Rooftop unit / DOAS controller · BACnet points list

CaptiveAire Paragon RTU / DOAS DDC (Protocessor BACnet) BACnet points list

Updated 28 October 2026

Short answer

CaptiveAire's Paragon rooftop units and DOAS are run by the unit's own controller board; BACnet comes from a factory-mounted Protocessor gateway in the control panel, set up at the factory for either BACnet IP (Ethernet) or BACnet MS/TP (RS-485). The 300 objects cover DDC commands, occupied/unoccupied setpoints, the on-board schedule, mode selections, sensor readings, compressor/ERV data and six active fault codes. The simplest BMS control is to enable scheduling once, set the on-board schedule to unoccupied (1440) and drive BV-5 DDCOccupiedOverride.

This page lists 300 BACnet objects for the CaptiveAire Paragon RTU / DOAS DDC (Protocessor BACnet) — 194 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CaptiveAire’s own free documentation, linked below.

Manufacturer
CaptiveAire
Model
Paragon RTU / DOAS DDC (Protocessor BACnet)
Equipment
Rooftop unit / DOAS controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
300 (194 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
50001
Also known as
Paragon, CaptiveAire DOAS, CaptiveAire RTU, Protocessor, CN0861, RTU DDC Points
Source document
DDC Application Guide for Paragon HVAC Series (RTU DDC Points) · rev. 2026-09
Download CSV 300 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: CaptiveAire Paragon RTU / DOAS DDC (Protocessor BACnet)

Integration in brief

Turn on scheduling once (BV-216), set every on-board schedule slot (AV-46..87) to 1440 so the unit is always unoccupied by its own clock, then command occupancy from the BMS with BV-5. Let the unit run on its own setpoints (intake/space/discharge, chosen by the Activate Based On and Tempering Mode AVs) and monitor UnitStatus, temperatures and the six fault-code AIs. Only use the raw DDC heat/cool/blower commands if the tempering modes are set to DDC.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 5DDCOccupiedOverrideOccupied/unoccupied command from the BMSWrite
BV 216SchedulingEnabledFlagMust be on (once) for BV-5 to workWrite
AV 18SpaceCoolOccSPOccupied space cooling setpointWrite
AV 8SpaceHeatOccSPOccupied space heating setpointWrite
AI 139UnitStatusIdle / blower / heating / cooling stateRead
AI 140CurrentOccupiedStatusConfirms the occupancy command took effectRead
AI 148DischargeTempDischarge air temperatureRead
AI 141AverageSpaceTempSpace temperature the unit is controlling toRead
AI 210ActiveFault1First active fault codeRead

Enable & remote start

BMS occupancy control needs BV-216 SchedulingEnabledFlag on and all internal schedule AVs (46-87) at 1440; an occupied input always wins over unoccupied, so any non-1440 slot keeps the unit occupied regardless of BV-5. Direct heat/cool/blower commands (BV-1..3, AV-4) need the heat/cool tempering modes (AV-217..220) set to DDC (3).

Sensors & values from the BMS

A BMS space temperature can be written to AV-248 ExternalSpaceTempValue after enabling BV-247 ExternalSpaceTempEnable; space humidity likewise via BV-269 ExternalSpaceRhEnable and AV-270 ExternalSpaceRhValue. BV-280..283 act as virtual thermostat calls when Activate Based On is set to Stat (4). The Paragon IOM (A0033507 Rev 39) also lists Virtual Space Input (Temp/RH from the BMS, default Off) with an optional Input Timer (1-120 min, default 2) that falls back to the wired sensor when the BMS value goes stale.

Network setup

Watch out for

CaptiveAire Paragon RTU / DOAS DDC (Protocessor BACnet) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

