- Home
- BACnet points lists
- Xylem
- Lowara hydrovar X HVX / HVX+ pump drive (BACnet MS/TP)
Pump frequency drive (motor-mounted) · BACnet points list
Xylem Lowara hydrovar X HVX / HVX+ pump drive (BACnet MS/TP) BACnet points list
Updated 12 November 2026
The hydrovar X HVX / HVX+ drive mounts on the pump motor and has BACnet MS/TP built in. Analog Inputs give the last ten errors with their logged operating data, actual pressure, flow, temperature and level, speed, current, power, voltages, temperatures, I/O status and firmware versions; Analog Values carry start/stop, error reset and the full drive parameter set (control mode, setpoints, ramps, limits, sensor scaling, multipump and communication settings). Three CharacterString values hold part and serial numbers.
This page lists 402 BACnet objects for the Xylem Lowara hydrovar X HVX / HVX+ pump drive (BACnet MS/TP) — 155 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Xylem’s own free documentation, linked below.
- Manufacturer
- Xylem
- Model
- Lowara hydrovar X HVX / HVX+ pump drive (BACnet MS/TP)
- Equipment
- Pump frequency drive (motor-mounted)
- Equipment type
- VFDs & pumps
- BACnet objects
- 402 (155 writable)
- Transport
- BACnet MS/TP
- Firmware
- 01.00.00
- Default device instance
- 84003
- Also known as
- hydrovar X, HVX, HVX+, Lowara HVX, Lowara hydrovar X, 001088108
Reference only, provided as-is: verify against Xylem’s current documentation and the live device before use. Not official Xylem information. Terms of use.
BMS integration notes: Xylem Lowara hydrovar X HVX / HVX+ pump drive (BACnet MS/TP)
Start and stop the pump with AV 0 and reset errors with AV 1. Choose the control mode (AV 3) and write the active setpoint; read pump status (AI 211), actual pressure (AI 205), motor speed (AI 215/216), power and the most recent error (AI 0).
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 0 | SET_STARTSTOP | Start/stop: 0 = stop, 1 = start | Write |
| AV 3 | SET_CONTROLMOD | Control mode | Write |
| AV 1 | ERRORRESTCMD | Error reset command | Write |
| AI 211 | PUMPDEVICESTAT | Pump status | Read |
| AI 205 | HEAD | Actual pressure (head) | Read |
| AI 215 | MOTOR_SPEED | Motor speed, rpm | Read |
| AI 218 | OUTPUTPOWER | Motor power | Read |
| AI 0 | ERROR1CODE | Most recent error code | Read |
Enable & remote start
AV 0 SET_STARTSTOP starts (1) and stops (0) the pump.
Network setup
- Factory device instance 84003 (P08.2.04 or Object_Identifier); MAC address 1 (P08.2.01); MS/TP settings are AV 142-148.
- Wire RS-485 to terminals 31 (B), 32 (A) and 33 (C).
Watch out for
- Set P04.1.60 Limit Setpoint Saving (AV 163) to Yes before writing setpoints cyclically, to spare the EEPROM.
- Bitfield objects (error, alarm, status) must be split into bits; the meanings are in the manual.
Xylem Lowara hydrovar X HVX / HVX+ pump drive (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| CSV | 0 | PARTNUMBER | Unit Part Number; menu P03.4.01 | Read | ||
| CSV | 1 | SERIALFINISHED | Unit Serial Number; menu P03.4.03 | Read | ||
| CSV | 2 | SERIAL_DRIVE | Drive Serial Number; menu P03.4.06 | Read | ||
| AImin | 0 | ERROR1CODE | Error 1 (Most Recent); menu P02.0.01 | Read | ||
| AI | 1 | ERROR1DATE | Error 1 - Date | Read | ||
| AI | 2 | ERROR1TIME | Error 1 - Time | Read | ||
