Electric resistance steam humidifier · BACnet points list

CAREL heaterSteam UR (2018 manual, before heaterSteam 4) BACnet points list

Updated 4 November 2026

Short answer

heaterSteam UR is CAREL's resistance-heated steam humidifier. This entry covers the earlier heaterSteam UR generation documented in the 2018 manual (rel. 1.4), before heaterSteam 4. Its c.pHC controller speaks BACnet MS/TP on the RS485 BMS port or BACnet IP on the Ethernet port (one at a time) with no extra card. This edition of the object list has 74 positive integer values, 45 analog values and 69 binary values covering status, probes, set points, scheduler settings, network units and alarms.

This page lists 188 BACnet objects for the CAREL heaterSteam UR (2018 manual, before heaterSteam 4) — 76 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CAREL’s own free documentation, linked below.

Manufacturer
CAREL
Model
heaterSteam UR (2018 manual, before heaterSteam 4)
Equipment
Electric resistance steam humidifier
Equipment type
Humidifiers
BACnet objects
188 (76 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
77000
Also known as
heaterSteam, heaterSteam UR, UR002, UR080, CAREL resistance steam humidifier, +0300080EN
Source document
heaterSteam - UR Electric resistance humidifier - User manual · +0300080EN rel. 1.4 · rev. 2018-02-05
Download CSV 188 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CAREL’s current documentation and the live device before use. Not official CAREL information. Terms of use.

BMS integration notes: CAREL heaterSteam UR (2018 manual, before heaterSteam 4)

Integration in brief

Select BACnet on the BMS port (Eh01, plus MS/TP settings on Eh03) or on the Ethernet port (Eh06), set the device instance on Eh04, and enable 'On/Off from SV' and 'Control from SV'. The BMS then starts the unit with OnBySV (BV 6) and sends a production request on SV_PwrReq (AV 11), or writes the humidity set point (AV 14). Monitor OnOffStatus, UnitStatus, production and the summary alarm BVs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 6OnBySVUnit on/off from the BMSWrite
AV 11SV_PwrReqProduction request from the BMS, %Write
AV 14GlbSetP_HumHumidity set point (own probe control)Write
BV 5OnOffStatusUnit on/off statusRead
PIV 12UnitStatusOperating state codeRead
AV 0MainPrbMain probe readingRead
AV 12CurrProdPhCurrent steam production, kg/h or lb/hRead
BV 14CurrBlkAlrm.IsPresentResettable alarm activeRead
BV 13CurrBlkAlrm.IsBlockerShutdown alarm activeRead

Enable & remote start

On screen Eh01 set 'On/Off from SV' and 'Control from SV' to Yes (both default to No); otherwise the unit ignores the supervisor on/off and production request.

Sensors & values from the BMS

With control from supervisor the BMS sends the production request on SV_PwrReq (AV 11) instead of the unit using its own probe.

Network setup

Watch out for

CAREL heaterSteam UR (2018 manual, before heaterSteam 4) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