300 of 300 shown
Type
Access
Show
CaptiveAire Paragon RTU / DOAS DDC (Protocessor BACnet) BACnet Points List
DescriptionStates
BV1DDCHeatCommandHeating command. Requires heat tempering mode = DDCWrite
BV2DDCCoolCommandCooling command. Requires heat tempering mode = DDCWrite
BV3DDCBlowerCommandBlower command. Requires both heat and cool tempering mode = DDCWrite
AV4DDCModulationHeat modulation signal, 0-10V. 0V = low fire and 10V = highWrite
BVmin5DDCOccupiedOverrideOccupied override command, requires SchedulingEnabled = ON (1)Write
AV6IntakeHeatOccSPIntake Heating Occupied SetpointWrite
AV7IntakeHeatUnoccSPIntake Heating Unoccupied SetpointWrite
AVmin8SpaceHeatOccSPSpace Heating Occupied SetpointWrite
AV9SpaceHeatUnoccSPSpace Heating Unoccupied SetpointWrite
AV10MinDischargeHeatOccSPMin Discharge Heating when occupied, relevant only if heat tempering mode =Write
AV11MinDischargeHeatUnoccSPMin Discharge Heating when unoccupied, relevant only if heat tempering mode =Write
AV12DischargeHeatOccSPDischarge heating setpoint when occupied, requires heat tempering mode = dischargeWrite
AV13DischargeHeatUnoccSPDischarge heating setpoint when unoccupied, requires heat tempering mode = dischargeWrite
AV14MaxDischargeHeatOccSPMax Discharge Heating when occupied, relevant only if heat tempering mode =Write
AV15MaxDischargeHeatUnoccSPMax Discharge Heating when unoccupied, relevant only if heat tempering mode =Write
AV16IntakeCoolOccSPIntake Cooling Occupied SetpointWrite
AV17IntakeCoolUnoccSPIntake Cooling Unoccupied SetpointWrite
AVmin18SpaceCoolOccSPSpace Cooling Occupied SetpointWrite
AV19SpaceCoolUnoccSPSpace Cooling Unoccupied SetpointWrite
AV20MinDischargeCoolOccSPMin Discharge Cooling setpoint when occupied, relevant only if cool tempering modeWrite
AV21MinDischargeCoolUnoccSPMin Discharge Cooling setpoint when unoccupied, relevant only if cool tempering modeWrite
AV22DischargeCoolOccSPDischarge Cooling setpoint when occupied, relevant only if cool tempering mode =Write
AV23DischargeCoolUnoccSPDischarge Cooling setpoint when unoccupied, relevant only if cool tempering mode =Write
AV24MaxDischargeCoolOccSPMax Discharge Cooling setpoint when occupied, relevant only if cool tempering modeWrite
AV25MaxDischargeCoolUnoccSPMax Discharge Cooling setpoint when unoccupied, relevant only if cool tempering modeWrite
AV26RoomOverrideOccSPRoom Override Occupied SetpointWrite
AV27RoomOverrideUnoccSPRoom Override Unoccupied SetpointWrite
AV28FirestatIntakeSPFirestat Intake SetpointWrite
AV29FirestatDischargeSPFirestat Discharge SetpointWrite
AV30FreezestatSPFreezestat SetpointWrite
AV31OverheatDischargeSPOverheat Discharge SetpointWrite
AV32CabinetHeatSPCabinet Heat SetpointWrite
AV33FurnaceDrainHeatSPFurnace Drain Heat SetpointWrite
AV34IntakeRhOccSPIntake Relative Humidity Occupied SetpointWrite
AV35IntakeRhUnoccSPIntake Relative Humidity Unoccupied SetpointWrite
AV36SpaceRhOccSPSpace Relative Humidity Occupied SetpointWrite
AV37SpaceRhUnoccSPSpace Relative Humidity Unoccupied SetpointWrite
AV38DischargeRhOccSPDischarge Relative Humidity Occupied SetpointWrite
AV39DischargeRhUnoccSPDischarge Relative Humidity Unoccupied SetpointWrite
AV40IntakeDpOccSPIntake Dewpoint Occupied SetpointWrite
AV41IntakeDpUnoccSPIntake Dewpoint Unoccupied SetpointWrite
AV42SpaceDpOccSPSpace Dewpoint Occupied SetpointWrite
AV43SpaceDpUnoccSPSpace Dewpoint Unoccupied SetpointWrite
AV44DischargeDpOccSPDischarge Dewpoint Occupied SetpointWrite
AV45DischargeDpUnoccSPDischarge Dewpoint Unoccupied SetpointWrite
AV46ScheduleSundayAStartDaily schedule start/end time in minutesWrite
