Btu energy meter (transmitter) · BACnet points list
Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP) BACnet points list
Updated 12 November 2026Unofficial source
The 340 BN/MB computes hydronic thermal energy from a flow sensor and supply/return temperature sensors. Its RS-485 port runs Modbus or BACnet MS/TP (slave). The BACnet map has five analog inputs (both temperatures, input frequency, flow rate, energy rate) and 17 analog values for the flow and energy totals plus the calibration and filter settings.
This page lists 22 BACnet objects for the Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Badger Meter’s documentation hosted by Instrumart, not by Badger Meter itself, so treat it as unofficial.
- Manufacturer
- Badger Meter
- Model
- Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP)
- Equipment
- Btu energy meter (transmitter)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 22 (0 writable)
- Transport
- BACnet MS/TP
- Firmware
- Rev 1.00 (PICS)
- Also known as
- 340 BN/MB, 340BN/MB, B340BN, Series 340, Data Industrial 340, Badger 340 Btu transmitter, XMT-UM-01660
- Source document
- Series 340 BN/MB Btu Energy Transmitter User Manual · XMT-UM-01660-EN-05 · rev. 2018-04 (unofficial copy, hosted by Instrumart)
Reference only, provided as-is: verify against Badger Meter’s current documentation and the live device before use. Not official Badger Meter information. Terms of use.
BMS integration notes: Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP)
Program the transmitter with the Badger Meter software and A301 cable: choose BACnet for the RS-485 port, set the MS/TP address, baud rate, device name and device instance. Then read energy rate and total, flow rate and total and both temperatures.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 5 | EnrgyFlow | Energy rate | Read |
| AV 2 | TotEnergy | Energy total | Read |
| AI 4 | VolFlow | Flow rate | Read |
| AV 1 | TotalVol | Flow total | Read |
| AI 1 | TempIn | Supply temperature | Read |
| AI 2 | TempOut | Return temperature | Read |
Network setup
- BACnet settings are made with the Badger Meter Windows software, not over the network.
- Defaults: MS/TP address 1, 9600 baud, max master 127; no default device instance is given.
- The manual suggests building the device instance from the network number plus the MS/TP address.
- Change the default address before adding the unit to a live network.
Watch out for
- Pick BACnet (not Pulse Out Only or Modbus) for the RS-485 port, or the BACnet objects are not served.
Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | TempIn | Supply (inlet) temperature | °C, °F | Read | |
| AImin | 2 | TempOut | Return (outlet) temperature | °C, °F | Read | |
| AI | 3 | FreqIn | Flow sensor input frequency | Hz | Read | |
| AImin | 4 | VolFlow | Volumetric flow rate | gpm, gph, lpm, lph, ft3/s, ft3/m, ft3/h, m3/s, m3/min, m3/h | Read | |
| AImin | 5 | EnrgyFlow | Energy rate | kBtu/min, kBtu/h, kW, MW, HP, Tons | Read | |
| AVmin | 1 | TotalVol | Flow total | gallons, liters, ft3, m3 | Read | |
| AVmin | 2 | TotEnergy | Energy total | Btu, kBtu, MBtu, kWh, MWh, kJ, MJ | Read | |
| AV | 3 | Kfactor | Flow sensor K factor | dimensionless | Read | |
| AV | 4 | Offset | Flow sensor offset | dimensionless | Read | |
| AV | 5 | TempMode | Temperature calculation mode | dimensionless | Read | |
| AV | 6 | FFilterCoef | Flow filter coefficient | dimensionless | Read | |
| AV | 7 | TFiltCoef | Temperature filter coefficient | dimensionless | Read | |
| AV | 8 | SpHtCapac | Fluid specific heat | Btu/lb-F | Read | |
| AV | 9 | Density | Fluid density | lb/gallon | Read | |
| AV | 10 | InTACoef | Inlet sensor A coefficient | dimensionless | Read | |
| AV | 11 | InTBCoef | Inlet sensor B coefficient | dimensionless | Read | |
| AV | 12 | InTCCoef | Inlet sensor C coefficient | dimensionless | Read | |
| AV | 13 | InTOffset | Inlet temperature offset | °C, °F | Read | |
| AV | 14 | OutTACoef | Outlet sensor A coefficient | dimensionless | Read | |
| AV | 15 | OuTBCoef | Outlet sensor B coefficient | dimensionless | Read | |
| AV | 16 | OutTCCoef | Outlet sensor C coefficient | dimensionless | Read | |
| AV | 17 | OutTOffset | Outlet temperature offset | °C, °F | Read |
No points match these filters.
Object ID lookup: Badger Meter 340 BN/MB Btu Transmitter point IDs by name
Integration notes
- The manual prints the analog input IDs as AN1-AN5; they are shown here as AI 1-5.
