus IR403Read
PIV3772WrkHrs_Comp.WrkHrsCompressor - Working hours; 32-bit (2 Modbus registers); Modbus IR405Read
PIV3773WrkHrs_Comp.WrkHrs_LeftCompressor - Working hours left to the maintenance; 32-bit (2 ...; Modbus IR407Read
PIV3774WrkHrs_IEC.WrkHrsIEC - Working hours; 32-bit (2 Modbus registers); Modbus IR409Read
PIV3775WrkHrs_IEC.WrkHrs_LeftIEC - Working hours left to the maintenance; 32-bit (2 ...; Modbus IR411Read
PIV3776WrkHrs_Humidifier.WrkHrsHumidifier - Working hours; 32-bit (2 Modbus registers); Modbus IR413Read
PIV3777WrkHrs_Humidifier.WrkHrs_LeftHumidifier - Working hours left to the maintenance; 32-bit (2 ...; Modbus IR415Read
PIV3778WrkHrs_AuxDout.WrkHrsAuxiliary digital output - Working hours; 32-bit (2 Modbus registers); Modbus IR417Read
PIV3779WrkHrs_AuxDout.WrkHrs_LeftAuxiliary digital output - Working hours left to the maintenance; ...; 32-bit; Modbus IR419Read
PIV3780WrkHrs_AuxAout.WrkHrsAuxiliary analogue output - Working hours; 32-bit (2 Modbus registers); Modbus IR421Read
PIV3781WrkHrs_AuxAout.WrkHrs_LeftAuxiliary analogue output - Working hours left to the maintenance; ...; 32-bit; Modbus IR423Read
PIV3782WrkHrs_MainCoilPmp1.WrkHrsMain coil pump 1 - Working hours; 32-bit (2 Modbus registers); Modbus IR425Read
PIV3783WrkHrs_MainCoilPmp1.WrkHrs_LeftMain coil pump 1 - Working hours left to the ...; 32-bit; Modbus IR427Read
PIV3784WrkHrs_MainCoilPmp2.WrkHrsMain coil pump 2 - Working hours; 32-bit (2 Modbus registers); Modbus IR429Read
PIV3785WrkHrs_MainCoilPmp2.WrkHrs_LeftMain coil pump 2 - Working hours left to the ...; 32-bit; Modbus IR431Read
PIV3786WrkHrs_MainCoilAout.WrkHrsMain coil analog output - Working hours; 32-bit (2 Modbus registers); Modbus IR433Read
PIV3787WrkHrs_MainCoilAout.WrkHrs_LeftMain coil analog output - Working hours left to the ...; 32-bit; Modbus IR435Read
PIV3788WrkHrs_MainCoilStep1.WrkHrsMain coil step 1 - Working hours; 32-bit (2 Modbus registers); Modbus IR437Read
PIV3789WrkHrs_MainCoilStep1.WrkHrs_LeftMain coil step 1 - Working hours left to the ...; 32-bit; Modbus IR439Read
PIV3790WrkHrs_MainCoilStep2.WrkHrsMain coil step 2 - Working hours; 32-bit (2 Modbus registers); Modbus IR441Read
PIV3791WrkHrs_MainCoilStep2.WrkHrs_LeftMain coil step 2 - Working hours left to the ...; 32-bit; Modbus IR443Read
PIV3792WrkHrs_MainCoilStep3.WrkHrsMain coil step 3 - Working hours; 32-bit (2 Modbus registers); Modbus IR445Read
PIV3793WrkHrs_MainCoilStep3.WrkHrs_LeftMain coil step 3 - Working hours left to the ...; 32-bit; Modbus IR447Read
PIV3794WrkHrs_MainCoilStep4.WrkHrsMain coil step 4 - Working hours; 32-bit (2 Modbus registers); Modbus IR449Read
PIV3795WrkHrs_MainCoilStep4.WrkHrs_LeftMain coil step 4 - Working hours left to the ...; 32-bit; Modbus IR451Read
PIV3796WrkHrs_PreHeatCoilPmp1.WrkHrsPre-heat coil pump 1 - Working hours; 32-bit (2 Modbus registers); Modbus IR453Read
PIV3797WrkHrs_PreHeatCoilPmp1.WrkHrs_LeftPre-heat coil pump 1 - Working hours left to the ...; 32-bit; Modbus IR455Read
PIV3798WrkHrs_PreHeatCoilPmp2.WrkHrsPre-heat coil pump 2 - Working hours; 32-bit (2 Modbus registers); Modbus IR457Read
PIV3799WrkHrs_PreHeatCoilPmp2.WrkHrs_LeftPre-heat coil pump 2 - Working hours left to the ...; 32-bit; Modbus IR459Read
PIV3800WrkHrs_PreHeatCoilAout.WrkHrsPre-heat coil analog output - Working hours; 32-bit (2 Modbus registers); Modbus IR461Read
PIV3801WrkHrs_PreHeatCoilAout.WrkHrs_LeftPre-heat coil analog output - Working hours left to the ...; 32-bit; Modbus IR463Read
PIV3802WrkHrs_PreHeatCoilStep1.WrkHrsPre-heat coil step 1 - Working hours; 32-bit (2 Modbus registers); Modbus IR465Read
PIV3803WrkHrs_PreHeatCoilStep1.WrkHrs_LeftPre-heat coil step 1 - Working hours left to the ...; 32-bit; Modbus IR467Read
PIV3804WrkHrs_PreHeatCoilStep2.WrkHrsPre-heat coil step 2 - Working hours; 32-bit (2 Modbus registers); Modbus IR469Read
PIV3805WrkHrs_PreHeatCoilStep2.WrkHrs_LeftPre-heat coil step 2 - Working hours left to the ...; 32-bit; Modbus IR471Read
PIV3806WrkHrs_PreHeatCoilStep3.WrkHrsPre-heat coil step 3 - Working hours; 32-bit (2 Modbus registers); Modbus IR473Read
PIV3807WrkHrs_PreHeatCoilStep3.WrkHrs_LeftPre-heat coil step 3 - Working hours left to the ...; 32-bit; Modbus IR475Read
PIV3808WrkHrs_PreHeatCoilStep4.WrkHrsPre-heat coil step 4 - Working hours; 32-bit (2 Modbus registers); Modbus IR477Read
PIV3809WrkHrs_PreHeatCoilStep4.WrkHrs_LeftPre-heat coil step 4 - Working hours left to the ...; 32-bit; Modbus IR479Read
PIV3810WrkHrs_ReHeatCoilPmp1.WrkHrsRe-heat coil pump 1 - Working hours; 32-bit (2 Modbus registers); Modbus IR481Read
PIV3811WrkHrs_ReHeatCoilPmp1.WrkHrs_LeftRe-heat coil pump 1 - Working hours left to the ...; 32-bit; Modbus IR483Read
PIV3812WrkHrs_ReHeatCoilPmp2.WrkHrsRe-heat coil pump 2 - Working hours; 32-bit (2 Modbus registers); Modbus IR485Read
PIV3813WrkHrs_ReHeatCoilPmp2.WrkHrs_LeftRe-heat coil pump 2 - Working hours left to the ...; 32-bit; Modbus IR487Read
PIV3814WrkHrs_ReHeatCoilAout.WrkHrsRe-heat coil analog output - Working hours; 32-bit (2 Modbus registers); Modbus IR489Read
PIV3815WrkHrs_ReHeatCoilAout.WrkHrs_LeftRe-heat coil analog output - Working hours left to the ...; 32-bit; Modbus IR491Read
PIV3816WrkHrs_ReHeatCoilStep1.WrkHrsRe-heat coil step 1 - Working hours; 32-bit (2 Modbus registers); Modbus IR493Read
PIV3817WrkHrs_ReHeatCoilStep1.WrkHrs_LeftRe-heat coil step 1 - Working hours left to the ...; 32-bit; Modbus IR495Read
PIV3818WrkHrs_ReHeatCoilStep2.WrkHrsRe-heat coil step 2 - Working hours; 32-bit (2 Modbus registers); Modbus IR497Read
PIV3819WrkHrs_ReHeatCoilStep2.WrkHrs_LeftRe-heat coil step 2 - Working hours left to the ...; 32-bit; Modbus IR499Read
PIV3820WrkHrs_ReHeatCoilStep3.WrkHrsRe-heat coil step 3 - Working hours; 32-bit (2 Modbus registers); Modbus IR501Read
PIV3821WrkHrs_ReHeatCoilStep3.WrkHrs_LeftRe-heat coil step 3 - Working hours left to the ...; 32-bit; Modbus IR503Read
PIV3822WrkHrs_ReHeatCoilStep4.WrkHrsRe-heat coil step 4 - Working hours; 32-bit (2 Modbus registers); Modbus IR505Read
PIV3823WrkHrs_ReHeatCoilStep4.WrkHrs_LeftRe-heat coil step 4 - Working hours left to the ...; 32-bit; Modbus IR507Read
