CaptiveAire MUA Heater DDC (Protocessor BACnet) BACnet points list

Updated 28 October 2026

Short answer

CaptiveAire make-up air heaters with the DDC package expose their unit-board data through a factory gateway for BACnet IP or MS/TP. The 161 objects include DDC heat/cool/blower commands, tempering and activation modes, occupied/unoccupied setpoints and blower/damper limits, a 42-point on-board schedule, sensor readings, occupancy flags and six active fault codes. As with the Paragon RTUs, the preferred BMS approach is setpoints plus the DDC Occupied Override binary rather than the raw DDC commands.

This page lists 161 BACnet objects for the CaptiveAire MUA Heater DDC (Protocessor BACnet) — 118 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CaptiveAire’s own free documentation, linked below.

Manufacturer
CaptiveAire
Model
MUA Heater DDC (Protocessor BACnet)
Equipment
Make-up air unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
161 (118 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
50000
Also known as
CaptiveAire make-up air, Direct fired MUA, Tempered make-up air, DDC Application Guide MUA
Source document
DDC Application Guide for MUA Heater Units · rev. 2024-10
Download CSV 161 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: CaptiveAire MUA Heater DDC (Protocessor BACnet)

Integration in brief

Enable scheduling once (BV-8), set all on-board schedule slots (AV-61..102) to 1440, then drive occupancy from the BMS with BV-7 DDCOccupiedOverride and let the unit temper to its own setpoints. The guide calls setpoint adjustment plus the occupied override the preferred method; the DDC heat/cool/blower commands are only for jobs where the tempering modes are set to DDC. Monitor HVAC state, occupancy flags, temperatures and the six fault-code AIs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 7DDCOccupiedOverrideOccupied/unoccupied command from the BMSWrite
BV 8SchedulingEnabledMust be on (once) for BV-7 to workWrite
AV 45DischargeHeatOccSPOccupied discharge heating setpointWrite
AI 143CurrentHvacStateIdle / blower / heating / cooling stateRead
AI 148CurrentOccupiedStatusConfirms the occupancy command took effectRead
AI 121DischargeStatTempDischarge air temperatureRead
AI 154GasValveOutputBurner modulation levelRead
AI 137ActiveFault1IdFirst active fault codeRead

Enable & remote start

BV-8 SchedulingEnabled must be on and the internal schedule AVs (61-102) all set to 1440 so BV-7 has full control of occupancy. DDC commands (BV-1..5, AV-6) work only with the heat/cool tempering modes (AV-9..12) set to DDC; this disables temperature-based activation and heat and cool cannot be called together.

Network setup

Watch out for

CaptiveAire MUA Heater DDC (Protocessor BACnet) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

