Electric resistance steam humidifier · BACnet points list

CAREL heaterSteam 4 (UR) process / titanium BACnet points list

Updated 4 November 2026

Short answer

heaterSteam 4 is CAREL's resistance-heated isothermal steam humidifier; this entry covers the heaterSteam 4 generation documented in manual +0300087EN rel. 1.7 (2025). BACnet MS/TP (on the RS485 BMS port) and BACnet IP (on the Ethernet port) are built into the c.pHC controller, one at a time. The object list has positive-integer values for status, hours, probe and scheduler settings, analog values for probes, set points and production, and binary values for on/off commands, level sensors and every alarm.

This page lists 248 BACnet objects for the CAREL heaterSteam 4 (UR) process / titanium — 123 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CAREL’s own free documentation, linked below.

Manufacturer
CAREL
Model
heaterSteam 4 (UR) process / titanium
Equipment
Electric resistance steam humidifier
Equipment type
Humidifiers
BACnet objects
248 (123 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
77000
Also known as
heaterSteam, heaterSteam 4, heaterSteam process, heaterSteam titanium, UR, URH, CAREL electric resistance humidifier, +0300087EN
Source document
heaterSteam - UR Electric resistance humidifier - User manual · +0300087EN rel. 1.7 · rev. 2025-04-18
Download CSV 248 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CAREL’s current documentation and the live device before use. Not official CAREL information. Terms of use.

BMS integration notes: CAREL heaterSteam 4 (UR) process / titanium

Integration in brief

Pick the port and protocol (Eh01 for the BMS port, Eh06 for Ethernet), set the device instance and UDP port on Eh04, then enable on/off and control from supervisor on Eh07/Eh08. The BMS starts and stops the unit with OnBySV (BV 6) and either sends a production request on SV_PwrReq (AV 11) or writes the humidity set point (AV 14). Monitor OnOffStatus, UnitStatus, current production and the summary alarm BVs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 6OnBySVUnit on/off from the BMSWrite
AV 11SV_PwrReqProduction request from the BMS, 0-100 %Write
AV 14GlbSetP_HumHumidity set point, %RH (own probe control)Write
BV 5OnOffStatusUnit on/off statusRead
PIV 12UnitStatusOperating state codeRead
AV 0MainPrbMain probe readingRead
AV 12CurrProdPhCurrent steam production, kg/h or lb/hRead
BV 14CurrBlkAlrm.IsPresentResettable alarm activeRead
BV 13CurrBlkAlrm.IsBlockerShutdown alarm activeRead

Enable & remote start

On screens Eh07/Eh08 select the supervisor port and enable 'On/Off signal from supervisor' and 'control from supervisor' (the BMS-port Eh01 settings 'On/Off from SV' and 'Control from SV' default to No). Without them the unit ignores the supervisor on/off and production request.

Heartbeat & communication loss

Eh08 can enable a supervisor-offline alarm (Alrm_SVOffline.Active, BV 93). The manual does not describe what the unit does with its output when the supervisor goes offline.

Sensors & values from the BMS

With control from supervisor the BMS sends the production request on SV_PwrReq (AV 11) instead of the unit using its own probe. Up to four CAREL wireless probes can also feed the unit.

Network setup

Watch out for

CAREL heaterSteam 4 (UR) process / titanium BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

