Gas-fired steam humidifier · BACnet points list

CAREL gaSteam (UG) gas-fired humidifier BACnet points list

Updated 4 November 2026

Short answer

gaSteam is CAREL's gas-fired steam humidifier with a built-in controller and web server. BACnet MS/TP (on the BMS RS485 port) and BACnet IP (on the Ethernet port) are built in; only one of the two can be active at a time. The object list covers set points, probe readings, production, burner and fan data, scheduler settings, Main/Secondary data and one BV per alarm.

This page lists 350 BACnet objects for the CAREL gaSteam (UG) gas-fired humidifier — 350 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CAREL’s own free documentation, linked below.

Manufacturer
CAREL
Model
gaSteam (UG) gas-fired humidifier
Equipment
Gas-fired steam humidifier
Equipment type
Humidifiers
BACnet objects
350 (350 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
77000
Also known as
gaSteam, UG, UG045, UG090, UG180, CAREL gas-fired steam humidifier, +0300122EN
Source document
gaSteam - UG Gas-fired humidifier - User manual · +0300122EN rel. 1.4 · rev. 2026-02-26
Download CSV 350 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CAREL’s current documentation and the live device before use. Not official CAREL information. Terms of use.

BMS integration notes: CAREL gaSteam (UG) gas-fired humidifier

Integration in brief

Enable BACnet on the Ethernet port (Eh06, on by default) or on the BMS port (Eh01 protocol BACnet plus Eh03), and set the device instance on Eh04. Then enable On/Off and control from supervisor on Eh07/Eh08. Start and stop the unit with OnBySV (BV 0) and send the production request on SV_PwrReq (AV 73), or let the unit run its own humidity control with the set point on AV 1. Monitor OnOffStatus, UnitStatus, current production and the alarm summary BVs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0OnBySVUnit on/off from the BMSWrite
AV 73SV_PwrReqProduction request from the BMS, 0-100 %Write
AV 1GlbSetP_HumHumidity set point, %RH (own probe control)Write
BV 35OnOffStatusUnit on/off statusWrite
PIV 57UnitStatusOperating state codeWrite
AV 31MainPrbMain probe readingWrite
AV 34CurrProdPhCurrent steam production, kg/hWrite
BV 38CurrBlkAlrm.IsPresentAt least one alarm activeWrite
BV 37CurrBlkAlrm.IsBlockerNon-resettable alarm activeWrite

Enable & remote start

On screens Eh07/Eh08 (Installer menu) select the supervisor port and enable 'On/Off signal from supervisor' and 'control from supervisor'; on the BMS port the Eh01 settings 'On/Off from SV' and 'Control from SV' do the same. Without them the unit ignores the supervisor on/off and production request.

Heartbeat & communication loss

Eh08 can enable a supervisor-offline alarm (ALP21, BV 135) with an activation delay. The manual does not say what the unit does with its output when the supervisor goes offline.

Sensors & values from the BMS

With control from supervisor the BMS sends the production request on SV_PwrReq (AV 73) instead of the unit using a probe. Up to four CAREL wireless probes can also feed the unit (WirelessPrbVal AI objects).

Network setup

Watch out for

CAREL gaSteam (UG) gas-fired humidifier BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

