- Home
- BACnet points lists
- CAREL
- k.air air handling unit controller
Air handling unit controller · BACnet points list
CAREL k.air air handling unit controller BACnet points list
Updated 12 November 2026
k.air is CAREL's ready-made air handling unit controller. Its manual has a supervisor variable table with a Modbus address and a BACnet object for every variable: about 4,350 objects covering BMS commands, setpoints, every sensor and output (with its configuration), fan, humidifier, compressor and heat recovery data, and one alarm BV per alarm. Most of the list is configuration; an integrator normally maps a small part of it.
This page lists 4350 BACnet objects for the CAREL k.air air handling unit controller — 2473 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CAREL’s own free documentation, linked below.
- Manufacturer
- CAREL
- Model
- k.air air handling unit controller
- Equipment
- Air handling unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 4350 (2473 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- k.air, kair, k.air large, k.air mini, CAREL k.air, +030220981, CAREL AHU controller
Reference only, provided as-is: verify against CAREL’s current documentation and the live device before use. Not official CAREL information. Terms of use.
BMS integration notes: CAREL k.air air handling unit controller
Enable BMS on/off with BV 234, then switch the unit with BV 2 and select summer or winter with BV 4. Write the comfort temperature setpoints (AV 2585 winter, AV 2584 summer) if the BMS owns them. Read the unit status (PIV 3645), the supply, return and room temperatures, and the generic alarm BV 902; BV 1 resets alarms. Configure the BMS offline alarm (PIV 2898/2899) if the BMS should be supervised.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 234 | Scheduler_OnOffUnit.BMS_OnOff_En | Must be on for the BMS on/off command to work | Write |
| BV 2 | Scheduler_OnOffUnit.BMS_OnOff | Unit on/off command from the BMS | Write |
| BV 4 | SummerWinter_BMS | Summer/winter command (0 = summer, 1 = winter) | Write |
| AV 2585 | UnitSetP.TempSetP.Winter.Comfort | Winter comfort temperature setpoint | Write |
| AV 2584 | UnitSetP.TempSetP.Summer.Comfort | Summer comfort temperature setpoint | Write |
| BV 1 | AlarmsMng.AlrmResByBms | Alarm reset | Write |
| PIV 3645 | SchedStatus | Active status: 0 off, 1 economy, 2 pre-comfort, 3 comfort | Read |
| AV 3435 | SupplyTemp.Val_Hw_R | Supply air temperature (probe reading) | Read |
| AV 3442 | RetTemp.Val_R | Return air temperature | Read |
| BV 902 | GlobalAlrm_Dout.Val_W | Generic alarm active | Read |
Enable & remote start
The unit can be switched by keypad/th-Tune, BMS, digital input and scheduler; any enabled source set to off stops it. BMS on/off works only when BV 234 (enable on/off request by BMS) is on; BV 2 then turns the unit on or off.
Heartbeat & communication loss
PIV 2898 selects BMS offline handling (0 disabled, 1 warning only, 2 alarm, 3 alarm with timeout) and PIV 2899 sets the timeout, 120 s by default. BV 1347 shows the BMS offline alarm.
Network setup
- Choose the BACnet port in menu Y: BMS Line or BMS2 Line = 2 (BACnet MS/TP on RS485) or Ethernet 2 Line = 1 (BACnet IP).
- Y003 sets the BACnet device instance (also the MS/TP station address); baud rate, parity and stop bits are in menu Y too.
Watch out for
- Most of the ~4,350 objects are I/O configuration (board, channel, probe type, limits); writing them changes the unit's set-up.
- Setpoints exist per season and per mode (economy, pre-comfort, comfort); the current setpoint values are read-only status objects.
- Object instances are not derived from the Modbus address; use the table, not a formula.
CAREL k.air air handling unit controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 1 | AlarmsMng.AlrmResByBms | Alarm reset by BMS; Modbus CS001 | Write | ||
| BVmin | 2 | Scheduler_OnOffUnit.BMS_OnOff | On/off request by BMS; Modbus CS002 | Write | ||
| BVmin | 4 | SummerWinter_BMS | Summer/Winter mode by BMS (FALSE: Summer; TRUE: Winter); Modbus CS004 | Write | ||
| BV | 5 | Scheduler_OnOffUnit.BMS_UnitProfile_En | Enable the unit profile from BMS; Modbus CS005 | Write | ||
| BV | 6 | Scheduler_Cfg.Prg[0].Event[0].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS006 | Write | ||
| BV | 7 | Scheduler_Cfg.Prg[0].Event[1].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS007 | Write | ||
| BV | 8 | Scheduler_Cfg.Prg[0].Event[2].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS008 | Write | ||
| BV | 9 | Scheduler_Cfg.Prg[0].Event[3].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS009 | Write | ||
| BV | 10 | Scheduler_Cfg.Prg[0].Event[4].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS010 | Write | ||
| BV | 11 | Scheduler_Cfg.Prg[0].Event[5].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS011 | Write | ||
| BV | 12 | Scheduler_Cfg.Prg[0].Event[6].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS012 | Write | ||
| BV | 13 | Scheduler_Cfg.Prg[0].Event[7].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS013 | Write | ||
| BV | 14 | Scheduler_Cfg.Prg[0].Event[8].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS014 | Write | ||
| BV | 15 | Scheduler_Cfg.Prg[0].Event[9].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS015 | Write | ||
| BV | 16 | Scheduler_Cfg.Prg[1].Event[0].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS016 | Write | ||
| BV | 17 | Scheduler_Cfg.Prg[1].Event[1].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS017 | Write | ||
| BV | 18 | Scheduler_Cfg.Prg[1].Event[2].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS018 | Write | ||
| BV | 19 | Scheduler_Cfg.Prg[1].Event[3].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS019 | Write | ||
| BV | 20 | Scheduler_Cfg.Prg[1].Event[4].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS020 | Write | ||
| BV | 21 | Scheduler_Cfg.Prg[1].Event[5].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS021 | Write | ||
| BV | 22 | Scheduler_Cfg.Prg[1].Event[6].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS022 | Write | ||
| BV | 23 | Scheduler_Cfg.Prg[1].Event[7].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS023 | Write | ||
| BV | 24 | Scheduler_Cfg.Prg[1].Event[8].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS024 | Write | ||
| BV | 25 | Scheduler_Cfg.Prg[1].Event[9].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS025 | Write | ||
| BV | 26 | Scheduler_Cfg.Prg[2].Event[0].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS026 | Write | ||
| BV | 27 | Scheduler_Cfg.Prg[2].Event[1].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS027 | Write | ||
| BV | 28 | Scheduler_Cfg.Prg[2].Event[2].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS028 | Write | ||
| BV | 29 | Scheduler_Cfg.Prg[2].Event[3].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS029 | Write | ||
| BV | 30 | Scheduler_Cfg.Prg[2].Event[4].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS030 | Write | ||
| BV | 31 | Scheduler_Cfg.Prg[2].Event[5].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS031 | Write | ||
| BV | 32 | Scheduler_Cfg.Prg[2].Event[6].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS032 | Write | ||
| BV | 33 | Scheduler_Cfg.Prg[2].Event[7].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS033 | Write | ||
| BV | 34 | Scheduler_Cfg.Prg[2].Event[8].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS034 | Write | ||
| BV | 35 | Scheduler_Cfg.Prg[2].Event[9].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS035 | Write | ||
| BV | 36 | Scheduler_Cfg.Prg[3].Event[0].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS036 | Write | ||
| BV | 37 | Scheduler_Cfg.Prg[3].Event[1].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS037 | Write | ||
| BV | 38 | Scheduler_Cfg.Prg[3].Event[2].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS038 | Write | ||
| BV | 39 | Scheduler_Cfg.Prg[3].Event[3].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS039 | Write | ||
| BV | 40 | Scheduler_Cfg.Prg[3].Event[4].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS040 | Write | ||
| BV | 41 | Scheduler_Cfg.Prg[3].Event[5].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS041 | Write | ||
| BV | 42 | Scheduler_Cfg.Prg[3].Event[6].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS042 | Write | ||
| BV | 43 | Scheduler_Cfg.Prg[3].Event[7].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS043 | Write | ||
| BV | 44 | Scheduler_Cfg.Prg[3].Event[8].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS044 | Write | ||
| BV | 45 | Scheduler_Cfg.Prg[3].Event[9].Enabled | Scheduler: configuration - Program - Event - Enable event; Modbus CS045 | Write | ||
| BV | 46 | Scheduler_Cfg.SDays[0].Enabled | Scheduler: configuration - Special day - Enabled; Modbus CS046 | Write | ||
| BV | 47 | Scheduler_Cfg.SDays[1].Enabled | Scheduler: configuration - Special day - Enabled; Modbus CS047 | Write | ||
| BV | 48 | Scheduler_Cfg.SDays[2].Enabled | Scheduler: configuration - Special day - Enabled; Modbus CS048 | Write | ||
| BV | 49 | Scheduler_Cfg.SDays[3].Enabled | Scheduler: configuration - Special day - Enabled; Modbus CS049 | Write | ||
| BV | 50 | Scheduler_Cfg.SDays[4].Enabled | Scheduler: configuration - Special day - Enabled; Modbus CS050 | Write | ||
| BV | 51 | Scheduler_Cfg.SDays[5].Enabled | Scheduler: configuration - Special day - Enabled; Modbus CS051 | Write | ||
| BV | 52 | Scheduler_Cfg.SDays[6].Enabled | Scheduler: configuration - Special day - Enabled; Modbus CS052 | Write | ||
| BV | 53 | Scheduler_Cfg.SDays[7].Enabled | Scheduler: configuration - Special day - Enabled; Modbus CS053 | Write | ||
| BV | 54 | Scheduler_Cfg.SDays[8].Enabled | Scheduler: configuration - Special day - Enabled; Modbus CS054 | Write | ||
| BV | 55 | Scheduler_Cfg.SDays[9].Enabled | Scheduler: configuration - Special day - Enabled; Modbus CS055 | Write | ||
| BV | 56 | Scheduler_Cfg.SDays[10].Enabled | Scheduler: configuration - Special day - Enabled; Modbus CS056 | Write | ||
| BV | 57 | Scheduler_Cfg.SDays[11].Enabled | Scheduler: configuration - Special day - Enabled; Modbus CS057 | Write | ||
| BV | 58 | Scheduler_Cfg.SDays[12].Enabled | Scheduler: configuration - Special day - Enabled; Modbus CS058 | Write | ||
| BV | 59 | Scheduler_Cfg.SDays[13].Enabled | Scheduler: configuration - Special day - Enabled; Modbus CS059 | Write | ||
| BV | 60 | Scheduler_Cfg.SDays[14].Enabled | Scheduler: configuration - Special day - Enabled; Modbus CS060 | Write | ||
| BV | 61 | Scheduler_Cfg.Vac[0].Enabled | Scheduler: configuration - Vacation period - Enabled; Modbus CS061 | Write | ||
| BV | 62 | Scheduler_Cfg.Vac[1].Enabled | Scheduler: configuration - Vacation period - Enabled; Modbus CS062 | Write | ||
| BV | 63 | Scheduler_Cfg.Vac[2].Enabled | Scheduler: configuration - Vacation period - Enabled; Modbus CS063 | Write | ||
| BV | 65 | SupplyAirFlwSw.LogicDin_RW | Supply air flow switch - Logic digital input; Modbus CS065 | Write | ||
| BV | 66 | RetAirFlwSw.LogicDin_RW | Return air flow switch - Logic digital input; Modbus CS066 | Write | ||
| BV | 67 | AirFlwSw.LogicDin_RW | Air flow switch - Logic digital input; Modbus CS067 | Write | ||
| BV | 68 | AFreezeSw.LogicDin_RW | Antifreeze switch - Logic digital input; Modbus CS068 | Write | ||
| BV | 69 | RemOnOff.LogicDin_RW | Remote On/Off - Logic digital input; Modbus CS069 | Write | ||
| BV | 70 | SupplyFanOvld_1.LogicDin_RW | Supply fan overload 1 - Logic digital input; Modbus CS070 | Write | ||
| BV | 71 | RetFanOvld_1.LogicDin_RW | Return fan overload 1 - Logic digital input; Modbus CS071 | Write | ||
| BV | 72 | SupplyFanOvld_2.LogicDin_RW | Supply fan overload 2 - Logic digital input; Modbus CS072 | Write | ||
| BV | 73 | RetFanOvld_2.LogicDin_RW | Return fan overload 2 - Logic digital input; Modbus CS073 | Write | ||
| BV | 74 | SupplyFanInvAlrm.LogicDin_RW | Supply inverter alarm - Logic digital input; Modbus CS074 | Write | ||
| BV | 75 | RetFanInvAlrm.LogicDin_RW | Return inverter alarm - Logic digital input; Modbus CS075 | Write | ||
| BV | 76 | FansOvld.LogicDin_RW | Fans overload - Logic digital input; Modbus CS076 | Write | ||
| BV | 77 | CompOvld.LogicDin_RW | Compressor overload - Logic digital input; Modbus CS077 | Write | ||
| BV | 78 | HiPSw.LogicDin_RW | High discharge pressure switch - Logic digital input; Modbus CS078 | Write | ||
| BV | 79 | LowPSw.LogicDin_RW | Low suction pressure switch - Logic digital input; Modbus CS079 | Write | ||
| BV | 80 | RecoveryOvld.LogicDin_RW | Thermal wheel overload - Logic digital input; Modbus CS080 | Write | ||
| BV | 81 | SrsAlrm.LogicDin_RW | Serious alarm - Logic digital input; Modbus CS081 | Write | ||
| BV | 82 | GenAlrm.LogicDin_RW | Generic alarm - Logic digital input; Modbus CS082 | Write | ||
| BV | 83 | GenWarning.LogicDin_RW | Generic warning - Logic digital input; Modbus CS083 | Write | ||
| BV | 84 | FiltAlrm.LogicDin_RW | Filters alarm - Logic digital input; Modbus CS084 | Write | ||
| BV | 85 | SupplyFiltAlrm_1.LogicDin_RW | Supply filter alarm 1 - Logic digital input; Modbus CS085 | Write | ||
| BV | 86 | SupplyFiltAlrm_2.LogicDin_RW | Supply filter alarm 2 - Logic digital input; Modbus CS086 | Write | ||
| BV | 87 | RetFiltAlrm.LogicDin_RW | Return filter alarm - Logic digital input; Modbus CS087 | Write | ||
| BV | 88 | HumAlrm.LogicDin_RW | Humidifier alarm - Logic digital input; Modbus CS088 | Write | ||
| BV | 89 | MainCoilPmp1_Ovld.LogicDin_RW | Main coil pump 1 overload - Logic digital input; Modbus CS089 | Write | ||
| BV | 90 | MainCoilPmp2_Ovld.LogicDin_RW | Main coil pump 2 overload - Logic digital input; Modbus CS090 | Write | ||
| BV | 91 | ReHeatCoilPmp1_Ovld.LogicDin_RW | ReHeat coil pump 1 overload - Logic digital input; Modbus CS091 | Write | ||
| BV | 92 | ReHeatCoilPmp2_Ovld.LogicDin_RW | ReHeat coil pump 2 overload - Logic digital input; Modbus CS092 | Write | ||
| BV | 93 | PreHeatCoilPmp1_Ovld.LogicDin_RW | PreHeat coil pump 1 overload - Logic digital input; Modbus CS093 | Write | ||
| BV | 94 | PreHeatCoilPmp2_Ovld.LogicDin_RW | PreHeat coil pump 2 overload - Logic digital input; Modbus CS094 | Write | ||
| BV | 95 | OA_CoilPmp1_Ovld.LogicDin_RW | Outdoor air pre-treatment coil pump 1 overload - Logic digital input; Modbus CS095 | Write | ||
| BV | 96 | OA_CoilPmp2_Ovld.LogicDin_RW | Outdoor air pre-treatment coil pump 2 overload - Logic digital input; Modbus CS096 | Write | ||
| BV | 97 | FreshAirDampSw.LogicDin_RW | Fresh air damper switch - Logic digital input; Modbus CS097 | Write | ||
| BV | 98 | SupplyDamperSw.LogicDin_RW | Supply damper switch - Logic digital input; Modbus CS098 | Write | ||
| BV | 99 | RetDampSw.LogicDin_RW | Return damper switch - Logic digital input; Modbus CS099 | Write | ||
| BV | 100 | MainCoilFlwSw.LogicDin_RW | Main coil flow switch - Logic digital input; Modbus CS100 | Write | ||
| BV | 101 | PreHeatCoilFlwSw.LogicDin_RW | Pre-heating coil flow switch - Logic digital input; Modbus CS101 | Write | ||
| BV | 102 | ReHeatCoilFlwSw.LogicDin_RW | Post-Heating coil flow switch - Logic digital input; Modbus CS102 | Write | ||
| BV | 103 | OA_CoilFlwSw.LogicDin_RW | Outdoor air pre-treatment coil flow switch - Logic digital input; Modbus CS103 | Write | ||
| BV | 104 | RecoveryClogged.LogicDin_RW | Recovery clogged - Logic digital input; Modbus CS104 | Write | ||
| BV | 105 | ReHeatAlrm.LogicDin_RW | Re-heating alarm - Logic digital input; Modbus CS105 | Write | ||
| BV | 106 | PreHeatAlrm.LogicDin_RW | Pre-heating alarm - Logic digital input; Modbus CS106 | Write | ||
| BV | 107 | MainHeatCoilAlrm.LogicDin_RW | Main coil alarm - Logic digital input; Modbus CS107 | Write | ||
| BV | 108 | OA_CoilAlrm.LogicDin_RW | Outdoor air pre-treatment-Heat alarm - Logic digital input; Modbus CS108 | Write | ||
| BV | 109 | DoorSw.LogicDin_RW | Door Switch - Logic digital input; Modbus CS109 | Write | ||
| BV | 110 | FireSmokeAlrm.LogicDin_RW | Fire/Smoke alarm - Logic digital input; Modbus CS110 | Write | ||
| BV | 111 | FiremanOverrideSw.LogicDin_RW | Fireman override switch - Logic digital input; Modbus CS111 | Write | ||
| BV | 112 | SummerWinterModeByDin.LogicDin_RW | Summer/Winter mode by digital input - Logic; Modbus CS112 | Write | ||
| BV | 113 | Din_SetP.LogicDin_RW | Setpoint by digital input - Logic digital input; Modbus CS113 | Write | ||
| BV | 114 | Eco_Mode.LogicDin_RW | Eco mode - Logic digital input; Modbus CS114 | Write | ||
| BV | 115 | PreComf_Mode.LogicDin_RW | Precomfort mode - Logic digital input; Modbus CS115 | Write | ||
| BV | 116 | Comf_Mode.LogicDin_RW | Comfort mode - Logic digital input; Modbus CS116 | Write | ||
| BV | 117 | AuxDin_1.LogicDin_RW | Auxiliary digital input 1 - Logic digital input; Modbus CS117 | Write | ||
| BV | 118 | AuxDin_2.LogicDin_RW | Auxiliary digital input 2 - Logic digital input; Modbus CS118 | Write | ||
| BV | 119 | AuxDin_3.LogicDin_RW | Auxiliary digital input 3 - Logic digital input; Modbus CS119 | Write | ||
| BV | 120 | AuxDin_4.LogicDin_RW | Auxiliary digital input 4 - Logic digital input; Modbus CS120 | Write | ||
| BV | 121 | DfrHeatExch_Din.LogicDin_RW | Heat exchanger defrost by Din - Logic digital input; Modbus CS121 | Write | ||
| BV | 122 | BypassDamp_Dout.LogicDout_RW | Bypass damper - Logic digital output; Modbus CS122 | Write | ||
| BV | 123 | BypassDamp_Open.LogicDout_RW | Bypass damper floating (open) - Logic digital output; Modbus CS123 | Write | ||
| BV | 124 | BypassDamp_Close.LogicDout_RW | Bypass damper floating (close) - Logic digital output; Modbus CS124 | Write | ||
| BV | 125 | FreshAirDamp_Dout.LogicDout_RW | Fresh air damper - Logic digital output; Modbus CS125 | Write | ||
| BV | 126 | ExhAirDamp_Dout.LogicDout_RW | Exhaust air damper - Logic digital output; Modbus CS126 | Write | ||
| BV | 127 | MixingDamp_Dout.LogicDout_RW | Mixing damper - Logic digital output; Modbus CS127 | Write | ||
| BV | 128 | SupplyAirDamp_Dout.LogicDout_RW | Supply air damper - Logic digital output; Modbus CS128 | Write | ||
| BV | 129 | RetAirDamp_Dout.LogicDout_RW | Return air damper - Logic digital output; Modbus CS129 | Write | ||
| BV | 130 | MixingDamp_Open.LogicDout_RW | Mixing damper floating (OPEN) - Logic digital output; Modbus CS130 | Write | ||
| BV | 131 | MixingDamp_Close.LogicDout_RW | Mixing damper floating (CLOSE) - Logic digital output; Modbus CS131 | Write | ||
| BV | 132 | SupplyFan_Dout.LogicDout_RW | Supply fan - Logic digital output; Modbus CS132 | Write | ||
| BV | 133 | RetFan_Dout.LogicDout_RW | Return fan - Logic digital output; Modbus CS133 | Write | ||
| BV | 134 | SupplyFan2_Dout.LogicDout_RW | Supply fan 2 - Logic digital output; Modbus CS134 | Write | ||
| BV | 135 | RetFan2_Dout.LogicDout_RW | Return fan 2 - Logic digital output; Modbus CS135 | Write | ||
| BV | 136 | Comp_Dout.LogicDout_RW | Compressor - Logic digital output; Modbus CS136 | Write | ||
| BV | 137 | RevVlv.LogicDout_RW | Reverse valve - Logic digital output; Modbus CS137 | Write | ||
| BV | 138 | UnitOnOff_Dout.LogicDout_RW | Unit status (On/Off ) - Logic digital output; Modbus CS138 | Write | ||
| BV | 140 | GlobalAlrm_Dout.LogicDout_RW | Generic alarm info - Logic digital output; Modbus CS140 | Write | ||
| BV | 141 | LightAlrm_Dout.LogicDout_RW | Light alarm info - Logic digital output; Modbus CS141 | Write | ||
| BV | 142 | SrsAlrm_Dout.LogicDout_RW | Serious alarm info - Logic digital output; Modbus CS142 | Write | ||
| BV | 143 | Humidifier.LogicDout_RW | Humidifier - Logic digital output; Modbus CS143 | Write | ||
| BV | 144 | AuxOut1_Dout.LogicDout_RW | Auxiliary output 1 - Logic digital output; Modbus CS144 | Write | ||
| BV | 145 | AuxOut2_Dout.LogicDout_RW | Auxiliary output 2 - Logic digital output; Modbus CS145 | Write | ||
| BV | 146 | AuxOut3_Dout.LogicDout_RW | Auxiliary output 3 - Logic digital output; Modbus CS146 | Write | ||
| BV | 147 | AuxOut4_Dout.LogicDout_RW | Auxiliary output 4 - Logic digital output; Modbus CS147 | Write | ||
| BV | 148 | MainVlv_Open.LogicDout_RW | Main floating valve open - Logic digital output; Modbus CS148 | Write | ||
| BV | 149 | PreHeatVlv_Open.LogicDout_RW | Pre-heating floating valve open - Logic digital output; Modbus CS149 | Write | ||
| BV | 150 | ReHeatVlv_Open.LogicDout_RW | Re-Heating floating valve open - Logic digital output; Modbus CS150 | Write | ||
| BV | 151 | MainVlv_Close.LogicDout_RW | Main floating valve close - Logic digital output; Modbus CS151 | Write | ||
| BV | 152 | PreHeatVlv_Close.LogicDout_RW | Pre-heating floating valve close - Logic digital output; Modbus CS152 | Write | ||
| BV | 153 | ReHeatVlv_Close.LogicDout_RW | Re-Heating floating valve close - Logic digital output; Modbus CS153 | Write | ||
| BV | 154 | MainCoil_Step1.LogicDout_RW | Main step 1 - Logic digital output; Modbus CS154 | Write | ||
| BV | 155 | MainCoil_Step2.LogicDout_RW | Main step 2 - Logic digital output; Modbus CS155 | Write | ||
| BV | 156 | MainCoil_Step3.LogicDout_RW | Main step 3 - Logic digital output; Modbus CS156 | Write | ||
| BV | 157 | MainCoil_Step4.LogicDout_RW | Main step 4 - Logic digital output; Modbus CS157 | Write | ||
| BV | 158 | ReHeatCoil_Step1.LogicDout_RW | Postheat heater 1 - Logic digital output; Modbus CS158 | Write | ||
| BV | 159 | ReHeatCoil_Step2.LogicDout_RW | Postheat heater 2 - Logic digital output; Modbus CS159 | Write | ||
| BV | 160 | ReHeatCoil_Step3.LogicDout_RW | Postheat heater 3 - Logic digital output; Modbus CS160 | Write | ||
| BV | 161 | ReHeatCoil_Step4.LogicDout_RW | Postheat heater 4 - Logic digital output; Modbus CS161 | Write | ||
| BV | 162 | PreHeatCoil_Step1.LogicDout_RW | Preheat heater 1 - Logic digital output; Modbus CS162 | Write | ||
| BV | 163 | PreHeatCoil_Step2.LogicDout_RW | Preheat heater 2 - Logic digital output; Modbus CS163 | Write | ||
| BV | 164 | PreHeatCoil_Step3.LogicDout_RW | Preheat heater 3 - Logic digital output; Modbus CS164 | Write | ||
| BV | 165 | PreHeatCoil_Step4.LogicDout_RW | Preheat heater 4 - Logic digital output; Modbus CS165 | Write | ||
| BV | 166 | OA_Coil_Step1.LogicDout_RW | Outdoor air pre-treatment heater 1 - Logic digital output; Modbus CS166 | Write | ||
| BV | 167 | OA_Coil_Step2.LogicDout_RW | Outdoor air pre-treatment heater 2 - Logic digital output; Modbus CS167 | Write | ||
| BV | 168 | OA_Coil_Step3.LogicDout_RW | Outdoor air pre-treatment heater 3 - Logic digital output; Modbus CS168 | Write | ||
| BV | 169 | OA_Coil_Step4.LogicDout_RW | Outdoor air pre-treatment heater 4 - Logic digital output; Modbus CS169 | Write | ||
| BV | 170 | PreHeatPmp_1.LogicDout_RW | Pre-Heating pump 1 - Logic digital output; Modbus CS170 | Write | ||
| BV | 171 | PreHeatPmp_2.LogicDout_RW | Pre-Heating pump 2 - Logic digital output; Modbus CS171 | Write | ||
| BV | 172 | MainCoilPmp_1.LogicDout_RW | Main pump 1 - Logic digital output; Modbus CS172 | Write | ||
| BV | 173 | MainCoilPmp_2.LogicDout_RW | Main pump 2 - Logic digital output; Modbus CS173 | Write | ||
| BV | 174 | ReHeatPmp_1.LogicDout_RW | Re-Heating pump 1 - Logic digital output; Modbus CS174 | Write | ||
| BV | 175 | ReHeatPmp_2.LogicDout_RW | Re-Heating pump 2 - Logic digital output; Modbus CS175 | Write | ||
| BV | 176 | OA_CoilPmp_1.LogicDout_RW | Outdoor air pre-treatment -Heating pump 1 - Logic digital output; Modbus CS176 | Write | ||
| BV | 177 | OA_CoilPmp_2.LogicDout_RW | Outdoor air pre-treatment -Heating pump 2 - Logic digital output; Modbus CS177 | Write | ||
| BV | 178 | FiltAlrm_Dout.LogicDout_RW | Filters alarm - Logic digital output; Modbus CS178 | Write | ||
| BV | 179 | Recovery_Dout.LogicDout_RW | Recovery - Logic digital output; Modbus CS179 | Write | ||
| BV | 180 | IEC_Hum_Dout.LogicDout_RW | IEC humidifer - Logic digital output; Modbus CS180 | Write | ||
| BV | 181 | SummerWinter_UI | Summer/Winter mode by Keyboard (FALSE: Summer; TRUE: Winter); Modbus CS181 | Write | ||
| BV | 182 | Scheduler_OnOffUnit.PartyMode_Start | Party mode: start command; Modbus CS182 | Write | ||
| BV | 183 | VarToShow.Logic | Modbus CS183 | Write | ||
| BV | 184 | FreshAirDampEnMan | Fresh air damper manual mode enable; Modbus CS184 | Write | ||
| BV | 185 | MixDampEnMan | Mixing damper manual mode enable; Modbus CS185 | Write | ||
| BV | 186 | ExhAirDampEnMan | Exhaust air damper manual mode enable; Modbus CS186 | Write | ||
| BV | 187 | BypassDampEnMan | Bypass damper manual mode enable; Modbus CS187 | Write | ||
| BV | 188 | SupplyFanEnMan | Supply fan manual mode enable; Modbus CS188 | Write | ||
| BV | 189 | RetFanEnMan | Return fan manual mode enable; Modbus CS189 | Write | ||
| BV | 190 | PreHeatCoilEnMan | Pre heating coil manual mode enable; Modbus CS190 | Write | ||
| BV | 191 | MainCoilEnMan | Main coil manual mode enable; Modbus CS191 | Write | ||
| BV | 192 | ReHeatCoilEnMan | Post heating coil manual mode enable; Modbus CS192 | Write | ||
| BV | 193 | CompEnMan | Compressor manual mode enable; Modbus CS193 | Write | ||
| BV | 194 | HumEnMan | Humidifier manual mode enable; Modbus CS194 | Write | ||
| BV | 195 | En_SetPComp | Enable setpoint compensation by external temperature; Modbus CS195 | Write | ||
| BV | 196 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[0].Enabled | Event - Enable event; Modbus CS196 | Write | ||
| BV | 197 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[1].Enabled | Event - Enable event; Modbus CS197 | Write | ||
| BV | 198 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[2].Enabled | Event - Enable event; Modbus CS198 | Write | ||
| BV | 199 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[3].Enabled | Event - Enable event; Modbus CS199 | Write | ||
| BV | 200 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[4].Enabled | Event - Enable event; Modbus CS200 | Write | ||
| BV | 201 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[5].Enabled | Event - Enable event; Modbus CS201 | Write | ||
| BV | 202 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[6].Enabled | Event - Enable event; Modbus CS202 | Write | ||
| BV | 203 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[7].Enabled | Event - Enable event; Modbus CS203 | Write | ||
| BV | 204 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[8].Enabled | Event - Enable event; Modbus CS204 | Write | ||
| BV | 205 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[9].Enabled | Event - Enable event; Modbus CS205 | Write | ||
| BV | 206 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[0].Enabled | Vacation period - Enabled; Modbus CS206 | Write | ||
| BV | 207 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[1].Enabled | Vacation period - Enabled; Modbus CS207 | Write | ||
| BV | 208 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[2].Enabled | Vacation period - Enabled; Modbus CS208 | Write | ||
| BV | 209 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[0].Enabled | Special day - Enabled; Modbus CS209 | Write | ||
| BV | 210 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[1].Enabled | Special day - Enabled; Modbus CS210 | Write | ||
| BV | 211 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[2].Enabled | Special day - Enabled; Modbus CS211 | Write | ||
| BV | 212 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[3].Enabled | Special day - Enabled; Modbus CS212 | Write | ||
| BV | 213 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[4].Enabled | Special day - Enabled; Modbus CS213 | Write | ||
| BV | 214 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[5].Enabled | Special day - Enabled; Modbus CS214 | Write | ||
| BV | 215 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[6].Enabled | Special day - Enabled; Modbus CS215 | Write | ||
| BV | 216 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[7].Enabled | Special day - Enabled; Modbus CS216 | Write | ||
| BV | 217 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[8].Enabled | Special day - Enabled; Modbus CS217 | Write | ||
| BV | 218 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[9].Enabled | Special day - Enabled; Modbus CS218 | Write | ||
| BV | 219 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[10].Enabled | Special day - Enabled; Modbus CS219 | Write | ||
| BV | 220 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[11].Enabled | Special day - Enabled; Modbus CS220 | Write | ||
| BV | 221 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[12].Enabled | Special day - Enabled; Modbus CS221 | Write | ||
| BV | 222 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[13].Enabled | Special day - Enabled; Modbus CS222 | Write | ||
| BV | 223 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[14].Enabled | Special day - Enabled; Modbus CS223 | Write | ||
| BV | 224 | Scheduler_OnOffUnit.En_PartyMode | Enable Party mode from c.pCO; Modbus CS224 | Write | ||
| BV | 225 | En_RetFan | Enable return fan; Modbus CS225 | Write | ||
| BV | 226 | En_DehumReg | Enable dehumidification regulation; Modbus CS226 | Write | ||
| BV | 227 | Dehum_En_KWaterDWP | Dehumidification: enable kwater dew point calculation; Modbus CS227 | Write | ||
| BV | 228 | En_WarmUp | Enable warm up procedure during start up state; Modbus CS228 | Write | ||
| BV | 229 | En_AfreezeOffState | Enable antifreeze during off state; Modbus CS229 | Write | ||
| BV | 230 | RegPrbErrMode | FALSE=forced off; TRUE=manual activation; Modbus CS230 | Write | ||
| BV | 231 | StateMachine.En_RegPrbErr_UnitOff | Enabling of the regulation probe error status during the off state; Modbus CS231 | Write | ||
| BV | 232 | En_THTN | Enable th-Tune management; Modbus CS232 | Write | ||
| BVmin | 234 | Scheduler_OnOffUnit.BMS_OnOff_En | Enable on/off request by BMS; Modbus CS234 | Write | ||
| BV | 236 | En_VDI | Enable VDI management; Modbus CS236 | Write | ||
| BV | 237 | En_VDI_HiSatHumStartUp | VDI high saturation humidity startup enabled; Modbus CS237 | Write | ||
| BV | 238 | RetFanPrefRunDir | Preferred running direction (FALSE: left; TRUE: right) for fan; Modbus CS238 | Write | ||
| BV | 239 | RetFan_En_EmergFunct | Enable emergency function (FALSE: Inactive; TRUE: Active; ) for Ebmpapst fan; Modbus CS239 | Write | ||
| BV | 245 | En_Fan_CO2_Reg | Enable air quality regulation for fans; Modbus CS245 | Write | ||
| BV | 246 | En_FanTempLim | Enable fan temperature limit regulation; Modbus CS246 | Write | ||
| BV | 247 | En_FC_FH_FanReg | Enable fan regulation in case of FreeCooling/FreeHeating; Modbus CS247 | Write | ||
| BV | 248 | En_NightMinVent | Enable night minimum ventilation; Modbus CS248 | Write | ||
| BV | 249 | NightVentPriority | Priority between minimum ventilation and night free cooling (FALSE: minimum ...; Modbus CS249 | Write | ||
| BV | 250 | Antifreeze.DisLowSupplyTempAlrm | Disable Low supply temperature alarm; Modbus CS250 | Write | ||
| BV | 251 | Regulation.EnCompNightVent | Enable compressor during night ventilation; Modbus CS251 | Write | ||
| BV | 252 | Humisonic.ManDrain_HUMS | Manual drain request: FALSE=no request; TRUE=request to drain; Modbus CS252 | Write | ||
| BV | 253 | Humisonic.DevSettings_HUMS.HrsCountRes | Parameters for device configuration - Hours counter reset request; Modbus CS253 | Write | ||
| BV | 254 | SupplyFanPrefRunDir | Preferred running direction (FALSE: left; TRUE: right) for fan; Modbus CS254 | Write | ||
| BV | 255 | SupplyFan_En_EmergFunct | Settings of the emergency function - Enable emergency function (FALSE: ...; Modbus CS255 | Write | ||
| BV | 261 | AuxReg1_Cfg.DOut_ErrorValue | Auxiliary Regulation 1 - Dout: Error value; Modbus CS261 | Write | ||
| BV | 262 | AuxReg1_Cfg.EnableSel_ManualEn | Auxiliary Regulation 1 - Enable selection: Manual enabling; Modbus CS262 | Write | ||
| BV | 263 | AuxReg1_Cfg.En_ComfortReg | Auxiliary Regulation 1 - Enable comfort auxiliary regulation; Modbus CS263 | Write | ||
| BV | 264 | AuxReg1_Cfg.ReverseMode | Auxiliary Regulation 1 - Reverse mode; Modbus CS264 | Write | ||
| BV | 266 | AuxReg1_Cfg.ManModeEn | Auxiliary Regulation 1 - Manual mode enabled; Modbus CS266 | Write | ||
| BV | 267 | AuxReg1_Cfg.DOut_ManModeVal | Auxiliary Regulation 1 - Dout: Manual mode value; Modbus CS267 | Write | ||
| BV | 268 | AuxReg2_Cfg.DOut_ErrorValue | Auxiliary Regulation 2 - Dout: Error value; Modbus CS268 | Write | ||
| BV | 269 | AuxReg2_Cfg.EnableSel_ManualEn | Auxiliary Regulation 2 - Enable selection: Manual enabling; Modbus CS269 | Write | ||
| BV | 270 | AuxReg2_Cfg.En_ComfortReg | Auxiliary Regulation 2 - Enable comfort auxiliary regulation; Modbus CS270 | Write | ||
| BV | 271 | AuxReg2_Cfg.ReverseMode | Auxiliary Regulation 2 - Reverse mode; Modbus CS271 | Write | ||
| BV | 273 | AuxReg2_Cfg.ManModeEn | Auxiliary Regulation 2 - Manual mode enabled; Modbus CS273 | Write | ||
| BV | 274 | AuxReg2_Cfg.DOut_ManModeVal | Auxiliary Regulation 2 - Dout: Manual mode value; Modbus CS274 | Write | ||
| BV | 275 | AuxReg3_Cfg.DOut_ErrorValue | Auxiliary Regulation 3 - Dout: Error value; Modbus CS275 | Write | ||
| BV | 276 | AuxReg3_Cfg.EnableSel_ManualEn | Auxiliary Regulation 3 - Enable selection: Manual enabling; Modbus CS276 | Write | ||
| BV | 277 | AuxReg3_Cfg.En_ComfortReg | Auxiliary Regulation 3 - Enable comfort auxiliary regulation; Modbus CS277 | Write | ||
| BV | 278 | AuxReg3_Cfg.ReverseMode | Auxiliary Regulation 3 - Reverse mode; Modbus CS278 | Write | ||
| BV | 280 | AuxReg3_Cfg.ManModeEn | Auxiliary Regulation 3 - Manual mode enabled; Modbus CS280 | Write | ||
| BV | 281 | AuxReg3_Cfg.DOut_ManModeVal | Auxiliary Regulation 3 - Dout: Manual mode value; Modbus CS281 | Write | ||
| BV | 282 | AuxReg4_Cfg.DOut_ErrorValue | Auxiliary Regulation 4 - Dout: Error value; Modbus CS282 | Write | ||
| BV | 283 | AuxReg4_Cfg.EnableSel_ManualEn | Auxiliary Regulation 4 - Enable selection: Manual enabling; Modbus CS283 | Write | ||
| BV | 284 | AuxReg4_Cfg.En_ComfortReg | Auxiliary Regulation 4 - Enable comfort auxiliary regulation; Modbus CS284 | Write | ||
| BV | 285 | AuxReg4_Cfg.ReverseMode | Auxiliary Regulation 4 - Reverse mode; Modbus CS285 | Write | ||
| BV | 287 | AuxReg4_Cfg.ManModeEn | Auxiliary Regulation 4 - Manual mode enabled; Modbus CS287 | Write | ||
| BV | 288 | AuxReg4_Cfg.DOut_ManModeVal | Auxiliary Regulation 4 - Dout: Manual mode value; Modbus CS288 | Write | ||
| BV | 289 | En_Damp_CO2_Reg | Enable air quality regulation for fresh air OR mixing damper; Modbus CS289 | Write | ||
| BV | 290 | En_FC_FH_DampReg | Enable dampers regulation in case of FreeCooling/FreeHeating; Modbus CS290 | Write | ||
| BV | 291 | CompTyp | Compressor type (FALSE: ON/OFF; TRUE: BLDC); Modbus CS291 | Write | ||
| BV | 292 | En_EVD_Emb_1 | Enable EVD emb management; Modbus CS292 | Write | ||
| BV | 293 | Coils.MainCoil_PmpFlwChk_EnAntiLock | Cooling/Heating coil pumps enable antilock function; Modbus CS293 | Write | ||
| BV | 294 | Coils.PreHeatCoil_PmpFlwChk_EnAntiLock | PreHeating coil pumps enable antilock function; Modbus CS294 | Write | ||
| BV | 295 | Coils.ReHeatCoil_PmpFlwChk_EnAntiLock | Re Heating coil pumps enable antilock function; Modbus CS295 | Write | ||
| BV | 296 | VDI_Conf[0].Enabled | Enable of the VDI function; Modbus CS296 | Write | ||
| BV | 297 | VDI_Conf[0].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS297 | Write | ||
| BV | 298 | VDI_Conf[1].Enabled | Enable of the VDI function; Modbus CS298 | Write | ||
| BV | 299 | VDI_Conf[1].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS299 | Write | ||
| BV | 300 | VDI_Conf[2].Enabled | Enable of the VDI function; Modbus CS300 | Write | ||
| BV | 301 | VDI_Conf[2].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS301 | Write | ||
| BV | 302 | VDI_Conf[3].Enabled | Enable of the VDI function; Modbus CS302 | Write | ||
| BV | 303 | VDI_Conf[3].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS303 | Write | ||
| BV | 304 | VDI_Conf[4].Enabled | Enable of the VDI function; Modbus CS304 | Write | ||
| BV | 305 | VDI_Conf[4].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS305 | Write | ||
| BV | 306 | VDI_Conf[5].Enabled | Enable of the VDI function; Modbus CS306 | Write | ||
| BV | 307 | VDI_Conf[5].ResCmd | Reset timings after the inspection; Modbus CS307 | Write | ||
| BV | 308 | VDI_Conf[6].Enabled | Enable of the VDI function; Modbus CS308 | Write | ||
| BV | 309 | VDI_Conf[6].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS309 | Write | ||
| BV | 310 | VDI_Conf[7].Enabled | Enable of the VDI function; Modbus CS310 | Write | ||
| BV | 311 | VDI_Conf[7].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS311 | Write | ||
| BV | 312 | VDI_Conf[8].Enabled | Enable of the VDI function; Modbus CS312 | Write | ||
| BV | 313 | VDI_Conf[8].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS313 | Write | ||
| BV | 314 | VDI_Conf[9].Enabled | Enable of the VDI function; Modbus CS314 | Write | ||
| BV | 315 | VDI_Conf[9].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS315 | Write | ||
| BV | 316 | VDI_Conf[10].Enabled | Enable of the VDI function; Modbus CS316 | Write | ||
| BV | 317 | VDI_Conf[10].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS317 | Write | ||
| BV | 318 | VDI_Conf[11].Enabled | Enable of the VDI function; Modbus CS318 | Write | ||
| BV | 319 | VDI_Conf[11].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS319 | Write | ||
| BV | 320 | VDI_Conf[12].Enabled | Enable of the VDI function; Modbus CS320 | Write | ||
| BV | 321 | VDI_Conf[12].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS321 | Write | ||
| BV | 322 | VDI_Conf[13].Enabled | Enable of the VDI function; Modbus CS322 | Write | ||
| BV | 323 | VDI_Conf[13].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS323 | Write | ||
| BV | 324 | VDI_Conf[14].Enabled | Enable of the VDI function; Modbus CS324 | Write | ||
| BV | 325 | VDI_Conf[14].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS325 | Write | ||
| BV | 326 | VDI_Conf[15].Enabled | Enable of the VDI function; Modbus CS326 | Write | ||
| BV | 327 | VDI_Conf[15].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS327 | Write | ||
| BV | 328 | VDI_Conf[16].Enabled | Enable of the VDI function; Modbus CS328 | Write | ||
| BV | 329 | VDI_Conf[16].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS329 | Write | ||
| BV | 330 | VDI_Conf[17].Enabled | Enable of the VDI function; Modbus CS330 | Write | ||
| BV | 331 | VDI_Conf[17].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS331 | Write | ||
| BV | 332 | VDI_Conf[18].Enabled | Enable of the VDI function; Modbus CS332 | Write | ||
| BV | 333 | VDI_Conf[18].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS333 | Write | ||
| BV | 334 | VDI_Conf[19].Enabled | Enable of the VDI function; Modbus CS334 | Write | ||
| BV | 335 | VDI_Conf[19].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS335 | Write | ||
| BV | 336 | VDI_Conf[20].Enabled | Enable of the VDI function; Modbus CS336 | Write | ||
| BV | 337 | VDI_Conf[20].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS337 | Write | ||
| BV | 338 | VDI_Conf[21].Enabled | Enable of the VDI function; Modbus CS338 | Write | ||
| BV | 339 | VDI_Conf[21].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS339 | Write | ||
| BV | 340 | VDI_Conf[22].Enabled | Enable of the VDI function; Modbus CS340 | Write | ||
| BV | 341 | VDI_Conf[22].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS341 | Write | ||
| BV | 342 | VDI_Conf[23].Enabled | Enable of the VDI function; Modbus CS342 | Write | ||
| BV | 343 | VDI_Conf[23].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS343 | Write | ||
| BV | 344 | VDI_Conf[24].Enabled | Enable of the VDI function; Modbus CS344 | Write | ||
| BV | 345 | VDI_Conf[24].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS345 | Write | ||
| BV | 346 | VDI_Conf[25].Enabled | Enable of the VDI function; Modbus CS346 | Write | ||
| BV | 347 | VDI_Conf[25].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS347 | Write | ||
| BV | 348 | VDI_Conf[26].Enabled | Enable of the VDI function; Modbus CS348 | Write | ||
| BV | 349 | VDI_Conf[26].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS349 | Write | ||
| BV | 350 | VDI_Conf[27].Enabled | Enable of the VDI function; Modbus CS350 | Write | ||
| BV | 351 | VDI_Conf[27].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS351 | Write | ||
| BV | 352 | VDI_Conf[28].Enabled | Enable of the VDI function; Modbus CS352 | Write | ||
| BV | 353 | VDI_Conf[28].AlrmTyp | Reset type (FALSE: Blocker Alarm; TRUE: Warning); Modbus CS353 | Write | ||
| BV | 354 | VDI_Conf[0].ResCmd | Reset timings after the inspection; Modbus CS354 | Write | ||
| BV | 355 | VDI_Conf[1].ResCmd | Reset timings after the inspection; Modbus CS355 | Write | ||
| BV | 356 | VDI_Conf[2].ResCmd | Reset timings after the inspection; Modbus CS356 | Write | ||
| BV | 357 | VDI_Conf[3].ResCmd | Reset timings after the inspection; Modbus CS357 | Write | ||
| BV | 358 | VDI_Conf[4].ResCmd | Reset timings after the inspection; Modbus CS358 | Write | ||
| BV | 359 | VDI_Conf[6].ResCmd | Reset timings after the inspection; Modbus CS359 | Write | ||
| BV | 360 | VDI_Conf[7].ResCmd | Reset timings after the inspection; Modbus CS360 | Write | ||
| BV | 361 | VDI_Conf[8].ResCmd | Reset timings after the inspection; Modbus CS361 | Write | ||
| BV | 362 | VDI_Conf[9].ResCmd | Reset timings after the inspection; Modbus CS362 | Write | ||
| BV | 363 | VDI_Conf[10].ResCmd | Reset timings after the inspection; Modbus CS363 | Write | ||
| BV | 364 | VDI_Conf[11].ResCmd | Reset timings after the inspection; Modbus CS364 | Write | ||
| BV | 365 | VDI_Conf[12].ResCmd | Reset timings after the inspection; Modbus CS365 | Write | ||
| BV | 366 | VDI_Conf[13].ResCmd | Reset timings after the inspection; Modbus CS366 | Write | ||
| BV | 367 | VDI_Conf[14].ResCmd | Reset timings after the inspection; Modbus CS367 | Write | ||
| BV | 368 | VDI_Conf[15].ResCmd | Reset timings after the inspection; Modbus CS368 | Write | ||
| BV | 369 | VDI_Conf[16].ResCmd | Reset timings after the inspection; Modbus CS369 | Write | ||
| BV | 370 | VDI_Conf[17].ResCmd | Reset timings after the inspection; Modbus CS370 | Write | ||
| BV | 371 | VDI_Conf[18].ResCmd | Reset timings after the inspection; Modbus CS371 | Write | ||
| BV | 372 | VDI_Conf[19].ResCmd | Reset timings after the inspection; Modbus CS372 | Write | ||
| BV | 373 | VDI_Conf[20].ResCmd | Reset timings after the inspection; Modbus CS373 | Write | ||
| BV | 374 | VDI_Conf[21].ResCmd | Reset timings after the inspection; Modbus CS374 | Write | ||
| BV | 375 | VDI_Conf[22].ResCmd | Reset timings after the inspection; Modbus CS375 | Write | ||
| BV | 376 | VDI_Conf[23].ResCmd | Reset timings after the inspection; Modbus CS376 | Write | ||
| BV | 377 | VDI_Conf[24].ResCmd | Reset timings after the inspection; Modbus CS377 | Write | ||
| BV | 378 | VDI_Conf[25].ResCmd | Reset timings after the inspection; Modbus CS378 | Write | ||
| BV | 379 | VDI_Conf[26].ResCmd | Reset timings after the inspection; Modbus CS379 | Write | ||
| BV | 380 | VDI_Conf[27].ResCmd | Reset timings after the inspection; Modbus CS380 | Write | ||
| BV | 381 | VDI_Conf[28].ResCmd | Reset timings after the inspection; Modbus CS381 | Write | ||
| BV | 382 | GeneralMng.En_Buzz | Enable of Buzzer; Modbus CS382 | Write | ||
| BV | 383 | En_LiqSolVlv | Enable liquid solenoid valve; Modbus CS384 | Write | ||
| BV | 384 | EVD_Emb_Circ.EEV_ManPositEn | EEV enable manual position; Modbus CS385 | Write | ||
| BV | 385 | Data_EVD_Emb_1.EVD.System.DC_SupplyEn.Val | EVD parameters - System configuration - DC power supply enabling; Modbus CS386 | Write | ||
| BV | 386 | Data_EVD_Emb_1.EVD.EEV_Config.ExtraOpEn.Val | EVD parameters - Valve configuration - EEV opening position synchronization; Modbus CS387 | Write | ||
| BV | 387 | Data_EVD_Emb_1.EVD.EEV_Config.ExtraClosEn.Val | EVD parameters - Valve configuration - EEV closing position synchronization; Modbus CS388 | Write | ||
| BV | 388 | BLDC_compressor.MiscMng_PWRP1.Mng_SerNoCtrl_En | Serial number control enable; Modbus CS389 | Write | ||
| BV | 389 | BLDC_compressor.CurrCompCfg_PWRP1.HR22_0_SpeedProfStartMode | Curr compressor configuration (Powerplus) - Speed profile start mode (0= ...; Modbus CS390 | Write | ||
| BV | 390 | BLDC_compressor.CurrCompCfg_PWRP1.HR22_1_SpeedProfStartMode | Curr compressor configuration (Powerplus) - Speed profile start mode (0=-; ...; Modbus CS391 | Write | ||
| BV | 391 | BLDC_compressor.CurrCompCfg_PWRP1.HR76_0_DisPhLossDetect | Curr compressor configuration (Powerplus) - Disable phase loss algorithm (0=enabled; 1=disabled); Modbus CS392 | Write | ||
| BV | 392 | BLDC_compressor.CurrCompCfg_PWRP1.HR76_3_EnOvldThProtRetention | Curr compressor configuration (Powerplus) - Thermal Overload Retention Enable; Modbus CS393 | Write | ||
| BV | 393 | BLDC_compressor.MiscMng_PWRP1.MngCstm_SaveCustomCfg | Save custom config. command; Modbus CS394 | Write | ||
| BV | 394 | BLDC_compressor.AlrmResetMng_PWRP1.Al01_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS395 | Write | ||
| BV | 395 | BLDC_compressor.AlrmResetMng_PWRP1.Al02_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS396 | Write | ||
| BV | 396 | BLDC_compressor.AlrmResetMng_PWRP1.Al03_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS397 | Write | ||
| BV | 397 | BLDC_compressor.AlrmResetMng_PWRP1.Al04_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS398 | Write | ||
| BV | 398 | BLDC_compressor.AlrmResetMng_PWRP1.Al05_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS399 | Write | ||
| BV | 399 | BLDC_compressor.AlrmResetMng_PWRP1.Al06_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS400 | Write | ||
| BV | 400 | BLDC_compressor.AlrmResetMng_PWRP1.Al07_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS401 | Write | ||
| BV | 401 | BLDC_compressor.AlrmResetMng_PWRP1.Al08_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS402 | Write | ||
| BV | 402 | BLDC_compressor.AlrmResetMng_PWRP1.Al09_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS403 | Write | ||
| BV | 403 | BLDC_compressor.AlrmResetMng_PWRP1.Al10_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS404 | Write | ||
| BV | 404 | BLDC_compressor.AlrmResetMng_PWRP1.Al11_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS405 | Write | ||
| BV | 405 | BLDC_compressor.AlrmResetMng_PWRP1.Al12_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS406 | Write | ||
| BV | 406 | BLDC_compressor.AlrmResetMng_PWRP1.Al13_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS407 | Write | ||
| BV | 407 | BLDC_compressor.AlrmResetMng_PWRP1.Al14_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS408 | Write | ||
| BV | 408 | BLDC_compressor.AlrmResetMng_PWRP1.Al15_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS409 | Write | ||
| BV | 409 | BLDC_compressor.AlrmResetMng_PWRP1.Al16_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS410 | Write | ||
| BV | 410 | BLDC_compressor.AlrmResetMng_PWRP1.Al17_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS411 | Write | ||
| BV | 411 | BLDC_compressor.AlrmResetMng_PWRP1.Al18_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS412 | Write | ||
| BV | 412 | BLDC_compressor.AlrmResetMng_PWRP1.Al19_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS413 | Write | ||
| BV | 413 | BLDC_compressor.AlrmResetMng_PWRP1.Al20_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS414 | Write | ||
| BV | 414 | BLDC_compressor.AlrmResetMng_PWRP1.Al21_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS415 | Write | ||
| BV | 415 | BLDC_compressor.AlrmResetMng_PWRP1.Al22_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS416 | Write | ||
| BV | 416 | BLDC_compressor.AlrmResetMng_PWRP1.Al23_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS417 | Write | ||
| BV | 417 | BLDC_compressor.AlrmResetMng_PWRP1.Al24_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS418 | Write | ||
| BV | 418 | BLDC_compressor.AlrmResetMng_PWRP1.Al25_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS419 | Write | ||
| BV | 419 | BLDC_compressor.AlrmResetMng_PWRP1.Al26_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS420 | Write | ||
| BV | 420 | BLDC_compressor.AlrmResetMng_PWRP1.Al27_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS421 | Write | ||
| BV | 421 | BLDC_compressor.AlrmResetMng_PWRP1.Al28_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS422 | Write | ||
| BV | 422 | BLDC_compressor.AlrmResetMng_PWRP1.Al99_uMotorResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS423 | Write | ||
| BV | 423 | BLDC_compressor.AlrmResetMng_PWRP1.Al101_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS424 | Write | ||
| BV | 424 | BLDC_compressor.AlrmResetMng_PWRP1.Al102_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS425 | Write | ||
| BV | 425 | BLDC_compressor.AlrmResetMng_PWRP1.Al103_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS426 | Write | ||
| BV | 426 | BLDC_compressor.AlrmResetMng_PWRP1.Al104_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS427 | Write | ||
| BV | 427 | BLDC_compressor.AlrmResetMng_PWRP1.Al105_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS428 | Write | ||
| BV | 428 | BLDC_compressor.AlrmResetMng_PWRP1.Al106_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS429 | Write | ||
| BV | 429 | BLDC_compressor.AlrmResetMng_PWRP1.Al107_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS430 | Write | ||
| BV | 430 | BLDC_compressor.AlrmResetMng_PWRP1.Al108_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS431 | Write | ||
| BV | 431 | BLDC_compressor.AlrmResetMng_PWRP1.Al109_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS432 | Write | ||
| BV | 432 | BLDC_compressor.AlrmResetMng_PWRP1.Al110_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS433 | Write | ||
| BV | 433 | BLDC_compressor.AlrmResetMng_PWRP1.Al111_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS434 | Write | ||
| BV | 434 | BLDC_compressor.AlrmResetMng_PWRP1.Al112_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS435 | Write | ||
| BV | 435 | BLDC_compressor.AlrmResetMng_PWRP1.Al113_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS436 | Write | ||
| BV | 436 | BLDC_compressor.AlrmResetMng_PWRP1.Al114_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS437 | Write | ||
| BV | 437 | BLDC_compressor.AlrmResetMng_PWRP1.Al115_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS438 | Write | ||
| BV | 438 | BLDC_compressor.AlrmResetMng_PWRP1.Al116_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS439 | Write | ||
| BV | 439 | BLDC_compressor.AlrmResetMng_PWRP1.Al201_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS440 | Write | ||
| BV | 440 | BLDC_compressor.AlrmResetMng_PWRP1.Al202_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS441 | Write | ||
| BV | 441 | BLDC_compressor.AlrmResetMng_PWRP1.Al203_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS442 | Write | ||
| BV | 442 | BLDC_compressor.AlrmResetMng_PWRP1.Al204_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS443 | Write | ||
| BV | 443 | BLDC_compressor.AlrmResetMng_PWRP1.Al205_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS444 | Write | ||
| BV | 444 | BLDC_compressor.AlrmResetMng_PWRP1.Al206_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS445 | Write | ||
| BV | 445 | BLDC_compressor.AlrmResetMng_PWRP1.Al207_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS446 | Write | ||
| BV | 446 | BLDC_compressor.AlrmResetMng_PWRP1.Al208_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS447 | Write | ||
| BV | 447 | BLDC_compressor.AlrmResetMng_PWRP1.Al209_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS448 | Write | ||
| BV | 448 | BLDC_compressor.AlrmResetMng_PWRP1.Al210_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS449 | Write | ||
| BV | 449 | BLDC_compressor.AlrmResetMng_PWRP1.Al211_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS450 | Write | ||
| BV | 450 | BLDC_compressor.AlrmResetMng_PWRP1.Al212_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS451 | Write | ||
| BV | 451 | BLDC_compressor.AlrmResetMng_PWRP1.Al213_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS452 | Write | ||
| BV | 452 | BLDC_compressor.AlrmResetMng_PWRP1.Al214_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS453 | Write | ||
| BV | 453 | BLDC_compressor.AlrmResetMng_PWRP1.Al215_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS454 | Write | ||
| BV | 454 | BLDC_compressor.AlrmResetMng_PWRP1.Al216_uSafeResetTyp | Reset type: 0=Manual - 1=Semiautomatic; Modbus CS455 | Write | ||
| BV | 455 | BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_EnEqualBPVlv | BLDC envelope configuration - By-pass equalization solenoid valve enable; Modbus CS456 | Write | ||
| BV | 456 | BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_EnMopLowCompRatio | BLDC envelope configuration - Enable MOP control in low compression ...; Modbus CS457 | Write | ||
| BV | 457 | BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_EnSpeedUpMode | BLDC envelope configuration - Speed up mode enable to control ...; Modbus CS458 | Write | ||
| BV | 458 | BLDC_compressor.AlrmResetMng_BLDC_1.ResetTyp_BLDC_Alrm | Reset type: 0= Manual - 1= Semiautomatic; Modbus CS459 | Write | ||
| BV | 4011 | SanificationDevice.LogicDout_RW | Sanification device - Logic; Modbus CS460 | Write | ||
| BV | 3957 | En_SanificationDevice | Enable sanification device; Modbus CS461 | Write | ||
| BV | 4035 | PurgeCmd | Purge command ( 0: NO, 1: START); Modbus CS462 | Write | ||
| BV | 4036 | SanificationDeviceOvld.LogicDin_RW | Sanification deivce overload switch - Logic; Modbus CS463 | Write | ||
| BV | 4037 | SanificationDeviceOvld.Enable_W | Sanification deivce overload switch - Enable input; Modbus CS464 | Write | ||
| BV | 4025 | En_OilRecov | Enable BLDC oil recovery function; Modbus CS465 | Write | ||
| BV | 4288 | CstPrbCfg.Temp1FactOp | Custom serial probe - Factor Operator - Temp1; Modbus CS466 | Write | ||
| BV | 4289 | CstPrbCfg.Temp2FactOp | Custom serial probe - Factor Operator – Temp2; Modbus CS467 | Write | ||
| BV | 4290 | CstPrbCfg.Hum1FactOp | Custom serial probe - Factor Operator - Hum1; Modbus CS468 | Write | ||
| BV | 4291 | CstPrbCfg.Hum2FactOp | Custom serial probe - Factor Operator – Hum2; Modbus CS469 | Write | ||
| BV | 4292 | CstPrbCfg.Press1FactOp | Custom serial probe - Factor Operator - Press1; Modbus CS470 | Write | ||
| BV | 4293 | CstPrbCfg.Press2FactOp | Custom serial probe - Factor Operator – Press2; Modbus CS471 | Write | ||
| BV | 4294 | CstPrbCfg.Flow1FactOp | Custom serial probe - Factor Operator - Flow1; Modbus CS472 | Write | ||
| BV | 4295 | CstPrbCfg.Flow2FactOp | Custom serial probe - Factor Operator – Flow2; Modbus CS473 | Write | ||
| BV | 4342 | HumiSteamMng.Man_UEY.EnMan | HumiSteam - Manual management - Enable manual management; Modbus CS474 | Write | ||
| BV | 4343 | HumiSteamMng.Man_UEY.PreCleaning | HumiSteam - Manual management - Manual pre cleaning; Modbus CS475 | Write | ||
| BV | 4344 | HumiSteamMng.Man_UEY.Drn | HumiSteam - Manual management - Manual drain; Modbus CS476 | Write | ||
| BV | 4345 | HumiSteamMng.ResWorkHrs_UEY | HumiSteam - Reset working hours; Modbus CS477 | Write | ||
| BV | 4367 | MainCoilCoolHeat_Din.LogicDin_RW | Main coil cool/heat - digital input - Logic; Modbus CS478 | Write | ||
| BV | 4369 | En_FanTempReg | Enable fan temperature regulation; Modbus CS479 | Write | ||
| BV | 4447 | GenericDin1.LogicDin_RW | Generic Din1 - digital input - Logic; Modbus CS480 | Write | ||
| BV | 4454 | GenericDin2.LogicDin_RW | Generic Din2 - digital input - Logic; Modbus CS481 | Write | ||
| BV | 4461 | GenericDin3.LogicDin_RW | Generic Din3 - digital input - Logic; Modbus CS482 | Write | ||
| BV | 4468 | GenericDin4.LogicDin_RW | Generic Din4 - digital input - Logic; Modbus CS483 | Write | ||
| BV | 4475 | GenericDin5.LogicDin_RW | Generic Din5 - digital input - Logic; Modbus CS484 | Write | ||
| BV | 4499 | IEC_EnMan | IEC: manual mode enable; Modbus CS485 | Write | ||
| BV | 4504 | BMS_Reg_DigitalPrbMap[1] | BMS registers - Digital map – 1; Modbus CS486 | Write | ||
| BV | 4505 | BMS_Reg_DigitalPrbMap[2] | BMS registers - Digital map – 2; Modbus CS487 | Write | ||
| BV | 4506 | BMS_Reg_DigitalPrbMap[3] | BMS registers - Digital map – 3; Modbus CS488 | Write | ||
| BV | 4507 | BMS_Reg_DigitalPrbMap[4] | BMS registers - Digital map – 4; Modbus CS489 | Write | ||
| BV | 4508 | BMS_Reg_DigitalPrbMap[5] | BMS registers - Digital map – 5; Modbus CS490 | Write | ||
| BV | 4514 | OA_Vlv_Open.LogicDout_RW | Outdoor air pre-treatment floating valve open - Logic; Modbus CS491 | Write | ||
| BV | 4515 | OA_Vlv_Close.LogicDout_RW | Outdoor air pre-treatment floating valve close - Logic; Modbus CS492 | Write | ||
| BV | 4516 | OA_CoilEnMan | Outdoor air pre-treatment coil manual mode enable; Modbus CS493 | Write | ||
| BV | 459 | MainCoil_CoolHeatMode | Cooling/Heating coil working mode; Modbus DI001 | Read | ||
| BV | 461 | SupplyTemp.Enable_W | Supply temperature - Enable input; Modbus DI003 | Read | ||
| BV | 462 | SupplyTemp.Configured_R | Supply temperature - Analog input configured; Modbus DI004 | Read | ||
| BV | 463 | SupplyTemp.PrbOk_R | Supply temperature - Probe working correctly; Modbus DI005 | Read | ||
| BV | 464 | SupplyTemp.Alrm_R | Supply temperature - Alarm probe broken or disconnected; Modbus DI006 | Read | ||
| BV | 465 | SupplyHum.Enable_W | Supply humidity - Enable input; Modbus DI007 | Read | ||
| BV | 466 | SupplyHum.Configured_R | Supply humidity - Analog input configured; Modbus DI008 | Read | ||
| BV | 467 | SupplyHum.PrbOk_R | Supply humidity - Probe working correctly; Modbus DI009 | Read | ||
| BV | 468 | SupplyHum.Alrm_R | Supply humidity - Alarm probe broken or disconnected; Modbus DI010 | Read | ||
| BV | 469 | RetTemp.Enable_W | Return temperature - Enable input; Modbus DI011 | Read | ||
| BV | 470 | RetTemp.Configured_R | Return temperature - Analog input configured; Modbus DI012 | Read | ||
| BV | 471 | RetTemp.PrbOk_R | Return temperature - Probe working correctly; Modbus DI013 | Read | ||
| BV | 472 | RetTemp.Alrm_R | Return temperature - Alarm probe broken or disconnected; Modbus DI014 | Read | ||
| BV | 473 | RetHum.Enable_W | Return humidity - Enable input; Modbus DI015 | Read | ||
| BV | 474 | RetHum.Configured_R | Return humidity - Analog input configured; Modbus DI016 | Read | ||
| BV | 475 | RetHum.PrbOk_R | Return humidity - Probe working correctly; Modbus DI017 | Read | ||
| BV | 476 | RetHum.Alrm_R | Return humidity - Alarm probe broken or disconnected; Modbus DI018 | Read | ||
| BV | 477 | RoomTemp.Enable_W | Room temperature - Enable input; Modbus DI019 | Read | ||
| BV | 478 | RoomTemp.Configured_R | Room temperature - Analog input configured; Modbus DI020 | Read | ||
| BV | 479 | RoomTemp.PrbOk_R | Room temperature - Probe working correctly; Modbus DI021 | Read | ||
| BV | 480 | RoomTemp.Alrm_R | Room temperature - Alarm probe broken or disconnected; Modbus DI022 | Read | ||
| BV | 481 | RoomHum.Enable_W | Room humidity - Enable input; Modbus DI023 | Read | ||
| BV | 482 | RoomHum.Configured_R | Room humidity - Analog input configured; Modbus DI024 | Read | ||
| BV | 483 | RoomHum.PrbOk_R | Room humidity - Probe working correctly; Modbus DI025 | Read | ||
| BV | 484 | RoomHum.Alrm_R | Room humidity - Alarm probe broken or disconnected; Modbus DI026 | Read | ||
| BV | 485 | ExtTemp.Enable_W | Fresh air temperature - Enable input; Modbus DI027 | Read | ||
| BV | 487 | ExtTemp.PrbOk_R | Fresh air temperature - Probe working correctly; Modbus DI029 | Read | ||
| BV | 488 | ExtTemp.Alrm_R | Fresh air temperature - Alarm probe broken or disconnected; Modbus DI030 | Read | ||
| BV | 489 | ExtHum.Enable_W | Fresh air humidity - Enable input; Modbus DI031 | Read | ||
| BV | 490 | ExtHum.Configured_R | Fresh air humidity - Analog input configured; Modbus DI032 | Read | ||
| BV | 491 | ExtHum.PrbOk_R | Fresh air humidity - Probe working correctly; Modbus DI033 | Read | ||
| BV | 492 | ExtHum.Alrm_R | Fresh air humidity - Alarm probe broken or disconnected; Modbus DI034 | Read | ||
| BV | 493 | ExhTemp.Enable_W | Exhaust temperature - Enable input; Modbus DI035 | Read | ||
| BV | 494 | ExhTemp.Configured_R | Exhaust temperature - Analog input configured; Modbus DI036 | Read | ||
| BV | 495 | ExhTemp.PrbOk_R | Exhaust temperature - Probe working correctly; Modbus DI037 | Read | ||
| BV | 496 | ExhTemp.Alrm_R | Exhaust temperature - Alarm probe broken or disconnected; Modbus DI038 | Read | ||
| BV | 497 | ExhHum.Enable_W | Exhaust humidity - Enable input; Modbus DI039 | Read | ||
| BV | 498 | ExhHum.Configured_R | Exhaust humidity - Analog input configured; Modbus DI040 | Read | ||
| BV | 499 | ExhHum.PrbOk_R | Exhaust humidity - Probe working correctly; Modbus DI041 | Read | ||
| BV | 500 | ExhHum.Alrm_R | Exhaust humidity - Alarm probe broken or disconnected; Modbus DI042 | Read | ||
| BV | 501 | AFreezeTemp.Enable_W | Antifreeze temperature - Enable input; Modbus DI043 | Read | ||
| BV | 502 | AFreezeTemp.Configured_R | Antifreeze temperature - Analog input configured; Modbus DI044 | Read | ||
| BV | 503 | AFreezeTemp.PrbOk_R | Antifreeze temperature - Probe working correctly; Modbus DI045 | Read | ||
| BV | 504 | AFreezeTemp.Alrm_R | Antifreeze temperature - Alarm probe broken or disconnected; Modbus DI046 | Read | ||
| BV | 505 | SatTemp.Enable_W | Saturation temperature - Enable input; Modbus DI047 | Read | ||
| BV | 507 | SatTemp.PrbOk_R | Saturation temperature - Probe working correctly; Modbus DI049 | Read | ||
| BV | 508 | SatTemp.Alrm_R | Saturation temperature - Alarm probe broken or disconnected; Modbus DI050 | Read | ||
| BV | 509 | SatHum.Enable_W | Saturation humidity - Enable input; Modbus DI051 | Read | ||
| BV | 510 | SatHum.Configured_R | Saturation humidity - Analog input configured; Modbus DI052 | Read | ||
| BV | 511 | SatHum.PrbOk_R | Saturation humidity - Probe working correctly; Modbus DI053 | Read | ||
| BV | 512 | SatHum.Alrm_R | Saturation humidity - Alarm probe broken or disconnected; Modbus DI054 | Read | ||
| BV | 513 | OA_Temp.Enable_W | Outdoor air pre-treatment temperature - Enable input; Modbus DI055 | Read | ||
| BV | 514 | OA_Temp.Configured_R | Outdoor air pre-treatment temperature - Analog input configured; Modbus DI056 | Read | ||
| BV | 515 | OA_Temp.PrbOk_R | Outdoor air pre-treatment temperature - Probe working correctly; Modbus DI057 | Read | ||
| BV | 516 | OA_Temp.Alrm_R | Outdoor air pre-treatment temperature - Alarm probe broken or disconnected; Modbus DI058 | Read | ||
| BV | 517 | SupplyAirP.Enable_W | Supply air pressure - Enable input; Modbus DI059 | Read | ||
| BV | 518 | SupplyAirP.Configured_R | Supply air pressure - Analog input configured; Modbus DI060 | Read | ||
| BV | 519 | SupplyAirP.PrbOk_R | Supply air pressure - Probe working correctly; Modbus DI061 | Read | ||
| BV | 520 | SupplyAirP.Alrm_R | Supply air pressure - Alarm probe broken or disconnected; Modbus DI062 | Read | ||
| BV | 521 | RetAirP.Enable_W | Return air pressure - Enable input; Modbus DI063 | Read | ||
| BV | 522 | RetAirP.Configured_R | Return air pressure - Analog input configured; Modbus DI064 | Read | ||
| BV | 523 | RetAirP.PrbOk_R | Return air pressure - Probe working correctly; Modbus DI065 | Read | ||
| BV | 524 | RetAirP.Alrm_R | Return air pressure - Alarm probe broken or disconnected; Modbus DI066 | Read | ||
| BV | 525 | AirQuality_CO2.Enable_W | CO2 sensor - Enable input; Modbus DI067 | Read | ||
| BV | 526 | AirQuality_CO2.Configured_R | CO2 sensor - Analog input configured; Modbus DI068 | Read | ||
| BV | 527 | AirQuality_CO2.PrbOk_R | CO2 sensor - Probe working correctly; Modbus DI069 | Read | ||
| BV | 528 | AirQuality_CO2.Alrm_R | CO2 sensor - Alarm probe broken or disconnected; Modbus DI070 | Read | ||
| BV | 529 | AirQuality_VOC.Enable_W | VOC sensor - Enable input; Modbus DI071 | Read | ||
| BV | 530 | AirQuality_VOC.Configured_R | VOC sensor - Analog input configured; Modbus DI072 | Read | ||
| BV | 531 | AirQuality_VOC.PrbOk_R | VOC sensor - Probe working correctly; Modbus DI073 | Read | ||
| BV | 532 | AirQuality_VOC.Alrm_R | VOC sensor - Alarm probe broken or disconnected; Modbus DI074 | Read | ||
| BV | 533 | DscgP.Enable_W | Discharge pressure - Enable input; Modbus DI075 | Read | ||
| BV | 534 | DscgP.Configured_R | Discharge pressure - Analog input configured; Modbus DI076 | Read | ||
| BV | 535 | DscgP.PrbOk_R | Discharge pressure - Probe working correctly; Modbus DI077 | Read | ||
| BV | 536 | DscgP.Alrm_R | Discharge pressure - Alarm probe broken or disconnected; Modbus DI078 | Read | ||
| BV | 537 | DscgT.Enable_W | Discharge temperature - Enable input; Modbus DI079 | Read | ||
| BV | 538 | DscgT.Configured_R | Discharge temperature - Analog input configured; Modbus DI080 | Read | ||
| BV | 539 | DscgT.PrbOk_R | Discharge temperature - Probe working correctly; Modbus DI081 | Read | ||
| BV | 540 | DscgT.Alrm_R | Discharge temperature - Alarm probe broken or disconnected; Modbus DI082 | Read | ||
| BV | 541 | SuctP.Enable_W | Suction pressure - Enable input; Modbus DI083 | Read | ||
| BV | 542 | SuctP.Configured_R | Suction pressure - Analog input configured; Modbus DI084 | Read | ||
| BV | 543 | SuctP.PrbOk_R | Suction pressure - Probe working correctly; Modbus DI085 | Read | ||
| BV | 544 | SuctP.Alrm_R | Suction pressure - Alarm probe broken or disconnected; Modbus DI086 | Read | ||
| BV | 545 | SuctT.Enable_W | Suction temperature - Enable input; Modbus DI087 | Read | ||
| BV | 546 | SuctT.Configured_R | Suction temperature - Analog input configured; Modbus DI088 | Read | ||
| BV | 547 | SuctT.PrbOk_R | Suction temperature - Probe working correctly; Modbus DI089 | Read | ||
| BV | 548 | SuctT.Alrm_R | Suction temperature - Alarm probe broken or disconnected; Modbus DI090 | Read | ||
| BV | 549 | OA_CoilWaterTemp.Enable_W | Outdoor air pre-treatment coil water temperature - Enable input; Modbus DI091 | Read | ||
| BV | 550 | OA_CoilWaterTemp.Configured_R | Outdoor air pre-treatment coil water temperature - Analog input configured; Modbus DI092 | Read | ||
| BV | 551 | OA_CoilWaterTemp.PrbOk_R | Outdoor air pre-treatment coil water temperature - Probe working correctly; Modbus DI093 | Read | ||
| BV | 552 | OA_CoilWaterTemp.Alrm_R | Outdoor air pre-treatment coil water temperature - Alarm probe broken ...; Modbus DI094 | Read | ||
| BV | 553 | PreHeatCoilWaterTemp.Enable_W | Preheat coil water temperature - Enable input; Modbus DI095 | Read | ||
| BV | 554 | PreHeatCoilWaterTemp.Configured_R | Preheat coil water temperature - Analog input configured; Modbus DI096 | Read | ||
| BV | 555 | PreHeatCoilWaterTemp.PrbOk_R | Preheat coil water temperature - Probe working correctly; Modbus DI097 | Read | ||
| BV | 556 | PreHeatCoilWaterTemp.Alrm_R | Preheat coil water temperature - Alarm probe broken or disconnected; Modbus DI098 | Read | ||
| BV | 557 | MainCoilWaterTemp.Enable_W | Main coil water temperature - Enable input; Modbus DI099 | Read | ||
| BV | 558 | MainCoilWaterTemp.Configured_R | Main coil water temperature - Analog input configured; Modbus DI100 | Read | ||
| BV | 560 | MainCoilWaterTemp.Alrm_R | Main coil water temperature - Alarm probe broken or disconnected; Modbus DI102 | Read | ||
| BV | 561 | ReHeatCoilWaterTemp.Enable_W | Postheat coil water temperature - Enable input; Modbus DI103 | Read | ||
| BV | 562 | ReHeatCoilWaterTemp.Configured_R | Postheat coil water temperature - Analog input configured; Modbus DI104 | Read | ||
| BV | 563 | ReHeatCoilWaterTemp.PrbOk_R | Postheat coil water temperature - Probe working correctly; Modbus DI105 | Read | ||
| BV | 564 | ReHeatCoilWaterTemp.Alrm_R | Postheat coil water temperature - Alarm probe broken or disconnected; Modbus DI106 | Read | ||
| BV | 565 | AuxPrb_1.Enable_W | Auxiliary probe 1 - Enable input; Modbus DI107 | Read | ||
| BV | 566 | AuxPrb_1.Configured_R | Auxiliary probe 1 - Analog input configured; Modbus DI108 | Read | ||
| BV | 567 | AuxPrb_1.PrbOk_R | Auxiliary probe 1 - Probe working correctly; Modbus DI109 | Read | ||
| BV | 568 | AuxPrb_1.Alrm_R | Auxiliary probe 1 - Alarm probe broken or disconnected; Modbus DI110 | Read | ||
| BV | 569 | AuxPrb_2.Enable_W | Auxiliary probe 2 - Enable input; Modbus DI111 | Read | ||
| BV | 570 | AuxPrb_2.Configured_R | Auxiliary probe 2 - Analog input configured; Modbus DI112 | Read | ||
| BV | 571 | AuxPrb_2.PrbOk_R | Auxiliary probe 2 - Probe working correctly; Modbus DI113 | Read | ||
| BV | 572 | AuxPrb_2.Alrm_R | Auxiliary probe 2 - Alarm probe broken or disconnected; Modbus DI114 | Read | ||
| BV | 573 | AuxPrb_3.Enable_W | Auxiliary probe 3 - Enable input; Modbus DI115 | Read | ||
| BV | 574 | AuxPrb_3.Configured_R | Auxiliary probe 3 - Analog input configured; Modbus DI116 | Read | ||
| BV | 575 | AuxPrb_3.PrbOk_R | Auxiliary probe 3 - Probe working correctly; Modbus DI117 | Read | ||
| BV | 576 | AuxPrb_3.Alrm_R | Auxiliary probe 3 - Alarm probe broken or disconnected; Modbus DI118 | Read | ||
| BV | 577 | AuxPrb_4.Enable_W | Auxiliary probe 4 - Enable input; Modbus DI119 | Read | ||
| BV | 578 | AuxPrb_4.Configured_R | Auxiliary probe 4 - Analog input configured; Modbus DI120 | Read | ||
| BV | 579 | AuxPrb_4.PrbOk_R | Auxiliary probe 4 - Probe working correctly; Modbus DI121 | Read | ||
| BV | 580 | AuxPrb_4.Alrm_R | Auxiliary probe 4 - Alarm probe broken or disconnected; Modbus DI122 | Read | ||
| BV | 581 | Ain_SetP.Enable_W | Setpoint by AIN - Enable input; Modbus DI123 | Read | ||
| BV | 582 | Ain_SetP.Configured_R | Setpoint by AIN - Analog input configured; Modbus DI124 | Read | ||
| BV | 583 | Ain_SetP.PrbOk_R | Setpoint by AIN - Probe working correctly; Modbus DI125 | Read | ||
| BV | 584 | Ain_SetP.Alrm_R | Setpoint by AIN - Alarm probe broken or disconnected; Modbus DI126 | Read | ||
| BV | 585 | SupplyRecoveryTemp.Enable_W | Supply recovery temperature - Enable input; Modbus DI127 | Read | ||
| BV | 586 | SupplyRecoveryTemp.Configured_R | Supply recovery temperature - Analog input configured; Modbus DI128 | Read | ||
| BV | 587 | SupplyRecoveryTemp.PrbOk_R | Supply recovery temperature - Probe working correctly; Modbus DI129 | Read | ||
| BV | 588 | SupplyRecoveryTemp.Alrm_R | Supply recovery temperature - Alarm probe broken or disconnected; Modbus DI130 | Read | ||
| BV | 589 | RetRecoveryTemp.Enable_W | Return recovery temperature - Enable input; Modbus DI131 | Read | ||
| BV | 590 | RetRecoveryTemp.Configured_R | Return recovery temperature - Analog input configured; Modbus DI132 | Read | ||
| BV | 591 | RetRecoveryTemp.PrbOk_R | Return recovery temperature - Probe working correctly; Modbus DI133 | Read | ||
| BV | 592 | RetRecoveryTemp.Alrm_R | Return recovery temperature - Alarm probe broken or disconnected; Modbus DI134 | Read | ||
| BV | 593 | HepaFilt_1.Enable_W | Hepa filter 1 - Enable input; Modbus DI135 | Read | ||
| BV | 594 | HepaFilt_1.Configured_R | Hepa filter 1 - Analog input configured; Modbus DI136 | Read | ||
| BV | 595 | HepaFilt_1.PrbOk_R | Hepa filter 1 - Probe working correctly; Modbus DI137 | Read | ||
| BV | 596 | HepaFilt_1.Alrm_R | Hepa filter 1 - Alarm probe broken or disconnected; Modbus DI138 | Read | ||
| BV | 597 | HepaFilt_2.Enable_W | Hepa filter 2 - Enable input; Modbus DI139 | Read | ||
| BV | 598 | HepaFilt_2.Configured_R | Hepa filter 2 - Analog input configured; Modbus DI140 | Read | ||
| BV | 599 | HepaFilt_2.PrbOk_R | Hepa filter 2 - Probe working correctly; Modbus DI141 | Read | ||
| BV | 600 | HepaFilt_2.Alrm_R | Hepa filter 2 - Alarm probe broken or disconnected; Modbus DI142 | Read | ||
| BV | 601 | SupplyAirFlwSw.Val_Hw_R | Supply air flow switch - Value reads from board; Modbus DI143 | Read | ||
| BV | 602 | SupplyAirFlwSw.Enable_W | Supply air flow switch - Enable input; Modbus DI144 | Read | ||
| BV | 603 | SupplyAirFlwSw.Configured_R | Supply air flow switch - Digital input configured; Modbus DI145 | Read | ||
| BV | 604 | SupplyAirFlwSw.Val_R | Supply air flow switch; Modbus DI146 | Read | ||
| BV | 605 | RetAirFlwSw.Val_Hw_R | Return air flow switch - Value reads from board; Modbus DI147 | Read | ||
| BV | 606 | RetAirFlwSw.Enable_W | Return air flow switch - Enable input; Modbus DI148 | Read | ||
| BV | 607 | RetAirFlwSw.Configured_R | Return air flow switch - Digital input configured; Modbus DI149 | Read | ||
| BV | 608 | RetAirFlwSw.Val_R | Return air flow switch; Modbus DI150 | Read | ||
| BV | 609 | AirFlwSw.Val_Hw_R | Air flow switch - Value reads from board; Modbus DI151 | Read | ||
| BV | 610 | AirFlwSw.Enable_W | Air flow switch - Enable input; Modbus DI152 | Read | ||
| BV | 611 | AirFlwSw.Configured_R | Air flow switch - Digital input configured; Modbus DI153 | Read | ||
| BV | 612 | AirFlwSw.Val_R | Air flow switch; Modbus DI154 | Read | ||
| BV | 613 | AFreezeSw.Val_Hw_R | Antifreeze switch - Value reads from board; Modbus DI155 | Read | ||
| BV | 614 | AFreezeSw.Enable_W | Antifreeze switch - Enable input; Modbus DI156 | Read | ||
| BV | 615 | AFreezeSw.Configured_R | Antifreeze switch - Digital input configured; Modbus DI157 | Read | ||
| BV | 616 | AFreezeSw.Val_R | Antifreeze switch; Modbus DI158 | Read | ||
| BV | 617 | RemOnOff.Val_Hw_R | Remote On/Off - Value reads from board; Modbus DI159 | Read | ||
| BV | 618 | RemOnOff.Enable_W | Remote On/Off - Enable input; Modbus DI160 | Read | ||
| BV | 619 | RemOnOff.Configured_R | Remote On/Off - Digital input configured; Modbus DI161 | Read | ||
| BV | 620 | RemOnOff.Val_R | Remote On/Off; Modbus DI162 | Read | ||
| BV | 621 | SupplyFanOvld_1.Val_Hw_R | Supply fan overload 1 - Value reads from board; Modbus DI163 | Read | ||
| BV | 622 | SupplyFanOvld_1.Enable_W | Supply fan overload 1 - Enable input; Modbus DI164 | Read | ||
| BV | 623 | SupplyFanOvld_1.Configured_R | Supply fan overload 1 - Digital input configured; Modbus DI165 | Read | ||
| BV | 624 | SupplyFanOvld_1.Val_R | Supply fan overload 1; Modbus DI166 | Read | ||
| BV | 625 | RetFanOvld_1.Val_Hw_R | Return fan overload 1 - Value reads from board; Modbus DI167 | Read | ||
| BV | 626 | RetFanOvld_1.Enable_W | Return fan overload 1 - Enable input; Modbus DI168 | Read | ||
| BV | 627 | RetFanOvld_1.Configured_R | Return fan overload 1 - Digital input configured; Modbus DI169 | Read | ||
| BV | 628 | RetFanOvld_1.Val_R | Return fan overload 1; Modbus DI170 | Read | ||
| BV | 629 | SupplyFanOvld_2.Val_Hw_R | Supply fan overload 2 - Value reads from board; Modbus DI171 | Read | ||
| BV | 630 | SupplyFanOvld_2.Enable_W | Supply fan overload 2 - Enable input; Modbus DI172 | Read | ||
| BV | 631 | SupplyFanOvld_2.Configured_R | Supply fan overload 2 - Digital input configured; Modbus DI173 | Read | ||
| BV | 632 | SupplyFanOvld_2.Val_R | Supply fan overload 2; Modbus DI174 | Read | ||
| BV | 633 | RetFanOvld_2.Val_Hw_R | Return fan overload 2 - Value reads from board; Modbus DI175 | Read | ||
| BV | 634 | RetFanOvld_2.Enable_W | Return fan overload 2 - Enable input; Modbus DI176 | Read | ||
| BV | 635 | RetFanOvld_2.Configured_R | Return fan overload 2 - Digital input configured; Modbus DI177 | Read | ||
| BV | 636 | RetFanOvld_2.Val_R | Return fan overload 2; Modbus DI178 | Read | ||
| BV | 637 | SupplyFanInvAlrm.Val_Hw_R | Supply inverter alarm - Value reads from board; Modbus DI179 | Read | ||
| BV | 638 | SupplyFanInvAlrm.Enable_W | Supply inverter alarm - Enable input; Modbus DI180 | Read | ||
| BV | 639 | SupplyFanInvAlrm.Configured_R | Supply inverter alarm - Digital input configured; Modbus DI181 | Read | ||
| BV | 640 | SupplyFanInvAlrm.Val_R | Supply inverter alarm; Modbus DI182 | Read | ||
| BV | 641 | RetFanInvAlrm.Val_Hw_R | Return inverter alarm - Value reads from board; Modbus DI183 | Read | ||
| BV | 642 | RetFanInvAlrm.Enable_W | Return inverter alarm - Enable input; Modbus DI184 | Read | ||
| BV | 643 | RetFanInvAlrm.Configured_R | Return inverter alarm - Digital input configured; Modbus DI185 | Read | ||
| BV | 644 | RetFanInvAlrm.Val_R | Return inverter alarm; Modbus DI186 | Read | ||
| BV | 645 | FansOvld.Val_Hw_R | Fans overload - Value reads from board; Modbus DI187 | Read | ||
| BV | 646 | FansOvld.Enable_W | Fans overload - Enable input; Modbus DI188 | Read | ||
| BV | 647 | FansOvld.Configured_R | Fans overload - Digital input configured; Modbus DI189 | Read | ||
| BV | 648 | FansOvld.Val_R | Fans overload; Modbus DI190 | Read | ||
| BV | 649 | CompOvld.Val_Hw_R | Compressor overload - Value reads from board; Modbus DI191 | Read | ||
| BV | 650 | CompOvld.Enable_W | Compressor overload - Enable input; Modbus DI192 | Read | ||
| BV | 651 | CompOvld.Configured_R | Compressor overload - Digital input configured; Modbus DI193 | Read | ||
| BV | 652 | CompOvld.Val_R | Compressor overload; Modbus DI194 | Read | ||
| BV | 653 | HiPSw.Val_Hw_R | High discharge pressure switch - Value reads from board; Modbus DI195 | Read | ||
| BV | 654 | HiPSw.Enable_W | High discharge pressure switch - Enable input; Modbus DI196 | Read | ||
| BV | 655 | HiPSw.Configured_R | High discharge pressure switch - Digital input configured; Modbus DI197 | Read | ||
| BV | 656 | HiPSw.Val_R | High discharge pressure switch; Modbus DI198 | Read | ||
| BV | 657 | LowPSw.Val_Hw_R | Low suction pressure switch - Value reads from board; Modbus DI199 | Read | ||
| BV | 658 | LowPSw.Enable_W | Low suction pressure switch - Enable input; Modbus DI200 | Read | ||
| BV | 659 | LowPSw.Configured_R | Low suction pressure switch - Digital input configured; Modbus DI201 | Read | ||
| BV | 660 | LowPSw.Val_R | Low suction pressure switch; Modbus DI202 | Read | ||
| BV | 661 | RecoveryOvld.Val_Hw_R | Thermal wheel overload - Value reads from board; Modbus DI203 | Read | ||
| BV | 662 | RecoveryOvld.Enable_W | Thermal wheel overload - Enable input; Modbus DI204 | Read | ||
| BV | 663 | RecoveryOvld.Configured_R | Thermal wheel overload - Digital input configured; Modbus DI205 | Read | ||
| BV | 664 | RecoveryOvld.Val_R | Thermal wheel overload; Modbus DI206 | Read | ||
| BV | 665 | SrsAlrm.Val_Hw_R | Serious alarm - Value reads from board; Modbus DI207 | Read | ||
| BV | 666 | SrsAlrm.Enable_W | Serious alarm - Enable input; Modbus DI208 | Read | ||
| BV | 667 | SrsAlrm.Configured_R | Serious alarm - Digital input configured; Modbus DI209 | Read | ||
| BV | 668 | SrsAlrm.Val_R | Serious alarm; Modbus DI210 | Read | ||
| BV | 669 | GenAlrm.Val_Hw_R | Generic alarm - Value reads from board; Modbus DI211 | Read | ||
| BV | 670 | GenAlrm.Enable_W | Generic alarm - Enable input; Modbus DI212 | Read | ||
| BV | 671 | GenAlrm.Configured_R | Generic alarm - Digital input configured; Modbus DI213 | Read | ||
| BV | 672 | GenAlrm.Val_R | Generic alarm; Modbus DI214 | Read | ||
| BV | 673 | GenWarning.Val_Hw_R | Generic warning - Value reads from board; Modbus DI215 | Read | ||
| BV | 674 | GenWarning.Enable_W | Generic warning - Enable input; Modbus DI216 | Read | ||
| BV | 675 | GenWarning.Configured_R | Generic warning - Digital input configured; Modbus DI217 | Read | ||
| BV | 676 | GenWarning.Val_R | Generic warning; Modbus DI218 | Read | ||
| BV | 677 | FiltAlrm.Val_Hw_R | Filters alarm - Value reads from board; Modbus DI219 | Read | ||
| BV | 678 | FiltAlrm.Enable_W | Filters alarm - Enable input; Modbus DI220 | Read | ||
| BV | 679 | FiltAlrm.Configured_R | Filters alarm - Digital input configured; Modbus DI221 | Read | ||
| BV | 680 | FiltAlrm.Val_R | Filters alarm; Modbus DI222 | Read | ||
| BV | 681 | SupplyFiltAlrm_1.Val_Hw_R | Supply filter alarm 1 - Value reads from board; Modbus DI223 | Read | ||
| BV | 682 | SupplyFiltAlrm_1.Enable_W | Supply filter alarm 1 - Enable input; Modbus DI224 | Read | ||
| BV | 683 | SupplyFiltAlrm_1.Configured_R | Supply filter alarm 1 - Digital input configured; Modbus DI225 | Read | ||
| BV | 684 | SupplyFiltAlrm_1.Val_R | Supply filter alarm 1; Modbus DI226 | Read | ||
| BV | 685 | SupplyFiltAlrm_2.Val_Hw_R | Supply filter alarm 2 - Value reads from board; Modbus DI227 | Read | ||
| BV | 686 | SupplyFiltAlrm_2.Enable_W | Supply filter alarm 2 - Enable input; Modbus DI228 | Read | ||
| BV | 687 | SupplyFiltAlrm_2.Configured_R | Supply filter alarm 2 - Digital input configured; Modbus DI229 | Read | ||
| BV | 688 | SupplyFiltAlrm_2.Val_R | Supply filter alarm 2; Modbus DI230 | Read | ||
| BV | 689 | RetFiltAlrm.Val_Hw_R | Return filter alarm - Value reads from board; Modbus DI231 | Read | ||
| BV | 690 | RetFiltAlrm.Enable_W | Return filter alarm - Enable input; Modbus DI232 | Read | ||
| BV | 691 | RetFiltAlrm.Configured_R | Return filter alarm - Digital input configured; Modbus DI233 | Read | ||
| BV | 692 | RetFiltAlrm.Val_R | Return filter alarm; Modbus DI234 | Read | ||
| BV | 693 | HumAlrm.Val_Hw_R | Humidifier alarm - Value reads from board; Modbus DI235 | Read | ||
| BV | 694 | HumAlrm.Enable_W | Humidifier alarm - Enable input; Modbus DI236 | Read | ||
| BV | 695 | HumAlrm.Configured_R | Humidifier alarm - Digital input configured; Modbus DI237 | Read | ||
| BV | 696 | HumAlrm.Val_R | Humidifier alarm; Modbus DI238 | Read | ||
| BV | 697 | MainCoilPmp1_Ovld.Val_Hw_R | Main coil pump 1 overload - Value reads from board; Modbus DI239 | Read | ||
| BV | 698 | MainCoilPmp1_Ovld.Enable_W | Main coil pump 1 overload - Enable input; Modbus DI240 | Read | ||
| BV | 699 | MainCoilPmp1_Ovld.Configured_R | Main coil pump 1 overload - Digital input configured; Modbus DI241 | Read | ||
| BV | 700 | MainCoilPmp1_Ovld.Val_R | Main coil pump 1 overload; Modbus DI242 | Read | ||
| BV | 701 | MainCoilPmp2_Ovld.Val_Hw_R | Main coil pump 2 overload - Value reads from board; Modbus DI243 | Read | ||
| BV | 702 | MainCoilPmp2_Ovld.Enable_W | Main coil pump 2 overload - Enable input; Modbus DI244 | Read | ||
| BV | 703 | MainCoilPmp2_Ovld.Configured_R | Main coil pump 2 overload - Digital input configured; Modbus DI245 | Read | ||
| BV | 704 | MainCoilPmp2_Ovld.Val_R | Main coil pump 2 overload; Modbus DI246 | Read | ||
| BV | 705 | ReHeatCoilPmp1_Ovld.Val_Hw_R | ReHeat coil pump 1 overload - Value reads from board; Modbus DI247 | Read | ||
| BV | 706 | ReHeatCoilPmp1_Ovld.Enable_W | ReHeat coil pump 1 overload - Enable input; Modbus DI248 | Read | ||
| BV | 707 | ReHeatCoilPmp1_Ovld.Configured_R | ReHeat coil pump 1 overload - Digital input configured; Modbus DI249 | Read | ||
| BV | 708 | ReHeatCoilPmp1_Ovld.Val_R | ReHeat coil pump 1 overload; Modbus DI250 | Read | ||
| BV | 709 | ReHeatCoilPmp2_Ovld.Val_Hw_R | ReHeat coil pump 2 overload - Value reads from board; Modbus DI251 | Read | ||
| BV | 710 | ReHeatCoilPmp2_Ovld.Enable_W | ReHeat coil pump 2 overload - Enable input; Modbus DI252 | Read | ||
| BV | 711 | ReHeatCoilPmp2_Ovld.Configured_R | ReHeat coil pump 2 overload - Digital input configured; Modbus DI253 | Read | ||
| BV | 712 | ReHeatCoilPmp2_Ovld.Val_R | ReHeat coil pump 2 overload; Modbus DI254 | Read | ||
| BV | 713 | PreHeatCoilPmp1_Ovld.Val_Hw_R | PreHeat coil pump 1 overload - Value reads from board; Modbus DI255 | Read | ||
| BV | 714 | PreHeatCoilPmp1_Ovld.Enable_W | PreHeat coil pump 1 overload - Enable input; Modbus DI256 | Read | ||
| BV | 715 | PreHeatCoilPmp1_Ovld.Configured_R | PreHeat coil pump 1 overload - Digital input configured; Modbus DI257 | Read | ||
| BV | 716 | PreHeatCoilPmp1_Ovld.Val_R | PreHeat coil pump 1 overload; Modbus DI258 | Read | ||
| BV | 717 | PreHeatCoilPmp2_Ovld.Val_Hw_R | PreHeat coil pump 2 overload - Value reads from board; Modbus DI259 | Read | ||
| BV | 718 | PreHeatCoilPmp2_Ovld.Enable_W | PreHeat coil pump 2 overload - Enable input; Modbus DI260 | Read | ||
| BV | 719 | PreHeatCoilPmp2_Ovld.Configured_R | PreHeat coil pump 2 overload - Digital input configured; Modbus DI261 | Read | ||
| BV | 720 | PreHeatCoilPmp2_Ovld.Val_R | PreHeat coil pump 2 overload; Modbus DI262 | Read | ||
