- Home
- BACnet points lists
- CaptiveAire
- Lighting Control System (ECPM03, Protocessor BACnet)
Lighting control panel (8 zones) · BACnet points list
CaptiveAire Lighting Control System (ECPM03, Protocessor BACnet) BACnet points list
Updated 6 November 2026
CaptiveAire's lighting control panel switches up to eight lighting zones from schedules, board inputs and HMI buttons. A factory-wired Protocessor gateway gives BACnet IP or BACnet MS/TP access. For each zone the BMS can trigger an override, return the zone to automatic, force it off or add two hours to the schedule; read-only flags show which commands are allowed right now, plus the board fuse and the panel's Auto/Off/Manual switch positions.
This page lists 81 BACnet objects for the CaptiveAire Lighting Control System (ECPM03, Protocessor BACnet) — 32 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CaptiveAire’s own free documentation, linked below.
- Manufacturer
- CaptiveAire
- Model
- Lighting Control System (ECPM03, Protocessor BACnet)
- Equipment
- Lighting control panel (8 zones)
- Equipment type
- Other equipment
- BACnet objects
- 81 (32 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 50000
- Also known as
- A0027767, Lighting Control System, ECPM03, CASlink lighting, CaptiveAire lighting control panel, Protocessor
Reference only, provided as-is: verify against CaptiveAire’s current documentation and the live device before use. Not official CaptiveAire information. Terms of use.
BMS integration notes: CaptiveAire Lighting Control System (ECPM03, Protocessor BACnet)
The Protocessor's device instance, MAC and baud are set in its web configurator; BACnet IP address in its network settings page. Each zone has four command BVs: Override (on for the override time), Auto (back to schedule), Force Off and Add Time. Check the matching 'Allowed' BIs and watch the fuse and panel switch inputs.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | Zone 1 Override | Zone 1 on for the override time | Write |
| BV 17 | Zone 1 Force Off | Force zone 1 off | Write |
| BV 9 | Zone 1 Auto | Return zone 1 to schedule control | Write |
| BV 25 | Zone 1 Add Time | Extend zone 1 schedule by 2 hours | Write |
| BI 66 | Check Panel Switch 1 | Zone 1 panel switch set to off | Read |
| BI 74 | Output On by Panel Switch 1 | Zone 1 output switched on by hand | Read |
| BI 65 | Board Fuse Blown | Control board fuse blown | Read |
Network setup
- Protocessor defaults: device instance 50000, MS/TP MAC 127, baud 38400, Max Master 127, IP 192.168.1.24.
- Change instance, MAC, baud and Max Master on the Protocessor web configurator (Configure > Profile Configuration); each change restarts the gateway.
- Change the IP address under Diagnostics and Debugging > Setup > Network Settings; a restart is needed.
- MS/TP connects to the gateway's RS-485 field port, BACnet IP to its field Ethernet port.
Watch out for
- The minimum list shows zone 1; zones 2-8 use the next instances in each block of eight.
- Override time is set on the HMI (up to two hours); Auto is needed to leave a forced state.
- Zones that are not configured on the panel do nothing.
CaptiveAire Lighting Control System (ECPM03, Protocessor BACnet) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 1 | Zone 1 Override | Zone 1: turn zone lights on for the override time | Write | 1=On, 0=Off | |
| BV | 2 | Zone 2 Override | Zone 2: turn zone lights on for the override time | Write | 1=On, 0=Off | |
| BV | 3 | Zone 3 Override | Zone 3: turn zone lights on for the override time | Write | 1=On, 0=Off | |
| BV | 4 | Zone 4 Override | Zone 4: turn zone lights on for the override time | Write | 1=On, 0=Off | |
| BV | 5 | Zone 5 Override | Zone 5: turn zone lights on for the override time | Write | 1=On, 0=Off | |
| BV | 6 | Zone 6 Override | Zone 6: turn zone lights on for the override time | Write | 1=On, 0=Off | |