161 of 161 shown
Type
Binary
Access
Show
CaptiveAire MUA Heater DDC (Protocessor BACnet) BACnet Points List
DescriptionStates
BV1DDCHeatCommandHeating command, requires heat tempering mode = DDCWrite
BV2DDCCoolCommand1Cooling stage 1 command, requires cool tempering mode = DDCWrite
BV3DDCCoolCommand2Cooling stage 2 command, requires cool tempering mode = DDCWrite
BV4DDCCoolCommand3Cooling stage 3 command, requires cool tempering mode = DDCWrite
BV5DDCBlowerCommandBlower command, requires both heat and cool tempering modes = DDCWrite
AV6DDCHeatModulationHeat modulation signal, 0-10V. 0V = low fire and 10V = highWrite
BVmin7DDCOccupiedOverrideOccupied override command, requires SchedulingEnabled = ON (1)Write
BVmin8SchedulingEnabledEnable schedulingWrite
AV9HeatTemperModeOccHeat tempering mode during occupied timeWrite0=Discharge, 1=Space, 2=BAS, 3=DDC
AV10HeatTemperModeUnoccHeat tempering mode during unoccupied timeWrite0=Discharge, 1=Space, 2=BAS, 3=DDC
AV11CoolTemperModeOccCool tempering mode during occupied timeWrite0=Intake, 1=Space, 2=BAS, 3=DDC
AV12CoolTemperModeUnoccCool tempering mode during unoccupied timeWrite0=Intake, 1=Space, 2=BAS, 3=DDC
AV13ActivateOnOcc"Activate based on" during occupied timeWrite0=Intake, 1=Space, 2=Both, 3=Either, 4=Stat
AV14ActivateOnUnocc"Activate based on" during unoccupied timeWrite0=Intake, 1=Space, 2=Both, 3=Either, 4=Stat
AV15SpaceHeatHystSpace Heating HysteresisWrite
AV16IntakeHeatHystIntake Heating HysteresisWrite
AV17SpaceCoolHystSpace Cooling HysteresisWrite
AV18IntakeCoolHystIntake Cooling HysteresisWrite
AV19EvapHystEvap Cooling HysteresisWrite
AV20BlowerModeOccBlower mode during occupied timesWrite0=Auto, 1=Off, 2=On
AV21BlowerModeUnoccBlower mode during unoccupied timesWrite0=Auto, 1=Off, 2=On
AV22MixingBoxModeMixing box modeWrite0=Off, 1=Manual, 2=2 Position, 3=OA Percent, 4=Analog Ctrl, 5=PS, 6=100% OA, 7=Modes
AV23MixingBoxMinOAPercentOccMin occupied outdoor air percent when mixing box mode = outdoor airWrite
AV24MixingBoxMinOAPercentUnoccMin unoccupied outdoor air percent when mixing box mode = outdoor airWrite
AV25MixingBoxMaxOAPercentOccMax occupied outdoor air percent when mixing box mode = outdoor airWrite
AV26MixingBoxMaxOAPercentUnoccMax unoccupied outdoor air percent when mixing box mode = outdoor airWrite
AV27MixingBoxMinVoltsOccMin occupied mixing box voltage when mixing box mode = manualWrite
AV28MixingBoxMinVoltsUnoccMin unoccupied mixing box voltage when mixing box mode = manualWrite
AV29MixingBoxMaxVoltsOccMax occupied mixing box voltage when mixing box mode = manualWrite
AV30MixingBoxMaxVoltsUnoccMax unoccupied mixing box voltage when mixing box mode = manualWrite
AV31BlowerVFDMinFreqOccMin blower VFD Frequency when occupiedWrite
AV32BlowerVFDMinFreqUnoccMin blower VFD Frequency when unoccupiedWrite
AV33BlowerVFDMaxFreqOccMax blower VFD Frequency when occupiedWrite
AV34BlowerVFDMaxFreqUnoccMax blower VFD Frequency when unoccupiedWrite
AV35BlowerPWMMinOccMin blower ECM speed when occupiedWrite
AV36BlowerPWMMinUnoccMin blower ECM speed when unoccupiedWrite
AV37BlowerPWMMaxOccMax blower ECM speed when occupiedWrite
AV38BlowerPWMMaxUnoccMax blower ECM speed when unoccupiedWrite
AV39IntakeHeatOccSPIntake Heating Occupied SetpointWrite
AV40IntakeHeatUnoccSPIntake Heating Unoccupied SetpointWrite
AV41SpaceHeatOccSPSpace Heating Occupied SetpointWrite
AV42SpaceHeatUnoccSPSpace Heating Unoccupied SetpointWrite
AV43MinDischargeHeatOccSPMin Discharge Heating when occupied, relevant only if heat tempering mode =Write
AV44MinDischargeHeatUnoccSPMin Discharge Heating when unoccupied, relevant only if heat tempering mode =Write
AVmin45DischargeHeatOccSPDischarge heating setpoint when occupied, requires heat tempering mode = dischargeWrite
AV46DischargeHeatUnoccSPDischarge heating setpoint when unoccupied, requires heat tempering mode = dischargeWrite
AV47MaxDischargeHeatOccSPMax Discharge Heating when occupied, relevant only if heat tempering mode =Write