AV47ScheduleSundayAEndDaily schedule start/end time in minutesWrite
AV48ScheduleSundayBStartDaily schedule start/end time in minutesWrite
AV49ScheduleSundayBEndDaily schedule start/end time in minutesWrite
AV50ScheduleSundayCStartDaily schedule start/end time in minutesWrite
AV51ScheduleSundayCEndDaily schedule start/end time in minutesWrite
AV52ScheduleMondayAStartDaily schedule start/end time in minutesWrite
AV53ScheduleMondayAEndDaily schedule start/end time in minutesWrite
AV54ScheduleMondayBStartDaily schedule start/end time in minutesWrite
AV55ScheduleMondayBEndDaily schedule start/end time in minutesWrite
AV56ScheduleMondayCStartDaily schedule start/end time in minutesWrite
AV57ScheduleMondayCEndDaily schedule start/end time in minutesWrite
AV58ScheduleTuesdayAStartDaily schedule start/end time in minutesWrite
AV59ScheduleTuesdayAEndDaily schedule start/end time in minutesWrite
AV60ScheduleTuesdayBStartDaily schedule start/end time in minutesWrite
AV61ScheduleTuesdayBEndDaily schedule start/end time in minutesWrite
AV62ScheduleTuesdayCStartDaily schedule start/end time in minutesWrite
AV63ScheduleTuesdayCEndDaily schedule start/end time in minutesWrite
AV64ScheduleWednesdayAStartDaily schedule start/end time in minutesWrite
AV65ScheduleWednesdayAEndDaily schedule start/end time in minutesWrite
AV66ScheduleWednesdayBStartDaily schedule start/end time in minutesWrite
AV67ScheduleWednesdayBEndDaily schedule start/end time in minutesWrite
AV68ScheduleWednesdayCStartDaily schedule start/end time in minutesWrite
AV69ScheduleWednesdayCEndDaily schedule start/end time in minutesWrite
AV70ScheduleThursdayAStartDaily schedule start/end time in minutesWrite
AV71ScheduleThursdayAEndDaily schedule start/end time in minutesWrite
AV72ScheduleThursdayBStartDaily schedule start/end time in minutesWrite
AV73ScheduleThursdayBEndDaily schedule start/end time in minutesWrite
AV74ScheduleThursdayCStartDaily schedule start/end time in minutesWrite
AV75ScheduleThursdayCEndDaily schedule start/end time in minutesWrite
AV76ScheduleFridayAStartDaily schedule start/end time in minutesWrite
AV77ScheduleFridayAEndDaily schedule start/end time in minutesWrite
AV78ScheduleFridayBStartDaily schedule start/end time in minutesWrite
AV79ScheduleFridayBEndDaily schedule start/end time in minutesWrite
AV80ScheduleFridayCStartDaily schedule start/end time in minutesWrite
AV81ScheduleFridayCEndDaily schedule start/end time in minutesWrite
AV82ScheduleSaturdayAStartDaily schedule start/end time in minutesWrite
AV83ScheduleSaturdayAEndDaily schedule start/end time in minutesWrite
AV84ScheduleSaturdayBStartDaily schedule start/end time in minutesWrite
AV85ScheduleSaturdayBEndDaily schedule start/end time in minutesWrite
AV86ScheduleSaturdayCStartDaily schedule start/end time in minutesWrite
AV87ScheduleSaturdayCEndDaily schedule start/end time in minutesWrite
AV88BlowerManualFreqOccVFD frequency when occupied, requires blower control = VFD manualWrite
AV89BlowerManualFreqUnoccVFD frequency when unoccupied, requires blower control = VFD manualWrite
AV90BlowerManualPwmRateOccECM speed when occupied, requires blower control = ECM manualWrite
AV91BlowerManualPwmRateUnoccECM speed when unoccupied, requires blower control = ECM manualWrite
AV92MixingBoxManualOAOccMixing Box Outdoor Air Percent during occupied times, requires mixing box modeWrite
AV93MixingBoxManualOAUnoccMixing Box Outdoor Air Percent during unoccupied times, requires mixing box modeWrite
AV94EconomizerTempSPOccEconomizer Temperature Setpoint OccupiedWrite
AV95EconomizerTempSPUnoccEconomizer Temperature Setpoint UnoccupiedWrite