| BV | 721 | OA_CoilPmp1_Ovld.Val_Hw_R | Outdoor air pre-treatment coil pump 1 overload - Value reads ...; Modbus DI263 | Read | ||
| BV | 722 | OA_CoilPmp1_Ovld.Enable_W | Outdoor air pre-treatment coil pump 1 overload - Enable input; Modbus DI264 | Read | ||
| BV | 723 | OA_CoilPmp1_Ovld.Configured_R | Outdoor air pre-treatment coil pump 1 overload - Digital input configured; Modbus DI265 | Read | ||
| BV | 724 | OA_CoilPmp1_Ovld.Val_R | Outdoor air pre-treatment coil pump 2 overload - Value reads ...; Modbus DI266 | Read | ||
| BV | 725 | OA_CoilPmp2_Ovld.Val_Hw_R | Outdoor air pre-treatment coil pump 2 overload - Value reads ...; Modbus DI267 | Read | ||
| BV | 726 | OA_CoilPmp2_Ovld.Enable_W | Outdoor air pre-treatment coil pump 2 overload - Enable input; Modbus DI268 | Read | ||
| BV | 727 | OA_CoilPmp2_Ovld.Configured_R | Outdoor air pre-treatment coil pump 2 overload - Digital input configured; Modbus DI269 | Read | ||
| BV | 728 | OA_CoilPmp2_Ovld.Val_R | Outdoor air pre-treatment coil pump 2 overload; Modbus DI270 | Read | ||
| BV | 729 | FreshAirDampSw.Val_Hw_R | Fresh air damper switch - Value reads from board; Modbus DI271 | Read | ||
| BV | 730 | FreshAirDampSw.Enable_W | Fresh air damper switch - Enable input; Modbus DI272 | Read | ||
| BV | 731 | FreshAirDampSw.Configured_R | Fresh air damper switch - Digital input configured; Modbus DI273 | Read | ||
| BV | 732 | FreshAirDampSw.Val_R | Fresh air damper switch; Modbus DI274 | Read | ||
| BV | 733 | SupplyDamperSw.Val_Hw_R | Supply damper switch - Value reads from board; Modbus DI275 | Read | ||
| BV | 734 | SupplyDamperSw.Enable_W | Supply damper switch - Enable input; Modbus DI276 | Read | ||
| BV | 735 | SupplyDamperSw.Configured_R | Supply damper switch - Digital input configured; Modbus DI277 | Read | ||
| BV | 736 | SupplyDamperSw.Val_R | Supply damper switch; Modbus DI278 | Read | ||
| BV | 737 | RetDampSw.Val_Hw_R | Return damper switch - Value reads from board; Modbus DI279 | Read | ||
| BV | 738 | RetDampSw.Enable_W | Return damper switch - Enable input; Modbus DI280 | Read | ||
| BV | 739 | RetDampSw.Configured_R | Return damper switch - Digital input configured; Modbus DI281 | Read | ||
| BV | 740 | RetDampSw.Val_R | Return damper switch; Modbus DI282 | Read | ||
| BV | 741 | MainCoilFlwSw.Val_Hw_R | Main coil flow switch - Value reads from board; Modbus DI283 | Read | ||
| BV | 742 | MainCoilFlwSw.Enable_W | Main coil flow switch - Enable input; Modbus DI284 | Read | ||
| BV | 743 | MainCoilFlwSw.Configured_R | Main coil flow switch - Digital input configured; Modbus DI285 | Read | ||
| BV | 744 | MainCoilFlwSw.Val_R | Main coil flow switch; Modbus DI286 | Read | ||
| BV | 745 | PreHeatCoilFlwSw.Val_Hw_R | Pre-heating coil flow switch - Value reads from board; Modbus DI287 | Read | ||
| BV | 746 | PreHeatCoilFlwSw.Enable_W | Pre-heating coil flow switch - Enable input; Modbus DI288 | Read | ||
| BV | 747 | PreHeatCoilFlwSw.Configured_R | Pre-heating coil flow switch - Digital input configured; Modbus DI289 | Read | ||
| BV | 748 | PreHeatCoilFlwSw.Val_R | Pre-heating coil flow switch; Modbus DI290 | Read | ||
| BV | 749 | ReHeatCoilFlwSw.Val_Hw_R | Post-Heating coil flow switch - Value reads from board; Modbus DI291 | Read | ||
| BV | 750 | ReHeatCoilFlwSw.Enable_W | Post-Heating coil flow switch - Enable input; Modbus DI292 | Read | ||
| BV | 751 | ReHeatCoilFlwSw.Configured_R | Post-Heating coil flow switch - Digital input configured; Modbus DI293 | Read | ||
| BV | 752 | ReHeatCoilFlwSw.Val_R | Post-Heating coil flow switch; Modbus DI294 | Read | ||
| BV | 753 | OA_CoilFlwSw.Val_Hw_R | Outdoor air pre-treatment coil flow switch - Value reads from board; Modbus DI295 | Read | ||
| BV | 754 | OA_CoilFlwSw.Enable_W | Outdoor air pre-treatment coil flow switch - Enable input; Modbus DI296 | Read | ||
| BV | 755 | OA_CoilFlwSw.Configured_R | Outdoor air pre-treatment coil flow switch - Digital input configured; Modbus DI297 | Read | ||
| BV | 756 | OA_CoilFlwSw.Val_R | Outdoor air pre-treatment coil flow switch; Modbus DI298 | Read | ||
| BV | 757 | RecoveryClogged.Val_Hw_R | Recovery clogged - Value reads from board; Modbus DI299 | Read | ||
| BV | 758 | RecoveryClogged.Enable_W | Recovery clogged - Enable input; Modbus DI300 | Read | ||
| BV | 759 | RecoveryClogged.Configured_R | Recovery clogged - Digital input configured; Modbus DI301 | Read | ||
| BV | 760 | RecoveryClogged.Val_R | Recovery clogged; Modbus DI302 | Read | ||
| BV | 761 | ReHeatAlrm.Val_Hw_R | Re-heating alarm - Value reads from board; Modbus DI303 | Read | ||
| BV | 762 | ReHeatAlrm.Enable_W | Re-heating alarm - Enable input; Modbus DI304 | Read | ||
| BV | 763 | ReHeatAlrm.Configured_R | Re-heating alarm - Digital input configured; Modbus DI305 | Read | ||
| BV | 764 | ReHeatAlrm.Val_R | Re-heating alarm; Modbus DI306 | Read | ||
| BV | 765 | PreHeatAlrm.Val_Hw_R | Pre-heating alarm - Value reads from board; Modbus DI307 | Read | ||
| BV | 766 | PreHeatAlrm.Enable_W | Pre-heating alarm - Enable input; Modbus DI308 | Read | ||
| BV | 767 | PreHeatAlrm.Configured_R | Pre-heating alarm - Digital input configured; Modbus DI309 | Read | ||
| BV | 768 | PreHeatAlrm.Val_R | Pre-heating alarm; Modbus DI310 | Read | ||
| BV | 769 | MainHeatCoilAlrm.Val_Hw_R | Main coil alarm - Value reads from board; Modbus DI311 | Read | ||
| BV | 770 | MainHeatCoilAlrm.Enable_W | Main coil alarm - Enable input; Modbus DI312 | Read | ||
| BV | 771 | MainHeatCoilAlrm.Configured_R | Main coil alarm - Digital input configured; Modbus DI313 | Read | ||
| BV | 772 | MainHeatCoilAlrm.Val_R | Main coil alarm; Modbus DI314 | Read | ||
| BV | 773 | OA_CoilAlrm.Val_Hw_R | Outdoor air pre-treatment alarm - Value reads from board; Modbus DI315 | Read | ||
| BV | 774 | OA_CoilAlrm.Enable_W | Outdoor air pre-treatment alarm - Enable input; Modbus DI316 | Read | ||
| BV | 775 | OA_CoilAlrm.Configured_R | Outdoor air pre-treatment alarm - Digital input configured; Modbus DI317 | Read | ||
| BV | 776 | OA_CoilAlrm.Val_R | Outdoor air pre-treatment alarm; Modbus DI318 | Read | ||
| BV | 777 | DoorSw.Val_Hw_R | Door Switch - Value reads from board; Modbus DI319 | Read | ||
| BV | 778 | DoorSw.Enable_W | Door Switch - Enable input; Modbus DI320 | Read | ||
| BV | 779 | DoorSw.Configured_R | Door Switch - Digital input configured; Modbus DI321 | Read | ||
| BV | 780 | DoorSw.Val_R | Door Switch; Modbus DI322 | Read | ||
| BV | 781 | FireSmokeAlrm.Val_Hw_R | Fire/Smoke alarm - Value reads from board; Modbus DI323 | Read | ||
| BV | 782 | FireSmokeAlrm.Enable_W | Fire/Smoke alarm - Enable input; Modbus DI324 | Read | ||
| BV | 783 | FireSmokeAlrm.Configured_R | Fire/Smoke alarm - Digital input configured; Modbus DI325 | Read | ||
| BV | 784 | FireSmokeAlrm.Val_R | Fire/Smoke alarm; Modbus DI326 | Read | ||
| BV | 785 | FiremanOverrideSw.Val_Hw_R | Fireman override switch - Value reads from board; Modbus DI327 | Read | ||
| BV | 786 | FiremanOverrideSw.Enable_W | Fireman override switch - Enable input; Modbus DI328 | Read | ||
| BV | 787 | FiremanOverrideSw.Configured_R | Fireman override switch - Digital input configured; Modbus DI329 | Read | ||
| BV | 788 | FiremanOverrideSw.Val_R | Fireman override switch; Modbus DI330 | Read | ||
| BV | 789 | SummerWinterModeByDin.Val_Hw_R | Summer/Winter mode by digital input - Value reads from board; Modbus DI331 | Read | ||
| BV | 790 | SummerWinterModeByDin.Enable_W | Summer/Winter mode by digital input - Enable input; Modbus DI332 | Read | ||
| BV | 791 | SummerWinterModeByDin.Configured_R | Summer/Winter mode by digital input - Configured; Modbus DI333 | Read | ||
| BV | 792 | SummerWinterModeByDin.Val_R | Summer/Winter mode by digital input; Modbus DI334 | Read | ||
| BV | 793 | Din_SetP.Val_Hw_R | Setpoint by digital input - Value reads from board; Modbus DI335 | Read | ||
| BV | 794 | Din_SetP.Enable_W | Setpoint by digital input - Enable input; Modbus DI336 | Read | ||
| BV | 795 | Din_SetP.Configured_R | Setpoint by digital input - Digital input configured; Modbus DI337 | Read | ||
| BV | 796 | Din_SetP.Val_R | Setpoint by digital input; Modbus DI338 | Read | ||
| BV | 797 | Eco_Mode.Val_Hw_R | Eco mode - Value reads from board; Modbus DI339 | Read | ||
| BV | 798 | Eco_Mode.Enable_W | Eco mode - Enable input; Modbus DI340 | Read | ||
| BV | 799 | Eco_Mode.Configured_R | Eco mode - Digital input configured; Modbus DI341 | Read | ||
| BV | 800 | Eco_Mode.Val_R | Eco mode; Modbus DI342 | Read | ||
| BV | 801 | PreComf_Mode.Val_Hw_R | Precomfort mode - Value reads from board; Modbus DI343 | Read | ||
| BV | 802 | PreComf_Mode.Enable_W | Precomfort mode - Enable input; Modbus DI344 | Read | ||
| BV | 803 | PreComf_Mode.Configured_R | Precomfort mode - Digital input configured; Modbus DI345 | Read | ||
| BV | 804 | PreComf_Mode.Val_R | Precomfort mode; Modbus DI346 | Read | ||
| BV | 805 | Comf_Mode.Val_Hw_R | Comfort mode - Value reads from board; Modbus DI347 | Read | ||
| BV | 806 | Comf_Mode.Enable_W | Comfort mode - Enable input; Modbus DI348 | Read | ||
| BV | 807 | Comf_Mode.Configured_R | Comfort mode - Digital input configured; Modbus DI349 | Read | ||
| BV | 808 | Comf_Mode.Val_R | Comfort mode; Modbus DI350 | Read | ||
| BV | 809 | AuxDin_1.Val_Hw_R | Auxiliary digital input 1 - Value reads from board; Modbus DI351 | Read | ||
| BV | 810 | AuxDin_1.Enable_W | Auxiliary digital input 1 - Enable input; Modbus DI352 | Read | ||
| BV | 811 | AuxDin_1.Configured_R | Auxiliary digital input 1 - Digital input configured; Modbus DI353 | Read | ||
| BV | 812 | AuxDin_1.Val_R | Auxiliary digital input 1; Modbus DI354 | Read | ||
| BV | 813 | AuxDin_2.Val_Hw_R | Auxiliary digital input 2 - Value reads from board; Modbus DI355 | Read | ||
| BV | 814 | AuxDin_2.Enable_W | Auxiliary digital input 2 - Enable input; Modbus DI356 | Read | ||
| BV | 815 | AuxDin_2.Configured_R | Auxiliary digital input 2 - Digital input configured; Modbus DI357 | Read | ||
| BV | 816 | AuxDin_2.Val_R | Auxiliary digital input 2; Modbus DI358 | Read | ||
| BV | 817 | AuxDin_3.Val_Hw_R | Auxiliary digital input 3 - Value reads from board; Modbus DI359 | Read | ||
| BV | 818 | AuxDin_3.Enable_W | Auxiliary digital input 3 - Enable input; Modbus DI360 | Read | ||
| BV | 819 | AuxDin_3.Configured_R | Auxiliary digital input 3 - Digital input configured; Modbus DI361 | Read | ||
| BV | 820 | AuxDin_3.Val_R | Auxiliary digital input 3; Modbus DI362 | Read | ||
| BV | 821 | AuxDin_4.Val_Hw_R | Auxiliary digital input 4 - Value reads from board; Modbus DI363 | Read | ||
| BV | 822 | AuxDin_4.Enable_W | Auxiliary digital input 4 - Enable input; Modbus DI364 | Read | ||
| BV | 823 | AuxDin_4.Configured_R | Auxiliary digital input 4 - Digital input configured; Modbus DI365 | Read | ||
| BV | 824 | AuxDin_4.Val_R | Auxiliary digital input 4; Modbus DI366 | Read | ||
| BV | 825 | DfrHeatExch_Din.Val_Hw_R | Heat exchanger defrost by Din - Value reads from board; Modbus DI367 | Read | ||
| BV | 826 | DfrHeatExch_Din.Enable_W | Heat exchanger defrost by Din - Enable input; Modbus DI368 | Read | ||
| BV | 827 | DfrHeatExch_Din.Configured_R | Heat exchanger defrost by Din - Digital input configured; Modbus DI369 | Read | ||
| BV | 828 | DfrHeatExch_Din.Val_R | Heat exchanger defrost by Din; Modbus DI370 | Read | ||
| BV | 830 | BypassDamp_Dout.Val_W | Bypass damper; Modbus DI372 | Read | ||
| BV | 831 | BypassDamp_Dout.Enable_W | Bypass damper - Enable output; Modbus DI373 | Read | ||
| BV | 832 | BypassDamp_Dout.Configured_R | Bypass damper - Output configurated; Modbus DI374 | Read | ||
| BV | 833 | BypassDamp_Open.Val_Hw_R | Bypass damper floating (open) - Hardware value writes from board; Modbus DI375 | Read | ||
| BV | 834 | BypassDamp_Open.Val_W | Bypass damper floating (open); Modbus DI376 | Read | ||
| BV | 835 | BypassDamp_Open.Enable_W | Bypass damper floating (open) - Enable output; Modbus DI377 | Read | ||
| BV | 836 | BypassDamp_Open.Configured_R | Bypass damper floating (open) - Output configurated; Modbus DI378 | Read | ||
| BV | 837 | BypassDamp_Close.Val_Hw_R | Bypass damper floating (close) - Hardware value writes from board; Modbus DI379 | Read | ||
| BV | 838 | BypassDamp_Close.Val_W | Bypass damper floating (close); Modbus DI380 | Read | ||
| BV | 839 | BypassDamp_Close.Enable_W | Bypass damper floating (close) - Enable output; Modbus DI381 | Read | ||
| BV | 840 | BypassDamp_Close.Configured_R | Bypass damper floating (close) - Output configurated; Modbus DI382 | Read | ||
| BV | 841 | FreshAirDamp_Dout.Val_Hw_R | Fresh air damper - Hardware value writes from board; Modbus DI383 | Read | ||
| BV | 843 | FreshAirDamp_Dout.Enable_W | Fresh air damper - Enable output; Modbus DI385 | Read | ||
| BV | 844 | FreshAirDamp_Dout.Configured_R | Fresh air damper - Output configurated; Modbus DI386 | Read | ||
| BV | 846 | ExhAirDamp_Dout.Val_W | Exhaust air damper; Modbus DI388 | Read | ||
| BV | 847 | ExhAirDamp_Dout.Enable_W | Exhaust air damper - Enable output; Modbus DI389 | Read | ||
| BV | 848 | ExhAirDamp_Dout.Configured_R | Exhaust air damper - Output configurated; Modbus DI390 | Read | ||
| BV | 850 | MixingDamp_Dout.Val_W | Mixing damper; Modbus DI392 | Read | ||
| BV | 851 | MixingDamp_Dout.Enable_W | Mixing damper - Enable output; Modbus DI393 | Read | ||
| BV | 852 | MixingDamp_Dout.Configured_R | Mixing damper - Output configurated; Modbus DI394 | Read | ||
| BV | 853 | SupplyAirDamp_Dout.Val_Hw_R | Supply air damper - Hardware value writes from board; Modbus DI395 | Read | ||
| BV | 854 | SupplyAirDamp_Dout.Val_W | Supply air damper; Modbus DI396 | Read | ||
| BV | 855 | SupplyAirDamp_Dout.Enable_W | Supply air damper - Enable output; Modbus DI397 | Read | ||
| BV | 856 | SupplyAirDamp_Dout.Configured_R | Supply air damper - Output configurated; Modbus DI398 | Read | ||
| BV | 857 | RetAirDamp_Dout.Val_Hw_R | Return air damper - Hardware value writes from board; Modbus DI399 | Read | ||
| BV | 858 | RetAirDamp_Dout.Val_W | Return air damper; Modbus DI400 | Read | ||
| BV | 859 | RetAirDamp_Dout.Enable_W | Return air damper - Enable output; Modbus DI401 | Read | ||
| BV | 860 | RetAirDamp_Dout.Configured_R | Return air damper - Output configurated; Modbus DI402 | Read | ||
| BV | 861 | MixingDamp_Open.Val_Hw_R | Mixing damper floating (OPEN) - Hardware value writes from board; Modbus DI403 | Read | ||
| BV | 862 | MixingDamp_Open.Val_W | Mixing damper floating (OPEN); Modbus DI404 | Read | ||
| BV | 863 | MixingDamp_Open.Enable_W | Mixing damper floating (OPEN) - Enable output; Modbus DI405 | Read | ||
| BV | 864 | MixingDamp_Open.Configured_R | Mixing damper floating (OPEN) - Output configurated; Modbus DI406 | Read | ||
| BV | 865 | MixingDamp_Close.Val_Hw_R | Mixing damper floating (CLOSE) - Hardware value writes from board; Modbus DI407 | Read | ||
| BV | 866 | MixingDamp_Close.Val_W | Mixing damper floating (CLOSE); Modbus DI408 | Read | ||
| BV | 867 | MixingDamp_Close.Enable_W | Mixing damper floating (CLOSE) - Enable output; Modbus DI409 | Read | ||
| BV | 868 | MixingDamp_Close.Configured_R | Mixing damper floating (CLOSE) - Output configurated; Modbus DI410 | Read | ||
| BV | 870 | SupplyFan_Dout.Val_W | Supply fan; Modbus DI412 | Read | ||
| BV | 871 | SupplyFan_Dout.Enable_W | Supply fan - Enable output; Modbus DI413 | Read | ||
| BV | 872 | SupplyFan_Dout.Configured_R | Supply fan - Output configurated; Modbus DI414 | Read | ||
| BV | 874 | RetFan_Dout.Val_W | Return fan; Modbus DI416 | Read | ||
| BV | 875 | RetFan_Dout.Enable_W | Return fan - Enable output; Modbus DI417 | Read | ||
| BV | 876 | RetFan_Dout.Configured_R | Return fan - Output configurated; Modbus DI418 | Read | ||
| BV | 877 | SupplyFan2_Dout.Val_Hw_R | Supply fan 2 - Hardware value writes from board; Modbus DI419 | Read | ||
| BV | 878 | SupplyFan2_Dout.Val_W | Supply fan 2; Modbus DI420 | Read | ||
| BV | 879 | SupplyFan2_Dout.Enable_W | Supply fan 2 - Enable output; Modbus DI421 | Read | ||
| BV | 880 | SupplyFan2_Dout.Configured_R | Supply fan 2 - Output configurated; Modbus DI422 | Read | ||
| BV | 881 | RetFan2_Dout.Val_Hw_R | Return fan 2 - Hardware value writes from board; Modbus DI423 | Read | ||
| BV | 882 | RetFan2_Dout.Val_W | Return fan 2; Modbus DI424 | Read | ||
| BV | 883 | RetFan2_Dout.Enable_W | Return fan 2 - Enable output; Modbus DI425 | Read | ||
| BV | 884 | RetFan2_Dout.Configured_R | Return fan 2 - Output configurated; Modbus DI426 | Read | ||
| BV | 886 | Comp_Dout.Val_W | Compressor; Modbus DI428 | Read | ||
| BV | 887 | Comp_Dout.Enable_W | Compressor - Enable output; Modbus DI429 | Read | ||
| BV | 888 | Comp_Dout.Configured_R | Compressor - Output configurated; Modbus DI430 | Read | ||
| BV | 889 | RevVlv.Val_Hw_R | Reverse valve - Hardware value writes from board; Modbus DI431 | Read | ||
| BV | 890 | RevVlv.Val_W | Reverse valve; Modbus DI432 | Read | ||
| BV | 891 | RevVlv.Enable_W | Reverse valve - Enable output; Modbus DI433 | Read | ||
| BV | 892 | RevVlv.Configured_R | Reverse valve - Output configurated; Modbus DI434 | Read | ||
| BV | 893 | UnitOnOff_Dout.Val_Hw_R | Unit status (On/Off ) - Hardware value writes from board; Modbus DI435 | Read | ||
| BV | 894 | UnitOnOff_Dout.Val_W | Unit status (On/Off ); Modbus DI436 | Read | ||
| BV | 895 | UnitOnOff_Dout.Enable_W | Unit status (On/Off ) - Enable output; Modbus DI437 | Read | ||
| BV | 896 | UnitOnOff_Dout.Configured_R | Unit status (On/Off ) - Output configurated; Modbus DI438 | Read | ||
| BV | 897 | CoolHeat_Dout.Val_Hw_R | Cool/Heat status - Hardware value writes from board; Modbus DI439 | Read | ||
| BV | 898 | CoolHeat_Dout.Val_W | Cool/Heat status; Modbus DI440 | Read | ||
| BV | 899 | CoolHeat_Dout.Enable_W | Cool/Heat status - Enable output; Modbus DI441 | Read | ||
| BV | 900 | CoolHeat_Dout.Configured_R | Cool/Heat status - Output configurated; Modbus DI442 | Read | ||
| BV | 901 | GlobalAlrm_Dout.Val_Hw_R | Generic alarm info - Hardware value writes from board; Modbus DI443 | Read | ||
| BVmin | 902 | GlobalAlrm_Dout.Val_W | Generic alarm info; Modbus DI444 | Read | ||
| BV | 903 | GlobalAlrm_Dout.Enable_W | Generic alarm info - Enable output; Modbus DI445 | Read | ||
| BV | 904 | GlobalAlrm_Dout.Configured_R | Generic alarm info - Output configurated; Modbus DI446 | Read | ||
| BV | 905 | LightAlrm_Dout.Val_Hw_R | Light alarm info - Hardware value writes from board; Modbus DI447 | Read | ||
| BV | 906 | LightAlrm_Dout.Val_W | Light alarm info; Modbus DI448 | Read | ||
| BV | 907 | LightAlrm_Dout.Enable_W | Light alarm info - Enable output; Modbus DI449 | Read | ||
| BV | 908 | LightAlrm_Dout.Configured_R | Light alarm info - Output configurated; Modbus DI450 | Read | ||
| BV | 909 | SrsAlrm_Dout.Val_Hw_R | Serious alarm info - Hardware value writes from board; Modbus DI451 | Read | ||
| BV | 910 | SrsAlrm_Dout.Val_W | Serious alarm info; Modbus DI452 | Read | ||
| BV | 911 | SrsAlrm_Dout.Enable_W | Serious alarm info - Enable output; Modbus DI453 | Read | ||
| BV | 912 | SrsAlrm_Dout.Configured_R | Serious alarm info - Output configurated; Modbus DI454 | Read | ||
| BV | 913 | Humidifier.Val_Hw_R | Humidifier - Hardware value writes from board; Modbus DI455 | Read | ||
| BV | 914 | Humidifier.Val_W | Humidifier; Modbus DI456 | Read | ||
| BV | 915 | Humidifier.Enable_W | Humidifier - Enable output; Modbus DI457 | Read | ||
| BV | 916 | Humidifier.Configured_R | Humidifier - Output configurated; Modbus DI458 | Read | ||
| BV | 917 | AuxOut1_Dout.Val_Hw_R | Auxiliary output 1 - Hardware value writes from board; Modbus DI459 | Read | ||
| BV | 919 | AuxOut1_Dout.Enable_W | Auxiliary output 1 - Enable output; Modbus DI461 | Read | ||
| BV | 920 | AuxOut1_Dout.Configured_R | Auxiliary output 1 - Output configurated; Modbus DI462 | Read | ||
| BV | 921 | AuxOut2_Dout.Val_Hw_R | Auxiliary output 2 - Hardware value writes from board; Modbus DI463 | Read | ||
| BV | 923 | AuxOut2_Dout.Enable_W | Auxiliary output 2 - Enable output; Modbus DI465 | Read | ||
| BV | 924 | AuxOut2_Dout.Configured_R | Auxiliary output 2 - Output configurated; Modbus DI466 | Read | ||
| BV | 925 | AuxOut3_Dout.Val_Hw_R | Auxiliary output 3 - Hardware value writes from board; Modbus DI467 | Read | ||
| BV | 927 | AuxOut3_Dout.Enable_W | Auxiliary output 3 - Enable output; Modbus DI469 | Read | ||
| BV | 928 | AuxOut3_Dout.Configured_R | Auxiliary output 3 - Output configurated; Modbus DI470 | Read | ||
| BV | 929 | AuxOut4_Dout.Val_Hw_R | Auxiliary output 4 - Hardware value writes from board; Modbus DI471 | Read | ||
| BV | 931 | AuxOut4_Dout.Enable_W | Auxiliary output 4 - Enable output; Modbus DI473 | Read | ||
| BV | 932 | AuxOut4_Dout.Configured_R | Auxiliary output 4 - Output configurated; Modbus DI474 | Read | ||
| BV | 933 | MainVlv_Open.Val_Hw_R | Main floating valve open - Hardware value writes from board; Modbus DI475 | Read | ||
| BV | 934 | MainVlv_Open.Val_W | Main floating valve open; Modbus DI476 | Read | ||
| BV | 935 | MainVlv_Open.Enable_W | Main floating valve open - Enable output; Modbus DI477 | Read | ||
| BV | 936 | MainVlv_Open.Configured_R | Main floating valve open - Output configurated; Modbus DI478 | Read | ||
| BV | 937 | PreHeatVlv_Open.Val_Hw_R | Pre-heating floating valve open - Hardware value writes from board; Modbus DI479 | Read | ||
| BV | 938 | PreHeatVlv_Open.Val_W | Pre-heating floating valve open; Modbus DI480 | Read | ||
| BV | 939 | PreHeatVlv_Open.Enable_W | Pre-heating floating valve open - Enable output; Modbus DI481 | Read | ||
| BV | 940 | PreHeatVlv_Open.Configured_R | Pre-heating floating valve open - Output configurated; Modbus DI482 | Read | ||
| BV | 941 | ReHeatVlv_Open.Val_Hw_R | Re-Heating floating valve open - Hardware value writes from board; Modbus DI483 | Read | ||
| BV | 942 | ReHeatVlv_Open.Val_W | Re-Heating floating valve open; Modbus DI484 | Read | ||
| BV | 943 | ReHeatVlv_Open.Enable_W | Re-Heating floating valve open - Enable output; Modbus DI485 | Read | ||
| BV | 944 | ReHeatVlv_Open.Configured_R | Re-Heating floating valve open - Output configurated; Modbus DI486 | Read | ||
| BV | 945 | MainVlv_Close.Val_Hw_R | Main floating valve close - Hardware value writes from board; Modbus DI487 | Read | ||
| BV | 946 | MainVlv_Close.Val_W | Main floating valve close; Modbus DI488 | Read | ||
| BV | 947 | MainVlv_Close.Enable_W | Main floating valve close - Enable output; Modbus DI489 | Read | ||
| BV | 948 | MainVlv_Close.Configured_R | Main floating valve close - Output configurated; Modbus DI490 | Read | ||
| BV | 949 | PreHeatVlv_Close.Val_Hw_R | Pre-heating floating valve close - Hardware value writes from board; Modbus DI491 | Read | ||
| BV | 950 | PreHeatVlv_Close.Val_W | Pre-heating floating valve close; Modbus DI492 | Read | ||
| BV | 951 | PreHeatVlv_Close.Enable_W | Pre-heating floating valve close - Enable output; Modbus DI493 | Read | ||
| BV | 952 | PreHeatVlv_Close.Configured_R | Pre-heating floating valve close - Output configurated; Modbus DI494 | Read | ||
| BV | 953 | ReHeatVlv_Close.Val_Hw_R | Re-Heating floating valve close - Hardware value writes from board; Modbus DI495 | Read | ||
| BV | 954 | ReHeatVlv_Close.Val_W | Re-Heating floating valve close; Modbus DI496 | Read | ||
| BV | 955 | ReHeatVlv_Close.Enable_W | Re-Heating floating valve close - Enable output; Modbus DI497 | Read | ||
| BV | 956 | ReHeatVlv_Close.Configured_R | Re-Heating floating valve close - Output configurated; Modbus DI498 | Read | ||
| BV | 957 | MainCoil_Step1.Val_Hw_R | Main step 1 - Hardware value writes from board; Modbus DI499 | Read | ||
| BV | 958 | MainCoil_Step1.Val_W | Main step 1; Modbus DI500 | Read | ||
| BV | 959 | MainCoil_Step1.Enable_W | Main step 1 - Enable output; Modbus DI501 | Read | ||
| BV | 960 | MainCoil_Step1.Configured_R | Main step 1 - Output configurated; Modbus DI502 | Read | ||
| BV | 961 | MainCoil_Step2.Val_Hw_R | Main step 2 - Hardware value writes from board; Modbus DI503 | Read | ||
| BV | 962 | MainCoil_Step2.Val_W | Main step 2; Modbus DI504 | Read | ||
| BV | 963 | MainCoil_Step2.Enable_W | Main step 2 - Enable output; Modbus DI505 | Read | ||
| BV | 964 | MainCoil_Step2.Configured_R | Main step 2 - Output configurated; Modbus DI506 | Read | ||
| BV | 965 | MainCoil_Step3.Val_Hw_R | Main step 3 - Hardware value writes from board; Modbus DI507 | Read | ||
| BV | 966 | MainCoil_Step3.Val_W | Main step 3; Modbus DI508 | Read | ||
| BV | 967 | MainCoil_Step3.Enable_W | Main step 3 - Enable output; Modbus DI509 | Read | ||
| BV | 968 | MainCoil_Step3.Configured_R | Main step 3 - Output configurated; Modbus DI510 | Read | ||
| BV | 969 | MainCoil_Step4.Val_Hw_R | Main step 4 - Hardware value writes from board; Modbus DI511 | Read | ||
| BV | 970 | MainCoil_Step4.Val_W | Main step 4; Modbus DI512 | Read | ||
| BV | 971 | MainCoil_Step4.Enable_W | Main step 4 - Enable output; Modbus DI513 | Read | ||
| BV | 972 | MainCoil_Step4.Configured_R | Main step 4 - Output configurated; Modbus DI514 | Read | ||
| BV | 973 | ReHeatCoil_Step1.Val_Hw_R | Postheat heater 1 - Hardware value writes from board; Modbus DI515 | Read | ||
| BV | 974 | ReHeatCoil_Step1.Val_W | Postheat heater 1; Modbus DI516 | Read | ||
| BV | 975 | ReHeatCoil_Step1.Enable_W | Postheat heater 1 - Enable output; Modbus DI517 | Read | ||
| BV | 976 | ReHeatCoil_Step1.Configured_R | Postheat heater 1 - Output configurated; Modbus DI518 | Read | ||
| BV | 977 | ReHeatCoil_Step2.Val_Hw_R | Postheat heater 2 - Hardware value writes from board; Modbus DI519 | Read | ||
| BV | 978 | ReHeatCoil_Step2.Val_W | Postheat heater 2; Modbus DI520 | Read | ||
| BV | 979 | ReHeatCoil_Step2.Enable_W | Postheat heater 2 - Enable output; Modbus DI521 | Read | ||
| BV | 980 | ReHeatCoil_Step2.Configured_R | Postheat heater 2 - Output configurated; Modbus DI522 | Read | ||
| BV | 981 | ReHeatCoil_Step3.Val_Hw_R | Postheat heater 3 - Hardware value writes from board; Modbus DI523 | Read | ||
| BV | 982 | ReHeatCoil_Step3.Val_W | Postheat heater 3; Modbus DI524 | Read | ||
| BV | 983 | ReHeatCoil_Step3.Enable_W | Postheat heater 3 - Enable output; Modbus DI525 | Read | ||
| BV | 984 | ReHeatCoil_Step3.Configured_R | Postheat heater 3 - Output configurated; Modbus DI526 | Read | ||
| BV | 985 | ReHeatCoil_Step4.Val_Hw_R | Postheat heater 4 - Hardware value writes from board; Modbus DI527 | Read | ||
| BV | 986 | ReHeatCoil_Step4.Val_W | Postheat heater 4; Modbus DI528 | Read | ||
| BV | 987 | ReHeatCoil_Step4.Enable_W | Postheat heater 4 - Enable output; Modbus DI529 | Read | ||
| BV | 988 | ReHeatCoil_Step4.Configured_R | Postheat heater 4 - Output configurated; Modbus DI530 | Read | ||
| BV | 989 | PreHeatCoil_Step1.Val_Hw_R | Preheat heater 1 - Hardware value writes from board; Modbus DI531 | Read | ||
| BV | 990 | PreHeatCoil_Step1.Val_W | Preheat heater 1; Modbus DI532 | Read | ||
| BV | 991 | PreHeatCoil_Step1.Enable_W | Preheat heater 1 - Enable output; Modbus DI533 | Read | ||
| BV | 992 | PreHeatCoil_Step1.Configured_R | Preheat heater 1 - Output configurated; Modbus DI534 | Read | ||
| BV | 993 | PreHeatCoil_Step2.Val_Hw_R | Preheat heater 2 - Hardware value writes from board; Modbus DI535 | Read | ||
| BV | 994 | PreHeatCoil_Step2.Val_W | Preheat heater 2; Modbus DI536 | Read | ||
| BV | 995 | PreHeatCoil_Step2.Enable_W | Preheat heater 2 - Enable output; Modbus DI537 | Read | ||
| BV | 996 | PreHeatCoil_Step2.Configured_R | Preheat heater 2 - Output configurated; Modbus DI538 | Read | ||
| BV | 997 | PreHeatCoil_Step3.Val_Hw_R | Preheat heater 3 - Hardware value writes from board; Modbus DI539 | Read | ||
| BV | 998 | PreHeatCoil_Step3.Val_W | Preheat heater 3; Modbus DI540 | Read | ||
| BV | 999 | PreHeatCoil_Step3.Enable_W | Preheat heater 3 - Enable output; Modbus DI541 | Read | ||
| BV | 1000 | PreHeatCoil_Step3.Configured_R | Preheat heater 3 - Output configurated; Modbus DI542 | Read | ||
| BV | 1001 | PreHeatCoil_Step4.Val_Hw_R | Preheat heater 4 - Hardware value writes from board; Modbus DI543 | Read | ||
| BV | 1002 | PreHeatCoil_Step4.Val_W | Preheat heater 4; Modbus DI544 | Read | ||
| BV | 1003 | PreHeatCoil_Step4.Enable_W | Preheat heater 4 - Enable output; Modbus DI545 | Read | ||
| BV | 1004 | PreHeatCoil_Step4.Configured_R | Preheat heater 4 - Output configurated; Modbus DI546 | Read | ||
| BV | 1005 | OA_Coil_Step1.Val_Hw_R | Outdoor air pre-treatment heater 1 - Hardware value writes from board; Modbus DI547 | Read | ||
| BV | 1006 | OA_Coil_Step1.Val_W | Outdoor air pre-treatment heater 1; Modbus DI548 | Read | ||
| BV | 1007 | OA_Coil_Step1.Enable_W | Outdoor air pre-treatment heater 1 - Enable output; Modbus DI549 | Read | ||
| BV | 1008 | OA_Coil_Step1.Configured_R | Outdoor air pre-treatment heater 1 - Output configurated; Modbus DI550 | Read | ||
| BV | 1009 | OA_Coil_Step2.Val_Hw_R | Outdoor air pre-treatment heater 2 - Hardware value writes from board; Modbus DI551 | Read | ||
| BV | 1010 | OA_Coil_Step2.Val_W | Outdoor air pre-treatment heater 2; Modbus DI552 | Read | ||
| BV | 1011 | OA_Coil_Step2.Enable_W | Outdoor air pre-treatment heater 2 - Enable output; Modbus DI553 | Read | ||
| BV | 1012 | OA_Coil_Step2.Configured_R | Outdoor air pre-treatment heater 2 - Output configurated; Modbus DI554 | Read | ||
| BV | 1013 | OA_Coil_Step3.Val_Hw_R | Outdoor air pre-treatment heater 3 - Hardware value writes from board; Modbus DI555 | Read | ||
| BV | 1014 | OA_Coil_Step3.Val_W | Outdoor air pre-treatment heater 3; Modbus DI556 | Read | ||
| BV | 1015 | OA_Coil_Step3.Enable_W | Outdoor air pre-treatment heater 3 - Enable output; Modbus DI557 | Read | ||
| BV | 1016 | OA_Coil_Step3.Configured_R | Outdoor air pre-treatment heater 3 - Output configurated; Modbus DI558 | Read | ||
| BV | 1017 | OA_Coil_Step4.Val_Hw_R | Outdoor air pre-treatment heater 4 - Hardware value writes from board; Modbus DI559 | Read | ||
| BV | 1018 | OA_Coil_Step4.Val_W | Outdoor air pre-treatment heater 4; Modbus DI560 | Read | ||
| BV | 1019 | OA_Coil_Step4.Enable_W | Outdoor air pre-treatment heater 4 - Enable output; Modbus DI561 | Read | ||
| BV | 1020 | OA_Coil_Step4.Configured_R | Outdoor air pre-treatment heater 4 - Output configurated; Modbus DI562 | Read | ||
| BV | 1021 | PreHeatPmp_1.Val_Hw_R | Pre-Heating pump 1 - Hardware value writes from board; Modbus DI563 | Read | ||
| BV | 1022 | PreHeatPmp_1.Val_W | Pre-Heating pump 1; Modbus DI564 | Read | ||
| BV | 1023 | PreHeatPmp_1.Enable_W | Pre-Heating pump 1 - Enable output; Modbus DI565 | Read | ||
| BV | 1024 | PreHeatPmp_1.Configured_R | Pre-Heating pump 1 - Output configurated; Modbus DI566 | Read | ||
| BV | 1025 | PreHeatPmp_2.Val_Hw_R | Pre-Heating pump 2 - Hardware value writes from board; Modbus DI567 | Read | ||
| BV | 1026 | PreHeatPmp_2.Val_W | Pre-Heating pump 2; Modbus DI568 | Read | ||
| BV | 1027 | PreHeatPmp_2.Enable_W | Pre-Heating pump 2 - Enable output; Modbus DI569 | Read | ||
| BV | 1028 | PreHeatPmp_2.Configured_R | Pre-Heating pump 2 - Output configurated; Modbus DI570 | Read | ||
| BV | 1029 | MainCoilPmp_1.Val_Hw_R | Main pump 1 - Hardware value writes from board; Modbus DI571 | Read | ||
| BV | 1030 | MainCoilPmp_1.Val_W | Main pump 1; Modbus DI572 | Read | ||
| BV | 1031 | MainCoilPmp_1.Enable_W | Main pump 1 - Enable output; Modbus DI573 | Read | ||
| BV | 1032 | MainCoilPmp_1.Configured_R | Main pump 1 - Output configurated; Modbus DI574 | Read | ||
| BV | 1033 | MainCoilPmp_2.Val_Hw_R | Main pump 2 - Hardware value writes from board; Modbus DI575 | Read | ||
| BV | 1034 | MainCoilPmp_2.Val_W | Main pump 2; Modbus DI576 | Read | ||
| BV | 1035 | MainCoilPmp_2.Enable_W | Main pump 2 - Enable output; Modbus DI577 | Read | ||
| BV | 1036 | MainCoilPmp_2.Configured_R | Main pump 2 - Output configurated; Modbus DI578 | Read | ||
| BV | 1037 | ReHeatPmp_1.Val_Hw_R | Re-Heating pump 1 - Hardware value writes from board; Modbus DI579 | Read | ||
| BV | 1038 | ReHeatPmp_1.Val_W | Re-Heating pump 1; Modbus DI580 | Read | ||
| BV | 1039 | ReHeatPmp_1.Enable_W | Re-Heating pump 1 - Enable output; Modbus DI581 | Read | ||
| BV | 1040 | ReHeatPmp_1.Configured_R | Re-Heating pump 1 - Output configurated; Modbus DI582 | Read | ||
| BV | 1041 | ReHeatPmp_2.Val_Hw_R | Re-Heating pump 2 - Hardware value writes from board; Modbus DI583 | Read | ||
| BV | 1042 | ReHeatPmp_2.Val_W | Re-Heating pump 2; Modbus DI584 | Read | ||
| BV | 1043 | ReHeatPmp_2.Enable_W | Re-Heating pump 2 - Enable output; Modbus DI585 | Read | ||
| BV | 1044 | ReHeatPmp_2.Configured_R | Re-Heating pump 2 - Output configurated; Modbus DI586 | Read | ||
| BV | 1045 | OA_CoilPmp_1.Val_Hw_R | Outdoor air pre-treatment-Heating pump 1 - Hardware value writes from board; Modbus DI587 | Read | ||
| BV | 1046 | OA_CoilPmp_1.Val_W | Outdoor air pre-treatment-Heating pump 1; Modbus DI588 | Read | ||
| BV | 1047 | OA_CoilPmp_1.Enable_W | Outdoor air pre-treatment-Heating pump 1 - Enable output; Modbus DI589 | Read | ||
| BV | 1048 | OA_CoilPmp_1.Configured_R | Outdoor air pre-treatment-Heating pump 1 - Output configurated; Modbus DI590 | Read | ||
| BV | 1049 | OA_CoilPmp_2.Val_Hw_R | Outdoor air pre-treatment-Heating pump 2 - Hardware value writes from board; Modbus DI591 | Read | ||
| BV | 1050 | OA_CoilPmp_2.Val_W | Outdoor air pre-treatment-Heating pump 2; Modbus DI592 | Read | ||
| BV | 1051 | OA_CoilPmp_2.Enable_W | Outdoor air pre-treatment-Heating pump 2 - Enable output; Modbus DI593 | Read | ||
| BV | 1052 | OA_CoilPmp_2.Configured_R | Outdoor air pre-treatment-Heating pump 2 - Output configurated; Modbus DI594 | Read | ||
| BV | 1053 | FiltAlrm_Dout.Val_Hw_R | Filters alarm - Hardware value writes from board; Modbus DI595 | Read | ||
| BV | 1054 | FiltAlrm_Dout.Val_W | Filters alarm; Modbus DI596 | Read | ||
| BV | 1055 | FiltAlrm_Dout.Enable_W | Filters alarm - Enable output; Modbus DI597 | Read | ||
| BV | 1056 | FiltAlrm_Dout.Configured_R | Filters alarm - Output configurated; Modbus DI598 | Read | ||
| BV | 1057 | Recovery_Dout.Val_Hw_R | Recovery - Hardware value writes from board; Modbus DI599 | Read | ||
| BV | 1058 | Recovery_Dout.Val_W | Recovery; Modbus DI600 | Read | ||
| BV | 1059 | Recovery_Dout.Enable_W | Recovery - Enable output; Modbus DI601 | Read | ||
| BV | 1060 | Recovery_Dout.Configured_R | Recovery - Output configurated; Modbus DI602 | Read | ||
| BV | 1061 | IEC_Hum_Dout.Val_Hw_R | IEC humidifer - Hardware value writes from board; Modbus DI603 | Read | ||
| BV | 1062 | IEC_Hum_Dout.Val_W | IEC humidifer; Modbus DI604 | Read | ||
| BV | 1063 | IEC_Hum_Dout.Enable_W | IEC humidifer - Enable output; Modbus DI605 | Read | ||
| BV | 1064 | IEC_Hum_Dout.Configured_R | IEC humidifer - Output configurated; Modbus DI606 | Read | ||
| BV | 1065 | SupplyFan_Aout.Enable_W | Supply fan - Enable output; Modbus DI607 | Read | ||
| BV | 1066 | SupplyFan_Aout.Configured_R | Supply fan - Analog output configured; Modbus DI608 | Read | ||
| BV | 1067 | RetFan_Aout.Enable_W | Return fan - Enable output; Modbus DI609 | Read | ||
| BV | 1068 | RetFan_Aout.Configured_R | Return fan - Analog output configured; Modbus DI610 | Read | ||
| BV | 1069 | BypassDamp_Aout.Enable_W | Bypass damper - Enable output; Modbus DI611 | Read | ||
| BV | 1070 | BypassDamp_Aout.Configured_R | Bypass damper - Analog output configured; Modbus DI612 | Read | ||
| BV | 1071 | MixingDamp_Aout.Enable_W | Mixing damper - Enable output; Modbus DI613 | Read | ||
| BV | 1072 | MixingDamp_Aout.Configured_R | Mixing damper - Analog output configured; Modbus DI614 | Read | ||
| BV | 1073 | FreshAirDamp_Aout.Enable_W | Fresh air damper - Enable output; Modbus DI615 | Read | ||
| BV | 1074 | FreshAirDamp_Aout.Configured_R | Fresh air damper - Analog output configured; Modbus DI616 | Read | ||
| BV | 1075 | ReHeatCoil_Aout.Enable_W | Reheat heater - Enable output; Modbus DI617 | Read | ||
| BV | 1076 | ReHeatCoil_Aout.Configured_R | Reheat heater - Analog output configured; Modbus DI618 | Read | ||
| BV | 1077 | PreHeatCoil_Aout.Enable_W | Pre-Heating heater - Enable output; Modbus DI619 | Read | ||
| BV | 1078 | PreHeatCoil_Aout.Configured_R | Pre-Heating heater - Analog output configured; Modbus DI620 | Read | ||
| BV | 1079 | OA_Coil_Aout.Enable_W | Outdoor air pre-treatment heater - Enable output; Modbus DI621 | Read | ||
| BV | 1080 | OA_Coil_Aout.Configured_R | Outdoor air pre-treatment heater - Analog output configured; Modbus DI622 | Read | ||
| BV | 1081 | MainCoil_Aout.Enable_W | Main coil valve - Enable output; Modbus DI623 | Read | ||
| BV | 1082 | MainCoil_Aout.Configured_R | Main coil valve - Analog output configured; Modbus DI624 | Read | ||
| BV | 1083 | ThrmlWheel_Aout.Enable_W | Thermal wheel - Enable output; Modbus DI625 | Read | ||
| BV | 1084 | ThrmlWheel_Aout.Configured_R | Thermal wheel - Analog output configured; Modbus DI626 | Read | ||
| BV | 1085 | Humidifier_Aout.Enable_W | Humidifier - Enable output; Modbus DI627 | Read | ||
| BV | 1086 | Humidifier_Aout.Configured_R | Humidifier - Analog output configured; Modbus DI628 | Read | ||
| BV | 1087 | ExhAirDamp_Aout.Enable_W | Exhaust air damper - Enable output; Modbus DI629 | Read | ||
| BV | 1088 | ExhAirDamp_Aout.Configured_R | Exhaust air damper - Analog output configured; Modbus DI630 | Read | ||
| BV | 1089 | AuxAout_1.Enable_W | Auxiliary output 1 - Enable output; Modbus DI631 | Read | ||
| BV | 1090 | AuxAout_1.Configured_R | Auxiliary output 1 - Analog output configured; Modbus DI632 | Read | ||
| BV | 1091 | AuxAout_2.Enable_W | Auxiliary output 2 - Enable output; Modbus DI633 | Read | ||
| BV | 1092 | AuxAout_2.Configured_R | Auxiliary output 2 - Analog output configured; Modbus DI634 | Read | ||
| BV | 1093 | AuxAout_3.Enable_W | Auxiliary output 3 - Enable output; Modbus DI635 | Read | ||
| BV | 1094 | AuxAout_3.Configured_R | Auxiliary output 3 - Analog output configured; Modbus DI636 | Read | ||
| BV | 1095 | AuxAout_4.Enable_W | Auxiliary output 4 - Enable output; Modbus DI637 | Read | ||
| BV | 1096 | AuxAout_4.Configured_R | Auxiliary output 4 - Analog output configured; Modbus DI638 | Read | ||
| BV | 1097 | IEC_Aout.Enable_W | IEC - Enable output; Modbus DI639 | Read | ||
| BV | 1098 | IEC_Aout.Configured_R | IEC - Analog output configured; Modbus DI640 | Read | ||
| BV | 1099 | Recovery_Aout.Enable_W | Recovery pump - Enable output; Modbus DI641 | Read | ||
| BV | 1100 | Recovery_Aout.Configured_R | Recovery pump - Analog output configured; Modbus DI642 | Read | ||
| BV | 1101 | SupplyAirDamp_Aout.Enable_W | Supply air damper - Enable output; Modbus DI643 | Read | ||
| BV | 1102 | SupplyAirDamp_Aout.Configured_R | Supply air damper - Analog output configured; Modbus DI644 | Read | ||
| BV | 1103 | RetAirDamp_Aout.Enable_W | Return air damper - Enable output; Modbus DI645 | Read | ||
| BV | 1104 | RetAirDamp_Aout.Configured_R | Return air damper - Analog output configured; Modbus DI646 | Read | ||
| BV | 1115 | Scheduler_OnOffUnit.FB_SchedulerMngK_1.StatusChk | Modbus DI657 | Read | ||
| BV | 1116 | Scheduler_OnOffUnit.FB_SchedulerMngK_1.VacChk | Modbus DI658 | Read | ||
| BV | 1117 | Scheduler_OnOffUnit.FB_SchedulerMngK_1.SDayChk | Modbus DI659 | Read | ||
| BV | 1152 | GeneralMng.WizardCustom | Modbus DI694 | Read | ||
| BV | 1153 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.CfgErr_SCHED | Modbus DI695 | Read | ||
| BV | 1157 | GenericHumidifier.ModulHum_IO_CfgWarn | Modbus DI699 | Read | ||
| BV | 1164 | AuxiliaryRegulation.AuxReg1_Info.InputCheckCfgErr | Auxiliary regulation 1: Informations - Input check configuration error; Modbus DI706 | Read | ||
| BV | 1165 | AuxiliaryRegulation.AuxReg1_Info.OutputCheckCfgErr | Auxiliary regulation 1: Informations - Output check configuration error; Modbus DI707 | Read | ||
| BV | 1166 | AuxiliaryRegulation.AuxReg1_Info.DOut | Auxiliary regulation 1: Informations - Dout configured; Modbus DI708 | Read | ||
| BV | 1167 | AuxiliaryRegulation.AuxReg1_Info.EnableCheckCfgErr | Auxiliary regulation 1: Informations - Enable check configuration error; Modbus DI709 | Read | ||
| BV | 1168 | AuxiliaryRegulation.AuxReg2_Info.InputCheckCfgErr | Auxiliary regulation 2: Informations - Input check configuration error; Modbus DI710 | Read | ||
| BV | 1169 | AuxiliaryRegulation.AuxReg2_Info.OutputCheckCfgErr | Auxiliary regulation 2: Informations - Output check configuration error; Modbus DI711 | Read | ||
| BV | 1170 | AuxiliaryRegulation.AuxReg2_Info.DOut | Auxiliary regulation 2: Informations - Dout configured; Modbus DI712 | Read | ||
| BV | 1171 | AuxiliaryRegulation.AuxReg2_Info.EnableCheckCfgErr | Auxiliary regulation 2: Informations - Enable check configuration error; Modbus DI713 | Read | ||
| BV | 1172 | AuxiliaryRegulation.AuxReg3_Info.InputCheckCfgErr | Auxiliary regulation 3: Informations - Input check configuration error; Modbus DI714 | Read | ||
| BV | 1173 | AuxiliaryRegulation.AuxReg3_Info.OutputCheckCfgErr | Auxiliary regulation 3: Informations - Output check configuration error; Modbus DI715 | Read | ||
| BV | 1174 | AuxiliaryRegulation.AuxReg3_Info.DOut | Auxiliary regulation 3: Informations - Dout configured; Modbus DI716 | Read | ||
| BV | 1175 | AuxiliaryRegulation.AuxReg3_Info.EnableCheckCfgErr | Auxiliary regulation 3: Informations - Enable check configuration error; Modbus DI717 | Read | ||
| BV | 1176 | AuxiliaryRegulation.AuxReg4_Info.InputCheckCfgErr | Auxiliary regulation 4: Informations - Input check configuration error; Modbus DI718 | Read | ||
| BV | 1177 | AuxiliaryRegulation.AuxReg4_Info.OutputCheckCfgErr | Auxiliary regulation 4: Informations - Output check configuration error; Modbus DI719 | Read | ||
| BV | 1178 | AuxiliaryRegulation.AuxReg4_Info.DOut | Auxiliary regulation 4: Informations - Dout configured; Modbus DI720 | Read | ||
| BV | 1179 | AuxiliaryRegulation.AuxReg4_Info.EnableCheckCfgErr | Auxiliary regulation 4: Informations - Enable check configuration error; Modbus DI721 | Read | ||
| BV | 1180 | Comp_OnOff.OnOffComp_IO_CfgWarn | Modbus DI722 | Read | ||
| BV | 1181 | BLDC_compressor.BLDC_Comp_IO_CfgWarn | Modbus DI723 | Read | ||
| BV | 1182 | cpCOmini_HighEnd | c.pCOmini high end version present; Modbus DI724 | Read | ||
| BV | 1183 | GeneralMng.DHCP_State_1 | Automatically generated; Modbus DI725 | Read | ||
| BV | 1184 | BLDC_compressor.Info_PWRP1.StatusReg_Bit_15 | Inverter Power Plus Info - Status register bit 15; Modbus DI726 | Read | ||
| BV | 1185 | BLDC_compressor.Info_PWRP1.StatusReg_Bit_14 | Inverter Power Plus Info - Status register bit 14; Modbus DI727 | Read | ||
| BV | 1186 | BLDC_compressor.Info_PWRP1.StatusReg_Bit_13 | Inverter Power Plus Info - Status register bit 13; Modbus DI728 | Read | ||
| BV | 1187 | BLDC_compressor.Info_PWRP1.StatusReg_Bit_12 | Inverter Power Plus Info - Status register bit 12; Modbus DI729 | Read | ||
| BV | 1188 | BLDC_compressor.Info_PWRP1.StatusReg_DriveTripped | Inverter Power Plus Info - Drive in alarm; Modbus DI730 | Read | ||
| BV | 1189 | BLDC_compressor.Info_PWRP1.StatusReg_Bit_10 | Inverter Power Plus Info - Status register bit 10; Modbus DI731 | Read | ||
| BV | 1190 | BLDC_compressor.Info_PWRP1.StatusReg_MainSupplyLossed | Inverter Power Plus Info - Power supply status: 0=OK; 1=loss ...; Modbus DI732 | Read | ||
| BV | 1191 | BLDC_compressor.Info_PWRP1.StatusReg_MotorOverload | Inverter Power Plus Info - Motor overload; Modbus DI733 | Read | ||
| BV | 1192 | BLDC_compressor.Info_PWRP1.StatusReg_DriveInAutotune | Inverter Power Plus Info - Autotune running; Modbus DI734 | Read | ||
| BV | 1193 | BLDC_compressor.Info_PWRP1.StatusReg_Bit_06 | Inverter Power Plus Info - Status register bit 06; Modbus DI735 | Read | ||
| BV | 1194 | BLDC_compressor.Info_PWRP1.StatusReg_SwitchingFreqDeratingON | Inverter Power Plus Info - Switching frequency derating ON; Modbus DI736 | Read | ||
| BV | 1195 | BLDC_compressor.Info_PWRP1.StatusReg_FanON | Inverter Power Plus Info - Fan ON; Modbus DI737 | Read | ||
| BV | 1196 | BLDC_compressor.Info_PWRP1.StatusReg_UnderVoltage | Inverter Power Plus Info - Under voltage; Modbus DI738 | Read | ||
| BV | 1197 | BLDC_compressor.Info_PWRP1.StatusReg_MotorPTC_OverHeat | Inverter Power Plus Info - Motor PTC overheating; Modbus DI739 | Read | ||
| BV | 1198 | BLDC_compressor.Info_PWRP1.StatusReg_RelayConfigON | Inverter Power Plus Info - Relay config. ON; Modbus DI740 | Read | ||
| BV | 1199 | BLDC_compressor.Info_PWRP1.StatusReg_DriveInhibit | Inverter Power Plus Info - Safety input status (STO); 0=drive ...; Modbus DI741 | Read | ||
| BV | 1200 | BLDC_compressor.Info_PWRP1.SpeedReg_Bit_15 | Inverter Power Plus Info - Speed register bit 15; Modbus DI742 | Read | ||
| BV | 1201 | BLDC_compressor.Info_PWRP1.SpeedReg_Bit_14 | Inverter Power Plus Info - Speed register bit 14; Modbus DI743 | Read | ||
| BV | 1202 | BLDC_compressor.Info_PWRP1.SpeedReg_Bit_13 | Inverter Power Plus Info - Speed register bit 13; Modbus DI744 | Read | ||
| BV | 1203 | BLDC_compressor.Info_PWRP1.SpeedReg_Bit_12 | Inverter Power Plus Info - Speed register bit 12; Modbus DI745 | Read | ||
| BV | 1204 | BLDC_compressor.Info_PWRP1.SpeedReg_Bit_11 | Inverter Power Plus Info - Speed register bit 11; Modbus DI746 | Read | ||
| BV | 1205 | BLDC_compressor.Info_PWRP1.SpeedReg_Bit_10 | Inverter Power Plus Info - Speed register bit 10; Modbus DI747 | Read | ||
| BV | 1206 | BLDC_compressor.Info_PWRP1.SpeedReg_Bit_09 | Inverter Power Plus Info - Speed register bit 09; Modbus DI748 | Read | ||
| BV | 1207 | BLDC_compressor.Info_PWRP1.SpeedReg_Bit_08 | Inverter Power Plus Info - Speed register bit 08; Modbus DI749 | Read | ||
| BV | 1208 | BLDC_compressor.Info_PWRP1.SpeedReg_Bit_07 | Inverter Power Plus Info - Speed register bit 07; Modbus DI750 | Read | ||
| BV | 1209 | BLDC_compressor.Info_PWRP1.SpeedReg_Bit_06 | Inverter Power Plus Info - Speed register bit 06; Modbus DI751 | Read | ||
| BV | 1210 | BLDC_compressor.Info_PWRP1.SpeedReg_Bit_05 | Inverter Power Plus Info - Speed register bit 05; Modbus DI752 | Read | ||
| BV | 1211 | BLDC_compressor.Info_PWRP1.SpeedReg_Bit_04 | Inverter Power Plus Info - Speed register bit 04; Modbus DI753 | Read | ||
| BV | 1212 | BLDC_compressor.Info_PWRP1.SpeedReg_Bit_03 | Inverter Power Plus Info - Speed register bit 03; Modbus DI754 | Read | ||
| BV | 1213 | BLDC_compressor.Info_PWRP1.SpeedReg_Bit_02 | Inverter Power Plus Info - Speed register bit 02; Modbus DI755 | Read | ||
| BV | 1214 | BLDC_compressor.Info_PWRP1.SpeedReg_Bit_01 | Inverter Power Plus Info - Speed register bit 01; Modbus DI756 | Read | ||
| BV | 1215 | BLDC_compressor.Info_PWRP1.SpeedReg_Bit_00 | Inverter Power Plus Info - Speed register bit 00; Modbus DI757 | Read | ||
| BV | 1216 | BLDC_compressor.Info_PWRP1.Mng_CheckVI_NotOK | Inverter Power Plus Info - Reserved; Modbus DI758 | Read | ||
| BV | 1217 | BLDC_compressor.Info_PWRP1.Mng_LoadDefFail | Inverter Power Plus Info - Reserved; Modbus DI759 | Read | ||
| BV | 1218 | BLDC_compressor.Info_PWRP1.Info_PSD_400V | Inverter Power Plus Info - Main supply as three phases; Modbus DI760 | Read | ||
| BV | 1219 | BLDC_compressor.Info_PWRP1.Mng_MotSelect_400V | Inverter Power Plus Info - Three-phase inverter required for compressor; Modbus DI761 | Read | ||
| BV | 1220 | BLDC_compressor.MiscMng_PWRP1.MngCstm_SaveCustomCfgInProgress | Custom cofiguration data saving in progress; Modbus DI762 | Read | ||
| BV | 1221 | BLDC_compressor.PwrpOnline_BLDC1 | Inverter is online; Modbus DI763 | Read | ||
| BV | 1222 | Info_BLDC1.Mng_TestMode | BLDC informations - Managing test mode; Modbus DI764 | Read | ||
| BV | 1223 | Info_BLDC1.Info_SIAM_90rpsZone | BLDC informations - Working zone 1c - max speed 90 ...; Modbus DI765 | Read | ||
| BV | 1224 | Info_BLDC1.UI_EqualizationStatus | BLDC informations - Show pressure equalization status (blinking); Modbus DI766 | Read | ||
| BV | 1225 | Info_BLDC1.UI_LowDeltaP | BLDC informations - Show low pressure difference condition; Modbus DI767 | Read | ||
| BV | 1226 | Info_BLDC1.EnvTyp_SiamComp | BLDC informations - Envelope Type: Siam compressor; Modbus DI768 | Read | ||
| BV | 1227 | SPV_Warning_Config | Warning: SPV Configuration error; Modbus DI769 | Read | ||
| BV | 1228 | SPV_Warning_License | Warning: SPV License not compatible; Modbus DI770 | Read | ||
| BV | 1229 | Al_NOT_USED.Active | Alarm to make the alarms list compatible with mask - ...; Modbus DI1000 | Read | ||
| BV | 1230 | Al_SupplyTemp.Active | Supply temperature probe alarm - Alarm status; Modbus DI1001 | Read | ||
| BV | 1231 | Al_SupplyHum.Active | Supply humidity probe alarm - Alarm status; Modbus DI1002 | Read | ||
| BV | 1232 | Al_RetTemp.Active | Return temperature probe alarm - Alarm status; Modbus DI1003 | Read | ||
| BV | 1233 | Al_RetHum.Active | Return humidity probe alarm - Alarm status; Modbus DI1004 | Read | ||
| BV | 1234 | Al_RoomTemp.Active | Room temperature probe alarm - Alarm status; Modbus DI1005 | Read | ||
| BV | 1235 | Al_RoomHum.Active | Room humidity probe alarm - Alarm status; Modbus DI1006 | Read | ||
| BV | 1236 | Al_ExtTemp.Active | Fresh air temperature probe alarm - Alarm status; Modbus DI1007 | Read | ||
| BV | 1237 | Al_ExtHum.Active | Fresh air humidity probe alarm - Alarm status; Modbus DI1008 | Read | ||
| BV | 1238 | Al_ExhTemp.Active | Exhaust temperature probe alarm - Alarm status; Modbus DI1009 | Read | ||
| BV | 1239 | Al_ExhHum.Active | Exhaust humidity probe alarm - Alarm status; Modbus DI1010 | Read | ||
| BV | 1240 | Al_AFreezeTemp.Active | Antifreeze temperature probe alarm - Alarm status; Modbus DI1011 | Read | ||
| BV | 1241 | Al_SatTemp.Active | Saturation temperature probe alarm - Alarm status; Modbus DI1012 | Read | ||
| BV | 1242 | Al_SatHum.Active | Saturation humidity probe alarm - Alarm status; Modbus DI1013 | Read | ||
| BV | 1243 | Al_OutdoorAirTemp.Active | Outdoor air pre-treatment temperature probe alarm- Alarm status; Modbus DI1014 | Read | ||
| BV | 1244 | Al_SupplyAirP.Active | Supply air pressure probe alarm - Alarm status; Modbus DI1015 | Read | ||
| BV | 1245 | Al_RetAirP.Active | Return air pressure probe alarm - Alarm status; Modbus DI1016 | Read | ||
| BV | 1246 | Al_AirQuality_CO2.Active | CO2 sensor probe alarm - Alarm status; Modbus DI1017 | Read | ||
| BV | 1247 | Al_AirQuality_VOC.Active | VOC sensor probe alarm - Alarm status; Modbus DI1018 | Read | ||
| BV | 1248 | Al_DscgP.Active | Discharge pressure probe alarm - Alarm status; Modbus DI1019 | Read | ||
| BV | 1249 | Al_DscgT.Active | Discharge temperature probe alarm - Alarm status; Modbus DI1020 | Read | ||
| BV | 1250 | Al_SuctP.Active | Suction pressure probe alarm - Alarm status; Modbus DI1021 | Read | ||
| BV | 1251 | Al_SuctT.Active | Suction temperature probe alarm - Alarm status; Modbus DI1022 | Read | ||
| BV | 1252 | Al_OA_CoilWaterTemp.Active | Outdoor air pre-treatment coil water temperature probe alarm - Alarm status; Modbus DI1023 | Read | ||
| BV | 1253 | Al_PreHeatCoilWaterTemp.Active | Preheat coil water temperature probe alarm - Alarm status; Modbus DI1024 | Read | ||
| BV | 1254 | Al_MainCoilWaterTemp.Active | Main coil water temperature probe alarm - Alarm status; Modbus DI1025 | Read | ||
| BV | 1255 | Al_ReHeatCoilWaterTemp.Active | Re heat coil water temperature probe alarm - Alarm status; Modbus DI1026 | Read | ||
| BV | 1256 | Al_AuxPrb_1.Active | Auxiliary probe 1 probe alarm - Alarm status; Modbus DI1027 | Read | ||
| BV | 1257 | Al_AuxPrb_2.Active | Auxiliary probe 2 probe alarm - Alarm status; Modbus DI1028 | Read | ||
| BV | 1258 | Al_AuxPrb_3.Active | Auxiliary probe 3 probe alarm - Alarm status; Modbus DI1029 | Read | ||
| BV | 1259 | Al_AuxPrb_4.Active | Auxiliary probe 4 probe alarm - Alarm status; Modbus DI1030 | Read | ||
| BV | 1260 | Al_Ain_SetP.Active | Setpoint by AIN probe alarm - Alarm status; Modbus DI1031 | Read | ||
| BV | 1261 | Al_SupplyRecoveryTemp.Active | Supply recovery temperature probe alarm - Alarm status; Modbus DI1032 | Read | ||
| BV | 1262 | Al_RetRecoveryTemp.Active | Return recovery temperature probe alarm - Alarm status; Modbus DI1033 | Read | ||
| BV | 1263 | Al_HepaFilt_1.Active | Hepa filter 1 probe alarm - Alarm status; Modbus DI1034 | Read | ||
| BV | 1264 | Al_HepaFilt_2.Active | Hepa filter 2 probe alarm - Alarm status; Modbus DI1035 | Read | ||
| BV | 1265 | Al_GenericAlrmByDin.Active | Generic alarm from digital input - Alarm status; Modbus DI1036 | Read | ||
| BV | 1266 | Al_MainHeat_Ovld.Active | Main coil alarm - Alarm status; Modbus DI1037 | Read | ||
| BV | 1267 | Al_SupplyFanOvld.Active | Supply fan overload - Alarm status; Modbus DI1038 | Read | ||
| BV | 1268 | Al_RetFanOvld.Active | Return fan overload - Alarm status; Modbus DI1039 | Read | ||
| BV | 1269 | Al_FansOvld.Active | Fans overload - Alarm status; Modbus DI1040 | Read | ||
| BV | 1270 | Al_CompOvld.Active | Compressor overload - Alarm status; Modbus DI1041 | Read | ||
| BV | 1271 | Al_HiP_Sw.Active | High discharge pressure switch - Alarm status; Modbus DI1042 | Read | ||
| BV | 1272 | Al_LowP_Sw.Active | Low suction pressure switch - Alarm status; Modbus DI1043 | Read | ||
| BV | 1273 | Al_SupplyAirFlwSw.Active | Supply air flow switch alarm - Alarm status; Modbus DI1044 | Read | ||
| BV | 1274 | Al_RetAirFlwSw.Active | Return air flow switch alarm - Alarm status; Modbus DI1045 | Read | ||
| BV | 1275 | Al_AirFlwSw.Active | Air flow switch alarm - Alarm status; Modbus DI1046 | Read | ||
| BV | 1276 | Al_AFreeze.Active | Antifreeze alarm - Alarm status; Modbus DI1047 | Read | ||
| BV | 1277 | Al_LowSH_EVD_Emb.Active | EVD - Low SH - Alarm status; Modbus DI1048 | Read | ||
| BV | 1278 | Al_EEV_MotErr.Active | EVD - Motor error - Alarm status; Modbus DI1049 | Read | ||
| BV | 1279 | Al_SettingOutOfBound_EVD_Emb.Active | EVD - Setting out of bound - Alarm status; Modbus DI1050 | Read | ||
| BV | 1280 | Al_RangeErr_EVD_Emb.Active | EVD - Settings range error - Alarm status; Modbus DI1051 | Read | ||
| BV | 1281 | Al_InvOffline.Active | Inverter - Offline - Alarm status; Modbus DI1052 | Read | ||
| BV | 1282 | Al_Inv01_OverA.Active | Inverter - Drive overcurrent (01) - Alarm status; Modbus DI1053 | Read | ||
| BV | 1283 | Al_Inv02_MotOvld.Active | Inverter - Motor overload (02) - Alarm status; Modbus DI1054 | Read | ||
| BV | 1284 | Al_Inv03_DC_BusOverV.Active | Inverter - DC Bus overvoltage (03) - Alarm status; Modbus DI1055 | Read | ||
| BV | 1285 | Al_Inv04_DC_BusUnderV.Active | Inverter - DC bus undervoltage (04) - Alarm status; Modbus DI1056 | Read | ||
| BV | 1286 | Al_Inv05_OverTemp.Active | Inverter - Drive overtemperature (05) - Alarm status; Modbus DI1057 | Read | ||
| BV | 1287 | Al_Inv06_DrvUnderTemp.Active | Inverter - Drive undertemperature (06) - Alarm status; Modbus DI1058 | Read | ||
| BV | 1288 | Al_Inv07_HW_OverA.Active | Inverter - HW overcurrent HW(07) - Alarm status; Modbus DI1059 | Read | ||
| BV | 1289 | Al_Inv08_MotOverTemp.Active | Inverter - PTC motor overtemperature (08) - Alarm status; Modbus DI1060 | Read | ||
| BV | 1290 | Al_Inv09_OutputFault.Active | Inverter - IGBT module error (09) - Alarm status; Modbus DI1061 | Read | ||
| BV | 1291 | Al_Inv10_FlashDataErr.Active | Inverter - CPU error (10) - Alarm status; Modbus DI1062 | Read | ||
| BV | 1292 | Al_Inv11_ParamDef.Active | Inverter - Parameter default (11) - Alarm status; Modbus DI1063 | Read | ||
| BV | 1293 | Al_Inv12_DC_RippTooLarge.Active | Inverter - DC bus ripple (12) - Alarm status; Modbus DI1064 | Read | ||
| BV | 1294 | Al_Inv13_MB_CommFault.Active | Inverter - Data communication fault (13) - Alarm status; Modbus DI1065 | Read | ||
| BV | 1295 | Al_Inv14_DrvThermistorFault.Active | Inverter - Drive thermistor fault (14) - Alarm status; Modbus DI1066 | Read | ||
| BV | 1296 | Al_Inv15_AutotuneFault.Active | Inverter - Autotuning fault (15) - Alarm status; Modbus DI1067 | Read | ||
| BV | 1297 | Al_Inv16_DrvDis.Active | Inverter - Drive disabled (16) - Alarm status; Modbus DI1068 | Read | ||
| BV | 1298 | Al_Inv17_MotPhaseFault.Active | Inverter - Motor phase fault (17) - Alarm status; Modbus DI1069 | Read | ||
| BV | 1299 | Al_Inv18_FanFault.Active | Inverter - Internal fan fault (18) - Alarm status; Modbus DI1070 | Read | ||
| BV | 1300 | Al_Inv19_SpeedFault.Active | Inverter - Speed fault (19) - Alarm status; Modbus DI1071 | Read | ||
| BV | 1301 | Al_Inv20_PFC_Failure.Active | Inverter - PFC module error (20) - Alarm status; Modbus DI1072 | Read | ||
| BV | 1302 | Al_Inv21_PFC_OverVolt.Active | Inverter - PFC overvoltage (21) - Alarm status; Modbus DI1073 | Read | ||
| BV | 1303 | Al_Inv22_PFC_UnderVolt.Active | Inverter - PFC undervoltage (22) - Alarm status; Modbus DI1074 | Read | ||
| BV | 1304 | Al_Inv23_STO_Survey1.Active | Inverter - STO detection error (23) - Alarm status; Modbus DI1075 | Read | ||
| BV | 1305 | Al_Inv24_STO_Survey2.Active | Inverter - STO detection error (24) - Alarm status; Modbus DI1076 | Read | ||
| BV | 1306 | Al_Inv25_GroundFault.Active | Inverter - Ground fault (25) - Alarm status; Modbus DI1077 | Read | ||
| BV | 1307 | Al_Inv26_ADC_ConvSync.Active | Inverter - ADC conversion sync fault (26) - Alarm status; Modbus DI1078 | Read | ||
| BV | 1308 | Al_Inv27_HW_Sync.Active | Inverter - HW sync fault (27) - Alarm status; Modbus DI1079 | Read | ||
| BV | 1309 | Al_Inv28_DrvOvrld.Active | Inverter - Drive overload (28) - Alarm status; Modbus DI1080 | Read | ||
| BV | 1310 | Al_Inv29_uCSafe_DriveStop.Active | Inverter - Drive overtemperature (HW) (29) - Alarm status; Modbus DI1081 | Read | ||
| BV | 1311 | Al_Inv99_UnexpectedStop.Active | Inverter - Unexpected stop (99) - Alarm status; Modbus DI1082 | Read | ||
| BV | 1312 | Al_StartFail_BLDC1.Active | BLDC - Starting failure - Alarm status; Modbus DI1083 | Read | ||
| BV | 1313 | Al_SwPrototype.Active | Prototype software - Alarm status; Modbus DI1084 | Read | ||
| BV | 1314 | Al_retain.Active | High number of retain memory writings - Alarm status; Modbus DI1085 | Read | ||
| BV | 1315 | Al_Err_retain_write.Active | Error in retain memory writings - Alarm status; Modbus DI1086 | Read | ||
| BV | 1316 | Al_Offline_THTN.Active | th-Tune offline - Alarm status; Modbus DI1087 | Read | ||
| BV | 1317 | Al_LowSupplyTemp.Active | Low supply temperature - Alarm status; Modbus DI1088 | Read | ||
| BV | 1318 | Warn_MainCoilTOutOfRange.Active | Main coil water temperature out of range warning - Alarm status; Modbus DI1090 | Read | ||
| BV | 1319 | Al_SupplyAirFlwSwWarn.Active | Supply air flow warning - Alarm status; Modbus DI1091 | Read | ||
| BV | 1320 | Al_RetAirFlwSwWarn.Active | Return air flow warning - Alarm status; Modbus DI1092 | Read | ||
| BV | 1321 | Al_AirFlwSwWarn.Active | Air flow warning - Alarm status; Modbus DI1093 | Read | ||
| BV | 1322 | Warn_AFreezeWarn.Active | Antifreeze warning - Alarm status; Modbus DI1094 | Read | ||
| BV | 1323 | Al_HumAlrm.Active | Humidifier alarm - Alarm status; Modbus DI1095 | Read | ||
| BV | 1324 | Al_WrkHrs_Hum.Active | Warning - Humidifier maintenance required - Alarm status; Modbus DI1096 | Read | ||
| BV | 1325 | Al_WrkHrs_SupplyFan.Active | Warning - Supply fan maintenance required - Alarm status; Modbus DI1097 | Read | ||
| BV | 1326 | Al_WrkHrs_ReturnFan.Active | Warning - Return fan maintenance required - Alarm status; Modbus DI1098 | Read | ||
| BV | 1327 | Al_WrkHrs_ThrmlWheel.Active | Warning - Thermal wheel maintenance required - Alarm status; Modbus DI1099 | Read | ||
| BV | 1328 | Al_WrkHrs_DirtyFilt.Active | Warning - Filters maintenance required - Alarm status; Modbus DI1100 | Read | ||
| BV | 1329 | Al_DirtyFiltByDin.Active | Common - Dirty filters alarm - Alarm status; Modbus DI1101 | Read | ||
| BV | 1330 | Al_WrkHrs_Comp.Active | Warning - Compressor maintenance required - Alarm status; Modbus DI1102 | Read | ||
| BV | 1331 | Al_HiRatioP_BLDC.Active | Compressor envelope - High compression ratio - Alarm status; Modbus DI1103 | Read | ||
| BV | 1332 | Al_DscgHiP_BLDC.Active | Compressor envelope - High discharge pressure - Alarm status; Modbus DI1104 | Read | ||
| BV | 1333 | Al_HiCurr_BLDC.Active | Compressor envelope - High motor current - Alarm status; Modbus DI1105 | Read | ||
| BV | 1334 | Al_SuctHiP_BLDC.Active | Compressor envelope - High suction pressure - Alarm status; Modbus DI1106 | Read | ||
| BV | 1335 | Al_LowRatioP_BLDC.Active | Compressor envelope - Low compression ratio - Alarm status; Modbus DI1107 | Read | ||
| BV | 1336 | Al_LowDeltaP_BLDC.Active | Compressor envelope - Low differential pressure - Alarm status; Modbus DI1108 | Read | ||
| BV | 1337 | Al_LowDscgP_BLDC.Active | Compressor envelope - Low discharge pressure - Alarm status; Modbus DI1109 | Read | ||
| BV | 1338 | Al_LowSuctP_BLDC.Active | Compressor envelope - Low suction pressure - Alarm status; Modbus DI1110 | Read | ||
| BV | 1339 | Al_HiDscgTemp_BLDC.Active | Compressor envelope - High discharge temperature - Alarm status; Modbus DI1111 | Read | ||
| BV | 1340 | Al_LOP_EVD_Emb.Active | EVD - LOP - Alarm status; Modbus DI1112 | Read | ||
| BV | 1341 | Al_MOP_EVD_Emb.Active | EVD - MOP - Alarm status; Modbus DI1113 | Read | ||
| BV | 1342 | Al_HiCondTemp_EVD_Emb.Active | EVD - High condensing temperature - Alarm status; Modbus DI1114 | Read | ||
| BV | 1343 | Al_LowSuctTemp_EVD_Emb.Active | EVD - Low suction temperature - Alarm status; Modbus DI1115 | Read | ||
| BV | 1344 | Al_EmergClos_EVD_Emb.Active | EVD - Emergency closing - Alarm status; Modbus DI1116 | Read | ||
| BV | 1345 | Al_DisStartDp_BLDC.Active | BLDC - Delta pressure greater than the allowable at startup ...; Modbus DI1117 | Read | ||
| BV | 1346 | Al_ThTune_ClkBrd.Active | th-Tune clock not working - Alarm status; Modbus DI1118 | Read | ||
| BV | 1347 | Al_BMS_Offline.Active | BMS offline - Alarm status; Modbus DI1121 | Read | ||
| BV | 1348 | Al_Selftuning_EVD_Emb.Active | EVD - Selftuning alarm - Alarm status; Modbus DI1122 | Read | ||
| BV | 1349 | Al_Offline_Humisonic.Active | Humisonic - Offline - Alarm status; Modbus DI1123 | Read | ||
| BV | 1350 | Al_HiHum_Humisonic.Active | Humisonic - High humidity - Alarm status; Modbus DI1124 | Read | ||
| BV | 1351 | Al_LowHum_Humisonic.Active | Humisonic - Low humidity - Alarm status; Modbus DI1125 | Read | ||
| BV | 1352 | Al_NoProd_Humisonic.Active | Humisonic - No production - Alarm status; Modbus DI1126 | Read | ||
| BV | 1353 | Al_FaultyDrn_Humisonic.Active | Humisonic - Faulty drain - Alarm status; Modbus DI1127 | Read | ||
| BV | 1354 | Al_Wmissing_Humisonic.Active | Humisonic - Missing water - Alarm status; Modbus DI1128 | Read | ||
| BV | 1355 | Al_ExtSignal_Humisonic.Active | Humisonic - External signal not correctly connected - Alarm status; Modbus DI1129 | Read | ||
| BV | 1356 | Al_Functest_Humisonic.Active | Humisonic - Functional test not executed - Alarm status; Modbus DI1130 | Read | ||
| BV | 1357 | Al_Autotest_Humisonic.Active | Humisonic - Autotest failure - Alarm status; Modbus DI1131 | Read | ||
| BV | 1358 | Al_EEPROM_Err_Humisonic.Active | Humisonic - EEPROM error - Alarm status; Modbus DI1132 | Read | ||
| BV | 1359 | Al_Offline_EBM_SupplyFan.Active | EBM supply fan - Offline - Alarm status; Modbus DI1133 | Read | ||
| BV | 1360 | Al_Generic_EBM_SupplyFan.Active | EBM supply fan 1 - Generic alarm; Modbus DI1134 | Read | ||
| BV | 1385 | Al_Offline_EBM_RetFan.Active | EBM return fan - Offline - Alarm status; Modbus DI1159 | Read | ||
| BV | 1361 | Al_Offline_EBM_SupplyFan2.Active | EBM supply fan 2 - Offline; Modbus DI1135 | Read | ||
| BV | 1362 | Al_Generic_EBM_SupplyFan2.Active | EBM supply fan 2 - Generic alarm; Modbus DI1136 | Read | ||
| BV | 1363 | Al_Offline_EBM_SupplyFan3.Active | EBM supply fan 3 - Offline; Modbus DI1137 | Read | ||
| BV | 1364 | Al_Generic_EBM_SupplyFan3.Active | EBM supply fan 3 - Generic alarm; Modbus DI1138 | Read | ||
| BV | 1365 | Al_Offline_EBM_SupplyFan4.Active | EBM supply fan 4 - Offline; Modbus DI1139 | Read | ||
| BV | 1366 | Al_Generic_EBM_SupplyFan4.Active | EBM supply fan 4 - Generic alarm; Modbus DI1140 | Read | ||
| BV | 1367 | Al_NOT_USED_138.Active | Alarm NOT USED 138; Modbus DI1141 | Read | ||
| BV | 1368 | Al_NOT_USED_139.Active | Alarm NOT USED 139; Modbus DI1142 | Read | ||
| BV | 1369 | Al_NOT_USED_140.Active | Alarm NOT USED 140; Modbus DI1143 | Read | ||
| BV | 1370 | Al_NOT_USED_141.Active | Alarm NOT USED 141; Modbus DI1144 | Read | ||
| BV | 1371 | Al_NOT_USED_142.Active | Alarm NOT USED 142; Modbus DI1145 | Read | ||
| BV | 1372 | Al_NOT_USED_143.Active | Alarm NOT USED 143; Modbus DI1146 | Read | ||
| BV | 1373 | Al_NOT_USED_144.Active | Alarm NOT USED 144; Modbus DI1147 | Read | ||
| BV | 1374 | Al_NOT_USED_145.Active | Alarm NOT USED 145; Modbus DI1148 | Read | ||
| BV | 1375 | Al_NOT_USED_146.Active | Alarm NOT USED 146; Modbus DI1149 | Read | ||
| BV | 1376 | Al_NOT_USED_147.Active | Alarm NOT USED 147; Modbus DI1150 | Read | ||
| BV | 1377 | Al_NOT_USED_148.Active | Alarm NOT USED 148; Modbus DI1151 | Read | ||
| BV | 1378 | Al_NOT_USED_149.Active | Alarm NOT USED 149; Modbus DI1152 | Read | ||
| BV | 1379 | Al_NOT_USED_150.Active | Alarm NOT USED 150; Modbus DI1153 | Read | ||
| BV | 1380 | Al_NOT_USED_151.Active | Alarm NOT USED 151; Modbus DI1154 | Read | ||
| BV | 1381 | Al_NOT_USED_152.Active | Alarm NOT USED 152; Modbus DI1155 | Read | ||
| BV | 1382 | Al_NOT_USED_153.Active | Alarm NOT USED 153; Modbus DI1156 | Read | ||
| BV | 1383 | Al_NOT_USED_154.Active | Alarm NOT USED 154; Modbus DI1157 | Read | ||
| BV | 1384 | Al_NOT_USED_155.Active | Alarm NOT USED 155; Modbus DI1158 | Read | ||
| BV | 1386 | Al_Generic_EBM_RetFan.Active | EBM return fan 1 - Generic alarm; Modbus DI1160 | Read | ||
| BV | 1387 | Al_Offline_EBM_RetFan2.Active | EBM return fan 2 - Offline; Modbus DI1161 | Read | ||
| BV | 1388 | Al_Generic_EBM_RetFan2.Active | EBM return fan 2 - Generic alarm; Modbus DI1162 | Read | ||
| BV | 1389 | Al_Offline_EBM_RetFan3.Active | EBM return fan 3 - Offline; Modbus DI1163 | Read | ||
| BV | 1390 | Al_Generic_EBM_RetFan3.Active | EBM return fan 3 - Generic alarm; Modbus DI1164 | Read | ||
| BV | 1391 | Al_Offline_EBM_RetFan4.Active | EBM return fan 4 - Offline; Modbus DI1165 | Read | ||
| BV | 1392 | Al_Generic_EBM_RetFan4.Active | EBM return fan 4 - Generic alarm; Modbus DI1166 | Read | ||
| BV | 1393 | Al_NOT_USED_164.Active | Alarm NOT USED 164; Modbus DI1167 | Read | ||
| BV | 1394 | Al_NOT_USED_165.Active | Alarm NOT USED 165; Modbus DI1168 | Read | ||
| BV | 1395 | Al_NOT_USED_166.Active | Alarm NOT USED 166; Modbus DI1169 | Read | ||
| BV | 1396 | Al_NOT_USED_167.Active | Alarm NOT USED 167; Modbus DI1170 | Read | ||
| BV | 1397 | Al_NOT_USED_168.Active | Alarm NOT USED 168; Modbus DI1171 | Read | ||
| BV | 1398 | Al_NOT_USED_169.Active | Alarm NOT USED 169; Modbus DI1172 | Read | ||
| BV | 1399 | Al_NOT_USED_170.Active | Alarm NOT USED 170; Modbus DI1173 | Read | ||
| BV | 1400 | Al_NOT_USED_171.Active | Alarm NOT USED 171; Modbus DI1174 | Read | ||
| BV | 1401 | Al_NOT_USED_172.Active | Alarm NOT USED 172; Modbus DI1175 | Read | ||
| BV | 1402 | Al_NOT_USED_173.Active | Alarm NOT USED 173; Modbus DI1176 | Read | ||
| BV | 1403 | Al_NOT_USED_174.Active | Alarm NOT USED 174; Modbus DI1177 | Read | ||
| BV | 1404 | Al_NOT_USED_175.Active | Alarm NOT USED 175; Modbus DI1178 | Read | ||
| BV | 1405 | Al_NOT_USED_176.Active | Alarm NOT USED 176; Modbus DI1179 | Read | ||
| BV | 1406 | Al_NOT_USED_177.Active | Alarm NOT USED 177; Modbus DI1180 | Read | ||
| BV | 1407 | Al_NOT_USED_178.Active | Alarm NOT USED 178; Modbus DI1181 | Read | ||
| BV | 1408 | Al_NOT_USED_179.Active | Alarm NOT USED 179; Modbus DI1182 | Read | ||
| BV | 1409 | Al_NOT_USED_180.Active | Alarm NOT USED 180; Modbus DI1183 | Read | ||
| BV | 1410 | Al_NOT_USED_181.Active | Alarm NOT USED 181; Modbus DI1184 | Read | ||
| BV | 1411 | Al_WrkHrs_ModulHum.Active | Warning - Modulating humidifier maintenance required - Alarm status; Modbus DI1185 | Read | ||
| BV | 1412 | Al_RecoveryOvld.Active | Thermal wheel overload - Alarm status; Modbus DI1186 | Read | ||
| BV | 1413 | Al_Offline_ZA_SupplyFan.Active | ZA supply fan - Offline - Alarm status; Modbus DI1187 | Read | ||
| BV | 1414 | Al_Generic_ZA_SupplyFan.Active | ZA supply fan 1 - Generic alarm; Modbus DI1188 | Read | ||
| BV | 1415 | Al_Offline_ZA_SupplyFan2.Active | ZA supply fan 2 - Offline; Modbus DI1189 | Read | ||
| BV | 1416 | Al_Generic_ZA_SupplyFan2.Active | ZA supply fan 2 - Generic alarm; Modbus DI1190 | Read | ||
| BV | 1417 | Al_Offline_ZA_SupplyFan3.Active | ZA supply fan 3 - Offline; Modbus DI1191 | Read | ||
| BV | 1418 | Al_Generic_ZA_SupplyFan3.Active | ZA supply fan 3 - Generic alarm; Modbus DI1192 | Read | ||
| BV | 1419 | Al_Offline_ZA_SupplyFan4.Active | ZA supply fan 4 - Offline; Modbus DI1193 | Read | ||
| BV | 1420 | Al_Generic_ZA_SupplyFan4.Active | ZA supply fan 4 - Generic alarm; Modbus DI1194 | Read | ||
| BV | 1421 | Al_FwIncompatible_ZA_SupplyFan.Active | ZA supply fan 1 - Firmware incompatible; Modbus DI1195 | Read | ||
| BV | 1422 | Al_FwIncompatible_ZA_SupplyFan2.Active | ZA supply fan 2 - Firmware incompatible; Modbus DI1196 | Read | ||
| BV | 1423 | Al_FwIncompatible_ZA_SupplyFan3.Active | ZA supply fan 3 - Firmware incompatible; Modbus DI1197 | Read | ||
| BV | 1424 | Al_FwIncompatible_ZA_SupplyFan4.Active | ZA supply fan 4 - Firmware incompatible; Modbus DI1198 | Read | ||
| BV | 1426 | Al_Generic_ZA_RetFan.Active | ZA return fan 1 - Generic alarm; Modbus DI1200 | Read | ||
| BV | 1427 | Al_Offline_ZA_RetFan2.Active | ZA return fan 2 - Offline; Modbus DI1201 | Read | ||
| BV | 1428 | Al_Generic_ZA_RetFan2.Active | ZA return fan 2 - Generic alarm; Modbus DI1202 | Read | ||
| BV | 1429 | Al_Offline_ZA_RetFan3.Active | ZA return fan 3 - Offline; Modbus DI1203 | Read | ||
| BV | 1430 | Al_Generic_ZA_RetFan3.Active | ZA return fan 3 - Generic alarm; Modbus DI1204 | Read | ||
| BV | 1431 | Al_Offline_ZA_RetFan4.Active | ZA return fan 4 - Offline; Modbus DI1205 | Read | ||
| BV | 1432 | Al_Generic_ZA_RetFan4.Active | ZA return fan 4 - Generic alarm; Modbus DI1206 | Read | ||
| BV | 1433 | Al_FwIncompatible_ZA_RetFan.Active | ZA return fan 1 - Firmware incompatible; Modbus DI1207 | Read | ||
| BV | 1434 | Al_FwIncompatible_ZA_RetFan2.Active | ZA return fan 2 - Firmware incompatible; Modbus DI1208 | Read | ||
| BV | 1435 | Al_FwIncompatible_ZA_RetFan3.Active | ZA return fan 3 - Firmware incompatible; Modbus DI1209 | Read | ||
| BV | 1436 | Al_FwIncompatible_ZA_RetFan4.Active | ZA return fan 4 - Firmware incompatible; Modbus DI1210 | Read | ||
| BV | 1436 | Al_PeakCurrent_ZA_RetFan.Active | ZA return fan - Peak current - Alarm status; Modbus DI1210 | Read | ||
| BV | 1437 | Al_ErrCfgB2P.Active | IO - Configuration error - Alarm status; Modbus DI1211 | Read | ||
| BV | 1438 | Al_HighSupplyTemp.Active | High supply temperature - Alarm status; Modbus DI1212 | Read | ||
| BV | 1439 | Al_VDI_HygieneInspection_0_0.Active | Alarm VDI - Hygiene Inspection - Alarm status; Modbus DI1213 | Read | ||
| BV | 1440 | Al_VDI_OutdoorAirInlets_1_1.Active | Alarm VDI - Check for contamination, damage and corrosion - ...; Modbus DI1214 | Read | ||
| BV | 1441 | Al_VDI_Dehum_3_1.Active | Alarm VDI - Check for contamination, damage and corrosion - ...; Modbus DI1215 | Read | ||
| BV | 1442 | Al_VDI_Dehum_3_2.Active | Alarm VDI - Function check drain and syphon - Alarm status; Modbus DI1216 | Read | ||
| BV | 1443 | Al_VDI_Dehum_3_3.Active | Alarm VDI - Clean wet cooler, mist collector and condensate ...; Modbus DI1217 | Read | ||
| BV | 1444 | Al_VDI_AHUHousing_4_1.Active | Alarm VDI - Check for contamination, damage and corrosion on ...; Modbus DI1218 | Read | ||
| BV | 1445 | Al_VDI_AHUHousing_4_2.Active | Alarm VDI - Check for water precipitation - Alarm status; Modbus DI1219 | Read | ||
| BV | 1446 | Al_VDI_AHUHousing_4_3.Active | Alarm VDI - Check empty housings for contamination, damage, and ...; Modbus DI1220 | Read | ||
| BV | 1447 | Al_VDI_AirHumWithNoClearW_6_2_1.Active | Alarm VDI - Check for contamination, damage, microbial growth and ...; Modbus DI1221 | Read | ||
| BV | 1448 | Al_VDI_AirHumWithNoClearW_6_2_2.Active | Alarm VDI - Check condensate precipitation in the humidifier chamber ...; Modbus DI1222 | Read | ||
| BV | 1449 | Al_VDI_AirHumWithNoClearW_6_2_3.Active | Alarm VDI - Check vapour distribution system for deposit - ...; Modbus DI1223 | Read | ||
| BV | 1450 | Al_VDI_AirHumWithNoClearW_6_2_4.Active | Alarm VDI - Check spray nozzle for deposits - Alarm status; Modbus DI1224 | Read | ||
| BV | 1451 | Al_VDI_AirHumWithNoClearW_6_2_5.Active | Alarm VDI - Check drain - Alarm status; Modbus DI1225 | Read | ||
| BV | 1452 | Al_VDI_AirHumWithNoClearW_6_2_6.Active | Alarm VDI - Determine number of CFU in the humidifier ...; Modbus DI1226 | Read | ||
| BV | 1453 | Al_VDI_AirHumWithNoClearW_6_2_7.Active | Alarm VDI - Function check control valve - Alarm status; Modbus DI1227 | Read | ||
| BV | 1454 | Al_VDI_AirHumWithNoClearW_6_2_8.Active | Alarm VDI - Check humidity limiter - Alarm status; Modbus DI1228 | Read | ||
| BV | 1455 | Al_VDI_AirFilt_8_1.Active | Alarm VDI - Check for unacceptable contamination and damage (leakage) ...; Modbus DI1229 | Read | ||
| BV | 1456 | Al_VDI_AirFilt_8_2.Active | Alarm VDI - Check differential pressure - Alarm status; Modbus DI1230 | Read | ||
| BV | 1457 | Al_VDI_AirFilt_8_3.Active | Alarm VDI - Maximum interval until first filter stage is ...; Modbus DI1231 | Read | ||
| BV | 1458 | Al_VDI_AirFilt_8_4.Active | Alarm VDI - Maximum interval until second filter stage is ...; Modbus DI1232 | Read | ||
| BV | 1459 | Al_VDI_AirDuct_9_1.Active | Alarm VDI - Check accessible duct section for damage - ...; Modbus DI1233 | Read | ||
| BV | 1460 | Al_VDI_AirDuct_9_2.Active | Alarm VDI - Check two or three representative locations on ...; Modbus DI1234 | Read | ||
| BV | 1461 | Al_VDI_Silencers_11_1.Active | Alarm VDI - Check silencers for contamination. Damage, and corrosion ...; Modbus DI1235 | Read | ||
| BV | 1462 | Al_VDI_Fan_12_1.Active | Alarm VDI - Check for contamination, damage, and corrosion - ...; Modbus DI1236 | Read | ||
| BV | 1463 | Al_VDI_HeatExch_13_1.Active | Alarm VDI - Visual inspection of air-to-air plate or cross ...; Modbus DI1237 | Read | ||
| BV | 1464 | Al_VDI_HeatExch_13_2.Active | Alarm VDI - Visual inspection of air-to-air rotary heat exchanger ...; Modbus DI1238 | Read | ||
| BV | 1465 | Al_VDI_HeatExch_13_4.Active | Alarm VDI - Heaters: Check for contamination damage, corrosion and ...; Modbus DI1239 | Read | ||
| BV | 1466 | Al_VDI_HeatExch_13_5.Active | Alarm VDI - Coolers: Check tube bundles, mist collectors and ...; Modbus DI1240 | Read | ||
| BV | 1467 | Al_VDI_HeatExch_13_6.Active | Alarm VDI - Function-check drain and syphon - Alarm status; Modbus DI1241 | Read | ||
| BV | 1468 | Al_VDI_SupplyHum.Active | Alarm VDI - Supply humidity probe is needed - Alarm status; Modbus DI1242 | Read | ||
| BV | 1469 | Al_DoorSw.Active | Alarm - Door open - Alarm status; Modbus DI1243 | Read | ||
| BV | 1470 | Al_FireSmoke.Active | Alarm - Fire/Smoke - Alarm status; Modbus DI1244 | Read | ||
| BV | 1471 | Al_SrsAlrmByDin.Active | Serious alarm from digital input - Alarm status; Modbus DI1245 | Read | ||
| BV | 1472 | Al_GenericWarnByDin.Active | Generic warning from digital input - Alarm status; Modbus DI1246 | Read | ||
| BV | 1473 | Al_Sup1_DirtyFiltByDin.Active | Supply - Dirty filter alarm - Alarm status; Modbus DI1247 | Read | ||
| BV | 1474 | Al_Sup2_DirtyFiltByDin.Active | Supply 2 - Dirty filter alarm - Alarm status; Modbus DI1248 | Read | ||
| BV | 1475 | Al_Ret_DirtyFiltByDin.Active | Return - Dirty filter alarm - Alarm status; Modbus DI1249 | Read | ||
| BV | 1476 | Al_HEPA_Filt1.Active | HEPA Filter 1 alarm - Alarm status; Modbus DI1250 | Read | ||
| BV | 1477 | Al_HEPA_Filt2.Active | HEPA Filter 2 alarm - Alarm status; Modbus DI1251 | Read | ||
| BV | 1478 | Al_MainCoilPmp1_Ovld.Active | Main coil pump 1 overload - Alarm status; Modbus DI1252 | Read | ||
| BV | 1479 | Al_MainCoilPmp2_Ovld.Active | Main coil pump 2 overload - Alarm status; Modbus DI1253 | Read | ||
| BV | 1480 | Al_ReHeatCoilPmp1_Ovld.Active | Re heat coil pump 1 overload - Alarm status; Modbus DI1254 | Read | ||
| BV | 1481 | Al_ReHeatCoilPmp2_Ovld.Active | Re heat coil pump 2 overload - Alarm status; Modbus DI1255 | Read | ||
| BV | 1482 | Al_PreHeatCoilPmp1_Ovld.Active | Pre heat coil pump 1 overload - Alarm status; Modbus DI1256 | Read | ||
| BV | 1483 | Al_PreHeatCoilPmp2_Ovld.Active | Pre heat coil pump 2 overload - Alarm status; Modbus DI1257 | Read | ||
| BV | 1484 | Al_MainCoilFlwSw.Active | Main coil flow switch alarm - Alarm status; Modbus DI1258 | Read | ||
| BV | 1485 | Al_ReHeatCoilFlwSw.Active | Re heat coil flow switch alarm - Alarm status; Modbus DI1259 | Read | ||
| BV | 1486 | Al_PreHeatCoilFlwSw.Active | Pre heat coil flow switch alarm - Alarm status; Modbus DI1260 | Read | ||
| BV | 1487 | Al_RecoveryClogged.Active | Recovery clogged alarm - Alarm status; Modbus DI1261 | Read | ||
| BV | 1488 | Al_ReHeat_Ovld.Active | Re heat coil alarm - Alarm status; Modbus DI1262 | Read | ||
| BV | 1489 | Al_PreHeat_Ovld.Active | Pre heat coil alarm - Alarm status; Modbus DI1263 | Read | ||
| BV | 1490 | Al_uChiller_Alrm.Active | Alarm - uChiller - Alarm status; Modbus DI1264 | Read | ||
| BV | 1491 | Al_uChiller_Offline.Active | Alarm - uChiller offline - Alarm status; Modbus DI1265 | Read | ||
| BV | 1492 | Al_WrkHrs_MainCoilPmp1.Active | Warning - Main coil pump 1 maintenance required - Alarm status; Modbus DI1266 | Read | ||
| BV | 1493 | Al_WrkHrs_MainCoilPmp2.Active | Warning - Main coil pump 2 maintenance required - Alarm status; Modbus DI1267 | Read | ||
| BV | 1494 | Al_WrkHrs_MainCoilAout.Active | Warning - Main coil analog output maintenance required - Alarm status; Modbus DI1268 | Read | ||
| BV | 1495 | Al_WrkHrs_MainCoilStep1.Active | Warning - Main coil step 1 maintenance required - Alarm status; Modbus DI1269 | Read | ||
| BV | 1496 | Al_WrkHrs_MainCoilStep2.Active | Warning - Main coil step 2 maintenance required - Alarm status; Modbus DI1270 | Read | ||
| BV | 1497 | Al_WrkHrs_MainCoilStep3.Active | Warning - Main coil step 3 maintenance required - Alarm status; Modbus DI1271 | Read | ||
| BV | 1498 | Al_WrkHrs_MainCoilStep4.Active | Warning - Main coil step 4 maintenance required - Alarm status; Modbus DI1272 | Read | ||
| BV | 1499 | Al_WrkHrs_PreHeatCoilPmp1.Active | Warning - Pre-heating coil pump 1 maintenance required - Alarm status; Modbus DI1273 | Read | ||
| BV | 1500 | Al_WrkHrs_PreHeatCoilPmp2.Active | Warning - Pre-heating coil pump 2 maintenance required - Alarm status; Modbus DI1274 | Read | ||
| BV | 1501 | Al_WrkHrs_PreHeatCoilAout.Active | Warning - Pre-heating coil analog output maintenance required - Alarm status; Modbus DI1275 | Read | ||
| BV | 1502 | Al_WrkHrs_PreHeatCoilStep1.Active | Warning - Pre-heating coil step 1 maintenance required - Alarm status; Modbus DI1276 | Read | ||
| BV | 1503 | Al_WrkHrs_PreHeatCoilStep2.Active | Warning - Pre-heating coil step 2 maintenance required - Alarm status; Modbus DI1277 | Read | ||
| BV | 1504 | Al_WrkHrs_PreHeatCoilStep3.Active | Warning - Pre-heating coil step 3 maintenance required - Alarm status; Modbus DI1278 | Read | ||
| BV | 1505 | Al_WrkHrs_PreHeatCoilStep4.Active | Warning - Pre-heating coil step 4 maintenance required - Alarm status; Modbus DI1279 | Read | ||
| BV | 1506 | Al_WrkHrs_ReHeatCoilStep4.Active | Warning - Re-heating coil step 4 maintenance required - Alarm status; Modbus DI1280 | Read | ||
| BV | 1507 | Al_WrkHrs_ReHeatCoilPmp1.Active | Warning - Re-heating coil pump 1 maintenance required - Alarm status; Modbus DI1281 | Read | ||
| BV | 1508 | Al_WrkHrs_ReHeatCoilPmp2.Active | Warning - Re-heating coil pump 2 maintenance required - Alarm status; Modbus DI1282 | Read | ||
| BV | 1509 | Al_WrkHrs_ReHeatCoilAout.Active | Warning - Re-heating coil analog output maintenance required - Alarm status; Modbus DI1283 | Read | ||
| BV | 1510 | Al_WrkHrs_ReHeatCoilStep1.Active | Warning - Re-heating coil step 1 maintenance required - Alarm status; Modbus DI1284 | Read | ||
| BV | 1511 | Al_WrkHrs_ReHeatCoilStep2.Active | Warning - Re-heating coil step 2 maintenance required - Alarm status; Modbus DI1285 | Read | ||
| BV | 1512 | Al_WrkHrs_ReHeatCoilStep3.Active | Warning - Re-heating coil step 3 maintenance required - Alarm status; Modbus DI1286 | Read | ||
| BV | 1513 | Al_WrkHrs_AuxDout.Active | Warning - Auxiliary digital output maintenance required - Alarm status; Modbus DI1287 | Read | ||
| BV | 1514 | Al_WrkHrs_AuxAout.Active | Warning - Auxiliary analogue output maintenance required - Alarm status; Modbus DI1288 | Read | ||
| BV | 1515 | Al_WrkHrs_IEC.Active | Warning - IEC maintenance required - Alarm status; Modbus DI1289 | Read | ||
| BV | 1516 | Al_WrkHrs_Unit.Active | Warning - Unit maintenance required - Alarm status; Modbus DI1290 | Read | ||
| BV | 1517 | Al_Humifog.Active | Alarm - Humifog alarms present - Alarm status; Modbus DI1291 | Read | ||
| BV | 1518 | Al_IEC_Humifog.Active | Alarm - IEC Humifog alarms present - Alarm status; Modbus DI1292 | Read | ||
| BV | 1519 | Al_Humifog_Offline.Active | Alarm - Humifog offline - Alarm status; Modbus DI1293 | Read | ||
| BV | 1520 | Al_IEC_Humifog_Offline.Active | Alarm - IEC Humifog offline - Alarm status; Modbus DI1294 | Read | ||
| BV | 1522 | Al_EEV_HWCompatErr.Active | Alarm - EEV Hardware compatibility error - Alarm status; Modbus DI1296 | Read | ||
| BV | 1523 | Al_PGDx_Offline.Active | Warning - pGDx Offline - Alarm status; Modbus DI1297 | Read | ||
| BV | 3934 | Al_cpCOe_1_Offline.Active | Alarm - c.pCOe n.1 Offline - Alarm status; Modbus DI1298 | Read | ||
| BV | 3935 | Al_cpCOe_2_Offline.Active | Alarm - c.pCOe n.2 Offline - Alarm status; Modbus DI1299 | Read | ||
| BV | 3936 | Al_cpCOe_3_Offline.Active | Alarm - c.pCOe n.3 Offline - Alarm status; Modbus DI1300 | Read | ||
| BV | 3937 | Al_cpCOe_4_Offline.Active | Alarm - c.pCOe n.4 Offline - Alarm status; Modbus DI1301 | Read | ||
| BV | 3932 | Warn_PreHeatCoilTOutOfRange.Active | Preheating coil water temperature out of range warning - Alarm status; Modbus DI1302 | Read | ||
| BV | 3933 | Warn_ReHeatCoilTOutOfRange.Active | Reheating coil water temperature out of range warning - Alarm status; Modbus DI1303 | Read | ||
| BV | 3941 | MainCoil_FloatVlv | Main Coil type: floating valve; Modbus DI1304 | Read | ||
| BV | 3942 | Coils.PreHeatCoil_FloatVlv | PreHeat coil type: floating valve; Modbus DI1305 | Read | ||
| BV | 3943 | Coils.ReHeatCoil_FloatVlv | ReHeat coil type: floating valve; Modbus DI1306 | Read | ||
| BV | 3944 | MainVlv_ReadyToGo | Main Coil: floating valve ready to go( FALSE: Pre-positioning in ...; Modbus DI1307 | Read | ||
| BV | 3945 | PreHeatVlv_ReadyToGo | PreHeat Coil: floating valve ready to go( FALSE: Pre-positioning in ...; Modbus DI1308 | Read | ||
| BV | 3946 | ReHeatVlv_ReadyToGo | ReHeat Coil: floating valve ready to go( FALSE: Pre-positioning in ...; Modbus DI1309 | Read | ||
| BV | 3951 | AirQuality_PM10.Alrm_R | Air quality: PM 10 - Alarm probe broken or disconnected; Modbus DI1310 | Read | ||
| BV | 3981 | AirQuality_PM10.Configured_R | Air quality: PM 10 - Configured; Modbus DI1311 | Read | ||
| BV | 3982 | AirQuality_PM10.Enable_W | Air quality: PM 10 - Enable input; Modbus DI1312 | Read | ||
| BV | 3986 | AirQuality_PM10.PrbOk_R | Air quality: PM 10 - Probe working correctly; Modbus DI1313 | Read | ||
| BV | 3990 | AirQuality_PM25.Alrm_R | Air quality: PM 2.5 - Alarm probe broken or disconnected; Modbus DI1314 | Read | ||
| BV | 3995 | AirQuality_PM25.Configured_R | Air quality: PM 2.5 - Configured; Modbus DI1315 | Read | ||
| BV | 3996 | AirQuality_PM25.Enable_W | Air quality: PM 2.5 - Enable input; Modbus DI1316 | Read | ||
| BV | 4000 | AirQuality_PM25.PrbOk_R | Air quality: PM 2.5 - Probe working correctly; Modbus DI1317 | Read | ||