350 of 350 shown
Type
Binary
Show
CAREL gaSteam (UG) gas-fired humidifier BACnet Points List
DescriptionStates
AI41WirelessPrbVal_1.HumWireless probe 1 humidity, %rH (SA and SI probes only)Write
AI42WirelessPrbVal_1.TempWireless probe 1 - Temperature value in °CWrite
AI45WirelessPrbVal_2.HumWireless probe 2 humidity, %rH (SA and SI probes only)Write
AI46WirelessPrbVal_2.TempWireless probe 2 - Temperature value in °CWrite
AI49WirelessPrbVal_3.HumWireless probe 3 humidity, %rH (SA and SI probes only)Write
AI50WirelessPrbVal_3.TempWireless probe 3 - Temperature value in °CWrite
AI53WirelessPrbVal_4.HumWireless probe 4 humidity, %rH (SA and SI probes only)Write
AI54WirelessPrbVal_4.TempWireless probe 4 - Temperature value in °CWrite
AV0ManReqSet production request in manual mode%Write
AVmin1GlbSetP_HumSet humidity value (humidity set point)%RHWrite
AV2GlbSetP_TempTemperature value setting (temperature set point)°CWrite
AV3RegulationCfg.HystUnit control parameters - Control hysteresisWrite
AV4RegulationCfg.DiffUnit control parameters - Differential (for modulating control)Write
AV5GlbSetPLim_HumSet humidity limit value (humidity limit set point)%RHWrite
AV6GlbSetPLim_TempSet temperature limit value (temperature limit set point)°CWrite
AV7RegulationCfg.DiffLimUnit control parameters - Limit differential (for modulating control)Write
AV8RegulationCfg.MinReqUnit control parameters - Minimum request%Write
AV9AlrmThrshHumLoSet low humidity alarm threshold, main probe%RHWrite
AV10AlrmThrshHumHiSet high humidity alarm threshold, main probe%RHWrite
AV11AlrmThrshHumHiLimSet low humidity alarm threshold, limit probe%RHWrite
AV12AlrmThrshTempLoSet low temperature alarm threshold, main probe°CWrite
AV13AlrmThrshTempHiSet high temperature alarm threshold, main probe°CWrite
AV14AlrmThrshTempHiLimSet low temperature alarm threshold, limit probe°CWrite
AV15MainPrbCfg.Mi_HumMain probe configuration - Minimum for humidity control%RHWrite
AV16MainPrbCfg.Ma_HumMain probe configuration - Maximum for humidity control%RHWrite
AV17MainPrbCfg.Mi_TempMain probe configuration - Minimum for temperature control°CWrite
AV18MainPrbCfg.Ma_TempMain probe configuration - Maximum for temperature control°CWrite
AV19LimitPrbCfg.Mi_HumLimit probe configuration - Minimum for humidity control%RHWrite
AV20LimitPrbCfg.Ma_HumLimit probe configuration - Maximum for humidity control%RHWrite
AV21LimitPrbCfg.Mi_TempLimit probe configuration - Minimum for temperature control°CWrite
AV22LimitPrbCfg.Ma_TempLimit probe configuration - Maximum for temperature control°CWrite
AV23RegulationCfg.PwrCorrectionFactorUnit control parameters - Correction factorWrite0=no correction
AV24SchedDayCfg[0].SetPScheduler - Set point for ON+SET mode (2) (Monday)Write
AV25SchedDayCfg[1].SetPScheduler - Set point for ON+SET mode (2) (Tuesday)Write
AV26SchedDayCfg[2].SetPScheduler - Set point for ON+SET mode (2) (Wednesday)Write
AV27SchedDayCfg[3].SetPScheduler - Set point for ON+SET mode (2) (2) (Thursday)Write
AV28SchedDayCfg[4].SetPScheduler - Set point for ON+SET mode (2) (2) (Friday)Write
AV29SchedDayCfg[5].SetPScheduler - Set point for ON+SET mode (2) (Saturday)Write
AV30Man_ProdReqM8Manual production requestWrite
AVmin31MainPrbMain probe readingWrite
AV32LimitPrbLimit probe readingWrite
AV33PreheatPrbPreheating probe reading°CWrite
AVmin34CurrProdPhCurrent productionkg/hWrite
AV35NetReqTotal current production as a % (M/S mode only)%Write
AV36NetProdTotal current production in kg/h / lb/h (M/S mode only)kgWrite
AV37Burner_1_TachFan 1 speed readingrpmWrite
AV38Burner_2_TachFan 2 speed readingrpmWrite
AV39Burner_MB_3_TachFan 3 speed readingrpmWrite
AV40Temp_Fumes_1Flue gas temperature - Probe 1 reading°CWrite
AV41Temp_Fumes_2Flue gas temperature - Probe 2 reading°CWrite
AV42Temp_Fumes_MB_3Flue gas temperature - Probe 3 reading°CWrite
AV43Fan1_PWMFan 1 speed set pointWrite
AV44Fan2_PWMFan 2 speed set pointWrite
AV45Fan3_PWMFan 3 speed set pointWrite
AV46Fan1_SetSpeedFan 1 speed settingWrite
AV47Fan2_SetSpeedFan 2 speed settingWrite
AV48FoamLevRealSignal reading from foam sensorWrite
AV59RegulationCfg.W_MinTempThrshSet water preheating temperature°CWrite
AV60PreheatOffset_TempPreheating offset from temperature set point°CWrite
AV61PreheatOffset_HumPreheating offset from humidity set point%RHWrite
AV62ManMode_Fan1_PWMFan 1 speed setting in manual moderpmWrite
AV63ManMode_Fan2_PWMFan 2 speed setting in manual moderpmWrite
AV64ManMode_Fan3_PWMFan 3 speed setting in manual moderpmWrite
AV65Man_ProdReqM8Manual production requestWrite
