Easy BACnet
  1. Home
  2. BACnet points lists
  3. Badger Meter
  4. Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP)

Ultrasonic flow / energy meter · BACnet points list

Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The TFX Ultra is a clamp-on transit-time ultrasonic flow meter; energy models add two temperature inputs. On BACnet MS/TP it serves 11 analog inputs (signal strength, rate, three totalizers, both temperatures in °C and °F, flow in GPM and LPM) and a binary output that resets the totalizers.

This page lists 12 BACnet objects for the Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP) — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Badger Meter’s documentation hosted by Instrumart, not by Badger Meter itself, so treat it as unofficial.

Manufacturer
Badger Meter
Model
Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP)
Equipment
Ultrasonic flow / energy meter
Equipment type
Thermostats, sensors & meters
BACnet objects
12 (1 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
TFX Ultra, TFX Ultra BACnet MS/TP, Dynasonics TFX Ultra, TTM-UM-00136
Source document
TFX Ultra Flow and Energy Meters User Manual · TTM-UM-00136-EN-08 · rev. 2018-03 (unofficial copy, hosted by Instrumart)
Download CSV 12 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Badger Meter’s current documentation and the live device before use. Not official Badger Meter information. Terms of use.

BMS integration notes: Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP)

Integration in brief

Set the meter address (MS/TP MAC), baud rate and BACnet device ID from the keypad or UltraLink, then read the rate, the totalizers and (energy models) the temperatures.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1Reset TotalizersWrite 1 to reset all totalizersWrite
AI 2Flow Rate (Flow model) / Energy Rate (BTU model)Flow rate (flow models) or energy rate (BTU models)Read
AI 3Net TotalizerNet totalRead
AI 16Flow RateFlow rate, GPMRead
AI 11Temperature 1Temperature 1, °F (energy models)Read
AI 12Temperature 2Temperature 2, °F (energy models)Read
AI 1Signal StrengthSignal strength; low means poor couplingRead

Network setup

Watch out for

Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

12 of 12 shown
Type
AnalogBinary
Access
Show
Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1Signal StrengthUltrasonic signal strengthRead
AImin2Flow Rate (Flow model) / Energy Rate (BTU model)Flow rate, or energy rate on energy modelsGallons, Liters, MGallons, Cubic Feet, Cubic Meters, Acre Feet, Oil Barrel, Liquid Barrel, Feet, Meters, Lb, Kg, BTU, MBTU, MMBTU, TON per Second, Minute, Hour, DayRead
AImin3Net TotalizerNet totalGallons, Liters, MGallons, Cubic Feet, Cubic Meters, Acre Feet, Oil Barrel, Liquid Barrel, Feet, Meters, Lb, Kg, BTU, MBTU, MMBTU, TONRead
AI4Positive TotalizerForward totalGallons, Liters, MGallons, Cubic Feet, Cubic Meters, Acre Feet, Oil Barrel, Liquid Barrel, Feet, Meters, Lb, Kg, BTU, MBTU, MMBTU, TONRead
AI5Negative TotalizerReverse totalGallons, Liters, MGallons, Cubic Feet, Cubic Meters, Acre Feet, Oil Barrel, Liquid Barrel, Feet, Meters, Lb, Kg, BTU, MBTU, MMBTU, TONRead
AI6Temperature 1Temperature sensor 1°CRead
AI7Temperature 2Temperature sensor 2°CRead
AImin11Temperature 1Temperature sensor 1°FRead
AImin12Temperature 2Temperature sensor 2°FRead
AImin16Flow RateFlow rate in GPMGPMRead
AI17Flow RateFlow rate in LPMLPMRead
BOmin1Reset TotalizersWrite 1 to reset all totalizers; returns to 0Write0=Inactive, 1=Active (reset)
Object ID lookup: Badger Meter TFX Ultra BACnet MS/TP point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP)

How many BACnet points does the Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP) have?

This list has 12 BACnet objects: 11 analog inputs, 1 binary output. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP) BACnet points are writable?

1 of the 12 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP) BACnet documentation?

Badger Meter does not publish it on its own website. This list comes from TFX Ultra Flow and Energy Meters User Manual (TTM-UM-00136-EN-08), revision 2018-03, a copy hosted by Instrumart at https://core.instrumart.com/assets/Dynasonics-TFX-Ultra-manual.pdf. Ask Badger Meter or its representative for the current revision.

What are the minimum BACnet points to integrate the Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP)?

Start with BO 1 Reset Totalizers (Write 1 to reset all totalizers); AI 2 Flow Rate (Flow model) / Energy Rate (BTU model) (Flow rate (flow models) or energy rate (BTU models)); AI 3 Net Totalizer (Net total); AI 16 Flow Rate (Flow rate, GPM); AI 11 Temperature 1 (Temperature 1, °F (energy models)); AI 12 Temperature 2 (Temperature 2, °F (energy models)); AI 1 Signal Strength (Signal strength; low means poor coupling).

How do I check these points on the real Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Badger Meter BACnet points lists

Source: TFX Ultra Flow and Energy Meters User Manual · TTM-UM-00136-EN-08 · rev. 2018-03. Object names, instances and units are reproduced as published; descriptions are our own.