| BV | 4007 | SanificationDevice.Val_W | Sanification device; Modbus DI1318 | Read | ||
| BV | 4008 | SanificationDevice.Val_Hw_R | Sanification device - Hardware value writes from board; Modbus DI1319 | Read | ||
| BV | 4012 | SanificationDevice.Enable_W | Sanification device - Enable output; Modbus DI1320 | Read | ||
| BV | 4013 | SanificationDevice.Configured_R | Sanification device - Configurated; Modbus DI1321 | Read | ||
| BV | 3968 | Al_AirQuality_PM10.Active | PM10 probe alarm - Alarm status; Modbus DI1322 | Read | ||
| BV | 3969 | Al_AirQuality_PM25.Active | PM2.5 probe alarm - Alarm status; Modbus DI1323 | Read | ||
| BV | 3958 | Sanification.SanificationDevice_IO_CfgWarn | Modbus DI1324 | Read | ||
| BV | 3960 | Regulation.QualityAirDevNotSel | Modbus DI1325 | Read | ||
| BV | 3970 | Al_SanificationWarn.Active | Alarm - Sanification device - Alarm status; Modbus DI1326 | Read | ||
| BV | 3971 | Al_WrkHrs_SanificationDevice.Active | Warning - Sanification device maintenance required - Alarm status; Modbus DI1327 | Read | ||
| BV | 4038 | PurgeOn | Purge is on; Modbus DI1328 | Read | ||
| BV | 4039 | SanificationDeviceOvld.Val_Hw_R | Sanification deivce overload switch - Value reads from board; Modbus DI1329 | Read | ||
| BV | 4040 | SanificationDeviceOvld.Configured_R | Sanification deivce overload switch - Configured; Modbus DI1330 | Read | ||
| BV | 4041 | SanificationDeviceOvld.Val_R | Sanification deivce overload switch; Modbus DI1331 | Read | ||
| BV | 4042 | FC_Act | Freecooling activated; Modbus DI1332 | Read | ||
| BV | 4043 | FH_Act | Freeheating activated; Modbus DI1333 | Read | ||
| BV | 4071 | Al_WrkHrs_SupplyFan_2.Active | Warning - Supply fan 2 maintenance required; Modbus DI1334 | Read | ||
| BV | 4072 | Al_WrkHrs_SupplyFan_3.Active | Warning - Supply fan 3 maintenance required; Modbus DI1335 | Read | ||
| BV | 4073 | Al_WrkHrs_SupplyFan_4.Active | Warning - Supply fan 4 maintenance required; Modbus DI1336 | Read | ||
| BV | 4074 | Al_WrkHrs_ReturnFan_2.Active | Warning - Return 2 fan maintenance required; Modbus DI1337 | Read | ||
| BV | 4075 | Al_WrkHrs_ReturnFan_3.Active | Warning - Return 3 fan maintenance required; Modbus DI1338 | Read | ||
| BV | 4076 | Al_WrkHrs_ReturnFan_4.Active | Warning - Return 4 fan maintenance required; Modbus DI1339 | Read | ||
| BV | 4286 | SupplyFan_FireSmokeAlrm_Act | Supply Fans active during Fire/Smoke alarm; Modbus DI1340 | Read | ||
| BV | 4287 | RetFan_FireSmokeAlrm_Act | Return Fans active during Fire/Smoke alarm; Modbus DI1341 | Read | ||
| BV | 4330 | Al_SupplyFanInv.Active | Alarm - Supply fan inverter feedback - Alarm status; Modbus DI1342 | Read | ||
| BV | 4331 | Al_RetFanInv.Active | Alarm - Return fan inverter feedback - Alarm status; Modbus DI1343 | Read | ||
| BV | 4332 | Al_SupplyDampSw.Active | Alarm - Supply damper feedback - Alarm status; Modbus DI1344 | Read | ||
| BV | 4333 | Al_RetDampSw.Active | Alarm - Return damper feedback - Alarm status; Modbus DI1345 | Read | ||
| BV | 4334 | Al_FreshAirDampSw.Active | Alarm - Fresh air damper feedback - Alarm status; Modbus DI1346 | Read | ||
| BV | 4335 | Al_ExhAirDampSw.Active | Alarm - Exhaust air damper feedback - Alarm status; Modbus DI1347 | Read | ||
| BV | 4336 | Al_MixAirDampSw.Active | Alarm - Mixing air damper feedback - Alarm status; Modbus DI1348 | Read | ||
| BV | 4337 | Al_HumiSteam_Offline.Active | HumiSteam - Offline alarm - Alarm status; Modbus DI1349 | Read | ||
| BV | 4338 | Al_HumiSteam_Generic.Active | HumiSteam - Generic alarm - Alarm status; Modbus DI1350 | Read | ||
| BV | 4362 | SummerWinter | Summer/Winter mode (FALSE:Summer, TRUE:Winter); Modbus DI1351 | Read | ||
| BV | 4363 | MainCoil_CoolHeat | Main coil cooling/heating; Modbus DI1352 | Read | ||
| BV | 4364 | MainCoilCoolHeat_Din.Configured_R | Main coil cool/heat - digital input - Configured; Modbus DI1353 | Read | ||
| BV | 4365 | MainCoilCoolHeat_Din.Enable_W | Main coil cool/heat - digital input - Enable input; Modbus DI1354 | Read | ||
| BV | 4366 | MainCoilCoolHeat_Din.Val_R | Main coil cool/heat - digital input; Modbus DI1355 | Read | ||
| BV | 4368 | HumDehum_Mode | Humidification/Dehumidification (FALSE: humidification; TRUE: dehumidification); Modbus DI1356 | Read | ||
| BV | 4377 | GenericAin1.Enable_W | Generic Ain1 - Enable input; Modbus DI1357 | Read | ||
| BV | 4378 | GenericAin1.Configured_R | Generic Ain1 - Configured; Modbus DI1358 | Read | ||
| BV | 4379 | GenericAin1.PrbOk_R | Generic Ain1 - Probe working correctly; Modbus DI1359 | Read | ||
| BV | 4380 | GenericAin1.Alrm_R | Generic Ain1 - Alarm probe broken or disconnected; Modbus DI1360 | Read | ||
| BV | 4391 | GenericAin2.Enable_W | Generic Ain2 - Enable input; Modbus DI1361 | Read | ||
| BV | 4392 | GenericAin2.Configured_R | Generic Ain2 - Configured; Modbus DI1362 | Read | ||
| BV | 4393 | GenericAin2.PrbOk_R | Generic Ain2 - Probe working correctly; Modbus DI1363 | Read | ||
| BV | 4394 | GenericAin2.Alrm_R | Generic Ain2 - Alarm probe broken or disconnected; Modbus DI1364 | Read | ||
| BV | 4405 | GenericAin3.Enable_W | Generic Ain3 - Enable input; Modbus DI1365 | Read | ||
| BV | 4406 | GenericAin3.Configured_R | Generic Ain3 - Configured; Modbus DI1366 | Read | ||
| BV | 4407 | GenericAin3.PrbOk_R | Generic Ain3 - Probe working correctly; Modbus DI1367 | Read | ||
| BV | 4408 | GenericAin3.Alrm_R | Generic Ain3 - Alarm probe broken or disconnected; Modbus DI1368 | Read | ||
| BV | 4419 | GenericAin4.Enable_W | Generic Ain4 - Enable input; Modbus DI1369 | Read | ||
| BV | 4420 | GenericAin4.Configured_R | Generic Ain4 - Configured; Modbus DI1370 | Read | ||
| BV | 4421 | GenericAin4.PrbOk_R | Generic Ain4 - Probe working correctly; Modbus DI1371 | Read | ||
| BV | 4422 | GenericAin4.Alrm_R | Generic Ain4 - Alarm probe broken or disconnected; Modbus DI1372 | Read | ||
| BV | 4433 | GenericAin5.Enable_W | Generic Ain5 - Enable input; Modbus DI1373 | Read | ||
| BV | 4434 | GenericAin5.Configured_R | Generic Ain5 - Configured; Modbus DI1374 | Read | ||
| BV | 4435 | GenericAin5.PrbOk_R | Generic Ain5 - Probe working correctly; Modbus DI1375 | Read | ||
| BV | 4436 | GenericAin5.Alrm_R | Generic Ain5 - Alarm probe broken or disconnected; Modbus DI1376 | Read | ||
| BV | 4448 | GenericDin1.Val_Hw_R | Generic Din1 - digital input - Value reads from board; Modbus DI1377 | Read | ||
| BV | 4449 | GenericDin1.Enable_W | Generic Din1 - digital input - Enable input; Modbus DI1378 | Read | ||
| BV | 4450 | GenericDin1.Configured_R | Generic Din1 - digital input - Configured; Modbus DI1379 | Read | ||
| BV | 4451 | GenericDin1.Val_R | Generic Din1 - digital input; Modbus DI1380 | Read | ||
| BV | 4455 | GenericDin2.Val_Hw_R | Generic Din2 - digital input - Value reads from board; Modbus DI1381 | Read | ||
| BV | 4456 | GenericDin2.Enable_W | Generic Din2 - digital input - Enable input; Modbus DI1382 | Read | ||
| BV | 4457 | GenericDin2.Configured_R | Generic Din2 - digital input - Configured; Modbus DI1383 | Read | ||
| BV | 4458 | GenericDin2.Val_R | Generic Din2 - digital input; Modbus DI1384 | Read | ||
| BV | 4462 | GenericDin3.Val_Hw_R | Generic Din3 - digital input - Value reads from board; Modbus DI1385 | Read | ||
| BV | 4463 | GenericDin3.Enable_W | Generic Din3 - digital input - Enable input; Modbus DI1386 | Read | ||
| BV | 4464 | GenericDin3.Configured_R | Generic Din3 - digital input - Configured; Modbus DI1387 | Read | ||
| BV | 4465 | GenericDin3.Val_R | Generic Din3 - digital input; Modbus DI1388 | Read | ||
| BV | 4469 | GenericDin4.Val_Hw_R | Generic Din4 - digital input - Value reads from board; Modbus DI1389 | Read | ||
| BV | 4470 | GenericDin4.Enable_W | Generic Din4 - digital input - Enable input; Modbus DI1390 | Read | ||
| BV | 4471 | GenericDin4.Configured_R | Generic Din4 - digital input - Configured; Modbus DI1391 | Read | ||
| BV | 4472 | GenericDin4.Val_R | Generic Din4 - digital input; Modbus DI1392 | Read | ||
| BV | 4476 | GenericDin5.Val_Hw_R | Generic Din5 - digital input - Value reads from board; Modbus DI1393 | Read | ||
| BV | 4477 | GenericDin5.Enable_W | Generic Din5 - digital input - Enable input; Modbus DI1394 | Read | ||
| BV | 4478 | GenericDin5.Configured_R | Generic Din5 - digital input - Configured; Modbus DI1395 | Read | ||
| BV | 4479 | GenericDin5.Val_R | Generic Din5 - digital input; Modbus DI1396 | Read | ||
| BV | 4487 | Al_GenericAin1.Active | Generic Ain1 probe alarm - Alarm status; Modbus DI1397 | Read | ||
| BV | 4488 | Al_GenericAin2.Active | Generic Ain2 probe alarm - Alarm status; Modbus DI1398 | Read | ||
| BV | 4489 | Al_GenericAin3.Active | Generic Ain3 probe alarm - Alarm status; Modbus DI1399 | Read | ||
| BV | 4490 | Al_GenericAin4.Active | Generic Ain4 probe alarm - Alarm status; Modbus DI1400 | Read | ||
| BV | 4491 | Al_GenericAin5.Active | Generic Ain5 probe alarm - Alarm status; Modbus DI1401 | Read | ||
| BV | 4492 | Al_GenericDin1.Active | Alarm - Generic Din 1 - Alarm status; Modbus DI1402 | Read | ||
| BV | 4493 | Al_GenericDin2.Active | Alarm - Generic Din 2 - Alarm status; Modbus DI1403 | Read | ||
| BV | 4494 | Al_GenericDin3.Active | Alarm - Generic Din 3 - Alarm status; Modbus DI1404 | Read | ||
| BV | 4495 | Al_GenericDin4.Active | Alarm - Generic Din 4 - Alarm status; Modbus DI1405 | Read | ||
| BV | 4496 | Al_GenericDin5.Active | Alarm - Generic Din 5 - Alarm status; Modbus DI1406 | Read | ||
| BV | 4517 | OA_Vlv_Open.Val_Hw_R | Outdoor air pre-treatment floating valve open - Hardware value writes ...; Modbus DI1407 | Read | ||
| BV | 4518 | OA_Vlv_Open.Val_W | Outdoor air pre-treatment floating valve open; Modbus DI1408 | Read | ||
| BV | 4519 | OA_Vlv_Open.Enable_W | Outdoor air pre-treatment floating valve open - Enable output; Modbus DI1409 | Read | ||
| BV | 4520 | OA_Vlv_Open.Configured_R | Outdoor air pre-treatment floating valve open - Configurated; Modbus DI1410 | Read | ||
| BV | 4521 | OA_Vlv_Close.Val_Hw_R | Outdoor air pre-treatment floating valve close - Hardware value writes ...; Modbus DI1411 | Read | ||
| BV | 4522 | OA_Vlv_Close.Val_W | Outdoor air pre-treatment floating valve close; Modbus DI1412 | Read | ||
| BV | 4523 | OA_Vlv_Close.Enable_W | Outdoor air pre-treatment floating valve close - Enable output; Modbus DI1413 | Read | ||
| BV | 4524 | OA_Vlv_Close.Configured_R | Outdoor air pre-treatment floating valve close - Configurated; Modbus DI1414 | Read | ||
| BV | 4525 | OA_Coil_Enabled | Enable outdoor air pre-treatment coil; Modbus DI1415 | Read | ||
| BV | 4526 | Al_WrkHrs_OA_CoilAout.Active | Warning - Outdoor air pre-treatment coil analog output maintenance required ...; Modbus DI1416 | Read | ||
| BV | 4527 | Al_WrkHrs_OA_CoilStep1.Active | Warning - Outdoor air pre-treatment coil step 1 maintenance required ...; Modbus DI1417 | Read | ||
| BV | 4528 | Al_WrkHrs_OA_CoilStep2.Active | Warning - Outdoor air pre-treatment coil step 2 maintenance required ...; Modbus DI1418 | Read | ||
| BV | 4529 | Al_WrkHrs_OA_CoilStep3.Active | Warning - Outdoor air pre-treatment coil step 3 maintenance required ...; Modbus DI1419 | Read | ||
| BV | 4530 | Al_WrkHrs_OA_CoilStep4.Active | Warning - Outdoor air pre-treatment coil step 4 maintenance required ...; Modbus DI1420 | Read | ||
| BV | 4531 | Warn_OA_CoilTOutOfRange.Active | Outdoor air pre-treatment coil water temperature out of range warning ...; Modbus DI1421 | Read | ||
| BV | 4532 | Coils.OA_Coil_FloatVlv | Outdoor air pre-treatment coil type: floating valve; Modbus DI1422 | Read | ||
| BV | 4533 | OA_Vlv_ReadyToGo | Outdoor air pre-treatment Coil: floating valve ready to go( FALSE: ...; Modbus DI1423 | Read | ||
| PIV | 1524 | Scheduler_OnOffUnit.BMS_UnitProfile | BMS unit profile; Modbus HR001 | Write | ||
| PIV | 1525 | Scheduler_Cfg.Prg[0].Event[0].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR002 | Write | ||
| PIV | 1526 | Scheduler_Cfg.Prg[0].Event[0].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR003 | Write | ||
| PIV | 1527 | Scheduler_Cfg.Prg[0].Event[0].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR004 | Write | ||
| PIV | 1528 | Scheduler_Cfg.Prg[0].Event[1].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR005 | Write | ||
| PIV | 1529 | Scheduler_Cfg.Prg[0].Event[1].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR006 | Write | ||
| PIV | 1530 | Scheduler_Cfg.Prg[0].Event[1].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR007 | Write | ||
| PIV | 1531 | Scheduler_Cfg.Prg[0].Event[2].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR008 | Write | ||
| PIV | 1532 | Scheduler_Cfg.Prg[0].Event[2].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR009 | Write | ||
| PIV | 1533 | Scheduler_Cfg.Prg[0].Event[2].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR010 | Write | ||
| PIV | 1534 | Scheduler_Cfg.Prg[0].Event[3].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR011 | Write | ||
| PIV | 1535 | Scheduler_Cfg.Prg[0].Event[3].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR012 | Write | ||
| PIV | 1536 | Scheduler_Cfg.Prg[0].Event[3].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR013 | Write | ||
| PIV | 1537 | Scheduler_Cfg.Prg[0].Event[4].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR014 | Write | ||
| PIV | 1538 | Scheduler_Cfg.Prg[0].Event[4].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR015 | Write | ||
| PIV | 1539 | Scheduler_Cfg.Prg[0].Event[4].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR016 | Write | ||
| PIV | 1540 | Scheduler_Cfg.Prg[0].Event[5].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR017 | Write | ||
| PIV | 1541 | Scheduler_Cfg.Prg[0].Event[5].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR018 | Write | ||
| PIV | 1542 | Scheduler_Cfg.Prg[0].Event[5].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR019 | Write | ||
| PIV | 1543 | Scheduler_Cfg.Prg[0].Event[6].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR020 | Write | ||
| PIV | 1544 | Scheduler_Cfg.Prg[0].Event[6].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR021 | Write | ||
| PIV | 1545 | Scheduler_Cfg.Prg[0].Event[6].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR022 | Write | ||
| PIV | 1546 | Scheduler_Cfg.Prg[0].Event[7].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR023 | Write | ||
| PIV | 1547 | Scheduler_Cfg.Prg[0].Event[7].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR024 | Write | ||
| PIV | 1548 | Scheduler_Cfg.Prg[0].Event[7].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR025 | Write | ||
| PIV | 1549 | Scheduler_Cfg.Prg[0].Event[8].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR026 | Write | ||
| PIV | 1550 | Scheduler_Cfg.Prg[0].Event[8].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR027 | Write | ||
| PIV | 1551 | Scheduler_Cfg.Prg[0].Event[8].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR028 | Write | ||
| PIV | 1552 | Scheduler_Cfg.Prg[0].Event[9].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR029 | Write | ||
| PIV | 1553 | Scheduler_Cfg.Prg[0].Event[9].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR030 | Write | ||
| PIV | 1554 | Scheduler_Cfg.Prg[0].Event[9].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR031 | Write | ||
| PIV | 1555 | Scheduler_Cfg.Prg[1].Event[0].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR032 | Write | ||
| PIV | 1556 | Scheduler_Cfg.Prg[1].Event[0].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR033 | Write | ||
| PIV | 1557 | Scheduler_Cfg.Prg[1].Event[0].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR034 | Write | ||
| PIV | 1558 | Scheduler_Cfg.Prg[1].Event[1].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR035 | Write | ||
| PIV | 1559 | Scheduler_Cfg.Prg[1].Event[1].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR036 | Write | ||
| PIV | 1560 | Scheduler_Cfg.Prg[1].Event[1].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR037 | Write | ||
| PIV | 1561 | Scheduler_Cfg.Prg[1].Event[2].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR038 | Write | ||
| PIV | 1562 | Scheduler_Cfg.Prg[1].Event[2].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR039 | Write | ||
| PIV | 1563 | Scheduler_Cfg.Prg[1].Event[2].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR040 | Write | ||
| PIV | 1564 | Scheduler_Cfg.Prg[1].Event[3].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR041 | Write | ||
| PIV | 1565 | Scheduler_Cfg.Prg[1].Event[3].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR042 | Write | ||
| PIV | 1566 | Scheduler_Cfg.Prg[1].Event[3].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR043 | Write | ||
| PIV | 1567 | Scheduler_Cfg.Prg[1].Event[4].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR044 | Write | ||
| PIV | 1568 | Scheduler_Cfg.Prg[1].Event[4].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR045 | Write | ||
| PIV | 1569 | Scheduler_Cfg.Prg[1].Event[4].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Eco-; Modbus HR046 | Write | ||
| PIV | 1570 | Scheduler_Cfg.Prg[1].Event[5].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR047 | Write | ||
| PIV | 1571 | Scheduler_Cfg.Prg[1].Event[5].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR048 | Write | ||
| PIV | 1572 | Scheduler_Cfg.Prg[1].Event[5].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR049 | Write | ||
| PIV | 1573 | Scheduler_Cfg.Prg[1].Event[6].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR050 | Write | ||
| PIV | 1574 | Scheduler_Cfg.Prg[1].Event[6].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR051 | Write | ||
| PIV | 1575 | Scheduler_Cfg.Prg[1].Event[6].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR052 | Write | ||
| PIV | 1576 | Scheduler_Cfg.Prg[1].Event[7].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR053 | Write | ||
| PIV | 1577 | Scheduler_Cfg.Prg[1].Event[7].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR054 | Write | ||
| PIV | 1578 | Scheduler_Cfg.Prg[1].Event[7].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR055 | Write | ||
| PIV | 1579 | Scheduler_Cfg.Prg[1].Event[8].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR056 | Write | ||
| PIV | 1580 | Scheduler_Cfg.Prg[1].Event[8].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR057 | Write | ||
| PIV | 1581 | Scheduler_Cfg.Prg[1].Event[8].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR058 | Write | ||
| PIV | 1582 | Scheduler_Cfg.Prg[1].Event[9].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR059 | Write | ||
| PIV | 1583 | Scheduler_Cfg.Prg[1].Event[9].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR060 | Write | ||
| PIV | 1584 | Scheduler_Cfg.Prg[1].Event[9].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR061 | Write | ||
| PIV | 1585 | Scheduler_Cfg.Prg[2].Event[0].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR062 | Write | ||
| PIV | 1586 | Scheduler_Cfg.Prg[2].Event[0].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR063 | Write | ||
| PIV | 1587 | Scheduler_Cfg.Prg[2].Event[0].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR064 | Write | ||
| PIV | 1588 | Scheduler_Cfg.Prg[2].Event[1].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR065 | Write | ||
| PIV | 1589 | Scheduler_Cfg.Prg[2].Event[1].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR066 | Write | ||
| PIV | 1590 | Scheduler_Cfg.Prg[2].Event[1].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR067 | Write | ||
| PIV | 1591 | Scheduler_Cfg.Prg[2].Event[2].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR068 | Write | ||
| PIV | 1592 | Scheduler_Cfg.Prg[2].Event[2].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR069 | Write | ||
| PIV | 1593 | Scheduler_Cfg.Prg[2].Event[2].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR070 | Write | ||
| PIV | 1594 | Scheduler_Cfg.Prg[2].Event[3].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR071 | Write | ||
| PIV | 1595 | Scheduler_Cfg.Prg[2].Event[3].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR072 | Write | ||
| PIV | 1596 | Scheduler_Cfg.Prg[2].Event[3].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR073 | Write | ||
| PIV | 1597 | Scheduler_Cfg.Prg[2].Event[4].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR074 | Write | ||
| PIV | 1598 | Scheduler_Cfg.Prg[2].Event[4].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR075 | Write | ||
| PIV | 1599 | Scheduler_Cfg.Prg[2].Event[4].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR076 | Write | ||
| PIV | 1600 | Scheduler_Cfg.Prg[2].Event[5].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR077 | Write | ||
| PIV | 1601 | Scheduler_Cfg.Prg[2].Event[5].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR078 | Write | ||
| PIV | 1602 | Scheduler_Cfg.Prg[2].Event[5].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR079 | Write | ||
| PIV | 1603 | Scheduler_Cfg.Prg[2].Event[6].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR080 | Write | ||
| PIV | 1604 | Scheduler_Cfg.Prg[2].Event[6].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR081 | Write | ||
| PIV | 1605 | Scheduler_Cfg.Prg[2].Event[6].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR082 | Write | ||
| PIV | 1606 | Scheduler_Cfg.Prg[2].Event[7].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR083 | Write | ||
| PIV | 1607 | Scheduler_Cfg.Prg[2].Event[7].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR084 | Write | ||
| PIV | 1608 | Scheduler_Cfg.Prg[2].Event[7].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR085 | Write | ||
| PIV | 1609 | Scheduler_Cfg.Prg[2].Event[8].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR086 | Write | ||
| PIV | 1610 | Scheduler_Cfg.Prg[2].Event[8].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR087 | Write | ||
| PIV | 1611 | Scheduler_Cfg.Prg[2].Event[8].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR088 | Write | ||
| PIV | 1612 | Scheduler_Cfg.Prg[2].Event[9].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR089 | Write | ||
| PIV | 1613 | Scheduler_Cfg.Prg[2].Event[9].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR090 | Write | ||
| PIV | 1614 | Scheduler_Cfg.Prg[2].Event[9].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR091 | Write | ||
| PIV | 1615 | Scheduler_Cfg.Prg[3].Event[0].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR092 | Write | ||
| PIV | 1616 | Scheduler_Cfg.Prg[3].Event[0].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR093 | Write | ||
| PIV | 1617 | Scheduler_Cfg.Prg[3].Event[0].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR094 | Write | ||
| PIV | 1618 | Scheduler_Cfg.Prg[3].Event[1].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR095 | Write | ||
| PIV | 1619 | Scheduler_Cfg.Prg[3].Event[1].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR096 | Write | ||
| PIV | 1620 | Scheduler_Cfg.Prg[3].Event[1].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR097 | Write | ||
| PIV | 1621 | Scheduler_Cfg.Prg[3].Event[2].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR098 | Write | ||
| PIV | 1622 | Scheduler_Cfg.Prg[3].Event[2].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR099 | Write | ||
| PIV | 1623 | Scheduler_Cfg.Prg[3].Event[2].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR100 | Write | ||
| PIV | 1624 | Scheduler_Cfg.Prg[3].Event[3].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR101 | Write | ||
| PIV | 1625 | Scheduler_Cfg.Prg[3].Event[3].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR102 | Write | ||
| PIV | 1626 | Scheduler_Cfg.Prg[3].Event[3].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR103 | Write | ||
| PIV | 1627 | Scheduler_Cfg.Prg[3].Event[4].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR104 | Write | ||
| PIV | 1628 | Scheduler_Cfg.Prg[3].Event[4].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR105 | Write | ||
| PIV | 1629 | Scheduler_Cfg.Prg[3].Event[4].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR106 | Write | ||
| PIV | 1630 | Scheduler_Cfg.Prg[3].Event[5].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR107 | Write | ||
| PIV | 1631 | Scheduler_Cfg.Prg[3].Event[5].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR108 | Write | ||
| PIV | 1632 | Scheduler_Cfg.Prg[3].Event[5].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR109 | Write | ||
| PIV | 1633 | Scheduler_Cfg.Prg[3].Event[6].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR110 | Write | ||
| PIV | 1634 | Scheduler_Cfg.Prg[3].Event[6].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR111 | Write | ||
| PIV | 1635 | Scheduler_Cfg.Prg[3].Event[6].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR112 | Write | ||
| PIV | 1636 | Scheduler_Cfg.Prg[3].Event[7].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR113 | Write | ||
| PIV | 1637 | Scheduler_Cfg.Prg[3].Event[7].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR114 | Write | ||
| PIV | 1638 | Scheduler_Cfg.Prg[3].Event[7].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR115 | Write | ||
| PIV | 1639 | Scheduler_Cfg.Prg[3].Event[8].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR116 | Write | ||
| PIV | 1640 | Scheduler_Cfg.Prg[3].Event[8].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR117 | Write | ||
| PIV | 1641 | Scheduler_Cfg.Prg[3].Event[8].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR118 | Write | ||
| PIV | 1642 | Scheduler_Cfg.Prg[3].Event[9].Hours | Scheduler: configuration - Program - Event - Start hours event; Modbus HR119 | Write | ||
| PIV | 1643 | Scheduler_Cfg.Prg[3].Event[9].Mins | Scheduler: configuration - Program - Event - Start minutes event; Modbus HR120 | Write | ||
| PIV | 1644 | Scheduler_Cfg.Prg[3].Event[9].Mode | Scheduler: configuration - Program - Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR121 | Write | ||
| PIV | 1651 | Scheduler_Cfg.SDays[2].Day | Scheduler: configuration - Special day - Day; Modbus HR128 | Write | ||
| PIV | 1652 | Scheduler_Cfg.SDays[2].Mode | Scheduler: configuration - Special day - Mode; Modbus HR129 | Write | ||
| PIV | 1653 | Scheduler_Cfg.SDays[2].Month | Scheduler: configuration - Special day - Month; Modbus HR130 | Write | ||
| PIV | 1654 | Scheduler_Cfg.SDays[3].Day | Scheduler: configuration - Special day - Day; Modbus HR131 | Write | ||
| PIV | 1655 | Scheduler_Cfg.SDays[3].Mode | Scheduler: configuration - Special day - Mode; Modbus HR132 | Write | ||
| PIV | 1656 | Scheduler_Cfg.SDays[3].Month | Scheduler: configuration - Special day - Month; Modbus HR133 | Write | ||
| PIV | 1657 | Scheduler_Cfg.SDays[4].Day | Scheduler: configuration - Special day - Day; Modbus HR134 | Write | ||
| PIV | 1658 | Scheduler_Cfg.SDays[4].Mode | Scheduler: configuration - Special day - Mode; Modbus HR135 | Write | ||
| PIV | 1659 | Scheduler_Cfg.SDays[4].Month | Scheduler: configuration - Special day - Month; Modbus HR136 | Write | ||
| PIV | 1660 | Scheduler_Cfg.SDays[5].Day | Scheduler: configuration - Special day - Day; Modbus HR137 | Write | ||
| PIV | 1661 | Scheduler_Cfg.SDays[5].Mode | Scheduler: configuration - Special day - Mode; Modbus HR138 | Write | ||
| PIV | 1662 | Scheduler_Cfg.SDays[5].Month | Scheduler: configuration - Special day - Month; Modbus HR139 | Write | ||
| PIV | 1663 | Scheduler_Cfg.SDays[6].Day | Scheduler: configuration - Special day - Day; Modbus HR140 | Write | ||
| PIV | 1664 | Scheduler_Cfg.SDays[6].Mode | Scheduler: configuration - Special day - Mode; Modbus HR141 | Write | ||
| PIV | 1665 | Scheduler_Cfg.SDays[6].Month | Scheduler: configuration - Special day - Month; Modbus HR142 | Write | ||
| PIV | 1666 | Scheduler_Cfg.SDays[7].Day | Scheduler: configuration - Special day - Day; Modbus HR143 | Write | ||
| PIV | 1667 | Scheduler_Cfg.SDays[7].Mode | Scheduler: configuration - Special day - Mode; Modbus HR144 | Write | ||
| PIV | 1668 | Scheduler_Cfg.SDays[7].Month | Scheduler: configuration - Special day - Month; Modbus HR145 | Write | ||
| PIV | 1669 | Scheduler_Cfg.SDays[8].Day | Scheduler: configuration - Special day - Day; Modbus HR146 | Write | ||
| PIV | 1670 | Scheduler_Cfg.SDays[8].Mode | Scheduler: configuration - Special day - Mode; Modbus HR147 | Write | ||
| PIV | 1671 | Scheduler_Cfg.SDays[8].Month | Scheduler: configuration - Special day - Month; Modbus HR148 | Write | ||
| PIV | 1672 | Scheduler_Cfg.SDays[9].Day | Scheduler: configuration - Special day - Day; Modbus HR149 | Write | ||
| PIV | 1673 | Scheduler_Cfg.SDays[9].Mode | Scheduler: configuration - Special day - Mode; Modbus HR150 | Write | ||
| PIV | 1674 | Scheduler_Cfg.SDays[9].Month | Scheduler: configuration - Special day - Month; Modbus HR151 | Write | ||
| PIV | 1675 | Scheduler_Cfg.SDays[10].Day | Scheduler: configuration - Special day - Day; Modbus HR152 | Write | ||
| PIV | 1676 | Scheduler_Cfg.SDays[10].Mode | Scheduler: configuration - Special day - Mode; Modbus HR153 | Write | ||
| PIV | 1677 | Scheduler_Cfg.SDays[10].Month | Scheduler: configuration - Special day - Month; Modbus HR154 | Write | ||
| PIV | 1678 | Scheduler_Cfg.SDays[11].Day | Scheduler: configuration - Special day - Day; Modbus HR155 | Write | ||
| PIV | 1679 | Scheduler_Cfg.SDays[11].Mode | Scheduler: configuration - Special day - Mode; Modbus HR156 | Write | ||
| PIV | 1680 | Scheduler_Cfg.SDays[11].Month | Scheduler: configuration - Special day - Month; Modbus HR157 | Write | ||
| PIV | 1681 | Scheduler_Cfg.SDays[12].Day | Scheduler: configuration - Special day - Day; Modbus HR158 | Write | ||
| PIV | 1682 | Scheduler_Cfg.SDays[12].Mode | Scheduler: configuration - Special day - Mode; Modbus HR159 | Write | ||
| PIV | 1683 | Scheduler_Cfg.SDays[12].Month | Scheduler: configuration - Special day - Month; Modbus HR160 | Write | ||
| PIV | 1684 | Scheduler_Cfg.SDays[13].Day | Scheduler: configuration - Special day - Day; Modbus HR161 | Write | ||
| PIV | 1685 | Scheduler_Cfg.SDays[13].Mode | Scheduler: configuration - Special day - Mode; Modbus HR162 | Write | ||
| PIV | 1686 | Scheduler_Cfg.SDays[13].Month | Scheduler: configuration - Special day - Month; Modbus HR163 | Write | ||
| PIV | 1687 | Scheduler_Cfg.SDays[14].Day | Scheduler: configuration - Special day - Day; Modbus HR164 | Write | ||
| PIV | 1688 | Scheduler_Cfg.SDays[14].Mode | Scheduler: configuration - Special day - Mode; Modbus HR165 | Write | ||
| PIV | 1689 | Scheduler_Cfg.SDays[14].Month | Scheduler: configuration - Special day - Month; Modbus HR166 | Write | ||
| PIV | 1690 | Scheduler_Cfg.Vac[0].EndDay | Scheduler: configuration - Vacation period - End day; Modbus HR167 | Write | ||
| PIV | 1691 | Scheduler_Cfg.Vac[0].EndMonth | Scheduler: configuration - Vacation period - End month; Modbus HR168 | Write | ||
| PIV | 1692 | Scheduler_Cfg.Vac[0].Mode | Scheduler: configuration - Vacation period - Mode; Modbus HR169 | Write | ||
| PIV | 1693 | Scheduler_Cfg.Vac[0].StartDay | Scheduler: configuration - Vacation period - Start day; Modbus HR170 | Write | ||
| PIV | 1694 | Scheduler_Cfg.Vac[0].StartMonth | Scheduler: configuration - Vacation period - Start month; Modbus HR171 | Write | ||
| PIV | 1695 | Scheduler_Cfg.Vac[1].EndDay | Scheduler: configuration - Vacation period - End day; Modbus HR172 | Write | ||
| PIV | 1696 | Scheduler_Cfg.Vac[1].EndMonth | Scheduler: configuration - Vacation period - End month; Modbus HR173 | Write | ||
| PIV | 1697 | Scheduler_Cfg.Vac[1].Mode | Scheduler: configuration - Vacation period - Mode; Modbus HR174 | Write | ||
| PIV | 1698 | Scheduler_Cfg.Vac[1].StartDay | Scheduler: configuration - Vacation period - Start day; Modbus HR175 | Write | ||
| PIV | 1699 | Scheduler_Cfg.Vac[1].StartMonth | Scheduler: configuration - Vacation period - Start month; Modbus HR176 | Write | ||
| PIV | 1700 | Scheduler_Cfg.Vac[2].EndDay | Scheduler: configuration - Vacation period - End day; Modbus HR177 | Write | ||
| PIV | 1701 | Scheduler_Cfg.Vac[2].EndMonth | Scheduler: configuration - Vacation period - End month; Modbus HR178 | Write | ||
| PIV | 1702 | Scheduler_Cfg.Vac[2].Mode | Scheduler: configuration - Vacation period - Mode; Modbus HR179 | Write | ||
| PIV | 1703 | Scheduler_Cfg.Vac[2].StartDay | Scheduler: configuration - Vacation period - Start day; Modbus HR180 | Write | ||
| PIV | 1704 | Scheduler_Cfg.Vac[2].StartMonth | Scheduler: configuration - Vacation period - Start month; Modbus HR181 | Write | ||
| PIV | 1705 | Scheduler_Cfg.WkDays[0] | Scheduler: configuration - Week day; Modbus HR182 | Write | ||
| PIV | 1706 | Scheduler_Cfg.WkDays[1] | Scheduler: configuration - Week day; Modbus HR183 | Write | ||
| PIV | 1707 | Scheduler_Cfg.WkDays[2] | Scheduler: configuration - Week day; Modbus HR184 | Write | ||
| PIV | 1708 | Scheduler_Cfg.WkDays[3] | Scheduler: configuration - Week day; Modbus HR185 | Write | ||
| PIV | 1709 | Scheduler_Cfg.WkDays[4] | Scheduler: configuration - Week day; Modbus HR186 | Write | ||
| PIV | 1710 | Scheduler_Cfg.WkDays[5] | Scheduler: configuration - Week day; Modbus HR187 | Write | ||
| PIV | 1711 | Scheduler_Cfg.WkDays[6] | Scheduler: configuration - Week day; Modbus HR188 | Write | ||
| PIV | 1712 | GeneralMng.RTC_BMS.Day | BMS real time clock; Modbus HR189 | Write | ||
| PIV | 1713 | GeneralMng.RTC_BMS.Month | BMS real time clock; Modbus HR190 | Write | ||
| PIV | 1714 | GeneralMng.RTC_BMS.Year | BMS real time clock; Modbus HR191 | Write | ||
| AV | 1715 | CoilRegOffset | Offset to switch on the el heater and pump; Modbus HR192 (garbled row) | Write | ||
| PIV | 1716 | SupplyTemp.Board_RW | Supply temperature - Board selected; Modbus HR193 | Write | ||
| PIV | 1717 | SupplyTemp.Ch_Id_RW | Supply temperature - Channel id selected; Modbus HR194 | Write | ||
| PIV | 1718 | SupplyTemp.Ch_Type_RW | Supply temperature - Type probe used; Modbus HR195 | Write | ||
| AV | 1719 | SupplyTemp.MinVal_RW | Supply temperature - Minimum value analog input; Modbus HR196 | Write | ||
| AV | 1720 | SupplyTemp.MaxVal_RW | Supply temperature - Maximum value analog input; Modbus HR197 | Write | ||
| AV | 1721 | SupplyTemp.Offset_RW | Supply temperature - Offset analog input; Modbus HR198 | Write | ||
| PIV | 1722 | SupplyTemp.ChFilter_RW | Supply temperature - Filter channel; Modbus HR199 | Write | ||
| PIV | 1723 | SupplyHum.Board_RW | Supply humidity - Board selected; Modbus HR200 | Write | ||
| PIV | 1724 | SupplyHum.Ch_Id_RW | Supply humidity - Channel id selected; Modbus HR201 | Write | ||
| PIV | 1725 | SupplyHum.Ch_Type_RW | Supply humidity - Type probe used; Modbus HR202 | Write | ||
| AV | 1726 | SupplyHum.MinVal_RW | Supply humidity - Minimum value analog input; Modbus HR203 | Write | ||
| AV | 1727 | SupplyHum.MaxVal_RW | Supply humidity - Maximum value analog input; Modbus HR204 | Write | ||
| AV | 1728 | SupplyHum.Offset_RW | Supply humidity - Offset analog input; Modbus HR205 | Write | ||
| PIV | 1729 | SupplyHum.ChFilter_RW | Supply humidity - Filter channel; Modbus HR206 | Write | ||
| PIV | 1730 | RetTemp.Board_RW | Return temperature - Board selected; Modbus HR207 | Write | ||
| PIV | 1731 | RetTemp.Ch_Id_RW | Return temperature - Channel id selected; Modbus HR208 | Write | ||
| PIV | 1732 | RetTemp.Ch_Type_RW | Return temperature - Type probe used; Modbus HR209 | Write | ||
| AV | 1733 | RetTemp.MinVal_RW | Return temperature - Minimum value analog input; Modbus HR210 | Write | ||
| AV | 1734 | RetTemp.MaxVal_RW | Return temperature - Maximum value analog input; Modbus HR211 | Write | ||
| AV | 1735 | RetTemp.Offset_RW | Return temperature - Offset analog input; Modbus HR212 | Write | ||
| PIV | 1736 | RetTemp.ChFilter_RW | Return temperature - Filter channel; Modbus HR213 | Write | ||
| PIV | 1737 | RetHum.Board_RW | Return humidity - Board selected; Modbus HR214 | Write | ||
| PIV | 1738 | RetHum.Ch_Id_RW | Return humidity - Channel id selected; Modbus HR215 | Write | ||
| PIV | 1739 | RetHum.Ch_Type_RW | Return humidity - Type probe used; Modbus HR216 | Write | ||
| AV | 1740 | RetHum.MinVal_RW | Return humidity - Minimum value analog input; Modbus HR217 | Write | ||
| AV | 1741 | RetHum.MaxVal_RW | Return humidity - Maximum value analog input; Modbus HR218 | Write | ||
| AV | 1742 | RetHum.Offset_RW | Return humidity - Offset analog input; Modbus HR219 | Write | ||
| PIV | 1743 | RetHum.ChFilter_RW | Return humidity - Filter channel; Modbus HR220 | Write | ||
| PIV | 1744 | RoomTemp.Board_RW | Room temperature - Board selected; Modbus HR221 | Write | ||
| PIV | 1745 | RoomTemp.Ch_Id_RW | Room temperature - Channel id selected; Modbus HR222 | Write | ||
| PIV | 1746 | RoomTemp.Ch_Type_RW | Room temperature - Type probe used; Modbus HR223 | Write | ||
| AV | 1747 | RoomTemp.MinVal_RW | Room temperature - Minimum value analog input; Modbus HR224 | Write | ||
| AV | 1748 | RoomTemp.MaxVal_RW | Room temperature - Maximum value analog input; Modbus HR225 | Write | ||
| AV | 1749 | RoomTemp.Offset_RW | Room temperature - Offset analog input; Modbus HR226 | Write | ||
| PIV | 1750 | RoomTemp.ChFilter_RW | Room temperature - Filter channel; Modbus HR227 | Write | ||
| PIV | 1751 | RoomHum.Board_RW | Room humidity - Board selected; Modbus HR228 | Write | ||
| PIV | 1752 | RoomHum.Ch_Id_RW | Room humidity - Channel id selected; Modbus HR229 | Write | ||
| PIV | 1753 | RoomHum.Ch_Type_RW | Room humidity - Type probe used; Modbus HR230 | Write | ||
| AV | 1754 | RoomHum.MinVal_RW | Room humidity - Minimum value analog input; Modbus HR231 | Write | ||
| AV | 1755 | RoomHum.MaxVal_RW | Room humidity - Maximum value analog input; Modbus HR232 | Write | ||
| AV | 1756 | RoomHum.Offset_RW | Room humidity - Offset analog input; Modbus HR233 | Write | ||
| PIV | 1757 | RoomHum.ChFilter_RW | Room humidity - Filter channel; Modbus HR234 | Write | ||
| PIV | 1758 | ExtTemp.Board_RW | Fresh air temperature - Board selected; Modbus HR235 | Write | ||
| PIV | 1759 | ExtTemp.Ch_Id_RW | Fresh air temperature - Channel id selected; Modbus HR236 | Write | ||
| PIV | 1760 | ExtTemp.Ch_Type_RW | Fresh air temperature - Type probe used; Modbus HR237 | Write | ||
| AV | 1761 | ExtTemp.MinVal_RW | Fresh air temperature - Minimum value analog input; Modbus HR238 | Write | ||
| AV | 1762 | ExtTemp.MaxVal_RW | Fresh air temperature - Maximum value analog input; Modbus HR239 | Write | ||
| AV | 1763 | ExtTemp.Offset_RW | Fresh air temperature - Offset analog input; Modbus HR240 | Write | ||
| PIV | 1764 | ExtTemp.ChFilter_RW | Fresh air temperature - Filter channel; Modbus HR241 | Write | ||
| PIV | 1765 | ExtHum.Board_RW | Fresh air humidity - Board selected; Modbus HR242 | Write | ||
| PIV | 1766 | ExtHum.Ch_Id_RW | Fresh air humidity - Channel id selected; Modbus HR243 | Write | ||
| PIV | 1767 | ExtHum.Ch_Type_RW | Fresh air humidity - Type probe used; Modbus HR244 | Write | ||
| AV | 1768 | ExtHum.MinVal_RW | Fresh air humidity - Minimum value analog input; Modbus HR245 | Write | ||
| AV | 1769 | ExtHum.MaxVal_RW | Fresh air humidity - Maximum value analog input; Modbus HR246 | Write | ||
| AV | 1770 | ExtHum.Offset_RW | Fresh air humidity - Offset analog input; Modbus HR247 | Write | ||
| PIV | 1771 | ExtHum.ChFilter_RW | Fresh air humidity - Filter channel; Modbus HR248 | Write | ||
| PIV | 1772 | ExhTemp.Board_RW | Exhaust temperature - Board selected; Modbus HR249 | Write | ||
| PIV | 1773 | ExhTemp.Ch_Id_RW | Exhaust temperature - Channel id selected; Modbus HR250 | Write | ||
| PIV | 1774 | ExhTemp.Ch_Type_RW | Exhaust temperature - Type probe used; Modbus HR251 | Write | ||
| AV | 1775 | ExhTemp.MinVal_RW | Exhaust temperature - Minimum value analog input; Modbus HR252 | Write | ||
| AV | 1776 | ExhTemp.MaxVal_RW | Exhaust temperature - Maximum value analog input; Modbus HR253 | Write | ||
| AV | 1777 | ExhTemp.Offset_RW | Exhaust temperature - Offset analog input; Modbus HR254 | Write | ||
| PIV | 1778 | ExhTemp.ChFilter_RW | Exhaust temperature - Filter channel; Modbus HR255 | Write | ||
| PIV | 1779 | ExhHum.Board_RW | Exhaust humidity - Board selected; Modbus HR256 | Write | ||
| PIV | 1780 | ExhHum.Ch_Id_RW | Exhaust humidity - Channel id selected; Modbus HR257 | Write | ||
| PIV | 1781 | ExhHum.Ch_Type_RW | Exhaust humidity - Type probe used; Modbus HR258 | Write | ||
| AV | 1782 | ExhHum.MinVal_RW | Exhaust humidity - Minimum value analog input; Modbus HR259 | Write | ||
| AV | 1783 | ExhHum.MaxVal_RW | Exhaust humidity - Maximum value analog input; Modbus HR260 | Write | ||
| AV | 1784 | ExhHum.Offset_RW | Exhaust humidity - Offset analog input; Modbus HR261 | Write | ||
| PIV | 1785 | ExhHum.ChFilter_RW | Exhaust humidity - Filter channel; Modbus HR262 | Write | ||
| PIV | 1786 | AFreezeTemp.Board_RW | Antifreeze temperature - Board selected; Modbus HR263 | Write | ||
| PIV | 1787 | AFreezeTemp.Ch_Id_RW | Antifreeze temperature - Channel id selected; Modbus HR264 | Write | ||
| PIV | 1788 | AFreezeTemp.Ch_Type_RW | Antifreeze temperature - Type probe used; Modbus HR265 | Write | ||
| AV | 1789 | AFreezeTemp.MinVal_RW | Antifreeze temperature - Minimum value analog input; Modbus HR266 | Write | ||
| AV | 1790 | AFreezeTemp.MaxVal_RW | Antifreeze temperature - Maximum value analog input; Modbus HR267 | Write | ||
| AV | 1791 | AFreezeTemp.Offset_RW | Antifreeze temperature - Offset analog input; Modbus HR268 | Write | ||
| PIV | 1792 | AFreezeTemp.ChFilter_RW | Antifreeze temperature - Filter channel; Modbus HR269 | Write | ||
| PIV | 1793 | SatTemp.Board_RW | Saturation temperature - Board selected; Modbus HR270 | Write | ||
| PIV | 1794 | SatTemp.Ch_Id_RW | Saturation temperature - Channel id selected; Modbus HR271 | Write | ||
| PIV | 1795 | SatTemp.Ch_Type_RW | Saturation temperature - Type probe used; Modbus HR272 | Write | ||
| AV | 1796 | SatTemp.MinVal_RW | Saturation temperature - Minimum value analog input; Modbus HR273 | Write | ||
| AV | 1797 | SatTemp.MaxVal_RW | Saturation temperature - Maximum value analog input; Modbus HR274 | Write | ||
| AV | 1798 | SatTemp.Offset_RW | Saturation temperature - Offset analog input; Modbus HR275 | Write | ||
| PIV | 1799 | SatTemp.ChFilter_RW | Saturation temperature - Filter channel; Modbus HR276 | Write | ||
| PIV | 1800 | SatHum.Board_RW | Saturation humidity - Board selected; Modbus HR277 | Write | ||
| PIV | 1801 | SatHum.Ch_Id_RW | Saturation humidity - Channel id selected; Modbus HR278 | Write | ||
| PIV | 1802 | SatHum.Ch_Type_RW | Saturation humidity - Type probe used; Modbus HR279 | Write | ||
| AV | 1803 | SatHum.MinVal_RW | Saturation humidity - Minimum value analog input; Modbus HR280 | Write | ||
| AV | 1804 | SatHum.MaxVal_RW | Saturation humidity - Maximum value analog input; Modbus HR281 | Write | ||
| AV | 1805 | SatHum.Offset_RW | Saturation humidity - Offset analog input; Modbus HR282 | Write | ||
| PIV | 1806 | SatHum.ChFilter_RW | Saturation humidity - Filter channel; Modbus HR283 | Write | ||
| PIV | 1807 | OA_Temp.Board_RW | Outdoor air pre-treatment temperature - Board selected; Modbus HR284 | Write | ||
| PIV | 1808 | OA_Temp.Ch_Id_RW | Outdoor air pre-treatment temperature - Channel id selected; Modbus HR285 | Write | ||
| PIV | 1809 | OA_Temp.Ch_Type_RW | Outdoor air pre-treatment temperature - Type probe used; Modbus HR286 | Write | ||
| AV | 1810 | OA_Temp.MinVal_RW | Outdoor air pre-treatment temperature - Minimum value analog input; Modbus HR287 | Write | ||
| AV | 1811 | OA_Temp.MaxVal_RW | Outdoor air pre-treatment temperature - Maximum value analog input; Modbus HR288 | Write | ||
| AV | 1812 | OA_Temp.Offset_RW | Outdoor air pre-treatment temperature - Offset analog input; Modbus HR289 | Write | ||
| PIV | 1813 | OA_Temp.ChFilter_RW | Outdoor air pre-treatment temperature - Filter channel; Modbus HR290 | Write | ||
| PIV | 1814 | SupplyAirP.Board_RW | Supply air pressure - Board selected; Modbus HR291 | Write | ||
| PIV | 1815 | SupplyAirP.Ch_Id_RW | Supply air pressure - Channel id selected; Modbus HR292 | Write | ||
| PIV | 1816 | SupplyAirP.Ch_Type_RW | Supply air pressure - Type probe used; Modbus HR293 | Write | ||
| AV | 1817 | SupplyAirP.MinVal_RW | Supply air pressure - Minimum value analog input; Modbus HR294 | Write | ||
| AV | 1818 | SupplyAirP.MaxVal_RW | Supply air pressure - Maximum value analog input; Modbus HR295 | Write | ||
| AV | 1819 | SupplyAirP.Offset_RW | Supply air pressure - Offset analog input; Modbus HR296 | Write | ||
| PIV | 1820 | SupplyAirP.ChFilter_RW | Supply air pressure - Filter channel; Modbus HR297 | Write | ||
| PIV | 1821 | RetAirP.Board_RW | Return air pressure - Board selected; Modbus HR298 | Write | ||
| PIV | 1822 | RetAirP.Ch_Id_RW | Return air pressure - Channel id selected; Modbus HR299 | Write | ||
| PIV | 1823 | RetAirP.Ch_Type_RW | Return air pressure - Type probe used; Modbus HR300 | Write | ||
| AV | 1824 | RetAirP.MinVal_RW | Return air pressure - Minimum value analog input; Modbus HR301 | Write | ||
| AV | 1825 | RetAirP.MaxVal_RW | Return air pressure - Maximum value analog input; Modbus HR302 | Write | ||
| AV | 1826 | RetAirP.Offset_RW | Return air pressure - Offset analog input; Modbus HR303 | Write | ||
| PIV | 1827 | RetAirP.ChFilter_RW | Return air pressure - Filter channel; Modbus HR304 | Write | ||
| PIV | 1828 | AirQuality_CO2.Board_RW | CO2 sensor - Board selected; Modbus HR305 | Write | ||
| PIV | 1829 | AirQuality_CO2.Ch_Id_RW | CO2 sensor - Channel id selected; Modbus HR306 | Write | ||
| PIV | 1830 | AirQuality_CO2.Ch_Type_RW | CO2 sensor - Type probe used; Modbus HR307 | Write | ||
| AV | 1831 | AirQuality_CO2.MinVal_RW | CO2 sensor - Minimum value analog input; Modbus HR308 | Write | ||
| AV | 1832 | AirQuality_CO2.MaxVal_RW | CO2 sensor - Maximum value analog input; Modbus HR309 | Write | ||
| AV | 1833 | AirQuality_CO2.Offset_RW | CO2 sensor - Offset analog input; Modbus HR310 | Write | ||
| PIV | 1834 | AirQuality_CO2.ChFilter_RW | CO2 sensor - Filter channel; Modbus HR311 | Write | ||
| PIV | 1835 | AirQuality_VOC.Board_RW | VOC sensor - Board selected; Modbus HR312 | Write | ||
| PIV | 1836 | AirQuality_VOC.Ch_Id_RW | VOC sensor - Channel id selected; Modbus HR313 | Write | ||
| PIV | 1837 | AirQuality_VOC.Ch_Type_RW | VOC sensor - Type probe used; Modbus HR314 | Write | ||
| AV | 1838 | AirQuality_VOC.MinVal_RW | VOC sensor - Minimum value analog input; Modbus HR315 | Write | ||
| AV | 1839 | AirQuality_VOC.MaxVal_RW | VOC sensor - Maximum value analog input; Modbus HR316 | Write | ||
| AV | 1840 | AirQuality_VOC.Offset_RW | VOC sensor - Offset analog input; Modbus HR317 | Write | ||
| PIV | 1841 | AirQuality_VOC.ChFilter_RW | VOC sensor - Filter channel; Modbus HR318 | Write | ||
| PIV | 1842 | DscgP.Board_RW | Discharge pressure - Board selected; Modbus HR319 | Write | ||
| PIV | 1843 | DscgP.Ch_Id_RW | Discharge pressure - Channel id selected; Modbus HR320 | Write | ||
| PIV | 1844 | DscgP.Ch_Type_RW | Discharge pressure - Type probe used; Modbus HR321 | Write | ||
| AV | 1845 | DscgP.MinVal_RW | Discharge pressure - Minimum value analog input; Modbus HR322 | Write | ||
| AV | 1846 | DscgP.MaxVal_RW | Discharge pressure - Maximum value analog input; Modbus HR323 | Write | ||
| AV | 1847 | DscgP.Offset_RW | Discharge pressure - Offset analog input; Modbus HR324 | Write | ||
| PIV | 1848 | DscgP.ChFilter_RW | Discharge pressure - Filter channel; Modbus HR325 | Write | ||
| PIV | 1849 | DscgT.Board_RW | Discharge temperature - Board selected; Modbus HR326 | Write | ||
| PIV | 1850 | DscgT.Ch_Id_RW | Discharge temperature - Channel id selected; Modbus HR327 | Write | ||
| PIV | 1851 | DscgT.Ch_Type_RW | Discharge temperature - Type probe used; Modbus HR328 | Write | ||
| AV | 1852 | DscgT.MinVal_RW | Discharge temperature - Minimum value analog input; Modbus HR329 | Write | ||
| AV | 1853 | DscgT.MaxVal_RW | Discharge temperature - Maximum value analog input; Modbus HR330 | Write | ||
| AV | 1854 | DscgT.Offset_RW | Discharge temperature - Offset analog input; Modbus HR331 | Write | ||
| PIV | 1855 | DscgT.ChFilter_RW | Discharge temperature - Filter channel; Modbus HR332 | Write | ||
| PIV | 1856 | SuctP.Board_RW | Suction pressure - Board selected; Modbus HR333 | Write | ||
| PIV | 1857 | SuctP.Ch_Id_RW | Suction pressure - Channel id selected; Modbus HR334 | Write | ||
| PIV | 1858 | SuctP.Ch_Type_RW | Suction pressure - Type probe used; Modbus HR335 | Write | ||
| AV | 1859 | SuctP.MinVal_RW | Suction pressure - Minimum value analog input; Modbus HR336 | Write | ||
| AV | 1860 | SuctP.MaxVal_RW | Suction pressure - Maximum value analog input; Modbus HR337 | Write | ||
| AV | 1861 | SuctP.Offset_RW | Suction pressure - Offset analog input; Modbus HR338 | Write | ||
| PIV | 1862 | SuctP.ChFilter_RW | Suction pressure - Filter channel; Modbus HR339 | Write | ||
| PIV | 1863 | SuctT.Board_RW | Suction temperature - Board selected; Modbus HR340 | Write | ||
| PIV | 1864 | SuctT.Ch_Id_RW | Suction temperature - Channel id selected; Modbus HR341 | Write | ||
| PIV | 1865 | SuctT.Ch_Type_RW | Suction temperature - Type probe used; Modbus HR342 | Write | ||
| AV | 1866 | SuctT.MinVal_RW | Suction temperature - Minimum value analog input; Modbus HR343 | Write | ||
| AV | 1867 | SuctT.MaxVal_RW | Suction temperature - Maximum value analog input; Modbus HR344 | Write | ||
| AV | 1868 | SuctT.Offset_RW | Suction temperature - Offset analog input; Modbus HR345 | Write | ||
| PIV | 1869 | SuctT.ChFilter_RW | Suction temperature - Filter channel; Modbus HR346 | Write | ||
| PIV | 1870 | OA_CoilWaterTemp.Board_RW | Outdoor air pre-treatment coil water temperature - Board selected; Modbus HR347 | Write | ||
| PIV | 1871 | OA_CoilWaterTemp.Ch_Id_RW | Outdoor air pre-treatment coil water temperature - Channel id selected; Modbus HR348 | Write | ||
| PIV | 1872 | OA_CoilWaterTemp.Ch_Type_RW | Outdoor air pre-treatment coil water temperature - Type probe used; Modbus HR349 | Write | ||
| AV | 1873 | OA_CoilWaterTemp.MinVal_RW | Outdoor air pre-treatment coil water temperature - Minimum value analog input; Modbus HR350 | Write | ||
| AV | 1874 | OA_CoilWaterTemp.MaxVal_RW | Outdoor air pre-treatment coil water temperature - Maximum value analog; Modbus HR351 | Write | ||
| AV | 1875 | OA_CoilWaterTemp.Offset_RW | Outdoor air pre-treatment coil water temperature - Offset analog input; Modbus HR352 | Write | ||
| PIV | 1876 | OA_CoilWaterTemp.ChFilter_RW | Outdoor air pre-treatment coil water temperature - Filter channel; Modbus HR353 | Write | ||
| PIV | 1877 | PreHeatCoilWaterTemp.Board_RW | Preheat coil water temperature - Board selected; Modbus HR354 | Write | ||
| PIV | 1878 | PreHeatCoilWaterTemp.Ch_Id_RW | Preheat coil water temperature - Channel id selected; Modbus HR355 | Write | ||
| PIV | 1879 | PreHeatCoilWaterTemp.Ch_Type_RW | Preheat coil water temperature - Type probe used; Modbus HR356 | Write | ||
| AV | 1880 | PreHeatCoilWaterTemp.MinVal_RW | Preheat coil water temperature - Minimum value analog input; Modbus HR357 | Write | ||
| AV | 1881 | PreHeatCoilWaterTemp.MaxVal_RW | Preheat coil water temperature - Maximum value analog input; Modbus HR358 | Write | ||
| AV | 1882 | PreHeatCoilWaterTemp.Offset_RW | Preheat coil water temperature - Offset analog input; Modbus HR359 | Write | ||
| PIV | 1883 | PreHeatCoilWaterTemp.ChFilter_RW | Preheat coil water temperature - Filter channel; Modbus HR360 | Write | ||
| PIV | 1884 | MainCoilWaterTemp.Board_RW | Main coil water temperature - Board selected; Modbus HR361 | Write | ||
| PIV | 1885 | MainCoilWaterTemp.Ch_Id_RW | Main coil water temperature - Channel id selected; Modbus HR362 | Write | ||
| PIV | 1886 | MainCoilWaterTemp.Ch_Type_RW | Main coil water temperature - Type probe used; Modbus HR363 | Write | ||
| AV | 1887 | MainCoilWaterTemp.MinVal_RW | Main coil water temperature - Minimum value analog input; Modbus HR364 | Write | ||
| AV | 1888 | MainCoilWaterTemp.MaxVal_RW | Main coil water temperature - Maximum value analog input; Modbus HR365 | Write | ||
| AV | 1889 | MainCoilWaterTemp.Offset_RW | Main coil water temperature - Offset analog input; Modbus HR366 | Write | ||
| PIV | 1890 | MainCoilWaterTemp.ChFilter_RW | Main coil water temperature - Filter channel; Modbus HR367 | Write | ||
| PIV | 1891 | ReHeatCoilWaterTemp.Board_RW | Postheat coil water temperature - Board selected; Modbus HR368 | Write | ||
| PIV | 1892 | ReHeatCoilWaterTemp.Ch_Id_RW | Postheat coil water temperature - Channel id selected; Modbus HR369 | Write | ||
| PIV | 1893 | ReHeatCoilWaterTemp.Ch_Type_RW | Postheat coil water temperature - Type probe used; Modbus HR370 | Write | ||
| AV | 1894 | ReHeatCoilWaterTemp.MinVal_RW | Postheat coil water temperature - Minimum value analog input; Modbus HR371 | Write | ||
| AV | 1895 | ReHeatCoilWaterTemp.MaxVal_RW | Postheat coil water temperature - Maximum value analog input; Modbus HR372 | Write | ||
| AV | 1896 | ReHeatCoilWaterTemp.Offset_RW | Postheat coil water temperature - Offset analog input; Modbus HR373 | Write | ||
| PIV | 1897 | ReHeatCoilWaterTemp.ChFilter_RW | Postheat coil water temperature - Filter channel; Modbus HR374 | Write | ||
| PIV | 1898 | AuxPrb_1.Board_RW | Auxiliary probe 1 - Board selected; Modbus HR375 | Write | ||
| PIV | 1899 | AuxPrb_1.Ch_Id_RW | Auxiliary probe 1 - Channel id selected; Modbus HR376 | Write | ||
| PIV | 1900 | AuxPrb_1.Ch_Type_RW | Auxiliary probe 1 - Type probe used; Modbus HR377 | Write | ||
| AV | 1901 | AuxPrb_1.MinVal_RW | Auxiliary probe 1 - Minimum value analog input; Modbus HR378 | Write | ||
| AV | 1902 | AuxPrb_1.MaxVal_RW | Auxiliary probe 1 - Maximum value analog input; Modbus HR379 | Write | ||
| AV | 1903 | AuxPrb_1.Offset_RW | Auxiliary probe 1 - Offset analog input; Modbus HR380 | Write | ||
| PIV | 1904 | AuxPrb_1.ChFilter_RW | Auxiliary probe 1 - Filter channel; Modbus HR381 | Write | ||
| PIV | 1905 | AuxPrb_2.Board_RW | Auxiliary probe 2 - Board selected; Modbus HR382 | Write | ||
| PIV | 1906 | AuxPrb_2.Ch_Id_RW | Auxiliary probe 2 - Channel id selected; Modbus HR383 | Write | ||
| PIV | 1907 | AuxPrb_2.Ch_Type_RW | Auxiliary probe 2 - Type probe used; Modbus HR384 | Write | ||
| AV | 1908 | AuxPrb_2.MinVal_RW | Auxiliary probe 2 - Minimum value analog input; Modbus HR385 | Write | ||
| AV | 1909 | AuxPrb_2.MaxVal_RW | Auxiliary probe 2 - Maximum value analog input; Modbus HR386 | Write | ||
| AV | 1910 | AuxPrb_2.Offset_RW | Auxiliary probe 2 - Offset analog input; Modbus HR387 | Write | ||
| PIV | 1911 | AuxPrb_2.ChFilter_RW | Auxiliary probe 2 - Filter channel; Modbus HR388 | Write | ||
| PIV | 1912 | AuxPrb_3.Board_RW | Auxiliary probe 3 - Board selected; Modbus HR389 | Write | ||
| PIV | 1913 | AuxPrb_3.Ch_Id_RW | Auxiliary probe 3 - Channel id selected; Modbus HR390 | Write | ||
| PIV | 1914 | AuxPrb_3.Ch_Type_RW | Auxiliary probe 3 - Type probe used; Modbus HR391 | Write | ||
| AV | 1915 | AuxPrb_3.MinVal_RW | Auxiliary probe 3 - Minimum value analog input; Modbus HR392 | Write | ||
| AV | 1916 | AuxPrb_3.MaxVal_RW | Auxiliary probe 3 - Maximum value analog input; Modbus HR393 | Write | ||
| AV | 1917 | AuxPrb_3.Offset_RW | Auxiliary probe 3 - Offset analog input; Modbus HR394 | Write | ||
| PIV | 1918 | AuxPrb_3.ChFilter_RW | Auxiliary probe 3 - Filter channel; Modbus HR395 | Write | ||
| PIV | 1919 | AuxPrb_4.Board_RW | Auxiliary probe 4 - Board selected; Modbus HR396 | Write | ||
| PIV | 1920 | AuxPrb_4.Ch_Id_RW | Auxiliary probe 4 - Channel id selected; Modbus HR397 | Write | ||
| PIV | 1921 | AuxPrb_4.Ch_Type_RW | Auxiliary probe 4 - Type probe used; Modbus HR398 | Write | ||
| AV | 1922 | AuxPrb_4.MinVal_RW | Auxiliary probe 4 - Minimum value analog input; Modbus HR399 | Write | ||
| AV | 1923 | AuxPrb_4.MaxVal_RW | Auxiliary probe 4 - Maximum value analog input; Modbus HR400 | Write | ||
| AV | 1924 | AuxPrb_4.Offset_RW | Auxiliary probe 4 - Offset analog input; Modbus HR401 | Write | ||
| PIV | 1925 | AuxPrb_4.ChFilter_RW | Auxiliary probe 4 - Filter channel; Modbus HR402 | Write | ||
| PIV | 1926 | Ain_SetP.Board_RW | Setpoint by AIN - Board selected; Modbus HR403 | Write | ||
| PIV | 1927 | Ain_SetP.Ch_Id_RW | Setpoint by AIN - Channel id selected; Modbus HR404 | Write | ||
| PIV | 1928 | Ain_SetP.Ch_Type_RW | Setpoint by AIN - Type probe used; Modbus HR405 | Write | ||
| AV | 1929 | Ain_SetP.MinVal_RW | Setpoint by AIN - Minimum value analog input; Modbus HR406 | Write | ||
| AV | 1930 | Ain_SetP.MaxVal_RW | Setpoint by AIN - Maximum value analog input; Modbus HR407 | Write | ||
| AV | 1931 | Ain_SetP.Offset_RW | Setpoint by AIN - Offset analog input; Modbus HR408 | Write | ||
| PIV | 1932 | Ain_SetP.ChFilter_RW | Setpoint by AIN - Filter channel; Modbus HR409 | Write | ||
| PIV | 1933 | SupplyRecoveryTemp.Board_RW | Supply recovery temperature - Board selected; Modbus HR410 | Write | ||
| PIV | 1934 | SupplyRecoveryTemp.Ch_Id_RW | Supply recovery temperature - Channel id selected; Modbus HR411 | Write | ||
| PIV | 1935 | SupplyRecoveryTemp.Ch_Type_RW | Supply recovery temperature - Type probe used; Modbus HR412 | Write | ||
| AV | 1936 | SupplyRecoveryTemp.MinVal_RW | Supply recovery temperature - Minimum value analog input; Modbus HR413 | Write | ||
| AV | 1937 | SupplyRecoveryTemp.MaxVal_RW | Supply recovery temperature - Maximum value analog input; Modbus HR414 | Write | ||
| AV | 1938 | SupplyRecoveryTemp.Offset_RW | Supply recovery temperature - Offset analog input; Modbus HR415 | Write | ||
| PIV | 1939 | SupplyRecoveryTemp.ChFilter_RW | Supply recovery temperature - Filter channel; Modbus HR416 | Write | ||
| PIV | 1940 | RetRecoveryTemp.Board_RW | Return recovery temperature - Board selected; Modbus HR417 | Write | ||
| PIV | 1941 | RetRecoveryTemp.Ch_Id_RW | Return recovery temperature - Channel id selected; Modbus HR418 | Write | ||
| PIV | 1942 | RetRecoveryTemp.Ch_Type_RW | Return recovery temperature - Type probe used; Modbus HR419 | Write | ||
| AV | 1943 | RetRecoveryTemp.MinVal_RW | Return recovery temperature - Minimum value analog input; Modbus HR420 | Write | ||
| AV | 1944 | RetRecoveryTemp.MaxVal_RW | Return recovery temperature - Maximum value analog input; Modbus HR421 | Write | ||
| AV | 1945 | RetRecoveryTemp.Offset_RW | Return recovery temperature - Offset analog input; Modbus HR422 | Write | ||
| PIV | 1946 | RetRecoveryTemp.ChFilter_RW | Return recovery temperature - Filter channel; Modbus HR423 | Write | ||
| PIV | 1947 | HepaFilt_1.Board_RW | Hepa filter 1 - Board selected; Modbus HR424 | Write | ||
| PIV | 1948 | HepaFilt_1.Ch_Id_RW | Hepa filter 1 - Channel id selected; Modbus HR425 | Write | ||
| PIV | 1949 | HepaFilt_1.Ch_Type_RW | Hepa filter 1 - Type probe used; Modbus HR426 | Write | ||
| AV | 1950 | HepaFilt_1.MinVal_RW | Hepa filter 1 - Minimum value analog input; Modbus HR427 | Write | ||
| AV | 1951 | HepaFilt_1.MaxVal_RW | Hepa filter 1 - Maximum value analog input; Modbus HR428 | Write | ||
| AV | 1952 | HepaFilt_1.Offset_RW | Hepa filter 1 - Offset analog input; Modbus HR429 | Write | ||
| PIV | 1953 | HepaFilt_1.ChFilter_RW | Hepa filter 1 - Filter channel; Modbus HR430 | Write | ||
| PIV | 1954 | HepaFilt_2.Board_RW | Hepa filter 2 - Board selected; Modbus HR431 | Write | ||
| PIV | 1955 | HepaFilt_2.Ch_Id_RW | Hepa filter 2 - Channel id selected; Modbus HR432 | Write | ||
| PIV | 1956 | HepaFilt_2.Ch_Type_RW | Hepa filter 2 - Type probe used; Modbus HR433 | Write | ||
| AV | 1957 | HepaFilt_2.MinVal_RW | Hepa filter 2 - Minimum value analog input; Modbus HR434 | Write | ||
| AV | 1958 | HepaFilt_2.MaxVal_RW | Hepa filter 2 - Maximum value analog input; Modbus HR435 | Write | ||
| AV | 1959 | HepaFilt_2.Offset_RW | Hepa filter 2 - Offset analog input; Modbus HR436 | Write | ||
| PIV | 1960 | HepaFilt_2.ChFilter_RW | Hepa filter 2 - Filter channel; Modbus HR437 | Write | ||
| PIV | 1961 | SupplyAirFlwSw.Board_RW | Supply air flow switch - Board selected; Modbus HR438 | Write | ||
| PIV | 1962 | SupplyAirFlwSw.Ch_Id_RW | Supply air flow switch - Channel id selected; Modbus HR439 | Write | ||
| PIV | 1963 | RetAirFlwSw.Board_RW | Return air flow switch - Board selected; Modbus HR440 | Write | ||
| PIV | 1964 | RetAirFlwSw.Ch_Id_RW | Return air flow switch - Channel id selected; Modbus HR441 | Write | ||
| PIV | 1965 | AirFlwSw.Board_RW | Air flow switch - Board selected; Modbus HR442 | Write | ||
| PIV | 1966 | AirFlwSw.Ch_Id_RW | Air flow switch - Channel id selected; Modbus HR443 | Write | ||
| PIV | 1967 | AFreezeSw.Board_RW | Antifreeze switch - Board selected; Modbus HR444 | Write | ||
| PIV | 1968 | AFreezeSw.Ch_Id_RW | Antifreeze switch - Channel id selected; Modbus HR445 | Write | ||
| PIV | 1969 | RemOnOff.Board_RW | Remote On/Off - Board selected; Modbus HR446 | Write | ||
| PIV | 1970 | RemOnOff.Ch_Id_RW | Remote On/Off - Channel id selected; Modbus HR447 | Write | ||
| PIV | 1971 | SupplyFanOvld_1.Board_RW | Supply fan overload 1 - Board selected; Modbus HR448 | Write | ||
| PIV | 1972 | SupplyFanOvld_1.Ch_Id_RW | Supply fan overload 1 - Channel id selected; Modbus HR449 | Write | ||
| PIV | 1973 | RetFanOvld_1.Board_RW | Return fan overload 1 - Board selected; Modbus HR450 | Write | ||
| PIV | 1974 | RetFanOvld_1.Ch_Id_RW | Return fan overload 1 - Channel id selected; Modbus HR451 | Write | ||
| PIV | 1975 | SupplyFanOvld_2.Board_RW | Supply fan overload 2 - Board selected; Modbus HR452 | Write | ||
| PIV | 1976 | SupplyFanOvld_2.Ch_Id_RW | Supply fan overload 2 - Channel id selected; Modbus HR453 | Write | ||
| PIV | 1977 | RetFanOvld_2.Board_RW | Return fan overload 2 - Board selected; Modbus HR454 | Write | ||
| PIV | 1978 | RetFanOvld_2.Ch_Id_RW | Return fan overload 2 - Channel id selected; Modbus HR455 | Write | ||
| PIV | 1979 | SupplyFanInvAlrm.Board_RW | Supply inverter alarm - Board selected; Modbus HR456 | Write | ||
| PIV | 1980 | SupplyFanInvAlrm.Ch_Id_RW | Supply inverter alarm - Channel id selected; Modbus HR457 | Write | ||
| PIV | 1981 | RetFanInvAlrm.Board_RW | Return inverter alarm - Board selected; Modbus HR458 | Write | ||
| PIV | 1982 | RetFanInvAlrm.Ch_Id_RW | Return inverter alarm - Channel id selected; Modbus HR459 | Write | ||
| PIV | 1983 | FansOvld.Board_RW | Fans overload - Board selected; Modbus HR460 | Write | ||
| PIV | 1984 | FansOvld.Ch_Id_RW | Fans overload - Channel id selected; Modbus HR461 | Write | ||
| PIV | 1985 | CompOvld.Board_RW | Compressor overload - Board selected; Modbus HR462 | Write | ||
| PIV | 1986 | CompOvld.Ch_Id_RW | Compressor overload - Channel id selected; Modbus HR463 | Write | ||
| PIV | 1987 | HiPSw.Board_RW | High discharge pressure switch - Board selected; Modbus HR464 | Write | ||
| PIV | 1988 | HiPSw.Ch_Id_RW | High discharge pressure switch - Channel id selected; Modbus HR465 | Write | ||
| PIV | 1989 | LowPSw.Board_RW | Low suction pressure switch - Board selected; Modbus HR466 | Write | ||
| PIV | 1990 | LowPSw.Ch_Id_RW | Low suction pressure switch - Channel id selected; Modbus HR467 | Write | ||
| PIV | 1991 | RecoveryOvld.Board_RW | Thermal wheel overload - Board selected; Modbus HR468 | Write | ||
| PIV | 1992 | RecoveryOvld.Ch_Id_RW | Thermal wheel overload - Channel id selected; Modbus HR469 | Write | ||
| PIV | 1993 | SrsAlrm.Board_RW | Serious alarm - Board selected; Modbus HR470 | Write | ||
| PIV | 1994 | SrsAlrm.Ch_Id_RW | Serious alarm - Channel id selected; Modbus HR471 | Write | ||
| PIV | 1995 | GenAlrm.Board_RW | Generic alarm - Board selected; Modbus HR472 | Write | ||
| PIV | 1996 | GenAlrm.Ch_Id_RW | Generic alarm - Channel id selected; Modbus HR473 | Write | ||
| PIV | 1997 | GenWarning.Board_RW | Generic warning - Board selected; Modbus HR474 | Write | ||
| PIV | 1998 | GenWarning.Ch_Id_RW | Generic warning - Channel id selected; Modbus HR475 | Write | ||
| PIV | 1999 | FiltAlrm.Board_RW | Filters alarm - Board selected; Modbus HR476 | Write | ||
| PIV | 2000 | FiltAlrm.Ch_Id_RW | Filters alarm - Channel id selected; Modbus HR477 | Write | ||
| PIV | 2001 | SupplyFiltAlrm_1.Board_RW | Supply filter alarm 1 - Board selected; Modbus HR478 | Write | ||
| PIV | 2002 | SupplyFiltAlrm_1.Ch_Id_RW | Supply filter alarm 1 - Channel id selected; Modbus HR479 | Write | ||
| PIV | 2003 | SupplyFiltAlrm_2.Board_RW | Supply filter alarm 2 - Board selected; Modbus HR480 | Write | ||
| PIV | 2004 | SupplyFiltAlrm_2.Ch_Id_RW | Supply filter alarm 2 - Channel id selected; Modbus HR481 | Write | ||
| PIV | 2005 | RetFiltAlrm.Board_RW | Return filter alarm - Board selected; Modbus HR482 | Write | ||
| PIV | 2006 | RetFiltAlrm.Ch_Id_RW | Return filter alarm - Channel id selected; Modbus HR483 | Write | ||
| PIV | 2007 | HumAlrm.Board_RW | Humidifier alarm - Board selected; Modbus HR484 | Write | ||
| PIV | 2008 | HumAlrm.Ch_Id_RW | Humidifier alarm - Channel id selected; Modbus HR485 | Write | ||
| PIV | 2009 | MainCoilPmp1_Ovld.Board_RW | Main coil pump 1 overload - Board selected; Modbus HR486 | Write | ||
| PIV | 2010 | MainCoilPmp1_Ovld.Ch_Id_RW | Main coil pump 1 overload - Channel id selected; Modbus HR487 | Write | ||
| PIV | 2011 | MainCoilPmp2_Ovld.Board_RW | Main coil pump 2 overload - Board selected; Modbus HR488 | Write | ||
| PIV | 2012 | MainCoilPmp2_Ovld.Ch_Id_RW | Main coil pump 2 overload - Channel id selected; Modbus HR489 | Write | ||
| PIV | 2013 | ReHeatCoilPmp1_Ovld.Board_RW | ReHeat coil pump 1 overload - Board selected; Modbus HR490 | Write | ||
| PIV | 2014 | ReHeatCoilPmp1_Ovld.Ch_Id_RW | ReHeat coil pump 1 overload - Channel id selected; Modbus HR491 | Write | ||
| PIV | 2015 | ReHeatCoilPmp2_Ovld.Board_RW | ReHeat coil pump 2 overload - Board selected; Modbus HR492 | Write | ||
| PIV | 2016 | ReHeatCoilPmp2_Ovld.Ch_Id_RW | ReHeat coil pump 2 overload - Channel id selected; Modbus HR493 | Write | ||
| PIV | 2017 | PreHeatCoilPmp1_Ovld.Board_RW | PreHeat coil pump 1 overload - Board selected; Modbus HR494 | Write | ||
| PIV | 2018 | PreHeatCoilPmp1_Ovld.Ch_Id_RW | PreHeat coil pump 1 overload - Channel id selected; Modbus HR495 | Write | ||
| PIV | 2019 | PreHeatCoilPmp2_Ovld.Board_RW | PreHeat coil pump 2 overload - Board selected; Modbus HR496 | Write | ||
| PIV | 2020 | PreHeatCoilPmp2_Ovld.Ch_Id_RW | PreHeat coil pump 2 overload - Channel id selected; Modbus HR497 | Write | ||
| PIV | 2021 | OA_CoilPmp1_Ovld.Board_RW | Outdoor air pre-treatment coil pump 1 overload - Board selected; Modbus HR498 | Write | ||
| PIV | 2022 | OA_CoilPmp1_Ovld.Ch_Id_RW | Outdoor air pre-treatment coil pump 1 overload - Channel id selected; Modbus HR499 | Write | ||
| PIV | 2023 | OA_CoilPmp2_Ovld.Board_RW | Outdoor air pre-treatment coil pump 2 overload - Board selected; Modbus HR500 | Write | ||
| PIV | 2024 | OA_CoilPmp2_Ovld.Ch_Id_RW | Outdoor air pre-treatment coil pump 2 overload - Channel id selected; Modbus HR501 | Write | ||
| PIV | 2025 | FreshAirDampSw.Board_RW | Fresh air damper switch - Board selected; Modbus HR502 | Write | ||
| PIV | 2026 | FreshAirDampSw.Ch_Id_RW | Fresh air damper switch - Channel id selected; Modbus HR503 | Write | ||
| PIV | 2027 | SupplyDamperSw.Board_RW | Supply damper switch - Board selected; Modbus HR504 | Write | ||
| PIV | 2028 | SupplyDamperSw.Ch_Id_RW | Supply damper switch - Channel id selected; Modbus HR505 | Write | ||
| PIV | 2029 | RetDampSw.Board_RW | Return damper switch - Board selected; Modbus HR506 | Write | ||
| PIV | 2030 | RetDampSw.Ch_Id_RW | Return damper switch - Channel id selected; Modbus HR507 | Write | ||
| PIV | 2031 | MainCoilFlwSw.Board_RW | Main coil flow switch - Board selected; Modbus HR508 | Write | ||
| PIV | 2032 | MainCoilFlwSw.Ch_Id_RW | Main coil flow switch - Channel id selected; Modbus HR509 | Write | ||
| PIV | 2033 | PreHeatCoilFlwSw.Board_RW | Pre-heating coil flow switch - Board selected; Modbus HR510 | Write | ||
| PIV | 2034 | PreHeatCoilFlwSw.Ch_Id_RW | Pre-heating coil flow switch - Channel id selected; Modbus HR511 | Write | ||
| PIV | 2035 | ReHeatCoilFlwSw.Board_RW | Post-Heating coil flow switch - Board selected; Modbus HR512 | Write | ||
| PIV | 2036 | ReHeatCoilFlwSw.Ch_Id_RW | Post-Heating coil flow switch - Channel id selected; Modbus HR513 | Write | ||
| PIV | 2037 | OA_CoilFlwSw.Board_RW | Outdoor air pre-treatment coil flow switch - Board selected; Modbus HR514 | Write | ||
| PIV | 2038 | OA_CoilFlwSw.Ch_Id_RW | Outdoor air pre-treatment coil flow switch - Channel id selected; Modbus HR515 | Write | ||
| PIV | 2039 | RecoveryClogged.Board_RW | Recovery clogged - Board selected; Modbus HR516 | Write | ||
| PIV | 2040 | RecoveryClogged.Ch_Id_RW | Recovery clogged - Channel id selected; Modbus HR517 | Write | ||
| PIV | 2041 | ReHeatAlrm.Board_RW | Re-heating alarm - Board selected; Modbus HR518 | Write | ||
| PIV | 2042 | ReHeatAlrm.Ch_Id_RW | Re-heating alarm - Channel id selected; Modbus HR519 | Write | ||
| PIV | 2043 | PreHeatAlrm.Board_RW | Pre-heating alarm - Board selected; Modbus HR520 | Write | ||
| PIV | 2044 | PreHeatAlrm.Ch_Id_RW | Pre-heating alarm - Channel id selected; Modbus HR521 | Write | ||
| PIV | 2045 | MainHeatCoilAlrm.Board_RW | Main coil alarm - Board selected; Modbus HR522 | Write | ||
| PIV | 2046 | MainHeatCoilAlrm.Ch_Id_RW | Main coil alarm - Channel id selected; Modbus HR523 | Write | ||
| PIV | 2047 | OA_CoilAlrm.Board_RW | Outdoor air pre-treatment -Heat alarm - Board selected; Modbus HR524 | Write | ||
| PIV | 2048 | OA_CoilAlrm.Ch_Id_RW | Outdoor air pre-treatment -Heat alarm - Channel id selected; Modbus HR525 | Write | ||
| PIV | 2049 | DoorSw.Board_RW | Door Switch - Board selected; Modbus HR526 | Write | ||
| PIV | 2050 | DoorSw.Ch_Id_RW | Door Switch - Channel id selected; Modbus HR527 | Write | ||
| PIV | 2051 | FireSmokeAlrm.Board_RW | Fire/Smoke alarm - Board selected; Modbus HR528 | Write | ||
| PIV | 2052 | FireSmokeAlrm.Ch_Id_RW | Fire/Smoke alarm - Channel id selected; Modbus HR529 | Write | ||
| PIV | 2053 | FiremanOverrideSw.Board_RW | Fireman override switch - Board selected; Modbus HR530 | Write | ||
| PIV | 2054 | FiremanOverrideSw.Ch_Id_RW | Fireman override switch - Channel id selected; Modbus HR531 | Write | ||
| PIV | 2055 | SummerWinterModeByDin.Board_RW | Summer/Winter mode by digital input - Board selected; Modbus HR532 | Write | ||
| PIV | 2056 | SummerWinterModeByDin.Ch_Id_RW | Summer/Winter mode by digital input - Channel id selected; Modbus HR533 | Write | ||
| PIV | 2057 | Din_SetP.Board_RW | Setpoint by digital input - Board selected; Modbus HR534 | Write | ||
| PIV | 2058 | Din_SetP.Ch_Id_RW | Setpoint by digital input - Channel id selected; Modbus HR535 | Write | ||
| PIV | 2059 | Eco_Mode.Board_RW | Eco mode - Board selected; Modbus HR536 | Write | ||
| PIV | 2060 | Eco_Mode.Ch_Id_RW | Eco mode - Channel id selected; Modbus HR537 | Write | ||
| PIV | 2061 | PreComf_Mode.Board_RW | Precomfort mode - Board selected; Modbus HR538 | Write | ||
| PIV | 2062 | PreComf_Mode.Ch_Id_RW | Precomfort mode - Channel id selected; Modbus HR539 | Write | ||
| PIV | 2063 | Comf_Mode.Board_RW | Comfort mode - Board selected; Modbus HR540 | Write | ||
| PIV | 2064 | Comf_Mode.Ch_Id_RW | Comfort mode - Channel id selected; Modbus HR541 | Write | ||
| PIV | 2065 | AuxDin_1.Board_RW | Auxiliary digital input 1 - Board selected; Modbus HR542 | Write | ||
| PIV | 2066 | AuxDin_1.Ch_Id_RW | Auxiliary digital input 1 - Channel id selected; Modbus HR543 | Write | ||
| PIV | 2067 | AuxDin_2.Board_RW | Auxiliary digital input 2 - Board selected; Modbus HR544 | Write | ||
| PIV | 2068 | AuxDin_2.Ch_Id_RW | Auxiliary digital input 2 - Channel id selected; Modbus HR545 | Write | ||
| PIV | 2069 | AuxDin_3.Board_RW | Auxiliary digital input 3 - Board selected; Modbus HR546 | Write | ||
| PIV | 2070 | AuxDin_3.Ch_Id_RW | Auxiliary digital input 3 - Channel id selected; Modbus HR547 | Write | ||
| PIV | 2071 | AuxDin_4.Board_RW | Auxiliary digital input 4 - Board selected; Modbus HR548 | Write | ||
| PIV | 2072 | AuxDin_4.Ch_Id_RW | Auxiliary digital input 4 - Channel id selected; Modbus HR549 | Write | ||
| PIV | 2073 | DfrHeatExch_Din.Board_RW | Heat exchanger defrost by Din - Board selected; Modbus HR550 | Write | ||
| PIV | 2074 | DfrHeatExch_Din.Ch_Id_RW | Heat exchanger defrost by Din - Channel id selected; Modbus HR551 | Write | ||
| PIV | 2075 | BypassDamp_Dout.Board_RW | Bypass damper - Board selected; Modbus HR552 | Write | ||
| PIV | 2076 | BypassDamp_Dout.Ch_Id_RW | Bypass damper - Channel id selected; Modbus HR553 | Write | ||
| PIV | 2077 | BypassDamp_Dout.T_On_RW | Bypass damper - Time on cycle relay; Modbus HR554 | Write | ||
| PIV | 2078 | BypassDamp_Dout.T_Off_RW | Bypass damper - Time off cycle releay; Modbus HR555 | Write | ||
| PIV | 2079 | BypassDamp_Dout.Ch_Type_RW | Bypass damper - Digital output type; Modbus HR556 | Write | ||
| PIV | 2080 | BypassDamp_Open.Board_RW | Bypass damper floating (open) - Board selected; Modbus HR557 | Write | ||
| PIV | 2081 | BypassDamp_Open.Ch_Id_RW | Bypass damper floating (open) - Channel id selected; Modbus HR558 | Write | ||
| PIV | 2082 | BypassDamp_Open.T_On_RW | Bypass damper floating (open) - Time on cycle relay; Modbus HR559 | Write | ||
| PIV | 2083 | BypassDamp_Open.T_Off_RW | Bypass damper floating (open) - Time off cycle releay; Modbus HR560 | Write | ||
| PIV | 2084 | BypassDamp_Open.Ch_Type_RW | Bypass damper floating (open) - Digital output type; Modbus HR561 | Write | ||
| PIV | 2085 | BypassDamp_Close.Board_RW | Bypass damper floating (close) - Board selected; Modbus HR562 | Write | ||
| PIV | 2086 | BypassDamp_Close.Ch_Id_RW | Bypass damper floating (close) - Channel id selected; Modbus HR563 | Write | ||
| PIV | 2087 | BypassDamp_Close.T_On_RW | Bypass damper floating (close) - Time on cycle relay; Modbus HR564 | Write | ||
| PIV | 2088 | BypassDamp_Close.T_Off_RW | Bypass damper floating (close) - Time off cycle releay; Modbus HR565 | Write | ||
| PIV | 2089 | BypassDamp_Close.Ch_Type_RW | Bypass damper floating (close) - Digital output type; Modbus HR566 | Write | ||
| PIV | 2090 | FreshAirDamp_Dout.Board_RW | Fresh air damper - Board selected; Modbus HR567 | Write | ||
| PIV | 2091 | FreshAirDamp_Dout.Ch_Id_RW | Fresh air damper - Channel id selected; Modbus HR568 | Write | ||
| PIV | 2092 | FreshAirDamp_Dout.T_On_RW | Fresh air damper - Time on cycle relay; Modbus HR569 | Write | ||
| PIV | 2093 | FreshAirDamp_Dout.T_Off_RW | Fresh air damper - Time off cycle releay; Modbus HR570 | Write | ||
| PIV | 2094 | FreshAirDamp_Dout.Ch_Type_RW | Fresh air damper - Digital output type; Modbus HR571 | Write | ||
| PIV | 2095 | ExhAirDamp_Dout.Board_RW | Exhaust air damper - Board selected; Modbus HR572 | Write | ||
| PIV | 2096 | ExhAirDamp_Dout.Ch_Id_RW | Exhaust air damper - Channel id selected; Modbus HR573 | Write | ||
| PIV | 2097 | ExhAirDamp_Dout.T_On_RW | Exhaust air damper - Time on cycle relay; Modbus HR574 | Write | ||
| PIV | 2098 | ExhAirDamp_Dout.T_Off_RW | Exhaust air damper - Time off cycle releay; Modbus HR575 | Write | ||
| PIV | 2099 | ExhAirDamp_Dout.Ch_Type_RW | Exhaust air damper - Digital output type; Modbus HR576 | Write | ||
| PIV | 2100 | MixingDamp_Dout.Board_RW | Mixing damper - Board selected; Modbus HR577 | Write | ||
| PIV | 2101 | MixingDamp_Dout.Ch_Id_RW | Mixing damper - Channel id selected; Modbus HR578 | Write | ||
| PIV | 2102 | MixingDamp_Dout.T_On_RW | Mixing damper - Time on cycle relay; Modbus HR579 | Write | ||
| PIV | 2103 | MixingDamp_Dout.T_Off_RW | Mixing damper - Time off cycle releay; Modbus HR580 | Write | ||
| PIV | 2104 | MixingDamp_Dout.Ch_Type_RW | Mixing damper - Digital output type; Modbus HR581 | Write | ||
| PIV | 2105 | SupplyAirDamp_Dout.Board_RW | Supply air damper - Board selected; Modbus HR582 | Write | ||
| PIV | 2106 | SupplyAirDamp_Dout.Ch_Id_RW | Supply air damper - Channel id selected; Modbus HR583 | Write | ||
| PIV | 2107 | SupplyAirDamp_Dout.T_On_RW | Supply air damper - Time on cycle relay; Modbus HR584 | Write | ||
| PIV | 2108 | SupplyAirDamp_Dout.T_Off_RW | Supply air damper - Time off cycle releay; Modbus HR585 | Write | ||
| PIV | 2109 | SupplyAirDamp_Dout.Ch_Type_RW | Supply air damper - Digital output type; Modbus HR586 | Write | ||
| PIV | 2110 | RetAirDamp_Dout.Board_RW | Return air damper - Board selected; Modbus HR587 | Write | ||
| PIV | 2111 | RetAirDamp_Dout.Ch_Id_RW | Return air damper - Channel id selected; Modbus HR588 | Write | ||
| PIV | 2112 | RetAirDamp_Dout.T_On_RW | Return air damper - Time on cycle relay; Modbus HR589 | Write | ||
| PIV | 2113 | RetAirDamp_Dout.T_Off_RW | Return air damper - Time off cycle releay; Modbus HR590 | Write | ||
| PIV | 2114 | RetAirDamp_Dout.Ch_Type_RW | Return air damper - Digital output type; Modbus HR591 | Write | ||
| PIV | 2115 | MixingDamp_Open.Board_RW | Mixing damper floating (OPEN) - Board selected; Modbus HR592 | Write | ||
| PIV | 2116 | MixingDamp_Open.Ch_Id_RW | Mixing damper floating (OPEN) - Channel id selected; Modbus HR593 | Write | ||
| PIV | 2117 | MixingDamp_Open.T_On_RW | Mixing damper floating (OPEN) - Time on cycle relay; Modbus HR594 | Write | ||
| PIV | 2118 | MixingDamp_Open.T_Off_RW | Mixing damper floating (OPEN) - Time off cycle releay; Modbus HR595 | Write | ||
| PIV | 2119 | MixingDamp_Open.Ch_Type_RW | Mixing damper floating (OPEN) - Digital output type; Modbus HR596 | Write | ||
| PIV | 2120 | MixingDamp_Close.Board_RW | Mixing damper floating (CLOSE) - Board selected; Modbus HR597 | Write | ||
| PIV | 2121 | MixingDamp_Close.Ch_Id_RW | Mixing damper floating (CLOSE) - Channel id selected; Modbus HR598 | Write | ||
| PIV | 2122 | MixingDamp_Close.T_On_RW | Mixing damper floating (CLOSE) - Time on cycle relay; Modbus HR599 | Write | ||
| PIV | 2123 | MixingDamp_Close.T_Off_RW | Mixing damper floating (CLOSE) - Time off cycle releay; Modbus HR600 | Write | ||
| PIV | 2124 | MixingDamp_Close.Ch_Type_RW | Mixing damper floating (CLOSE) - Digital output type; Modbus HR601 | Write | ||
| PIV | 2125 | SupplyFan_Dout.Board_RW | Supply fan - Board selected; Modbus HR602 | Write | ||
| PIV | 2126 | SupplyFan_Dout.Ch_Id_RW | Supply fan - Channel id selected; Modbus HR603 | Write | ||
| PIV | 2127 | SupplyFan_Dout.T_On_RW | Supply fan - Time on cycle relay; Modbus HR604 | Write | ||
| PIV | 2128 | SupplyFan_Dout.T_Off_RW | Supply fan - Time off cycle releay; Modbus HR605 | Write | ||
| PIV | 2129 | SupplyFan_Dout.Ch_Type_RW | Supply fan - Digital output type; Modbus HR606 | Write | ||
| PIV | 2130 | RetFan_Dout.Board_RW | Return fan - Board selected; Modbus HR607 | Write | ||
| PIV | 2131 | RetFan_Dout.Ch_Id_RW | Return fan - Channel id selected; Modbus HR608 | Write | ||
| PIV | 2132 | RetFan_Dout.T_On_RW | Return fan - Time on cycle relay; Modbus HR609 | Write | ||
| PIV | 2133 | RetFan_Dout.T_Off_RW | Return fan - Time off cycle releay; Modbus HR610 | Write | ||
| PIV | 2134 | RetFan_Dout.Ch_Type_RW | Return fan - Digital output type; Modbus HR611 | Write | ||
| PIV | 2135 | SupplyFan2_Dout.Board_RW | Supply fan 2 - Board selected; Modbus HR612 | Write | ||
| PIV | 2136 | SupplyFan2_Dout.Ch_Id_RW | Supply fan 2 - Channel id selected; Modbus HR613 | Write | ||
| PIV | 2137 | SupplyFan2_Dout.T_On_RW | Supply fan 2 - Time on cycle relay; Modbus HR614 | Write | ||
| PIV | 2138 | SupplyFan2_Dout.T_Off_RW | Supply fan 2 - Time off cycle releay; Modbus HR615 | Write | ||
| PIV | 2139 | SupplyFan2_Dout.Ch_Type_RW | Supply fan 2 - Digital output type; Modbus HR616 | Write | ||
| PIV | 2140 | RetFan2_Dout.Board_RW | Return fan 2 - Board selected; Modbus HR617 | Write | ||
| PIV | 2141 | RetFan2_Dout.Ch_Id_RW | Return fan 2 - Channel id selected; Modbus HR618 | Write | ||
| PIV | 2142 | RetFan2_Dout.T_On_RW | Return fan 2 - Time on cycle relay; Modbus HR619 | Write | ||
| PIV | 2143 | RetFan2_Dout.T_Off_RW | Return fan 2 - Time off cycle releay; Modbus HR620 | Write | ||
| PIV | 2144 | RetFan2_Dout.Ch_Type_RW | Return fan 2 - Digital output type; Modbus HR621 | Write | ||
| PIV | 2145 | Comp_Dout.Board_RW | Compressor - Board selected; Modbus HR622 | Write | ||
| PIV | 2146 | Comp_Dout.Ch_Id_RW | Compressor - Channel id selected; Modbus HR623 | Write | ||
| PIV | 2147 | Comp_Dout.T_On_RW | Compressor - Time on cycle relay; Modbus HR624 | Write | ||
| PIV | 2148 | Comp_Dout.T_Off_RW | Compressor - Time off cycle releay; Modbus HR625 | Write | ||
| PIV | 2149 | Comp_Dout.Ch_Type_RW | Compressor - Digital output type; Modbus HR626 | Write | ||
| PIV | 2150 | RevVlv.Board_RW | Reverse valve - Board selected; Modbus HR627 | Write | ||
| PIV | 2151 | RevVlv.Ch_Id_RW | Reverse valve - Channel id selected; Modbus HR628 | Write | ||
| PIV | 2152 | RevVlv.T_On_RW | Reverse valve - Time on cycle relay; Modbus HR629 | Write | ||
| PIV | 2153 | RevVlv.T_Off_RW | Reverse valve - Time off cycle releay; Modbus HR630 | Write | ||
| PIV | 2154 | RevVlv.Ch_Type_RW | Reverse valve - Digital output type; Modbus HR631 | Write | ||
| PIV | 2155 | UnitOnOff_Dout.Board_RW | Unit status (On/Off) - Board selected; Modbus HR632 | Write | ||
| PIV | 2156 | UnitOnOff_Dout.Ch_Id_RW | Unit status (On/Off ) - Channel id selected; Modbus HR633 | Write | ||
| PIV | 2157 | UnitOnOff_Dout.T_On_RW | Unit status (On/Off ) - Time on cycle relay; Modbus HR634 | Write | ||
| PIV | 2158 | UnitOnOff_Dout.T_Off_RW | Unit status (On/Off ) - Time off cycle releay; Modbus HR635 | Write | ||
| PIV | 2159 | UnitOnOff_Dout.Ch_Type_RW | Unit status (On/Off ) - Digital output type; Modbus HR636 | Write | ||
| PIV | 2160 | CoolHeat_Dout.Board_RW | Cool/Heat status - Board selected; Modbus HR637 | Write | ||
| PIV | 2161 | CoolHeat_Dout.Ch_Id_RW | Cool/Heat status - Channel id selected; Modbus HR638 | Write | ||
| PIV | 2162 | CoolHeat_Dout.T_On_RW | Cool/Heat status - Time on cycle relay; Modbus HR639 | Write | ||
| PIV | 2163 | CoolHeat_Dout.T_Off_RW | Cool/Heat status - Time off cycle releay; Modbus HR640 | Write | ||
| PIV | 2164 | CoolHeat_Dout.Ch_Type_RW | Cool/Heat status - Digital output type; Modbus HR641 | Write | ||
| PIV | 2167 | GlobalAlrm_Dout.T_On_RW | Generic alarm info - Time on cycle relay; Modbus HR644 | Write | ||
| PIV | 2168 | GlobalAlrm_Dout.T_Off_RW | Generic alarm info - Time off cycle releay; Modbus HR645 | Write | ||
| PIV | 2169 | GlobalAlrm_Dout.Ch_Type_RW | Generic alarm info - Digital output type; Modbus HR646 | Write | ||
| PIV | 2170 | LightAlrm_Dout.Board_RW | Light alarm info - Board selected; Modbus HR647 | Write | ||
| PIV | 2171 | LightAlrm_Dout.Ch_Id_RW | Light alarm info - Channel id selected; Modbus HR648 | Write | ||
| PIV | 2172 | LightAlrm_Dout.T_On_RW | Light alarm info - Time on cycle relay; Modbus HR649 | Write | ||
| PIV | 2173 | LightAlrm_Dout.T_Off_RW | Light alarm info - Time off cycle releay; Modbus HR650 | Write | ||
| PIV | 2174 | LightAlrm_Dout.Ch_Type_RW | Light alarm info - Digital output type; Modbus HR651 | Write | ||
| PIV | 2175 | SrsAlrm_Dout.Board_RW | Serious alarm info - Board selected; Modbus HR652 | Write | ||
| PIV | 2176 | SrsAlrm_Dout.Ch_Id_RW | Serious alarm info - Channel id selected; Modbus HR653 | Write | ||
| PIV | 2177 | SrsAlrm_Dout.T_On_RW | Serious alarm info - Time on cycle relay; Modbus HR654 | Write | ||
| PIV | 2178 | SrsAlrm_Dout.T_Off_RW | Serious alarm info - Time off cycle releay; Modbus HR655 | Write | ||
| PIV | 2179 | SrsAlrm_Dout.Ch_Type_RW | Serious alarm info - Digital output type; Modbus HR656 | Write | ||
| PIV | 2180 | Humidifier.Board_RW | Humidifier - Board selected; Modbus HR657 | Write | ||
| PIV | 2181 | Humidifier.Ch_Id_RW | Humidifier - Channel id selected; Modbus HR658 | Write | ||
| PIV | 2182 | Humidifier.T_On_RW | Humidifier - Time on cycle relay; Modbus HR659 | Write | ||
| PIV | 2183 | Humidifier.T_Off_RW | Humidifier - Time off cycle releay; Modbus HR660 | Write | ||
| PIV | 2184 | Humidifier.Ch_Type_RW | Humidifier - Digital output type; Modbus HR661 | Write | ||
| PIV | 2185 | AuxOut1_Dout.Board_RW | Auxiliary output 1 - Board selected; Modbus HR662 | Write | ||
| PIV | 2186 | AuxOut1_Dout.Ch_Id_RW | Auxiliary output 1 - Channel id selected; Modbus HR663 | Write | ||