AV66MaxUnitProdSet maximum production value%Write
AV70ProdReqMskProduction request%Write
AV71ProdReqMsk_SecondarySecondary unit production request%Write
AV72CurrProdPh_SecondarySecondary unit current productionkg/hWrite
AVmin73SV_PwrReqProduction request from supervisor%Write
AV74PreheatPrb_SecondarySecondary unit preheating probe reading°CWrite
BVmin0OnBySVUnit On/Off signal from supervisorWrite
BV5WHardnessTypSet water hardness management modeWrite0=AUTO, 1=MANUAL
BV6SchedDayCfg[0].EnTBScheduler - Enable time band (Monday)Write
BV7SchedDayCfg[1].EnTBScheduler - Enable time band (Tuesday)Write
BV8SchedDayCfg[2].EnTBScheduler - Enable time band (Wednesday)Write
BV9SchedDayCfg[3].EnTBScheduler - Enable time band (Thursday)Write
BV10SchedDayCfg[4].EnTBScheduler - Enable time band (Friday)Write
BV11SchedDayCfg[5].EnTBScheduler - Enable time band (Saturday)Write
BV12ManExtFanBlower command in manual modeWrite0=OFF, 1=ON
BV15ManFillPmpStatus_SecondaryFill valve control in manual mode, Secondary unitWrite0=OFF, 1=ON
BV16ManDrainPmpStatus_SecondaryDrain pump command in manual mode, Secondary unitWrite0=OFF, 1=ON
BV17ManExtFan_SecondaryBlower command in manual mode, Secondary unitWrite0=OFF, 1=ON
BV30RemOnUnit On/Off signal from digital input (ON = TRUE)Write
BV32LevSenStatus.LowLevel sensor status - Low levelWrite
BV33LevSenStatus.HiLevel sensor status - High levelWrite
BV34LevSenStatus.FoamLevel sensor status - Foam levelWrite
BVmin35OnOffStatusUnit On/Off statusWrite
BV36PreMaintWarnNext maintenance pre-alertWrite
BVmin37CurrBlkAlrm.IsBlockerAt least 1 non-resettable alarm activeWrite
BVmin38CurrBlkAlrm.IsPresentAt least 1 alarm activeWrite
BV39CurrBlkAlrm.WarningAt least 1 warning activeWrite
BV40Alrm_Autotest.ActiveAlarm ALC01: Autotest failedWrite
BV41Alrm_HighConductAl.ActiveAlarm ALC02: High conductivityWrite
BV42Alrm_LevSen.ActiveAlarm ALC03: Level sensor blockedWrite
BV44Alrm_WMiss.ActiveAlarm ALB01: No waterWrite
BV45Alrm_LowProd.ActiveAlarm ALB02: Low productionWrite
BV46Alrm_MainPrb.ActiveAlarm ALA01: Main probe broken or not connectedWrite
BV47Alrm_LimPrb.ActiveAlarm ALA02: Limit probe broken or not connectedWrite
BV48Alrm_PreHPrb.ActiveAlarm ALA03: Preheating probe broken or not connectedWrite
BV49Alrm_HiHum.ActiveAlarm ALH01: High humidity/temperatureWrite
BV50Alrm_LoHum.ActiveAlarm ALH02: Low humidity/temperatureWrite
BV51Alrm_HiHum_Lim.ActiveAlarm ALH03: High limit humidity/temperatureWrite
BV52Alrm_Foam.ActiveAlarm ALW01: Foam warningWrite
BV53Alrm_PeriodicMaint.ActiveAlarm ALT01: Maintenance requestWrite
BV54Alrm_CylFull.ActiveAlarm ALW02: Cylinder fullWrite
BV55Alrm_ConductPrb.ActiveAlarm ALA04: Conductivity meterWrite
BV56Alrm_HighConductWr.ActiveWarning ALW03: High conductivityWrite
BV57Alrm_RetMem.ActiveAlarm ALR01: Retain memoryWrite
BV58Warn_Autotest.ActiveWarning ALW04: Autotest log onlyWrite
BV59Warn_LevSen.ActiveWarning ALW05: Level sensor log onlyWrite
BV60Warn_LowProd.ActiveWarning ALW06: Low production log onlyWrite
BV61Alrm_WirelessPrb_1_Offline.ActiveAlarm ALP01: Wireless probe 1 offlineWrite
BV62Alrm_WirelessPrb_2_Offline.ActiveAlarm ALP02: Wireless probe 2 offlineWrite
BV63Alrm_WirelessPrb_3_Offline.ActiveAlarm ALP03: Wireless probe 3 offlineWrite
BV64Alrm_WirelessPrb_4_Offline.ActiveAlarm ALP04: Wireless probe 4 offlineWrite
BV65Alrm_MissingModel.ActiveAlarm ALM01: Model not setWrite
BV66Alrm_NetUnit_1.ActiveAlarm ALN01: Problems on network unit 1Write
BV67Alrm_NetUnit_2.ActiveAlarm ALN02: Problems on network unit 2Write
BV68Alrm_NetUnit_3.ActiveAlarm ALN03: Problems on network unit 3Write
BV69Alrm_NetUnit_4.ActiveAlarm ALN04: Problems on network unit 4Write
BV70Alrm_NetUnit_5.ActiveAlarm ALN05: Problems on network unit 5Write
BV71Alrm_NetUnit_6.ActiveAlarm ALN06: Problems on network unit 6Write
BV72Alrm_NetUnit_7.ActiveAlarm ALN07: Problems on network unit 7Write
BV73Alrm_NetUnit_8.ActiveAlarm ALN08: Problems on network unit 8Write
BV74Alrm_NetUnit_9.ActiveAlarm ALN09: Problems on network unit 9Write
BV75Alrm_NetUnit_10.ActiveAlarm ALN10: Problems on network unit 10Write
BV76Alrm_NetUnit_11.ActiveAlarm ALN11: Problems on network unit 11Write
BV77Alrm_NetUnit_12.ActiveAlarm ALN12: Problems on network unit 12Write
BV78Alrm_NetUnit_13.ActiveAlarm ALN13: Problems on network unit 13Write
BV79Alrm_NetUnit_14.ActiveAlarm ALN14: Problems on network unit 14Write
BV80Alrm_NetUnit_15.ActiveAlarm ALN15: Problems on network unit 15Write
BV81Alrm_NetUnit_16.ActiveAlarm ALN16: Problems on network unit 16Write
BV82Alrm_NetUnit_17.ActiveAlarm ALN17: Problems on network unit 17Write