248 of 248 shown
Type
AnalogBinaryOther
Access
Show
CAREL heaterSteam 4 (UR) process / titanium BACnet Points List
DescriptionStates
PIV0SV_SWVerSoftware versionRead
PIV1SV_OSVerOS versionRead
PIV2UnitModelModel versionRead
PIV3ConductivityInlet water conductivity readingµS/cmRead
PIV4WirelessPrbInfo_1.BattLevWireless probe 1 reading: battery levelRead0=Empty, 1=25%, 2=50%, 3=75%, 4=100%
PIV5WirelessPrbInfo_1.RadioSignalLevWireless probe 1 reading: radio signal levelRead0=Absent, 1-7=Very poor, 8-14=Poor, 15-30=Good, 31-100=Excellent
PIV6WirelessPrbInfo_2.BattLevWireless probe 2 reading: battery levelRead0=Empty, 1=25%, 2=50%, 3=75%, 4=100%
PIV7WirelessPrbInfo_2.RadioSignalLevWireless probe 2 reading: radio signal levelRead0=Absent, 1-7=Very poor, 8-14=Poor, 15-30=Good, 31-100=Excellent
PIV8WirelessPrbInfo_3.BattLevWireless probe 3 reading: battery levelRead0=Empty, 1=25%, 2=50%, 3=75%, 4=100%
PIV9WirelessPrbInfo_3.RadioSignalLevWireless probe 3 reading: radio signal levelRead0=Absent, 1-7=Very poor, 8-14=Poor, 15-30=Good, 31-100=Excellent
PIV10WirelessPrbInfo_4.BattLevWireless probe 4 reading: battery levelRead0=Empty, 1=25%, 2=50%, 3=75%, 4=100%
PIV11WirelessPrbInfo_4.RadioSignalLevWireless probe 4 reading: radio signal levelRead0=Absent, 1-7=Very poor, 8-14=Poor, 15-30=Good, 31-100=Excellent
PIVmin12UnitStatusUnit statusRead0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV13WorkHrUnit lifetime hourshRead
PIV14CylWorkHrCylinder lifetime hourshRead
PIV15ManMode_mskStart manual modeWrite0=Disabled, 1=Manual outputs, 2=Manual production
PIV16ManSSR_OpTSet ON time for SSR heater power control cycle in manual modemsWrite
PIV17ManSSR_ClTSet OFF time for SSR heater power control cycle in manual modemsWrite
PIV18RegulationCfg.RegTypControl modeWrite0=External proportional signal, 1=External proportional signal + limit, 2=ON/OFF signal, 3=Humidity (one probe), 4=Temperature (one probe), 5=Humidity + limit, 6=Temperature + limit, 7=Humidity (two probes), 8=Temperature (two probes)
PIV19ThrshAlrmDTSet high humidity/temperature alarm thresholdsWrite
PIV20MainPrbCfg.UITypSet main probe typeWrite0=0-1V, 1=0-10V, 2=2-10V, 5=NTC, 3=0-20mA, 4=4-20mA
PIV21LimitPrbCfg.UITypSet limit probe typeWrite0=0-1V, 1=0-10V, 2=2-10V, 3=0-20mA, 4=4-20mA, 5=NTC
PIV22WHardnessManSet water hardness value, if manual modeWrite0=0-10°F, 1=10-20°F, 2=20-30°F, 3=30-40°F, 4=Demineralised
PIV23EvapCycleNoThrshEvaporation cycles before drain to dilute (micro-filling off)Write0=AUTO
PIV24FillTScaleExtra filling time after green LED level (micro-filling off)%Write
PIV25DilDrainTScaleSet drain time modification%Write
PIV26Scheduler.SchedDayToSetScheduler: day of week to configureWrite1=Monday, 2=Tuesday, 3=Wednesday, 4=Thursday, 5=Friday, 6=Saturday, 7=Sunday
PIV27SchedDayCfg[0].StartHrScheduler: band 1 start hourshWrite
PIV28SchedDayCfg[0].StartMinScheduler: band 1 start minutesminWrite
PIV29SchedDayCfg[0].WorkModeScheduler: band 1 operating modeWrite
PIV30SchedDayCfg[1].StartHrScheduler: band 2 start hourshWrite
PIV31SchedDayCfg[1].StartMinScheduler: band 2 start minutesminWrite
PIV32SchedDayCfg[1].WorkModeScheduler: band 2 operating modeWrite
PIV33SchedDayCfg[2].StartHrScheduler: band 3 start hourshWrite
PIV34SchedDayCfg[2].StartMinScheduler: band 3 start minutesminWrite
PIV35SchedDayCfg[2].WorkModeScheduler: band 3 operating modeWrite
PIV36SchedDayCfg[3].StartHrScheduler: band 4 start hourshWrite
PIV37SchedDayCfg[3].StartMinScheduler: band 4 start minutesminWrite
PIV38SchedDayCfg[3].WorkModeScheduler: band 4 operating modeWrite
PIV39SchedDayCfg[4].StartHrScheduler: band 5 start hourshWrite
PIV40SchedDayCfg[4].StartMinScheduler: band 5 start minutesminWrite
PIV41SchedDayCfg[4].WorkModeScheduler: band 5 operating modeWrite
