Ultrasonic flow and BTU meter (BACnet MS/TP) · BACnet points list

Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet MS/TP) BACnet points list

Updated 28 October 2026

Short answer

The TFX-5000's RS-485 port can run Modbus RTU or BACnet MS/TP. In BACnet MS/TP mode it serves flow rate, velocity and totalizer Analog Values in home-screen, US and metric units, 64-bit Large Analog Value copies of each total, Multi-state Values that report the selected units, three writable cutoff settings, and four Binary Output actions (reset totals, unlatch alarms, clear alarm history, reboot). Energy meters add energy rate, two temperatures, delta T and energy totals. This list is the energy-meter table; flow-only meters have the same objects minus the energy and temperature ones.

This page lists 99 BACnet objects for the Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet MS/TP) — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Badger Meter’s own free documentation, linked below.

Manufacturer
Badger Meter
Model
Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet MS/TP)
Equipment
Ultrasonic flow and BTU meter (BACnet MS/TP)
Equipment type
Thermostats, sensors & meters
BACnet objects
99 (7 writable)
Transport
BACnet MS/TP
Firmware
02.02.536 (PICS)
Also known as
TFX-5000, Dynasonics TFX-5000, TFX-5000 BACnet, TFX-5000 Energy, TTM-UM-03074, clamp-on BTU meter BACnet, Badger ultrasonic flow meter BACnet
Source document
TFX-5000 Meter BACnet MS/TP Protocol User Manual · TTM-UM-03074-EN-07 · rev. 2026-01
Download CSV 99 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet MS/TP)

Integration in brief

Select BACnet MS/TP in the meter's communication menu, set the MAC address and BACnet ID, and match baud, parity and stop bits. Read flow rate and totals (and energy rate, temperatures and energy totals on BTU meters). Use the 64-bit LAV totals where possible. Writes (cutoffs and the BO actions) need the Access setting at read/write.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 600Flow Rate on ScreenFlow rate, home-screen unitsRead
LAV 2600Net Flow TotalizerNet volume total, 64-bitRead
AV 604Energy/BTU RateEnergy rate (BTU meters)Read
AV 605Temperature #1Temperature 1 (BTU meters)Read
AV 606Temperature #2Temperature 2 (BTU meters)Read
LAV 2608Energy/BTU Net TotalNet energy total, 64-bit (BTU meters)Read
AV 5500Signal StrengthUltrasonic signal strengthRead

