 "manufacturer": "CaptiveAire",
 "manufacturer_slug": "captiveaire",
 "model": "Paragon RTU / DOAS DDC (Protocessor BACnet)",
 "model_slug": "paragon-rtu-doas-ddc",
 "aliases": [
  "Paragon",
  "CaptiveAire DOAS",
  "CaptiveAire RTU",
  "Protocessor",
  "CN0861",
  "RTU DDC Points"
 ],
 "equipment_type": "Rooftop unit / DOAS controller",
 "applies_to": "CaptiveAire Paragon HVAC series packaged rooftop units and dedicated outdoor air systems with the factory DDC package.",
 "summary": "CaptiveAire's Paragon rooftop units and DOAS are run by the unit's own controller board; BACnet comes from a factory-mounted Protocessor gateway in the control panel, set up at the factory for either BACnet IP (Ethernet) or BACnet MS/TP (RS-485). The 300 objects cover DDC commands, occupied/unoccupied setpoints, the on-board schedule, mode selections, sensor readings, compressor/ERV data and six active fault codes. The simplest BMS control is to enable scheduling once, set the on-board schedule to unoccupied (1440) and drive BV-5 DDCOccupiedOverride.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": 50001,
 "access_inferred": false,
 "notes": [
  "Protocessor defaults: device instance 50001, MS/TP MAC 51, 38400 baud, Max Master 127, IP 192.168.1.24; increment instance/MAC per unit.",
  "For BMS occupancy control set BV-216 SchedulingEnabledFlag on once, set schedule AVs 46-87 to 1440 (no schedule), then write BV-5.",
  "DDC heat/cool/blower commands (BV-1..3, AV-4) only act when the tempering mode AVs (217-220) are set to DDC (3).",
  "Fault AIs 210-215 return codes from the guide's fault table; temperatures follow the unit's F/C setting. The guide lists no engineering units.",
  "Access comes from the guide's Control/Monitor vs Monitor Only column; BI-294..296 are listed as Control/Monitor but are inputs, so shown read-only here.",
  "Points depend on unit options (gas/electric heat, DX stages, ERV, economizer); unused ones read zero or are meaningless."
 ],
 "source": {
  "title": "DDC Application Guide for Paragon HVAC Series (RTU DDC Points)",
  "doc_number": null,
  "revision_date": "2026-09",
  "url": "https://www.captiveaire.com/CatalogContent/Fans/RTU_DOAS/doc/rtu-ddc-guide.pdf"
 },
 "integration": {
  "summary": "Turn on scheduling once (BV-216), set every on-board schedule slot (AV-46..87) to 1440 so the unit is always unoccupied by its own clock, then command occupancy from the BMS with BV-5. Let the unit run on its own setpoints (intake/space/discharge, chosen by the Activate Based On and Tempering Mode AVs) and monitor UnitStatus, temperatures and the six fault-code AIs. Only use the raw DDC heat/cool/blower commands if the tempering modes are set to DDC.",
  "minimum_points": [
   {
    "ref": "BV 5",
    "name": "DDCOccupiedOverride",
    "why": "Occupied/unoccupied command from the BMS"
   },
   {
    "ref": "BV 216",
    "name": "SchedulingEnabledFlag",
    "why": "Must be on (once) for BV-5 to work"
   },
   {
    "ref": "AV 18",
    "name": "SpaceCoolOccSP",
    "why": "Occupied space cooling setpoint"
   },
   {
    "ref": "AV 8",
    "name": "SpaceHeatOccSP",
    "why": "Occupied space heating setpoint"
   },
   {
    "ref": "AI 139",
    "name": "UnitStatus",
    "why": "Idle / blower / heating / cooling state"
   },
   {
    "ref": "AI 140",
    "name": "CurrentOccupiedStatus",
    "why": "Confirms the occupancy command took effect"
   },
   {
    "ref": "AI 148",
    "name": "DischargeTemp",
    "why": "Discharge air temperature"
   },
   {
    "ref": "AI 141",
    "name": "AverageSpaceTemp",
    "why": "Space temperature the unit is controlling to"
   },
   {
    "ref": "AI 210",
    "name": "ActiveFault1",
    "why": "First active fault code"
   }
  ],
  "enable": "BMS occupancy control needs BV-216 SchedulingEnabledFlag on and all internal schedule AVs (46-87) at 1440; an occupied input always wins over unoccupied, so any non-1440 slot keeps the unit occupied regardless of BV-5. Direct heat/cool/blower commands (BV-1..3, AV-4) need the heat/cool tempering modes (AV-217..220) set to DDC (3).",
  "heartbeat": null,
  "remote_sensors": "A BMS space temperature can be written to AV-248 ExternalSpaceTempValue after enabling BV-247 ExternalSpaceTempEnable; space humidity likewise via BV-269 ExternalSpaceRhEnable and AV-270 ExternalSpaceRhValue. BV-280..283 act as virtual thermostat calls when Activate Based On is set to Stat (4). The Paragon IOM (A0033507 Rev 39) also lists Virtual Space Input (Temp/RH from the BMS, default Off) with an optional Input Timer (1-120 min, default 2) that falls back to the wired sensor when the BMS value goes stale.",
  "setup": [
   "Protocessor default device instance 50001, MS/TP MAC 51, 38400 baud, Max Master 127; the guide increments instance and MAC per unit number.",
   "Protocessor default IP 192.168.1.24 /255.255.255.0; web configurator login admin/admin (or the password printed by the Ethernet port).",
   "The gateway is factory set to either BACnet IP or MS/TP for the job; objects are only reachable on that port.",
   "Each changed gateway parameter needs its own Submit and a system restart."
