Kitchen hood demand control ventilation (DCV) controller (exhaust and make-up air fans) · BACnet points list

CaptiveAire DCV Package DDC (Protocessor BACnet) BACnet points list

Updated 28 October 2026

Short answer

CaptiveAire DCV packages start and modulate kitchen hood exhaust and supply fans from temperature, occupancy, buttons, inputs or the BMS. BACnet IP or MS/TP comes from a factory-mounted Protocessor gateway in the electrical control panel, set at the factory for one of the two. The 231 objects are mostly read-only: 32 temperature sensors, zone and HMI readings, VFD frequency/current/power/fault for up to 8 exhaust and 2 supply fans, 'fans on by' and 'lights on by' reason flags, CORE fire-system fault codes, PCU filter monitoring and per-zone faults. Ten writable BVs carry the names of the panel's Prep Time, Fans On, Wash, Lights and Max Air buttons for two zones.

This page lists 231 BACnet objects for the CaptiveAire DCV Package DDC (Protocessor BACnet) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CaptiveAire’s own free documentation, linked below.

Manufacturer
CaptiveAire
Model
DCV Package DDC (Protocessor BACnet)
Equipment
Kitchen hood demand control ventilation (DCV) controller (exhaust and make-up air fans)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
231 (10 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
50000
Also known as
CaptiveAire DCV, Demand Control Ventilation, DCV Packages Network, Kitchen hood DCV, CASlink, Protocessor, CN0861
Source document
Direct Digital Controls (DDC) Application Guide: Demand Control Ventilation (DCV) Packages Network
Download CSV 231 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: CaptiveAire DCV Package DDC (Protocessor BACnet)

Integration in brief

Most DCV integrations are monitoring: map the zone temperatures, the fan VFD readings, the fans-on-by-BMS flags and the fire, fault and Modbus fault points. The only writable objects are the per-zone button BVs (Prep Time, Fans On, Wash, Lights, Max Air); the guide does not describe their behaviour, so test a write and watch the matching Zone-FansONbyBMS / LightsONbyBMS flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 223FansONButtonZone1Zone 1 fans button; write effect not described in guideWrite
BI 94Zone1-FansONbyBMSConfirms zone 1 fans are on by BMS commandRead
AI 33Temperature Zone 1Zone 1 temperature, °FRead
AI 48VFD Frequency Exhaust 1Exhaust fan 1 drive speed, HzRead
AI 56VFD Frequency Supply 1Supply (make-up air) fan 1 drive speed, HzRead
BI 189DCVFireZone1Fire system tripped, zone 1Read
AI 78VFD Fault Exhaust 1Exhaust fan 1 drive faultRead
AI 132ErrorCOREBoard1Fire system fault code; highest-priority fault shownRead
AI 221ModbusFaultCodeModbus fault code; codes not listed in the guideRead

Network setup

Watch out for

CaptiveAire DCV Package DDC (Protocessor BACnet) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