Network setup

Watch out for

Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

99 of 99 shown
Type
AnalogBinaryMulti-stateOther
Access
Show
Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet MS/TP) BACnet Points List
DescriptionStates
AVmin600Flow Rate on ScreenFlow Rate in home-screen unitsRead
AV601Velocity on ScreenVelocity in home-screen unitsRead
AV602Delta Time Filtered (ns)Upstream/downstream transit-time differencensRead
AVmin604Energy/BTU RateEnergy rate in home-screen unitsRead
AVmin605Temperature #1Temperature 1 in home-screen unitsRead
AVmin606Temperature #2Temperature 2 in home-screen unitsRead
AV607Delta TemperatureTemperature difference in home-screen unitsRead
AV800Flow Rate (gal/min)Flow rategal/minRead
AV801Velocity (ft/sec)Fluid velocityft/sRead
AV802Energy Rate (kBTU/h)Energy ratekBTU/hRead
AV1000Flow Rate (l/min)Flow rateL/minRead
AV1001Velocity (m/sec)Fluid velocitym/sRead
AV1002Energy Rate (kW)Energy ratekWRead
AV2300Net Flow TotalizerForward minus reverse volume, home-screen unitsRead
LAVmin2600Net Flow Totalizer64-bit copy of AV 2300Read
AV2301Positive Flow TotalizerForward volume total, home-screen unitsRead
LAV2601Positive Flow Totalizer64-bit copy of AV 2301Read
AV2302Negative Flow TotalizerReverse volume total, home-screen unitsRead
LAV2602Negative Flow Totalizer64-bit copy of AV 2302Read
AV2303Gross Flow TotalizerForward plus reverse volume, home-screen unitsRead
LAV2603Gross Flow Totalizer64-bit copy of AV 2303Read
AV2304Flow Totalizer Overflow Counter (Net)Times this total has rolled overRead
AV2305Flow Totalizer Overflow Counter (Positive)Times this total has rolled overRead
AV2306Flow Totalizer Overflow Counter (Negative)Times this total has rolled overRead
AV2307Flow Totalizer Overflow Counter (Gross)Times this total has rolled overRead
AV2308Energy/BTU Net TotalPositive minus negative energy, home-screen unitsRead
LAVmin2608Energy/BTU Net Total64-bit copy of AV 2308Read
AV2309Energy/BTU Positive TotalEnergy total, forward (heating), home-screen unitsRead
LAV2609Energy/BTU Positive Total64-bit copy of AV 2309Read
AV2310Energy/BTU Negative TotalEnergy total, reverse (cooling), home-screen unitsRead
LAV2610Energy/BTU Negative Total64-bit copy of AV 2310Read
AV2311Energy/BTU Gross TotalPositive plus negative energy, home-screen unitsRead
LAV2611Energy/BTU Gross Total64-bit copy of AV 2311Read
AV2312Energy/BTU Totalizer Overflow Counter (Net)Times this total has rolled overRead
AV2313Energy/BTU Totalizer Overflow Counter (Positive)Times this total has rolled overRead
AV2314Energy/BTU Totalizer Overflow Counter (Negative)Times this total has rolled overRead
AV2315Energy/BTU Totalizer Overflow Counter (Gross)Times this total has rolled overRead
AV2400Net Flow Totalizer (gal)Forward minus reverse volumegalRead
LAV2700Net Flow Totalizer (gal)64-bit copy of AV 2400galRead
AV2401Positive Flow Totalizer (gal)Forward volume totalgalRead
LAV2701Positive Flow Totalizer (gal)64-bit copy of AV 2401galRead
AV2402Negative Flow Totalizer (gal)Reverse volume totalgalRead
LAV2702Negative Flow Totalizer (gal)64-bit copy of AV 2402galRead
AV2403Gross Flow Totalizer (gal)Forward plus reverse volumegalRead
LAV2703Gross Flow Totalizer (gal)64-bit copy of AV 2403galRead
AV2404Totalizer Overflow Counter (Net)Times this total has rolled overRead
AV2405Totalizer Overflow Counter (Positive)Times this total has rolled overRead
AV2406Totalizer Overflow Counter (Negative)Times this total has rolled overRead
AV2407Totalizer Overflow Counter (Gross)Times this total has rolled overRead
AV2408Energy/BTU Net Total (kBTU)Positive minus negative energykBTURead
LAV2708Energy/BTU Net Total (kBTU)64-bit copy of AV 2408kBTURead
AV2409Energy/BTU Positive Total (kBTU)Energy total, forward (heating)kBTURead
LAV2709Energy/BTU Positive Total (kBTU)64-bit copy of AV 2409kBTURead
AV2410Energy/BTU Negative Total (kBTU)Energy total, reverse (cooling)kBTURead
LAV2710Energy/BTU Negative Total (kBTU)64-bit copy of AV 2410kBTURead
AV2411Energy/BTU Gross Total (kBTU)Positive plus negative energykBTURead
LAV2711Energy/BTU Gross Total (kBTU)64-bit copy of AV 2411kBTURead
AV2412Net kBTU Totalizer Overflow CounterTimes this total has rolled overRead
AV2413Positive kBTU Totalizer Overflow CounterTimes this total has rolled overRead
AV2414Negative kBTU Totalizer Overflow CounterTimes this total has rolled overRead
AV2415Gross kBTU Totalizer Overflow CounterTimes this total has rolled overRead