  ],
  "gotchas": [
   "If any internal schedule slot is not 1440, BV-5 cannot turn the unit off during that slot.",
   "The controller board reboots when some factory settings are changed.",
   "Gas valve output reads 10 V both at high fire and when the unit is not heating.",
   "Setpoints used depend on Activate Based On (AV-221/222) and Tempering Mode (AV-217..220); unused setpoints have no effect.",
   "Blower speed AVs (88-91) must stay within the min/max speed limits in AV-228..235.",
   "Paragon IOM (A0033507 Rev 39): the HMI settings BMS User Write and BMS Factory Write, which allow BMS writes to user and factory settings, default to Disabled."
  ]
 },
 "points": [
  {
   "type": "BV",
   "instance": 1,
   "name": "DDCHeatCommand",
   "description": "Heating command. Requires heat tempering mode = DDC",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "DDCCoolCommand",
   "description": "Cooling command. Requires heat tempering mode = DDC",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "DDCBlowerCommand",
   "description": "Blower command. Requires both heat and cool tempering mode = DDC",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "DDCModulation",
   "description": "Heat modulation signal, 0-10V. 0V = low fire and 10V = high",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "DDCOccupiedOverride",
   "description": "Occupied override command, requires SchedulingEnabled = ON (1)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "IntakeHeatOccSP",
   "description": "Intake Heating Occupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "IntakeHeatUnoccSP",
   "description": "Intake Heating Unoccupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "SpaceHeatOccSP",
   "description": "Space Heating Occupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "SpaceHeatUnoccSP",
   "description": "Space Heating Unoccupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "MinDischargeHeatOccSP",
   "description": "Min Discharge Heating when occupied, relevant only if heat tempering mode =",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "MinDischargeHeatUnoccSP",
   "description": "Min Discharge Heating when unoccupied, relevant only if heat tempering mode =",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "DischargeHeatOccSP",
   "description": "Discharge heating setpoint when occupied, requires heat tempering mode = discharge",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "DischargeHeatUnoccSP",
   "description": "Discharge heating setpoint when unoccupied, requires heat tempering mode = discharge",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "MaxDischargeHeatOccSP",
   "description": "Max Discharge Heating when occupied, relevant only if heat tempering mode =",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "MaxDischargeHeatUnoccSP",
   "description": "Max Discharge Heating when unoccupied, relevant only if heat tempering mode =",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "IntakeCoolOccSP",
   "description": "Intake Cooling Occupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "IntakeCoolUnoccSP",
   "description": "Intake Cooling Unoccupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "SpaceCoolOccSP",
   "description": "Space Cooling Occupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "SpaceCoolUnoccSP",
   "description": "Space Cooling Unoccupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "MinDischargeCoolOccSP",
   "description": "Min Discharge Cooling setpoint when occupied, relevant only if cool tempering mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "MinDischargeCoolUnoccSP",
   "description": "Min Discharge Cooling setpoint when unoccupied, relevant only if cool tempering mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "DischargeCoolOccSP",
   "description": "Discharge Cooling setpoint when occupied, relevant only if cool tempering mode =",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "DischargeCoolUnoccSP",
   "description": "Discharge Cooling setpoint when unoccupied, relevant only if cool tempering mode =",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "MaxDischargeCoolOccSP",
   "description": "Max Discharge Cooling setpoint when occupied, relevant only if cool tempering mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "MaxDischargeCoolUnoccSP",
   "description": "Max Discharge Cooling setpoint when unoccupied, relevant only if cool tempering mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "RoomOverrideOccSP",
   "description": "Room Override Occupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "RoomOverrideUnoccSP",
   "description": "Room Override Unoccupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "FirestatIntakeSP",
   "description": "Firestat Intake Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "FirestatDischargeSP",
   "description": "Firestat Discharge Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "FreezestatSP",
   "description": "Freezestat Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "OverheatDischargeSP",
   "description": "Overheat Discharge Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "CabinetHeatSP",
   "description": "Cabinet Heat Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "FurnaceDrainHeatSP",
   "description": "Furnace Drain Heat Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "IntakeRhOccSP",
   "description": "Intake Relative Humidity Occupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "IntakeRhUnoccSP",
   "description": "Intake Relative Humidity Unoccupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "SpaceRhOccSP",
   "description": "Space Relative Humidity Occupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "SpaceRhUnoccSP",
   "description": "Space Relative Humidity Unoccupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "DischargeRhOccSP",
   "description": "Discharge Relative Humidity Occupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "DischargeRhUnoccSP",
   "description": "Discharge Relative Humidity Unoccupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "IntakeDpOccSP",