| AI | 3 | ERROR1ENDDATE | Error 1 - End Date | Read | ||
| AI | 4 | ERROR1ENDTIME | Error 1 - End time | Read | ||
| AI | 5 | LOGERRORCOUN 1 | Log: Error Counter | Read | ||
| AI | 6 | LOGERROR1BF 1 | Log: Error 1 Bitfield | Read | ||
| AI | 7 | LOGERROR2BF 1 | Log: Error 2 Bitfield | Read | ||
| AI | 8 | LOGALARM1BF 1 | Log: Alarm 1 Bitfield | Read | ||
| AI | 9 | LOGSYSSTATUS 1 | Log: System Status | Read | ||
| AI | 10 | LOGINTERNALC 1 | Log: Error code | Read | ||
| AI | 11 | LOGFLOW 1 | Log: Flow Rate; unit per P04.0.12 | Read | ||
| AI | 12 | LOGHEAD 1 | Log: Head; unit per P04.0.11 | Read | ||
| AI | 13 | LOGIGBTTEMP 1 | Log: Power Module Temperature; unit per P04.0.13 | Read | ||
| AI | 14 | LOG_I_MOT 1 | Log: Motor Current | A | Read | |
| AI | 15 | LOG_V_MOT 1 | Log: Motor Voltage | V | Read | |
| AI | 16 | LOGINNERTEMP 1 | Log: Inverter Temperature; unit per P04.0.13 | Read | ||
| AI | 17 | LOGTORQUE 1 | Log: Motor Power | Read | ||
| AI | 18 | LOG_DC_BUSVO 1 | Log: DC Bus Voltage | V | Read | |
| AI | 19 | LOGGRIDVOLTA 1 | Log: Grid Voltage | V | Read | |
| AI | 20 | ERROR2CODE | Error 2; menu P02.0.02 | Read | ||
| AI | 21 | ERROR2DATE | Error 2 - Date | Read | ||
| AI | 22 | ERROR2TIME | Error 2 - Time | Read | ||
| AI | 23 | ERROR2ENDDATE | Error 2 - End Date | Read | ||
| AI | 24 | ERROR2ENDTIME | Error 2 - End time | Read | ||
| AI | 25 | LOGERRORCOUN 2 | Log: Error Counter | Read | ||
| AI | 26 | LOGERROR1BF 2 | Log: Error 1 Bitfield | Read | ||
| AI | 27 | LOGERROR2BF 2 | Log: Error 2 Bitfield | Read | ||
| AI | 28 | LOGALARM1BF 2 | Log: Alarm 1 Bitfield | Read | ||
| AI | 29 | LOGSYSSTATUS 2 | Log: System Status | Read | ||
| AI | 30 | LOGINTERNALC 2 | Log: Error code | Read | ||
| AI | 31 | LOGFLOW 2 | Log: Flow Rate; unit per P04.0.12 | Read | ||
| AI | 32 | LOGHEAD 2 | Log: Head; unit per P04.0.11 | Read | ||
| AI | 33 | LOGIGBTTEMP 2 | Log: Power Module Temperature; unit per P04.0.13 | Read | ||
| AI | 34 | LOG_I_MOT 2 | Log: Motor Current | A | Read | |
| AI | 35 | LOG_V_MOT 2 | Log: Motor Voltage | V | Read | |
| AI | 36 | LOGINNERTEMP 2 | Log: Inverter Temperature; unit per P04.0.13 | Read | ||
| AI | 37 | LOGTORQUE 2 | Log: Motor Power | Read | ||
| AI | 38 | LOG_DC_BUSVO 2 | Log: DC Bus Voltage | V | Read | |
| AI | 39 | LOGGRIDVOLTA 2 | Log: Grid Voltage | V | Read | |
| AI | 40 | ERROR3CODE | Error 3; menu P02.0.03 | Read | ||
| AI | 41 | ERROR3DATE | Error 3 - Date | Read | ||
| AI | 42 | ERROR3TIME | Error 3 - Time | Read | ||
| AI | 43 | ERROR3ENDDATE | Error 3 - End Date | Read | ||
| AI | 44 | ERROR3ENDTIME | Error 3 - End time | Read | ||
| AI | 45 | LOGERRORCOUN 3 | Log: Error Counter | Read | ||
| AI | 46 | LOGERROR1BF 3 | Log: Error 1 Bitfield | Read | ||
| AI | 47 | LOGERROR2BF 3 | Log: Error 2 Bitfield | Read | ||
| AI | 48 | LOGALARM1BF 3 | Log: Alarm 1 Bitfield | Read | ||
| AI | 49 | LOGSYSSTATUS 3 | Log: System Status | Read | ||
| AI | 50 | LOGINTERNALC 3 | Log: Error code | Read | ||
| AI | 51 | LOGFLOW 3 | Log: Flow Rate; unit per P04.0.12 | Read | ||
| AI | 52 | LOGHEAD 3 | Log: Head; unit per P04.0.11 | Read | ||
| AI | 53 | LOGIGBTTEMP 3 | Log: Power Module Temperature; unit per P04.0.13 | Read | ||
| AI | 54 | LOG_I_MOT 3 | Log: Motor Current | A | Read | |
| AI | 55 | LOG_V_MOT 3 | Log: Motor Voltage | V | Read | |
