- humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller
High-pressure atomising humidifier (multizone zone controller) · BACnet points list
CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller BACnet points list
Updated 12 November 2026
Each humiFog Multizone zone controller can be supervised on its own over BACnet MS/TP or BACnet IP. Its list starts at address 300 and holds the zone's production request and actual production, probe readings, humidity and temperature set points and limits, supervisor request, alarm and warning flags, supervisor on/off and enable commands, zone status, control mode and versions.
This page lists 117 BACnet objects for the CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller — 48 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CAREL’s own free documentation, linked below.
- Manufacturer
- CAREL
- Model
- humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller
- Equipment
- High-pressure atomising humidifier (multizone zone controller)
- Equipment type
- Humidifiers
- BACnet objects
- 117 (48 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 77000
- Also known as
- humiFog Multizone zone, humiFog zone cabinet, humiFog Multizone Touch zone, humiFog zone controller BACnet, +0300116EN, +0300115EN, +0300127EN
Reference only, provided as-is: verify against CAREL’s current documentation and the live device before use. Not official CAREL information. Terms of use.
BMS integration notes: CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller
Enable supervisor on/off and control for the zone, then switch it with SVOnOff and either write the humidity (or temperature) set point or a production request (SVReq). Monitor zone status, production, probe readings and the alarm and warning flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 372 | ZoneData_S.Z_WorkPar.SVEnOnOff | Enable zone on/off from supervisor | Write |
| BV 371 | ZoneData_S.Z_WorkPar.SVEnReg | Enable zone control from supervisor | Write |
| BV 373 | ZoneData_S.Z_WorkPar.SVOnOff | Zone on/off from supervisor | Write |
| AV 306 | ZoneData_S.Z_WorkPar.GlbSetP_Hum | Zone humidity set point, %rh | Write |
| AV 331 | ZoneData_S.Z_WorkPar.SVReq | Production request from supervisor, % | Write |
| PIV 300 | ZoneData_S.Z_Info.ZoneStatus | Zone status code | Read |
| AV 301 | ZoneData_S.Z_Info.CurrProd | Current zone production | Read |
| AV 303 | ZoneData_S.Z_Info.MainPrb | Main probe reading | Read |
| BV 369 | ZoneData_S.Z_Info.ZoneAlrmPresent | Any zone alarm active | Read |
| BV 370 | ZoneData_S.Z_Info.ZoneWarning | Any zone warning active | Read |
Enable & remote start
SVEnOnOff enables zone on/off from the supervisor and SVEnReg enables zone control from the supervisor; then SVOnOff switches the zone.
Heartbeat & communication loss
Zone warning and alarm objects report a supervisor offline condition (WRO05 / WRO09).
Sensors & values from the BMS
SVReq (AV 331) is the zone production request from the supervisor, used when the zone control mode takes an external request.
Network setup
- Supervisor settings are under Menu > Settings > System > BMS: BMS port address, baud, stop bits, parity, Ethernet IP settings, and BACnet MS/TP station address, max masters, max frames and device instance.
- MS/TP defaults: station address 0, max masters 127, max frames 10, device instance 77000 (range 0-4194302); BMS port default 19200 baud.
- Only one BACnet instance is available: BACnet cannot run on the BMS (RS485) port and the Ethernet port at the same time.
- Each supervisor channel (Menu > Settings > System > Functions > Channel 1-3) is set to Supervisor or Supervisor + Controller with a protocol + port (ModBus BMS/ETH, BACnet BMS/ETH).
Watch out for
- Do not write variables that are not in the tables.
- Values are scaled by the resolution shown (0.1 for most analog values).
CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 300 | ZoneData_S.Z_Info.FlowReq | Zone production request | kg/h / lb/h | Read | |
| AVmin | 301 | ZoneData_S.Z_Info.CurrProd | Current zone production | kg/h / lb/h | Read | |
| AV | 302 | ZoneData_S.Z_Info.RealReq | Zone request from control signal | % | Read | |
| AVmin | 303 | ZoneData_S.Z_Info.MainPrb | Zone main probe reading | Read | ||
| AV | 304 | ZoneData_S.Z_Info.LimitPrb | Zone limit probe reading | Read | ||
| AV | 305 | ZoneData_S.Z_Info.RackTPrb | Zone rack temperature probe reading | Read | ||
| AVmin | 306 | ZoneData_S.Z_WorkPar.GlbSetP_Hum | Set zone humidity set point | %rh | Write | |
| AV | 307 | ZoneData_S.Z_WorkPar.GlbSetP_Temp | Set zone temperature set point | °C / °F | Write | |
| AV | 308 | ZoneData_S.Z_WorkPar.GlbSetPLim_Hum | Set zone humidity limit set point | %rh | Write | |
| AV | 309 | ZoneData_S.Z_WorkPar.GlbSetPLim_Temp | Set zone temperature limit set point | °C / °F | Write | |
| AV | 310 | ZoneData_S.Z_Reg.RackMaxProd | Set zone maximum production | % | Write | |
| AV | 311 | ZoneData_S.Z_RackCfg.RackFlowRate | Nominal rack flow-rate | kg/h / lb/h | Read | |
| AV | 312 | ZoneData_S.Z_FctsCfg.PressReliefT[1] | Pressure relief function duration for step 1 | s | Write | |
| AV | 313 | ZoneData_S.Z_FctsCfg.PressReliefT[2] | Pressure relief function duration for step 2 | s | Write | |
| AV | 314 | ZoneData_S.Z_FctsCfg.PressReliefT[3] | Pressure relief function duration for step 3 | s | Write | |
| AV | 315 | ZoneData_S.Z_FctsCfg.PressReliefT[4] | Pressure relief function duration for step 4 | s | Write | |
| AV | 316 | ZoneData_S.Z_FctsCfg.PressReliefT[5] | Pressure relief function duration for step 5 | s | Write | |
| AV | 317 | ZoneData_S.Z_FctsCfg.PressReliefT[6] | Pressure relief function duration for step 6 | s | Write | |
| AV | 318 | ZoneData_S.Z_PrbCfg.RackTPrb.Mi_Temp | Minimum rack temperature probe value | °C / °F | Write | |
| AV | 319 | ZoneData_S.Z_PrbCfg.RackTPrb.Ma_Temp | Maximum rack temperature probe value | °C / °F | Write | |
| AV | 320 | ZoneData_S.Z_PrbCfg.RackTPrb.Offs | Rack temperature probe reading offset | °C / °F | Write | |
| AV | 321 | ZoneData_S.Z_FctsCfg.RackTempMng.RackTSetP | Temperature set point for production modulation function from rack probe | °C / °F | Write | |
| AV | 322 | ZoneData_S.Z_FctsCfg.RackTempMng.RackTBand | Proportional band for production modulation function from rack probe | °C / °F | Write | |
| AV | 323 | ZoneData_S.Z_FctsCfg.RackTempMng.RackTDiff | Differential for disabling the production modulation function from rack probe warning | °C / °F | Write | |
| AV | 325 | ZoneData_S.Z_FctsCfg.HighMainHum_WarnThrsh | Set main probe high humidity alarm threshold | %rh | Write | |
| AV | 326 | ZoneData_S.Z_FctsCfg.HighMainTemp_WarnThrsh | Set main probe high temperature alarm threshold | °C / °F | Write | |
| AV | 327 | ZoneData_S.Z_FctsCfg.LowMainHum_WarnThrsh | Set main probe low humidity alarm threshold | %rh | Write | |
| AV | 328 | ZoneData_S.Z_FctsCfg.LowMainTemp_WarnThrsh | Set main probe low temperature alarm threshold | °C / °F | Write | |
| AV | 329 | ZoneData_S.Z_FctsCfg.HighLimitHum_WarnThrsh | Set limit probe high humidity alarm threshold | %rh | Write | |
| AV | 330 | ZoneData_S.Z_FctsCfg.LowLimitTemp_WarnThrsh | Set limit probe low temperature alarm threshold | °C / °F | Write | |
| AVmin | 331 | ZoneData_S.Z_WorkPar.SVReq | Zone production request from supervisor | % | Write | |
| AV | 332 | ZoneData_S.Z_Info.TempDewPoint | Zone dew point temperature calculation | °C / °F | Read | |
| AV | 333 | ZoneData_S.Z_Info.TwoPrbsAvg | Two zone probe reading average calculation | Read | ||