   "description": "Intake Dewpoint Occupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "IntakeDpUnoccSP",
   "description": "Intake Dewpoint Unoccupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "SpaceDpOccSP",
   "description": "Space Dewpoint Occupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "SpaceDpUnoccSP",
   "description": "Space Dewpoint Unoccupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "DischargeDpOccSP",
   "description": "Discharge Dewpoint Occupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "DischargeDpUnoccSP",
   "description": "Discharge Dewpoint Unoccupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "ScheduleSundayAStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "ScheduleSundayAEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "ScheduleSundayBStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "ScheduleSundayBEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "ScheduleSundayCStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "ScheduleSundayCEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "ScheduleMondayAStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "ScheduleMondayAEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "ScheduleMondayBStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "ScheduleMondayBEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "ScheduleMondayCStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "ScheduleMondayCEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "ScheduleTuesdayAStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "ScheduleTuesdayAEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "ScheduleTuesdayBStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "ScheduleTuesdayBEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "ScheduleTuesdayCStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "ScheduleTuesdayCEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "ScheduleWednesdayAStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "ScheduleWednesdayAEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "ScheduleWednesdayBStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "ScheduleWednesdayBEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "ScheduleWednesdayCStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "ScheduleWednesdayCEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "ScheduleThursdayAStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "ScheduleThursdayAEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "ScheduleThursdayBStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "ScheduleThursdayBEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "ScheduleThursdayCStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "ScheduleThursdayCEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 76,
   "name": "ScheduleFridayAStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 77,
   "name": "ScheduleFridayAEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 78,
   "name": "ScheduleFridayBStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "ScheduleFridayBEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "ScheduleFridayCStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "ScheduleFridayCEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "ScheduleSaturdayAStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 83,
   "name": "ScheduleSaturdayAEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "ScheduleSaturdayBStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "ScheduleSaturdayBEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "ScheduleSaturdayCStart",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 87,
   "name": "ScheduleSaturdayCEnd",
   "description": "Daily schedule start/end time in minutes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 88,
   "name": "BlowerManualFreqOcc",
   "description": "VFD frequency when occupied, requires blower control = VFD manual",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "BlowerManualFreqUnocc",
   "description": "VFD frequency when unoccupied, requires blower control = VFD manual",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 90,
   "name": "BlowerManualPwmRateOcc",
   "description": "ECM speed when occupied, requires blower control = ECM manual",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 91,
   "name": "BlowerManualPwmRateUnocc",
   "description": "ECM speed when unoccupied, requires blower control = ECM manual",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 92,
   "name": "MixingBoxManualOAOcc",
   "description": "Mixing Box Outdoor Air Percent during occupied times, requires mixing box mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 93,
   "name": "MixingBoxManualOAUnocc",
   "description": "Mixing Box Outdoor Air Percent during unoccupied times, requires mixing box mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 94,
   "name": "EconomizerTempSPOcc",
   "description": "Economizer Temperature Setpoint Occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 95,
   "name": "EconomizerTempSPUnocc",
   "description": "Economizer Temperature Setpoint Unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 96,
   "name": "EconomizerTempBandOcc",
   "description": "Economizer Temperature Band Setpoint Occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 97,
   "name": "EconomizerTempBandUnocc",
   "description": "Economizer Temperature Band Setpoint Unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 98,
   "name": "EconomizerTotalBandOcc",
   "description": "Economizer Temperature Total Band Setpoint Occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 99,
   "name": "EconomizerTotalBandUnocc",
   "description": "Economizer Temperature Total Band Setpoint Unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 100,
   "name": "EconomizerRhSPOcc",
   "description": "Economizer Relative Humidity Setpoint Occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "EconomizerRhSPUnocc",
   "description": "Economizer Relative Humidity Setpoint Unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "MixingBoxManualVoltsOcc",
