Btu energy meter (transmitter) · BACnet points list

Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The 340 BN/MB computes hydronic thermal energy from a flow sensor and supply/return temperature sensors. Its RS-485 port runs Modbus or BACnet MS/TP (slave). The BACnet map has five analog inputs (both temperatures, input frequency, flow rate, energy rate) and 17 analog values for the flow and energy totals plus the calibration and filter settings.

This page lists 22 BACnet objects for the Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Badger Meter’s documentation hosted by Instrumart, not by Badger Meter itself, so treat it as unofficial.

Manufacturer
Badger Meter
Model
Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP)
Equipment
Btu energy meter (transmitter)
Equipment type
Thermostats, sensors & meters
BACnet objects
22 (0 writable)
Transport
BACnet MS/TP
Firmware
Rev 1.00 (PICS)
Also known as
340 BN/MB, 340BN/MB, B340BN, Series 340, Data Industrial 340, Badger 340 Btu transmitter, XMT-UM-01660
Source document
Series 340 BN/MB Btu Energy Transmitter User Manual · XMT-UM-01660-EN-05 · rev. 2018-04 (unofficial copy, hosted by Instrumart)
Download CSV 22 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Badger Meter’s current documentation and the live device before use. Not official Badger Meter information. Terms of use.

BMS integration notes: Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP)

Integration in brief

Program the transmitter with the Badger Meter software and A301 cable: choose BACnet for the RS-485 port, set the MS/TP address, baud rate, device name and device instance. Then read energy rate and total, flow rate and total and both temperatures.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 5EnrgyFlowEnergy rateRead
AV 2TotEnergyEnergy totalRead
AI 4VolFlowFlow rateRead
AV 1TotalVolFlow totalRead
AI 1TempInSupply temperatureRead
AI 2TempOutReturn temperatureRead

Network setup

Watch out for

Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

22 of 22 shown
Type
Show
Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1TempInSupply (inlet) temperature°C, °FRead
AImin2TempOutReturn (outlet) temperature°C, °FRead
AI3FreqInFlow sensor input frequencyHzRead
AImin4VolFlowVolumetric flow rategpm, gph, lpm, lph, ft3/s, ft3/m, ft3/h, m3/s, m3/min, m3/hRead
AImin5EnrgyFlowEnergy ratekBtu/min, kBtu/h, kW, MW, HP, TonsRead
AVmin1TotalVolFlow totalgallons, liters, ft3, m3Read
AVmin2TotEnergyEnergy totalBtu, kBtu, MBtu, kWh, MWh, kJ, MJRead
AV3KfactorFlow sensor K factordimensionlessRead
AV4OffsetFlow sensor offsetdimensionlessRead
AV5TempModeTemperature calculation modedimensionlessRead
AV6FFilterCoefFlow filter coefficientdimensionlessRead
AV7TFiltCoefTemperature filter coefficientdimensionlessRead
AV8SpHtCapacFluid specific heatBtu/lb-FRead
AV9DensityFluid densitylb/gallonRead
AV10InTACoefInlet sensor A coefficientdimensionlessRead
AV11InTBCoefInlet sensor B coefficientdimensionlessRead
AV12InTCCoefInlet sensor C coefficientdimensionlessRead
AV13InTOffsetInlet temperature offset°C, °FRead
AV14OutTACoefOutlet sensor A coefficientdimensionlessRead
AV15OuTBCoefOutlet sensor B coefficientdimensionlessRead
AV16OutTCCoefOutlet sensor C coefficientdimensionlessRead
AV17OutTOffsetOutlet temperature offset°C, °FRead
Object ID lookup: Badger Meter 340 BN/MB Btu Transmitter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP)

How many BACnet points does the Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP) have?

This list has 22 BACnet objects: 5 analog inputs, 17 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP) BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP) BACnet documentation?

Badger Meter does not publish it on its own website. This list comes from Series 340 BN/MB Btu Energy Transmitter User Manual (XMT-UM-01660-EN-05), revision 2018-04, a copy hosted by Instrumart at https://www.instrumart.com/assets/badger-340_manual.pdf. Ask Badger Meter or its representative for the current revision.

What are the minimum BACnet points to integrate the Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP)?

Start with AI 5 EnrgyFlow (Energy rate); AV 2 TotEnergy (Energy total); AI 4 VolFlow (Flow rate); AV 1 TotalVol (Flow total); AI 1 TempIn (Supply temperature); AI 2 TempOut (Return temperature).

How do I check these points on the real Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Badger Meter BACnet points lists

Source: Series 340 BN/MB Btu Energy Transmitter User Manual · XMT-UM-01660-EN-05 · rev. 2018-04. Object names, instances and units are reproduced as published; descriptions are our own.