| AI | 56 | LOGINNERTEMP 3 | Log: Inverter Temperature; unit per P04.0.13 | Read | ||
| AI | 57 | LOGTORQUE 3 | Log: Motor Power | Read | ||
| AI | 58 | LOG_DC_BUSVO 3 | Log: DC Bus Voltage | V | Read | |
| AI | 59 | LOGGRIDVOLTA 3 | Log: Grid Voltage | V | Read | |
| AI | 60 | ERROR4CODE | Error 4; menu P02.0.04 | Read | ||
| AI | 61 | ERROR4DATE | Error 4 - Date | Read | ||
| AI | 62 | ERROR4TIME | Error 4 - Time | Read | ||
| AI | 63 | ERROR4ENDDATE | Error 4 - End Date | Read | ||
| AI | 64 | ERROR4ENDTIME | Error 4 - End time | Read | ||
| AI | 65 | LOGERRORCOUN 4 | Log: Error Counter | Read | ||
| AI | 66 | LOGERROR1BF 4 | Log: Error 1 Bitfield | Read | ||
| AI | 67 | LOGERROR2BF 4 | Log: Error 2 Bitfield | Read | ||
| AI | 68 | LOGALARM1BF 4 | Log: Alarm 1 Bitfield | Read | ||
| AI | 69 | LOGSYSSTATUS 4 | Log: System Status | Read | ||
| AI | 70 | LOGINTERNALC 4 | Log: Error code | Read | ||
| AI | 71 | LOGFLOW 4 | Log: Flow Rate; unit per P04.0.12 | Read | ||
| AI | 72 | LOGHEAD 4 | Log: Head; unit per P04.0.11 | Read | ||
| AI | 73 | LOGIGBTTEMP 4 | Log: Power Module Temperature; unit per P04.0.13 | Read | ||
| AI | 74 | LOG_I_MOT 4 | Log: Motor Current | A | Read | |
| AI | 75 | LOG_V_MOT 4 | Log: Motor Voltage | V | Read | |
| AI | 76 | LOGINNERTEMP 4 | Log: Inverter Temperature; unit per P04.0.13 | Read | ||
| AI | 77 | LOGTORQUE 4 | Log: Motor Power | Read | ||
| AI | 78 | LOG_DC_BUSVO 4 | Log: DC Bus Voltage | V | Read | |
| AI | 79 | LOGGRIDVOLTA 4 | Log: Grid Voltage | V | Read | |
| AI | 80 | ERROR5CODE | Error 5; menu P02.0.05 | Read | ||
| AI | 81 | ERROR5DATE | Error 5 - Date | Read | ||
| AI | 82 | ERROR5TIME | Error 5 - Time | Read | ||
| AI | 83 | ERROR5ENDDATE | Error 5 - End Date | Read | ||
| AI | 84 | ERROR5ENDTIME | Error 5 - End time | Read | ||
| AI | 85 | LOGERRORCOUN 5 | Log: Error Counter | Read | ||
| AI | 86 | LOGERROR1BF 5 | Log: Error 1 Bitfield | Read | ||
| AI | 87 | LOGERROR2BF 5 | Log: Error 2 Bitfield | Read | ||
| AI | 88 | LOGALARM1BF 5 | Log: Alarm 1 Bitfield | Read | ||
| AI | 89 | LOGSYSSTATUS 5 | Log: System Status | Read | ||
| AI | 90 | LOGINTERNALC 5 | Log: Error code | Read | ||
| AI | 91 | LOGFLOW 5 | Log: Flow Rate; unit per P04.0.12 | Read | ||
| AI | 92 | LOGHEAD 5 | Log: Head; unit per P04.0.11 | Read | ||
| AI | 93 | LOGIGBTTEMP 5 | Log: Power Module Temperature; unit per P04.0.13 | Read | ||
| AI | 94 | LOG_I_MOT 5 | Log: Motor Current | A | Read | |
| AI | 95 | LOG_V_MOT 5 | Log: Motor Voltage | V | Read | |
| AI | 96 | LOGINNERTEMP 5 | Log: Inverter Temperature; unit per P04.0.13 | Read | ||
| AI | 97 | LOGTORQUE 5 | Log: Motor Power | Read | ||
| AI | 98 | LOG_DC_BUSVO 5 | Log: DC Bus Voltage | V | Read | |
| AI | 99 | LOGGRIDVOLTA 5 | Log: Grid Voltage | V | Read | |
| AI | 100 | ERROR6CODE | Error 6; menu P02.0.06 | Read | ||
| AI | 101 | ERROR6DATE | Error 6 - Date | Read | ||
| AI | 102 | ERROR6TIME | Error 6 - Time | Read | ||
| AI | 103 | ERROR6ENDDATE | Error 6 - End Date | Read | ||
| AI | 104 | ERROR6ENDTIME | Error 6 - End time | Read | ||
| AI | 105 | LOGERRORCOUN 6 | Log: Error Counter | Read | ||
| AI | 106 | LOGERROR1BF 6 | Log: Error 1 Bitfield | Read | ||
| AI | 107 | LOGERROR2BF 6 | Log: Error 2 Bitfield | Read | ||
| AI | 108 | LOGALARM1BF 6 | Log: Alarm 1 Bitfield | Read | ||