PIV42SchedDayCfg[5].StartHrScheduler: band 6 start hourshWrite
PIV43SchedDayCfg[5].StartMinScheduler: band 6 start minutesminWrite
PIV44SchedDayCfg[5].WorkModeScheduler: band 6 operating modeWrite
PIV45UoMUnit of measureWrite0=Default, 1=Int. system °C, kg/h, 2=Imperial °F, lb/h
PIV46YearYearyearsWrite
PIV47MonthMonthmonthsWrite
PIV48DayDaydaysWrite
PIV49HourHourshWrite
PIV50MinuteMinutesminWrite
PIV51SetTimezoneTime zoneWriteTime-zone code; see the manual list (0=not set)
PIV52NetStatus[1]Network unit status: unit 1Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV53NetStatus[2]Network unit status: unit 2Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV54NetStatus[3]Network unit status: unit 3Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV55NetStatus[4]Network unit status: unit 4Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV56NetStatus[5]Network unit status: unit 5Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV57NetStatus[6]Network unit status: unit 6Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV58NetStatus[7]Network unit status: unit 7Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV59NetStatus[8]Network unit status: unit 8Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV60NetStatus[9]Network unit status: unit 9Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV61NetStatus[10]Network unit status: unit 10Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV62NetStatus[11]Network unit status: unit 11Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV63NetStatus[12]Network unit status: unit 12Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV64NetStatus[13]Network unit status: unit 13Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV65NetStatus[14]Network unit status: unit 14Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV66NetStatus[15]Network unit status: unit 15Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV67NetStatus[16]Network unit status: unit 16Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV68NetStatus[17]Network unit status: unit 17Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV69NetStatus[18]Network unit status: unit 18Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV70NetStatus[19]Network unit status: unit 19Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV71NetStatus[20]Network unit status: unit 20Read0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring
PIV72SV_CommandSupervisor command: reset alarms or hour counterWrite1=reset alarm, 2=reset hour counter
PIV73SV_CommandResultResult of the commandRead1=successful, 2=failed, 3=invalid command
PIV80PreMaintWarnThrshSet next maintenance pre-alert timehWrite
PIV81HiConductAlrmDlyTSet high conductivity alarm delayminWrite
PIV82HiConductWarnThrshSet high conductivity warning thresholdµS/cmWrite
PIV83HiConductAlrmThrshSet high conductivity alarm thresholdµS/cmWrite
PIV84HiConductWarnHystSet high conductivity warning threshold hysteresis%Write
PIV85FoamLevSetPScaleFoam sensor sensitivity (0%-200% - def. 100%)%Write
PIV86PartFillsTSet micro-fill cycle durationsWrite
PIV87DilDrainCfg.TypDrain to dilute mode with micro-fill activeWrite0=Disabled, 1=Daily scheduler, 2=Periodic
PIV89DilDrainCfg.PeriodicDilDrainThrshHours between periodic drain to dilute cycles (micro-filling on)hWrite
PIV90DilDrainCfg.DailySched[1].Start_hDrain to dilute - Daily scheduler (Monday) - hourshWrite
PIV91DilDrainCfg.DailySched[1].Start_minDrain to dilute - Daily scheduler (Monday) - minutesminWrite
PIV92DilDrainCfg.DailySched[2].Start_hDrain to dilute - Daily scheduler (Tuesday) - hourshWrite
PIV93DilDrainCfg.DailySched[2].Start_minDrain to dilute - Daily scheduler (Tuesday) - minutesminWrite
