- HVLS and General Ventilation Fan Control (ECPM03, Protocessor BACnet)
HVLS / ventilation fan control panel (up to 10 fans) · BACnet points list
CaptiveAire HVLS and General Ventilation Fan Control (ECPM03, Protocessor BACnet) BACnet points list
Updated 12 November 2026
CaptiveAire's HVLS control package runs up to ten VFD-driven fans in up to ten groups, switching them from room temperature, HMI buttons or the BMS. A factory-wired Protocessor gateway gives BACnet IP or BACnet MS/TP access to temperatures, per-fan VFD data, group settings and fault flags. With DDC mode enabled the BMS can put each group in DDC Auto or DDC Manual, switch groups on and off, and set occupied speed and fan direction.
This page lists 307 BACnet objects for the CaptiveAire HVLS and General Ventilation Fan Control (ECPM03, Protocessor BACnet) — 40 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CaptiveAire’s own free documentation, linked below.
- Manufacturer
- CaptiveAire
- Model
- HVLS and General Ventilation Fan Control (ECPM03, Protocessor BACnet)
- Equipment
- HVLS / ventilation fan control panel (up to 10 fans)
- Equipment type
- Other equipment
- BACnet objects
- 307 (40 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 50000
- Also known as
- A0025729, CaptiveAire HVLS, HVLS fan control, High Volume Low Speed fan, ECPM03, CASlink HVLS, Protocessor
Reference only, provided as-is: verify against CaptiveAire’s current documentation and the live device before use. Not official CaptiveAire information. Terms of use.
BMS integration notes: CaptiveAire HVLS and General Ventilation Fan Control (ECPM03, Protocessor BACnet)
Enable DDC mode on the HVLS controller so start and stop commands come over the network. For each fan group, write ModeG to DDC Auto (the controller runs the fans from its temperature sensors) or DDC Manual, and in Manual write ButtonG to switch the group on or off. SpeedF sets the occupied speed in Hz; monitor StateVFD, frequency and the fault flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 288 | ModeG1 | Group 1: 0 = DDC Auto, 1 = DDC Manual | Write |
| BV 298 | ButtonG1 | Group 1 on/off in DDC Manual (1 = on) | Write |
| AV 268 | SpeedF1 | Group 1 occupied fan speed, Hz | Write |
| AI 55 | StateVFD1 | Fan 1 run state and reason code | Read |
| AI 45 | FrequencyF1 | Fan 1 VFD output frequency, Hz | Read |
| AI 1 | TempSensor1 | Room temperature, sensor 1 | Read |
| AI 85 | VFDFaultF1 | Fan 1 VFD fault code (0 = no fault) | Read |
| BI 175 | EmergencyShutdownG1 | Group 1 hard-wired emergency shutdown active | Read |
Enable & remote start
Set the controller's DDC Mode menu to ENABLED; then all fan start and stop commands come from the network. Per group, ModeG selects DDC Auto (temperature control) or DDC Manual (ButtonG on/off).
Network setup
- Protocessor default device instance 50000; MS/TP MAC 127 and 38400 baud by default, set in the Protocessor web configurator (Configure > Profile Configuration).
- Protocessor default IP 192.168.1.24; change it under Diagnostics and Debugging > Setup > Network Settings, then restart.
- The Protocessor is factory set to one field protocol; objects are reachable only on that port.
Watch out for
- Each change in the Protocessor web configurator needs its own Submit and restarts the gateway.
- Group settings use one implied decimal (725 = 72.5 °F).
- Objects for fans or groups that are not installed still appear in the list.
CaptiveAire HVLS and General Ventilation Fan Control (ECPM03, Protocessor BACnet) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | TempSensor1 | Room temperature sensor 1 | Read | ||
| AI | 2 | TempSensor2 | Room temperature sensor 2 | Read | ||
| AI | 3 | TempSensor3 | Room temperature sensor 3 | Read | ||
| AI | 4 | TempSensor4 | Room temperature sensor 4 | Read | ||
| AI | 5 | TempSensor5 | Room temperature sensor 5 | Read | ||
| AI | 6 | TempSensor6 | Room temperature sensor 6 | Read | ||
| AI | 7 | TempSensor7 | Room temperature sensor 7 | Read | ||
| AI | 8 | TempSensor8 | Room temperature sensor 8 | Read | ||
| AI | 9 | EXPTemp1 | Expansion board room temperature 1 | Read | ||
| AI | 10 | EXPTemp2 | Expansion board room temperature 2 | Read | ||
| AI | 11 | EXPTemp3 | Expansion board room temperature 3 | Read | ||
| AI | 12 | EXPTemp4 | Expansion board room temperature 4 | Read | ||
| AI | 13 | EXPTemp5 | Expansion board room temperature 5 | Read | ||
| AI | 14 | EXPTemp6 | Expansion board room temperature 6 | Read | ||
| AI | 15 | EXPTemp7 | Expansion board room temperature 7 | Read | ||
| AI | 16 | EXPTemp8 | Expansion board room temperature 8 | Read | ||
| AI | 17 | EXPTemp9 | Expansion board room temperature 9 | Read | ||
| AI | 18 | EXPTemp10 | Expansion board room temperature 10 | Read | ||
| AI | 19 | EXPTemp11 | Expansion board room temperature 11 | Read | ||
| AI | 20 | EXPTemp12 | Expansion board room temperature 12 | Read | ||
| AI | 21 | EXPTemp13 | Expansion board room temperature 13 | Read | ||
| AI | 22 | EXPTemp14 | Expansion board room temperature 14 | Read | ||
| AI | 23 | EXPTemp15 | Expansion board room temperature 15 | Read | ||
| AI | 24 | EXPTemp16 | Expansion board room temperature 16 | Read | ||
