High-pressure atomising humidifier (multizone zone controller) · BACnet points list

CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller BACnet points list

Updated 12 November 2026

Short answer

Each humiFog Multizone zone controller can be supervised on its own over BACnet MS/TP or BACnet IP. Its list starts at address 300 and holds the zone's production request and actual production, probe readings, humidity and temperature set points and limits, supervisor request, alarm and warning flags, supervisor on/off and enable commands, zone status, control mode and versions.

This page lists 117 BACnet objects for the CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller — 48 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CAREL’s own free documentation, linked below.

Manufacturer
CAREL
Model
humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller
Equipment
High-pressure atomising humidifier (multizone zone controller)
Equipment type
Humidifiers
BACnet objects
117 (48 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
77000
Also known as
humiFog Multizone zone, humiFog zone cabinet, humiFog Multizone Touch zone, humiFog zone controller BACnet, +0300116EN, +0300115EN, +0300127EN
Source document
humiFog Multizone Touch pumping station and zone panel - Commissioning manual · +0300116EN rel. 1.3 · rev. 2025-10-28
Download CSV 117 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CAREL’s current documentation and the live device before use. Not official CAREL information. Terms of use.

BMS integration notes: CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller

Integration in brief

Enable supervisor on/off and control for the zone, then switch it with SVOnOff and either write the humidity (or temperature) set point or a production request (SVReq). Monitor zone status, production, probe readings and the alarm and warning flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 372ZoneData_S.Z_WorkPar.SVEnOnOffEnable zone on/off from supervisorWrite
BV 371ZoneData_S.Z_WorkPar.SVEnRegEnable zone control from supervisorWrite
BV 373ZoneData_S.Z_WorkPar.SVOnOffZone on/off from supervisorWrite
AV 306ZoneData_S.Z_WorkPar.GlbSetP_HumZone humidity set point, %rhWrite
AV 331ZoneData_S.Z_WorkPar.SVReqProduction request from supervisor, %Write
PIV 300ZoneData_S.Z_Info.ZoneStatusZone status codeRead
AV 301ZoneData_S.Z_Info.CurrProdCurrent zone productionRead
AV 303ZoneData_S.Z_Info.MainPrbMain probe readingRead
BV 369ZoneData_S.Z_Info.ZoneAlrmPresentAny zone alarm activeRead
BV 370ZoneData_S.Z_Info.ZoneWarningAny zone warning activeRead

Enable & remote start

SVEnOnOff enables zone on/off from the supervisor and SVEnReg enables zone control from the supervisor; then SVOnOff switches the zone.

Heartbeat & communication loss

Zone warning and alarm objects report a supervisor offline condition (WRO05 / WRO09).

Sensors & values from the BMS

SVReq (AV 331) is the zone production request from the supervisor, used when the zone control mode takes an external request.