188 of 188 shown
Type
AnalogBinaryOther
Access
Show
CAREL heaterSteam UR (2018 manual, before heaterSteam 4) BACnet Points List
DescriptionStates
PIV0SV_SWVerSoftware versionRead
PIV1SV_OSVerOS versionRead
PIV2UnitModelModel versionRead
PIV3ConductivityConductivityRead
PIV4WirelessPrbInfo_1.BattLevWireless probe 1: battery levelRead
PIV5WirelessPrbInfo_1.RadioSignalLevWireless probe 1: wireless signal levelRead
PIV6WirelessPrbInfo_2.BattLevWireless probe 2: battery levelRead
PIV7WirelessPrbInfo_2.RadioSignalLevWireless probe 2: wireless signal levelRead
PIV8WirelessPrbInfo_3.BattLevWireless probe 3: battery levelRead
PIV9WirelessPrbInfo_3.RadioSignalLevWireless probe 3: wireless signal levelRead
PIV10WirelessPrbInfo_4.BattLevWireless probe 4: battery levelRead
PIV11WirelessPrbInfo_4.RadioSignalLevWireless probe 4: wireless signal levelRead
PIVmin12UnitStatusUnit statusRead
PIV13WorkHrUnit operating hoursRead
PIV14CylWorkHrCylinder operating hoursRead
PIV15ManModeManual modeWrite1=outputs, 2=request
PIV16ManSSR_OpTSSR opening time (manual mode)Write
PIV17ManSSR_ClTSSR closing time (manual mode)Write
PIV18RegulationCfg.RegTypControl typeWrite
PIV19ThrshAlrmDTHigh humidity/temperature alarm delayWrite
PIV20MainPrbCfg.TypMain probe typeWrite
PIV21LimitPrbCfg.TypLimit probe typeWrite
PIV22WHardnessManManual water hardness value (when WHardnessTyp is TRUE)Write
PIV23EvapCycleNoThrshshNumber of evaporation cyclesWrite0=auto
PIV24FillTScaleVariation in fill timeWrite
PIV25DilDrainTScaleVariation in drain timeWrite
PIV26Scheduler.SchedDayToSetScheduler: day of week to configure when above 0Write1=Monday ... 7=Sunday
PIV27SchedDayCfg[0].StartHrBand 1 start hoursWrite
PIV28SchedDayCfg[0].StartMinBand 1 start minutesWrite
PIV29SchedDayCfg[0].WorkModeBand 1 operating modeWrite
PIV30SchedDayCfg[1].StartHrBand 2 start hoursWrite
PIV31SchedDayCfg[1].StartMinBand 2 start minutesWrite
PIV32SchedDayCfg[1].WorkModeBand 2 operating modeWrite
PIV33SchedDayCfg[2].StartHrBand 3 start hoursWrite
PIV34SchedDayCfg[2].StartMinBand 3 start minutesWrite
PIV35SchedDayCfg[2].WorkModeBand 3 operating modeWrite
PIV36SchedDayCfg[3].StartHrBand 4 start hoursWrite
PIV37SchedDayCfg[3].StartMinBand 4 start minutesWrite
PIV38SchedDayCfg[3].WorkModeBand 4 operating modeWrite
PIV39SchedDayCfg[4].StartHrBand 5 start hoursWrite
PIV40SchedDayCfg[4].StartMinBand 5 start minutesWrite
PIV41SchedDayCfg[4].WorkModeBand 5 operating modeWrite
PIV42SchedDayCfg[5].StartHrBand 6 start hoursWrite
PIV43SchedDayCfg[5].StartMinBand 6 start minutesWrite
PIV44SchedDayCfg[5].WorkModeBand 6 operating modeWrite
PIV45UoMUnit of measureWrite
PIV46YearYearWrite
PIV47MonthMonthWrite
PIV48DayDayWrite
PIV49HourHourWrite
PIV50MinuteMinutesWrite
PIV51SetTimezoneTime zoneWrite
PIV52NetStatus[1]Unit 1 statusRead
PIV53NetStatus[2]Unit 2 statusRead
PIV54NetStatus[3]Unit 3 statusRead
PIV55NetStatus[4]Unit 4 statusRead
PIV56NetStatus[5]Unit 5 statusRead
PIV57NetStatus[6]Unit 6 statusRead
PIV58NetStatus[7]Unit 7 statusRead
PIV59NetStatus[8]Unit 8 statusRead
PIV60NetStatus[9]Unit 9 statusRead
PIV61NetStatus[10]Unit 10 statusRead
PIV62NetStatus[11]Unit 11 statusRead
PIV63NetStatus[12]Unit 12 statusRead
PIV64NetStatus[13]Unit 13 statusRead
PIV65NetStatus[14]Unit 14 statusRead
PIV66NetStatus[15]Unit 15 statusRead
PIV67NetStatus[16]Unit 16 statusRead
PIV68NetStatus[17]Unit 17 statusRead