| BV | 7 | Zone 7 Override | Zone 7: turn zone lights on for the override time | Write | 1=On, 0=Off | |
| BV | 8 | Zone 8 Override | Zone 8: turn zone lights on for the override time | Write | 1=On, 0=Off | |
| BVmin | 9 | Zone 1 Auto | Zone 1: return zone to board (schedule) control | Write | 1=On, 0=Off | |
| BV | 10 | Zone 2 Auto | Zone 2: return zone to board (schedule) control | Write | 1=On, 0=Off | |
| BV | 11 | Zone 3 Auto | Zone 3: return zone to board (schedule) control | Write | 1=On, 0=Off | |
| BV | 12 | Zone 4 Auto | Zone 4: return zone to board (schedule) control | Write | 1=On, 0=Off | |
| BV | 13 | Zone 5 Auto | Zone 5: return zone to board (schedule) control | Write | 1=On, 0=Off | |
| BV | 14 | Zone 6 Auto | Zone 6: return zone to board (schedule) control | Write | 1=On, 0=Off | |
| BV | 15 | Zone 7 Auto | Zone 7: return zone to board (schedule) control | Write | 1=On, 0=Off | |
| BV | 16 | Zone 8 Auto | Zone 8: return zone to board (schedule) control | Write | 1=On, 0=Off | |
| BVmin | 17 | Zone 1 Force Off | Zone 1: force zone off | Write | 1=Force off, 0=Off | |
| BV | 18 | Zone 2 Force Off | Zone 2: force zone off | Write | 1=Force off, 0=Off | |
| BV | 19 | Zone 3 Force Off | Zone 3: force zone off | Write | 1=Force off, 0=Off | |
| BV | 20 | Zone 4 Force Off | Zone 4: force zone off | Write | 1=Force off, 0=Off | |
| BV | 21 | Zone 5 Force Off | Zone 5: force zone off | Write | 1=Force off, 0=Off | |
| BV | 22 | Zone 6 Force Off | Zone 6: force zone off | Write | 1=Force off, 0=Off | |
| BV | 23 | Zone 7 Force Off | Zone 7: force zone off | Write | 1=Force off, 0=Off | |
| BV | 24 | Zone 8 Force Off | Zone 8: force zone off | Write | 1=Force off, 0=Off | |
| BVmin | 25 | Zone 1 Add Time | Zone 1: extend zone schedule by 2 hours | Write | 1=On, 0=Off | |
| BV | 26 | Zone 2 Add Time | Zone 2: extend zone schedule by 2 hours | Write | 1=On, 0=Off | |
| BV | 27 | Zone 3 Add Time | Zone 3: extend zone schedule by 2 hours | Write | 1=On, 0=Off | |
| BV | 28 | Zone 4 Add Time | Zone 4: extend zone schedule by 2 hours | Write | 1=On, 0=Off | |
| BV | 29 | Zone 5 Add Time | Zone 5: extend zone schedule by 2 hours | Write | 1=On, 0=Off | |
| BV | 30 | Zone 6 Add Time | Zone 6: extend zone schedule by 2 hours | Write | 1=On, 0=Off | |
| BV | 31 | Zone 7 Add Time | Zone 7: extend zone schedule by 2 hours | Write | 1=On, 0=Off | |
| BV | 32 | Zone 8 Add Time | Zone 8: extend zone schedule by 2 hours | Write | 1=On, 0=Off | |
| BI | 33 | OverrideAllowed Zone 1 | Shows whether this command is currently available for the zone | Read | ||
| BI | 34 | OverrideAllowed Zone 2 | Shows whether this command is currently available for the zone | Read | ||
| BI | 35 | OverrideAllowed Zone 3 | Shows whether this command is currently available for the zone | Read | ||
| BI | 36 | OverrideAllowed Zone 4 | Shows whether this command is currently available for the zone | Read | ||
| BI | 37 | OverrideAllowed Zone 5 | Shows whether this command is currently available for the zone | Read | ||
| BI | 38 | OverrideAllowed Zone 6 | Shows whether this command is currently available for the zone | Read | ||
| BI | 39 | OverrideAllowed Zone 7 | Shows whether this command is currently available for the zone | Read | ||
| BI | 40 | OverrideAllowed Zone 8 | Shows whether this command is currently available for the zone | Read | ||
| BI | 41 | AutoAllowed Zone 1 | Shows whether this command is currently available for the zone | Read | ||
| BI | 42 | AutoAllowed Zone 2 | Shows whether this command is currently available for the zone | Read | ||
| BI | 43 | AutoAllowed Zone 3 | Shows whether this command is currently available for the zone | Read | ||
| BI | 44 | AutoAllowed Zone 4 | Shows whether this command is currently available for the zone | Read | ||
| BI | 45 | AutoAllowed Zone 5 | Shows whether this command is currently available for the zone | Read | ||
| BI | 46 | AutoAllowed Zone 6 | Shows whether this command is currently available for the zone | Read | ||
