Btu energy meter (impeller) · BACnet points list

Badger Meter Data Industrial Series 380 impeller Btu system 380CS / 380HS (BACnet MS/TP) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The Series 380 is an impeller flow sensor tee with two temperature probes and built-in Btu electronics. Its RS-485 port runs Modbus RTU or BACnet MS/TP (slave). The BACnet map has two temperature inputs and ten analog values: flow and energy rate, flow and energy totals, calculation mode, filter coefficients, specific heat, density and serial number.

This page lists 12 BACnet objects for the Badger Meter Data Industrial Series 380 impeller Btu system 380CS / 380HS (BACnet MS/TP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Badger Meter’s documentation hosted by Instrumart, not by Badger Meter itself, so treat it as unofficial.

Manufacturer
Badger Meter
Model
Data Industrial Series 380 impeller Btu system 380CS / 380HS (BACnet MS/TP)
Equipment
Btu energy meter (impeller)
Equipment type
Thermostats, sensors & meters
BACnet objects
12 (0 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
Series 380, 380CS, 380HS, 380CS/HS, Data Industrial 380, Badger 380 Btu meter, 880102-0001
Source document
Series 380 Impeller Btu System Installation & Operation Manual · 880102-0001 Rev. 4 · rev. 2011-07 (unofficial copy, hosted by Instrumart)
Download CSV 12 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Badger Meter’s current documentation and the live device before use. Not official Badger Meter information. Terms of use.

BMS integration notes: Badger Meter Data Industrial Series 380 impeller Btu system 380CS / 380HS (BACnet MS/TP)

Integration in brief

Commission the meter with the Series 380 software over USB: choose BACnet, then set device name, device ID, baud rate and max master. Read energy rate and total, flow rate and total and the two temperatures.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 2EnergyFlowEnergy rateRead
AV 4TotEnergyEnergy totalRead
AV 1VolFlowFlow rateRead
AV 3TotalVolFlow totalRead
AI 1TempInTemperature at the flow teeRead
AI 2TempOutRemote temperature probeRead

Network setup

Watch out for

Badger Meter Data Industrial Series 380 impeller Btu system 380CS / 380HS (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

12 of 12 shown
Type
Show
Badger Meter Data Industrial Series 380 impeller Btu system 380CS / 380HS (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1TempInTemperature of the sensor in the flow tee°C, °FRead
AImin2TempOutRemote temperature sensor°C, °FRead
AVmin1VolFlowFlow rategpm, gph, lpm, lps, lph, ft3/s, ft3/m, ft3/h, m3/s, m3/min, m3/h, customRead
AVmin2EnergyFlowEnergy ratekBtu/min, kBtu/h, kW, MW, HP, Tons, customRead
AVmin3TotalVolFlow totalgallons, galx100, galx1000, liters, ft3, m3, customRead
AVmin4TotEnergyEnergy totalBtu, kBtu, MBtu, kWh, MWh, kJ, MJ, customRead
AV5TempModeEnergy calculation modedimensionlessRead
AV6FFilterCoefFlow filter coefficientdimensionlessRead
AV7TFiltCoefTemperature filter coefficientdimensionlessRead
AV8SpHtCapacFluid specific heatBtu/lb-FRead
AV9DensityFluid densitylb/gallonRead
AV10SerialNumMeter serial numberdimensionlessRead
Object ID lookup: Badger Meter Series 380 Btu System point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Data Industrial Series 380 impeller Btu system 380CS / 380HS (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Badger Meter Data Industrial Series 380 impeller Btu system 380CS / 380HS (BACnet MS/TP)

How many BACnet points does the Badger Meter Data Industrial Series 380 impeller Btu system 380CS / 380HS (BACnet MS/TP) have?

This list has 12 BACnet objects: 2 analog inputs, 10 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Badger Meter Data Industrial Series 380 impeller Btu system 380CS / 380HS (BACnet MS/TP) BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Badger Meter Data Industrial Series 380 impeller Btu system 380CS / 380HS (BACnet MS/TP) BACnet documentation?

Badger Meter does not publish it on its own website. This list comes from Series 380 Impeller Btu System Installation & Operation Manual (880102-0001 Rev. 4), revision 2011-07, a copy hosted by Instrumart at https://core.instrumart.com/assets/badger-380-manual.pdf. Ask Badger Meter or its representative for the current revision.

What are the minimum BACnet points to integrate the Badger Meter Data Industrial Series 380 impeller Btu system 380CS / 380HS (BACnet MS/TP)?

Start with AV 2 EnergyFlow (Energy rate); AV 4 TotEnergy (Energy total); AV 1 VolFlow (Flow rate); AV 3 TotalVol (Flow total); AI 1 TempIn (Temperature at the flow tee); AI 2 TempOut (Remote temperature probe).

How do I check these points on the real Data Industrial Series 380 impeller Btu system 380CS / 380HS (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Badger Meter BACnet points lists

Source: Series 380 Impeller Btu System Installation & Operation Manual · 880102-0001 Rev. 4 · rev. 2011-07. Object names, instances and units are reproduced as published; descriptions are our own.