IV3824GeneralMng.ErrParamImpExpError communication for Import/Export blocks; 32-bit (2 Modbus registers); Modbus IR509Read
PIV3825Ebmpapst_ReturnFan.ParamsChgComStatus_EBM_1.StatusNewAddrProc0:Check condition;1: Write new addr.; 2: Reboot fan firmware; 3: ...; Modbus IR511Read
PIV3826Ebmpapst_ReturnFan.ParamsChgComStatus_EBM_1.CommChangeStatus0:Idle; 1: Write password; 2:Write parameters; 3:Send adopt parameters; 4:Wait ...; Modbus IR512Read
PIV3827ZiehlAbegg_ReturnFan.FanStatus_ZA_1.CommChangeStatusFan status (working mode, errors) - Status of the COM ...; Modbus IR513Read
PIV3828Humisonic.HumCylinderWorkHrsLeftNumber of working hours left before check the humidifier cylinder; Modbus IR514Read
PIV3829Ebmpapst_SupplyFan.ParamsChgComStatus_EBM_1.StatusNewAddrProc0:Check condition;1: Write new addr.; 2: Reboot fan firmware; 3: ...; Modbus IR515Read
PIV3830Ebmpapst_SupplyFan.ParamsChgComStatus_EBM_1.CommChangeStatus0:Idle; 1: Write password; 2:Write parameters; 3:Send adopt parameters; 4:Wait ...; Modbus IR516Read
PIV3831ZiehlAbegg_SupplyFan.FanStatus_ZA_1.CommChangeStatusFan status (working mode, errors) - Status of the COM ...; Modbus IR517Read
PIV3832VDI_Conf[0].CntDwnCountdown before the next inspection; Modbus IR518Read
PIV3833VDI_Conf[1].CntDwnCountdown before the next inspection; Modbus IR519Read
PIV3834VDI_Conf[2].CntDwnCountdown before the next inspection; Modbus IR520Read
PIV3835VDI_Conf[3].CntDwnCountdown before the next inspection; Modbus IR521Read
PIV3836VDI_Conf[4].CntDwnCountdown before the next inspection; Modbus IR522Read
PIV3837VDI_Conf[5].CntDwnCountdown before the next inspection; Modbus IR523Read
PIV3838VDI_Conf[6].CntDwnCountdown before the next inspection; Modbus IR524Read
PIV3839VDI_Conf[7].CntDwnCountdown before the next inspection; Modbus IR525Read
PIV3840VDI_Conf[8].CntDwnCountdown before the next inspection; Modbus IR526Read
PIV3841VDI_Conf[9].CntDwnCountdown before the next inspection; Modbus IR527Read
PIV3842VDI_Conf[10].CntDwnCountdown before the next inspection; Modbus IR528Read
PIV3843VDI_Conf[11].CntDwnCountdown before the next inspection; Modbus IR529Read
PIV3844VDI_Conf[12].CntDwnCountdown before the next inspection; Modbus IR530Read
PIV3845VDI_Conf[13].CntDwnCountdown before the next inspection; Modbus IR531Read
PIV3846VDI_Conf[14].CntDwnCountdown before the next inspection; Modbus IR532Read
PIV3847VDI_Conf[15].CntDwnCountdown before the next inspection; Modbus IR533Read
PIV3848VDI_Conf[16].CntDwnCountdown before the next inspection; Modbus IR534Read
PIV3849VDI_Conf[17].CntDwnCountdown before the next inspection; Modbus IR535Read
PIV3850VDI_Conf[18].CntDwnCountdown before the next inspection; Modbus IR536Read
PIV3851VDI_Conf[19].CntDwnCountdown before the next inspection; Modbus IR537Read
PIV3852VDI_Conf[20].CntDwnCountdown before the next inspection; Modbus IR538Read
PIV3853VDI_Conf[21].CntDwnCountdown before the next inspection; Modbus IR539Read
PIV3854VDI_Conf[22].CntDwnCountdown before the next inspection; Modbus IR540Read
PIV3855VDI_Conf[23].CntDwnCountdown before the next inspection; Modbus IR541Read
PIV3856VDI_Conf[24].CntDwnCountdown before the next inspection; Modbus IR542Read
PIV3857VDI_Conf[25].CntDwnCountdown before the next inspection; Modbus IR543Read
PIV3858VDI_Conf[26].CntDwnCountdown before the next inspection; Modbus IR544Read
PIV3859VDI_Conf[27].CntDwnCountdown before the next inspection; Modbus IR545Read
PIV3860VDI_Conf[28].CntDwnCountdown before the next inspection; Modbus IR546Read
PIV3861GeneralMng.RTC_BMS.SecondBMS real time clock; Modbus IR547Read
PIV3862GeneralMng.Zone_ReadIndex of the zone read; Modbus IR548Read
IV3863GeneralMng.SPV_ErrorBMS error; Modbus IR549Read
PIV3864GeneralMng.IP_Byte4Automatically generated; Modbus IR550Read
PIV3865GeneralMng.IP_Byte3Automatically generated; Modbus IR551Read
PIV3866GeneralMng.IP_Byte2Automatically generated; Modbus IR552Read
PIV3867GeneralMng.IP_Byte1Automatically generated; Modbus IR553Read
PIV3868GeneralMng.GW_Byte4Automatically generated; Modbus IR554Read
PIV3869GeneralMng.GW_Byte3Automatically generated; Modbus IR555Read
PIV3870GeneralMng.GW_Byte2Automatically generated; Modbus IR556Read
PIV3871GeneralMng.GW_Byte1Automatically generated; Modbus IR557Read
PIV3872GeneralMng.NMSK_Byte4Automatically generated; Modbus IR558Read
PIV3873GeneralMng.NMSK_Byte3Automatically generated; Modbus IR559Read
PIV3874GeneralMng.NMSK_Byte2Automatically generated; Modbus IR560Read
PIV3875GeneralMng.NMSK_Byte1Automatically generated; Modbus IR561Read
PIV3876GeneralMng.DNS_Byte4Automatically generated; Modbus IR562Read
PIV3877GeneralMng.DNS_Byte3Automatically generated; Modbus IR563Read
PIV3878GeneralMng.DNS_Byte2Automatically generated; Modbus IR564Read
PIV3879GeneralMng.DNS_Byte1Automatically generated; Modbus IR565Read
IV3880Data_EVD_Emb_1.Superparameters.MainRegulation.ValSuperparameters - Main regulation; Modbus IR566Read
AV3881Data_EVD_Emb_1.Inputs.S1.ValProbes data - Probe S1 - Value; Modbus IR567Read
AV3882Data_EVD_Emb_1.Inputs.S2.ValProbes data - Probe S2 - Value; Modbus IR568Read
AV3883Data_EVD_Emb_1.Inputs.S3.ValProbes data - Probe S3 - Value; Modbus IR569Read
AV3884Data_EVD_Emb_1.Inputs.S4.ValProbes data - Probe S4 - Value; Modbus IR570Read
PIV3885BLDC_compressor.IRparam_PWRP1.IR104_DriveStatus0: Stop; 1: Run; 2: Alarm; 3: Crankcase heating; 4:DCbus ready); Modbus IR571Read
AV3886BLDC_compressor.Info_PWRP1.Info_DriveTempInverter Power Plus Info - Drive temperature; Modbus IR572Read
PIV3887BLDC_compressor.IRparam_PWRP1.IR105_AlrmCodesee doc; Modbus IR573Read
AV3888BLDC_compressor.Info_PWRP1.Info_FreqSetPInverter Power Plus Info - Speed reference [Hz/rps]; Modbus IR574Read
AV3889BLDC_compressor.Info_PWRP1.Info_RotorSpeed_HzInverter Power Plus Info - Current rotor speed [Hz]; Modbus IR575Read
PIV3890BLDC_compressor.Info_PWRP1.Info_RotorSpeed_rpmInverter Power Plus Info - Current rotorspeed [rpm]; Modbus IR576Read
AV3891BLDC_compressor.Info_PWRP1.Info_MotAInverter Power Plus Info - Current motor current [A]; Modbus IR577Read
PIV3892BLDC_compressor.Info_PWRP1.Info_MotVInverter Power Plus Info - Current motor voltage [V]; Modbus IR578Read
AV3893BLDC_compressor.Info_PWRP1.Info_MotPwrInverter Power Plus Info - Current motor consumption [W]; Modbus IR579Read