AV48MaxDischargeHeatUnoccSPMax Discharge Heating when unoccupied, relevant only if heat tempering mode =Write
AV49IntakeCoolOccSPIntake Cooling Occupied SetpointWrite
AV50IntakeCoolUnoccSPIntake Cooling Unoccupied SetpointWrite
AV51SpaceCoolOccSPSpace Cooling Occupied SetpointWrite
AV52SpaceCoolUnoccSPSpace Cooling Unoccupied SetpointWrite
AV53IntakeCoolStagingDiffOccIntake Cooling Stage Differential Setpoint when occupiedWrite
AV54IntakeCoolStagingDiffUnoccIntake Cooling Stage Differential Setpoint when unoccupiedWrite
AV55SpaceCoolStagingDiffOccSpace Cooling Stage Differential Setpoint when occupiedWrite
AV56SpaceCoolStagingDiffUnoccSpace Cooling Stage Differential Setpoint when unoccupiedWrite
AV57RoomOverrideOccSPRoom Override Occupied SetpointWrite
AV58RoomOverrideUnoccSPRoom Override Unoccupied SetpointWrite
AV59OAEvapCoolOccSPOutdoor air evap cooling occupied setpointWrite
AV60OAEvapCoolUnoccSPOutdoor air evap cooling unoccupied setpointWrite
AV61ScheduleSundayAStartDaily schedule start/end time in minutesWrite
AV62ScheduleSundayAEndDaily schedule start/end time in minutesWrite
AV63ScheduleSundayBStartDaily schedule start/end time in minutesWrite
AV64ScheduleSundayBEndDaily schedule start/end time in minutesWrite
AV65ScheduleSundayCStartDaily schedule start/end time in minutesWrite
AV66ScheduleSundayCEndDaily schedule start/end time in minutesWrite
AV67ScheduleMondayAStartDaily schedule start/end time in minutesWrite
AV68ScheduleMondayAEndDaily schedule start/end time in minutesWrite
AV69ScheduleMondayBStartDaily schedule start/end time in minutesWrite
AV70ScheduleMondayBEndDaily schedule start/end time in minutesWrite
AV71ScheduleMondayCStartDaily schedule start/end time in minutesWrite
AV72ScheduleMondayCEndDaily schedule start/end time in minutesWrite
AV73ScheduleTuesdayAStartDaily schedule start/end time in minutesWrite
AV74ScheduleTuesdayAEndDaily schedule start/end time in minutesWrite
AV75ScheduleTuesdayBStartDaily schedule start/end time in minutesWrite
AV76ScheduleTuesdayBEndDaily schedule start/end time in minutesWrite
AV77ScheduleTuesdayCStartDaily schedule start/end time in minutesWrite
AV78ScheduleTuesdayCEndDaily schedule start/end time in minutesWrite
AV79ScheduleWednesdayAStartDaily schedule start/end time in minutesWrite
AV80ScheduleWednesdayAEndDaily schedule start/end time in minutesWrite
AV81ScheduleWednesdayBStartDaily schedule start/end time in minutesWrite
AV82ScheduleWednesdayBEndDaily schedule start/end time in minutesWrite
AV83ScheduleWednesdayCStartDaily schedule start/end time in minutesWrite
AV84ScheduleWednesdayCEndDaily schedule start/end time in minutesWrite
AV85ScheduleThursdayAStartDaily schedule start/end time in minutesWrite
AV86ScheduleThursdayAEndDaily schedule start/end time in minutesWrite
AV87ScheduleThursdayBStartDaily schedule start/end time in minutesWrite
AV88ScheduleThursdayBEndDaily schedule start/end time in minutesWrite
AV89ScheduleThursdayCStartDaily schedule start/end time in minutesWrite
AV90ScheduleThursdayCEndDaily schedule start/end time in minutesWrite
AV91ScheduleFridayAStartDaily schedule start/end time in minutesWrite
AV92ScheduleFridayAEndDaily schedule start/end time in minutesWrite
AV93ScheduleFridayBStartDaily schedule start/end time in minutesWrite
AV94ScheduleFridayBEndDaily schedule start/end time in minutesWrite
AV95ScheduleFridayCStartDaily schedule start/end time in minutesWrite
AV96ScheduleFridayCEndDaily schedule start/end time in minutesWrite
AV97ScheduleSaturdayAStartDaily schedule start/end time in minutesWrite
AV98ScheduleSaturdayAEndDaily schedule start/end time in minutesWrite
AV99ScheduleSaturdayBStartDaily schedule start/end time in minutesWrite
AV100ScheduleSaturdayBEndDaily schedule start/end time in minutesWrite
AV101ScheduleSaturdayCStartDaily schedule start/end time in minutesWrite
AV102ScheduleSaturdayCEndDaily schedule start/end time in minutesWrite
