Kitchen hood self-cleaning wash system control panel · BACnet points list

CaptiveAire Self Cleaning System (SCS) Control Panel BACnet points list

Updated 28 October 2026

Short answer

The CaptiveAire Self Cleaning System (SCS) is a wall-mounted panel with a water manifold, wash solenoids and a surfactant pump that washes kitchen exhaust hoods (hot water wash) or sprays cold water mist while cooking. Its ECPM03 board can also run two exhaust/supply fan zones and two light zones and monitor fire, kill/tamper switch, overloads and PCU filters. BACnet IP or MS/TP comes from a factory-mounted Protocessor gateway set at the factory for one of the two. The 131 objects are read-only temperatures, 'on by' reason flags, faults and PCU alarms, plus seven button BVs for fans, lights and wash.

This page lists 131 BACnet objects for the CaptiveAire Self Cleaning System (SCS) Control Panel — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CaptiveAire’s own free documentation, linked below.

Manufacturer
CaptiveAire
Model
Self Cleaning System (SCS) Control Panel
Equipment
Kitchen hood self-cleaning wash system control panel
Equipment type
Other equipment
BACnet objects
131 (7 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
50000 (manual text); 50001 (configuration screenshot)
Also known as
CaptiveAire SCS, Self Cleaning System, Hood wash panel, Hot Water Wash, Cold Water Mist, ECPM03, Protocessor
Source document
Self Cleaning System Control Panel Installation, Operation, and Maintenance Manual · A0017476 · rev. February 2025 Rev. 13
Download CSV 131 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: CaptiveAire Self Cleaning System (SCS) Control Panel

Integration in brief

Map the fan, light and wash button BVs for control, confirm with the FanZoneONbyBMS and LightONbyBMS flags, and monitor the fire, KTS, overload, surfactant and Modbus faults. A BMS wash runs once at any time, regardless of whether the fans are on, so the BMS should check the fan state first.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 125FansONButtonZone1Zone 1 fans button, BMS fan startWrite
BV 129WashButtonZone1Zone 1 wash button; runs even with fans onWrite
BI 44FanZoneONbyBMS1Confirms zone 1 fans are on by BMS commandRead
AI 33Temperature Zone 1Zone 1 temperature, °FRead
BI 71FaultFireZ1Fire system trippedRead
BI 73FaultKTSZ1Kill/tamper switch (KTS) trippedRead
BI 74FaultOverloadZoneOneZ1Fan zone 1 overload trippedRead
BI 76FaultSurfactantLowZ1Surfactant tank lowRead
BI 97ModbusFaultCodeModbus fault (typed BI despite 'Code' in the name)Read

Enable & remote start

Fans may be started via BACnet, LonWorks or CASlink, but fan and light zones only exist when the wash operation is set to Local; in Remote wash the ECPM03 only monitors. With 'Lights With Fan' enabled the lights follow the fans; otherwise the HMI button or BMS can switch them.

Network setup

Watch out for

CaptiveAire Self Cleaning System (SCS) Control Panel BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

