Easy BACnet
  1. Home
  2. BACnet points lists
  3. Badger Meter
  4. Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)

Ultrasonic flow and BTU meter (BACnet IP card) · BACnet points list

Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) BACnet points list

Updated 28 October 2026

Short answer

With the optional Ethernet card set to BACnet/IP, the TFX-5000 serves a read-only set of Analog Values: flow rate and velocity (home-screen, US and metric units), totals and overflow counters in home-screen units, gallons and liters, cutoff settings and signal strength, plus Multi-state Values that report the selected units. Energy meters add energy rate, two temperatures, delta T and energy totals in home-screen units, kBTU and kWh. The instance numbers differ from the RS-485 BACnet MS/TP list.

This page lists 73 BACnet objects for the Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Badger Meter’s own free documentation, linked below.

Manufacturer
Badger Meter
Model
Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)
Equipment
Ultrasonic flow and BTU meter (BACnet IP card)
Equipment type
Thermostats, sensors & meters
BACnet objects
73 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
TFX-5000 BACnet/IP, TFX-5000 Ethernet, Dynasonics TFX-5000 BACnet IP, TTM-UM-03250, TFX-5000 Energy BACnet IP
Source document
TFX-5000 Meter BACnet/IP Ethernet Protocol User Manual · TTM-UM-03250-EN-04 · rev. 2026-01
Download CSV 73 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)

Integration in brief

Fit the Ethernet card, set Card Type to Autodetect or BACnet/IP, then read flow rate, the net total and (on BTU meters) energy rate, temperatures and the net energy total. All objects are read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 600Flow Rate on ScreenFlow rate, home-screen unitsRead
AV 1100Flow Totalizer, NetNet volume total, home-screen unitsRead
AV 604Energy/BTU RateEnergy rate (BTU meters)Read
AV 605Temperature #1Temperature 1 (BTU meters)Read
AV 606Temperature #2Temperature 2 (BTU meters)Read
AV 1108Energy/BTU Total, NetNet energy total (BTU meters)Read
AV 1500Signal QualityUltrasonic signal strengthRead