| AI | 25 | HMITemp1 | HMI 1 temperature | Read | ||
| AI | 26 | HMIWiredTemp1 | Wired sensor temperature at HMI 1 | Read | ||
| AI | 27 | HMITemp2 | HMI 2 temperature | Read | ||
| AI | 28 | HMIWiredTemp2 | Wired sensor temperature at HMI 2 | Read | ||
| AI | 29 | HMITemp3 | HMI 3 temperature | Read | ||
| AI | 30 | HMIWiredTemp3 | Wired sensor temperature at HMI 3 | Read | ||
| AI | 31 | HMITemp4 | HMI 4 temperature | Read | ||
| AI | 32 | HMIWiredTemp4 | Wired sensor temperature at HMI 4 | Read | ||
| AI | 33 | HMITemp5 | HMI 5 temperature | Read | ||
| AI | 34 | HMIWiredTemp5 | Wired sensor temperature at HMI 5 | Read | ||
| AI | 35 | HMITemp6 | HMI 6 temperature | Read | ||
| AI | 36 | HMIWiredTemp6 | Wired sensor temperature at HMI 6 | Read | ||
| AI | 37 | HMITemp7 | HMI 7 temperature | Read | ||
| AI | 38 | HMIWiredTemp7 | Wired sensor temperature at HMI 7 | Read | ||
| AI | 39 | HMITemp8 | HMI 8 temperature | Read | ||
| AI | 40 | HMIWiredTemp8 | Wired sensor temperature at HMI 8 | Read | ||
| AI | 41 | HMITemp9 | HMI 9 temperature | Read | ||
| AI | 42 | HMIWiredTemp9 | Wired sensor temperature at HMI 9 | Read | ||
| AI | 43 | HMITemp10 | HMI 10 temperature | Read | ||
| AI | 44 | HMIWiredTemp10 | Wired sensor temperature at HMI 10 | Read | ||
| AImin | 45 | FrequencyF1 | Fan 1 VFD output frequency | Hz | Read | |
| AI | 46 | FrequencyF2 | Fan 2 VFD output frequency | Hz | Read | |
| AI | 47 | FrequencyF3 | Fan 3 VFD output frequency | Hz | Read | |
| AI | 48 | FrequencyF4 | Fan 4 VFD output frequency | Hz | Read | |
| AI | 49 | FrequencyF5 | Fan 5 VFD output frequency | Hz | Read | |
| AI | 50 | FrequencyF6 | Fan 6 VFD output frequency | Hz | Read | |
| AI | 51 | FrequencyF7 | Fan 7 VFD output frequency | Hz | Read | |
| AI | 52 | FrequencyF8 | Fan 8 VFD output frequency | Hz | Read | |
| AI | 53 | FrequencyF9 | Fan 9 VFD output frequency | Hz | Read | |
| AI | 54 | FrequencyF10 | Fan 10 VFD output frequency | Hz | Read | |
| AImin | 55 | StateVFD1 | Fan 1 run state / reason code | Read | 1=Off by temperature, 2=Off by high temp alarm, 3=Off by low temp alarm, 4=Off by emergency shutdown, 5=Off by manual mode timer expire, 6=On by temperature, 7=On by HMI command, 8=On by system bypass, 9=On by BMS 1, 10=On by BMS 2, 11=Off by HMI command | |
| AI | 56 | StateVFD2 | Fan 2 run state / reason code | Read | 1=Off by temperature, 2=Off by high temp alarm, 3=Off by low temp alarm, 4=Off by emergency shutdown, 5=Off by manual mode timer expire, 6=On by temperature, 7=On by HMI command, 8=On by system bypass, 9=On by BMS 1, 10=On by BMS 2, 11=Off by HMI command | |
| AI | 57 | StateVFD3 | Fan 3 run state / reason code | Read | 1=Off by temperature, 2=Off by high temp alarm, 3=Off by low temp alarm, 4=Off by emergency shutdown, 5=Off by manual mode timer expire, 6=On by temperature, 7=On by HMI command, 8=On by system bypass, 9=On by BMS 1, 10=On by BMS 2, 11=Off by HMI command | |
| AI | 58 | StateVFD4 | Fan 4 run state / reason code | Read | 1=Off by temperature, 2=Off by high temp alarm, 3=Off by low temp alarm, 4=Off by emergency shutdown, 5=Off by manual mode timer expire, 6=On by temperature, 7=On by HMI command, 8=On by system bypass, 9=On by BMS 1, 10=On by BMS 2, 11=Off by HMI command | |
| AI | 59 | StateVFD5 | Fan 5 run state / reason code | Read | 1=Off by temperature, 2=Off by high temp alarm, 3=Off by low temp alarm, 4=Off by emergency shutdown, 5=Off by manual mode timer expire, 6=On by temperature, 7=On by HMI command, 8=On by system bypass, 9=On by BMS 1, 10=On by BMS 2, 11=Off by HMI command | |
| AI | 60 | StateVFD6 | Fan 6 run state / reason code | Read | 1=Off by temperature, 2=Off by high temp alarm, 3=Off by low temp alarm, 4=Off by emergency shutdown, 5=Off by manual mode timer expire, 6=On by temperature, 7=On by HMI command, 8=On by system bypass, 9=On by BMS 1, 10=On by BMS 2, 11=Off by HMI command | |
| AI | 61 | StateVFD7 | Fan 7 run state / reason code | Read | 1=Off by temperature, 2=Off by high temp alarm, 3=Off by low temp alarm, 4=Off by emergency shutdown, 5=Off by manual mode timer expire, 6=On by temperature, 7=On by HMI command, 8=On by system bypass, 9=On by BMS 1, 10=On by BMS 2, 11=Off by HMI command | |
| AI | 62 | StateVFD8 | Fan 8 run state / reason code | Read | 1=Off by temperature, 2=Off by high temp alarm, 3=Off by low temp alarm, 4=Off by emergency shutdown, 5=Off by manual mode timer expire, 6=On by temperature, 7=On by HMI command, 8=On by system bypass, 9=On by BMS 1, 10=On by BMS 2, 11=Off by HMI command | |
| AI | 63 | StateVFD9 | Fan 9 run state / reason code | Read | 1=Off by temperature, 2=Off by high temp alarm, 3=Off by low temp alarm, 4=Off by emergency shutdown, 5=Off by manual mode timer expire, 6=On by temperature, 7=On by HMI command, 8=On by system bypass, 9=On by BMS 1, 10=On by BMS 2, 11=Off by HMI command | |
| AI | 64 | StateVFD10 | Fan 10 run state / reason code | Read | 1=Off by temperature, 2=Off by high temp alarm, 3=Off by low temp alarm, 4=Off by emergency shutdown, 5=Off by manual mode timer expire, 6=On by temperature, 7=On by HMI command, 8=On by system bypass, 9=On by BMS 1, 10=On by BMS 2, 11=Off by HMI command | |
| AI | 65 | AmperageF1 | Fan 1 motor current | A | Read | |
