 "manufacturer": "CAREL",
 "manufacturer_slug": "carel",
 "model": "heaterSteam 4 (UR) process / titanium",
 "model_slug": "heatersteam-4-ur",
 "aliases": [
  "heaterSteam",
  "heaterSteam 4",
  "heaterSteam process",
  "heaterSteam titanium",
  "UR",
  "URH",
  "CAREL electric resistance humidifier",
  "+0300087EN"
 ],
 "equipment_type": "Electric resistance steam humidifier",
 "applies_to": "CAREL heaterSteam UR electric heater steam humidifiers (process and titanium versions) with the c.pHC-based controller, manual +0300087EN.",
 "summary": "heaterSteam 4 is CAREL's resistance-heated isothermal steam humidifier; this entry covers the heaterSteam 4 generation documented in manual +0300087EN rel. 1.7 (2025). BACnet MS/TP (on the RS485 BMS port) and BACnet IP (on the Ethernet port) are built into the c.pHC controller, one at a time. The object list has positive-integer values for status, hours, probe and scheduler settings, analog values for probes, set points and production, and binary values for on/off commands, level sensors and every alarm.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": 77000,
 "access_inferred": false,
 "notes": [
  "Source: section 11.2.3 'Table of BACnet variables', manual pages 55-59 (106 positive integer values, 51 analog values, 91 binary values).",
  "The earlier heaterSteam UR manual (+0300080EN rel. 1.4, 2018) lists 188 objects; most share instance and name with this list, but SV_Command/SV_CommandResult sit at PIV 92/93 there (PIV 72/73 here), a few names differ and 60 objects here are new. See the separate heaterSteam UR (2018) entry.",
  "Temperature, production and probe units follow the unit-of-measure setting (UoM, PIV 45: 1 = °C and kg/h, 2 = °F and lb/h).",
  "Objects ending in NetStatus / Alrm_NetUnit only report in Main/Secondary networks; wireless probe objects only with CAREL wireless probes.",
  "UnitStatus and NetStatus codes are the footnote list printed under the table."
 ],
 "source": {
  "title": "heaterSteam - UR Electric resistance humidifier - User manual",
  "doc_number": "+0300087EN rel. 1.7",
  "revision_date": "2025-04-18",
  "url": "https://www.carel.com/documents/10191/0/%2B0300087EN/14647f23-54fd-4503-99a0-b2399a24cc60?version=1.16"
 },
 "integration": {
  "summary": "Pick the port and protocol (Eh01 for the BMS port, Eh06 for Ethernet), set the device instance and UDP port on Eh04, then enable on/off and control from supervisor on Eh07/Eh08. The BMS starts and stops the unit with OnBySV (BV 6) and either sends a production request on SV_PwrReq (AV 11) or writes the humidity set point (AV 14). Monitor OnOffStatus, UnitStatus, current production and the summary alarm BVs.",
  "minimum_points": [
   {
    "ref": "BV 6",
    "name": "OnBySV",
    "why": "Unit on/off from the BMS"
   },
   {
    "ref": "AV 11",
    "name": "SV_PwrReq",
    "why": "Production request from the BMS, 0-100 %"
   },
   {
    "ref": "AV 14",
    "name": "GlbSetP_Hum",
    "why": "Humidity set point, %RH (own probe control)"
   },
   {
    "ref": "BV 5",
    "name": "OnOffStatus",
    "why": "Unit on/off status"
   },
   {
    "ref": "PIV 12",
    "name": "UnitStatus",
    "why": "Operating state code"
   },
   {
    "ref": "AV 0",
    "name": "MainPrb",
    "why": "Main probe reading"
   },
   {
    "ref": "AV 12",
    "name": "CurrProdPh",
    "why": "Current steam production, kg/h or lb/h"
   },
   {
    "ref": "BV 14",
    "name": "CurrBlkAlrm.IsPresent",
    "why": "Resettable alarm active"
   },
   {
    "ref": "BV 13",
    "name": "CurrBlkAlrm.IsBlocker",
    "why": "Shutdown alarm active"
   }
  ],
  "enable": "On screens Eh07/Eh08 select the supervisor port and enable 'On/Off signal from supervisor' and 'control from supervisor' (the BMS-port Eh01 settings 'On/Off from SV' and 'Control from SV' default to No). Without them the unit ignores the supervisor on/off and production request.",
  "heartbeat": "Eh08 can enable a supervisor-offline alarm (Alrm_SVOffline.Active, BV 93). The manual does not describe what the unit does with its output when the supervisor goes offline.",
  "remote_sensors": "With control from supervisor the BMS sends the production request on SV_PwrReq (AV 11) instead of the unit using its own probe. Up to four CAREL wireless probes can also feed the unit.",
  "setup": [
   "Device instance default 77000, UDP port default 47808 (screen Eh04).",
   "BACnet MS/TP on the BMS port: Eh03 sets the MAC address (default 0), max masters (127) and max info frames (10).",
   "Ethernet IP settings (DHCP, IP, mask, gateway, DNS) are on the Ethernet settings screen; select BACnet for the Ethernet port on Eh06.",
   "Only one BACnet instance exists, so BACnet cannot run on the BMS port and Ethernet at the same time."