PIV94DilDrainCfg.DailySched[3].Start_hDrain to dilute - Daily scheduler (Wednesday) - hourshWrite
PIV95DilDrainCfg.DailySched[3].Start_minDrain to dilute - Daily scheduler (Wednesday) - minutesminWrite
PIV96DilDrainCfg.DailySched[4].Start_hDrain to dilute - Daily scheduler (Thursday) - hourshWrite
PIV97DilDrainCfg.DailySched[4].Start_minDrain to dilute - Daily scheduler (Thursday) - minutesminWrite
PIV98DilDrainCfg.DailySched[5].Start_hDrain to dilute - Daily scheduler (Friday) - hourshWrite
PIV99DilDrainCfg.DailySched[5].Start_minDrain to dilute - Daily scheduler (Friday) - minutesminWrite
PIV100DilDrainCfg.DailySched[6].Start_hDrain to dilute - Daily scheduler (Saturday) - hourshWrite
PIV101DilDrainCfg.DailySched[6].Start_minDrain to dilute - Daily scheduler (Saturday) - minutesminWrite
PIV102DilDrainCfg.DailySched[7].Start_hDrain to dilute - Daily scheduler (Sunday) - hourshWrite
PIV103DilDrainCfg.DailySched[7].Start_minDrain to dilute - Daily scheduler (Sunday) - minutesminWrite
PIV104PeriodicDrainThrshProduction hours between two periodic total drainshWrite
PIV105ExtFanDTOnSet start blower delay from start of productionsWrite
PIV106ExtFanDTOffSet stop blower delay from end of productionsWrite
PIV129WorkHrCntDwnTime remaining until next maintenancehRead
PIV130CylResDate.YearCylinder production hours reset date - YearyearsRead
PIV131CylResDate.MonthCylinder production hours reset date - MonthmonthsRead
PIV132CylResDate.DayCylinder production hours reset date - DaydaysRead
PIV133CylResDate.HourCylinder production hours reset date - HourshRead
PIV134CylResDate.MinuteCylinder production hours reset date - MinutesminRead
AVmin0MainPrbMain probe readingRead
AV1LimitPrbLimit probe readingRead
AV2PreheatPrbWater preheating probe reading°C or °FRead
AV3WirelessPrbVal_1.HumWireless probe 1 reading: Humidity%RHRead
AV4WirelessPrbVal_1.TempWireless probe 1 reading: Temperature°C or °FRead
AV5WirelessPrbVal_2.HumWireless probe 2 reading: Humidity%RHRead
AV6WirelessPrbVal_2.TempWireless probe 2 reading: Temperature°C or °FRead
AV7WirelessPrbVal_3.HumWireless probe 3 reading: Humidity%RHRead
AV8WirelessPrbVal_3.TempWireless probe 3 reading: Temperature°C or °FRead
AV9WirelessPrbVal_4.HumWireless probe 4 reading: Humidity%RHRead
AV10WirelessPrbVal_4.TempWireless probe 4 reading: Temperature°C or °FRead
AVmin11SV_PwrReqSet production percentage request from supervisor%Write
AVmin12CurrProdPhCurrent production kg/h (lbs/h)kg/h or lb/hRead
AV13ManReqEnable manual production request%Write
AVmin14GlbSetP_HumSet humidity value (humidity set point)%RHWrite
AV15GlbSetP_TempSet temperature value (temperature set point)°C or °FWrite
AV16RegulationCfg.HystSet control hysteresis%Write
AV17RegulationCfg.DiffSet control differentialWrite
AV18GlbSetPLim_HumSet humidity limit value (humidity limit set point)%RHWrite
AV19GlbSetPLim_TempSet temperature limit value (temperature limit set point)°C or °FWrite
AV20RegulationCfg.DiffLimSet limit differentialWrite
AV21RegulationCfg.MinReqSet maximum production value%Write
AV22AlrmThrshHumLoSet main probe low humidity alarm threshold%RHWrite
AV23AlrmThrshHumHiSet main probe high humidity alarm threshold%RHWrite
AV24AlrmThrshHumHiLimSet limit probe low humidity alarm threshold%RHWrite
AV25AlrmThrshTempLoSet main probe low temperature alarm threshold°C or °FWrite
AV26AlrmThrshTempHiSet main probe high temperature alarm threshold°C or °FWrite
AV27AlrmThrshTempHiLimSet limit probe low temperature alarm threshold°C or °FWrite
AV28MainPrbCfg.Mi_HumSet main probe minimum humidity value%RHWrite
AV29MainPrbCfg.Ma_HumSet main probe maximum humidity%RHWrite
AV30MainPrbCfg.Mi_TempSet main probe minimum temperature°C or °FWrite
AV31MainPrbCfg.Ma_TempSet main probe maximum temperature°C or °FWrite
