Ultrasonic flow and BTU meter (BACnet IP card) · BACnet points list
Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) BACnet points list
Updated 28 October 2026
With the optional Ethernet card set to BACnet/IP, the TFX-5000 serves a read-only set of Analog Values: flow rate and velocity (home-screen, US and metric units), totals and overflow counters in home-screen units, gallons and liters, cutoff settings and signal strength, plus Multi-state Values that report the selected units. Energy meters add energy rate, two temperatures, delta T and energy totals in home-screen units, kBTU and kWh. The instance numbers differ from the RS-485 BACnet MS/TP list.
This page lists 73 BACnet objects for the Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Badger Meter’s own free documentation, linked below.
- Manufacturer
- Badger Meter
- Model
- Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)
- Equipment
- Ultrasonic flow and BTU meter (BACnet IP card)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 73 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- TFX-5000 BACnet/IP, TFX-5000 Ethernet, Dynasonics TFX-5000 BACnet IP, TTM-UM-03250, TFX-5000 Energy BACnet IP
BMS integration notes: Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)
Fit the Ethernet card, set Card Type to Autodetect or BACnet/IP, then read flow rate, the net total and (on BTU meters) energy rate, temperatures and the net energy total. All objects are read-only.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 600 | Flow Rate on Screen | Flow rate, home-screen units | Read |
| AV 1100 | Flow Totalizer, Net | Net volume total, home-screen units | Read |
| AV 604 | Energy/BTU Rate | Energy rate (BTU meters) | Read |
| AV 605 | Temperature #1 | Temperature 1 (BTU meters) | Read |
| AV 606 | Temperature #2 | Temperature 2 (BTU meters) | Read |
| AV 1108 | Energy/BTU Total, Net | Net energy total (BTU meters) | Read |
| AV 1500 | Signal Quality | Ultrasonic signal strength | Read |
Network setup
- The BACnet/IP card is an option with an RJ-45 port; set Main Menu > System Setup > Options > Card Type to Autodetect or BACnet/IP.
- Network and BACnet settings are made in the meter's BACnet/IP menu.
Watch out for
- Totals are 32-bit AVs only on this card; watch the overflow counters on large totals.
- Flow-only meters do not have the energy and temperature objects.
- Instance numbers differ from the RS-485 BACnet MS/TP list; don't reuse an MS/TP mapping.
Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 600 | Flow Rate on Screen | Flow Rate in home-screen units | Read | ||
| AV | 601 | Velocity on Screen | Velocity in home-screen units | Read | ||
| AV | 602 | Delta Time Filtered (ns) | Upstream/downstream transit-time difference | ns | Read | |
| AVmin | 604 | Energy/BTU Rate | Energy rate in home-screen units | Read | ||
| AVmin | 605 | Temperature #1 | Temperature 1 in home-screen units | Read | ||
| AVmin | 606 | Temperature #2 | Temperature 2 in home-screen units | Read | ||
| AV | 607 | Delta Temperature | Temperature difference in home-screen units | Read | ||
| AV | 800 | Flow Rate (gal/min) | Flow rate | gal/min | Read | |
| AV | 801 | Velocity (ft/sec) | Fluid velocity | ft/s | Read | |
| AV | 802 | Energy Rate (kBTU/h) | Energy rate | kBTU/h | Read | |
| AV | 1000 | Flow Rate (l/min) | Flow rate | L/min | Read | |
| AV | 1001 | Velocity (m/sec) | Fluid velocity | m/s | Read | |
| AV | 1002 | Energy Rate (kW) | Energy rate | kW | Read | |
| AV | 1304 | Flow Total Decimal Places | Decimal places shown for flow totals | Read | ||
| AV | 1309 | Energy Total Decimal Places | Decimal places shown for energy totals | Read | ||
| AVmin | 1100 | Flow Totalizer, Net | Forward minus reverse volume, home-screen units | Read | ||
| AV | 1101 | Flow Totalizer, Positive | Forward volume total, home-screen units | Read | ||
| AV | 1102 | Flow Totalizer, Negative | Reverse volume total, home-screen units | Read | ||
| AV | 1103 | Flow Totalizer, Gross | Forward plus reverse volume, home-screen units | Read | ||
| AV | 1104 | Flow Totalizer Overflow Counter, Net | Times this total has rolled over | Read | ||
| AV | 1105 | Flow Totalizer Overflow Counter, Positive | Times this total has rolled over | Read | ||