| AI | 66 | AmperageF2 | Fan 2 motor current | A | Read | |
| AI | 67 | AmperageF3 | Fan 3 motor current | A | Read | |
| AI | 68 | AmperageF4 | Fan 4 motor current | A | Read | |
| AI | 69 | AmperageF5 | Fan 5 motor current | A | Read | |
| AI | 70 | AmperageF6 | Fan 6 motor current | A | Read | |
| AI | 71 | AmperageF7 | Fan 7 motor current | A | Read | |
| AI | 72 | AmperageF8 | Fan 8 motor current | A | Read | |
| AI | 73 | AmperageF9 | Fan 9 motor current | A | Read | |
| AI | 74 | AmperageF10 | Fan 10 motor current | A | Read | |
| AI | 75 | PowerF1 | Fan 1 VFD power | kW | Read | |
| AI | 76 | PowerF2 | Fan 2 VFD power | kW | Read | |
| AI | 77 | PowerF3 | Fan 3 VFD power | kW | Read | |
| AI | 78 | PowerF4 | Fan 4 VFD power | kW | Read | |
| AI | 79 | PowerF5 | Fan 5 VFD power | kW | Read | |
| AI | 80 | PowerF6 | Fan 6 VFD power | kW | Read | |
| AI | 81 | PowerF7 | Fan 7 VFD power | kW | Read | |
| AI | 82 | PowerF8 | Fan 8 VFD power | kW | Read | |
| AI | 83 | PowerF9 | Fan 9 VFD power | kW | Read | |
| AI | 84 | PowerF10 | Fan 10 VFD power | kW | Read | |
| AImin | 85 | VFDFaultF1 | Fan 1 VFD fault code | Read | ||
| AI | 86 | VFDFaultF2 | Fan 2 VFD fault code | Read | ||
| AI | 87 | VFDFaultF3 | Fan 3 VFD fault code | Read | ||
| AI | 88 | VFDFaultF4 | Fan 4 VFD fault code | Read | ||
| AI | 89 | VFDFaultF5 | Fan 5 VFD fault code | Read | ||
| AI | 90 | VFDFaultF6 | Fan 6 VFD fault code | Read | ||
| AI | 91 | VFDFaultF7 | Fan 7 VFD fault code | Read | ||
| AI | 92 | VFDFaultF8 | Fan 8 VFD fault code | Read | ||
| AI | 93 | VFDFaultF9 | Fan 9 VFD fault code | Read | ||
| AI | 94 | VFDFaultF10 | Fan 10 VFD fault code | Read | ||
| AI | 95 | VFDLoadF1 | Fan 1 motor load, % of VFD output current | % | Read | |
| AI | 96 | VFDLoadF2 | Fan 2 motor load, % of VFD output current | % | Read | |
| AI | 97 | VFDLoadF3 | Fan 3 motor load, % of VFD output current | % | Read | |
| AI | 98 | VFDLoadF4 | Fan 4 motor load, % of VFD output current | % | Read | |
| AI | 99 | VFDLoadF5 | Fan 5 motor load, % of VFD output current | % | Read | |
| AI | 100 | VFDLoadF6 | Fan 6 motor load, % of VFD output current | % | Read | |
| AI | 101 | VFDLoadF7 | Fan 7 motor load, % of VFD output current | % | Read | |
| AI | 102 | VFDLoadF8 | Fan 8 motor load, % of VFD output current | % | Read | |
| AI | 103 | VFDLoadF9 | Fan 9 motor load, % of VFD output current | % | Read | |
| AI | 104 | VFDLoadF10 | Fan 10 motor load, % of VFD output current | % | Read | |
| AI | 105 | VFDTempF1 | Fan 1 VFD heat sink temperature | °C | Read | |
| AI | 106 | VFDTempF2 | Fan 2 VFD heat sink temperature | °C | Read | |
| AI | 107 | VFDTempF3 | Fan 3 VFD heat sink temperature | °C | Read | |
| AI | 108 | VFDTempF4 | Fan 4 VFD heat sink temperature | °C | Read | |
| AI | 109 | VFDTempF5 | Fan 5 VFD heat sink temperature | °C | Read | |
| AI | 110 | VFDTempF6 | Fan 6 VFD heat sink temperature | °C | Read | |
| AI | 111 | VFDTempF7 | Fan 7 VFD heat sink temperature | °C | Read | |
| AI | 112 | VFDTempF8 | Fan 8 VFD heat sink temperature | °C | Read | |
| AI | 113 | VFDTempF9 | Fan 9 VFD heat sink temperature | °C | Read | |
| AI | 114 | VFDTempF10 | Fan 10 VFD heat sink temperature | °C | Read | |
| AI | 115 | VFDVoltageF1 | Fan 1 VFD output voltage to motor | V | Read | |
| AI | 116 | VFDVoltageF2 | Fan 2 VFD output voltage to motor | V | Read | |
| AI | 117 | VFDVoltageF3 | Fan 3 VFD output voltage to motor | V | Read | |
| AI | 118 | VFDVoltageF4 | Fan 4 VFD output voltage to motor | V | Read | |
| AI | 119 | VFDVoltageF5 | Fan 5 VFD output voltage to motor | V | Read | |
| AI | 120 | VFDVoltageF6 | Fan 6 VFD output voltage to motor | V | Read | |
| AI | 121 | VFDVoltageF7 | Fan 7 VFD output voltage to motor | V | Read | |
| AI | 122 | VFDVoltageF8 | Fan 8 VFD output voltage to motor | V | Read | |
| AI | 123 | VFDVoltageF9 | Fan 9 VFD output voltage to motor | V | Read | |
| AI | 124 | VFDVoltageF10 | Fan 10 VFD output voltage to motor | V | Read | |
| AI | 125 | ModulationG1 | Group 1 modulation band setting | °F | Read | |
| AI | 126 | ModulationG2 | Group 2 modulation band setting | °F | Read | |
| AI | 127 | ModulationG3 | Group 3 modulation band setting | °F | Read | |
| AI | 128 | ModulationG4 | Group 4 modulation band setting | °F | Read | |
| AI | 129 | ModulationG5 | Group 5 modulation band setting | °F | Read | |
| AI | 130 | ModulationG6 | Group 6 modulation band setting | °F | Read | |
| AI | 131 | ModulationG7 | Group 7 modulation band setting | °F | Read | |
| AI | 132 | ModulationG8 | Group 8 modulation band setting | °F | Read | |
| AI | 133 | ModulationG9 | Group 9 modulation band setting | °F | Read | |
| AI | 134 | ModulationG10 | Group 10 modulation band setting | °F | Read | |
| AI | 135 | MinG1 | Group 1 minimum VFD frequency setting | Hz | Read | |
| AI | 136 | MinG2 | Group 2 minimum VFD frequency setting | Hz | Read | |
| AI | 137 | MinG3 | Group 3 minimum VFD frequency setting | Hz | Read | |
| AI | 138 | MinG4 | Group 4 minimum VFD frequency setting | Hz | Read | |
| AI | 139 | MinG5 | Group 5 minimum VFD frequency setting | Hz | Read | |
| AI | 140 | MinG6 | Group 6 minimum VFD frequency setting | Hz | Read | |