PIV3894BLDC_compressor.IRparam_PWRP1.IR113_DCBusVoltageDC bus voltage; Modbus IR580Read
PIV3895BLDC_compressor.IRparam_PWRP1.IR134_DCBusRippleDC bus ripple; Modbus IR581Read
PIV3896BLDC_compressor.IRparam_PWRP1.IR124_OperatingSwitchingFreqPWM switching frequency (0: 4kHz, 1: 6kHz, 2: 8kHz); Modbus IR582Read
AV3897BLDC_compressor.IRparam_PWRP1.IR125_PreRampOutput_SpeedRefPre-ramp output frequency reference; Modbus IR583Read
AV3898BLDC_compressor.IRparam_PWRP1.IR153_OvldMot_accumulatorMotor Overload Accumulator; Modbus IR584Read
AV3899BLDC_compressor.IRparam_PWRP1.IR154_OvldDrive_accumulatorDrive Overload Accumulator; Modbus IR585Read
AV3900BLDC_compressor.Info_PWRP1.Info_PSD_AAaInverter Power Plus Info - Device rated current [AA.a]; Modbus IR586Read
PIV3901BLDC_compressor.Info_PWRP1.Mng_MotSelect_AAaInverter Power Plus Info - Rated current of compressor; Modbus IR587Read
AV3902BLDC_compressor.Info_PWRP1.UI_RatedStartingAInverter Power Plus Info - Rated starting current; Modbus IR588Read
AV3903BLDC_compressor.Info_PWRP1.UI_RatedCrankCaseHeatAInverter Power Plus Info - Rated crankcase heating current; Modbus IR589Read
AV3904BLDC_compressor.Info_PWRP1.UI_RatedInductsatReductAInverter Power Plus Info - Inductance saturation reduction (percentage at ...; Modbus IR590Read
PIV3905BLDC_compressor.Info_PWRP1.Dbg_FBVersion_XInverter Power Plus Info - FB version x; Modbus IR591Read
PIV3906BLDC_compressor.Info_PWRP1.Dbg_FBVersion_YInverter Power Plus Info - FB version y; Modbus IR592Read
PIV3907BLDC_compressor.Info_PWRP1.Dbg_FBVersion_ZInverter Power Plus Info - FB version zzz; Modbus IR593Read
PIV3908BLDC_compressor.Info_PWRP1.Dbg_FBVersion_BetaInverter Power Plus Info - FB version beta; Modbus IR594Read
PIV3909BLDC_compressor.IRparam_PWRP1.IR141_BootLoaderReleaseBootloader version; Modbus IR595Read
PIV3910BLDC_compressor.IRparam_PWRP1.IR142_FirmwareReleaseFirmware version; Modbus IR596Read
PIV3911BLDC_compressor.IRparam_PWRP1.IR143_FirmwareCRCFirmware checksum; Modbus IR597Read
PIV3912BLDC_compressor.IRparam_PWRP1.IR144_MotCtrlReleaseMotor control version; Modbus IR598Read
PIV3913BLDC_compressor.IRparam_PWRP1.IR149_HardwareIdentificationHardware identification; Modbus IR599Read
AV3914Info_BLDC1.Info_CompRequestBLDC informations - Compressor power request [%]; Modbus IR600Read
AV3915Info_BLDC1.Info_ReqSpeedToPWRPBLDC informations - Required speed to PowerPlus [%]; Modbus IR601Read
AV3916Info_BLDC1.Press_DscgP_BarBLDC informations - Discharge pressure relative [bar]; Modbus IR602Read
AV3917Info_BLDC1.Press_SuctP_BarBLDC informations - Suction pressure relative [bar]; Modbus IR603Read
IV3918Info_BLDC1.Info_EnvZoneBLDC informations - Current envelope zone; Modbus IR604Read
IV3919Info_BLDC1.Time_CntDwnOutEnvBLDC informations - Out of envelop timing countdown; Modbus IR605Read
AV3920Info_BLDC1.Press_DeltaPBLDC informations - Current delta pressure; Modbus IR606Read
AV3921Info_BLDC1.Press_RatioPBLDC informations - Current pressure ratio; Modbus IR607Read
IV3922Info_BLDC1.Time_CntDwnDeltaPAlrmBLDC informations - Low pressure difference alarm timing countdown; Modbus IR608Read
AV3923Info_BLDC1.Info_DscgTempBLDC informations - Current discharge temperature; Modbus IR609Read
IV3924Info_BLDC1.Info_HTZoneBLDC informations - High discharge temperature zone; Modbus IR610Read
AV3925Info_BLDC1.Info_ActiveDscgHTLimBLDC informations - Show active value of discharge temp. alarm ...; Modbus IR611Read
AV3926Info_BLDC1.Info_DscgSHBLDC informations - Current discharge superheat; Modbus IR612Read
PIV3927Info_BLDC1.Dbg_FBVersion_XBLDC informations - Debug: FB version x; Modbus IR613Read
PIV3928Info_BLDC1.Dbg_FBVersion_YBLDC informations - Debug: FB version y; Modbus IR614Read
PIV3929Info_BLDC1.Dbg_FBVersion_ZBLDC informations - Debug: FB version z; Modbus IR615Read
PIV3930Info_BLDC1.Dbg_FBVersion_BetaBLDC informations - Debug: FB version beta; Modbus IR616Read
PIV3931GeneralMng.BACnet_ID_MaxBACnet maximum ID (MSTP: 127; IP: 4194303); 32-bit (2 Modbus registers); Modbus IR617Read
AV3947MainVlv_PercMain coil floating valve: Estimating position valve; Modbus IR619Read
AV3948PreHeatVlv_PercPreHeat coil floating valve: Estimating position valve; Modbus IR620Read
AV3949ReHeatVlv_PercReHeat coil floating valve: Estimating position valve; Modbus IR621Read
AV4033SupplyTempRegSetPTemperature compensated setpoint; Modbus IR622Read
AV4034TempRegTemperature regulation; Modbus IR623Read
PIV3987AirQuality_PM10.Uom_WAir quality: PM 10 - Uom; Modbus IR624Read
AV3988AirQuality_PM10.Val_Hw_RAir quality: PM 10 - Value reads from board; Modbus IR625Read
AV3989AirQuality_PM10.Val_RAir quality: PM 10; Modbus IR626Read
PIV4001AirQuality_PM25.Uom_WAir quality: PM 2.5 - Uom; Modbus IR627Read
AV4002AirQuality_PM25.Val_Hw_RAir quality: PM 2.5 - Value reads from board; Modbus IR628Read
AV4003AirQuality_PM25.Val_RAir quality: PM 2.5; Modbus IR629Read
PIV3964WrkHrs_SanificationDevice.WrkHrsSanification device - Working hours; 32-bit (2 Modbus registers); Modbus IR630Read
PIV3966WrkHrs_SanificationDevice.WrkHrs_LeftSanification device - Working hours left to the maintenance; 32-bit ...; Modbus IR632Read
IV4077EBM_AlrmCode_SupplyFan1EBM alarms code number - Fan Supply 1; Modbus IR634Read
PIV4078Ebmpapst_SupplyFan.SenVal_EBM_1.AnemometerSpeedEBM1 Supply - Ebmpapst sensors values - Anemometer speed (only RadiCal); Modbus IR635Read
PIV4079Ebmpapst_SupplyFan.SenVal_EBM_1.AirFlowEBM1 Supply - Ebmpapst sensors values - Air flow (only RadiCal); Modbus IR636Read
PIV4080Ebmpapst_SupplyFan.SenVal_EBM_1.MassFlowEBM1 Supply - Ebmpapst sensors values - Mass flow (only RadiCal); Modbus IR637Read
IV4081EBM_AlrmCode_ReturnFan1EBM alarms code number - Fan Return 1; Modbus IR638Read
PIV4082Ebmpapst_ReturnFan.SenVal_EBM_1.AnemometerSpeedEBM1 Return - Ebmpapst sensors values - Anemometer speed (only RadiCal); Modbus IR639Read
PIV4083Ebmpapst_ReturnFan.SenVal_EBM_1.AirFlowEBM1 Return - Ebmpapst sensors values - Air flow (only RadiCal); Modbus IR640Read
PIV4084Ebmpapst_ReturnFan.SenVal_EBM_1.MassFlowEBM1 Return - Ebmpapst sensors values - Mass flow (only RadiCal); Modbus IR641Read