| AV | 1106 | Flow Totalizer Overflow Counter, Negative | Times this total has rolled over | Read | ||
| AV | 1107 | Flow Totalizer Overflow Counter, Gross | Times this total has rolled over | Read | ||
| AVmin | 1108 | Energy/BTU Total, Net | Positive minus negative energy, home-screen units | Read | ||
| AV | 1109 | Energy/BTU Total, Positive | Energy total, forward (heating), home-screen units | Read | ||
| AV | 1110 | Energy/BTU Total, Negative | Energy total, reverse (cooling), home-screen units | Read | ||
| AV | 1111 | Energy/BTU Total, Gross | Positive plus negative energy, home-screen units | Read | ||
| AV | 1112 | Energy/BTU Totalizer Overflow Counter, Net | Times this total has rolled over | Read | ||
| AV | 1113 | Energy/BTU Totalizer Overflow Counter, Positive | Times this total has rolled over | Read | ||
| AV | 1114 | Energy/BTU Totalizer Overflow Counter, Negative | Times this total has rolled over | Read | ||
| AV | 1115 | Energy/BTU Totalizer Overflow Counter, Gross | Times this total has rolled over | Read | ||
| AV | 1150 | Flow Totalizer (gal), Net | Forward minus reverse volume | gal | Read | |
| AV | 1151 | Flow Totalizer (gal), Positive | Forward volume total | gal | Read | |
| AV | 1152 | Flow Totalizer (gal), Negative | Reverse volume total | gal | Read | |
| AV | 1153 | Flow Totalizer (gal), Gross | Forward plus reverse volume | gal | Read | |
| AV | 1154 | Totalizer Overflow Counter, Net | Times this total has rolled over | Read | ||
| AV | 1155 | Totalizer Overflow Counter, Positive | Times this total has rolled over | Read | ||
| AV | 1156 | Totalizer Overflow Counter, Negative | Times this total has rolled over | Read | ||
| AV | 1157 | Totalizer Overflow Counter, Gross | Times this total has rolled over | Read | ||
| AV | 1158 | Energy/BTU Total (kBTU), Net | Positive minus negative energy | kBTU | Read | |
| AV | 1159 | Energy/BTU Total (kBTU), Positive | Energy total, forward (heating) | kBTU | Read | |
| AV | 1160 | Energy/BTU Total (kBTU), Negative | Energy total, reverse (cooling) | kBTU | Read | |
| AV | 1161 | Energy/BTU Total (kBTU), Gross | Positive plus negative energy | kBTU | Read | |
| AV | 1162 | kBTU Totalizer Overflow Counter, Net | Times this total has rolled over | Read | ||
| AV | 1163 | kBTU Totalizer Overflow Counter, Positive | Times this total has rolled over | Read | ||
| AV | 1164 | kBTU Totalizer Overflow Counter, Negative | Times this total has rolled over | Read | ||
| AV | 1165 | kBTU Totalizer Overflow Counter, Gross | Times this total has rolled over | Read | ||
| AV | 1200 | Flow Totalizer (liters), Net | Forward minus reverse volume | L | Read | |
| AV | 1201 | Flow Totalizer (liters), Positive | Forward volume total | L | Read | |
| AV | 1202 | Flow Totalizer (liters), Negative | Reverse volume total | L | Read | |
| AV | 1203 | Flow Totalizer (liters), Gross | Forward plus reverse volume | L | Read | |
| AV | 1204 | Totalizer Overflow Counter, Net | Times this total has rolled over | Read | ||
| AV | 1205 | Totalizer Overflow Counter, Positive | Times this total has rolled over | Read | ||
| AV | 1206 | Totalizer Overflow Counter, Negative | Times this total has rolled over | Read | ||
| AV | 1207 | Totalizer Overflow Counter, Gross | Times this total has rolled over | Read | ||
| AV | 1208 | Energy Total (kWh), Net | Positive minus negative energy | kWh | Read | |
| AV | 1209 | Energy Total (kWh), Positive | Energy total, forward (heating) | kWh | Read | |
| AV | 1210 | Energy Total (kWh), Negative | Energy total, reverse (cooling) | kWh | Read | |
| AV | 1211 | Energy Total (kWh), Gross | Positive plus negative energy | kWh | Read | |
| AV | 1212 | kWh Totalizer Overflow Counter, Net | Times this total has rolled over | Read | ||
| AV | 1213 | kWh Totalizer Overflow Counter, Positive | Times this total has rolled over | Read | ||
| AV | 1214 | kWh Totalizer Overflow Counter, Negative | Times this total has rolled over | Read | ||
| AV | 1215 | kWh Totalizer Overflow Counter, Gross | Times this total has rolled over | Read | ||
| AV | 1400 | Low Flow Cutoff | Flow below this reads zero and stops totalizing | Read | ||