  ],
  "gotchas": [
   "Scheduler, probe range and drain-to-dilute settings are configuration; avoid cyclic writes.",
   "SV_Command (PIV 72) is a one-shot reset (1 = alarms, 2 = hour counter), not a value to hold."
  ]
 },
 "points": [
  {
   "type": "PIV",
   "instance": 0,
   "name": "SV_SWVer",
   "description": "Software version",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 1,
   "name": "SV_OSVer",
   "description": "OS version",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 2,
   "name": "UnitModel",
   "description": "Model version",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 3,
   "name": "Conductivity",
   "description": "Inlet water conductivity reading",
   "units": "µS/cm",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 4,
   "name": "WirelessPrbInfo_1.BattLev",
   "description": "Wireless probe 1 reading: battery level",
   "units": "",
   "access": "R",
   "states": "0=Empty, 1=25%, 2=50%, 3=75%, 4=100%"
  },
  {
   "type": "PIV",
   "instance": 5,
   "name": "WirelessPrbInfo_1.RadioSignalLev",
   "description": "Wireless probe 1 reading: radio signal level",
   "units": "",
   "access": "R",
   "states": "0=Absent, 1-7=Very poor, 8-14=Poor, 15-30=Good, 31-100=Excellent"
  },
  {
   "type": "PIV",
   "instance": 6,
   "name": "WirelessPrbInfo_2.BattLev",
   "description": "Wireless probe 2 reading: battery level",
   "units": "",
   "access": "R",
   "states": "0=Empty, 1=25%, 2=50%, 3=75%, 4=100%"
  },
  {
   "type": "PIV",
   "instance": 7,
   "name": "WirelessPrbInfo_2.RadioSignalLev",
   "description": "Wireless probe 2 reading: radio signal level",
   "units": "",
   "access": "R",
   "states": "0=Absent, 1-7=Very poor, 8-14=Poor, 15-30=Good, 31-100=Excellent"
  },
  {
   "type": "PIV",
   "instance": 8,
   "name": "WirelessPrbInfo_3.BattLev",
   "description": "Wireless probe 3 reading: battery level",
   "units": "",
   "access": "R",
   "states": "0=Empty, 1=25%, 2=50%, 3=75%, 4=100%"
  },
  {
   "type": "PIV",
   "instance": 9,
   "name": "WirelessPrbInfo_3.RadioSignalLev",
   "description": "Wireless probe 3 reading: radio signal level",
   "units": "",
   "access": "R",
   "states": "0=Absent, 1-7=Very poor, 8-14=Poor, 15-30=Good, 31-100=Excellent"
  },
  {
   "type": "PIV",
   "instance": 10,
   "name": "WirelessPrbInfo_4.BattLev",
   "description": "Wireless probe 4 reading: battery level",
   "units": "",
   "access": "R",
   "states": "0=Empty, 1=25%, 2=50%, 3=75%, 4=100%"
  },
  {
   "type": "PIV",
   "instance": 11,
   "name": "WirelessPrbInfo_4.RadioSignalLev",
   "description": "Wireless probe 4 reading: radio signal level",
   "units": "",
   "access": "R",
   "states": "0=Absent, 1-7=Very poor, 8-14=Poor, 15-30=Good, 31-100=Excellent"
  },
  {
   "type": "PIV",
   "instance": 12,
   "name": "UnitStatus",
   "description": "Unit status",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 13,
   "name": "WorkHr",
   "description": "Unit lifetime hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 14,
   "name": "CylWorkHr",
   "description": "Cylinder lifetime hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 15,
   "name": "ManMode_msk",
   "description": "Start manual mode",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Manual outputs, 2=Manual production"
  },
  {
   "type": "PIV",
   "instance": 16,
   "name": "ManSSR_OpT",
   "description": "Set ON time for SSR heater power control cycle in manual mode",
   "units": "ms",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 17,
   "name": "ManSSR_ClT",
   "description": "Set OFF time for SSR heater power control cycle in manual mode",
   "units": "ms",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 18,
   "name": "RegulationCfg.RegTyp",
   "description": "Control mode",
   "units": "",
   "access": "W",
   "states": "0=External proportional signal, 1=External proportional signal + limit, 2=ON/OFF signal, 3=Humidity (one probe), 4=Temperature (one probe), 5=Humidity + limit, 6=Temperature + limit, 7=Humidity (two probes), 8=Temperature (two probes)"
  },
  {
   "type": "PIV",
   "instance": 19,
   "name": "ThrshAlrmDT",
   "description": "Set high humidity/temperature alarm threshold",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 20,
   "name": "MainPrbCfg.UITyp",
   "description": "Set main probe type",
   "units": "",
   "access": "W",
   "states": "0=0-1V, 1=0-10V, 2=2-10V, 5=NTC, 3=0-20mA, 4=4-20mA"
  },
  {
   "type": "PIV",
   "instance": 21,
   "name": "LimitPrbCfg.UITyp",
   "description": "Set limit probe type",
   "units": "",
   "access": "W",
   "states": "0=0-1V, 1=0-10V, 2=2-10V, 3=0-20mA, 4=4-20mA, 5=NTC"
  },
  {
   "type": "PIV",
   "instance": 22,
   "name": "WHardnessMan",
   "description": "Set water hardness value, if manual mode",
   "units": "",
   "access": "W",
   "states": "0=0-10°F, 1=10-20°F, 2=20-30°F, 3=30-40°F, 4=Demineralised"
  },
  {
   "type": "PIV",
   "instance": 23,
   "name": "EvapCycleNoThrsh",
   "description": "Evaporation cycles before drain to dilute (micro-filling off)",
   "units": "",
   "access": "W",
   "states": "0=AUTO"
  },
  {
   "type": "PIV",
   "instance": 24,
   "name": "FillTScale",
   "description": "Extra filling time after green LED level (micro-filling off)",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 25,
   "name": "DilDrainTScale",
   "description": "Set drain time modification",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 26,
   "name": "Scheduler.SchedDayToSet",