| AI | 141 | MinG7 | Group 7 minimum VFD frequency setting | Hz | Read | |
| AI | 142 | MinG8 | Group 8 minimum VFD frequency setting | Hz | Read | |
| AI | 143 | MinG9 | Group 9 minimum VFD frequency setting | Hz | Read | |
| AI | 144 | MinG10 | Group 10 minimum VFD frequency setting | Hz | Read | |
| AI | 145 | MaxG1 | Group 1 maximum VFD frequency setting | Hz | Read | |
| AI | 146 | MaxG2 | Group 2 maximum VFD frequency setting | Hz | Read | |
| AI | 147 | MaxG3 | Group 3 maximum VFD frequency setting | Hz | Read | |
| AI | 148 | MaxG4 | Group 4 maximum VFD frequency setting | Hz | Read | |
| AI | 149 | MaxG5 | Group 5 maximum VFD frequency setting | Hz | Read | |
| AI | 150 | MaxG6 | Group 6 maximum VFD frequency setting | Hz | Read | |
| AI | 151 | MaxG7 | Group 7 maximum VFD frequency setting | Hz | Read | |
| AI | 152 | MaxG8 | Group 8 maximum VFD frequency setting | Hz | Read | |
| AI | 153 | MaxG9 | Group 9 maximum VFD frequency setting | Hz | Read | |
| AI | 154 | MaxG10 | Group 10 maximum VFD frequency setting | Hz | Read | |
| AI | 155 | ActivationTempG1 | Group 1 fan activation temperature | °F | Read | |
| AI | 156 | ActivationTempG2 | Group 2 fan activation temperature | °F | Read | |
| AI | 157 | ActivationTempG3 | Group 3 fan activation temperature | °F | Read | |
| AI | 158 | ActivationTempG4 | Group 4 fan activation temperature | °F | Read | |
| AI | 159 | ActivationTempG5 | Group 5 fan activation temperature | °F | Read | |
| AI | 160 | ActivationTempG6 | Group 6 fan activation temperature | °F | Read | |
| AI | 161 | ActivationTempG7 | Group 7 fan activation temperature | °F | Read | |
| AI | 162 | ActivationTempG8 | Group 8 fan activation temperature | °F | Read | |
| AI | 163 | ActivationTempG9 | Group 9 fan activation temperature | °F | Read | |
| AI | 164 | ActivationTempG10 | Group 10 fan activation temperature | °F | Read | |
| AI | 165 | VFDMSCFaults1 | VFD/MSC 1 faults | Read | ||
| AI | 166 | VFDMSCFaults2 | VFD/MSC 2 faults | Read | ||
| AI | 167 | VFDMSCFaults3 | VFD/MSC 3 faults | Read | ||
| AI | 168 | VFDMSCFaults4 | VFD/MSC 4 faults | Read | ||
| AI | 169 | VFDMSCFaults5 | VFD/MSC 5 faults | Read | ||
| AI | 170 | VFDMSCFaults6 | VFD/MSC 6 faults | Read | ||
| AI | 171 | VFDMSCFaults7 | VFD/MSC 7 faults | Read | ||
| AI | 172 | VFDMSCFaults8 | VFD/MSC 8 faults | Read | ||
| AI | 173 | VFDMSCFaults9 | VFD/MSC 9 faults | Read | ||
| AI | 174 | VFDMSCFaults10 | VFD/MSC 10 faults | Read | ||
| BImin | 175 | EmergencyShutdownG1 | Group 1 hard-wired emergency shutdown | Read | 0=No shutdown, 1=Emergency shutdown | |
| BI | 176 | EmergencyShutdownG2 | Group 2 hard-wired emergency shutdown | Read | 0=No shutdown, 1=Emergency shutdown | |
| BI | 177 | EmergencyShutdownG3 | Group 3 hard-wired emergency shutdown | Read | 0=No shutdown, 1=Emergency shutdown | |
| BI | 178 | EmergencyShutdownG4 | Group 4 hard-wired emergency shutdown | Read | 0=No shutdown, 1=Emergency shutdown | |
| BI | 179 | EmergencyShutdownG5 | Group 5 hard-wired emergency shutdown | Read | 0=No shutdown, 1=Emergency shutdown | |
| BI | 180 | EmergencyShutdownG6 | Group 6 hard-wired emergency shutdown | Read | 0=No shutdown, 1=Emergency shutdown | |
| BI | 181 | EmergencyShutdownG7 | Group 7 hard-wired emergency shutdown | Read | 0=No shutdown, 1=Emergency shutdown | |
| BI | 182 | EmergencyShutdownG8 | Group 8 hard-wired emergency shutdown | Read | 0=No shutdown, 1=Emergency shutdown | |
| BI | 183 | EmergencyShutdownG9 | Group 9 hard-wired emergency shutdown | Read | 0=No shutdown, 1=Emergency shutdown | |
| BI | 184 | EmergencyShutdownG10 | Group 10 hard-wired emergency shutdown | Read | 0=No shutdown, 1=Emergency shutdown | |
| BI | 185 | OccupiedG1 | Group 1 occupancy state | Read | 0=Unoccupied, 1=Occupied | |
| BI | 186 | OccupiedG2 | Group 2 occupancy state | Read | 0=Unoccupied, 1=Occupied | |
| BI | 187 | OccupiedG3 | Group 3 occupancy state | Read | 0=Unoccupied, 1=Occupied | |
| BI | 188 | OccupiedG4 | Group 4 occupancy state | Read | 0=Unoccupied, 1=Occupied | |
| BI | 189 | OccupiedG5 | Group 5 occupancy state | Read | 0=Unoccupied, 1=Occupied | |
| BI | 190 | OccupiedG6 | Group 6 occupancy state | Read | 0=Unoccupied, 1=Occupied | |
| BI | 191 | OccupiedG7 | Group 7 occupancy state | Read | 0=Unoccupied, 1=Occupied | |
| BI | 192 | OccupiedG8 | Group 8 occupancy state | Read | 0=Unoccupied, 1=Occupied | |
| BI | 193 | OccupiedG9 | Group 9 occupancy state | Read | 0=Unoccupied, 1=Occupied | |
| BI | 194 | OccupiedG10 | Group 10 occupancy state | Read | 0=Unoccupied, 1=Occupied | |
| AI | 195 | ModbusFault | Modbus communication faults | Read | ||
| BI | 196 | BrokenStatG1 | Group 1 broken sensor fault | Read | 0=No fault, 1=Broken sensor | |
| BI | 197 | BrokenStatG2 | Group 2 broken sensor fault | Read | 0=No fault, 1=Broken sensor | |
| BI | 198 | BrokenStatG3 | Group 3 broken sensor fault | Read | 0=No fault, 1=Broken sensor | |
| BI | 199 | BrokenStatG4 | Group 4 broken sensor fault | Read | 0=No fault, 1=Broken sensor | |
| BI | 200 | BrokenStatG5 | Group 5 broken sensor fault | Read | 0=No fault, 1=Broken sensor | |
| BI | 201 | BrokenStatG6 | Group 6 broken sensor fault | Read | 0=No fault, 1=Broken sensor | |