| AV | 1401 | Low Signal Cutoff | Signal below this reads zero flow | Read | ||
| AV | 1402 | High Signal Cutoff | Signal above this reads zero flow | Read | ||
| AVmin | 1500 | Signal Quality | Ultrasonic signal strength | Read | ||
| MV | 1300 | Flow Rate Units | Flow Rate units selected for the home screen | Read | 1=L/s, 2=L/min, 3=L/h, 4=m³/s, 5=m³/min, 6=m³/h, 7=ft³/s, 8=ft³/min, 9=ft³/h, 10=gal/s, 11=gal/min, 12=gal/h, 13=Mgal/day, 14=Imp gal/s, 15=Imp gal/min, 16=Imp gal/h, 19=oil bbl/min, 20=Mega Imp gal/day, 21=oil bbl/day, 22=acre-ft/day, 23=fluid bbl/day, 24=Imp bbl/day, 25=custom | |
| MV | 1302 | Velocity Units | Velocity units selected for the home screen | Read | 1=m/s, 10=ft/s | |
| MV | 1303 | Flow Total Units | Flow Total units selected for the home screen | Read | 1=L, 2=hL, 3=m³, 4=ft³, 5=gal, 6=Mgal, 7=Imp gal, 10=acre-ft, 11=oil bbl, 12=Imp Mgal, 13=liquid bbl, 17=custom | |
| MV | 1306 | Energy Rate Units | Energy Rate units selected for the home screen | Read | 1=custom, 2=W, 3=kW, 4=MW, 5=BTU/h, 6=kBTU/h, 7=MBTU/h, 8=kJ/h, 9=MJ/h, 10=kcal/h, 11=Mcal/h, 12=tons | |
| MV | 1308 | Temperature Units | Temperature units selected for the home screen | Read | 1=°C, 2=°F, 3=K | |
| MV | 1309 | Energy Total Units | Energy Total units selected for the home screen | Read | 1=custom, 2=Wh, 3=kWh, 4=MWh, 5=BTU, 6=kBTU, 7=MMBTU, 8=kJ, 9=MJ, 10=kcal, 11=Mcal, 12=ton-hours |
No points match these filters.
Integration notes
- This is the energy-meter table; flow-only meters lack AV 604-607, AV 802, AV 1002, AV 1309, the energy totals and counters (AV 1108-1115, 1158-1165, 1208-1215) and MV 1306, 1308, 1309.
- Every object in this list is read-only; the BACnet/IP card has no reset or reboot objects.
- The flow-meter table names AV 1500 'Signal Strength'; the energy-meter table calls it 'Signal Quality'.
- Several overflow counters share a name; the instance tells them apart.
- If the BACnet/IP menu is missing, set Main Menu > System Setup > Options > Card Type to Autodetect or BACnet/IP.
- Source is user manual TTM-UM-03250-EN-04 (January 2026).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)
How many BACnet points does the Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) have?
This list has 73 BACnet objects: 67 analog values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) BACnet documentation?
The source is TFX-5000 Meter BACnet/IP Ethernet Protocol User Manual (TTM-UM-03250-EN-04), revision 2026-01, published free by Badger Meter at https://badgermeter.widen.net/content/slo6qi1gwu/original?download=false&x.app=api.
What are the minimum BACnet points to integrate the Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)?
Start with AV 600 Flow Rate on Screen (Flow rate, home-screen units); AV 1100 Flow Totalizer, Net (Net volume total, home-screen units); AV 604 Energy/BTU Rate (Energy rate (BTU meters)); AV 605 Temperature #1 (Temperature 1 (BTU meters)); AV 606 Temperature #2 (Temperature 2 (BTU meters)); AV 1108 Energy/BTU Total, Net (Net energy total (BTU meters)); AV 1500 Signal Quality (Ultrasonic signal strength).
How do I check these points on the real Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Badger Meter BACnet points lists
- Ultrasonic flow and BTU meter (BACnet MS/TP)
Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet MS/TP)
Badger Meter Dynasonics TFX-5000 clamp-on ultrasonic flow meters and TFX-5000 energy (BTU) meters, using the built-in RS-485 port in BACnet MS/TP mode.
Also known as: TFX-5000, Dynasonics TFX-5000, TFX-5000 BACnet, TFX-5000 Energy, TTM-UM-03074, clamp-on BTU meter BACnet, Badger ultrasonic flow meter BACnet - Electromagnetic flow meter (BACnet daughterboard)
Badger Meter ModMAG M2000 electromagnetic flow meter (BACnet MS/TP and BACnet/IP)
Badger Meter ModMAG M2000 electromagnetic flow meters with the BACnet MS/TP or BACnet/IP communication daughterboard.
Also known as: M2000, ModMAG M2000, M2000 BACnet, M2000 mag meter BACnet, MAG-UM-03547, MAG-UM-03548, Badger mag meter BACnet
Source: TFX-5000 Meter BACnet/IP Ethernet Protocol User Manual · TTM-UM-03250-EN-04 · rev. 2026-01. Object names, instances and units are reproduced as published; descriptions are our own.