   "description": "Mixing Box damper voltage during occupied times, requires mixing box mode =",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "MixingBoxManualVoltsUnocc",
   "description": "Mixing Box damper voltage during unoccupied times, requires mixing box mode =",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "BlowerPsSpLowOcc",
   "description": "Blower Low Static Pressure Setting Occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 105,
   "name": "BlowerPsSpLowUnocc",
   "description": "Blower Low Static Pressure Setting Unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 106,
   "name": "BlowerPsSpHighOcc",
   "description": "Blower High Static Pressure Setting Occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 107,
   "name": "BlowerPsSpHighUnocc",
   "description": "Blower High Static Pressure Setting Unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 108,
   "name": "DryModeDischTempSPOcc",
   "description": "Dry Mode Discharge Occupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "DryModeDischTempSPUnocc",
   "description": "Dry Mode Discharge Unoccupied Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 110,
   "name": "OaResetLowTempSp",
   "description": "Outdoor Air Reset Low Temperature Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "OaResetHighTempSp",
   "description": "Outdoor Air Reset High Temperature Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 112,
   "name": "OaResetHeatDischTempSp",
   "description": "Outdoor Air Reset Heat Discharge Temperature Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "OaResetCoolDischTempSp",
   "description": "Outdoor Air Reset Cool Discharge Temperature Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 114,
   "name": "OaResetHeatSpaceTempSp",
   "description": "Outdoor Air Reset Heat Space Temperature Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 115,
   "name": "OaResetCoolSpaceTempSp",
   "description": "Outdoor Air Reset Cool Space Temperature Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 116,
   "name": "CO2SensorPpmMin",
   "description": "CO2 PPM level at 0V",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 117,
   "name": "CO2SensorPpmMax",
   "description": "CO2 PPM level at 10V",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 118,
   "name": "CO2ThresholdLimitOcc",
   "description": "CO2 sensor threshold limit for the fan/damper to operate when occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 119,
   "name": "CO2ThresholdLimitUnocc",
   "description": "CO2 sensor threshold limit for the fan/damper to operate when unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 120,
   "name": "DynamicSpDiff",
   "description": "Dynamic Setpoint Differential",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 121,
   "name": "DynamicSpOffset",
   "description": "Dynamic Setpoint Differential Offset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 122,
   "name": "DynamicSpHeatOa",
   "description": "Dynamic Setpoint Heat Outdoor Air",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 123,
   "name": "DynamicSpCoolOa",
   "description": "Dynamic Setpoint Cool Outdoor Air",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 124,
   "name": "ErvWheelSpeed",
   "description": "Energy Wheel Speed Setting",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 125,
   "name": "ErvExhaustFanSpeedOcc",
   "description": "Energy Wheel Exhaust Fan Speed Occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 126,
   "name": "ErvExhaustFanSpeedUnocc",
   "description": "Energy Wheel Exhaust Fan Speed Unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 127,
   "name": "ErvExhaustLowPsSpOcc",
   "description": "Energy Wheel Exhaust Low Pressure Setpoint Occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 128,
   "name": "ErvExhaustLowPsSpUnocc",
   "description": "Energy Wheel Exhaust Low Pressure Setpoint Unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 129,
   "name": "ErvExhaustHighPsSpOcc",
   "description": "Energy Wheel Exhaust High Pressure Setpoint Occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 130,
   "name": "ErvExhaustHighPsSpUnocc",
   "description": "Energy Wheel Exhaust High Pressure Setpoint Unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 131,
   "name": "CO2OverrideHighLimitOcc",
   "description": "CO2 high limit setting at which fan/damper will operate occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 132,
   "name": "CO2OverrideLowLimitOcc",
   "description": "CO2 low limit setting at which fan/damper will operate occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 133,
   "name": "CO2OverrideHighLimitUnocc",
   "description": "CO2 high limit setting at which fan/damper will operate unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 134,
   "name": "CO2OverrideLowLimitUnocc",
   "description": "CO2 low limit setting at which fan/damper will operate unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 135,
   "name": "DryModeOASP",
   "description": "Dry Mode Outdoor Air Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 136,
   "name": "DryModeCoolSP",
   "description": "Dry Mode Cool Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 137,
   "name": "PoweredExhaustManVoltsOcc",
   "description": "Powered Exhaust PWM Setpoint Occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 138,
   "name": "PoweredExhaustManVoltsUnocc",
   "description": "Powered Exhaust PWM Setpoint Unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 139,
   "name": "UnitStatus",
   "description": "HVAC State (Idle = 0, Blower = 1, Heating = 2, Cooling",
   "units": "",
   "access": "R",
   "states": "0=Idle, 1=Blower, 2=Heating, 3=Cooling"
  },
  {
   "type": "AI",
   "instance": 140,
   "name": "CurrentOccupiedStatus",
   "description": "Occupancy status, occupied = 1, unoccupied = 0",
   "units": "",
   "access": "R",
   "states": "0=Unoccupied, 1=Occupied"
  },
  {
   "type": "AI",
   "instance": 141,
   "name": "AverageSpaceTemp",