PIV69NetStatus[18]Unit 18 statusRead
PIV70NetStatus[19]Unit 19 statusRead
PIV71NetStatus[20]Unit 20 statusRead
PIV92SV_CommandSupervisor command: reset alarms or hour counterWrite1=reset alarms, 2=reset hour counter
PIV93SV_CommandResultResult of the supervisor commandRead1=successful, 2=failed, 3=invalid command
AVmin0MainPrbMain probe value (REAL)Read
AV1LimitPrbLimit probe/second probe value (REAL)Read
AV2PreheatPrbNTC preheating probe value (REAL)Read
AV3WirelessPrbVal_1.HumWireless probe 1: HumidityRead
AV4WirelessPrbVal_1.TempWireless probe 1: TemperatureRead
AV5WirelessPrbVal_2.HumWireless probe 2: HumidityRead
AV6WirelessPrbVal_2.TempWireless probe 2: TemperatureRead
AV7WirelessPrbVal_3.HumWireless probe 3: HumidityRead
AV8WirelessPrbVal_3.TempWireless probe 3: TemperatureRead
AV9WirelessPrbVal_4.HumWireless probe 4: HumidityRead
AV10WirelessPrbVal_4.TempWireless probe 4: TemperatureRead
AVmin11SV_PwrReqProduction request percentage from supervisorWrite
AVmin12CurrProdPhCurrent production in kg/h (lbs/h)Read
AV13ManReqManual requestWrite
AVmin14GlbSetP_HumHumidity control set pointWrite
AV15GlbSetP_TempTemperature control set pointWrite
AV16RegulationCfg.HystControl hysteresisWrite
AV17RegulationCfg.DiffControl differentialWrite
AV18GlbSetPLim_HumSet point limit for humidity controlWrite
AV19GlbSetPLim_TempSet point limit for temperature controlWrite
AV20RegulationCfg.DiffLimLimit differentialWrite
AV21RegulationCfg.MinReqMinimum productionWrite
AV22AlrmThrshHumLoLow humidity alarm thresholdWrite
AV23AlrmThrshHumHiHigh humidity alarm thresholdWrite
AV24AlrmThrshHumHiLimHigh humidity limit alarm thresholdWrite
AV25AlrmThrshTempLoLow temperature alarm thresholdWrite
AV26AlrmThrshTempHiHigh temperature alarm thresholdWrite
AV27AlrmThrshTempHiLimHigh temperature limit alarm thresholdWrite
AV28MainPrbCfg.Mi_HumMain probe minimum humidity valueWrite
AV29MainPrbCfg.Ma_HumMain probe maximum humidity valueWrite
AV30MainPrbCfg.Mi_TempMain probe minimum temperature valueWrite
AV31MainPrbCfg.Ma_TempMain probe maximum temperature valueWrite
AV32LimitPrbCfg.Mi_HumLimit probe minimum humidity valueWrite
AV33LimitPrbCfg.Ma_HumLimit probe maximum humidity valueWrite
AV34LimitPrbCfg.Mi_TempLimit probe minimum temperature valueWrite
AV35LimitPrbCfg.Ma_TempLimit probe maximum temperature valueWrite
AV36RegulationCfg.PwrCorrectionFactorPower correction for thermal dissipationWrite
AV37SchedDayCfg[0].SetPBand 1 set pointWrite
AV38SchedDayCfg[1].SetPBand 2 set pointWrite
AV39SchedDayCfg[2].SetPBand 3 set pointWrite
AV40SchedDayCfg[3].SetPBand 4 set pointWrite
AV41SchedDayCfg[4].SetPBand 5 set pointWrite
AV42SchedDayCfg[5].SetPBand 6 set pointWrite
AV43NetReqCurrent system requestRead
AV44NetProdCurrent system productionRead
BV0RemOnRemote on/offRead
BV1ThermPtcDinThermal DIN statusRead
BV2LevSenStatus.LowLevel sensor: low levelRead
BV3LevSenStatus.HiLevel sensor: high levelRead
BV4LevSenStatus.FoamHigh level sensor: foamRead
BVmin5OnOffStatusUnit status On or OFFRead
BVmin6OnBySVStart command from SV (Supervisor)Write
BV12PreMainWarnMaintenance pre-alert (not an alarm)Read
BVmin13CurrBlkAlrm.IsBlockerShutdown alarmRead
BVmin14CurrBlkAlrm.IsPresentResettable alarmRead
BV15CurrBlkAlrm.WarningWarningRead
BV16Alrm_Autotest.ActiveAutotest alarmRead
BV17Alrm_HighConductAl.ActiveHigh conductivity alarmRead