AV96EconomizerTempBandOccEconomizer Temperature Band Setpoint OccupiedWrite
AV97EconomizerTempBandUnoccEconomizer Temperature Band Setpoint UnoccupiedWrite
AV98EconomizerTotalBandOccEconomizer Temperature Total Band Setpoint OccupiedWrite
AV99EconomizerTotalBandUnoccEconomizer Temperature Total Band Setpoint UnoccupiedWrite
AV100EconomizerRhSPOccEconomizer Relative Humidity Setpoint OccupiedWrite
AV101EconomizerRhSPUnoccEconomizer Relative Humidity Setpoint UnoccupiedWrite
AV102MixingBoxManualVoltsOccMixing Box damper voltage during occupied times, requires mixing box mode =Write
AV103MixingBoxManualVoltsUnoccMixing Box damper voltage during unoccupied times, requires mixing box mode =Write
AV104BlowerPsSpLowOccBlower Low Static Pressure Setting OccupiedWrite
AV105BlowerPsSpLowUnoccBlower Low Static Pressure Setting UnoccupiedWrite
AV106BlowerPsSpHighOccBlower High Static Pressure Setting OccupiedWrite
AV107BlowerPsSpHighUnoccBlower High Static Pressure Setting UnoccupiedWrite
AV108DryModeDischTempSPOccDry Mode Discharge Occupied SetpointWrite
AV109DryModeDischTempSPUnoccDry Mode Discharge Unoccupied SetpointWrite
AV110OaResetLowTempSpOutdoor Air Reset Low Temperature SetpointWrite
AV111OaResetHighTempSpOutdoor Air Reset High Temperature SetpointWrite
AV112OaResetHeatDischTempSpOutdoor Air Reset Heat Discharge Temperature SetpointWrite
AV113OaResetCoolDischTempSpOutdoor Air Reset Cool Discharge Temperature SetpointWrite
AV114OaResetHeatSpaceTempSpOutdoor Air Reset Heat Space Temperature SetpointWrite
AV115OaResetCoolSpaceTempSpOutdoor Air Reset Cool Space Temperature SetpointWrite
AV116CO2SensorPpmMinCO2 PPM level at 0VWrite
AV117CO2SensorPpmMaxCO2 PPM level at 10VWrite
AV118CO2ThresholdLimitOccCO2 sensor threshold limit for the fan/damper to operate when occupiedWrite
AV119CO2ThresholdLimitUnoccCO2 sensor threshold limit for the fan/damper to operate when unoccupiedWrite
AV120DynamicSpDiffDynamic Setpoint DifferentialWrite
AV121DynamicSpOffsetDynamic Setpoint Differential OffsetWrite
AV122DynamicSpHeatOaDynamic Setpoint Heat Outdoor AirWrite
AV123DynamicSpCoolOaDynamic Setpoint Cool Outdoor AirWrite
AV124ErvWheelSpeedEnergy Wheel Speed SettingWrite
AV125ErvExhaustFanSpeedOccEnergy Wheel Exhaust Fan Speed OccupiedWrite
AV126ErvExhaustFanSpeedUnoccEnergy Wheel Exhaust Fan Speed UnoccupiedWrite
AV127ErvExhaustLowPsSpOccEnergy Wheel Exhaust Low Pressure Setpoint OccupiedWrite
AV128ErvExhaustLowPsSpUnoccEnergy Wheel Exhaust Low Pressure Setpoint UnoccupiedWrite
AV129ErvExhaustHighPsSpOccEnergy Wheel Exhaust High Pressure Setpoint OccupiedWrite
AV130ErvExhaustHighPsSpUnoccEnergy Wheel Exhaust High Pressure Setpoint UnoccupiedWrite
AV131CO2OverrideHighLimitOccCO2 high limit setting at which fan/damper will operate occupiedWrite
AV132CO2OverrideLowLimitOccCO2 low limit setting at which fan/damper will operate occupiedWrite
AV133CO2OverrideHighLimitUnoccCO2 high limit setting at which fan/damper will operate unoccupiedWrite
AV134CO2OverrideLowLimitUnoccCO2 low limit setting at which fan/damper will operate unoccupiedWrite
AV135DryModeOASPDry Mode Outdoor Air SetpointWrite
AV136DryModeCoolSPDry Mode Cool SetpointWrite
AV137PoweredExhaustManVoltsOccPowered Exhaust PWM Setpoint OccupiedWrite
AV138PoweredExhaustManVoltsUnoccPowered Exhaust PWM Setpoint UnoccupiedWrite
AImin139UnitStatusHVAC State (Idle = 0, Blower = 1, Heating = 2, CoolingRead0=Idle, 1=Blower, 2=Heating, 3=Cooling
AImin140CurrentOccupiedStatusOccupancy status, occupied = 1, unoccupied = 0Read0=Unoccupied, 1=Occupied
AImin141AverageSpaceTempAverage Space TemperatureRead
AI142BlowerFrequencyBlower VFD FrequencyRead