| AV | 334 | ZoneData_S.Z_Info.ThreePrbsAvg | Three zone probe reading average calculation | Read | ||
| BV | 301 | ZoneData_S.Z_FctsCfg.RackTempMng.EnRackTMng | Enable production modulation function from rack temperature probe reading | Write | 0 = disabled, 1 = enabled | |
| BV | 302 | ZoneData_S.Z_FctsCfg.RackTempMng.EnRackTReducedProd | Enable production reduction based on rack temperature | Write | 0/1 | |
| BV | 303 | ZoneData_S.Z_FctsCfg.RackTempMng.EnRackTWarn | Select type of signal for low rack temperature | Write | 0 = notification, 1 = warning | |
| BV | 304 | ZoneData_S.Z_FctsCfg.EnDlydHumPrbAlrmCtrl | Enable humidity probe control delay for alarm activation | Write | 0/1 | |
| BV | 305 | ZoneData_S.Z_FctsCfg.RackEnLogic | Enable zone production digital input (RACKEN) status | Write | 0 = contact closed, 1 = contact open | |
| BV | 306 | ZoneData_S.Z_FctsCfg.AirFlowSwitchLogic | Flow switch digital input (FLUX) status | Write | 0 = contact closed, 1 = contact open | |
| BV | 307 | ZoneData_S.Z_FctsCfg.ZoneStatusDout_Logic | "Zone status" ZONE digital output logic | Write | 0 = NC, 1 = NO | |
| BV | 308 | ZoneData_S.Z_FctsCfg.AlrmDOutLogic | "Alarm status" AL digital output logic | Write | 0 = NC, 1 = NO | |
| BV | 309 | ZoneData_S.Z_FctsCfg.RelayLogicNO7 | "Programmable relay NO7" digital output logic | Write | 0 = NC, 1 = NO | |
| BV | 310 | ZoneData_S.Z_DigIO.RackEnStatus_NoLogic | Enable zone production digital input (RACKEN) status | Read | 0 = contact closed, 1 = contact open | |
| BV | 311 | ZoneData_S.Z_DigIO.AirFlowSwitchStatus_NoLogic | Flow switch digital input (FLUX) status | Read | 0 = contact closed, 1 = contact open | |
| BV | 312 | ZoneData_S.Z_RackSteps.LineDrain | Line drain digital output (NOL) status | Read | 0 = output not energised, 1 = output energised | |
| BV | 313 | ZoneData_S.Z_DigIO.NO7_PrgDout | Programmable relay NO7 digital output status | Read | 0 = output not energised, 1 = output energised | |
| BV | 314 | ZoneData_S.Z_DigIO.Alrm_Dout | Alarm status digital input (AL) status | Read | 0 = output not energised, 1 = output energised | |
| BV | 315 | ZoneData_S.Z_RackSteps.Ventilation | Rack ventilation solenoid valve digital output (NOV) status | Read | 0 = output energised, 1 = output not energised | |
| BV | 316 | ZoneData_S.Z_FctsCfg.ZoneManModeEnFill | Enable filling function for zone manual mode | Write | 0 = disabled, 1 = enabled | |
| BV | 323 | ZoneData_S.Z_RackSteps.Step[1].Fill | Rack fill solenoid valve status - step 1 | Read | 0 = closed, 1 = open | |
| BV | 324 | ZoneData_S.Z_RackSteps.Step[2].Fill | Rack fill solenoid valve status - step 2 | Read | 0 = closed, 1 = open | |
| BV | 325 | ZoneData_S.Z_RackSteps.Step[3].Fill | Rack fill solenoid valve status - step 3 | Read | 0 = closed, 1 = open | |
| BV | 326 | ZoneData_S.Z_RackSteps.Step[4].Fill | Rack fill solenoid valve status - step 4 | Read | 0 = closed, 1 = open | |
| BV | 327 | ZoneData_S.Z_RackSteps.Step[5].Fill | Rack fill solenoid valve status - step 5 | Read | 0 = closed, 1 = open | |
| BV | 328 | ZoneData_S.Z_RackSteps.Step[6].Fill | Rack fill solenoid valve status - step 6 | Read | 0 = closed, 1 = open | |
| BV | 329 | ZoneData_S.Z_RackSteps.Step[1].Drain | Rack drain solenoid valve status - step 1 | Read | 0 = closed, 1 = open | |
| BV | 330 | ZoneData_S.Z_RackSteps.Step[2].Drain | Rack drain solenoid valve status - step 2 | Read | 0 = closed, 1 = open | |
| BV | 331 | ZoneData_S.Z_RackSteps.Step[3].Drain | Rack drain solenoid valve status - step 3 | Read | 0 = closed, 1 = open | |
| BV | 332 | ZoneData_S.Z_RackSteps.Step[4].Drain | Rack drain solenoid valve status - step 4 | Read | 0 = closed, 1 = open | |