| PIV | 2187 | AuxOut1_Dout.T_On_RW | Auxiliary output 1 - Time on cycle relay; Modbus HR664 | Write | ||
| PIV | 2188 | AuxOut1_Dout.T_Off_RW | Auxiliary output 1 - Time off cycle releay; Modbus HR665 | Write | ||
| PIV | 2189 | AuxOut1_Dout.Ch_Type_RW | Auxiliary output 1 - Digital output type; Modbus HR666 | Write | ||
| PIV | 2190 | AuxOut2_Dout.Board_RW | Auxiliary output 2 - Board selected; Modbus HR667 | Write | ||
| PIV | 2191 | AuxOut2_Dout.Ch_Id_RW | Auxiliary output 2 - Channel id selected; Modbus HR668 | Write | ||
| PIV | 2192 | AuxOut2_Dout.T_On_RW | Auxiliary output 2 - Time on cycle relay; Modbus HR669 | Write | ||
| PIV | 2193 | AuxOut2_Dout.T_Off_RW | Auxiliary output 2 - Time off cycle releay; Modbus HR670 | Write | ||
| PIV | 2194 | AuxOut2_Dout.Ch_Type_RW | Auxiliary output 2 - Digital output type; Modbus HR671 | Write | ||
| PIV | 2195 | AuxOut3_Dout.Board_RW | Auxiliary output 3 - Board selected; Modbus HR672 | Write | ||
| PIV | 2196 | AuxOut3_Dout.Ch_Id_RW | Auxiliary output 3 - Channel id selected; Modbus HR673 | Write | ||
| PIV | 2197 | AuxOut3_Dout.T_On_RW | Auxiliary output 3 - Time on cycle relay; Modbus HR674 | Write | ||
| PIV | 2198 | AuxOut3_Dout.T_Off_RW | Auxiliary output 3 - Time off cycle releay; Modbus HR675 | Write | ||
| PIV | 2199 | AuxOut3_Dout.Ch_Type_RW | Auxiliary output 3 - Digital output type; Modbus HR676 | Write | ||
| PIV | 2200 | AuxOut4_Dout.Board_RW | Auxiliary output 4 - Board selected; Modbus HR677 | Write | ||
| PIV | 2201 | AuxOut4_Dout.Ch_Id_RW | Auxiliary output 4 - Channel id selected; Modbus HR678 | Write | ||
| PIV | 2202 | AuxOut4_Dout.T_On_RW | Auxiliary output 4 - Time on cycle relay; Modbus HR679 | Write | ||
| PIV | 2203 | AuxOut4_Dout.T_Off_RW | Auxiliary output 4 - Time off cycle releay; Modbus HR680 | Write | ||
| PIV | 2204 | AuxOut4_Dout.Ch_Type_RW | Auxiliary output 4 - Digital output type; Modbus HR681 | Write | ||
| PIV | 2205 | MainVlv_Open.Board_RW | Main floating valve open - Board selected; Modbus HR682 | Write | ||
| PIV | 2206 | MainVlv_Open.Ch_Id_RW | Main floating valve open - Channel id selected; Modbus HR683 | Write | ||
| PIV | 2207 | MainVlv_Open.T_On_RW | Main floating valve open - Time on cycle relay; Modbus HR684 | Write | ||
| PIV | 2208 | MainVlv_Open.T_Off_RW | Main floating valve open - Time off cycle releay; Modbus HR685 | Write | ||
| PIV | 2209 | MainVlv_Open.Ch_Type_RW | Main floating valve open - Digital output type; Modbus HR686 | Write | ||
| PIV | 2210 | PreHeatVlv_Open.Board_RW | Pre-heating floating valve open - Board selected; Modbus HR687 | Write | ||
| PIV | 2211 | PreHeatVlv_Open.Ch_Id_RW | Pre-heating floating valve open - Channel id selected; Modbus HR688 | Write | ||
| PIV | 2212 | PreHeatVlv_Open.T_On_RW | Pre-heating floating valve open - Time on cycle relay; Modbus HR689 | Write | ||
| PIV | 2213 | PreHeatVlv_Open.T_Off_RW | Pre-heating floating valve open - Time off cycle releay; Modbus HR690 | Write | ||
| PIV | 2214 | PreHeatVlv_Open.Ch_Type_RW | Pre-heating floating valve open - Digital output type; Modbus HR691 | Write | ||
| PIV | 2215 | ReHeatVlv_Open.Board_RW | Re-Heating floating valve open - Board selected; Modbus HR692 | Write | ||
| PIV | 2216 | ReHeatVlv_Open.Ch_Id_RW | Re-Heating floating valve open - Channel id selected; Modbus HR693 | Write | ||
| PIV | 2217 | ReHeatVlv_Open.T_On_RW | Re-Heating floating valve open - Time on cycle relay; Modbus HR694 | Write | ||
| PIV | 2218 | ReHeatVlv_Open.T_Off_RW | Re-Heating floating valve open - Time off cycle releay; Modbus HR695 | Write | ||
| PIV | 2219 | ReHeatVlv_Open.Ch_Type_RW | Re-Heating floating valve open - Digital output type; Modbus HR696 | Write | ||
| PIV | 2220 | MainVlv_Close.Board_RW | Main floating valve close - Board selected; Modbus HR697 | Write | ||
| PIV | 2221 | MainVlv_Close.Ch_Id_RW | Main floating valve close - Channel id selected; Modbus HR698 | Write | ||
| PIV | 2222 | MainVlv_Close.T_On_RW | Main floating valve close - Time on cycle relay; Modbus HR699 | Write | ||
| PIV | 2223 | MainVlv_Close.T_Off_RW | Main floating valve close - Time off cycle releay; Modbus HR700 | Write | ||
| PIV | 2224 | MainVlv_Close.Ch_Type_RW | Main floating valve close - Digital output type; Modbus HR701 | Write | ||
| PIV | 2225 | PreHeatVlv_Close.Board_RW | Pre-heating floating valve close - Board selected; Modbus HR702 | Write | ||
| PIV | 2226 | PreHeatVlv_Close.Ch_Id_RW | Pre-heating floating valve close - Channel id selected; Modbus HR703 | Write | ||
| PIV | 2227 | PreHeatVlv_Close.T_On_RW | Pre-heating floating valve close - Time on cycle relay; Modbus HR704 | Write | ||
| PIV | 2228 | PreHeatVlv_Close.T_Off_RW | Pre-heating floating valve close - Time off cycle releay; Modbus HR705 | Write | ||
| PIV | 2229 | PreHeatVlv_Close.Ch_Type_RW | Pre-heating floating valve close - Digital output type; Modbus HR706 | Write | ||
| PIV | 2230 | ReHeatVlv_Close.Board_RW | Re-Heating floating valve close - Board selected; Modbus HR707 | Write | ||
| PIV | 2231 | ReHeatVlv_Close.Ch_Id_RW | Re-Heating floating valve close - Channel id selected; Modbus HR708 | Write | ||
| PIV | 2232 | ReHeatVlv_Close.T_On_RW | Re-Heating floating valve close - Time on cycle relay; Modbus HR709 | Write | ||
| PIV | 2233 | ReHeatVlv_Close.T_Off_RW | Re-Heating floating valve close - Time off cycle releay; Modbus HR710 | Write | ||
| PIV | 2234 | ReHeatVlv_Close.Ch_Type_RW | Re-Heating floating valve close - Digital output type; Modbus HR711 | Write | ||
| PIV | 2235 | MainCoil_Step1.Board_RW | Main step 1 - Board selected; Modbus HR712 | Write | ||
| PIV | 2236 | MainCoil_Step1.Ch_Id_RW | Main step 1 - Channel id selected; Modbus HR713 | Write | ||
| PIV | 2237 | MainCoil_Step1.T_On_RW | Main step 1 - Time on cycle relay; Modbus HR714 | Write | ||
| PIV | 2238 | MainCoil_Step1.T_Off_RW | Main step 1 - Time off cycle releay; Modbus HR715 | Write | ||
| PIV | 2239 | MainCoil_Step1.Ch_Type_RW | Main step 1 - Digital output type; Modbus HR716 | Write | ||
| PIV | 2240 | MainCoil_Step2.Board_RW | Main step 2 - Board selected; Modbus HR717 | Write | ||
| PIV | 2241 | MainCoil_Step2.Ch_Id_RW | Main step 2 - Channel id selected; Modbus HR718 | Write | ||
| PIV | 2242 | MainCoil_Step2.T_On_RW | Main step 2 - Time on cycle relay; Modbus HR719 | Write | ||
| PIV | 2243 | MainCoil_Step2.T_Off_RW | Main step 2 - Time off cycle releay; Modbus HR720 | Write | ||
| PIV | 2244 | MainCoil_Step2.Ch_Type_RW | Main step 2 - Digital output type; Modbus HR721 | Write | ||
| PIV | 2245 | MainCoil_Step3.Board_RW | Main step 3 - Board selected; Modbus HR722 | Write | ||
| PIV | 2246 | MainCoil_Step3.Ch_Id_RW | Main step 3 - Channel id selected; Modbus HR723 | Write | ||
| PIV | 2247 | MainCoil_Step3.T_On_RW | Main step 3 - Time on cycle relay; Modbus HR724 | Write | ||
| PIV | 2248 | MainCoil_Step3.T_Off_RW | Main step 3 - Time off cycle releay; Modbus HR725 | Write | ||
| PIV | 2249 | MainCoil_Step3.Ch_Type_RW | Main step 3 - Digital output type; Modbus HR726 | Write | ||
| PIV | 2250 | MainCoil_Step4.Board_RW | Main step 4 - Board selected; Modbus HR727 | Write | ||
| PIV | 2251 | MainCoil_Step4.Ch_Id_RW | Main step 4 - Channel id selected; Modbus HR728 | Write | ||
| PIV | 2252 | MainCoil_Step4.T_On_RW | Main step 4 - Time on cycle relay; Modbus HR729 | Write | ||
| PIV | 2253 | MainCoil_Step4.T_Off_RW | Main step 4 - Time off cycle releay; Modbus HR730 | Write | ||
| PIV | 2254 | MainCoil_Step4.Ch_Type_RW | Main step 4 - Digital output type; Modbus HR731 | Write | ||
| PIV | 2255 | ReHeatCoil_Step1.Board_RW | Postheat heater 1 - Board selected; Modbus HR732 | Write | ||
| PIV | 2256 | ReHeatCoil_Step1.Ch_Id_RW | Postheat heater 1 - Channel id selected; Modbus HR733 | Write | ||
| PIV | 2257 | ReHeatCoil_Step1.T_On_RW | Postheat heater 1 - Time on cycle relay; Modbus HR734 | Write | ||
| PIV | 2258 | ReHeatCoil_Step1.T_Off_RW | Postheat heater 1 - Time off cycle releay; Modbus HR735 | Write | ||
| PIV | 2259 | ReHeatCoil_Step1.Ch_Type_RW | Postheat heater 1 - Digital output type; Modbus HR736 | Write | ||
| PIV | 2260 | ReHeatCoil_Step2.Board_RW | Postheat heater 2 - Board selected; Modbus HR737 | Write | ||
| PIV | 2261 | ReHeatCoil_Step2.Ch_Id_RW | Postheat heater 2 - Channel id selected; Modbus HR738 | Write | ||
| PIV | 2262 | ReHeatCoil_Step2.T_On_RW | Postheat heater 2 - Time on cycle relay; Modbus HR739 | Write | ||
| PIV | 2263 | ReHeatCoil_Step2.T_Off_RW | Postheat heater 2 - Time off cycle releay; Modbus HR740 | Write | ||
| PIV | 2264 | ReHeatCoil_Step2.Ch_Type_RW | Postheat heater 2 - Digital output type; Modbus HR741 | Write | ||
| PIV | 2265 | ReHeatCoil_Step3.Board_RW | Postheat heater 3 - Board selected; Modbus HR742 | Write | ||
| PIV | 2266 | ReHeatCoil_Step3.Ch_Id_RW | Postheat heater 3 - Channel id selected; Modbus HR743 | Write | ||
| PIV | 2267 | ReHeatCoil_Step3.T_On_RW | Postheat heater 3 - Time on cycle relay; Modbus HR744 | Write | ||
| PIV | 2268 | ReHeatCoil_Step3.T_Off_RW | Postheat heater 3 - Time off cycle releay; Modbus HR745 | Write | ||
| PIV | 2269 | ReHeatCoil_Step3.Ch_Type_RW | Postheat heater 3 - Digital output type; Modbus HR746 | Write | ||
| PIV | 2270 | ReHeatCoil_Step4.Board_RW | Postheat heater 4 - Board selected; Modbus HR747 | Write | ||
| PIV | 2271 | ReHeatCoil_Step4.Ch_Id_RW | Postheat heater 4 - Channel id selected; Modbus HR748 | Write | ||
| PIV | 2272 | ReHeatCoil_Step4.T_On_RW | Postheat heater 4 - Time on cycle relay; Modbus HR749 | Write | ||
| PIV | 2273 | ReHeatCoil_Step4.T_Off_RW | Postheat heater 4 - Time off cycle releay; Modbus HR750 | Write | ||
| PIV | 2274 | ReHeatCoil_Step4.Ch_Type_RW | Postheat heater 4 - Digital output type; Modbus HR751 | Write | ||
| PIV | 2275 | PreHeatCoil_Step1.Board_RW | Preheat heater 1 - Board selected; Modbus HR752 | Write | ||
| PIV | 2276 | PreHeatCoil_Step1.Ch_Id_RW | Preheat heater 1 - Channel id selected; Modbus HR753 | Write | ||
| PIV | 2277 | PreHeatCoil_Step1.T_On_RW | Preheat heater 1 - Time on cycle relay; Modbus HR754 | Write | ||
| PIV | 2278 | PreHeatCoil_Step1.T_Off_RW | Preheat heater 1 - Time off cycle releay; Modbus HR755 | Write | ||
| PIV | 2279 | PreHeatCoil_Step1.Ch_Type_RW | Preheat heater 1 - Digital output type; Modbus HR756 | Write | ||
| PIV | 2280 | PreHeatCoil_Step2.Board_RW | Preheat heater 2 - Board selected; Modbus HR757 | Write | ||
| PIV | 2281 | PreHeatCoil_Step2.Ch_Id_RW | Preheat heater 2 - Channel id selected; Modbus HR758 | Write | ||
| PIV | 2282 | PreHeatCoil_Step2.T_On_RW | Preheat heater 2 - Time on cycle relay; Modbus HR759 | Write | ||
| PIV | 2283 | PreHeatCoil_Step2.T_Off_RW | Preheat heater 2 - Time off cycle releay; Modbus HR760 | Write | ||
| PIV | 2284 | PreHeatCoil_Step2.Ch_Type_RW | Preheat heater 2 - Digital output type; Modbus HR761 | Write | ||
| PIV | 2285 | PreHeatCoil_Step3.Board_RW | Preheat heater 3 - Board selected; Modbus HR762 | Write | ||
| PIV | 2286 | PreHeatCoil_Step3.Ch_Id_RW | Preheat heater 3 - Channel id selected; Modbus HR763 | Write | ||
| PIV | 2287 | PreHeatCoil_Step3.T_On_RW | Preheat heater 3 - Time on cycle relay; Modbus HR764 | Write | ||
| PIV | 2288 | PreHeatCoil_Step3.T_Off_RW | Preheat heater 3 - Time off cycle releay; Modbus HR765 | Write | ||
| PIV | 2289 | PreHeatCoil_Step3.Ch_Type_RW | Preheat heater 3 - Digital output type; Modbus HR766 | Write | ||
| PIV | 2290 | PreHeatCoil_Step4.Board_RW | Preheat heater 4 - Board selected; Modbus HR767 | Write | ||
| PIV | 2291 | PreHeatCoil_Step4.Ch_Id_RW | Preheat heater 4 - Channel id selected; Modbus HR768 | Write | ||
| PIV | 2292 | PreHeatCoil_Step4.T_On_RW | Preheat heater 4 - Time on cycle relay; Modbus HR769 | Write | ||
| PIV | 2293 | PreHeatCoil_Step4.T_Off_RW | Preheat heater 4 - Time off cycle releay; Modbus HR770 | Write | ||
| PIV | 2294 | PreHeatCoil_Step4.Ch_Type_RW | Preheat heater 4 - Digital output type; Modbus HR771 | Write | ||
| PIV | 2295 | OA_Coil_Step1.Board_RW | Outdoor air pre-treatment heater 1 - Board selected; Modbus HR772 | Write | ||
| PIV | 2296 | OA_Coil_Step1.Ch_Id_RW | Outdoor air pre-treatment heater 1 - Channel id selected; Modbus HR773 | Write | ||
| PIV | 2297 | OA_Coil_Step1.T_On_RW | Outdoor air pre-treatment heater 1 - Time on cycle relay; Modbus HR774 | Write | ||
| PIV | 2298 | OA_Coil_Step1.T_Off_RW | Outdoor air pre-treatment heater 1 - Time off cycle relay; Modbus HR775 | Write | ||
| PIV | 2299 | OA_Coil_Step1.Ch_Type_RW | Outdoor air pre-treatment heater 1 - Digital output type; Modbus HR776 | Write | ||
| PIV | 2300 | OA_Coil_Step2.Board_RW | Outdoor air pre-treatment heater 2 - Board selected; Modbus HR777 | Write | ||
| PIV | 2301 | OA_Coil_Step2.Ch_Id_RW | Outdoor air pre-treatment heater 2 - Channel id selected; Modbus HR778 | Write | ||
| PIV | 2302 | OA_Coil_Step2.T_On_RW | Outdoor air pre-treatment heater 2 - Time on cycle relay; Modbus HR779 | Write | ||
| PIV | 2303 | OA_Coil_Step2.T_Off_RW | Outdoor air pre-treatment heater 2 - Time off cycle relay; Modbus HR780 | Write | ||
| PIV | 2304 | OA_Coil_Step2.Ch_Type_RW | Outdoor air pre-treatment heater 2 - Digital output type; Modbus HR781 | Write | ||
| PIV | 2305 | OA_Coil_Step3.Board_RW | Outdoor air pre-treatment heater 3 - Board selected; Modbus HR782 | Write | ||
| PIV | 2306 | OA_Coil_Step3.Ch_Id_RW | Outdoor air pre-treatment heater 3 - Channel id selected; Modbus HR783 | Write | ||
| PIV | 2307 | OA_Coil_Step3.T_On_RW | Outdoor air pre-treatment heater 3 - Time on cycle relay; Modbus HR784 | Write | ||
| PIV | 2308 | OA_Coil_Step3.T_Off_RW | Outdoor air pre-treatment heater 3 - Time off cycle relay; Modbus HR785 | Write | ||
| PIV | 2309 | OA_Coil_Step3.Ch_Type_RW | Outdoor air pre-treatment heater 3 - Digital output type; Modbus HR786 | Write | ||
| PIV | 2310 | OA_Coil_Step4.Board_RW | Outdoor air pre-treatment heater 4 - Board selected; Modbus HR787 | Write | ||
| PIV | 2311 | OA_Coil_Step4.Ch_Id_RW | Outdoor air pre-treatment heater 4 - Channel id selected; Modbus HR788 | Write | ||
| PIV | 2312 | OA_Coil_Step4.T_On_RW | Outdoor air pre-treatment heater 4 - Time on cycle relay; Modbus HR789 | Write | ||
| PIV | 2313 | OA_Coil_Step4.T_Off_RW | Outdoor air pre-treatment heater 4 - Time off cycle relay; Modbus HR790 | Write | ||
| PIV | 2314 | OA_Coil_Step4.Ch_Type_RW | Outdoor air pre-treatment heater 4 - Digital output type; Modbus HR791 | Write | ||
| PIV | 2315 | PreHeatPmp_1.Board_RW | Pre-Heating pump 1 - Board selected; Modbus HR792 | Write | ||
| PIV | 2316 | PreHeatPmp_1.Ch_Id_RW | Pre-Heating pump 1 - Channel id selected; Modbus HR793 | Write | ||
| PIV | 2317 | PreHeatPmp_1.T_On_RW | Pre-Heating pump 1 - Time on cycle relay; Modbus HR794 | Write | ||
| PIV | 2318 | PreHeatPmp_1.T_Off_RW | Pre-Heating pump 1 - Time off cycle releay; Modbus HR795 | Write | ||
| PIV | 2319 | PreHeatPmp_1.Ch_Type_RW | Pre-Heating pump 1 - Digital output type; Modbus HR796 | Write | ||
| PIV | 2320 | PreHeatPmp_2.Board_RW | Pre-Heating pump 2 - Board selected; Modbus HR797 | Write | ||
| PIV | 2321 | PreHeatPmp_2.Ch_Id_RW | Pre-Heating pump 2 - Channel id selected; Modbus HR798 | Write | ||
| PIV | 2322 | PreHeatPmp_2.T_On_RW | Pre-Heating pump 2 - Time on cycle relay; Modbus HR799 | Write | ||
| PIV | 2323 | PreHeatPmp_2.T_Off_RW | Pre-Heating pump 2 - Time off cycle releay; Modbus HR800 | Write | ||
| PIV | 2324 | PreHeatPmp_2.Ch_Type_RW | Pre-Heating pump 2 - Digital output type; Modbus HR801 | Write | ||
| PIV | 2325 | MainCoilPmp_1.Board_RW | Main pump 1 - Board selected; Modbus HR802 | Write | ||
| PIV | 2326 | MainCoilPmp_1.Ch_Id_RW | Main pump 1 - Channel id selected; Modbus HR803 | Write | ||
| PIV | 2327 | MainCoilPmp_1.T_On_RW | Main pump 1 - Time on cycle relay; Modbus HR804 | Write | ||
| PIV | 2328 | MainCoilPmp_1.T_Off_RW | Main pump 1 - Time off cycle releay; Modbus HR805 | Write | ||
| PIV | 2329 | MainCoilPmp_1.Ch_Type_RW | Main pump 1 - Digital output type; Modbus HR806 | Write | ||
| PIV | 2330 | MainCoilPmp_2.Board_RW | Main pump 2 - Board selected; Modbus HR807 | Write | ||
| PIV | 2331 | MainCoilPmp_2.Ch_Id_RW | Main pump 2 - Channel id selected; Modbus HR808 | Write | ||
| PIV | 2332 | MainCoilPmp_2.T_On_RW | Main pump 2 - Time on cycle relay; Modbus HR809 | Write | ||
| PIV | 2333 | MainCoilPmp_2.T_Off_RW | Main pump 2 - Time off cycle releay; Modbus HR810 | Write | ||
| PIV | 2334 | MainCoilPmp_2.Ch_Type_RW | Main pump 2 - Digital output type; Modbus HR811 | Write | ||
| PIV | 2335 | ReHeatPmp_1.Board_RW | Re-Heating pump 1 - Board selected; Modbus HR812 | Write | ||
| PIV | 2336 | ReHeatPmp_1.Ch_Id_RW | Re-Heating pump 1 - Channel id selected; Modbus HR813 | Write | ||
| PIV | 2337 | ReHeatPmp_1.T_On_RW | Re-Heating pump 1 - Time on cycle relay; Modbus HR814 | Write | ||
| PIV | 2338 | ReHeatPmp_1.T_Off_RW | Re-Heating pump 1 - Time off cycle releay; Modbus HR815 | Write | ||
| PIV | 2339 | ReHeatPmp_1.Ch_Type_RW | Re-Heating pump 1 - Digital output type; Modbus HR816 | Write | ||
| PIV | 2340 | ReHeatPmp_2.Board_RW | Re-Heating pump 2 - Board selected; Modbus HR817 | Write | ||
| PIV | 2341 | ReHeatPmp_2.Ch_Id_RW | Re-Heating pump 2 - Channel id selected; Modbus HR818 | Write | ||
| PIV | 2342 | ReHeatPmp_2.T_On_RW | Re-Heating pump 2 - Time on cycle relay; Modbus HR819 | Write | ||
| PIV | 2343 | ReHeatPmp_2.T_Off_RW | Re-Heating pump 2 - Time off cycle releay; Modbus HR820 | Write | ||
| PIV | 2344 | ReHeatPmp_2.Ch_Type_RW | Re-Heating pump 2 - Digital output type; Modbus HR821 | Write | ||
| PIV | 2345 | OA_CoilPmp_1.Board_RW | Outdoor air pre-treatment -Heating pump 1 - Board selected; Modbus HR822 | Write | ||
| PIV | 2346 | OA_CoilPmp_1.Ch_Id_RW | Outdoor air pre-treatment -Heating pump 1 - Channel id selected; Modbus HR823 | Write | ||
| PIV | 2347 | OA_CoilPmp_1.T_On_RW | Outdoor air pre-treatment -Heating pump 1 - Time on cycle relay; Modbus HR824 | Write | ||
| PIV | 2348 | OA_CoilPmp_1.T_Off_RW | Outdoor air pre-treatment -Heating pump 1 - Time off cycle releay; Modbus HR825 | Write | ||
| PIV | 2349 | OA_CoilPmp_1.Ch_Type_RW | Outdoor air pre-treatment -Heating pump 1 - Digital output type; Modbus HR826 | Write | ||
| PIV | 2350 | OA_CoilPmp_2.Board_RW | Outdoor air pre-treatment -Heating pump 2 - Board selected; Modbus HR827 | Write | ||
| PIV | 2351 | OA_CoilPmp_2.Ch_Id_RW | Outdoor air pre-treatment -Heating pump 2 - Channel id selected; Modbus HR828 | Write | ||
| PIV | 2352 | OA_CoilPmp_2.T_On_RW | Outdoor air pre-treatment -Heating pump 2 - Time on cycle relay; Modbus HR829 | Write | ||
| PIV | 2353 | OA_CoilPmp_2.T_Off_RW | Outdoor air pre-treatment -Heating pump 2 - Time off cycle releay; Modbus HR830 | Write | ||
| PIV | 2354 | OA_CoilPmp_2.Ch_Type_RW | Outdoor air pre-treatment -Heating pump 2 - Digital output type; Modbus HR831 | Write | ||
| PIV | 2355 | FiltAlrm_Dout.Board_RW | Filters alarm - Board selected; Modbus HR832 | Write | ||
| PIV | 2356 | FiltAlrm_Dout.Ch_Id_RW | Filters alarm - Channel id selected; Modbus HR833 | Write | ||
| PIV | 2357 | FiltAlrm_Dout.T_On_RW | Filters alarm - Time on cycle relay; Modbus HR834 | Write | ||
| PIV | 2358 | FiltAlrm_Dout.T_Off_RW | Filters alarm - Time off cycle releay; Modbus HR835 | Write | ||
| PIV | 2359 | FiltAlrm_Dout.Ch_Type_RW | Filters alarm - Digital output type; Modbus HR836 | Write | ||
| PIV | 2360 | Recovery_Dout.Board_RW | Recovery - Board selected; Modbus HR837 | Write | ||
| PIV | 2361 | Recovery_Dout.Ch_Id_RW | Recovery - Channel id selected; Modbus HR838 | Write | ||
| PIV | 2362 | Recovery_Dout.T_On_RW | Recovery - Time on cycle relay; Modbus HR839 | Write | ||
| PIV | 2363 | Recovery_Dout.T_Off_RW | Recovery - Time off cycle releay; Modbus HR840 | Write | ||
| PIV | 2364 | Recovery_Dout.Ch_Type_RW | Recovery - Digital output type; Modbus HR841 | Write | ||
| PIV | 2365 | IEC_Hum_Dout.Board_RW | IEC humidifer - Board selected; Modbus HR842 | Write | ||
| PIV | 2366 | IEC_Hum_Dout.Ch_Id_RW | IEC humidifer - Channel id selected; Modbus HR843 | Write | ||
| PIV | 2367 | IEC_Hum_Dout.T_On_RW | IEC humidifer - Time on cycle relay; Modbus HR844 | Write | ||
| PIV | 2368 | IEC_Hum_Dout.T_Off_RW | IEC humidifer - Time off cycle releay; Modbus HR845 | Write | ||
| PIV | 2369 | IEC_Hum_Dout.Ch_Type_RW | IEC humidifer - Digital output type; Modbus HR846 | Write | ||
| PIV | 2370 | SupplyFan_Aout.Board_RW | Supply fan - Board selected; Modbus HR847 | Write | ||
| PIV | 2371 | SupplyFan_Aout.Ch_Id_RW | Supply fan - Channel id selected; Modbus HR848 | Write | ||
| AV | 2372 | SupplyFan_Aout.MinOut_RW | Supply fan - Minimum signal analog output; Modbus HR849 | Write | ||
| AV | 2373 | SupplyFan_Aout.MaxOut_RW | Supply fan - Maximum signal analog output; Modbus HR850 | Write | ||
| AV | 2374 | SupplyFan_Aout.PulseWidth_RW | Supply fan - Pulse width setting; Modbus HR851 | Write | ||
| PIV | 2375 | SupplyFan_Aout.Ch_Type_RW | Supply fan - Analog output type; Modbus HR852 | Write | ||
| PIV | 2376 | RetFan_Aout.Board_RW | Return fan - Board selected; Modbus HR853 | Write | ||
| PIV | 2377 | RetFan_Aout.Ch_Id_RW | Return fan - Channel id selected; Modbus HR854 | Write | ||
| AV | 2378 | RetFan_Aout.MinOut_RW | Return fan - Minimum signal analog output; Modbus HR855 | Write | ||
| AV | 2379 | RetFan_Aout.MaxOut_RW | Return fan - Maximum signal analog output; Modbus HR856 | Write | ||
| AV | 2380 | RetFan_Aout.PulseWidth_RW | Return fan - Pulse width setting; Modbus HR857 | Write | ||
| PIV | 2381 | RetFan_Aout.Ch_Type_RW | Return fan - Analog output type; Modbus HR858 | Write | ||
| PIV | 2382 | BypassDamp_Aout.Board_RW | Bypass damper - Board selected; Modbus HR859 | Write | ||
| PIV | 2383 | BypassDamp_Aout.Ch_Id_RW | Bypass damper - Channel id selected; Modbus HR860 | Write | ||
| AV | 2384 | BypassDamp_Aout.MinOut_RW | Bypass damper - Minimum signal analog output; Modbus HR861 | Write | ||
| AV | 2385 | BypassDamp_Aout.MaxOut_RW | Bypass damper - Maximum signal analog output; Modbus HR862 | Write | ||
| AV | 2386 | BypassDamp_Aout.PulseWidth_RW | Bypass damper - Pulse width setting; Modbus HR863 | Write | ||
| PIV | 2387 | BypassDamp_Aout.Ch_Type_RW | Bypass damper - Analog output type; Modbus HR864 | Write | ||
| PIV | 2388 | MixingDamp_Aout.Board_RW | Mixing damper - Board selected; Modbus HR865 | Write | ||
| PIV | 2389 | MixingDamp_Aout.Ch_Id_RW | Mixing damper - Channel id selected; Modbus HR866 | Write | ||
| AV | 2390 | MixingDamp_Aout.MinOut_RW | Mixing damper - Minimum signal analog output; Modbus HR867 | Write | ||
| AV | 2391 | MixingDamp_Aout.MaxOut_RW | Mixing damper - Maximum signal analog output; Modbus HR868 | Write | ||
| AV | 2392 | MixingDamp_Aout.PulseWidth_RW | Mixing damper - Pulse width setting; Modbus HR869 | Write | ||
| PIV | 2393 | MixingDamp_Aout.Ch_Type_RW | Mixing damper - Analog output type; Modbus HR870 | Write | ||
| PIV | 2394 | FreshAirDamp_Aout.Board_RW | Fresh air damper - Board selected; Modbus HR871 | Write | ||
| PIV | 2395 | FreshAirDamp_Aout.Ch_Id_RW | Fresh air damper - Channel id selected; Modbus HR872 | Write | ||
| AV | 2396 | FreshAirDamp_Aout.MinOut_RW | Fresh air damper - Minimum signal analog output; Modbus HR873 | Write | ||
| AV | 2397 | FreshAirDamp_Aout.MaxOut_RW | Fresh air damper - Maximum signal analog output; Modbus HR874 | Write | ||
| AV | 2398 | FreshAirDamp_Aout.PulseWidth_RW | Fresh air damper - Pulse width setting; Modbus HR875 | Write | ||
| PIV | 2399 | FreshAirDamp_Aout.Ch_Type_RW | Fresh air damper - Analog output type; Modbus HR876 | Write | ||
| PIV | 2400 | ReHeatCoil_Aout.Board_RW | Reheat heater - Board selected; Modbus HR877 | Write | ||
| PIV | 2401 | ReHeatCoil_Aout.Ch_Id_RW | Reheat heater - Channel id selected; Modbus HR878 | Write | ||
| AV | 2402 | ReHeatCoil_Aout.MinOut_RW | Reheat heater - Minimum signal analog output; Modbus HR879 | Write | ||
| AV | 2403 | ReHeatCoil_Aout.MaxOut_RW | Reheat heater - Maximum signal analog output; Modbus HR880 | Write | ||
| AV | 2404 | ReHeatCoil_Aout.PulseWidth_RW | Reheat heater - Pulse width setting; Modbus HR881 | Write | ||
| PIV | 2405 | ReHeatCoil_Aout.Ch_Type_RW | Reheat heater - Analog output type; Modbus HR882 | Write | ||
| PIV | 2406 | PreHeatCoil_Aout.Board_RW | Pre-Heating heater - Board selected; Modbus HR883 | Write | ||
| PIV | 2407 | PreHeatCoil_Aout.Ch_Id_RW | Pre-Heating heater - Channel id selected; Modbus HR884 | Write | ||
| AV | 2408 | PreHeatCoil_Aout.MinOut_RW | Pre-Heating heater - Minimum signal analog output; Modbus HR885 | Write | ||
| AV | 2409 | PreHeatCoil_Aout.MaxOut_RW | Pre-Heating heater - Maximum signal analog output; Modbus HR886 | Write | ||
| AV | 2410 | PreHeatCoil_Aout.PulseWidth_RW | Pre-Heating heater - Pulse width setting; Modbus HR887 | Write | ||
| PIV | 2411 | PreHeatCoil_Aout.Ch_Type_RW | Pre-Heating heater - Analog output type; Modbus HR888 | Write | ||
| PIV | 2412 | OA_Coil_Aout.Board_RW | Outdoor air pre-treatment heater - Board selected; Modbus HR889 | Write | ||
| PIV | 2413 | OA_Coil_Aout.Ch_Id_RW | Outdoor air pre-treatment heater - Channel id selected; Modbus HR890 | Write | ||
| AV | 2414 | OA_Coil_Aout.MinOut_RW | Outdoor air pre-treatment heater - Minimum signal analog output; Modbus HR891 | Write | ||
| AV | 2415 | OA_Coil_Aout.MaxOut_RW | Outdoor air pre-treatment heater - Maximum signal analog output; Modbus HR892 | Write | ||
| AV | 2416 | OA_Coil_Aout.PulseWi-dth_RW | Outdoor air pre-treatment heater - Pulse width setting; Modbus HR893 | Write | ||
| PIV | 2417 | OA_Coil_Aout.Ch_Type_RW | Outdoor air pre-treatment heater - Analog output type; Modbus HR894 | Write | ||
| PIV | 2418 | MainCoil_Aout.Board_RW | Main coil valve - Board selected; Modbus HR895 | Write | ||
| PIV | 2419 | MainCoil_Aout.Ch_Id_RW | Main coil valve - Channel id selected; Modbus HR896 | Write | ||
| AV | 2420 | MainCoil_Aout.MinOut_RW | Main coil valve - Minimum signal analog output; Modbus HR897 | Write | ||
| AV | 2421 | MainCoil_Aout.MaxOut_RW | Main coil valve - Maximum signal analog output; Modbus HR898 | Write | ||
| AV | 2422 | MainCoil_Aout.PulseWidth_RW | Main coil valve - Pulse width setting; Modbus HR899 | Write | ||
| PIV | 2423 | MainCoil_Aout.Ch_Type_RW | Main coil valve - Analog output type; Modbus HR900 | Write | ||
| PIV | 2424 | ThrmlWheel_Aout.Board_RW | Thermal wheel - Board selected; Modbus HR901 | Write | ||
| PIV | 2425 | ThrmlWheel_Aout.Ch_Id_RW | Thermal wheel - Channel id selected; Modbus HR902 | Write | ||
| AV | 2426 | ThrmlWheel_Aout.MinOut_RW | Thermal wheel - Minimum signal analog output; Modbus HR903 | Write | ||
| AV | 2427 | ThrmlWheel_Aout.MaxOut_RW | Thermal wheel - Maximum signal analog output; Modbus HR904 | Write | ||
| AV | 2428 | ThrmlWheel_Aout.PulseWidth_RW | Thermal wheel - Pulse width setting; Modbus HR905 | Write | ||
| PIV | 2429 | ThrmlWheel_Aout.Ch_Type_RW | Thermal wheel - Analog output type; Modbus HR906 | Write | ||
| PIV | 2430 | Humidifier_Aout.Board_RW | Humidifier - Board selected; Modbus HR907 | Write | ||
| PIV | 2431 | Humidifier_Aout.Ch_Id_RW | Humidifier - Channel id selected; Modbus HR908 | Write | ||
| AV | 2432 | Humidifier_Aout.MinOut_RW | Humidifier - Minimum signal analog output; Modbus HR909 | Write | ||
| AV | 2433 | Humidifier_Aout.MaxOut_RW | Humidifier - Maximum signal analog output; Modbus HR910 | Write | ||
| AV | 2434 | Humidifier_Aout.PulseWidth_RW | Humidifier - Pulse width setting; Modbus HR911 | Write | ||
| PIV | 2435 | Humidifier_Aout.Ch_Type_RW | Humidifier - Analog output type; Modbus HR912 | Write | ||
| PIV | 2436 | ExhAirDamp_Aout.Board_RW | Exhaust air damper - Board selected; Modbus HR913 | Write | ||
| PIV | 2437 | ExhAirDamp_Aout.Ch_Id_RW | Exhaust air damper - Channel id selected; Modbus HR914 | Write | ||
| AV | 2438 | ExhAirDamp_Aout.MinOut_RW | Exhaust air damper - Minimum signal analog output; Modbus HR915 | Write | ||
| AV | 2439 | ExhAirDamp_Aout.MaxOut_RW | Exhaust air damper - Maximum signal analog output; Modbus HR916 | Write | ||
| AV | 2440 | ExhAirDamp_Aout.PulseWidth_RW | Exhaust air damper - Pulse width setting; Modbus HR917 | Write | ||
| PIV | 2441 | ExhAirDamp_Aout.Ch_Type_RW | Exhaust air damper - Analog output type; Modbus HR918 | Write | ||
| PIV | 2442 | AuxAout_1.Board_RW | Auxiliary output 1 - Board selected; Modbus HR919 | Write | ||
| PIV | 2443 | AuxAout_1.Ch_Id_RW | Auxiliary output 1 - Channel id selected; Modbus HR920 | Write | ||
| AV | 2444 | AuxAout_1.MinOut_RW | Auxiliary output 1 - Minimum signal analog output; Modbus HR921 | Write | ||
| AV | 2445 | AuxAout_1.MaxOut_RW | Auxiliary output 1 - Maximum signal analog output; Modbus HR922 | Write | ||
| AV | 2446 | AuxAout_1.PulseWidth_RW | Auxiliary output 1 - Pulse width setting; Modbus HR923 | Write | ||
| PIV | 2447 | AuxAout_1.Ch_Type_RW | Auxiliary output 1 - Analog output type; Modbus HR924 | Write | ||
| PIV | 2448 | AuxAout_2.Board_RW | Auxiliary output 2 - Board selected; Modbus HR925 | Write | ||
| PIV | 2449 | AuxAout_2.Ch_Id_RW | Auxiliary output 2 - Channel id selected; Modbus HR926 | Write | ||
| AV | 2450 | AuxAout_2.MinOut_RW | Auxiliary output 2 - Minimum signal analog output; Modbus HR927 | Write | ||
| AV | 2451 | AuxAout_2.MaxOut_RW | Auxiliary output 2 - Maximum signal analog output; Modbus HR928 | Write | ||
| AV | 2452 | AuxAout_2.PulseWidth_RW | Auxiliary output 2 - Pulse width setting; Modbus HR929 | Write | ||
| PIV | 2453 | AuxAout_2.Ch_Type_RW | Auxiliary output 2 - Analog output type; Modbus HR930 | Write | ||
| PIV | 2454 | AuxAout_3.Board_RW | Auxiliary output 3 - Board selected; Modbus HR931 | Write | ||
| PIV | 2455 | AuxAout_3.Ch_Id_RW | Auxiliary output 3 - Channel id selected; Modbus HR932 | Write | ||
| AV | 2456 | AuxAout_3.MinOut_RW | Auxiliary output 3 - Minimum signal analog output; Modbus HR933 | Write | ||
| AV | 2457 | AuxAout_3.MaxOut_RW | Auxiliary output 3 - Maximum signal analog output; Modbus HR934 | Write | ||
| AV | 2458 | AuxAout_3.PulseWidth_RW | Auxiliary output 3 - Pulse width setting; Modbus HR935 | Write | ||
| PIV | 2459 | AuxAout_3.Ch_Type_RW | Auxiliary output 3 - Analog output type; Modbus HR936 | Write | ||
| PIV | 2460 | AuxAout_4.Board_RW | Auxiliary output 4 - Board selected; Modbus HR937 | Write | ||
| PIV | 2461 | AuxAout_4.Ch_Id_RW | Auxiliary output 4 - Channel id selected; Modbus HR938 | Write | ||
| AV | 2462 | AuxAout_4.MinOut_RW | Auxiliary output 4 - Minimum signal analog output; Modbus HR939 | Write | ||
| AV | 2463 | AuxAout_4.MaxOut_RW | Auxiliary output 4 - Maximum signal analog output; Modbus HR940 | Write | ||
| AV | 2464 | AuxAout_4.PulseWidth_RW | Auxiliary output 4 - Pulse width setting; Modbus HR941 | Write | ||
| PIV | 2465 | AuxAout_4.Ch_Type_RW | Auxiliary output 4 - Analog output type; Modbus HR942 | Write | ||
| PIV | 2466 | IEC_Aout.Board_RW | IEC - Board selected; Modbus HR943 | Write | ||
| PIV | 2467 | IEC_Aout.Ch_Id_RW | IEC - Channel id selected; Modbus HR944 | Write | ||
| AV | 2468 | IEC_Aout.MinOut_RW | IEC - Minimum signal analog output; Modbus HR945 | Write | ||
| AV | 2469 | IEC_Aout.MaxOut_RW | IEC - Maximum signal analog output; Modbus HR946 | Write | ||
| AV | 2470 | IEC_Aout.PulseWidth_RW | IEC - Pulse width setting; Modbus HR947 | Write | ||
| PIV | 2471 | IEC_Aout.Ch_Type_RW | IEC - Analog output type; Modbus HR948 | Write | ||
| PIV | 2472 | Recovery_Aout.Board_RW | Recovery pump - Board selected; Modbus HR949 | Write | ||
| PIV | 2473 | Recovery_Aout.Ch_Id_RW | Recovery pump - Channel id selected; Modbus HR950 | Write | ||
| AV | 2474 | Recovery_Aout.MinOut_RW | Recovery pump - Minimum signal analog output; Modbus HR951 | Write | ||
| AV | 2475 | Recovery_Aout.MaxOut_RW | Recovery pump - Maximum signal analog output; Modbus HR952 | Write | ||
| AV | 2476 | Recovery_Aout.PulseWidth_RW | Recovery pump - Pulse width setting; Modbus HR953 | Write | ||
| PIV | 2477 | Recovery_Aout.Ch_Type_RW | Recovery pump - Analog output type; Modbus HR954 | Write | ||
| PIV | 2478 | SupplyAirDamp_Aout.Board_RW | Supply air damper - Board selected; Modbus HR955 | Write | ||
| PIV | 2479 | SupplyAirDamp_Aout.Ch_Id_RW | Supply air damper - Channel id selected; Modbus HR956 | Write | ||
| AV | 2480 | SupplyAirDamp_Aout.MinOut_RW | Supply air damper - Minimum signal analog output; Modbus HR957 | Write | ||
| AV | 2481 | SupplyAirDamp_Aout.MaxOut_RW | Supply air damper - Maximum signal analog output; Modbus HR958 | Write | ||
| AV | 2482 | SupplyAirDamp_Aout.PulseWidth_RW | Supply air damper - Pulse width setting; Modbus HR959 | Write | ||
| PIV | 2483 | SupplyAirDamp_Aout.Ch_Type_RW | Supply air damper - Analog output type; Modbus HR960 | Write | ||
| PIV | 2484 | RetAirDamp_Aout.Board_RW | Return air damper - Board selected; Modbus HR961 | Write | ||
| PIV | 2485 | RetAirDamp_Aout.Ch_Id_RW | Return air damper - Channel id selected; Modbus HR962 | Write | ||
| AV | 2486 | RetAirDamp_Aout.MinOut_RW | Return air damper - Minimum signal analog output; Modbus HR963 | Write | ||
| AV | 2487 | RetAirDamp_Aout.MaxOut_RW | Return air damper - Maximum signal analog output; Modbus HR964 | Write | ||
| AV | 2488 | RetAirDamp_Aout.PulseWidth_RW | Return air damper - Pulse width setting; Modbus HR965 | Write | ||
| PIV | 2489 | RetAirDamp_Aout.Ch_Type_RW | Return air damper - Analog output type; Modbus HR966 | Write | ||
| AV | 2493 | CurrTempSetP | Current temperature setpoint; Modbus HR970 | Write | ||
| AV | 2496 | CurrSupplyAirFlwSetP | Current supply air flow setpoint; 32-bit (2 Modbus registers); Modbus HR971 | Write | ||
| AV | 2497 | CurrAirQuality_CO2_SetP | Current air quality CO2 setpoint; Modbus HR973 | Write | ||
| AV | 2498 | CurrSupplyStaticP_SetP | Current supply static pressure setpoint; Modbus HR974 | Write | ||
| AV | 2499 | CurrRetAirFlwSetP | Current return air flow setpoint; 32-bit (2 Modbus registers); Modbus HR975 | Write | ||
| AV | 2500 | CurrRetStaticP_SetP | Current return static pressure setpoint; Modbus HR977 | Write | ||
| IV | 2501 | STD_UOM_ZONE_UI | Unit of measure for user interface; 32-bit (2 Modbus registers); Modbus HR978 | Write | ||
| AV | 2502 | AuxReg1_Cfg.SetP | Auxiliary Regulation 1 - Regulation setpoint; Modbus HR980 | Write | ||
| AV | 2503 | CurrHumSetP | Current humidity setpoint; Modbus HR981 | Write | ||
| PIV | 2504 | CoolHeat_Chg_DT | Cooling/Heating change delay time; Modbus HR982 | Write | ||
| PIV | 2505 | VarToShow.Ch_Type | Modbus HR983 | Write | ||
| AV | 2506 | ObjMsk.Min_StaticPress | High/low limit alarm with hysteresis - Minimum value static pressure; Modbus HR984 | Write | ||
| AV | 2507 | ObjMsk.Min_AirQual | High/low limit alarm with hysteresis - Minimum value air quality; Modbus HR985 | Write | ||
| AV | 2508 | ObjMsk.Min_RfrgPress | High/low limit alarm with hysteresis - Minimum value refrigerant pressure; Modbus HR986 | Write | ||
| AV | 2509 | ObjMsk.Min_FlowRate | High/low limit alarm with hysteresis - Minimum flow rate; Modbus HR987 | Write | ||
| AV | 2510 | ObjMsk.Min_AirFlow | High/low limit alarm with hysteresis - Minimum value air flow; Modbus HR988 | Write | ||
| AV | 2511 | ObjMsk.Min_Temp | High/low limit alarm with hysteresis - Minimum value temperature; Modbus HR989 | Write | ||
| AV | 2512 | ObjMsk.Min_Aout | High/low limit alarm with hysteresis - Minimum value AOUT; Modbus HR990 | Write | ||
| AV | 2513 | ObjMsk.Min_Hum | High/low limit alarm with hysteresis - Minimum value humidity; Modbus HR991 | Write | ||
| AV | 2514 | ObjMsk.Min_Generic | High/low limit alarm with hysteresis - Minimum value generic; Modbus HR992 | Write | ||
| AV | 2515 | ObjMsk.Min_Percent | High/low limit alarm with hysteresis - Minimum value percent; Modbus HR993 | Write | ||
| AV | 2516 | ObjMsk.Max_StaticPress | High/low limit alarm with hysteresis - Maximum value static pressure; Modbus HR994 | Write | ||
| AV | 2517 | ObjMsk.Max_AirQual | High/low limit alarm with hysteresis - Maximum value air quality; Modbus HR995 | Write | ||
| AV | 2518 | ObjMsk.Max_RfrgPress | High/low limit alarm with hysteresis - Maximum value refrigerant pressure; Modbus HR996 | Write | ||
| AV | 2519 | ObjMsk.Max_FlowRate | High/low limit alarm with hysteresis - Maximum flow rate; Modbus HR997 | Write | ||
| AV | 2520 | ObjMsk.Max_AirFlow | High/low limit alarm with hysteresis - Maximum air flow; Modbus HR998 | Write | ||
| AV | 2521 | ObjMsk.Max_Hum | High/low limit alarm with hysteresis - Maxmimum value humidity; Modbus HR999 | Write | ||
| AV | 2522 | ObjMsk.Max_Temp | High/low limit alarm with hysteresis - Maximum value temperature; Modbus HR1000 | Write | ||
| AV | 2523 | ObjMsk.Max_Aout | High/low limit alarm with hysteresis - Maximum value AOUT; Modbus HR1001 | Write | ||
| AV | 2524 | ObjMsk.Max_Generic | High/low limit alarm with hysteresis - Maximum value generic; Modbus HR1002 | Write | ||
| AV | 2525 | ObjMsk.Max_Percent | High/low limit alarm with hysteresis - Maximum value percent; Modbus HR1003 | Write | ||
| AV | 2526 | ObjMsk.ValOffsetRfrgPress | High/low limit alarm with hysteresis - Offset value refrigerant pressure; Modbus HR1004 | Write | ||
| AV | 2527 | ObjMsk.ValOffsetFlowRate | High/low limit alarm with hysteresis - Offset value flow rate; Modbus HR1005 | Write | ||
| AV | 2528 | ObjMsk.ValOffsetAirFLow | High/low limit alarm with hysteresis - Offset value air flow; Modbus HR1006 | Write | ||
| AV | 2529 | ObjMsk.ValOffsetHum | High/low limit alarm with hysteresis - Offset value humidity; Modbus HR1007 | Write | ||
| AV | 2530 | ObjMsk.ValOffsetTemp | High/low limit alarm with hysteresis - Offset value temperature; Modbus HR1008 | Write | ||
| AV | 2531 | ObjMsk.ValOffsetPercent | High/low limit alarm with hysteresis - Offset value percent; Modbus HR1009 | Write | ||
| AV | 2532 | ObjMsk.ValOffsetAirQual | High/low limit alarm with hysteresis - Offset value air quality; Modbus HR1010 | Write | ||
| AV | 2533 | ObjMsk.ValOffsetStaticPress | High/low limit alarm with hysteresis - Offset value static pressure; Modbus HR1011 | Write | ||
| AV | 2534 | ObjMsk.ValOffsetGeneric | High/low limit alarm with hysteresis - Offset value generic probe; Modbus HR1012 | Write | ||
| PIV | 2535 | VarToShow.ChFilter | Modbus HR1013 | Write | ||
| PIV | 2536 | GeneralMng.WizardType | Wizard type ( 0: skip, 1: Pre-Loaded, 2: Custom); Modbus HR1014 | Write | ||
| PIV | 2537 | GeneralMng.DriveTyp | Drive type (0: Internal public volume; 1: USB pendrive); Modbus HR1015 | Write | ||
| IV | 2538 | GeneralMng.PreLoadConfNumber | 32-bit (2 Modbus registers); Modbus HR1016 | Write | ||
| IV | 2539 | GeneralMng.ExpCfg_Char0 | 32-bit (2 Modbus registers); Modbus HR1018 | Write | ||
| IV | 2540 | GeneralMng.ExpCfg_Char1 | 32-bit (2 Modbus registers); Modbus HR1020 | Write | ||
| IV | 2541 | GeneralMng.ExpCfg_Char2 | 32-bit (2 Modbus registers); Modbus HR1022 | Write | ||
| IV | 2542 | GeneralMng.ExpCfg_Char3 | 32-bit (2 Modbus registers); Modbus HR1024 | Write | ||
| IV | 2543 | GeneralMng.ExpCfg_Char4 | 32-bit (2 Modbus registers); Modbus HR1026 | Write | ||
| IV | 2544 | GeneralMng.ExpCfg_Char5 | 32-bit (2 Modbus registers); Modbus HR1028 | Write | ||
| IV | 2545 | GeneralMng.ExpCfg_Char6 | 32-bit (2 Modbus registers); Modbus HR1030 | Write | ||
| IV | 2546 | GeneralMng.ExpCfg_Char7 | 32-bit (2 Modbus registers); Modbus HR1032 | Write | ||
| IV | 2547 | GeneralMng.ExpCfg_Char8 | 32-bit (2 Modbus registers); Modbus HR1034 | Write | ||
| IV | 2548 | GeneralMng.ExpCfg_Char9 | 32-bit (2 Modbus registers); Modbus HR1036 | Write | ||
| IV | 2549 | GeneralMng.ExpCfg_Char10 | 32-bit (2 Modbus registers); Modbus HR1038 | Write | ||
| BV | 2550 | GeneralMng.WizardConfirm | Modbus HR1040 | Write | ||
| AV | 2551 | FreshAirDampManModeVal | Fresh air damper manual mode value; Modbus HR1041 | Write | ||
| PIV | 2552 | FreshAirDampManModeVal_OnOff | For mask usage; Modbus HR1042 | Write | ||
| AV | 2553 | MixDampManModeVal | Mixing damper manual mode value; Modbus HR1043 | Write | ||
| PIV | 2554 | MixDampManModeVal_OnOff | For mask usage; Modbus HR1044 | Write | ||
| AV | 2555 | ExhAirDampManModeVal | Exhaust air damper manual mode value; Modbus HR1045 | Write | ||
| PIV | 2556 | ExhAirDampManModeVal_OnOff | For mask usage; Modbus HR1046 | Write | ||
| AV | 2557 | BypassDampManModeVal | Bypaas damper manual mode value; Modbus HR1047 | Write | ||
| PIV | 2558 | BypassDampManModeVal_OnOff | For mask usage; Modbus HR1048 | Write | ||
| PIV | 2559 | SupplyFanManModeVal_3Speed | For mask usage; Modbus HR1049 | Write | ||
| AV | 2560 | SupplyFanManModeVal | Supply fan manual mode value; Modbus HR1050 | Write | ||
| PIV | 2561 | SupplyFanManModeVal_OnOff | For mask usage; Modbus HR1051 | Write | ||
| PIV | 2562 | RetFanManModeVal_3Speed | For mask usage; Modbus HR1052 | Write | ||
| AV | 2563 | RetFanManModeVal | Return fan manual mode value; Modbus HR1053 | Write | ||
| PIV | 2564 | RetFanManModeVal_OnOff | For mask usage; Modbus HR1054 | Write | ||
| AV | 2565 | PreHeatCoilManModeVal | Pre heating coil manual mode value; Modbus HR1055 | Write | ||
| AV | 2566 | MainCoilManModeVal | Main coil manual mode value; Modbus HR1056 | Write | ||
| AV | 2567 | ReHeatCoilManModeVal | Post heating coil manual mode value; Modbus HR1057 | Write | ||
| AV | 2568 | CompManModeVal | Compressor manual mode value; Modbus HR1058 | Write | ||
| PIV | 2569 | CompManModeVal_USINT | For mask usage; Modbus HR1059 | Write | ||
| AV | 2570 | HumManModeVal | Humidifier manual mode value; Modbus HR1060 | Write | ||
| AV | 2571 | ThermWhlManModeVal | Thermal wheel manual mode value; Modbus HR1061 | Write | ||
| AV | 2578 | UnitSetP.TempSetP.Summer.PreComfort | Unit setpoints - Temperature setpoint - Summer - Pre-comfort; Modbus HR1068 | Write | ||
| AV | 2579 | UnitSetP.TempSetP.Winter.PreComfort | Unit setpoints - Temperature setpoint - Winter - Pre-comfort; Modbus HR1069 | Write | ||
| AVmin | 2584 | UnitSetP.TempSetP.Summer.Comfort | Unit setpoints - Temperature setpoint - Summer - Comfort; Modbus HR1074 | Write | ||
| AVmin | 2585 | UnitSetP.TempSetP.Winter.Comfort | Unit setpoints - Temperature setpoint - Winter - Comfort; Modbus HR1075 | Write | ||
| AV | 2586 | TempSetP_MinVal | Temperature setpoint - minimum value; Modbus HR1076 | Write | ||
| AV | 2587 | TempSetP_MaxVal | Temperature setpoint - maximum value; Modbus HR1077 | Write | ||
| AV | 2626 | UnitSetP.SupplyStaticP_SetP.Economy | Unit setpoints - Supply static pressure - Economy; Modbus HR1116 | Write | ||
| AV | 2629 | UnitSetP.SupplyStaticP_SetP.PreComfort | Unit setpoints - Supply static pressure - Pre-comfort; Modbus HR1119 | Write | ||
| AV | 2632 | UnitSetP.SupplyStaticP_SetP.Comfort | Unit setpoints - Supply static pressure - Comfort; Modbus HR1122 | Write | ||
| AV | 2633 | SupplyStaticPressSetP_MinVal | Supply static pressure setpoint - minimum value; Modbus HR1123 | Write | ||
| AV | 2634 | SupplyStaticPressSetP_MaxVal | Supply static pressure setpoint - maximum value; Modbus HR1124 | Write | ||
| PIV | 2635 | UnitSetP.SupplyAirFlwSetP.Economy | Unit setpoints - Supply air flow - Economy; 32-bit (2 ...; Modbus HR1125 | Write | ||
| PIV | 2637 | UnitSetP.SupplyAirFlwSetP.PreComfort | Unit setpoints - Supply air flow - Pre-comfort; 32-bit (2 ...; Modbus HR1127 | Write | ||
| PIV | 2639 | UnitSetP.SupplyAirFlwSetP.Comfort | Unit setpoints - Supply air flow - Comfort; 32-bit (2 ...; Modbus HR1129 | Write | ||
| PIV | 2641 | SupplyAirFlwSetP_MinVal | Supply air flow setpoint - minimum value; 32-bit (2 Modbus registers); Modbus HR1131 | Write | ||
| PIV | 2643 | SupplyAirFlwSetP_MaxVal | Supply air flow setpoint - maximum value; 32-bit (2 Modbus registers); Modbus HR1133 | Write | ||
| AV | 2645 | UnitSetP.AirQuality_CO2_SetP.Economy | Unit setpoints - Air quality CO2 - Economy; Modbus HR1135 | Write | ||
| AV | 2647 | UnitSetP.AirQuality_CO2_SetP.PreComfort | Unit setpoints - Air quality CO2 - Pre-comfort; Modbus HR1137 | Write | ||
| AV | 2650 | UnitSetP.AirQuality_CO2_SetP.Comfort | Unit setpoints - Air quality CO2 - Comfort; Modbus HR1140 | Write | ||
| AV | 2651 | AirQualityCO2SetP_MinVal | Air quality CO2 setpoint - minimum value; Modbus HR1141 | Write | ||
| AV | 2652 | AirQualityCO2SetP_MaxVal | Air quality CO2 setpoint - maximum value; Modbus HR1142 | Write | ||
| AV | 2653 | UnitSetP.RetStaticP_SetP.Economy | Unit setpoints - Return static pressure - Economy; Modbus HR1143 | Write | ||
| AV | 2656 | UnitSetP.RetStaticP_SetP.PreComfort | Unit setpoints - Return static pressure - Pre-comfort; Modbus HR1146 | Write | ||
| AV | 2659 | UnitSetP.RetStaticP_SetP.Comfort | Unit setpoints - Return static pressure - Comfort; Modbus HR1149 | Write | ||
| AV | 2660 | RetStaticPressSetP_MinVal | Return static pressure setpoint - minimum value; Modbus HR1150 | Write | ||
| AV | 2661 | RetStaticPressSetP_MaxVal | Return static pressure setpoint - maximum value; Modbus HR1151 | Write | ||
| PIV | 2662 | UnitSetP.RetAirFlwSetP.Economy | Unit setpoints - Return air flow - Economy; Modbus HR1152 | Write | ||
| PIV | 2664 | UnitSetP.RetAirFlwSetP.PreComfort | Unit setpoints - Return air flow - Pre-comfort; 32-bit (2 ...; Modbus HR1154 | Write | ||
| PIV | 2666 | UnitSetP.RetAirFlwSetP.Comfort | Unit setpoints - Return air flow - Comfort; 32-bit (2 ...; Modbus HR1156 | Write | ||
| PIV | 2668 | RetAirFlwSetP_MinVal | Return air flow setpoint - minimum value; 32-bit (2 Modbus registers); Modbus HR1158 | Write | ||
| PIV | 2670 | RetAirFlwSetP_MaxVal | Return air flow setpoint - maximum value; 32-bit (2 Modbus registers); Modbus HR1160 | Write | ||
| AV | 2672 | UnitSetP.HumSetP.Summer.Economy | Unit setpoints - Humidity - Summer - Economy; Modbus HR1162 | Write | ||
| AV | 2673 | UnitSetP.HumSetP.Winter.Economy | Unit setpoints - Humidity - Winter - Economy; Modbus HR1163 | Write | ||
| AV | 2677 | UnitSetP.HumSetP.Summer.PreComfort | Unit setpoints - Humidity - Summer - Pre-comfort; Modbus HR1167 | Write | ||
| AV | 2678 | UnitSetP.HumSetP.Winter.PreComfort | Unit setpoints - Humidity - Winter - Pre-comfort; Modbus HR1168 | Write | ||
| AV | 2683 | UnitSetP.HumSetP.Summer.Comfort | Unit setpoints - Humidity - Summer - Comfort; Modbus HR1173 | Write | ||
| AV | 2684 | UnitSetP.HumSetP.Winter.Comfort | Unit setpoints - Humidity - Winter - Comfort; Modbus HR1174 | Write | ||
| AV | 2685 | HumSetP_MinVal | Humidity setpoint - minimum value; Modbus HR1175 | Write | ||
| AV | 2686 | HumSetP_MaxVal | Humidity setpoint - maximum value; Modbus HR1176 | Write | ||
| AV | 2689 | Regulation.SummerExtTempCompensThrsh | Summer: external temperature compensation delta; Modbus HR1179 | Write | ||
| AV | 2690 | Regulation.SummerExtTempCompensDelta | Summer: external temperature compensation delta; Modbus HR1180 | Write | ||
| AV | 2691 | Regulation.SummerMaxCompensOffset | Summer: maximum compensation offset; Modbus HR1181 | Write | ||
| AV | 2692 | Regulation.WinterExtTempCompensThrsh | Winter: external temperature compensation threshold; Modbus HR1182 | Write | ||
| AV | 2693 | Regulation.WinterExtTempCompensDelta | Winter: external temperature compensation delta; Modbus HR1183 | Write | ||
| AV | 2694 | Regulation.WinterMaxCompensOffset | Winter: maximum compensation offset; Modbus HR1184 | Write | ||
| IV | 2695 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.PrgNr | 32-bit (2 Modbus registers); Modbus HR1185 | Write | ||
| PIV | 2696 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[0].Hours | Event - Start hours event; Modbus HR1187 | Write | ||
| PIV | 2697 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[0].Mins | Event - Start minutes event; Modbus HR1188 | Write | ||
| PIV | 2698 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[0].Mode | Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1189 | Write | ||
| PIV | 2699 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[1].Hours | Event - Start hours event; Modbus HR1190 | Write | ||
| PIV | 2700 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[1].Mins | Event - Start minutes event; Modbus HR1191 | Write | ||
| PIV | 2701 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[1].Mode | Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1192 | Write | ||
| PIV | 2702 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[2].Hours | Event - Start hours event; Modbus HR1193 | Write | ||
| PIV | 2703 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[2].Mins | Event - Start minutes event; Modbus HR1194 | Write | ||
| PIV | 2704 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[2].Mode | Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1195 | Write | ||
| PIV | 2705 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[3].Hours | Event - Start hours event; Modbus HR1196 | Write | ||
| PIV | 2706 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[3].Mins | Event - Start minutes event; Modbus HR1197 | Write | ||
| PIV | 2707 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[3].Mode | Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1198 | Write | ||
| PIV | 2708 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[4].Hours | Event - Start hours event; Modbus HR1199 | Write | ||
| PIV | 2709 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[4].Mins | Event - Start minutes event; Modbus HR1200 | Write | ||
| PIV | 2710 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[4].Mode | Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1201 | Write | ||
| PIV | 2711 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[5].Hours | Event - Start hours event; Modbus HR1202 | Write | ||
| PIV | 2712 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[5].Mins | Event - Start minutes event; Modbus HR1203 | Write | ||
| PIV | 2713 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[5].Mode | Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1204 | Write | ||
| PIV | 2714 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[6].Hours | Event - Start hours event; Modbus HR1205 | Write | ||
| PIV | 2715 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[6].Mins | Event - Start minutes event; Modbus HR1206 | Write | ||
| PIV | 2716 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[6].Mode | Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1207 | Write | ||
| PIV | 2717 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[7].Hours | Event - Start hours event; Modbus HR1208 | Write | ||
| PIV | 2718 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[7].Mins | Event - Start minutes event; Modbus HR1209 | Write | ||
| PIV | 2719 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[7].Mode | Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1210 | Write | ||
| PIV | 2720 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[8].Hours | Event - Start hours event; Modbus HR1211 | Write | ||
| PIV | 2721 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[8].Mins | Event - Start minutes event; Modbus HR1212 | Write | ||
| PIV | 2722 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[8].Mode | Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1213 | Write | ||
| PIV | 2723 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[9].Hours | Event - Start hours event; Modbus HR1214 | Write | ||
| PIV | 2724 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[9].Mins | Event - Start minutes event; Modbus HR1215 | Write | ||
| PIV | 2725 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[9].Mode | Event - 0=OFF; 1=Economy; 2=Comfort; Modbus HR1216 | Write | ||
| PIV | 2726 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SaveData | Modbus HR1217 | Write | ||
| IV | 2727 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.CopyTo_Prg | 32-bit (2 Modbus registers); Modbus HR1218 | Write | ||
| PIV | 2728 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.En_PrgCopy | Modbus HR1220 | Write | ||
| PIV | 2729 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[0] | Monday program; Modbus HR1221 | Write | ||
| PIV | 2730 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[1] | Tuesday program; Modbus HR1222 | Write | ||
| PIV | 2731 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[2] | Wednesday program; Modbus HR1223 | Write | ||
| PIV | 2732 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[3] | Thursday program; Modbus HR1224 | Write | ||
| PIV | 2733 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[4] | Friday program; Modbus HR1225 | Write | ||
| PIV | 2734 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[5] | Saturday program; Modbus HR1226 | Write | ||
| PIV | 2735 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[6] | Sunday program; Modbus HR1227 | Write | ||
| PIV | 2736 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SaveData_DaysPrg | Modbus HR1228 | Write | ||
| PIV | 2737 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[0].StartDay | Vacation period - Start day; Modbus HR1229 | Write | ||
| PIV | 2738 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[0].StartMonth | Vacation period - Start month; Modbus HR1230 | Write | ||
| PIV | 2739 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[0].EndDay | Vacation period - End day; Modbus HR1231 | Write | ||
| PIV | 2740 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[0].EndMonth | Vacation period - End month; Modbus HR1232 | Write | ||
| PIV | 2741 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[0].Mode | Vacation period - Mode; Modbus HR1233 | Write | ||
| PIV | 2742 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[1].StartDay | Vacation period - Start day; Modbus HR1234 | Write | ||
| PIV | 2743 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[1].StartMonth | Vacation period - Start month; Modbus HR1235 | Write | ||
| PIV | 2744 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[1].EndDay | Vacation period - End day; Modbus HR1236 | Write | ||
| PIV | 2745 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[1].EndMonth | Vacation period - End month; Modbus HR1237 | Write | ||
| PIV | 2746 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[1].Mode | Vacation period - Mode; Modbus HR1238 | Write | ||
| PIV | 2747 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[2].StartDay | Vacation period - Start day; Modbus HR1239 | Write | ||
| PIV | 2748 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[2].StartMonth | Vacation period - Start month; Modbus HR1240 | Write | ||
| PIV | 2749 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[2].EndDay | Vacation period - End day; Modbus HR1241 | Write | ||
| PIV | 2750 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[2].EndMonth | Vacation period - End month; Modbus HR1242 | Write | ||
| PIV | 2751 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[2].Mode | Vacation period - Mode; Modbus HR1243 | Write | ||
| PIV | 2752 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SaveData_VacationsPrg | Modbus HR1244 | Write | ||
| PIV | 2753 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[0].Day | Special day - Day; Modbus HR1245 | Write | ||
| PIV | 2754 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[0].Month | Special day - Month; Modbus HR1246 | Write | ||
| PIV | 2755 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[0].Mode | Special day - Mode; Modbus HR1247 | Write | ||
| PIV | 2756 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[1].Day | Special day - Day; Modbus HR1248 | Write | ||
| PIV | 2757 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[1].Month | Special day - Month; Modbus HR1249 | Write | ||
| PIV | 2758 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[1].Mode | Special day - Mode; Modbus HR1250 | Write | ||
| PIV | 2759 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[2].Day | Special day - Day; Modbus HR1251 | Write | ||
| PIV | 2760 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[2].Month | Special day - Month; Modbus HR1252 | Write | ||
| PIV | 2761 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[2].Mode | Special day - Mode; Modbus HR1253 | Write | ||
| PIV | 2762 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[3].Day | Special day - Day; Modbus HR1254 | Write | ||
| PIV | 2763 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[3].Month | Special day - Month; Modbus HR1255 | Write | ||
| PIV | 2764 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[3].Mode | Special day - Mode; Modbus HR1256 | Write | ||
| PIV | 2765 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[4].Day | Special day - Day; Modbus HR1257 | Write | ||
| PIV | 2766 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[4].Month | Special day - Month; Modbus HR1258 | Write | ||
| PIV | 2767 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[4].Mode | Special day - Mode; Modbus HR1259 | Write | ||
| PIV | 2768 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[5].Day | Special day - Day; Modbus HR1260 | Write | ||
| PIV | 2769 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[5].Month | Special day - Month; Modbus HR1261 | Write | ||
| PIV | 2770 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[5].Mode | Special day - Mode; Modbus HR1262 | Write | ||
| PIV | 2771 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[6].Day | Special day - Day; Modbus HR1263 | Write | ||
| PIV | 2772 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[6].Month | Special day - Month; Modbus HR1264 | Write | ||
| PIV | 2773 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[6].Mode | Special day - Mode; Modbus HR1265 | Write | ||
| PIV | 2774 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[7].Day | Special day - Day; Modbus HR1266 | Write | ||
| PIV | 2775 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[7].Month | Special day - Month; Modbus HR1267 | Write | ||
| PIV | 2776 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[7].Mode | Special day - Mode; Modbus HR1268 | Write | ||
| PIV | 2777 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[8].Day | Special day - Day; Modbus HR1269 | Write | ||
| PIV | 2778 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[8].Month | Special day - Month; Modbus HR1270 | Write | ||
| PIV | 2779 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[8].Mode | Special day - Mode; Modbus HR1271 | Write | ||
| PIV | 2780 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[9].Day | Special day - Day; Modbus HR1272 | Write | ||
| PIV | 2781 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[9].Month | Special day - Month; Modbus HR1273 | Write | ||
| PIV | 2782 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[9].Mode | Special day - Mode; Modbus HR1274 | Write | ||
| PIV | 2783 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[10].Day | Special day - Day; Modbus HR1275 | Write | ||
| PIV | 2784 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[10].Month | Special day - Month; Modbus HR1276 | Write | ||
| PIV | 2785 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[10].Mode | Special day - Mode; Modbus HR1277 | Write | ||
| PIV | 2786 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[11].Day | Special day - Day; Modbus HR1278 | Write | ||
| PIV | 2787 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[11].Month | Special day - Month; Modbus HR1279 | Write | ||
| PIV | 2788 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[11].Mode | Special day - Mode; Modbus HR1280 | Write | ||
| PIV | 2789 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[12].Day | Special day - Day; Modbus HR1281 | Write | ||
| PIV | 2790 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[12].Month | Special day - Month; Modbus HR1282 | Write | ||
| PIV | 2791 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[12].Mode | Special day - Mode; Modbus HR1283 | Write | ||
| PIV | 2792 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[13].Day | Special day - Day; Modbus HR1284 | Write | ||
| PIV | 2793 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[13].Month | Special day - Month; Modbus HR1285 | Write | ||
| PIV | 2794 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[13].Mode | Special day - Mode; Modbus HR1286 | Write | ||
| PIV | 2795 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[14].Day | Special day - Day; Modbus HR1287 | Write | ||
| PIV | 2796 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[14].Month | Special day - Month; Modbus HR1288 | Write | ||
| PIV | 2797 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[14].Mode | Special day - Mode; Modbus HR1289 | Write | ||
| PIV | 2798 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SaveData_SpecDays | Modbus HR1290 | Write | ||
| PIV | 2799 | Scheduler_OnOffUnit.PartyMode_DT | Party mode duration; Modbus HR1291 | Write | ||
| PIV | 2800 | FanTyp | Fans type (0: On/Off; 1: 3 speeds; 2: Modulating; 3: ...; Modbus HR1292 | Write | ||
| PIV | 2801 | HeatExchgTyp | Heating exchanger type; Modbus HR1293 | Write | ||
| PIV | 2802 | HumTyp | Humidifier type (0:None;1:Isothermal;2:Adiabatic;3:Humisonic;4:Humifog; 5:HumiSteam); Modbus HR1294 | Write | ||
| PIV | 2803 | IEC_Typ | IEC type (0: None; 1: OnOff; 2: Modulating; 3: Humisonic); Modbus HR1295 | Write | ||
| PIV | 2804 | PreHeatCoil_Typ | PreHeating coil type; Modbus HR1296 | Write | ||
| PIV | 2805 | MainCoil_Typ | Main coil type; Modbus HR1297 | Write | ||
| PIV | 2806 | ReHeatCoil_Typ | PostHeating coil type; Modbus HR1298 | Write | ||
| PIV | 2807 | FreshAirDampTyp | Fresh air damper type (0: On/Off; 1: Modulating); Modbus HR1299 | Write | ||
| PIV | 2808 | ExhAirDampTyp | Exhaust air damper type (0: On/Off; 1: Modulating); Modbus HR1300 | Write | ||
| PIV | 2809 | MixingAirDampTyp | Mixing air damper type (0: On/Off; 1: Modulating); Modbus HR1301 | Write | ||
| PIV | 2810 | SupplyAirDampTyp | Supply air damper type (0: On/Off; 1: Modulating); Modbus HR1302 | Write | ||
| PIV | 2811 | RetAirDampTyp | Return air damper type (0: On/Off; 1: Modulating); Modbus HR1303 | Write | ||
| PIV | 2812 | BypassDampTyp | Bypass damper type (0: On/Off; 1: Modulating); Modbus HR1304 | Write | ||
| PIV | 2813 | Filters_Cfg | Filters configuration; Modbus HR1305 | Write | ||
| PIV | 2814 | HEPA_Filt_Cfg | HEPA Filter configuration (0: None; 1: Filt 1; Filt 1 ...; Modbus HR1306 | Write | ||
| PIV | 2815 | RegTyp | Regulation type (0: Supply only; 1:Return only; 2: Room only; ...; Modbus HR1307 | Write | ||
| AV | 2816 | Regulation.SetP_Offs_Kp | Regulation set point offset: proportional gain; Modbus HR1308 | Write | ||
| PIV | 2817 | Regulation.SetP_Offs_Ti | Regulation set point offset: integral time; Modbus HR1309 | Write | ||
| PIV | 2818 | UnitHumDehumMode_Cfg | Unit humidification/dehumidification mode configuration (0: Fixed by season; 1: Automatic ...; Modbus HR1310 | Write | ||
| PIV | 2819 | UnitCoolHeatMode_Cfg | Unit cooling heating mode configuration; Modbus HR1311 | Write | ||
| AV | 2820 | Regulation.SummerExtTempThrsh | Summer external temperature threshold; Modbus HR1312 | Write | ||
| AV | 2821 | Regulation.WinterExtTempThrsh | Winter external temperature threshold; Modbus HR1313 | Write | ||
| AV | 2822 | Coil_SummerThrsh | Summer coil water temperature threshold; Modbus HR1314 | Write | ||
| AV | 2823 | Coil_WinterThrsh | Winter coil water temperature threshold; Modbus HR1315 | Write | ||
| PIV | 2824 | Coil_WaterT_OutOfRange_DT | Main coil: water temperature out of range warning delay time; Modbus HR1316 | Write | ||
| PIV | 2825 | Coil_WaterT_Cfg | Coil water temperature: action configuration; Modbus HR1317 | Write | ||
| PIV | 2826 | HumDehum_CtrlPrb | Humidification/Dehumidification: Control probe (0: Supply; 1: Return; 2: Room); Modbus HR1318 | Write | ||
| PIV | 2827 | HumDehum_CtrlTyp | Humidification/Dehumidification: Control type (0: Relative; 1: Absolute); Modbus HR1319 | Write | ||
| PIV | 2828 | Dehum_RegTyp | Dehumidification: Regulation type (0: DewPoint; 1: Request); Modbus HR1320 | Write | ||
| AV | 2829 | HumDehum_RegBand | Humidification/Dehumidification: Regulation band; Modbus HR1321 | Write | ||
| PIV | 2830 | HumDehum_RegChgDT | Humidification/Dehumidification: Regulation change delay time; Modbus HR1322 | Write | ||
| AV | 2831 | Regulation.FC_DeltaT_Act | Freecooling activation delta; Modbus HR1323 | Write | ||
| AV | 2832 | Regulation.FH_DeltaT_Act | Freeheating activation delta; Modbus HR1324 | Write | ||
| AV | 2833 | FC_PID_Params.Kp | Free cooling PID parameters - Proportional gain; Modbus HR1325 | Write | ||
| PIV | 2834 | FC_PID_Params.Ti | Free cooling PID parameters - Integral time; Modbus HR1326 | Write | ||
| AV | 2835 | FH_PID_Params.Kp | Free heating PID parameters - Proportional gain; Modbus HR1327 | Write | ||
| PIV | 2836 | FH_PID_Params.Ti | Free heating PID parameters - Integral time; Modbus HR1328 | Write | ||
| AV | 2837 | StateMachine.LowWarmUpThrshExtTemp | Low external temperature threshold for the activation of warm up procedure; Modbus HR1329 | Write | ||
| PIV | 2838 | StateMachine.StartUpFanActDT | Settable delay between return and supply fan activation (seconds). To ...; Modbus HR1330 | Write | ||
| PIV | 2839 | StateMachine.WarmUpDT | Warm up delay time; Modbus HR1331 | Write | ||
| PIV | 2840 | StateMachine.WarmUpFanActDT | Warm up fan activation delay time; Modbus HR1332 | Write | ||
| PIV | 2841 | SupplyFanWarmUpReq_3Speed | For mask usage; Modbus HR1333 | Write | ||
| AV | 2842 | SupplyFanWarmUpReq | Supply fan request for automatic warm up; Modbus HR1334 | Write | ||
| PIV | 2843 | SupplyFanWarmUpReq_OnOff | For mask usage; Modbus HR1335 | Write | ||
| PIV | 2844 | RetFanWarmUpReq_3Speed | For mask usage; Modbus HR1336 | Write | ||
| AV | 2845 | RetFanWarmUpReq | Return fan request for automatic warm up; Modbus HR1337 | Write | ||
| PIV | 2846 | RetFanWarmUpReq_OnOff | For mask usage; Modbus HR1338 | Write | ||
| AV | 2847 | PreHeatCoilWarmUpReq | PreHeating coil warm up request; Modbus HR1339 | Write | ||
| AV | 2848 | MainCoilWarmUpReq | Main coil warm up request; Modbus HR1340 | Write | ||
| AV | 2849 | ReHeatCoilWarmUpReq | PostHeating coil warm up request; Modbus HR1341 | Write | ||
| AV | 2850 | ByPassDampWarmUpReq | Bypass damper warm up request; Modbus HR1342 | Write | ||
| AV | 2851 | ThermWhlWarmUpReq | Thermal wheel warm up request; Modbus HR1343 | Write | ||
| PIV | 2852 | BypassDampWarmUpReq_OnOff | For mask usage; Modbus HR1344 | Write | ||
| PIV | 2853 | SupplyFanSwitchOnReq_3Speed | For mask usage; Modbus HR1345 | Write | ||
| AV | 2854 | SupplyFanSwitchOnReq | Supply fan request for automatic switch on when warm up ...; Modbus HR1346 | Write | ||
| PIV | 2855 | SupplyFanSwitchOnReq_OnOff | For mask usage; Modbus HR1347 | Write | ||
| PIV | 2856 | AFreezeTyp | Antifreeze type (0: NONE; 1: Ext.Temp.; 2: AFreeze Temp.; 3: DigitalInput); Modbus HR1348 | Write | ||
| AV | 2857 | Antifreeze.AfreezeTempThrsh | Antifreeze temperature threshold; Modbus HR1349 | Write | ||
| AV | 2858 | Antifreeze.AFreezeEndingDelta | Antifreeze ending delta; Modbus HR1350 | Write | ||
| PIV | 2859 | Antifreeze.AFreezeWarnDT | Anti freeze warning delay time; Modbus HR1351 | Write | ||
| PIV | 2860 | Antifreeze.Al_AFreezeDT | Antifreeze alarm delay time; Modbus HR1352 | Write | ||
| AV | 2861 | Antifreeze.PrevAFreezeTempThrsh | Prevent antifreeze threshold; Modbus HR1353 | Write | ||
| AV | 2862 | LowSupplyTempThrsh | Low supply temperature threshold; Modbus HR1354 | Write | ||
| PIV | 2863 | LowTempAlrmDT_StartUp | Low supply temperature alarm delay time at start up; Modbus HR1355 | Write | ||
| PIV | 2864 | LowTempAlrmDT_Run | Low supply temperature alarm delay time at unit in run mode; Modbus HR1356 | Write | ||
| AV | 2865 | HighSupplyTempThrsh | High supply temperature threshold; Modbus HR1357 | Write | ||
| PIV | 2866 | HighTempAlrmDT_StartUp | High supply temperature alarm delay time at start up; Modbus HR1358 | Write | ||
| PIV | 2867 | HighTempAlrmDT_Run | High supply temperature alarm delay time at unit in run mode; Modbus HR1359 | Write | ||
| AV | 2868 | LowHighSupplyT_Kp | Low supply temp: proportional part; Modbus HR1360 | Write | ||
| PIV | 2869 | LowHighSupplyT_Ti | Low supply temp: integral time; Modbus HR1361 | Write | ||
| AV | 2870 | RegPrbErrFreshAirDampReq | Fresh air damper request in case of regulation probe error: modulating; Modbus HR1362 | Write | ||
| PIV | 2871 | RegPrbErrFreshAirDampReq_OnOff | Fresh air damper request in case of regulation probe error: on/off; Modbus HR1363 | Write | ||
| AV | 2872 | RegPrbErrByPassDampReq | Bypass damper request in case of regulation probe error: modulating; Modbus HR1364 | Write | ||
| AV | 2873 | RegPrbErrThermWhlReq | Thermal wheel request in case of regulation probe error: modulating; Modbus HR1365 | Write | ||
| PIV | 2874 | RegPrbErrByPassDampReq_OnOff | Bypass damper request in case of regulation probe error: on/off; Modbus HR1366 | Write | ||
| AV | 2875 | RegPrbErrMixDampReq | Mixing damper request in case of regulation probe error; Modbus HR1367 | Write | ||
| PIV | 2876 | RegPrbErrMixDampReq_OnOff | Mixing damper request in case of regulation probe error; Modbus HR1368 | Write | ||
| AV | 2877 | RegPrbErrExhDampReq | Exhaust damper request in case of regulation probe error; Modbus HR1369 | Write | ||
| PIV | 2878 | RegPrbErrExhDampReq_OnOff | Exhaust damper request in case of regulation probe error; Modbus HR1370 | Write | ||
| AV | 2879 | RegPrbErrSupplyAirDampReq | Supply damper request in case of regulation probe error; Modbus HR1371 | Write | ||
| PIV | 2880 | RegPrbErrSupplyAirDampReq_OnOff | Supply damper request in case of regulation probe error; Modbus HR1372 | Write | ||
| AV | 2881 | RegPrbErrRetAirDampReq | Return damper request in case of regulation probe error; Modbus HR1373 | Write | ||
| PIV | 2882 | RegPrbErrRetAirDampReq_OnOff | Return damper request in case of regulation probe error; Modbus HR1374 | Write | ||
| AV | 2883 | RegPrbErrMainCoilReq | Main coil request in case of regulation probe error; Modbus HR1375 | Write | ||
| AV | 2884 | RegPrbErrPreHeatCoilReq | PreHeating coil request in case of regulation probe error; Modbus HR1376 | Write | ||
| AV | 2885 | RegPrbErrReHeatCoilReq | PostHeating coil request in case of regulation probe error; Modbus HR1377 | Write | ||
| PIV | 2886 | RegPrbErrSupplyFanReq_3Speed | Supply fan speed request in case of regulation probe error; Modbus HR1378 | Write | ||
| AV | 2887 | RegPrbErrSupplyFanReq | Supply fan speed request in case of regulation probe error; Modbus HR1379 | Write | ||
| PIV | 2888 | RegPrbErrSupplyFanReq_OnOff | Supply fan speed request in case of regulation probe error; Modbus HR1380 | Write | ||
| PIV | 2889 | RegPrbErrRetFanReq_3Speed | Supply fan speed request in case of regulation probe error; Modbus HR1381 | Write | ||
| AV | 2890 | RegPrbErrRetFanReq | Return fan speed request in case of regulation probe error; Modbus HR1382 | Write | ||
| PIV | 2891 | RegPrbErrRetFanReq_OnOff | Supply fan speed request in case of regulation probe error; Modbus HR1383 | Write | ||
| AV | 2892 | RegPrbErrCompReq | Compressor request in case of regulation probe error: BLDC; Modbus HR1384 | Write | ||
| PIV | 2893 | RegPrbErrCompReq_OnOff | Compressor request in case of regulation probe error: On/off; Modbus HR1385 | Write | ||
| AV | 2894 | RegPrbErrHumReq | Humidification request in case of regulation probe error; Modbus HR1386 | Write | ||
| AV | 2895 | RegPrbErr_IECReq | IEC: request in case of regulation probe error; Modbus HR1387 | Write | ||
| PIV | 2897 | AuxRegTyp | Auxiliary regulation type; Modbus HR1389 | Write | ||
| PIV | 2898 | BMS_Offline_MngTyp | BMS Offline alarm management (0: Disabled; 1: Only Warning; 2: ...; Modbus HR1390 | Write | ||
| PIV | 2899 | BMS_Offline_Alrm_Timeout | BMS Offline alarm timeout [s]; Modbus HR1391 | Write | ||
| PIV | 2900 | MaskMng.ValA_Selection_PGDX | pGDx: Main variable selection; Modbus HR1392 | Write | ||
| PIV | 2901 | MaskMng.ValB_Selection_PGDX | pGDx: Second variable selection; Modbus HR1393 | Write | ||
| PIV | 2902 | GeneralMng.SetWipeMem | Set wipe memory; Modbus HR1394 | Write | ||
| PIV | 2903 | WrkHrs_Unit.WrkHrs_Thrsh | Unit - Working hours threshold (1000hrs); Modbus HR1395 | Write | ||
| PIV | 2904 | WrkHrs_Unit.WrkHrs_Res | Unit - Working hours reset; Modbus HR1396 | Write | ||
| PIV | 2905 | WrkHrs_SupplyFan.WrkHrs_Thrsh | Supply Fan - Working hours threshold (1000hrs); Modbus HR1397 | Write | ||
| PIV | 2906 | WrkHrs_SupplyFan.WrkHrs_Res | Supply Fan - Working hours reset; Modbus HR1398 | Write | ||
| PIV | 2907 | WrkHrs_ReturnFan.WrkHrs_Thrsh | Return Fan - Working hours threshold (1000hrs); Modbus HR1399 | Write | ||
| PIV | 2908 | WrkHrs_ReturnFan.WrkHrs_Res | Return Fan - Working hours reset; Modbus HR1400 | Write | ||
| PIV | 2909 | WrkHrs_DirtyFilt.WrkHrs_Thrsh | Dirty filters - Working hours threshold (1000hrs); Modbus HR1401 | Write | ||
| PIV | 2910 | WrkHrs_DirtyFilt.WrkHrs_Res | Dirty filters - Working hours reset; Modbus HR1402 | Write | ||
| PIV | 2911 | WrkHrs_ThrmlWheel.WrkHrs_Thrsh | Thermal wheel - Working hours threshold (1000hrs); Modbus HR1403 | Write | ||
| PIV | 2912 | WrkHrs_ThrmlWheel.WrkHrs_Res | Thermal wheel - Working hours reset; Modbus HR1404 | Write | ||
| PIV | 2913 | WrkHrs_Comp.WrkHrs_Thrsh | Compressor - Working hours threshold (1000hrs); Modbus HR1405 | Write | ||
| PIV | 2914 | WrkHrs_Comp.WrkHrs_Res | Compressor - Working hours reset; Modbus HR1406 | Write | ||
| PIV | 2915 | WrkHrs_IEC.WrkHrs_Thrsh | IEC - Working hours threshold (1000hrs); Modbus HR1407 | Write | ||
| PIV | 2916 | WrkHrs_IEC.WrkHrs_Res | IEC - Working hours reset; Modbus HR1408 | Write | ||
| PIV | 2917 | WrkHrs_Humidifier.WrkHrs_Thrsh | Humidifier - Working hours threshold (1000hrs); Modbus HR1409 | Write | ||
| PIV | 2918 | WrkHrs_Humidifier.WrkHrs_Res | Humidifier - Working hours reset; Modbus HR1410 | Write | ||
| PIV | 2919 | WrkHrs_AuxDout.WrkHrs_Thrsh | Auxiliary digital output - Working hours threshold (1000hrs); Modbus HR1411 | Write | ||
| PIV | 2920 | WrkHrs_AuxDout.WrkHrs_Res | Auxiliary digital output - Working hours reset; Modbus HR1412 | Write | ||
| PIV | 2921 | WrkHrs_AuxAout.WrkHrs_Thrsh | Auxiliary analogue output - Working hours threshold (1000hrs); Modbus HR1413 | Write | ||
| PIV | 2922 | WrkHrs_AuxAout.WrkHrs_Res | Auxiliary analogue output - Working hours reset; Modbus HR1414 | Write | ||
| PIV | 2923 | WrkHrs_MainCoilPmp1.WrkHrs_Thrsh | Main coil pump 1 - Working hours threshold (1000hrs); Modbus HR1415 | Write | ||
| PIV | 2924 | WrkHrs_MainCoilPmp1.WrkHrs_Res | Main coil pump 1 - Working hours reset; Modbus HR1416 | Write | ||
| PIV | 2925 | WrkHrs_MainCoilPmp2.WrkHrs_Thrsh | Main coil pump 2 - Working hours threshold (1000hrs); Modbus HR1417 | Write | ||
| PIV | 2926 | WrkHrs_MainCoilPmp2.WrkHrs_Res | Main coil pump 2 - Working hours reset; Modbus HR1418 | Write | ||
| PIV | 2927 | WrkHrs_MainCoilAout.WrkHrs_Thrsh | Main coil analog output - Working hours threshold (1000hrs); Modbus HR1419 | Write | ||
| PIV | 2928 | WrkHrs_MainCoilAout.WrkHrs_Res | Main coil analog output - Working hours reset; Modbus HR1420 | Write | ||
| PIV | 2929 | WrkHrs_MainCoilStep1.WrkHrs_Thrsh | Main coil step 1 - Working hours threshold (1000hrs); Modbus HR1421 | Write | ||
| PIV | 2930 | WrkHrs_MainCoilStep1.WrkHrs_Res | Main coil step 1 - Working hours reset; Modbus HR1422 | Write | ||
| PIV | 2931 | WrkHrs_MainCoilStep2.WrkHrs_Thrsh | Main coil step 2 - Working hours threshold (1000hrs); Modbus HR1423 | Write | ||
| PIV | 2932 | WrkHrs_MainCoilStep2.WrkHrs_Res | Main coil step 2 - Working hours reset; Modbus HR1424 | Write | ||
| PIV | 2933 | WrkHrs_MainCoilStep3.WrkHrs_Thrsh | Main coil step 3 - Working hours threshold (1000hrs); Modbus HR1425 | Write | ||
| PIV | 2934 | WrkHrs_MainCoilStep3.WrkHrs_Res | Main coil step 3 - Working hours reset; Modbus HR1426 | Write | ||
| PIV | 2935 | WrkHrs_MainCoilStep4.WrkHrs_Thrsh | Main coil step 4 - Working hours threshold (1000hrs); Modbus HR1427 | Write | ||
| PIV | 2936 | WrkHrs_MainCoilStep4.WrkHrs_Res | Main coil step 4 - Working hours reset; Modbus HR1428 | Write | ||
| PIV | 2937 | WrkHrs_PreHeatCoilPmp1.WrkHrs_Thrsh | Pre-heat coil pump 1 - Working hours threshold (1000hrs); Modbus HR1429 | Write | ||
| PIV | 2938 | WrkHrs_PreHeatCoilPmp1.WrkHrs_Res | Pre-heat coil pump 1 - Working hours reset; Modbus HR1430 | Write | ||
| PIV | 2939 | WrkHrs_PreHeatCoilPmp2.WrkHrs_Thrsh | Pre-heat coil pump 2 - Working hours threshold (1000hrs); Modbus HR1431 | Write | ||
| PIV | 2940 | WrkHrs_PreHeatCoilPmp2.WrkHrs_Res | Pre-heat coil pump 2 - Working hours reset; Modbus HR1432 | Write | ||
| PIV | 2941 | WrkHrs_PreHeatCoilAout.WrkHrs_Thrsh | Pre-heat coil analog output - Working hours threshold (1000hrs); Modbus HR1433 | Write | ||
| PIV | 2942 | WrkHrs_PreHeatCoilAout.WrkHrs_Res | Pre-heat coil analog output - Working hours reset; Modbus HR1434 | Write | ||
| PIV | 2943 | WrkHrs_PreHeatCoilStep1.WrkHrs_Thrsh | Pre-heat coil step 1 - Working hours threshold (1000hrs); Modbus HR1435 | Write | ||
| PIV | 2944 | WrkHrs_PreHeatCoilStep1.WrkHrs_Res | Pre-heat coil step 1 - Working hours reset; Modbus HR1436 | Write | ||
| PIV | 2945 | WrkHrs_PreHeatCoilStep2.WrkHrs_Thrsh | Pre-heat coil step 2 - Working hours threshold (1000hrs); Modbus HR1437 | Write | ||
| PIV | 2946 | WrkHrs_PreHeatCoilStep2.WrkHrs_Res | Pre-heat coil step 2 - Working hours reset; Modbus HR1438 | Write | ||
| PIV | 2947 | WrkHrs_PreHeatCoilStep3.WrkHrs_Thrsh | Pre-heat coil step 3 - Working hours threshold (1000hrs); Modbus HR1439 | Write | ||
| PIV | 2948 | WrkHrs_PreHeatCoilStep3.WrkHrs_Res | Pre-heat coil step 3 - Working hours reset; Modbus HR1440 | Write | ||
| PIV | 2949 | WrkHrs_PreHeatCoilStep4.WrkHrs_Thrsh | Pre-heat coil step 4 - Working hours threshold (1000hrs); Modbus HR1441 | Write | ||
| PIV | 2950 | WrkHrs_PreHeatCoilStep4.WrkHrs_Res | Pre-heat coil step 4 - Working hours reset; Modbus HR1442 | Write | ||
| PIV | 2951 | WrkHrs_ReHeatCoilPmp1.WrkHrs_Thrsh | Re-heat coil pump 1 - Working hours threshold (1000hrs); Modbus HR1443 | Write | ||
| PIV | 2952 | WrkHrs_ReHeatCoilPmp1.WrkHrs_Res | Re-heat coil pump 1 - Working hours reset; Modbus HR1444 | Write | ||
| PIV | 2953 | WrkHrs_ReHeatCoilPmp2.WrkHrs_Thrsh | Re-heat coil pump 2 - Working hours threshold (1000hrs); Modbus HR1445 | Write | ||
| PIV | 2954 | WrkHrs_ReHeatCoilPmp2.WrkHrs_Res | Re-heat coil pump 2 - Working hours reset; Modbus HR1446 | Write | ||
| PIV | 2955 | WrkHrs_ReHeatCoilAout.WrkHrs_Thrsh | Re-heat coil analog output - Working hours threshold (1000hrs); Modbus HR1447 | Write | ||
| PIV | 2956 | WrkHrs_ReHeatCoilAout.WrkHrs_Res | Re-heat coil analog output - Working hours reset; Modbus HR1448 | Write | ||
| PIV | 2957 | WrkHrs_ReHeatCoilStep1.WrkHrs_Thrsh | Re-heat coil step 1 - Working hours threshold (1000hrs); Modbus HR1449 | Write | ||
| PIV | 2958 | WrkHrs_ReHeatCoilStep1.WrkHrs_Res | Re-heat coil step 1 - Working hours reset; Modbus HR1450 | Write | ||
| PIV | 2959 | WrkHrs_ReHeatCoilStep2.WrkHrs_Thrsh | Re-heat coil step 2 - Working hours threshold (1000hrs); Modbus HR1451 | Write | ||
| PIV | 2960 | WrkHrs_ReHeatCoilStep2.WrkHrs_Res | Re-heat coil step 2 - Working hours reset; Modbus HR1452 | Write | ||
| PIV | 2961 | WrkHrs_ReHeatCoilStep3.WrkHrs_Thrsh | Re-heat coil step 3 - Working hours threshold (1000hrs); Modbus HR1453 | Write | ||
| PIV | 2962 | WrkHrs_ReHeatCoilStep3.WrkHrs_Res | Re-heat coil step 3 - Working hours reset; Modbus HR1454 | Write | ||
| PIV | 2963 | WrkHrs_ReHeatCoilStep4.WrkHrs_Thrsh | Re-heat coil step 4 - Working hours threshold (1000hrs); Modbus HR1455 | Write | ||
| PIV | 2964 | WrkHrs_ReHeatCoilStep4.WrkHrs_Res | Re-heat coil step 4 - Working hours reset; Modbus HR1456 | Write | ||
| PIV | 2965 | WorkingHrs.WrkHrs_ResTotCnt | Reset total working hours counter of all devices; Modbus HR1457 | Write | ||
| AV | 2966 | Regulation.BypassDampHeatRecovDelta_Cool | Heat recovery delta for bypass damp in cooling mode; Modbus HR1458 | Write | ||
| AV | 2967 | Regulation.BypassDampHeatRecovDelta_Heat | Heat recovery delta for bypass damp in heating mode; Modbus HR1459 | Write | ||
| AV | 2968 | HeatExchg_PID_Params.Kp | Heat exchanger PID parameters - Proportional gain; Modbus HR1460 | Write | ||
| PIV | 2969 | HeatExchg_PID_Params.Ti | Heat exchanger PID parameters - Integral time; Modbus HR1461 | Write | ||
| AV | 2970 | Defrost.BypassDamp_MinOpThrsh | Bypass damper: minimum opening threshold; Modbus HR1462 | Write | ||
| AV | 2971 | Defrost.BypassDamp_MaxOpThrsh | Bypass damper: maximum opening threshold; Modbus HR1463 | Write | ||
| PIV | 2972 | Defrost.MinT_BetweenDfr_HeatExchg | Minimum time between heat exchanger defrost; 32-bit (2 Modbus registers); Modbus HR1464 | Write | ||
| PIV | 2973 | Defrost.MaxDfrDuration_HeatExchg | Maximum defrost heat exchanger duration; 32-bit (2 Modbus registers); Modbus HR1466 | Write | ||
| AV | 2974 | Defrost.ExhTempThrsh | Exhaust temperature threshold for defrost; Modbus HR1468 | Write | ||
| AV | 2975 | HeatExchanger.DeltaHeatExchgEfficiency | Stratification correction factor of the room temperature; Modbus HR1469 | Write | ||
| AV | 2976 | Fans.AirP_PrbErr_RetFanReq | Return fan request in case of air pressure probe error; Modbus HR1470 | Write | ||
| AV | 2977 | Fans_regulation.RetFanOffsetReq | Return fan offset request; Modbus HR1471 | Write | ||
| PIV | 2978 | RetFanRampUpT | Time in [s]for a positive change for return fan; Modbus HR1472 | Write | ||
| PIV | 2979 | RetFanRampDwnT | Time in [s] for a negative change of set value ...; Modbus HR1473 | Write | ||
| IV | 2980 | RetFan_EmergencySet_rpm | Return Fan ebmpapst - speed in emergency in rpm; 32-bit ...; Modbus HR1474 | Write | ||
| PIV | 2981 | RetFan_EmergLagT | Time in ms before entering in emergency mode for Ebmpapst ...; Modbus HR1476 | Write | ||
| PIV | 2985 | RetFan_SerDevCfg_Timeout | Return Fan - Serial interface settings - Frame timeout (ms); ...; 32-bit; Modbus HR1481 | Write | ||
| PIV | 2986 | RetFan_SerDevCfg_CmdDT | Return Fan - Serial interface settings - Command delay time ...; 32-bit; Modbus HR1483 | Write | ||
| PIV | 2989 | ZiehlAbegg_ReturnFan.SerialInterface_ZA_1.SerDevCfg.DevAddr | ZA1 Return - Serial interface parameters - Fan Network address; ...; 32-bit; Modbus HR1487 | Write | ||
| PIV | 2992 | FanRegTyp | Fan regulation type (0: Static pressure; 1: Air flow; 2: ...; Modbus HR1491 | Write | ||
| AV | 2993 | FansAirQuality_PID_Params.Kp | Air Quality - Fans PID parameters - Proportional gain; Modbus HR1492 | Write | ||
| PIV | 2994 | FansAirQuality_PID_Params.Ti | Air Quality - Fans PID parameters - Integral time; Modbus HR1493 | Write | ||
| PIV | 2995 | AirFlwSwTyp | Air flow switch check type: 0=none; 1=common; 2=supply onlu; 3=supply+return; Modbus HR1494 | Write | ||
| PIV | 2996 | AirFlw_ChkTyp | Air flow check type; Modbus HR1495 | Write | ||
| PIV | 2997 | StateMachine.RetryNoAirFlwAlrm | Number of retry after return or supply air flow switch ...; Modbus HR1496 | Write | ||
| PIV | 2998 | AirFlwSwDT | Timeout for air flow switch detection (seconds); Modbus HR1497 | Write | ||
| PIV | 2999 | Fans.AirFlwSwRunAlrmDT | Air flow switch alarm delay time in running mode (s); Modbus HR1498 | Write | ||
| AV | 3000 | AirFlw_ChkPThrsh | Air flow check pressure threshold; Modbus HR1499 | Write | ||
| PIV | 3001 | StateMachine.FanPostVentilationT | Fan post ventilation time; Modbus HR1500 | Write | ||
| PIV | 3002 | NightMinVent_StartHour | Night minimum ventilation: starting hour; Modbus HR1501 | Write | ||
| PIV | 3003 | NightMinVent_StartMin | Night minimum ventilation: starting minutes; Modbus HR1502 | Write | ||
| PIV | 3004 | NightMinVent_EndHour | Night minimum ventilation: ending hour; Modbus HR1503 | Write | ||
| PIV | 3005 | NightMinVent_EndMin | Night minimum ventilation: ending minutes; Modbus HR1504 | Write | ||
| AV | 3006 | Fans_regulation.NightMinVent_MaxReq | Night minimum ventilation request; Modbus HR1505 | Write | ||
| AV | 3007 | Fans_regulation.AirFlw_K_Factor | Fan K factor for air flow calculations; Modbus HR1506 | Write | ||