AI143BlowerCurrentBlower VFD CurrentRead
AI144BlowerPowerBlower VFD PowerRead
AI145AverageRhAverage space relative humidityRead
AI146OutdoorTempOutdoor TemperatureRead
AI147ReturnTempReturn TemperatureRead
AImin148DischargeTempDischarge TemperatureRead
AI149IntakeTempIntake TemperatureRead
AI150SpaceTempSpace Temperature (thermistor)Read
AI151Hmi1TempUnit HMI temperatureRead
AI152Hmi2TempRemote HMI 1 TemperatureRead
AI153Hmi3TempRemote HMI 2 TemperatureRead
AI154Hmi4TempRemote HMI 3 TemperatureRead
AI155Hmi5TempRemote HMI 4 TemperatureRead
AI156SuctionLineTempSuction Line TemperatureRead
AI157LiquidLineTempLiquid Line TemperatureRead
AI158EvapIndoorCoilTempEvaporator TemperatureRead
AI159CondOutdoorCoilTempCondenser TemperatureRead
AI160CompressorDischargeTempCompressor Discharge TemperatureRead
AI161IntakeRhIntake Sensor Relative HumidityRead
AI162SpaceRhSpace Sensor Relative HumidityRead
AI163OutdoorRhOutdoor Sensor Relative HumidityRead
AI164DischargeRhDischarge Sensor Relative HumidityRead
AI165ReturnRhReturn Sensor Relative HumidityRead
AI166SuctionLinePsSuction Line PressureRead
AI167DischargeLinePsDischarge Line PressureRead
AI168LiquidLinePsLiquid Line PressureRead
AI169Hmi1RhUnit HMI Relative HumidityRead
AI170Hmi2RhRemote HMI 1 Relative HumidityRead
AI171Hmi3RhRemote HMI 2 Relative HumidityRead
AI172Hmi4RhRemote HMI 3 Relative HumidityRead
AI173Hmi5RhRemote HMI 4 Relative HumidityRead
AI174SupplyPwmRatePWM Signal to Supply FanRead
AI175ExhaustPwmRatePWM Signal to Exhaust FanRead
AI176CondFan1PwmRatePWM Signal to set #1 of Condensing FansRead
AI177CondFan2PwmRatePWM Signal to set #2 of Condensing FansRead
AI178ModulatingGasValve1OutputController output to the modulating gas valve #1. 0V = Low FireRead
AI179ModulatingGasValve2OutputController output to the modulating gas valve #2. 0V = Low FireRead
AI180AdjustableDamperOutputOutput Voltage to DamperRead
AI181ElectricHeaterOutputOutput Voltage to Electric HeaterRead
BI182OilBoostActiveFlagRead0=Oil Boost Not Active, 1=Oil Boost Active
BI183ReheatActiveFlagRead0=Reheat Not Active, 1=Reheat Active
BI184DefrostActiveFlagRead0=Defrost Not Active, 1=Defrost Active
BI185PumpdownOffActiveFlagRead0=Pumpdown Off Not Active, 1=Pumpdown Off Active
BI186PumpdownOnActiveFlagRead0=Pumpdown On Not Active, 1=Pumpdown On Active
AI187ReheatValvePositionPercentage of the Reheat Valve's PositionRead
AI188EevValvePositionPercentage of the EEV Valve's PositionRead
AI189IntakeDpActualActual Intake Dew Point ReadingRead
AI190SpaceDpActualActual Space Dew Point ReadingRead
AI191CompressorPowerCompressor Power ReadingRead
AI192CompressorFrequencyCompressor Frequency ReadingRead
AI193CompressorCurrentCompressor Current ReadingRead
AI194ERVExhaustAirRhERV Exhaust Air Relative HumidityRead
AI195ERVWheelSupplyPsInchesERV Wheel Supply Pressure DifferentialRead
AI196ERVWheelExhPsInchesERV Wheel Exhaust Pressure DifferentialRead
AI197ERVExhCtrlVolts0-10 Volt ERV Exhaust Speed ControlRead
AI198ERVExhAirTempERV Exhaust Air TemperatureRead
AI199ERVOutsideAirRhERV Outside Air Relative HumidityRead
AI200ERVOutsideAirTempERV Outside Air TemperatureRead
AI201ERVExhBlowerDutyCyclePWM Signal to Exhaust Fan ECMRead
BI202ERVExhBlowerPwmEnableRead0=Disable, 1=Enable
AI203ERVWheelDutyCyclePWM Signal to ERV Wheel ECMRead
BI204ERVWheelPwmEnableRead0=Disable, 1=Enable
AI205ERVStateRead0=Idle, 5=Defrost, 6=Clean, 7=Test, 8=Stop
AI206ERVAppliedWheelSpeedDesired Energy Wheel Fan SpeedRead
AI207ERVAppliedExhFanSpeedDesired ERV Exhaust Fan SpeedRead
AI208SubcoolSubcool ReadingsRead
AI209SuperheatSuperheat ReadingsRead
AImin210ActiveFault1Active Fault Code (see fault code table)Read