Network setup

Watch out for

CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

117 of 117 shown
Type
AnalogBinaryOther
Access
Show
CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller BACnet Points List
DescriptionStates
AV300ZoneData_S.Z_Info.FlowReqZone production requestkg/h / lb/hRead
AVmin301ZoneData_S.Z_Info.CurrProdCurrent zone productionkg/h / lb/hRead
AV302ZoneData_S.Z_Info.RealReqZone request from control signal%Read
AVmin303ZoneData_S.Z_Info.MainPrbZone main probe readingRead
AV304ZoneData_S.Z_Info.LimitPrbZone limit probe readingRead
AV305ZoneData_S.Z_Info.RackTPrbZone rack temperature probe readingRead
AVmin306ZoneData_S.Z_WorkPar.GlbSetP_HumSet zone humidity set point%rhWrite
AV307ZoneData_S.Z_WorkPar.GlbSetP_TempSet zone temperature set point°C / °FWrite
AV308ZoneData_S.Z_WorkPar.GlbSetPLim_HumSet zone humidity limit set point%rhWrite
AV309ZoneData_S.Z_WorkPar.GlbSetPLim_TempSet zone temperature limit set point°C / °FWrite
AV310ZoneData_S.Z_Reg.RackMaxProdSet zone maximum production%Write
AV311ZoneData_S.Z_RackCfg.RackFlowRateNominal rack flow-ratekg/h / lb/hRead
AV312ZoneData_S.Z_FctsCfg.PressReliefT[1]Pressure relief function duration for step 1sWrite
AV313ZoneData_S.Z_FctsCfg.PressReliefT[2]Pressure relief function duration for step 2sWrite
AV314ZoneData_S.Z_FctsCfg.PressReliefT[3]Pressure relief function duration for step 3sWrite
AV315ZoneData_S.Z_FctsCfg.PressReliefT[4]Pressure relief function duration for step 4sWrite
AV316ZoneData_S.Z_FctsCfg.PressReliefT[5]Pressure relief function duration for step 5sWrite
AV317ZoneData_S.Z_FctsCfg.PressReliefT[6]Pressure relief function duration for step 6sWrite
AV318ZoneData_S.Z_PrbCfg.RackTPrb.Mi_TempMinimum rack temperature probe value°C / °FWrite
AV319ZoneData_S.Z_PrbCfg.RackTPrb.Ma_TempMaximum rack temperature probe value°C / °FWrite
AV320ZoneData_S.Z_PrbCfg.RackTPrb.OffsRack temperature probe reading offset°C / °FWrite
AV321ZoneData_S.Z_FctsCfg.RackTempMng.RackTSetPTemperature set point for production modulation function from rack probe°C / °FWrite
AV322ZoneData_S.Z_FctsCfg.RackTempMng.RackTBandProportional band for production modulation function from rack probe°C / °FWrite
AV323ZoneData_S.Z_FctsCfg.RackTempMng.RackTDiffDifferential for disabling the production modulation function from rack probe warning°C / °FWrite
AV325ZoneData_S.Z_FctsCfg.HighMainHum_WarnThrshSet main probe high humidity alarm threshold%rhWrite
AV326ZoneData_S.Z_FctsCfg.HighMainTemp_WarnThrshSet main probe high temperature alarm threshold°C / °FWrite
AV327ZoneData_S.Z_FctsCfg.LowMainHum_WarnThrshSet main probe low humidity alarm threshold%rhWrite
AV328ZoneData_S.Z_FctsCfg.LowMainTemp_WarnThrshSet main probe low temperature alarm threshold°C / °FWrite
AV329ZoneData_S.Z_FctsCfg.HighLimitHum_WarnThrshSet limit probe high humidity alarm threshold%rhWrite
AV330ZoneData_S.Z_FctsCfg.LowLimitTemp_WarnThrshSet limit probe low temperature alarm threshold°C / °FWrite
AVmin331ZoneData_S.Z_WorkPar.SVReqZone production request from supervisor%Write
AV332ZoneData_S.Z_Info.TempDewPointZone dew point temperature calculation°C / °FRead
AV333ZoneData_S.Z_Info.TwoPrbsAvgTwo zone probe reading average calculationRead
AV334ZoneData_S.Z_Info.ThreePrbsAvgThree zone probe reading average calculationRead
BV301ZoneData_S.Z_FctsCfg.RackTempMng.EnRackTMngEnable production modulation function from rack temperature probe readingWrite0 = disabled, 1 = enabled
BV302ZoneData_S.Z_FctsCfg.RackTempMng.EnRackTReducedProdEnable production reduction based on rack temperatureWrite0/1
BV303ZoneData_S.Z_FctsCfg.RackTempMng.EnRackTWarnSelect type of signal for low rack temperatureWrite0 = notification, 1 = warning
BV304ZoneData_S.Z_FctsCfg.EnDlydHumPrbAlrmCtrlEnable humidity probe control delay for alarm activationWrite0/1
BV305ZoneData_S.Z_FctsCfg.RackEnLogicEnable zone production digital input (RACKEN) statusWrite0 = contact closed, 1 = contact open
BV306ZoneData_S.Z_FctsCfg.AirFlowSwitchLogicFlow switch digital input (FLUX) statusWrite0 = contact closed, 1 = contact open
BV307ZoneData_S.Z_FctsCfg.ZoneStatusDout_Logic"Zone status" ZONE digital output logicWrite0 = NC, 1 = NO