PIV4085Ebmpapst_SupplyFan.InfoSpeed_EBM_2.CurrSpeedEBM2 Supply - Speed info of the Ebmpapst fan - ...; Modbus IR642Read
PIV4086Ebmpapst_SupplyFan.ElectrInfo_EBM_2.DC_Link_VEBM2 Supply - Electrical info - DC link voltage for ...; Modbus IR643Read
PIV4087Ebmpapst_SupplyFan.ElectrInfo_EBM_2.DC_Link_AEBM2 Supply - Electrical info - DC link current for ...; Modbus IR644Read
PIV4088Ebmpapst_SupplyFan.ElectrInfo_EBM_2.CurrPowerEBM2 Supply - Electrical info - Current power in [W] ...; Modbus IR645Read
PIV4089Ebmpapst_SupplyFan.ElectrInfo_EBM_2.ElectrTempEBM2 Supply - Electrical info - Internal circuit temperature for ...; Modbus IR646Read
PIV4090Ebmpapst_SupplyFan.MotStatus_EBM_2.IR_MotStatusEBM2 Supply - Motor status defines errors currently detected for ...; Modbus IR647Read
PIV4091Ebmpapst_SupplyFan.Warn_EBM_2.IR_WarnEBM2 Supply - Warning bitfield variable for Ebmpast fan - ...; Modbus IR648Read
PIV4092Ebmpapst_SupplyFan.InfoSpeed_EBM_2.MaxSpeedEBM2 Supply - Speed info of the Ebmpapst fan - ...; Modbus IR649Read
PIV4093Ebmpapst_SupplyFan.CntWorkHrsBkp_EBM_2EBM2 Supply - Working hour counter for Ebmpapst fan; Modbus IR650Read
PIV4094Ebmpapst_SupplyFan.SenVal_EBM_2.AnemometerSpeedEBM2 Supply - Ebmpapst sensors values - Anemometer speed (only RadiCal); Modbus IR651Read
PIV4095Ebmpapst_SupplyFan.SenVal_EBM_2.AirFlowEBM2 Supply - Ebmpapst sensors values - Air flow (only RadiCal); Modbus IR652Read
PIV4096Ebmpapst_SupplyFan.SenVal_EBM_2.MassFlowEBM2 Supply - Ebmpapst sensors values - Mass flow (only RadiCal); Modbus IR653Read
PIV4097ComStatus_Supply_EBM_2EBM2 Supply - Communication status of supply ebm fan (0:Online; ...; Modbus IR654Read
IV4098EBM_AlrmCode_SupplyFan2EBM alarms code number - Fan Supply 2; Modbus IR655Read
PIV4099Ebmpapst_SupplyFan.InfoSpeed_EBM_3.CurrSpeedEBM3 Supply - Speed info of the Ebmpapst fan - ...; Modbus IR656Read
PIV4100Ebmpapst_SupplyFan.ElectrInfo_EBM_3.DC_Link_VEBM3 Supply - Electrical info - DC link voltage for ...; Modbus IR657Read
PIV4101Ebmpapst_SupplyFan.ElectrInfo_EBM_3.DC_Link_AEBM3 Supply - Electrical info - DC link current for ...; Modbus IR658Read
PIV4102Ebmpapst_SupplyFan.ElectrInfo_EBM_3.CurrPowerEBM3 Supply - Electrical info - Current power in [W] ...; Modbus IR659Read
PIV4103Ebmpapst_SupplyFan.ElectrInfo_EBM_3.ElectrTempEBM3 Supply - Electrical info - Internal circuit temperature for ...; Modbus IR660Read
PIV4104Ebmpapst_SupplyFan.MotStatus_EBM_3.IR_MotStatusEBM3 Supply - Motor status defines errors currently detected for ...; Modbus IR661Read
PIV4105Ebmpapst_SupplyFan.Warn_EBM_3.IR_WarnEBM3 Supply - Warning bitfield variable for Ebmpast fan - ...; Modbus IR662Read
PIV4106Ebmpapst_SupplyFan.InfoSpeed_EBM_3.MaxSpeedEBM3 Supply - Speed info of the Ebmpapst fan - ...; Modbus IR663Read
PIV4107Ebmpapst_SupplyFan.CntWorkHrsBkp_EBM_3EBM3 Supply - Working hour counter for Ebmpapst fan; Modbus IR664Read
PIV4108Ebmpapst_SupplyFan.SenVal_EBM_3.AnemometerSpeedEBM3 Supply - Ebmpapst sensors values - Anemometer speed (only RadiCal); Modbus IR665Read
PIV4109Ebmpapst_SupplyFan.SenVal_EBM_3.AirFlowEBM3 Supply - Ebmpapst sensors values - Air flow (only RadiCal); Modbus IR666Read
PIV4110Ebmpapst_SupplyFan.SenVal_EBM_3.MassFlowEBM3 Supply - Ebmpapst sensors values - Mass flow (only RadiCal); Modbus IR667Read
PIV4111ComStatus_Supply_EBM_3EBM3 Supply - Communication status of supply ebm fan (0:Online; ...; Modbus IR668Read
IV4112EBM_AlrmCode_SupplyFan3EBM alarms code number - Fan Supply 3; Modbus IR669Read
PIV4113Ebmpapst_SupplyFan.InfoSpeed_EBM_4.CurrSpeedEBM4 Supply - Speed info of the Ebmpapst fan - ...; Modbus IR670Read
PIV4114Ebmpapst_SupplyFan.ElectrInfo_EBM_4.DC_Link_VEBM4 Supply - Electrical info - DC link voltage for ...; Modbus IR671Read
PIV4115Ebmpapst_SupplyFan.ElectrInfo_EBM_4.DC_Link_AEBM4 Supply - Electrical info - DC link current for ...; Modbus IR672Read
PIV4116Ebmpapst_SupplyFan.ElectrInfo_EBM_4.CurrPowerEBM4 Supply - Electrical info - Current power in [W] ...; Modbus IR673Read
PIV4117Ebmpapst_SupplyFan.ElectrInfo_EBM_4.ElectrTempEBM4 Supply - Electrical info - Internal circuit temperature for ...; Modbus IR674Read
PIV4118Ebmpapst_SupplyFan.MotStatus_EBM_4.IR_MotStatusEBM4 Supply - Motor status defines errors currently detected for ...; Modbus IR675Read
PIV4119Ebmpapst_SupplyFan.Warn_EBM_4.IR_WarnEBM4 Supply - Warning bitfield variable for Ebmpast fan - ...; Modbus IR676Read
PIV4120Ebmpapst_SupplyFan.InfoSpeed_EBM_4.MaxSpeedEBM4 Supply - Speed info of the Ebmpapst fan - ...; Modbus IR677Read
PIV4121Ebmpapst_SupplyFan.CntWorkHrsBkp_EBM_4EBM4 Supply - Working hour counter for Ebmpapst fan; Modbus IR678Read
PIV4122Ebmpapst_SupplyFan.SenVal_EBM_4.AnemometerSpeedEBM4 Supply - Ebmpapst sensors values - Anemometer speed (only RadiCal); Modbus IR679Read
PIV4123Ebmpapst_SupplyFan.SenVal_EBM_4.AirFlowEBM4 Supply - Ebmpapst sensors values - Air flow (only RadiCal); Modbus IR680Read
PIV4124Ebmpapst_SupplyFan.SenVal_EBM_4.MassFlowEBM4 Supply - Ebmpapst sensors values - Mass flow (only RadiCal); Modbus IR681Read
PIV4125ComStatus_Supply_EBM_4EBM4 Supply - Communication status of supply ebm fan (0:Online; ...; Modbus IR682Read
IV4126EBM_AlrmCode_SupplyFan4EBM alarms code number - Fan Supply 4; Modbus IR683Read
PIV4127Ebmpapst_ReturnFan.InfoSpeed_EBM_2.CurrSpeedEBM2 Return - Speed info of the Ebmpapst fan - ...; Modbus IR684Read
PIV4128Ebmpapst_ReturnFan.ElectrInfo_EBM_2.DC_Link_VEBM2 Return - Electrical info - DC link voltage for ...; Modbus IR685Read
PIV4129Ebmpapst_ReturnFan.ElectrInfo_EBM_2.DC_Link_AEBM2 Return - Electrical info - DC link current for ...; Modbus IR686Read
PIV4130Ebmpapst_ReturnFan.ElectrInfo_EBM_2.CurrPowerEBM2 Return - Electrical info - Current power in [W] ...; Modbus IR687Read
PIV4131Ebmpapst_ReturnFan.ElectrInfo_EBM_2.ElectrTempEBM2 Return - Electrical info - Internal circuit temperature for ...; Modbus IR688Read
PIV4132Ebmpapst_ReturnFan.MotStatus_EBM_2.IR_MotStatusEBM2 Return - Motor status defines errors currently detected for ...; Modbus IR689Read
PIV4133Ebmpapst_ReturnFan.Warn_EBM_2.IR_WarnEBM2 Return - Warning bitfield variable for Ebmpast fan - ...; Modbus IR690Read
