High-pressure atomising humidifier (direct room) · BACnet points list

CAREL humiFog direct (UA) high-pressure atomising humidifier BACnet points list

Updated 4 November 2026

Short answer

humiFog direct is CAREL's high-pressure water atomising humidifier for direct room humidification, with one or two zones. Its c.pHC controller has Modbus and BACnet built in: BACnet MS/TP on the RS485 BMS port or BACnet IP on the Ethernet port (BACnet is the Ethernet default). The object list holds alarm BVs, a unit status code, zone requests, production, water use, probe readings and per-zone set points.

This page lists 61 BACnet objects for the CAREL humiFog direct (UA) high-pressure atomising humidifier — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CAREL’s own free documentation, linked below.

Manufacturer
CAREL
Model
humiFog direct (UA) high-pressure atomising humidifier
Equipment
High-pressure atomising humidifier (direct room)
Equipment type
Humidifiers
BACnet objects
61 (12 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
humiFog direct, humiFog Direct, UA, c.pHC, CAREL humiFog, +0300073EN
Source document
humiFog direct - User manual · +0300073EN rel. 1.4 · rev. 2022-03-29
Download CSV 61 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CAREL’s current documentation and the live device before use. Not official CAREL information. Terms of use.

BMS integration notes: CAREL humiFog direct (UA) high-pressure atomising humidifier

Integration in brief

Choose BACnet on the Ethernet port (the default) or on the RS485 BMS port, set the address and device instance on Dg07, and enable unit on/off and control from supervisor on Dg01/Dg02. The BMS then switches the unit with OnOff_Status.SVOn (BV 44) and either sends a zone request (AV 29/30) or writes the zone set points. Monitor UnitStatus, zone production, the main probe and the alarm BVs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 44OnOff_Status.SVOnUnit on/off from the BMSWrite
AV 29Regulation.SVReq_1Zone 1 request from the BMS, 0-100 %Write
AV 31RegCfg_1.SetP_humZone 1 humidity set point, %RHWrite
BV 43Alarms.AlrmResBySVAlarm reset from the BMSWrite
BV 0UnitOnUnit on/off statusRead
PIV 0UnitStatusOperating state code (0-12)Read
AV 2Prod_1Zone 1 production, %Read
AV 6MainPrb_1Zone 1 main probe readingRead
BV 3Al_HiP.ActiveHigh pressure alarmRead
BV 4Al_LoP.ActiveLow pressure alarmRead

Enable & remote start

On screen Dg01 (single-zone) or Dg02 (two-zone) set the serial address and enable unit on/off and control from supervisor; Dg03 selects the supervisor protocol. Without these settings the unit does not act on the supervisor on/off or request.

Sensors & values from the BMS

Instead of its own probes the unit can take a 0-100 % request per zone from the BMS on Regulation.SVReq_1/2 (AV 29/30). Up to eight CAREL wireless probes can also be read (AV 13-28, humidity on odd and temperature on even instances).

Network setup

Watch out for

CAREL humiFog direct (UA) high-pressure atomising humidifier BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