AV32LimitPrbCfg.Mi_HumSet limit probe minimum humidity value%RHWrite
AV33LimitPrbCfg.Ma_HumSet limit probe maximum humidity value%RHWrite
AV34LimitPrbCfg.Mi_TempSet limit probe minimum temperature value°C or °FWrite
AV35LimitPrbCfg.Ma_TempSet limit probe maximum temperature value°C or °FWrite
AV36RegulationCfg.PwrCorrectionFactorSet power correction for thermal dissipation%Write
AV37SchedDayCfg[0].SetPScheduler: band 1 set pointWrite
AV38SchedDayCfg[1].SetPScheduler: band 2 set pointWrite
AV39SchedDayCfg[2].SetPScheduler: band 3 set pointWrite
AV40SchedDayCfg[3].SetPScheduler: band 4 set pointWrite
AV41SchedDayCfg[4].SetPScheduler: band 5 set pointWrite
AV42SchedDayCfg[5].SetPScheduler: band 6 set pointWrite
AV43NetReqCurrent system request%Read
AV44NetProdCurrent system productionkg/h or lb/hRead
AV45MaxUnitProdSet maximum production value%Write
AV46RegulationCfg.W_MinTempThrshSet water preheating temperature°C or °FWrite
AV47PreheatOffset_TempPreheating offset from temperature set point°C or °FWrite
AV48PreheatOffset_HumPreheating offset from humidity set point%RHWrite
AV49ProdReqMskProduction request%Read
AV53FoamLevRealSignal reading from foam sensorRead
BV0RemOnRemote on/off commandRead
BV1ThermPtcDinThermal protection statusRead
BV2LevSenStatus.LowLevel sensor reading: low levelRead
BV3LevSenStatus.HiLevel sensor reading: high levelRead
BV4LevSenStatus.FoamHigh level sensor reading: foamRead
BVmin5OnOffStatusUnit status on/offRead
BVmin6OnBySVOn/off control from supervisor (SV)Write
BV11WHardnessTypSet water hardness management modeWrite0=AUTO, 1=MANUAL
BV12PreMaintWarnSet next maintenance pre-alert timeRead
BVmin13CurrBlkAlrm.IsBlockerShutdown alarm activeRead
BVmin14CurrBlkAlrm.IsPresentResettable alarm activeRead
BV15CurrBlkAlrm.WarningWarningRead
BV16Alrm_Autotest.ActiveAlarm ALC01: AutotestRead
BV17Alrm_HighConductAl.ActiveAlarm ALC02: High conductivityRead
BV18Alrm_LevSen.ActiveAlarm ALC03: Level sensor brokenRead
BV19Alrm_ThermPtc.ActiveAlarm ALC04: Motor protectionRead
BV20Alrm_WMiss.ActiveAlarm ALB01: No waterRead
BV21Alrm_LowProd.ActiveAlarm ALB02: Low productionRead
BV22Alrm_MainPrb.ActiveAlarm ALA01: Main probe brokenRead
BV23Alrm_LimPrb.ActiveAlarm ALA02: Limit probe brokenRead
BV24Alrm_PreHPrb.ActiveAlarm ALA03: Preheating probe brokenRead
BV25Alrm_HiHum.ActiveAlarm ALH01: High humidity/temperatureRead
BV26Alrm_LoHum.ActiveAlarm ALH02: Low humidity/temperatureRead
BV27Alrm_HiHum_Lim.ActiveAlarm ALH03: High humidity/temperature: limit probeRead
BV28Alrm_Foam.ActiveAlarm ALW01: Foam warningRead
BV29Alrm_PeriodicMaint.ActiveAlarm ALT01: Maintenance requestRead
BV30Alrm_CylFull.ActiveAlarm ALW02: Cylinder fullRead
BV31Alrm_ConductPrb.ActiveAlarm ALA04: Conductivity meter broken/not connectedRead
BV32Alrm_HighConductWr.ActiveWarning ALW03: High conductivityRead
BV33Alrm_RetMem.ActiveAlarm ALR01: Retain memoryRead
BV34Warn_Autotest.ActiveWarning ALW04: Autotest, saved only, not displayedRead
BV35Warn_LevSen.ActiveWarning ALW05: Level sensorRead
BV36Warn_LowProd.ActiveWarning ALW06: Low production, saved only, not displayedRead
BV37Alrm_WirelessPrb_1_Offline.ActiveAlarm ALP01: Wireless probe 1: offlineRead
BV38Alrm_WirelessPrb_2_Offline.ActiveAlarm ALP02: Wireless probe 2: offlineRead
BV39Alrm_WirelessPrb_3_Offline.ActiveAlarm ALP03: Wireless probe 3: offlineRead
BV40Alrm_WirelessPrb_4_Offline.ActiveAlarm ALP04: Wireless probe 4: offlineRead
BV41Alrm_MissingModel.ActiveAlarm ALM01: Humidifi er model not setRead
BV42Alrm_NetUnit_1.ActiveAlarm ALN01: Network: unit 1 alarmRead
BV43Alrm_NetUnit_2.ActiveAlarm ALN2: Network: unit 2 alarmRead
BV44Alrm_NetUnit_3.ActiveAlarm ALN3: Network: unit 3 alarmRead
BV45Alrm_NetUnit_4.ActiveAlarm ALN4: Network: unit 4 alarmRead
BV46Alrm_NetUnit_5.ActiveAlarm ALN5: Network: unit 5 alarmRead