| BI | 47 | AutoAllowed Zone 7 | Shows whether this command is currently available for the zone | Read | ||
| BI | 48 | AutoAllowed Zone 8 | Shows whether this command is currently available for the zone | Read | ||
| BI | 49 | ForceOFFAllowed Zone 1 | Shows whether this command is currently available for the zone | Read | ||
| BI | 50 | ForceOFFAllowed Zone 2 | Shows whether this command is currently available for the zone | Read | ||
| BI | 51 | ForceOFFAllowed Zone 3 | Shows whether this command is currently available for the zone | Read | ||
| BI | 52 | ForceOFFAllowed Zone 4 | Shows whether this command is currently available for the zone | Read | ||
| BI | 53 | ForceOFFAllowed Zone 5 | Shows whether this command is currently available for the zone | Read | ||
| BI | 54 | ForceOFFAllowed Zone 6 | Shows whether this command is currently available for the zone | Read | ||
| BI | 55 | ForceOFFAllowed Zone 7 | Shows whether this command is currently available for the zone | Read | ||
| BI | 56 | ForceOFFAllowed Zone 8 | Shows whether this command is currently available for the zone | Read | ||
| BI | 57 | AddTimeAllowed Zone 1 | Shows whether this command is currently available for the zone | Read | ||
| BI | 58 | AddTimeAllowed Zone 2 | Shows whether this command is currently available for the zone | Read | ||
| BI | 59 | AddTimeAllowed Zone 3 | Shows whether this command is currently available for the zone | Read | ||
| BI | 60 | AddTimeAllowed Zone 4 | Shows whether this command is currently available for the zone | Read | ||
| BI | 61 | AddTimeAllowed Zone 5 | Shows whether this command is currently available for the zone | Read | ||
| BI | 62 | AddTimeAllowed Zone 6 | Shows whether this command is currently available for the zone | Read | ||
| BI | 63 | AddTimeAllowed Zone 7 | Shows whether this command is currently available for the zone | Read | ||
| BI | 64 | AddTimeAllowed Zone 8 | Shows whether this command is currently available for the zone | Read | ||
| BImin | 65 | Board Fuse Blown | Control board fuse blown | Read | 1=Fuse blown, 0=Off | |
| BImin | 66 | Check Panel Switch 1 | Panel Auto/Off/Manual switch is off | Read | 1=Switch off, 0=Off | |
| BI | 67 | Check Panel Switch 2 | Panel Auto/Off/Manual switch is off | Read | 1=Switch off, 0=Off | |
| BI | 68 | Check Panel Switch 3 | Panel Auto/Off/Manual switch is off | Read | 1=Switch off, 0=Off | |
| BI | 69 | Check Panel Switch 4 | Panel Auto/Off/Manual switch is off | Read | 1=Switch off, 0=Off | |
| BI | 70 | Check Panel Switch 5 | Panel Auto/Off/Manual switch is off | Read | 1=Switch off, 0=Off | |
| BI | 71 | Check Panel Switch 6 | Panel Auto/Off/Manual switch is off | Read | 1=Switch off, 0=Off | |
| BI | 72 | Check Panel Switch 7 | Panel Auto/Off/Manual switch is off | Read | 1=Switch off, 0=Off | |
| BI | 73 | Check Panel Switch 8 | Panel Auto/Off/Manual switch is off | Read | 1=Switch off, 0=Off | |
| BImin | 74 | Output On by Panel Switch 1 | Output switched on manually at the panel | Read | 1=Manually on, 0=Off | |
| BI | 75 | Output On by Panel Switch 2 | Output switched on manually at the panel | Read | 1=Manually on, 0=Off | |
| BI | 76 | Output On by Panel Switch 3 | Output switched on manually at the panel | Read | 1=Manually on, 0=Off | |
| BI | 77 | Output On by Panel Switch 4 | Output switched on manually at the panel | Read | 1=Manually on, 0=Off | |
| BI | 78 | Output On by Panel Switch 5 | Output switched on manually at the panel | Read | 1=Manually on, 0=Off | |
| BI | 79 | Output On by Panel Switch 6 | Output switched on manually at the panel | Read | 1=Manually on, 0=Off | |
| BI | 80 | Output On by Panel Switch 7 | Output switched on manually at the panel | Read | 1=Manually on, 0=Off | |
| BI | 81 | Output On by Panel Switch 8 | Output switched on manually at the panel | Read | 1=Manually on, 0=Off |
No points match these filters.