| AI | 109 | LOGSYSSTATUS 6 | Log: System Status | Read | ||
| AI | 110 | LOGINTERNALC 6 | Log: Error code | Read | ||
| AI | 111 | LOGFLOW 6 | Log: Flow Rate; unit per P04.0.12 | Read | ||
| AI | 112 | LOGHEAD 6 | Log: Head; unit per P04.0.11 | Read | ||
| AI | 113 | LOGIGBTTEMP 6 | Log: Power Module Temperature; unit per P04.0.13 | Read | ||
| AI | 114 | LOG_I_MOT 6 | Log: Motor Current | A | Read | |
| AI | 115 | LOG_V_MOT 6 | Log: Motor Voltage | V | Read | |
| AI | 116 | LOGINNERTEMP 6 | Log: Inverter Temperature; unit per P04.0.13 | Read | ||
| AI | 117 | LOGTORQUE 6 | Log: Motor Power | Read | ||
| AI | 118 | LOG_DC_BUSVO 6 | Log: DC Bus Voltage | V | Read | |
| AI | 119 | LOGGRIDVOLTA 6 | Log: Grid Voltage | V | Read | |
| AI | 120 | ERROR7CODE | Error 7; menu P02.0.07 | Read | ||
| AI | 121 | ERROR7DATE | Error 7 - Date | Read | ||
| AI | 122 | ERROR7TIME | Error 7 - Time | Read | ||
| AI | 123 | ERROR7ENDDATE | Error 7 - End Date | Read | ||
| AI | 124 | ERROR7ENDTIME | Error 7 - End time | Read | ||
| AI | 125 | LOGERRORCOUN 7 | Log: Error Counter | Read | ||
| AI | 126 | LOGERROR1BF 7 | Log: Error 1 Bitfield | Read | ||
| AI | 127 | LOGERROR2BF 7 | Log: Error 2 Bitfield | Read | ||
| AI | 128 | LOGALARM1BF 7 | Log: Alarm 1 Bitfield | Read | ||
| AI | 129 | LOGSYSSTATUS 7 | Log: System Status | Read | ||
| AI | 130 | LOGINTERNALC 7 | Log: Error code | Read | ||
| AI | 131 | LOGFLOW 7 | Log: Flow Rate; unit per P04.0.12 | Read | ||
| AI | 132 | LOGHEAD 7 | Log: Head; unit per P04.0.11 | Read | ||
| AI | 133 | LOGIGBTTEMP 7 | Log: Power Module Temperature; unit per P04.0.13 | Read | ||
| AI | 134 | LOG_I_MOT 7 | Log: Motor Current | A | Read | |
| AI | 135 | LOG_V_MOT 7 | Log: Motor Voltage | V | Read | |
| AI | 136 | LOGINNERTEMP 7 | Log: Inverter Temperature; unit per P04.0.13 | Read | ||
| AI | 137 | LOGTORQUE 7 | Log: Motor Power | Read | ||
| AI | 138 | LOG_DC_BUSVO 7 | Log: DC Bus Voltage | V | Read | |
| AI | 139 | LOGGRIDVOLTA 7 | Log: Grid Voltage | V | Read | |
| AI | 140 | ERROR8CODE | Error 8; menu P02.0.08 | Read | ||
| AI | 141 | ERROR8DATE | Error 8 - Date | Read | ||
| AI | 142 | ERROR8TIME | Error 8 - Time | Read | ||
| AI | 143 | ERROR8ENDDATE | Error 8 - End Date | Read | ||
| AI | 144 | ERROR8ENDTIME | Error 8 - End time | Read | ||
| AI | 145 | LOGERRORCOUN 8 | Log: Error Counter | Read | ||
| AI | 146 | LOGERROR1BF 8 | Log: Error 1 Bitfield | Read | ||
| AI | 147 | LOGERROR2BF 8 | Log: Error 2 Bitfield | Read | ||
| AI | 148 | LOGALARM1BF 8 | Log: Alarm 1 Bitfield | Read | ||
| AI | 149 | LOGSYSSTATUS 8 | Log: System Status | Read | ||
| AI | 150 | LOGINTERNALC 8 | Log: Error code | Read | ||
| AI | 151 | LOGFLOW 8 | Log: Flow Rate; unit per P04.0.12 | Read | ||
| AI | 152 | LOGHEAD 8 | Log: Head; unit per P04.0.11 | Read | ||
| AI | 153 | LOGIGBTTEMP 8 | Log: Power Module Temperature; unit per P04.0.13 | Read | ||
| AI | 154 | LOG_I_MOT 8 | Log: Motor Current | A | Read | |
| AI | 155 | LOG_V_MOT 8 | Log: Motor Voltage | V | Read | |
| AI | 156 | LOGINNERTEMP 8 | Log: Inverter Temperature; unit per P04.0.13 | Read | ||
| AI | 157 | LOGTORQUE 8 | Log: Motor Power | Read | ||
| AI | 158 | LOG_DC_BUSVO 8 | Log: DC Bus Voltage | V | Read | |
| AI | 159 | LOGGRIDVOLTA 8 | Log: Grid Voltage | V | Read | |