| BV | 333 | ZoneData_S.Z_RackSteps.Step[5].Drain | Rack drain solenoid valve status - step 5 | Read | 0 = closed, 1 = open | |
| BV | 334 | ZoneData_S.Z_RackSteps.Step[6].Drain | Rack drain solenoid valve status - step 6 | Read | 0 = closed, 1 = open | |
| BV | 341 | ZoneData_S.Z_Alrms.Alrm_MainPrb | ALA01 - Zone alarm: main probe broken or disconnected | Read | 0/1 | |
| BV | 342 | ZoneData_S.Z_Alrms.Alrm_LimitPrb | ALA02 - Zone alarm: limit probe broken or disconnected | Read | 0/1 | |
| BV | 343 | ZoneData_S.Z_Alrms.Alrm_NoRack | ABC02 - Zone alarm: distribution system not configured | Read | 0/1 | |
| BV | 344 | ZoneData_S.Z_Alrms.Alrm_MasterOffline | ABO01 - Zone alarm: pumping station offline | Read | 0/1 | |
| BV | 345 | ZoneData_S.Z_Alrms.Alrm_RackTPrb | ABA06 - Zone alarm: rack temperature probe broken or disconnected | Read | 0/1 | |
| BV | 346 | ZoneData_S.Z_Alrms.Warn_LowRackTemp | WRA10 - Zone warning: low rack temperature | Read | 0/1 | |
| BV | 347 | ZoneData_S.Z_Alrms.Warn_HighHumMainPrb | WRA11 - Zone warning: high humidity measured by main probe | Read | 0/1 | |
| BV | 348 | ZoneData_S.Z_Alrms.Warn_LowHumMainPrb | WRA12 - Zone warning: low humidity measured by main probe | Read | 0/1 | |
| BV | 349 | ZoneData_S.Z_Alrms.Warn_HighTempMainPrb | WRA13 - Zone warning: high temperature measured by main probe | Read | 0/1 | |
| BV | 350 | ZoneData_S.Z_Alrms.Warn_LowTempMainPrb | WRA14 - Zone warning: low temperature measured by main probe | Read | 0/1 | |
| BV | 351 | ZoneData_S.Z_Alrms.Warn_HighHumLimPrb | WRA15 - Zone warning: high humidity measured by limit probe | Read | 0/1 | |
| BV | 352 | ZoneData_S.Z_Alrms.Warn_LowTempLimPrb | WRA16 - Zone warning: low humidity measured by limit probe | Read | 0/1 | |
| BV | 353 | ZoneData_S.Z_Alrms.Warn_HighHumTwoPrbsAvg | WRA17 - Zone warning: high humidity measured by average of 2 probes | Read | 0/1 | |
| BV | 354 | ZoneData_S.Z_Alrms.Warn_LowHumTwoPrbsAvg | WRA18 - Zone warning: low humidity measured by average of 2 probes | Read | 0/1 | |
| BV | 355 | ZoneData_S.Z_Alrms.Warn_HighTempTwoPrbsAvg | WRA19 - Zone warning: high temperature measured by average of 2 probes | Read | 0/1 | |
| BV | 356 | ZoneData_S.Z_Alrms.Warn_LowTempTwoPrbsAvg | WRA20 - Zone warning: low temperature measured by average of 2 probes | Read | 0/1 | |
| BV | 357 | ZoneData_S.Z_Alrms.Warn_HighHumThreePrbsAvg | WRA21 - Zone warning: high humidity measured by average of 3 probes | Read | 0/1 | |
| BV | 358 | ZoneData_S.Z_Alrms.Warn_LowHumThreePrbsAvg | WRA22 - Zone warning: low humidity measured by average of 3 probes | Read | 0/1 | |
| BV | 359 | ZoneData_S.Z_Alrms.Warn_HighTempThreePrbsAvg | WRA23 - Zone warning: high temperature measured by average of 3 probes | Read | 0/1 | |
| BV | 360 | ZoneData_S.Z_Alrms.Warn_LowTempThreePrbsAvg | WRA24 - Zone warning: low temperature measured by average of 3 probes | Read | 0/1 | |
| BV | 361 | ZoneData_S.Z_Alrms.Warn_SVOffline | WRO05 - Zone warning: supervisor offline | Read | 0/1 | |
| BV | 362 | ZoneData_S.Z_Alrms.Alrm_SVOffline | WRO09 - Zone alarm: supervisor offline | Read | 0/1 | |
| BV | 363 | ZoneData_S.Z_Alrms.Alrm_Retain | ALG01 - Zone alarm: error in number of retain memory writes | Read | 0/1 | |
| BV | 364 | ZoneData_S.Z_Alrms.Alrm_Err_retain_write | ALG02 - Zone alarm: too many retain memory writes | Read | 0/1 | |
| BV | 365 | ZoneData_S.Z_Alrms.Warn_RetMem | WRG03 - Zone warning: too many retain memory writes | Read | 0/1 | |
| BV | 366 | ZoneData_S.Z_Alrms.Alrm_NoModel | ABC01 - Zone alarm: no model configured | Read | 0/1 | |
| BV | 367 | ZoneData_S.Z_WorkPar.UnitPause | Unit setting paused | Write | 0=not paused; 1=paused | |