PIV4134Ebmpapst_ReturnFan.InfoSpeed_EBM_2.MaxSpeedEBM2 Return - Speed info of the Ebmpapst fan - ...; Modbus IR691Read
PIV4135Ebmpapst_ReturnFan.CntWorkHrsBkp_EBM_2EBM2 Return - Working hour counter for Ebmpapst fan; Modbus IR692Read
PIV4136Ebmpapst_ReturnFan.SenVal_EBM_2.AnemometerSpeedEBM2 Return - Ebmpapst sensors values - Anemometer speed (only RadiCal); Modbus IR693Read
PIV4137Ebmpapst_ReturnFan.SenVal_EBM_2.AirFlowEBM2 Return - Ebmpapst sensors values - Air flow (only RadiCal); Modbus IR694Read
PIV4138Ebmpapst_ReturnFan.SenVal_EBM_2.MassFlowEBM2 Return - Ebmpapst sensors values - Mass flow (only RadiCal); Modbus IR695Read
PIV4139ComStatus_Return_EBM_2EBM2 Return - Communication status of return ebm fan (0:Online; ...; Modbus IR696Read
IV4140EBM_AlrmCode_ReturnFan2EBM alarms code number - Fan Return 2; Modbus IR697Read
PIV4141Ebmpapst_ReturnFan.InfoSpeed_EBM_3.CurrSpeedEBM3 Return - Speed info of the Ebmpapst fan - ...; Modbus IR698Read
PIV4142Ebmpapst_ReturnFan.ElectrInfo_EBM_3.DC_Link_VEBM3 Return - Electrical info - DC link voltage for ...; Modbus IR699Read
PIV4143Ebmpapst_ReturnFan.ElectrInfo_EBM_3.DC_Link_AEBM3 Return - Electrical info - DC link current for ...; Modbus IR700Read
PIV4144Ebmpapst_ReturnFan.ElectrInfo_EBM_3.CurrPowerEBM3 Return - Electrical info - Current power in [W] ...; Modbus IR701Read
PIV4145Ebmpapst_ReturnFan.ElectrInfo_EBM_3.ElectrTempEBM3 Return - Electrical info - Internal circuit temperature for ...; Modbus IR702Read
PIV4146Ebmpapst_ReturnFan.MotStatus_EBM_3.IR_MotStatusEBM3 Return - Motor status defines errors currently detected for ...; Modbus IR703Read
PIV4147Ebmpapst_ReturnFan.Warn_EBM_3.IR_WarnEBM3 Return - Warning bitfield variable for Ebmpast fan - ...; Modbus IR704Read
PIV4148Ebmpapst_ReturnFan.InfoSpeed_EBM_3.MaxSpeedEBM3 Return - Speed info of the Ebmpapst fan - ...; Modbus IR705Read
PIV4149Ebmpapst_ReturnFan.CntWorkHrsBkp_EBM_3EBM3 Return - Working hour counter for Ebmpapst fan; Modbus IR706Read
PIV4150Ebmpapst_ReturnFan.SenVal_EBM_3.AnemometerSpeedEBM3 Return - Ebmpapst sensors values - Anemometer speed (only RadiCal); Modbus IR707Read
PIV4151Ebmpapst_ReturnFan.SenVal_EBM_3.AirFlowEBM3 Return - Ebmpapst sensors values - Air flow (only RadiCal); Modbus IR708Read
PIV4152Ebmpapst_ReturnFan.SenVal_EBM_3.MassFlowEBM3 Return - Ebmpapst sensors values - Mass flow (only RadiCal); Modbus IR709Read
PIV4153ComStatus_Return_EBM_3EBM3 Return - Communication status of return ebm fan (0:Online; ...; Modbus IR710Read
IV4154EBM_AlrmCode_ReturnFan3EBM alarms code number - Fan Return 3; Modbus IR711Read
PIV4155Ebmpapst_ReturnFan.InfoSpeed_EBM_4.CurrSpeedEBM4 Return - Speed info of the Ebmpapst fan - ...; Modbus IR712Read
PIV4156Ebmpapst_ReturnFan.ElectrInfo_EBM_4.DC_Link_VEBM4 Return - Electrical info - DC link voltage for ...; Modbus IR713Read
PIV4157Ebmpapst_ReturnFan.ElectrInfo_EBM_4.DC_Link_AEBM4 Return - Electrical info - DC link current for ...; Modbus IR714Read
PIV4158Ebmpapst_ReturnFan.ElectrInfo_EBM_4.CurrPowerEBM4 Return - Electrical info - Current power in [W] ...; Modbus IR715Read
PIV4159Ebmpapst_ReturnFan.ElectrInfo_EBM_4.ElectrTempEBM4 Return - Electrical info - Internal circuit temperature for ...; Modbus IR716Read
PIV4160Ebmpapst_ReturnFan.MotStatus_EBM_4.IR_MotStatusEBM4 Return - Motor status defines errors currently detected for ...; Modbus IR717Read
PIV4161Ebmpapst_ReturnFan.Warn_EBM_4.IR_WarnEBM4 Return - Warning bitfield variable for Ebmpast fan - ...; Modbus IR718Read
PIV4162Ebmpapst_ReturnFan.InfoSpeed_EBM_4.MaxSpeedEBM4 Return - Speed info of the Ebmpapst fan - ...; Modbus IR719Read
PIV4163Ebmpapst_ReturnFan.CntWorkHrsBkp_EBM_4EBM4 Return - Working hour counter for Ebmpapst fan; Modbus IR720Read
PIV4164Ebmpapst_ReturnFan.SenVal_EBM_4.AnemometerSpeedEBM4 Return - Ebmpapst sensors values - Anemometer speed (only RadiCal); Modbus IR721Read
PIV4165Ebmpapst_ReturnFan.SenVal_EBM_4.AirFlowEBM4 Return - Ebmpapst sensors values - Air flow (only RadiCal); Modbus IR722Read
PIV4166Ebmpapst_ReturnFan.SenVal_EBM_4.MassFlowEBM4 Return - Ebmpapst sensors values - Mass flow (only RadiCal); Modbus IR723Read
PIV4167ComStatus_Return_EBM_4EBM4 Return - Communication status of return ebm fan (0:Online; ...; Modbus IR724Read
IV4168EBM_AlrmCode_ReturnFan4EBM alarms code number - Fan Return 4; Modbus IR725Read
IV4169ZA_AlrmCode_SupplyFan1ZA alarms code number - Fan Supply 1; Modbus IR726Read
IV4170ZA_AlrmCode_ReturnFan1ZA alarms code number - Fan Return 1; Modbus IR727Read
PIV4171ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_2.CurrSpeed_rpmZA2 Supply - Fan speed informations - Actual speed [rpm] ...; Modbus IR728Read
PIV4172ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.DC_LinkVZA2 Supply - Fan electrical informations - DC link voltage (V); Modbus IR729Read
PIV4173ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.LineVZA2 Supply - Fan electrical informations - Supply voltage (peak voltage); Modbus IR730Read
PIV4174ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_2.MaxSpeed_rpmZA2 Supply - Fan speed informations - Maximum set speed; Modbus IR731Read
PIV4175ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_2.MinSpeed_rpmZA2 Supply - Fan speed informations - Minimum set speed; Modbus IR732Read
PIV4176ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.MotPwrZA2 Supply - Fan electrical informations - Motor input power (W); Modbus IR733Read
IV4177ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.ElectronicTempZA2 Supply - Fan electrical informations - Electronics temperature (°C); Modbus IR734Read
IV4178ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.IGBT_tempZA2 Supply - Fan electrical informations - IGBT temperature (°C); Modbus IR735Read
IV4179ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.MCU_TempZA2 Supply - Fan electrical informations - MCU temperature; Modbus IR736Read
IV4180ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.MotTempZA2 Supply - Fan electrical informations - Motr temperature (°C); Modbus IR737Read
PIV4181FanAlrm_ZA_SupplyFan_2.ErrStatusZA2 supply - Fan alarms - Error status defines errors ...; Modbus IR738Read
PIV4182ZiehlAbegg_SupplyFan.FanStatus_ZA_2.WorkingStatusZA2 Supply - Fan status - Working status defines current ...; Modbus IR739Read