| AI | 160 | ERROR9CODE | Error 9; menu P02.0.09 | Read | ||
| AI | 161 | ERROR9DATE | Error 9 - Date | Read | ||
| AI | 162 | ERROR9TIME | Error 9 - Time | Read | ||
| AI | 163 | ERROR9ENDDATE | Error 9 - End Date | Read | ||
| AI | 164 | ERROR9ENDTIME | Error 9 - End time | Read | ||
| AI | 165 | LOGERRORCOUN 9 | Log: Error Counter | Read | ||
| AI | 166 | LOGERROR1BF 9 | Log: Error 1 Bitfield | Read | ||
| AI | 167 | LOGERROR2BF 9 | Log: Error 2 Bitfield | Read | ||
| AI | 168 | LOGALARM1BF 9 | Log: Alarm 1 Bitfield | Read | ||
| AI | 169 | LOGSYSSTATUS 9 | Log: System Status | Read | ||
| AI | 170 | LOGINTERNALC 9 | Log: Error code | Read | ||
| AI | 171 | LOGFLOW 9 | Log: Flow Rate; unit per P04.0.12 | Read | ||
| AI | 172 | LOGHEAD 9 | Log: Head; unit per P04.0.11 | Read | ||
| AI | 173 | LOGIGBTTEMP 9 | Log: Power Module Temperature; unit per P04.0.13 | Read | ||
| AI | 174 | LOG_I_MOT 9 | Log: Motor Current | A | Read | |
| AI | 175 | LOG_V_MOT 9 | Log: Motor Voltage | V | Read | |
| AI | 176 | LOGINNERTEMP 9 | Log: Inverter Temperature; unit per P04.0.13 | Read | ||
| AI | 177 | LOGTORQUE 9 | Log: Motor Power | Read | ||
| AI | 178 | LOG_DC_BUSVO 9 | Log: DC Bus Voltage | V | Read | |
| AI | 179 | LOGGRIDVOLTA 9 | Log: Grid Voltage | V | Read | |
| AI | 180 | ERROR10CODE | Error 10; menu P02.0.10 | Read | ||
| AI | 181 | ERROR10DATE | Error 10 - Date | Read | ||
| AI | 182 | ERROR10TIME | Error 10 - Time | Read | ||
| AI | 183 | ERROR10ENDDATE | Error 10 - End Date | Read | ||
| AI | 184 | ERROR10ENDTIME | Error 10 - End time | Read | ||
| AI | 185 | LOGERRORCOU 10 | Log: Error Counter | Read | ||
| AI | 186 | LOGERROR1BF 10 | Log: Error 1 Bitfield | Read | ||
| AI | 187 | LOGERROR2BF 10 | Log: Error 2 Bitfield | Read | ||
| AI | 188 | LOGALARM1BF 10 | Log: Alarm 1 Bitfield | Read | ||
| AI | 189 | LOGSYSSTATU 10 | Log: System Status | Read | ||
| AI | 190 | LOGINTERNAL 10 | Log: Error code | Read | ||
| AI | 191 | LOGFLOW 10 | Log: Flow Rate; unit per P04.0.12 | Read | ||
| AI | 192 | LOGHEAD 10 | Log: Head; unit per P04.0.11 | Read | ||
| AI | 193 | LOGIGBTTEMP 10 | Log: Power Module Temperature; unit per P04.0.13 | Read | ||
| AI | 194 | LOG_I_MOT 10 | Log: Motor Current | A | Read | |
| AI | 195 | LOG_V_MOT 10 | Log: Motor Voltage | V | Read | |
| AI | 196 | LOGINNERTEM 10 | Log: Inverter Temperature; unit per P04.0.13 | Read | ||
| AI | 197 | LOGTORQUE 10 | Log: Motor Power | Read | ||
| AI | 198 | LOG_DC_BUSV 10 | Log: DC Bus Voltage | V | Read | |
| AI | 199 | LOGGRIDVOLT 10 | Log: Grid Voltage | V | Read | |
| AI | 200 | TOTAL_ERRORS_C | Total Error Counter | Read | ||
| AI | 201 | TOTAL_ALARMS_C | Total Alarms Counter | Read | ||
| AI | 202 | ERROR1_BF | Read | |||
| AI | 203 | ERROR2_BF | Read | |||
| AI | 204 | ALARM1_BF | Alarm bitfield (bit list in manual) | Read | ||
| AImin | 205 | HEAD | Current pressure (head); menu P03.0.01 | Read | ||
| AI | 206 | FLOW | Actual Flow; menu P03.0.02; unit per P04.0.12; HVX+ only | Read | ||
| AI | 207 | FLUIDTEMP | Current Fluid Temp.; menu P03.0.03; unit per P04.0.13; HVX+ only | Read | ||
| AI | 208 | ACTUALLEVEL | Actual Level; menu P03.0.04; unit per P04.0.14; HVX+ only | Read | ||
| AI | 209 | EFFREQVAL | Effective Value Required; menu P03.0.10 | Read | ||