   "description": "Scheduler: day of week to configure",
   "units": "",
   "access": "W",
   "states": "1=Monday, 2=Tuesday, 3=Wednesday, 4=Thursday, 5=Friday, 6=Saturday, 7=Sunday"
  },
  {
   "type": "PIV",
   "instance": 27,
   "name": "SchedDayCfg[0].StartHr",
   "description": "Scheduler: band 1 start hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 28,
   "name": "SchedDayCfg[0].StartMin",
   "description": "Scheduler: band 1 start minutes",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 29,
   "name": "SchedDayCfg[0].WorkMode",
   "description": "Scheduler: band 1 operating mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 30,
   "name": "SchedDayCfg[1].StartHr",
   "description": "Scheduler: band 2 start hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 31,
   "name": "SchedDayCfg[1].StartMin",
   "description": "Scheduler: band 2 start minutes",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 32,
   "name": "SchedDayCfg[1].WorkMode",
   "description": "Scheduler: band 2 operating mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 33,
   "name": "SchedDayCfg[2].StartHr",
   "description": "Scheduler: band 3 start hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 34,
   "name": "SchedDayCfg[2].StartMin",
   "description": "Scheduler: band 3 start minutes",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 35,
   "name": "SchedDayCfg[2].WorkMode",
   "description": "Scheduler: band 3 operating mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 36,
   "name": "SchedDayCfg[3].StartHr",
   "description": "Scheduler: band 4 start hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 37,
   "name": "SchedDayCfg[3].StartMin",
   "description": "Scheduler: band 4 start minutes",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 38,
   "name": "SchedDayCfg[3].WorkMode",
   "description": "Scheduler: band 4 operating mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 39,
   "name": "SchedDayCfg[4].StartHr",
   "description": "Scheduler: band 5 start hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 40,
   "name": "SchedDayCfg[4].StartMin",
   "description": "Scheduler: band 5 start minutes",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 41,
   "name": "SchedDayCfg[4].WorkMode",
   "description": "Scheduler: band 5 operating mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 42,
   "name": "SchedDayCfg[5].StartHr",
   "description": "Scheduler: band 6 start hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 43,
   "name": "SchedDayCfg[5].StartMin",
   "description": "Scheduler: band 6 start minutes",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 44,
   "name": "SchedDayCfg[5].WorkMode",
   "description": "Scheduler: band 6 operating mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 45,
   "name": "UoM",
   "description": "Unit of measure",
   "units": "",
   "access": "W",
   "states": "0=Default, 1=Int. system °C, kg/h, 2=Imperial °F, lb/h"
  },
  {
   "type": "PIV",
   "instance": 46,
   "name": "Year",
   "description": "Year",
   "units": "years",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 47,
   "name": "Month",
   "description": "Month",
   "units": "months",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 48,
   "name": "Day",
   "description": "Day",
   "units": "days",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 49,
   "name": "Hour",
   "description": "Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 50,
   "name": "Minute",
   "description": "Minutes",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 51,
   "name": "SetTimezone",
   "description": "Time zone",
   "units": "",
   "access": "W",
   "states": "Time-zone code; see the manual list (0=not set)"
  },
  {
   "type": "PIV",
   "instance": 52,
   "name": "NetStatus[1]",
   "description": "Network unit status: unit 1",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 53,
   "name": "NetStatus[2]",
   "description": "Network unit status: unit 2",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 54,
   "name": "NetStatus[3]",
   "description": "Network unit status: unit 3",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 55,
   "name": "NetStatus[4]",
   "description": "Network unit status: unit 4",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 56,
   "name": "NetStatus[5]",
   "description": "Network unit status: unit 5",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 57,
   "name": "NetStatus[6]",
   "description": "Network unit status: unit 6",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 58,
   "name": "NetStatus[7]",
   "description": "Network unit status: unit 7",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 59,
   "name": "NetStatus[8]",
   "description": "Network unit status: unit 8",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 60,
   "name": "NetStatus[9]",
   "description": "Network unit status: unit 9",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 61,
   "name": "NetStatus[10]",
   "description": "Network unit status: unit 10",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 62,
   "name": "NetStatus[11]",
   "description": "Network unit status: unit 11",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 63,
   "name": "NetStatus[12]",
   "description": "Network unit status: unit 12",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 64,
   "name": "NetStatus[13]",
   "description": "Network unit status: unit 13",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 65,