AI211ActiveFault2Active Fault Code (see fault code table)Read
AI212ActiveFault3Active Fault Code (see fault code table)Read
AI213ActiveFault4Active Fault Code (see fault code table)Read
AI214ActiveFault5Active Fault Code (see fault code table)Read
AI215ActiveFault6Active Fault Code (see fault code table)Read
BVmin216SchedulingEnabledFlagEnable scheduling. Not an occupancy command. Refer to ID 5 “DDCOccupiedOverride” toWrite
AV217HeatTemperModeOccHeat tempering mode during occupied timeWrite0=Discharge, 1=Space, 2=BAS, 3=DDC
AV218HeatTemperModeUnoccHeat tempering mode during unoccupied timeWrite0=Discharge, 1=Space, 2=BAS, 3=DDC
AV219CoolTemperModeOccCool tempering mode during occupied timeWrite0=Discharge, 1=Space, 2=BAS, 3=DDC
AV220CoolTemperModeUnoccCool tempering mode during unoccupied timeWrite0=Discharge, 1=Space, 2=BAS, 3=DDC
AV221ActivateOnOcc"Activate based on" during occupied timeWrite0=Intake, 1=Space, 2=Both, 3=Either, 4=Stat
AV222ActivateOnUnocc"Activate based on" during unoccupied timeWrite0=Intake, 1=Space, 2=Both, 3=Either, 4=Stat
AV223BlowerModeOccBlower mode during occupied timesWrite0=Auto, 1=Off, 2=On
AV224BlowerModeUnoccBlower mode during unoccupied timesWrite0=Auto, 1=Off, 2=On
AV225MixingBoxModeMixing Box mode selectionWrite0=Off, 1=Manual, 2=Position, 3=OAPercent, 4=AnalogCtrl, 5=PS, 6=100% OA
AV226ReheatDPAdjOccReheat Dew Point adjust setpoint value when occupiedWrite
AV227ReheatDPAdjUnoccReheat Dew Point adjust setpoint value when unoccupiedWrite
AV228BlowerVfdMinFreqOccMin blower VFD Frequency when occupiedWrite
AV229BlowerVfdMinFreqUnoccMin blower VFD Frequency when unoccupiedWrite
AV230BlowerVfdMaxFreqOccMax blower VFD Frequency when occupiedWrite
AV231BlowerVfdMaxFreqUnoccMax blower VFD Frequency when unoccupiedWrite
AV232BlowerPwmMinRateOccMin blower ECM speed when occupiedWrite
AV233BlowerPwmMinRateUnoccMin blower ECM speed when unoccupiedWrite
AV234BlowerPwmMaxRateOccMax blower ECM speed when occupiedWrite
AV235BlowerPwmMaxRateUnoccMax blower ECM speed when unoccupiedWrite
AV236MixingBoxMinOAPercentOccMin occupied outdoor air percent when mixing box mode = outdoor airWrite
AV237MixingBoxMinOAPercentUnoccMin unoccupied outdoor air percent when mixing box mode = outdoor airWrite
AV238MixingBoxMaxOAPercentOccMax occupied outdoor air percent when mixing box mode = outdoor airWrite
AV239MixingBoxMaxOAPercentUnoccMax unoccupied outdoor air percent when mixing box mode = outdoor airWrite
AV240MixingBoxMinVoltsOccMax unoccupied mixing box voltage when mixing box mode = manualWrite
AV241MixingBoxMinVoltsUnoccMin unoccupied mixing box voltage when mixing box mode = manualWrite
AV242MixingBoxMaxVoltsOccMax occupied mixing box voltage when mixing box mode = manualWrite
AV243MixingBoxMaxVoltsUnoccMax unoccupied mixing box voltage when mixing box mode = manualWrite
AI244CFMReadingFan CFM ReadingRead
AI245PressureSensor1Duct Static PressureRead
AI246CO2ReadingCO2 Reading in PPMRead
BV247ExternalSpaceTempEnableWrite0=Disable, 1=Enable
AV248ExternalSpaceTempValueVirtual Space Temperature Value, 1 decimalWrite
AI249Stg2CompressorPowerStage 2 Compressor Power ReadingRead
AI250Stg2CompressorFrequencyStage 2 Compressor Frequency ReadingRead
AI251Stg2CompressorCurrentStage 2 Compressor Current ReadingRead
AI252Stg3CompressorPowerStage 3 Compressor Power ReadingRead
AI253Stg3CompressorFrequencyStage 3 Compressor Frequency ReadingRead
AI254Stg3CompressorCurrentStage 3 Compressor Current ReadingRead
BI255Stg2OilBoostActiveFlagStage 2Read0=Oil Boost Not Active, 1=Oil Boost Active
BI256Stg2ReheatActiveFlagStage 2Read0=Reheat Not Active, 1=Reheat Active