| AI | 210 | INITIALREQVAL | Required Value; menu P03.0.20 | Read | ||
| AImin | 211 | PUMPDEVICESTAT | Pump status; menu P03.0.30 | Read | ||
| AI | 212 | POWERUPTIME | Unit Powered Time; menu P03.1.01 | h | Read | |
| AI | 213 | MOTORRUNNINGTI | Operating time; menu P03.1.02 | h | Read | |
| AI | 214 | ENERGYCOUNTER | Energy Counter; menu P03.1.05; unit per P04.0.16 | Read | ||
| AImin | 215 | MOTOR_SPEED | Motor Speed; menu P03.2.01 | rpm | Read | |
| AI | 216 | MOTOR_SPEED_PE | Motor Speed %; menu P03.2.02 | % | Read | |
| AI | 217 | OUTPUTCURRENT | Motor Current; menu P03.2.05 | A | Read | |
| AImin | 218 | OUTPUTPOWER | Motor Power; menu P03.2.06; unit per P04.0.15 | Read | ||
| AI | 219 | OUTPUTVOLTAGE | Motor Voltage; menu P03.2.07 | V | Read | |
| AI | 220 | GRIDVOLTAGE | Grid Voltage; menu P03.2.08 | V | Read | |
| AI | 221 | DCLINKVOLTAGE | DC Bus Voltage; menu P03.2.09 | V | Read | |
| AI | 222 | INVERTERPOWERM | Power Module Temperature; menu P03.2.20; unit per P04.0.13 | Read | ||
| AI | 223 | INVERTERCARDTE | Inverter Temperature; menu P03.2.21; unit per P04.0.13 | Read | ||
| AI | 224 | MOTORPTCVALUE | Motor Ptc; menu P03.2.22 | Read | ||
| AI | 225 | DIGITAL_IO_STA | Digital I/O Status; menu P03.3.01 | Read | ||
| AI | 226 | ANALOGVALUE1 | Analogue Input 1 Value; menu P03.3.11; unit per P05.1.02 | Read | ||
| AI | 227 | ANALOGVALUE2 | Analogue Input 2 Value; menu P03.3.12; unit per P05.1.12 | Read | ||
| AI | 228 | ANALOGVALUE3 | Analogue Input 3 Value; menu P03.3.13; unit per P05.1.22; HVX+ only | Read | ||
| AI | 229 | ANALOGVALUE4 | Analogue Input 4 Value; menu P03.3.14; unit per P05.1.32; HVX+ only | Read | ||
| AI | 230 | ANALOGOUTVALUE | Analogue Output Value; menu P03.3.20; unit per P05.3.02 | Read | ||
| AI | 231 | DATE_SERIALFIN | Unit Production Date; menu P03.4.02 | Read | ||
| AI | 232 | PRODUCTIONDATE | Drive Production Date; menu P03.4.05 | Read | ||
| AI | 233 | DRIVETYPE | Type of Drive | Read | ||
| AI | 234 | MULTIPUMPSMAP | Multipump Map; menu P06.0.04 | Read | ||
| AI | 235 | MPO_MYPUMPPRIO | Multipump Priority; menu P06.0.05 | Read | ||
| AI | 236 | AOC_VERSION | Control Card Firmware Version; menu P03.4.13 | Read | ||
| AI | 237 | MOC_VERSION | Power Card Firmware Version; menu P03.4.12 | Read | ||
| AI | 238 | UI_VERSION | Hmi Firmware Version; menu P03.4.10 | Read | ||
| AI | 239 | BTLE_VERSION | Hmi-Bt Firmware Version; menu P03.4.11 | Read | ||
| AI | 240 | MAPS_VERSION | Map File Version; menu P03.4.14 | Read | ||
| AI | 241 | DEFAULT_VERSIO | Default File Version; menu P03.4.15 | Read | ||
| AI | 242 | LUT_PAR_VERSIO | Parameter File Version; menu P03.4.16 | Read | ||
| AI | 243 | UI_LANGUAGES_V | Language File Version; menu P03.4.17; HVX+ only | Read | ||
| AVmin | 0 | SET_STARTSTOP | Start/stop: 0 = stop, 1 = start | Write | ||
| AVmin | 1 | ERRORRESTCMD | Error reset command | Write | ||
| AV | 2 | SYSTEMTYPE | System Type; menu P04.0.01 | Write | ||
| AVmin | 3 | SET_CONTROLMOD | Control Mode; menu P04.0.02 | Write | ||
| AV | 4 | DIRECTION_OF_R | Regulation Mode; menu P04.0.03 | Write | ||
| AV | 5 | SET_RESTARTVAL | Start Value; menu P04.0.05 | % | Write | |
| AV | 6 | AUTOSTART | Auto Start; menu P04.0.06 | Write | ||
| AV | 7 | SET_MINSPEEDCO | Configuration of minimum speed; menu P04.0.07 | Write | ||