PIV4183ZiehlAbegg_SupplyFan.FanStatus_ZA_2.WorkStatusCodeZA2 Supply - Fan status - Working status code; Modbus IR740Read
IV4184ZA_AlrmCode_SupplyFan2ZA alarms code number - Fan Supply 2; Modbus IR741Read
PIV4185ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_3.CurrSpeed_rpmZA3 Supply - Fan speed informations - Actual speed [rpm] ...; Modbus IR742Read
PIV4186ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.DC_LinkVZA3 Supply - Fan electrical informations - DC link voltage (V); Modbus IR743Read
PIV4187ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.LineVZA3 Supply - Fan electrical informations - Supply voltage (peak voltage); Modbus IR744Read
PIV4188ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_3.MaxSpeed_rpmZA3 Supply - Fan speed informations - Maximum set speed; Modbus IR745Read
PIV4189ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_3.MinSpeed_rpmZA3 Supply - Fan speed informations - Minimum set speed; Modbus IR746Read
PIV4190ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.MotPwrZA3 Supply - Fan electrical informations - Motor input power (W); Modbus IR747Read
IV4191ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.ElectronicTempZA3 Supply - Fan electrical informations - Electronics temperature (°C); Modbus IR748Read
IV4192ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.IGBT_tempZA3 Supply - Fan electrical informations - IGBT temperature (°C); Modbus IR749Read
IV4193ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.MCU_TempZA3 Supply - Fan electrical informations - MCU temperature; Modbus IR750Read
IV4194ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.MotTempZA3 Supply - Fan electrical informations - Motr temperature (°C); Modbus IR751Read
PIV4195FanAlrm_ZA_SupplyFan_3.ErrStatusZA3 supply - Fan alarms - Error status defines errors ...; Modbus IR752Read
PIV4196ZiehlAbegg_SupplyFan.FanStatus_ZA_3.WorkingStatusZA3 Supply - Fan status - Working status defines current ...; Modbus IR753Read
PIV4197ZiehlAbegg_SupplyFan.FanStatus_ZA_3.WorkStatusCodeZA3 Supply - Fan status - Working status code; Modbus IR754Read
IV4198ZA_AlrmCode_SupplyFan3ZA alarms code number - Fan Supply 3; Modbus IR755Read
PIV4199ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_4.CurrSpeed_rpmZA4 Supply - Fan speed informations - Actual speed [rpm] ...; Modbus IR756Read
PIV4200ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.DC_LinkVZA4 Supply - Fan electrical informations - DC link voltage (V); Modbus IR757Read
PIV4201ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.LineVZA4 Supply - Fan electrical informations - Supply voltage (peak voltage); Modbus IR758Read
PIV4202ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_4.MaxSpeed_rpmZA4 Supply - Fan speed informations - Maximum set speed; Modbus IR759Read
PIV4203ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_4.MinSpeed_rpmZA4 Supply - Fan speed informations - Minimum set speed; Modbus IR760Read
PIV4204ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.MotPwrZA4 Supply - Fan electrical informations - Motor input power (W); Modbus IR761Read
IV4205ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.ElectronicTempZA4 Supply - Fan electrical informations - Electronics temperature (°C); Modbus IR762Read
IV4206ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.IGBT_tempZA4 Supply - Fan electrical informations - IGBT temperature (°C); Modbus IR763Read
IV4207ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.MCU_TempZA4 Supply - Fan electrical informations - MCU temperature; Modbus IR764Read
IV4208ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.MotTempZA4 Supply - Fan electrical informations - Motr temperature (°C); Modbus IR765Read
PIV4209FanAlrm_ZA_SupplyFan_4.ErrStatusZA4 supply - Fan alarms - Error status defines errors ...; Modbus IR766Read
PIV4210ZiehlAbegg_SupplyFan.FanStatus_ZA_4.WorkingStatusZA4 Supply - Fan status - Working status defines current ...; Modbus IR767Read
PIV4211ZiehlAbegg_SupplyFan.FanStatus_ZA_4.WorkStatusCodeZA4 Supply - Fan status - Working status code; Modbus IR768Read
IV4212ZA_AlrmCode_SupplyFan4ZA alarms code number - Fan Supply 4; Modbus IR769Read
PIV4213ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_2.CurrSpeed_rpmZA2 Return - Fan speed informations - Actual speed [rpm] ...; Modbus IR770Read
PIV4214ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.DC_LinkVZA2 Return - Fan electrical informations - DC link voltage (V); Modbus IR771Read
PIV4215ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.LineVZA2 Return - Fan electrical informations - Supply voltage (peak voltage); Modbus IR772Read
PIV4216ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_2.MaxSpeed_rpmZA2 Return - Fan speed informations - Maximum set speed; Modbus IR773Read
PIV4217ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_2.MinSpeed_rpmZA2 Return - Fan speed informations - Minimum set speed; Modbus IR774Read
PIV4218ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.MotPwrZA2 Return - Fan electrical informations - Motor input power (W); Modbus IR775Read
IV4219ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.ElectronicTempZA2 Return - Fan electrical informations - Electronics temperature (°C); Modbus IR776Read
IV4220ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.IGBT_tempZA2 Return - Fan electrical informations - IGBT temperature (°C); Modbus IR777Read
IV4221ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.MCU_TempZA2 Return - Fan electrical informations - MCU temperature; Modbus IR778Read
IV4222ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.MotTempZA2 Return - Fan electrical informations - Motr temperature (°C); Modbus IR779Read
PIV4223FanAlrm_ZA_RetFan_2.ErrStatusZA2 return - Fan alarms - Error status defines errors ...; Modbus IR780Read
PIV4224ZiehlAbegg_ReturnFan.FanStatus_ZA_2.WorkingStatusZA2 Return - Fan status - Working status defines current ...; Modbus IR781Read
PIV4225ZiehlAbegg_ReturnFan.FanStatus_ZA_2.WorkStatusCodeZA2 Return - Fan status - Working status code; Modbus IR782Read
IV4226ZA_AlrmCode_ReturnFan2ZA alarms code number - Fan Return 2; Modbus IR783Read