- The BACnet map has no read/write column; all objects are shown as read-only. The matching Modbus registers are all marked read-only.
- Units follow the units chosen when the transmitter is programmed; the map lists the possible units.
- The device is an MS/TP slave, so it does not pass the token.
- Source: Table 2 'BACnet object map', page 22 (22 objects).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP)
How many BACnet points does the Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP) have?
This list has 22 BACnet objects: 5 analog inputs, 17 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP) BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP) BACnet documentation?
Badger Meter does not publish it on its own website. This list comes from Series 340 BN/MB Btu Energy Transmitter User Manual (XMT-UM-01660-EN-05), revision 2018-04, a copy hosted by Instrumart at https://www.instrumart.com/assets/badger-340_manual.pdf. Ask Badger Meter or its representative for the current revision.
What are the minimum BACnet points to integrate the Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP)?
Start with AI 5 EnrgyFlow (Energy rate); AV 2 TotEnergy (Energy total); AI 4 VolFlow (Flow rate); AV 1 TotalVol (Flow total); AI 1 TempIn (Supply temperature); AI 2 TempOut (Return temperature).
How do I check these points on the real Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Badger Meter BACnet points lists
- Btu energy meter (impeller)
Badger Meter Data Industrial Series 380 impeller Btu system 380CS / 380HS (BACnet MS/TP)
Badger Meter / Data Industrial Series 380 impeller Btu systems (380CS cold, 380HS hot) with the RS-485 output set to BACnet.
Also known as: Series 380, 380CS, 380HS, 380CS/HS, Data Industrial 380, Badger 380 Btu meter, 880102-0001 - Ultrasonic flow / energy meter
Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet IP Ethernet module)
Dynasonics TFX Ultra clamp-on flow and energy transmitters ordered with the Ethernet module, set to BACnet IP.
Also known as: TFX Ultra, TFX Ultra BACnet IP, Dynasonics TFX Ultra, TFX Ultra Ethernet, TTM-UM-00136 - Ultrasonic flow / energy meter
Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP)
Dynasonics TFX Ultra clamp-on flow and energy transmitters ordered with the BACnet MS/TP RS-485 option.
Also known as: TFX Ultra, TFX Ultra BACnet MS/TP, Dynasonics TFX Ultra, TTM-UM-00136 - Ultrasonic flow and BTU meter (BACnet MS/TP)
Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet MS/TP)
Badger Meter Dynasonics TFX-5000 clamp-on ultrasonic flow meters and TFX-5000 energy (BTU) meters, using the built-in RS-485 port in BACnet MS/TP mode.
Also known as: TFX-5000, Dynasonics TFX-5000, TFX-5000 BACnet, TFX-5000 Energy, TTM-UM-03074, clamp-on BTU meter BACnet, Badger ultrasonic flow meter BACnet - Ultrasonic flow and BTU meter (BACnet IP card)
Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)
Badger Meter Dynasonics TFX-5000 flow and energy (BTU) meters fitted with the optional Ethernet card set to BACnet/IP.
Also known as: TFX-5000 BACnet/IP, TFX-5000 Ethernet, Dynasonics TFX-5000 BACnet IP, TTM-UM-03250, TFX-5000 Energy BACnet IP - Ultrasonic flow meter (clamp-on)
Badger Meter Dynasonics TFX-500w clamp-on ultrasonic flow meter (BACnet MS/TP)
Badger Meter Dynasonics TFX-500w clamp-on transit-time ultrasonic flow meters with the RS-485 port set to BACnet MS/TP.
Also known as: TFX-500w, TFX-500, Dynasonics TFX-500w, TTM-UM-02773 - Electromagnetic flow meter (BACnet daughterboard)
Badger Meter ModMAG M2000 electromagnetic flow meter (BACnet MS/TP and BACnet/IP)
Badger Meter ModMAG M2000 electromagnetic flow meters with the BACnet MS/TP or BACnet/IP communication daughterboard.
Also known as: M2000, ModMAG M2000, M2000 BACnet, M2000 mag meter BACnet, MAG-UM-03547, MAG-UM-03548, Badger mag meter BACnet - Vortex flow / BTU energy meter
Badger Meter VN2000 vortex flow meter (BACnet MS/TP)
Badger Meter VN2000 vortex flow meters for steam, gas and liquids (including BTU/energy models) with the optional BACnet MS/TP card.
Also known as: VN2000, Badger VN2000 vortex, VN2000 BTU meter
Source: Series 340 BN/MB Btu Energy Transmitter User Manual · XMT-UM-01660-EN-05 · rev. 2018-04. Object names, instances and units are reproduced as published; descriptions are our own.