BV18Alrm_LevSen.ActiveLevel sensor broken alarmRead
BV19Alrm_ThermPtc.ActiveThermal overload alarmRead
BV20Alrm_Wmiss.ActiveNo water alarmRead
BV21Alrm_LowProd.ActiveLow production alarmRead
BV22Alrm_MainPrb.ActiveMain probe fault alarmRead
BV23Alrm_LimPrb.ActiveLimit probe fault alarmRead
BV24Alrm_PreHPrb.ActiveNTC preheating probe fault alarmRead
BV25Alrm_HiHum.ActiveHigh humidity alarmRead
BV26Alrm_LoHum.ActiveLow humidity alarmRead
BV27Alrm_HiHumLim.ActiveHigh humidity limit alarmRead
BV28Alrm_Foam.ActiveFoam alarmRead
BV29Alrm_PeriodicMaint.ActivePeriodical maintenance requestRead
BV30Alrm_CylFull.ActiveCylinder full alarmRead
BV31Alrm_ConductPrb.ActiveConductivity probe fault alarmRead
BV32Alrm_HighConductWr.ActiveHigh conductivity warningRead
BV33Alrm_RetMem.ActiveRetain memory damaged warningRead
BV34Warn_Autotest.ActiveAutotest warningRead
BV35Warn_LevSen.ActiveLevel sensor warningRead
BV36Warn_LowProd.ActiveLow production warningRead
BV37Alrm_WirelessPrb_1_Offline.ActiveWireless probe 1 offlineRead
BV38Alrm_WirelessPrb_2_Offline.ActiveWireless probe 2 offlineRead
BV39Alrm_WirelessPrb_3_Offline.ActiveWireless probe 3 offlineRead
BV40Alrm_WirelessPrb_4_Offline.ActiveWireless probe 4 offlineRead
BV41Alrm_MissingModel.ActiveModel not configuredRead
BV42Alrm_NetUnit_1.ActiveActive alarm on unit 1Read
BV43Alrm_NetUnit_2.ActiveActive alarm on unit 2Read
BV44Alrm_NetUnit_3.ActiveActive alarm on unit 3Read
BV45Alrm_NetUnit_4.ActiveActive alarm on unit 4Read
BV46Alrm_NetUnit_5.ActiveActive alarm on unit 5Read
BV47Alrm_NetUnit_6.ActiveActive alarm on unit 6Read
BV48Alrm_NetUnit_7.ActiveActive alarm on unit 7Read
BV49Alrm_NetUnit_8.ActiveActive alarm on unit 8Read
BV50Alrm_NetUnit_9.ActiveActive alarm on unit 9Read
BV51Alrm_NetUnit_10.ActiveActive alarm on unit 10Read
BV52Alrm_NetUnit_11.ActiveActive alarm on unit 11Read
BV53Alrm_NetUnit_12.ActiveActive alarm on unit 12Read
BV54Alrm_NetUnit_13.ActiveActive alarm on unit 13Read
BV55Alrm_NetUnit_14.ActiveActive alarm on unit 14Read
BV56Alrm_NetUnit_15.ActiveActive alarm on unit 15Read
BV57Alrm_NetUnit_16.ActiveActive alarm on unit 16Read
BV58Alrm_NetUnit_17.ActiveActive alarm on unit 17Read
BV59Alrm_NetUnit_18.ActiveActive alarm on unit 18Read
BV60Alrm_NetUnit_19.ActiveActive alarm on unit 19Read
BV61Alrm_NetUnit_20.ActiveActive alarm on unit 20Read
BV62Alrm_WirelessPrb_1_LowBatt.ActiveWireless probe 1: Low battery level alarmRead
BV63Alrm_WirelessPrb_2_LowBatt.ActiveWireless probe 2: Low battery level alarmRead
BV64Alrm_WirelessPrb_3_LowBatt.ActiveWireless probe 3: Low battery level alarmRead
BV65Alrm_WirelessPrb_4_LowBatt.ActiveWireless probe 4: Low battery level alarmRead
BV66Alrm_WirelessPrb_Main.ActiveWireless probe fault (main group)Read
BV67Alrm_WirelessPrb_Limit.ActiveWireless probe fault (limit group)Read
BV68SchedDayCfg[0].EnTBScheduler: Enable band 1Write
BV69SchedDayCfg[1].EnTBScheduler: Enable band 2Write
BV70SchedDayCfg[2].EnTBScheduler: Enable band 3Write
BV71SchedDayCfg[3].EnTBScheduler: Enable band 4Write
BV72SchedDayCfg[4].EnTBScheduler: Enable band 5Write
BV73SchedDayCfg[5].EnTBScheduler: Enable band 6Write
Object ID lookup: CAREL heaterSteam UR point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the heaterSteam UR (2018 manual, before heaterSteam 4) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CAREL heaterSteam UR (2018 manual, before heaterSteam 4)