| BI | 202 | BrokenStatG7 | Group 7 broken sensor fault | Read | 0=No fault, 1=Broken sensor | |
| BI | 203 | BrokenStatG8 | Group 8 broken sensor fault | Read | 0=No fault, 1=Broken sensor | |
| BI | 204 | BrokenStatG9 | Group 9 broken sensor fault | Read | 0=No fault, 1=Broken sensor | |
| BI | 205 | BrokenStatG10 | Group 10 broken sensor fault | Read | 0=No fault, 1=Broken sensor | |
| BI | 206 | MissingStatG1 | Group 1 missing sensor fault | Read | 0=No fault, 1=Missing sensor | |
| BI | 207 | MissingStatG2 | Group 2 missing sensor fault | Read | 0=No fault, 1=Missing sensor | |
| BI | 208 | MissingStatG3 | Group 3 missing sensor fault | Read | 0=No fault, 1=Missing sensor | |
| BI | 209 | MissingStatG4 | Group 4 missing sensor fault | Read | 0=No fault, 1=Missing sensor | |
| BI | 210 | MissingStatG5 | Group 5 missing sensor fault | Read | 0=No fault, 1=Missing sensor | |
| BI | 211 | MissingStatG6 | Group 6 missing sensor fault | Read | 0=No fault, 1=Missing sensor | |
| BI | 212 | MissingStatG7 | Group 7 missing sensor fault | Read | 0=No fault, 1=Missing sensor | |
| BI | 213 | MissingStatG8 | Group 8 missing sensor fault | Read | 0=No fault, 1=Missing sensor | |
| BI | 214 | MissingStatG9 | Group 9 missing sensor fault | Read | 0=No fault, 1=Missing sensor | |
| BI | 215 | MissingStatG10 | Group 10 missing sensor fault | Read | 0=No fault, 1=Missing sensor | |
| BI | 216 | BoardFuseBlown | Control board fuse blown | Read | 0=No fault, 1=Fuse blown | |
| BI | 217 | TemperatureSensorNotAssigned | Temperature sensor not assigned | Read | 0=No fault, 1=Not assigned | |
| BI | 218 | LowTempAlarmFaultG1 | Group 1 low temperature fault | Read | 0=No fault, 1=Low temperature fault | |
| BI | 219 | LowTempAlarmFaultG2 | Group 2 low temperature fault | Read | 0=No fault, 1=Low temperature fault | |
| BI | 220 | LowTempAlarmFaultG3 | Group 3 low temperature fault | Read | 0=No fault, 1=Low temperature fault | |
| BI | 221 | LowTempAlarmFaultG4 | Group 4 low temperature fault | Read | 0=No fault, 1=Low temperature fault | |
| BI | 222 | LowTempAlarmFaultG5 | Group 5 low temperature fault | Read | 0=No fault, 1=Low temperature fault | |
| BI | 223 | LowTempAlarmFaultG6 | Group 6 low temperature fault | Read | 0=No fault, 1=Low temperature fault | |
| BI | 224 | LowTempAlarmFaultG7 | Group 7 low temperature fault | Read | 0=No fault, 1=Low temperature fault | |
| BI | 225 | LowTempAlarmFaultG8 | Group 8 low temperature fault | Read | 0=No fault, 1=Low temperature fault | |
| BI | 226 | LowTempAlarmFaultG9 | Group 9 low temperature fault | Read | 0=No fault, 1=Low temperature fault | |
| BI | 227 | LowTempAlarmFaultG10 | Group 10 low temperature fault | Read | 0=No fault, 1=Low temperature fault | |
| BI | 228 | HighTempAlarmFaultG1 | Group 1 high temperature fault | Read | 0=No fault, 1=High temperature fault | |
| BI | 229 | HighTempAlarmFaultG2 | Group 2 high temperature fault | Read | 0=No fault, 1=High temperature fault | |
| BI | 230 | HighTempAlarmFaultG3 | Group 3 high temperature fault | Read | 0=No fault, 1=High temperature fault | |
| BI | 231 | HighTempAlarmFaultG4 | Group 4 high temperature fault | Read | 0=No fault, 1=High temperature fault | |
| BI | 232 | HighTempAlarmFaultG5 | Group 5 high temperature fault | Read | 0=No fault, 1=High temperature fault | |
| BI | 233 | HighTempAlarmFaultG6 | Group 6 high temperature fault | Read | 0=No fault, 1=High temperature fault | |
| BI | 234 | HighTempAlarmFaultG7 | Group 7 high temperature fault | Read | 0=No fault, 1=High temperature fault | |
| BI | 235 | HighTempAlarmFaultG8 | Group 8 high temperature fault | Read | 0=No fault, 1=High temperature fault | |
| BI | 236 | HighTempAlarmFaultG9 | Group 9 high temperature fault | Read | 0=No fault, 1=High temperature fault | |
| BI | 237 | HighTempAlarmFaultG10 | Group 10 high temperature fault | Read | 0=No fault, 1=High temperature fault | |
| BI | 238 | MembraneStatFaultG1 | Group 1 membrane thermostat fault | Read | 0=No fault, 1=Membrane stat fault | |
| BI | 239 | MembraneStatFaultG2 | Group 2 membrane thermostat fault | Read | 0=No fault, 1=Membrane stat fault | |
| BI | 240 | MembraneStatFaultG3 | Group 3 membrane thermostat fault | Read | 0=No fault, 1=Membrane stat fault | |
| BI | 241 | MembraneStatFaultG4 | Group 4 membrane thermostat fault | Read | 0=No fault, 1=Membrane stat fault | |
| BI | 242 | MembraneStatFaultG5 | Group 5 membrane thermostat fault | Read | 0=No fault, 1=Membrane stat fault | |
| BI | 243 | MembraneStatFaultG6 | Group 6 membrane thermostat fault | Read | 0=No fault, 1=Membrane stat fault | |
| BI | 244 | MembraneStatFaultG7 | Group 7 membrane thermostat fault | Read | 0=No fault, 1=Membrane stat fault | |
| BI | 245 | MembraneStatFaultG8 | Group 8 membrane thermostat fault | Read | 0=No fault, 1=Membrane stat fault | |
| BI | 246 | MembraneStatFaultG9 | Group 9 membrane thermostat fault | Read | 0=No fault, 1=Membrane stat fault | |
| BI | 247 | MembraneStatFaultG10 | Group 10 membrane thermostat fault | Read | 0=No fault, 1=Membrane stat fault | |
| BI | 248 | WiredStatFaultG1 | Group 1 HMI wired thermostat fault | Read | 0=No fault, 1=Wired stat fault | |