   "description": "Average Space Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 142,
   "name": "BlowerFrequency",
   "description": "Blower VFD Frequency",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 143,
   "name": "BlowerCurrent",
   "description": "Blower VFD Current",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 144,
   "name": "BlowerPower",
   "description": "Blower VFD Power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 145,
   "name": "AverageRh",
   "description": "Average space relative humidity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 146,
   "name": "OutdoorTemp",
   "description": "Outdoor Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 147,
   "name": "ReturnTemp",
   "description": "Return Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 148,
   "name": "DischargeTemp",
   "description": "Discharge Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 149,
   "name": "IntakeTemp",
   "description": "Intake Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 150,
   "name": "SpaceTemp",
   "description": "Space Temperature (thermistor)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 151,
   "name": "Hmi1Temp",
   "description": "Unit HMI temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 152,
   "name": "Hmi2Temp",
   "description": "Remote HMI 1 Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 153,
   "name": "Hmi3Temp",
   "description": "Remote HMI 2 Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 154,
   "name": "Hmi4Temp",
   "description": "Remote HMI 3 Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 155,
   "name": "Hmi5Temp",
   "description": "Remote HMI 4 Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 156,
   "name": "SuctionLineTemp",
   "description": "Suction Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 157,
   "name": "LiquidLineTemp",
   "description": "Liquid Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 158,
   "name": "EvapIndoorCoilTemp",
   "description": "Evaporator Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 159,
   "name": "CondOutdoorCoilTemp",
   "description": "Condenser Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 160,
   "name": "CompressorDischargeTemp",
   "description": "Compressor Discharge Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 161,
   "name": "IntakeRh",
   "description": "Intake Sensor Relative Humidity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 162,
   "name": "SpaceRh",
   "description": "Space Sensor Relative Humidity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 163,
   "name": "OutdoorRh",
   "description": "Outdoor Sensor Relative Humidity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 164,
   "name": "DischargeRh",
   "description": "Discharge Sensor Relative Humidity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 165,
   "name": "ReturnRh",
   "description": "Return Sensor Relative Humidity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 166,
   "name": "SuctionLinePs",
   "description": "Suction Line Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 167,
   "name": "DischargeLinePs",
   "description": "Discharge Line Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 168,
   "name": "LiquidLinePs",
   "description": "Liquid Line Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 169,
   "name": "Hmi1Rh",
   "description": "Unit HMI Relative Humidity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 170,
   "name": "Hmi2Rh",
   "description": "Remote HMI 1 Relative Humidity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 171,
   "name": "Hmi3Rh",
   "description": "Remote HMI 2 Relative Humidity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 172,
   "name": "Hmi4Rh",
   "description": "Remote HMI 3 Relative Humidity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 173,
   "name": "Hmi5Rh",
   "description": "Remote HMI 4 Relative Humidity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 174,
   "name": "SupplyPwmRate",
   "description": "PWM Signal to Supply Fan",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 175,
   "name": "ExhaustPwmRate",
   "description": "PWM Signal to Exhaust Fan",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 176,
   "name": "CondFan1PwmRate",
   "description": "PWM Signal to set #1 of Condensing Fans",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 177,
   "name": "CondFan2PwmRate",
   "description": "PWM Signal to set #2 of Condensing Fans",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 178,
   "name": "ModulatingGasValve1Output",
   "description": "Controller output to the modulating gas valve #1. 0V = Low Fire",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 179,
   "name": "ModulatingGasValve2Output",
   "description": "Controller output to the modulating gas valve #2. 0V = Low Fire",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 180,
   "name": "AdjustableDamperOutput",
   "description": "Output Voltage to Damper",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 181,
   "name": "ElectricHeaterOutput",
   "description": "Output Voltage to Electric Heater",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 182,
   "name": "OilBoostActiveFlag",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Oil Boost Not Active, 1=Oil Boost Active"
  },
  {
   "type": "BI",
   "instance": 183,
   "name": "ReheatActiveFlag",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Reheat Not Active, 1=Reheat Active"
  },
  {
   "type": "BI",
   "instance": 184,
   "name": "DefrostActiveFlag",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Defrost Not Active, 1=Defrost Active"
  },
  {
   "type": "BI",
   "instance": 185,
   "name": "PumpdownOffActiveFlag",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Pumpdown Off Not Active, 1=Pumpdown Off Active"
  },
  {
   "type": "BI",
   "instance": 186,
   "name": "PumpdownOnActiveFlag",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Pumpdown On Not Active, 1=Pumpdown On Active"
  },
  {
   "type": "AI",
   "instance": 187,