How many BACnet points does the CAREL heaterSteam UR (2018 manual, before heaterSteam 4) have?

This list has 188 BACnet objects: 45 analog values, 69 binary values, 74 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CAREL heaterSteam UR (2018 manual, before heaterSteam 4) BACnet points are writable?

76 of the 188 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official CAREL heaterSteam UR (2018 manual, before heaterSteam 4) BACnet documentation?

The source is heaterSteam - UR Electric resistance humidifier - User manual (+0300080EN rel. 1.4), revision 2018-02-05, published free by CAREL at https://www.carel.com/documents/10191/0/%2B0300080EN/8e3b3908-4f1c-41c0-8712-bddd86881a07?version=1.12.

What are the minimum BACnet points to integrate the CAREL heaterSteam UR (2018 manual, before heaterSteam 4)?

Start with BV 6 OnBySV (Unit on/off from the BMS); AV 11 SV_PwrReq (Production request from the BMS, %); AV 14 GlbSetP_Hum (Humidity set point (own probe control)); BV 5 OnOffStatus (Unit on/off status); PIV 12 UnitStatus (Operating state code); AV 0 MainPrb (Main probe reading); AV 12 CurrProdPh (Current steam production, kg/h or lb/h); BV 14 CurrBlkAlrm.IsPresent (Resettable alarm active); BV 13 CurrBlkAlrm.IsBlocker (Shutdown alarm active).

How do I enable BMS control of the CAREL heaterSteam UR (2018 manual, before heaterSteam 4)?

On screen Eh01 set 'On/Off from SV' and 'Control from SV' to Yes (both default to No); otherwise the unit ignores the supervisor on/off and production request.

Can the BMS supply sensor values to the CAREL heaterSteam UR (2018 manual, before heaterSteam 4)?

With control from supervisor the BMS sends the production request on SV_PwrReq (AV 11) instead of the unit using its own probe.

How do I check these points on the real heaterSteam UR (2018 manual, before heaterSteam 4)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CAREL BACnet points lists