| BI | 249 | WiredStatFaultG2 | Group 2 HMI wired thermostat fault | Read | 0=No fault, 1=Wired stat fault | |
| BI | 250 | WiredStatFaultG3 | Group 3 HMI wired thermostat fault | Read | 0=No fault, 1=Wired stat fault | |
| BI | 251 | WiredStatFaultG4 | Group 4 HMI wired thermostat fault | Read | 0=No fault, 1=Wired stat fault | |
| BI | 252 | WiredStatFaultG5 | Group 5 HMI wired thermostat fault | Read | 0=No fault, 1=Wired stat fault | |
| BI | 253 | WiredStatFaultG6 | Group 6 HMI wired thermostat fault | Read | 0=No fault, 1=Wired stat fault | |
| BI | 254 | WiredStatFaultG7 | Group 7 HMI wired thermostat fault | Read | 0=No fault, 1=Wired stat fault | |
| BI | 255 | WiredStatFaultG8 | Group 8 HMI wired thermostat fault | Read | 0=No fault, 1=Wired stat fault | |
| BI | 256 | WiredStatFaultG9 | Group 9 HMI wired thermostat fault | Read | 0=No fault, 1=Wired stat fault | |
| BI | 257 | WiredStatFaultG10 | Group 10 HMI wired thermostat fault | Read | 0=No fault, 1=Wired stat fault | |
| BI | 258 | SensorRequiredFaultG1 | Group 1 sensor required fault | Read | 0=No fault, 1=Sensor required | |
| BI | 259 | SensorRequiredFaultG2 | Group 2 sensor required fault | Read | 0=No fault, 1=Sensor required | |
| BI | 260 | SensorRequiredFaultG3 | Group 3 sensor required fault | Read | 0=No fault, 1=Sensor required | |
| BI | 261 | SensorRequiredFaultG4 | Group 4 sensor required fault | Read | 0=No fault, 1=Sensor required | |
| BI | 262 | SensorRequiredFaultG5 | Group 5 sensor required fault | Read | 0=No fault, 1=Sensor required | |
| BI | 263 | SensorRequiredFaultG6 | Group 6 sensor required fault | Read | 0=No fault, 1=Sensor required | |
| BI | 264 | SensorRequiredFaultG7 | Group 7 sensor required fault | Read | 0=No fault, 1=Sensor required | |
| BI | 265 | SensorRequiredFaultG8 | Group 8 sensor required fault | Read | 0=No fault, 1=Sensor required | |
| BI | 266 | SensorRequiredFaultG9 | Group 9 sensor required fault | Read | 0=No fault, 1=Sensor required | |
| BI | 267 | SensorRequiredFaultG10 | Group 10 sensor required fault | Read | 0=No fault, 1=Sensor required | |
| AVmin | 268 | SpeedF1 | Group 1 occupied fan speed | Hz | Write | |
| AV | 269 | SpeedF2 | Group 2 occupied fan speed | Hz | Write | |
| AV | 270 | SpeedF3 | Group 3 occupied fan speed | Hz | Write | |
| AV | 271 | SpeedF4 | Group 4 occupied fan speed | Hz | Write | |
| AV | 272 | SpeedF5 | Group 5 occupied fan speed | Hz | Write | |
| AV | 273 | SpeedF6 | Group 6 occupied fan speed | Hz | Write | |
| AV | 274 | SpeedF7 | Group 7 occupied fan speed | Hz | Write | |
| AV | 275 | SpeedF8 | Group 8 occupied fan speed | Hz | Write | |
| AV | 276 | SpeedF9 | Group 9 occupied fan speed | Hz | Write | |
| AV | 277 | SpeedF10 | Group 10 occupied fan speed | Hz | Write | |
| AV | 278 | DirectionF1 | Fan 1 direction (0 forward, 1 reverse) | Write | ||
| AV | 279 | DirectionF2 | Fan 2 direction (0 forward, 1 reverse) | Write | ||
| AV | 280 | DirectionF3 | Fan 3 direction (0 forward, 1 reverse) | Write | ||
| AV | 281 | DirectionF4 | Fan 4 direction (0 forward, 1 reverse) | Write | ||
| AV | 282 | DirectionF5 | Fan 5 direction (0 forward, 1 reverse) | Write | ||
| AV | 283 | DirectionF6 | Fan 6 direction (0 forward, 1 reverse) | Write | ||
| AV | 284 | DirectionF7 | Fan 7 direction (0 forward, 1 reverse) | Write | ||
| AV | 285 | DirectionF8 | Fan 8 direction (0 forward, 1 reverse) | Write | ||
| AV | 286 | DirectionF9 | Fan 9 direction (0 forward, 1 reverse) | Write | ||
| AV | 287 | DirectionF10 | Fan 10 direction (0 forward, 1 reverse) | Write | ||
| BVmin | 288 | ModeG1 | Group 1 DDC mode | Write | 0=DDC Auto, 1=DDC Manual | |
| BV | 289 | ModeG2 | Group 2 DDC mode | Write | 0=DDC Auto, 1=DDC Manual | |
| BV | 290 | ModeG3 | Group 3 DDC mode | Write | 0=DDC Auto, 1=DDC Manual | |
| BV | 291 | ModeG4 | Group 4 DDC mode | Write | 0=DDC Auto, 1=DDC Manual | |
| BV | 292 | ModeG5 | Group 5 DDC mode | Write | 0=DDC Auto, 1=DDC Manual | |
| BV | 293 | ModeG6 | Group 6 DDC mode | Write | 0=DDC Auto, 1=DDC Manual | |
| BV | 294 | ModeG7 | Group 7 DDC mode | Write | 0=DDC Auto, 1=DDC Manual | |
| BV | 295 | ModeG8 | Group 8 DDC mode | Write | 0=DDC Auto, 1=DDC Manual | |
| BV | 296 | ModeG9 | Group 9 DDC mode | Write | 0=DDC Auto, 1=DDC Manual | |
| BV | 297 | ModeG10 | Group 10 DDC mode | Write | 0=DDC Auto, 1=DDC Manual | |
| BVmin | 298 | ButtonG1 | Group 1 on/off in DDC Manual mode | Write | 0=Off, 1=On | |
| BV | 299 | ButtonG2 | Group 2 on/off in DDC Manual mode | Write | 0=Off, 1=On | |
| BV | 300 | ButtonG3 | Group 3 on/off in DDC Manual mode | Write | 0=Off, 1=On | |
| BV | 301 | ButtonG4 | Group 4 on/off in DDC Manual mode | Write | 0=Off, 1=On | |
| BV | 302 | ButtonG5 | Group 5 on/off in DDC Manual mode | Write | 0=Off, 1=On | |
| BV | 303 | ButtonG6 | Group 6 on/off in DDC Manual mode | Write | 0=Off, 1=On | |
| BV | 304 | ButtonG7 | Group 7 on/off in DDC Manual mode | Write | 0=Off, 1=On | |
| BV | 305 | ButtonG8 | Group 8 on/off in DDC Manual mode | Write | 0=Off, 1=On | |
| BV | 306 | ButtonG9 | Group 9 on/off in DDC Manual mode | Write | 0=Off, 1=On | |
| BV | 307 | ButtonG10 | Group 10 on/off in DDC Manual mode | Write | 0=Off, 1=On |
No points match these filters.