BV83Alrm_NetUnit_18.ActiveAlarm ALN18: Problems on network unit 18Write
BV84Alrm_NetUnit_19.ActiveAlarm ALN19: Problems on network unit 19Write
BV85Alrm_NetUnit_20.ActiveAlarm ALN20: Problems on network unit 20Write
BV86Alrm_WirelessPrb_1_LowBatt.ActiveAlarm ALP05: Wireless probe 1 low batteryWrite
BV87Alrm_WirelessPrb_2_LowBatt.ActiveAlarm ALP06: Wireless probe 2 low batteryWrite
BV88Alrm_WirelessPrb_3_LowBatt.ActiveAlarm ALP07: Wireless probe 3 low batteryWrite
BV89Alrm_WirelessPrb_4_LowBatt.ActiveAlarm ALP08: Wireless probe 4 low batteryWrite
BV90Alrm_WirelessPrb_Main.ActiveAlarm ALA05: Main probe probe not availableWrite
BV91Alrm_WirelessPrb_Limit.ActiveAlarm ALA06: Limit probe probe not availableWrite
BV100Klixon_Fan_1Flue gas Klixon safety thermostat status 1Write
BV101Klixon_Fan_2Flue gas Klixon safety thermostat status 2Write
BV102Klixon_Fan_MB_3Flue gas Klixon safety thermostat status 3Write
BV103Flame_1_PresentBurner 1 flame presence statusWrite
BV104Flame_2_PresentBurner 2 flame presence statusWrite
BV105Flame_MB_3_PresentBurner 3 flame presence statusWrite
BV106Burner1_GOBurner 1 gas ignition command statusWrite
BV107Burner2_GOBurner 2 gas ignition command statusWrite
BV108Burner3_GOBurner 3 gas ignition command statusWrite
BV112BackupHwReqHardware backup requestWrite
BV113Alrm_Termic_Fan_1.ActiveAlarm ALA07: Thermal protector 1 activeWrite
BV114Alrm_Termic_Fan_2.ActiveAlarm ALA08: Thermal protector 2 activeWrite
BV115Alrm_Fumes_1_broke.ActiveAlarm ALP10: Flue gas probe 1 brokenWrite
BV116Alrm_Fumes_2_broke.ActiveAlarm ALP11: Flue gas probe 2 brokenWrite
BV117Alrm_warning_fumes_1.ActiveWarning ALP13: flue gas temperature 1Write
BV118Alrm_warning_fumes_2.ActiveWarning ALP14: flue gas temperature 2Write
BV119Alrm_fumes_1.ActiveAlarm ALP16: flue gas temperature 1Write
BV120Alrm_fumes_2.ActiveAlarm ALP17: flue gas temperature 2Write
BV121Alrm_Termic_Fan_3.ActiveAlarm ALA09: Thermal protector 3 activeWrite
BV122Alrm_Fumes_3_broke.ActiveAlarm ALP12: Flue gas probe 3 brokenWrite
BV123Alrm_fumes_3.ActiveAlarm ALP18: flue gas temperature 3Write
BV124Alrm_warning_fumes_3.ActiveWarning ALP15: flue gas temperature 3Write
BV125Alrm_Fan_1.ActiveAlarm ALA10: burner 1 flame failureWrite
BV126Alrm_Fan_2.ActiveAlarm ALA11: burner 2 flame failureWrite
BV127Alrm_Fan_3.ActiveAlarm ALA12: burner 3 flame failureWrite
BV128Al_AntiFreeze_1.ActiveAlarm ALA13: First anti-freeze threshold alarmWrite
BV129Al_Secondary_450_OffLine.ActiveAlarm ALA14: Secondary 450 onlineWrite
BV130Al_Main_450_OffLine.ActiveAlarm ALA15: Main 450 offlineWrite
BV131Al_AntiFreeze_2_Secondary.ActiveAlarm ALA17: Second anti-freeze threshold alarm - SecondaryWrite
BV132Al_Speed_Fault_Fan_1.ActiveAlarm ALA20: Fan 1 speed errorWrite
BV133Al_Speed_Fault_Fan_2.ActiveAlarm ALA21: Fan 2 speed errorWrite
BV134Al_Speed_Fault_Fan_3.ActiveAlarm ALA22: Fan 3 speed errorWrite
BV135Alrm_SVOffline.ActiveAlarm ALP21: Supervisor offlineWrite
BV136Alrm_MissingModel_S.ActiveAlarm ALP24: No secondary modelWrite
BV137Alrm_WMiss_S.ActiveAlarm ALP25: Secondary no waterWrite
BV138Alrm_Foam_S.ActiveAlarm ALM21: Secondary foam warningWrite
BV139Alrm_LowProd_S.ActiveAlarm ALB03: Secondary low productionWrite
BV140Alrm_LevSen_S.ActiveAlarm ALC05: Secondary level sensor brokenWrite
BV141Alrm_Autotest_S.ActiveAlarm ALC06: Secondary autotest failedWrite
BV142Alrm_CylFull_S.ActiveAlarm ALW12: Secondary cylinder full alarmWrite
BV143Alrm_HighConductAl_S.ActiveAlarm ALC07: Secondary high conductivityWrite
BV144Alrm_PreHPrb_S.ActiveAlarm ALA18: Secondary preheating probe broken or disconnectedWrite
BV145Alrm_ConductPrb_S.ActiveAlarm ALA19: Secondary conductivity probeWrite
BV146Alrm_RetMem_S.ActiveAlarm ALR02: Retain memory alarm - SecondaryWrite
BV147Warn_Autotest_S.ActiveWarning ALW07: Secondary autotestWrite
BV148Warn_LevSen_S.ActiveWarning ALW10: Secondary level sensorWrite
BV149Warn_LowProd_S.ActiveWarning ALW11: Secondary low productionWrite
BV155Al_AntiFreeze_2.ActiveAlarm ALA16: Second anti-freeze threshold alarmWrite
BV156EnHiConductAlrmEnable high conductivity alarmWrite
BV157ManDrainManual total drain command; returns to 0 when drain is doneWrite1=start drain
BV158ManDrain_SecondaryManual total drain command, Secondary unit; returns to 0 when doneWrite1=start drain
BV159EnPreheatOffEnable preheating functionWrite0=disabled, 1=enabled
BV160EnPartFillsEnable micro-filling function to restore water levelWrite0=disabled, 1=enabled
BV161DilDrainCfg.DailySched[1].EnableDrain to dilute - Daily scheduler (Monday) - enableWrite