AV103BlowerManualFreqOccVFD frequency when occupied, requires blower control = VFD manualWrite
AV104BlowerManualFreqUnoccVFD frequency when unoccupied, requires blower control = VFD manualWrite
AV105BlowerManualPwmRateOccECM speed when occupied, requires blower control = ECM manualWrite
AV106BlowerManualPwmRateUnoccECM speed when unoccupied, requires blower control = ECM manualWrite
AV107MixingBoxManualOAOccMixing Box Outdoor Air Percent during occupied times, requires mixing box modeWrite
AV108MixingBoxManualOAUnoccMixing Box Outdoor Air Percent during unoccupied times, requires mixing box modeWrite
AV109MixingBoxManualVoltsOccMixing Box damper voltage during occupied times, requires mixing box mode =Write
AV110MixingBoxManualVoltsUnoccMixing Box damper voltage during unoccupied times, requires mixing box mode =Write
AV111DryModeDischTempSpOccDry mode discharge temperature setpoint when occupiedWrite
AV112DryModeDischTempSpUnoccDry mode discharge temperature setpoint when unoccupiedWrite
AV113DryModeDewPointSPDry mode dew point setpointWrite
AV114DryModeOAPercentDry mode outdoor air percentageWrite
AV115StaticPressureLowOccStatic Pressure Low setpoint when occupiedWrite
AV116StaticPressureLowUnoccStatic Pressure Low setpoint when unoccupiedWrite
AV117StaticPressureHighOccStatic Pressure High setpoint when occupiedWrite
AV118StaticPressureHighUnoccStatic Pressure High setpoint when unoccupiedWrite
AI119OutdoorStatTempOutdoor temperatureRead
AI120ReturnStatTempReturn temperatureRead
AImin121DischargeStatTempDischarge temperatureRead
AI122IntakeStatTempIntake temperatureRead
AI123SpaceStatTempSpace temperature (thermistor)Read
AI124Hmi1TempUnit HMI temperatureRead
AI125Hmi2TempRemote HMI 1 temperatureRead
AI126Hmi3TempRemote HMI 2 temperatureRead
AI127Hmi4TempRemote HMI 3 temperatureRead
AI128Hmi5TempRemote HMI 4 temperatureRead
AI129IntakeRhIntake relative humidityRead
AI130SpaceRhSpace relative humidityRead
AI131AdjustableDamperPositionMixing Box Damper signalRead
AI132Hmi1RhUnit HMI relative humidityRead
AI133Hmi2RhRemote HMI 1 relative humidityRead
AI134Hmi3RhRemote HMI 2 relative humidityRead
AI135Hmi4RhRemote HMI 3 relative humidityRead
AI136Hmi5RhRemote HMI 4 relative humidityRead
AImin137ActiveFault1IdActive Fault Code (see fault code table)Read
AI138ActiveFault2IdActive Fault Code (see fault code table)Read
AI139ActiveFault3IdActive Fault Code (see fault code table)Read
AI140ActiveFault4IdActive Fault Code (see fault code table)Read
AI141ActiveFault5IdActive Fault Code (see fault code table)Read
AI142ActiveFault6IdActive Fault Code (see fault code table)Read
AImin143CurrentHvacStateHVAC State (Idle = 0, Blower = 1, Heating = 2, CoolingRead0=Idle, 1=Blower, 2=Heating, 3=Cooling
AI144OccupiedbyScheduleOccupied due to the scheduleRead
AI145OccupiedbyInputOccupied due to hardware inputRead
AI146OccupiedbyDDCOccupied due to DDC commandRead
AI147OccupiedbyHMIOverrideOccupied due to HMI commandRead
AImin148CurrentOccupiedStatusOccupancy status, occupied = 1, unoccupied = 0Read0=Unoccupied, 1=Occupied
AI149CalculatedAverageSpaceTempAverage space temperatureRead
AI150BlowerVFDFrequencyBlower VFD frequencyRead
AI151BlowerVFDCurrentBlower VFD currentRead
AI152BlowerVFDPowerBlower VFD powerRead
AI153CalculatedAverageRhAverage space relative humidityRead
AImin154GasValveOutputController output to the modulating gas valve. 0% = Low Fire, 100%Read
AI155CFMReadingFan CFM ReadingRead
AI156StaticOaPsLowOccStatic Outdoor Air Pressure Low (Occupied)Read
AI157StaticOaPsLowUnoccStatic Outdoor Air Pressure Low (Unoccupied)Read
AI158StaticOaPsHighOccStatic Outdoor Air Pressure High (Occupied)Read
AI159StaticOaPsHighUnoccStatic Outdoor Air Pressure High (Unoccupied)Read
AI160PressureSensor1Duct Static PressureRead
AI161PressureSensor2Building Static PressureRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MUA Heater DDC (Protocessor BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CaptiveAire MUA Heater DDC (Protocessor BACnet)