   "name": "ReheatValvePosition",
   "description": "Percentage of the Reheat Valve's Position",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 188,
   "name": "EevValvePosition",
   "description": "Percentage of the EEV Valve's Position",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 189,
   "name": "IntakeDpActual",
   "description": "Actual Intake Dew Point Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 190,
   "name": "SpaceDpActual",
   "description": "Actual Space Dew Point Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 191,
   "name": "CompressorPower",
   "description": "Compressor Power Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 192,
   "name": "CompressorFrequency",
   "description": "Compressor Frequency Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 193,
   "name": "CompressorCurrent",
   "description": "Compressor Current Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 194,
   "name": "ERVExhaustAirRh",
   "description": "ERV Exhaust Air Relative Humidity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 195,
   "name": "ERVWheelSupplyPsInches",
   "description": "ERV Wheel Supply Pressure Differential",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 196,
   "name": "ERVWheelExhPsInches",
   "description": "ERV Wheel Exhaust Pressure Differential",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 197,
   "name": "ERVExhCtrlVolts",
   "description": "0-10 Volt ERV Exhaust Speed Control",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 198,
   "name": "ERVExhAirTemp",
   "description": "ERV Exhaust Air Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 199,
   "name": "ERVOutsideAirRh",
   "description": "ERV Outside Air Relative Humidity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 200,
   "name": "ERVOutsideAirTemp",
   "description": "ERV Outside Air Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 201,
   "name": "ERVExhBlowerDutyCycle",
   "description": "PWM Signal to Exhaust Fan ECM",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 202,
   "name": "ERVExhBlowerPwmEnable",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AI",
   "instance": 203,
   "name": "ERVWheelDutyCycle",
   "description": "PWM Signal to ERV Wheel ECM",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 204,
   "name": "ERVWheelPwmEnable",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AI",
   "instance": 205,
   "name": "ERVState",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Idle, 5=Defrost, 6=Clean, 7=Test, 8=Stop"
  },
  {
   "type": "AI",
   "instance": 206,
   "name": "ERVAppliedWheelSpeed",
   "description": "Desired Energy Wheel Fan Speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 207,
   "name": "ERVAppliedExhFanSpeed",
   "description": "Desired ERV Exhaust Fan Speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 208,
   "name": "Subcool",
   "description": "Subcool Readings",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 209,
   "name": "Superheat",
   "description": "Superheat Readings",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 210,
   "name": "ActiveFault1",
   "description": "Active Fault Code (see fault code table)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 211,
   "name": "ActiveFault2",
   "description": "Active Fault Code (see fault code table)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 212,
   "name": "ActiveFault3",
   "description": "Active Fault Code (see fault code table)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 213,
   "name": "ActiveFault4",
   "description": "Active Fault Code (see fault code table)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 214,
   "name": "ActiveFault5",
   "description": "Active Fault Code (see fault code table)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 215,
   "name": "ActiveFault6",
   "description": "Active Fault Code (see fault code table)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 216,
   "name": "SchedulingEnabledFlag",
   "description": "Enable scheduling. Not an occupancy command. Refer to ID 5 “DDCOccupiedOverride” to",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 217,
   "name": "HeatTemperModeOcc",
   "description": "Heat tempering mode during occupied time",
   "units": "",
   "access": "W",
   "states": "0=Discharge, 1=Space, 2=BAS, 3=DDC"
  },
  {
   "type": "AV",
   "instance": 218,
   "name": "HeatTemperModeUnocc",
   "description": "Heat tempering mode during unoccupied time",
   "units": "",
   "access": "W",
   "states": "0=Discharge, 1=Space, 2=BAS, 3=DDC"
  },
  {
   "type": "AV",
   "instance": 219,
   "name": "CoolTemperModeOcc",
   "description": "Cool tempering mode during occupied time",
   "units": "",
   "access": "W",
   "states": "0=Discharge, 1=Space, 2=BAS, 3=DDC"
  },
  {
   "type": "AV",
   "instance": 220,
   "name": "CoolTemperModeUnocc",
   "description": "Cool tempering mode during unoccupied time",
   "units": "",
   "access": "W",
   "states": "0=Discharge, 1=Space, 2=BAS, 3=DDC"
  },
  {
   "type": "AV",
   "instance": 221,
   "name": "ActivateOnOcc",
   "description": "\"Activate based on\" during occupied time",
   "units": "",
   "access": "W",
   "states": "0=Intake, 1=Space, 2=Both, 3=Either, 4=Stat"
  },
  {
   "type": "AV",
   "instance": 222,
   "name": "ActivateOnUnocc",
   "description": "\"Activate based on\" during unoccupied time",
   "units": "",
   "access": "W",
   "states": "0=Intake, 1=Space, 2=Both, 3=Either, 4=Stat"
  },
  {
   "type": "AV",
   "instance": 223,
   "name": "BlowerModeOcc",
   "description": "Blower mode during occupied times",
   "units": "",
   "access": "W",
   "states": "0=Auto, 1=Off, 2=On"
  },
  {
   "type": "AV",
   "instance": 224,
   "name": "BlowerModeUnocc",
   "description": "Blower mode during unoccupied times",
   "units": "",
   "access": "W",
   "states": "0=Auto, 1=Off, 2=On"
  },
  {
   "type": "AV",
   "instance": 225,
   "name": "MixingBoxMode",
   "description": "Mixing Box mode selection",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=Manual, 2=Position, 3=OAPercent, 4=AnalogCtrl, 5=PS, 6=100% OA"