| AV | 8 | UNITSELECTION | Measuring Unit Selection; menu P04.0.09 | Write | ||
| AV | 9 | PRESSUREUNITSE | Pressure Measuring Unit; menu P04.0.11 | Write | ||
| AV | 10 | FLOWUNITSEL | Flow Measuring Unit; menu P04.0.12; HVX+ only | Write | ||
| AV | 11 | TEMPUNITSEL | Temperature Measuring Unit; menu P04.0.13; HVX+ only | Write | ||
| AV | 12 | LEVELUNITSEL | Level Measuring Unit; menu P04.0.14; HVX+ only | Write | ||
| AV | 13 | POWERUNITSEL | Power Measuring Unit; menu P04.0.15; HVX+ only | Write | ||
| AV | 14 | ENERGYUNITSEL | Energy Measuring Unit; menu P04.0.16; HVX+ only | Write | ||
| AV | 15 | SPENUNITSEL | Specific Energy Meas. Unit; menu P04.0.17; HVX+ only | Write | ||
| AV | 16 | MAXDECIMALS | Max Decimals; menu P09.1.11 | Write | ||
| AV | 17 | CONFSETP 1 | Setpoint 1 Selection; menu P04.0.21 | Write | ||
| AV | 18 | CONFSETP 2 | Setpoint 2 Selection; menu P04.0.22 | Write | ||
| AV | 19 | CONFSETP 3 | Setpoint 3 Selection; menu P04.0.23; HVX+ only | Write | ||
| AV | 20 | CONFSETP 4 | Setpoint 4 Selection; menu P04.0.24; HVX+ only | Write | ||
| AV | 21 | SETPOINTSPEED1 | Speed Setpoint 1; menu P04.1.01 | rpm | Write | |
| AV | 22 | SETPOINTSPEED2 | Speed Setpoint 2; menu P04.1.02 | rpm | Write | |
| AV | 23 | SETPOINTSPEED3 | Speed Setpoint 3; menu P04.1.03; HVX+ only | rpm | Write | |
| AV | 24 | SETPOINTSPEED4 | Speed Setpoint 4; menu P04.1.04; HVX+ only | rpm | Write | |
| AV | 25 | SETPOINTPRESS1 | Pressure-Setpoint 1; menu P04.1.11; unit per P04.0.11 | Write | ||
| AV | 26 | SETPOINTPRESS2 | Pressure-Setpoint 2; menu P04.1.12; unit per P04.0.11 | Write | ||
| AV | 27 | SETPOINTPRESS3 | Pressure-Setpoint 3; menu P04.1.13; unit per P04.0.11; HVX+ only | Write | ||
| AV | 28 | SETPOINTPRESS4 | Pressure-Setpoint 4; menu P04.1.14; unit per P04.0.11; HVX+ only | Write | ||
| AV | 29 | SETPOINTFLOW1 | Flow Setpoint 1; menu P04.1.21; unit per P04.0.12; HVX+ only | Write | ||
| AV | 30 | SETPOINTFLOW2 | Flow Setpoint 2; menu P04.1.22; unit per P04.0.12; HVX+ only | Write | ||
| AV | 31 | SETPOINTFLOW3 | Flow Setpoint 3; menu P04.1.23; unit per P04.0.12; HVX+ only | Write | ||
| AV | 32 | SETPOINTFLOW4 | Flow Setpoint 4; menu P04.1.24; unit per P04.0.12; HVX+ only | Write | ||
| AV | 33 | SETPOINTTEMP1 | Temperature-Setp. 1; menu P04.1.31; unit per P04.0.13; HVX+ only | Write | ||
| AV | 34 | SETPOINTTEMP2 | Temperature-Setp. 2; menu P04.1.32; unit per P04.0.13; HVX+ only | Write | ||
| AV | 35 | SETPOINTTEMP3 | Temperature-Setp. 3; menu P04.1.33; unit per P04.0.13; HVX+ only | Write | ||
| AV | 36 | SETPOINTTEMP4 | Temperature-Setp. 4; menu P04.1.34; unit per P04.0.13; HVX+ only | Write | ||
| AV | 37 | SETPOINTLEVEL1 | Level Setpoint 1; menu P04.1.41; unit per P04.0.14; HVX+ only | Write | ||
| AV | 38 | SETPOINTLEVEL2 | Level Setpoint 2; menu P04.1.42; unit per P04.0.14; HVX+ only | Write | ||
| AV | 39 | SETPOINTLEVEL3 | Level Setpoint 3; menu P04.1.43; unit per P04.0.14; HVX+ only | Write | ||
| AV | 40 | SETPOINTLEVEL4 | Level Setpoint 4; menu P04.1.44; unit per P04.0.14; HVX+ only | Write | ||
| AV | 45 | SET_RPMWINDOW_ | Window; menu P04.2.01 | % | Write | |
| AV | 46 | SET_RPMHYST_PE | Hysteresis; menu P04.2.02 | % | Write | |
| AV | 47 | SPEEDLIFTKNEE | Lift Speed; menu P04.2.06 | rpm | Write | |
| AV | 48 | SPEEDLIFTAMOUN | Linear Lift Amount; menu P04.2.07 | % | Write | |