BV308ZoneData_S.Z_FctsCfg.AlrmDOutLogic"Alarm status" AL digital output logicWrite0 = NC, 1 = NO
BV309ZoneData_S.Z_FctsCfg.RelayLogicNO7"Programmable relay NO7" digital output logicWrite0 = NC, 1 = NO
BV310ZoneData_S.Z_DigIO.RackEnStatus_NoLogicEnable zone production digital input (RACKEN) statusRead0 = contact closed, 1 = contact open
BV311ZoneData_S.Z_DigIO.AirFlowSwitchStatus_NoLogicFlow switch digital input (FLUX) statusRead0 = contact closed, 1 = contact open
BV312ZoneData_S.Z_RackSteps.LineDrainLine drain digital output (NOL) statusRead0 = output not energised, 1 = output energised
BV313ZoneData_S.Z_DigIO.NO7_PrgDoutProgrammable relay NO7 digital output statusRead0 = output not energised, 1 = output energised
BV314ZoneData_S.Z_DigIO.Alrm_DoutAlarm status digital input (AL) statusRead0 = output not energised, 1 = output energised
BV315ZoneData_S.Z_RackSteps.VentilationRack ventilation solenoid valve digital output (NOV) statusRead0 = output energised, 1 = output not energised
BV316ZoneData_S.Z_FctsCfg.ZoneManModeEnFillEnable filling function for zone manual modeWrite0 = disabled, 1 = enabled
BV323ZoneData_S.Z_RackSteps.Step[1].FillRack fill solenoid valve status - step 1Read0 = closed, 1 = open
BV324ZoneData_S.Z_RackSteps.Step[2].FillRack fill solenoid valve status - step 2Read0 = closed, 1 = open
BV325ZoneData_S.Z_RackSteps.Step[3].FillRack fill solenoid valve status - step 3Read0 = closed, 1 = open
BV326ZoneData_S.Z_RackSteps.Step[4].FillRack fill solenoid valve status - step 4Read0 = closed, 1 = open
BV327ZoneData_S.Z_RackSteps.Step[5].FillRack fill solenoid valve status - step 5Read0 = closed, 1 = open
BV328ZoneData_S.Z_RackSteps.Step[6].FillRack fill solenoid valve status - step 6Read0 = closed, 1 = open
BV329ZoneData_S.Z_RackSteps.Step[1].DrainRack drain solenoid valve status - step 1Read0 = closed, 1 = open
BV330ZoneData_S.Z_RackSteps.Step[2].DrainRack drain solenoid valve status - step 2Read0 = closed, 1 = open
BV331ZoneData_S.Z_RackSteps.Step[3].DrainRack drain solenoid valve status - step 3Read0 = closed, 1 = open
BV332ZoneData_S.Z_RackSteps.Step[4].DrainRack drain solenoid valve status - step 4Read0 = closed, 1 = open
BV333ZoneData_S.Z_RackSteps.Step[5].DrainRack drain solenoid valve status - step 5Read0 = closed, 1 = open
BV334ZoneData_S.Z_RackSteps.Step[6].DrainRack drain solenoid valve status - step 6Read0 = closed, 1 = open
BV341ZoneData_S.Z_Alrms.Alrm_MainPrbALA01 - Zone alarm: main probe broken or disconnectedRead0/1
BV342ZoneData_S.Z_Alrms.Alrm_LimitPrbALA02 - Zone alarm: limit probe broken or disconnectedRead0/1
BV343ZoneData_S.Z_Alrms.Alrm_NoRackABC02 - Zone alarm: distribution system not configuredRead0/1
BV344ZoneData_S.Z_Alrms.Alrm_MasterOfflineABO01 - Zone alarm: pumping station offlineRead0/1
BV345ZoneData_S.Z_Alrms.Alrm_RackTPrbABA06 - Zone alarm: rack temperature probe broken or disconnectedRead0/1
BV346ZoneData_S.Z_Alrms.Warn_LowRackTempWRA10 - Zone warning: low rack temperatureRead0/1
BV347ZoneData_S.Z_Alrms.Warn_HighHumMainPrbWRA11 - Zone warning: high humidity measured by main probeRead0/1
BV348ZoneData_S.Z_Alrms.Warn_LowHumMainPrbWRA12 - Zone warning: low humidity measured by main probeRead0/1
BV349ZoneData_S.Z_Alrms.Warn_HighTempMainPrbWRA13 - Zone warning: high temperature measured by main probeRead0/1
BV350ZoneData_S.Z_Alrms.Warn_LowTempMainPrbWRA14 - Zone warning: low temperature measured by main probeRead0/1
BV351ZoneData_S.Z_Alrms.Warn_HighHumLimPrbWRA15 - Zone warning: high humidity measured by limit probeRead0/1
BV352ZoneData_S.Z_Alrms.Warn_LowTempLimPrbWRA16 - Zone warning: low humidity measured by limit probeRead0/1
BV353ZoneData_S.Z_Alrms.Warn_HighHumTwoPrbsAvgWRA17 - Zone warning: high humidity measured by average of 2 probesRead0/1
BV354ZoneData_S.Z_Alrms.Warn_LowHumTwoPrbsAvgWRA18 - Zone warning: low humidity measured by average of 2 probesRead0/1
BV355ZoneData_S.Z_Alrms.Warn_HighTempTwoPrbsAvgWRA19 - Zone warning: high temperature measured by average of 2 probesRead0/1
BV356ZoneData_S.Z_Alrms.Warn_LowTempTwoPrbsAvgWRA20 - Zone warning: low temperature measured by average of 2 probesRead0/1
BV357ZoneData_S.Z_Alrms.Warn_HighHumThreePrbsAvgWRA21 - Zone warning: high humidity measured by average of 3 probesRead0/1