231 of 231 shown
Type
Analog
Access
Show
CaptiveAire DCV Package DDC (Protocessor BACnet) BACnet Points List
DescriptionStates
AI1Temperature Sensor 1Temperature sensor 1 reading°FRead
AI2Temperature Sensor 2Temperature sensor 2 reading°FRead
AI3Temperature Sensor 3Temperature sensor 3 reading°FRead
AI4Temperature Sensor 4Temperature sensor 4 reading°FRead
AI5Temperature Sensor 5Temperature sensor 5 reading°FRead
AI6Temperature Sensor 6Temperature sensor 6 reading°FRead
AI7Temperature Sensor 7Temperature sensor 7 reading°FRead
AI8Temperature Sensor 8Temperature sensor 8 reading°FRead
AI9Temperature Sensor 9Temperature sensor 9 reading°FRead
AI10Temperature Sensor 10Temperature sensor 10 reading°FRead
AI11Temperature Sensor 11Temperature sensor 11 reading°FRead
AI12Temperature Sensor 12Temperature sensor 12 reading°FRead
AI13Temperature Sensor 13Temperature sensor 13 reading°FRead
AI14Temperature Sensor 14Temperature sensor 14 reading°FRead
AI15Temperature Sensor 15Temperature sensor 15 reading°FRead
AI16Temperature Sensor 16Temperature sensor 16 reading°FRead
AI17Temperature Sensor 17Temperature sensor 17 reading°FRead
AI18Temperature Sensor 18Temperature sensor 18 reading°FRead
AI19Temperature Sensor 19Temperature sensor 19 reading°FRead
AI20Temperature Sensor 20Temperature sensor 20 reading°FRead
AI21Temperature Sensor 21Temperature sensor 21 reading°FRead
AI22Temperature Sensor 22Temperature sensor 22 reading°FRead
AI23Temperature Sensor 23Temperature sensor 23 reading°FRead
AI24Temperature Sensor 24Temperature sensor 24 reading°FRead
AI25Temperature Sensor 25Temperature sensor 25 reading°FRead
AI26Temperature Sensor 26Temperature sensor 26 reading°FRead
AI27Temperature Sensor 27Temperature sensor 27 reading°FRead
AI28Temperature Sensor 28Temperature sensor 28 reading°FRead
AI29Temperature Sensor 29Temperature sensor 29 reading°FRead
AI30Temperature Sensor 30Temperature sensor 30 reading°FRead
AI31Temperature Sensor 31Temperature sensor 31 reading°FRead
AI32Temperature Sensor 32Temperature sensor 32 reading°FRead
AImin33Temperature Zone 1Zone 1 temperature°FRead
AI34Temperature Zone 2Zone 2 temperature°FRead
AI35Temperature HMI 1Temperature at HMI 1°FRead
AI36Temperature HMI 2Temperature at HMI 2°FRead
AI37Temperature HMI 3Temperature at HMI 3°FRead
AI38Temperature HMI 4Temperature at HMI 4°FRead
AI39Humidity HMI 1Relative humidity at HMI 1Read
AI40Humidity HMI 2Relative humidity at HMI 2Read
AI41Humidity HMI 3Relative humidity at HMI 3Read
AI42Humidity HMI 4Relative humidity at HMI 4Read
AI43ECMOutput1ECM fan output 1Read
AI44ECMOutput2ECM fan output 2Read
AI45ECMOutput3ECM fan output 3Read
AI46ECMOutput4ECM fan output 4Read
AI47VDCOutputDC voltage output valueRead
AImin48VFD Frequency Exhaust 1Exhaust fan 1 drive frequencyHzRead
AI49VFD Frequency Exhaust 2Exhaust fan 2 drive frequencyHzRead
AI50VFD Frequency Exhaust 3Exhaust fan 3 drive frequencyHzRead
AI51VFD Frequency Exhaust 4Exhaust fan 4 drive frequencyHzRead
AI52VFD Frequency Exhaust 5Exhaust fan 5 drive frequencyHzRead
AI53VFD Frequency Exhaust 6Exhaust fan 6 drive frequencyHzRead
AI54VFD Frequency Exhaust 7Exhaust fan 7 drive frequencyHzRead
AI55VFD Frequency Exhaust 8Exhaust fan 8 drive frequencyHzRead
AImin56VFD Frequency Supply 1Supply fan 1 drive frequencyHzRead
AI57VFD Frequency Supply 2Supply fan 2 drive frequencyHzRead
AI58VFD Amperage Exhaust 1Exhaust fan 1 drive currentARead
AI59VFD Amperage Exhaust 2Exhaust fan 2 drive currentARead
