Vortex flow / BTU energy meter · BACnet points list
Badger Meter VN2000 vortex flow meter (BACnet MS/TP) BACnet points list
Updated 6 November 2026
The VN2000 vortex meter has an optional BACnet MS/TP interface with a short fixed object list: flow or energy rate, net totalizer, two temperatures and pressure, plus a totalizer reset. Flow and energy units follow the meter setup.
This page lists 6 BACnet objects for the Badger Meter VN2000 vortex flow meter (BACnet MS/TP) — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Badger Meter’s own free documentation, linked below.
- Manufacturer
- Badger Meter
- Model
- VN2000 vortex flow meter (BACnet MS/TP)
- Equipment
- Vortex flow / BTU energy meter
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 6 (1 writable)
- Transport
- BACnet MS/TP
- Firmware
- 14.01, application 3.00 (PICS, 10/27/2017)
- Also known as
- VN2000, Badger VN2000 vortex, VN2000 BTU meter
Reference only, provided as-is: verify against Badger Meter’s current documentation and the live device before use. Not official Badger Meter information. Terms of use.
BMS integration notes: Badger Meter VN2000 vortex flow meter (BACnet MS/TP)
Set the MS/TP baud, MAC (0-127) and device ID from the keypad in program mode level 2, then read flow or energy rate (AI 1), the totalizer and temperatures.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1 | Flow Rate(Flow Model) / Energy Rate (BTU Model) | Flow rate, or energy rate on BTU models | Read |
| PIV 2 | Net Totalizer | Net totalized flow or energy | Read |
| AI 3 | Temperature 1 | Supply temperature (BTU models) | Read |
| AI 4 | Temperature 2 (BTU) | Return temperature (BTU models) | Read |
| AI 5 | Pressure | Process pressure | Read |
Network setup
- Baud 9600, 19,200, 38,400 or 76,800 (per the intro; the PICS lists 19,200-115,200), MAC 0-127 and device ID 0-4194302 are set on the keypad.
- Bus length up to 4000 ft; the meter does not terminate the line.
Watch out for
- Writing BV 1 resets the totalizer.
- On meters with a manual temperature or pressure override, the AI returns the override value, not a live reading.
Badger Meter VN2000 vortex flow meter (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BV | 1 | Reset Totalizer | Resets the totalizer | Write | ||
| AImin | 1 | Flow Rate(Flow Model) / Energy Rate (BTU Model) | Flow rate, or energy rate on BTU models | gal, L, ft3, m3, lb, kg, BTU, kBTU, ton per s/min/h/day | Read | |
| PIVmin | 2 | Net Totalizer | Net totalized flow or energy | Read | ||
| AImin | 3 | Temperature 1 | Temperature (supply temperature on BTU models) | °C / °F | Read | |
| AImin | 4 | Temperature 2 (BTU) | Return temperature on BTU models | °C / °F | Read | |
| AImin | 5 | Pressure | Pressure used in the flow calculation | psig / bar | Read |
No points match these filters.
Object ID lookup: Badger Meter VN2000 vortex flow meter point IDs by name
Integration notes
- Points from Table 1 of the protocol manual; the table gives a description per object rather than a separate object name.
- The object table lists the reset as BV-1, but the PICS in the same manual lists a Binary Output instead of a Binary Value; check on the meter.
- Temperature and pressure values may be manual override values or not live on meters without the matching sensor.
- No access column; access is inferred from object type.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VN2000 vortex flow meter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Badger Meter VN2000 vortex flow meter (BACnet MS/TP)
How many BACnet points does the Badger Meter VN2000 vortex flow meter (BACnet MS/TP) have?
This list has 6 BACnet objects: 4 analog inputs, 1 binary value, 1 positive integer value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Badger Meter VN2000 vortex flow meter (BACnet MS/TP) BACnet points are writable?
1 of the 6 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Badger Meter VN2000 vortex flow meter (BACnet MS/TP) BACnet documentation?
The source is VN2000 Flow Meters - BACnet MS/TP Communication Protocol (VRX-UM-02583-EN-03), revision June 2022, published free by Badger Meter at https://badgermeter.widen.net/content/hsrxzm4kxt/original?download=true&x.app=api.
What are the minimum BACnet points to integrate the Badger Meter VN2000 vortex flow meter (BACnet MS/TP)?
Start with AI 1 Flow Rate(Flow Model) / Energy Rate (BTU Model) (Flow rate, or energy rate on BTU models); PIV 2 Net Totalizer (Net totalized flow or energy); AI 3 Temperature 1 (Supply temperature (BTU models)); AI 4 Temperature 2 (BTU) (Return temperature (BTU models)); AI 5 Pressure (Process pressure).
How do I check these points on the real VN2000 vortex flow meter (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Badger Meter BACnet points lists
- Ultrasonic flow and BTU meter (BACnet MS/TP)
Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet MS/TP)
Badger Meter Dynasonics TFX-5000 clamp-on ultrasonic flow meters and TFX-5000 energy (BTU) meters, using the built-in RS-485 port in BACnet MS/TP mode.
Also known as: TFX-5000, Dynasonics TFX-5000, TFX-5000 BACnet, TFX-5000 Energy, TTM-UM-03074, clamp-on BTU meter BACnet, Badger ultrasonic flow meter BACnet - Ultrasonic flow and BTU meter (BACnet IP card)
Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)
Badger Meter Dynasonics TFX-5000 flow and energy (BTU) meters fitted with the optional Ethernet card set to BACnet/IP.
Also known as: TFX-5000 BACnet/IP, TFX-5000 Ethernet, Dynasonics TFX-5000 BACnet IP, TTM-UM-03250, TFX-5000 Energy BACnet IP - Ultrasonic flow meter (clamp-on)
Badger Meter Dynasonics TFX-500w clamp-on ultrasonic flow meter (BACnet MS/TP)
Badger Meter Dynasonics TFX-500w clamp-on transit-time ultrasonic flow meters with the RS-485 port set to BACnet MS/TP.
Also known as: TFX-500w, TFX-500, Dynasonics TFX-500w, TTM-UM-02773 - Electromagnetic flow meter (BACnet daughterboard)
Badger Meter ModMAG M2000 electromagnetic flow meter (BACnet MS/TP and BACnet/IP)
Badger Meter ModMAG M2000 electromagnetic flow meters with the BACnet MS/TP or BACnet/IP communication daughterboard.
Also known as: M2000, ModMAG M2000, M2000 BACnet, M2000 mag meter BACnet, MAG-UM-03547, MAG-UM-03548, Badger mag meter BACnet
Source: VN2000 Flow Meters - BACnet MS/TP Communication Protocol · VRX-UM-02583-EN-03 · rev. June 2022. Object names, instances and units are reproduced as published; descriptions are our own.