BI257Stg2DefrostActiveFlagStage 2Read0=Defrost Not Active, 1=Defrost Active
BI258Stg2PumpdownOffActiveFlagStage 2Read0=Pumpdown Off Not Active, 1=Pumpdown Off Active
BI259Stg2PumpdownOnActiveFlagStage 2Read0=Pumpdown On Not Active, 1=Pumpdown On Active
AI260Stg2ReheatValvePositionStage 2 Percentage of the Reheat Valve's PositionRead
AI261Stg2EevValvePositionStage 2 Percentage of the EEV Valve's PositionRead
BI262Stg3OilBoostActiveFlagStage 3Read0=Oil Boost Not Active, 1=Oil Boost Active
AI263Stg3ReheatActiveFlagStage 3Read0=Reheat Not Active, 1=Reheat Active
AI264Stg3DefrostActiveFlagStage 3Read0=Defrost Not Active, 1=Defrost Active
AI265Stg3PumpdownOffActiveFlagStage 3Read0=Pumpdown Off Not Active, 1=Pumpdown Off Active
BI266Stg3PumpdownOnActiveFlagStage 3Read0=Pumpdown On Not Active, 1=Pumpdown On Active
AI267Stg3ReheatValvePositionStage 3 Percentage of the Reheat Valve's PositionRead
AI268Stg3EevValvePositionStage 3 Percentage of the EEV Valve's PositionRead
BV269ExternalSpaceRhEnableWrite0=Disable, 1=Enable
AV270ExternalSpaceRhValueVirtual Relative Humidity Value, 1 decimalWrite
AI271PressureSensor2Building Static PressureRead
AV272StaticOaPsLowOccSpace Static Pressure Low Setpoint when occupied for Outdoor Air Damper controlWrite
AV273StaticOaPsLowUnoccSpace Static Pressure Low Setpoint when unoccupied for Outdoor Air Damper controlWrite
AV274StaticOaPsHighOccSpace Static Pressure High Setpoint when occupied for Outdoor Air Damper controlWrite
AV275StaticOaPsHighUnoccSpace Static Pressure High Setpoint when unoccupied for Outdoor Air Damper controlWrite
AV276StaticPePsLowOccPS based Powered Exhaust control low set point when occupiedWrite
AV277StaticPePsLowUnoccPS based Powered Exhaust control low set point when unoccupiedWrite
AV278StaticPePsHighOccPS based Powered Exhaust control high set point when occupiedWrite
AV279StaticPePsHighUnoccPS based Powered Exhaust control high set point when unoccupiedWrite
BV280StatCtrlBlowerVirtual 'call for blower' for Activate On StatWrite0=Off, 1=On
BV281StatCtrlHeatVirtual 'call for heat' for Activate On StatWrite0=Off, 1=On
BV282StatCtrlCoolVirtual 'call for cool' for Activate On StatWrite0=Off, 1=On
BV283StatCtrlDehumidVirtual "call for dehumidification" for Activate On StatWrite0=Off, 1=ON
AV284CfmKFactorSet K factor for airflow calculationsWrite
AV285Hmi1TempOffsetManual temperature offset (degrees) for HMI 1Write
AV286Hmi2TempOffsetManual temperature offset (degrees) for HMI 2Write
AV287Hmi3TempOffsetManual temperature offset (degrees) for HMI 3Write
AV288Hmi4TempOffsetManual temperature offset (degrees) for HMI 4Write
AV289Hmi1RhOffsetManual relative humidity offset (percent) for HMI 1Write
AV290Hmi2RhOffsetManual relative humidity offset (percent) for HMI 2Write
AV291Hmi3RhOffsetManual relative humidity offset (percent) for HMI 3Write
AV292Hmi4RhOffsetManual relative humidity offset (percent) for HMI 4Write
AV293ReturnAsSpaceUse Return temperature as Space temperatureWrite0=Off, 1=ON
BI294FSC1GasONMain Gas Valve Status - Stage 1Read0=OFF, 1=ON
BI295FSC2GasONMain Gas Valve Status - Stage 2Read0=OFF, 1=ON
BI296EconomizerActiveEconomizer StatusRead0=Inactive, 1=Active
AV297EconomizerTargetSpOccTarget Economizer Setpoint, OccupiedWrite
AV298EconomizerTargetSpUnoccTarget Economizer Setpoint, UnoccupiedWrite
AI299OaCFMReadingCalculated Outdoor Air CFMRead
AI300ErvExhaustFanCfmReadingCalculated ERV Exhaust CFMRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Paragon RTU / DOAS DDC (Protocessor BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CaptiveAire Paragon RTU / DOAS DDC (Protocessor BACnet)