Network setup

Watch out for

Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

73 of 73 shown
Type
AnalogMulti-state
Show
Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) BACnet Points List
DescriptionStates
AVmin600Flow Rate on ScreenFlow Rate in home-screen unitsRead
AV601Velocity on ScreenVelocity in home-screen unitsRead
AV602Delta Time Filtered (ns)Upstream/downstream transit-time differencensRead
AVmin604Energy/BTU RateEnergy rate in home-screen unitsRead
AVmin605Temperature #1Temperature 1 in home-screen unitsRead
AVmin606Temperature #2Temperature 2 in home-screen unitsRead
AV607Delta TemperatureTemperature difference in home-screen unitsRead
AV800Flow Rate (gal/min)Flow rategal/minRead
AV801Velocity (ft/sec)Fluid velocityft/sRead
AV802Energy Rate (kBTU/h)Energy ratekBTU/hRead
AV1000Flow Rate (l/min)Flow rateL/minRead
AV1001Velocity (m/sec)Fluid velocitym/sRead
AV1002Energy Rate (kW)Energy ratekWRead
AV1304Flow Total Decimal PlacesDecimal places shown for flow totalsRead
AV1309Energy Total Decimal PlacesDecimal places shown for energy totalsRead
AVmin1100Flow Totalizer, NetForward minus reverse volume, home-screen unitsRead
AV1101Flow Totalizer, PositiveForward volume total, home-screen unitsRead
AV1102Flow Totalizer, NegativeReverse volume total, home-screen unitsRead
AV1103Flow Totalizer, GrossForward plus reverse volume, home-screen unitsRead
AV1104Flow Totalizer Overflow Counter, NetTimes this total has rolled overRead
AV1105Flow Totalizer Overflow Counter, PositiveTimes this total has rolled overRead
AV1106Flow Totalizer Overflow Counter, NegativeTimes this total has rolled overRead
AV1107Flow Totalizer Overflow Counter, GrossTimes this total has rolled overRead
AVmin1108Energy/BTU Total, NetPositive minus negative energy, home-screen unitsRead
AV1109Energy/BTU Total, PositiveEnergy total, forward (heating), home-screen unitsRead
AV1110Energy/BTU Total, NegativeEnergy total, reverse (cooling), home-screen unitsRead
AV1111Energy/BTU Total, GrossPositive plus negative energy, home-screen unitsRead
AV1112Energy/BTU Totalizer Overflow Counter, NetTimes this total has rolled overRead
AV1113Energy/BTU Totalizer Overflow Counter, PositiveTimes this total has rolled overRead
AV1114Energy/BTU Totalizer Overflow Counter, NegativeTimes this total has rolled overRead
AV1115Energy/BTU Totalizer Overflow Counter, GrossTimes this total has rolled overRead
AV1150Flow Totalizer (gal), NetForward minus reverse volumegalRead
AV1151Flow Totalizer (gal), PositiveForward volume totalgalRead
AV1152Flow Totalizer (gal), NegativeReverse volume totalgalRead
AV1153Flow Totalizer (gal), GrossForward plus reverse volumegalRead
AV1154Totalizer Overflow Counter, NetTimes this total has rolled overRead
AV1155Totalizer Overflow Counter, PositiveTimes this total has rolled overRead
AV1156Totalizer Overflow Counter, NegativeTimes this total has rolled overRead
AV1157Totalizer Overflow Counter, GrossTimes this total has rolled overRead
AV1158Energy/BTU Total (kBTU), NetPositive minus negative energykBTURead
AV1159Energy/BTU Total (kBTU), PositiveEnergy total, forward (heating)kBTURead
AV1160Energy/BTU Total (kBTU), NegativeEnergy total, reverse (cooling)kBTURead
AV1161Energy/BTU Total (kBTU), GrossPositive plus negative energykBTURead
AV1162kBTU Totalizer Overflow Counter, NetTimes this total has rolled overRead
AV1163kBTU Totalizer Overflow Counter, PositiveTimes this total has rolled overRead
AV1164kBTU Totalizer Overflow Counter, NegativeTimes this total has rolled overRead
AV1165kBTU Totalizer Overflow Counter, GrossTimes this total has rolled overRead
AV1200Flow Totalizer (liters), NetForward minus reverse volumeLRead
AV1201Flow Totalizer (liters), PositiveForward volume totalLRead
AV1202Flow Totalizer (liters), NegativeReverse volume totalLRead
AV1203Flow Totalizer (liters), GrossForward plus reverse volumeLRead
AV1204Totalizer Overflow Counter, NetTimes this total has rolled overRead
AV1205Totalizer Overflow Counter, PositiveTimes this total has rolled overRead
AV1206Totalizer Overflow Counter, NegativeTimes this total has rolled overRead
AV1207Totalizer Overflow Counter, GrossTimes this total has rolled overRead
AV1208Energy Total (kWh), NetPositive minus negative energykWhRead
AV1209Energy Total (kWh), PositiveEnergy total, forward (heating)kWhRead
AV1210Energy Total (kWh), NegativeEnergy total, reverse (cooling)kWhRead
AV1211Energy Total (kWh), GrossPositive plus negative energykWhRead
AV1212kWh Totalizer Overflow Counter, NetTimes this total has rolled overRead
AV1213kWh Totalizer Overflow Counter, PositiveTimes this total has rolled overRead
AV1214kWh Totalizer Overflow Counter, NegativeTimes this total has rolled overRead
AV1215kWh Totalizer Overflow Counter, GrossTimes this total has rolled overRead
AV1400Low Flow CutoffFlow below this reads zero and stops totalizingRead
AV1401Low Signal CutoffSignal below this reads zero flowRead
AV1402High Signal CutoffSignal above this reads zero flowRead
AVmin1500Signal QualityUltrasonic signal strengthRead
MV1300Flow Rate UnitsFlow Rate units selected for the home screenRead1=L/s, 2=L/min, 3=L/h, 4=m³/s, 5=m³/min, 6=m³/h, 7=ft³/s, 8=ft³/min, 9=ft³/h, 10=gal/s, 11=gal/min, 12=gal/h, 13=Mgal/day, 14=Imp gal/s, 15=Imp gal/min, 16=Imp gal/h, 19=oil bbl/min, 20=Mega Imp gal/day, 21=oil bbl/day, 22=acre-ft/day, 23=fluid bbl/day, 24=Imp bbl/day, 25=custom
MV1302Velocity UnitsVelocity units selected for the home screenRead1=m/s, 10=ft/s
MV1303Flow Total UnitsFlow Total units selected for the home screenRead1=L, 2=hL, 3=m³, 4=ft³, 5=gal, 6=Mgal, 7=Imp gal, 10=acre-ft, 11=oil bbl, 12=Imp Mgal, 13=liquid bbl, 17=custom
MV1306Energy Rate UnitsEnergy Rate units selected for the home screenRead1=custom, 2=W, 3=kW, 4=MW, 5=BTU/h, 6=kBTU/h, 7=MBTU/h, 8=kJ/h, 9=MJ/h, 10=kcal/h, 11=Mcal/h, 12=tons
MV1308Temperature UnitsTemperature units selected for the home screenRead1=°C, 2=°F, 3=K
MV1309Energy Total UnitsEnergy Total units selected for the home screenRead1=custom, 2=Wh, 3=kWh, 4=MWh, 5=BTU, 6=kBTU, 7=MMBTU, 8=kJ, 9=MJ, 10=kcal, 11=Mcal, 12=ton-hours

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)

How many BACnet points does the Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) have?

This list has 73 BACnet objects: 67 analog values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) BACnet documentation?

The source is TFX-5000 Meter BACnet/IP Ethernet Protocol User Manual (TTM-UM-03250-EN-04), revision 2026-01, published free by Badger Meter at https://badgermeter.widen.net/content/slo6qi1gwu/original?download=false&x.app=api.

What are the minimum BACnet points to integrate the Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)?

Start with AV 600 Flow Rate on Screen (Flow rate, home-screen units); AV 1100 Flow Totalizer, Net (Net volume total, home-screen units); AV 604 Energy/BTU Rate (Energy rate (BTU meters)); AV 605 Temperature #1 (Temperature 1 (BTU meters)); AV 606 Temperature #2 (Temperature 2 (BTU meters)); AV 1108 Energy/BTU Total, Net (Net energy total (BTU meters)); AV 1500 Signal Quality (Ultrasonic signal strength).

How do I check these points on the real Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Badger Meter BACnet points lists

Source: TFX-5000 Meter BACnet/IP Ethernet Protocol User Manual · TTM-UM-03250-EN-04 · rev. 2026-01. Object names, instances and units are reproduced as published; descriptions are our own.