PIV4227ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_3.CurrSpeed_rpmZA3 Return - Fan speed informations - Actual speed [rpm] ...; Modbus IR784Read
PIV4228ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.DC_LinkVZA3 Return - Fan electrical informations - DC link voltage (V); Modbus IR785Read
PIV4229ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.LineVZA3 Return - Fan electrical informations - Supply voltage (peak voltage); Modbus IR786Read
PIV4230ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_3.MaxSpeed_rpmZA3 Return - Fan speed informations - Maximum set speed; Modbus IR787Read
PIV4231ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_3.MinSpeed_rpmZA3 Return - Fan speed informations - Minimum set speed; Modbus IR788Read
PIV4232ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.MotPwrZA3 Return - Fan electrical informations - Motor input power (W); Modbus IR789Read
IV4233ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.ElectronicTempZA3 Return - Fan electrical informations - Electronics temperature (°C); Modbus IR790Read
IV4234ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.IGBT_tempZA3 Return - Fan electrical informations - IGBT temperature (°C); Modbus IR791Read
IV4235ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.MCU_TempZA3 Return - Fan electrical informations - MCU temperature; Modbus IR792Read
IV4236ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.MotTempZA3 Return - Fan electrical informations - Motr temperature (°C); Modbus IR793Read
PIV4237FanAlrm_ZA_RetFan_3.ErrStatusZA3 return - Fan alarms - Error status defines errors ...; Modbus IR794Read
PIV4238ZiehlAbegg_ReturnFan.FanStatus_ZA_3.WorkingStatusZA3 Return - Fan status - Working status defines current ...; Modbus IR795Read
PIV4239ZiehlAbegg_ReturnFan.FanStatus_ZA_3.WorkStatusCodeZA3 Return - Fan status - Working status code; Modbus IR796Read
IV4240ZA_AlrmCode_ReturnFan3ZA alarms code number - Fan Return 3; Modbus IR797Read
PIV4241ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_4.CurrSpeed_rpmZA4 Return - Fan speed informations - Actual speed [rpm] ...; Modbus IR798Read
PIV4242ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.DC_LinkVZA4 Return - Fan electrical informations - DC link voltage (V); Modbus IR799Read
PIV4243ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.LineVZA4 Return - Fan electrical informations - Supply voltage (peak voltage); Modbus IR800Read
PIV4244ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_4.MaxSpeed_rpmZA4 Return - Fan speed informations - Maximum set speed; Modbus IR801Read
PIV4245ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_4.MinSpeed_rpmZA4 Return - Fan speed informations - Minimum set speed; Modbus IR802Read
PIV4246ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.MotPwrZA4 Return - Fan electrical informations - Motor input power (W); Modbus IR803Read
IV4247ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.ElectronicTempZA4 Return - Fan electrical informations - Electronics temperature (°C); Modbus IR804Read
IV4248ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.IGBT_tempZA4 Return - Fan electrical informations - IGBT temperature (°C); Modbus IR805Read
IV4249ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.MCU_TempZA4 Return - Fan electrical informations - MCU temperature; Modbus IR806Read
IV4250ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.MotTempZA4 Return - Fan electrical informations - Motr temperature (°C); Modbus IR807Read
PIV4251FanAlrm_ZA_RetFan_4.ErrStatusZA4 return - Fan alarms - Error status defines errors ...; Modbus IR808Read
PIV4252ZiehlAbegg_ReturnFan.FanStatus_ZA_4.WorkingStatusZA4 Return - Fan status - Working status defines current ...; Modbus IR809Read
PIV4253ZiehlAbegg_ReturnFan.FanStatus_ZA_4.WorkStatusCodeZA4 Return - Fan status - Working status code; Modbus IR810Read
IV4254ZA_AlrmCode_ReturnFan4ZA alarms code number - Fan Return 4; Modbus IR811Read
PIV4267WrkHrs_SupplyFan_2.WrkHrsSupply Fan - Working hours; 32-bit (2 Modbus registers); Modbus IR812Read
PIV4268WrkHrs_SupplyFan_2.WrkHrs_LeftSupply Fan - Working hours left to the maintenance; 32-bit ...; Modbus IR814Read
PIV4269WrkHrs_SupplyFan_3.WrkHrsSupply Fan - Working hours; 32-bit (2 Modbus registers); Modbus IR816Read
PIV4270WrkHrs_SupplyFan_3.WrkHrs_LeftSupply Fan - Working hours left to the maintenance; 32-bit ...; Modbus IR818Read
PIV4271WrkHrs_SupplyFan_4.WrkHrsSupply Fan - Working hours; 32-bit (2 Modbus registers); Modbus IR820Read
PIV4272WrkHrs_SupplyFan_4.WrkHrs_LeftSupply Fan - Working hours left to the maintenance; 32-bit ...; Modbus IR822Read
PIV4273WrkHrs_ReturnFan_2.WrkHrsReturn Fan - Working hours; 32-bit (2 Modbus registers); Modbus IR824Read
PIV4274WrkHrs_ReturnFan_2.WrkHrs_LeftReturn Fan - Working hours left to the maintenance; 32-bit ...; Modbus IR826Read
PIV4275WrkHrs_ReturnFan_3.WrkHrsReturn Fan - Working hours; 32-bit (2 Modbus registers); Modbus IR828Read
PIV4276WrkHrs_ReturnFan_3.WrkHrs_LeftReturn Fan - Working hours left to the maintenance; 32-bit ...; Modbus IR830Read
PIV4277WrkHrs_ReturnFan_4.WrkHrsReturn Fan - Working hours; 32-bit (2 Modbus registers); Modbus IR832Read
PIV4278WrkHrs_ReturnFan_4.WrkHrs_LeftReturn Fan - Working hours left to the maintenance; 32-bit ...; Modbus IR834Read
AV4279Fans.Value_AVGSFP - Value to calculate the average; Modbus IR836Read
AV4280Fans.AvgTimeData_AVG.DailySFP - Calculated average time data - Daily average; Modbus IR837Read
AV4281Fans.AvgTimeData_AVG.MonthlySFP - Calculated average time data - Monthly average; Modbus IR838Read
AV4282HeatExchanger.Value_AVGHeat Rec. Eff. - Value to calculate the average; Modbus IR839Read
AV4283HeatExchanger.AvgTimeData_AVG.DailyHeat Rec. Eff. - Calculated average time data - Daily average; Modbus IR840Read
AV4284HeatExchanger.AvgTimeData_AVG.MonthlyHeat Rec. Eff. - Calculated average time data - Monthly average; Modbus IR841Read
IV4346HumiSteamMng.CntCylHr_UEYHumiSteam - Cylinder hours counter value; Modbus IR842Read
IV4347HumiSteamMng.HumState_UEYHumiSteam - Humidifier satus; Modbus IR843Read
IV4348HumiSteamMng.Curr_UEYHumiSteam - Immersed electrode current; 32-bit (2 Modbus registers); Modbus IR844Read