How many BACnet points does the CaptiveAire Paragon RTU / DOAS DDC (Protocessor BACnet) have?

This list has 300 BACnet objects: 89 analog inputs, 183 analog values, 17 binary inputs, 11 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CaptiveAire Paragon RTU / DOAS DDC (Protocessor BACnet) BACnet points are writable?

194 of the 300 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official CaptiveAire Paragon RTU / DOAS DDC (Protocessor BACnet) BACnet documentation?

The source is DDC Application Guide for Paragon HVAC Series (RTU DDC Points), revision 2026-09, published free by CaptiveAire at https://www.captiveaire.com/CatalogContent/Fans/RTU_DOAS/doc/rtu-ddc-guide.pdf.

What are the minimum BACnet points to integrate the CaptiveAire Paragon RTU / DOAS DDC (Protocessor BACnet)?

Start with BV 5 DDCOccupiedOverride (Occupied/unoccupied command from the BMS); BV 216 SchedulingEnabledFlag (Must be on (once) for BV-5 to work); AV 18 SpaceCoolOccSP (Occupied space cooling setpoint); AV 8 SpaceHeatOccSP (Occupied space heating setpoint); AI 139 UnitStatus (Idle / blower / heating / cooling state); AI 140 CurrentOccupiedStatus (Confirms the occupancy command took effect); AI 148 DischargeTemp (Discharge air temperature); AI 141 AverageSpaceTemp (Space temperature the unit is controlling to); AI 210 ActiveFault1 (First active fault code).

How do I enable BMS control of the CaptiveAire Paragon RTU / DOAS DDC (Protocessor BACnet)?

BMS occupancy control needs BV-216 SchedulingEnabledFlag on and all internal schedule AVs (46-87) at 1440; an occupied input always wins over unoccupied, so any non-1440 slot keeps the unit occupied regardless of BV-5. Direct heat/cool/blower commands (BV-1..3, AV-4) need the heat/cool tempering modes (AV-217..220) set to DDC (3).

Can the BMS supply sensor values to the CaptiveAire Paragon RTU / DOAS DDC (Protocessor BACnet)?

A BMS space temperature can be written to AV-248 ExternalSpaceTempValue after enabling BV-247 ExternalSpaceTempEnable; space humidity likewise via BV-269 ExternalSpaceRhEnable and AV-270 ExternalSpaceRhValue. BV-280..283 act as virtual thermostat calls when Activate Based On is set to Stat (4). The Paragon IOM (A0033507 Rev 39) also lists Virtual Space Input (Temp/RH from the BMS, default Off) with an optional Input Timer (1-120 min, default 2) that falls back to the wired sensor when the BMS value goes stale.

How do I check these points on the real Paragon RTU / DOAS DDC (Protocessor BACnet)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CaptiveAire BACnet points lists

Source: DDC Application Guide for Paragon HVAC Series (RTU DDC Points) · rev. 2026-09. Object names, instances and units are reproduced as published; descriptions are our own.