131 of 131 shown
Type
Analog
Access
Show
CaptiveAire Self Cleaning System (SCS) Control Panel BACnet Points List
DescriptionStates
AI1Temperature Sensor 1Temperature sensor 1 reading°FRead
AI2Temperature Sensor 2Temperature sensor 2 reading°FRead
AI3Temperature Sensor 3Temperature sensor 3 reading°FRead
AI4Temperature Sensor 4Temperature sensor 4 reading°FRead
AI5Temperature Sensor 5Temperature sensor 5 reading°FRead
AI6Temperature Sensor 6Temperature sensor 6 reading°FRead
AI7Temperature Sensor 7Temperature sensor 7 reading°FRead
AI8Temperature Sensor 8Temperature sensor 8 reading°FRead
AI9Temperature Sensor 9Temperature sensor 9 reading°FRead
AI10Temperature Sensor 10Temperature sensor 10 reading°FRead
AI11Temperature Sensor 11Temperature sensor 11 reading°FRead
AI12Temperature Sensor 12Temperature sensor 12 reading°FRead
AI13Temperature Sensor 13Temperature sensor 13 reading°FRead
AI14Temperature Sensor 14Temperature sensor 14 reading°FRead
AI15Temperature Sensor 15Temperature sensor 15 reading°FRead
AI16Temperature Sensor 16Temperature sensor 16 reading°FRead
AI17Temperature Sensor 17Temperature sensor 17 reading°FRead
AI18Temperature Sensor 18Temperature sensor 18 reading°FRead
AI19Temperature Sensor 19Temperature sensor 19 reading°FRead
AI20Temperature Sensor 20Temperature sensor 20 reading°FRead
AI21Temperature Sensor 21Temperature sensor 21 reading°FRead
AI22Temperature Sensor 22Temperature sensor 22 reading°FRead
AI23Temperature Sensor 23Temperature sensor 23 reading°FRead
AI24Temperature Sensor 24Temperature sensor 24 reading°FRead
AI25Temperature Sensor 25Temperature sensor 25 reading°FRead
AI26Temperature Sensor 26Temperature sensor 26 reading°FRead
AI27Temperature Sensor 27Temperature sensor 27 reading°FRead
AI28Temperature Sensor 28Temperature sensor 28 reading°FRead
AI29Temperature Sensor 29Temperature sensor 29 reading°FRead
AI30Temperature Sensor 30Temperature sensor 30 reading°FRead
AI31Temperature Sensor 31Temperature sensor 31 reading°FRead
AI32Temperature Sensor 32Temperature sensor 32 reading°FRead
AImin33Temperature Zone 1Zone 1 temperature°FRead
AI34Temperature Zone 2Zone 2 temperature°FRead
AI35Temperature HMI 1Temperature at HMI 1°FRead
AI36Temperature HMI 2Temperature at HMI 2°FRead
AI37Temperature HMI 3Temperature at HMI 3°FRead
AI38Temperature HMI 4Temperature at HMI 4°FRead
AI39FanZoneONbyFire1Zone 1 fans on by fireRead
AI40FanZoneONbyBypass1Zone 1 fans on by bypassRead
AI41FanZoneONbyTemperature1Zone 1 fans on by temperatureRead
AI42FanZoneONbyFansButton1Zone 1 fans on by fans buttonRead
BI43FanZoneONbyOccupied1Zone 1 fans on by occupied scheduleRead
BImin44FanZoneONbyBMS1Zone 1 fans on by BMS commandRead
BI45FanZoneONbyIO1Zone 1 fans on by IO inputRead
BI46FanZoneONbyDefrost1Zone 1 fans on by defrostRead
BI47LightONbyWash1Zone 1 lights on by washRead
BI48LightONbyBypass1Zone 1 lights on by bypassRead
BI49LightONbyBMS1Zone 1 lights on by BMS commandRead
BI50LightONbyButton1Zone 1 lights on by panel buttonRead
BI51LightONbyOccupied1Zone 1 lights on by occupied scheduleRead
BI52LightONbyIO1Zone 1 lights on by IO inputRead
BI53LightONbyFansButton1Zone 1 lights on by fans buttonRead
BI54LightONbyAutomatic1Zone 1 lights on by automatic (with fans)Read
BI55FanZoneONbyFire2Zone 2 fans on by fireRead
BI56FanZoneONbyBypass2Zone 2 fans on by bypassRead
BI57FanZoneONbyTemperature2Zone 2 fans on by temperatureRead
BI58FanZoneONbyFansButton2Zone 2 fans on by fans buttonRead
BI59FanZoneONbyOccupied2Zone 2 fans on by occupied scheduleRead
BI60FanZoneONbyBMS2Zone 2 fans on by BMS commandRead
BI61FanZoneONbyIO2Zone 2 fans on by IO inputRead
BI62FanZoneONbyDefrost2Zone 2 fans on by defrostRead
BI63LightONbyWash2Zone 2 lights on by washRead
BI64LightONbyBypass2Zone 2 lights on by bypassRead
BI65LightONbyBMS2Zone 2 lights on by BMS commandRead