AI60VFD Amperage Exhaust 3Exhaust fan 3 drive currentARead
AI61VFD Amperage Exhaust 4Exhaust fan 4 drive currentARead
AI62VFD Amperage Exhaust 5Exhaust fan 5 drive currentARead
AI63VFD Amperage Exhaust 6Exhaust fan 6 drive currentARead
AI64VFD Amperage Exhaust 7Exhaust fan 7 drive currentARead
AI65VFD Amperage Exhaust 8Exhaust fan 8 drive currentARead
AI66VFD Amperage Supply 1Supply fan 1 drive currentARead
AI67VFD Amperage Supply 2Supply fan 2 drive currentARead
AI68VFD Power Usage Exhaust 1Exhaust fan 1 drive powerkWRead
AI69VFD Power Usage Exhaust 2Exhaust fan 2 drive powerkWRead
AI70VFD Power Usage Exhaust 3Exhaust fan 3 drive powerkWRead
AI71VFD Power Usage Exhaust 4Exhaust fan 4 drive powerkWRead
AI72VFD Power Usage Exhaust 5Exhaust fan 5 drive powerkWRead
AI73VFD Power Usage Exhaust 6Exhaust fan 6 drive powerkWRead
AI74VFD Power Usage Exhaust 7Exhaust fan 7 drive powerkWRead
AI75VFD Power Usage Exhaust 8Exhaust fan 8 drive powerkWRead
AI76VFD Power Usage Supply 1Supply fan 1 drive powerkWRead
AI77VFD Power Usage Supply 2Supply fan 2 drive powerkWRead
AImin78VFD Fault Exhaust 1Exhaust fan 1 drive fault valueRead
AI79VFD Fault Exhaust 2Exhaust fan 2 drive fault valueRead
AI80VFD Fault Exhaust 3Exhaust fan 3 drive fault valueRead
AI81VFD Fault Exhaust 4Exhaust fan 4 drive fault valueRead
AI82VFD Fault Exhaust 5Exhaust fan 5 drive fault valueRead
AI83VFD Fault Exhaust 6Exhaust fan 6 drive fault valueRead
AI84VFD Fault Exhaust 7Exhaust fan 7 drive fault valueRead
AI85VFD Fault Exhaust 8Exhaust fan 8 drive fault valueRead
AI86VFD Fault Supply 1Supply fan 1 drive fault valueRead
AI87VFD Fault Supply 2Supply fan 2 drive fault valueRead
BI88Zone1-FansONbyProvingZone 1 fans on by fan provingRead
BI89Zone1-FansONbyBypassZone 1 fans on by bypassRead
BI90Zone1-FansONbyIO1HighSpeedZone 1 fans on by IO1 high-speed inputRead
BI91Zone1-FansONbyMaxAirZone 1 fans on by Max AirRead
BI92Zone1-FansONbyTemperatureZone 1 fans on by temperatureRead
BI93Zone1-FansONbyOccupancyZone 1 fans on by occupied scheduleRead
BImin94Zone1-FansONbyBMSZone 1 fans on by BMS commandRead
BI95Zone1-FansONbyIO1Zone 1 fans on by IO1 inputRead
BI96Zone1-FansONbyButtonZone 1 fans on by panel buttonRead
BI97Zone1-FansONbyHRCZone 1 fans on by HRCRead
BI98Zone1-FansONbyWashZone 1 fans on by washRead
BI99Zone1-FansONbyBMSPrepZone 1 fans on by BMS prep timeRead
BI100Zone1-FansONbyButtonPrepZone 1 fans on by button prep timeRead
BI101Zone1-FansONbyTemperaturePrepZone 1 fans on by temperature prep timeRead
BI102Zone2-FansONbyProvingZone 2 fans on by fan provingRead
BI103Zone2-FansONbyBypassZone 2 fans on by bypassRead
BI104Zone2-FansONbyIO1HighSpeedZone 2 fans on by IO1 high-speed inputRead
BI105Zone2-FansONbyMaxAirZone 2 fans on by Max AirRead
BI106Zone2-FansONbyTemperatureZone 2 fans on by temperatureRead
BI107Zone2-FansONbyOccupancyZone 2 fans on by occupied scheduleRead
BI108Zone2-FansONbyBMSZone 2 fans on by BMS commandRead
BI109Zone2-FansONbyIO1Zone 2 fans on by IO1 inputRead
BI110Zone2-FansONbyButtonZone 2 fans on by panel buttonRead
BI111Zone2-FansONbyHRCZone 2 fans on by HRCRead
BI112Zone2-FansONbyWashZone 2 fans on by washRead
BI113Zone2-FansONbyBMSPrepZone 2 fans on by BMS prep timeRead
BI114Zone2-FansONbyButtonPrepZone 2 fans on by button prep timeRead
BI115Zone2-FansONbyTemperaturePrepZone 2 fans on by temperature prep timeRead
BI116Zone1-LightsONbyWashZone 1 lights on by washRead
BI117Zone1-LightsONbyBypassZone 1 lights on by bypassRead