BV162DilDrainCfg.DailySched[2].EnableDrain to dilute - Daily scheduler (Tuesday) - enableWrite
BV163DilDrainCfg.DailySched[3].EnableDrain to dilute - Daily scheduler (Wednesday) - enableWrite
BV164DilDrainCfg.DailySched[4].EnableDrain to dilute - Daily scheduler (Thursday) - enableWrite
BV165DilDrainCfg.DailySched[5].EnableDrain to dilute - Daily scheduler (Friday) - enableWrite
BV166EnPeriodicDrainEnable periodic total drainWrite0=disabled, 1=enabled
BV167UnitPauseSet unit pausedWrite0=not paused, 1=paused
BV168CylWorkHrRes_SecondarySecondary unit cylinder production hours reset commandWrite
BV170ManMode_Fan1Fan 1 command in manual modeWrite0=OFF, 1=ON
BV171ManMode_Fan2Fan 2 command in manual modeWrite0=OFF, 1=ON
BV172ManMode_Burner1Burner 1 command in manual modeWrite0=OFF, 1=ON
BV173ManMode_Burner2Burner 2 command in manual modeWrite0=OFF, 1=ON
BV174Man_DOutM5Value of programmable digital output M5.2 (see DOutM5Cfg)Write
BV175Man_DOutM6Value of programmable digital output M6 (see DOutM5Cfg)Write
BV176Man_OnOffStatusUnit manual On/Off commandWrite
BV178DisableVarUnitPauseDisable pause from monitoring serviceWrite0=pause not disabled, 1=pause disabled
BV182EnManReqEnable manual production requestWrite
BV183Main_450Main-Secondary 450 mode statusWrite0=NOT ACTIVE, 1=ACTIVE
BV184ManMode_Fan3Fan 3 command in manual modeWrite0=OFF, 1=ON
BV185ManMode_Burner3Burner 3 command in manual modeWrite0=OFF, 1=ON
BV186CurrBlkAlrm_S_IsPresentAt least 1 alarm active, Secondary unitWrite
BV187CurrBlkAlrm_S_WarningAt least 1 warning active, Secondary unitWrite
BV188Alrm_HiBoilerTemp.ActiveAlarm ALP09: High boiler temperature (>110°)Write
BV189Al_AntiFreeze_1_Secondary.ActiveAlarm ALA23: Frost protection check components, Secondary unitWrite
BV190EnPreheatNoReqEnabling of pre-heating without offsetWrite0=disabled, 1=enabled
IV6ID_LangCurrent user interface languageWrite0=English, 1=Italian, 2=French, 3=German, 4=Spanish
IV102Fan_1_cfg.FAN_STATUSStatus of fan 1Write1=running, 2=pre-purge, 3=manual, 4=alarm, 5=calibration, 6=off, 7=startup pre-purge, 8=starting
IV103Fan_2_cfg.FAN_STATUSStatus of fan 2Write1=running, 2=pre-purge, 3=manual, 4=alarm, 5=calibration, 6=off, 7=startup pre-purge, 8=starting
IV107Fan_3_STATUSStatus of fan 3Write1=running, 2=pre-purge, 3=manual, 4=alarm, 5=calibration, 6=off, 7=startup pre-purge, 8=starting
PIV1ManMode_mskStart manual modeWrite0=disabled, 1=outputs controlled manually, 2=production request set manually
PIV2RegulationCfg.RegTypControl modeWrite0=external proportional signal, 1=external signal + limit, 2=ON/OFF signal, 3=humidity (one probe), 4=temperature (one probe), 5=humidity + limit, 6=temperature + limit, 7=humidity (two probes), 8=temperature (two probes)
PIV3ThrshAlrmDTDelay for each humidity/temperature threshold alarmsWrite
PIV4MainPrbCfg.UITypMain probe configuration - Probe typeWrite
PIV5LimitPrbCfg.UITypLimit probe configuration - Probe typeWrite
PIV6WHardnessManWater hardness value when hardness mode is manualWrite0=0-10 °F, 1=10-20 °F, 2=20-30 °F, 3=30-40 °F, 4=demineralised water
PIV7EvapCycleNoThrshEvaporation cycles before drain to dilute (micro-filling off)Write0=AUTO
PIV8FillTScaleExtra filling time after green LED level (micro-filling off)%Write
PIV9DilDrainTScaleSet drain time modification%Write
PIV10Scheduler.SchedDayToSetScheduler day to configure; above 0 enables editingWrite
PIV11SchedDayCfg[0].StartHrScheduler - Time band start time (Monday)Write
PIV12SchedDayCfg[0].StartMinScheduler - Time band end time (Monday)Write
PIV13SchedDayCfg[0].WorkModeScheduler - Time band mode (Monday)Write0=OFF, 1=ON, 2=ON+SET
PIV14SchedDayCfg[1].StartHrScheduler - Time band start time (Tuesday)Write
PIV15SchedDayCfg[1].StartMinScheduler - Time band end time (Tuesday)Write
PIV16SchedDayCfg[1].WorkModeScheduler - Time band mode (Tuesday)Write0=OFF, 1=ON, 2=ON+SET
PIV17SchedDayCfg[2].StartHrScheduler - Time band start time (Wednesday)Write
PIV18SchedDayCfg[2].StartMinScheduler - Time band end time (Wednesday)Write
PIV19SchedDayCfg[2].WorkModeScheduler - Time band mode (Wednesday)Write0=OFF, 1=ON, 2=ON+SET
PIV20SchedDayCfg[3].StartHrScheduler - Time band start time (Thursday)Write
PIV21SchedDayCfg[3].StartMinScheduler - Time band end time (Thursday)Write
PIV22SchedDayCfg[3].WorkModeScheduler - Time band mode (Thursday)Write0=OFF, 1=ON, 2=ON+SET
PIV23SchedDayCfg[4].StartHrScheduler - Time band start time (Friday)Write
PIV24SchedDayCfg[4].StartMinScheduler - Time band end time (Friday)Write