BI66LightONbyButton2Zone 2 lights on by panel buttonRead
BI67LightONbyOccupied2Zone 2 lights on by occupied scheduleRead
BI68LightONbyIO2Zone 2 lights on by IO inputRead
BI69LightONbyFansButton2Zone 2 lights on by fans buttonRead
BI70LightONbyAutomatic2Zone 2 lights on by automatic (with fans)Read
BImin71FaultFireZ1Fire system tripped (Z1)Read
BI72FaultFuseZ1Board fuse fault (Z1)Read
BImin73FaultKTSZ1Kill/tamper switch (KTS) tripped (Z1)Read
BImin74FaultOverloadZoneOneZ1Overload, fan zone 1 (Z1)Read
BI75FaultOverloadZoneTwoZ1Overload, fan zone 2 (Z1)Read
BImin76FaultSurfactantLowZ1Surfactant low (Z1)Read
BI77FaultPCUInputZ1PCU input fault (Z1)Read
BI78FaultBrokenTempSensorZ1Broken temperature sensor (Z1)Read
BI79FaultMissingTempSensorZ1Missing temperature sensor (Z1)Read
BI80FaultB1EnergizedZ1Lights energized fault, input B1 (Z1)Read
BI81FaultB1DeEnergizedZ1Lights de-energized fault, input B1 (Z1)Read
BI82FaultB2EnergizedZ1Lights energized fault, input B2 (Z1)Read
BI83FaultB2DeEnergizedZ1Lights de-energized fault, input B2 (Z1)Read
BI84FaultFireZ2Fire system tripped (Z2)Read
BI85FaultFuseZ2Board fuse fault (Z2)Read
BI86FaultKTSZ2Kill/tamper switch (KTS) tripped (Z2)Read
BI87FaultOverloadZoneOneZ2Overload, fan zone 1 (Z2)Read
BI88FaultOverloadZoneTwoZ2Overload, fan zone 2 (Z2)Read
BI89FaultSurfactantLowZ2Surfactant low (Z2)Read
BI90FaultPCUInputZ2PCU input fault (Z2)Read
BI91FaultBrokenTempSensorZ2Broken temperature sensor (Z2)Read
BI92FaultMissingTempSensorZ2Missing temperature sensor (Z2)Read
BI93FaultB1EnergizedZ2Lights energized fault, input B1 (Z2)Read
BI94FaultB1DeEnergizedZ2Lights de-energized fault, input B1 (Z2)Read
BI95FaultB2EnergizedZ2Lights energized fault, input B2 (Z2)Read
BI96FaultB2DeEnergizedZ2Lights de-energized fault, input B2 (Z2)Read
BImin97ModbusFaultCodeModbus device communication fault codeRead
BI98CloggedFilter_PCU1PCU 1 clogged filterRead
BI99MissingFilter_PCU1PCU 1 missing filterRead
BI10072HourCloggedFilter_PCU1PCU 1 filter clogged for 72 hoursRead
BI101CloggedPCU_PCU1PCU 1 cloggedRead
BI102DoorMissing_PCU1PCU 1 door missingRead
BI103NeedCalibration_PCU1PCU 1 needs calibrationRead
BI10424HourCloggedFilter_PCU1PCU 1 filter clogged for 24 hoursRead
BI105ESPDoorMissing_PCU1PCU 1 ESP door missingRead
BI106ESPDrainClogged_PCU1PCU 1 ESP drain cloggedRead
BI107CloggedFilter_PCU2PCU 2 clogged filterRead
BI108MissingFilter_PCU2PCU 2 missing filterRead
BI10972HourCloggedFilter_PCU2PCU 2 filter clogged for 72 hoursRead
BI110CloggedPCU_PCU2PCU 2 cloggedRead
BI111DoorMissing_PCU2PCU 2 door missingRead
BI112NeedCalibration_PCU2PCU 2 needs calibrationRead
BI11324HourCloggedFilter_PCU2PCU 2 filter clogged for 24 hoursRead
BI114ESPDoorMissing_PCU2PCU 2 ESP door missingRead
BI115ESPDrainClogged_PCU2PCU 2 ESP drain cloggedRead
BI116CloggedFilter_PCU3PCU 3 clogged filterRead
BI117MissingFilter_PCU3PCU 3 missing filterRead
BI11872HourCloggedFilter_PCU3PCU 3 filter clogged for 72 hoursRead
BI119CloggedPCU_PCU3PCU 3 cloggedRead
BI120DoorMissing_PCU3PCU 3 door missingRead
BI121NeedCalibration_PCU3PCU 3 needs calibrationRead
BI12224HourCloggedFilter_PCU3PCU 3 filter clogged for 24 hoursRead
BI123ESPDoorMissing_PCU3PCU 3 ESP door missingRead
BI124ESPDrainClogged_PCU3PCU 3 ESP drain cloggedRead
BVmin125FansONButtonZone1Zone 1 Fans On buttonWrite
BV126LightsButtonZone1Zone 1 Lights buttonWrite
BV127FansONButtonZone2Zone 2 Fans On buttonWrite
BV128LightsButtonZone2Zone 2 Lights buttonWrite
BVmin129WashButtonZone1Zone 1 Wash buttonWrite
BV130WashButtonZone2Zone 2 Wash buttonWrite
BV131WashButtonZone3Zone 3 Wash buttonWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Self Cleaning System (SCS) Control Panel and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CaptiveAire Self Cleaning System (SCS) Control Panel