BV47Alrm_NetUnit_6.ActiveAlarm ALN6: Network: unit 6 alarmRead
BV48Alrm_NetUnit_7.ActiveAlarm ALN7: Network: unit 7 alarmRead
BV49Alrm_NetUnit_8.ActiveAlarm ALN8: Network: unit 8 alarmRead
BV50Alrm_NetUnit_9.ActiveAlarm ALN9: Network: unit 9 alarmRead
BV51Alrm_NetUnit_10.ActiveAlarm ALN10: Network: unit 10 alarmRead
BV52Alrm_NetUnit_11.ActiveAlarm ALN11: Network: unit 11 alarmRead
BV53Alrm_NetUnit_12.ActiveAlarm ALN12: Network: unit 12 alarmRead
BV54Alrm_NetUnit_13.ActiveAlarm ALN13: Network: unit 13 alarmRead
BV55Alrm_NetUnit_14.ActiveAlarm ALN14: Network: unit 14 alarmRead
BV56Alrm_NetUnit_15.ActiveAlarm ALN15: Network: unit 15 alarmRead
BV57Alrm_NetUnit_16.ActiveAlarm ALN16: Network: unit 16 alarmRead
BV58Alrm_NetUnit_17.ActiveAlarm ALN17: Network: unit 17 alarmRead
BV59Alrm_NetUnit_18.ActiveAlarm ALN18: Network: unit 18 alarmRead
BV60Alrm_NetUnit_19.ActiveAlarm ALN19: Network: unit 19 alarmRead
BV61Alrm_NetUnit_20.ActiveAlarm ALN20: Network: unit 20 alarmRead
BV62Alrm_WirelessPrb_1_LowBatt.ActiveAlarm ALP05: Wireless probe 1: low battery levelRead
BV63Alrm_WirelessPrb_2_LowBatt.ActiveAlarm ALP06: Wireless probe 2: low battery levelRead
BV64Alrm_WirelessPrb_3_LowBatt.ActiveAlarm ALP07: Wireless probe 3: low battery levelRead
BV65Alrm_WirelessPrb_4_LowBatt.ActiveAlarm ALP08: Wireless probe 4: low battery levelRead
BV66Alrm_WirelessPrb_Main.ActiveAlarm ALA05: Main probe from wireless probe not availableRead
BV67Alrm_WirelessPrb_Limit.ActiveAlarm ALA06: Limit probe from wireless probe not availableRead
BV68SchedDayCfg[0].EnTBScheduler: Enable time band 1Write
BV69SchedDayCfg[1].EnTBScheduler: Enable time band 2Write
BV70SchedDayCfg[2].EnTBScheduler: Enable time band 3Write
BV71SchedDayCfg[3].EnTBScheduler: Enable time band 4Write
BV72SchedDayCfg[4].EnTBScheduler: Enable time band 5Write
BV73SchedDayCfg[5].EnTBScheduler: Enable time band 6Write
BV75ManExtFanBlower command in manual modeWrite
BV79EnSchedEnable schedulerWrite
BV80EnHiConductAlrmEnable high conductivity alarmWrite
BV81ManDrainManual total drain command; returns to 0 when drain is doneWrite
BV82EnPreheatOffEnable preheating functionWrite
BV83EnPartFillsEnable micro-filling function to restore water levelWrite
BV84DilDrainCfg.DailySched[1].EnableDrain to dilute - Daily scheduler (Monday) - enableWrite
BV85DilDrainCfg.DailySched[2].EnableDrain to dilute - Daily scheduler (Tuesday) - enableWrite
BV86DilDrainCfg.DailySched[3].EnableDrain to dilute - Daily scheduler (Wednesday) - enableWrite
BV87DilDrainCfg.DailySched[4].EnableDrain to dilute - Daily scheduler (Thursday) - enableWrite
BV88DilDrainCfg.DailySched[5].EnableDrain to dilute - Daily scheduler (Friday) - enableWrite
BV89DilDrainCfg.DailySched[6].EnableDrain to dilute - Daily scheduler (Saturday) - enableWrite
BV90DilDrainCfg.DailySched[7].EnableDrain to dilute - Daily scheduler (Sunday) - enableWrite
BV91EnPeriodicDrainEnable periodic total drainWrite
BV92UnitPauseSet unit pausedWrite0=not paused, 1=paused
BV93Alrm_SVOffline.ActiveAlarm ALA07: Supervisor offlineRead
BV101Alrm_HiBoilerTemp.ActiveAlarm ALC05: High boiler temperature (>110°)Read
BV102Warn_AutotestCancel.ActiveWarning ALW07: Autotest cancelled, saved and displayedRead
BV103Warn_NoDrainYet.ActiveWarning ALW08: No drain to dilute (if micro-filling active)Read
BV108DisableVarUnitPauseDisable paused by monitoring serviceRead0=not disabled, 1=disabled
BV110EnPreheatNoReqEnable preheating without offsetWrite0=disabled, 1=enabled
Object ID lookup: CAREL heaterSteam 4 process / titanium point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the heaterSteam 4 (UR) process / titanium and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CAREL heaterSteam 4 (UR) process / titanium