PIV25SchedDayCfg[4].WorkModeScheduler - Time band mode (Friday)Write0=OFF, 1=ON, 2=ON+SET
PIV26SchedDayCfg[5].StartHrScheduler - Time band start time (Saturday)Write
PIV27SchedDayCfg[5].StartMinScheduler - Time band end time (Saturday)Write
PIV28SchedDayCfg[5].WorkModeScheduler - Time band mode (Saturday)Write0=OFF, 1=ON, 2=ON+SET
PIV29UoMUnit of measure systemWrite0=not set, 1=international system, 2=imperial system
PIV30YearCurrent yearyearsWrite
PIV31MonthCurrent monthmonthsWrite
PIV32DayCurrent daydaysWrite
PIV33HourCurrent timehWrite
PIV34MinuteCurrent minuteminWrite
PIV35SetTimezoneTime zone setWrite
PIV36SV_CommandReset commandWrite1=cancel alarms, 2=reset cylinder production hours, reset after 5 seconds
PIV37SV_SWVerSoftware versionWrite
PIV38SV_OSVerOperating system versionWrite
PIV39UnitModelUnit modelWrite
PIV40Conductivity_CalcInlet water conductivity readingWrite
PIV43WirelessPrbInfo_1.BattLevWireless probe 1 battery, 0-3600 mV (low below 2800 mV)Write
PIV44WirelessPrbInfo_1.RadioSignalLevWireless probe 1 radio signal, dBm+100Write8-15=low, 15-30=medium, >30=excellent
PIV47WirelessPrbInfo_2.BattLevWireless probe 2 battery, 0-3600 mV (low below 2800 mV)Write
PIV48WirelessPrbInfo_2.RadioSignalLevWireless probe 2 radio signal, dBm+100Write8-15=low, 15-30=medium, >30=excellent
PIV51WirelessPrbInfo_3.BattLevWireless probe 3 battery, 0-3600 mV (low below 2800 mV)Write
PIV52WirelessPrbInfo_3.RadioSignalLevWireless probe 3 radio signal, dBm+100Write8-15=low, 15-30=medium, >30=excellent
PIV55WirelessPrbInfo_4.BattLevWireless probe 4 battery, 0-3600 mV (low below 2800 mV)Write
PIV56WirelessPrbInfo_4.RadioSignalLevWireless probe 4 radio signal, dBm+100Write8-15=low, 15-30=medium, >30=excellent
PIVmin57UnitStatusUnit statusWrite0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV58WorkHrTotal unit operating hourshWrite
PIV59CylWorkHrCylinder production hourshWrite
PIV60NetStatus[1]Status of network unit 1Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV61NetStatus[2]Status of network unit 2Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV62NetStatus[3]Status of network unit 3Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV63NetStatus[4]Status of network unit 4Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV64NetStatus[5]Status of network unit 5Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV65NetStatus[6]Status of network unit 6Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV66NetStatus[7]Status of network unit 7Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV67NetStatus[8]Status of network unit 8Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV68NetStatus[9]Status of network unit 9Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV69NetStatus[10]Status of network unit 10Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV70NetStatus[11]Status of network unit 11Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV71NetStatus[12]Status of network unit 12Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV72NetStatus[13]Status of network unit 13Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV73NetStatus[14]Status of network unit 14Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV74NetStatus[15]Status of network unit 15Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV75NetStatus[16]Status of network unit 16Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV76NetStatus[17]Status of network unit 17Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV77NetStatus[18]Status of network unit 18Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV78NetStatus[19]Status of network unit 19Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV79NetStatus[20]Status of network unit 20Write0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV100SV_CommandResultResponse to cylinder hours reset command; resets after 5 sWrite1=ok, 2=failed, 3=invalid command
PIV102PreMaintWarnThrshSet next maintenance pre-alert timehWrite
PIV103PreMaintWarnThrsh_SecondarySet next maintenance pre-alert time, Secondary unithWrite
PIV104HiConductAlrmDlyTSet high conductivity alarm delayminWrite
PIV105HiConductWarnThrshSet high conductivity warning thresholdWrite
PIV106HiConductAlrmThrshSet high conductivity alarm thresholdWrite
PIV107HiConductWarnHystSet high conductivity warning high conductivityWrite
PIV108FoamLevSetPScaleFoam sensor sensitivity (0%-200% - def.100%)Write
PIV109FoamLevSetPScale_SecondaryFoam sensor sensitivity (0%-200% - def.100%), Secondary unitWrite
PIV110PartFillsTSet micro-fill cycle durationsWrite