| AV | 3008 | Fans_regulation.FanFixSpeed_Req | Fan fixed speed request; Modbus HR1507 | Write | ||
| PIV | 3009 | Fans_regulation.FansThreeSpeedFixSpeedReq | (0 = SPEED1; 1= SPEED2; 2= SPEED 3) Three speed ...; Modbus HR1508 | Write | ||
| AV | 3010 | FansThreeSpeed1 | Three speed fan limit 1; Modbus HR1509 | Write | ||
| AV | 3011 | FansThreeSpeed2 | Three speed fan limit 2; Modbus HR1510 | Write | ||
| AV | 3012 | FansThreeSpeed3 | Three speed fan limit 3; Modbus HR1511 | Write | ||
| AV | 3013 | Fans_regulation.AirQualityFanMinReq | Fan air quality minimum request; Modbus HR1512 | Write | ||
| AV | 3014 | FanTempReg_PID_Params.Kp | Fan temperature regulation PID parameters - Proportional gain; Modbus HR1513 | Write | ||
| PIV | 3015 | FanTempReg_PID_Params.Ti | Fan temperature regulation PID parameters - Integral time; Modbus HR1514 | Write | ||
| AV | 3016 | Fans_regulation.SupplyFan_PID_Params.Kp | Proportional gain; Modbus HR1515 | Write | ||
| PIV | 3017 | Fans_regulation.SupplyFan_PID_Params.Ti | Integral time; Modbus HR1516 | Write | ||
| AV | 3018 | Fans_regulation.SupplyFan_PID_Params.DeadBand | Dead band; Modbus HR1517 | Write | ||
| AV | 3019 | Fans_regulation.SupplyAirFlwDeadband | Supply air flow deadband; Modbus HR1518 | Write | ||
| PIV | 3020 | CompMinOnT | Compressor minumum On time; Modbus HR1519 | Write | ||
| PIV | 3021 | CompMinOffT | Compressor minumum Off time; Modbus HR1520 | Write | ||
| PIV | 3022 | CompMinOnOnSameT | Compressor minumum time between two start; Modbus HR1521 | Write | ||
| PIV | 3023 | AlarmsMng.LowSuctP_Sw_AlrmStartUpDT | Low suction pressure alarm delay time at start up; Modbus HR1522 | Write | ||
| PIV | 3024 | AlarmsMng.LowSuctP_Sw_AlrmRunDT | Low suction pressure alarm delay time at running time; Modbus HR1523 | Write | ||
| PIV | 3025 | LowSuctP_Alrm_CntMax | Low suction pressure alarm: counter max; Modbus HR1524 | Write | ||
| PIV | 3026 | LowSuctP_Alrm_TimeValue | Low suction pressure alarm: time value; Modbus HR1525 | Write | ||
| AV | 3027 | Defrost.DfrStartThrsh | Evaporator defrost start threshold; Modbus HR1526 | Write | ||
| AV | 3028 | Defrost.DfrEndThrsh | Evaporator defrost end threshold; Modbus HR1527 | Write | ||
| AV | 3029 | Defrost.DfrDeltaBypassDamp | Defrost delta bypass damper; Modbus HR1528 | Write | ||
| PIV | 3030 | Defrost.DfrStartDT | Evaporator defrost start delay time; Modbus HR1529 | Write | ||
| PIV | 3031 | Defrost.DfrT_StopComp | Defrost time for stop compressor; Modbus HR1530 | Write | ||
| PIV | 3032 | DfrMinT | Defrost minimum time; Modbus HR1531 | Write | ||
| PIV | 3033 | DfrMaxT | Defrost maximum time; Modbus HR1532 | Write | ||
| PIV | 3034 | DfrIntervalT | Time between two defrost; Modbus HR1533 | Write | ||
| PIV | 3035 | DfrDripT | Defrost dripping time; Modbus HR1534 | Write | ||
| PIV | 3036 | DfrPostDripT | Post-dripping time [s]; Modbus HR1535 | Write | ||
| AV | 3037 | RevVlvSpeedRps | BLDC minimum speed in defrost; Modbus HR1536 | Write | ||
| AV | 3038 | RevVlvDeltaP | Reverse valve delta P; Modbus HR1537 | Write | ||
| PIV | 3039 | Defrost.DfrBeforeChgOverDT | Defrost: delay time before change over; Modbus HR1538 | Write | ||
| PIV | 3040 | Defrost.DfrAfterChgOverDT | Defrost: delay time after change over; Modbus HR1539 | Write | ||
| PIV | 3041 | FansDfrReq_3Speed | Fans request during evaporator defrost; Modbus HR1540 | Write | ||
| AV | 3042 | FansDfrReq | Fans request during evaporator defrost; Modbus HR1541 | Write | ||
| PIV | 3043 | FansDfrReq_OnOff | Fans request during evaporator defrost; Modbus HR1542 | Write | ||
| PIV | 3044 | FansDfrDrippingReq_3Speed | Fans request during evaporator defrost: dripping; Modbus HR1543 | Write | ||
| AV | 3045 | FansDfrDrippingReq | Fans request during evaporator defrost: dripping; Modbus HR1544 | Write | ||
| PIV | 3046 | FansDfrDrippingReq_OnOff | Fans request during evaporator defrost: dripping; Modbus HR1545 | Write | ||
| PIV | 3047 | FansDfrPostDrippingReq_3Speed | Fans request during evaporator defrost: post dripping; Modbus HR1546 | Write | ||
| AV | 3048 | FansDfrPostDrippingReq | Fans request during evaporator defrost: post dripping; Modbus HR1547 | Write | ||
| PIV | 3049 | FansDfrPostDrippingReq_OnOff | Fans request during evaporator defrost: post dripping; Modbus HR1548 | Write | ||
| AV | 3050 | HumDehumReg.Hum_PID.Kp | Humidification PID parameters - Proportional gain; Modbus HR1549 | Write | ||
| PIV | 3051 | HumDehumReg.Hum_PID.Ti | Humidification PID parameters - Integral time; Modbus HR1550 | Write | ||
| PIV | 3052 | HumDehumReg.Hum_PID.Td | Humidification PID parameters - Derivative time; Modbus HR1551 | Write | ||
| AV | 3053 | Hum_MaxLim_Thrsh | Humidifier: Max humidity threshold; Modbus HR1552 | Write | ||
| AV | 3054 | Hum_MaxLim_Kp | Humidifier: Max humidity proportional part; Modbus HR1553 | Write | ||
| PIV | 3055 | Hum_MaxLim_Ti | Humidifier: Max humidity integral time; Modbus HR1554 | Write | ||
| AV | 3056 | Hum_MinTemp_Kp | Humidifier: Min temperature proportional part (Only adiabatic hum); Modbus HR1555 | Write | ||
| PIV | 3057 | Hum_MinTemp_Ti | Humidifier: Min temperature integral time (Only adiabatic hum); Modbus HR1556 | Write | ||
| IV | 3058 | Humisonic.DevSettings_HUMS.WashingTimeSet.DTBetweenWash | Parameters for device configuration - Timings for washing operations - ...; Modbus HR1557 | Write | ||
| IV | 3059 | Humisonic.DevSettings_HUMS.WashingTimeSet.DTInactivWash | Parameters for device configuration - Timings for washing operations - ...; Modbus HR1558 | Write | ||
| IV | 3060 | Humisonic.DevSettings_HUMS.WashingTimeSet.WashTime | Parameters for device configuration - Timings for washing operations - ...; Modbus HR1559 | Write | ||
| PIV | 3061 | AlarmsMng.DirtyFiltAlrmDT | Delay time for dirty filter by DIN; 32-bit (2 Modbus registers); Modbus HR1560 | Write | ||
| AV | 3062 | HEPA_Filter_AlrmThrsh | HEPA filter alarm threshold; Modbus HR1562 | Write | ||
| AV | 3063 | Fans.AirP_PrbErr_SupplyFanReq | Supply fan request in case of air pressure probe error; Modbus HR1563 | Write | ||
| AV | 3064 | AFreezeFansMinSpeed | Minimum fan speed during antifreeze; Modbus HR1564 | Write | ||
| PIV | 3065 | SupplyFanRampUpT | Time in [s]for a positive change for Supply fan; Modbus HR1565 | Write | ||
| PIV | 3066 | SupplyFanRampDwnT | Time in [s] for a negative change of set value ...; Modbus HR1566 | Write | ||
| IV | 3067 | SupplyFan_EmergencySet_rpm | Fan speed in emergency in rpm; 32-bit (2 Modbus registers); Modbus HR1567 | Write | ||
| PIV | 3068 | SupplyFan_EmergLagT | Time in ms before entering in emergency mode for Ebmpapst fan; Modbus HR1569 | Write | ||
| PIV | 3069 | Ebmpapst_SupplyFan.SerInterfaceSet_EBM_1.CfgProtocol.DevAddr | EBM1 Supply - Serial interface settings - Network address for ...; 32-bit; Modbus HR1570 | Write | ||
| PIV | 3072 | SupplyFan_SerDevCfg_Timeout | Supply Fan - Serial interface settings - Frame timeout (ms); ...; 32-bit; Modbus HR1574 | Write | ||
| PIV | 3073 | SupplyFan_SerDevCfg_CmdDT | Supply Fan - Serial interface settings - Command delay time ...; 32-bit; Modbus HR1576 | Write | ||
| PIV | 3076 | ZiehlAbegg_SupplyFan.SerialInterface_ZA_1.SerDevCfg.DevAddr | ZA1 Supply - Serial interface parameters - Fan Network address; ...; 32-bit; Modbus HR1580 | Write | ||
| PIV | 3079 | AuxReg1_Cfg.InputSel | Auxiliary Regulation 1 - Input selection; Modbus HR1584 | Write | ||
| PIV | 3080 | AuxReg1_Cfg.OutputSel | Auxiliary Regulation 1 - Output selection; Modbus HR1585 | Write | ||
| AV | 3081 | AuxReg1_Cfg.Modul_ErrorValue | Auxiliary Regulation 1 - Modulating: Error value; Modbus HR1586 | Write | ||
| PIV | 3082 | AuxReg1_Cfg.EnableSel | Auxiliary Regulation 1 - Enable selection; Modbus HR1587 | Write | ||
| PIV | 3083 | AuxReg1_Cfg.SetPSel | Auxiliary Regulation 1 - Setpoint selection; Modbus HR1588 | Write | ||
| AV | 3084 | AuxReg1_Cfg.Modul_LowLim | Auxiliary Regulation 1 - Modulating: Low limit; Modbus HR1589 | Write | ||
| AV | 3085 | AuxReg1_Cfg.DOut_Diff | Auxiliary Regulation 1 - Dout: Differential; Modbus HR1590 | Write | ||
| AV | 3086 | AuxReg1_Cfg.Modul_HighLim | Auxiliary Regulation 1 - Modulating: High limit; Modbus HR1591 | Write | ||
| AV | 3087 | AuxReg1_Cfg.Modul_Kp | Auxiliary Regulation 1 - Modulating: Kp; Modbus HR1592 | Write | ||
| PIV | 3088 | AuxReg1_Cfg.Modul_Ti | Auxiliary Regulation 1 - Modulating: Integral time; Modbus HR1593 | Write | ||
| PIV | 3089 | AuxReg1_Cfg.Modul_Td | Auxiliary Regulation 1 - Modulating: Derivative time; Modbus HR1594 | Write | ||
| AV | 3090 | AuxReg1_Cfg.Modul_DeadBand | Auxiliary Regulation 1 - Modulating: Dead Band; Modbus HR1595 | Write | ||
| AV | 3091 | AuxReg1_Cfg.Modul_ManModeVal | Auxiliary Regulation 1 - Modulating: Manual mode value; Modbus HR1596 | Write | ||
| PIV | 3092 | AuxReg2_Cfg.InputSel | Auxiliary Regulation 2 - Input selection; Modbus HR1597 | Write | ||
| PIV | 3093 | AuxReg2_Cfg.OutputSel | Auxiliary Regulation 2 - Output selection; Modbus HR1598 | Write | ||
| AV | 3094 | AuxReg2_Cfg.Modul_ErrorValue | Auxiliary Regulation 2 - Modulating: Error value; Modbus HR1599 | Write | ||
| PIV | 3095 | AuxReg2_Cfg.EnableSel | Auxiliary Regulation 2 - Enable selection; Modbus HR1600 | Write | ||
| PIV | 3096 | AuxReg2_Cfg.SetPSel | Auxiliary Regulation 2 - Setpoint selection; Modbus HR1601 | Write | ||
| AV | 3097 | AuxReg2_Cfg.SetP | Auxiliary Regulation 2 - Regulation setpoint; Modbus HR1602 | Write | ||
| AV | 3098 | AuxReg2_Cfg.Modul_LowLim | Auxiliary Regulation 2 - Modulating: Low limit; Modbus HR1603 | Write | ||
| AV | 3099 | AuxReg2_Cfg.DOut_Diff | Auxiliary Regulation 2 - Dout: Differential; Modbus HR1604 | Write | ||
| AV | 3100 | AuxReg2_Cfg.Modul_HighLim | Auxiliary Regulation 2 - Modulating: High limit; Modbus HR1605 | Write | ||
| AV | 3101 | AuxReg2_Cfg.Modul_Kp | Auxiliary Regulation 2 - Modulating: Kp; Modbus HR1606 | Write | ||
| PIV | 3102 | AuxReg2_Cfg.Modul_Ti | Auxiliary Regulation 2 - Modulating: Integral time; Modbus HR1607 | Write | ||
| PIV | 3103 | AuxReg2_Cfg.Modul_Td | Auxiliary Regulation 2 - Modulating: Derivative time; Modbus HR1608 | Write | ||
| AV | 3104 | AuxReg2_Cfg.Modul_DeadBand | Auxiliary Regulation 2 - Modulating: Dead Band; Modbus HR1609 | Write | ||
| AV | 3105 | AuxReg2_Cfg.Modul_ManModeVal | Auxiliary Regulation 2 - Modulating: Manual mode value; Modbus HR1610 | Write | ||
| PIV | 3106 | AuxReg3_Cfg.InputSel | Auxiliary Regulation 3 - Input selection; Modbus HR1611 | Write | ||
| PIV | 3107 | AuxReg3_Cfg.OutputSel | Auxiliary Regulation 3 - Output selection; Modbus HR1612 | Write | ||
| AV | 3108 | AuxReg3_Cfg.Modul_ErrorValue | Auxiliary Regulation 3 - Modulating: Error value; Modbus HR1613 | Write | ||
| PIV | 3109 | AuxReg3_Cfg.EnableSel | Auxiliary Regulation 3 - Enable selection; Modbus HR1614 | Write | ||
| PIV | 3110 | AuxReg3_Cfg.SetPSel | Auxiliary Regulation 3 - Setpoint selection; Modbus HR1615 | Write | ||
| AV | 3111 | AuxReg3_Cfg.SetP | Auxiliary Regulation 3 - Regulation setpoint; Modbus HR1616 | Write | ||
| AV | 3112 | AuxReg3_Cfg.Modul_LowLim | Auxiliary Regulation 3 - Modulating: Low limit; Modbus HR1617 | Write | ||
| AV | 3113 | AuxReg3_Cfg.DOut_Diff | Auxiliary Regulation 3 - Dout: Differential; Modbus HR1618 | Write | ||
| AV | 3114 | AuxReg3_Cfg.Modul_HighLim | Auxiliary Regulation 3 - Modulating: High limit; Modbus HR1619 | Write | ||
| AV | 3115 | AuxReg3_Cfg.Modul_Kp | Auxiliary Regulation 3 - Modulating: Kp; Modbus HR1620 | Write | ||
| PIV | 3116 | AuxReg3_Cfg.Modul_Ti | Auxiliary Regulation 3 - Modulating: Integral time; Modbus HR1621 | Write | ||
| PIV | 3117 | AuxReg3_Cfg.Modul_Td | Auxiliary Regulation 3 - Modulating: Derivative time; Modbus HR1622 | Write | ||
| AV | 3118 | AuxReg3_Cfg.Modul_DeadBand | Auxiliary Regulation 3 - Modulating: Dead Band; Modbus HR1623 | Write | ||
| AV | 3119 | AuxReg3_Cfg.Modul_ManModeVal | Auxiliary Regulation 3 - Modulating: Manual mode value; Modbus HR1624 | Write | ||
| PIV | 3120 | AuxReg4_Cfg.InputSel | Auxiliary Regulation 4 - Input selection; Modbus HR1625 | Write | ||
| PIV | 3121 | AuxReg4_Cfg.OutputSel | Auxiliary Regulation 4 - Output selection; Modbus HR1626 | Write | ||
| AV | 3122 | AuxReg4_Cfg.Modul_ErrorValue | Auxiliary Regulation 4 - Modulating: Error value; Modbus HR1627 | Write | ||
| PIV | 3123 | AuxReg4_Cfg.EnableSel | Auxiliary Regulation 4 - Enable selection; Modbus HR1628 | Write | ||
| PIV | 3124 | AuxReg4_Cfg.SetPSel | Auxiliary Regulation 4 - Setpoint selection; Modbus HR1629 | Write | ||
| AV | 3125 | AuxReg4_Cfg.SetP | Auxiliary Regulation 4 - Regulation setpoint; Modbus HR1630 | Write | ||
| AV | 3126 | AuxReg4_Cfg.Modul_LowLim | Auxiliary Regulation 4 - Modulating: Low limit; Modbus HR1631 | Write | ||
| AV | 3127 | AuxReg4_Cfg.DOut_Diff | Auxiliary Regulation 4 - Dout: Differential; Modbus HR1632 | Write | ||
| AV | 3128 | AuxReg4_Cfg.Modul_HighLim | Auxiliary Regulation 4 - Modulating: High limit; Modbus HR1633 | Write | ||
| AV | 3129 | AuxReg4_Cfg.Modul_Kp | Auxiliary Regulation 4 - Modulating: Kp; Modbus HR1634 | Write | ||
| PIV | 3130 | AuxReg4_Cfg.Modul_Ti | Auxiliary Regulation 4 - Modulating: Integral time; Modbus HR1635 | Write | ||
| PIV | 3131 | AuxReg4_Cfg.Modul_Td | Auxiliary Regulation 4 - Modulating: Derivative time; Modbus HR1636 | Write | ||
| AV | 3132 | AuxReg4_Cfg.Modul_DeadBand | Auxiliary Regulation 4 - Modulating: Dead Band; Modbus HR1637 | Write | ||
| AV | 3133 | AuxReg4_Cfg.Modul_ManModeVal | Auxiliary Regulation 4 - Modulating: Manual mode value; Modbus HR1638 | Write | ||
| PIV | 3134 | DampOpT | Damper opening time; Modbus HR1639 | Write | ||
| AV | 3135 | DampAirQuality_PID_Params.Kp | Air Quality - Dampers PID parameters - Proportional gain; Modbus HR1640 | Write | ||
| PIV | 3136 | DampAirQuality_PID_Params.Ti | Air Quality - Dampers PID parameters - Integral time; Modbus HR1641 | Write | ||
| AV | 3137 | FreshAirDamp_MinVal | Fresh air damper - Minimum regulation value; Modbus HR1642 | Write | ||
| AV | 3138 | FreshAirDamp_MaxVal | Fresh air damper - Maximum regulation value; Modbus HR1643 | Write | ||
| AV | 3139 | MixAirDamp_MinVal | Mixing air damper - Minimum regulation value; Modbus HR1644 | Write | ||
| AV | 3140 | MixAirDamp_MaxVal | Mixing air damper - Maximum regulation value; Modbus HR1645 | Write | ||
| AV | 3141 | IEC_PID_Params.Kp | IEC: PID parameters - Proportional gain; Modbus HR1646 | Write | ||
| PIV | 3142 | IEC_PID_Params.Ti | IEC: PID parameters - Integral time; Modbus HR1647 | Write | ||
| AV | 3143 | IEC_RetHumActThrsh | IEC: Return humidity activation threshold; Modbus HR1648 | Write | ||
| AV | 3144 | IEC_RetHumActDiff | IEC: Return humidity activation differential; Modbus HR1649 | Write | ||
| AV | 3145 | Regulation.IEC_ExhHumLim_Thrsh | IEC: Exhaust humidity limit threshold; Modbus HR1650 | Write | ||
| AV | 3146 | Regulation.IEC_ExhHumLim_Kp | IEC: Exhaust humidity limit proportional gain; Modbus HR1651 | Write | ||
| PIV | 3147 | Regulation.IEC_ExhHumLim_Ti | IEC: Exhaust humidity limit integral time; Modbus HR1652 | Write | ||
| AV | 3148 | Regulation.IEC_FreshAirDamp_MaxLim | IEC: Fresh air damper maximum limitation; Modbus HR1653 | Write | ||
| PIV | 3149 | MainCoil_Cfg | Main coil configuration; Modbus HR1654 | Write | ||
| PIV | 3150 | MainCoil_StpN | Main coil steps number; Modbus HR1655 | Write | ||
| AV | 3151 | CoolCoil_PID_Params.Kp | Cooling coil PID parameters - Proportional gain; Modbus HR1656 | Write | ||
| PIV | 3152 | CoolCoil_PID_Params.Ti | Cooling coil PID parameters - Integral time; Modbus HR1657 | Write | ||
| AV | 3153 | HeatCoil_PID_Params.Kp | Heating coil PID parameters - Proportional gain; Modbus HR1658 | Write | ||
| PIV | 3154 | HeatCoil_PID_Params.Ti | Heating coil PID parameters - Integral time; Modbus HR1659 | Write | ||
| AV | 3155 | HumDehumReg.DeHum_PID.Kp | Dehumidification PID parameters - Proportional gain; Modbus HR1660 | Write | ||
| PIV | 3156 | HumDehumReg.DeHum_PID.Ti | Dehumidification PID parameters - Integral time; Modbus HR1661 | Write | ||
| PIV | 3157 | HumDehumReg.DeHum_PID.Td | Dehumidification PID parameters - Derivative time; Modbus HR1662 | Write | ||
| AV | 3158 | HumDehumReg.Dehum_MaxDelta | Maximum dehumidification offset; Modbus HR1663 | Write | ||
| AV | 3159 | AFreezeHeatCoilReq | Heating coil request during antifreeze off status; Modbus HR1664 | Write | ||
| AV | 3160 | AFreezeCoolCoilReq | Cooling coil request during antifreeze off status; Modbus HR1665 | Write | ||
| PIV | 3161 | MainCoil_PmpNo | Cooling/Heating coil pumps number; Modbus HR1666 | Write | ||
| PIV | 3162 | Coils.MainCoil_PmpFlwChk_StartupT | Cooling/Heating coil pumps flow check startup delay; Modbus HR1667 | Write | ||
| PIV | 3163 | Coils.MainCoil_PmpFlwChk_RunT | Cooling/Heating coil pumps flow check run delay; Modbus HR1668 | Write | ||
| PIV | 3164 | Coils.MainCoil_PmpRotT | Cooling/Heating coil pumps rotation time; Modbus HR1669 | Write | ||
| PIV | 3165 | PreHeatCoil_StpN | PreHeating coil steps number; Modbus HR1670 | Write | ||
| AV | 3166 | PreHeatCoil_PID_Params.Kp | Pre heating PID parameters - Proportional gain; Modbus HR1671 | Write | ||
| PIV | 3167 | PreHeatCoil_PID_Params.Ti | Pre heating PID parameters - Integral time; Modbus HR1672 | Write | ||
| AV | 3168 | AFreezePreHeatCoilReq | PreHeating coil request during antifreeze off status; Modbus HR1673 | Write | ||
| PIV | 3169 | PreHeatCoil_PmpNo | PreHeating coil pumps number; Modbus HR1674 | Write | ||
| PIV | 3170 | Coils.PreHeatCoil_PmpFlwChk_StartupT | PreHeating coil pumps flow check startup delay; Modbus HR1675 | Write | ||
| PIV | 3171 | Coils.PreHeatCoil_PmpFlwChk_RunT | PreHeating coil pumps flow check run delay; Modbus HR1676 | Write | ||
| PIV | 3172 | Coils.PreHeatCoil_PmpRotT | PreHeating coil pumps rotation time; Modbus HR1677 | Write | ||
| PIV | 3173 | ReHeatCoil_StpN | PostHeating coil steps number; Modbus HR1678 | Write | ||
| AV | 3174 | ReHeatCoil_PID_Params.Kp | Post heating PID parameters - Proportional gain; Modbus HR1679 | Write | ||
| PIV | 3175 | ReHeatCoil_PID_Params.Ti | Post heating PID parameters - Integral time; Modbus HR1680 | Write | ||
| AV | 3176 | AFreezeReHeatCoilReq | PostHeating coil request during antifreeze off status; Modbus HR1681 | Write | ||
| PIV | 3177 | ReHeatCoil_PmpNo | Post Heating coil pumps number; Modbus HR1682 | Write | ||
| PIV | 3178 | Coils.ReHeatCoil_PmpFlwChk_StartupT | Re Heating coil pumps flow check startup delay; Modbus HR1683 | Write | ||
| PIV | 3179 | Coils.ReHeatCoil_PmpFlwChk_RunT | ReHeating coil pumps flow check run delay; Modbus HR1684 | Write | ||
| PIV | 3180 | Coils.ReHeatCoil_PmpRotT | Re Heating coil pumps rotation time; Modbus HR1685 | Write | ||
| PIV | 3181 | VDI_InactivityStartUp_Delay | VDI Inactivity startup activation delay; Modbus HR1686 | Write | ||
| PIV | 3182 | VDI_InactStartUp_Duration | VDI Inactivity startup duration; Modbus HR1687 | Write | ||
| AV | 3183 | VDI_HiSatHumThrsh | VDI high saturation humidity threshold; Modbus HR1688 | Write | ||
| AV | 3184 | VDI_HiSatHumDiff | VDI high saturation humidity differential; Modbus HR1689 | Write | ||
| PIV | 3185 | VDI_Typ | VDI Type: 0: Standard; 1: Custom; Modbus HR1690 | Write | ||
| PIV | 3186 | VDI_Conf[0].MonthSel | Month selection variable; Modbus HR1691 | Write | ||
| PIV | 3187 | VDI_Conf[1].MonthSel | Month selection variable; Modbus HR1692 | Write | ||
| PIV | 3188 | VDI_Conf[2].MonthSel | Month selection variable; Modbus HR1693 | Write | ||
| PIV | 3189 | VDI_Conf[3].MonthSel | Month selection variable; Modbus HR1694 | Write | ||
| PIV | 3190 | VDI_Conf[4].MonthSel | Month selection variable; Modbus HR1695 | Write | ||
| PIV | 3191 | VDI_Conf[5].MonthSel | Month selection variable; Modbus HR1696 | Write | ||
| PIV | 3192 | VDI_Conf[6].MonthSel | Month selection variable; Modbus HR1697 | Write | ||
| PIV | 3193 | VDI_Conf[7].MonthSel | Month selection variable; Modbus HR1698 | Write | ||
| PIV | 3194 | VDI_Conf[8].MonthSel | Month selection variable; Modbus HR1699 | Write | ||
| PIV | 3195 | VDI_Conf[9].MonthSel | Month selection variable; Modbus HR1700 | Write | ||
| PIV | 3196 | VDI_Conf[10].MonthSel | Month selection variable; Modbus HR1701 | Write | ||
| PIV | 3197 | VDI_Conf[11].MonthSel | Month selection variable; Modbus HR1702 | Write | ||
| PIV | 3198 | VDI_Conf[12].MonthSel | Month selection variable; Modbus HR1703 | Write | ||
| PIV | 3199 | VDI_Conf[13].MonthSel | Month selection variable; Modbus HR1704 | Write | ||
| PIV | 3200 | VDI_Conf[14].MonthSel | Month selection variable; Modbus HR1705 | Write | ||
| PIV | 3201 | VDI_Conf[15].MonthSel | Month selection variable; Modbus HR1706 | Write | ||
| PIV | 3202 | VDI_Conf[16].MonthSel | Month selection variable; Modbus HR1707 | Write | ||
| PIV | 3203 | VDI_Conf[17].MonthSel | Month selection variable; Modbus HR1708 | Write | ||
| PIV | 3204 | VDI_Conf[18].MonthSel | Month selection variable; Modbus HR1709 | Write | ||
| PIV | 3205 | VDI_Conf[19].MonthSel | Month selection variable; Modbus HR1710 | Write | ||
| PIV | 3206 | VDI_Conf[20].MonthSel | Month selection variable; Modbus HR1711 | Write | ||
| PIV | 3207 | VDI_Conf[21].MonthSel | Month selection variable; Modbus HR1712 | Write | ||
| PIV | 3208 | VDI_Conf[22].MonthSel | Month selection variable; Modbus HR1713 | Write | ||
| PIV | 3209 | VDI_Conf[23].MonthSel | Month selection variable; Modbus HR1714 | Write | ||
| PIV | 3210 | VDI_Conf[24].MonthSel | Month selection variable; Modbus HR1715 | Write | ||
| PIV | 3211 | VDI_Conf[25].MonthSel | Month selection variable; Modbus HR1716 | Write | ||
| PIV | 3212 | VDI_Conf[26].MonthSel | Month selection variable; Modbus HR1717 | Write | ||
| PIV | 3213 | VDI_Conf[27].MonthSel | Month selection variable; Modbus HR1718 | Write | ||
| PIV | 3214 | VDI_Conf[28].MonthSel | Month selection variable; Modbus HR1719 | Write | ||
| IV | 3215 | GeneralMng.DateFormat | Date format (0: DD/MM/YY; 1: MM/DD/YY; 2: YY/MM/DD); Modbus HR1720 | Write | ||
| PIV | 3216 | GeneralMng.RTC_BMS.Hour | BMS real time clock; Modbus HR1721 | Write | ||
| PIV | 3217 | GeneralMng.RTC_BMS.Minute | BMS real time clock; Modbus HR1722 | Write | ||
| PIV | 3218 | PwdUser | User password; Modbus HR1723 | Write | ||
| PIV | 3219 | PwdService | Service password; Modbus HR1724 | Write | ||
| PIV | 3220 | PwdManuf | Manufacturer password; Modbus HR1725 | Write | ||
| PIV | 3221 | GeneralMng.SPV_Addr | BMS address; Modbus HR1727 | Write | ||
| PIV | 3222 | GeneralMng.SPV_Timeout | BMS timeout; Modbus HR1728 | Write | ||
| PIV | 3223 | GeneralMng.BMS_Baudrate_msk | BMS baudrate (0=9600; 1=19200; 2=38400); Modbus HR1729 | Write | ||
| PIV | 3224 | GeneralMng.BMS_Parity | BMS parity; Modbus HR1730 | Write | ||
| PIV | 3225 | GeneralMng.BMS_StopBit | BMS stopbit; Modbus HR1731 | Write | ||
| PIV | 3226 | GeneralMng.FB_Baudrate_msk | For mask usage; Modbus HR1732 | Write | ||
| PIV | 3227 | GeneralMng.FB_Parity | Fieldbus parity; Modbus HR1733 | Write | ||
| PIV | 3228 | GeneralMng.FB_StopBit | Fieldbus stopbit; Modbus HR1734 | Write | ||
| PIV | 3229 | BLDC_compressor.MiscMng_BLDC1.Mng_PwrpAddr | PowerPlus address; 32-bit (2 Modbus registers); Modbus HR1735 | Write | ||
| PIV | 3230 | uChiller_mng.DevAddr_uCh | Device address; Modbus HR1737 | Write | ||
| PIV | 3231 | IEC.IEC_HUMFOG_DevAddr | Device address; 32-bit (2 Modbus registers); Modbus HR1738 | Write | ||
| PIV | 3232 | Humisonic.DevAddr_HUMS | Device address; 32-bit (2 Modbus registers); Modbus HR1740 | Write | ||
| PIV | 3233 | Humisonic.Timeout_HUMS | 32-bit (2 Modbus registers); Modbus timeout for Humisonic (delete after Humisonic library update); Modbus HR1742 | Write | ||
| PIV | 3234 | Humisonic.CmdDelay_HUMS | 32-bit (2 Modbus registers); Modbus command delay for Humisonic (delete after Humisonic library update); Modbus HR1744 | Write | ||
| PIV | 3235 | HumifogMng.HUMFOG_DevAddr | Device address; 32-bit (2 Modbus registers); Modbus HR1746 | Write | ||
| PIV | 3236 | Scheduler_OnOffUnit.SerDevCfg_THTN.DevAddr | Serial device configuration - Device address; 32-bit (2 Modbus registers); Modbus HR1748 | Write | ||
| PIV | 3237 | GeneralMng.StationAdr | 7seg number; 32-bit (2 Modbus registers); Modbus HR1750 | Write | ||
| IV | 3238 | Data_EVD_Emb_1.Superparameters.EEVtype.Val | Superparameters - Valve; Modbus HR1752 | Write | ||
| IV | 3239 | Data_EVD_Emb_1.EVD.Regulation.GasTyp.Val | EVD parameters - Regulation parameters configuration - Refrigerant; Modbus HR1753 | Write | ||
| AV | 3240 | EVD_Emb_Circ.EEV_SH_SetP_Cool | Superheat setpoint: cooling mode; Modbus HR1754 | Write | ||
| AV | 3241 | EVD_Emb_Circ.EEV_SH_SetP_Heat | Superheat setpoint: heating mode; Modbus HR1755 | Write | ||
| IV | 3242 | EVD_Emb_Circ.EEV_StartOpRatio_Cool | EEV start opening ratio: cooling mode; Modbus HR1756 | Write | ||
| IV | 3243 | EVD_Emb_Circ.EEV_StartOpRatio_Heat | EEV start opening ratio: heating mode; Modbus HR1757 | Write | ||
| IV | 3244 | Data_EVD_Emb_1.EVD.Regulation.SH_WaitDT.Val | EVD parameters - Regulation parameters configuration - Regulation starting delay; Modbus HR1758 | Write | ||
| IV | 3245 | Data_EVD_Emb_1.EVD.Regulation.StandByEEV_OpPos.Val | EVD parameters - Regulation parameters configuration - Standby valve opening ...; Modbus HR1759 | Write | ||
| AV | 3246 | EVD_Emb_Circ.EEV_PID_Kp_Cool | EEV Proportional gain: cooling mode; Modbus HR1760 | Write | ||
| AV | 3247 | EVD_Emb_Circ.EEV_PID_Ti_Cool | EEV Integral time: cooling mode; Modbus HR1761 | Write | ||
| AV | 3248 | EVD_Emb_Circ.EEV_PID_Td_Cool | EEV Integral time: cooling mode; Modbus HR1762 | Write | ||
| AV | 3249 | EVD_Emb_Circ.EEV_PID_Kp_Heat | EEV Proportional gain: heating mode; Modbus HR1763 | Write | ||
| AV | 3250 | EVD_Emb_Circ.EEV_PID_Ti_Heat | EEV Integral time: heating mode; Modbus HR1764 | Write | ||
| AV | 3251 | EVD_Emb_Circ.EEV_PID_Td_Heat | EEV Integral time: cooling mode; Modbus HR1765 | Write | ||
| IV | 3252 | Data_EVD_Emb_1.EVD.Regulation.LowSH_AlrmDT.Val | EVD parameters - Regulation parameters configuration - LowSH (low superheat) ...; Modbus HR1766 | Write | ||
| AV | 3253 | EVD_Emb_Circ.EEV_LowSH_Thrsh_Cool | EEV Low superheat threshold: cooling mode; Modbus HR1767 | Write | ||
| AV | 3254 | EVD_Emb_Circ.EEV_LowSH_Ti_Cool | EEV Low superheat integral time: cooling mode; Modbus HR1768 | Write | ||
| AV | 3255 | EVD_Emb_Circ.EEV_LowSH_Thrsh_Heat | EEV Low superheat threshold: heating mode; Modbus HR1769 | Write | ||
| AV | 3256 | EVD_Emb_Circ.EEV_LowSH_Ti_Heat | EEV Low superheat integral time: heating mode; Modbus HR1770 | Write | ||
| IV | 3257 | Data_EVD_Emb_1.EVD.Regulation.LOP_AlrmDT.Val | EVD parameters - Regulation parameters configuration - LOP (low evaporating ...; Modbus HR1771 | Write | ||
| AV | 3258 | EVD_Emb_Circ.EEV_LOP_Thrsh_Cool | EEV LOP threshold: cooling mode; Modbus HR1772 | Write | ||
| AV | 3259 | EVD_Emb_Circ.EEV_LOP_Ti_Cool | EEV LOP integral time: cooling mode; Modbus HR1773 | Write | ||
| AV | 3260 | EVD_Emb_Circ.EEV_LOP_Thrsh_Heat | EEV LOP threshold: heating mode; Modbus HR1774 | Write | ||
| AV | 3261 | EVD_Emb_Circ.EEV_LOP_Ti_Heat | EEV LOP integral time: heating mode; Modbus HR1775 | Write | ||
| IV | 3262 | Data_EVD_Emb_1.EVD.Regulation.MOP_AlrmDT.Val | EVD parameters - Regulation parameters configuration - MOP (high evaporating ...; Modbus HR1776 | Write | ||
| AV | 3263 | EVD_Emb_Circ.EEV_MOP_Thrsh_Cool | EEV MOP threshold: cooling mode; Modbus HR1777 | Write | ||
| AV | 3264 | EVD_Emb_Circ.EEV_MOP_Ti_Cool | EEV MOP integral time: cooling mode; Modbus HR1778 | Write | ||
| AV | 3265 | EVD_Emb_Circ.EEV_MOP_Thrsh_Heat | EEV MOP threshold: heating mode; Modbus HR1779 | Write | ||
| AV | 3266 | EVD_Emb_Circ.EEV_MOP_Ti_Heat | EEV MOP integral time: heating mode; Modbus HR1780 | Write | ||
| IV | 3267 | EVD_Emb_Circ.EEV_ManPositSteps | EEV manual poition steps; Modbus HR1781 | Write | ||
| AV | 3268 | Data_EVD_Emb_1.EVD.Regulation.LowSuctAlrmThrsh.Val | EVD parameters - Regulation parameters configuration - Low suction temperature ...; Modbus HR1782 | Write | ||
| IV | 3269 | Data_EVD_Emb_1.EVD.Regulation.LowSuctAlrmDT.Val | EVD parameters - Regulation parameters configuration - Low suction temperature ...; Modbus HR1783 | Write | ||
| IV | 3270 | Data_EVD_Emb_1.EVD.EEV_Config.RegMinPos.Val | EVD parameters - Valve configuration - EEV minimum steps; Modbus HR1784 | Write | ||
| IV | 3271 | Data_EVD_Emb_1.EVD.EEV_Config.RegMaxPos.Val | EVD parameters - Valve configuration - EEV maximum steps; Modbus HR1785 | Write | ||
| IV | 3272 | Data_EVD_Emb_1.EVD.EEV_Config.FullClosSteps.Val | EVD parameters - Valve configuration - EEV closing steps; Modbus HR1786 | Write | ||
| IV | 3273 | Data_EVD_Emb_1.EVD.EEV_Config.MoveRate.Val | EVD parameters - Valve configuration - EEV step rate; Modbus HR1787 | Write | ||
| IV | 3274 | Data_EVD_Emb_1.EVD.EEV_Config.FastClosMoveRate.Val | EVD parameters - Valve configuration - EEV: emergency EEV closing speed; Modbus HR1788 | Write | ||
| IV | 3275 | Data_EVD_Emb_1.EVD.EEV_Config.MoveDuty.Val | EVD parameters - Valve configuration - EEV duty cycle; Modbus HR1789 | Write | ||
| PIV | 3276 | BLDC_compressor.MiscMng_BLDC1.Mng_PwrpMotTyp | Compressor model (PowerPlus); Modbus HR1790 | Write | ||
| PIV | 3277 | BLDC_compressor.MiscMng_BLDC1.Mng_CompTyp | Compressor model; Modbus HR1791 | Write | ||
| PIV | 3278 | BLDC_compressor.MiscMng_PWRP1.Mng_DriveTyp | Drive type; Modbus HR1792 | Write | ||
| IV | 3279 | BLDC_compressor.MiscMng_PWRP1.Mng_WriteDefault | Write default request; Modbus HR1793 | Write | ||
| PIV | 3280 | BLDC_compressor.CurrCompCfg_PWRP1.HR29_DataCommTimeout | Curr compressor configuration (Powerplus) - Data communication fault timeout; Modbus HR1794 | Write | ||
| AV | 3281 | BLDC_compressor.CurrCompCfg_PWRP1.HR07_MinOutFreq | Curr compressor configuration (Powerplus) - Min output frequency; Modbus HR1795 | Write | ||
| AV | 3282 | BLDC_compressor.CurrCompCfg_PWRP1.HR06_MaxOutFreq | Curr compressor configuration (Powerplus) - Max output frequency; Modbus HR1796 | Write | ||
| AV | 3283 | BLDC_compressor.CurrCompCfg_PWRP1.HR10_SkipFreqSetP | Curr compressor configuration (Powerplus) - Skip frequency: set 1; Modbus HR1797 | Write | ||
| AV | 3284 | BLDC_compressor.CurrCompCfg_PWRP1.HR11_SkipFreqBand | Curr compressor configuration (Powerplus) - Skip frequency: band 1; Modbus HR1798 | Write | ||
| AV | 3285 | BLDC_compressor.CurrCompCfg_PWRP1.HR67_SkipFreqSetP_2 | Curr compressor configuration (Powerplus) - Skip frequency setpoint 2; Modbus HR1799 | Write | ||
| AV | 3286 | BLDC_compressor.CurrCompCfg_PWRP1.HR68_SkipFreqBand_2 | Curr compressor configuration (Powerplus) - Skip frequency band 2; Modbus HR1800 | Write | ||
| AV | 3287 | BLDC_compressor.CurrCompCfg_PWRP1.HR69_SkipFreqSetp_3 | Curr compressor configuration (Powerplus) - Skip frequency setpoint 3; Modbus HR1801 | Write | ||
| AV | 3288 | BLDC_compressor.CurrCompCfg_PWRP1.HR70_SkipFreqBand_3 | Curr compressor configuration (Powerplus) - Skip frequency band 3; Modbus HR1802 | Write | ||
| PIV | 3289 | BLDC_compressor.CurrCompCfg_PWRP1.HR24_SwitchingFreq | Curr compressor configuration (Powerplus) - Switching frequency; Modbus HR1803 | Write | ||
| PIV | 3290 | BLDC_compressor.CurrCompCfg_PWRP1.HR25_SwitchingFreqDerating | Curr compressor configuration (Powerplus) - Switching frequency derating; Modbus HR1804 | Write | ||
| PIV | 3291 | BLDC_compressor.CurrCompCfg_PWRP1.HR27_MotOvTempAlrmPTC_En | Curr compressor configuration (Powerplus) - Motor overtemperature alarm (PTC) enable; Modbus HR1805 | Write | ||
| PIV | 3292 | BLDC_compressor.CurrCompCfg_PWRP1.HR28_MotOvTempAlrmPTC_Delay | Curr compressor configuration (Powerplus) - Motor overtemperature alarm delay; Modbus HR1806 | Write | ||
| PIV | 3293 | BLDC_compressor.CurrCompCfg_PWRP1.HR08_EnRevSpeed | Curr compressor configuration (Powerplus) - Reverse speed enable; Modbus HR1807 | Write | ||
| PIV | 3294 | BLDC_compressor.CurrCompCfg_PWRP1.HR09_SpeedDeratingMode | Curr compressor configuration (Powerplus) - Speed derating mode; Modbus HR1808 | Write | ||
| PIV | 3295 | BLDC_compressor.CurrCompCfg_PWRP1.HR33_StopMode | Curr compressor configuration (Powerplus) - Stop mode; Modbus HR1809 | Write | ||
| PIV | 3296 | BLDC_compressor.CurrCompCfg_PWRP1.HR34_FlyingRestart | Curr compressor configuration (Powerplus) - Flying restart; Modbus HR1810 | Write | ||
| PIV | 3297 | BLDC_compressor.CurrCompCfg_PWRP1.HR26_RelayCfg | Curr compressor configuration (Powerplus) - Relay configuration; Modbus HR1811 | Write | ||
| PIV | 3298 | BLDC_compressor.MiscMng_PWRP1.Mng_MotPoles | Motor pole pairs; Modbus HR1812 | Write | ||
| PIV | 3299 | BLDC_compressor.CurrCompCfg_PWRP1.HR00_MotCtrlMode | Curr compressor configuration (Powerplus) - Motor control mode; Modbus HR1813 | Write | ||
| AV | 3300 | BLDC_compressor.CurrCompCfg_PWRP1.HR01_MotBaseFreq | Curr compressor configuration (Powerplus) - Motor base frequency; Modbus HR1814 | Write | ||
| PIV | 3301 | BLDC_compressor.CurrCompCfg_PWRP1.HR02_MotBaseV | Curr compressor configuration (Powerplus) - Motor base voltage; Modbus HR1815 | Write | ||
| AV | 3302 | BLDC_compressor.CurrCompCfg_PWRP1.HR03_MotRatedA | Curr compressor configuration (Powerplus) - Motor rated current; Modbus HR1816 | Write | ||
| PIV | 3303 | BLDC_compressor.CurrCompCfg_PWRP1.HR04_MotPwrFactor | Curr compressor configuration (Powerplus) - Motor power factor; Modbus HR1817 | Write | ||
| AV | 3304 | BLDC_compressor.CurrCompCfg_PWRP1.HR05_MaxOutCurrent | Curr compressor configuration (Powerplus) - Max output current; Modbus HR1818 | Write | ||
| AV | 3305 | BLDC_compressor.CurrCompCfg_PWRP1.HR12_SpeedProfileFreq1 | Curr compressor configuration (Powerplus) - Speed profile: frequency 1; Modbus HR1819 | Write | ||
| AV | 3306 | BLDC_compressor.CurrCompCfg_PWRP1.HR13_SpeedProfileFreq2 | Curr compressor configuration (Powerplus) - Speed profile: frequency 2; Modbus HR1820 | Write | ||
| AV | 3307 | BLDC_compressor.CurrCompCfg_PWRP1.HR14_SpeedProfileFreq3 | Curr compressor configuration (Powerplus) - Speed profile: frequency 3; Modbus HR1821 | Write | ||
| AV | 3308 | BLDC_compressor.CurrCompCfg_PWRP1.HR15_SpeedProfileAcceleration1 | Curr compressor configuration (Powerplus) - Speed profile: acceleration 1 [Hz/s]; Modbus HR1822 | Write | ||
| AV | 3309 | BLDC_compressor.CurrCompCfg_PWRP1.HR16_SpeedProfileAcceleration2 | Curr compressor configuration (Powerplus) - Speed profile: acceleration 2 [Hz/s]; Modbus HR1823 | Write | ||
| AV | 3310 | BLDC_compressor.CurrCompCfg_PWRP1.HR17_SpeedProfileAcceleration3 | Curr compressor configuration (Powerplus) - Speed profile: acceleration 3 [Hz/s]; Modbus HR1824 | Write | ||
| AV | 3311 | BLDC_compressor.CurrCompCfg_PWRP1.HR18_SpeedProfileAcceleration4 | Curr compressor configuration (Powerplus) - Speed profile: acceleration 4 [Hz/s]; Modbus HR1825 | Write | ||
| PIV | 3312 | BLDC_compressor.CurrCompCfg_PWRP1.HR19_SpeedProfileDelay1 | Curr compressor configuration (Powerplus) - Speed profile: delay 1; Modbus HR1826 | Write | ||
| PIV | 3313 | BLDC_compressor.CurrCompCfg_PWRP1.HR20_SpeedProfileDelay2 | Curr compressor configuration (Powerplus) - Speed profile: delay 2; Modbus HR1827 | Write | ||
| PIV | 3314 | BLDC_compressor.CurrCompCfg_PWRP1.HR21_SpeedProfileDelay3 | Curr compressor configuration (Powerplus) - Speed profile: delay 3; Modbus HR1828 | Write | ||
| AV | 3315 | BLDC_compressor.CurrCompCfg_PWRP1.HR23_SpeedProfileDeceleration | Curr compressor configuration (Powerplus) - Speed profile: deceleration [Hz/s]; Modbus HR1829 | Write | ||
| AV | 3316 | BLDC_compressor.CurrCompCfg_PWRP1.HR35_V_F_BoostV | Curr compressor configuration (Powerplus) - V/f boost voltage; Modbus HR1830 | Write | ||
| AV | 3317 | BLDC_compressor.CurrCompCfg_PWRP1.HR36_V_F_FreqAdj | Curr compressor configuration (Powerplus) - V/f frequency adjustment; Modbus HR1831 | Write | ||
| AV | 3318 | BLDC_compressor.CurrCompCfg_PWRP1.HR37_V_F_VAdj | Curr compressor configuration (Powerplus) - V/f voltage adjustment; Modbus HR1832 | Write | ||
| AV | 3319 | BLDC_compressor.CurrCompCfg_PWRP1.HR45_MotMagnetizingCurrent | Curr compressor configuration (Powerplus) - Motor magnetizing current; Modbus HR1833 | Write | ||
| PIV | 3320 | BLDC_compressor.CurrCompCfg_PWRP1.HR46_StatorResistance | Curr compressor configuration (Powerplus) - Stator resistance [mohm]; Modbus HR1834 | Write | ||
| PIV | 3321 | BLDC_compressor.CurrCompCfg_PWRP1.HR47_RotorResistance | Curr compressor configuration (Powerplus) - Rotor resistance [mohm]; Modbus HR1835 | Write | ||
| AV | 3322 | BLDC_compressor.CurrCompCfg_PWRP1.HR48_StatorInductanceLd | Curr compressor configuration (Powerplus) - Stator inductance Ld [mH]; Modbus HR1836 | Write | ||
| PIV | 3323 | BLDC_compressor.CurrCompCfg_PWRP1.HR49_LeakageFactor | Curr compressor configuration (Powerplus) - Leakage factor; Modbus HR1837 | Write | ||
| AV | 3324 | BLDC_compressor.CurrCompCfg_PWRP1.HR50_LqInductance | Curr compressor configuration (Powerplus) - Stator inductance Lq [mH]; Modbus HR1838 | Write | ||
| AV | 3325 | BLDC_compressor.CurrCompCfg_PWRP1.HR55_SpeedLoopKp | Curr compressor configuration (Powerplus) - Speed loop Kp; Modbus HR1839 | Write | ||
| PIV | 3326 | BLDC_compressor.CurrCompCfg_PWRP1.HR56_SpeedLoopTi | Curr compressor configuration (Powerplus) - Speed loop Ti; Modbus HR1840 | Write | ||
| PIV | 3327 | BLDC_compressor.CurrCompCfg_PWRP1.HR51_MagnetizingTime | Curr compressor configuration (Powerplus) - Magnetizing time; Modbus HR1841 | Write | ||
| AV | 3328 | BLDC_compressor.CurrCompCfg_PWRP1.HR57_StartingCurrent | Curr compressor configuration (Powerplus) - Starting current; Modbus HR1842 | Write | ||
| AV | 3329 | BLDC_compressor.CurrCompCfg_PWRP1.HR58_StartingAFreq | Curr compressor configuration (Powerplus) - Frequency for starting current; Modbus HR1843 | Write | ||
| PIV | 3330 | BLDC_compressor.CurrCompCfg_PWRP1.CrankCaseHeaterMode | Curr compressor configuration (Powerplus) - Crank-case heater mode (0=Strategy mng; ...; Modbus HR1844 | Write | ||
| AV | 3331 | BLDC_compressor.CurrCompCfg_PWRP1.HR65_CrankCaseHeaterCurrent | Curr compressor configuration (Powerplus) - Crank-case heater current; Modbus HR1845 | Write | ||
| PIV | 3332 | BLDC_compressor.CurrCompCfg_PWRP1.HR66_STOResetStrategy | Curr compressor configuration (Powerplus) - Safety torque off alarm autoreset ...; Modbus HR1846 | Write | ||
| AV | 3333 | BLDC_compressor.CurrCompCfg_PWRP1.HR77_InductSaturFactor | Curr compressor configuration (Powerplus) - Inductance saturation factor; Modbus HR1847 | Write | ||
| IV | 3334 | BLDC_compressor.AlrmResetMng_PWRP1.RetryThrs | Maximum semiautomatic alarm reset retry number; 32-bit (2 Modbus registers); Modbus HR1848 | Write | ||
| PIV | 3335 | BLDC_compressor.AlrmResetMng_PWRP1.TimeThrs | Time threshold for semiautomatic reset; 32-bit (2 Modbus registers); Modbus HR1850 | Write | ||
| PIV | 3336 | BLDC_compressor.MiscMng_BLDC1.Mng_ModbusTimeout | 32-bit (2 Modbus registers); Modbus communication timeout [ms]; Modbus HR1852 | Write | ||
| PIV | 3337 | BLDC_compressor.MiscMng_BLDC1.Mng_ModbusCmdDelay | 32-bit (2 Modbus registers); Modbus command delay [ms]; Modbus HR1854 | Write | ||
| AV | 3338 | BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_MaxDeltaP | BLDC envelope configuration - Max. permitted Delta P to start ...; Modbus HR1856 | Write | ||
| IV | 3339 | BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_EVDEqualMaxT | BLDC envelope configuration - Maximum time of EVD propening to ...; Modbus HR1857 | Write | ||
| IV | 3340 | BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_EVDEqualPreopen | BLDC envelope configuration - Preopening of EVD in case of ...; Modbus HR1858 | Write | ||
| AV | 3341 | BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_DeltaPVariation | BLDC envelope configuration - Min. variation of Delta P to ...; Modbus HR1859 | Write | ||
| IV | 3342 | BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_DeltaPDelay | BLDC envelope configuration - Delay to check increasing DeltaP to ...; Modbus HR1860 | Write | ||
| IV | 3343 | BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_RestartDelay | BLDC envelope configuration - Restart delay after a start failure; Modbus HR1861 | Write | ||
| IV | 3344 | BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_Attempts | BLDC envelope configuration - Max Number of starting attempts; Modbus HR1862 | Write | ||
| AV | 3345 | BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_StartUpSpeed | BLDC envelope configuration - Start up speed; Modbus HR1863 | Write | ||
| AV | 3347 | BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_MinSpeedRpsCustom | BLDC envelope configuration - Min speed custom (rps); Modbus HR1865 | Write | ||
| AV | 3348 | BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_MaxDescendSpeedRate | BLDC envelope configuration - Max. decrease speed rate (in regulation) [rps/s]; Modbus HR1866 | Write | ||
| AV | 3349 | BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_MaxRisingSpeedRate | BLDC envelope configuration - Max. increase speed rate (in regulation) [rps/s]; Modbus HR1867 | Write | ||
| AV | 3350 | BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_SwitchOffSpeedRate | BLDC envelope configuration - Decrease max speed rate (= max ...; Modbus HR1868 | Write | ||
| AV | 3351 | BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_MaxSlowdownSpeedRate | BLDC envelope configuration - Decrease speed rate (to come back ...; Modbus HR1869 | Write | ||
| AV | 3352 | BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_MinSpeedControlled | BLDC envelope configuration - Min speed permitted to control compressor ...; Modbus HR1870 | Write | ||
| IV | 3353 | BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_EnvOutMaxT | BLDC envelope configuration - Out of envelop alarm delay time; Modbus HR1871 | Write | ||
| IV | 3354 | BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_LowDeltaPAlrmDelay | BLDC envelope configuration - Low Delta P alarm delay; Modbus HR1872 | Write | ||
| AV | 3355 | BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_SuctTSaturationThrshZone1b1c | BLDC envelope configuration - Suction sat.temp. threshold from zone 1b ...; Modbus HR1873 | Write | ||
| IV | 3356 | BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_MaxSpeedZone1c | BLDC envelope configuration - Max Speed in rps for Zone ...; Modbus HR1874 | Write | ||
| AV | 3357 | BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempCtrlThrshZone1a | BLDC envelope configuration - Discharge gas temperature control threshold for ...; Modbus HR1875 | Write | ||
| AV | 3358 | BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempAlrmThrshZone1a | BLDC envelope configuration - Discharge gas limit temperature for Zone ...; Modbus HR1876 | Write | ||
| AV | 3359 | BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempCtrlThrsh | BLDC envelope configuration - Discharge gas temperature control threshold (SIAM ...; Modbus HR1877 | Write | ||
| AV | 3360 | BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempAlrmThrsh | BLDC envelope configuration - Discharge gas limit temperature (SIAM Scroll ...; Modbus HR1878 | Write | ||
| AV | 3361 | BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempLimDistance | BLDC envelope configuration - Action distance from High Temperature limit ...; Modbus HR1879 | Write | ||
| IV | 3362 | BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempPause | BLDC envelope configuration - Pause between speed reductions when discharge ...; Modbus HR1880 | Write | ||
| AV | 3363 | BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempSpeedReduction | BLDC envelope configuration - Speed Reduction percentage when discharge temp ...; Modbus HR1881 | Write | ||
| AV | 3364 | CstEvapMinTemp | Custom minimum evaporating temperature; Modbus HR1882 | Write | ||
| AV | 3365 | CstCondMaxTemp | Custom maximum temperature condensing; Modbus HR1883 | Write | ||
| IV | 3366 | BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_SubTypeRegMode | BLDC envelope configuration - Regol. Evd SubType: 0=null; 1=SSH; 2=DSH; ...; Modbus HR1884 | Write | ||
| AV | 3367 | BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DscgTempNTCT | BLDC envelope configuration - Time constant of discharge temp sensor; Modbus HR1885 | Write | ||
| AV | 3368 | BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DscgSHSetP | BLDC envelope configuration - SetPoint of Discharge SH (sent to EVD); Modbus HR1886 | Write | ||
| AV | 3369 | BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DTDscgSHRegOn | BLDC envelope configuration - Setpoint offset for Discharge Super Heat ...; Modbus HR1887 | Write | ||
| AV | 3370 | BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DTDscgSHHyst | BLDC envelope configuration - Hysteresys for Discharge Super Heat regulation deactivation; Modbus HR1888 | Write | ||
| AV | 3371 | BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DscgTempSetP | BLDC envelope configuration - SetPoint of Discharge Temp (sent to EVD); Modbus HR1889 | Write | ||
| AV | 3372 | BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DTDLTRegOn | BLDC envelope configuration - Setpoint offset for Discharge Limit Temp. ...; Modbus HR1890 | Write | ||
| AV | 3373 | BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DTDLTHyst | BLDC envelope configuration - Hysteresys for Discharge Limit Temp. regulation deactivation; Modbus HR1891 | Write | ||
| IV | 3374 | BLDC_compressor.AlrmResetMng_BLDC_1.RetryThrs | Maximum semiautomatic alarm reset retry number; 32-bit (2 Modbus registers); Modbus HR1892 | Write | ||
| PIV | 3375 | BLDC_compressor.AlrmResetMng_BLDC_1.TimeThrs | Time threshold for semiautomatic reset; 32-bit (2 Modbus registers); Modbus HR1894 | Write | ||
| AV | 3376 | SupplyFanMinVal | Supply fan: Minimum regulation value; Modbus HR1896 | Write | ||
| AV | 3377 | SupplyFanMaxVal | Supply fan: Maximum regulation value; Modbus HR1897 | Write | ||
| AV | 3378 | RetFanMinVal | Return fan: Minimum regulation value; Modbus HR1898 | Write | ||
| AV | 3379 | RetFanMaxVal | Return fan: Maximum regulation value; Modbus HR1899 | Write | ||
| PIV | 3380 | GeneralMng.pGDx_MACAddress1 | PGDx Browser - MAC Address Last Four Digit - Part ...; Modbus HR1900 | Write | ||
| PIV | 3381 | GeneralMng.pGDx_MACAddress2 | PGDx Browser - MAC Address Last Four Digit - Part ...; Modbus HR1901 | Write | ||
| PIV | 3382 | GeneralMng.pGDx_MACAddress3 | PGDx Browser - MAC Address Last Four Digit - Part ...; Modbus HR1902 | Write | ||
| PIV | 3383 | GeneralMng.pGDx_MACAddress4 | PGDx Browser - MAC Address Last Four Digit - Part ...; Modbus HR1903 | Write | ||
| PIV | 3384 | BMS_Line | BMS Line (0=None; 1=Modbus; 2=BACnet); Modbus HR1904 | Write | ||
| PIV | 3385 | BMS2_Line | BMS2 Line (0=None; 1=Modbus; 2=BACnet); Modbus HR1905 | Write | ||
| PIV | 3386 | ETH_Line | Ethernet Line (0=None; 1=Modbus); Modbus HR1906 | Write | ||
| PIV | 3387 | ETH2_Line | Ethernet 2 Line (0=None; 1=BACnet); Modbus HR1907 | Write | ||
| PIV | 3388 | GeneralMng.BACnet_ID | BACnet Device Instance (and Station address in MSTP); 32-bit (2 ...; Modbus HR1908 | Write | ||
| PIV | 3389 | GeneralMng.BACnet_Timeout | BACnet timeout; Modbus HR1910 | Write | ||
| PIV | 3390 | GeneralMng.BMS2_Baudrate_msk | BMS baudrate (0=9600; 1=19200; 2=38400); Modbus HR1911 | Write | ||
| PIV | 3391 | GeneralMng.BMS2_Parity | BMS 2 parity; Modbus HR1912 | Write | ||
| PIV | 3392 | GeneralMng.BMS2_StopBit | BMS 2 stopbit; Modbus HR1913 | Write | ||
| PIV | 3940 | CoilVlv_OpenTime | Coil floating valve: Opening duration total time(from0% to100%); Modbus HR1914 | Write | ||
| PIV | 265 | AuxReg1_Cfg.CoolHeatMode | Auxiliary Regulation 1 - Cooling/Heating mode; Modbus HR1915 | Write | ||
| PIV | 272 | AuxReg2_Cfg.CoolHeatMode | Auxiliary Regulation 2 - Cooling/Heating mode; Modbus HR1916 | Write | ||
| PIV | 279 | AuxReg3_Cfg.CoolHeatMode | Auxiliary Regulation 3 - Cooling/Heating mode; Modbus HR1917 | Write | ||
| PIV | 286 | AuxReg4_Cfg.CoolHeatMode | Auxiliary Regulation 4 - Cooling/Heating mode; Modbus HR1918 | Write | ||
| PIV | 3950 | HumDehumStartReg_DT | Humidification/Dehumidification: start regulation delay time; Modbus HR1919 | Write | ||
| PIV | 3952 | AirQuality_PM10.Board_RW | Air quality: PM 10 - Board selected; Modbus HR1920 | Write | ||
| PIV | 3978 | AirQuality_PM10.Ch_Id_RW | Air quality: PM 10 - Channel id selected; Modbus HR1921 | Write | ||
| PIV | 3979 | AirQuality_PM10.Ch_Type_RW | Air quality: PM 10 - Type probe used; Modbus HR1922 | Write | ||
| PIV | 3980 | AirQuality_PM10.ChFilter_RW | Air quality: PM 10 - Filter channel; Modbus HR1923 | Write | ||
| AV | 3983 | AirQuality_PM10.MaxVal_RW | Air quality: PM 10 - Maximum value; Modbus HR1924 | Write | ||
| AV | 3984 | AirQuality_PM10.MinVal_RW | Air quality: PM 10 - Minimum value; Modbus HR1925 | Write | ||
| AV | 3985 | AirQuality_PM10.Offset_RW | Air quality: PM 10 - Offset; Modbus HR1926 | Write | ||
| PIV | 3991 | AirQuality_PM25.Board_RW | Air quality: PM 2.5 - Board selected; Modbus HR1927 | Write | ||
| PIV | 3992 | AirQuality_PM25.Ch_Id_RW | Air quality: PM 2.5 - Channel id selected; Modbus HR1928 | Write | ||
| PIV | 3993 | AirQuality_PM25.Ch_Type_RW | Air quality: PM 2.5 - Type probe used; Modbus HR1929 | Write | ||
| PIV | 3994 | AirQuality_PM25.ChFilter_RW | Air quality: PM 2.5 - Filter channel; Modbus HR1930 | Write | ||
| AV | 3997 | AirQuality_PM25.MaxVal_RW | Air quality: PM 2.5 - Maximum value; Modbus HR1931 | Write | ||
| AV | 3998 | AirQuality_PM25.MinVal_RW | Air quality: PM 2.5 - Minimum value; Modbus HR1932 | Write | ||
| AV | 3999 | AirQuality_PM25.Offset_RW | Air quality: PM 2.5 - Offset; Modbus HR1933 | Write | ||
| PIV | 4004 | SanificationDevice.Board_RW | Sanification device - Board selected; Modbus HR1934 | Write | ||
| PIV | 4005 | SanificationDevice.Ch_Id_RW | Sanification device - Channel id selected; Modbus HR1935 | Write | ||
| PIV | 4006 | SanificationDevice.Ch_Type_RW | Sanification device - Digital output type; Modbus HR1936 | Write | ||
| PIV | 4009 | SanificationDevice.T_On_RW | Sanification device - Time on cycle relay; Modbus HR1937 | Write | ||
| PIV | 4010 | SanificationDevice.T_Off_RW | Sanification device - Time off cycle releay; Modbus HR1938 | Write | ||
| AV | 3954 | FansAirQualityVOC_PID_Params.Kp | Air Quality VOC - Fans PID parameters - Proportional gain; Modbus HR1939 | Write | ||
| PIV | 3953 | FansAirQualityVOC_PID_Params.Ti | Air Quality VOC - Fans PID parameters - Integral time; Modbus HR1940 | Write | ||
| AV | 3955 | DampAirQualityVOC_PID_Params.Kp | Air Quality VOC - Dampers PID parameters - Proportional gain; Modbus HR1941 | Write | ||
| PIV | 3956 | DampAirQualityVOC_PID_Params.Ti | Air Quality VOC - Dampers PID parameters - Integral time; Modbus HR1942 | Write | ||
| PIV | 3959 | QualitySignal | Quality signal used (0: NONE, 1:CO2; 2: VOC;3:CO2 + VOC); Modbus HR1943 | Write | ||
| PIV | 3961 | ModeSanDevOffByBmsOrSched | Mode sanification during off by BMS or scheduler (0: OFF,1:ON,2:Blink); Modbus HR1944 | Write | ||
| PIV | 3962 | SanificationDeviceTimeOn | Sanification device time on; Modbus HR1945 | Write | ||
| PIV | 3963 | SanificationDeviceTimeOff | Sanification device time off; Modbus HR1946 | Write | ||
| PIV | 3965 | WrkHrs_SanificationDevice.WrkHrs_Thrsh | Sanification device - Working hours threshold (1000hrs); Modbus HR1947 | Write | ||
| PIV | 3967 | WrkHrs_SanificationDevice.WrkHrs_Res | Sanification device - Working hours reset; Modbus HR1948 | Write | ||
| PIV | 3972 | PurgeTime | Purge time; Modbus HR1949 | Write | ||
| PIV | 3973 | PurgeMode | Purge mode (0:NO AUTO, 1:FIXED TIME, 2:DAILY SCHED, 3: FIXED+DAILY SCHED); Modbus HR1950 | Write | ||
| PIV | 3974 | PurgeHour | Purge start time - Hour; Modbus HR1951 | Write | ||
| PIV | 3975 | PurgeMinute | Purge start time - Minute; Modbus HR1952 | Write | ||
| AV | 3976 | BLDC_compressor.Speed_MaxSpeedRpsCustom_Cooling | Maximum speed in cooling mode; Modbus HR1953 | Write | ||
| AV | 3977 | BLDC_compressor.Speed_MaxSpeedRpsCustom_Heating | Maximum speed in heating mode; Modbus HR1954 | Write | ||
| PIV | 4044 | SanificationDeviceOvld.Board_RW | Sanification deivce overload switch - Board selected; Modbus HR1955 | Write | ||
| PIV | 4045 | SanificationDeviceOvld.Ch_Id_RW | Sanification deivce overload switch - Channel id selected; Modbus HR1956 | Write | ||
| AV | 4014 | CurrAirQuality_VOC_SetP | Current air quality VOC setpoint; Modbus HR1957 | Write | ||
| AV | 4023 | AirQualityVOCSetP_MaxVal | Air quality VOC setpoint - maximum value; Modbus HR1958 | Write | ||
| AV | 4022 | AirQualityVOCSetP_MinVal | Air quality VOC setpoint - minimum value; Modbus HR1959 | Write | ||
| AV | 4021 | UnitSetP.AirQuality_VOC_SetP.Comfort | Unit setpoints - Air quality VOC - Comfort; Modbus HR1960 | Write | ||
| AV | 4015 | UnitSetP.AirQuality_VOC_SetP.Economy | Unit setpoints - Air quality VOC - Economy; Modbus HR1963 | Write | ||
| AV | 4018 | UnitSetP.AirQuality_VOC_SetP.PreComfort | Unit setpoints - Air quality VOC - Pre-comfort; Modbus HR1966 | Write | ||
| PIV | 4024 | DfrEnActions | Defrost enabled actions (0=None, 1=Only phase 1, 2=Only phase 2, ...; Modbus HR1967 | Write | ||
| AV | 4026 | OilRecov_CompMinSpeedThrsh | Oil recovery minimun compressor speed for activation; Modbus HR1968 | Write | ||
| AV | 4027 | OilRecov_FrcCompSpeed | Oil recovery compressor speed in which the compressor is forced; Modbus HR1969 | Write | ||
| PIV | 4028 | OilRecov_FrcSpeedT | Oil recovery duration in which the compressor speed is forced; Modbus HR1970 | Write | ||
| PIV | 4029 | OilRecov_WaitT | Oil recovery time before activation in which the compressor can ...; Modbus HR1971 | Write | ||
| AV | 4046 | EVD_Emb_Circ.EEV_PID_Kp_Cool_Dfr | EEV Proportional gain: cooling mode (Defrost); Modbus HR1972 | Write | ||
| AV | 4047 | EVD_Emb_Circ.EEV_PID_Kp_Heat_Dfr | EEV Proportional gain: heating mode (Defrost); Modbus HR1973 | Write | ||
| AV | 4048 | EVD_Emb_Circ.EEV_PID_Td_Cool_Dfr | EEV Integral time: cooling mode (Defrost); Modbus HR1974 | Write | ||
| AV | 4049 | EVD_Emb_Circ.EEV_PID_Td_Heat_Dfr | EEV Integral time: cooling mode (Defrost); Modbus HR1975 | Write | ||
| AV | 4050 | EVD_Emb_Circ.EEV_PID_Ti_Cool_Dfr | EEV Integral time: cooling mode (Defrost); Modbus HR1976 | Write | ||
| AV | 4051 | EVD_Emb_Circ.EEV_PID_Ti_Heat_Dfr | EEV Integral time: heating mode (Defrost); Modbus HR1977 | Write | ||
| PIV | 4030 | FC_FH_Typ | Free cooling/Free heating selection type (0=Temperature, 1=Enthalpy); Modbus HR1978 | Write | ||
| AV | 4031 | Regulation.FC_DeltaEnth_Act | Freecooling activation delta enthalpy; Modbus HR1979 | Write | ||
| AV | 4032 | Regulation.FH_DeltaEnth_Act | Freeheating activation delta enthalpy; Modbus HR1980 | Write | ||
| IV | 4052 | GeneralMng.pGDx_HostName_ASCII[1] | PGDx - hostname prefix ASCII; Modbus HR1981 | Write | ||
| IV | 4053 | GeneralMng.pGDx_HostName_ASCII[2] | PGDx - hostname prefix ASCII; Modbus HR1982 | Write | ||
| IV | 4054 | GeneralMng.pGDx_HostName_ASCII[3] | PGDx - hostname prefix ASCII; Modbus HR1983 | Write | ||
| IV | 4055 | GeneralMng.pGDx_HostName_ASCII[4] | PGDx - hostname prefix ASCII; Modbus HR1984 | Write | ||
| IV | 4056 | GeneralMng.pGDx_HostName_ASCII[5] | PGDx - hostname prefix ASCII; Modbus HR1985 | Write | ||
| IV | 4057 | GeneralMng.pGDx_HostName_ASCII[6] | PGDx - hostname prefix ASCII; Modbus HR1986 | Write | ||
| PIV | 4058 | FanNr | Fan number enabled via Bus; Modbus HR1987 | Write | ||
| PIV | 4059 | Ebmpapst_SupplyFan.SerInterfaceSet_EBM_2.CfgProtocol.DevAddr | EBM2 Supply - Serial interface settings - Network address for ...; 32-bit; Modbus HR1988 | Write | ||
| PIV | 4060 | Ebmpapst_SupplyFan.SerInterfaceSet_EBM_3.CfgProtocol.DevAddr | EBM3 Supply - Serial interface settings - Network address for ...; 32-bit; Modbus HR1990 | Write | ||
| PIV | 4061 | Ebmpapst_SupplyFan.SerInterfaceSet_EBM_4.CfgProtocol.DevAddr | EBM4 Supply - Serial interface settings - Network address for ...; 32-bit; Modbus HR1992 | Write | ||
| PIV | 4062 | Ebmpapst_ReturnFan.SerInterfaceSet_EBM_2.CfgProtocol.DevAddr | EBM2 Return - Serial interface settings - Network address for ...; 32-bit; Modbus HR1994 | Write | ||
| PIV | 4063 | Ebmpapst_ReturnFan.SerInterfaceSet_EBM_3.CfgProtocol.DevAddr | EBM3 Return - Serial interface settings - Network address for ...; 32-bit; Modbus HR1996 | Write | ||
| PIV | 4064 | Ebmp3pst_ReturnFan.SerInterfaceSet_EBM_4.CfgProtocol.DevAddr | EBM4 Return - Serial interface settings - Network address for ...; 32-bit; Modbus HR1998 | Write | ||
| PIV | 4065 | ZiehlAbegg_SupplyFan.SerialInterfa-ce_ZA_2.SerDevCfg.DevAddr | ZA2 Supply - Serial interface parameters - Fan Network address; ...; 32-bit; Modbus HR2000 | Write | ||
| PIV | 4066 | ZiehlAbegg_SupplyFan.SerialInterfa-ce_ZA_3.SerDevCfg.DevAddr | ZA3 Supply - Serial interface parameters - Fan Network address; ...; 32-bit; Modbus HR2002 | Write | ||
| PIV | 4067 | ZiehlAbegg_SupplyFan.SerialInterfa-ce_ZA_4.SerDevCfg.DevAddr | ZA4 Supply - Serial interface parameters - Fan Network address; ...; 32-bit; Modbus HR2004 | Write | ||
| PIV | 4068 | ZiehlAbegg_ReturnFan.SerialInterfa-ce_ZA_2.SerDevCfg.DevAddr | ZA2 Return - Serial interface parameters - Fan Network address; ...; 32-bit; Modbus HR2006 | Write | ||
| PIV | 4069 | ZiehlAbegg_ReturnFan.SerialInterfa-ce_ZA_3.SerDevCfg.DevAddr | ZA3 Return - Serial interface parameters - Fan Network address; ...; 32-bit; Modbus HR2008 | Write | ||
| PIV | 4070 | ZiehlAbegg_ReturnFan.SerialInterfa-ce_ZA_4.SerDevCfg.DevAddr | ZA4 Return - Serial interface parameters - Fan Network address; ...; 32-bit; Modbus HR2010 | Write | ||
| PIV | 4255 | WrkHrs_SupplyFan_2.WrkHrs_Thrsh | Supply Fan 2- Working hours threshold (1000hrs); Modbus HR2012 | Write | ||
| PIV | 4256 | WrkHrs_SupplyFan_2.WrkHrs_Res | Supply Fan 2- Working hours reset; Modbus HR2013 | Write | ||
| PIV | 4257 | WrkHrs_SupplyFan_3.WrkHrs_Thrsh | Supply Fan 3- Working hours threshold (1000hrs); Modbus HR2014 | Write | ||
| PIV | 4258 | WrkHrs_SupplyFan_3.WrkHrs_Res | Supply Fan 3- Working hours reset; Modbus HR2015 | Write | ||
| PIV | 4259 | WrkHrs_SupplyFan_4.WrkHrs_Thrsh | Supply Fan 4- Working hours threshold (1000hrs); Modbus HR2016 | Write | ||
| PIV | 4260 | WrkHrs_SupplyFan_4.WrkHrs_Res | Supply Fan 4- Working hours reset; Modbus HR2017 | Write | ||
| PIV | 4261 | WrkHrs_ReturnFan_2.WrkHrs_Thrsh | Return Fan 2- Working hours threshold (1000hrs); Modbus HR2018 | Write | ||
| PIV | 4262 | WrkHrs_ReturnFan_2.WrkHrs_Res | Return Fan 2- Working hours reset; Modbus HR2019 | Write | ||
| PIV | 4263 | WrkHrs_ReturnFan_3.WrkHrs_Thrsh | Return Fan 3- Working hours threshold (1000hrs); Modbus HR2020 | Write | ||
| PIV | 4264 | WrkHrs_ReturnFan_3.WrkHrs_Res | Return Fan 3- Working hours reset; Modbus HR2021 | Write | ||
| PIV | 4265 | WrkHrs_ReturnFan_4.WrkHrs_Thrsh | Return Fan 4- Working hours threshold (1000hrs); Modbus HR2022 | Write | ||
| PIV | 4266 | WrkHrs_ReturnFan_4.WrkHrs_Res | Return Fan 4- Working hours reset; Modbus HR2023 | Write | ||
| PIV | 4285 | FireSmokeMngTyp | Fire Smoke management (0=Stop fans - 1=Only supply fans - ...; Modbus HR2024 | Write | ||
| PIV | 4296 | IOs.CstSerPrb_DevAddr[1] | Custom serial probe 1 - device address; 32-bit (2 Modbus registers); Modbus HR2025 | Write | ||
| PIV | 4297 | IOs.CstSerPrb_DevAddr[2] | Custom serial probe 2 - device address; 32-bit (2 Modbus registers); Modbus HR2027 | Write | ||
| PIV | 4298 | IOs.CstSerPrb_DevAddr[3] | Custom serial probe 3 - device address; 32-bit (2 Modbus registers); Modbus HR2029 | Write | ||
| PIV | 4299 | IOs.CstSerPrb_DevAddr[4] | Custom serial probe 4 - device address; 32-bit (2 Modbus registers); Modbus HR2031 | Write | ||
| PIV | 4300 | IOs.CstSerPrb_DevAddr[5] | Custom serial probe 5 - device address; 32-bit (2 Modbus registers); Modbus HR2033 | Write | ||
| PIV | 4301 | CstPrbCfg.Temp1Adr | Custom serial probe - Serial address - Temp1; Modbus HR2035 | Write | ||
| PIV | 4302 | CstPrbCfg.Temp2Adr | Custom serial probe - Serial address – Temp2; Modbus HR2036 | Write | ||
| PIV | 4303 | CstPrbCfg.Hum1Adr | Custom serial probe - Serial address - Hum1; Modbus HR2037 | Write | ||
| PIV | 4304 | CstPrbCfg.Hum2Adr | Custom serial probe - Serial address – Hum2; Modbus HR2038 | Write | ||
| PIV | 4305 | CstPrbCfg.Press1Adr | Custom serial probe - Serial address - Press1; Modbus HR2039 | Write | ||
| PIV | 4306 | CstPrbCfg.Press2Adr | Custom serial probe - Serial address – Press2; Modbus HR2040 | Write | ||
| PIV | 4307 | CstPrbCfg.Flow1Adr | Custom serial probe - Serial address - Flow1; Modbus HR2041 | Write | ||
| PIV | 4308 | CstPrbCfg.Flow2Adr | Custom serial probe - Serial address – Flow2; Modbus HR2042 | Write | ||
| IV | 4309 | CstPrbCfg.Temp1Fact | Custom serial probe - Factor - Temp1; Modbus HR2043 | Write | ||
| IV | 4310 | CstPrbCfg.Temp2Fact | Custom serial probe - Factor – Temp2; Modbus HR2044 | Write | ||
| IV | 4311 | CstPrbCfg.Hum1Fact | Custom serial probe - Factor - Hum1; Modbus HR2045 | Write | ||
| IV | 4312 | CstPrbCfg.Hum2Fact | Custom serial probe - Factor – Hum2; Modbus HR2046 | Write | ||
| IV | 4313 | CstPrbCfg.Press1Fact | Custom serial probe - Factor - Press1; Modbus HR2047 | Write | ||
| IV | 4314 | CstPrbCfg.Press2Fact | Custom serial probe - Factor – Press2; Modbus HR2048 | Write | ||
| IV | 4315 | CstPrbCfg.Flow1Fact | Custom serial probe - Factor - Flow1; Modbus HR2049 | Write | ||
| IV | 4316 | CstPrbCfg.Flow2Fact | Custom serial probe - Factor – Flow2; Modbus HR2050 | Write | ||
| AV | 4317 | CstPrbCfg.TempAlmMin | Custom serial probe - Temp. minimum value limit for trigger ...; 32-bit; Modbus HR2051 | Write | ||
| AV | 4318 | CstPrbCfg.TempAlmMax | Custom serial probe - Temp. maximum value limit for trigger ...; 32-bit; Modbus HR2053 | Write | ||
| AV | 4319 | CstPrbCfg.HumAlmMin | Custom serial probe - Press. minimum value limit for trigger ...; 32-bit; Modbus HR2055 | Write | ||
| AV | 4320 | CstPrbCfg.HumAlmMax | Custom serial probe - Press. maximum value limit for trigger ...; 32-bit; Modbus HR2057 | Write | ||
| AV | 4321 | CstPrbCfg.PressAlmMin | Custom serial probe - Press. minimum value limit for trigger ...; 32-bit; Modbus HR2059 | Write | ||
| AV | 4322 | CstPrbCfg.PressAlmMax | Custom serial probe - Press. maximum value limit for trigger ...; 32-bit; Modbus HR2061 | Write | ||
| AV | 4323 | CstPrbCfg.FlowAlmMin | Custom serial probe - Flow minimum value limit for trigger ...; 32-bit; Modbus HR2063 | Write | ||
| AV | 4324 | CstPrbCfg.FlowAlmMax | Custom serial probe - Flow maximum value limit for trigger ...; 32-bit; Modbus HR2065 | Write | ||
| PIV | 4325 | CstPrbCfg.Timeout | Custom serial probe - Modbus - Timeout; Modbus HR2067 | Write | ||
| PIV | 4326 | CstPrbCfg.CmdDelay | Custom serial probe - Modbus - Cmd delay; Modbus HR2068 | Write | ||
| PIV | 4327 | IAQ_PrbCfg.VOC_sensibility | IAQ configuration - VOC sensibility (0=disabled,1=low,2=medium,3=high); Modbus HR2069 | Write | ||
| PIV | 4328 | IAQ_PrbCfg.Timeout | IAQ configuration - Modbus - Timeout; Modbus HR2070 | Write | ||
| PIV | 4329 | IAQ_PrbCfg.CmdDelay | IAQ configuration - Modbus - Cmd delay; Modbus HR2071 | Write | ||
| PIV | 4339 | HumiSteamMng.DevAddr_UEY | HumiSteam - Device address; 32-bit (2 Modbus registers); Modbus HR2072 | Write | ||
| PIV | 4340 | HumiSteamMng.Timeout_UEY | HumiSteam - Modbus timeout for UEY; 32-bit (2 Modbus registers); Modbus HR2074 | Write | ||
| PIV | 4341 | HumiSteamMng.CmdDelay_UEY | HumiSteam - Modbus command delay for UEY; 32-bit (2 Modbus registers); Modbus HR2076 | Write | ||
| PIV | 4352 | SummerWinterDT | Summer/Winter mode change delay time; Modbus HR2078 | Write | ||
| PIV | 4353 | SummerWinterSel | Summer/Winter selection type; Modbus HR2079 | Write | ||
| AV | 4354 | CoolHeat_Chg_Offset | Cooling/Heating change offset; 32-bit (2 Modbus registers); Modbus HR2080 | Write | ||
| PIV | 4355 | MainCoilCoolHeat_Din.Board_RW | Main coil cool/heat - digital input - Board selected; Modbus HR2082 | Write | ||
| PIV | 4356 | MainCoilCoolHeat_Din.Ch_Id_RW | Main coil cool/heat - digital input - Channel id selected; Modbus HR2083 | Write | ||
| PIV | 4357 | UnitAutoModeCfg | Unit automatic mode configuration (0: Standard; 1: Energy saving); Modbus HR2084 | Write | ||
| PIV | 4358 | SummerEndDay | Summer season ending day; Modbus HR2085 | Write | ||
| PIV | 4359 | SummerEndMonth | Summer season ending month; Modbus HR2086 | Write | ||
| PIV | 4360 | SummerStartDay | Summer season starting day; Modbus HR2087 | Write | ||
| PIV | 4361 | SummerStartMonth | Summer season starting month; Modbus HR2088 | Write | ||
| AV | 4374 | Fans_regulation.RetFan_PID_Params.DeadBand | Return fan - PID parameters - Dead band; 32-bit (2 ...; Modbus HR2089 | Write | ||
| AV | 4375 | Fans_regulation.RetFan_PID_Params.Kp | Return fan - PID parameters - Proportional gain; 32-bit (2 ...; Modbus HR2091 | Write | ||
| PIV | 4376 | Fans_regulation.RetFan_PID_Params.Ti | Return fan - PID parameters - Integral time; Modbus HR2093 | Write | ||
| PIV | 4381 | GenericAin1.Board_RW | Generic Ain1 - Board selected; Modbus HR2094 | Write | ||
| PIV | 4382 | GenericAin1.Ch_Id_RW | Generic Ain1 - Channel id selected; Modbus HR2095 | Write | ||
| PIV | 4383 | GenericAin1.Ch_Type_RW | Generic Ain1 - Type probe used; Modbus HR2096 | Write | ||
| AV | 4384 | GenericAin1.MinVal_RW | Generic Ain1 - Minimum value; Modbus HR2097 | Write | ||
| AV | 4385 | GenericAin1.MaxVal_RW | Generic Ain1 - Maximum value; Modbus HR2098 | Write | ||
| AV | 4386 | GenericAin1.Offset_RW | Generic Ain1 - Offset; Modbus HR2099 | Write | ||
| PIV | 4387 | GenericAin1.ChFilter_RW | Generic Ain1 - Filter channel; Modbus HR2100 | Write | ||
| PIV | 4395 | GenericAin2.Board_RW | Generic Ain2 - Board selected; Modbus HR2101 | Write | ||
| PIV | 4396 | GenericAin2.Ch_Id_RW | Generic Ain2 - Channel id selected; Modbus HR2102 | Write | ||
| PIV | 4397 | GenericAin2.Ch_Type_RW | Generic Ain2 - Type probe used; Modbus HR2103 | Write | ||
| AV | 4398 | GenericAin2.MinVal_RW | Generic Ain2 - Minimum value; Modbus HR2104 | Write | ||
| AV | 4399 | GenericAin2.MaxVal_RW | Generic Ain2 - Maximum value; Modbus HR2105 | Write | ||
| AV | 4400 | GenericAin2.Offset_RW | Generic Ain2 - Offset; Modbus HR2106 | Write | ||
| PIV | 4401 | GenericAin2.ChFilter_RW | Generic Ain2 - Filter channel; Modbus HR2107 | Write | ||
| PIV | 4409 | GenericAin3.Board_RW | Generic Ain3 - Board selected; Modbus HR2108 | Write | ||
| PIV | 4410 | GenericAin3.Ch_Id_RW | Generic Ain3 - Channel id selected; Modbus HR2109 | Write | ||
| PIV | 4411 | GenericAin3.Ch_Type_RW | Generic Ain3 - Type probe used; Modbus HR2110 | Write | ||
| AV | 4412 | GenericAin3.MinVal_RW | Generic Ain3 - Minimum value; Modbus HR2111 | Write | ||
| AV | 4413 | GenericAin3.MaxVal_RW | Generic Ain3 - Maximum value; Modbus HR2112 | Write | ||
| AV | 4414 | GenericAin3.Offset_RW | Generic Ain3 - Offset; Modbus HR2113 | Write | ||
| PIV | 4415 | GenericAin3.ChFilter_RW | Generic Ain3 - Filter channel; Modbus HR2114 | Write | ||
| PIV | 4423 | GenericAin4.Board_RW | Generic Ain4 - Board selected; Modbus HR2115 | Write | ||
| PIV | 4424 | GenericAin4.Ch_Id_RW | Generic Ain4 - Channel id selected; Modbus HR2116 | Write | ||
| PIV | 4425 | GenericAin4.Ch_Type_RW | Generic Ain4 - Type probe used; Modbus HR2117 | Write | ||
| AV | 4426 | GenericAin4.MinVal_RW | Generic Ain4 - Minimum value; Modbus HR2118 | Write | ||
| AV | 4427 | GenericAin4.MaxVal_RW | Generic Ain4 - Maximum value; Modbus HR2119 | Write | ||
| AV | 4428 | GenericAin4.Offset_RW | Generic Ain4 - Offset; Modbus HR2120 | Write | ||
| PIV | 4429 | GenericAin4.ChFilter_RW | Generic Ain4 - Filter channel; Modbus HR2121 | Write | ||
| PIV | 4437 | GenericAin5.Board_RW | Generic Ain5 - Board selected; Modbus HR2122 | Write | ||
| PIV | 4438 | GenericAin5.Ch_Id_RW | Generic Ain5 - Channel id selected; Modbus HR2123 | Write | ||
| PIV | 4439 | GenericAin5.Ch_Type_RW | Generic Ain5 - Type probe used; Modbus HR2124 | Write | ||
| AV | 4440 | GenericAin5.MinVal_RW | Generic Ain5 - Minimum value; Modbus HR2125 | Write | ||
| AV | 4441 | GenericAin5.MaxVal_RW | Generic Ain5 - Maximum value; Modbus HR2126 | Write | ||
| AV | 4442 | GenericAin5.Offset_RW | Generic Ain5 - Offset; Modbus HR2127 | Write | ||
| PIV | 4443 | GenericAin5.ChFilter_RW | Generic Ain5 - Filter channel; Modbus HR2128 | Write | ||
| PIV | 4452 | GenericDin1.Board_RW | Generic Din1 - digital input - Board selected; Modbus HR2129 | Write | ||
| PIV | 4453 | GenericDin1.Ch_Id_RW | Generic Din1 - digital input - Channel id selected; Modbus HR2130 | Write | ||
| PIV | 4459 | GenericDin2.Board_RW | Generic Din2 - digital input - Board selected; Modbus HR2131 | Write | ||
| PIV | 4460 | GenericDin2.Ch_Id_RW | Generic Din2 - digital input - Channel id selected; Modbus HR2132 | Write | ||
| PIV | 4466 | GenericDin3.Board_RW | Generic Din3 - digital input - Board selected; Modbus HR2133 | Write | ||
| PIV | 4467 | GenericDin3.Ch_Id_RW | Generic Din3 - digital input - Channel id selected; Modbus HR2134 | Write | ||
| PIV | 4473 | GenericDin4.Board_RW | Generic Din4 - digital input - Board selected; Modbus HR2135 | Write | ||
| PIV | 4474 | GenericDin4.Ch_Id_RW | Generic Din4 - digital input - Channel id selected; Modbus HR2136 | Write | ||
| PIV | 4480 | GenericDin5.Board_RW | Generic Din5 - digital input - Board selected; Modbus HR2137 | Write | ||
| PIV | 4481 | GenericDin5.Ch_Id_RW | Generic Din5 - digital input - Channel id selected; Modbus HR2138 | Write | ||
| PIV | 4482 | GenericDin1_Alrm_MngTyp | Generic Ain1 - alarm management (0: Disabled; 1: Only Warning; ...; Modbus HR2139 | Write | ||
| PIV | 4483 | GenericDin2_Alrm_MngTyp | Generic Ain2 - alarm management (0: Disabled; 1: Only Warning; ...; Modbus HR2140 | Write | ||
| PIV | 4484 | GenericDin3_Alrm_MngTyp | Generic Ain3 - alarm management (0: Disabled; 1: Only Warning; ...; Modbus HR2141 | Write | ||
| PIV | 4485 | GenericDin4_Alrm_MngTyp | Generic Ain4 - alarm management (0: Disabled; 1: Only Warning; ...; Modbus HR2142 | Write | ||
| PIV | 4486 | GenericDin5_Alrm_MngTyp | Generic Ain5 - alarm management (0: Disabled; 1: Only Warning; ...; Modbus HR2143 | Write | ||
| AV | 4497 | Regulation.FC_ExtTempLimit | Free cooling external temperature; Modbus HR2144 | Write | ||
| AV | 4498 | Regulation.FH_ExtTempLimit | Free heating external temperature limit; Modbus HR2145 | Write | ||
| AV | 4500 | IEC_ManModeVal | IEC: manual mode value; Modbus HR2146 | Write | ||
| AV | 4501 | Regulation.FanTempReg_Kp | Regulation fans speed: proportional gain; Modbus HR2147 | Write | ||
| PIV | 4502 | Regulation.FanTempReg_Td | Regulation fans speed: derivative time; Modbus HR2148 | Write | ||
| AV | 4503 | Fans_regulation.RetAirFlw_K_Factor | Return fan - K factor for air flow calculations; Modbus HR2149 | Write | ||
| AV | 4509 | BMS_Reg_AnalogPrbMap[1] | BMS registers - Analog map - 1; Modbus HR2150 | Write | ||
| AV | 4510 | BMS_Reg_AnalogPrbMap[2] | BMS registers - Analog map – 2; Modbus HR2151 | Write | ||
| AV | 4511 | BMS_Reg_AnalogPrbMap[3] | BMS registers - Analog map – 3; Modbus HR2152 | Write | ||
| AV | 4512 | BMS_Reg_AnalogPrbMap[4] | BMS registers - Analog map – 4; Modbus HR2153 | Write | ||
| AV | 4513 | BMS_Reg_AnalogPrbMap[5] | BMS registers - Analog map – 5; Modbus HR2154 | Write | ||
| PIV | 4534 | OA_Vlv_Open.Board_RW | Outdoor air pre-treatment floating valve open - Board selected; Modbus HR2155 | Write | ||
| PIV | 4535 | OA_Vlv_Open.Ch_Id_RW | Outdoor air pre-treatment floating valve open - Channel id selected; Modbus HR2156 | Write | ||
| PIV | 4536 | OA_Vlv_Open.T_On_RW | Outdoor air pre-treatment floating valve open - Time on cycle relay; Modbus HR2157 | Write | ||
| PIV | 4537 | OA_Vlv_Open.T_Off_RW | Outdoor air pre-treatment floating valve open - Time off cycle releay; Modbus HR2158 | Write | ||
| PIV | 4538 | OA_Vlv_Open.Ch_Type_RW | Outdoor air pre-treatment floating valve open - Digital output type; Modbus HR2159 | Write | ||
| PIV | 4539 | OA_Vlv_Close.Board_RW | Outdoor air pre-treatment floating valve close - Board selected; Modbus HR2160 | Write | ||
| PIV | 4540 | OA_Vlv_Close.Ch_Id_RW | Outdoor air pre-treatment floating valve close - Channel id selected; Modbus HR2161 | Write | ||
| PIV | 4541 | OA_Vlv_Close.T_On_RW | Outdoor air pre-treatment floating valve close - Time on cycle relay; Modbus HR2162 | Write | ||
| PIV | 4542 | OA_Vlv_Close.T_Off_RW | Outdoor air pre-treatment floating valve close - Time off cycle releay; Modbus HR2163 | Write | ||
| PIV | 4543 | OA_Vlv_Close.Ch_Type_RW | Outdoor air pre-treatment floating valve close - Digital output type; Modbus HR2164 | Write | ||
| AV | 4544 | OA_CoilManModeVal | Outdoor air pre-treatment coil manual mode value; Modbus HR2165 | Write | ||
| PIV | 4545 | OA_Coil_Typ | Outdoor air pre-treatment coil type; Modbus HR2166 | Write | ||
| AV | 4546 | OA_CoilWarmUpReq | Outdoor air pre-treatment coil warm up request; Modbus HR2167 | Write | ||
| AV | 4547 | RegPrbErrOA_CoilReq | Outdoor air pre-treatment coil request in case of regulation probe error; Modbus HR2168 | Write | ||
| PIV | 4548 | WrkHrs_OA_CoilAout.WrkHrs_Thrsh | Outdoor air pre-treatment coil analog output - Working hours threshold (1000hrs); Modbus HR2169 | Write | ||
| PIV | 4549 | WrkHrs_OA_CoilAout.WrkHrs_Res | Outdoor air pre-treatment coil analog output - Working hours reset; Modbus HR2170 | Write | ||
| PIV | 4550 | WrkHrs_OA_CoilStep1.WrkHrs_Thrsh | Outdoor air pre-treatment coil step 1 - Working hours threshold (1000hrs); Modbus HR2171 | Write | ||
| PIV | 4551 | WrkHrs_OA_CoilStep1.WrkHrs_Res | Outdoor air pre-treatment coil step 1 - Working hours reset; Modbus HR2172 | Write | ||
| PIV | 4552 | WrkHrs_OA_CoilStep2.WrkHrs_Thrsh | Outdoor air pre-treatment coil step 2 - Working hours threshold (1000hrs); Modbus HR2173 | Write | ||
| PIV | 4553 | WrkHrs_OA_CoilStep2.WrkHrs_Res | Outdoor air pre-treatment coil step 2 - Working hours reset; Modbus HR2174 | Write | ||
| PIV | 4554 | WrkHrs_OA_CoilStep3.WrkHrs_Thrsh | Outdoor air pre-treatment coil step 3 - Working hours threshold (1000hrs); Modbus HR2175 | Write | ||
| PIV | 4555 | WrkHrs_OA_CoilStep3.WrkHrs_Res | Outdoor air pre-treatment coil step 3 - Working hours reset; Modbus HR2176 | Write | ||
| PIV | 4556 | WrkHrs_OA_CoilStep4.WrkHrs_Thrsh | Outdoor air pre-treatment coil step 4 - Working hours threshold (1000hrs); Modbus HR2177 | Write | ||
| PIV | 4557 | WrkHrs_OA_CoilStep4.WrkHrs_Res | Outdoor air pre-treatment coil step 4 - Working hours reset; Modbus HR2178 | Write | ||
| PIV | 4558 | OA_Coil_StpN | Outdoor air pre-treatment coil steps number; Modbus HR2179 | Write | ||
| AV | 4559 | OA_Coil_PID_Params.Kp | Outdoor air pre-treatment coil PID parameters - Proportional gain; Modbus HR2180 | Write | ||
| PIV | 4560 | OA_Coil_PID_Params.Ti | Outdoor air pre-treatment coil PID parameters - Integral time; Modbus HR2181 | Write | ||
| PIV | 4561 | AFreezeOA_CoilReq | Outdoor air pre-treatment coil request during antifreeze off status; Modbus HR2182 | Write | ||
| PIV | 4575 | OA_RegTyp | OA regulation type (0:OA probe;1: Supply only; 2:Return only; 3: ...; Modbus HR2183 | Write | ||
| AV | 4576 | OA_CoilTempSetP | Outdoor air pre-treatment - temperature setpoint; Modbus HR2184 | Write | ||
| PIV | 4577 | OA_CoilActMode | Outdoor air pre-treatment coil - PID enable (0=Always,1=Only DX defrost); Modbus HR2185 (printed as PI4577) | Write | ||
| PIV | 3393 | VDI_Conf[0].Month | Month before the required inspection; Modbus IR001 | Read | ||
| PIV | 3394 | VDI_Conf[1].Month | Month before the required inspection; Modbus IR002 | Read | ||
| PIV | 3395 | VDI_Conf[2].Month | Month before the required inspection; Modbus IR003 | Read | ||
| PIV | 3396 | VDI_Conf[3].Month | Month before the required inspection; Modbus IR004 | Read | ||
| PIV | 3397 | VDI_Conf[4].Month | Month before the required inspection; Modbus IR005 | Read | ||
| PIV | 3398 | VDI_Conf[5].Month | Month before the required inspection; Modbus IR006 | Read | ||
| PIV | 3399 | VDI_Conf[6].Month | Month before the required inspection; Modbus IR007 | Read | ||
| PIV | 3400 | VDI_Conf[7].Month | Month before the required inspection; Modbus IR008 | Read | ||
| PIV | 3401 | VDI_Conf[8].Month | Month before the required inspection; Modbus IR009 | Read | ||
| PIV | 3402 | VDI_Conf[9].Month | Month before the required inspection; Modbus IR010 | Read | ||
| PIV | 3403 | VDI_Conf[10].Month | Month before the required inspection; Modbus IR011 | Read | ||
| PIV | 3404 | VDI_Conf[11].Month | Month before the required inspection; Modbus IR012 | Read | ||
| PIV | 3405 | VDI_Conf[12].Month | Month before the required inspection; Modbus IR013 | Read | ||
| PIV | 3406 | VDI_Conf[13].Month | Month before the required inspection; Modbus IR014 | Read | ||
| PIV | 3407 | VDI_Conf[14].Month | Month before the required inspection; Modbus IR015 | Read | ||
| PIV | 3408 | VDI_Conf[15].Month | Month before the required inspection; Modbus IR016 | Read | ||
| PIV | 3409 | VDI_Conf[16].Month | Month before the required inspection; Modbus IR017 | Read | ||
| PIV | 3410 | VDI_Conf[17].Month | Month before the required inspection; Modbus IR018 | Read | ||
| PIV | 3411 | VDI_Conf[18].Month | Month before the required inspection; Modbus IR019 | Read | ||
| PIV | 3412 | VDI_Conf[19].Month | Month before the required inspection; Modbus IR020 | Read | ||
| PIV | 3413 | VDI_Conf[20].Month | Month before the required inspection; Modbus IR021 | Read | ||
| PIV | 3414 | VDI_Conf[21].Month | Month before the required inspection; Modbus IR022 | Read | ||
| PIV | 3415 | VDI_Conf[22].Month | Month before the required inspection; Modbus IR023 | Read | ||
| PIV | 3416 | VDI_Conf[23].Month | Month before the required inspection; Modbus IR024 | Read | ||
| PIV | 3417 | VDI_Conf[24].Month | Month before the required inspection; Modbus IR025 | Read | ||
| PIV | 3418 | VDI_Conf[25].Month | Month before the required inspection; Modbus IR026 | Read | ||
| PIV | 3419 | VDI_Conf[26].Month | Month before the required inspection; Modbus IR027 | Read | ||
| PIV | 3420 | VDI_Conf[27].Month | Month before the required inspection; Modbus IR028 | Read | ||
| PIV | 3421 | VDI_Conf[28].Month | Month before the required inspection; Modbus IR029 | Read | ||
| PIV | 3434 | SupplyTemp.Uom_W | Supply temperature - Uom analog input; Modbus IR042 | Read | ||
| AVmin | 3435 | SupplyTemp.Val_Hw_R | Supply temperature - Value reads from board; Modbus IR043 | Read | ||
| PIV | 3437 | SupplyHum.Uom_W | Supply humidity - Uom analog input; Modbus IR045 | Read | ||
| AV | 3438 | SupplyHum.Val_Hw_R | Supply humidity - Value reads from board; Modbus IR046 | Read | ||
| AV | 3439 | SupplyHum.Val_R | Supply humidity; Modbus IR047 | Read | ||
| PIV | 3440 | RetTemp.Uom_W | Return temperature - Uom analog input; Modbus IR048 | Read | ||
| AV | 3441 | RetTemp.Val_Hw_R | Return temperature - Value reads from board; Modbus IR049 | Read | ||
| AVmin | 3442 | RetTemp.Val_R | Return temperature; Modbus IR050 | Read | ||
| PIV | 3443 | RetHum.Uom_W | Return humidity - Uom analog input; Modbus IR051 | Read | ||
| AV | 3444 | RetHum.Val_Hw_R | Return humidity - Value reads from board; Modbus IR052 | Read | ||
| AV | 3445 | RetHum.Val_R | Return humidity; Modbus IR053 | Read | ||
| PIV | 3446 | RoomTemp.Uom_W | Room temperature - Uom analog input; Modbus IR054 | Read | ||
| AV | 3447 | RoomTemp.Val_Hw_R | Room temperature - Value reads from board; Modbus IR055 | Read | ||
| AV | 3448 | RoomTemp.Val_R | Room temperature; Modbus IR056 | Read | ||
| PIV | 3449 | RoomHum.Uom_W | Room humidity - Uom analog input; Modbus IR057 | Read | ||
| AV | 3450 | RoomHum.Val_Hw_R | Room humidity - Value reads from board; Modbus IR058 | Read | ||
| AV | 3451 | RoomHum.Val_R | Room humidity; Modbus IR059 | Read | ||
| PIV | 3452 | ExtTemp.Uom_W | Fresh air temperature - Uom analog input; Modbus IR060 | Read | ||
| AV | 3453 | ExtTemp.Val_Hw_R | Fresh air temperature - Value reads from board; Modbus IR061 | Read | ||
| PIV | 3455 | ExtHum.Uom_W | Fresh air humidity - Uom analog input; Modbus IR063 | Read | ||
| AV | 3456 | ExtHum.Val_Hw_R | Fresh air humidity - Value reads from board; Modbus IR064 | Read | ||
| AV | 3457 | ExtHum.Val_R | Fresh air humidity; Modbus IR065 | Read | ||
| PIV | 3458 | ExhTemp.Uom_W | Exhaust temperature - Uom analog input; Modbus IR066 | Read | ||
| AV | 3459 | ExhTemp.Val_Hw_R | Exhaust temperature - Value reads from board; Modbus IR067 | Read | ||
| AV | 3460 | ExhTemp.Val_R | Exhaust temperature; Modbus IR068 | Read | ||
| PIV | 3461 | ExhHum.Uom_W | Exhaust humidity - Uom analog input; Modbus IR069 | Read | ||
| AV | 3462 | ExhHum.Val_Hw_R | Exhaust humidity - Value reads from board; Modbus IR070 | Read | ||
| AV | 3463 | ExhHum.Val_R | Exhaust humidity; Modbus IR071 | Read | ||
| PIV | 3464 | AFreezeTemp.Uom_W | Antifreeze temperature - Uom analog input; Modbus IR072 | Read | ||
| AV | 3465 | AFreezeTemp.Val_Hw_R | Antifreeze temperature - Value reads from board; Modbus IR073 | Read | ||
| AV | 3466 | AFreezeTemp.Val_R | Antifreeze temperature; Modbus IR074 | Read | ||
| PIV | 3467 | SatTemp.Uom_W | Saturation temperature - Uom analog input; Modbus IR075 | Read | ||
| AV | 3468 | SatTemp.Val_Hw_R | Saturation temperature - Value reads from board; Modbus IR076 | Read | ||
| PIV | 3470 | SatHum.Uom_W | Saturation humidity - Uom analog input; Modbus IR078 | Read | ||
| AV | 3471 | SatHum.Val_Hw_R | Saturation humidity - Value reads from board; Modbus IR079 | Read | ||
| AV | 3472 | SatHum.Val_R | Saturation humidity; Modbus IR080 | Read | ||
| PIV | 3473 | OA_Temp.Uom_W | Outdoor air pre-treatment temperature - Uom analog input; Modbus IR081 | Read | ||
| AV | 3474 | OA_Temp.Val_Hw_R | Outdoor air pre-treatment temperature - Value reads from board; Modbus IR082 | Read | ||
| AV | 3475 | OA_Temp.Val_R | Outdoor air pre-treatment temperature; Modbus IR083 | Read | ||
| PIV | 3476 | SupplyAirP.Uom_W | Supply air pressure - Uom analog input; Modbus IR084 | Read | ||
| AV | 3477 | SupplyAirP.Val_Hw_R | Supply air pressure - Value reads from board; Modbus IR085 | Read | ||
| PIV | 3479 | RetAirP.Uom_W | Return air pressure - Uom analog input; Modbus IR087 | Read | ||
| AV | 3480 | RetAirP.Val_Hw_R | Return air pressure - Value reads from board; Modbus IR088 | Read | ||
| PIV | 3482 | AirQuality_CO2.Uom_W | CO2 sensor - Uom analog input; Modbus IR090 | Read | ||
| AV | 3483 | AirQuality_CO2.Val_Hw_R | CO2 sensor - Value reads from board; Modbus IR091 | Read | ||
| PIV | 3485 | AirQuality_VOC.Uom_W | VOC sensor - Uom analog input; Modbus IR093 | Read | ||
| AV | 3486 | AirQuality_VOC.Val_Hw_R | VOC sensor - Value reads from board; Modbus IR094 | Read | ||
| AV | 3487 | AirQuality_VOC.Val_R | VOC sensor; Modbus IR095 | Read | ||
| PIV | 3488 | DscgP.Uom_W | Discharge pressure - Uom analog input; Modbus IR096 | Read | ||
| AV | 3489 | DscgP.Val_Hw_R | Discharge pressure - Value reads from board; Modbus IR097 | Read | ||
| PIV | 3491 | DscgT.Uom_W | Discharge temperature - Uom analog input; Modbus IR099 | Read | ||
| AV | 3492 | DscgT.Val_Hw_R | Discharge temperature - Value reads from board; Modbus IR100 | Read | ||
| PIV | 3494 | SuctP.Uom_W | Suction pressure - Uom analog input; Modbus IR102 | Read | ||
| AV | 3495 | SuctP.Val_Hw_R | Suction pressure - Value reads from board; Modbus IR103 | Read | ||
| PIV | 3497 | SuctT.Uom_W | Suction temperature - Uom analog input; Modbus IR105 | Read | ||
| AV | 3498 | SuctT.Val_Hw_R | Suction temperature - Value reads from board; Modbus IR106 | Read | ||
| PIV | 3500 | OA_CoilWaterTemp.Uom_W | Outdoor air pre-treatment coil water temperature - Uom analog input; Modbus IR108 | Read | ||