  },
  {
   "type": "AV",
   "instance": 226,
   "name": "ReheatDPAdjOcc",
   "description": "Reheat Dew Point adjust setpoint value when occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 227,
   "name": "ReheatDPAdjUnocc",
   "description": "Reheat Dew Point adjust setpoint value when unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 228,
   "name": "BlowerVfdMinFreqOcc",
   "description": "Min blower VFD Frequency when occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 229,
   "name": "BlowerVfdMinFreqUnocc",
   "description": "Min blower VFD Frequency when unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 230,
   "name": "BlowerVfdMaxFreqOcc",
   "description": "Max blower VFD Frequency when occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 231,
   "name": "BlowerVfdMaxFreqUnocc",
   "description": "Max blower VFD Frequency when unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 232,
   "name": "BlowerPwmMinRateOcc",
   "description": "Min blower ECM speed when occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 233,
   "name": "BlowerPwmMinRateUnocc",
   "description": "Min blower ECM speed when unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 234,
   "name": "BlowerPwmMaxRateOcc",
   "description": "Max blower ECM speed when occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 235,
   "name": "BlowerPwmMaxRateUnocc",
   "description": "Max blower ECM speed when unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 236,
   "name": "MixingBoxMinOAPercentOcc",
   "description": "Min occupied outdoor air percent when mixing box mode = outdoor air",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 237,
   "name": "MixingBoxMinOAPercentUnocc",
   "description": "Min unoccupied outdoor air percent when mixing box mode = outdoor air",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 238,
   "name": "MixingBoxMaxOAPercentOcc",
   "description": "Max occupied outdoor air percent when mixing box mode = outdoor air",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 239,
   "name": "MixingBoxMaxOAPercentUnocc",
   "description": "Max unoccupied outdoor air percent when mixing box mode = outdoor air",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 240,
   "name": "MixingBoxMinVoltsOcc",
   "description": "Max unoccupied mixing box voltage when mixing box mode = manual",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 241,
   "name": "MixingBoxMinVoltsUnocc",
   "description": "Min unoccupied mixing box voltage when mixing box mode = manual",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 242,
   "name": "MixingBoxMaxVoltsOcc",
   "description": "Max occupied mixing box voltage when mixing box mode = manual",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 243,
   "name": "MixingBoxMaxVoltsUnocc",
   "description": "Max unoccupied mixing box voltage when mixing box mode = manual",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 244,
   "name": "CFMReading",
   "description": "Fan CFM Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 245,
   "name": "PressureSensor1",
   "description": "Duct Static Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 246,
   "name": "CO2Reading",
   "description": "CO2 Reading in PPM",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 247,
   "name": "ExternalSpaceTempEnable",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 248,
   "name": "ExternalSpaceTempValue",
   "description": "Virtual Space Temperature Value, 1 decimal",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 249,
   "name": "Stg2CompressorPower",
   "description": "Stage 2 Compressor Power Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 250,
   "name": "Stg2CompressorFrequency",
   "description": "Stage 2 Compressor Frequency Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 251,
   "name": "Stg2CompressorCurrent",
   "description": "Stage 2 Compressor Current Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 252,
   "name": "Stg3CompressorPower",
   "description": "Stage 3 Compressor Power Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 253,
   "name": "Stg3CompressorFrequency",
   "description": "Stage 3 Compressor Frequency Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 254,
   "name": "Stg3CompressorCurrent",
   "description": "Stage 3 Compressor Current Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 255,
   "name": "Stg2OilBoostActiveFlag",
   "description": "Stage 2",
   "units": "",
   "access": "R",
   "states": "0=Oil Boost Not Active, 1=Oil Boost Active"
  },
  {
   "type": "BI",
   "instance": 256,
   "name": "Stg2ReheatActiveFlag",
   "description": "Stage 2",
   "units": "",
   "access": "R",
   "states": "0=Reheat Not Active, 1=Reheat Active"
  },
  {
   "type": "BI",
   "instance": 257,
   "name": "Stg2DefrostActiveFlag",
   "description": "Stage 2",
   "units": "",
   "access": "R",
   "states": "0=Defrost Not Active, 1=Defrost Active"
  },
  {
   "type": "BI",
   "instance": 258,
   "name": "Stg2PumpdownOffActiveFlag",
   "description": "Stage 2",
   "units": "",
   "access": "R",
   "states": "0=Pumpdown Off Not Active, 1=Pumpdown Off Active"
  },
  {
   "type": "BI",
   "instance": 259,
   "name": "Stg2PumpdownOnActiveFlag",
   "description": "Stage 2",
   "units": "",
   "access": "R",
   "states": "0=Pumpdown On Not Active, 1=Pumpdown On Active"
  },
  {
   "type": "AI",
   "instance": 260,
   "name": "Stg2ReheatValvePosition",
   "description": "Stage 2 Percentage of the Reheat Valve's Position",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 261,
   "name": "Stg2EevValvePosition",
   "description": "Stage 2 Percentage of the EEV Valve's Position",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 262,
   "name": "Stg3OilBoostActiveFlag",
   "description": "Stage 3",
   "units": "",
   "access": "R",
   "states": "0=Oil Boost Not Active, 1=Oil Boost Active"
  },
  {
   "type": "AI",
   "instance": 263,
   "name": "Stg3ReheatActiveFlag",
   "description": "Stage 3",
   "units": "",
   "access": "R",