How many BACnet points does the CaptiveAire Self Cleaning System (SCS) Control Panel have?

This list has 131 BACnet objects: 42 analog inputs, 82 binary inputs, 7 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CaptiveAire Self Cleaning System (SCS) Control Panel BACnet points are writable?

7 of the 131 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official CaptiveAire Self Cleaning System (SCS) Control Panel BACnet documentation?

The source is Self Cleaning System Control Panel Installation, Operation, and Maintenance Manual (A0017476), revision February 2025 Rev. 13, published free by CaptiveAire at https://www.captiveaire.com/manuals/electrical/scs-oim.pdf.

What are the minimum BACnet points to integrate the CaptiveAire Self Cleaning System (SCS) Control Panel?

Start with BV 125 FansONButtonZone1 (Zone 1 fans button, BMS fan start); BV 129 WashButtonZone1 (Zone 1 wash button; runs even with fans on); BI 44 FanZoneONbyBMS1 (Confirms zone 1 fans are on by BMS command); AI 33 Temperature Zone 1 (Zone 1 temperature, °F); BI 71 FaultFireZ1 (Fire system tripped); BI 73 FaultKTSZ1 (Kill/tamper switch (KTS) tripped); BI 74 FaultOverloadZoneOneZ1 (Fan zone 1 overload tripped); BI 76 FaultSurfactantLowZ1 (Surfactant tank low); BI 97 ModbusFaultCode (Modbus fault (typed BI despite 'Code' in the name)).

How do I enable BMS control of the CaptiveAire Self Cleaning System (SCS) Control Panel?

Fans may be started via BACnet, LonWorks or CASlink, but fan and light zones only exist when the wash operation is set to Local; in Remote wash the ECPM03 only monitors. With 'Lights With Fan' enabled the lights follow the fans; otherwise the HMI button or BMS can switch them.

How do I check these points on the real Self Cleaning System (SCS) Control Panel?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.