BV358ZoneData_S.Z_Alrms.Warn_LowHumThreePrbsAvgWRA22 - Zone warning: low humidity measured by average of 3 probesRead0/1
BV359ZoneData_S.Z_Alrms.Warn_HighTempThreePrbsAvgWRA23 - Zone warning: high temperature measured by average of 3 probesRead0/1
BV360ZoneData_S.Z_Alrms.Warn_LowTempThreePrbsAvgWRA24 - Zone warning: low temperature measured by average of 3 probesRead0/1
BV361ZoneData_S.Z_Alrms.Warn_SVOfflineWRO05 - Zone warning: supervisor offlineRead0/1
BV362ZoneData_S.Z_Alrms.Alrm_SVOfflineWRO09 - Zone alarm: supervisor offlineRead0/1
BV363ZoneData_S.Z_Alrms.Alrm_RetainALG01 - Zone alarm: error in number of retain memory writesRead0/1
BV364ZoneData_S.Z_Alrms.Alrm_Err_retain_writeALG02 - Zone alarm: too many retain memory writesRead0/1
BV365ZoneData_S.Z_Alrms.Warn_RetMemWRG03 - Zone warning: too many retain memory writesRead0/1
BV366ZoneData_S.Z_Alrms.Alrm_NoModelABC01 - Zone alarm: no model configuredRead0/1
BV367ZoneData_S.Z_WorkPar.UnitPauseUnit setting pausedWrite0=not paused; 1=paused
BV368ZoneData_S.Z_WorkPar.DisableVarUnitPauseDisable pause from monitoring serviceRead0: pause not disabled, 1: pause disabled
BVmin369ZoneData_S.Z_Info.ZoneAlrmPresentAt least 1 alarm active in zoneRead0/1
BVmin370ZoneData_S.Z_Info.ZoneWarningAt least 1 warning active in zoneRead0/1
BVmin371ZoneData_S.Z_WorkPar.SVEnRegEnable zone control from supervisorWrite0/1
BVmin372ZoneData_S.Z_WorkPar.SVEnOnOffEnable zone on/off from supervisorWrite0/1
BVmin373ZoneData_S.Z_WorkPar.SVOnOffZone on/off from supervisorWrite0/1
BV374ZoneData_S.Z_RackCfg.EnRotStepsZone step rotation delayWrite0/1
BV375EnMultiNetEnabling of the multi-networkWrite0/1
PIVmin300ZoneData_S.Z_Info.ZoneStatusZone statusRead0=Power On, 10=Software initialisation, 20=Awaiting network, 30=Wash, 40=Fill, 50=Standby empty, 60=Standby full, 70=Water control, 80=Production, 90=Slowdown, 100=Pre-wash, 110=Alarm, 120=Bypass calibration fill, 130=Bypass calibration, 140=Waiting for control, 150=WTS water change, 160=Disabled
PIV301ZoneData_S.Z_Reg.RegTypControl modeWrite0=on/off, 1=on/off + humidity limit, 2=on/off + temperature limit, 3=external signal, 4=external signal + humidity limit, 5=external signal + temperature limit, 6=humidity, 7=humidity + limit humidity, 8=humidity + temperature limit, 9=temperature, 10=temperature + temperature limit, 11=temperature + humidity limit, 12=2 humidity probes, 13=2 temperature probes, 14=3 humidity probes, 15=3 temperature probes, 16=2 temperature probes + humidity limit, 17=dewpoint, 18=dewpoint + humidity limit
PIV302ZoneData_S.Z_SysInfo.SwVer.XSoftware version X (Major)Read
PIV303ZoneData_S.Z_SysInfo.SwVer.YOperating system version Y (Minor)Read
PIV304ZoneData_S.Z_SysInfo.SwVer.ZSoftware version Z (Patch)Read
PIV305ZoneData_S.Z_SysInfo.OSVer.XOperating system version X (Major)Read
PIV306ZoneData_S.Z_SysInfo.OSVer.YOperating system version Y (Minor)Read
PIV307ZoneData_S.Z_SysInfo.OSVer.ZOperating system version Z (Patch)Read
PIV308ZoneData_S.Z_SysInfo.CoreTypec.pCO core versionRead
PIV309ZoneData_S.Z_SysInfo.UnitModelUnit modelRead
PIV310ZoneData_S.Z_PrbCfg.RackTPrb.UITypSelect rack temperature probe typeWrite0 = 0-1 V, 1 = 0-10 V, 2 = 2-10 V, 3 = 0-20 mA, 4 = 4-20 mA, 5 = NTC
PIV311ZoneData_S.Z_FctsCfg.HumPrbAlrmCtrlDelEnable control probe alarm delay at start of productionminWrite0 = disabled, 1 = enabled
PIV312ZoneData_S.Z_FctsCfg.FunctSelNO7_SlvSelect programmable relay NO7 functionWrite0 = Unit life status, 1 = Low rack temperature warning
PIV314ZoneData_S.Z_Info.ZoneManModeWaitZone manual mode activation statusRead0=manual mode available, 1=waiting for wash to finish, 2=waiting for fill to finish, 3=waiting for production to finish
PIV332ZoneData_S.Z_FctsCfg.PrbThrshsWarnDlyHigh/low humidity/temperature alarm delayminWrite
PIV333ZoneData_S.Z_Info.IPConfig[2]Zone IP addressRead
PIV334UoM_SVUnit of measureWrite2: Imperial system, 6: International system
PIV335ZoneData_S.Z_Info.OnOffStatusReservedRead
PIV336ZoneData_S.Z_RackCfg.RotStepsTZone step rotation delayminWrite
PIV337NetNumNetwork number for multi-networkWrite
Object ID lookup: CAREL humiFog Multizone zone controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller

How many BACnet points does the CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller have?

This list has 117 BACnet objects: 34 analog values, 63 binary values, 20 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller BACnet points are writable?

48 of the 117 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller BACnet documentation?

The source is humiFog Multizone Touch pumping station and zone panel - Commissioning manual (+0300116EN rel. 1.3), revision 2025-10-28, published free by CAREL at https://www.carel.com/documents/10191/0/%2B0300116EN/1990b09e-81eb-47c9-b022-bf575f96bb0f?version=1.3.

What are the minimum BACnet points to integrate the CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller?

Start with BV 372 ZoneData_S.Z_WorkPar.SVEnOnOff (Enable zone on/off from supervisor); BV 371 ZoneData_S.Z_WorkPar.SVEnReg (Enable zone control from supervisor); BV 373 ZoneData_S.Z_WorkPar.SVOnOff (Zone on/off from supervisor); AV 306 ZoneData_S.Z_WorkPar.GlbSetP_Hum (Zone humidity set point, %rh); AV 331 ZoneData_S.Z_WorkPar.SVReq (Production request from supervisor, %); PIV 300 ZoneData_S.Z_Info.ZoneStatus (Zone status code); AV 301 ZoneData_S.Z_Info.CurrProd (Current zone production); AV 303 ZoneData_S.Z_Info.MainPrb (Main probe reading); BV 369 ZoneData_S.Z_Info.ZoneAlrmPresent (Any zone alarm active); BV 370 ZoneData_S.Z_Info.ZoneWarning (Any zone warning active).

How do I enable BMS control of the CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller?

SVEnOnOff enables zone on/off from the supervisor and SVEnReg enables zone control from the supervisor; then SVOnOff switches the zone.

Does the CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller need a BACnet heartbeat or have a communication timeout?

Zone warning and alarm objects report a supervisor offline condition (WRO05 / WRO09).

Can the BMS supply sensor values to the CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller?

SVReq (AV 331) is the zone production request from the supervisor, used when the zone control mode takes an external request.

How do I check these points on the real humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CAREL BACnet points lists

Source: humiFog Multizone Touch pumping station and zone panel - Commissioning manual · +0300116EN rel. 1.3 · rev. 2025-10-28. Object names, instances and units are reproduced as published; descriptions are our own.