   "states": "0=Reheat Not Active, 1=Reheat Active"
  },
  {
   "type": "AI",
   "instance": 264,
   "name": "Stg3DefrostActiveFlag",
   "description": "Stage 3",
   "units": "",
   "access": "R",
   "states": "0=Defrost Not Active, 1=Defrost Active"
  },
  {
   "type": "AI",
   "instance": 265,
   "name": "Stg3PumpdownOffActiveFlag",
   "description": "Stage 3",
   "units": "",
   "access": "R",
   "states": "0=Pumpdown Off Not Active, 1=Pumpdown Off Active"
  },
  {
   "type": "BI",
   "instance": 266,
   "name": "Stg3PumpdownOnActiveFlag",
   "description": "Stage 3",
   "units": "",
   "access": "R",
   "states": "0=Pumpdown On Not Active, 1=Pumpdown On Active"
  },
  {
   "type": "AI",
   "instance": 267,
   "name": "Stg3ReheatValvePosition",
   "description": "Stage 3 Percentage of the Reheat Valve's Position",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 268,
   "name": "Stg3EevValvePosition",
   "description": "Stage 3 Percentage of the EEV Valve's Position",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 269,
   "name": "ExternalSpaceRhEnable",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 270,
   "name": "ExternalSpaceRhValue",
   "description": "Virtual Relative Humidity Value, 1 decimal",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 271,
   "name": "PressureSensor2",
   "description": "Building Static Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 272,
   "name": "StaticOaPsLowOcc",
   "description": "Space Static Pressure Low Setpoint when occupied for Outdoor Air Damper control",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 273,
   "name": "StaticOaPsLowUnocc",
   "description": "Space Static Pressure Low Setpoint when unoccupied for Outdoor Air Damper control",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 274,
   "name": "StaticOaPsHighOcc",
   "description": "Space Static Pressure High Setpoint when occupied for Outdoor Air Damper control",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 275,
   "name": "StaticOaPsHighUnocc",
   "description": "Space Static Pressure High Setpoint when unoccupied for Outdoor Air Damper control",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 276,
   "name": "StaticPePsLowOcc",
   "description": "PS based Powered Exhaust control low set point when occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 277,
   "name": "StaticPePsLowUnocc",
   "description": "PS based Powered Exhaust control low set point when unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 278,
   "name": "StaticPePsHighOcc",
   "description": "PS based Powered Exhaust control high set point when occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 279,
   "name": "StaticPePsHighUnocc",
   "description": "PS based Powered Exhaust control high set point when unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 280,
   "name": "StatCtrlBlower",
   "description": "Virtual 'call for blower' for Activate On Stat",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 281,
   "name": "StatCtrlHeat",
   "description": "Virtual 'call for heat' for Activate On Stat",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 282,
   "name": "StatCtrlCool",
   "description": "Virtual 'call for cool' for Activate On Stat",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 283,
   "name": "StatCtrlDehumid",
   "description": "Virtual \"call for dehumidification\" for Activate On Stat",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=ON"
  },
  {
   "type": "AV",
   "instance": 284,
   "name": "CfmKFactor",
   "description": "Set K factor for airflow calculations",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 285,
   "name": "Hmi1TempOffset",
   "description": "Manual temperature offset (degrees) for HMI 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 286,
   "name": "Hmi2TempOffset",
   "description": "Manual temperature offset (degrees) for HMI 2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 287,
   "name": "Hmi3TempOffset",
   "description": "Manual temperature offset (degrees) for HMI 3",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 288,
   "name": "Hmi4TempOffset",
   "description": "Manual temperature offset (degrees) for HMI 4",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 289,
   "name": "Hmi1RhOffset",
   "description": "Manual relative humidity offset (percent) for HMI 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 290,
   "name": "Hmi2RhOffset",
   "description": "Manual relative humidity offset (percent) for HMI 2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 291,
   "name": "Hmi3RhOffset",
   "description": "Manual relative humidity offset (percent) for HMI 3",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 292,
   "name": "Hmi4RhOffset",
   "description": "Manual relative humidity offset (percent) for HMI 4",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 293,
   "name": "ReturnAsSpace",
   "description": "Use Return temperature as Space temperature",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=ON"
  },
  {
   "type": "BI",
   "instance": 294,
   "name": "FSC1GasON",
   "description": "Main Gas Valve Status - Stage 1",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 295,
   "name": "FSC2GasON",
   "description": "Main Gas Valve Status - Stage 2",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 296,
   "name": "EconomizerActive",
   "description": "Economizer Status",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "AV",
   "instance": 297,
   "name": "EconomizerTargetSpOcc",
   "description": "Target Economizer Setpoint, Occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 298,
   "name": "EconomizerTargetSpUnocc",
   "description": "Target Economizer Setpoint, Unoccupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 299,
   "name": "OaCFMReading",
   "description": "Calculated Outdoor Air CFM",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 300,
   "name": "ErvExhaustFanCfmReading",
   "description": "Calculated ERV Exhaust CFM",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/captiveaire/paragon-rtu-doas-ddc",