PIV111PartFillsT_SecondarySet micro-fill cycle duration on Secondary unitsWrite
PIV112DilDrainCfg.TypDrain to dilute mode with micro-fill activeWrite0=disabled, 1=daily scheduler, 2=periodic
PIV115DilDrainCfg.PeriodicDilDrainThrshHours between periodic drain to dilute cycles (micro-filling on)hWrite
PIV116DilDrainCfg.DailySched[1].Start_hDrain to dilute - Daily scheduler (Monday) - hourshWrite
PIV117DilDrainCfg.DailySched[1].Start_minDrain to dilute - Daily scheduler (Monday) - minutesminWrite
PIV118DilDrainCfg.DailySched[2].Start_hDrain to dilute - Daily scheduler (Tuesday) - hourshWrite
PIV119DilDrainCfg.DailySched[2].Start_minDrain to dilute - Daily scheduler (Tuesday) - minutesminWrite
PIV120DilDrainCfg.DailySched[3].Start_hDrain to dilute - Daily scheduler (Wednesday) - hourshWrite
PIV121DilDrainCfg.DailySched[3].Start_minDrain to dilute - Daily scheduler (Wednesday) - minutesminWrite
PIV122DilDrainCfg.DailySched[4].Start_hDrain to dilute - Daily scheduler (Thursday) - hourshWrite
PIV123DilDrainCfg.DailySched[4].Start_minDrain to dilute - Daily scheduler (Thursday) - minutesminWrite
PIV124DilDrainCfg.DailySched[5].Start_hDrain to dilute - Daily scheduler (Friday) - hourshWrite
PIV125DilDrainCfg.DailySched[5].Start_minDrain to dilute - Daily scheduler (Friday) - minutesminWrite
PIV126DilDrainCfg.DailySched[6].Start_hDrain to dilute - Daily scheduler (Saturday) - hourshWrite
PIV127DilDrainCfg.DailySched[6].Start_minDrain to dilute - Daily scheduler (Saturday) - minutesminWrite
PIV128DilDrainCfg.DailySched[7].Start_hDrain to dilute - Daily scheduler (Sunday) - hourshWrite
PIV129DilDrainCfg.DailySched[7].Start_minDrain to dilute - Daily scheduler (Sunday) - minutesminWrite
PIV130PeriodicDrainThrshSet number of production hours between two periodic total drain cycleshWrite
PIV131ExtFanDTOnSet start delay for blower from start of productionsWrite
PIV132ExtFanDTOffSet stop delay for blower from end of productionsWrite
PIV133EvapCycleNoThrsh_SEvaporation cycles before drain to dilute, Secondary unitWrite0=AUTO
PIV134FillTScale_SecondaryExtra filling time after green LED level, Secondary unit%Write
PIV135DilDrainTScale_SecondarySet drain time modification on Secondary unit%Write
PIV136WorkHr_SecondarySecondary unit total operating hourshWrite
PIV137CylWorkHr_SecondarySecondary unit cylinder production hourshWrite
PIV138Fan_1_cfg.Hours_CountFan 1 operating hourshWrite
PIV139WorkHrCntDwnTime remaining until next maintenance (demineralised water)hWrite
PIV140WorkHrCntDwn_120Time remaining until next maintenance (mains water)hWrite
PIV142CylResDate.YearCylinder production hours reset date - YearyearsWrite
PIV143CylResDate.MonthCylinder production hours reset date - MonthmonthsWrite
PIV144CylResDate.DayCylinder production hours reset date - DaydaysWrite
PIV145CylResDate.HourCylinder production hours reset date - HourshWrite
PIV146CylResDate.MinuteCylinder production hours reset date - MinutesminWrite
PIV147CylResDate_S.YearSecondary unit cylinder production hours reset date - YearyearsWrite
PIV148CylResDate_S.MonthSecondary unit cylinder production hours reset date - MonthmonthsWrite
PIV149CylResDate_S.DaySecondary unit cylinder production hours reset date - DaydaysWrite
PIV150CylResDate_S.HourSecondary unit cylinder production hours reset date - HourshWrite
PIV151CylResDate_S.MinuteSecondary unit cylinder production hours reset date - MinutesminWrite
PIV152WorkHrCntDwn_SecondaryTime remaining until next maintenance (demineralised water), SecondaryhWrite
PIV153WorkHrCntDwn_120_SecondaryTime remaining until next maintenance (mains water), SecondaryhWrite
PIV154UnitStatus_SecondarySecondary unit statusWrite0=standby, 1=production, 2=alarm, 3=off from BMS, 4=off from scheduler, 5=off from din, 6=off from display, 7=ready for backup, 8=manual mode, 9=warning, 10=preheat, 11=start preheat, 12=autotest, 13=manual drain, 14=thermal shock, 15=inactivity drain, 16=foam drain, 17=heaters off, 18=awaiting fill, 19=periodic drain, 20=pre-purge, 21=frost prot., 22=calibration, 23=ignition, 24=off from monitoring
PIV157Fan_2_cfg.Hours_CountFan 2 operating hourshWrite
PIV158Fan_3_cfg.Hours_CountFan 3 operating hourshWrite
PIV159OSVersion[1]Operating system version (major release)Write
PIV162Conductivity_SecondaryInlet water conductivity reading, Secondary unitWrite
Object ID lookup: CAREL gaSteam gas-fired humidifier point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the gaSteam (UG) gas-fired humidifier and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CAREL gaSteam (UG) gas-fired humidifier