Object ID lookup: CaptiveAire Lighting Control System point IDs by name
BV1Zone 1 OverrideBV2Zone 2 OverrideBV3Zone 3 OverrideBV4Zone 4 OverrideBV5Zone 5 OverrideBV6Zone 6 OverrideBV7Zone 7 OverrideBV8Zone 8 OverrideBV9Zone 1 AutoBV10Zone 2 AutoBV11Zone 3 AutoBV12Zone 4 AutoBV13Zone 5 AutoBV14Zone 6 AutoBV15Zone 7 AutoBV16Zone 8 AutoBV17Zone 1 Force OffBV18Zone 2 Force OffBV19Zone 3 Force OffBV20Zone 4 Force OffBV21Zone 5 Force OffBV22Zone 6 Force OffBV23Zone 7 Force OffBV24Zone 8 Force OffBV25Zone 1 Add TimeBV26Zone 2 Add TimeBV27Zone 3 Add TimeBV28Zone 4 Add TimeBV29Zone 5 Add TimeBV30Zone 6 Add TimeBV31Zone 7 Add TimeBV32Zone 8 Add TimeBI33OverrideAllowed Zone 1BI34OverrideAllowed Zone 2BI35OverrideAllowed Zone 3BI36OverrideAllowed Zone 4BI37OverrideAllowed Zone 5BI38OverrideAllowed Zone 6BI39OverrideAllowed Zone 7BI40OverrideAllowed Zone 8BI41AutoAllowed Zone 1BI42AutoAllowed Zone 2BI43AutoAllowed Zone 3BI44AutoAllowed Zone 4BI45AutoAllowed Zone 5BI46AutoAllowed Zone 6BI47AutoAllowed Zone 7BI48AutoAllowed Zone 8BI49ForceOFFAllowed Zone 1BI50ForceOFFAllowed Zone 2BI51ForceOFFAllowed Zone 3BI52ForceOFFAllowed Zone 4BI53ForceOFFAllowed Zone 5BI54ForceOFFAllowed Zone 6BI55ForceOFFAllowed Zone 7BI56ForceOFFAllowed Zone 8BI57AddTimeAllowed Zone 1BI58AddTimeAllowed Zone 2BI59AddTimeAllowed Zone 3BI60AddTimeAllowed Zone 4BI61AddTimeAllowed Zone 5BI62AddTimeAllowed Zone 6BI63AddTimeAllowed Zone 7BI64AddTimeAllowed Zone 8BI65Board Fuse BlownBI66Check Panel Switch 1BI67Check Panel Switch 2BI68Check Panel Switch 3BI69Check Panel Switch 4BI70Check Panel Switch 5BI71Check Panel Switch 6BI72Check Panel Switch 7BI73Check Panel Switch 8BI74Output On by Panel Switch 1BI75Output On by Panel Switch 2BI76Output On by Panel Switch 3BI77Output On by Panel Switch 4BI78Output On by Panel Switch 5BI79Output On by Panel Switch 6BI80Output On by Panel Switch 7BI81Output On by Panel Switch 8
Integration notes
- The table has no read/write column; the zone command BVs are shown as writable and the BIs as read-only.
- Each 'Allowed' BI shows whether the matching zone command (override, auto, force off, add time) is currently allowed.
- The description column in the manual repeats the zone number as the active value (e.g. '3 = Zone ON'); the state texts here read 1 = on.
- The Protocessor is set up at the factory for the jobsite protocol; objects are only reachable on that port.
- Source: BACnet IP and BACnet MS/TP Points table, manual pages 23-24 (81 objects).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Lighting Control System (ECPM03, Protocessor BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the CaptiveAire Lighting Control System (ECPM03, Protocessor BACnet)
How many BACnet points does the CaptiveAire Lighting Control System (ECPM03, Protocessor BACnet) have?
This list has 81 BACnet objects: 49 binary inputs, 32 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which CaptiveAire Lighting Control System (ECPM03, Protocessor BACnet) BACnet points are writable?
32 of the 81 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official CaptiveAire Lighting Control System (ECPM03, Protocessor BACnet) BACnet documentation?
The source is Lighting Control System - Installation, Operation, and Maintenance Manual (A0027767), revision February 2025 Rev 6, published free by CaptiveAire at https://captiveaire.com/manuals/electrical/lighting-control-oim.pdf.
What are the minimum BACnet points to integrate the CaptiveAire Lighting Control System (ECPM03, Protocessor BACnet)?