How many BACnet points does the CaptiveAire MUA Heater DDC (Protocessor BACnet) have?

This list has 161 BACnet objects: 43 analog inputs, 111 analog values, 7 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CaptiveAire MUA Heater DDC (Protocessor BACnet) BACnet points are writable?

118 of the 161 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official CaptiveAire MUA Heater DDC (Protocessor BACnet) BACnet documentation?

The source is DDC Application Guide for MUA Heater Units, revision 2024-10, published free by CaptiveAire at https://www.captiveaire.com/catalogcontent/fans/sup_ad/doc/ddc-application-guide.pdf.

What are the minimum BACnet points to integrate the CaptiveAire MUA Heater DDC (Protocessor BACnet)?

Start with BV 7 DDCOccupiedOverride (Occupied/unoccupied command from the BMS); BV 8 SchedulingEnabled (Must be on (once) for BV-7 to work); AV 45 DischargeHeatOccSP (Occupied discharge heating setpoint); AI 143 CurrentHvacState (Idle / blower / heating / cooling state); AI 148 CurrentOccupiedStatus (Confirms the occupancy command took effect); AI 121 DischargeStatTemp (Discharge air temperature); AI 154 GasValveOutput (Burner modulation level); AI 137 ActiveFault1Id (First active fault code).

How do I enable BMS control of the CaptiveAire MUA Heater DDC (Protocessor BACnet)?

BV-8 SchedulingEnabled must be on and the internal schedule AVs (61-102) all set to 1440 so BV-7 has full control of occupancy. DDC commands (BV-1..5, AV-6) work only with the heat/cool tempering modes (AV-9..12) set to DDC; this disables temperature-based activation and heat and cool cannot be called together.

How do I check these points on the real MUA Heater DDC (Protocessor BACnet)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CaptiveAire BACnet points lists

Source: DDC Application Guide for MUA Heater Units · rev. 2024-10. Object names, instances and units are reproduced as published; descriptions are our own.