   "name": "NetStatus[14]",
   "description": "Network unit status: unit 14",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 66,
   "name": "NetStatus[15]",
   "description": "Network unit status: unit 15",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 67,
   "name": "NetStatus[16]",
   "description": "Network unit status: unit 16",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 68,
   "name": "NetStatus[17]",
   "description": "Network unit status: unit 17",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 69,
   "name": "NetStatus[18]",
   "description": "Network unit status: unit 18",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 70,
   "name": "NetStatus[19]",
   "description": "Network unit status: unit 19",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 71,
   "name": "NetStatus[20]",
   "description": "Network unit status: unit 20",
   "units": "",
   "access": "R",
   "states": "0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from DIN, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheating, 11=startup preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=drain due to inactivity, 16=foam drain, 17=heater safety off, 18=wait fill, 19=periodic drain, 24=paused by monitoring"
  },
  {
   "type": "PIV",
   "instance": 72,
   "name": "SV_Command",
   "description": "Supervisor command: reset alarms or hour counter",
   "units": "",
   "access": "W",
   "states": "1=reset alarm, 2=reset hour counter"
  },
  {
   "type": "PIV",
   "instance": 73,
   "name": "SV_CommandResult",
   "description": "Result of the command",
   "units": "",
   "access": "R",
   "states": "1=successful, 2=failed, 3=invalid command"
  },
  {
   "type": "PIV",
   "instance": 80,
   "name": "PreMaintWarnThrsh",
   "description": "Set next maintenance pre-alert time",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 81,
   "name": "HiConductAlrmDlyT",
   "description": "Set high conductivity alarm delay",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 82,
   "name": "HiConductWarnThrsh",
   "description": "Set high conductivity warning threshold",
   "units": "µS/cm",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 83,
   "name": "HiConductAlrmThrsh",
   "description": "Set high conductivity alarm threshold",
   "units": "µS/cm",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 84,
   "name": "HiConductWarnHyst",
   "description": "Set high conductivity warning threshold hysteresis",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 85,
   "name": "FoamLevSetPScale",
   "description": "Foam sensor sensitivity (0%-200% - def. 100%)",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 86,
   "name": "PartFillsT",
   "description": "Set micro-fill cycle duration",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 87,
   "name": "DilDrainCfg.Typ",
   "description": "Drain to dilute mode with micro-fill active",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Daily scheduler, 2=Periodic"
  },
  {
   "type": "PIV",
   "instance": 89,
   "name": "DilDrainCfg.PeriodicDilDrainThrsh",
   "description": "Hours between periodic drain to dilute cycles (micro-filling on)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 90,
   "name": "DilDrainCfg.DailySched[1].Start_h",
   "description": "Drain to dilute - Daily scheduler (Monday) - hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 91,
   "name": "DilDrainCfg.DailySched[1].Start_min",
   "description": "Drain to dilute - Daily scheduler (Monday) - minutes",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 92,
   "name": "DilDrainCfg.DailySched[2].Start_h",
   "description": "Drain to dilute - Daily scheduler (Tuesday) - hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 93,
   "name": "DilDrainCfg.DailySched[2].Start_min",
   "description": "Drain to dilute - Daily scheduler (Tuesday) - minutes",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 94,
   "name": "DilDrainCfg.DailySched[3].Start_h",
   "description": "Drain to dilute - Daily scheduler (Wednesday) - hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 95,
   "name": "DilDrainCfg.DailySched[3].Start_min",
   "description": "Drain to dilute - Daily scheduler (Wednesday) - minutes",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 96,
   "name": "DilDrainCfg.DailySched[4].Start_h",
   "description": "Drain to dilute - Daily scheduler (Thursday) - hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 97,
   "name": "DilDrainCfg.DailySched[4].Start_min",
   "description": "Drain to dilute - Daily scheduler (Thursday) - minutes",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 98,
   "name": "DilDrainCfg.DailySched[5].Start_h",
   "description": "Drain to dilute - Daily scheduler (Friday) - hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 99,
   "name": "DilDrainCfg.DailySched[5].Start_min",
   "description": "Drain to dilute - Daily scheduler (Friday) - minutes",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 100,
   "name": "DilDrainCfg.DailySched[6].Start_h",
   "description": "Drain to dilute - Daily scheduler (Saturday) - hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 101,
   "name": "DilDrainCfg.DailySched[6].Start_min",
   "description": "Drain to dilute - Daily scheduler (Saturday) - minutes",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 102,
   "name": "DilDrainCfg.DailySched[7].Start_h",