| AV | 3501 | OA_CoilWaterTemp.Val_Hw_R | Outdoor air pre-treatment coil water temperature - Value reads from board; Modbus IR109 | Read | ||
| AV | 3502 | OA_CoilWaterTemp.Val_R | Outdoor air pre-treatment coil water temperature; Modbus IR110 | Read | ||
| PIV | 3503 | PreHeatCoilWaterTemp.Uom_W | Preheat coil water temperature - Uom analog input; Modbus IR111 | Read | ||
| AV | 3504 | PreHeatCoilWaterTemp.Val_Hw_R | Preheat coil water temperature - Value reads from board; Modbus IR112 | Read | ||
| AV | 3505 | PreHeatCoilWaterTemp.Val_R | Preheat coil water temperature; Modbus IR113 | Read | ||
| PIV | 3506 | MainCoilWaterTemp.Uom_W | Main coil water temperature - Uom analog input; Modbus IR114 | Read | ||
| AV | 3507 | MainCoilWaterTemp.Val_Hw_R | Main coil water temperature - Value reads from board; Modbus IR115 | Read | ||
| AV | 3508 | MainCoilWaterTemp.Val_R | Main coil water temperature; Modbus IR116 | Read | ||
| PIV | 3509 | ReHeatCoilWaterTemp.Uom_W | Postheat coil water temperature - Uom analog input; Modbus IR117 | Read | ||
| AV | 3510 | ReHeatCoilWaterTemp.Val_Hw_R | Postheat coil water temperature - Value reads from board; Modbus IR118 | Read | ||
| AV | 3511 | ReHeatCoilWaterTemp.Val_R | Postheat coil water temperature; Modbus IR119 | Read | ||
| PIV | 3512 | AuxPrb_1.Uom_W | Auxiliary probe 1 - Uom analog input; Modbus IR120 | Read | ||
| AV | 3513 | AuxPrb_1.Val_Hw_R | Auxiliary probe 1 - Value reads from board; Modbus IR121 | Read | ||
| AV | 3514 | AuxPrb_1.Val_R | Auxiliary probe 1; Modbus IR122 | Read | ||
| PIV | 3515 | AuxPrb_2.Uom_W | Auxiliary probe 2 - Uom analog input; Modbus IR123 | Read | ||
| AV | 3516 | AuxPrb_2.Val_Hw_R | Auxiliary probe 2 - Value reads from board; Modbus IR124 | Read | ||
| AV | 3517 | AuxPrb_2.Val_R | Auxiliary probe 2; Modbus IR125 | Read | ||
| PIV | 3518 | AuxPrb_3.Uom_W | Auxiliary probe 3 - Uom analog input; Modbus IR126 | Read | ||
| AV | 3519 | AuxPrb_3.Val_Hw_R | Auxiliary probe 3 - Value reads from board; Modbus IR127 | Read | ||
| AV | 3520 | AuxPrb_3.Val_R | Auxiliary probe 3; Modbus IR128 | Read | ||
| PIV | 3521 | AuxPrb_4.Uom_W | Auxiliary probe 4 - Uom analog input; Modbus IR129 | Read | ||
| AV | 3522 | AuxPrb_4.Val_Hw_R | Auxiliary probe 4 - Value reads from board; Modbus IR130 | Read | ||
| AV | 3523 | AuxPrb_4.Val_R | Auxiliary probe 4; Modbus IR131 | Read | ||
| PIV | 3524 | Ain_SetP.Uom_W | Setpoint by AIN - Uom analog input; Modbus IR132 | Read | ||
| AV | 3525 | Ain_SetP.Val_Hw_R | Setpoint by AIN - Value reads from board; Modbus IR133 | Read | ||
| AV | 3526 | Ain_SetP.Val_R | Setpoint by AIN; Modbus IR134 | Read | ||
| PIV | 3527 | SupplyRecoveryTemp.Uom_W | Supply recovery temperature - Uom analog input; Modbus IR135 | Read | ||
| AV | 3528 | SupplyRecoveryTemp.Val_Hw_R | Supply recovery temperature - Value reads from board; Modbus IR136 | Read | ||
| AV | 3529 | SupplyRecoveryTemp.Val_R | Supply recovery temperature; Modbus IR137 | Read | ||
| PIV | 3530 | RetRecoveryTemp.Uom_W | Return recovery temperature - Uom analog input; Modbus IR138 | Read | ||
| AV | 3531 | RetRecoveryTemp.Val_Hw_R | Return recovery temperature - Value reads from board; Modbus IR139 | Read | ||
| AV | 3532 | RetRecoveryTemp.Val_R | Return recovery temperature; Modbus IR140 | Read | ||
| PIV | 3533 | HepaFilt_1.Uom_W | Hepa filter 1 - Uom analog input; Modbus IR141 | Read | ||
| AV | 3534 | HepaFilt_1.Val_Hw_R | Hepa filter 1 - Value reads from board; Modbus IR142 | Read | ||
| AV | 3535 | HepaFilt_1.Val_R | Hepa filter 1; Modbus IR143 | Read | ||
| PIV | 3536 | HepaFilt_2.Uom_W | Hepa filter 2 - Uom analog input; Modbus IR144 | Read | ||
| AV | 3537 | HepaFilt_2.Val_Hw_R | Hepa filter 2 - Value reads from board; Modbus IR145 | Read | ||
| AV | 3538 | HepaFilt_2.Val_R | Hepa filter 2; Modbus IR146 | Read | ||
| AV | 3540 | SupplyFan_Aout.Val_Hw_R | Supply fan - Hardware value writes from board; Modbus IR148 | Read | ||
| AV | 3542 | RetFan_Aout.Val_Hw_R | Return fan - Hardware value writes from board; Modbus IR150 | Read | ||
| AV | 3544 | BypassDamp_Aout.Val_Hw_R | Bypass damper - Hardware value writes from board; Modbus IR152 | Read | ||
| AV | 3546 | MixingDamp_Aout.Val_Hw_R | Mixing damper - Hardware value writes from board; Modbus IR154 | Read | ||
| AV | 3548 | FreshAirDamp_Aout.Val_Hw_R | Fresh air damper - Hardware value writes from board; Modbus IR156 | Read | ||
| AV | 3549 | ReHeatCoil_Aout.Val_W | Reheat heater; Modbus IR157 | Read | ||
| AV | 3550 | ReHeatCoil_Aout.Val_Hw_R | Reheat heater - Hardware value writes from board; Modbus IR158 | Read | ||
| AV | 3551 | PreHeatCoil_Aout.Val_W | Pre-Heating heater; Modbus IR159 | Read | ||
| AV | 3552 | PreHeatCoil_Aout.Val_Hw_R | Pre-Heating heater - Hardware value writes from board; Modbus IR160 | Read | ||
| AV | 3553 | OA_Coil_Aout.Val_W | Outdoor air pre-treatment heater; Modbus IR161 | Read | ||
| AV | 3554 | OA_Coil_Aout.Val_Hw_R | Outdoor air pre-treatment heater - Hardware value writes from board; Modbus IR162 | Read | ||
| AV | 3555 | MainCoil_Aout.Val_W | Main coil valve; Modbus IR163 | Read | ||
| AV | 3556 | MainCoil_Aout.Val_Hw_R | Main coil valve - Hardware value writes from board; Modbus IR164 | Read | ||
| AV | 3558 | ThrmlWheel_Aout.Val_Hw_R | Thermal wheel - Hardware value writes from board; Modbus IR166 | Read | ||
| AV | 3559 | Humidifier_Aout.Val_W | Humidifier; Modbus IR167 | Read | ||
| AV | 3560 | Humidifier_Aout.Val_Hw_R | Humidifier - Hardware value writes from board; Modbus IR168 | Read | ||
| AV | 3562 | ExhAirDamp_Aout.Val_Hw_R | Exhaust air damper - Hardware value writes from board; Modbus IR170 | Read | ||
| AV | 3564 | AuxAout_1.Val_Hw_R | Auxiliary output 1 - Hardware value writes from board; Modbus IR172 | Read | ||
| AV | 3566 | AuxAout_2.Val_Hw_R | Auxiliary output 2 - Hardware value writes from board; Modbus IR174 | Read | ||
| AV | 3568 | AuxAout_3.Val_Hw_R | Auxiliary output 3 - Hardware value writes from board; Modbus IR176 | Read | ||
| AV | 3570 | AuxAout_4.Val_Hw_R | Auxiliary output 4 - Hardware value writes from board; Modbus IR178 | Read | ||
| AV | 3571 | IEC_Aout.Val_W | IEC; Modbus IR179 | Read | ||
| AV | 3572 | IEC_Aout.Val_Hw_R | IEC - Hardware value writes from board; Modbus IR180 | Read | ||
| AV | 3573 | Recovery_Aout.Val_W | Recovery pump; Modbus IR181 | Read | ||
| AV | 3574 | Recovery_Aout.Val_Hw_R | Recovery pump - Hardware value writes from board; Modbus IR182 | Read | ||
| AV | 3575 | SupplyAirDamp_Aout.Val_W | Supply air damper; Modbus IR183 | Read | ||
| AV | 3576 | SupplyAirDamp_Aout.Val_Hw_R | Supply air damper - Hardware value writes from board; Modbus IR184 | Read | ||
| AV | 3577 | RetAirDamp_Aout.Val_W | Return air damper; Modbus IR185 | Read | ||
| AV | 3578 | RetAirDamp_Aout.Val_Hw_R | Return air damper - Hardware value writes from board; Modbus IR186 | Read | ||
| PIV | 3579 | AlarmsMng.AlrmHour | Alarm timestamp to which alarm index refers, hour; Modbus IR187 | Read | ||
| PIV | 3580 | AlarmsMng.AlrmMinute | Alarm timestamp to which alarm index refers, minute; Modbus IR188 | Read | ||
| PIV | 3581 | AlarmsMng.AlrmDay | Alarm timestamp to which alarm index refers, day; Modbus IR189 | Read | ||
| PIV | 3582 | AlarmsMng.AlrmMonth | Alarm timestamp to which alarm index refers, month; Modbus IR190 | Read | ||
| PIV | 3583 | AlarmsMng.AlrmYear | Alarm timestamp to which alarm index refers, year; Modbus IR191 | Read | ||
| PIV | 3584 | AlarmsMng.AlrmLogHour | Alarm log. timestamp to which alarm log. index refers, hour; Modbus IR192 | Read | ||
| PIV | 3585 | AlarmsMng.AlrmLogMinute | Alarm log. timestamp to which alarm log. index refers, minute; Modbus IR193 | Read | ||
| PIV | 3586 | AlarmsMng.AlrmLogDay | Alarm log. timestamp to which alarm log. index refers, day; Modbus IR194 | Read | ||
| PIV | 3587 | AlarmsMng.AlrmLogMonth | Alarm log. timestamp to which alarm log. index refers, month; Modbus IR195 | Read | ||
| PIV | 3588 | AlarmsMng.AlrmLogYear | Alarm log. timestamp to which alarm log. index refers, year; Modbus IR196 | Read | ||
| IV | 3589 | AlarmsMng.ErrParamExpAlrms | 32-bit (2 Modbus registers); Modbus IR197 | Read | ||
| IV | 3590 | Scheduler_OnOffUnit.OnOffByKeb_SecLeft | Seconds left before switching on/ff by keyboard; Modbus IR199 | Read | ||
| PIV | 3591 | Scheduler_OnOffUnit.PartyMode_CntDwn | Party mode countdown; 32-bit (2 Modbus registers); Modbus IR200 | Read | ||
| PIV | 3592 | Dampers.DampersStatus | 0: Off; 1: Startup; 2: On; 3: Shutdown;; Modbus IR202 | Read | ||
| AV | 3593 | MaskMng.HeatExchgReq | Modbus IR203 | Read | ||
| PIV | 3594 | MaskMng.HeatExchgStatusSyn | Heat exchanger status (0: recovery; 1: freecooling; 2: freeheating; 3: ...; Modbus IR204 | Read | ||
| AV | 3595 | HeatExchanger.HeatExchgEfficiency | Heat exchanger efficiency (see comment on the algorithm for the formula); Modbus IR205 | Read | ||
| AV | 3596 | RetAirFlwVal | Return air flw value; Modbus IR206 | Read | ||
| AV | 3597 | AirFlwVal | Input probe air flow; Modbus IR207 | Read | ||
| AV | 3598 | SupplyFanReq | Supply fan request; Modbus IR208 | Read | ||
| PIV | 3599 | ComStatus_Supply_EBM_1 | Communication status of supply ebm fan (0:Online; 1:Offline; 2:Invalid packet; ...; Modbus IR209 | Read | ||
| PIV | 3600 | SupplyFanAct | Percentage of activation of ebmpapst supply fan; Modbus IR210 | Read | ||
| AV | 3601 | RetFanReq | Return fan request; Modbus IR211 | Read | ||
| PIV | 3602 | ComStatus_Return_EBM_1 | Communication status of return ebm fan (0:Online; 1:Offline; 2:Invalid packet; ...; Modbus IR212 | Read | ||
| PIV | 3603 | RetFanAct | Percentage of activation of ebmpapst return fan; Modbus IR213 | Read | ||
| AV | 3604 | Fans_regulation.RetFan_AirQuality_SetPOffs | Return fan - Air quality setpoint offset; Modbus IR214 | Read | ||
| AV | 3605 | Fans_regulation.SupplyFan_AirQuality_SetPOffs | Supply fan - Air quality setpoint offset; Modbus IR215 | Read | ||
| AV | 3606 | AirQuality_Damps_RegReq | Air Quality - Dampers regulation request; Modbus IR216 | Read | ||
| AV | 3607 | AirQuality_Fans_RegReq | Air Quality - Fans regulation request; Modbus IR217 | Read | ||
| AV | 3608 | SupplyTempRegSetP | Supply temperature regulation set point; Modbus IR218 | Read | ||
| AV | 3609 | PreHeatCoilRegReq | Pre-heating request from PID Seq; Modbus IR219 | Read | ||
| AV | 3610 | PreHeatCoilReq | Pre-heating request; Modbus IR220 | Read | ||
| AV | 3611 | Coils.ModulMainCoilReq | Cooling/Heating coil request; Modbus IR221 | Read | ||
| AV | 3612 | ReHeatCoilRegReq | Post-heating request from PID Seq; Modbus IR222 | Read | ||
| AV | 3613 | ReHeatCoilReq | Post-heating request; Modbus IR223 | Read | ||
| AV | 3614 | CondTemp | Condensing temperature; Modbus IR224 | Read | ||
| IV | 3615 | MaskMng.CompStatusMsk | Modbus IR225 | Read | ||
| IV | 3616 | MaskMng.CompOnOffCntDwn | OnOff compressor countdown; 32-bit (2 Modbus registers); Modbus IR226 | Read | ||
| AV | 3617 | CompReq | Compressor request; Modbus IR228 | Read | ||
| AV | 3618 | Data_EVD_Emb_1.EVD.Variables.SH_EvapTemp.Val | EVD parameters - Status variables - Evaporation temperature; Modbus IR229 | Read | ||
| AV | 3619 | Data_EVD_Emb_1.EVD.Variables.CondTemp.Val | EVD parameters - Status variables - Condensing temperature; Modbus IR230 | Read | ||
| IV | 3620 | MaskMng.BLDC_CompStatus | For mask usage; Modbus IR231 | Read | ||
| IV | 3621 | MaskMng.BLDC_CompCntDwn | For mask usage; 32-bit (2 Modbus registers); Modbus IR232 | Read | ||
| AV | 3622 | BLDC_PwrReq | BLDC power request; Modbus IR234 | Read | ||
| AV | 3623 | MaskMng.BLDC_CompPerc_Scaled | BLDC Compressore run request scaled with the custom maximum limit; Modbus IR235 | Read | ||
| IV | 3624 | BLDC_compressor.EnvZone | 0=Null;1=OK;2=Max.comp.rat;3=Max.dsc.P.;4=Curr.limit;5=Max. suct.P.;6=Min.comp.rat;7=Min.DeltaP;8=Min.dsc.P.;9=Min.suct.P.; Modbus IR236 | Read | ||
| IV | 3625 | BLDCtoEVD.RegSubTyp | BLDC to EVD parameters - EVD regulation subtype; Modbus IR237 | Read | ||
| IV | 3626 | MaskMng.EEV_Status | For mask usage; Modbus IR238 | Read | ||
| AV | 3627 | Data_EVD_Emb_1.EVD.Variables.SH.Val | EVD parameters - Status variables - Superheat; Modbus IR239 | Read | ||
| AV | 3628 | BLDC_compressor.Info_PWRP1.Info_RotorSpeed_rps | Inverter Power Plus Info - Current rotor speed [rps]; Modbus IR240 | Read | ||
| AV | 3629 | Data_EVD_Emb_1.EVD.Variables.EEV_PosPercent.Val | EVD parameters - Status variables - Valve opening; Modbus IR241 | Read | ||
| IV | 3630 | MaskMng.CompEnvCntDwn | Modbus IR242 | Read | ||
| IV | 3631 | Data_EVD_Emb_1.EVD.Variables.EEV_PosSteps.Val | EVD parameters - Status variables - Valve position; Modbus IR243 | Read | ||
| AV | 3632 | MaskMng.EEVSet | For mask usage; Modbus IR244 | Read | ||
| AV | 3633 | Data_EVD_Emb_1.EVD.Variables.DscgSH.Val | EVD parameters - Status variables - Discharge superheat; Modbus IR245 | Read | ||
| AV | 3634 | HumDehumReg.HumDehum_RegHum_Rel | Humidification/Dehumidification: Relative humidity variable; Modbus IR246 | Read | ||
| AV | 3635 | HumDehumReg.HumDehum_RegHum_Abs | Humidification/Dehumidification: Absolute humidity variable; Modbus IR247 | Read | ||
| AV | 3636 | HumDehumReg.HumDehum_SetP_Abs | Humidification/Dehumidification: Absolute setpoint; Modbus IR248 | Read | ||
| AV | 3637 | HumRegReq | Humidification request from PID Seq; Modbus IR249 | Read | ||
| AV | 3638 | DehumRegReq | Dehumidification request; Modbus IR250 | Read | ||
| AV | 3639 | Dehum_DewPointSetP | Dew point set point for dehumidification; Modbus IR251 | Read | ||
| AV | 3640 | AuxiliaryRegulation.AuxReg1_Info.RegVal | Auxiliary regulation 1: Informations - Regulation value; Modbus IR252 | Read | ||
| AV | 3641 | AuxiliaryRegulation.AuxReg2_Info.RegVal | Auxiliary regulation 2: Informations - Regulation value; Modbus IR253 | Read | ||
| AV | 3642 | AuxiliaryRegulation.AuxReg3_Info.RegVal | Auxiliary regulation 3: Informations - Regulation value; Modbus IR254 | Read | ||
| AV | 3643 | AuxiliaryRegulation.AuxReg4_Info.RegVal | Auxiliary regulation 4: Informations - Regulation value; Modbus IR255 | Read | ||
| PIV | 3644 | Scheduler_OnOffUnit.SchedSrc | Scheduler source (DIN, Party mode, SPV, cpCO, th-Tune); Modbus IR256 | Read | ||
| PIVmin | 3645 | SchedStatus | Unit status currently active: 0=Off; 1=Economy; 2=Pre-comfort; 3=Comfort; Modbus IR257 | Read | ||
| AV | 3646 | KWater_MB.HR18_ExtT | KWater modbus variables - External temperature; Modbus IR258 | Read | ||
| AV | 3647 | KWater_MB.HR21_TCircKAir | KWater modbus variables - KAir circuit temperature; Modbus IR259 | Read | ||
| PIV | 3648 | kWater_UnitStatus | Unit status kwater; Modbus IR260 | Read | ||
| AV | 3649 | HumifogMng.HUMFOG_PwrReq | Power request; Modbus IR261 | Read | ||
| AV | 3650 | HumifogMng.HUMFOG_ActualProd | Actual production of rack (kg/h-lb/h); Modbus IR262 | Read | ||
| PIV | 3651 | HumifogMng.HUMFOG_HoursWorsk | Pump running hour humifog; 32-bit (2 Modbus registers); Modbus IR263 | Read | ||
| IV | 3652 | HumifogMng.HUMFOG_UnitStatus | Machine status; Modbus IR265 | Read | ||
| AV | 3653 | IEC_Req | IEC: request; Modbus IR266 | Read | ||
| AV | 3654 | IEC.IEC_HUMFOG_ActualProd | Actual production of rack (kg/h-lb/h); Modbus IR267 | Read | ||
| PIV | 3655 | IEC.IEC_HUMFOG_HoursWorks | Pump running hour humifog; 32-bit (2 Modbus registers); Modbus IR268 | Read | ||
| IV | 3656 | IEC.IEC_HUMFOG_UnitStatus | Machine status; Modbus IR270 | Read | ||
| AV | 3657 | uChiller_mng.Info_uCh.BLDC_rps_Circ1 | Split an int value into digits - rps bldc circ1 ...; Modbus IR271 | Read | ||
| IV | 3658 | uChiller_mng.Info_uCh.EEV_PosPerc_Circ1 | Split an int value into digits - Opn1 - EEV ...; Modbus IR272 | Read | ||
| AV | 3659 | uChiller_mng.Info_uCh.DscgPCirc1 | Split an int value into digits - dSP1-Discharge press. probe ...; Modbus IR273 | Read | ||
| AV | 3660 | uChiller_mng.Info_uCh.SuctPCirc1 | Split an int value into digits - ScP1-Suction press. of circ.1; Modbus IR274 | Read | ||
| IV | 3661 | uChiller_mng.UnitStatus_uCh | Unitstatus(0=OffByDI; 1=OffByKeyb; 2=OffBySched; 3=OffByBMS; 4=OffByChgOvr; 5=OffByAl; 6=Dfr; 7=StdBy; 14=FCOn; 15=CoolOn; ...; Modbus IR275 | Read | ||
| AV | 3662 | uChiller_mng.Info_uCh.BLDC_rps_Circ2 | Split an int value into digits - rps bldc circ2 ...; Modbus IR276 | Read | ||
| PIV | 3663 | GeneralMng.CurrVer.X | Current version of the application according to standard - X ...; Modbus IR277 | Read | ||
| PIV | 3664 | GeneralMng.CurrVer.Y | Current version of the application according to standard - Y ...; Modbus IR278 | Read | ||
| PIV | 3665 | GeneralMng.CurrVer.Z | Current version of the application according to standard - Z ...; Modbus IR279 | Read | ||
| PIV | 3666 | GeneralMng.CurrVer.D | Current version of the application according to standard - D ...; Modbus IR280 | Read | ||
| PIV | 3667 | GeneralMng.OsVersion[1] | Application version; 32-bit (2 Modbus registers); Modbus IR281 | Read | ||
| PIV | 3668 | GeneralMng.OsVersion[2] | Application version; 32-bit (2 Modbus registers); Modbus IR283 | Read | ||
| PIV | 3669 | GeneralMng.OsVersion[3] | Application version; 32-bit (2 Modbus registers); Modbus IR285 | Read | ||
| PIV | 3670 | GeneralMng.BoardTyp[1] | Type of board (12 = c.pCO, 13 = uPC, 14 ...; 32-bit; Modbus IR287 | Read | ||
| PIV | 3671 | GeneralMng.BoardTyp[2] | Type of board (12 = c.pCO, 13 = uPC, 14 ...; 32-bit; Modbus IR289 | Read | ||
| PIV | 3672 | VarToShow.IdxChName | Modbus IR291 | Read | ||
| PIV | 3673 | VarToShow.Board | Modbus IR292 | Read | ||
| PIV | 3674 | VarToShow.Ch_Id | Modbus IR293 | Read | ||
| AV | 3675 | ObjMsk.ValStaticPress | High/low limit alarm with hysteresis - Value static pressure; Modbus IR294 | Read | ||
| AV | 3676 | ObjMsk.ValAirQual | High/low limit alarm with hysteresis - Value air quality; Modbus IR295 | Read | ||
| AV | 3677 | ObjMsk.ValRfrgPress | High/low limit alarm with hysteresis - Value refrigerant pressure; Modbus IR296 | Read | ||
| AV | 3678 | ObjMsk.ValFlowRate | High/low limit alarm with hysteresis - Value flow rate; Modbus IR297 | Read | ||
| AV | 3679 | ObjMsk.ValAirFlow | High/low limit alarm with hysteresis - Value air flow; Modbus IR298 | Read | ||
| AV | 3680 | ObjMsk.ValTemp | High/low limit alarm with hysteresis - Value temperature; Modbus IR299 | Read | ||
| AV | 3681 | ObjMsk.ValHum | High/low limit alarm with hysteresis - Value humidity; Modbus IR300 | Read | ||
| AV | 3682 | ObjMsk.ValAout | High/low limit alarm with hysteresis - Value analog output; Modbus IR301 | Read | ||
| AV | 3683 | ObjMsk.ValGeneric | High/low limit alarm with hysteresis - Value generic probe; Modbus IR302 | Read | ||
| AV | 3684 | ObjMsk.ValPercent | High/low limit alarm with hysteresis - Value percent probe; Modbus IR303 | Read | ||
| PIV | 3685 | SupplyFan_MainMask | Used only for main mask; Modbus IR304 | Read | ||
| PIV | 3686 | MaskMng.RetFan_MainMask | Used only for main mask; Modbus IR305 | Read | ||
| PIV | 3687 | Hour | Actual hour; Modbus IR306 | Read | ||
| PIV | 3688 | Minute | Actual minute; Modbus IR307 | Read | ||
| PIV | 3689 | Scheduler_OnOffUnit.UnitStatus | Unit status; Modbus IR308 | Read | ||
| PIV | 3690 | Ebmpapst_SupplyFan.InfoSpeed_EBM_1.CurrSpeed | Current speed in [rpm] of the fan for Ebmpapst fan; Modbus IR309 | Read | ||
| PIV | 3691 | Ebmpapst_SupplyFan.ElectrInfo_EBM_1.DC_Link_V | DC link voltage for Ebmpapst fan; Modbus IR310 | Read | ||
| PIV | 3692 | Ebmpapst_SupplyFan.ElectrInfo_EBM_1.DC_Link_A | DC link current for Ebmpapst fan; Modbus IR311 | Read | ||
| PIV | 3693 | Ebmpapst_SupplyFan.ElectrInfo_EBM_1.CurrPower | Current power in [W] for Ebmpapst fan; Modbus IR312 | Read | ||
| PIV | 3694 | Ebmpapst_SupplyFan.ElectrInfo_EBM_1.ElectrTemp | Internal circuit temperature for Ebmpapst fan; Modbus IR313 | Read | ||
| PIV | 3695 | Ebmpapst_SupplyFan.MotStatus_EBM_1.IR_MotStatus | Motor status input register; Modbus IR314 | Read | ||
| PIV | 3696 | Ebmpapst_SupplyFan.Warn_EBM_1.IR_Warn | Warining input register (Bitfield); Modbus IR315 | Read | ||
| PIV | 3697 | Ebmpapst_SupplyFan.InfoSpeed_EBM_1.MaxSpeed | Maximum admissible speed: all read or speed in [rpm] settings ...; Modbus IR316 | Read | ||
| PIV | 3698 | Ebmpapst_SupplyFan.CntWorkHrsBkp_EBM_1 | Working hour counter for Ebmpapst fan; Modbus IR317 | Read | ||
| PIV | 3699 | Ebmpapst_ReturnFan.InfoSpeed_EBM_1.CurrSpeed | Current speed in [rpm] of the fan for Ebmpapst fan; Modbus IR318 | Read | ||
| PIV | 3700 | Ebmpapst_ReturnFan.ElectrInfo_EBM_1.DC_Link_V | DC link voltage for Ebmpapst fan; Modbus IR319 | Read | ||
| PIV | 3701 | Ebmpapst_ReturnFan.ElectrInfo_EBM_1.DC_Link_A | DC link current for Ebmpapst fan; Modbus IR320 | Read | ||
| PIV | 3702 | Ebmpapst_ReturnFan.ElectrInfo_EBM_1.CurrPower | Current power in [W] for Ebmpapst fan; Modbus IR321 | Read | ||
| PIV | 3703 | Ebmpapst_ReturnFan.ElectrInfo_EBM_1.ElectrTemp | Internal circuit temperature for Ebmpapst fan; Modbus IR322 | Read | ||
| PIV | 3704 | Ebmpapst_ReturnFan.MotStatus_EBM_1.IR_MotStatus | Motor status input register; Modbus IR323 | Read | ||
| PIV | 3705 | Ebmpapst_ReturnFan.Warn_EBM_1.IR_Warn | Warining input register (Bitfield); Modbus IR324 | Read | ||
| PIV | 3706 | Ebmpapst_ReturnFan.InfoSpeed_EBM_1.MaxSpeed | Maximum admissible speed: all read or speed in [rpm] settings ...; Modbus IR325 | Read | ||
| PIV | 3707 | Ebmpapst_ReturnFan.CntWorkHrsBkp_EBM_1 | Working hour counter for Ebmpapst fan; Modbus IR326 | Read | ||
| PIV | 3708 | ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_1.CurrSpeed_rpm | Fan speed informations - Actual speed [rpm] of the Zhiel-Abegg fan; Modbus IR327 | Read | ||
| PIV | 3709 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.DC_LinkV | Fan electrical informations - DC link voltage (V); Modbus IR328 | Read | ||
| PIV | 3710 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.LineV | Fan electrical informations - Supply voltage (peak voltage); Modbus IR329 | Read | ||
| PIV | 3711 | ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_1.MaxSpeed_rpm | Fan speed informations - Maximum set speed; Modbus IR330 | Read | ||
| PIV | 3712 | ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_1.MinSpeed_rpm | Fan speed informations - Minimum set speed; Modbus IR331 | Read | ||
| PIV | 3713 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.MotPwr | Fan electrical informations - Motor input power (W); Modbus IR332 | Read | ||
| AV | 3714 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.ElectronicTemp | Fan electrical informations - Electronics temperature (°C); Modbus IR333 | Read | ||
| AV | 3715 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.IGBT_temp | Fan electrical informations - IGBT temperature (°C); Modbus IR334 | Read | ||
| AV | 3716 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.MCU_Temp | Fan electrical informations - MCU temperature; Modbus IR335 | Read | ||
| AV | 3717 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.MotTemp | Fan electrical informations - Motr temperature (°C); Modbus IR336 | Read | ||
| PIV | 3718 | FanAlrm_ZA_SupplyFan.ErrStatus | Fan alarms - Error status defines errors currently detected; Modbus IR337 | Read | ||
| PIV | 3719 | ZiehlAbegg_SupplyFan.FanStatus_ZA_1.WorkingStatus | Fan status (working mode, errors) - Working status defines current ...; Modbus IR338 | Read | ||
| PIV | 3720 | ZiehlAbegg_SupplyFan.FanStatus_ZA_1.WorkStatusCode | Fan status (working mode, errors) - Working status code; Modbus IR339 | Read | ||
| PIV | 3721 | ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_1.CurrSpeed_rpm | Fan speed informations - Actual speed [rpm] of the Zhiel-Abegg fan; Modbus IR340 | Read | ||
| PIV | 3722 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.DC_LinkV | Fan electrical informations - DC link voltage (V); Modbus IR341 | Read | ||
| PIV | 3723 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.LineV | Fan electrical informations - Supply voltage (peak voltage); Modbus IR342 | Read | ||
| PIV | 3724 | ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_1.MaxSpeed_rpm | Fan speed informations - Maximum set speed; Modbus IR343 | Read | ||
| PIV | 3725 | ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_1.MinSpeed_rpm | Fan speed informations - Minimum set speed; Modbus IR344 | Read | ||
| PIV | 3726 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.MotPwr | Fan electrical informations - Motor input power (W); Modbus IR345 | Read | ||
| AV | 3727 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.ElectronicTemp | Fan electrical informations - Electronics temperature (°C); Modbus IR346 | Read | ||
| AV | 3728 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.IGBT_temp | Fan electrical informations - IGBT temperature (°C); Modbus IR347 | Read | ||
| AV | 3729 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.MCU_Temp | Fan electrical informations - MCU temperature; Modbus IR348 | Read | ||
| AV | 3730 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.MotTemp | Fan electrical informations - Motr temperature (°C); Modbus IR349 | Read | ||
| PIV | 3731 | FanAlrm_ZA_RetFan.ErrStatus | Fan alarms - Error status defines errors currently detected; Modbus IR350 | Read | ||
| PIV | 3732 | ZiehlAbegg_ReturnFan.FanStatus_ZA_1.WorkingStatus | Fan status (working mode, errors) - Working status defines current ...; Modbus IR351 | Read | ||
| PIV | 3733 | ZiehlAbegg_ReturnFan.FanStatus_ZA_1.WorkStatusCode | Fan status (working mode, errors) - Working status code; Modbus IR352 | Read | ||
| PIV | 3734 | Humisonic.DevInfo_HUMS.FwRel_H | Device info - Firmware release (high part); Modbus IR353 | Read | ||
| PIV | 3735 | Humisonic.DevInfo_HUMS.FwRel_L | Device info - Firmware release (low part); Modbus IR354 | Read | ||
| IV | 3736 | Humisonic.DevInfo_HUMS.UnitHrsCount | Device info - Working hours of the unit; Modbus IR355 | Read | ||
| IV | 3737 | Humisonic.Humisonic_2_1.FwVars.CtrlState | Lists of variables of the device not managed by default; Modbus IR356 | Read | ||
| PIV | 3738 | Humisonic.AlrmCode_HUMS | Alarm code read from device; Modbus IR357 | Read | ||
| PIV | 3739 | GeneralMng.Day | Actual day; Modbus IR358 | Read | ||
| PIV | 3740 | GeneralMng.Month | Actual month; Modbus IR359 | Read | ||
| PIV | 3741 | GeneralMng.Year | Actual year; Modbus IR360 | Read | ||
| PIV | 3742 | GeneralMng.RTC.Hour | cpCO real time clock; Modbus IR361 | Read | ||
| PIV | 3743 | GeneralMng.RTC.Minute | cpCO real time clock; Modbus IR362 | Read | ||
| PIV | 3744 | GeneralMng.RTC.Second | cpCO real time clock; Modbus IR363 | Read | ||
| PIV | 3745 | GeneralMng.LastOnDay | Saving of last day before blackout; Modbus IR364 | Read | ||
| PIV | 3746 | GeneralMng.LastOnMonth | Saving of last month before blackout; Modbus IR365 | Read | ||
| PIV | 3747 | GeneralMng.LastOnYear | Saving of last year before blackout; Modbus IR366 | Read | ||
| PIV | 3748 | GeneralMng.LastOnHour | Saving of last hour before blackout; Modbus IR367 | Read | ||
| PIV | 3749 | GeneralMng.LastOnMinute | Saving of last minute before blackout; Modbus IR368 | Read | ||
| PIV | 3750 | GeneralMng.LastOnSecond | Saving of last second before blackout; Modbus IR369 | Read | ||
| PIV | 3751 | GeneralMng.OffDays | Number of days since the last blackout; Modbus IR370 | Read | ||
| PIV | 3752 | GeneralMng.OffHours | Number of hours since the last blackout; Modbus IR371 | Read | ||
| PIV | 3753 | GeneralMng.OffMinutes | Numbers of minutes since the last blackout; Modbus IR372 | Read | ||
| PIV | 3754 | GeneralMng.FB_PollT | Last polling loop time (ms); 32-bit (2 Modbus registers); Modbus IR373 | Read | ||
| PIV | 3755 | GeneralMng.FB_PollLoopNo | Number of Polling loops; 32-bit (2 Modbus registers); Modbus IR375 | Read | ||
| PIV | 3756 | MemWritingsNo | Absolute number of writings in retain memory during the entire ...; 32-bit; Modbus IR377 | Read | ||
| PIV | 3757 | GeneralMng.PrgCycleMs | Program speed in ms; Modbus IR379 | Read | ||
| AV | 3758 | GeneralMng.CyclesPerSecond | Program speed in CyclePerSecond; Modbus IR380 | Read | ||
| IV | 3759 | GeneralMng.ErrParamWizard | Error communication for Import/Export blocks; 32-bit (2 Modbus registers); Modbus IR381 | Read | ||
| PIV | 3760 | GeneralMng.DayOfWeek | Day of week; Modbus IR383 | Read | ||
| PIV | 3761 | Scheduler_OnOffUnit.FB_SchedulerMskMng_1.PrgsSchedMsg | Modbus IR384 | Read | ||
| PIV | 3762 | WrkHrs_Unit.WrkHrs | Unit - Working hours; 32-bit (2 Modbus registers); Modbus IR385 | Read | ||
| PIV | 3763 | WrkHrs_Unit.WrkHrs_Left | Unit - Working hours left to the maintenance; 32-bit (2 ...; Modbus IR387 | Read | ||
| PIV | 3764 | WrkHrs_SupplyFan.WrkHrs | Supply Fan - Working hours; 32-bit (2 Modbus registers); Modbus IR389 | Read | ||
| PIV | 3765 | WrkHrs_SupplyFan.WrkHrs_Left | Supply Fan - Working hours left to the maintenance; 32-bit ...; Modbus IR391 | Read | ||
| PIV | 3766 | WrkHrs_ReturnFan.WrkHrs | Return Fan - Working hours; 32-bit (2 Modbus registers); Modbus IR393 | Read | ||
| PIV | 3767 | WrkHrs_ReturnFan.WrkHrs_Left | Return Fan - Working hours left to the maintenance; 32-bit ...; Modbus IR395 | Read | ||
| PIV | 3768 | WrkHrs_DirtyFilt.WrkHrs | Dirty filters - Working hours; 32-bit (2 Modbus registers); Modbus IR397 | Read | ||
| PIV | 3769 | WrkHrs_DirtyFilt.WrkHrs_Left | Dirty filters - Working hours left to the maintenance; 32-bit ...; Modbus IR399 | Read | ||
| PIV | 3770 | WrkHrs_ThrmlWheel.WrkHrs | Thermal wheel - Working hours; 32-bit (2 Modbus registers); Modbus IR401 | Read | ||
| PIV | 3771 | WrkHrs_ThrmlWheel.WrkHrs_Left | Thermal wheel - Working hours left to the maintenance; 32-bit ...; Modbus IR403 | Read | ||
| PIV | 3772 | WrkHrs_Comp.WrkHrs | Compressor - Working hours; 32-bit (2 Modbus registers); Modbus IR405 | Read | ||
| PIV | 3773 | WrkHrs_Comp.WrkHrs_Left | Compressor - Working hours left to the maintenance; 32-bit (2 ...; Modbus IR407 | Read | ||
| PIV | 3774 | WrkHrs_IEC.WrkHrs | IEC - Working hours; 32-bit (2 Modbus registers); Modbus IR409 | Read | ||
| PIV | 3775 | WrkHrs_IEC.WrkHrs_Left | IEC - Working hours left to the maintenance; 32-bit (2 ...; Modbus IR411 | Read | ||
| PIV | 3776 | WrkHrs_Humidifier.WrkHrs | Humidifier - Working hours; 32-bit (2 Modbus registers); Modbus IR413 | Read | ||
| PIV | 3777 | WrkHrs_Humidifier.WrkHrs_Left | Humidifier - Working hours left to the maintenance; 32-bit (2 ...; Modbus IR415 | Read | ||
| PIV | 3778 | WrkHrs_AuxDout.WrkHrs | Auxiliary digital output - Working hours; 32-bit (2 Modbus registers); Modbus IR417 | Read | ||
| PIV | 3779 | WrkHrs_AuxDout.WrkHrs_Left | Auxiliary digital output - Working hours left to the maintenance; ...; 32-bit; Modbus IR419 | Read | ||
| PIV | 3780 | WrkHrs_AuxAout.WrkHrs | Auxiliary analogue output - Working hours; 32-bit (2 Modbus registers); Modbus IR421 | Read | ||
| PIV | 3781 | WrkHrs_AuxAout.WrkHrs_Left | Auxiliary analogue output - Working hours left to the maintenance; ...; 32-bit; Modbus IR423 | Read | ||
| PIV | 3782 | WrkHrs_MainCoilPmp1.WrkHrs | Main coil pump 1 - Working hours; 32-bit (2 Modbus registers); Modbus IR425 | Read | ||
| PIV | 3783 | WrkHrs_MainCoilPmp1.WrkHrs_Left | Main coil pump 1 - Working hours left to the ...; 32-bit; Modbus IR427 | Read | ||
| PIV | 3784 | WrkHrs_MainCoilPmp2.WrkHrs | Main coil pump 2 - Working hours; 32-bit (2 Modbus registers); Modbus IR429 | Read | ||
| PIV | 3785 | WrkHrs_MainCoilPmp2.WrkHrs_Left | Main coil pump 2 - Working hours left to the ...; 32-bit; Modbus IR431 | Read | ||
| PIV | 3786 | WrkHrs_MainCoilAout.WrkHrs | Main coil analog output - Working hours; 32-bit (2 Modbus registers); Modbus IR433 | Read | ||
| PIV | 3787 | WrkHrs_MainCoilAout.WrkHrs_Left | Main coil analog output - Working hours left to the ...; 32-bit; Modbus IR435 | Read | ||
| PIV | 3788 | WrkHrs_MainCoilStep1.WrkHrs | Main coil step 1 - Working hours; 32-bit (2 Modbus registers); Modbus IR437 | Read | ||
| PIV | 3789 | WrkHrs_MainCoilStep1.WrkHrs_Left | Main coil step 1 - Working hours left to the ...; 32-bit; Modbus IR439 | Read | ||
| PIV | 3790 | WrkHrs_MainCoilStep2.WrkHrs | Main coil step 2 - Working hours; 32-bit (2 Modbus registers); Modbus IR441 | Read | ||
| PIV | 3791 | WrkHrs_MainCoilStep2.WrkHrs_Left | Main coil step 2 - Working hours left to the ...; 32-bit; Modbus IR443 | Read | ||
| PIV | 3792 | WrkHrs_MainCoilStep3.WrkHrs | Main coil step 3 - Working hours; 32-bit (2 Modbus registers); Modbus IR445 | Read | ||
| PIV | 3793 | WrkHrs_MainCoilStep3.WrkHrs_Left | Main coil step 3 - Working hours left to the ...; 32-bit; Modbus IR447 | Read | ||
| PIV | 3794 | WrkHrs_MainCoilStep4.WrkHrs | Main coil step 4 - Working hours; 32-bit (2 Modbus registers); Modbus IR449 | Read | ||
| PIV | 3795 | WrkHrs_MainCoilStep4.WrkHrs_Left | Main coil step 4 - Working hours left to the ...; 32-bit; Modbus IR451 | Read | ||
| PIV | 3796 | WrkHrs_PreHeatCoilPmp1.WrkHrs | Pre-heat coil pump 1 - Working hours; 32-bit (2 Modbus registers); Modbus IR453 | Read | ||
| PIV | 3797 | WrkHrs_PreHeatCoilPmp1.WrkHrs_Left | Pre-heat coil pump 1 - Working hours left to the ...; 32-bit; Modbus IR455 | Read | ||
| PIV | 3798 | WrkHrs_PreHeatCoilPmp2.WrkHrs | Pre-heat coil pump 2 - Working hours; 32-bit (2 Modbus registers); Modbus IR457 | Read | ||
| PIV | 3799 | WrkHrs_PreHeatCoilPmp2.WrkHrs_Left | Pre-heat coil pump 2 - Working hours left to the ...; 32-bit; Modbus IR459 | Read | ||
| PIV | 3800 | WrkHrs_PreHeatCoilAout.WrkHrs | Pre-heat coil analog output - Working hours; 32-bit (2 Modbus registers); Modbus IR461 | Read | ||
| PIV | 3801 | WrkHrs_PreHeatCoilAout.WrkHrs_Left | Pre-heat coil analog output - Working hours left to the ...; 32-bit; Modbus IR463 | Read | ||
| PIV | 3802 | WrkHrs_PreHeatCoilStep1.WrkHrs | Pre-heat coil step 1 - Working hours; 32-bit (2 Modbus registers); Modbus IR465 | Read | ||
| PIV | 3803 | WrkHrs_PreHeatCoilStep1.WrkHrs_Left | Pre-heat coil step 1 - Working hours left to the ...; 32-bit; Modbus IR467 | Read | ||
| PIV | 3804 | WrkHrs_PreHeatCoilStep2.WrkHrs | Pre-heat coil step 2 - Working hours; 32-bit (2 Modbus registers); Modbus IR469 | Read | ||
| PIV | 3805 | WrkHrs_PreHeatCoilStep2.WrkHrs_Left | Pre-heat coil step 2 - Working hours left to the ...; 32-bit; Modbus IR471 | Read | ||
| PIV | 3806 | WrkHrs_PreHeatCoilStep3.WrkHrs | Pre-heat coil step 3 - Working hours; 32-bit (2 Modbus registers); Modbus IR473 | Read | ||
| PIV | 3807 | WrkHrs_PreHeatCoilStep3.WrkHrs_Left | Pre-heat coil step 3 - Working hours left to the ...; 32-bit; Modbus IR475 | Read | ||
| PIV | 3808 | WrkHrs_PreHeatCoilStep4.WrkHrs | Pre-heat coil step 4 - Working hours; 32-bit (2 Modbus registers); Modbus IR477 | Read | ||
| PIV | 3809 | WrkHrs_PreHeatCoilStep4.WrkHrs_Left | Pre-heat coil step 4 - Working hours left to the ...; 32-bit; Modbus IR479 | Read | ||
| PIV | 3810 | WrkHrs_ReHeatCoilPmp1.WrkHrs | Re-heat coil pump 1 - Working hours; 32-bit (2 Modbus registers); Modbus IR481 | Read | ||
| PIV | 3811 | WrkHrs_ReHeatCoilPmp1.WrkHrs_Left | Re-heat coil pump 1 - Working hours left to the ...; 32-bit; Modbus IR483 | Read | ||
| PIV | 3812 | WrkHrs_ReHeatCoilPmp2.WrkHrs | Re-heat coil pump 2 - Working hours; 32-bit (2 Modbus registers); Modbus IR485 | Read | ||
| PIV | 3813 | WrkHrs_ReHeatCoilPmp2.WrkHrs_Left | Re-heat coil pump 2 - Working hours left to the ...; 32-bit; Modbus IR487 | Read | ||
| PIV | 3814 | WrkHrs_ReHeatCoilAout.WrkHrs | Re-heat coil analog output - Working hours; 32-bit (2 Modbus registers); Modbus IR489 | Read | ||
| PIV | 3815 | WrkHrs_ReHeatCoilAout.WrkHrs_Left | Re-heat coil analog output - Working hours left to the ...; 32-bit; Modbus IR491 | Read | ||
| PIV | 3816 | WrkHrs_ReHeatCoilStep1.WrkHrs | Re-heat coil step 1 - Working hours; 32-bit (2 Modbus registers); Modbus IR493 | Read | ||
| PIV | 3817 | WrkHrs_ReHeatCoilStep1.WrkHrs_Left | Re-heat coil step 1 - Working hours left to the ...; 32-bit; Modbus IR495 | Read | ||
| PIV | 3818 | WrkHrs_ReHeatCoilStep2.WrkHrs | Re-heat coil step 2 - Working hours; 32-bit (2 Modbus registers); Modbus IR497 | Read | ||
| PIV | 3819 | WrkHrs_ReHeatCoilStep2.WrkHrs_Left | Re-heat coil step 2 - Working hours left to the ...; 32-bit; Modbus IR499 | Read | ||
| PIV | 3820 | WrkHrs_ReHeatCoilStep3.WrkHrs | Re-heat coil step 3 - Working hours; 32-bit (2 Modbus registers); Modbus IR501 | Read | ||
| PIV | 3821 | WrkHrs_ReHeatCoilStep3.WrkHrs_Left | Re-heat coil step 3 - Working hours left to the ...; 32-bit; Modbus IR503 | Read | ||
| PIV | 3822 | WrkHrs_ReHeatCoilStep4.WrkHrs | Re-heat coil step 4 - Working hours; 32-bit (2 Modbus registers); Modbus IR505 | Read | ||
| PIV | 3823 | WrkHrs_ReHeatCoilStep4.WrkHrs_Left | Re-heat coil step 4 - Working hours left to the ...; 32-bit; Modbus IR507 | Read | ||
| IV | 3824 | GeneralMng.ErrParamImpExp | Error communication for Import/Export blocks; 32-bit (2 Modbus registers); Modbus IR509 | Read | ||
| PIV | 3825 | Ebmpapst_ReturnFan.ParamsChgComStatus_EBM_1.StatusNewAddrProc | 0:Check condition;1: Write new addr.; 2: Reboot fan firmware; 3: ...; Modbus IR511 | Read | ||
| PIV | 3826 | Ebmpapst_ReturnFan.ParamsChgComStatus_EBM_1.CommChangeStatus | 0:Idle; 1: Write password; 2:Write parameters; 3:Send adopt parameters; 4:Wait ...; Modbus IR512 | Read | ||
| PIV | 3827 | ZiehlAbegg_ReturnFan.FanStatus_ZA_1.CommChangeStatus | Fan status (working mode, errors) - Status of the COM ...; Modbus IR513 | Read | ||
| PIV | 3828 | Humisonic.HumCylinderWorkHrsLeft | Number of working hours left before check the humidifier cylinder; Modbus IR514 | Read | ||
| PIV | 3829 | Ebmpapst_SupplyFan.ParamsChgComStatus_EBM_1.StatusNewAddrProc | 0:Check condition;1: Write new addr.; 2: Reboot fan firmware; 3: ...; Modbus IR515 | Read | ||
| PIV | 3830 | Ebmpapst_SupplyFan.ParamsChgComStatus_EBM_1.CommChangeStatus | 0:Idle; 1: Write password; 2:Write parameters; 3:Send adopt parameters; 4:Wait ...; Modbus IR516 | Read | ||
| PIV | 3831 | ZiehlAbegg_SupplyFan.FanStatus_ZA_1.CommChangeStatus | Fan status (working mode, errors) - Status of the COM ...; Modbus IR517 | Read | ||
| PIV | 3832 | VDI_Conf[0].CntDwn | Countdown before the next inspection; Modbus IR518 | Read | ||
| PIV | 3833 | VDI_Conf[1].CntDwn | Countdown before the next inspection; Modbus IR519 | Read | ||
| PIV | 3834 | VDI_Conf[2].CntDwn | Countdown before the next inspection; Modbus IR520 | Read | ||
| PIV | 3835 | VDI_Conf[3].CntDwn | Countdown before the next inspection; Modbus IR521 | Read | ||
| PIV | 3836 | VDI_Conf[4].CntDwn | Countdown before the next inspection; Modbus IR522 | Read | ||
| PIV | 3837 | VDI_Conf[5].CntDwn | Countdown before the next inspection; Modbus IR523 | Read | ||
| PIV | 3838 | VDI_Conf[6].CntDwn | Countdown before the next inspection; Modbus IR524 | Read | ||
| PIV | 3839 | VDI_Conf[7].CntDwn | Countdown before the next inspection; Modbus IR525 | Read | ||
| PIV | 3840 | VDI_Conf[8].CntDwn | Countdown before the next inspection; Modbus IR526 | Read | ||
| PIV | 3841 | VDI_Conf[9].CntDwn | Countdown before the next inspection; Modbus IR527 | Read | ||
| PIV | 3842 | VDI_Conf[10].CntDwn | Countdown before the next inspection; Modbus IR528 | Read | ||
| PIV | 3843 | VDI_Conf[11].CntDwn | Countdown before the next inspection; Modbus IR529 | Read | ||
| PIV | 3844 | VDI_Conf[12].CntDwn | Countdown before the next inspection; Modbus IR530 | Read | ||
| PIV | 3845 | VDI_Conf[13].CntDwn | Countdown before the next inspection; Modbus IR531 | Read | ||
| PIV | 3846 | VDI_Conf[14].CntDwn | Countdown before the next inspection; Modbus IR532 | Read | ||
| PIV | 3847 | VDI_Conf[15].CntDwn | Countdown before the next inspection; Modbus IR533 | Read | ||
| PIV | 3848 | VDI_Conf[16].CntDwn | Countdown before the next inspection; Modbus IR534 | Read | ||
| PIV | 3849 | VDI_Conf[17].CntDwn | Countdown before the next inspection; Modbus IR535 | Read | ||
| PIV | 3850 | VDI_Conf[18].CntDwn | Countdown before the next inspection; Modbus IR536 | Read | ||
| PIV | 3851 | VDI_Conf[19].CntDwn | Countdown before the next inspection; Modbus IR537 | Read | ||
| PIV | 3852 | VDI_Conf[20].CntDwn | Countdown before the next inspection; Modbus IR538 | Read | ||
| PIV | 3853 | VDI_Conf[21].CntDwn | Countdown before the next inspection; Modbus IR539 | Read | ||
| PIV | 3854 | VDI_Conf[22].CntDwn | Countdown before the next inspection; Modbus IR540 | Read | ||
| PIV | 3855 | VDI_Conf[23].CntDwn | Countdown before the next inspection; Modbus IR541 | Read | ||
| PIV | 3856 | VDI_Conf[24].CntDwn | Countdown before the next inspection; Modbus IR542 | Read | ||
| PIV | 3857 | VDI_Conf[25].CntDwn | Countdown before the next inspection; Modbus IR543 | Read | ||
| PIV | 3858 | VDI_Conf[26].CntDwn | Countdown before the next inspection; Modbus IR544 | Read | ||
| PIV | 3859 | VDI_Conf[27].CntDwn | Countdown before the next inspection; Modbus IR545 | Read | ||
| PIV | 3860 | VDI_Conf[28].CntDwn | Countdown before the next inspection; Modbus IR546 | Read | ||
| PIV | 3861 | GeneralMng.RTC_BMS.Second | BMS real time clock; Modbus IR547 | Read | ||
| PIV | 3862 | GeneralMng.Zone_Read | Index of the zone read; Modbus IR548 | Read | ||
| IV | 3863 | GeneralMng.SPV_Error | BMS error; Modbus IR549 | Read | ||
| PIV | 3864 | GeneralMng.IP_Byte4 | Automatically generated; Modbus IR550 | Read | ||
| PIV | 3865 | GeneralMng.IP_Byte3 | Automatically generated; Modbus IR551 | Read | ||
| PIV | 3866 | GeneralMng.IP_Byte2 | Automatically generated; Modbus IR552 | Read | ||
| PIV | 3867 | GeneralMng.IP_Byte1 | Automatically generated; Modbus IR553 | Read | ||
| PIV | 3868 | GeneralMng.GW_Byte4 | Automatically generated; Modbus IR554 | Read | ||
| PIV | 3869 | GeneralMng.GW_Byte3 | Automatically generated; Modbus IR555 | Read | ||
| PIV | 3870 | GeneralMng.GW_Byte2 | Automatically generated; Modbus IR556 | Read | ||
| PIV | 3871 | GeneralMng.GW_Byte1 | Automatically generated; Modbus IR557 | Read | ||
| PIV | 3872 | GeneralMng.NMSK_Byte4 | Automatically generated; Modbus IR558 | Read | ||
| PIV | 3873 | GeneralMng.NMSK_Byte3 | Automatically generated; Modbus IR559 | Read | ||
| PIV | 3874 | GeneralMng.NMSK_Byte2 | Automatically generated; Modbus IR560 | Read | ||
| PIV | 3875 | GeneralMng.NMSK_Byte1 | Automatically generated; Modbus IR561 | Read | ||
| PIV | 3876 | GeneralMng.DNS_Byte4 | Automatically generated; Modbus IR562 | Read | ||
| PIV | 3877 | GeneralMng.DNS_Byte3 | Automatically generated; Modbus IR563 | Read | ||
| PIV | 3878 | GeneralMng.DNS_Byte2 | Automatically generated; Modbus IR564 | Read | ||
| PIV | 3879 | GeneralMng.DNS_Byte1 | Automatically generated; Modbus IR565 | Read | ||
| IV | 3880 | Data_EVD_Emb_1.Superparameters.MainRegulation.Val | Superparameters - Main regulation; Modbus IR566 | Read | ||
| AV | 3881 | Data_EVD_Emb_1.Inputs.S1.Val | Probes data - Probe S1 - Value; Modbus IR567 | Read | ||
| AV | 3882 | Data_EVD_Emb_1.Inputs.S2.Val | Probes data - Probe S2 - Value; Modbus IR568 | Read | ||
| AV | 3883 | Data_EVD_Emb_1.Inputs.S3.Val | Probes data - Probe S3 - Value; Modbus IR569 | Read | ||
| AV | 3884 | Data_EVD_Emb_1.Inputs.S4.Val | Probes data - Probe S4 - Value; Modbus IR570 | Read | ||
| PIV | 3885 | BLDC_compressor.IRparam_PWRP1.IR104_DriveStatus | 0: Stop; 1: Run; 2: Alarm; 3: Crankcase heating; 4:DCbus ready); Modbus IR571 | Read | ||
| AV | 3886 | BLDC_compressor.Info_PWRP1.Info_DriveTemp | Inverter Power Plus Info - Drive temperature; Modbus IR572 | Read | ||
| PIV | 3887 | BLDC_compressor.IRparam_PWRP1.IR105_AlrmCode | see doc; Modbus IR573 | Read | ||
| AV | 3888 | BLDC_compressor.Info_PWRP1.Info_FreqSetP | Inverter Power Plus Info - Speed reference [Hz/rps]; Modbus IR574 | Read | ||
| AV | 3889 | BLDC_compressor.Info_PWRP1.Info_RotorSpeed_Hz | Inverter Power Plus Info - Current rotor speed [Hz]; Modbus IR575 | Read | ||
| PIV | 3890 | BLDC_compressor.Info_PWRP1.Info_RotorSpeed_rpm | Inverter Power Plus Info - Current rotorspeed [rpm]; Modbus IR576 | Read | ||
| AV | 3891 | BLDC_compressor.Info_PWRP1.Info_MotA | Inverter Power Plus Info - Current motor current [A]; Modbus IR577 | Read | ||
| PIV | 3892 | BLDC_compressor.Info_PWRP1.Info_MotV | Inverter Power Plus Info - Current motor voltage [V]; Modbus IR578 | Read | ||
| AV | 3893 | BLDC_compressor.Info_PWRP1.Info_MotPwr | Inverter Power Plus Info - Current motor consumption [W]; Modbus IR579 | Read | ||
| PIV | 3894 | BLDC_compressor.IRparam_PWRP1.IR113_DCBusVoltage | DC bus voltage; Modbus IR580 | Read | ||
| PIV | 3895 | BLDC_compressor.IRparam_PWRP1.IR134_DCBusRipple | DC bus ripple; Modbus IR581 | Read | ||
| PIV | 3896 | BLDC_compressor.IRparam_PWRP1.IR124_OperatingSwitchingFreq | PWM switching frequency (0: 4kHz, 1: 6kHz, 2: 8kHz); Modbus IR582 | Read | ||
| AV | 3897 | BLDC_compressor.IRparam_PWRP1.IR125_PreRampOutput_SpeedRef | Pre-ramp output frequency reference; Modbus IR583 | Read | ||
| AV | 3898 | BLDC_compressor.IRparam_PWRP1.IR153_OvldMot_accumulator | Motor Overload Accumulator; Modbus IR584 | Read | ||
| AV | 3899 | BLDC_compressor.IRparam_PWRP1.IR154_OvldDrive_accumulator | Drive Overload Accumulator; Modbus IR585 | Read | ||
| AV | 3900 | BLDC_compressor.Info_PWRP1.Info_PSD_AAa | Inverter Power Plus Info - Device rated current [AA.a]; Modbus IR586 | Read | ||
| PIV | 3901 | BLDC_compressor.Info_PWRP1.Mng_MotSelect_AAa | Inverter Power Plus Info - Rated current of compressor; Modbus IR587 | Read | ||
| AV | 3902 | BLDC_compressor.Info_PWRP1.UI_RatedStartingA | Inverter Power Plus Info - Rated starting current; Modbus IR588 | Read | ||
| AV | 3903 | BLDC_compressor.Info_PWRP1.UI_RatedCrankCaseHeatA | Inverter Power Plus Info - Rated crankcase heating current; Modbus IR589 | Read | ||
| AV | 3904 | BLDC_compressor.Info_PWRP1.UI_RatedInductsatReductA | Inverter Power Plus Info - Inductance saturation reduction (percentage at ...; Modbus IR590 | Read | ||
| PIV | 3905 | BLDC_compressor.Info_PWRP1.Dbg_FBVersion_X | Inverter Power Plus Info - FB version x; Modbus IR591 | Read | ||
| PIV | 3906 | BLDC_compressor.Info_PWRP1.Dbg_FBVersion_Y | Inverter Power Plus Info - FB version y; Modbus IR592 | Read | ||
| PIV | 3907 | BLDC_compressor.Info_PWRP1.Dbg_FBVersion_Z | Inverter Power Plus Info - FB version zzz; Modbus IR593 | Read | ||
| PIV | 3908 | BLDC_compressor.Info_PWRP1.Dbg_FBVersion_Beta | Inverter Power Plus Info - FB version beta; Modbus IR594 | Read | ||
| PIV | 3909 | BLDC_compressor.IRparam_PWRP1.IR141_BootLoaderRelease | Bootloader version; Modbus IR595 | Read | ||
| PIV | 3910 | BLDC_compressor.IRparam_PWRP1.IR142_FirmwareRelease | Firmware version; Modbus IR596 | Read | ||
| PIV | 3911 | BLDC_compressor.IRparam_PWRP1.IR143_FirmwareCRC | Firmware checksum; Modbus IR597 | Read | ||
| PIV | 3912 | BLDC_compressor.IRparam_PWRP1.IR144_MotCtrlRelease | Motor control version; Modbus IR598 | Read | ||
| PIV | 3913 | BLDC_compressor.IRparam_PWRP1.IR149_HardwareIdentification | Hardware identification; Modbus IR599 | Read | ||
| AV | 3914 | Info_BLDC1.Info_CompRequest | BLDC informations - Compressor power request [%]; Modbus IR600 | Read | ||
| AV | 3915 | Info_BLDC1.Info_ReqSpeedToPWRP | BLDC informations - Required speed to PowerPlus [%]; Modbus IR601 | Read | ||
| AV | 3916 | Info_BLDC1.Press_DscgP_Bar | BLDC informations - Discharge pressure relative [bar]; Modbus IR602 | Read | ||
| AV | 3917 | Info_BLDC1.Press_SuctP_Bar | BLDC informations - Suction pressure relative [bar]; Modbus IR603 | Read | ||
| IV | 3918 | Info_BLDC1.Info_EnvZone | BLDC informations - Current envelope zone; Modbus IR604 | Read | ||
| IV | 3919 | Info_BLDC1.Time_CntDwnOutEnv | BLDC informations - Out of envelop timing countdown; Modbus IR605 | Read | ||
| AV | 3920 | Info_BLDC1.Press_DeltaP | BLDC informations - Current delta pressure; Modbus IR606 | Read | ||
| AV | 3921 | Info_BLDC1.Press_RatioP | BLDC informations - Current pressure ratio; Modbus IR607 | Read | ||
| IV | 3922 | Info_BLDC1.Time_CntDwnDeltaPAlrm | BLDC informations - Low pressure difference alarm timing countdown; Modbus IR608 | Read | ||
| AV | 3923 | Info_BLDC1.Info_DscgTemp | BLDC informations - Current discharge temperature; Modbus IR609 | Read | ||
| IV | 3924 | Info_BLDC1.Info_HTZone | BLDC informations - High discharge temperature zone; Modbus IR610 | Read | ||
| AV | 3925 | Info_BLDC1.Info_ActiveDscgHTLim | BLDC informations - Show active value of discharge temp. alarm ...; Modbus IR611 | Read | ||
| AV | 3926 | Info_BLDC1.Info_DscgSH | BLDC informations - Current discharge superheat; Modbus IR612 | Read | ||
| PIV | 3927 | Info_BLDC1.Dbg_FBVersion_X | BLDC informations - Debug: FB version x; Modbus IR613 | Read | ||
| PIV | 3928 | Info_BLDC1.Dbg_FBVersion_Y | BLDC informations - Debug: FB version y; Modbus IR614 | Read | ||
| PIV | 3929 | Info_BLDC1.Dbg_FBVersion_Z | BLDC informations - Debug: FB version z; Modbus IR615 | Read | ||
| PIV | 3930 | Info_BLDC1.Dbg_FBVersion_Beta | BLDC informations - Debug: FB version beta; Modbus IR616 | Read | ||
| PIV | 3931 | GeneralMng.BACnet_ID_Max | BACnet maximum ID (MSTP: 127; IP: 4194303); 32-bit (2 Modbus registers); Modbus IR617 | Read | ||
| AV | 3947 | MainVlv_Perc | Main coil floating valve: Estimating position valve; Modbus IR619 | Read | ||
| AV | 3948 | PreHeatVlv_Perc | PreHeat coil floating valve: Estimating position valve; Modbus IR620 | Read | ||
| AV | 3949 | ReHeatVlv_Perc | ReHeat coil floating valve: Estimating position valve; Modbus IR621 | Read | ||
| AV | 4033 | SupplyTempRegSetP | Temperature compensated setpoint; Modbus IR622 | Read | ||
| AV | 4034 | TempReg | Temperature regulation; Modbus IR623 | Read | ||
| PIV | 3987 | AirQuality_PM10.Uom_W | Air quality: PM 10 - Uom; Modbus IR624 | Read | ||
| AV | 3988 | AirQuality_PM10.Val_Hw_R | Air quality: PM 10 - Value reads from board; Modbus IR625 | Read | ||
| AV | 3989 | AirQuality_PM10.Val_R | Air quality: PM 10; Modbus IR626 | Read | ||
| PIV | 4001 | AirQuality_PM25.Uom_W | Air quality: PM 2.5 - Uom; Modbus IR627 | Read | ||
| AV | 4002 | AirQuality_PM25.Val_Hw_R | Air quality: PM 2.5 - Value reads from board; Modbus IR628 | Read | ||
| AV | 4003 | AirQuality_PM25.Val_R | Air quality: PM 2.5; Modbus IR629 | Read | ||
| PIV | 3964 | WrkHrs_SanificationDevice.WrkHrs | Sanification device - Working hours; 32-bit (2 Modbus registers); Modbus IR630 | Read | ||
| PIV | 3966 | WrkHrs_SanificationDevice.WrkHrs_Left | Sanification device - Working hours left to the maintenance; 32-bit ...; Modbus IR632 | Read | ||
| IV | 4077 | EBM_AlrmCode_SupplyFan1 | EBM alarms code number - Fan Supply 1; Modbus IR634 | Read | ||
| PIV | 4078 | Ebmpapst_SupplyFan.SenVal_EBM_1.AnemometerSpeed | EBM1 Supply - Ebmpapst sensors values - Anemometer speed (only RadiCal); Modbus IR635 | Read | ||
| PIV | 4079 | Ebmpapst_SupplyFan.SenVal_EBM_1.AirFlow | EBM1 Supply - Ebmpapst sensors values - Air flow (only RadiCal); Modbus IR636 | Read | ||
| PIV | 4080 | Ebmpapst_SupplyFan.SenVal_EBM_1.MassFlow | EBM1 Supply - Ebmpapst sensors values - Mass flow (only RadiCal); Modbus IR637 | Read | ||
| IV | 4081 | EBM_AlrmCode_ReturnFan1 | EBM alarms code number - Fan Return 1; Modbus IR638 | Read | ||
| PIV | 4082 | Ebmpapst_ReturnFan.SenVal_EBM_1.AnemometerSpeed | EBM1 Return - Ebmpapst sensors values - Anemometer speed (only RadiCal); Modbus IR639 | Read | ||
| PIV | 4083 | Ebmpapst_ReturnFan.SenVal_EBM_1.AirFlow | EBM1 Return - Ebmpapst sensors values - Air flow (only RadiCal); Modbus IR640 | Read | ||
| PIV | 4084 | Ebmpapst_ReturnFan.SenVal_EBM_1.MassFlow | EBM1 Return - Ebmpapst sensors values - Mass flow (only RadiCal); Modbus IR641 | Read | ||
| PIV | 4085 | Ebmpapst_SupplyFan.InfoSpeed_EBM_2.CurrSpeed | EBM2 Supply - Speed info of the Ebmpapst fan - ...; Modbus IR642 | Read | ||
| PIV | 4086 | Ebmpapst_SupplyFan.ElectrInfo_EBM_2.DC_Link_V | EBM2 Supply - Electrical info - DC link voltage for ...; Modbus IR643 | Read | ||
| PIV | 4087 | Ebmpapst_SupplyFan.ElectrInfo_EBM_2.DC_Link_A | EBM2 Supply - Electrical info - DC link current for ...; Modbus IR644 | Read | ||
| PIV | 4088 | Ebmpapst_SupplyFan.ElectrInfo_EBM_2.CurrPower | EBM2 Supply - Electrical info - Current power in [W] ...; Modbus IR645 | Read | ||
| PIV | 4089 | Ebmpapst_SupplyFan.ElectrInfo_EBM_2.ElectrTemp | EBM2 Supply - Electrical info - Internal circuit temperature for ...; Modbus IR646 | Read | ||
| PIV | 4090 | Ebmpapst_SupplyFan.MotStatus_EBM_2.IR_MotStatus | EBM2 Supply - Motor status defines errors currently detected for ...; Modbus IR647 | Read | ||
| PIV | 4091 | Ebmpapst_SupplyFan.Warn_EBM_2.IR_Warn | EBM2 Supply - Warning bitfield variable for Ebmpast fan - ...; Modbus IR648 | Read | ||
| PIV | 4092 | Ebmpapst_SupplyFan.InfoSpeed_EBM_2.MaxSpeed | EBM2 Supply - Speed info of the Ebmpapst fan - ...; Modbus IR649 | Read | ||
| PIV | 4093 | Ebmpapst_SupplyFan.CntWorkHrsBkp_EBM_2 | EBM2 Supply - Working hour counter for Ebmpapst fan; Modbus IR650 | Read | ||
| PIV | 4094 | Ebmpapst_SupplyFan.SenVal_EBM_2.AnemometerSpeed | EBM2 Supply - Ebmpapst sensors values - Anemometer speed (only RadiCal); Modbus IR651 | Read | ||
| PIV | 4095 | Ebmpapst_SupplyFan.SenVal_EBM_2.AirFlow | EBM2 Supply - Ebmpapst sensors values - Air flow (only RadiCal); Modbus IR652 | Read | ||
| PIV | 4096 | Ebmpapst_SupplyFan.SenVal_EBM_2.MassFlow | EBM2 Supply - Ebmpapst sensors values - Mass flow (only RadiCal); Modbus IR653 | Read | ||
| PIV | 4097 | ComStatus_Supply_EBM_2 | EBM2 Supply - Communication status of supply ebm fan (0:Online; ...; Modbus IR654 | Read | ||
| IV | 4098 | EBM_AlrmCode_SupplyFan2 | EBM alarms code number - Fan Supply 2; Modbus IR655 | Read | ||
| PIV | 4099 | Ebmpapst_SupplyFan.InfoSpeed_EBM_3.CurrSpeed | EBM3 Supply - Speed info of the Ebmpapst fan - ...; Modbus IR656 | Read | ||
| PIV | 4100 | Ebmpapst_SupplyFan.ElectrInfo_EBM_3.DC_Link_V | EBM3 Supply - Electrical info - DC link voltage for ...; Modbus IR657 | Read | ||
| PIV | 4101 | Ebmpapst_SupplyFan.ElectrInfo_EBM_3.DC_Link_A | EBM3 Supply - Electrical info - DC link current for ...; Modbus IR658 | Read | ||
| PIV | 4102 | Ebmpapst_SupplyFan.ElectrInfo_EBM_3.CurrPower | EBM3 Supply - Electrical info - Current power in [W] ...; Modbus IR659 | Read | ||
| PIV | 4103 | Ebmpapst_SupplyFan.ElectrInfo_EBM_3.ElectrTemp | EBM3 Supply - Electrical info - Internal circuit temperature for ...; Modbus IR660 | Read | ||
| PIV | 4104 | Ebmpapst_SupplyFan.MotStatus_EBM_3.IR_MotStatus | EBM3 Supply - Motor status defines errors currently detected for ...; Modbus IR661 | Read | ||
| PIV | 4105 | Ebmpapst_SupplyFan.Warn_EBM_3.IR_Warn | EBM3 Supply - Warning bitfield variable for Ebmpast fan - ...; Modbus IR662 | Read | ||
| PIV | 4106 | Ebmpapst_SupplyFan.InfoSpeed_EBM_3.MaxSpeed | EBM3 Supply - Speed info of the Ebmpapst fan - ...; Modbus IR663 | Read | ||
| PIV | 4107 | Ebmpapst_SupplyFan.CntWorkHrsBkp_EBM_3 | EBM3 Supply - Working hour counter for Ebmpapst fan; Modbus IR664 | Read | ||
| PIV | 4108 | Ebmpapst_SupplyFan.SenVal_EBM_3.AnemometerSpeed | EBM3 Supply - Ebmpapst sensors values - Anemometer speed (only RadiCal); Modbus IR665 | Read | ||
| PIV | 4109 | Ebmpapst_SupplyFan.SenVal_EBM_3.AirFlow | EBM3 Supply - Ebmpapst sensors values - Air flow (only RadiCal); Modbus IR666 | Read | ||
| PIV | 4110 | Ebmpapst_SupplyFan.SenVal_EBM_3.MassFlow | EBM3 Supply - Ebmpapst sensors values - Mass flow (only RadiCal); Modbus IR667 | Read | ||
| PIV | 4111 | ComStatus_Supply_EBM_3 | EBM3 Supply - Communication status of supply ebm fan (0:Online; ...; Modbus IR668 | Read | ||
| IV | 4112 | EBM_AlrmCode_SupplyFan3 | EBM alarms code number - Fan Supply 3; Modbus IR669 | Read | ||
| PIV | 4113 | Ebmpapst_SupplyFan.InfoSpeed_EBM_4.CurrSpeed | EBM4 Supply - Speed info of the Ebmpapst fan - ...; Modbus IR670 | Read | ||
| PIV | 4114 | Ebmpapst_SupplyFan.ElectrInfo_EBM_4.DC_Link_V | EBM4 Supply - Electrical info - DC link voltage for ...; Modbus IR671 | Read | ||
| PIV | 4115 | Ebmpapst_SupplyFan.ElectrInfo_EBM_4.DC_Link_A | EBM4 Supply - Electrical info - DC link current for ...; Modbus IR672 | Read | ||
| PIV | 4116 | Ebmpapst_SupplyFan.ElectrInfo_EBM_4.CurrPower | EBM4 Supply - Electrical info - Current power in [W] ...; Modbus IR673 | Read | ||
| PIV | 4117 | Ebmpapst_SupplyFan.ElectrInfo_EBM_4.ElectrTemp | EBM4 Supply - Electrical info - Internal circuit temperature for ...; Modbus IR674 | Read | ||
| PIV | 4118 | Ebmpapst_SupplyFan.MotStatus_EBM_4.IR_MotStatus | EBM4 Supply - Motor status defines errors currently detected for ...; Modbus IR675 | Read | ||
| PIV | 4119 | Ebmpapst_SupplyFan.Warn_EBM_4.IR_Warn | EBM4 Supply - Warning bitfield variable for Ebmpast fan - ...; Modbus IR676 | Read | ||
| PIV | 4120 | Ebmpapst_SupplyFan.InfoSpeed_EBM_4.MaxSpeed | EBM4 Supply - Speed info of the Ebmpapst fan - ...; Modbus IR677 | Read | ||
| PIV | 4121 | Ebmpapst_SupplyFan.CntWorkHrsBkp_EBM_4 | EBM4 Supply - Working hour counter for Ebmpapst fan; Modbus IR678 | Read | ||
| PIV | 4122 | Ebmpapst_SupplyFan.SenVal_EBM_4.AnemometerSpeed | EBM4 Supply - Ebmpapst sensors values - Anemometer speed (only RadiCal); Modbus IR679 | Read | ||
| PIV | 4123 | Ebmpapst_SupplyFan.SenVal_EBM_4.AirFlow | EBM4 Supply - Ebmpapst sensors values - Air flow (only RadiCal); Modbus IR680 | Read | ||
| PIV | 4124 | Ebmpapst_SupplyFan.SenVal_EBM_4.MassFlow | EBM4 Supply - Ebmpapst sensors values - Mass flow (only RadiCal); Modbus IR681 | Read | ||
| PIV | 4125 | ComStatus_Supply_EBM_4 | EBM4 Supply - Communication status of supply ebm fan (0:Online; ...; Modbus IR682 | Read | ||
| IV | 4126 | EBM_AlrmCode_SupplyFan4 | EBM alarms code number - Fan Supply 4; Modbus IR683 | Read | ||
| PIV | 4127 | Ebmpapst_ReturnFan.InfoSpeed_EBM_2.CurrSpeed | EBM2 Return - Speed info of the Ebmpapst fan - ...; Modbus IR684 | Read | ||
| PIV | 4128 | Ebmpapst_ReturnFan.ElectrInfo_EBM_2.DC_Link_V | EBM2 Return - Electrical info - DC link voltage for ...; Modbus IR685 | Read | ||
| PIV | 4129 | Ebmpapst_ReturnFan.ElectrInfo_EBM_2.DC_Link_A | EBM2 Return - Electrical info - DC link current for ...; Modbus IR686 | Read | ||
| PIV | 4130 | Ebmpapst_ReturnFan.ElectrInfo_EBM_2.CurrPower | EBM2 Return - Electrical info - Current power in [W] ...; Modbus IR687 | Read | ||
| PIV | 4131 | Ebmpapst_ReturnFan.ElectrInfo_EBM_2.ElectrTemp | EBM2 Return - Electrical info - Internal circuit temperature for ...; Modbus IR688 | Read | ||
| PIV | 4132 | Ebmpapst_ReturnFan.MotStatus_EBM_2.IR_MotStatus | EBM2 Return - Motor status defines errors currently detected for ...; Modbus IR689 | Read | ||
| PIV | 4133 | Ebmpapst_ReturnFan.Warn_EBM_2.IR_Warn | EBM2 Return - Warning bitfield variable for Ebmpast fan - ...; Modbus IR690 | Read | ||
| PIV | 4134 | Ebmpapst_ReturnFan.InfoSpeed_EBM_2.MaxSpeed | EBM2 Return - Speed info of the Ebmpapst fan - ...; Modbus IR691 | Read | ||
| PIV | 4135 | Ebmpapst_ReturnFan.CntWorkHrsBkp_EBM_2 | EBM2 Return - Working hour counter for Ebmpapst fan; Modbus IR692 | Read | ||
| PIV | 4136 | Ebmpapst_ReturnFan.SenVal_EBM_2.AnemometerSpeed | EBM2 Return - Ebmpapst sensors values - Anemometer speed (only RadiCal); Modbus IR693 | Read | ||
| PIV | 4137 | Ebmpapst_ReturnFan.SenVal_EBM_2.AirFlow | EBM2 Return - Ebmpapst sensors values - Air flow (only RadiCal); Modbus IR694 | Read | ||
| PIV | 4138 | Ebmpapst_ReturnFan.SenVal_EBM_2.MassFlow | EBM2 Return - Ebmpapst sensors values - Mass flow (only RadiCal); Modbus IR695 | Read | ||
| PIV | 4139 | ComStatus_Return_EBM_2 | EBM2 Return - Communication status of return ebm fan (0:Online; ...; Modbus IR696 | Read | ||
| IV | 4140 | EBM_AlrmCode_ReturnFan2 | EBM alarms code number - Fan Return 2; Modbus IR697 | Read | ||
| PIV | 4141 | Ebmpapst_ReturnFan.InfoSpeed_EBM_3.CurrSpeed | EBM3 Return - Speed info of the Ebmpapst fan - ...; Modbus IR698 | Read | ||
| PIV | 4142 | Ebmpapst_ReturnFan.ElectrInfo_EBM_3.DC_Link_V | EBM3 Return - Electrical info - DC link voltage for ...; Modbus IR699 | Read | ||
| PIV | 4143 | Ebmpapst_ReturnFan.ElectrInfo_EBM_3.DC_Link_A | EBM3 Return - Electrical info - DC link current for ...; Modbus IR700 | Read | ||
| PIV | 4144 | Ebmpapst_ReturnFan.ElectrInfo_EBM_3.CurrPower | EBM3 Return - Electrical info - Current power in [W] ...; Modbus IR701 | Read | ||
| PIV | 4145 | Ebmpapst_ReturnFan.ElectrInfo_EBM_3.ElectrTemp | EBM3 Return - Electrical info - Internal circuit temperature for ...; Modbus IR702 | Read | ||
| PIV | 4146 | Ebmpapst_ReturnFan.MotStatus_EBM_3.IR_MotStatus | EBM3 Return - Motor status defines errors currently detected for ...; Modbus IR703 | Read | ||
| PIV | 4147 | Ebmpapst_ReturnFan.Warn_EBM_3.IR_Warn | EBM3 Return - Warning bitfield variable for Ebmpast fan - ...; Modbus IR704 | Read | ||
| PIV | 4148 | Ebmpapst_ReturnFan.InfoSpeed_EBM_3.MaxSpeed | EBM3 Return - Speed info of the Ebmpapst fan - ...; Modbus IR705 | Read | ||
| PIV | 4149 | Ebmpapst_ReturnFan.CntWorkHrsBkp_EBM_3 | EBM3 Return - Working hour counter for Ebmpapst fan; Modbus IR706 | Read | ||
| PIV | 4150 | Ebmpapst_ReturnFan.SenVal_EBM_3.AnemometerSpeed | EBM3 Return - Ebmpapst sensors values - Anemometer speed (only RadiCal); Modbus IR707 | Read | ||
| PIV | 4151 | Ebmpapst_ReturnFan.SenVal_EBM_3.AirFlow | EBM3 Return - Ebmpapst sensors values - Air flow (only RadiCal); Modbus IR708 | Read | ||
| PIV | 4152 | Ebmpapst_ReturnFan.SenVal_EBM_3.MassFlow | EBM3 Return - Ebmpapst sensors values - Mass flow (only RadiCal); Modbus IR709 | Read | ||
| PIV | 4153 | ComStatus_Return_EBM_3 | EBM3 Return - Communication status of return ebm fan (0:Online; ...; Modbus IR710 | Read | ||
| IV | 4154 | EBM_AlrmCode_ReturnFan3 | EBM alarms code number - Fan Return 3; Modbus IR711 | Read | ||
| PIV | 4155 | Ebmpapst_ReturnFan.InfoSpeed_EBM_4.CurrSpeed | EBM4 Return - Speed info of the Ebmpapst fan - ...; Modbus IR712 | Read | ||
| PIV | 4156 | Ebmpapst_ReturnFan.ElectrInfo_EBM_4.DC_Link_V | EBM4 Return - Electrical info - DC link voltage for ...; Modbus IR713 | Read | ||
| PIV | 4157 | Ebmpapst_ReturnFan.ElectrInfo_EBM_4.DC_Link_A | EBM4 Return - Electrical info - DC link current for ...; Modbus IR714 | Read | ||
| PIV | 4158 | Ebmpapst_ReturnFan.ElectrInfo_EBM_4.CurrPower | EBM4 Return - Electrical info - Current power in [W] ...; Modbus IR715 | Read | ||
| PIV | 4159 | Ebmpapst_ReturnFan.ElectrInfo_EBM_4.ElectrTemp | EBM4 Return - Electrical info - Internal circuit temperature for ...; Modbus IR716 | Read | ||
| PIV | 4160 | Ebmpapst_ReturnFan.MotStatus_EBM_4.IR_MotStatus | EBM4 Return - Motor status defines errors currently detected for ...; Modbus IR717 | Read | ||
| PIV | 4161 | Ebmpapst_ReturnFan.Warn_EBM_4.IR_Warn | EBM4 Return - Warning bitfield variable for Ebmpast fan - ...; Modbus IR718 | Read | ||
| PIV | 4162 | Ebmpapst_ReturnFan.InfoSpeed_EBM_4.MaxSpeed | EBM4 Return - Speed info of the Ebmpapst fan - ...; Modbus IR719 | Read | ||
| PIV | 4163 | Ebmpapst_ReturnFan.CntWorkHrsBkp_EBM_4 | EBM4 Return - Working hour counter for Ebmpapst fan; Modbus IR720 | Read | ||
| PIV | 4164 | Ebmpapst_ReturnFan.SenVal_EBM_4.AnemometerSpeed | EBM4 Return - Ebmpapst sensors values - Anemometer speed (only RadiCal); Modbus IR721 | Read | ||
| PIV | 4165 | Ebmpapst_ReturnFan.SenVal_EBM_4.AirFlow | EBM4 Return - Ebmpapst sensors values - Air flow (only RadiCal); Modbus IR722 | Read | ||
| PIV | 4166 | Ebmpapst_ReturnFan.SenVal_EBM_4.MassFlow | EBM4 Return - Ebmpapst sensors values - Mass flow (only RadiCal); Modbus IR723 | Read | ||
| PIV | 4167 | ComStatus_Return_EBM_4 | EBM4 Return - Communication status of return ebm fan (0:Online; ...; Modbus IR724 | Read | ||
| IV | 4168 | EBM_AlrmCode_ReturnFan4 | EBM alarms code number - Fan Return 4; Modbus IR725 | Read | ||
| IV | 4169 | ZA_AlrmCode_SupplyFan1 | ZA alarms code number - Fan Supply 1; Modbus IR726 | Read | ||
| IV | 4170 | ZA_AlrmCode_ReturnFan1 | ZA alarms code number - Fan Return 1; Modbus IR727 | Read | ||
| PIV | 4171 | ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_2.CurrSpeed_rpm | ZA2 Supply - Fan speed informations - Actual speed [rpm] ...; Modbus IR728 | Read | ||
| PIV | 4172 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.DC_LinkV | ZA2 Supply - Fan electrical informations - DC link voltage (V); Modbus IR729 | Read | ||
| PIV | 4173 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.LineV | ZA2 Supply - Fan electrical informations - Supply voltage (peak voltage); Modbus IR730 | Read | ||
| PIV | 4174 | ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_2.MaxSpeed_rpm | ZA2 Supply - Fan speed informations - Maximum set speed; Modbus IR731 | Read | ||
| PIV | 4175 | ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_2.MinSpeed_rpm | ZA2 Supply - Fan speed informations - Minimum set speed; Modbus IR732 | Read | ||
| PIV | 4176 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.MotPwr | ZA2 Supply - Fan electrical informations - Motor input power (W); Modbus IR733 | Read | ||
| IV | 4177 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.ElectronicTemp | ZA2 Supply - Fan electrical informations - Electronics temperature (°C); Modbus IR734 | Read | ||
| IV | 4178 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.IGBT_temp | ZA2 Supply - Fan electrical informations - IGBT temperature (°C); Modbus IR735 | Read | ||
| IV | 4179 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.MCU_Temp | ZA2 Supply - Fan electrical informations - MCU temperature; Modbus IR736 | Read | ||
| IV | 4180 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.MotTemp | ZA2 Supply - Fan electrical informations - Motr temperature (°C); Modbus IR737 | Read | ||
| PIV | 4181 | FanAlrm_ZA_SupplyFan_2.ErrStatus | ZA2 supply - Fan alarms - Error status defines errors ...; Modbus IR738 | Read | ||
| PIV | 4182 | ZiehlAbegg_SupplyFan.FanStatus_ZA_2.WorkingStatus | ZA2 Supply - Fan status - Working status defines current ...; Modbus IR739 | Read | ||
| PIV | 4183 | ZiehlAbegg_SupplyFan.FanStatus_ZA_2.WorkStatusCode | ZA2 Supply - Fan status - Working status code; Modbus IR740 | Read | ||
| IV | 4184 | ZA_AlrmCode_SupplyFan2 | ZA alarms code number - Fan Supply 2; Modbus IR741 | Read | ||
| PIV | 4185 | ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_3.CurrSpeed_rpm | ZA3 Supply - Fan speed informations - Actual speed [rpm] ...; Modbus IR742 | Read | ||
| PIV | 4186 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.DC_LinkV | ZA3 Supply - Fan electrical informations - DC link voltage (V); Modbus IR743 | Read | ||
| PIV | 4187 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.LineV | ZA3 Supply - Fan electrical informations - Supply voltage (peak voltage); Modbus IR744 | Read | ||
| PIV | 4188 | ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_3.MaxSpeed_rpm | ZA3 Supply - Fan speed informations - Maximum set speed; Modbus IR745 | Read | ||
| PIV | 4189 | ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_3.MinSpeed_rpm | ZA3 Supply - Fan speed informations - Minimum set speed; Modbus IR746 | Read | ||
| PIV | 4190 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.MotPwr | ZA3 Supply - Fan electrical informations - Motor input power (W); Modbus IR747 | Read | ||
| IV | 4191 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.ElectronicTemp | ZA3 Supply - Fan electrical informations - Electronics temperature (°C); Modbus IR748 | Read | ||
| IV | 4192 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.IGBT_temp | ZA3 Supply - Fan electrical informations - IGBT temperature (°C); Modbus IR749 | Read | ||
| IV | 4193 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.MCU_Temp | ZA3 Supply - Fan electrical informations - MCU temperature; Modbus IR750 | Read | ||
| IV | 4194 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.MotTemp | ZA3 Supply - Fan electrical informations - Motr temperature (°C); Modbus IR751 | Read | ||
| PIV | 4195 | FanAlrm_ZA_SupplyFan_3.ErrStatus | ZA3 supply - Fan alarms - Error status defines errors ...; Modbus IR752 | Read | ||
| PIV | 4196 | ZiehlAbegg_SupplyFan.FanStatus_ZA_3.WorkingStatus | ZA3 Supply - Fan status - Working status defines current ...; Modbus IR753 | Read | ||
| PIV | 4197 | ZiehlAbegg_SupplyFan.FanStatus_ZA_3.WorkStatusCode | ZA3 Supply - Fan status - Working status code; Modbus IR754 | Read | ||
| IV | 4198 | ZA_AlrmCode_SupplyFan3 | ZA alarms code number - Fan Supply 3; Modbus IR755 | Read | ||
| PIV | 4199 | ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_4.CurrSpeed_rpm | ZA4 Supply - Fan speed informations - Actual speed [rpm] ...; Modbus IR756 | Read | ||
| PIV | 4200 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.DC_LinkV | ZA4 Supply - Fan electrical informations - DC link voltage (V); Modbus IR757 | Read | ||
| PIV | 4201 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.LineV | ZA4 Supply - Fan electrical informations - Supply voltage (peak voltage); Modbus IR758 | Read | ||
| PIV | 4202 | ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_4.MaxSpeed_rpm | ZA4 Supply - Fan speed informations - Maximum set speed; Modbus IR759 | Read | ||
| PIV | 4203 | ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_4.MinSpeed_rpm | ZA4 Supply - Fan speed informations - Minimum set speed; Modbus IR760 | Read | ||
| PIV | 4204 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.MotPwr | ZA4 Supply - Fan electrical informations - Motor input power (W); Modbus IR761 | Read | ||
| IV | 4205 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.ElectronicTemp | ZA4 Supply - Fan electrical informations - Electronics temperature (°C); Modbus IR762 | Read | ||
| IV | 4206 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.IGBT_temp | ZA4 Supply - Fan electrical informations - IGBT temperature (°C); Modbus IR763 | Read | ||
| IV | 4207 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.MCU_Temp | ZA4 Supply - Fan electrical informations - MCU temperature; Modbus IR764 | Read | ||
| IV | 4208 | ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.MotTemp | ZA4 Supply - Fan electrical informations - Motr temperature (°C); Modbus IR765 | Read | ||
| PIV | 4209 | FanAlrm_ZA_SupplyFan_4.ErrStatus | ZA4 supply - Fan alarms - Error status defines errors ...; Modbus IR766 | Read | ||
| PIV | 4210 | ZiehlAbegg_SupplyFan.FanStatus_ZA_4.WorkingStatus | ZA4 Supply - Fan status - Working status defines current ...; Modbus IR767 | Read | ||
| PIV | 4211 | ZiehlAbegg_SupplyFan.FanStatus_ZA_4.WorkStatusCode | ZA4 Supply - Fan status - Working status code; Modbus IR768 | Read | ||
| IV | 4212 | ZA_AlrmCode_SupplyFan4 | ZA alarms code number - Fan Supply 4; Modbus IR769 | Read | ||
| PIV | 4213 | ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_2.CurrSpeed_rpm | ZA2 Return - Fan speed informations - Actual speed [rpm] ...; Modbus IR770 | Read | ||
| PIV | 4214 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.DC_LinkV | ZA2 Return - Fan electrical informations - DC link voltage (V); Modbus IR771 | Read | ||
| PIV | 4215 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.LineV | ZA2 Return - Fan electrical informations - Supply voltage (peak voltage); Modbus IR772 | Read | ||
| PIV | 4216 | ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_2.MaxSpeed_rpm | ZA2 Return - Fan speed informations - Maximum set speed; Modbus IR773 | Read | ||
| PIV | 4217 | ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_2.MinSpeed_rpm | ZA2 Return - Fan speed informations - Minimum set speed; Modbus IR774 | Read | ||
| PIV | 4218 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.MotPwr | ZA2 Return - Fan electrical informations - Motor input power (W); Modbus IR775 | Read | ||
| IV | 4219 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.ElectronicTemp | ZA2 Return - Fan electrical informations - Electronics temperature (°C); Modbus IR776 | Read | ||
| IV | 4220 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.IGBT_temp | ZA2 Return - Fan electrical informations - IGBT temperature (°C); Modbus IR777 | Read | ||
| IV | 4221 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.MCU_Temp | ZA2 Return - Fan electrical informations - MCU temperature; Modbus IR778 | Read | ||
| IV | 4222 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.MotTemp | ZA2 Return - Fan electrical informations - Motr temperature (°C); Modbus IR779 | Read | ||
| PIV | 4223 | FanAlrm_ZA_RetFan_2.ErrStatus | ZA2 return - Fan alarms - Error status defines errors ...; Modbus IR780 | Read | ||
| PIV | 4224 | ZiehlAbegg_ReturnFan.FanStatus_ZA_2.WorkingStatus | ZA2 Return - Fan status - Working status defines current ...; Modbus IR781 | Read | ||
| PIV | 4225 | ZiehlAbegg_ReturnFan.FanStatus_ZA_2.WorkStatusCode | ZA2 Return - Fan status - Working status code; Modbus IR782 | Read | ||
| IV | 4226 | ZA_AlrmCode_ReturnFan2 | ZA alarms code number - Fan Return 2; Modbus IR783 | Read | ||
| PIV | 4227 | ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_3.CurrSpeed_rpm | ZA3 Return - Fan speed informations - Actual speed [rpm] ...; Modbus IR784 | Read | ||
| PIV | 4228 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.DC_LinkV | ZA3 Return - Fan electrical informations - DC link voltage (V); Modbus IR785 | Read | ||
| PIV | 4229 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.LineV | ZA3 Return - Fan electrical informations - Supply voltage (peak voltage); Modbus IR786 | Read | ||
| PIV | 4230 | ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_3.MaxSpeed_rpm | ZA3 Return - Fan speed informations - Maximum set speed; Modbus IR787 | Read | ||
| PIV | 4231 | ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_3.MinSpeed_rpm | ZA3 Return - Fan speed informations - Minimum set speed; Modbus IR788 | Read | ||
| PIV | 4232 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.MotPwr | ZA3 Return - Fan electrical informations - Motor input power (W); Modbus IR789 | Read | ||
| IV | 4233 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.ElectronicTemp | ZA3 Return - Fan electrical informations - Electronics temperature (°C); Modbus IR790 | Read | ||
| IV | 4234 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.IGBT_temp | ZA3 Return - Fan electrical informations - IGBT temperature (°C); Modbus IR791 | Read | ||
| IV | 4235 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.MCU_Temp | ZA3 Return - Fan electrical informations - MCU temperature; Modbus IR792 | Read | ||
| IV | 4236 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.MotTemp | ZA3 Return - Fan electrical informations - Motr temperature (°C); Modbus IR793 | Read | ||
| PIV | 4237 | FanAlrm_ZA_RetFan_3.ErrStatus | ZA3 return - Fan alarms - Error status defines errors ...; Modbus IR794 | Read | ||
| PIV | 4238 | ZiehlAbegg_ReturnFan.FanStatus_ZA_3.WorkingStatus | ZA3 Return - Fan status - Working status defines current ...; Modbus IR795 | Read | ||
| PIV | 4239 | ZiehlAbegg_ReturnFan.FanStatus_ZA_3.WorkStatusCode | ZA3 Return - Fan status - Working status code; Modbus IR796 | Read | ||
| IV | 4240 | ZA_AlrmCode_ReturnFan3 | ZA alarms code number - Fan Return 3; Modbus IR797 | Read | ||
| PIV | 4241 | ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_4.CurrSpeed_rpm | ZA4 Return - Fan speed informations - Actual speed [rpm] ...; Modbus IR798 | Read | ||
| PIV | 4242 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.DC_LinkV | ZA4 Return - Fan electrical informations - DC link voltage (V); Modbus IR799 | Read | ||
| PIV | 4243 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.LineV | ZA4 Return - Fan electrical informations - Supply voltage (peak voltage); Modbus IR800 | Read | ||
| PIV | 4244 | ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_4.MaxSpeed_rpm | ZA4 Return - Fan speed informations - Maximum set speed; Modbus IR801 | Read | ||
| PIV | 4245 | ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_4.MinSpeed_rpm | ZA4 Return - Fan speed informations - Minimum set speed; Modbus IR802 | Read | ||
| PIV | 4246 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.MotPwr | ZA4 Return - Fan electrical informations - Motor input power (W); Modbus IR803 | Read | ||
| IV | 4247 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.ElectronicTemp | ZA4 Return - Fan electrical informations - Electronics temperature (°C); Modbus IR804 | Read | ||
| IV | 4248 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.IGBT_temp | ZA4 Return - Fan electrical informations - IGBT temperature (°C); Modbus IR805 | Read | ||
| IV | 4249 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.MCU_Temp | ZA4 Return - Fan electrical informations - MCU temperature; Modbus IR806 | Read | ||
| IV | 4250 | ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.MotTemp | ZA4 Return - Fan electrical informations - Motr temperature (°C); Modbus IR807 | Read | ||
| PIV | 4251 | FanAlrm_ZA_RetFan_4.ErrStatus | ZA4 return - Fan alarms - Error status defines errors ...; Modbus IR808 | Read | ||
| PIV | 4252 | ZiehlAbegg_ReturnFan.FanStatus_ZA_4.WorkingStatus | ZA4 Return - Fan status - Working status defines current ...; Modbus IR809 | Read | ||
| PIV | 4253 | ZiehlAbegg_ReturnFan.FanStatus_ZA_4.WorkStatusCode | ZA4 Return - Fan status - Working status code; Modbus IR810 | Read | ||
| IV | 4254 | ZA_AlrmCode_ReturnFan4 | ZA alarms code number - Fan Return 4; Modbus IR811 | Read | ||
| PIV | 4267 | WrkHrs_SupplyFan_2.WrkHrs | Supply Fan - Working hours; 32-bit (2 Modbus registers); Modbus IR812 | Read | ||
| PIV | 4268 | WrkHrs_SupplyFan_2.WrkHrs_Left | Supply Fan - Working hours left to the maintenance; 32-bit ...; Modbus IR814 | Read | ||
| PIV | 4269 | WrkHrs_SupplyFan_3.WrkHrs | Supply Fan - Working hours; 32-bit (2 Modbus registers); Modbus IR816 | Read | ||
| PIV | 4270 | WrkHrs_SupplyFan_3.WrkHrs_Left | Supply Fan - Working hours left to the maintenance; 32-bit ...; Modbus IR818 | Read | ||
| PIV | 4271 | WrkHrs_SupplyFan_4.WrkHrs | Supply Fan - Working hours; 32-bit (2 Modbus registers); Modbus IR820 | Read | ||
| PIV | 4272 | WrkHrs_SupplyFan_4.WrkHrs_Left | Supply Fan - Working hours left to the maintenance; 32-bit ...; Modbus IR822 | Read | ||
| PIV | 4273 | WrkHrs_ReturnFan_2.WrkHrs | Return Fan - Working hours; 32-bit (2 Modbus registers); Modbus IR824 | Read | ||
| PIV | 4274 | WrkHrs_ReturnFan_2.WrkHrs_Left | Return Fan - Working hours left to the maintenance; 32-bit ...; Modbus IR826 | Read | ||
| PIV | 4275 | WrkHrs_ReturnFan_3.WrkHrs | Return Fan - Working hours; 32-bit (2 Modbus registers); Modbus IR828 | Read | ||
| PIV | 4276 | WrkHrs_ReturnFan_3.WrkHrs_Left | Return Fan - Working hours left to the maintenance; 32-bit ...; Modbus IR830 | Read | ||
| PIV | 4277 | WrkHrs_ReturnFan_4.WrkHrs | Return Fan - Working hours; 32-bit (2 Modbus registers); Modbus IR832 | Read | ||
| PIV | 4278 | WrkHrs_ReturnFan_4.WrkHrs_Left | Return Fan - Working hours left to the maintenance; 32-bit ...; Modbus IR834 | Read | ||
| AV | 4279 | Fans.Value_AVG | SFP - Value to calculate the average; Modbus IR836 | Read | ||
| AV | 4280 | Fans.AvgTimeData_AVG.Daily | SFP - Calculated average time data - Daily average; Modbus IR837 | Read | ||
| AV | 4281 | Fans.AvgTimeData_AVG.Monthly | SFP - Calculated average time data - Monthly average; Modbus IR838 | Read | ||
| AV | 4282 | HeatExchanger.Value_AVG | Heat Rec. Eff. - Value to calculate the average; Modbus IR839 | Read | ||
| AV | 4283 | HeatExchanger.AvgTimeData_AVG.Daily | Heat Rec. Eff. - Calculated average time data - Daily average; Modbus IR840 | Read | ||
| AV | 4284 | HeatExchanger.AvgTimeData_AVG.Monthly | Heat Rec. Eff. - Calculated average time data - Monthly average; Modbus IR841 | Read | ||
| IV | 4346 | HumiSteamMng.CntCylHr_UEY | HumiSteam - Cylinder hours counter value; Modbus IR842 | Read | ||
| IV | 4347 | HumiSteamMng.HumState_UEY | HumiSteam - Humidifier satus; Modbus IR843 | Read | ||
| IV | 4348 | HumiSteamMng.Curr_UEY | HumiSteam - Immersed electrode current; 32-bit (2 Modbus registers); Modbus IR844 | Read | ||
| IV | 4349 | HumiSteamMng.Conductivity_UEY | HumiSteam - Conductivity of the water in the cylinder; Modbus IR846 | Read | ||
| IV | 4350 | HumiSteamMng.SteamInstantFlowRate_UEY | HumiSteam - Steam istant flow rate value returned by the ...; 32-bit; Modbus IR847 | Read | ||
| IV | 4351 | UEY_AlrmCode | HumiSteam - UEY alarms code number; Modbus IR849 | Read | ||
| AV | 4370 | Fans_regulation.SupplyFan_FanTempReg_SetPOffs | Supply fan - Temperature regulation setpoint offset; Modbus IR850 | Read | ||
| AV | 4371 | Fans_regulation.SupplyFan_FC_FH_SetPOffs | Supply fan - FC/FH setpoint offset; Modbus IR851 | Read | ||
| AV | 4372 | Fans_regulation.RetFan_FanTempReg_SetPOffs | Return fan - Temperature regulation setpoint offset; Modbus IR852 | Read | ||
| AV | 4373 | Fans_regulation.RetFan_FC_FH_SetPOffs | Return fan - FC/FH setpoint offset; Modbus IR853 | Read | ||
| PIV | 4388 | GenericAin1.Uom_W | Generic Ain1 - Uom; Modbus IR854 | Read | ||
| AV | 4389 | GenericAin1.Val_Hw_R | Generic Ain1 - Value reads from board; Modbus IR855 | Read | ||
| AV | 4390 | GenericAin1.Val_R | Generic Ain1; Modbus IR856 | Read | ||
| PIV | 4402 | GenericAin2.Uom_W | Generic Ain2 - Uom; Modbus IR857 | Read | ||
| AV | 4403 | GenericAin2.Val_Hw_R | Generic Ain2 - Value reads from board; Modbus IR858 | Read | ||
| AV | 4404 | GenericAin2.Val_R | Generic Ain2; Modbus IR859 | Read | ||
| PIV | 4416 | GenericAin3.Uom_W | Generic Ain3 - Uom; Modbus IR860 | Read | ||
| AV | 4417 | GenericAin3.Val_Hw_R | Generic Ain3 - Value reads from board; Modbus IR861 | Read | ||
| AV | 4418 | GenericAin3.Val_R | Generic Ain3; Modbus IR862 | Read | ||
| PIV | 4430 | GenericAin4.Uom_W | Generic Ain4 - Uom; Modbus IR863 | Read | ||
| AV | 4431 | GenericAin4.Val_Hw_R | Generic Ain4 - Value reads from board; Modbus IR864 | Read | ||
| AV | 4432 | GenericAin4.Val_R | Generic Ain4; Modbus IR865 | Read | ||
| PIV | 4444 | GenericAin5.Uom_W | Generic Ain5 - Uom; Modbus IR866 | Read | ||
| AV | 4445 | GenericAin5.Val_Hw_R | Generic Ain5 - Value reads from board; Modbus IR867 | Read | ||
| AV | 4446 | GenericAin5.Val_R | Generic Ain5; Modbus IR868 | Read | ||
| AV | 4562 | OA_CoilRegReq | Outdoor air pre-treatment request from PID Seq; Modbus IR869 | Read | ||
| AV | 4563 | OA_CoilReq | Outdoor air pre-treatment request; Modbus IR870 | Read | ||
| PIV | 4564 | WrkHrs_OA_CoilAout.WrkHrs | Outdoor air pre-treatment coil analog output - Working hours; 32-bit ...; Modbus IR871 | Read | ||
| PIV | 4565 | WrkHrs_OA_CoilAout.WrkHrs_Left | Outdoor air pre-treatment coil analog output - Working hours left ...; 32-bit; Modbus IR873 | Read | ||
| PIV | 4566 | WrkHrs_OA_CoilStep1.WrkHrs | Outdoor air pre-treatment coil step 1 - Working hours; 32-bit ...; Modbus IR875 | Read | ||
| PIV | 4567 | WrkHrs_OA_CoilStep1.WrkHrs_Left | Outdoor air pre-treatment coil step 1 - Working hours left ...; 32-bit; Modbus IR877 | Read | ||
| PIV | 4568 | WrkHrs_OA_CoilStep2.WrkHrs | Outdoor air pre-treatment coil step 2 - Working hours; 32-bit ...; Modbus IR879 | Read | ||
| PIV | 4569 | WrkHrs_OA_CoilStep2.WrkHrs_Left | Outdoor air pre-treatment coil step 2 - Working hours left ...; 32-bit; Modbus IR881 | Read | ||
| PIV | 4570 | WrkHrs_OA_CoilStep3.WrkHrs | Outdoor air pre-treatment coil step 3 - Working hours; 32-bit ...; Modbus IR883 | Read | ||
| PIV | 4571 | WrkHrs_OA_CoilStep3.WrkHrs_Left | Outdoor air pre-treatment coil step 3 - Working hours left ...; 32-bit; Modbus IR885 | Read | ||
| PIV | 4572 | WrkHrs_OA_CoilStep4.WrkHrs | Outdoor air pre-treatment coil step 4 - Working hours; 32-bit ...; Modbus IR887 | Read | ||
| PIV | 4573 | WrkHrs_OA_CoilStep4.WrkHrs_Left | Outdoor air pre-treatment coil step 4 - Working hours left ...; 32-bit; Modbus IR889 | Read | ||
| PIV | 4574 | OA_Vlv_Perc | Outdoor air pre-treatment floating valve: Estimating position valve; Modbus IR891 | Read | ||
| PIV | 3596 | AirFlwVal | Supply air flow value; 32-bit (2 Modbus registers); Modbus IR892 | Read | ||
| PIV | 3597 | RetAirFlwVal | Return air flow value; 32-bit (2 Modbus registers); Modbus IR894 | Read |
No points match these filters.