| BV | 368 | ZoneData_S.Z_WorkPar.DisableVarUnitPause | Disable pause from monitoring service | Read | 0: pause not disabled, 1: pause disabled | |
| BVmin | 369 | ZoneData_S.Z_Info.ZoneAlrmPresent | At least 1 alarm active in zone | Read | 0/1 | |
| BVmin | 370 | ZoneData_S.Z_Info.ZoneWarning | At least 1 warning active in zone | Read | 0/1 | |
| BVmin | 371 | ZoneData_S.Z_WorkPar.SVEnReg | Enable zone control from supervisor | Write | 0/1 | |
| BVmin | 372 | ZoneData_S.Z_WorkPar.SVEnOnOff | Enable zone on/off from supervisor | Write | 0/1 | |
| BVmin | 373 | ZoneData_S.Z_WorkPar.SVOnOff | Zone on/off from supervisor | Write | 0/1 | |
| BV | 374 | ZoneData_S.Z_RackCfg.EnRotSteps | Zone step rotation delay | Write | 0/1 | |
| BV | 375 | EnMultiNet | Enabling of the multi-network | Write | 0/1 | |
| PIVmin | 300 | ZoneData_S.Z_Info.ZoneStatus | Zone status | Read | 0=Power On, 10=Software initialisation, 20=Awaiting network, 30=Wash, 40=Fill, 50=Standby empty, 60=Standby full, 70=Water control, 80=Production, 90=Slowdown, 100=Pre-wash, 110=Alarm, 120=Bypass calibration fill, 130=Bypass calibration, 140=Waiting for control, 150=WTS water change, 160=Disabled | |
| PIV | 301 | ZoneData_S.Z_Reg.RegTyp | Control mode | Write | 0=on/off, 1=on/off + humidity limit, 2=on/off + temperature limit, 3=external signal, 4=external signal + humidity limit, 5=external signal + temperature limit, 6=humidity, 7=humidity + limit humidity, 8=humidity + temperature limit, 9=temperature, 10=temperature + temperature limit, 11=temperature + humidity limit, 12=2 humidity probes, 13=2 temperature probes, 14=3 humidity probes, 15=3 temperature probes, 16=2 temperature probes + humidity limit, 17=dewpoint, 18=dewpoint + humidity limit | |
| PIV | 302 | ZoneData_S.Z_SysInfo.SwVer.X | Software version X (Major) | Read | ||
| PIV | 303 | ZoneData_S.Z_SysInfo.SwVer.Y | Operating system version Y (Minor) | Read | ||
| PIV | 304 | ZoneData_S.Z_SysInfo.SwVer.Z | Software version Z (Patch) | Read | ||
| PIV | 305 | ZoneData_S.Z_SysInfo.OSVer.X | Operating system version X (Major) | Read | ||
| PIV | 306 | ZoneData_S.Z_SysInfo.OSVer.Y | Operating system version Y (Minor) | Read | ||
| PIV | 307 | ZoneData_S.Z_SysInfo.OSVer.Z | Operating system version Z (Patch) | Read | ||
| PIV | 308 | ZoneData_S.Z_SysInfo.CoreType | c.pCO core version | Read | ||
| PIV | 309 | ZoneData_S.Z_SysInfo.UnitModel | Unit model | Read | ||
| PIV | 310 | ZoneData_S.Z_PrbCfg.RackTPrb.UITyp | Select rack temperature probe type | Write | 0 = 0-1 V, 1 = 0-10 V, 2 = 2-10 V, 3 = 0-20 mA, 4 = 4-20 mA, 5 = NTC | |
| PIV | 311 | ZoneData_S.Z_FctsCfg.HumPrbAlrmCtrlDel | Enable control probe alarm delay at start of production | min | Write | 0 = disabled, 1 = enabled |
| PIV | 312 | ZoneData_S.Z_FctsCfg.FunctSelNO7_Slv | Select programmable relay NO7 function | Write | 0 = Unit life status, 1 = Low rack temperature warning | |
| PIV | 314 | ZoneData_S.Z_Info.ZoneManModeWait | Zone manual mode activation status | Read | 0=manual mode available, 1=waiting for wash to finish, 2=waiting for fill to finish, 3=waiting for production to finish | |
| PIV | 332 | ZoneData_S.Z_FctsCfg.PrbThrshsWarnDly | High/low humidity/temperature alarm delay | min | Write | |
| PIV | 333 | ZoneData_S.Z_Info.IPConfig[2] | Zone IP address | Read | ||
| PIV | 334 | UoM_SV | Unit of measure | Write | 2: Imperial system, 6: International system | |
| PIV | 335 | ZoneData_S.Z_Info.OnOffStatus | Reserved | Read | ||
| PIV | 336 | ZoneData_S.Z_RackCfg.RotStepsT | Zone step rotation delay | min | Write | |
| PIV | 337 | NetNum | Network number for multi-network | Write |
No points match these filters.