IV4349HumiSteamMng.Conductivity_UEYHumiSteam - Conductivity of the water in the cylinder; Modbus IR846Read
IV4350HumiSteamMng.SteamInstantFlowRate_UEYHumiSteam - Steam istant flow rate value returned by the ...; 32-bit; Modbus IR847Read
IV4351UEY_AlrmCodeHumiSteam - UEY alarms code number; Modbus IR849Read
AV4370Fans_regulation.SupplyFan_FanTempReg_SetPOffsSupply fan - Temperature regulation setpoint offset; Modbus IR850Read
AV4371Fans_regulation.SupplyFan_FC_FH_SetPOffsSupply fan - FC/FH setpoint offset; Modbus IR851Read
AV4372Fans_regulation.RetFan_FanTempReg_SetPOffsReturn fan - Temperature regulation setpoint offset; Modbus IR852Read
AV4373Fans_regulation.RetFan_FC_FH_SetPOffsReturn fan - FC/FH setpoint offset; Modbus IR853Read
PIV4388GenericAin1.Uom_WGeneric Ain1 - Uom; Modbus IR854Read
AV4389GenericAin1.Val_Hw_RGeneric Ain1 - Value reads from board; Modbus IR855Read
AV4390GenericAin1.Val_RGeneric Ain1; Modbus IR856Read
PIV4402GenericAin2.Uom_WGeneric Ain2 - Uom; Modbus IR857Read
AV4403GenericAin2.Val_Hw_RGeneric Ain2 - Value reads from board; Modbus IR858Read
AV4404GenericAin2.Val_RGeneric Ain2; Modbus IR859Read
PIV4416GenericAin3.Uom_WGeneric Ain3 - Uom; Modbus IR860Read
AV4417GenericAin3.Val_Hw_RGeneric Ain3 - Value reads from board; Modbus IR861Read
AV4418GenericAin3.Val_RGeneric Ain3; Modbus IR862Read
PIV4430GenericAin4.Uom_WGeneric Ain4 - Uom; Modbus IR863Read
AV4431GenericAin4.Val_Hw_RGeneric Ain4 - Value reads from board; Modbus IR864Read
AV4432GenericAin4.Val_RGeneric Ain4; Modbus IR865Read
PIV4444GenericAin5.Uom_WGeneric Ain5 - Uom; Modbus IR866Read
AV4445GenericAin5.Val_Hw_RGeneric Ain5 - Value reads from board; Modbus IR867Read
AV4446GenericAin5.Val_RGeneric Ain5; Modbus IR868Read
AV4562OA_CoilRegReqOutdoor air pre-treatment request from PID Seq; Modbus IR869Read
AV4563OA_CoilReqOutdoor air pre-treatment request; Modbus IR870Read
PIV4564WrkHrs_OA_CoilAout.WrkHrsOutdoor air pre-treatment coil analog output - Working hours; 32-bit ...; Modbus IR871Read
PIV4565WrkHrs_OA_CoilAout.WrkHrs_LeftOutdoor air pre-treatment coil analog output - Working hours left ...; 32-bit; Modbus IR873Read
PIV4566WrkHrs_OA_CoilStep1.WrkHrsOutdoor air pre-treatment coil step 1 - Working hours; 32-bit ...; Modbus IR875Read
PIV4567WrkHrs_OA_CoilStep1.WrkHrs_LeftOutdoor air pre-treatment coil step 1 - Working hours left ...; 32-bit; Modbus IR877Read
PIV4568WrkHrs_OA_CoilStep2.WrkHrsOutdoor air pre-treatment coil step 2 - Working hours; 32-bit ...; Modbus IR879Read
PIV4569WrkHrs_OA_CoilStep2.WrkHrs_LeftOutdoor air pre-treatment coil step 2 - Working hours left ...; 32-bit; Modbus IR881Read
PIV4570WrkHrs_OA_CoilStep3.WrkHrsOutdoor air pre-treatment coil step 3 - Working hours; 32-bit ...; Modbus IR883Read
PIV4571WrkHrs_OA_CoilStep3.WrkHrs_LeftOutdoor air pre-treatment coil step 3 - Working hours left ...; 32-bit; Modbus IR885Read
PIV4572WrkHrs_OA_CoilStep4.WrkHrsOutdoor air pre-treatment coil step 4 - Working hours; 32-bit ...; Modbus IR887Read
PIV4573WrkHrs_OA_CoilStep4.WrkHrs_LeftOutdoor air pre-treatment coil step 4 - Working hours left ...; 32-bit; Modbus IR889Read
PIV4574OA_Vlv_PercOutdoor air pre-treatment floating valve: Estimating position valve; Modbus IR891Read
PIV3596AirFlwValSupply air flow value; 32-bit (2 Modbus registers); Modbus IR892Read
PIV3597RetAirFlwValReturn air flow value; 32-bit (2 Modbus registers); Modbus IR894Read
Object ID lookup: CAREL k.air air handling unit controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the k.air air handling unit controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CAREL k.air air handling unit controller

How many BACnet points does the CAREL k.air air handling unit controller have?

This list has 4350 BACnet objects: 739 analog values, 1596 binary values, 136 integer values, 1879 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CAREL k.air air handling unit controller BACnet points are writable?

2473 of the 4350 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official CAREL k.air air handling unit controller BACnet documentation?

The source is k.air - Air handling unit controller, user manual (11. Supervisor variable table) (+030220981), revision rel. 1.8 - 2026-06-25, published free by CAREL at https://www.carel.com/documents/10191/0/%2B030220981/14d83d46-c7fc-403d-b38d-2688a78559ef?version=1.11.

What are the minimum BACnet points to integrate the CAREL k.air air handling unit controller?

Start with BV 234 Scheduler_OnOffUnit.BMS_OnOff_En (Must be on for the BMS on/off command to work); BV 2 Scheduler_OnOffUnit.BMS_OnOff (Unit on/off command from the BMS); BV 4 SummerWinter_BMS (Summer/winter command (0 = summer, 1 = winter)); AV 2585 UnitSetP.TempSetP.Winter.Comfort (Winter comfort temperature setpoint); AV 2584 UnitSetP.TempSetP.Summer.Comfort (Summer comfort temperature setpoint); BV 1 AlarmsMng.AlrmResByBms (Alarm reset); PIV 3645 SchedStatus (Active status: 0 off, 1 economy, 2 pre-comfort, 3 comfort); AV 3435 SupplyTemp.Val_Hw_R (Supply air temperature (probe reading)); AV 3442 RetTemp.Val_R (Return air temperature); BV 902 GlobalAlrm_Dout.Val_W (Generic alarm active).

How do I enable BMS control of the CAREL k.air air handling unit controller?

The unit can be switched by keypad/th-Tune, BMS, digital input and scheduler; any enabled source set to off stops it. BMS on/off works only when BV 234 (enable on/off request by BMS) is on; BV 2 then turns the unit on or off.

Does the CAREL k.air air handling unit controller need a BACnet heartbeat or have a communication timeout?

PIV 2898 selects BMS offline handling (0 disabled, 1 warning only, 2 alarm, 3 alarm with timeout) and PIV 2899 sets the timeout, 120 s by default. BV 1347 shows the BMS offline alarm.

How do I check these points on the real k.air air handling unit controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CAREL BACnet points lists

Source: k.air - Air handling unit controller, user manual (11. Supervisor variable table) · +030220981 · rev. rel. 1.8 - 2026-06-25. Object names, instances and units are reproduced as published; descriptions are our own.