- Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP)
Ultrasonic flow / energy meter · BACnet points list
Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP) BACnet points list
Updated 12 November 2026Unofficial source
The TFX Ultra is a clamp-on transit-time ultrasonic flow meter; energy models add two temperature inputs. On BACnet MS/TP it serves 11 analog inputs (signal strength, rate, three totalizers, both temperatures in °C and °F, flow in GPM and LPM) and a binary output that resets the totalizers.
This page lists 12 BACnet objects for the Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP) — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Badger Meter’s documentation hosted by Instrumart, not by Badger Meter itself, so treat it as unofficial.
- Manufacturer
- Badger Meter
- Model
- Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP)
- Equipment
- Ultrasonic flow / energy meter
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 12 (1 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- TFX Ultra, TFX Ultra BACnet MS/TP, Dynasonics TFX Ultra, TTM-UM-00136
- Source document
- TFX Ultra Flow and Energy Meters User Manual · TTM-UM-00136-EN-08 · rev. 2018-03 (unofficial copy, hosted by Instrumart)
Reference only, provided as-is: verify against Badger Meter’s current documentation and the live device before use. Not official Badger Meter information. Terms of use.
BMS integration notes: Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP)
Set the meter address (MS/TP MAC), baud rate and BACnet device ID from the keypad or UltraLink, then read the rate, the totalizers and (energy models) the temperatures.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 1 | Reset Totalizers | Write 1 to reset all totalizers | Write |
| AI 2 | Flow Rate (Flow model) / Energy Rate (BTU model) | Flow rate (flow models) or energy rate (BTU models) | Read |
| AI 3 | Net Totalizer | Net total | Read |
| AI 16 | Flow Rate | Flow rate, GPM | Read |
| AI 11 | Temperature 1 | Temperature 1, °F (energy models) | Read |
| AI 12 | Temperature 2 | Temperature 2, °F (energy models) | Read |
| AI 1 | Signal Strength | Signal strength; low means poor coupling | Read |
Network setup
- ADDRESS (0-127) is the MS/TP MAC, BAUD the RS-485 rate, BACNET ID the device instance (0-4194303); set them in the BSC menu or with UltraLink.
- The PICS lists MS/TP master at 9600, 19200, 38400 and 76800 baud.
- Save the changes when leaving the menu; settings are kept in flash memory.
Watch out for
- BO 1 returns to inactive by itself after the reset.
Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Signal Strength | Ultrasonic signal strength | Read | ||
| AImin | 2 | Flow Rate (Flow model) / Energy Rate (BTU model) | Flow rate, or energy rate on energy models | Gallons, Liters, MGallons, Cubic Feet, Cubic Meters, Acre Feet, Oil Barrel, Liquid Barrel, Feet, Meters, Lb, Kg, BTU, MBTU, MMBTU, TON per Second, Minute, Hour, Day | Read | |
| AImin | 3 | Net Totalizer | Net total | Gallons, Liters, MGallons, Cubic Feet, Cubic Meters, Acre Feet, Oil Barrel, Liquid Barrel, Feet, Meters, Lb, Kg, BTU, MBTU, MMBTU, TON | Read | |
| AI | 4 | Positive Totalizer | Forward total | Gallons, Liters, MGallons, Cubic Feet, Cubic Meters, Acre Feet, Oil Barrel, Liquid Barrel, Feet, Meters, Lb, Kg, BTU, MBTU, MMBTU, TON | Read | |
| AI | 5 | Negative Totalizer | Reverse total | Gallons, Liters, MGallons, Cubic Feet, Cubic Meters, Acre Feet, Oil Barrel, Liquid Barrel, Feet, Meters, Lb, Kg, BTU, MBTU, MMBTU, TON | Read | |
| AI | 6 | Temperature 1 | Temperature sensor 1 | °C | Read | |
| AI | 7 | Temperature 2 | Temperature sensor 2 | °C | Read | |
| AImin | 11 | Temperature 1 | Temperature sensor 1 | °F | Read | |
| AImin | 12 | Temperature 2 | Temperature sensor 2 | °F | Read | |
| AImin | 16 | Flow Rate | Flow rate in GPM | GPM | Read | |
| AI | 17 | Flow Rate | Flow rate in LPM | LPM | Read | |
| BOmin | 1 | Reset Totalizers | Write 1 to reset all totalizers; returns to 0 | Write | 0=Inactive, 1=Active (reset) |
No points match these filters.
Object ID lookup: Badger Meter TFX Ultra BACnet MS/TP point IDs by name
Integration notes
- The table gives a description and object ID only, with no Object_Name column; the description is used as the name here.
- AI 2 carries flow rate on flow models and energy rate on energy (BTU) models, in the units chosen in the meter. The MS/TP map has no unit-code objects.
- Instances are not contiguous (AI 1-7, 11, 12, 16, 17); they match the BACnet IP map numbering.