How many BACnet points does the CAREL heaterSteam 4 (UR) process / titanium have?

This list has 248 BACnet objects: 51 analog values, 91 binary values, 106 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CAREL heaterSteam 4 (UR) process / titanium BACnet points are writable?

123 of the 248 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official CAREL heaterSteam 4 (UR) process / titanium BACnet documentation?

The source is heaterSteam - UR Electric resistance humidifier - User manual (+0300087EN rel. 1.7), revision 2025-04-18, published free by CAREL at https://www.carel.com/documents/10191/0/%2B0300087EN/14647f23-54fd-4503-99a0-b2399a24cc60?version=1.16.

What are the minimum BACnet points to integrate the CAREL heaterSteam 4 (UR) process / titanium?

Start with BV 6 OnBySV (Unit on/off from the BMS); AV 11 SV_PwrReq (Production request from the BMS, 0-100 %); AV 14 GlbSetP_Hum (Humidity set point, %RH (own probe control)); BV 5 OnOffStatus (Unit on/off status); PIV 12 UnitStatus (Operating state code); AV 0 MainPrb (Main probe reading); AV 12 CurrProdPh (Current steam production, kg/h or lb/h); BV 14 CurrBlkAlrm.IsPresent (Resettable alarm active); BV 13 CurrBlkAlrm.IsBlocker (Shutdown alarm active).

How do I enable BMS control of the CAREL heaterSteam 4 (UR) process / titanium?

On screens Eh07/Eh08 select the supervisor port and enable 'On/Off signal from supervisor' and 'control from supervisor' (the BMS-port Eh01 settings 'On/Off from SV' and 'Control from SV' default to No). Without them the unit ignores the supervisor on/off and production request.

Does the CAREL heaterSteam 4 (UR) process / titanium need a BACnet heartbeat or have a communication timeout?

Eh08 can enable a supervisor-offline alarm (Alrm_SVOffline.Active, BV 93). The manual does not describe what the unit does with its output when the supervisor goes offline.

Can the BMS supply sensor values to the CAREL heaterSteam 4 (UR) process / titanium?

With control from supervisor the BMS sends the production request on SV_PwrReq (AV 11) instead of the unit using its own probe. Up to four CAREL wireless probes can also feed the unit.

How do I check these points on the real heaterSteam 4 (UR) process / titanium?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.