   "description": "Drain to dilute - Daily scheduler (Sunday) - hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 103,
   "name": "DilDrainCfg.DailySched[7].Start_min",
   "description": "Drain to dilute - Daily scheduler (Sunday) - minutes",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 104,
   "name": "PeriodicDrainThrsh",
   "description": "Production hours between two periodic total drains",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 105,
   "name": "ExtFanDTOn",
   "description": "Set start blower delay from start of production",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 106,
   "name": "ExtFanDTOff",
   "description": "Set stop blower delay from end of production",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 129,
   "name": "WorkHrCntDwn",
   "description": "Time remaining until next maintenance",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 130,
   "name": "CylResDate.Year",
   "description": "Cylinder production hours reset date - Year",
   "units": "years",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 131,
   "name": "CylResDate.Month",
   "description": "Cylinder production hours reset date - Month",
   "units": "months",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 132,
   "name": "CylResDate.Day",
   "description": "Cylinder production hours reset date - Day",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 133,
   "name": "CylResDate.Hour",
   "description": "Cylinder production hours reset date - Hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 134,
   "name": "CylResDate.Minute",
   "description": "Cylinder production hours reset date - Minutes",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "MainPrb",
   "description": "Main probe reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "LimitPrb",
   "description": "Limit probe reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "PreheatPrb",
   "description": "Water preheating probe reading",
   "units": "°C or °F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "WirelessPrbVal_1.Hum",
   "description": "Wireless probe 1 reading: Humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "WirelessPrbVal_1.Temp",
   "description": "Wireless probe 1 reading: Temperature",
   "units": "°C or °F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "WirelessPrbVal_2.Hum",
   "description": "Wireless probe 2 reading: Humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "WirelessPrbVal_2.Temp",
   "description": "Wireless probe 2 reading: Temperature",
   "units": "°C or °F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "WirelessPrbVal_3.Hum",
   "description": "Wireless probe 3 reading: Humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "WirelessPrbVal_3.Temp",
   "description": "Wireless probe 3 reading: Temperature",
   "units": "°C or °F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "WirelessPrbVal_4.Hum",
   "description": "Wireless probe 4 reading: Humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "WirelessPrbVal_4.Temp",
   "description": "Wireless probe 4 reading: Temperature",
   "units": "°C or °F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "SV_PwrReq",
   "description": "Set production percentage request from supervisor",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "CurrProdPh",
   "description": "Current production kg/h (lbs/h)",
   "units": "kg/h or lb/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "ManReq",
   "description": "Enable manual production request",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "GlbSetP_Hum",
   "description": "Set humidity value (humidity set point)",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "GlbSetP_Temp",
   "description": "Set temperature value (temperature set point)",
   "units": "°C or °F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "RegulationCfg.Hyst",
   "description": "Set control hysteresis",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "RegulationCfg.Diff",
   "description": "Set control differential",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "GlbSetPLim_Hum",
   "description": "Set humidity limit value (humidity limit set point)",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "GlbSetPLim_Temp",
   "description": "Set temperature limit value (temperature limit set point)",
   "units": "°C or °F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "RegulationCfg.DiffLim",
   "description": "Set limit differential",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "RegulationCfg.MinReq",
   "description": "Set maximum production value",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "AlrmThrshHumLo",
   "description": "Set main probe low humidity alarm threshold",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "AlrmThrshHumHi",
   "description": "Set main probe high humidity alarm threshold",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "AlrmThrshHumHiLim",
   "description": "Set limit probe low humidity alarm threshold",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "AlrmThrshTempLo",
   "description": "Set main probe low temperature alarm threshold",
   "units": "°C or °F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "AlrmThrshTempHi",
   "description": "Set main probe high temperature alarm threshold",
   "units": "°C or °F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "AlrmThrshTempHiLim",
   "description": "Set limit probe low temperature alarm threshold",
   "units": "°C or °F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "MainPrbCfg.Mi_Hum",