AV2500Net Flow Totalizer (liters)Forward minus reverse volumeLRead
LAV2800Net Flow Totalizer (liters)64-bit copy of AV 2500LRead
AV2501Positive Flow Totalizer (liters)Forward volume totalLRead
LAV2801Positive Flow Totalizer (liters)64-bit copy of AV 2501LRead
AV2502Negative Flow Totalizer (liters)Reverse volume totalLRead
LAV2802Negative Flow Totalizer (liters)64-bit copy of AV 2502LRead
AV2503Gross Flow Totalizer (liters)Forward plus reverse volumeLRead
LAV2803Gross Flow Totalizer (liters)64-bit copy of AV 2503LRead
AV2504Totalizer Overflow Counter (Net)Times this total has rolled overRead
AV2505Totalizer Overflow Counter (Positive)Times this total has rolled overRead
AV2506Totalizer Overflow Counter (Negative)Times this total has rolled overRead
AV2507Totalizer Overflow Counter (Gross)Times this total has rolled overRead
AV2508Energy Net Total (kWh)Positive minus negative energykWhRead
LAV2808Energy Net Total (kWh)64-bit copy of AV 2508kWhRead
AV2509Energy Positive Total (kWh)Energy total, forward (heating)kWhRead
LAV2809Energy Positive Total (kWh)64-bit copy of AV 2509kWhRead
AV2510Energy Negative Total (kWh)Energy total, reverse (cooling)kWhRead
LAV2810Energy Negative Total (kWh)64-bit copy of AV 2510kWhRead
AV2511Energy Gross Total (kWh)Positive plus negative energykWhRead
LAV2811Energy Gross Total (kWh)64-bit copy of AV 2511kWhRead
AV2512Net kWh Totalizer Overflow CounterTimes this total has rolled overRead
AV2513Positive kWh Totalizer Overflow CounterTimes this total has rolled overRead
AV2514Negative kWh Totalizer Overflow CounterTimes this total has rolled overRead
AV2515Gross kWh Totalizer Overflow CounterTimes this total has rolled overRead
MV3000Flow Rate UnitsFlow Rate units selected for the home screenRead1=L/s, 2=L/min, 3=L/h, 4=m³/s, 5=m³/min, 6=m³/h, 7=ft³/s, 8=ft³/min, 9=ft³/h, 10=gal/s, 11=gal/min, 12=gal/h, 13=Mgal/day, 14=Imp gal/s, 15=Imp gal/min, 16=Imp gal/h, 19=oil bbl/min, 20=Mega Imp gal/day, 21=oil bbl/day, 22=acre-ft/day, 23=fluid bbl/day, 24=Imp bbl/day, 25=custom
MV3002Velocity UnitsVelocity units selected for the home screenRead1=m/s, 10=ft/s
MV3003Flow Total UnitsFlow Total units selected for the home screenRead1=L, 2=hL, 3=m³, 4=ft³, 5=gal, 6=Mgal, 7=Imp gal, 10=acre-ft, 11=oil bbl, 12=Imp Mgal, 13=liquid bbl, 17=custom
MV3006Energy Rate UnitsEnergy Rate units selected for the home screenRead1=custom, 2=W, 3=kW, 4=MW, 5=BTU/h, 6=kBTU/h, 7=MBTU/h, 8=kJ/h, 9=MJ/h, 10=kcal/h, 11=Mcal/h, 12=tons
MV3008Temperature UnitsTemperature units selected for the home screenRead1=°C, 2=°F, 3=K
MV3009Energy Total UnitsEnergy Total units selected for the home screenRead1=custom, 2=Wh, 3=kWh, 4=MWh, 5=BTU, 6=kBTU, 7=MMBTU, 8=kJ, 9=MJ, 10=kcal, 11=Mcal, 12=ton-hours
AV4000Low Flow CutoffFlow below this reads zero and stops totalizingWrite
AV4001Low Signal CutoffSignal below this reads zero flowWrite
AV4002High Signal CutoffSignal above this reads zero flowWrite
AVmin5500Signal StrengthUltrasonic signal strengthRead
BO0Reset TotalizersReset all flow totals to zeroWrite
BO1Unlatch AlarmsRelease latched alarm outputsWrite
BO2Clear Alarm HistoryClear stored errors, alarms and eventsWrite
BO3Reboot DeviceRestart the meterWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet MS/TP)

How many BACnet points does the Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet MS/TP) have?

This list has 99 BACnet objects: 65 analog values, 4 binary outputs, 6 multi-state values, 24 large analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet MS/TP) BACnet points are writable?

7 of the 99 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet MS/TP) BACnet documentation?

The source is TFX-5000 Meter BACnet MS/TP Protocol User Manual (TTM-UM-03074-EN-07), revision 2026-01, published free by Badger Meter at https://badgermeter.widen.net/content/8nc9jpqgfl/original?download=false&x.app=api.

What are the minimum BACnet points to integrate the Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet MS/TP)?

Start with AV 600 Flow Rate on Screen (Flow rate, home-screen units); LAV 2600 Net Flow Totalizer (Net volume total, 64-bit); AV 604 Energy/BTU Rate (Energy rate (BTU meters)); AV 605 Temperature #1 (Temperature 1 (BTU meters)); AV 606 Temperature #2 (Temperature 2 (BTU meters)); LAV 2608 Energy/BTU Net Total (Net energy total, 64-bit (BTU meters)); AV 5500 Signal Strength (Ultrasonic signal strength).

How do I check these points on the real Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Badger Meter BACnet points lists