Object ID lookup: CAREL humiFog Multizone zone controller point IDs by name
AV300ZoneData_S.Z_Info.FlowReqAV301ZoneData_S.Z_Info.CurrProdAV302ZoneData_S.Z_Info.RealReqAV303ZoneData_S.Z_Info.MainPrbAV304ZoneData_S.Z_Info.LimitPrbAV305ZoneData_S.Z_Info.RackTPrbAV306ZoneData_S.Z_WorkPar.GlbSetP_HumAV307ZoneData_S.Z_WorkPar.GlbSetP_TempAV308ZoneData_S.Z_WorkPar.GlbSetPLim_HumAV309ZoneData_S.Z_WorkPar.GlbSetPLim_TempAV310ZoneData_S.Z_Reg.RackMaxProdAV311ZoneData_S.Z_RackCfg.RackFlowRateAV312ZoneData_S.Z_FctsCfg.PressReliefT[1]AV313ZoneData_S.Z_FctsCfg.PressReliefT[2]AV314ZoneData_S.Z_FctsCfg.PressReliefT[3]AV315ZoneData_S.Z_FctsCfg.PressReliefT[4]AV316ZoneData_S.Z_FctsCfg.PressReliefT[5]AV317ZoneData_S.Z_FctsCfg.PressReliefT[6]AV318ZoneData_S.Z_PrbCfg.RackTPrb.Mi_TempAV319ZoneData_S.Z_PrbCfg.RackTPrb.Ma_TempAV320ZoneData_S.Z_PrbCfg.RackTPrb.OffsAV321ZoneData_S.Z_FctsCfg.RackTempMng.RackTSetPAV322ZoneData_S.Z_FctsCfg.RackTempMng.RackTBandAV323ZoneData_S.Z_FctsCfg.RackTempMng.RackTDiffAV325ZoneData_S.Z_FctsCfg.HighMainHum_WarnThrshAV326ZoneData_S.Z_FctsCfg.HighMainTemp_WarnThrshAV327ZoneData_S.Z_FctsCfg.LowMainHum_WarnThrshAV328ZoneData_S.Z_FctsCfg.LowMainTemp_WarnThrshAV329ZoneData_S.Z_FctsCfg.HighLimitHum_WarnThrshAV330ZoneData_S.Z_FctsCfg.LowLimitTemp_WarnThrshAV331ZoneData_S.Z_WorkPar.SVReqAV332ZoneData_S.Z_Info.TempDewPointAV333ZoneData_S.Z_Info.TwoPrbsAvgAV334ZoneData_S.Z_Info.ThreePrbsAvgBV301ZoneData_S.Z_FctsCfg.RackTempMng.EnRackTMngBV302ZoneData_S.Z_FctsCfg.RackTempMng.EnRackTReducedProdBV303ZoneData_S.Z_FctsCfg.RackTempMng.EnRackTWarnBV304ZoneData_S.Z_FctsCfg.EnDlydHumPrbAlrmCtrlBV305ZoneData_S.Z_FctsCfg.RackEnLogicBV306ZoneData_S.Z_FctsCfg.AirFlowSwitchLogicBV307ZoneData_S.Z_FctsCfg.ZoneStatusDout_LogicBV308ZoneData_S.Z_FctsCfg.AlrmDOutLogicBV309ZoneData_S.Z_FctsCfg.RelayLogicNO7BV310ZoneData_S.Z_DigIO.RackEnStatus_NoLogicBV311ZoneData_S.Z_DigIO.AirFlowSwitchStatus_NoLogicBV312ZoneData_S.Z_RackSteps.LineDrainBV313ZoneData_S.Z_DigIO.NO7_PrgDoutBV314ZoneData_S.Z_DigIO.Alrm_DoutBV315ZoneData_S.Z_RackSteps.VentilationBV316ZoneData_S.Z_FctsCfg.ZoneManModeEnFillBV323ZoneData_S.Z_RackSteps.Step[1].FillBV324ZoneData_S.Z_RackSteps.Step[2].FillBV325ZoneData_S.Z_RackSteps.Step[3].FillBV326ZoneData_S.Z_RackSteps.Step[4].FillBV327ZoneData_S.Z_RackSteps.Step[5].FillBV328ZoneData_S.Z_RackSteps.Step[6].FillBV329ZoneData_S.Z_RackSteps.Step[1].DrainBV330ZoneData_S.Z_RackSteps.Step[2].DrainBV331ZoneData_S.Z_RackSteps.Step[3].DrainBV332ZoneData_S.Z_RackSteps.Step[4].DrainBV333ZoneData_S.Z_RackSteps.Step[5].DrainBV334ZoneData_S.Z_RackSteps.Step[6].DrainBV341ZoneData_S.Z_Alrms.Alrm_MainPrbBV342ZoneData_S.Z_Alrms.Alrm_LimitPrbBV343ZoneData_S.Z_Alrms.Alrm_NoRackBV344ZoneData_S.Z_Alrms.Alrm_MasterOfflineBV345ZoneData_S.Z_Alrms.Alrm_RackTPrbBV346ZoneData_S.Z_Alrms.Warn_LowRackTempBV347ZoneData_S.Z_Alrms.Warn_HighHumMainPrbBV348ZoneData_S.Z_Alrms.Warn_LowHumMainPrbBV349ZoneData_S.Z_Alrms.Warn_HighTempMainPrbBV350ZoneData_S.Z_Alrms.Warn_LowTempMainPrbBV351ZoneData_S.Z_Alrms.Warn_HighHumLimPrbBV352ZoneData_S.Z_Alrms.Warn_LowTempLimPrbBV353ZoneData_S.Z_Alrms.Warn_HighHumTwoPrbsAvgBV354ZoneData_S.Z_Alrms.Warn_LowHumTwoPrbsAvgBV355ZoneData_S.Z_Alrms.Warn_HighTempTwoPrbsAvgBV356ZoneData_S.Z_Alrms.Warn_LowTempTwoPrbsAvgBV357ZoneData_S.Z_Alrms.Warn_HighHumThreePrbsAvgBV358ZoneData_S.Z_Alrms.Warn_LowHumThreePrbsAvgBV359ZoneData_S.Z_Alrms.Warn_HighTempThreePrbsAvgBV360ZoneData_S.Z_Alrms.Warn_LowTempThreePrbsAvgBV361ZoneData_S.Z_Alrms.Warn_SVOfflineBV362ZoneData_S.Z_Alrms.Alrm_SVOfflineBV363ZoneData_S.Z_Alrms.Alrm_RetainBV364ZoneData_S.Z_Alrms.Alrm_Err_retain_writeBV365ZoneData_S.Z_Alrms.Warn_RetMemBV366ZoneData_S.Z_Alrms.Alrm_NoModelBV367ZoneData_S.Z_WorkPar.UnitPauseBV368ZoneData_S.Z_WorkPar.DisableVarUnitPauseBV369ZoneData_S.Z_Info.ZoneAlrmPresentBV370ZoneData_S.Z_Info.ZoneWarningBV371ZoneData_S.Z_WorkPar.SVEnRegBV372ZoneData_S.Z_WorkPar.SVEnOnOffBV373ZoneData_S.Z_WorkPar.SVOnOffBV374ZoneData_S.Z_RackCfg.EnRotStepsBV375EnMultiNetPIV300ZoneData_S.Z_Info.ZoneStatusPIV301ZoneData_S.Z_Reg.RegTypPIV302ZoneData_S.Z_SysInfo.SwVer.XPIV303ZoneData_S.Z_SysInfo.SwVer.YPIV304ZoneData_S.Z_SysInfo.SwVer.ZPIV305ZoneData_S.Z_SysInfo.OSVer.XPIV306ZoneData_S.Z_SysInfo.OSVer.YPIV307ZoneData_S.Z_SysInfo.OSVer.ZPIV308ZoneData_S.Z_SysInfo.CoreTypePIV309ZoneData_S.Z_SysInfo.UnitModelPIV310ZoneData_S.Z_PrbCfg.RackTPrb.UITypPIV311ZoneData_S.Z_FctsCfg.HumPrbAlrmCtrlDelPIV312ZoneData_S.Z_FctsCfg.FunctSelNO7_SlvPIV314ZoneData_S.Z_Info.ZoneManModeWaitPIV332ZoneData_S.Z_FctsCfg.PrbThrshsWarnDlyPIV333ZoneData_S.Z_Info.IPConfig[2]PIV334UoM_SVPIV335ZoneData_S.Z_Info.OnOffStatusPIV336ZoneData_S.Z_RackCfg.RotStepsTPIV337NetNum
Integration notes
- When connected to a zone controller, only that zone's variables are available and addresses always start at 300 (ZoneData_S structure).
- Object type follows the data type column (Real = AV, Bool = BV, integers = PIV). Values are scaled 0.1 where the UoM column says 0.1.
- The Multizone (+0300115EN) and Touch Oil-free (+0300127EN) manuals print the same zone tables.
- Rows printed with access 'OR' are read-only. Units switch between metric and imperial with UoM_SV.
- Source: +0300116EN rel. 1.3 section 9.4.4-9.4.6, pages 92-94 (117 objects).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller
How many BACnet points does the CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller have?