Object ID lookup: CaptiveAire HVLS and General Ventilation Fan Control point IDs by name
AI1TempSensor1AI2TempSensor2AI3TempSensor3AI4TempSensor4AI5TempSensor5AI6TempSensor6AI7TempSensor7AI8TempSensor8AI9EXPTemp1AI10EXPTemp2AI11EXPTemp3AI12EXPTemp4AI13EXPTemp5AI14EXPTemp6AI15EXPTemp7AI16EXPTemp8AI17EXPTemp9AI18EXPTemp10AI19EXPTemp11AI20EXPTemp12AI21EXPTemp13AI22EXPTemp14AI23EXPTemp15AI24EXPTemp16AI25HMITemp1AI26HMIWiredTemp1AI27HMITemp2AI28HMIWiredTemp2AI29HMITemp3AI30HMIWiredTemp3AI31HMITemp4AI32HMIWiredTemp4AI33HMITemp5AI34HMIWiredTemp5AI35HMITemp6AI36HMIWiredTemp6AI37HMITemp7AI38HMIWiredTemp7AI39HMITemp8AI40HMIWiredTemp8AI41HMITemp9AI42HMIWiredTemp9AI43HMITemp10AI44HMIWiredTemp10AI45FrequencyF1AI46FrequencyF2AI47FrequencyF3AI48FrequencyF4AI49FrequencyF5AI50FrequencyF6AI51FrequencyF7AI52FrequencyF8AI53FrequencyF9AI54FrequencyF10AI55StateVFD1AI56StateVFD2AI57StateVFD3AI58StateVFD4AI59StateVFD5AI60StateVFD6AI61StateVFD7AI62StateVFD8AI63StateVFD9AI64StateVFD10AI65AmperageF1AI66AmperageF2AI67AmperageF3AI68AmperageF4AI69AmperageF5AI70AmperageF6AI71AmperageF7AI72AmperageF8AI73AmperageF9AI74AmperageF10AI75PowerF1AI76PowerF2AI77PowerF3AI78PowerF4AI79PowerF5AI80PowerF6AI81PowerF7AI82PowerF8AI83PowerF9AI84PowerF10AI85VFDFaultF1AI86VFDFaultF2AI87VFDFaultF3AI88VFDFaultF4AI89VFDFaultF5AI90VFDFaultF6AI91VFDFaultF7AI92VFDFaultF8AI93VFDFaultF9AI94VFDFaultF10AI95VFDLoadF1AI96VFDLoadF2AI97VFDLoadF3AI98VFDLoadF4AI99VFDLoadF5AI100VFDLoadF6AI101VFDLoadF7AI102VFDLoadF8AI103VFDLoadF9AI104VFDLoadF10AI105VFDTempF1AI106VFDTempF2AI107VFDTempF3AI108VFDTempF4AI109VFDTempF5AI110VFDTempF6AI111VFDTempF7AI112VFDTempF8AI113VFDTempF9AI114VFDTempF10AI115VFDVoltageF1AI116VFDVoltageF2AI117VFDVoltageF3AI118VFDVoltageF4AI119VFDVoltageF5AI120VFDVoltageF6AI121VFDVoltageF7AI122VFDVoltageF8AI123VFDVoltageF9AI124VFDVoltageF10AI125ModulationG1AI126ModulationG2AI127ModulationG3AI128ModulationG4AI129ModulationG5AI130ModulationG6AI131ModulationG7AI132ModulationG8AI133ModulationG9AI134ModulationG10AI135MinG1AI136MinG2AI137MinG3AI138MinG4AI139MinG5AI140MinG6AI141MinG7AI142MinG8AI143MinG9AI144MinG10AI145MaxG1AI146MaxG2AI147MaxG3AI148MaxG4AI149MaxG5AI150MaxG6AI151MaxG7AI152MaxG8AI153MaxG9AI154MaxG10AI155ActivationTempG1AI156ActivationTempG2AI157ActivationTempG3AI158ActivationTempG4AI159ActivationTempG5AI160ActivationTempG6AI161ActivationTempG7AI162ActivationTempG8AI163ActivationTempG9AI164ActivationTempG10AI165VFDMSCFaults1AI166VFDMSCFaults2AI167VFDMSCFaults3AI168VFDMSCFaults4AI169VFDMSCFaults5AI170VFDMSCFaults6AI171VFDMSCFaults7AI172VFDMSCFaults8AI173VFDMSCFaults9AI174VFDMSCFaults10BI175EmergencyShutdownG1BI176EmergencyShutdownG2BI177EmergencyShutdownG3BI178EmergencyShutdownG4BI179EmergencyShutdownG5BI180EmergencyShutdownG6BI181EmergencyShutdownG7BI182EmergencyShutdownG8BI183EmergencyShutdownG9BI184EmergencyShutdownG10BI185OccupiedG1BI186OccupiedG2BI187OccupiedG3BI188OccupiedG4BI189OccupiedG5BI190OccupiedG6BI191OccupiedG7BI192OccupiedG8BI193OccupiedG9BI194OccupiedG10AI195ModbusFaultBI196BrokenStatG1BI197BrokenStatG2BI198BrokenStatG3BI199BrokenStatG4BI200BrokenStatG5BI201BrokenStatG6BI202BrokenStatG7BI203BrokenStatG8BI204BrokenStatG9BI205BrokenStatG10BI206MissingStatG1BI207MissingStatG2BI208MissingStatG3BI209MissingStatG4BI210MissingStatG5BI211MissingStatG6BI212MissingStatG7BI213MissingStatG8BI214MissingStatG9BI215MissingStatG10BI216BoardFuseBlownBI217TemperatureSensorNotAssignedBI218LowTempAlarmFaultG1BI219LowTempAlarmFaultG2BI220LowTempAlarmFaultG3BI221LowTempAlarmFaultG4BI222LowTempAlarmFaultG5BI223LowTempAlarmFaultG6BI224LowTempAlarmFaultG7BI225LowTempAlarmFaultG8BI226LowTempAlarmFaultG9BI227LowTempAlarmFaultG10BI228HighTempAlarmFaultG1BI229HighTempAlarmFaultG2BI230HighTempAlarmFaultG3BI231HighTempAlarmFaultG4BI232HighTempAlarmFaultG5BI233HighTempAlarmFaultG6BI234HighTempAlarmFaultG7BI235HighTempAlarmFaultG8BI236HighTempAlarmFaultG9BI237HighTempAlarmFaultG10BI238MembraneStatFaultG1BI239MembraneStatFaultG2BI240MembraneStatFaultG3BI241MembraneStatFaultG4BI242MembraneStatFaultG5BI243MembraneStatFaultG6BI244MembraneStatFaultG7BI245MembraneStatFaultG8BI246MembraneStatFaultG9BI247MembraneStatFaultG10BI248WiredStatFaultG1BI249WiredStatFaultG2BI250WiredStatFaultG3BI251WiredStatFaultG4BI252WiredStatFaultG5BI253WiredStatFaultG6BI254WiredStatFaultG7BI255WiredStatFaultG8BI256WiredStatFaultG9BI257WiredStatFaultG10BI258SensorRequiredFaultG1BI259SensorRequiredFaultG2BI260SensorRequiredFaultG3BI261SensorRequiredFaultG4BI262SensorRequiredFaultG5BI263SensorRequiredFaultG6BI264SensorRequiredFaultG7BI265SensorRequiredFaultG8BI266SensorRequiredFaultG9BI267SensorRequiredFaultG10AV268SpeedF1AV269SpeedF2AV270SpeedF3AV271SpeedF4AV272SpeedF5AV273SpeedF6AV274SpeedF7AV275SpeedF8AV276SpeedF9AV277SpeedF10AV278DirectionF1AV279DirectionF2AV280DirectionF3AV281DirectionF4AV282DirectionF5AV283DirectionF6AV284DirectionF7AV285DirectionF8AV286DirectionF9AV287DirectionF10BV288ModeG1BV289ModeG2BV290ModeG3BV291ModeG4BV292ModeG5BV293ModeG6BV294ModeG7BV295ModeG8BV296ModeG9BV297ModeG10BV298ButtonG1BV299ButtonG2BV300ButtonG3BV301ButtonG4BV302ButtonG5BV303ButtonG6BV304ButtonG7BV305ButtonG8BV306ButtonG9BV307ButtonG10
Integration notes
- The table has no read/write column. The Analog Variable and Binary Value objects carry LON input variables and are shown as writable; all inputs are read-only.