61 of 61 shown
Type
AnalogBinaryOther
Access
Show
CAREL humiFog direct (UA) high-pressure atomising humidifier BACnet Points List
DescriptionStates
BVmin0UnitOnUnit on/offRead
BV1Al_CircBreaker.ActiveCircuit breaker interventionRead
BV2Al_HiPSwitch.ActiveHigh pressure switch interventionRead
BVmin3Al_HiP.ActiveHigh pressureRead
BVmin4Al_LoP.ActiveLow pressureRead
BV5Al_HiPByPassBlk.ActiveHigh pressure on bypassRead
BV6Al_HiPByPass.ActiveHigh pressure on bypassRead
BV7Al_HiTByPassBlk.ActiveHigh temperature on bypassRead
BV8Al_HiTByPass.ActiveHigh temperature on bypassRead
BV9Al_LoPByPass.ActiveLow pressure on bypassRead
BV10Al_Drain.ActiveZone drain valves errorRead
BV11Al_ExpOffline.ActiveExpansion offlineRead
BV12Wr_HiTByPass.ActiveWarning high temperature on bypassRead
BV13Al_Retain.ActiveRetain memory errorRead
BV14Al_RetainWrite.ActiveRetain memory writes errorRead
BV15Al_MainPrb_1.ActiveMain probe 1 errorRead
BV16Al_LimPrb_1.ActiveLimit probe 1 errorRead
BV17Al_MainPrb_2.ActiveMain probe 2 errorRead
BV18Al_LimPrb_2.ActiveLimit probe 2 errorRead
BV19Al_PressByPass.ActiveLow pressure transducer errorRead
BV20Al_TempByPass.ActiveBypass temperature probe errorRead
BV21Al_Press.ActiveHigh pressure transducer errorRead
BV22Al_MissModel.ActiveMissing modelRead
BV23Al_WTS.ActiveWater treatment system alarmRead
BV24Al_WPrb_1 ÷ 8.ActiveWireless probe 1-8 offline (one object each, BV 24-31)Read
BV32Al_WPrbMain_1.ActiveMain probe 1 from wireless errorRead
BV33Al_WPrbLim_1.ActiveLimit probe 1 from wireless errorRead
BV34Al_WPrbMain_2.ActiveMain probe 2 from wireless errorRead
BV35Al_WPrbLim_2.ActiveLimit probe 2 from wireless errorRead
BV36Al_NetUnit_1 ÷ 4.ActiveUnit 1-4 alarm (one object each, BV 36-39)Read
BV40Al_Maint_50.ActiveChange oilRead
BV41Wr_Maint_1000.ActiveMaintenanceRead
BV42Al_Maint_3000.ActiveMaintenance requiredRead
BVmin43Alarms.AlrmResBySVAlarms resetWrite
BVmin44OnOff_Status.SVOnUnit on/off from supervisorWrite
PIVmin0UnitStatusUnit statusRead0=off by keyboard, 1=off by digital input, 2=off by supervisor, 3=off by scheduler, 4=startup, 5=standby, 6=production, 7=alarm, 8=fill, 9=wash, 10=manual mode, 11=ready backup, 12=switch off
AV0ReqMsk_1Request zone 1%Read
AV1ReqMsk_2Request zone 2%Read
AVmin2Prod_1Production zone 1%Read
AV3Prod_2Production zone 2%Read
AV4WProd_1Water consumption 1kg/h or lb/hRead
AV5WProd_2Water consumption 2kg/h or lb/hRead
AVmin6MainPrb_1Main probe 1%RH or °C/°FRead
AV7MainPrb_2Main probe 2%RH or °C/°FRead
AV8LimPrb_1Limit probe 1%RH or °C/°FRead
AV9LimPrb_2Limit probe 2%RH or °C/°FRead
AV10PressByPassPressure on bypassbar or psiRead
AV11PressPressure on main linebar or psiRead
AV12TempByPassBypass temperature°C or °FRead
AV13Inputs_WPrbs.WirelessPrbVal_1 ÷ 8.HumHumidity from wireless probes 1-8 (AV 13-27, odd)%RHRead
AV14Inputs_WPrbs.WirelessPrbVal_1 ÷ 8.TempTemperature from wireless probes 1-8 (AV 14-28, even)°C or °FRead
AVmin29Regulation.SVReq_1Unit request from supervisor zone 1%Write
AV30Regulation.SVReq_2Unit request from supervisor zone 2%Write
AVmin31RegCfg_1.SetP_humSetpoint zone 1 (humidity)%RHWrite
AV32RegCfg_1.SetP_tempSetpoint zone 1 (temperature)°C or °FWrite
AV33RegCfg_1.SetPLim_humSetpoint limit zone 1 (humidity)%RHWrite
AV34RegCfg_1.SetPLim_tempSetpoint limit zone 1 (temperature)°C or °FWrite
AV35RegCfg_2.SetP_humSetpoint zone 2 (humidity)%Write
AV36RegCfg_2.SetP_tempSetpoint zone 2 (temperature)°C or °FWrite
AV37RegCfg_2.SetPLim_humSetpoint limit zone 2 (humidity)%Write
AV38RegCfg_2.SetPLim_tempSetpoint limit zone 2 (temperature)°C or °FWrite
Object ID lookup: CAREL humiFog direct high-pressure atomising humidifier point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the humiFog direct (UA) high-pressure atomising humidifier and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CAREL humiFog direct (UA) high-pressure atomising humidifier

How many BACnet points does the CAREL humiFog direct (UA) high-pressure atomising humidifier have?

This list has 61 BACnet objects: 25 analog values, 35 binary values, 1 positive integer value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CAREL humiFog direct (UA) high-pressure atomising humidifier BACnet points are writable?

12 of the 61 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official CAREL humiFog direct (UA) high-pressure atomising humidifier BACnet documentation?

The source is humiFog direct - User manual (+0300073EN rel. 1.4), revision 2022-03-29, published free by CAREL at https://www.carel.com/documents/10191/0/%2B0300073EN/76c9e973-2bb0-41ed-baa2-aae19caeccf5?version=1.11.

What are the minimum BACnet points to integrate the CAREL humiFog direct (UA) high-pressure atomising humidifier?

Start with BV 44 OnOff_Status.SVOn (Unit on/off from the BMS); AV 29 Regulation.SVReq_1 (Zone 1 request from the BMS, 0-100 %); AV 31 RegCfg_1.SetP_hum (Zone 1 humidity set point, %RH); BV 43 Alarms.AlrmResBySV (Alarm reset from the BMS); BV 0 UnitOn (Unit on/off status); PIV 0 UnitStatus (Operating state code (0-12)); AV 2 Prod_1 (Zone 1 production, %); AV 6 MainPrb_1 (Zone 1 main probe reading); BV 3 Al_HiP.Active (High pressure alarm); BV 4 Al_LoP.Active (Low pressure alarm).

How do I enable BMS control of the CAREL humiFog direct (UA) high-pressure atomising humidifier?

On screen Dg01 (single-zone) or Dg02 (two-zone) set the serial address and enable unit on/off and control from supervisor; Dg03 selects the supervisor protocol. Without these settings the unit does not act on the supervisor on/off or request.

Can the BMS supply sensor values to the CAREL humiFog direct (UA) high-pressure atomising humidifier?

Instead of its own probes the unit can take a 0-100 % request per zone from the BMS on Regulation.SVReq_1/2 (AV 29/30). Up to eight CAREL wireless probes can also be read (AV 13-28, humidity on odd and temperature on even instances).

How do I check these points on the real humiFog direct (UA) high-pressure atomising humidifier?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CAREL BACnet points lists

Source: humiFog direct - User manual · +0300073EN rel. 1.4 · rev. 2022-03-29. Object names, instances and units are reproduced as published; descriptions are our own.