This list has 117 BACnet objects: 34 analog values, 63 binary values, 20 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller BACnet points are writable?
48 of the 117 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller BACnet documentation?
The source is humiFog Multizone Touch pumping station and zone panel - Commissioning manual (+0300116EN rel. 1.3), revision 2025-10-28, published free by CAREL at https://www.carel.com/documents/10191/0/%2B0300116EN/1990b09e-81eb-47c9-b022-bf575f96bb0f?version=1.3.
What are the minimum BACnet points to integrate the CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller?
Start with BV 372 ZoneData_S.Z_WorkPar.SVEnOnOff (Enable zone on/off from supervisor); BV 371 ZoneData_S.Z_WorkPar.SVEnReg (Enable zone control from supervisor); BV 373 ZoneData_S.Z_WorkPar.SVOnOff (Zone on/off from supervisor); AV 306 ZoneData_S.Z_WorkPar.GlbSetP_Hum (Zone humidity set point, %rh); AV 331 ZoneData_S.Z_WorkPar.SVReq (Production request from supervisor, %); PIV 300 ZoneData_S.Z_Info.ZoneStatus (Zone status code); AV 301 ZoneData_S.Z_Info.CurrProd (Current zone production); AV 303 ZoneData_S.Z_Info.MainPrb (Main probe reading); BV 369 ZoneData_S.Z_Info.ZoneAlrmPresent (Any zone alarm active); BV 370 ZoneData_S.Z_Info.ZoneWarning (Any zone warning active).
How do I enable BMS control of the CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller?
SVEnOnOff enables zone on/off from the supervisor and SVEnReg enables zone control from the supervisor; then SVOnOff switches the zone.
Does the CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller need a BACnet heartbeat or have a communication timeout?
Zone warning and alarm objects report a supervisor offline condition (WRO05 / WRO09).
Can the BMS supply sensor values to the CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller?
SVReq (AV 331) is the zone production request from the supervisor, used when the zone control mode takes an external request.
How do I check these points on the real humiFog Multizone / Multizone Touch / Touch Oil-free - zone controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More CAREL BACnet points lists
- Gas-fired steam humidifier
CAREL gaSteam (UG) gas-fired humidifier
CAREL gaSteam UG gas-fired isothermal steam humidifiers (indoor and outdoor versions, single unit or Main/Secondary pairs).
Also known as: gaSteam, UG, UG045, UG090, UG180, CAREL gas-fired steam humidifier, +0300122EN - Electric resistance steam humidifier
CAREL heaterSteam 4 (UR) process / titanium
CAREL heaterSteam UR electric heater steam humidifiers (process and titanium versions) with the c.pHC-based controller, manual +0300087EN.
Also known as: heaterSteam, heaterSteam 4, heaterSteam process, heaterSteam titanium, UR, URH, CAREL electric resistance humidifier, +0300087EN - Electric resistance steam humidifier
CAREL heaterSteam UR (2018 manual, before heaterSteam 4)
CAREL heaterSteam UR electric heater steam humidifiers of the generation before heaterSteam 4, as covered by manual +0300080EN rel. 1.4 (2018).
Also known as: heaterSteam, heaterSteam UR, UR002, UR080, CAREL resistance steam humidifier, +0300080EN - High-pressure atomising humidifier (direct room)
CAREL humiFog direct (UA) high-pressure atomising humidifier
CAREL humiFog direct UA pumping stations with c.pHC controller, one or two humidification zones in the room.
Also known as: humiFog direct, humiFog Direct, UA, c.pHC, CAREL humiFog, +0300073EN - High-pressure atomising humidifier (multizone pumping station)
CAREL humiFog Multizone / Multizone Touch / Touch Oil-free high-pressure humidifier - pumping station
CAREL humiFog Multizone, Multizone Touch and Touch Oil-free high-pressure water atomising humidifier pumping stations (c.pCO), which supervise up to 12 zones.
Also known as: humiFog Multizone, humiFog Multizone Touch, humiFog Touch Oil-free, humiFog multizone pumping station, UA multizone, c.pCO humiFog, +0300116EN, +0300115EN, +0300127EN - Air handling unit controller
CAREL k.air air handling unit controller
CAREL k.air mini and k.air large air handling unit controllers (the versions with BACnet IP and BACnet MS/TP); k.air smart is Modbus only.
Also known as: k.air, kair, k.air large, k.air mini, CAREL k.air, +030220981, CAREL AHU controller
Source: humiFog Multizone Touch pumping station and zone panel - Commissioning manual · +0300116EN rel. 1.3 · rev. 2025-10-28. Object names, instances and units are reproduced as published; descriptions are our own.