Start with BV 1 Zone 1 Override (Zone 1 on for the override time); BV 17 Zone 1 Force Off (Force zone 1 off); BV 9 Zone 1 Auto (Return zone 1 to schedule control); BV 25 Zone 1 Add Time (Extend zone 1 schedule by 2 hours); BI 66 Check Panel Switch 1 (Zone 1 panel switch set to off); BI 74 Output On by Panel Switch 1 (Zone 1 output switched on by hand); BI 65 Board Fuse Blown (Control board fuse blown).
How do I check these points on the real Lighting Control System (ECPM03, Protocessor BACnet)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More CaptiveAire BACnet points lists
- Kitchen hood demand control ventilation (DCV) controller (exhaust and make-up air fans)
CaptiveAire DCV Package DDC (Protocessor BACnet)
CaptiveAire demand control ventilation packages that run kitchen hood exhaust and supply (make-up air) fans, with the factory BACnet option.
Also known as: CaptiveAire DCV, Demand Control Ventilation, DCV Packages Network, Kitchen hood DCV, CASlink, Protocessor, CN0861 - Make-up air heater / tempered air unit DDC controller
CaptiveAire Direct Digital Controls (DDC) Heater Controller
CaptiveAire heater (make-up air) units shipped with the factory Direct Digital Controls (DDC) controller covered by IOM A0020659.
Also known as: A0020659, CaptiveAire DDC, DDC controller, ctrl_source - DOAS rooftop unit
CaptiveAire DOAS RTU Series packaged rooftop unit, legacy IBT controls (Protocessor BACnet)
CaptiveAire DOAS RTU Series packaged rooftop units built with the older IBT-based unit controls (listed as 'Paragon - IBT Controls (Legacy)').
Also known as: A0026936, CaptiveAire DOAS RTU, Paragon IBT controls (legacy), DOAS RTU Series, CaptiveAire DOAS, Protocessor - Kitchen hood exhaust / make-up air fan controller (demand control)
CaptiveAire EMSplus Kitchen Hood Exhaust Controls (BACnet IP)
CaptiveAire EMSplus kitchen ventilation control panels ordered with the BACnet IP communication option.
Also known as: EMSplus, EMS Plus, EMS+, A0017802, CaptiveAire EMSplus - HVLS / ventilation fan control panel (up to 10 fans)
CaptiveAire HVLS and General Ventilation Fan Control (ECPM03, Protocessor BACnet)
CaptiveAire HVLS and general ventilation fan control packages with the ECPM03 board and the factory Protocessor BACnet gateway.
Also known as: A0025729, CaptiveAire HVLS, HVLS fan control, High Volume Low Speed fan, ECPM03, CASlink HVLS, Protocessor - Make-up air unit (indirect gas-fired heater)
CaptiveAire Modular Indirect Fired Heater (IBT controls, Protocessor BACnet)
CaptiveAire modular indirect-fired make-up air heaters, modules and furnace inserts run by the IBT controller with the optional Protocessor BACnet gateway.
Also known as: A0016988, IBT heater, IBT board, Indirect Fired Bent Tube, Modular Indirect Fired Heater, Indirect Fired Module, Indirect Fired Furnace, Protocessor - Make-up air unit controller
CaptiveAire MUA Heater DDC (Protocessor BACnet)
CaptiveAire make-up air heater units (including direct-fired) with the factory DDC/BMS package.
Also known as: CaptiveAire make-up air, Direct fired MUA, Tempered make-up air, DDC Application Guide MUA - Rooftop unit / DOAS controller
CaptiveAire Paragon RTU / DOAS DDC (Protocessor BACnet)
CaptiveAire Paragon HVAC series packaged rooftop units and dedicated outdoor air systems with the factory DDC package.
Also known as: Paragon, CaptiveAire DOAS, CaptiveAire RTU, Protocessor, CN0861, RTU DDC Points - Kitchen hood self-cleaning wash system control panel
CaptiveAire Self Cleaning System (SCS) Control Panel
CaptiveAire Self Cleaning System panels that hot-water wash or cold-water mist kitchen exhaust hoods and plenums, and can also run the hood's fan and light zones.
Also known as: CaptiveAire SCS, Self Cleaning System, Hood wash panel, Hot Water Wash, Cold Water Mist, ECPM03, Protocessor
Source: Lighting Control System - Installation, Operation, and Maintenance Manual · A0027767 · rev. February 2025 Rev 6. Object names, instances and units are reproduced as published; descriptions are our own.