BI118Zone1-LightsONbyBMSZone 1 lights on by BMS commandRead
BI119Zone1-LightsONbyButtonZone 1 lights on by panel buttonRead
BI120Zone1-LightsONbyOccupiedZone 1 lights on by occupied scheduleRead
BI121Zone1-LightsONbyIOZone 1 lights on by IO inputRead
BI122Zone1-LightsONbyFansButtonZone 1 lights on by fans buttonRead
BI123Zone1-LightsONbyFansAutomaticZone 1 lights on by fans automaticRead
BI124Zone2-LightsONbyWashZone 2 lights on by washRead
BI125Zone2-LightsONbyBypassZone 2 lights on by bypassRead
BI126Zone2-LightsONbyBMSZone 2 lights on by BMS commandRead
BI127Zone2-LightsONbyButtonZone 2 lights on by panel buttonRead
BI128Zone2-LightsONbyOccupiedZone 2 lights on by occupied scheduleRead
BI129Zone2-LightsONbyIOZone 2 lights on by IO inputRead
BI130Zone2-LightsONbyFansButtonZone 2 lights on by fans buttonRead
BI131Zone2-LightsONbyAutomaticZone 2 lights on by automatic (with fans)Read
AImin132ErrorCOREBoard1CORE board 1 fire system fault codeRead
AI133ErrorCOREBoard2CORE board 2 fire system fault codeRead
AI134ErrorCOREBoard3CORE board 3 fire system fault codeRead
AI135ErrorCOREBoard4CORE board 4 fire system fault codeRead
AI136ErrorCOREBoard5CORE board 5 fire system fault codeRead
AI137ErrorCOREBoard6CORE board 6 fire system fault codeRead
AI138ErrorCOREBoard7CORE board 7 fire system fault codeRead
AI139ErrorCOREBoard8CORE board 8 fire system fault codeRead
AI140ErrorCOREBoard9CORE board 9 fire system fault codeRead
AI141ErrorCOREBoard10CORE board 10 fire system fault codeRead
AI142ErrorCOREBoard11CORE board 11 fire system fault codeRead
AI143ErrorCOREBoard12CORE board 12 fire system fault codeRead
AI144ErrorCOREBoard13CORE board 13 fire system fault codeRead
AI145ErrorCOREBoard14CORE board 14 fire system fault codeRead
AI146ErrorCOREBoard15CORE board 15 fire system fault codeRead
AI147PercentClogged_PCU1_Filter1PCU 1 filter 1 percent cloggedRead
AI148PercentClogged_PCU1_Filter2PCU 1 filter 2 percent cloggedRead
AI149PercentClogged_PCU1_Filter3PCU 1 filter 3 percent cloggedRead
AI150PercentClogged_PCU1_Filter4PCU 1 filter 4 percent cloggedRead
AI151PercentClogged_PCU1_Filter5PCU 1 filter 5 percent cloggedRead
BI152CloggedFilter_PCU1PCU 1 clogged filterRead
BI153MissingFilter_PCU1PCU 1 missing filterRead
BI15472HourCloggedFilter_PCU1PCU 1 filter clogged for 72 hoursRead
BI155CloggedPCU_PCU1PCU 1 cloggedRead
BI156DoorMissing_PCU1PCU 1 door missingRead
BI157NeedCalibration_PCU1PCU 1 needs calibrationRead
BI15824HourCloggedFilter_PCU1PCU 1 filter clogged for 24 hoursRead
BI159ESPDoorMissing_PCU1PCU 1 ESP door missingRead
BI160ESPDrainClogged_PCU1PCU 1 ESP drain cloggedRead
AI161PercentClogged_PCU2_Filter1PCU 2 filter 1 percent cloggedRead
AI162PercentClogged_PCU2_Filter2PCU 2 filter 2 percent cloggedRead
AI163PercentClogged_PCU2_Filter3PCU 2 filter 3 percent cloggedRead
AI164PercentClogged_PCU2_Filter4PCU 2 filter 4 percent cloggedRead
AI165PercentClogged_PCU2_Filter5PCU 2 filter 5 percent cloggedRead
BI166CloggedFilter_PCU2PCU 2 clogged filterRead
BI167MissingFilter_PCU2PCU 2 missing filterRead
BI16872HourCloggedFilter_PCU2PCU 2 filter clogged for 72 hoursRead
BI169CloggedPCU_PCU2PCU 2 cloggedRead
BI170DoorMissing_PCU2PCU 2 door missingRead
BI171NeedCalibration_PCU2PCU 2 needs calibrationRead
BI172ESPDoorMissing_PCU2PCU 2 ESP door missingRead
BI173ESPDrainClogged_PCU2PCU 2 ESP drain cloggedRead
BI17424HourCloggedFilter_PCU2PCU 2 filter clogged for 24 hoursRead
AI175PercentClogged_PCU3_Filter1PCU 3 filter 1 percent cloggedRead