- The manual's 'Object ID' numbers run 1-307 across all object types; they are used here as the instance of the printed type ('Analog Variable' listed as AV).
- Per-fan objects are F1-F10 and per-group objects G1-G10; objects for fans or groups that are not installed have no meaning.
- Group settings (modulation band, min/max frequency, activation temperature) are printed with one implied decimal, e.g. 72.5 °F is read as 725. The other temperature and frequency points say '1 decimal precision' without giving the scaling.
- The manual prints no units for the room/HMI temperature points; the group settings are in °F.
- VFD fault code meanings are in the manual's VFD fault list (0 = no fault).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the HVLS and General Ventilation Fan Control (ECPM03, Protocessor BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the CaptiveAire HVLS and General Ventilation Fan Control (ECPM03, Protocessor BACnet)
How many BACnet points does the CaptiveAire HVLS and General Ventilation Fan Control (ECPM03, Protocessor BACnet) have?
This list has 307 BACnet objects: 175 analog inputs, 20 analog values, 92 binary inputs, 20 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which CaptiveAire HVLS and General Ventilation Fan Control (ECPM03, Protocessor BACnet) BACnet points are writable?
40 of the 307 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official CaptiveAire HVLS and General Ventilation Fan Control (ECPM03, Protocessor BACnet) BACnet documentation?
The source is High Volume Low Speed (HVLS) Fan - HVLS and General Ventilation Fan Control Software - Installation, Operation, and Maintenance Manual (A0025729), revision August 2026 Rev 26, published free by CaptiveAire at https://www.captiveaire.com/manuals/hvls/hvls-oim.pdf.
What are the minimum BACnet points to integrate the CaptiveAire HVLS and General Ventilation Fan Control (ECPM03, Protocessor BACnet)?
Start with BV 288 ModeG1 (Group 1: 0 = DDC Auto, 1 = DDC Manual); BV 298 ButtonG1 (Group 1 on/off in DDC Manual (1 = on)); AV 268 SpeedF1 (Group 1 occupied fan speed, Hz); AI 55 StateVFD1 (Fan 1 run state and reason code); AI 45 FrequencyF1 (Fan 1 VFD output frequency, Hz); AI 1 TempSensor1 (Room temperature, sensor 1); AI 85 VFDFaultF1 (Fan 1 VFD fault code (0 = no fault)); BI 175 EmergencyShutdownG1 (Group 1 hard-wired emergency shutdown active).
How do I enable BMS control of the CaptiveAire HVLS and General Ventilation Fan Control (ECPM03, Protocessor BACnet)?
Set the controller's DDC Mode menu to ENABLED; then all fan start and stop commands come from the network. Per group, ModeG selects DDC Auto (temperature control) or DDC Manual (ButtonG on/off).
How do I check these points on the real HVLS and General Ventilation Fan Control (ECPM03, Protocessor BACnet)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More CaptiveAire BACnet points lists
- Kitchen hood demand control ventilation (DCV) controller (exhaust and make-up air fans)
CaptiveAire DCV Package DDC (Protocessor BACnet)
CaptiveAire demand control ventilation packages that run kitchen hood exhaust and supply (make-up air) fans, with the factory BACnet option.
Also known as: CaptiveAire DCV, Demand Control Ventilation, DCV Packages Network, Kitchen hood DCV, CASlink, Protocessor, CN0861 - Make-up air heater / tempered air unit DDC controller
CaptiveAire Direct Digital Controls (DDC) Heater Controller
CaptiveAire heater (make-up air) units shipped with the factory Direct Digital Controls (DDC) controller covered by IOM A0020659.
Also known as: A0020659, CaptiveAire DDC, DDC controller, ctrl_source - DOAS rooftop unit
CaptiveAire DOAS RTU Series packaged rooftop unit, legacy IBT controls (Protocessor BACnet)
CaptiveAire DOAS RTU Series packaged rooftop units built with the older IBT-based unit controls (listed as 'Paragon - IBT Controls (Legacy)').
Also known as: A0026936, CaptiveAire DOAS RTU, Paragon IBT controls (legacy), DOAS RTU Series, CaptiveAire DOAS, Protocessor - Kitchen hood exhaust / make-up air fan controller (demand control)
CaptiveAire EMSplus Kitchen Hood Exhaust Controls (BACnet IP)
CaptiveAire EMSplus kitchen ventilation control panels ordered with the BACnet IP communication option.
Also known as: EMSplus, EMS Plus, EMS+, A0017802, CaptiveAire EMSplus - Lighting control panel (8 zones)
CaptiveAire Lighting Control System (ECPM03, Protocessor BACnet)
CaptiveAire Lighting Control System panels with the ECPM03 board and the factory Protocessor BACnet gateway.
Also known as: A0027767, Lighting Control System, ECPM03, CASlink lighting, CaptiveAire lighting control panel, Protocessor - Make-up air unit (indirect gas-fired heater)
CaptiveAire Modular Indirect Fired Heater (IBT controls, Protocessor BACnet)
CaptiveAire modular indirect-fired make-up air heaters, modules and furnace inserts run by the IBT controller with the optional Protocessor BACnet gateway.
Also known as: A0016988, IBT heater, IBT board, Indirect Fired Bent Tube, Modular Indirect Fired Heater, Indirect Fired Module, Indirect Fired Furnace, Protocessor - Make-up air unit controller
CaptiveAire MUA Heater DDC (Protocessor BACnet)
CaptiveAire make-up air heater units (including direct-fired) with the factory DDC/BMS package.
Also known as: CaptiveAire make-up air, Direct fired MUA, Tempered make-up air, DDC Application Guide MUA - Rooftop unit / DOAS controller
CaptiveAire Paragon RTU / DOAS DDC (Protocessor BACnet)
CaptiveAire Paragon HVAC series packaged rooftop units and dedicated outdoor air systems with the factory DDC package.
Also known as: Paragon, CaptiveAire DOAS, CaptiveAire RTU, Protocessor, CN0861, RTU DDC Points - Kitchen hood self-cleaning wash system control panel
CaptiveAire Self Cleaning System (SCS) Control Panel
CaptiveAire Self Cleaning System panels that hot-water wash or cold-water mist kitchen exhaust hoods and plenums, and can also run the hood's fan and light zones.
Also known as: CaptiveAire SCS, Self Cleaning System, Hood wash panel, Hot Water Wash, Cold Water Mist, ECPM03, Protocessor
Source: High Volume Low Speed (HVLS) Fan - HVLS and General Ventilation Fan Control Software - Installation, Operation, and Maintenance Manual · A0025729 · rev. August 2026 Rev 26. Object names, instances and units are reproduced as published; descriptions are our own.