Object ID lookup: CAREL k.air air handling unit controller point IDs by name
BV1AlarmsMng.AlrmResByBmsBV2Scheduler_OnOffUnit.BMS_OnOffBV4SummerWinter_BMSBV5Scheduler_OnOffUnit.BMS_UnitProfile_EnBV6Scheduler_Cfg.Prg[0].Event[0].EnabledBV7Scheduler_Cfg.Prg[0].Event[1].EnabledBV8Scheduler_Cfg.Prg[0].Event[2].EnabledBV9Scheduler_Cfg.Prg[0].Event[3].EnabledBV10Scheduler_Cfg.Prg[0].Event[4].EnabledBV11Scheduler_Cfg.Prg[0].Event[5].EnabledBV12Scheduler_Cfg.Prg[0].Event[6].EnabledBV13Scheduler_Cfg.Prg[0].Event[7].EnabledBV14Scheduler_Cfg.Prg[0].Event[8].EnabledBV15Scheduler_Cfg.Prg[0].Event[9].EnabledBV16Scheduler_Cfg.Prg[1].Event[0].EnabledBV17Scheduler_Cfg.Prg[1].Event[1].EnabledBV18Scheduler_Cfg.Prg[1].Event[2].EnabledBV19Scheduler_Cfg.Prg[1].Event[3].EnabledBV20Scheduler_Cfg.Prg[1].Event[4].EnabledBV21Scheduler_Cfg.Prg[1].Event[5].EnabledBV22Scheduler_Cfg.Prg[1].Event[6].EnabledBV23Scheduler_Cfg.Prg[1].Event[7].EnabledBV24Scheduler_Cfg.Prg[1].Event[8].EnabledBV25Scheduler_Cfg.Prg[1].Event[9].EnabledBV26Scheduler_Cfg.Prg[2].Event[0].EnabledBV27Scheduler_Cfg.Prg[2].Event[1].EnabledBV28Scheduler_Cfg.Prg[2].Event[2].EnabledBV29Scheduler_Cfg.Prg[2].Event[3].EnabledBV30Scheduler_Cfg.Prg[2].Event[4].EnabledBV31Scheduler_Cfg.Prg[2].Event[5].EnabledBV32Scheduler_Cfg.Prg[2].Event[6].EnabledBV33Scheduler_Cfg.Prg[2].Event[7].EnabledBV34Scheduler_Cfg.Prg[2].Event[8].EnabledBV35Scheduler_Cfg.Prg[2].Event[9].EnabledBV36Scheduler_Cfg.Prg[3].Event[0].EnabledBV37Scheduler_Cfg.Prg[3].Event[1].EnabledBV38Scheduler_Cfg.Prg[3].Event[2].EnabledBV39Scheduler_Cfg.Prg[3].Event[3].EnabledBV40Scheduler_Cfg.Prg[3].Event[4].EnabledBV41Scheduler_Cfg.Prg[3].Event[5].EnabledBV42Scheduler_Cfg.Prg[3].Event[6].EnabledBV43Scheduler_Cfg.Prg[3].Event[7].EnabledBV44Scheduler_Cfg.Prg[3].Event[8].EnabledBV45Scheduler_Cfg.Prg[3].Event[9].EnabledBV46Scheduler_Cfg.SDays[0].EnabledBV47Scheduler_Cfg.SDays[1].EnabledBV48Scheduler_Cfg.SDays[2].EnabledBV49Scheduler_Cfg.SDays[3].EnabledBV50Scheduler_Cfg.SDays[4].EnabledBV51Scheduler_Cfg.SDays[5].EnabledBV52Scheduler_Cfg.SDays[6].EnabledBV53Scheduler_Cfg.SDays[7].EnabledBV54Scheduler_Cfg.SDays[8].EnabledBV55Scheduler_Cfg.SDays[9].EnabledBV56Scheduler_Cfg.SDays[10].EnabledBV57Scheduler_Cfg.SDays[11].EnabledBV58Scheduler_Cfg.SDays[12].EnabledBV59Scheduler_Cfg.SDays[13].EnabledBV60Scheduler_Cfg.SDays[14].EnabledBV61Scheduler_Cfg.Vac[0].EnabledBV62Scheduler_Cfg.Vac[1].EnabledBV63Scheduler_Cfg.Vac[2].EnabledBV65SupplyAirFlwSw.LogicDin_RWBV66RetAirFlwSw.LogicDin_RWBV67AirFlwSw.LogicDin_RWBV68AFreezeSw.LogicDin_RWBV69RemOnOff.LogicDin_RWBV70SupplyFanOvld_1.LogicDin_RWBV71RetFanOvld_1.LogicDin_RWBV72SupplyFanOvld_2.LogicDin_RWBV73RetFanOvld_2.LogicDin_RWBV74SupplyFanInvAlrm.LogicDin_RWBV75RetFanInvAlrm.LogicDin_RWBV76FansOvld.LogicDin_RWBV77CompOvld.LogicDin_RWBV78HiPSw.LogicDin_RWBV79LowPSw.LogicDin_RWBV80RecoveryOvld.LogicDin_RWBV81SrsAlrm.LogicDin_RWBV82GenAlrm.LogicDin_RWBV83GenWarning.LogicDin_RWBV84FiltAlrm.LogicDin_RWBV85SupplyFiltAlrm_1.LogicDin_RWBV86SupplyFiltAlrm_2.LogicDin_RWBV87RetFiltAlrm.LogicDin_RWBV88HumAlrm.LogicDin_RWBV89MainCoilPmp1_Ovld.LogicDin_RWBV90MainCoilPmp2_Ovld.LogicDin_RWBV91ReHeatCoilPmp1_Ovld.LogicDin_RWBV92ReHeatCoilPmp2_Ovld.LogicDin_RWBV93PreHeatCoilPmp1_Ovld.LogicDin_RWBV94PreHeatCoilPmp2_Ovld.LogicDin_RWBV95OA_CoilPmp1_Ovld.LogicDin_RWBV96OA_CoilPmp2_Ovld.LogicDin_RWBV97FreshAirDampSw.LogicDin_RWBV98SupplyDamperSw.LogicDin_RWBV99RetDampSw.LogicDin_RWBV100MainCoilFlwSw.LogicDin_RWBV101PreHeatCoilFlwSw.LogicDin_RWBV102ReHeatCoilFlwSw.LogicDin_RWBV103OA_CoilFlwSw.LogicDin_RWBV104RecoveryClogged.LogicDin_RWBV105ReHeatAlrm.LogicDin_RWBV106PreHeatAlrm.LogicDin_RWBV107MainHeatCoilAlrm.LogicDin_RWBV108OA_CoilAlrm.LogicDin_RWBV109DoorSw.LogicDin_RWBV110FireSmokeAlrm.LogicDin_RWBV111FiremanOverrideSw.LogicDin_RWBV112SummerWinterModeByDin.LogicDin_RWBV113Din_SetP.LogicDin_RWBV114Eco_Mode.LogicDin_RWBV115PreComf_Mode.LogicDin_RWBV116Comf_Mode.LogicDin_RWBV117AuxDin_1.LogicDin_RWBV118AuxDin_2.LogicDin_RWBV119AuxDin_3.LogicDin_RWBV120AuxDin_4.LogicDin_RWBV121DfrHeatExch_Din.LogicDin_RWBV122BypassDamp_Dout.LogicDout_RWBV123BypassDamp_Open.LogicDout_RWBV124BypassDamp_Close.LogicDout_RWBV125FreshAirDamp_Dout.LogicDout_RWBV126ExhAirDamp_Dout.LogicDout_RWBV127MixingDamp_Dout.LogicDout_RWBV128SupplyAirDamp_Dout.LogicDout_RWBV129RetAirDamp_Dout.LogicDout_RWBV130MixingDamp_Open.LogicDout_RWBV131MixingDamp_Close.LogicDout_RWBV132SupplyFan_Dout.LogicDout_RWBV133RetFan_Dout.LogicDout_RWBV134SupplyFan2_Dout.LogicDout_RWBV135RetFan2_Dout.LogicDout_RWBV136Comp_Dout.LogicDout_RWBV137RevVlv.LogicDout_RWBV138UnitOnOff_Dout.LogicDout_RWBV140GlobalAlrm_Dout.LogicDout_RWBV141LightAlrm_Dout.LogicDout_RWBV142SrsAlrm_Dout.LogicDout_RWBV143Humidifier.LogicDout_RWBV144AuxOut1_Dout.LogicDout_RWBV145AuxOut2_Dout.LogicDout_RWBV146AuxOut3_Dout.LogicDout_RWBV147AuxOut4_Dout.LogicDout_RWBV148MainVlv_Open.LogicDout_RWBV149PreHeatVlv_Open.LogicDout_RWBV150ReHeatVlv_Open.LogicDout_RWBV151MainVlv_Close.LogicDout_RWBV152PreHeatVlv_Close.LogicDout_RWBV153ReHeatVlv_Close.LogicDout_RWBV154MainCoil_Step1.LogicDout_RWBV155MainCoil_Step2.LogicDout_RWBV156MainCoil_Step3.LogicDout_RWBV157MainCoil_Step4.LogicDout_RWBV158ReHeatCoil_Step1.LogicDout_RWBV159ReHeatCoil_Step2.LogicDout_RWBV160ReHeatCoil_Step3.LogicDout_RWBV161ReHeatCoil_Step4.LogicDout_RWBV162PreHeatCoil_Step1.LogicDout_RWBV163PreHeatCoil_Step2.LogicDout_RWBV164PreHeatCoil_Step3.LogicDout_RWBV165PreHeatCoil_Step4.LogicDout_RWBV166OA_Coil_Step1.LogicDout_RWBV167OA_Coil_Step2.LogicDout_RWBV168OA_Coil_Step3.LogicDout_RWBV169OA_Coil_Step4.LogicDout_RWBV170PreHeatPmp_1.LogicDout_RWBV171PreHeatPmp_2.LogicDout_RWBV172MainCoilPmp_1.LogicDout_RWBV173MainCoilPmp_2.LogicDout_RWBV174ReHeatPmp_1.LogicDout_RWBV175ReHeatPmp_2.LogicDout_RWBV176OA_CoilPmp_1.LogicDout_RWBV177OA_CoilPmp_2.LogicDout_RWBV178FiltAlrm_Dout.LogicDout_RWBV179Recovery_Dout.LogicDout_RWBV180IEC_Hum_Dout.LogicDout_RWBV181SummerWinter_UIBV182Scheduler_OnOffUnit.PartyMode_StartBV183VarToShow.LogicBV184FreshAirDampEnManBV185MixDampEnManBV186ExhAirDampEnManBV187BypassDampEnManBV188SupplyFanEnManBV189RetFanEnManBV190PreHeatCoilEnManBV191MainCoilEnManBV192ReHeatCoilEnManBV193CompEnManBV194HumEnManBV195En_SetPCompBV196Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[0].EnabledBV197Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[1].EnabledBV198Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[2].EnabledBV199Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[3].EnabledBV200Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[4].EnabledBV201Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[5].EnabledBV202Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[6].EnabledBV203Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[7].EnabledBV204Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[8].EnabledBV205Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[9].EnabledBV206Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[0].EnabledBV207Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[1].EnabledBV208Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[2].EnabledBV209Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[0].EnabledBV210Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[1].EnabledBV211Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[2].EnabledBV212Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[3].EnabledBV213Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[4].EnabledBV214Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[5].EnabledBV215Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[6].EnabledBV216Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[7].EnabledBV217Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[8].EnabledBV218Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[9].EnabledBV219Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[10].EnabledBV220Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[11].EnabledBV221Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[12].EnabledBV222Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[13].EnabledBV223Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[14].EnabledBV224Scheduler_OnOffUnit.En_PartyModeBV225En_RetFanBV226En_DehumRegBV227Dehum_En_KWaterDWPBV228En_WarmUpBV229En_AfreezeOffStateBV230RegPrbErrModeBV231StateMachine.En_RegPrbErr_UnitOffBV232En_THTNBV234Scheduler_OnOffUnit.BMS_OnOff_EnBV236En_VDIBV237En_VDI_HiSatHumStartUpBV238RetFanPrefRunDirBV239RetFan_En_EmergFunctBV245En_Fan_CO2_RegBV246En_FanTempLimBV247En_FC_FH_FanRegBV248En_NightMinVentBV249NightVentPriorityBV250Antifreeze.DisLowSupplyTempAlrmBV251Regulation.EnCompNightVentBV252Humisonic.ManDrain_HUMSBV253Humisonic.DevSettings_HUMS.HrsCountResBV254SupplyFanPrefRunDirBV255SupplyFan_En_EmergFunctBV261AuxReg1_Cfg.DOut_ErrorValueBV262AuxReg1_Cfg.EnableSel_ManualEnBV263AuxReg1_Cfg.En_ComfortRegBV264AuxReg1_Cfg.ReverseModeBV266AuxReg1_Cfg.ManModeEnBV267AuxReg1_Cfg.DOut_ManModeValBV268AuxReg2_Cfg.DOut_ErrorValueBV269AuxReg2_Cfg.EnableSel_ManualEnBV270AuxReg2_Cfg.En_ComfortRegBV271AuxReg2_Cfg.ReverseModeBV273AuxReg2_Cfg.ManModeEnBV274AuxReg2_Cfg.DOut_ManModeValBV275AuxReg3_Cfg.DOut_ErrorValueBV276AuxReg3_Cfg.EnableSel_ManualEnBV277AuxReg3_Cfg.En_ComfortRegBV278AuxReg3_Cfg.ReverseModeBV280AuxReg3_Cfg.ManModeEnBV281AuxReg3_Cfg.DOut_ManModeValBV282AuxReg4_Cfg.DOut_ErrorValueBV283AuxReg4_Cfg.EnableSel_ManualEnBV284AuxReg4_Cfg.En_ComfortRegBV285AuxReg4_Cfg.ReverseModeBV287AuxReg4_Cfg.ManModeEnBV288AuxReg4_Cfg.DOut_ManModeValBV289En_Damp_CO2_RegBV290En_FC_FH_DampRegBV291CompTypBV292En_EVD_Emb_1BV293Coils.MainCoil_PmpFlwChk_EnAntiLockBV294Coils.PreHeatCoil_PmpFlwChk_EnAntiLockBV295Coils.ReHeatCoil_PmpFlwChk_EnAntiLockBV296VDI_Conf[0].EnabledBV297VDI_Conf[0].AlrmTypBV298VDI_Conf[1].EnabledBV299VDI_Conf[1].AlrmTypBV300VDI_Conf[2].EnabledBV301VDI_Conf[2].AlrmTypBV302VDI_Conf[3].EnabledBV303VDI_Conf[3].AlrmTypBV304VDI_Conf[4].EnabledBV305VDI_Conf[4].AlrmTypBV306VDI_Conf[5].EnabledBV307VDI_Conf[5].ResCmdBV308VDI_Conf[6].EnabledBV309VDI_Conf[6].AlrmTypBV310VDI_Conf[7].EnabledBV311VDI_Conf[7].AlrmTypBV312VDI_Conf[8].EnabledBV313VDI_Conf[8].AlrmTypBV314VDI_Conf[9].EnabledBV315VDI_Conf[9].AlrmTypBV316VDI_Conf[10].EnabledBV317VDI_Conf[10].AlrmTypBV318VDI_Conf[11].EnabledBV319VDI_Conf[11].AlrmTypBV320VDI_Conf[12].EnabledBV321VDI_Conf[12].AlrmTypBV322VDI_Conf[13].EnabledBV323VDI_Conf[13].AlrmTypBV324VDI_Conf[14].EnabledBV325VDI_Conf[14].AlrmTypBV326VDI_Conf[15].EnabledBV327VDI_Conf[15].AlrmTypBV328VDI_Conf[16].EnabledBV329VDI_Conf[16].AlrmTypBV330VDI_Conf[17].EnabledBV331VDI_Conf[17].AlrmTypBV332VDI_Conf[18].EnabledBV333VDI_Conf[18].AlrmTypBV334VDI_Conf[19].EnabledBV335VDI_Conf[19].AlrmTypBV336VDI_Conf[20].EnabledBV337VDI_Conf[20].AlrmTypBV338VDI_Conf[21].EnabledBV339VDI_Conf[21].AlrmTypBV340VDI_Conf[22].EnabledBV341VDI_Conf[22].AlrmTypBV342VDI_Conf[23].EnabledBV343VDI_Conf[23].AlrmTypBV344VDI_Conf[24].EnabledBV345VDI_Conf[24].AlrmTypBV346VDI_Conf[25].EnabledBV347VDI_Conf[25].AlrmTypBV348VDI_Conf[26].EnabledBV349VDI_Conf[26].AlrmTypBV350VDI_Conf[27].EnabledBV351VDI_Conf[27].AlrmTypBV352VDI_Conf[28].EnabledBV353VDI_Conf[28].AlrmTypBV354VDI_Conf[0].ResCmdBV355VDI_Conf[1].ResCmdBV356VDI_Conf[2].ResCmdBV357VDI_Conf[3].ResCmdBV358VDI_Conf[4].ResCmdBV359VDI_Conf[6].ResCmdBV360VDI_Conf[7].ResCmdBV361VDI_Conf[8].ResCmdBV362VDI_Conf[9].ResCmdBV363VDI_Conf[10].ResCmdBV364VDI_Conf[11].ResCmdBV365VDI_Conf[12].ResCmdBV366VDI_Conf[13].ResCmdBV367VDI_Conf[14].ResCmdBV368VDI_Conf[15].ResCmdBV369VDI_Conf[16].ResCmdBV370VDI_Conf[17].ResCmdBV371VDI_Conf[18].ResCmdBV372VDI_Conf[19].ResCmdBV373VDI_Conf[20].ResCmdBV374VDI_Conf[21].ResCmdBV375VDI_Conf[22].ResCmdBV376VDI_Conf[23].ResCmdBV377VDI_Conf[24].ResCmdBV378VDI_Conf[25].ResCmdBV379VDI_Conf[26].ResCmdBV380VDI_Conf[27].ResCmdBV381VDI_Conf[28].ResCmdBV382GeneralMng.En_BuzzBV383En_LiqSolVlvBV384EVD_Emb_Circ.EEV_ManPositEnBV385Data_EVD_Emb_1.EVD.System.DC_SupplyEn.ValBV386Data_EVD_Emb_1.EVD.EEV_Config.ExtraOpEn.ValBV387Data_EVD_Emb_1.EVD.EEV_Config.ExtraClosEn.ValBV388BLDC_compressor.MiscMng_PWRP1.Mng_SerNoCtrl_EnBV389BLDC_compressor.CurrCompCfg_PWRP1.HR22_0_SpeedProfStartModeBV390BLDC_compressor.CurrCompCfg_PWRP1.HR22_1_SpeedProfStartModeBV391BLDC_compressor.CurrCompCfg_PWRP1.HR76_0_DisPhLossDetectBV392BLDC_compressor.CurrCompCfg_PWRP1.HR76_3_EnOvldThProtRetentionBV393BLDC_compressor.MiscMng_PWRP1.MngCstm_SaveCustomCfgBV394BLDC_compressor.AlrmResetMng_PWRP1.Al01_uMotorResetTypBV395BLDC_compressor.AlrmResetMng_PWRP1.Al02_uMotorResetTypBV396BLDC_compressor.AlrmResetMng_PWRP1.Al03_uMotorResetTypBV397BLDC_compressor.AlrmResetMng_PWRP1.Al04_uMotorResetTypBV398BLDC_compressor.AlrmResetMng_PWRP1.Al05_uMotorResetTypBV399BLDC_compressor.AlrmResetMng_PWRP1.Al06_uMotorResetTypBV400BLDC_compressor.AlrmResetMng_PWRP1.Al07_uMotorResetTypBV401BLDC_compressor.AlrmResetMng_PWRP1.Al08_uMotorResetTypBV402BLDC_compressor.AlrmResetMng_PWRP1.Al09_uMotorResetTypBV403BLDC_compressor.AlrmResetMng_PWRP1.Al10_uMotorResetTypBV404BLDC_compressor.AlrmResetMng_PWRP1.Al11_uMotorResetTypBV405BLDC_compressor.AlrmResetMng_PWRP1.Al12_uMotorResetTypBV406BLDC_compressor.AlrmResetMng_PWRP1.Al13_uMotorResetTypBV407BLDC_compressor.AlrmResetMng_PWRP1.Al14_uMotorResetTypBV408BLDC_compressor.AlrmResetMng_PWRP1.Al15_uMotorResetTypBV409BLDC_compressor.AlrmResetMng_PWRP1.Al16_uMotorResetTypBV410BLDC_compressor.AlrmResetMng_PWRP1.Al17_uMotorResetTypBV411BLDC_compressor.AlrmResetMng_PWRP1.Al18_uMotorResetTypBV412BLDC_compressor.AlrmResetMng_PWRP1.Al19_uMotorResetTypBV413BLDC_compressor.AlrmResetMng_PWRP1.Al20_uMotorResetTypBV414BLDC_compressor.AlrmResetMng_PWRP1.Al21_uMotorResetTypBV415BLDC_compressor.AlrmResetMng_PWRP1.Al22_uMotorResetTypBV416BLDC_compressor.AlrmResetMng_PWRP1.Al23_uMotorResetTypBV417BLDC_compressor.AlrmResetMng_PWRP1.Al24_uMotorResetTypBV418BLDC_compressor.AlrmResetMng_PWRP1.Al25_uMotorResetTypBV419BLDC_compressor.AlrmResetMng_PWRP1.Al26_uMotorResetTypBV420BLDC_compressor.AlrmResetMng_PWRP1.Al27_uMotorResetTypBV421BLDC_compressor.AlrmResetMng_PWRP1.Al28_uMotorResetTypBV422BLDC_compressor.AlrmResetMng_PWRP1.Al99_uMotorResetTypBV423BLDC_compressor.AlrmResetMng_PWRP1.Al101_uSafeResetTypBV424BLDC_compressor.AlrmResetMng_PWRP1.Al102_uSafeResetTypBV425BLDC_compressor.AlrmResetMng_PWRP1.Al103_uSafeResetTypBV426BLDC_compressor.AlrmResetMng_PWRP1.Al104_uSafeResetTypBV427BLDC_compressor.AlrmResetMng_PWRP1.Al105_uSafeResetTypBV428BLDC_compressor.AlrmResetMng_PWRP1.Al106_uSafeResetTypBV429BLDC_compressor.AlrmResetMng_PWRP1.Al107_uSafeResetTypBV430BLDC_compressor.AlrmResetMng_PWRP1.Al108_uSafeResetTypBV431BLDC_compressor.AlrmResetMng_PWRP1.Al109_uSafeResetTypBV432BLDC_compressor.AlrmResetMng_PWRP1.Al110_uSafeResetTypBV433BLDC_compressor.AlrmResetMng_PWRP1.Al111_uSafeResetTypBV434BLDC_compressor.AlrmResetMng_PWRP1.Al112_uSafeResetTypBV435BLDC_compressor.AlrmResetMng_PWRP1.Al113_uSafeResetTypBV436BLDC_compressor.AlrmResetMng_PWRP1.Al114_uSafeResetTypBV437BLDC_compressor.AlrmResetMng_PWRP1.Al115_uSafeResetTypBV438BLDC_compressor.AlrmResetMng_PWRP1.Al116_uSafeResetTypBV439BLDC_compressor.AlrmResetMng_PWRP1.Al201_uSafeResetTypBV440BLDC_compressor.AlrmResetMng_PWRP1.Al202_uSafeResetTypBV441BLDC_compressor.AlrmResetMng_PWRP1.Al203_uSafeResetTypBV442BLDC_compressor.AlrmResetMng_PWRP1.Al204_uSafeResetTypBV443BLDC_compressor.AlrmResetMng_PWRP1.Al205_uSafeResetTypBV444BLDC_compressor.AlrmResetMng_PWRP1.Al206_uSafeResetTypBV445BLDC_compressor.AlrmResetMng_PWRP1.Al207_uSafeResetTypBV446BLDC_compressor.AlrmResetMng_PWRP1.Al208_uSafeResetTypBV447BLDC_compressor.AlrmResetMng_PWRP1.Al209_uSafeResetTypBV448BLDC_compressor.AlrmResetMng_PWRP1.Al210_uSafeResetTypBV449BLDC_compressor.AlrmResetMng_PWRP1.Al211_uSafeResetTypBV450BLDC_compressor.AlrmResetMng_PWRP1.Al212_uSafeResetTypBV451BLDC_compressor.AlrmResetMng_PWRP1.Al213_uSafeResetTypBV452BLDC_compressor.AlrmResetMng_PWRP1.Al214_uSafeResetTypBV453BLDC_compressor.AlrmResetMng_PWRP1.Al215_uSafeResetTypBV454BLDC_compressor.AlrmResetMng_PWRP1.Al216_uSafeResetTypBV455BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_EnEqualBPVlvBV456BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_EnMopLowCompRatioBV457BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_EnSpeedUpModeBV458BLDC_compressor.AlrmResetMng_BLDC_1.ResetTyp_BLDC_AlrmBV4011SanificationDevice.LogicDout_RWBV3957En_SanificationDeviceBV4035PurgeCmdBV4036SanificationDeviceOvld.LogicDin_RWBV4037SanificationDeviceOvld.Enable_WBV4025En_OilRecovBV4288CstPrbCfg.Temp1FactOpBV4289CstPrbCfg.Temp2FactOpBV4290CstPrbCfg.Hum1FactOpBV4291CstPrbCfg.Hum2FactOpBV4292CstPrbCfg.Press1FactOpBV4293CstPrbCfg.Press2FactOpBV4294CstPrbCfg.Flow1FactOpBV4295CstPrbCfg.Flow2FactOpBV4342HumiSteamMng.Man_UEY.EnManBV4343HumiSteamMng.Man_UEY.PreCleaningBV4344HumiSteamMng.Man_UEY.DrnBV4345HumiSteamMng.ResWorkHrs_UEYBV4367MainCoilCoolHeat_Din.LogicDin_RWBV4369En_FanTempRegBV4447GenericDin1.LogicDin_RWBV4454GenericDin2.LogicDin_RWBV4461GenericDin3.LogicDin_RWBV4468GenericDin4.LogicDin_RWBV4475GenericDin5.LogicDin_RWBV4499IEC_EnManBV4504BMS_Reg_DigitalPrbMap[1]BV4505BMS_Reg_DigitalPrbMap[2]BV4506BMS_Reg_DigitalPrbMap[3]BV4507BMS_Reg_DigitalPrbMap[4]BV4508BMS_Reg_DigitalPrbMap[5]BV4514OA_Vlv_Open.LogicDout_RWBV4515OA_Vlv_Close.LogicDout_RWBV4516OA_CoilEnManBV459MainCoil_CoolHeatModeBV461SupplyTemp.Enable_WBV462SupplyTemp.Configured_RBV463SupplyTemp.PrbOk_RBV464SupplyTemp.Alrm_RBV465SupplyHum.Enable_WBV466SupplyHum.Configured_RBV467SupplyHum.PrbOk_RBV468SupplyHum.Alrm_RBV469RetTemp.Enable_WBV470RetTemp.Configured_RBV471RetTemp.PrbOk_RBV472RetTemp.Alrm_RBV473RetHum.Enable_WBV474RetHum.Configured_RBV475RetHum.PrbOk_RBV476RetHum.Alrm_RBV477RoomTemp.Enable_WBV478RoomTemp.Configured_RBV479RoomTemp.PrbOk_RBV480RoomTemp.Alrm_RBV481RoomHum.Enable_WBV482RoomHum.Configured_RBV483RoomHum.PrbOk_RBV484RoomHum.Alrm_RBV485ExtTemp.Enable_WBV487ExtTemp.PrbOk_RBV488ExtTemp.Alrm_RBV489ExtHum.Enable_WBV490ExtHum.Configured_RBV491ExtHum.PrbOk_RBV492ExtHum.Alrm_RBV493ExhTemp.Enable_WBV494ExhTemp.Configured_RBV495ExhTemp.PrbOk_RBV496ExhTemp.Alrm_RBV497ExhHum.Enable_WBV498ExhHum.Configured_RBV499ExhHum.PrbOk_RBV500ExhHum.Alrm_RBV501AFreezeTemp.Enable_WBV502AFreezeTemp.Configured_RBV503AFreezeTemp.PrbOk_RBV504AFreezeTemp.Alrm_RBV505SatTemp.Enable_WBV507SatTemp.PrbOk_RBV508SatTemp.Alrm_RBV509SatHum.Enable_WBV510SatHum.Configured_RBV511SatHum.PrbOk_RBV512SatHum.Alrm_RBV513OA_Temp.Enable_WBV514OA_Temp.Configured_RBV515OA_Temp.PrbOk_RBV516OA_Temp.Alrm_RBV517SupplyAirP.Enable_WBV518SupplyAirP.Configured_RBV519SupplyAirP.PrbOk_RBV520SupplyAirP.Alrm_RBV521RetAirP.Enable_WBV522RetAirP.Configured_RBV523RetAirP.PrbOk_RBV524RetAirP.Alrm_RBV525AirQuality_CO2.Enable_WBV526AirQuality_CO2.Configured_RBV527AirQuality_CO2.PrbOk_RBV528AirQuality_CO2.Alrm_RBV529AirQuality_VOC.Enable_WBV530AirQuality_VOC.Configured_RBV531AirQuality_VOC.PrbOk_RBV532AirQuality_VOC.Alrm_RBV533DscgP.Enable_WBV534DscgP.Configured_RBV535DscgP.PrbOk_RBV536DscgP.Alrm_RBV537DscgT.Enable_WBV538DscgT.Configured_RBV539DscgT.PrbOk_RBV540DscgT.Alrm_RBV541SuctP.Enable_WBV542SuctP.Configured_RBV543SuctP.PrbOk_RBV544SuctP.Alrm_RBV545SuctT.Enable_WBV546SuctT.Configured_RBV547SuctT.PrbOk_RBV548SuctT.Alrm_RBV549OA_CoilWaterTemp.Enable_WBV550OA_CoilWaterTemp.Configured_RBV551OA_CoilWaterTemp.PrbOk_RBV552OA_CoilWaterTemp.Alrm_RBV553PreHeatCoilWaterTemp.Enable_WBV554PreHeatCoilWaterTemp.Configured_RBV555PreHeatCoilWaterTemp.PrbOk_RBV556PreHeatCoilWaterTemp.Alrm_RBV557MainCoilWaterTemp.Enable_WBV558MainCoilWaterTemp.Configured_RBV560MainCoilWaterTemp.Alrm_RBV561ReHeatCoilWaterTemp.Enable_WBV562ReHeatCoilWaterTemp.Configured_RBV563ReHeatCoilWaterTemp.PrbOk_RBV564ReHeatCoilWaterTemp.Alrm_RBV565AuxPrb_1.Enable_WBV566AuxPrb_1.Configured_RBV567AuxPrb_1.PrbOk_RBV568AuxPrb_1.Alrm_RBV569AuxPrb_2.Enable_WBV570AuxPrb_2.Configured_RBV571AuxPrb_2.PrbOk_RBV572AuxPrb_2.Alrm_RBV573AuxPrb_3.Enable_WBV574AuxPrb_3.Configured_RBV575AuxPrb_3.PrbOk_RBV576AuxPrb_3.Alrm_RBV577AuxPrb_4.Enable_WBV578AuxPrb_4.Configured_RBV579AuxPrb_4.PrbOk_RBV580AuxPrb_4.Alrm_RBV581Ain_SetP.Enable_WBV582Ain_SetP.Configured_RBV583Ain_SetP.PrbOk_RBV584Ain_SetP.Alrm_RBV585SupplyRecoveryTemp.Enable_WBV586SupplyRecoveryTemp.Configured_RBV587SupplyRecoveryTemp.PrbOk_RBV588SupplyRecoveryTemp.Alrm_RBV589RetRecoveryTemp.Enable_WBV590RetRecoveryTemp.Configured_RBV591RetRecoveryTemp.PrbOk_RBV592RetRecoveryTemp.Alrm_RBV593HepaFilt_1.Enable_WBV594HepaFilt_1.Configured_RBV595HepaFilt_1.PrbOk_RBV596HepaFilt_1.Alrm_RBV597HepaFilt_2.Enable_WBV598HepaFilt_2.Configured_RBV599HepaFilt_2.PrbOk_RBV600HepaFilt_2.Alrm_RBV601SupplyAirFlwSw.Val_Hw_RBV602SupplyAirFlwSw.Enable_WBV603SupplyAirFlwSw.Configured_RBV604SupplyAirFlwSw.Val_RBV605RetAirFlwSw.Val_Hw_RBV606RetAirFlwSw.Enable_WBV607RetAirFlwSw.Configured_RBV608RetAirFlwSw.Val_RBV609AirFlwSw.Val_Hw_RBV610AirFlwSw.Enable_WBV611AirFlwSw.Configured_RBV612AirFlwSw.Val_RBV613AFreezeSw.Val_Hw_RBV614AFreezeSw.Enable_WBV615AFreezeSw.Configured_RBV616AFreezeSw.Val_RBV617RemOnOff.Val_Hw_RBV618RemOnOff.Enable_WBV619RemOnOff.Configured_RBV620RemOnOff.Val_RBV621SupplyFanOvld_1.Val_Hw_RBV622SupplyFanOvld_1.Enable_WBV623SupplyFanOvld_1.Configured_RBV624SupplyFanOvld_1.Val_RBV625RetFanOvld_1.Val_Hw_RBV626RetFanOvld_1.Enable_WBV627RetFanOvld_1.Configured_RBV628RetFanOvld_1.Val_RBV629SupplyFanOvld_2.Val_Hw_RBV630SupplyFanOvld_2.Enable_WBV631SupplyFanOvld_2.Configured_RBV632SupplyFanOvld_2.Val_RBV633RetFanOvld_2.Val_Hw_RBV634RetFanOvld_2.Enable_WBV635RetFanOvld_2.Configured_RBV636RetFanOvld_2.Val_RBV637SupplyFanInvAlrm.Val_Hw_RBV638SupplyFanInvAlrm.Enable_WBV639SupplyFanInvAlrm.Configured_RBV640SupplyFanInvAlrm.Val_RBV641RetFanInvAlrm.Val_Hw_RBV642RetFanInvAlrm.Enable_WBV643RetFanInvAlrm.Configured_RBV644RetFanInvAlrm.Val_RBV645FansOvld.Val_Hw_RBV646FansOvld.Enable_WBV647FansOvld.Configured_RBV648FansOvld.Val_RBV649CompOvld.Val_Hw_RBV650CompOvld.Enable_WBV651CompOvld.Configured_RBV652CompOvld.Val_RBV653HiPSw.Val_Hw_RBV654HiPSw.Enable_WBV655HiPSw.Configured_RBV656HiPSw.Val_RBV657LowPSw.Val_Hw_RBV658LowPSw.Enable_WBV659LowPSw.Configured_RBV660LowPSw.Val_RBV661RecoveryOvld.Val_Hw_RBV662RecoveryOvld.Enable_WBV663RecoveryOvld.Configured_RBV664RecoveryOvld.Val_RBV665SrsAlrm.Val_Hw_RBV666SrsAlrm.Enable_WBV667SrsAlrm.Configured_RBV668SrsAlrm.Val_RBV669GenAlrm.Val_Hw_RBV670GenAlrm.Enable_WBV671GenAlrm.Configured_RBV672GenAlrm.Val_RBV673GenWarning.Val_Hw_RBV674GenWarning.Enable_WBV675GenWarning.Configured_RBV676GenWarning.Val_RBV677FiltAlrm.Val_Hw_RBV678FiltAlrm.Enable_WBV679FiltAlrm.Configured_RBV680FiltAlrm.Val_RBV681SupplyFiltAlrm_1.Val_Hw_RBV682SupplyFiltAlrm_1.Enable_WBV683SupplyFiltAlrm_1.Configured_RBV684SupplyFiltAlrm_1.Val_RBV685SupplyFiltAlrm_2.Val_Hw_RBV686SupplyFiltAlrm_2.Enable_WBV687SupplyFiltAlrm_2.Configured_RBV688SupplyFiltAlrm_2.Val_RBV689RetFiltAlrm.Val_Hw_RBV690RetFiltAlrm.Enable_WBV691RetFiltAlrm.Configured_RBV692RetFiltAlrm.Val_RBV693HumAlrm.Val_Hw_RBV694HumAlrm.Enable_WBV695HumAlrm.Configured_RBV696HumAlrm.Val_RBV697MainCoilPmp1_Ovld.Val_Hw_RBV698MainCoilPmp1_Ovld.Enable_WBV699MainCoilPmp1_Ovld.Configured_RBV700MainCoilPmp1_Ovld.Val_RBV701MainCoilPmp2_Ovld.Val_Hw_RBV702MainCoilPmp2_Ovld.Enable_WBV703MainCoilPmp2_Ovld.Configured_RBV704MainCoilPmp2_Ovld.Val_RBV705ReHeatCoilPmp1_Ovld.Val_Hw_RBV706ReHeatCoilPmp1_Ovld.Enable_WBV707ReHeatCoilPmp1_Ovld.Configured_RBV708ReHeatCoilPmp1_Ovld.Val_RBV709ReHeatCoilPmp2_Ovld.Val_Hw_RBV710ReHeatCoilPmp2_Ovld.Enable_WBV711ReHeatCoilPmp2_Ovld.Configured_RBV712ReHeatCoilPmp2_Ovld.Val_RBV713PreHeatCoilPmp1_Ovld.Val_Hw_RBV714PreHeatCoilPmp1_Ovld.Enable_WBV715PreHeatCoilPmp1_Ovld.Configured_RBV716PreHeatCoilPmp1_Ovld.Val_RBV717PreHeatCoilPmp2_Ovld.Val_Hw_RBV718PreHeatCoilPmp2_Ovld.Enable_WBV719PreHeatCoilPmp2_Ovld.Configured_RBV720PreHeatCoilPmp2_Ovld.Val_RBV721OA_CoilPmp1_Ovld.Val_Hw_RBV722OA_CoilPmp1_Ovld.Enable_WBV723OA_CoilPmp1_Ovld.Configured_RBV724OA_CoilPmp1_Ovld.Val_RBV725OA_CoilPmp2_Ovld.Val_Hw_RBV726OA_CoilPmp2_Ovld.Enable_WBV727OA_CoilPmp2_Ovld.Configured_RBV728OA_CoilPmp2_Ovld.Val_RBV729FreshAirDampSw.Val_Hw_RBV730FreshAirDampSw.Enable_WBV731FreshAirDampSw.Configured_RBV732FreshAirDampSw.Val_RBV733SupplyDamperSw.Val_Hw_RBV734SupplyDamperSw.Enable_WBV735SupplyDamperSw.Configured_RBV736SupplyDamperSw.Val_RBV737RetDampSw.Val_Hw_RBV738RetDampSw.Enable_WBV739RetDampSw.Configured_RBV740RetDampSw.Val_RBV741MainCoilFlwSw.Val_Hw_RBV742MainCoilFlwSw.Enable_WBV743MainCoilFlwSw.Configured_RBV744MainCoilFlwSw.Val_RBV745PreHeatCoilFlwSw.Val_Hw_RBV746PreHeatCoilFlwSw.Enable_WBV747PreHeatCoilFlwSw.Configured_RBV748PreHeatCoilFlwSw.Val_RBV749ReHeatCoilFlwSw.Val_Hw_RBV750ReHeatCoilFlwSw.Enable_WBV751ReHeatCoilFlwSw.Configured_RBV752ReHeatCoilFlwSw.Val_RBV753OA_CoilFlwSw.Val_Hw_RBV754OA_CoilFlwSw.Enable_WBV755OA_CoilFlwSw.Configured_RBV756OA_CoilFlwSw.Val_RBV757RecoveryClogged.Val_Hw_RBV758RecoveryClogged.Enable_WBV759RecoveryClogged.Configured_RBV760RecoveryClogged.Val_RBV761ReHeatAlrm.Val_Hw_RBV762ReHeatAlrm.Enable_WBV763ReHeatAlrm.Configured_RBV764ReHeatAlrm.Val_RBV765PreHeatAlrm.Val_Hw_RBV766PreHeatAlrm.Enable_WBV767PreHeatAlrm.Configured_RBV768PreHeatAlrm.Val_RBV769MainHeatCoilAlrm.Val_Hw_RBV770MainHeatCoilAlrm.Enable_WBV771MainHeatCoilAlrm.Configured_RBV772MainHeatCoilAlrm.Val_RBV773OA_CoilAlrm.Val_Hw_RBV774OA_CoilAlrm.Enable_WBV775OA_CoilAlrm.Configured_RBV776OA_CoilAlrm.Val_RBV777DoorSw.Val_Hw_RBV778DoorSw.Enable_WBV779DoorSw.Configured_RBV780DoorSw.Val_RBV781FireSmokeAlrm.Val_Hw_RBV782FireSmokeAlrm.Enable_WBV783FireSmokeAlrm.Configured_RBV784FireSmokeAlrm.Val_RBV785FiremanOverrideSw.Val_Hw_RBV786FiremanOverrideSw.Enable_WBV787FiremanOverrideSw.Configured_RBV788FiremanOverrideSw.Val_RBV789SummerWinterModeByDin.Val_Hw_RBV790SummerWinterModeByDin.Enable_WBV791SummerWinterModeByDin.Configured_RBV792SummerWinterModeByDin.Val_RBV793Din_SetP.Val_Hw_RBV794Din_SetP.Enable_WBV795Din_SetP.Configured_RBV796Din_SetP.Val_RBV797Eco_Mode.Val_Hw_RBV798Eco_Mode.Enable_WBV799Eco_Mode.Configured_RBV800Eco_Mode.Val_RBV801PreComf_Mode.Val_Hw_RBV802PreComf_Mode.Enable_WBV803PreComf_Mode.Configured_RBV804PreComf_Mode.Val_RBV805Comf_Mode.Val_Hw_RBV806Comf_Mode.Enable_WBV807Comf_Mode.Configured_RBV808Comf_Mode.Val_RBV809AuxDin_1.Val_Hw_RBV810AuxDin_1.Enable_WBV811AuxDin_1.Configured_RBV812AuxDin_1.Val_RBV813AuxDin_2.Val_Hw_RBV814AuxDin_2.Enable_WBV815AuxDin_2.Configured_RBV816AuxDin_2.Val_RBV817AuxDin_3.Val_Hw_RBV818AuxDin_3.Enable_WBV819AuxDin_3.Configured_RBV820AuxDin_3.Val_RBV821AuxDin_4.Val_Hw_RBV822AuxDin_4.Enable_WBV823AuxDin_4.Configured_RBV824AuxDin_4.Val_RBV825DfrHeatExch_Din.Val_Hw_RBV826DfrHeatExch_Din.Enable_WBV827DfrHeatExch_Din.Configured_RBV828DfrHeatExch_Din.Val_RBV830BypassDamp_Dout.Val_WBV831BypassDamp_Dout.Enable_WBV832BypassDamp_Dout.Configured_RBV833BypassDamp_Open.Val_Hw_RBV834BypassDamp_Open.Val_WBV835BypassDamp_Open.Enable_WBV836BypassDamp_Open.Configured_RBV837BypassDamp_Close.Val_Hw_RBV838BypassDamp_Close.Val_WBV839BypassDamp_Close.Enable_WBV840BypassDamp_Close.Configured_RBV841FreshAirDamp_Dout.Val_Hw_RBV843FreshAirDamp_Dout.Enable_WBV844FreshAirDamp_Dout.Configured_RBV846ExhAirDamp_Dout.Val_WBV847ExhAirDamp_Dout.Enable_WBV848ExhAirDamp_Dout.Configured_RBV850MixingDamp_Dout.Val_WBV851MixingDamp_Dout.Enable_WBV852MixingDamp_Dout.Configured_RBV853SupplyAirDamp_Dout.Val_Hw_RBV854SupplyAirDamp_Dout.Val_WBV855SupplyAirDamp_Dout.Enable_WBV856SupplyAirDamp_Dout.Configured_RBV857RetAirDamp_Dout.Val_Hw_RBV858RetAirDamp_Dout.Val_WBV859RetAirDamp_Dout.Enable_WBV860RetAirDamp_Dout.Configured_RBV861MixingDamp_Open.Val_Hw_RBV862MixingDamp_Open.Val_WBV863MixingDamp_Open.Enable_WBV864MixingDamp_Open.Configured_RBV865MixingDamp_Close.Val_Hw_RBV866MixingDamp_Close.Val_WBV867MixingDamp_Close.Enable_WBV868MixingDamp_Close.Configured_RBV870SupplyFan_Dout.Val_WBV871SupplyFan_Dout.Enable_WBV872SupplyFan_Dout.Configured_RBV874RetFan_Dout.Val_WBV875RetFan_Dout.Enable_WBV876RetFan_Dout.Configured_RBV877SupplyFan2_Dout.Val_Hw_RBV878SupplyFan2_Dout.Val_WBV879SupplyFan2_Dout.Enable_WBV880SupplyFan2_Dout.Configured_RBV881RetFan2_Dout.Val_Hw_RBV882RetFan2_Dout.Val_WBV883RetFan2_Dout.Enable_WBV884RetFan2_Dout.Configured_RBV886Comp_Dout.Val_WBV887Comp_Dout.Enable_WBV888Comp_Dout.Configured_RBV889RevVlv.Val_Hw_RBV890RevVlv.Val_WBV891RevVlv.Enable_WBV892RevVlv.Configured_RBV893UnitOnOff_Dout.Val_Hw_RBV894UnitOnOff_Dout.Val_WBV895UnitOnOff_Dout.Enable_WBV896UnitOnOff_Dout.Configured_RBV897CoolHeat_Dout.Val_Hw_RBV898CoolHeat_Dout.Val_WBV899CoolHeat_Dout.Enable_WBV900CoolHeat_Dout.Configured_RBV901GlobalAlrm_Dout.Val_Hw_RBV902GlobalAlrm_Dout.Val_WBV903GlobalAlrm_Dout.Enable_WBV904GlobalAlrm_Dout.Configured_RBV905LightAlrm_Dout.Val_Hw_RBV906LightAlrm_Dout.Val_WBV907LightAlrm_Dout.Enable_WBV908LightAlrm_Dout.Configured_RBV909SrsAlrm_Dout.Val_Hw_RBV910SrsAlrm_Dout.Val_WBV911SrsAlrm_Dout.Enable_WBV912SrsAlrm_Dout.Configured_RBV913Humidifier.Val_Hw_RBV914Humidifier.Val_WBV915Humidifier.Enable_WBV916Humidifier.Configured_RBV917AuxOut1_Dout.Val_Hw_RBV919AuxOut1_Dout.Enable_WBV920AuxOut1_Dout.Configured_RBV921AuxOut2_Dout.Val_Hw_RBV923AuxOut2_Dout.Enable_WBV924AuxOut2_Dout.Configured_RBV925AuxOut3_Dout.Val_Hw_RBV927AuxOut3_Dout.Enable_WBV928AuxOut3_Dout.Configured_RBV929AuxOut4_Dout.Val_Hw_RBV931AuxOut4_Dout.Enable_WBV932AuxOut4_Dout.Configured_RBV933MainVlv_Open.Val_Hw_RBV934MainVlv_Open.Val_WBV935MainVlv_Open.Enable_WBV936MainVlv_Open.Configured_RBV937PreHeatVlv_Open.Val_Hw_RBV938PreHeatVlv_Open.Val_WBV939PreHeatVlv_Open.Enable_WBV940PreHeatVlv_Open.Configured_RBV941ReHeatVlv_Open.Val_Hw_RBV942ReHeatVlv_Open.Val_WBV943ReHeatVlv_Open.Enable_WBV944ReHeatVlv_Open.Configured_RBV945MainVlv_Close.Val_Hw_RBV946MainVlv_Close.Val_WBV947MainVlv_Close.Enable_WBV948MainVlv_Close.Configured_RBV949PreHeatVlv_Close.Val_Hw_RBV950PreHeatVlv_Close.Val_WBV951PreHeatVlv_Close.Enable_WBV952PreHeatVlv_Close.Configured_RBV953ReHeatVlv_Close.Val_Hw_RBV954ReHeatVlv_Close.Val_WBV955ReHeatVlv_Close.Enable_WBV956ReHeatVlv_Close.Configured_RBV957MainCoil_Step1.Val_Hw_RBV958MainCoil_Step1.Val_WBV959MainCoil_Step1.Enable_WBV960MainCoil_Step1.Configured_RBV961MainCoil_Step2.Val_Hw_RBV962MainCoil_Step2.Val_WBV963MainCoil_Step2.Enable_WBV964MainCoil_Step2.Configured_RBV965MainCoil_Step3.Val_Hw_RBV966MainCoil_Step3.Val_WBV967MainCoil_Step3.Enable_WBV968MainCoil_Step3.Configured_RBV969MainCoil_Step4.Val_Hw_RBV970MainCoil_Step4.Val_WBV971MainCoil_Step4.Enable_WBV972MainCoil_Step4.Configured_RBV973ReHeatCoil_Step1.Val_Hw_RBV974ReHeatCoil_Step1.Val_WBV975ReHeatCoil_Step1.Enable_WBV976ReHeatCoil_Step1.Configured_RBV977ReHeatCoil_Step2.Val_Hw_RBV978ReHeatCoil_Step2.Val_WBV979ReHeatCoil_Step2.Enable_WBV980ReHeatCoil_Step2.Configured_RBV981ReHeatCoil_Step3.Val_Hw_RBV982ReHeatCoil_Step3.Val_WBV983ReHeatCoil_Step3.Enable_WBV984ReHeatCoil_Step3.Configured_RBV985ReHeatCoil_Step4.Val_Hw_RBV986ReHeatCoil_Step4.Val_WBV987ReHeatCoil_Step4.Enable_WBV988ReHeatCoil_Step4.Configured_RBV989PreHeatCoil_Step1.Val_Hw_RBV990PreHeatCoil_Step1.Val_WBV991PreHeatCoil_Step1.Enable_WBV992PreHeatCoil_Step1.Configured_RBV993PreHeatCoil_Step2.Val_Hw_RBV994PreHeatCoil_Step2.Val_WBV995PreHeatCoil_Step2.Enable_WBV996PreHeatCoil_Step2.Configured_RBV997PreHeatCoil_Step3.Val_Hw_RBV998PreHeatCoil_Step3.Val_WBV999PreHeatCoil_Step3.Enable_WBV1000PreHeatCoil_Step3.Configured_RBV1001PreHeatCoil_Step4.Val_Hw_RBV1002PreHeatCoil_Step4.Val_WBV1003PreHeatCoil_Step4.Enable_WBV1004PreHeatCoil_Step4.Configured_RBV1005OA_Coil_Step1.Val_Hw_RBV1006OA_Coil_Step1.Val_WBV1007OA_Coil_Step1.Enable_WBV1008OA_Coil_Step1.Configured_RBV1009OA_Coil_Step2.Val_Hw_RBV1010OA_Coil_Step2.Val_WBV1011OA_Coil_Step2.Enable_WBV1012OA_Coil_Step2.Configured_RBV1013OA_Coil_Step3.Val_Hw_RBV1014OA_Coil_Step3.Val_WBV1015OA_Coil_Step3.Enable_WBV1016OA_Coil_Step3.Configured_RBV1017OA_Coil_Step4.Val_Hw_RBV1018OA_Coil_Step4.Val_WBV1019OA_Coil_Step4.Enable_WBV1020OA_Coil_Step4.Configured_RBV1021PreHeatPmp_1.Val_Hw_RBV1022PreHeatPmp_1.Val_WBV1023PreHeatPmp_1.Enable_WBV1024PreHeatPmp_1.Configured_RBV1025PreHeatPmp_2.Val_Hw_RBV1026PreHeatPmp_2.Val_WBV1027PreHeatPmp_2.Enable_WBV1028PreHeatPmp_2.Configured_RBV1029MainCoilPmp_1.Val_Hw_RBV1030MainCoilPmp_1.Val_WBV1031MainCoilPmp_1.Enable_WBV1032MainCoilPmp_1.Configured_RBV1033MainCoilPmp_2.Val_Hw_RBV1034MainCoilPmp_2.Val_WBV1035MainCoilPmp_2.Enable_WBV1036MainCoilPmp_2.Configured_RBV1037ReHeatPmp_1.Val_Hw_RBV1038ReHeatPmp_1.Val_WBV1039ReHeatPmp_1.Enable_WBV1040ReHeatPmp_1.Configured_RBV1041ReHeatPmp_2.Val_Hw_RBV1042ReHeatPmp_2.Val_WBV1043ReHeatPmp_2.Enable_WBV1044ReHeatPmp_2.Configured_RBV1045OA_CoilPmp_1.Val_Hw_RBV1046OA_CoilPmp_1.Val_WBV1047OA_CoilPmp_1.Enable_WBV1048OA_CoilPmp_1.Configured_RBV1049OA_CoilPmp_2.Val_Hw_RBV1050OA_CoilPmp_2.Val_WBV1051OA_CoilPmp_2.Enable_WBV1052OA_CoilPmp_2.Configured_RBV1053FiltAlrm_Dout.Val_Hw_RBV1054FiltAlrm_Dout.Val_WBV1055FiltAlrm_Dout.Enable_WBV1056FiltAlrm_Dout.Configured_RBV1057Recovery_Dout.Val_Hw_RBV1058Recovery_Dout.Val_WBV1059Recovery_Dout.Enable_WBV1060Recovery_Dout.Configured_RBV1061IEC_Hum_Dout.Val_Hw_RBV1062IEC_Hum_Dout.Val_WBV1063IEC_Hum_Dout.Enable_WBV1064IEC_Hum_Dout.Configured_RBV1065SupplyFan_Aout.Enable_WBV1066SupplyFan_Aout.Configured_RBV1067RetFan_Aout.Enable_WBV1068RetFan_Aout.Configured_RBV1069BypassDamp_Aout.Enable_WBV1070BypassDamp_Aout.Configured_RBV1071MixingDamp_Aout.Enable_WBV1072MixingDamp_Aout.Configured_RBV1073FreshAirDamp_Aout.Enable_WBV1074FreshAirDamp_Aout.Configured_RBV1075ReHeatCoil_Aout.Enable_WBV1076ReHeatCoil_Aout.Configured_RBV1077PreHeatCoil_Aout.Enable_WBV1078PreHeatCoil_Aout.Configured_RBV1079OA_Coil_Aout.Enable_WBV1080OA_Coil_Aout.Configured_RBV1081MainCoil_Aout.Enable_WBV1082MainCoil_Aout.Configured_RBV1083ThrmlWheel_Aout.Enable_WBV1084ThrmlWheel_Aout.Configured_RBV1085Humidifier_Aout.Enable_WBV1086Humidifier_Aout.Configured_RBV1087ExhAirDamp_Aout.Enable_WBV1088ExhAirDamp_Aout.Configured_RBV1089AuxAout_1.Enable_WBV1090AuxAout_1.Configured_RBV1091AuxAout_2.Enable_WBV1092AuxAout_2.Configured_RBV1093AuxAout_3.Enable_WBV1094AuxAout_3.Configured_RBV1095AuxAout_4.Enable_WBV1096AuxAout_4.Configured_RBV1097IEC_Aout.Enable_WBV1098IEC_Aout.Configured_RBV1099Recovery_Aout.Enable_WBV1100Recovery_Aout.Configured_RBV1101SupplyAirDamp_Aout.Enable_WBV1102SupplyAirDamp_Aout.Configured_RBV1103RetAirDamp_Aout.Enable_WBV1104RetAirDamp_Aout.Configured_RBV1115Scheduler_OnOffUnit.FB_SchedulerMngK_1.StatusChkBV1116Scheduler_OnOffUnit.FB_SchedulerMngK_1.VacChkBV1117Scheduler_OnOffUnit.FB_SchedulerMngK_1.SDayChkBV1152GeneralMng.WizardCustomBV1153Scheduler_OnOffUnit.FB_SchedulerMskMng_1.CfgErr_SCHEDBV1157GenericHumidifier.ModulHum_IO_CfgWarnBV1164AuxiliaryRegulation.AuxReg1_Info.InputCheckCfgErrBV1165AuxiliaryRegulation.AuxReg1_Info.OutputCheckCfgErrBV1166AuxiliaryRegulation.AuxReg1_Info.DOutBV1167AuxiliaryRegulation.AuxReg1_Info.EnableCheckCfgErrBV1168AuxiliaryRegulation.AuxReg2_Info.InputCheckCfgErrBV1169AuxiliaryRegulation.AuxReg2_Info.OutputCheckCfgErrBV1170AuxiliaryRegulation.AuxReg2_Info.DOutBV1171AuxiliaryRegulation.AuxReg2_Info.EnableCheckCfgErrBV1172AuxiliaryRegulation.AuxReg3_Info.InputCheckCfgErrBV1173AuxiliaryRegulation.AuxReg3_Info.OutputCheckCfgErrBV1174AuxiliaryRegulation.AuxReg3_Info.DOutBV1175AuxiliaryRegulation.AuxReg3_Info.EnableCheckCfgErrBV1176AuxiliaryRegulation.AuxReg4_Info.InputCheckCfgErrBV1177AuxiliaryRegulation.AuxReg4_Info.OutputCheckCfgErrBV1178AuxiliaryRegulation.AuxReg4_Info.DOutBV1179AuxiliaryRegulation.AuxReg4_Info.EnableCheckCfgErrBV1180Comp_OnOff.OnOffComp_IO_CfgWarnBV1181BLDC_compressor.BLDC_Comp_IO_CfgWarnBV1182cpCOmini_HighEndBV1183GeneralMng.DHCP_State_1BV1184BLDC_compressor.Info_PWRP1.StatusReg_Bit_15BV1185BLDC_compressor.Info_PWRP1.StatusReg_Bit_14BV1186BLDC_compressor.Info_PWRP1.StatusReg_Bit_13BV1187BLDC_compressor.Info_PWRP1.StatusReg_Bit_12BV1188BLDC_compressor.Info_PWRP1.StatusReg_DriveTrippedBV1189BLDC_compressor.Info_PWRP1.StatusReg_Bit_10BV1190BLDC_compressor.Info_PWRP1.StatusReg_MainSupplyLossedBV1191BLDC_compressor.Info_PWRP1.StatusReg_MotorOverloadBV1192BLDC_compressor.Info_PWRP1.StatusReg_DriveInAutotuneBV1193BLDC_compressor.Info_PWRP1.StatusReg_Bit_06BV1194BLDC_compressor.Info_PWRP1.StatusReg_SwitchingFreqDeratingONBV1195BLDC_compressor.Info_PWRP1.StatusReg_FanONBV1196BLDC_compressor.Info_PWRP1.StatusReg_UnderVoltageBV1197BLDC_compressor.Info_PWRP1.StatusReg_MotorPTC_OverHeatBV1198BLDC_compressor.Info_PWRP1.StatusReg_RelayConfigONBV1199BLDC_compressor.Info_PWRP1.StatusReg_DriveInhibitBV1200BLDC_compressor.Info_PWRP1.SpeedReg_Bit_15BV1201BLDC_compressor.Info_PWRP1.SpeedReg_Bit_14BV1202BLDC_compressor.Info_PWRP1.SpeedReg_Bit_13BV1203BLDC_compressor.Info_PWRP1.SpeedReg_Bit_12BV1204BLDC_compressor.Info_PWRP1.SpeedReg_Bit_11BV1205BLDC_compressor.Info_PWRP1.SpeedReg_Bit_10BV1206BLDC_compressor.Info_PWRP1.SpeedReg_Bit_09BV1207BLDC_compressor.Info_PWRP1.SpeedReg_Bit_08BV1208BLDC_compressor.Info_PWRP1.SpeedReg_Bit_07BV1209BLDC_compressor.Info_PWRP1.SpeedReg_Bit_06BV1210BLDC_compressor.Info_PWRP1.SpeedReg_Bit_05BV1211BLDC_compressor.Info_PWRP1.SpeedReg_Bit_04BV1212BLDC_compressor.Info_PWRP1.SpeedReg_Bit_03BV1213BLDC_compressor.Info_PWRP1.SpeedReg_Bit_02BV1214BLDC_compressor.Info_PWRP1.SpeedReg_Bit_01BV1215BLDC_compressor.Info_PWRP1.SpeedReg_Bit_00BV1216BLDC_compressor.Info_PWRP1.Mng_CheckVI_NotOKBV1217BLDC_compressor.Info_PWRP1.Mng_LoadDefFailBV1218BLDC_compressor.Info_PWRP1.Info_PSD_400VBV1219BLDC_compressor.Info_PWRP1.Mng_MotSelect_400VBV1220BLDC_compressor.MiscMng_PWRP1.MngCstm_SaveCustomCfgInProgressBV1221BLDC_compressor.PwrpOnline_BLDC1BV1222Info_BLDC1.Mng_TestModeBV1223Info_BLDC1.Info_SIAM_90rpsZoneBV1224Info_BLDC1.UI_EqualizationStatusBV1225Info_BLDC1.UI_LowDeltaPBV1226Info_BLDC1.EnvTyp_SiamCompBV1227SPV_Warning_ConfigBV1228SPV_Warning_LicenseBV1229Al_NOT_USED.ActiveBV1230Al_SupplyTemp.ActiveBV1231Al_SupplyHum.ActiveBV1232Al_RetTemp.ActiveBV1233Al_RetHum.ActiveBV1234Al_RoomTemp.ActiveBV1235Al_RoomHum.ActiveBV1236Al_ExtTemp.ActiveBV1237Al_ExtHum.ActiveBV1238Al_ExhTemp.ActiveBV1239Al_ExhHum.ActiveBV1240Al_AFreezeTemp.ActiveBV1241Al_SatTemp.ActiveBV1242Al_SatHum.ActiveBV1243Al_OutdoorAirTemp.ActiveBV1244Al_SupplyAirP.ActiveBV1245Al_RetAirP.ActiveBV1246Al_AirQuality_CO2.ActiveBV1247Al_AirQuality_VOC.ActiveBV1248Al_DscgP.ActiveBV1249Al_DscgT.ActiveBV1250Al_SuctP.ActiveBV1251Al_SuctT.ActiveBV1252Al_OA_CoilWaterTemp.ActiveBV1253Al_PreHeatCoilWaterTemp.ActiveBV1254Al_MainCoilWaterTemp.ActiveBV1255Al_ReHeatCoilWaterTemp.ActiveBV1256Al_AuxPrb_1.ActiveBV1257Al_AuxPrb_2.ActiveBV1258Al_AuxPrb_3.ActiveBV1259Al_AuxPrb_4.ActiveBV1260Al_Ain_SetP.ActiveBV1261Al_SupplyRecoveryTemp.ActiveBV1262Al_RetRecoveryTemp.ActiveBV1263Al_HepaFilt_1.ActiveBV1264Al_HepaFilt_2.ActiveBV1265Al_GenericAlrmByDin.ActiveBV1266Al_MainHeat_Ovld.ActiveBV1267Al_SupplyFanOvld.ActiveBV1268Al_RetFanOvld.ActiveBV1269Al_FansOvld.ActiveBV1270Al_CompOvld.ActiveBV1271Al_HiP_Sw.ActiveBV1272Al_LowP_Sw.ActiveBV1273Al_SupplyAirFlwSw.ActiveBV1274Al_RetAirFlwSw.ActiveBV1275Al_AirFlwSw.ActiveBV1276Al_AFreeze.ActiveBV1277Al_LowSH_EVD_Emb.ActiveBV1278Al_EEV_MotErr.ActiveBV1279Al_SettingOutOfBound_EVD_Emb.ActiveBV1280Al_RangeErr_EVD_Emb.ActiveBV1281Al_InvOffline.ActiveBV1282Al_Inv01_OverA.ActiveBV1283Al_Inv02_MotOvld.ActiveBV1284Al_Inv03_DC_BusOverV.ActiveBV1285Al_Inv04_DC_BusUnderV.ActiveBV1286Al_Inv05_OverTemp.ActiveBV1287Al_Inv06_DrvUnderTemp.ActiveBV1288Al_Inv07_HW_OverA.ActiveBV1289Al_Inv08_MotOverTemp.ActiveBV1290Al_Inv09_OutputFault.ActiveBV1291Al_Inv10_FlashDataErr.ActiveBV1292Al_Inv11_ParamDef.ActiveBV1293Al_Inv12_DC_RippTooLarge.ActiveBV1294Al_Inv13_MB_CommFault.ActiveBV1295Al_Inv14_DrvThermistorFault.ActiveBV1296Al_Inv15_AutotuneFault.ActiveBV1297Al_Inv16_DrvDis.ActiveBV1298Al_Inv17_MotPhaseFault.ActiveBV1299Al_Inv18_FanFault.ActiveBV1300Al_Inv19_SpeedFault.ActiveBV1301Al_Inv20_PFC_Failure.ActiveBV1302Al_Inv21_PFC_OverVolt.ActiveBV1303Al_Inv22_PFC_UnderVolt.ActiveBV1304Al_Inv23_STO_Survey1.ActiveBV1305Al_Inv24_STO_Survey2.ActiveBV1306Al_Inv25_GroundFault.ActiveBV1307Al_Inv26_ADC_ConvSync.ActiveBV1308Al_Inv27_HW_Sync.ActiveBV1309Al_Inv28_DrvOvrld.ActiveBV1310Al_Inv29_uCSafe_DriveStop.ActiveBV1311Al_Inv99_UnexpectedStop.ActiveBV1312Al_StartFail_BLDC1.ActiveBV1313Al_SwPrototype.ActiveBV1314Al_retain.ActiveBV1315Al_Err_retain_write.ActiveBV1316Al_Offline_THTN.ActiveBV1317Al_LowSupplyTemp.ActiveBV1318Warn_MainCoilTOutOfRange.ActiveBV1319Al_SupplyAirFlwSwWarn.ActiveBV1320Al_RetAirFlwSwWarn.ActiveBV1321Al_AirFlwSwWarn.ActiveBV1322Warn_AFreezeWarn.ActiveBV1323Al_HumAlrm.ActiveBV1324Al_WrkHrs_Hum.ActiveBV1325Al_WrkHrs_SupplyFan.ActiveBV1326Al_WrkHrs_ReturnFan.ActiveBV1327Al_WrkHrs_ThrmlWheel.ActiveBV1328Al_WrkHrs_DirtyFilt.ActiveBV1329Al_DirtyFiltByDin.ActiveBV1330Al_WrkHrs_Comp.ActiveBV1331Al_HiRatioP_BLDC.ActiveBV1332Al_DscgHiP_BLDC.ActiveBV1333Al_HiCurr_BLDC.ActiveBV1334Al_SuctHiP_BLDC.ActiveBV1335Al_LowRatioP_BLDC.ActiveBV1336Al_LowDeltaP_BLDC.ActiveBV1337Al_LowDscgP_BLDC.ActiveBV1338Al_LowSuctP_BLDC.ActiveBV1339Al_HiDscgTemp_BLDC.ActiveBV1340Al_LOP_EVD_Emb.ActiveBV1341Al_MOP_EVD_Emb.ActiveBV1342Al_HiCondTemp_EVD_Emb.ActiveBV1343Al_LowSuctTemp_EVD_Emb.ActiveBV1344Al_EmergClos_EVD_Emb.ActiveBV1345Al_DisStartDp_BLDC.ActiveBV1346Al_ThTune_ClkBrd.ActiveBV1347Al_BMS_Offline.ActiveBV1348Al_Selftuning_EVD_Emb.ActiveBV1349Al_Offline_Humisonic.ActiveBV1350Al_HiHum_Humisonic.ActiveBV1351Al_LowHum_Humisonic.ActiveBV1352Al_NoProd_Humisonic.ActiveBV1353Al_FaultyDrn_Humisonic.ActiveBV1354Al_Wmissing_Humisonic.ActiveBV1355Al_ExtSignal_Humisonic.ActiveBV1356Al_Functest_Humisonic.ActiveBV1357Al_Autotest_Humisonic.ActiveBV1358Al_EEPROM_Err_Humisonic.ActiveBV1359Al_Offline_EBM_SupplyFan.ActiveBV1360Al_Generic_EBM_SupplyFan.ActiveBV1385Al_Offline_EBM_RetFan.ActiveBV1361Al_Offline_EBM_SupplyFan2.ActiveBV1362Al_Generic_EBM_SupplyFan2.ActiveBV1363Al_Offline_EBM_SupplyFan3.ActiveBV1364Al_Generic_EBM_SupplyFan3.ActiveBV1365Al_Offline_EBM_SupplyFan4.ActiveBV1366Al_Generic_EBM_SupplyFan4.ActiveBV1367Al_NOT_USED_138.ActiveBV1368Al_NOT_USED_139.ActiveBV1369Al_NOT_USED_140.ActiveBV1370Al_NOT_USED_141.ActiveBV1371Al_NOT_USED_142.ActiveBV1372Al_NOT_USED_143.ActiveBV1373Al_NOT_USED_144.ActiveBV1374Al_NOT_USED_145.ActiveBV1375Al_NOT_USED_146.ActiveBV1376Al_NOT_USED_147.ActiveBV1377Al_NOT_USED_148.ActiveBV1378Al_NOT_USED_149.ActiveBV1379Al_NOT_USED_150.ActiveBV1380Al_NOT_USED_151.ActiveBV1381Al_NOT_USED_152.ActiveBV1382Al_NOT_USED_153.ActiveBV1383Al_NOT_USED_154.ActiveBV1384Al_NOT_USED_155.ActiveBV1386Al_Generic_EBM_RetFan.ActiveBV1387Al_Offline_EBM_RetFan2.ActiveBV1388Al_Generic_EBM_RetFan2.ActiveBV1389Al_Offline_EBM_RetFan3.ActiveBV1390Al_Generic_EBM_RetFan3.ActiveBV1391Al_Offline_EBM_RetFan4.ActiveBV1392Al_Generic_EBM_RetFan4.ActiveBV1393Al_NOT_USED_164.ActiveBV1394Al_NOT_USED_165.ActiveBV1395Al_NOT_USED_166.ActiveBV1396Al_NOT_USED_167.ActiveBV1397Al_NOT_USED_168.ActiveBV1398Al_NOT_USED_169.ActiveBV1399Al_NOT_USED_170.ActiveBV1400Al_NOT_USED_171.ActiveBV1401Al_NOT_USED_172.ActiveBV1402Al_NOT_USED_173.ActiveBV1403Al_NOT_USED_174.ActiveBV1404Al_NOT_USED_175.ActiveBV1405Al_NOT_USED_176.ActiveBV1406Al_NOT_USED_177.ActiveBV1407Al_NOT_USED_178.ActiveBV1408Al_NOT_USED_179.ActiveBV1409Al_NOT_USED_180.ActiveBV1410Al_NOT_USED_181.ActiveBV1411Al_WrkHrs_ModulHum.ActiveBV1412Al_RecoveryOvld.ActiveBV1413Al_Offline_ZA_SupplyFan.ActiveBV1414Al_Generic_ZA_SupplyFan.ActiveBV1415Al_Offline_ZA_SupplyFan2.ActiveBV1416Al_Generic_ZA_SupplyFan2.ActiveBV1417Al_Offline_ZA_SupplyFan3.ActiveBV1418Al_Generic_ZA_SupplyFan3.ActiveBV1419Al_Offline_ZA_SupplyFan4.ActiveBV1420Al_Generic_ZA_SupplyFan4.ActiveBV1421Al_FwIncompatible_ZA_SupplyFan.ActiveBV1422Al_FwIncompatible_ZA_SupplyFan2.ActiveBV1423Al_FwIncompatible_ZA_SupplyFan3.ActiveBV1424Al_FwIncompatible_ZA_SupplyFan4.ActiveBV1426Al_Generic_ZA_RetFan.ActiveBV1427Al_Offline_ZA_RetFan2.ActiveBV1428Al_Generic_ZA_RetFan2.ActiveBV1429Al_Offline_ZA_RetFan3.ActiveBV1430Al_Generic_ZA_RetFan3.ActiveBV1431Al_Offline_ZA_RetFan4.ActiveBV1432Al_Generic_ZA_RetFan4.ActiveBV1433Al_FwIncompatible_ZA_RetFan.ActiveBV1434Al_FwIncompatible_ZA_RetFan2.ActiveBV1435Al_FwIncompatible_ZA_RetFan3.ActiveBV1436Al_FwIncompatible_ZA_RetFan4.ActiveBV1436Al_PeakCurrent_ZA_RetFan.ActiveBV1437Al_ErrCfgB2P.ActiveBV1438Al_HighSupplyTemp.ActiveBV1439Al_VDI_HygieneInspection_0_0.ActiveBV1440Al_VDI_OutdoorAirInlets_1_1.ActiveBV1441Al_VDI_Dehum_3_1.ActiveBV1442Al_VDI_Dehum_3_2.ActiveBV1443Al_VDI_Dehum_3_3.ActiveBV1444Al_VDI_AHUHousing_4_1.ActiveBV1445Al_VDI_AHUHousing_4_2.ActiveBV1446Al_VDI_AHUHousing_4_3.ActiveBV1447Al_VDI_AirHumWithNoClearW_6_2_1.ActiveBV1448Al_VDI_AirHumWithNoClearW_6_2_2.ActiveBV1449Al_VDI_AirHumWithNoClearW_6_2_3.ActiveBV1450Al_VDI_AirHumWithNoClearW_6_2_4.ActiveBV1451Al_VDI_AirHumWithNoClearW_6_2_5.ActiveBV1452Al_VDI_AirHumWithNoClearW_6_2_6.ActiveBV1453Al_VDI_AirHumWithNoClearW_6_2_7.ActiveBV1454Al_VDI_AirHumWithNoClearW_6_2_8.ActiveBV1455Al_VDI_AirFilt_8_1.ActiveBV1456Al_VDI_AirFilt_8_2.ActiveBV1457Al_VDI_AirFilt_8_3.ActiveBV1458Al_VDI_AirFilt_8_4.ActiveBV1459Al_VDI_AirDuct_9_1.ActiveBV1460Al_VDI_AirDuct_9_2.ActiveBV1461Al_VDI_Silencers_11_1.ActiveBV1462Al_VDI_Fan_12_1.ActiveBV1463Al_VDI_HeatExch_13_1.ActiveBV1464Al_VDI_HeatExch_13_2.ActiveBV1465Al_VDI_HeatExch_13_4.ActiveBV1466Al_VDI_HeatExch_13_5.ActiveBV1467Al_VDI_HeatExch_13_6.ActiveBV1468Al_VDI_SupplyHum.ActiveBV1469Al_DoorSw.ActiveBV1470Al_FireSmoke.ActiveBV1471Al_SrsAlrmByDin.ActiveBV1472Al_GenericWarnByDin.ActiveBV1473Al_Sup1_DirtyFiltByDin.ActiveBV1474Al_Sup2_DirtyFiltByDin.ActiveBV1475Al_Ret_DirtyFiltByDin.ActiveBV1476Al_HEPA_Filt1.ActiveBV1477Al_HEPA_Filt2.ActiveBV1478Al_MainCoilPmp1_Ovld.ActiveBV1479Al_MainCoilPmp2_Ovld.ActiveBV1480Al_ReHeatCoilPmp1_Ovld.ActiveBV1481Al_ReHeatCoilPmp2_Ovld.ActiveBV1482Al_PreHeatCoilPmp1_Ovld.ActiveBV1483Al_PreHeatCoilPmp2_Ovld.ActiveBV1484Al_MainCoilFlwSw.ActiveBV1485Al_ReHeatCoilFlwSw.ActiveBV1486Al_PreHeatCoilFlwSw.ActiveBV1487Al_RecoveryClogged.ActiveBV1488Al_ReHeat_Ovld.ActiveBV1489Al_PreHeat_Ovld.ActiveBV1490Al_uChiller_Alrm.ActiveBV1491Al_uChiller_Offline.ActiveBV1492Al_WrkHrs_MainCoilPmp1.ActiveBV1493Al_WrkHrs_MainCoilPmp2.ActiveBV1494Al_WrkHrs_MainCoilAout.ActiveBV1495Al_WrkHrs_MainCoilStep1.ActiveBV1496Al_WrkHrs_MainCoilStep2.ActiveBV1497Al_WrkHrs_MainCoilStep3.ActiveBV1498Al_WrkHrs_MainCoilStep4.ActiveBV1499Al_WrkHrs_PreHeatCoilPmp1.ActiveBV1500Al_WrkHrs_PreHeatCoilPmp2.ActiveBV1501Al_WrkHrs_PreHeatCoilAout.ActiveBV1502Al_WrkHrs_PreHeatCoilStep1.ActiveBV1503Al_WrkHrs_PreHeatCoilStep2.ActiveBV1504Al_WrkHrs_PreHeatCoilStep3.ActiveBV1505Al_WrkHrs_PreHeatCoilStep4.ActiveBV1506Al_WrkHrs_ReHeatCoilStep4.ActiveBV1507Al_WrkHrs_ReHeatCoilPmp1.ActiveBV1508Al_WrkHrs_ReHeatCoilPmp2.ActiveBV1509Al_WrkHrs_ReHeatCoilAout.ActiveBV1510Al_WrkHrs_ReHeatCoilStep1.ActiveBV1511Al_WrkHrs_ReHeatCoilStep2.ActiveBV1512Al_WrkHrs_ReHeatCoilStep3.ActiveBV1513Al_WrkHrs_AuxDout.ActiveBV1514Al_WrkHrs_AuxAout.ActiveBV1515Al_WrkHrs_IEC.ActiveBV1516Al_WrkHrs_Unit.ActiveBV1517Al_Humifog.ActiveBV1518Al_IEC_Humifog.ActiveBV1519Al_Humifog_Offline.ActiveBV1520Al_IEC_Humifog_Offline.ActiveBV1522Al_EEV_HWCompatErr.ActiveBV1523Al_PGDx_Offline.ActiveBV3934Al_cpCOe_1_Offline.ActiveBV3935Al_cpCOe_2_Offline.ActiveBV3936Al_cpCOe_3_Offline.ActiveBV3937Al_cpCOe_4_Offline.ActiveBV3932Warn_PreHeatCoilTOutOfRange.ActiveBV3933Warn_ReHeatCoilTOutOfRange.ActiveBV3941MainCoil_FloatVlvBV3942Coils.PreHeatCoil_FloatVlvBV3943Coils.ReHeatCoil_FloatVlvBV3944MainVlv_ReadyToGoBV3945PreHeatVlv_ReadyToGoBV3946ReHeatVlv_ReadyToGoBV3951AirQuality_PM10.Alrm_RBV3981AirQuality_PM10.Configured_RBV3982AirQuality_PM10.Enable_WBV3986AirQuality_PM10.PrbOk_RBV3990AirQuality_PM25.Alrm_RBV3995AirQuality_PM25.Configured_RBV3996AirQuality_PM25.Enable_WBV4000AirQuality_PM25.PrbOk_RBV4007SanificationDevice.Val_WBV4008SanificationDevice.Val_Hw_RBV4012SanificationDevice.Enable_WBV4013SanificationDevice.Configured_RBV3968Al_AirQuality_PM10.ActiveBV3969Al_AirQuality_PM25.ActiveBV3958Sanification.SanificationDevice_IO_CfgWarnBV3960Regulation.QualityAirDevNotSelBV3970Al_SanificationWarn.ActiveBV3971Al_WrkHrs_SanificationDevice.ActiveBV4038PurgeOnBV4039SanificationDeviceOvld.Val_Hw_RBV4040SanificationDeviceOvld.Configured_RBV4041SanificationDeviceOvld.Val_RBV4042FC_ActBV4043FH_ActBV4071Al_WrkHrs_SupplyFan_2.ActiveBV4072Al_WrkHrs_SupplyFan_3.ActiveBV4073Al_WrkHrs_SupplyFan_4.ActiveBV4074Al_WrkHrs_ReturnFan_2.ActiveBV4075Al_WrkHrs_ReturnFan_3.ActiveBV4076Al_WrkHrs_ReturnFan_4.ActiveBV4286SupplyFan_FireSmokeAlrm_ActBV4287RetFan_FireSmokeAlrm_ActBV4330Al_SupplyFanInv.ActiveBV4331Al_RetFanInv.ActiveBV4332Al_SupplyDampSw.ActiveBV4333Al_RetDampSw.ActiveBV4334Al_FreshAirDampSw.ActiveBV4335Al_ExhAirDampSw.ActiveBV4336Al_MixAirDampSw.ActiveBV4337Al_HumiSteam_Offline.ActiveBV4338Al_HumiSteam_Generic.ActiveBV4362SummerWinterBV4363MainCoil_CoolHeatBV4364MainCoilCoolHeat_Din.Configured_RBV4365MainCoilCoolHeat_Din.Enable_WBV4366MainCoilCoolHeat_Din.Val_RBV4368HumDehum_ModeBV4377GenericAin1.Enable_WBV4378GenericAin1.Configured_RBV4379GenericAin1.PrbOk_RBV4380GenericAin1.Alrm_RBV4391GenericAin2.Enable_WBV4392GenericAin2.Configured_RBV4393GenericAin2.PrbOk_RBV4394GenericAin2.Alrm_RBV4405GenericAin3.Enable_WBV4406GenericAin3.Configured_RBV4407GenericAin3.PrbOk_RBV4408GenericAin3.Alrm_RBV4419GenericAin4.Enable_WBV4420GenericAin4.Configured_RBV4421GenericAin4.PrbOk_RBV4422GenericAin4.Alrm_RBV4433GenericAin5.Enable_WBV4434GenericAin5.Configured_RBV4435GenericAin5.PrbOk_RBV4436GenericAin5.Alrm_RBV4448GenericDin1.Val_Hw_RBV4449GenericDin1.Enable_WBV4450GenericDin1.Configured_RBV4451GenericDin1.Val_RBV4455GenericDin2.Val_Hw_RBV4456GenericDin2.Enable_WBV4457GenericDin2.Configured_RBV4458GenericDin2.Val_RBV4462GenericDin3.Val_Hw_RBV4463GenericDin3.Enable_WBV4464GenericDin3.Configured_RBV4465GenericDin3.Val_RBV4469GenericDin4.Val_Hw_RBV4470GenericDin4.Enable_WBV4471GenericDin4.Configured_RBV4472GenericDin4.Val_RBV4476GenericDin5.Val_Hw_RBV4477GenericDin5.Enable_WBV4478GenericDin5.Configured_RBV4479GenericDin5.Val_RBV4487Al_GenericAin1.ActiveBV4488Al_GenericAin2.ActiveBV4489Al_GenericAin3.ActiveBV4490Al_GenericAin4.ActiveBV4491Al_GenericAin5.ActiveBV4492Al_GenericDin1.ActiveBV4493Al_GenericDin2.ActiveBV4494Al_GenericDin3.ActiveBV4495Al_GenericDin4.ActiveBV4496Al_GenericDin5.ActiveBV4517OA_Vlv_Open.Val_Hw_RBV4518OA_Vlv_Open.Val_WBV4519OA_Vlv_Open.Enable_WBV4520OA_Vlv_Open.Configured_RBV4521OA_Vlv_Close.Val_Hw_RBV4522OA_Vlv_Close.Val_WBV4523OA_Vlv_Close.Enable_WBV4524OA_Vlv_Close.Configured_RBV4525OA_Coil_EnabledBV4526Al_WrkHrs_OA_CoilAout.ActiveBV4527Al_WrkHrs_OA_CoilStep1.ActiveBV4528Al_WrkHrs_OA_CoilStep2.ActiveBV4529Al_WrkHrs_OA_CoilStep3.ActiveBV4530Al_WrkHrs_OA_CoilStep4.ActiveBV4531Warn_OA_CoilTOutOfRange.ActiveBV4532Coils.OA_Coil_FloatVlvBV4533OA_Vlv_ReadyToGoPIV1524Scheduler_OnOffUnit.BMS_UnitProfilePIV1525Scheduler_Cfg.Prg[0].Event[0].HoursPIV1526Scheduler_Cfg.Prg[0].Event[0].MinsPIV1527Scheduler_Cfg.Prg[0].Event[0].ModePIV1528Scheduler_Cfg.Prg[0].Event[1].HoursPIV1529Scheduler_Cfg.Prg[0].Event[1].MinsPIV1530Scheduler_Cfg.Prg[0].Event[1].ModePIV1531Scheduler_Cfg.Prg[0].Event[2].HoursPIV1532Scheduler_Cfg.Prg[0].Event[2].MinsPIV1533Scheduler_Cfg.Prg[0].Event[2].ModePIV1534Scheduler_Cfg.Prg[0].Event[3].HoursPIV1535Scheduler_Cfg.Prg[0].Event[3].MinsPIV1536Scheduler_Cfg.Prg[0].Event[3].ModePIV1537Scheduler_Cfg.Prg[0].Event[4].HoursPIV1538Scheduler_Cfg.Prg[0].Event[4].MinsPIV1539Scheduler_Cfg.Prg[0].Event[4].ModePIV1540Scheduler_Cfg.Prg[0].Event[5].HoursPIV1541Scheduler_Cfg.Prg[0].Event[5].MinsPIV1542Scheduler_Cfg.Prg[0].Event[5].ModePIV1543Scheduler_Cfg.Prg[0].Event[6].HoursPIV1544Scheduler_Cfg.Prg[0].Event[6].MinsPIV1545Scheduler_Cfg.Prg[0].Event[6].ModePIV1546Scheduler_Cfg.Prg[0].Event[7].HoursPIV1547Scheduler_Cfg.Prg[0].Event[7].MinsPIV1548Scheduler_Cfg.Prg[0].Event[7].ModePIV1549Scheduler_Cfg.Prg[0].Event[8].HoursPIV1550Scheduler_Cfg.Prg[0].Event[8].MinsPIV1551Scheduler_Cfg.Prg[0].Event[8].ModePIV1552Scheduler_Cfg.Prg[0].Event[9].HoursPIV1553Scheduler_Cfg.Prg[0].Event[9].MinsPIV1554Scheduler_Cfg.Prg[0].Event[9].ModePIV1555Scheduler_Cfg.Prg[1].Event[0].HoursPIV1556Scheduler_Cfg.Prg[1].Event[0].MinsPIV1557Scheduler_Cfg.Prg[1].Event[0].ModePIV1558Scheduler_Cfg.Prg[1].Event[1].HoursPIV1559Scheduler_Cfg.Prg[1].Event[1].MinsPIV1560Scheduler_Cfg.Prg[1].Event[1].ModePIV1561Scheduler_Cfg.Prg[1].Event[2].HoursPIV1562Scheduler_Cfg.Prg[1].Event[2].MinsPIV1563Scheduler_Cfg.Prg[1].Event[2].ModePIV1564Scheduler_Cfg.Prg[1].Event[3].HoursPIV1565Scheduler_Cfg.Prg[1].Event[3].MinsPIV1566Scheduler_Cfg.Prg[1].Event[3].ModePIV1567Scheduler_Cfg.Prg[1].Event[4].HoursPIV1568Scheduler_Cfg.Prg[1].Event[4].MinsPIV1569Scheduler_Cfg.Prg[1].Event[4].ModePIV1570Scheduler_Cfg.Prg[1].Event[5].HoursPIV1571Scheduler_Cfg.Prg[1].Event[5].MinsPIV1572Scheduler_Cfg.Prg[1].Event[5].ModePIV1573Scheduler_Cfg.Prg[1].Event[6].HoursPIV1574Scheduler_Cfg.Prg[1].Event[6].MinsPIV1575Scheduler_Cfg.Prg[1].Event[6].ModePIV1576Scheduler_Cfg.Prg[1].Event[7].HoursPIV1577Scheduler_Cfg.Prg[1].Event[7].MinsPIV1578Scheduler_Cfg.Prg[1].Event[7].ModePIV1579Scheduler_Cfg.Prg[1].Event[8].HoursPIV1580Scheduler_Cfg.Prg[1].Event[8].MinsPIV1581Scheduler_Cfg.Prg[1].Event[8].ModePIV1582Scheduler_Cfg.Prg[1].Event[9].HoursPIV1583Scheduler_Cfg.Prg[1].Event[9].MinsPIV1584Scheduler_Cfg.Prg[1].Event[9].ModePIV1585Scheduler_Cfg.Prg[2].Event[0].HoursPIV1586Scheduler_Cfg.Prg[2].Event[0].MinsPIV1587Scheduler_Cfg.Prg[2].Event[0].ModePIV1588Scheduler_Cfg.Prg[2].Event[1].HoursPIV1589Scheduler_Cfg.Prg[2].Event[1].MinsPIV1590Scheduler_Cfg.Prg[2].Event[1].ModePIV1591Scheduler_Cfg.Prg[2].Event[2].HoursPIV1592Scheduler_Cfg.Prg[2].Event[2].MinsPIV1593Scheduler_Cfg.Prg[2].Event[2].ModePIV1594Scheduler_Cfg.Prg[2].Event[3].HoursPIV1595Scheduler_Cfg.Prg[2].Event[3].MinsPIV1596Scheduler_Cfg.Prg[2].Event[3].ModePIV1597Scheduler_Cfg.Prg[2].Event[4].HoursPIV1598Scheduler_Cfg.Prg[2].Event[4].MinsPIV1599Scheduler_Cfg.Prg[2].Event[4].ModePIV1600Scheduler_Cfg.Prg[2].Event[5].HoursPIV1601Scheduler_Cfg.Prg[2].Event[5].MinsPIV1602Scheduler_Cfg.Prg[2].Event[5].ModePIV1603Scheduler_Cfg.Prg[2].Event[6].HoursPIV1604Scheduler_Cfg.Prg[2].Event[6].MinsPIV1605Scheduler_Cfg.Prg[2].Event[6].ModePIV1606Scheduler_Cfg.Prg[2].Event[7].HoursPIV1607Scheduler_Cfg.Prg[2].Event[7].MinsPIV1608Scheduler_Cfg.Prg[2].Event[7].ModePIV1609Scheduler_Cfg.Prg[2].Event[8].HoursPIV1610Scheduler_Cfg.Prg[2].Event[8].MinsPIV1611Scheduler_Cfg.Prg[2].Event[8].ModePIV1612Scheduler_Cfg.Prg[2].Event[9].HoursPIV1613Scheduler_Cfg.Prg[2].Event[9].MinsPIV1614Scheduler_Cfg.Prg[2].Event[9].ModePIV1615Scheduler_Cfg.Prg[3].Event[0].HoursPIV1616Scheduler_Cfg.Prg[3].Event[0].MinsPIV1617Scheduler_Cfg.Prg[3].Event[0].ModePIV1618Scheduler_Cfg.Prg[3].Event[1].HoursPIV1619Scheduler_Cfg.Prg[3].Event[1].MinsPIV1620Scheduler_Cfg.Prg[3].Event[1].ModePIV1621Scheduler_Cfg.Prg[3].Event[2].HoursPIV1622Scheduler_Cfg.Prg[3].Event[2].MinsPIV1623Scheduler_Cfg.Prg[3].Event[2].ModePIV1624Scheduler_Cfg.Prg[3].Event[3].HoursPIV1625Scheduler_Cfg.Prg[3].Event[3].MinsPIV1626Scheduler_Cfg.Prg[3].Event[3].ModePIV1627Scheduler_Cfg.Prg[3].Event[4].HoursPIV1628Scheduler_Cfg.Prg[3].Event[4].MinsPIV1629Scheduler_Cfg.Prg[3].Event[4].ModePIV1630Scheduler_Cfg.Prg[3].Event[5].HoursPIV1631Scheduler_Cfg.Prg[3].Event[5].MinsPIV1632Scheduler_Cfg.Prg[3].Event[5].ModePIV1633Scheduler_Cfg.Prg[3].Event[6].HoursPIV1634Scheduler_Cfg.Prg[3].Event[6].MinsPIV1635Scheduler_Cfg.Prg[3].Event[6].ModePIV1636Scheduler_Cfg.Prg[3].Event[7].HoursPIV1637Scheduler_Cfg.Prg[3].Event[7].MinsPIV1638Scheduler_Cfg.Prg[3].Event[7].ModePIV1639Scheduler_Cfg.Prg[3].Event[8].HoursPIV1640Scheduler_Cfg.Prg[3].Event[8].MinsPIV1641Scheduler_Cfg.Prg[3].Event[8].ModePIV1642Scheduler_Cfg.Prg[3].Event[9].HoursPIV1643Scheduler_Cfg.Prg[3].Event[9].MinsPIV1644Scheduler_Cfg.Prg[3].Event[9].ModePIV1651Scheduler_Cfg.SDays[2].DayPIV1652Scheduler_Cfg.SDays[2].ModePIV1653Scheduler_Cfg.SDays[2].MonthPIV1654Scheduler_Cfg.SDays[3].DayPIV1655Scheduler_Cfg.SDays[3].ModePIV1656Scheduler_Cfg.SDays[3].MonthPIV1657Scheduler_Cfg.SDays[4].DayPIV1658Scheduler_Cfg.SDays[4].ModePIV1659Scheduler_Cfg.SDays[4].MonthPIV1660Scheduler_Cfg.SDays[5].DayPIV1661Scheduler_Cfg.SDays[5].ModePIV1662Scheduler_Cfg.SDays[5].MonthPIV1663Scheduler_Cfg.SDays[6].DayPIV1664Scheduler_Cfg.SDays[6].ModePIV1665Scheduler_Cfg.SDays[6].MonthPIV1666Scheduler_Cfg.SDays[7].DayPIV1667Scheduler_Cfg.SDays[7].ModePIV1668Scheduler_Cfg.SDays[7].MonthPIV1669Scheduler_Cfg.SDays[8].DayPIV1670Scheduler_Cfg.SDays[8].ModePIV1671Scheduler_Cfg.SDays[8].MonthPIV1672Scheduler_Cfg.SDays[9].DayPIV1673Scheduler_Cfg.SDays[9].ModePIV1674Scheduler_Cfg.SDays[9].MonthPIV1675Scheduler_Cfg.SDays[10].DayPIV1676Scheduler_Cfg.SDays[10].ModePIV1677Scheduler_Cfg.SDays[10].MonthPIV1678Scheduler_Cfg.SDays[11].DayPIV1679Scheduler_Cfg.SDays[11].ModePIV1680Scheduler_Cfg.SDays[11].MonthPIV1681Scheduler_Cfg.SDays[12].DayPIV1682Scheduler_Cfg.SDays[12].ModePIV1683Scheduler_Cfg.SDays[12].MonthPIV1684Scheduler_Cfg.SDays[13].DayPIV1685Scheduler_Cfg.SDays[13].ModePIV1686Scheduler_Cfg.SDays[13].MonthPIV1687Scheduler_Cfg.SDays[14].DayPIV1688Scheduler_Cfg.SDays[14].ModePIV1689Scheduler_Cfg.SDays[14].MonthPIV1690Scheduler_Cfg.Vac[0].EndDayPIV1691Scheduler_Cfg.Vac[0].EndMonthPIV1692Scheduler_Cfg.Vac[0].ModePIV1693Scheduler_Cfg.Vac[0].StartDayPIV1694Scheduler_Cfg.Vac[0].StartMonthPIV1695Scheduler_Cfg.Vac[1].EndDayPIV1696Scheduler_Cfg.Vac[1].EndMonthPIV1697Scheduler_Cfg.Vac[1].ModePIV1698Scheduler_Cfg.Vac[1].StartDayPIV1699Scheduler_Cfg.Vac[1].StartMonthPIV1700Scheduler_Cfg.Vac[2].EndDayPIV1701Scheduler_Cfg.Vac[2].EndMonthPIV1702Scheduler_Cfg.Vac[2].ModePIV1703Scheduler_Cfg.Vac[2].StartDayPIV1704Scheduler_Cfg.Vac[2].StartMonthPIV1705Scheduler_Cfg.WkDays[0]PIV1706Scheduler_Cfg.WkDays[1]PIV1707Scheduler_Cfg.WkDays[2]PIV1708Scheduler_Cfg.WkDays[3]PIV1709Scheduler_Cfg.WkDays[4]PIV1710Scheduler_Cfg.WkDays[5]PIV1711Scheduler_Cfg.WkDays[6]PIV1712GeneralMng.RTC_BMS.DayPIV1713GeneralMng.RTC_BMS.MonthPIV1714GeneralMng.RTC_BMS.YearAV1715CoilRegOffsetPIV1716SupplyTemp.Board_RWPIV1717SupplyTemp.Ch_Id_RWPIV1718SupplyTemp.Ch_Type_RWAV1719SupplyTemp.MinVal_RWAV1720SupplyTemp.MaxVal_RWAV1721SupplyTemp.Offset_RWPIV1722SupplyTemp.ChFilter_RWPIV1723SupplyHum.Board_RWPIV1724SupplyHum.Ch_Id_RWPIV1725SupplyHum.Ch_Type_RWAV1726SupplyHum.MinVal_RWAV1727SupplyHum.MaxVal_RWAV1728SupplyHum.Offset_RWPIV1729SupplyHum.ChFilter_RWPIV1730RetTemp.Board_RWPIV1731RetTemp.Ch_Id_RWPIV1732RetTemp.Ch_Type_RWAV1733RetTemp.MinVal_RWAV1734RetTemp.MaxVal_RWAV1735RetTemp.Offset_RWPIV1736RetTemp.ChFilter_RWPIV1737RetHum.Board_RWPIV1738RetHum.Ch_Id_RWPIV1739RetHum.Ch_Type_RWAV1740RetHum.MinVal_RWAV1741RetHum.MaxVal_RWAV1742RetHum.Offset_RWPIV1743RetHum.ChFilter_RWPIV1744RoomTemp.Board_RWPIV1745RoomTemp.Ch_Id_RWPIV1746RoomTemp.Ch_Type_RWAV1747RoomTemp.MinVal_RWAV1748RoomTemp.MaxVal_RWAV1749RoomTemp.Offset_RWPIV1750RoomTemp.ChFilter_RWPIV1751RoomHum.Board_RWPIV1752RoomHum.Ch_Id_RWPIV1753RoomHum.Ch_Type_RWAV1754RoomHum.MinVal_RWAV1755RoomHum.MaxVal_RWAV1756RoomHum.Offset_RWPIV1757RoomHum.ChFilter_RWPIV1758ExtTemp.Board_RWPIV1759ExtTemp.Ch_Id_RWPIV1760ExtTemp.Ch_Type_RWAV1761ExtTemp.MinVal_RWAV1762ExtTemp.MaxVal_RWAV1763ExtTemp.Offset_RWPIV1764ExtTemp.ChFilter_RWPIV1765ExtHum.Board_RWPIV1766ExtHum.Ch_Id_RWPIV1767ExtHum.Ch_Type_RWAV1768ExtHum.MinVal_RWAV1769ExtHum.MaxVal_RWAV1770ExtHum.Offset_RWPIV1771ExtHum.ChFilter_RWPIV1772ExhTemp.Board_RWPIV1773ExhTemp.Ch_Id_RWPIV1774ExhTemp.Ch_Type_RWAV1775ExhTemp.MinVal_RWAV1776ExhTemp.MaxVal_RWAV1777ExhTemp.Offset_RWPIV1778ExhTemp.ChFilter_RWPIV1779ExhHum.Board_RWPIV1780ExhHum.Ch_Id_RWPIV1781ExhHum.Ch_Type_RWAV1782ExhHum.MinVal_RWAV1783ExhHum.MaxVal_RWAV1784ExhHum.Offset_RWPIV1785ExhHum.ChFilter_RWPIV1786AFreezeTemp.Board_RWPIV1787AFreezeTemp.Ch_Id_RWPIV1788AFreezeTemp.Ch_Type_RWAV1789AFreezeTemp.MinVal_RWAV1790AFreezeTemp.MaxVal_RWAV1791AFreezeTemp.Offset_RWPIV1792AFreezeTemp.ChFilter_RWPIV1793SatTemp.Board_RWPIV1794SatTemp.Ch_Id_RWPIV1795SatTemp.Ch_Type_RWAV1796SatTemp.MinVal_RWAV1797SatTemp.MaxVal_RWAV1798SatTemp.Offset_RWPIV1799SatTemp.ChFilter_RWPIV1800SatHum.Board_RWPIV1801SatHum.Ch_Id_RWPIV1802SatHum.Ch_Type_RWAV1803SatHum.MinVal_RWAV1804SatHum.MaxVal_RWAV1805SatHum.Offset_RWPIV1806SatHum.ChFilter_RWPIV1807OA_Temp.Board_RWPIV1808OA_Temp.Ch_Id_RWPIV1809OA_Temp.Ch_Type_RWAV1810OA_Temp.MinVal_RWAV1811OA_Temp.MaxVal_RWAV1812OA_Temp.Offset_RWPIV1813OA_Temp.ChFilter_RWPIV1814SupplyAirP.Board_RWPIV1815SupplyAirP.Ch_Id_RWPIV1816SupplyAirP.Ch_Type_RWAV1817SupplyAirP.MinVal_RWAV1818SupplyAirP.MaxVal_RWAV1819SupplyAirP.Offset_RWPIV1820SupplyAirP.ChFilter_RWPIV1821RetAirP.Board_RWPIV1822RetAirP.Ch_Id_RWPIV1823RetAirP.Ch_Type_RWAV1824RetAirP.MinVal_RWAV1825RetAirP.MaxVal_RWAV1826RetAirP.Offset_RWPIV1827RetAirP.ChFilter_RWPIV1828AirQuality_CO2.Board_RWPIV1829AirQuality_CO2.Ch_Id_RWPIV1830AirQuality_CO2.Ch_Type_RWAV1831AirQuality_CO2.MinVal_RWAV1832AirQuality_CO2.MaxVal_RWAV1833AirQuality_CO2.Offset_RWPIV1834AirQuality_CO2.ChFilter_RWPIV1835AirQuality_VOC.Board_RWPIV1836AirQuality_VOC.Ch_Id_RWPIV1837AirQuality_VOC.Ch_Type_RWAV1838AirQuality_VOC.MinVal_RWAV1839AirQuality_VOC.MaxVal_RWAV1840AirQuality_VOC.Offset_RWPIV1841AirQuality_VOC.ChFilter_RWPIV1842DscgP.Board_RWPIV1843DscgP.Ch_Id_RWPIV1844DscgP.Ch_Type_RWAV1845DscgP.MinVal_RWAV1846DscgP.MaxVal_RWAV1847DscgP.Offset_RWPIV1848DscgP.ChFilter_RWPIV1849DscgT.Board_RWPIV1850DscgT.Ch_Id_RWPIV1851DscgT.Ch_Type_RWAV1852DscgT.MinVal_RWAV1853DscgT.MaxVal_RWAV1854DscgT.Offset_RWPIV1855DscgT.ChFilter_RWPIV1856SuctP.Board_RWPIV1857SuctP.Ch_Id_RWPIV1858SuctP.Ch_Type_RWAV1859SuctP.MinVal_RWAV1860SuctP.MaxVal_RWAV1861SuctP.Offset_RWPIV1862SuctP.ChFilter_RWPIV1863SuctT.Board_RWPIV1864SuctT.Ch_Id_RWPIV1865SuctT.Ch_Type_RWAV1866SuctT.MinVal_RWAV1867SuctT.MaxVal_RWAV1868SuctT.Offset_RWPIV1869SuctT.ChFilter_RWPIV1870OA_CoilWaterTemp.Board_RWPIV1871OA_CoilWaterTemp.Ch_Id_RWPIV1872OA_CoilWaterTemp.Ch_Type_RWAV1873OA_CoilWaterTemp.MinVal_RWAV1874OA_CoilWaterTemp.MaxVal_RWAV1875OA_CoilWaterTemp.Offset_RWPIV1876OA_CoilWaterTemp.ChFilter_RWPIV1877PreHeatCoilWaterTemp.Board_RWPIV1878PreHeatCoilWaterTemp.Ch_Id_RWPIV1879PreHeatCoilWaterTemp.Ch_Type_RWAV1880PreHeatCoilWaterTemp.MinVal_RWAV1881PreHeatCoilWaterTemp.MaxVal_RWAV1882PreHeatCoilWaterTemp.Offset_RWPIV1883PreHeatCoilWaterTemp.ChFilter_RWPIV1884MainCoilWaterTemp.Board_RWPIV1885MainCoilWaterTemp.Ch_Id_RWPIV1886MainCoilWaterTemp.Ch_Type_RWAV1887MainCoilWaterTemp.MinVal_RWAV1888MainCoilWaterTemp.MaxVal_RWAV1889MainCoilWaterTemp.Offset_RWPIV1890MainCoilWaterTemp.ChFilter_RWPIV1891ReHeatCoilWaterTemp.Board_RWPIV1892ReHeatCoilWaterTemp.Ch_Id_RWPIV1893ReHeatCoilWaterTemp.Ch_Type_RWAV1894ReHeatCoilWaterTemp.MinVal_RWAV1895ReHeatCoilWaterTemp.MaxVal_RWAV1896ReHeatCoilWaterTemp.Offset_RWPIV1897ReHeatCoilWaterTemp.ChFilter_RWPIV1898AuxPrb_1.Board_RWPIV1899AuxPrb_1.Ch_Id_RWPIV1900AuxPrb_1.Ch_Type_RWAV1901AuxPrb_1.MinVal_RWAV1902AuxPrb_1.MaxVal_RWAV1903AuxPrb_1.Offset_RWPIV1904AuxPrb_1.ChFilter_RWPIV1905AuxPrb_2.Board_RWPIV1906AuxPrb_2.Ch_Id_RWPIV1907AuxPrb_2.Ch_Type_RWAV1908AuxPrb_2.MinVal_RWAV1909AuxPrb_2.MaxVal_RWAV1910AuxPrb_2.Offset_RWPIV1911AuxPrb_2.ChFilter_RWPIV1912AuxPrb_3.Board_RWPIV1913AuxPrb_3.Ch_Id_RWPIV1914AuxPrb_3.Ch_Type_RWAV1915AuxPrb_3.MinVal_RWAV1916AuxPrb_3.MaxVal_RWAV1917AuxPrb_3.Offset_RWPIV1918AuxPrb_3.ChFilter_RWPIV1919AuxPrb_4.Board_RWPIV1920AuxPrb_4.Ch_Id_RWPIV1921AuxPrb_4.Ch_Type_RWAV1922AuxPrb_4.MinVal_RWAV1923AuxPrb_4.MaxVal_RWAV1924AuxPrb_4.Offset_RWPIV1925AuxPrb_4.ChFilter_RWPIV1926Ain_SetP.Board_RWPIV1927Ain_SetP.Ch_Id_RWPIV1928Ain_SetP.Ch_Type_RWAV1929Ain_SetP.MinVal_RWAV1930Ain_SetP.MaxVal_RWAV1931Ain_SetP.Offset_RWPIV1932Ain_SetP.ChFilter_RWPIV1933SupplyRecoveryTemp.Board_RWPIV1934SupplyRecoveryTemp.Ch_Id_RWPIV1935SupplyRecoveryTemp.Ch_Type_RWAV1936SupplyRecoveryTemp.MinVal_RWAV1937SupplyRecoveryTemp.MaxVal_RWAV1938SupplyRecoveryTemp.Offset_RWPIV1939SupplyRecoveryTemp.ChFilter_RWPIV1940RetRecoveryTemp.Board_RWPIV1941RetRecoveryTemp.Ch_Id_RWPIV1942RetRecoveryTemp.Ch_Type_RWAV1943RetRecoveryTemp.MinVal_RWAV1944RetRecoveryTemp.MaxVal_RWAV1945RetRecoveryTemp.Offset_RWPIV1946RetRecoveryTemp.ChFilter_RWPIV1947HepaFilt_1.Board_RWPIV1948HepaFilt_1.Ch_Id_RWPIV1949HepaFilt_1.Ch_Type_RWAV1950HepaFilt_1.MinVal_RWAV1951HepaFilt_1.MaxVal_RWAV1952HepaFilt_1.Offset_RWPIV1953HepaFilt_1.ChFilter_RWPIV1954HepaFilt_2.Board_RWPIV1955HepaFilt_2.Ch_Id_RWPIV1956HepaFilt_2.Ch_Type_RWAV1957HepaFilt_2.MinVal_RWAV1958HepaFilt_2.MaxVal_RWAV1959HepaFilt_2.Offset_RWPIV1960HepaFilt_2.ChFilter_RWPIV1961SupplyAirFlwSw.Board_RWPIV1962SupplyAirFlwSw.Ch_Id_RWPIV1963RetAirFlwSw.Board_RWPIV1964RetAirFlwSw.Ch_Id_RWPIV1965AirFlwSw.Board_RWPIV1966AirFlwSw.Ch_Id_RWPIV1967AFreezeSw.Board_RWPIV1968AFreezeSw.Ch_Id_RWPIV1969RemOnOff.Board_RWPIV1970RemOnOff.Ch_Id_RWPIV1971SupplyFanOvld_1.Board_RWPIV1972SupplyFanOvld_1.Ch_Id_RWPIV1973RetFanOvld_1.Board_RWPIV1974RetFanOvld_1.Ch_Id_RWPIV1975SupplyFanOvld_2.Board_RWPIV1976SupplyFanOvld_2.Ch_Id_RWPIV1977RetFanOvld_2.Board_RWPIV1978RetFanOvld_2.Ch_Id_RWPIV1979SupplyFanInvAlrm.Board_RWPIV1980SupplyFanInvAlrm.Ch_Id_RWPIV1981RetFanInvAlrm.Board_RWPIV1982RetFanInvAlrm.Ch_Id_RWPIV1983FansOvld.Board_RWPIV1984FansOvld.Ch_Id_RWPIV1985CompOvld.Board_RWPIV1986CompOvld.Ch_Id_RWPIV1987HiPSw.Board_RWPIV1988HiPSw.Ch_Id_RWPIV1989LowPSw.Board_RWPIV1990LowPSw.Ch_Id_RWPIV1991RecoveryOvld.Board_RWPIV1992RecoveryOvld.Ch_Id_RWPIV1993SrsAlrm.Board_RWPIV1994SrsAlrm.Ch_Id_RWPIV1995GenAlrm.Board_RWPIV1996GenAlrm.Ch_Id_RWPIV1997GenWarning.Board_RWPIV1998GenWarning.Ch_Id_RWPIV1999FiltAlrm.Board_RWPIV2000FiltAlrm.Ch_Id_RWPIV2001SupplyFiltAlrm_1.Board_RWPIV2002SupplyFiltAlrm_1.Ch_Id_RWPIV2003SupplyFiltAlrm_2.Board_RWPIV2004SupplyFiltAlrm_2.Ch_Id_RWPIV2005RetFiltAlrm.Board_RWPIV2006RetFiltAlrm.Ch_Id_RWPIV2007HumAlrm.Board_RWPIV2008HumAlrm.Ch_Id_RWPIV2009MainCoilPmp1_Ovld.Board_RWPIV2010MainCoilPmp1_Ovld.Ch_Id_RWPIV2011MainCoilPmp2_Ovld.Board_RWPIV2012MainCoilPmp2_Ovld.Ch_Id_RWPIV2013ReHeatCoilPmp1_Ovld.Board_RWPIV2014ReHeatCoilPmp1_Ovld.Ch_Id_RWPIV2015ReHeatCoilPmp2_Ovld.Board_RWPIV2016ReHeatCoilPmp2_Ovld.Ch_Id_RWPIV2017PreHeatCoilPmp1_Ovld.Board_RWPIV2018PreHeatCoilPmp1_Ovld.Ch_Id_RWPIV2019PreHeatCoilPmp2_Ovld.Board_RWPIV2020PreHeatCoilPmp2_Ovld.Ch_Id_RWPIV2021OA_CoilPmp1_Ovld.Board_RWPIV2022OA_CoilPmp1_Ovld.Ch_Id_RWPIV2023OA_CoilPmp2_Ovld.Board_RWPIV2024OA_CoilPmp2_Ovld.Ch_Id_RWPIV2025FreshAirDampSw.Board_RWPIV2026FreshAirDampSw.Ch_Id_RWPIV2027SupplyDamperSw.Board_RWPIV2028SupplyDamperSw.Ch_Id_RWPIV2029RetDampSw.Board_RWPIV2030RetDampSw.Ch_Id_RWPIV2031MainCoilFlwSw.Board_RWPIV2032MainCoilFlwSw.Ch_Id_RWPIV2033PreHeatCoilFlwSw.Board_RWPIV2034PreHeatCoilFlwSw.Ch_Id_RWPIV2035ReHeatCoilFlwSw.Board_RWPIV2036ReHeatCoilFlwSw.Ch_Id_RWPIV2037OA_CoilFlwSw.Board_RWPIV2038OA_CoilFlwSw.Ch_Id_RWPIV2039RecoveryClogged.Board_RWPIV2040RecoveryClogged.Ch_Id_RWPIV2041ReHeatAlrm.Board_RWPIV2042ReHeatAlrm.Ch_Id_RWPIV2043PreHeatAlrm.Board_RWPIV2044PreHeatAlrm.Ch_Id_RWPIV2045MainHeatCoilAlrm.Board_RWPIV2046MainHeatCoilAlrm.Ch_Id_RWPIV2047OA_CoilAlrm.Board_RWPIV2048OA_CoilAlrm.Ch_Id_RWPIV2049DoorSw.Board_RWPIV2050DoorSw.Ch_Id_RWPIV2051FireSmokeAlrm.Board_RWPIV2052FireSmokeAlrm.Ch_Id_RWPIV2053FiremanOverrideSw.Board_RWPIV2054FiremanOverrideSw.Ch_Id_RWPIV2055SummerWinterModeByDin.Board_RWPIV2056SummerWinterModeByDin.Ch_Id_RWPIV2057Din_SetP.Board_RWPIV2058Din_SetP.Ch_Id_RWPIV2059Eco_Mode.Board_RWPIV2060Eco_Mode.Ch_Id_RWPIV2061PreComf_Mode.Board_RWPIV2062PreComf_Mode.Ch_Id_RWPIV2063Comf_Mode.Board_RWPIV2064Comf_Mode.Ch_Id_RWPIV2065AuxDin_1.Board_RWPIV2066AuxDin_1.Ch_Id_RWPIV2067AuxDin_2.Board_RWPIV2068AuxDin_2.Ch_Id_RWPIV2069AuxDin_3.Board_RWPIV2070AuxDin_3.Ch_Id_RWPIV2071AuxDin_4.Board_RWPIV2072AuxDin_4.Ch_Id_RWPIV2073DfrHeatExch_Din.Board_RWPIV2074DfrHeatExch_Din.Ch_Id_RWPIV2075BypassDamp_Dout.Board_RWPIV2076BypassDamp_Dout.Ch_Id_RWPIV2077BypassDamp_Dout.T_On_RWPIV2078BypassDamp_Dout.T_Off_RWPIV2079BypassDamp_Dout.Ch_Type_RWPIV2080BypassDamp_Open.Board_RWPIV2081BypassDamp_Open.Ch_Id_RWPIV2082BypassDamp_Open.T_On_RWPIV2083BypassDamp_Open.T_Off_RWPIV2084BypassDamp_Open.Ch_Type_RWPIV2085BypassDamp_Close.Board_RWPIV2086BypassDamp_Close.Ch_Id_RWPIV2087BypassDamp_Close.T_On_RWPIV2088BypassDamp_Close.T_Off_RWPIV2089BypassDamp_Close.Ch_Type_RWPIV2090FreshAirDamp_Dout.Board_RWPIV2091FreshAirDamp_Dout.Ch_Id_RWPIV2092FreshAirDamp_Dout.T_On_RWPIV2093FreshAirDamp_Dout.T_Off_RWPIV2094FreshAirDamp_Dout.Ch_Type_RWPIV2095ExhAirDamp_Dout.Board_RWPIV2096ExhAirDamp_Dout.Ch_Id_RWPIV2097ExhAirDamp_Dout.T_On_RWPIV2098ExhAirDamp_Dout.T_Off_RWPIV2099ExhAirDamp_Dout.Ch_Type_RWPIV2100MixingDamp_Dout.Board_RWPIV2101MixingDamp_Dout.Ch_Id_RWPIV2102MixingDamp_Dout.T_On_RWPIV2103MixingDamp_Dout.T_Off_RWPIV2104MixingDamp_Dout.Ch_Type_RWPIV2105SupplyAirDamp_Dout.Board_RWPIV2106SupplyAirDamp_Dout.Ch_Id_RWPIV2107SupplyAirDamp_Dout.T_On_RWPIV2108SupplyAirDamp_Dout.T_Off_RWPIV2109SupplyAirDamp_Dout.Ch_Type_RWPIV2110RetAirDamp_Dout.Board_RWPIV2111RetAirDamp_Dout.Ch_Id_RWPIV2112RetAirDamp_Dout.T_On_RWPIV2113RetAirDamp_Dout.T_Off_RWPIV2114RetAirDamp_Dout.Ch_Type_RWPIV2115MixingDamp_Open.Board_RWPIV2116MixingDamp_Open.Ch_Id_RWPIV2117MixingDamp_Open.T_On_RWPIV2118MixingDamp_Open.T_Off_RWPIV2119MixingDamp_Open.Ch_Type_RWPIV2120MixingDamp_Close.Board_RWPIV2121MixingDamp_Close.Ch_Id_RWPIV2122MixingDamp_Close.T_On_RWPIV2123MixingDamp_Close.T_Off_RWPIV2124MixingDamp_Close.Ch_Type_RWPIV2125SupplyFan_Dout.Board_RWPIV2126SupplyFan_Dout.Ch_Id_RWPIV2127SupplyFan_Dout.T_On_RWPIV2128SupplyFan_Dout.T_Off_RWPIV2129SupplyFan_Dout.Ch_Type_RWPIV2130RetFan_Dout.Board_RWPIV2131RetFan_Dout.Ch_Id_RWPIV2132RetFan_Dout.T_On_RWPIV2133RetFan_Dout.T_Off_RWPIV2134RetFan_Dout.Ch_Type_RWPIV2135SupplyFan2_Dout.Board_RWPIV2136SupplyFan2_Dout.Ch_Id_RWPIV2137SupplyFan2_Dout.T_On_RWPIV2138SupplyFan2_Dout.T_Off_RWPIV2139SupplyFan2_Dout.Ch_Type_RWPIV2140RetFan2_Dout.Board_RWPIV2141RetFan2_Dout.Ch_Id_RWPIV2142RetFan2_Dout.T_On_RWPIV2143RetFan2_Dout.T_Off_RWPIV2144RetFan2_Dout.Ch_Type_RWPIV2145Comp_Dout.Board_RWPIV2146Comp_Dout.Ch_Id_RWPIV2147Comp_Dout.T_On_RWPIV2148Comp_Dout.T_Off_RWPIV2149Comp_Dout.Ch_Type_RWPIV2150RevVlv.Board_RWPIV2151RevVlv.Ch_Id_RWPIV2152RevVlv.T_On_RWPIV2153RevVlv.T_Off_RWPIV2154RevVlv.Ch_Type_RWPIV2155UnitOnOff_Dout.Board_RWPIV2156UnitOnOff_Dout.Ch_Id_RWPIV2157UnitOnOff_Dout.T_On_RWPIV2158UnitOnOff_Dout.T_Off_RWPIV2159UnitOnOff_Dout.Ch_Type_RWPIV2160CoolHeat_Dout.Board_RWPIV2161CoolHeat_Dout.Ch_Id_RWPIV2162CoolHeat_Dout.T_On_RWPIV2163CoolHeat_Dout.T_Off_RWPIV2164CoolHeat_Dout.Ch_Type_RWPIV2167GlobalAlrm_Dout.T_On_RWPIV2168GlobalAlrm_Dout.T_Off_RWPIV2169GlobalAlrm_Dout.Ch_Type_RWPIV2170LightAlrm_Dout.Board_RWPIV2171LightAlrm_Dout.Ch_Id_RWPIV2172LightAlrm_Dout.T_On_RWPIV2173LightAlrm_Dout.T_Off_RWPIV2174LightAlrm_Dout.Ch_Type_RWPIV2175SrsAlrm_Dout.Board_RWPIV2176SrsAlrm_Dout.Ch_Id_RWPIV2177SrsAlrm_Dout.T_On_RWPIV2178SrsAlrm_Dout.T_Off_RWPIV2179SrsAlrm_Dout.Ch_Type_RWPIV2180Humidifier.Board_RWPIV2181Humidifier.Ch_Id_RWPIV2182Humidifier.T_On_RWPIV2183Humidifier.T_Off_RWPIV2184Humidifier.Ch_Type_RWPIV2185AuxOut1_Dout.Board_RWPIV2186AuxOut1_Dout.Ch_Id_RWPIV2187AuxOut1_Dout.T_On_RWPIV2188AuxOut1_Dout.T_Off_RWPIV2189AuxOut1_Dout.Ch_Type_RWPIV2190AuxOut2_Dout.Board_RWPIV2191AuxOut2_Dout.Ch_Id_RWPIV2192AuxOut2_Dout.T_On_RWPIV2193AuxOut2_Dout.T_Off_RWPIV2194AuxOut2_Dout.Ch_Type_RWPIV2195AuxOut3_Dout.Board_RWPIV2196AuxOut3_Dout.Ch_Id_RWPIV2197AuxOut3_Dout.T_On_RWPIV2198AuxOut3_Dout.T_Off_RWPIV2199AuxOut3_Dout.Ch_Type_RWPIV2200AuxOut4_Dout.Board_RWPIV2201AuxOut4_Dout.Ch_Id_RWPIV2202AuxOut4_Dout.T_On_RWPIV2203AuxOut4_Dout.T_Off_RWPIV2204AuxOut4_Dout.Ch_Type_RWPIV2205MainVlv_Open.Board_RWPIV2206MainVlv_Open.Ch_Id_RWPIV2207MainVlv_Open.T_On_RWPIV2208MainVlv_Open.T_Off_RWPIV2209MainVlv_Open.Ch_Type_RWPIV2210PreHeatVlv_Open.Board_RWPIV2211PreHeatVlv_Open.Ch_Id_RWPIV2212PreHeatVlv_Open.T_On_RWPIV2213PreHeatVlv_Open.T_Off_RWPIV2214PreHeatVlv_Open.Ch_Type_RWPIV2215ReHeatVlv_Open.Board_RWPIV2216ReHeatVlv_Open.Ch_Id_RWPIV2217ReHeatVlv_Open.T_On_RWPIV2218ReHeatVlv_Open.T_Off_RWPIV2219ReHeatVlv_Open.Ch_Type_RWPIV2220MainVlv_Close.Board_RWPIV2221MainVlv_Close.Ch_Id_RWPIV2222MainVlv_Close.T_On_RWPIV2223MainVlv_Close.T_Off_RWPIV2224MainVlv_Close.Ch_Type_RWPIV2225PreHeatVlv_Close.Board_RWPIV2226PreHeatVlv_Close.Ch_Id_RWPIV2227PreHeatVlv_Close.T_On_RWPIV2228PreHeatVlv_Close.T_Off_RWPIV2229PreHeatVlv_Close.Ch_Type_RWPIV2230ReHeatVlv_Close.Board_RWPIV2231ReHeatVlv_Close.Ch_Id_RWPIV2232ReHeatVlv_Close.T_On_RWPIV2233ReHeatVlv_Close.T_Off_RWPIV2234ReHeatVlv_Close.Ch_Type_RWPIV2235MainCoil_Step1.Board_RWPIV2236MainCoil_Step1.Ch_Id_RWPIV2237MainCoil_Step1.T_On_RWPIV2238MainCoil_Step1.T_Off_RWPIV2239MainCoil_Step1.Ch_Type_RWPIV2240MainCoil_Step2.Board_RWPIV2241MainCoil_Step2.Ch_Id_RWPIV2242MainCoil_Step2.T_On_RWPIV2243MainCoil_Step2.T_Off_RWPIV2244MainCoil_Step2.Ch_Type_RWPIV2245MainCoil_Step3.Board_RWPIV2246MainCoil_Step3.Ch_Id_RWPIV2247MainCoil_Step3.T_On_RWPIV2248MainCoil_Step3.T_Off_RWPIV2249MainCoil_Step3.Ch_Type_RWPIV2250MainCoil_Step4.Board_RWPIV2251MainCoil_Step4.Ch_Id_RWPIV2252MainCoil_Step4.T_On_RWPIV2253MainCoil_Step4.T_Off_RWPIV2254MainCoil_Step4.Ch_Type_RWPIV2255ReHeatCoil_Step1.Board_RWPIV2256ReHeatCoil_Step1.Ch_Id_RWPIV2257ReHeatCoil_Step1.T_On_RWPIV2258ReHeatCoil_Step1.T_Off_RWPIV2259ReHeatCoil_Step1.Ch_Type_RWPIV2260ReHeatCoil_Step2.Board_RWPIV2261ReHeatCoil_Step2.Ch_Id_RWPIV2262ReHeatCoil_Step2.T_On_RWPIV2263ReHeatCoil_Step2.T_Off_RWPIV2264ReHeatCoil_Step2.Ch_Type_RWPIV2265ReHeatCoil_Step3.Board_RWPIV2266ReHeatCoil_Step3.Ch_Id_RWPIV2267ReHeatCoil_Step3.T_On_RWPIV2268ReHeatCoil_Step3.T_Off_RWPIV2269ReHeatCoil_Step3.Ch_Type_RWPIV2270ReHeatCoil_Step4.Board_RWPIV2271ReHeatCoil_Step4.Ch_Id_RWPIV2272ReHeatCoil_Step4.T_On_RWPIV2273ReHeatCoil_Step4.T_Off_RWPIV2274ReHeatCoil_Step4.Ch_Type_RWPIV2275PreHeatCoil_Step1.Board_RWPIV2276PreHeatCoil_Step1.Ch_Id_RWPIV2277PreHeatCoil_Step1.T_On_RWPIV2278PreHeatCoil_Step1.T_Off_RWPIV2279PreHeatCoil_Step1.Ch_Type_RWPIV2280PreHeatCoil_Step2.Board_RWPIV2281PreHeatCoil_Step2.Ch_Id_RWPIV2282PreHeatCoil_Step2.T_On_RWPIV2283PreHeatCoil_Step2.T_Off_RWPIV2284PreHeatCoil_Step2.Ch_Type_RWPIV2285PreHeatCoil_Step3.Board_RWPIV2286PreHeatCoil_Step3.Ch_Id_RWPIV2287PreHeatCoil_Step3.T_On_RWPIV2288PreHeatCoil_Step3.T_Off_RWPIV2289PreHeatCoil_Step3.Ch_Type_RWPIV2290PreHeatCoil_Step4.Board_RWPIV2291PreHeatCoil_Step4.Ch_Id_RWPIV2292PreHeatCoil_Step4.T_On_RWPIV2293PreHeatCoil_Step4.T_Off_RWPIV2294PreHeatCoil_Step4.Ch_Type_RWPIV2295OA_Coil_Step1.Board_RWPIV2296OA_Coil_Step1.Ch_Id_RWPIV2297OA_Coil_Step1.T_On_RWPIV2298OA_Coil_Step1.T_Off_RWPIV2299OA_Coil_Step1.Ch_Type_RWPIV2300OA_Coil_Step2.Board_RWPIV2301OA_Coil_Step2.Ch_Id_RWPIV2302OA_Coil_Step2.T_On_RWPIV2303OA_Coil_Step2.T_Off_RWPIV2304OA_Coil_Step2.Ch_Type_RWPIV2305OA_Coil_Step3.Board_RWPIV2306OA_Coil_Step3.Ch_Id_RWPIV2307OA_Coil_Step3.T_On_RWPIV2308OA_Coil_Step3.T_Off_RWPIV2309OA_Coil_Step3.Ch_Type_RWPIV2310OA_Coil_Step4.Board_RWPIV2311OA_Coil_Step4.Ch_Id_RWPIV2312OA_Coil_Step4.T_On_RWPIV2313OA_Coil_Step4.T_Off_RWPIV2314OA_Coil_Step4.Ch_Type_RWPIV2315PreHeatPmp_1.Board_RWPIV2316PreHeatPmp_1.Ch_Id_RWPIV2317PreHeatPmp_1.T_On_RWPIV2318PreHeatPmp_1.T_Off_RWPIV2319PreHeatPmp_1.Ch_Type_RWPIV2320PreHeatPmp_2.Board_RWPIV2321PreHeatPmp_2.Ch_Id_RWPIV2322PreHeatPmp_2.T_On_RWPIV2323PreHeatPmp_2.T_Off_RWPIV2324PreHeatPmp_2.Ch_Type_RWPIV2325MainCoilPmp_1.Board_RWPIV2326MainCoilPmp_1.Ch_Id_RWPIV2327MainCoilPmp_1.T_On_RWPIV2328MainCoilPmp_1.T_Off_RWPIV2329MainCoilPmp_1.Ch_Type_RWPIV2330MainCoilPmp_2.Board_RWPIV2331MainCoilPmp_2.Ch_Id_RWPIV2332MainCoilPmp_2.T_On_RWPIV2333MainCoilPmp_2.T_Off_RWPIV2334MainCoilPmp_2.Ch_Type_RWPIV2335ReHeatPmp_1.Board_RWPIV2336ReHeatPmp_1.Ch_Id_RWPIV2337ReHeatPmp_1.T_On_RWPIV2338ReHeatPmp_1.T_Off_RWPIV2339ReHeatPmp_1.Ch_Type_RWPIV2340ReHeatPmp_2.Board_RWPIV2341ReHeatPmp_2.Ch_Id_RWPIV2342ReHeatPmp_2.T_On_RWPIV2343ReHeatPmp_2.T_Off_RWPIV2344ReHeatPmp_2.Ch_Type_RWPIV2345OA_CoilPmp_1.Board_RWPIV2346OA_CoilPmp_1.Ch_Id_RWPIV2347OA_CoilPmp_1.T_On_RWPIV2348OA_CoilPmp_1.T_Off_RWPIV2349OA_CoilPmp_1.Ch_Type_RWPIV2350OA_CoilPmp_2.Board_RWPIV2351OA_CoilPmp_2.Ch_Id_RWPIV2352OA_CoilPmp_2.T_On_RWPIV2353OA_CoilPmp_2.T_Off_RWPIV2354OA_CoilPmp_2.Ch_Type_RWPIV2355FiltAlrm_Dout.Board_RWPIV2356FiltAlrm_Dout.Ch_Id_RWPIV2357FiltAlrm_Dout.T_On_RWPIV2358FiltAlrm_Dout.T_Off_RWPIV2359FiltAlrm_Dout.Ch_Type_RWPIV2360Recovery_Dout.Board_RWPIV2361Recovery_Dout.Ch_Id_RWPIV2362Recovery_Dout.T_On_RWPIV2363Recovery_Dout.T_Off_RWPIV2364Recovery_Dout.Ch_Type_RWPIV2365IEC_Hum_Dout.Board_RWPIV2366IEC_Hum_Dout.Ch_Id_RWPIV2367IEC_Hum_Dout.T_On_RWPIV2368IEC_Hum_Dout.T_Off_RWPIV2369IEC_Hum_Dout.Ch_Type_RWPIV2370SupplyFan_Aout.Board_RWPIV2371SupplyFan_Aout.Ch_Id_RWAV2372SupplyFan_Aout.MinOut_RWAV2373SupplyFan_Aout.MaxOut_RWAV2374SupplyFan_Aout.PulseWidth_RWPIV2375SupplyFan_Aout.Ch_Type_RWPIV2376RetFan_Aout.Board_RWPIV2377RetFan_Aout.Ch_Id_RWAV2378RetFan_Aout.MinOut_RWAV2379RetFan_Aout.MaxOut_RWAV2380RetFan_Aout