   "description": "Set main probe minimum humidity value",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "MainPrbCfg.Ma_Hum",
   "description": "Set main probe maximum humidity",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "MainPrbCfg.Mi_Temp",
   "description": "Set main probe minimum temperature",
   "units": "°C or °F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "MainPrbCfg.Ma_Temp",
   "description": "Set main probe maximum temperature",
   "units": "°C or °F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "LimitPrbCfg.Mi_Hum",
   "description": "Set limit probe minimum humidity value",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "LimitPrbCfg.Ma_Hum",
   "description": "Set limit probe maximum humidity value",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "LimitPrbCfg.Mi_Temp",
   "description": "Set limit probe minimum temperature value",
   "units": "°C or °F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "LimitPrbCfg.Ma_Temp",
   "description": "Set limit probe maximum temperature value",
   "units": "°C or °F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "RegulationCfg.PwrCorrectionFactor",
   "description": "Set power correction for thermal dissipation",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "SchedDayCfg[0].SetP",
   "description": "Scheduler: band 1 set point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "SchedDayCfg[1].SetP",
   "description": "Scheduler: band 2 set point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "SchedDayCfg[2].SetP",
   "description": "Scheduler: band 3 set point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "SchedDayCfg[3].SetP",
   "description": "Scheduler: band 4 set point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "SchedDayCfg[4].SetP",
   "description": "Scheduler: band 5 set point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "SchedDayCfg[5].SetP",
   "description": "Scheduler: band 6 set point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "NetReq",
   "description": "Current system request",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "NetProd",
   "description": "Current system production",
   "units": "kg/h or lb/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "MaxUnitProd",
   "description": "Set maximum production value",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "RegulationCfg.W_MinTempThrsh",
   "description": "Set water preheating temperature",
   "units": "°C or °F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "PreheatOffset_Temp",
   "description": "Preheating offset from temperature set point",
   "units": "°C or °F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "PreheatOffset_Hum",
   "description": "Preheating offset from humidity set point",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "ProdReqMsk",
   "description": "Production request",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "FoamLevReal",
   "description": "Signal reading from foam sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 0,
   "name": "RemOn",
   "description": "Remote on/off command",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "ThermPtcDin",
   "description": "Thermal protection status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "LevSenStatus.Low",
   "description": "Level sensor reading: low level",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "LevSenStatus.Hi",
   "description": "Level sensor reading: high level",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "LevSenStatus.Foam",
   "description": "High level sensor reading: foam",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "OnOffStatus",
   "description": "Unit status on/off",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "OnBySV",
   "description": "On/off control from supervisor (SV)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "WHardnessTyp",
   "description": "Set water hardness management mode",
   "units": "",
   "access": "W",
   "states": "0=AUTO, 1=MANUAL"
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "PreMaintWarn",
   "description": "Set next maintenance pre-alert time",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "CurrBlkAlrm.IsBlocker",
   "description": "Shutdown alarm active",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "CurrBlkAlrm.IsPresent",
   "description": "Resettable alarm active",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "CurrBlkAlrm.Warning",
   "description": "Warning",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "Alrm_Autotest.Active",
   "description": "Alarm ALC01: Autotest",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "Alrm_HighConductAl.Active",
   "description": "Alarm ALC02: High conductivity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "Alrm_LevSen.Active",
   "description": "Alarm ALC03: Level sensor broken",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "Alrm_ThermPtc.Active",
   "description": "Alarm ALC04: Motor protection",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "Alrm_WMiss.Active",
   "description": "Alarm ALB01: No water",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "Alrm_LowProd.Active",
   "description": "Alarm ALB02: Low production",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "Alrm_MainPrb.Active",
   "description": "Alarm ALA01: Main probe broken",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "Alrm_LimPrb.Active",