AI176PercentClogged_PCU3_Filter2PCU 3 filter 2 percent cloggedRead
AI177PercentClogged_PCU3_Filter3PCU 3 filter 3 percent cloggedRead
AI178PercentClogged_PCU3_Filter4PCU 3 filter 4 percent cloggedRead
AI179PercentClogged_PCU3_Filter5PCU 3 filter 5 percent cloggedRead
BI180CloggedFilter_PCU3PCU 3 clogged filterRead
BI181MissingFilter_PCU3PCU 3 missing filterRead
BI18272HourCloggedFilter_PCU3PCU 3 filter clogged for 72 hoursRead
BI183CloggedPCU_PCU3PCU 3 cloggedRead
BI184DoorMissing_PCU3PCU 3 door missingRead
BI185NeedCalibration_PCU3PCU 3 needs calibrationRead
BI18624HourCloggedFilter_PCU3PCU 3 filter clogged for 24 hoursRead
BI187ESPDoorMissing_PCU3PCU 3 ESP door missingRead
BI188ESPDrainClogged_PCU3PCU 3 ESP drain cloggedRead
BImin189DCVFireZone1Fire system tripped, zone 1Read
BI190DCVAuxFaultZone1Auxiliary input fault, zone 1Read
BI191DCVFuseFaultZone1Board fuse fault, zone 1Read
BI192DCVKTSZone1KTS (kill tamper switch) tripped, zone 1Read
BI193DCVProvingFaultZone1Fan proving fault, zone 1Read
BI194DCVMUAInterlockErr1Zone1MUA interlock error 1, zone 1Read
BI195DCVMUAInterlockErr2Zone1MUA interlock error 2, zone 1Read
BI196DCVBrokenTempSensorZone1Broken temperature sensor, zone 1Read
BI197DCVMissingTempSensorZone1Missing temperature sensor, zone 1Read
BI198DCVOverloadZone1Overload 1 tripped, zone 1Read
BI199DCVOverload2Zone1Overload 2 tripped, zone 1Read
BI200DCVPCUFaultZone1PCU fault, zone 1Read
BI201DCVLightsEnergizedFaultZone1Lights energized fault (power seen when off), zone 1Read
BI202DCVLightsDeenergizedFaultZone1Lights de-energized fault (no power when on), zone 1Read
BI203DCVSurfactantLowZone1Surfactant low, zone 1Read
BI204DCVCheckAppliancePilotsZone1Check appliance pilots, zone 1Read
BI205DCVFireZone2Fire system tripped, zone 2Read
BI206DCVAuxFaultZone2Auxiliary input fault, zone 2Read
BI207DCVFuseFaultZone2Board fuse fault, zone 2Read
BI208DCVKTSZone2KTS (kill tamper switch) tripped, zone 2Read
BI209DCVProvingFaultZone2Fan proving fault, zone 2Read
BI210DCVMUAInterlockErr1Zone2MUA interlock error 1, zone 2Read
BI211DCVMUAInterlockErr2Zone2MUA interlock error 2, zone 2Read
BI212DCVBrokenTempSensorZone2Broken temperature sensor, zone 2Read
BI213DCVMissingTempSensorZone2Missing temperature sensor, zone 2Read
BI214DCVOverload1Zone2Overload 1 tripped, zone 2Read
BI215DCVOverload2Zone2Overload 2 tripped, zone 2Read
BI216DCVPCUFaultZone2PCU fault, zone 2Read
BI217DCVLightsEnergizedFaultZone2Lights energized fault (power seen when off), zone 2Read
BI218DCVLightsDeenergizedFaultZone2Lights de-energized fault (no power when on), zone 2Read
BI219DCVSurfactantLowZone2Surfactant low, zone 2Read
BI220DCVCheckAppliancePilotsZone2Check appliance pilots, zone 2Read
AImin221ModbusFaultCodeModbus device communication fault codeRead
BV222PrepTimeButtonZone1Zone 1 Prep Time buttonWrite
BVmin223FansONButtonZone1Zone 1 Fans On buttonWrite
BV224WashButtonZone1Zone 1 Wash buttonWrite
BV225LightsButtonZone1Zone 1 Lights buttonWrite
BV226MaxAirZone1Zone 1 Max Air buttonWrite
BV227PrepTimeButtonZone2Zone 2 Prep Time buttonWrite
BV228FansONButtonZone2Zone 2 Fans On buttonWrite
BV229WashButtonZone2Zone 2 Wash buttonWrite
BV230LightsButtonZone2Zone 2 Lights buttonWrite
BV231MaxAirZone2Zone 2 Max Air buttonWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the DCV Package DDC (Protocessor BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CaptiveAire DCV Package DDC (Protocessor BACnet)