How many BACnet points does the CAREL gaSteam (UG) gas-fired humidifier have?

This list has 350 BACnet objects: 8 analog inputs, 62 analog values, 150 binary values, 4 integer values, 126 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CAREL gaSteam (UG) gas-fired humidifier BACnet points are writable?

350 of the 350 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official CAREL gaSteam (UG) gas-fired humidifier BACnet documentation?

The source is gaSteam - UG Gas-fired humidifier - User manual (+0300122EN rel. 1.4), revision 2026-02-26, published free by CAREL at https://www.carel.com/documents/10191/0/%2B0300122EN/b5f100a2-099e-475f-a2d6-26bd03b55518?version=1.5.

What are the minimum BACnet points to integrate the CAREL gaSteam (UG) gas-fired humidifier?

Start with BV 0 OnBySV (Unit on/off from the BMS); AV 73 SV_PwrReq (Production request from the BMS, 0-100 %); AV 1 GlbSetP_Hum (Humidity set point, %RH (own probe control)); BV 35 OnOffStatus (Unit on/off status); PIV 57 UnitStatus (Operating state code); AV 31 MainPrb (Main probe reading); AV 34 CurrProdPh (Current steam production, kg/h); BV 38 CurrBlkAlrm.IsPresent (At least one alarm active); BV 37 CurrBlkAlrm.IsBlocker (Non-resettable alarm active).

How do I enable BMS control of the CAREL gaSteam (UG) gas-fired humidifier?

On screens Eh07/Eh08 (Installer menu) select the supervisor port and enable 'On/Off signal from supervisor' and 'control from supervisor'; on the BMS port the Eh01 settings 'On/Off from SV' and 'Control from SV' do the same. Without them the unit ignores the supervisor on/off and production request.

Does the CAREL gaSteam (UG) gas-fired humidifier need a BACnet heartbeat or have a communication timeout?

Eh08 can enable a supervisor-offline alarm (ALP21, BV 135) with an activation delay. The manual does not say what the unit does with its output when the supervisor goes offline.

Can the BMS supply sensor values to the CAREL gaSteam (UG) gas-fired humidifier?

With control from supervisor the BMS sends the production request on SV_PwrReq (AV 73) instead of the unit using a probe. Up to four CAREL wireless probes can also feed the unit (WirelessPrbVal AI objects).

How do I check these points on the real gaSteam (UG) gas-fired humidifier?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CAREL BACnet points lists

Source: gaSteam - UG Gas-fired humidifier - User manual · +0300122EN rel. 1.4 · rev. 2026-02-26. Object names, instances and units are reproduced as published; descriptions are our own.