   "description": "Alarm ALA02: Limit probe broken",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "Alrm_PreHPrb.Active",
   "description": "Alarm ALA03: Preheating probe broken",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "Alrm_HiHum.Active",
   "description": "Alarm ALH01: High humidity/temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "Alrm_LoHum.Active",
   "description": "Alarm ALH02: Low humidity/temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "Alrm_HiHum_Lim.Active",
   "description": "Alarm ALH03: High humidity/temperature: limit probe",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 28,
   "name": "Alrm_Foam.Active",
   "description": "Alarm ALW01: Foam warning",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "Alrm_PeriodicMaint.Active",
   "description": "Alarm ALT01: Maintenance request",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "Alrm_CylFull.Active",
   "description": "Alarm ALW02: Cylinder full",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "Alrm_ConductPrb.Active",
   "description": "Alarm ALA04: Conductivity meter broken/not connected",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "Alrm_HighConductWr.Active",
   "description": "Warning ALW03: High conductivity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "Alrm_RetMem.Active",
   "description": "Alarm ALR01: Retain memory",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 34,
   "name": "Warn_Autotest.Active",
   "description": "Warning ALW04: Autotest, saved only, not displayed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 35,
   "name": "Warn_LevSen.Active",
   "description": "Warning ALW05: Level sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 36,
   "name": "Warn_LowProd.Active",
   "description": "Warning ALW06: Low production, saved only, not displayed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 37,
   "name": "Alrm_WirelessPrb_1_Offline.Active",
   "description": "Alarm ALP01: Wireless probe 1: offline",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "Alrm_WirelessPrb_2_Offline.Active",
   "description": "Alarm ALP02: Wireless probe 2: offline",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 39,
   "name": "Alrm_WirelessPrb_3_Offline.Active",
   "description": "Alarm ALP03: Wireless probe 3: offline",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "Alrm_WirelessPrb_4_Offline.Active",
   "description": "Alarm ALP04: Wireless probe 4: offline",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 41,
   "name": "Alrm_MissingModel.Active",
   "description": "Alarm ALM01: Humidifi er model not set",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 42,
   "name": "Alrm_NetUnit_1.Active",
   "description": "Alarm ALN01: Network: unit 1 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 43,
   "name": "Alrm_NetUnit_2.Active",
   "description": "Alarm ALN2: Network: unit 2 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 44,
   "name": "Alrm_NetUnit_3.Active",
   "description": "Alarm ALN3: Network: unit 3 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 45,
   "name": "Alrm_NetUnit_4.Active",
   "description": "Alarm ALN4: Network: unit 4 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 46,
   "name": "Alrm_NetUnit_5.Active",
   "description": "Alarm ALN5: Network: unit 5 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 47,
   "name": "Alrm_NetUnit_6.Active",
   "description": "Alarm ALN6: Network: unit 6 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 48,
   "name": "Alrm_NetUnit_7.Active",
   "description": "Alarm ALN7: Network: unit 7 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 49,
   "name": "Alrm_NetUnit_8.Active",
   "description": "Alarm ALN8: Network: unit 8 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 50,
   "name": "Alrm_NetUnit_9.Active",
   "description": "Alarm ALN9: Network: unit 9 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 51,
   "name": "Alrm_NetUnit_10.Active",
   "description": "Alarm ALN10: Network: unit 10 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 52,
   "name": "Alrm_NetUnit_11.Active",
   "description": "Alarm ALN11: Network: unit 11 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 53,
   "name": "Alrm_NetUnit_12.Active",
   "description": "Alarm ALN12: Network: unit 12 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 54,
   "name": "Alrm_NetUnit_13.Active",
   "description": "Alarm ALN13: Network: unit 13 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 55,
   "name": "Alrm_NetUnit_14.Active",
   "description": "Alarm ALN14: Network: unit 14 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 56,
   "name": "Alrm_NetUnit_15.Active",
   "description": "Alarm ALN15: Network: unit 15 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 57,
   "name": "Alrm_NetUnit_16.Active",
   "description": "Alarm ALN16: Network: unit 16 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 58,
   "name": "Alrm_NetUnit_17.Active",
   "description": "Alarm ALN17: Network: unit 17 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 59,
   "name": "Alrm_NetUnit_18.Active",
   "description": "Alarm ALN18: Network: unit 18 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 60,
   "name": "Alrm_NetUnit_19.Active",
   "description": "Alarm ALN19: Network: unit 19 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 61,
   "name": "Alrm_NetUnit_20.Active",
   "description": "Alarm ALN20: Network: unit 20 alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 62,