How many BACnet points does the CaptiveAire DCV Package DDC (Protocessor BACnet) have?

This list has 231 BACnet objects: 118 analog inputs, 103 binary inputs, 10 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CaptiveAire DCV Package DDC (Protocessor BACnet) BACnet points are writable?

10 of the 231 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official CaptiveAire DCV Package DDC (Protocessor BACnet) BACnet documentation?

The source is Direct Digital Controls (DDC) Application Guide: Demand Control Ventilation (DCV) Packages Network, published free by CaptiveAire at https://www.captiveaire.com/catalogcontent/electriccontrols/doc/dcv-ddc.pdf.

What are the minimum BACnet points to integrate the CaptiveAire DCV Package DDC (Protocessor BACnet)?

Start with BV 223 FansONButtonZone1 (Zone 1 fans button; write effect not described in guide); BI 94 Zone1-FansONbyBMS (Confirms zone 1 fans are on by BMS command); AI 33 Temperature Zone 1 (Zone 1 temperature, °F); AI 48 VFD Frequency Exhaust 1 (Exhaust fan 1 drive speed, Hz); AI 56 VFD Frequency Supply 1 (Supply (make-up air) fan 1 drive speed, Hz); BI 189 DCVFireZone1 (Fire system tripped, zone 1); AI 78 VFD Fault Exhaust 1 (Exhaust fan 1 drive fault); AI 132 ErrorCOREBoard1 (Fire system fault code; highest-priority fault shown); AI 221 ModbusFaultCode (Modbus fault code; codes not listed in the guide).

How do I check these points on the real DCV Package DDC (Protocessor BACnet)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.