.PulseWidth_RWPIV2381RetFan_Aout.Ch_Type_RWPIV2382BypassDamp_Aout.Board_RWPIV2383BypassDamp_Aout.Ch_Id_RWAV2384BypassDamp_Aout.MinOut_RWAV2385BypassDamp_Aout.MaxOut_RWAV2386BypassDamp_Aout.PulseWidth_RWPIV2387BypassDamp_Aout.Ch_Type_RWPIV2388MixingDamp_Aout.Board_RWPIV2389MixingDamp_Aout.Ch_Id_RWAV2390MixingDamp_Aout.MinOut_RWAV2391MixingDamp_Aout.MaxOut_RWAV2392MixingDamp_Aout.PulseWidth_RWPIV2393MixingDamp_Aout.Ch_Type_RWPIV2394FreshAirDamp_Aout.Board_RWPIV2395FreshAirDamp_Aout.Ch_Id_RWAV2396FreshAirDamp_Aout.MinOut_RWAV2397FreshAirDamp_Aout.MaxOut_RWAV2398FreshAirDamp_Aout.PulseWidth_RWPIV2399FreshAirDamp_Aout.Ch_Type_RWPIV2400ReHeatCoil_Aout.Board_RWPIV2401ReHeatCoil_Aout.Ch_Id_RWAV2402ReHeatCoil_Aout.MinOut_RWAV2403ReHeatCoil_Aout.MaxOut_RWAV2404ReHeatCoil_Aout.PulseWidth_RWPIV2405ReHeatCoil_Aout.Ch_Type_RWPIV2406PreHeatCoil_Aout.Board_RWPIV2407PreHeatCoil_Aout.Ch_Id_RWAV2408PreHeatCoil_Aout.MinOut_RWAV2409PreHeatCoil_Aout.MaxOut_RWAV2410PreHeatCoil_Aout.PulseWidth_RWPIV2411PreHeatCoil_Aout.Ch_Type_RWPIV2412OA_Coil_Aout.Board_RWPIV2413OA_Coil_Aout.Ch_Id_RWAV2414OA_Coil_Aout.MinOut_RWAV2415OA_Coil_Aout.MaxOut_RWAV2416OA_Coil_Aout.PulseWi-dth_RWPIV2417OA_Coil_Aout.Ch_Type_RWPIV2418MainCoil_Aout.Board_RWPIV2419MainCoil_Aout.Ch_Id_RWAV2420MainCoil_Aout.MinOut_RWAV2421MainCoil_Aout.MaxOut_RWAV2422MainCoil_Aout.PulseWidth_RWPIV2423MainCoil_Aout.Ch_Type_RWPIV2424ThrmlWheel_Aout.Board_RWPIV2425ThrmlWheel_Aout.Ch_Id_RWAV2426ThrmlWheel_Aout.MinOut_RWAV2427ThrmlWheel_Aout.MaxOut_RWAV2428ThrmlWheel_Aout.PulseWidth_RWPIV2429ThrmlWheel_Aout.Ch_Type_RWPIV2430Humidifier_Aout.Board_RWPIV2431Humidifier_Aout.Ch_Id_RWAV2432Humidifier_Aout.MinOut_RWAV2433Humidifier_Aout.MaxOut_RWAV2434Humidifier_Aout.PulseWidth_RWPIV2435Humidifier_Aout.Ch_Type_RWPIV2436ExhAirDamp_Aout.Board_RWPIV2437ExhAirDamp_Aout.Ch_Id_RWAV2438ExhAirDamp_Aout.MinOut_RWAV2439ExhAirDamp_Aout.MaxOut_RWAV2440ExhAirDamp_Aout.PulseWidth_RWPIV2441ExhAirDamp_Aout.Ch_Type_RWPIV2442AuxAout_1.Board_RWPIV2443AuxAout_1.Ch_Id_RWAV2444AuxAout_1.MinOut_RWAV2445AuxAout_1.MaxOut_RWAV2446AuxAout_1.PulseWidth_RWPIV2447AuxAout_1.Ch_Type_RWPIV2448AuxAout_2.Board_RWPIV2449AuxAout_2.Ch_Id_RWAV2450AuxAout_2.MinOut_RWAV2451AuxAout_2.MaxOut_RWAV2452AuxAout_2.PulseWidth_RWPIV2453AuxAout_2.Ch_Type_RWPIV2454AuxAout_3.Board_RWPIV2455AuxAout_3.Ch_Id_RWAV2456AuxAout_3.MinOut_RWAV2457AuxAout_3.MaxOut_RWAV2458AuxAout_3.PulseWidth_RWPIV2459AuxAout_3.Ch_Type_RWPIV2460AuxAout_4.Board_RWPIV2461AuxAout_4.Ch_Id_RWAV2462AuxAout_4.MinOut_RWAV2463AuxAout_4.MaxOut_RWAV2464AuxAout_4.PulseWidth_RWPIV2465AuxAout_4.Ch_Type_RWPIV2466IEC_Aout.Board_RWPIV2467IEC_Aout.Ch_Id_RWAV2468IEC_Aout.MinOut_RWAV2469IEC_Aout.MaxOut_RWAV2470IEC_Aout.PulseWidth_RWPIV2471IEC_Aout.Ch_Type_RWPIV2472Recovery_Aout.Board_RWPIV2473Recovery_Aout.Ch_Id_RWAV2474Recovery_Aout.MinOut_RWAV2475Recovery_Aout.MaxOut_RWAV2476Recovery_Aout.PulseWidth_RWPIV2477Recovery_Aout.Ch_Type_RWPIV2478SupplyAirDamp_Aout.Board_RWPIV2479SupplyAirDamp_Aout.Ch_Id_RWAV2480SupplyAirDamp_Aout.MinOut_RWAV2481SupplyAirDamp_Aout.MaxOut_RWAV2482SupplyAirDamp_Aout.PulseWidth_RWPIV2483SupplyAirDamp_Aout.Ch_Type_RWPIV2484RetAirDamp_Aout.Board_RWPIV2485RetAirDamp_Aout.Ch_Id_RWAV2486RetAirDamp_Aout.MinOut_RWAV2487RetAirDamp_Aout.MaxOut_RWAV2488RetAirDamp_Aout.PulseWidth_RWPIV2489RetAirDamp_Aout.Ch_Type_RWAV2493CurrTempSetPAV2496CurrSupplyAirFlwSetPAV2497CurrAirQuality_CO2_SetPAV2498CurrSupplyStaticP_SetPAV2499CurrRetAirFlwSetPAV2500CurrRetStaticP_SetPIV2501STD_UOM_ZONE_UIAV2502AuxReg1_Cfg.SetPAV2503CurrHumSetPPIV2504CoolHeat_Chg_DTPIV2505VarToShow.Ch_TypeAV2506ObjMsk.Min_StaticPressAV2507ObjMsk.Min_AirQualAV2508ObjMsk.Min_RfrgPressAV2509ObjMsk.Min_FlowRateAV2510ObjMsk.Min_AirFlowAV2511ObjMsk.Min_TempAV2512ObjMsk.Min_AoutAV2513ObjMsk.Min_HumAV2514ObjMsk.Min_GenericAV2515ObjMsk.Min_PercentAV2516ObjMsk.Max_StaticPressAV2517ObjMsk.Max_AirQualAV2518ObjMsk.Max_RfrgPressAV2519ObjMsk.Max_FlowRateAV2520ObjMsk.Max_AirFlowAV2521ObjMsk.Max_HumAV2522ObjMsk.Max_TempAV2523ObjMsk.Max_AoutAV2524ObjMsk.Max_GenericAV2525ObjMsk.Max_PercentAV2526ObjMsk.ValOffsetRfrgPressAV2527ObjMsk.ValOffsetFlowRateAV2528ObjMsk.ValOffsetAirFLowAV2529ObjMsk.ValOffsetHumAV2530ObjMsk.ValOffsetTempAV2531ObjMsk.ValOffsetPercentAV2532ObjMsk.ValOffsetAirQualAV2533ObjMsk.ValOffsetStaticPressAV2534ObjMsk.ValOffsetGenericPIV2535VarToShow.ChFilterPIV2536GeneralMng.WizardTypePIV2537GeneralMng.DriveTypIV2538GeneralMng.PreLoadConfNumberIV2539GeneralMng.ExpCfg_Char0IV2540GeneralMng.ExpCfg_Char1IV2541GeneralMng.ExpCfg_Char2IV2542GeneralMng.ExpCfg_Char3IV2543GeneralMng.ExpCfg_Char4IV2544GeneralMng.ExpCfg_Char5IV2545GeneralMng.ExpCfg_Char6IV2546GeneralMng.ExpCfg_Char7IV2547GeneralMng.ExpCfg_Char8IV2548GeneralMng.ExpCfg_Char9IV2549GeneralMng.ExpCfg_Char10BV2550GeneralMng.WizardConfirmAV2551FreshAirDampManModeValPIV2552FreshAirDampManModeVal_OnOffAV2553MixDampManModeValPIV2554MixDampManModeVal_OnOffAV2555ExhAirDampManModeValPIV2556ExhAirDampManModeVal_OnOffAV2557BypassDampManModeValPIV2558BypassDampManModeVal_OnOffPIV2559SupplyFanManModeVal_3SpeedAV2560SupplyFanManModeValPIV2561SupplyFanManModeVal_OnOffPIV2562RetFanManModeVal_3SpeedAV2563RetFanManModeValPIV2564RetFanManModeVal_OnOffAV2565PreHeatCoilManModeValAV2566MainCoilManModeValAV2567ReHeatCoilManModeValAV2568CompManModeValPIV2569CompManModeVal_USINTAV2570HumManModeValAV2571ThermWhlManModeValAV2578UnitSetP.TempSetP.Summer.PreComfortAV2579UnitSetP.TempSetP.Winter.PreComfortAV2584UnitSetP.TempSetP.Summer.ComfortAV2585UnitSetP.TempSetP.Winter.ComfortAV2586TempSetP_MinValAV2587TempSetP_MaxValAV2626UnitSetP.SupplyStaticP_SetP.EconomyAV2629UnitSetP.SupplyStaticP_SetP.PreComfortAV2632UnitSetP.SupplyStaticP_SetP.ComfortAV2633SupplyStaticPressSetP_MinValAV2634SupplyStaticPressSetP_MaxValPIV2635UnitSetP.SupplyAirFlwSetP.EconomyPIV2637UnitSetP.SupplyAirFlwSetP.PreComfortPIV2639UnitSetP.SupplyAirFlwSetP.ComfortPIV2641SupplyAirFlwSetP_MinValPIV2643SupplyAirFlwSetP_MaxValAV2645UnitSetP.AirQuality_CO2_SetP.EconomyAV2647UnitSetP.AirQuality_CO2_SetP.PreComfortAV2650UnitSetP.AirQuality_CO2_SetP.ComfortAV2651AirQualityCO2SetP_MinValAV2652AirQualityCO2SetP_MaxValAV2653UnitSetP.RetStaticP_SetP.EconomyAV2656UnitSetP.RetStaticP_SetP.PreComfortAV2659UnitSetP.RetStaticP_SetP.ComfortAV2660RetStaticPressSetP_MinValAV2661RetStaticPressSetP_MaxValPIV2662UnitSetP.RetAirFlwSetP.EconomyPIV2664UnitSetP.RetAirFlwSetP.PreComfortPIV2666UnitSetP.RetAirFlwSetP.ComfortPIV2668RetAirFlwSetP_MinValPIV2670RetAirFlwSetP_MaxValAV2672UnitSetP.HumSetP.Summer.EconomyAV2673UnitSetP.HumSetP.Winter.EconomyAV2677UnitSetP.HumSetP.Summer.PreComfortAV2678UnitSetP.HumSetP.Winter.PreComfortAV2683UnitSetP.HumSetP.Summer.ComfortAV2684UnitSetP.HumSetP.Winter.ComfortAV2685HumSetP_MinValAV2686HumSetP_MaxValAV2689Regulation.SummerExtTempCompensThrshAV2690Regulation.SummerExtTempCompensDeltaAV2691Regulation.SummerMaxCompensOffsetAV2692Regulation.WinterExtTempCompensThrshAV2693Regulation.WinterExtTempCompensDeltaAV2694Regulation.WinterMaxCompensOffsetIV2695Scheduler_OnOffUnit.FB_SchedulerMskMng_1.PrgNrPIV2696Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[0].HoursPIV2697Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[0].MinsPIV2698Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[0].ModePIV2699Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[1].HoursPIV2700Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[1].MinsPIV2701Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[1].ModePIV2702Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[2].HoursPIV2703Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[2].MinsPIV2704Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[2].ModePIV2705Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[3].HoursPIV2706Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[3].MinsPIV2707Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[3].ModePIV2708Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[4].HoursPIV2709Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[4].MinsPIV2710Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[4].ModePIV2711Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[5].HoursPIV2712Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[5].MinsPIV2713Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[5].ModePIV2714Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[6].HoursPIV2715Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[6].MinsPIV2716Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[6].ModePIV2717Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[7].HoursPIV2718Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[7].MinsPIV2719Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[7].ModePIV2720Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[8].HoursPIV2721Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[8].MinsPIV2722Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[8].ModePIV2723Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[9].HoursPIV2724Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[9].MinsPIV2725Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Prg_T_Msk.Event[9].ModePIV2726Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SaveDataIV2727Scheduler_OnOffUnit.FB_SchedulerMskMng_1.CopyTo_PrgPIV2728Scheduler_OnOffUnit.FB_SchedulerMskMng_1.En_PrgCopyPIV2729Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[0]PIV2730Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[1]PIV2731Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[2]PIV2732Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[3]PIV2733Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[4]PIV2734Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[5]PIV2735Scheduler_OnOffUnit.FB_SchedulerMskMng_1.WkDays_T_Msk[6]PIV2736Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SaveData_DaysPrgPIV2737Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[0].StartDayPIV2738Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[0].StartMonthPIV2739Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[0].EndDayPIV2740Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[0].EndMonthPIV2741Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[0].ModePIV2742Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[1].StartDayPIV2743Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[1].StartMonthPIV2744Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[1].EndDayPIV2745Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[1].EndMonthPIV2746Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[1].ModePIV2747Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[2].StartDayPIV2748Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[2].StartMonthPIV2749Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[2].EndDayPIV2750Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[2].EndMonthPIV2751Scheduler_OnOffUnit.FB_SchedulerMskMng_1.Vac_T_Msk[2].ModePIV2752Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SaveData_VacationsPrgPIV2753Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[0].DayPIV2754Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[0].MonthPIV2755Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[0].ModePIV2756Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[1].DayPIV2757Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[1].MonthPIV2758Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[1].ModePIV2759Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[2].DayPIV2760Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[2].MonthPIV2761Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[2].ModePIV2762Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[3].DayPIV2763Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[3].MonthPIV2764Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[3].ModePIV2765Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[4].DayPIV2766Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[4].MonthPIV2767Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[4].ModePIV2768Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[5].DayPIV2769Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[5].MonthPIV2770Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[5].ModePIV2771Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[6].DayPIV2772Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[6].MonthPIV2773Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[6].ModePIV2774Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[7].DayPIV2775Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[7].MonthPIV2776Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[7].ModePIV2777Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[8].DayPIV2778Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[8].MonthPIV2779Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[8].ModePIV2780Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[9].DayPIV2781Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[9].MonthPIV2782Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[9].ModePIV2783Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[10].DayPIV2784Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[10].MonthPIV2785Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[10].ModePIV2786Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[11].DayPIV2787Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[11].MonthPIV2788Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[11].ModePIV2789Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[12].DayPIV2790Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[12].MonthPIV2791Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[12].ModePIV2792Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[13].DayPIV2793Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[13].MonthPIV2794Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[13].ModePIV2795Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[14].DayPIV2796Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[14].MonthPIV2797Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SDays_T_Msk[14].ModePIV2798Scheduler_OnOffUnit.FB_SchedulerMskMng_1.SaveData_SpecDaysPIV2799Scheduler_OnOffUnit.PartyMode_DTPIV2800FanTypPIV2801HeatExchgTypPIV2802HumTypPIV2803IEC_TypPIV2804PreHeatCoil_TypPIV2805MainCoil_TypPIV2806ReHeatCoil_TypPIV2807FreshAirDampTypPIV2808ExhAirDampTypPIV2809MixingAirDampTypPIV2810SupplyAirDampTypPIV2811RetAirDampTypPIV2812BypassDampTypPIV2813Filters_CfgPIV2814HEPA_Filt_CfgPIV2815RegTypAV2816Regulation.SetP_Offs_KpPIV2817Regulation.SetP_Offs_TiPIV2818UnitHumDehumMode_CfgPIV2819UnitCoolHeatMode_CfgAV2820Regulation.SummerExtTempThrshAV2821Regulation.WinterExtTempThrshAV2822Coil_SummerThrshAV2823Coil_WinterThrshPIV2824Coil_WaterT_OutOfRange_DTPIV2825Coil_WaterT_CfgPIV2826HumDehum_CtrlPrbPIV2827HumDehum_CtrlTypPIV2828Dehum_RegTypAV2829HumDehum_RegBandPIV2830HumDehum_RegChgDTAV2831Regulation.FC_DeltaT_ActAV2832Regulation.FH_DeltaT_ActAV2833FC_PID_Params.KpPIV2834FC_PID_Params.TiAV2835FH_PID_Params.KpPIV2836FH_PID_Params.TiAV2837StateMachine.LowWarmUpThrshExtTempPIV2838StateMachine.StartUpFanActDTPIV2839StateMachine.WarmUpDTPIV2840StateMachine.WarmUpFanActDTPIV2841SupplyFanWarmUpReq_3SpeedAV2842SupplyFanWarmUpReqPIV2843SupplyFanWarmUpReq_OnOffPIV2844RetFanWarmUpReq_3SpeedAV2845RetFanWarmUpReqPIV2846RetFanWarmUpReq_OnOffAV2847PreHeatCoilWarmUpReqAV2848MainCoilWarmUpReqAV2849ReHeatCoilWarmUpReqAV2850ByPassDampWarmUpReqAV2851ThermWhlWarmUpReqPIV2852BypassDampWarmUpReq_OnOffPIV2853SupplyFanSwitchOnReq_3SpeedAV2854SupplyFanSwitchOnReqPIV2855SupplyFanSwitchOnReq_OnOffPIV2856AFreezeTypAV2857Antifreeze.AfreezeTempThrshAV2858Antifreeze.AFreezeEndingDeltaPIV2859Antifreeze.AFreezeWarnDTPIV2860Antifreeze.Al_AFreezeDTAV2861Antifreeze.PrevAFreezeTempThrshAV2862LowSupplyTempThrshPIV2863LowTempAlrmDT_StartUpPIV2864LowTempAlrmDT_RunAV2865HighSupplyTempThrshPIV2866HighTempAlrmDT_StartUpPIV2867HighTempAlrmDT_RunAV2868LowHighSupplyT_KpPIV2869LowHighSupplyT_TiAV2870RegPrbErrFreshAirDampReqPIV2871RegPrbErrFreshAirDampReq_OnOffAV2872RegPrbErrByPassDampReqAV2873RegPrbErrThermWhlReqPIV2874RegPrbErrByPassDampReq_OnOffAV2875RegPrbErrMixDampReqPIV2876RegPrbErrMixDampReq_OnOffAV2877RegPrbErrExhDampReqPIV2878RegPrbErrExhDampReq_OnOffAV2879RegPrbErrSupplyAirDampReqPIV2880RegPrbErrSupplyAirDampReq_OnOffAV2881RegPrbErrRetAirDampReqPIV2882RegPrbErrRetAirDampReq_OnOffAV2883RegPrbErrMainCoilReqAV2884RegPrbErrPreHeatCoilReqAV2885RegPrbErrReHeatCoilReqPIV2886RegPrbErrSupplyFanReq_3SpeedAV2887RegPrbErrSupplyFanReqPIV2888RegPrbErrSupplyFanReq_OnOffPIV2889RegPrbErrRetFanReq_3SpeedAV2890RegPrbErrRetFanReqPIV2891RegPrbErrRetFanReq_OnOffAV2892RegPrbErrCompReqPIV2893RegPrbErrCompReq_OnOffAV2894RegPrbErrHumReqAV2895RegPrbErr_IECReqPIV2897AuxRegTypPIV2898BMS_Offline_MngTypPIV2899BMS_Offline_Alrm_TimeoutPIV2900MaskMng.ValA_Selection_PGDXPIV2901MaskMng.ValB_Selection_PGDXPIV2902GeneralMng.SetWipeMemPIV2903WrkHrs_Unit.WrkHrs_ThrshPIV2904WrkHrs_Unit.WrkHrs_ResPIV2905WrkHrs_SupplyFan.WrkHrs_ThrshPIV2906WrkHrs_SupplyFan.WrkHrs_ResPIV2907WrkHrs_ReturnFan.WrkHrs_ThrshPIV2908WrkHrs_ReturnFan.WrkHrs_ResPIV2909WrkHrs_DirtyFilt.WrkHrs_ThrshPIV2910WrkHrs_DirtyFilt.WrkHrs_ResPIV2911WrkHrs_ThrmlWheel.WrkHrs_ThrshPIV2912WrkHrs_ThrmlWheel.WrkHrs_ResPIV2913WrkHrs_Comp.WrkHrs_ThrshPIV2914WrkHrs_Comp.WrkHrs_ResPIV2915WrkHrs_IEC.WrkHrs_ThrshPIV2916WrkHrs_IEC.WrkHrs_ResPIV2917WrkHrs_Humidifier.WrkHrs_ThrshPIV2918WrkHrs_Humidifier.WrkHrs_ResPIV2919WrkHrs_AuxDout.WrkHrs_ThrshPIV2920WrkHrs_AuxDout.WrkHrs_ResPIV2921WrkHrs_AuxAout.WrkHrs_ThrshPIV2922WrkHrs_AuxAout.WrkHrs_ResPIV2923WrkHrs_MainCoilPmp1.WrkHrs_ThrshPIV2924WrkHrs_MainCoilPmp1.WrkHrs_ResPIV2925WrkHrs_MainCoilPmp2.WrkHrs_ThrshPIV2926WrkHrs_MainCoilPmp2.WrkHrs_ResPIV2927WrkHrs_MainCoilAout.WrkHrs_ThrshPIV2928WrkHrs_MainCoilAout.WrkHrs_ResPIV2929WrkHrs_MainCoilStep1.WrkHrs_ThrshPIV2930WrkHrs_MainCoilStep1.WrkHrs_ResPIV2931WrkHrs_MainCoilStep2.WrkHrs_ThrshPIV2932WrkHrs_MainCoilStep2.WrkHrs_ResPIV2933WrkHrs_MainCoilStep3.WrkHrs_ThrshPIV2934WrkHrs_MainCoilStep3.WrkHrs_ResPIV2935WrkHrs_MainCoilStep4.WrkHrs_ThrshPIV2936WrkHrs_MainCoilStep4.WrkHrs_ResPIV2937WrkHrs_PreHeatCoilPmp1.WrkHrs_ThrshPIV2938WrkHrs_PreHeatCoilPmp1.WrkHrs_ResPIV2939WrkHrs_PreHeatCoilPmp2.WrkHrs_ThrshPIV2940WrkHrs_PreHeatCoilPmp2.WrkHrs_ResPIV2941WrkHrs_PreHeatCoilAout.WrkHrs_ThrshPIV2942WrkHrs_PreHeatCoilAout.WrkHrs_ResPIV2943WrkHrs_PreHeatCoilStep1.WrkHrs_ThrshPIV2944WrkHrs_PreHeatCoilStep1.WrkHrs_ResPIV2945WrkHrs_PreHeatCoilStep2.WrkHrs_ThrshPIV2946WrkHrs_PreHeatCoilStep2.WrkHrs_ResPIV2947WrkHrs_PreHeatCoilStep3.WrkHrs_ThrshPIV2948WrkHrs_PreHeatCoilStep3.WrkHrs_ResPIV2949WrkHrs_PreHeatCoilStep4.WrkHrs_ThrshPIV2950WrkHrs_PreHeatCoilStep4.WrkHrs_ResPIV2951WrkHrs_ReHeatCoilPmp1.WrkHrs_ThrshPIV2952WrkHrs_ReHeatCoilPmp1.WrkHrs_ResPIV2953WrkHrs_ReHeatCoilPmp2.WrkHrs_ThrshPIV2954WrkHrs_ReHeatCoilPmp2.WrkHrs_ResPIV2955WrkHrs_ReHeatCoilAout.WrkHrs_ThrshPIV2956WrkHrs_ReHeatCoilAout.WrkHrs_ResPIV2957WrkHrs_ReHeatCoilStep1.WrkHrs_ThrshPIV2958WrkHrs_ReHeatCoilStep1.WrkHrs_ResPIV2959WrkHrs_ReHeatCoilStep2.WrkHrs_ThrshPIV2960WrkHrs_ReHeatCoilStep2.WrkHrs_ResPIV2961WrkHrs_ReHeatCoilStep3.WrkHrs_ThrshPIV2962WrkHrs_ReHeatCoilStep3.WrkHrs_ResPIV2963WrkHrs_ReHeatCoilStep4.WrkHrs_ThrshPIV2964WrkHrs_ReHeatCoilStep4.WrkHrs_ResPIV2965WorkingHrs.WrkHrs_ResTotCntAV2966Regulation.BypassDampHeatRecovDelta_CoolAV2967Regulation.BypassDampHeatRecovDelta_HeatAV2968HeatExchg_PID_Params.KpPIV2969HeatExchg_PID_Params.TiAV2970Defrost.BypassDamp_MinOpThrshAV2971Defrost.BypassDamp_MaxOpThrshPIV2972Defrost.MinT_BetweenDfr_HeatExchgPIV2973Defrost.MaxDfrDuration_HeatExchgAV2974Defrost.ExhTempThrshAV2975HeatExchanger.DeltaHeatExchgEfficiencyAV2976Fans.AirP_PrbErr_RetFanReqAV2977Fans_regulation.RetFanOffsetReqPIV2978RetFanRampUpTPIV2979RetFanRampDwnTIV2980RetFan_EmergencySet_rpmPIV2981RetFan_EmergLagTPIV2985RetFan_SerDevCfg_TimeoutPIV2986RetFan_SerDevCfg_CmdDTPIV2989ZiehlAbegg_ReturnFan.SerialInterface_ZA_1.SerDevCfg.DevAddrPIV2992FanRegTypAV2993FansAirQuality_PID_Params.KpPIV2994FansAirQuality_PID_Params.TiPIV2995AirFlwSwTypPIV2996AirFlw_ChkTypPIV2997StateMachine.RetryNoAirFlwAlrmPIV2998AirFlwSwDTPIV2999Fans.AirFlwSwRunAlrmDTAV3000AirFlw_ChkPThrshPIV3001StateMachine.FanPostVentilationTPIV3002NightMinVent_StartHourPIV3003NightMinVent_StartMinPIV3004NightMinVent_EndHourPIV3005NightMinVent_EndMinAV3006Fans_regulation.NightMinVent_MaxReqAV3007Fans_regulation.AirFlw_K_FactorAV3008Fans_regulation.FanFixSpeed_ReqPIV3009Fans_regulation.FansThreeSpeedFixSpeedReqAV3010FansThreeSpeed1AV3011FansThreeSpeed2AV3012FansThreeSpeed3AV3013Fans_regulation.AirQualityFanMinReqAV3014FanTempReg_PID_Params.KpPIV3015FanTempReg_PID_Params.TiAV3016Fans_regulation.SupplyFan_PID_Params.KpPIV3017Fans_regulation.SupplyFan_PID_Params.TiAV3018Fans_regulation.SupplyFan_PID_Params.DeadBandAV3019Fans_regulation.SupplyAirFlwDeadbandPIV3020CompMinOnTPIV3021CompMinOffTPIV3022CompMinOnOnSameTPIV3023AlarmsMng.LowSuctP_Sw_AlrmStartUpDTPIV3024AlarmsMng.LowSuctP_Sw_AlrmRunDTPIV3025LowSuctP_Alrm_CntMaxPIV3026LowSuctP_Alrm_TimeValueAV3027Defrost.DfrStartThrshAV3028Defrost.DfrEndThrshAV3029Defrost.DfrDeltaBypassDampPIV3030Defrost.DfrStartDTPIV3031Defrost.DfrT_StopCompPIV3032DfrMinTPIV3033DfrMaxTPIV3034DfrIntervalTPIV3035DfrDripTPIV3036DfrPostDripTAV3037RevVlvSpeedRpsAV3038RevVlvDeltaPPIV3039Defrost.DfrBeforeChgOverDTPIV3040Defrost.DfrAfterChgOverDTPIV3041FansDfrReq_3SpeedAV3042FansDfrReqPIV3043FansDfrReq_OnOffPIV3044FansDfrDrippingReq_3SpeedAV3045FansDfrDrippingReqPIV3046FansDfrDrippingReq_OnOffPIV3047FansDfrPostDrippingReq_3SpeedAV3048FansDfrPostDrippingReqPIV3049FansDfrPostDrippingReq_OnOffAV3050HumDehumReg.Hum_PID.KpPIV3051HumDehumReg.Hum_PID.TiPIV3052HumDehumReg.Hum_PID.TdAV3053Hum_MaxLim_ThrshAV3054Hum_MaxLim_KpPIV3055Hum_MaxLim_TiAV3056Hum_MinTemp_KpPIV3057Hum_MinTemp_TiIV3058Humisonic.DevSettings_HUMS.WashingTimeSet.DTBetweenWashIV3059Humisonic.DevSettings_HUMS.WashingTimeSet.DTInactivWashIV3060Humisonic.DevSettings_HUMS.WashingTimeSet.WashTimePIV3061AlarmsMng.DirtyFiltAlrmDTAV3062HEPA_Filter_AlrmThrshAV3063Fans.AirP_PrbErr_SupplyFanReqAV3064AFreezeFansMinSpeedPIV3065SupplyFanRampUpTPIV3066SupplyFanRampDwnTIV3067SupplyFan_EmergencySet_rpmPIV3068SupplyFan_EmergLagTPIV3069Ebmpapst_SupplyFan.SerInterfaceSet_EBM_1.CfgProtocol.DevAddrPIV3072SupplyFan_SerDevCfg_TimeoutPIV3073SupplyFan_SerDevCfg_CmdDTPIV3076ZiehlAbegg_SupplyFan.SerialInterface_ZA_1.SerDevCfg.DevAddrPIV3079AuxReg1_Cfg.InputSelPIV3080AuxReg1_Cfg.OutputSelAV3081AuxReg1_Cfg.Modul_ErrorValuePIV3082AuxReg1_Cfg.EnableSelPIV3083AuxReg1_Cfg.SetPSelAV3084AuxReg1_Cfg.Modul_LowLimAV3085AuxReg1_Cfg.DOut_DiffAV3086AuxReg1_Cfg.Modul_HighLimAV3087AuxReg1_Cfg.Modul_KpPIV3088AuxReg1_Cfg.Modul_TiPIV3089AuxReg1_Cfg.Modul_TdAV3090AuxReg1_Cfg.Modul_DeadBandAV3091AuxReg1_Cfg.Modul_ManModeValPIV3092AuxReg2_Cfg.InputSelPIV3093AuxReg2_Cfg.OutputSelAV3094AuxReg2_Cfg.Modul_ErrorValuePIV3095AuxReg2_Cfg.EnableSelPIV3096AuxReg2_Cfg.SetPSelAV3097AuxReg2_Cfg.SetPAV3098AuxReg2_Cfg.Modul_LowLimAV3099AuxReg2_Cfg.DOut_DiffAV3100AuxReg2_Cfg.Modul_HighLimAV3101AuxReg2_Cfg.Modul_KpPIV3102AuxReg2_Cfg.Modul_TiPIV3103AuxReg2_Cfg.Modul_TdAV3104AuxReg2_Cfg.Modul_DeadBandAV3105AuxReg2_Cfg.Modul_ManModeValPIV3106AuxReg3_Cfg.InputSelPIV3107AuxReg3_Cfg.OutputSelAV3108AuxReg3_Cfg.Modul_ErrorValuePIV3109AuxReg3_Cfg.EnableSelPIV3110AuxReg3_Cfg.SetPSelAV3111AuxReg3_Cfg.SetPAV3112AuxReg3_Cfg.Modul_LowLimAV3113AuxReg3_Cfg.DOut_DiffAV3114AuxReg3_Cfg.Modul_HighLimAV3115AuxReg3_Cfg.Modul_KpPIV3116AuxReg3_Cfg.Modul_TiPIV3117AuxReg3_Cfg.Modul_TdAV3118AuxReg3_Cfg.Modul_DeadBandAV3119AuxReg3_Cfg.Modul_ManModeValPIV3120AuxReg4_Cfg.InputSelPIV3121AuxReg4_Cfg.OutputSelAV3122AuxReg4_Cfg.Modul_ErrorValuePIV3123AuxReg4_Cfg.EnableSelPIV3124AuxReg4_Cfg.SetPSelAV3125AuxReg4_Cfg.SetPAV3126AuxReg4_Cfg.Modul_LowLimAV3127AuxReg4_Cfg.DOut_DiffAV3128AuxReg4_Cfg.Modul_HighLimAV3129AuxReg4_Cfg.Modul_KpPIV3130AuxReg4_Cfg.Modul_TiPIV3131AuxReg4_Cfg.Modul_TdAV3132AuxReg4_Cfg.Modul_DeadBandAV3133AuxReg4_Cfg.Modul_ManModeValPIV3134DampOpTAV3135DampAirQuality_PID_Params.KpPIV3136DampAirQuality_PID_Params.TiAV3137FreshAirDamp_MinValAV3138FreshAirDamp_MaxValAV3139MixAirDamp_MinValAV3140MixAirDamp_MaxValAV3141IEC_PID_Params.KpPIV3142IEC_PID_Params.TiAV3143IEC_RetHumActThrshAV3144IEC_RetHumActDiffAV3145Regulation.IEC_ExhHumLim_ThrshAV3146Regulation.IEC_ExhHumLim_KpPIV3147Regulation.IEC_ExhHumLim_TiAV3148Regulation.IEC_FreshAirDamp_MaxLimPIV3149MainCoil_CfgPIV3150MainCoil_StpNAV3151CoolCoil_PID_Params.KpPIV3152CoolCoil_PID_Params.TiAV3153HeatCoil_PID_Params.KpPIV3154HeatCoil_PID_Params.TiAV3155HumDehumReg.DeHum_PID.KpPIV3156HumDehumReg.DeHum_PID.TiPIV3157HumDehumReg.DeHum_PID.TdAV3158HumDehumReg.Dehum_MaxDeltaAV3159AFreezeHeatCoilReqAV3160AFreezeCoolCoilReqPIV3161MainCoil_PmpNoPIV3162Coils.MainCoil_PmpFlwChk_StartupTPIV3163Coils.MainCoil_PmpFlwChk_RunTPIV3164Coils.MainCoil_PmpRotTPIV3165PreHeatCoil_StpNAV3166PreHeatCoil_PID_Params.KpPIV3167PreHeatCoil_PID_Params.TiAV3168AFreezePreHeatCoilReqPIV3169PreHeatCoil_PmpNoPIV3170Coils.PreHeatCoil_PmpFlwChk_StartupTPIV3171Coils.PreHeatCoil_PmpFlwChk_RunTPIV3172Coils.PreHeatCoil_PmpRotTPIV3173ReHeatCoil_StpNAV3174ReHeatCoil_PID_Params.KpPIV3175ReHeatCoil_PID_Params.TiAV3176AFreezeReHeatCoilReqPIV3177ReHeatCoil_PmpNoPIV3178Coils.ReHeatCoil_PmpFlwChk_StartupTPIV3179Coils.ReHeatCoil_PmpFlwChk_RunTPIV3180Coils.ReHeatCoil_PmpRotTPIV3181VDI_InactivityStartUp_DelayPIV3182VDI_InactStartUp_DurationAV3183VDI_HiSatHumThrshAV3184VDI_HiSatHumDiffPIV3185VDI_TypPIV3186VDI_Conf[0].MonthSelPIV3187VDI_Conf[1].MonthSelPIV3188VDI_Conf[2].MonthSelPIV3189VDI_Conf[3].MonthSelPIV3190VDI_Conf[4].MonthSelPIV3191VDI_Conf[5].MonthSelPIV3192VDI_Conf[6].MonthSelPIV3193VDI_Conf[7].MonthSelPIV3194VDI_Conf[8].MonthSelPIV3195VDI_Conf[9].MonthSelPIV3196VDI_Conf[10].MonthSelPIV3197VDI_Conf[11].MonthSelPIV3198VDI_Conf[12].MonthSelPIV3199VDI_Conf[13].MonthSelPIV3200VDI_Conf[14].MonthSelPIV3201VDI_Conf[15].MonthSelPIV3202VDI_Conf[16].MonthSelPIV3203VDI_Conf[17].MonthSelPIV3204VDI_Conf[18].MonthSelPIV3205VDI_Conf[19].MonthSelPIV3206VDI_Conf[20].MonthSelPIV3207VDI_Conf[21].MonthSelPIV3208VDI_Conf[22].MonthSelPIV3209VDI_Conf[23].MonthSelPIV3210VDI_Conf[24].MonthSelPIV3211VDI_Conf[25].MonthSelPIV3212VDI_Conf[26].MonthSelPIV3213VDI_Conf[27].MonthSelPIV3214VDI_Conf[28].MonthSelIV3215GeneralMng.DateFormatPIV3216GeneralMng.RTC_BMS.HourPIV3217GeneralMng.RTC_BMS.MinutePIV3218PwdUserPIV3219PwdServicePIV3220PwdManufPIV3221GeneralMng.SPV_AddrPIV3222GeneralMng.SPV_TimeoutPIV3223GeneralMng.BMS_Baudrate_mskPIV3224GeneralMng.BMS_ParityPIV3225GeneralMng.BMS_StopBitPIV3226GeneralMng.FB_Baudrate_mskPIV3227GeneralMng.FB_ParityPIV3228GeneralMng.FB_StopBitPIV3229BLDC_compressor.MiscMng_BLDC1.Mng_PwrpAddrPIV3230uChiller_mng.DevAddr_uChPIV3231IEC.IEC_HUMFOG_DevAddrPIV3232Humisonic.DevAddr_HUMSPIV3233Humisonic.Timeout_HUMSPIV3234Humisonic.CmdDelay_HUMSPIV3235HumifogMng.HUMFOG_DevAddrPIV3236Scheduler_OnOffUnit.SerDevCfg_THTN.DevAddrPIV3237GeneralMng.StationAdrIV3238Data_EVD_Emb_1.Superparameters.EEVtype.ValIV3239Data_EVD_Emb_1.EVD.Regulation.GasTyp.ValAV3240EVD_Emb_Circ.EEV_SH_SetP_CoolAV3241EVD_Emb_Circ.EEV_SH_SetP_HeatIV3242EVD_Emb_Circ.EEV_StartOpRatio_CoolIV3243EVD_Emb_Circ.EEV_StartOpRatio_HeatIV3244Data_EVD_Emb_1.EVD.Regulation.SH_WaitDT.ValIV3245Data_EVD_Emb_1.EVD.Regulation.StandByEEV_OpPos.ValAV3246EVD_Emb_Circ.EEV_PID_Kp_CoolAV3247EVD_Emb_Circ.EEV_PID_Ti_CoolAV3248EVD_Emb_Circ.EEV_PID_Td_CoolAV3249EVD_Emb_Circ.EEV_PID_Kp_HeatAV3250EVD_Emb_Circ.EEV_PID_Ti_HeatAV3251EVD_Emb_Circ.EEV_PID_Td_HeatIV3252Data_EVD_Emb_1.EVD.Regulation.LowSH_AlrmDT.ValAV3253EVD_Emb_Circ.EEV_LowSH_Thrsh_CoolAV3254EVD_Emb_Circ.EEV_LowSH_Ti_CoolAV3255EVD_Emb_Circ.EEV_LowSH_Thrsh_HeatAV3256EVD_Emb_Circ.EEV_LowSH_Ti_HeatIV3257Data_EVD_Emb_1.EVD.Regulation.LOP_AlrmDT.ValAV3258EVD_Emb_Circ.EEV_LOP_Thrsh_CoolAV3259EVD_Emb_Circ.EEV_LOP_Ti_CoolAV3260EVD_Emb_Circ.EEV_LOP_Thrsh_HeatAV3261EVD_Emb_Circ.EEV_LOP_Ti_HeatIV3262Data_EVD_Emb_1.EVD.Regulation.MOP_AlrmDT.ValAV3263EVD_Emb_Circ.EEV_MOP_Thrsh_CoolAV3264EVD_Emb_Circ.EEV_MOP_Ti_CoolAV3265EVD_Emb_Circ.EEV_MOP_Thrsh_HeatAV3266EVD_Emb_Circ.EEV_MOP_Ti_HeatIV3267EVD_Emb_Circ.EEV_ManPositStepsAV3268Data_EVD_Emb_1.EVD.Regulation.LowSuctAlrmThrsh.ValIV3269Data_EVD_Emb_1.EVD.Regulation.LowSuctAlrmDT.ValIV3270Data_EVD_Emb_1.EVD.EEV_Config.RegMinPos.ValIV3271Data_EVD_Emb_1.EVD.EEV_Config.RegMaxPos.ValIV3272Data_EVD_Emb_1.EVD.EEV_Config.FullClosSteps.ValIV3273Data_EVD_Emb_1.EVD.EEV_Config.MoveRate.ValIV3274Data_EVD_Emb_1.EVD.EEV_Config.FastClosMoveRate.ValIV3275Data_EVD_Emb_1.EVD.EEV_Config.MoveDuty.ValPIV3276BLDC_compressor.MiscMng_BLDC1.Mng_PwrpMotTypPIV3277BLDC_compressor.MiscMng_BLDC1.Mng_CompTypPIV3278BLDC_compressor.MiscMng_PWRP1.Mng_DriveTypIV3279BLDC_compressor.MiscMng_PWRP1.Mng_WriteDefaultPIV3280BLDC_compressor.CurrCompCfg_PWRP1.HR29_DataCommTimeoutAV3281BLDC_compressor.CurrCompCfg_PWRP1.HR07_MinOutFreqAV3282BLDC_compressor.CurrCompCfg_PWRP1.HR06_MaxOutFreqAV3283BLDC_compressor.CurrCompCfg_PWRP1.HR10_SkipFreqSetPAV3284BLDC_compressor.CurrCompCfg_PWRP1.HR11_SkipFreqBandAV3285BLDC_compressor.CurrCompCfg_PWRP1.HR67_SkipFreqSetP_2AV3286BLDC_compressor.CurrCompCfg_PWRP1.HR68_SkipFreqBand_2AV3287BLDC_compressor.CurrCompCfg_PWRP1.HR69_SkipFreqSetp_3AV3288BLDC_compressor.CurrCompCfg_PWRP1.HR70_SkipFreqBand_3PIV3289BLDC_compressor.CurrCompCfg_PWRP1.HR24_SwitchingFreqPIV3290BLDC_compressor.CurrCompCfg_PWRP1.HR25_SwitchingFreqDeratingPIV3291BLDC_compressor.CurrCompCfg_PWRP1.HR27_MotOvTempAlrmPTC_EnPIV3292BLDC_compressor.CurrCompCfg_PWRP1.HR28_MotOvTempAlrmPTC_DelayPIV3293BLDC_compressor.CurrCompCfg_PWRP1.HR08_EnRevSpeedPIV3294BLDC_compressor.CurrCompCfg_PWRP1.HR09_SpeedDeratingModePIV3295BLDC_compressor.CurrCompCfg_PWRP1.HR33_StopModePIV3296BLDC_compressor.CurrCompCfg_PWRP1.HR34_FlyingRestartPIV3297BLDC_compressor.CurrCompCfg_PWRP1.HR26_RelayCfgPIV3298BLDC_compressor.MiscMng_PWRP1.Mng_MotPolesPIV3299BLDC_compressor.CurrCompCfg_PWRP1.HR00_MotCtrlModeAV3300BLDC_compressor.CurrCompCfg_PWRP1.HR01_MotBaseFreqPIV3301BLDC_compressor.CurrCompCfg_PWRP1.HR02_MotBaseVAV3302BLDC_compressor.CurrCompCfg_PWRP1.HR03_MotRatedAPIV3303BLDC_compressor.CurrCompCfg_PWRP1.HR04_MotPwrFactorAV3304BLDC_compressor.CurrCompCfg_PWRP1.HR05_MaxOutCurrentAV3305BLDC_compressor.CurrCompCfg_PWRP1.HR12_SpeedProfileFreq1AV3306BLDC_compressor.CurrCompCfg_PWRP1.HR13_SpeedProfileFreq2AV3307BLDC_compressor.CurrCompCfg_PWRP1.HR14_SpeedProfileFreq3AV3308BLDC_compressor.CurrCompCfg_PWRP1.HR15_SpeedProfileAcceleration1AV3309BLDC_compressor.CurrCompCfg_PWRP1.HR16_SpeedProfileAcceleration2AV3310BLDC_compressor.CurrCompCfg_PWRP1.HR17_SpeedProfileAcceleration3AV3311BLDC_compressor.CurrCompCfg_PWRP1.HR18_SpeedProfileAcceleration4PIV3312BLDC_compressor.CurrCompCfg_PWRP1.HR19_SpeedProfileDelay1PIV3313BLDC_compressor.CurrCompCfg_PWRP1.HR20_SpeedProfileDelay2PIV3314BLDC_compressor.CurrCompCfg_PWRP1.HR21_SpeedProfileDelay3AV3315BLDC_compressor.CurrCompCfg_PWRP1.HR23_SpeedProfileDecelerationAV3316BLDC_compressor.CurrCompCfg_PWRP1.HR35_V_F_BoostVAV3317BLDC_compressor.CurrCompCfg_PWRP1.HR36_V_F_FreqAdjAV3318BLDC_compressor.CurrCompCfg_PWRP1.HR37_V_F_VAdjAV3319BLDC_compressor.CurrCompCfg_PWRP1.HR45_MotMagnetizingCurrentPIV3320BLDC_compressor.CurrCompCfg_PWRP1.HR46_StatorResistancePIV3321BLDC_compressor.CurrCompCfg_PWRP1.HR47_RotorResistanceAV3322BLDC_compressor.CurrCompCfg_PWRP1.HR48_StatorInductanceLdPIV3323BLDC_compressor.CurrCompCfg_PWRP1.HR49_LeakageFactorAV3324BLDC_compressor.CurrCompCfg_PWRP1.HR50_LqInductanceAV3325BLDC_compressor.CurrCompCfg_PWRP1.HR55_SpeedLoopKpPIV3326BLDC_compressor.CurrCompCfg_PWRP1.HR56_SpeedLoopTiPIV3327BLDC_compressor.CurrCompCfg_PWRP1.HR51_MagnetizingTimeAV3328BLDC_compressor.CurrCompCfg_PWRP1.HR57_StartingCurrentAV3329BLDC_compressor.CurrCompCfg_PWRP1.HR58_StartingAFreqPIV3330BLDC_compressor.CurrCompCfg_PWRP1.CrankCaseHeaterModeAV3331BLDC_compressor.CurrCompCfg_PWRP1.HR65_CrankCaseHeaterCurrentPIV3332BLDC_compressor.CurrCompCfg_PWRP1.HR66_STOResetStrategyAV3333BLDC_compressor.CurrCompCfg_PWRP1.HR77_InductSaturFactorIV3334BLDC_compressor.AlrmResetMng_PWRP1.RetryThrsPIV3335BLDC_compressor.AlrmResetMng_PWRP1.TimeThrsPIV3336BLDC_compressor.MiscMng_BLDC1.Mng_ModbusTimeoutPIV3337BLDC_compressor.MiscMng_BLDC1.Mng_ModbusCmdDelayAV3338BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_MaxDeltaPIV3339BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_EVDEqualMaxTIV3340BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_EVDEqualPreopenAV3341BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_DeltaPVariationIV3342BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_DeltaPDelayIV3343BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_RestartDelayIV3344BLDC_compressor.CfgEnvCtrl_BLDC1.StartUp_AttemptsAV3345BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_StartUpSpeedAV3347BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_MinSpeedRpsCustomAV3348BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_MaxDescendSpeedRateAV3349BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_MaxRisingSpeedRateAV3350BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_SwitchOffSpeedRateAV3351BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_MaxSlowdownSpeedRateAV3352BLDC_compressor.CfgEnvCtrl_BLDC1.Speed_MinSpeedControlledIV3353BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_EnvOutMaxTIV3354BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_LowDeltaPAlrmDelayAV3355BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_SuctTSaturationThrshZone1b1cIV3356BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_MaxSpeedZone1cAV3357BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempCtrlThrshZone1aAV3358BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempAlrmThrshZone1aAV3359BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempCtrlThrshAV3360BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempAlrmThrshAV3361BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempLimDistanceIV3362BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempPauseAV3363BLDC_compressor.CfgEnvCtrl_BLDC1.CstmEnv_DscgTempSpeedReductionAV3364CstEvapMinTempAV3365CstCondMaxTempIV3366BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_SubTypeRegModeAV3367BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DscgTempNTCTAV3368BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DscgSHSetPAV3369BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DTDscgSHRegOnAV3370BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DTDscgSHHystAV3371BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DscgTempSetPAV3372BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DTDLTRegOnAV3373BLDC_compressor.CfgEnvCtrl_BLDC1.EvdReg_DTDLTHystIV3374BLDC_compressor.AlrmResetMng_BLDC_1.RetryThrsPIV3375BLDC_compressor.AlrmResetMng_BLDC_1.TimeThrsAV3376SupplyFanMinValAV3377SupplyFanMaxValAV3378RetFanMinValAV3379RetFanMaxValPIV3380GeneralMng.pGDx_MACAddress1PIV3381GeneralMng.pGDx_MACAddress2PIV3382GeneralMng.pGDx_MACAddress3PIV3383GeneralMng.pGDx_MACAddress4PIV3384BMS_LinePIV3385BMS2_LinePIV3386ETH_LinePIV3387ETH2_LinePIV3388GeneralMng.BACnet_IDPIV3389GeneralMng.BACnet_TimeoutPIV3390GeneralMng.BMS2_Baudrate_mskPIV3391GeneralMng.BMS2_ParityPIV3392GeneralMng.BMS2_StopBitPIV3940CoilVlv_OpenTimePIV265AuxReg1_Cfg.CoolHeatModePIV272AuxReg2_Cfg.CoolHeatModePIV279AuxReg3_Cfg.CoolHeatModePIV286AuxReg4_Cfg.CoolHeatModePIV3950HumDehumStartReg_DTPIV3952AirQuality_PM10.Board_RWPIV3978AirQuality_PM10.Ch_Id_RWPIV3979AirQuality_PM10.Ch_Type_RWPIV3980AirQuality_PM10.ChFilter_RWAV3983AirQuality_PM10.MaxVal_RWAV3984AirQuality_PM10.MinVal_RWAV3985AirQuality_PM10.Offset_RWPIV3991AirQuality_PM25.Board_RWPIV3992AirQuality_PM25.Ch_Id_RWPIV3993AirQuality_PM25.Ch_Type_RWPIV3994AirQuality_PM25.ChFilter_RWAV3997AirQuality_PM25.MaxVal_RWAV3998AirQuality_PM25.MinVal_RWAV3999AirQuality_PM25.Offset_RWPIV4004SanificationDevice.Board_RWPIV4005SanificationDevice.Ch_Id_RWPIV4006SanificationDevice.Ch_Type_RWPIV4009SanificationDevice.T_On_RWPIV4010SanificationDevice.T_Off_RWAV3954FansAirQualityVOC_PID_Params.KpPIV3953FansAirQualityVOC_PID_Params.TiAV3955DampAirQualityVOC_PID_Params.KpPIV3956DampAirQualityVOC_PID_Params.TiPIV3959QualitySignalPIV3961ModeSanDevOffByBmsOrSchedPIV3962SanificationDeviceTimeOnPIV3963SanificationDeviceTimeOffPIV3965WrkHrs_SanificationDevice.WrkHrs_ThrshPIV3967WrkHrs_SanificationDevice.WrkHrs_ResPIV3972PurgeTimePIV3973PurgeModePIV3974PurgeHourPIV3975PurgeMinuteAV3976BLDC_compressor.Speed_MaxSpeedRpsCustom_CoolingAV3977BLDC_compressor.Speed_MaxSpeedRpsCustom_HeatingPIV4044SanificationDeviceOvld.Board_RWPIV4045SanificationDeviceOvld.Ch_Id_RWAV4014CurrAirQuality_VOC_SetPAV4023AirQualityVOCSetP_MaxValAV4022AirQualityVOCSetP_MinValAV4021UnitSetP.AirQuality_VOC_SetP.ComfortAV4015UnitSetP.AirQuality_VOC_SetP.EconomyAV4018UnitSetP.AirQuality_VOC_SetP.PreComfortPIV4024DfrEnActionsAV4026OilRecov_CompMinSpeedThrshAV4027OilRecov_FrcCompSpeedPIV4028OilRecov_FrcSpeedTPIV4029OilRecov_WaitTAV4046EVD_Emb_Circ.EEV_PID_Kp_Cool_DfrAV4047EVD_Emb_Circ.EEV_PID_Kp_Heat_DfrAV4048EVD_Emb_Circ.EEV_PID_Td_Cool_DfrAV4049EVD_Emb_Circ.EEV_PID_Td_Heat_DfrAV4050EVD_Emb_Circ.EEV_PID_Ti_Cool_DfrAV4051EVD_Emb_Circ.EEV_PID_Ti_Heat_DfrPIV4030FC_FH_TypAV4031Regulation.FC_DeltaEnth_ActAV4032Regulation.FH_DeltaEnth_ActIV4052GeneralMng.pGDx_HostName_ASCII[1]IV4053GeneralMng.pGDx_HostName_ASCII[2]IV4054GeneralMng.pGDx_HostName_ASCII[3]IV4055GeneralMng.pGDx_HostName_ASCII[4]IV4056GeneralMng.pGDx_HostName_ASCII[5]IV4057GeneralMng.pGDx_HostName_ASCII[6]PIV4058FanNrPIV4059Ebmpapst_SupplyFan.SerInterfaceSet_EBM_2.CfgProtocol.DevAddrPIV4060Ebmpapst_SupplyFan.SerInterfaceSet_EBM_3.CfgProtocol.DevAddrPIV4061Ebmpapst_SupplyFan.SerInterfaceSet_EBM_4.CfgProtocol.DevAddrPIV4062Ebmpapst_ReturnFan.SerInterfaceSet_EBM_2.CfgProtocol.DevAddrPIV4063Ebmpapst_ReturnFan.SerInterfaceSet_EBM_3.CfgProtocol.DevAddrPIV4064Ebmp3pst_ReturnFan.SerInterfaceSet_EBM_4.CfgProtocol.DevAddrPIV4065ZiehlAbegg_SupplyFan.SerialInterfa-ce_ZA_2.SerDevCfg.DevAddrPIV4066ZiehlAbegg_SupplyFan.SerialInterfa-ce_ZA_3.SerDevCfg.DevAddrPIV4067ZiehlAbegg_SupplyFan.SerialInterfa-ce_ZA_4.SerDevCfg.DevAddrPIV4068ZiehlAbegg_ReturnFan.SerialInterfa-ce_ZA_2.SerDevCfg.DevAddrPIV4069ZiehlAbegg_ReturnFan.SerialInterfa-ce_ZA_3.SerDevCfg.DevAddrPIV4070ZiehlAbegg_ReturnFan.SerialInterfa-ce_ZA_4.SerDevCfg.DevAddrPIV4255WrkHrs_SupplyFan_2.WrkHrs_ThrshPIV4256WrkHrs_SupplyFan_2.WrkHrs_ResPIV4257WrkHrs_SupplyFan_3.WrkHrs_ThrshPIV4258WrkHrs_SupplyFan_3.WrkHrs_ResPIV4259WrkHrs_SupplyFan_4.WrkHrs_ThrshPIV4260WrkHrs_SupplyFan_4.WrkHrs_ResPIV4261WrkHrs_ReturnFan_2.WrkHrs_ThrshPIV4262WrkHrs_ReturnFan_2.WrkHrs_ResPIV4263WrkHrs_ReturnFan_3.WrkHrs_ThrshPIV4264WrkHrs_ReturnFan_3.WrkHrs_ResPIV4265WrkHrs_ReturnFan_4.WrkHrs_ThrshPIV4266WrkHrs_ReturnFan_4.WrkHrs_ResPIV4285FireSmokeMngTypPIV4296IOs.CstSerPrb_DevAddr[1]PIV4297IOs.CstSerPrb_DevAddr[2]PIV4298IOs.CstSerPrb_DevAddr[3]PIV4299IOs.CstSerPrb_DevAddr[4]PIV4300IOs.CstSerPrb_DevAddr[5]PIV4301CstPrbCfg.Temp1AdrPIV4302CstPrbCfg.Temp2AdrPIV4303CstPrbCfg.Hum1AdrPIV4304CstPrbCfg.Hum2AdrPIV4305CstPrbCfg.Press1AdrPIV4306CstPrbCfg.Press2AdrPIV4307CstPrbCfg.Flow1AdrPIV4308CstPrbCfg.Flow2AdrIV4309CstPrbCfg.Temp1FactIV4310CstPrbCfg.Temp2FactIV4311CstPrbCfg.Hum1FactIV4312CstPrbCfg.Hum2FactIV4313CstPrbCfg.Press1FactIV4314CstPrbCfg.Press2FactIV4315CstPrbCfg.Flow1FactIV4316CstPrbCfg.Flow2FactAV4317CstPrbCfg.TempAlmMinAV4318CstPrbCfg.TempAlmMaxAV4319CstPrbCfg.HumAlmMinAV4320CstPrbCfg.HumAlmMaxAV4321CstPrbCfg.PressAlmMinAV4322CstPrbCfg.PressAlmMaxAV4323CstPrbCfg.FlowAlmMinAV4324CstPrbCfg.FlowAlmMaxPIV4325CstPrbCfg.TimeoutPIV4326CstPrbCfg.CmdDelayPIV4327IAQ_PrbCfg.VOC_sensibilityPIV4328IAQ_PrbCfg.TimeoutPIV4329IAQ_PrbCfg.CmdDelayPIV4339HumiSteamMng.DevAddr_UEYPIV4340HumiSteamMng.Timeout_UEYPIV4341HumiSteamMng.CmdDelay_UEYPIV4352SummerWinterDTPIV4353SummerWinterSelAV4354CoolHeat_Chg_OffsetPIV4355MainCoilCoolHeat_Din.Board_RWPIV4356MainCoilCoolHeat_Din.Ch_Id_RWPIV4357UnitAutoModeCfgPIV4358SummerEndDayPIV4359SummerEndMonthPIV4360SummerStartDayPIV4361SummerStartMonthAV4374Fans_regulation.RetFan_PID_Params.DeadBandAV4375Fans_regulation.RetFan_PID_Params.KpPIV4376Fans_regulation.RetFan_PID_Params.TiPIV4381GenericAin1.Board_RWPIV4382GenericAin1.Ch_Id_RWPIV4383GenericAin1.Ch_Type_RWAV4384GenericAin1.MinVal_RWAV4385GenericAin1.MaxVal_RWAV4386GenericAin1.Offset_RWPIV4387GenericAin1.ChFilter_RWPIV4395GenericAin2.Board_RWPIV4396GenericAin2.Ch_Id_RWPIV4397GenericAin2.Ch_Type_RWAV4398GenericAin2.MinVal_RWAV4399GenericAin2.MaxVal_RWAV4400GenericAin2.Offset_RWPIV4401GenericAin2.ChFilter_RWPIV4409GenericAin3.Board_RWPIV4410GenericAin3.Ch_Id_RWPIV4411GenericAin3.Ch_Type_RWAV4412GenericAin3.MinVal_RWAV4413GenericAin3.MaxVal_RWAV4414GenericAin3.Offset_RWPIV4415GenericAin3.ChFilter_RWPIV4423GenericAin4.Board_RWPIV4424GenericAin4.Ch_Id_RWPIV4425GenericAin4.Ch_Type_RWAV4426GenericAin4.MinVal_RWAV4427GenericAin4.MaxVal_RWAV4428GenericAin4.Offset_RWPIV4429GenericAin4.ChFilter_RWPIV4437GenericAin5.Board_RWPIV4438GenericAin5.Ch_Id_RWPIV4439GenericAin5.Ch_Type_RWAV4440GenericAin5.MinVal_RWAV4441GenericAin5.MaxVal_RWAV4442GenericAin5.Offset_RWPIV4443GenericAin5.ChFilter_RWPIV4452GenericDin1.Board_RWPIV4453GenericDin1.Ch_Id_RWPIV4459GenericDin2.Board_RWPIV4460GenericDin2.Ch_Id_RWPIV4466GenericDin3.Board_RWPIV4467GenericDin3.Ch_Id_RWPIV4473GenericDin4.Board_RWPIV4474GenericDin4.Ch_Id_RWPIV4480GenericDin5.Board_RWPIV4481GenericDin5.Ch_Id_RWPIV4482GenericDin1_Alrm_MngTypPIV4483GenericDin2_Alrm_MngTypPIV4484GenericDin3_Alrm_MngTypPIV4485GenericDin4_Alrm_MngTypPIV4486GenericDin5_Alrm_MngTypAV4497Regulation.FC_ExtTempLimitAV4498Regulation.FH_ExtTempLimitAV4500IEC_ManModeValAV4501Regulation.FanTempReg_KpPIV4502Regulation.FanTempReg_TdAV4503Fans_regulation.RetAirFlw_K_FactorAV4509BMS_Reg_AnalogPrbMap[1]AV4510BMS_Reg_AnalogPrbMap[2]AV4511BMS_Reg_AnalogPrbMap[3]AV4512BMS_Reg_AnalogPrbMap[4]AV4513BMS_Reg_AnalogPrbMap[5]PIV4534OA_Vlv_Open.Board_RWPIV4535OA_Vlv_Open.Ch_Id_RWPIV4536OA_Vlv_Open.T_On_RWPIV4537OA_Vlv_Open.T_Off_RWPIV4538OA_Vlv_Open.Ch_Type_RWPIV4539OA_Vlv_Close.Board_RWPIV4540OA_Vlv_Close.Ch_Id_RWPIV4541OA_Vlv_Close.T_On_RWPIV4542OA_Vlv_Close.T_Off_RWPIV4543OA_Vlv_Close.Ch_Type_RWAV4544OA_CoilManModeValPIV4545OA_Coil_TypAV4546OA_CoilWarmUpReqAV4547RegPrbErrOA_CoilReqPIV4548WrkHrs_OA_CoilAout.WrkHrs_ThrshPIV4549WrkHrs_OA_CoilAout.WrkHrs_ResPIV4550WrkHrs_OA_CoilStep1.WrkHrs_ThrshPIV4551WrkHrs_OA_CoilStep1.WrkHrs_ResPIV4552WrkHrs_OA_CoilStep2.WrkHrs_ThrshPIV4553WrkHrs_OA_CoilStep2.WrkHrs_ResPIV4554WrkHrs_OA_CoilStep3.WrkHrs_ThrshPIV4555WrkHrs_OA_CoilStep3.WrkHrs_ResPIV4556WrkHrs_OA_CoilStep4.WrkHrs_ThrshPIV4557WrkHrs_OA_CoilStep4.WrkHrs_ResPIV4558OA_Coil_StpNAV4559OA_Coil_PID_Params.KpPIV4560OA_Coil_PID_Params.TiPIV4561AFreezeOA_CoilReqPIV4575OA_RegTypAV4576OA_CoilTempSetPPIV4577OA_CoilActModePIV3393VDI_Conf[0].MonthPIV3394VDI_Conf[1].MonthPIV3395VDI_Conf[2].MonthPIV3396VDI_Conf[3].MonthPIV3397VDI_Conf[4].MonthPIV3398VDI_Conf[5].MonthPIV3399VDI_Conf[6].MonthPIV3400VDI_Conf[7].MonthPIV3401VDI_Conf[8].MonthPIV3402VDI_Conf[9].MonthPIV3403VDI_Conf[10].MonthPIV3404VDI_Conf[11].MonthPIV3405VDI_Conf[12].MonthPIV3406VDI_Conf[13].MonthPIV3407VDI_Conf[14].MonthPIV3408VDI_Conf[15].MonthPIV3409VDI_Conf[16].MonthPIV3410VDI_Conf[17].MonthPIV3411VDI_Conf[18].MonthPIV3412VDI_Conf[19].MonthPIV3413VDI_Conf[20].MonthPIV3414VDI_Conf[21].MonthPIV3415VDI_Conf[22].MonthPIV3416VDI_Conf[23].MonthPIV3417VDI_Conf[24].MonthPIV3418VDI_Conf[25].MonthPIV3419VDI_Conf[26].MonthPIV3420VDI_Conf[27].MonthPIV3421VDI_Conf[28].MonthPIV3434SupplyTemp.Uom_WAV3435SupplyTemp.Val_Hw_RPIV3437SupplyHum.Uom_WAV3438SupplyHum.Val_Hw_RAV3439SupplyHum.Val_RPIV3440RetTemp.Uom_WAV3441RetTemp.Val_Hw_RAV3442RetTemp.Val_RPIV3443RetHum.Uom_WAV3444RetHum.Val_Hw_RAV3445RetHum.Val_RPIV3446RoomTemp.Uom_WAV3447RoomTemp.Val_Hw_RAV3448RoomTemp.Val_RPIV3449RoomHum.Uom_WAV3450RoomHum.Val_Hw_RAV3451RoomHum.Val_RPIV3452ExtTemp.Uom_WAV3453ExtTemp.Val_Hw_RPIV3455ExtHum.Uom_WAV3456ExtHum.Val_Hw_RAV3457ExtHum.Val_RPIV3458ExhTemp.Uom_WAV3459ExhTemp.Val_Hw_RAV3460ExhTemp.Val_RPIV3461ExhHum.Uom_WAV3462ExhHum.Val_Hw_RAV3463ExhHum.Val_RPIV3464AFreezeTemp.Uom_WAV3465AFreezeTemp.Val_Hw_RAV3466AFreezeTemp.Val_RPIV3467SatTemp.Uom_WAV3468SatTemp.Val_Hw_RPIV3470SatHum.Uom_WAV3471SatHum.Val_Hw_RAV3472SatHum.Val_RPIV3473OA_Temp.Uom_WAV3474OA_Temp.Val_Hw_RAV3475OA_Temp.Val_RPIV3476SupplyAirP.Uom_WAV3477SupplyAirP.Val_Hw_RPIV3479RetAirP.Uom_WAV3480RetAirP.Val_Hw_RPIV3482AirQuality_CO2.Uom_WAV3483AirQuality_CO2.Val_Hw_RPIV3485AirQuality_VOC.Uom_WAV3486AirQuality_VOC.Val_Hw_RAV3487AirQuality_VOC.Val_RPIV3488DscgP.Uom_WAV3489DscgP.Val_Hw_RPIV3491DscgT.Uom_WAV3492DscgT.Val_Hw_RPIV3494SuctP.Uom_WAV3495SuctP.Val_Hw_RPIV3497SuctT.Uom_WAV3498SuctT.Val_Hw_RPIV3500OA_CoilWaterTemp.Uom_WAV3501OA_CoilWaterTemp.Val_Hw_RAV3502OA_CoilWaterTemp.Val_RPIV3503PreHeatCoilWaterTemp.Uom_WAV3504PreHeatCoilWaterTemp.Val_Hw_RAV3505PreHeatCoilWaterTemp.Val_RPIV3506MainCoilWaterTemp.Uom_WAV3507MainCoilWaterTemp.Val_Hw_RAV3508MainCoilWaterTemp.Val_RPIV3509ReHeatCoilWaterTemp.Uom_WAV3510ReHeatCoilWaterTemp.Val_Hw_RAV3511ReHeatCoilWaterTemp.Val_RPIV3512AuxPrb_1.Uom_WAV3513AuxPrb_1.Val_Hw_RAV3514AuxPrb_1.Val_RPIV3515AuxPrb_2.Uom_WAV3516AuxPrb_2.Val_Hw_RAV3517AuxPrb_2.Val_RPIV3518AuxPrb_3.Uom_WAV3519AuxPrb_3.Val_Hw_RAV3520AuxPrb_3.Val_RPIV3521AuxPrb_4.Uom_WAV3522AuxPrb_4.Val_Hw_RAV3523AuxPrb_4.Val_RPIV3524Ain_SetP.Uom_WAV3525Ain_SetP.Val_Hw_RAV3526Ain_SetP.Val_RPIV3527SupplyRecoveryTemp.Uom_WAV3528SupplyRecoveryTemp.Val_Hw_RAV3529SupplyRecoveryTemp.Val_RPIV3530RetRecoveryTemp.Uom_WAV3531RetRecoveryTemp.Val_Hw_RAV3532RetRecoveryTemp.Val_RPIV3533HepaFilt_1.Uom_WAV3534HepaFilt_1.Val_Hw_RAV3535HepaFilt_1.Val_RPIV3536HepaFilt_2.Uom_WAV3537HepaFilt_2.Val_Hw_RAV3538HepaFilt_2.Val_RAV3540SupplyFan_Aout.Val_Hw_RAV3542RetFan_Aout.Val_Hw_RAV3544BypassDamp_Aout.Val_Hw_RAV3546MixingDamp_Aout.Val_Hw_RAV3548FreshAirDamp_Aout.Val_Hw_RAV3549ReHeatCoil_Aout.Val_WAV3550ReHeatCoil_Aout.Val_Hw_RAV3551PreHeatCoil_Aout.Val_WAV3552PreHeatCoil_Aout.Val_Hw_RAV3553OA_Coil_Aout.Val_WAV3554OA_Coil_Aout.Val_Hw_RAV3555MainCoil_Aout.Val_WAV3556MainCoil_Aout.Val_Hw_RAV3558ThrmlWheel_Aout.Val_Hw_RAV3559Humidifier_Aout.Val_WAV3560Humidifier_Aout.Val_Hw_RAV3562ExhAirDamp_Aout.Val_Hw_RAV3564AuxAout_1.Val_Hw_RAV3566AuxAout_2.Val_Hw_RAV3568AuxAout_3.Val_Hw_RAV3570AuxAout_4.Val_Hw_RAV3571IEC_Aout.Val_WAV3572IEC_Aout.Val_Hw_RAV3573Recovery_Aout.Val_WAV3574Recovery_Aout.Val_Hw_RAV3575SupplyAirDamp_Aout.Val_WAV3576SupplyAirDamp_Aout.Val_Hw_RAV3577RetAirDamp_Aout.Val_WAV3578RetAirDamp_Aout.Val_Hw_RPIV3579AlarmsMng.AlrmHourPIV3580AlarmsMng.AlrmMinutePIV3581AlarmsMng.AlrmDayPIV3582AlarmsMng.AlrmMonthPIV3583AlarmsMng.AlrmYearPIV3584AlarmsMng.AlrmLogHourPIV3585AlarmsMng.AlrmLogMinutePIV3586AlarmsMng.AlrmLogDayPIV3587AlarmsMng.AlrmLogMonthPIV3588AlarmsMng.AlrmLogYearIV3589AlarmsMng.ErrParamExpAlrmsIV3590Scheduler_OnOffUnit.OnOffByKeb_SecLeftPIV3591Scheduler_OnOffUnit.PartyMode_CntDwnPIV3592Dampers.DampersStatusAV3593MaskMng.HeatExchgReqPIV3594MaskMng.HeatExchgStatusSynAV3595HeatExchanger.HeatExchgEfficiencyAV3596RetAirFlwValAV3597AirFlwValAV3598SupplyFanReqPIV3599ComStatus_Supply_EBM_1PIV3600SupplyFanActAV3601RetFanReqPIV3602ComStatus_Return_EBM_1PIV3603RetFanActAV3604Fans_regulation.RetFan_AirQuality_SetPOffsAV3605Fans_regulation.SupplyFan_AirQuality_SetPOffsAV3606AirQuality_Damps_RegReqAV3607AirQuality_Fans_RegReqAV3608SupplyTempRegSetPAV3609PreHeatCoilRegReqAV3610PreHeatCoilReqAV3611Coils.ModulMainCoilReqAV3612ReHeatCoilRegReqAV3613ReHeatCoilReqAV3614CondTempIV3615MaskMng.CompStatusMskIV3616MaskMng.CompOnOffCntDwnAV3617CompReqAV3618Data_EVD_Emb_1.EVD.Variables.SH_EvapTemp.ValAV3619Data_EVD_Emb_1.EVD.Variables.CondTemp.ValIV3620MaskMng.BLDC_CompStatusIV3621MaskMng.BLDC_CompCntDwnAV3622BLDC_PwrReqAV3623MaskMng.BLDC_CompPerc_ScaledIV3624BLDC_compressor.EnvZoneIV3625BLDCtoEVD.RegSubTypIV3626MaskMng.EEV_StatusAV3627Data_EVD_Emb_1.EVD.Variables.SH.ValAV3628BLDC_compressor.Info_PWRP1.Info_RotorSpeed_rpsAV3629Data_EVD_Emb_1.EVD.Variables.EEV_PosPercent.ValIV3630MaskMng.CompEnvCntDwnIV3631Data_EVD_Emb_1.EVD.Variables.EEV_PosSteps.ValAV3632MaskMng.EEVSetAV3633Data_EVD_Emb_1.EVD.Variables.DscgSH.ValAV3634HumDehumReg.HumDehum_RegHum_RelAV3635HumDehumReg.HumDehum_RegHum_AbsAV3636HumDehumReg.HumDehum_SetP_AbsAV3637HumRegReqAV3638DehumRegReqAV3639Dehum_DewPointSetPAV3640AuxiliaryRegulation.AuxReg1_Info.RegValAV3641AuxiliaryRegulation.AuxReg2_Info.RegValAV3642AuxiliaryRegulation.AuxReg3_Info.RegValAV3643AuxiliaryRegulation.AuxReg4_Info.RegValPIV3644Scheduler_OnOffUnit.SchedSrcPIV3645SchedStatusAV3646KWater_MB.HR18_ExtTAV3647KWater_MB.HR21_TCircKAirPIV3648kWater_UnitStatusAV3649HumifogMng.HUMFOG_PwrReqAV3650HumifogMng.HUMFOG_ActualProdPIV3651HumifogMng.HUMFOG_HoursWorskIV3652HumifogMng.HUMFOG_UnitStatusAV3653IEC_ReqAV3654IEC.IEC_HUMFOG_ActualProdPIV3655IEC.IEC_HUMFOG_HoursWorksIV3656IEC.IEC_HUMFOG_UnitStatusAV3657uChiller_mng.Info_uCh.BLDC_rps_Circ1IV3658uChiller_mng.Info_uCh.EEV_PosPerc_Circ1AV3659uChiller_mng.Info_uCh.DscgPCirc1AV3660uChiller_mng.Info_uCh.SuctPCirc1IV3661uChiller_mng.UnitStatus_uChAV3662uChiller_mng.Info_uCh.BLDC_rps_Circ2PIV3663GeneralMng.CurrVer.XPIV3664GeneralMng.CurrVer.YPIV3665GeneralMng.CurrVer.ZPIV3666GeneralMng.CurrVer.DPIV3667GeneralMng.OsVersion[1]PIV3668GeneralMng.OsVersion[2]PIV3669GeneralMng.OsVersion[3]PIV3670GeneralMng.BoardTyp[1]PIV3671GeneralMng.BoardTyp[2]PIV3672VarToShow.IdxChNamePIV3673VarToShow.BoardPIV3674VarToShow.Ch_IdAV3675ObjMsk.ValStaticPressAV3676ObjMsk.ValAirQualAV3677ObjMsk.ValRfrgPressAV3678ObjMsk.ValFlowRateAV3679ObjMsk.ValAirFlowAV3680ObjMsk.ValTempAV3681ObjMsk.ValHumAV3682ObjMsk.ValAoutAV3683ObjMsk.ValGenericAV3684ObjMsk.ValPercentPIV3685SupplyFan_MainMaskPIV3686MaskMng.RetFan_MainMaskPIV3687HourPIV3688MinutePIV3689Scheduler_OnOffUnit.UnitStatusPIV3690Ebmpapst_SupplyFan.InfoSpeed_EBM_1.CurrSpeedPIV3691Ebmpapst_SupplyFan.ElectrInfo_EBM_1.DC_Link_VPIV3692Ebmpapst_SupplyFan.ElectrInfo_EBM_1.DC_Link_APIV3693Ebmpapst_SupplyFan.ElectrInfo_EBM_1.CurrPowerPIV3694Ebmpapst_SupplyFan.ElectrInfo_EBM_1.ElectrTempPIV3695Ebmpapst_SupplyFan.MotStatus_EBM_1.IR_MotStatusPIV3696Ebmpapst_SupplyFan.Warn_EBM_1.IR_WarnPIV3697Ebmpapst_SupplyFan.InfoSpeed_EBM_1.MaxSpeedPIV3698Ebmpapst_SupplyFan.CntWorkHrsBkp_EBM_1PIV3699Ebmpapst_ReturnFan.InfoSpeed_EBM_1.CurrSpeedPIV3700Ebmpapst_ReturnFan.ElectrInfo_EBM_1.DC_Link_VPIV3701Ebmpapst_ReturnFan.ElectrInfo_EBM_1.DC_Link_APIV3702Ebmpapst_ReturnFan.ElectrInfo_EBM_1.CurrPowerPIV3703Ebmpapst_ReturnFan.ElectrInfo_EBM_1.ElectrTempPIV3704Ebmpapst_ReturnFan.MotStatus_EBM_1.IR_MotStatusPIV3705Ebmpapst_ReturnFan.Warn_EBM_1.IR_WarnPIV3706Ebmpapst_ReturnFan.InfoSpeed_EBM_1.MaxSpeedPIV3707Ebmpapst_ReturnFan.CntWorkHrsBkp_EBM_1PIV3708ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_1.CurrSpeed_rpmPIV3709ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.DC_LinkVPIV3710ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.LineVPIV3711ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_1.MaxSpeed_rpmPIV3712ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_1.MinSpeed_rpmPIV3713ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.MotPwrAV3714ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.ElectronicTempAV3715ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.IGBT_tempAV3716ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.MCU_TempAV3717ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_1.MotTempPIV3718FanAlrm_ZA_SupplyFan.ErrStatusPIV3719ZiehlAbegg_SupplyFan.FanStatus_ZA_1.WorkingStatusPIV3720ZiehlAbegg_SupplyFan.FanStatus_ZA_1.WorkStatusCodePIV3721ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_1.CurrSpeed_rpmPIV3722ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.DC_LinkVPIV3723ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.LineVPIV3724ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_1.MaxSpeed_rpmPIV3725ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_1.MinSpeed_rpmPIV3726ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.MotPwrAV3727ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.ElectronicTempAV3728ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.IGBT_tempAV3729ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.MCU_TempAV3730ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_1.MotTempPIV3731FanAlrm_ZA_RetFan.ErrStatusPIV3732ZiehlAbegg_ReturnFan.FanStatus_ZA_1.WorkingStatusPIV3733ZiehlAbegg_ReturnFan.FanStatus_ZA_1.WorkStatusCodePIV3734Humisonic.DevInfo_HUMS.FwRel_HPIV3735Humisonic.DevInfo_HUMS.FwRel_LIV3736Humisonic.DevInfo_HUMS.UnitHrsCountIV3737Humisonic.Humisonic_2_1.FwVars.CtrlStatePIV3738Humisonic.AlrmCode_HUMSPIV3739GeneralMng.DayPIV3740GeneralMng.MonthPIV3741GeneralMng.YearPIV3742GeneralMng.RTC.HourPIV3743GeneralMng.RTC.MinutePIV3744GeneralMng.RTC.SecondPIV3745GeneralMng.LastOnDayPIV3746GeneralMng.LastOnMonthPIV3747GeneralMng.LastOnYearPIV3748GeneralMng.LastOnHourPIV3749GeneralMng.LastOnMinutePIV3750GeneralMng.LastOnSecondPIV3751GeneralMng.OffDaysPIV3752GeneralMng.OffHoursPIV3753GeneralMng.OffMinutesPIV3754GeneralMng.FB_PollTPIV3755GeneralMng.FB_PollLoopNoPIV3756MemWritingsNoPIV3757GeneralMng.PrgCycleMsAV3758GeneralMng.CyclesPerSecondIV3759GeneralMng.ErrParamWizardPIV3760GeneralMng.DayOfWeekPIV3761Scheduler_OnOffUnit.FB_SchedulerMskMng_1.PrgsSchedMsgPIV3762WrkHrs_Unit.WrkHrsPIV3763WrkHrs_Unit.WrkHrs_LeftPIV3764WrkHrs_SupplyFan.WrkHrsPIV3765WrkHrs_SupplyFan.WrkHrs_LeftPIV3766WrkHrs_ReturnFan.WrkHrsPIV3767WrkHrs_ReturnFan.WrkHrs_LeftPIV3768WrkHrs_DirtyFilt.WrkHrsPIV3769WrkHrs_DirtyFilt.WrkHrs_LeftPIV3770WrkHrs_ThrmlWheel.WrkHrsPIV3771WrkHrs_ThrmlWheel.WrkHrs_LeftPIV3772WrkHrs_Comp.WrkHrsPIV3773WrkHrs_Comp.WrkHrs_LeftPIV3774WrkHrs_IEC.WrkHrsPIV3775WrkHrs_IEC.WrkHrs_LeftPIV3776WrkHrs_Humidifier.WrkHrsPIV3777WrkHrs_Humidifier.WrkHrs_LeftPIV3778WrkHrs_AuxDout.WrkHrsPIV3779WrkHrs_AuxDout.WrkHrs_LeftPIV3780WrkHrs_AuxAout.WrkHrsPIV3781WrkHrs_AuxAout.WrkHrs_LeftPIV3782WrkHrs_MainCoilPmp1.WrkHrsPIV3783WrkHrs_MainCoilPmp1.WrkHrs_LeftPIV3784WrkHrs_MainCoilPmp2.WrkHrsPIV3785WrkHrs_MainCoilPmp2.WrkHrs_LeftPIV3786WrkHrs_MainCoilAout.WrkHrsPIV3787WrkHrs_MainCoilAout.WrkHrs_LeftPIV3788WrkHrs_MainCoilStep1.WrkHrsPIV3789WrkHrs_MainCoilStep1.WrkHrs_LeftPIV3790WrkHrs_MainCoilStep2.WrkHrsPIV3791WrkHrs_MainCoilStep2.WrkHrs_LeftPIV3792WrkHrs_MainCoilStep3.WrkHrsPIV3793WrkHrs_MainCoilStep3.WrkHrs_LeftPIV3794WrkHrs_MainCoilStep4.WrkHrsPIV3795WrkHrs_MainCoilStep4.WrkHrs_LeftPIV3796WrkHrs_PreHeatCoilPmp1.WrkHrsPIV3797WrkHrs_PreHeatCoilPmp1.WrkHrs_LeftPIV3798WrkHrs_PreHeatCoilPmp2.WrkHrsPIV3799WrkHrs_PreHeatCoilPmp2.WrkHrs_LeftPIV3800WrkHrs_PreHeatCoilAout.WrkHrsPIV3801WrkHrs_PreHeatCoilAout.WrkHrs_LeftPIV3802WrkHrs_PreHeatCoilStep1.WrkHrsPIV3803WrkHrs_PreHeatCoilStep1.WrkHrs_LeftPIV3804WrkHrs_PreHeatCoilStep2.WrkHrsPIV3805WrkHrs_PreHeatCoilStep2.WrkHrs_LeftPIV3806WrkHrs_PreHeatCoilStep3.WrkHrsPIV3807WrkHrs_PreHeatCoilStep3.WrkHrs_LeftPIV3808WrkHrs_PreHeatCoilStep4.WrkHrsPIV3809WrkHrs_PreHeatCoilStep4.WrkHrs_LeftPIV3810WrkHrs_ReHeatCoilPmp1.WrkHrsPIV3811WrkHrs_ReHeatCoilPmp1.WrkHrs_LeftPIV3812WrkHrs_ReHeatCoilPmp2.WrkHrsPIV3813WrkHrs_ReHeatCoilPmp2.WrkHrs_LeftPIV3814WrkHrs_ReHeatCoilAout.WrkHrsPIV3815WrkHrs_ReHeatCoilAout.WrkHrs_LeftPIV3816WrkHrs_ReHeatCoilStep1.WrkHrsPIV3817WrkHrs_ReHeatCoilStep1.WrkHrs_LeftPIV3818WrkHrs_ReHeatCoilStep2.WrkHrsPIV3819WrkHrs_ReHeatCoilStep2.WrkHrs_LeftPIV3820WrkHrs_ReHeatCoilStep3.WrkHrsPIV3821WrkHrs_ReHeatCoilStep3.WrkHrs_LeftPIV3822WrkHrs_ReHeatCoilStep4.WrkHrsPIV3823WrkHrs_ReHeatCoilStep4.WrkHrs_LeftIV3824GeneralMng.ErrParamImpExpPIV3825Ebmpapst_ReturnFan.ParamsChgComStatus_EBM_1.StatusNewAddrProcPIV3826Ebmpapst_ReturnFan.ParamsChgComStatus_EBM_1.CommChangeStatusPIV3827ZiehlAbegg_ReturnFan.FanStatus_ZA_1.CommChangeStatusPIV3828Humisonic.HumCylinderWorkHrsLeftPIV3829Ebmpapst_SupplyFan.ParamsChgComStatus_EBM_1.StatusNewAddrProcPIV3830Ebmpapst_SupplyFan.ParamsChgComStatus_EBM_1.CommChangeStatusPIV3831ZiehlAbegg_SupplyFan.FanStatus_ZA_1.CommChangeStatusPIV3832VDI_Conf[0].CntDwnPIV3833VDI_Conf[1].CntDwnPIV3834VDI_Conf[2].CntDwnPIV3835VDI_Conf[3].CntDwnPIV3836VDI_Conf[4].CntDwnPIV3837VDI_Conf[5].CntDwnPIV3838VDI_Conf[6].CntDwnPIV3839VDI_Conf[7].CntDwnPIV3840VDI_Conf[8].CntDwnPIV3841VDI_Conf[9].CntDwnPIV3842VDI_Conf[10].CntDwnPIV3843VDI_Conf[11].CntDwnPIV3844VDI_Conf[12].CntDwnPIV3845VDI_Conf[13].CntDwnPIV3846VDI_Conf[14].CntDwnPIV3847VDI_Conf[15].CntDwnPIV3848VDI_Conf[16].CntDwnPIV3849VDI_Conf[17].CntDwnPIV3850VDI_Conf[18].CntDwnPIV3851VDI_Conf[19].CntDwnPIV3852VDI_Conf[20].CntDwnPIV3853VDI_Conf[21].CntDwnPIV3854VDI_Conf[22].CntDwnPIV3855VDI_Conf[23].CntDwnPIV3856VDI_Conf[24].CntDwnPIV3857VDI_Conf[25].CntDwnPIV3858VDI_Conf[26].CntDwnPIV3859VDI_Conf[27].CntDwnPIV3860VDI_Conf[28].CntDwnPIV3861GeneralMng.RTC_BMS.SecondPIV3862GeneralMng.Zone_ReadIV3863GeneralMng.SPV_ErrorPIV3864GeneralMng.IP_Byte4PIV3865GeneralMng.IP_Byte3PIV3866GeneralMng.IP_Byte2PIV3867GeneralMng.IP_Byte1PIV3868GeneralMng.GW_Byte4PIV3869GeneralMng.GW_Byte3PIV3870GeneralMng.GW_Byte2PIV3871GeneralMng.GW_Byte1PIV3872GeneralMng.NMSK_Byte4PIV3873GeneralMng.NMSK_Byte3PIV3874GeneralMng.NMSK_Byte2PIV3875GeneralMng.NMSK_Byte1PIV3876GeneralMng.DNS_Byte4PIV3877GeneralMng.DNS_Byte3PIV3878GeneralMng.DNS_Byte2PIV3879GeneralMng.DNS_Byte1IV3880Data_EVD_Emb_1.Superparameters.MainRegulation.ValAV3881Data_EVD_Emb_1.Inputs.S1.ValAV3882Data_EVD_Emb_1.Inputs.S2.ValAV3883Data_EVD_Emb_1.Inputs.S3.ValAV3884Data_EVD_Emb_1.Inputs.S4.ValPIV3885BLDC_compressor.IRparam_PWRP1.IR104_DriveStatusAV3886BLDC_compressor.Info_PWRP1.Info_DriveTempPIV3887BLDC_compressor.IRparam_PWRP1.IR105_AlrmCodeAV3888BLDC_compressor.Info_PWRP1.Info_FreqSetPAV3889BLDC_compressor.Info_PWRP1.Info_RotorSpeed_HzPIV3890BLDC_compressor.Info_PWRP1.Info_RotorSpeed_rpmAV3891BLDC_compressor.Info_PWRP1.Info_MotAPIV3892BLDC_compressor.Info_PWRP1.Info_MotVAV3893BLDC_compressor.Info_PWRP1.Info_MotPwrPIV3894BLDC_compressor.IRparam_PWRP1.IR113_DCBusVoltagePIV3895BLDC_compressor.IRparam_PWRP1.IR134_DCBusRipplePIV3896BLDC_compressor.IRparam_PWRP1.IR124_OperatingSwitchingFreqAV3897BLDC_compressor.IRparam_PWRP1.IR125_PreRampOutput_SpeedRefAV3898BLDC_compressor.IRparam_PWRP1.IR153_OvldMot_accumulatorAV3899BLDC_compressor.IRparam_PWRP1.IR154_OvldDrive_accumulatorAV3900BLDC_compressor.Info_PWRP1.Info_PSD_AAaPIV3901BLDC_compressor.Info_PWRP1.Mng_MotSelect_AAaAV3902BLDC_compressor.Info_PWRP1.UI_RatedStartingAAV3903BLDC_compressor.Info_PWRP1.UI_RatedCrankCaseHeatAAV3904BLDC_compressor.Info_PWRP1.UI_RatedInductsatReductAPIV3905BLDC_compressor.Info_PWRP1.Dbg_FBVersion_XPIV3906BLDC_compressor.Info_PWRP1.Dbg_FBVersion_YPIV3907BLDC_compressor.Info_PWRP1.Dbg_FBVersion_ZPIV3908BLDC_compressor.Info_PWRP1.Dbg_FBVersion_BetaPIV3909BLDC_compressor.IRparam_PWRP1.IR141_BootLoaderReleasePIV3910BLDC_compressor.IRparam_PWRP1.IR142_FirmwareReleasePIV3911BLDC_compressor.IRparam_PWRP1.IR143_FirmwareCRCPIV3912BLDC_compressor.IRparam_PWRP1.IR144_MotCtrlReleasePIV3913BLDC_compressor.IRparam_PWRP1.IR149_HardwareIdentificationAV3914Info_BLDC1.Info_CompRequestAV3915Info_BLDC1.Info_ReqSpeedToPWRPAV3916Info_BLDC1.Press_DscgP_BarAV3917Info_BLDC1.Press_SuctP_BarIV3918Info_BLDC1.Info_EnvZoneIV3919Info_BLDC1.Time_CntDwnOutEnvAV3920Info_BLDC1.Press_DeltaPAV3921Info_BLDC1.Press_RatioPIV3922Info_BLDC1.Time_CntDwnDeltaPAlrmAV3923Info_BLDC1.Info_DscgTempIV3924Info_BLDC1.Info_HTZoneAV3925Info_BLDC1.Info_ActiveDscgHTLimAV3926Info_BLDC1.Info_DscgSHPIV3927Info_BLDC1.Dbg_FBVersion_XPIV3928Info_BLDC1.Dbg_FBVersion_YPIV3929Info_BLDC1.Dbg_FBVersion_ZPIV3930Info_BLDC1.Dbg_FBVersion_BetaPIV3931GeneralMng.BACnet_ID_MaxAV3947MainVlv_PercAV3948PreHeatVlv_PercAV3949ReHeatVlv_PercAV4033SupplyTempRegSetPAV4034TempRegPIV3987AirQuality_PM10.Uom_WAV3988AirQuality_PM10.Val_Hw_RAV3989AirQuality_PM10.Val_RPIV4001AirQuality_PM25.Uom_WAV4002AirQuality_PM25.Val_Hw_RAV4003AirQuality_PM25.Val_RPIV3964WrkHrs_SanificationDevice.WrkHrsPIV3966WrkHrs_SanificationDevice.WrkHrs_LeftIV4077EBM_AlrmCode_SupplyFan1PIV4078Ebmpapst_SupplyFan.SenVal_EBM_1.AnemometerSpeedPIV4079Ebmpapst_SupplyFan.SenVal_EBM_1.AirFlowPIV4080Ebmpapst_SupplyFan.SenVal_EBM_1.MassFlowIV4081EBM_AlrmCode_ReturnFan1PIV4082Ebmpapst_ReturnFan.SenVal_EBM_1.AnemometerSpeedPIV4083Ebmpapst_ReturnFan.SenVal_EBM_1.AirFlowPIV4084Ebmpapst_ReturnFan.SenVal_EBM_1.MassFlowPIV4085Ebmpapst_SupplyFan.InfoSpeed_EBM_2.CurrSpeedPIV4086Ebmpapst_SupplyFan.ElectrInfo_EBM_2.DC_Link_VPIV4087Ebmpapst_SupplyFan.ElectrInfo_EBM_2.DC_Link_APIV4088Ebmpapst_SupplyFan.ElectrInfo_EBM_2.CurrPowerPIV4089Ebmpapst_SupplyFan.ElectrInfo_EBM_2.ElectrTempPIV4090Ebmpapst_SupplyFan.MotStatus_EBM_2.IR_MotStatusPIV4091Ebmpapst_SupplyFan.Warn_EBM_2.IR_WarnPIV4092Ebmpapst_SupplyFan.InfoSpeed_EBM_2.MaxSpeedPIV4093Ebmpapst_SupplyFan.CntWorkHrsBkp_EBM_2PIV4094Ebmpapst_SupplyFan.SenVal_EBM_2.AnemometerSpeedPIV4095Ebmpapst_SupplyFan.SenVal_EBM_2.AirFlowPIV4096Ebmpapst_SupplyFan.SenVal_EBM_2.MassFlowPIV4097ComStatus_Supply_EBM_2IV4098EBM_AlrmCode_SupplyFan2PIV4099Ebmpapst_SupplyFan.InfoSpeed_EBM_3.CurrSpeedPIV4100Ebmpapst_SupplyFan.ElectrInfo_EBM_3.DC_Link_VPIV4101Ebmpapst_SupplyFan.ElectrInfo_EBM_3.DC_Link_APIV4102Ebmpapst_SupplyFan.ElectrInfo_EBM_3.CurrPowerPIV4103Ebmpapst_SupplyFan.ElectrInfo_EBM_3.ElectrTempPIV4104Ebmpapst_SupplyFan.MotStatus_EBM_3.IR_MotStatusPIV4105Ebmpapst_SupplyFan.Warn_EBM_3.IR_WarnPIV4106Ebmpapst_SupplyFan.InfoSpeed_EBM_3.MaxSpeedPIV4107Ebmpapst_SupplyFan.CntWorkHrsBkp_EBM_3PIV4108Ebmpapst_SupplyFan.SenVal_EBM_3.AnemometerSpeedPIV4109Ebmpapst_SupplyFan.SenVal_EBM_3.AirFlowPIV4110Ebmpapst_SupplyFan.SenVal_EBM_3.MassFlowPIV4111ComStatus_Supply_EBM_3IV4112EBM_AlrmCode_SupplyFan3PIV4113Ebmpapst_SupplyFan.InfoSpeed_EBM_4.CurrSpeedPIV4114Ebmpapst_SupplyFan.ElectrInfo_EBM_4.DC_Link_VPIV4115Ebmpapst_SupplyFan.ElectrInfo_EBM_4.DC_Link_APIV4116Ebmpapst_SupplyFan.ElectrInfo_EBM_4.CurrPowerPIV4117Ebmpapst_SupplyFan.ElectrInfo_EBM_4.ElectrTempPIV4118Ebmpapst_SupplyFan.MotStatus_EBM_4.IR_MotStatusPIV4119Ebmpapst_SupplyFan.Warn_EBM_4.IR_WarnPIV4120Ebmpapst_SupplyFan.InfoSpeed_EBM_4.MaxSpeedPIV4121Ebmpapst_SupplyFan.CntWorkHrsBkp_EBM_4PIV4122Ebmpapst_SupplyFan.SenVal_EBM_4.AnemometerSpeedPIV4123Ebmpapst_SupplyFan.SenVal_EBM_4.AirFlowPIV4124Ebmpapst_SupplyFan.SenVal_EBM_4.MassFlowPIV4125ComStatus_Supply_EBM_4IV4126EBM_AlrmCode_SupplyFan4PIV4127Ebmpapst_ReturnFan.InfoSpeed_EBM_2.CurrSpeedPIV4128Ebmpapst_ReturnFan.ElectrInfo_EBM_2.DC_Link_VPIV4129Ebmpapst_ReturnFan.ElectrInfo_EBM_2.DC_Link_APIV4130Ebmpapst_ReturnFan.ElectrInfo_EBM_2.CurrPowerPIV4131Ebmpapst_ReturnFan.ElectrInfo_EBM_2.ElectrTempPIV4132Ebmpapst_ReturnFan.MotStatus_EBM_2.IR_MotStatusPIV4133Ebmpapst_ReturnFan.Warn_EBM_2.IR_WarnPIV4134Ebmpapst_ReturnFan.InfoSpeed_EBM_2.MaxSpeedPIV4135Ebmpapst_ReturnFan.CntWorkHrsBkp_EBM_2PIV4136Ebmpapst_ReturnFan.SenVal_EBM_2.AnemometerSpeedPIV4137Ebmpapst_ReturnFan.SenVal_EBM_2.AirFlowPIV4138Ebmpapst_ReturnFan.SenVal_EBM_2.MassFlowPIV4139ComStatus_Return_EBM_2IV4140EBM_AlrmCode_ReturnFan2PIV4141Ebmpapst_ReturnFan.InfoSpeed_EBM_3.CurrSpeedPIV4142Ebmpapst_ReturnFan.ElectrInfo_EBM_3.DC_Link_VPIV4143Ebmpapst_ReturnFan.ElectrInfo_EBM_3.DC_Link_APIV4144Ebmpapst_ReturnFan.ElectrInfo_EBM_3.CurrPowerPIV4145Ebmpapst_ReturnFan.ElectrInfo_EBM_3.ElectrTempPIV4146Ebmpapst_ReturnFan.MotStatus_EBM_3.IR_MotStatusPIV4147Ebmpapst_ReturnFan.Warn_EBM_3.IR_WarnPIV4148Ebmpapst_ReturnFan.InfoSpeed_EBM_3.MaxSpeedPIV4149Ebmpapst_ReturnFan.CntWorkHrsBkp_EBM_3PIV4150Ebmpapst_ReturnFan.SenVal_EBM_3.AnemometerSpeedPIV4151Ebmpapst_ReturnFan.SenVal_EBM_3.AirFlowPIV4152Ebmpapst_ReturnFan.SenVal_EBM_3.MassFlowPIV4153ComStatus_Return_EBM_3IV4154EBM_AlrmCode_ReturnFan3PIV4155Ebmpapst_ReturnFan.InfoSpeed_EBM_4.CurrSpeedPIV4156Ebmpapst_ReturnFan.ElectrInfo_EBM_4.DC_Link_VPIV4157Ebmpapst_ReturnFan.ElectrInfo_EBM_4.DC_Link_APIV4158Ebmpapst_ReturnFan.ElectrInfo_EBM_4.CurrPowerPIV4159Ebmpapst_ReturnFan.ElectrInfo_EBM_4.ElectrTempPIV4160Ebmpapst_ReturnFan.MotStatus_EBM_4.IR_MotStatusPIV4161Ebmpapst_ReturnFan.Warn_EBM_4.IR_WarnPIV4162Ebmpapst_ReturnFan.InfoSpeed_EBM_4.MaxSpeedPIV4163Ebmpapst_ReturnFan.CntWorkHrsBkp_EBM_4PIV4164Ebmpapst_ReturnFan.SenVal_EBM_4.AnemometerSpeedPIV4165Ebmpapst_ReturnFan.SenVal_EBM_4.AirFlowPIV4166Ebmpapst_ReturnFan.SenVal_EBM_4.MassFlowPIV4167ComStatus_Return_EBM_4IV4168EBM_AlrmCode_ReturnFan4IV4169ZA_AlrmCode_SupplyFan1IV4170ZA_AlrmCode_ReturnFan1PIV4171ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_2.CurrSpeed_rpmPIV4172ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.DC_LinkVPIV4173ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.LineVPIV4174ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_2.MaxSpeed_rpmPIV4175ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_2.MinSpeed_rpmPIV4176ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.MotPwrIV4177ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.ElectronicTempIV4178ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.IGBT_tempIV4179ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.MCU_TempIV4180ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_2.MotTempPIV4181FanAlrm_ZA_SupplyFan_2.ErrStatusPIV4182ZiehlAbegg_SupplyFan.FanStatus_ZA_2.WorkingStatusPIV4183ZiehlAbegg_SupplyFan.FanStatus_ZA_2.WorkStatusCodeIV4184ZA_AlrmCode_SupplyFan2PIV4185ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_3.CurrSpeed_rpmPIV4186ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.DC_LinkVPIV4187ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.LineVPIV4188ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_3.MaxSpeed_rpmPIV4189ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_3.MinSpeed_rpmPIV4190ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.MotPwrIV4191ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.ElectronicTempIV4192ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.IGBT_tempIV4193ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.MCU_TempIV4194ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_3.MotTempPIV4195FanAlrm_ZA_SupplyFan_3.ErrStatusPIV4196ZiehlAbegg_SupplyFan.FanStatus_ZA_3.WorkingStatusPIV4197ZiehlAbegg_SupplyFan.FanStatus_ZA_3.WorkStatusCodeIV4198ZA_AlrmCode_SupplyFan3PIV4199ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_4.CurrSpeed_rpmPIV4200ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.DC_LinkVPIV4201ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.LineVPIV4202ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_4.MaxSpeed_rpmPIV4203ZiehlAbegg_SupplyFan.FanSpeedInfo_ZA_4.MinSpeed_rpmPIV4204ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.MotPwrIV4205ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.ElectronicTempIV4206ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.IGBT_tempIV4207ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.MCU_TempIV4208ZiehlAbegg_SupplyFan.FanElectricalInfo_ZA_4.MotTempPIV4209FanAlrm_ZA_SupplyFan_4.ErrStatusPIV4210ZiehlAbegg_SupplyFan.FanStatus_ZA_4.WorkingStatusPIV4211ZiehlAbegg_SupplyFan.FanStatus_ZA_4.WorkStatusCodeIV4212ZA_AlrmCode_SupplyFan4PIV4213ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_2.CurrSpeed_rpmPIV4214ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.DC_LinkVPIV4215ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.LineVPIV4216ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_2.MaxSpeed_rpmPIV4217ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_2.MinSpeed_rpmPIV4218ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.MotPwrIV4219ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.ElectronicTempIV4220ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.IGBT_tempIV4221ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.MCU_TempIV4222ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_2.MotTempPIV4223FanAlrm_ZA_RetFan_2.ErrStatusPIV4224ZiehlAbegg_ReturnFan.FanStatus_ZA_2.WorkingStatusPIV4225ZiehlAbegg_ReturnFan.FanStatus_ZA_2.WorkStatusCodeIV4226ZA_AlrmCode_ReturnFan2PIV4227ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_3.CurrSpeed_rpmPIV4228ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.DC_LinkVPIV4229ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.LineVPIV4230ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_3.MaxSpeed_rpmPIV4231ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_3.MinSpeed_rpmPIV4232ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.MotPwrIV4233ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.ElectronicTempIV4234ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.IGBT_tempIV4235ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.MCU_TempIV4236ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_3.MotTempPIV4237FanAlrm_ZA_RetFan_3.ErrStatusPIV4238ZiehlAbegg_ReturnFan.FanStatus_ZA_3.WorkingStatusPIV4239ZiehlAbegg_ReturnFan.FanStatus_ZA_3.WorkStatusCodeIV4240ZA_AlrmCode_ReturnFan3PIV4241ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_4.CurrSpeed_rpmPIV4242ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.DC_LinkVPIV4243ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.LineVPIV4244ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_4.MaxSpeed_rpmPIV4245ZiehlAbegg_ReturnFan.FanSpeedInfo_ZA_4.MinSpeed_rpmPIV4246ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.MotPwrIV4247ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.ElectronicTempIV4248ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.IGBT_tempIV4249ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.MCU_TempIV4250ZiehlAbegg_ReturnFan.FanElectricalInfo_ZA_4.MotTempPIV4251FanAlrm_ZA_RetFan_4.ErrStatusPIV4252ZiehlAbegg_ReturnFan.FanStatus_ZA_4.WorkingStatusPIV4253ZiehlAbegg_ReturnFan.FanStatus_ZA_4.WorkStatusCodeIV4254ZA_AlrmCode_ReturnFan4PIV4267WrkHrs_SupplyFan_2.WrkHrsPIV4268WrkHrs_SupplyFan_2.WrkHrs_LeftPIV4269WrkHrs_SupplyFan_3.WrkHrsPIV4270WrkHrs_SupplyFan_3.WrkHrs_LeftPIV4271WrkHrs_SupplyFan_4.WrkHrsPIV4272WrkHrs_SupplyFan_4.WrkHrs_LeftPIV4273WrkHrs_ReturnFan_2.WrkHrsPIV4274WrkHrs_ReturnFan_2.WrkHrs_LeftPIV4275WrkHrs_ReturnFan_3.WrkHrsPIV4276WrkHrs_ReturnFan_3.WrkHrs_LeftPIV4277WrkHrs_ReturnFan_4.WrkHrsPIV4278WrkHrs_ReturnFan_4.WrkHrs_LeftAV4279Fans.Value_AVGAV4280Fans.AvgTimeData_AVG.DailyAV4281Fans.AvgTimeData_AVG.MonthlyAV4282HeatExchanger.Value_AVGAV4283HeatExchanger.AvgTimeData_AVG.DailyAV4284HeatExchanger.AvgTimeData_AVG.MonthlyIV4346HumiSteamMng.CntCylHr_UEYIV4347HumiSteamMng.HumState_UEYIV4348HumiSteamMng.Curr_UEYIV4349HumiSteamMng.Conductivity_UEYIV4350HumiSteamMng.SteamInstantFlowRate_UEYIV4351UEY_AlrmCodeAV4370Fans_regulation.SupplyFan_FanTempReg_SetPOffsAV4371Fans_regulation.SupplyFan_FC_FH_SetPOffsAV4372Fans_regulation.RetFan_FanTempReg_SetPOffsAV4373Fans_regulation.RetFan_FC_FH_SetPOffsPIV4388GenericAin1.Uom_WAV4389GenericAin1.Val_Hw_RAV4390GenericAin1.Val_RPIV4402GenericAin2.Uom_WAV4403GenericAin2.Val_Hw_RAV4404GenericAin2.Val_RPIV4416GenericAin3.Uom_WAV4417GenericAin3.Val_Hw_RAV4418GenericAin3.Val_RPIV4430GenericAin4.Uom_WAV4431GenericAin4.Val_Hw_RAV4432GenericAin4.Val_RPIV4444GenericAin5.Uom_WAV4445GenericAin5.Val_Hw_RAV4446GenericAin5.Val_RAV4562OA_CoilRegReqAV4563OA_CoilReqPIV4564WrkHrs_OA_CoilAout.WrkHrsPIV4565WrkHrs_OA_CoilAout.WrkHrs_LeftPIV4566WrkHrs_OA_CoilStep1.WrkHrsPIV4567WrkHrs_OA_CoilStep1.WrkHrs_LeftPIV4568WrkHrs_OA_CoilStep2.WrkHrsPIV4569WrkHrs_OA_CoilStep2.WrkHrs_LeftPIV4570WrkHrs_OA_CoilStep3.WrkHrsPIV4571WrkHrs_OA_CoilStep3.WrkHrs_LeftPIV4572WrkHrs_OA_CoilStep4.WrkHrsPIV4573WrkHrs_OA_CoilStep4.WrkHrs_LeftPIV4574OA_Vlv_PercPIV3596AirFlwValPIV3597RetAirFlwVal
Integration notes
- The table gives Modbus classes, not a BACnet access column. Access here follows the Modbus class: coils and holding registers W, discrete inputs and input registers R.
- Object names are the CAREL variable names from the table. No engineering units are printed; descriptions carry the Modbus address, value meanings, and a 32-bit flag for Dim 2 variables.
- Repeated rows in the source were dropped (CS112, DI1159, HR614/615, IR118/119, IR626-632). On page 136 the source repeats 12 rows from page 133 (DI340-DI366) between wrapped variable names; those repeats were dropped and the wrapped names joined.
- One printed instance clash is kept as printed: BV 1436 (DI1210) for two ZA return fan alarms. The CoilRegOffset row on page 144 is garbled (it repeats HR143/PIV1666 and PIV1667 from the previous page next to HR192/AV1715); it is listed as AV 1715 (Modbus HR192), which fits the table's sequence. OA_CoilActMode is printed as PI4577 and listed as PIV 4577.
- The supervisor table skips some Modbus addresses; a few objects (for example AV 3436) appear only in the manual's parameter tables and are not in this list.
- Which serial or Ethernet port speaks BACnet is set in menu Y (BMS Line or BMS2 Line = BACnet MS/TP, Ethernet 2 Line = BACnet IP).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the k.air air handling unit controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the CAREL k.air air handling unit controller
How many BACnet points does the CAREL k.air air handling unit controller have?
This list has 4350 BACnet objects: 739 analog values, 1596 binary values, 136 integer values, 1879 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which CAREL k.air air handling unit controller BACnet points are writable?
2473 of the 4350 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official CAREL k.air air handling unit controller BACnet documentation?
The source is k.air - Air handling unit controller, user manual (11. Supervisor variable table) (+030220981), revision rel. 1.8 - 2026-06-25, published free by CAREL at https://www.carel.com/documents/10191/0/%2B030220981/14d83d46-c7fc-403d-b38d-2688a78559ef?version=1.11.
What are the minimum BACnet points to integrate the CAREL k.air air handling unit controller?
Start with BV 234 Scheduler_OnOffUnit.BMS_OnOff_En (Must be on for the BMS on/off command to work); BV 2 Scheduler_OnOffUnit.BMS_OnOff (Unit on/off command from the BMS); BV 4 SummerWinter_BMS (Summer/winter command (0 = summer, 1 = winter)); AV 2585 UnitSetP.TempSetP.Winter.Comfort (Winter comfort temperature setpoint); AV 2584 UnitSetP.TempSetP.Summer.Comfort (Summer comfort temperature setpoint); BV 1 AlarmsMng.AlrmResByBms (Alarm reset); PIV 3645 SchedStatus (Active status: 0 off, 1 economy, 2 pre-comfort, 3 comfort); AV 3435 SupplyTemp.Val_Hw_R (Supply air temperature (probe reading)); AV 3442 RetTemp.Val_R (Return air temperature); BV 902 GlobalAlrm_Dout.Val_W (Generic alarm active).
How do I enable BMS control of the CAREL k.air air handling unit controller?
The unit can be switched by keypad/th-Tune, BMS, digital input and scheduler; any enabled source set to off stops it. BMS on/off works only when BV 234 (enable on/off request by BMS) is on; BV 2 then turns the unit on or off.
Does the CAREL k.air air handling unit controller need a BACnet heartbeat or have a communication timeout?
PIV 2898 selects BMS offline handling (0 disabled, 1 warning only, 2 alarm, 3 alarm with timeout) and PIV 2899 sets the timeout, 120 s by default. BV 1347 shows the BMS offline alarm.
How do I check these points on the real k.air air handling unit controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More CAREL BACnet points lists
- Gas-fired steam humidifier
CAREL gaSteam (UG) gas-fired humidifier
CAREL gaSteam UG gas-fired isothermal steam humidifiers (indoor and outdoor versions, single unit or Main/Secondary pairs).
Also known as: gaSteam, UG, UG045, UG090, UG180, CAREL gas-fired steam humidifier, +0300122EN - Electric resistance steam humidifier
CAREL heaterSteam 4 (UR) process / titanium
CAREL heaterSteam UR electric heater steam humidifiers (process and titanium versions) with the c.pHC-based controller, manual +0300087EN.
Also known as: heaterSteam, heaterSteam 4, heaterSteam process, heaterSteam titanium, UR, URH, CAREL electric resistance humidifier, +0300087EN - Electric resistance steam humidifier
CAREL heaterSteam UR (2018 manual, before heaterSteam 4)
CAREL heaterSteam UR electric heater steam humidifiers of the generation before heaterSteam 4, as covered by manual +0300080EN rel. 1.4 (2018).
Also known as: heaterSteam, heaterSteam UR, UR002, UR080, CAREL resistance steam humidifier, +0300080EN - High-pressure atomising humidifier (direct room)
CAREL humiFog direct (UA) high-pressure atomising humidifier
CAREL humiFog direct UA pumping stations with c.pHC controller, one or two humidification zones in the room.
Also known as: humiFog direct, humiFog Direct, UA, c.pHC, CAREL humiFog, +0300073EN
Source: k.air - Air handling unit controller, user manual (11. Supervisor variable table) · +030220981 · rev. rel. 1.8 - 2026-06-25. Object names, instances and units are reproduced as published; descriptions are our own.