   "name": "Alrm_WirelessPrb_1_LowBatt.Active",
   "description": "Alarm ALP05: Wireless probe 1: low battery level",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 63,
   "name": "Alrm_WirelessPrb_2_LowBatt.Active",
   "description": "Alarm ALP06: Wireless probe 2: low battery level",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 64,
   "name": "Alrm_WirelessPrb_3_LowBatt.Active",
   "description": "Alarm ALP07: Wireless probe 3: low battery level",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 65,
   "name": "Alrm_WirelessPrb_4_LowBatt.Active",
   "description": "Alarm ALP08: Wireless probe 4: low battery level",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 66,
   "name": "Alrm_WirelessPrb_Main.Active",
   "description": "Alarm ALA05: Main probe from wireless probe not available",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 67,
   "name": "Alrm_WirelessPrb_Limit.Active",
   "description": "Alarm ALA06: Limit probe from wireless probe not available",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 68,
   "name": "SchedDayCfg[0].EnTB",
   "description": "Scheduler: Enable time band 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 69,
   "name": "SchedDayCfg[1].EnTB",
   "description": "Scheduler: Enable time band 2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 70,
   "name": "SchedDayCfg[2].EnTB",
   "description": "Scheduler: Enable time band 3",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 71,
   "name": "SchedDayCfg[3].EnTB",
   "description": "Scheduler: Enable time band 4",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 72,
   "name": "SchedDayCfg[4].EnTB",
   "description": "Scheduler: Enable time band 5",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 73,
   "name": "SchedDayCfg[5].EnTB",
   "description": "Scheduler: Enable time band 6",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 75,
   "name": "ManExtFan",
   "description": "Blower command in manual mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 79,
   "name": "EnSched",
   "description": "Enable scheduler",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 80,
   "name": "EnHiConductAlrm",
   "description": "Enable high conductivity alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 81,
   "name": "ManDrain",
   "description": "Manual total drain command; returns to 0 when drain is done",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 82,
   "name": "EnPreheatOff",
   "description": "Enable preheating function",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 83,
   "name": "EnPartFills",
   "description": "Enable micro-filling function to restore water level",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 84,
   "name": "DilDrainCfg.DailySched[1].Enable",
   "description": "Drain to dilute - Daily scheduler (Monday) - enable",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 85,
   "name": "DilDrainCfg.DailySched[2].Enable",
   "description": "Drain to dilute - Daily scheduler (Tuesday) - enable",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 86,
   "name": "DilDrainCfg.DailySched[3].Enable",
   "description": "Drain to dilute - Daily scheduler (Wednesday) - enable",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 87,
   "name": "DilDrainCfg.DailySched[4].Enable",
   "description": "Drain to dilute - Daily scheduler (Thursday) - enable",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 88,
   "name": "DilDrainCfg.DailySched[5].Enable",
   "description": "Drain to dilute - Daily scheduler (Friday) - enable",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 89,
   "name": "DilDrainCfg.DailySched[6].Enable",
   "description": "Drain to dilute - Daily scheduler (Saturday) - enable",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 90,
   "name": "DilDrainCfg.DailySched[7].Enable",
   "description": "Drain to dilute - Daily scheduler (Sunday) - enable",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 91,
   "name": "EnPeriodicDrain",
   "description": "Enable periodic total drain",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 92,
   "name": "UnitPause",
   "description": "Set unit paused",
   "units": "",
   "access": "W",
   "states": "0=not paused, 1=paused"
  },
  {
   "type": "BV",
   "instance": 93,
   "name": "Alrm_SVOffline.Active",
   "description": "Alarm ALA07: Supervisor offline",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 101,
   "name": "Alrm_HiBoilerTemp.Active",
   "description": "Alarm ALC05: High boiler temperature (>110°)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 102,
   "name": "Warn_AutotestCancel.Active",
   "description": "Warning ALW07: Autotest cancelled, saved and displayed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 103,
   "name": "Warn_NoDrainYet.Active",
   "description": "Warning ALW08: No drain to dilute (if micro-filling active)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 108,
   "name": "DisableVarUnitPause",
   "description": "Disable paused by monitoring service",
   "units": "",
   "access": "R",
   "states": "0=not disabled, 1=disabled"
  },
  {
   "type": "BV",
   "instance": 110,
   "name": "EnPreheatNoReq",
   "description": "Enable preheating without offset",
   "units": "",
   "access": "W",
   "states": "0=disabled, 1=enabled"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/carel/heatersteam-4-ur",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}