- Access is not printed per object; inputs are shown read-only and BO 1 writable as the notes describe.
- Source: Table 18 'BACnet MSTP object mappings', page 76 (12 objects).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP)
How many BACnet points does the Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP) have?
This list has 12 BACnet objects: 11 analog inputs, 1 binary output. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP) BACnet points are writable?
1 of the 12 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP) BACnet documentation?
Badger Meter does not publish it on its own website. This list comes from TFX Ultra Flow and Energy Meters User Manual (TTM-UM-00136-EN-08), revision 2018-03, a copy hosted by Instrumart at https://core.instrumart.com/assets/Dynasonics-TFX-Ultra-manual.pdf. Ask Badger Meter or its representative for the current revision.
What are the minimum BACnet points to integrate the Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP)?
Start with BO 1 Reset Totalizers (Write 1 to reset all totalizers); AI 2 Flow Rate (Flow model) / Energy Rate (BTU model) (Flow rate (flow models) or energy rate (BTU models)); AI 3 Net Totalizer (Net total); AI 16 Flow Rate (Flow rate, GPM); AI 11 Temperature 1 (Temperature 1, °F (energy models)); AI 12 Temperature 2 (Temperature 2, °F (energy models)); AI 1 Signal Strength (Signal strength; low means poor coupling).
How do I check these points on the real Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Badger Meter BACnet points lists
- Btu energy meter (transmitter)
Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP)
Badger Meter / Data Industrial 340 BN/MB Btu energy transmitters with one pulse or sine flow sensor and two temperature sensors.
Also known as: 340 BN/MB, 340BN/MB, B340BN, Series 340, Data Industrial 340, Badger 340 Btu transmitter, XMT-UM-01660 - Btu energy meter (impeller)
Badger Meter Data Industrial Series 380 impeller Btu system 380CS / 380HS (BACnet MS/TP)
Badger Meter / Data Industrial Series 380 impeller Btu systems (380CS cold, 380HS hot) with the RS-485 output set to BACnet.
Also known as: Series 380, 380CS, 380HS, 380CS/HS, Data Industrial 380, Badger 380 Btu meter, 880102-0001 - Ultrasonic flow / energy meter
Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet IP Ethernet module)
Dynasonics TFX Ultra clamp-on flow and energy transmitters ordered with the Ethernet module, set to BACnet IP.
Also known as: TFX Ultra, TFX Ultra BACnet IP, Dynasonics TFX Ultra, TFX Ultra Ethernet, TTM-UM-00136 - Ultrasonic flow and BTU meter (BACnet MS/TP)
Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet MS/TP)
Badger Meter Dynasonics TFX-5000 clamp-on ultrasonic flow meters and TFX-5000 energy (BTU) meters, using the built-in RS-485 port in BACnet MS/TP mode.
Also known as: TFX-5000, Dynasonics TFX-5000, TFX-5000 BACnet, TFX-5000 Energy, TTM-UM-03074, clamp-on BTU meter BACnet, Badger ultrasonic flow meter BACnet - Ultrasonic flow and BTU meter (BACnet IP card)
Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)
Badger Meter Dynasonics TFX-5000 flow and energy (BTU) meters fitted with the optional Ethernet card set to BACnet/IP.
Also known as: TFX-5000 BACnet/IP, TFX-5000 Ethernet, Dynasonics TFX-5000 BACnet IP, TTM-UM-03250, TFX-5000 Energy BACnet IP - Ultrasonic flow meter (clamp-on)
Badger Meter Dynasonics TFX-500w clamp-on ultrasonic flow meter (BACnet MS/TP)
Badger Meter Dynasonics TFX-500w clamp-on transit-time ultrasonic flow meters with the RS-485 port set to BACnet MS/TP.
Also known as: TFX-500w, TFX-500, Dynasonics TFX-500w, TTM-UM-02773 - Electromagnetic flow meter (BACnet daughterboard)
Badger Meter ModMAG M2000 electromagnetic flow meter (BACnet MS/TP and BACnet/IP)
Badger Meter ModMAG M2000 electromagnetic flow meters with the BACnet MS/TP or BACnet/IP communication daughterboard.
Also known as: M2000, ModMAG M2000, M2000 BACnet, M2000 mag meter BACnet, MAG-UM-03547, MAG-UM-03548, Badger mag meter BACnet - Vortex flow / BTU energy meter
Badger Meter VN2000 vortex flow meter (BACnet MS/TP)
Badger Meter VN2000 vortex flow meters for steam, gas and liquids (including BTU/energy models) with the optional BACnet MS/TP card.
Also known as: VN2000, Badger VN2000 vortex, VN2000 BTU meter
Source: TFX Ultra Flow and Energy Meters User Manual · TTM-UM-00136-EN-08 · rev. 2018-03. Object names, instances and units are reproduced as published; descriptions are our own.