| AV | 49 | QUADRATICLIFTA | Quadrat. Incr. Val.; menu P04.2.08; HVX+ only | % | Write | |
| AV | 50 | RAMP1_SEC | Ramp 1; menu P04.2.11 | s | Write | |
| AV | 51 | RAMP2_SEC | Ramp 2; menu P04.2.12 | s | Write | |
| AV | 52 | RAMP3_SEC | Ramp 3; menu P04.2.13 | s | Write | |
| AV | 53 | RAMP4_SEC | Ramp 4; menu P04.2.14 | s | Write | |
| AV | 54 | RAMPSPEEDMIN_A | Ramp Speed Min Acceleration; menu P04.2.15 | s | Write | |
| AV | 55 | RAMPSPEEDMIN_D | Ramp Speed Min Deceleration; menu P04.2.16 | s | Write | |
| AV | 56 | SET_MINRPM_RPM | Min. speed; menu P04.2.31 | rpm | Write | |
| AV | 57 | SET_MAXRPM_RPM | Max RPM set; menu P04.2.32 | rpm | Write | |
| AV | 58 | MINSPEEDTIME | Min Speed Time; menu P04.2.35 | s | Write | |
| AV | 59 | AUTOMATICERROR | Automatic Error Reset; menu P04.3.00 | Write | ||
| AV | 60 | MINTHRESHPRESS | Pressure - Minimum Threshold; menu P04.3.01; unit per P04.0.11 | Write | ||
| AV | 61 | MINTHRESHTEMP | Flow - Minimum Threshold; menu P04.3.02; unit per P04.0.12; HVX+ only | Write | ||
| AV | 62 | MINTHRESHFLVL | Temperature - Minimum Threshold; menu P04.3.03; unit per P04.0.13; HVX+ only | Write | ||
| AV | 63 | MINTHRESHFLOW | Level - Minimum Threshold; menu P04.3.04; unit per P04.0.14; HVX+ only | Write | ||
| AV | 65 | MINTHRESHDELAY | Minimum Threshold Delay; menu P04.3.10 | s | Write | |
| AV | 66 | LOW_DELAY | Lack Of Water Delay; menu P04.3.11 | s | Write | |
| AV | 67 | TESTRUNSPEED | Test Run Speed; menu P04.4.01 | rpm | Write | |
| AV | 68 | TESTRUNTIMEOUT | Test Run Timeout; menu P04.4.02 | h | Write | |
| AV | 69 | TESTRUNTIME | Test Run Time; menu P04.4.03 | s | Write | |
| AV | 70 | TESTRUNCOMMAND | Test Run Command; menu P04.4.05 | Write | ||
| AV | 71 | SET_PIPEFILLIN | Pipe Filling Function; menu P04.6.01 | Write | ||
| AV | 72 | PIPE_FILL_THRE | Pipe Filling Threshold; menu P04.6.03; unit per P04.0.11 | Write | ||
| AV | 73 | SET_RAMP_PF_SE | Pipe Filling Time; menu P04.6.05 | s | Write | |
| AV | 74 | MAXPIPEFILLING | Max Pipe Filling Pumps; menu P04.6.06 | Write | ||
| AV | 75 | SET_STEADYTIME | Pipe Filling Steady Time; menu P04.6.10 | s | Write | |
| AV | 76 | SET_RPMSTEPPF | Pipe Filling Speed Step; menu P04.6.15 | % | Write | |
| AV | 77 | ACT_VAL_SOURCE | Actual Value Source; menu P05.0.00 | Write | ||
| AV | 78 | ACTUATOR_ZERO | Actuator - Zero Value; menu P05.0.01 | rpm | Write | |
| AV | 79 | ACTUATOR_FULL | Actuator - Full Scale; menu P05.0.02 | rpm | Write | |
| AV | 80 | PRESS_ZERO_VAL | Pressure - Zero Value; menu P05.0.11; unit per P04.0.11 | Write | ||
| AV | 81 | PRESS_FULL | Pressure - Full Scale; menu P05.0.12; unit per P04.0.11 | Write | ||
| AV | 82 | FLOW_ZERO_VAL | Flow - Zero Value; menu P05.0.21; unit per P04.0.12; HVX+ only | Write | ||
| AV | 83 | FLOW_FULL | Flow - Full Scale; menu P05.0.22; unit per P04.0.12; HVX+ only | Write | ||
| AV | 84 | TEMPE_ZERO_VAL | Temperature - Zero Value; menu P05.0.31; unit per P04.0.13; HVX+ only | Write | ||
| AV | 85 | TEMP_FULL | Temperature - Full Scale; menu P05.0.32; unit per P04.0.13; HVX+ only | Write | ||
| AV | 86 | LEVEL_ZERO_VAL | Level - Zero Value; menu P05.0.41; unit per P04.0.14; HVX+ only | Write | ||
| AV | 87 | LEVEL_FULL | Level - Full Scale; menu P05.0.42; unit per P04.0.14; HVX+ only | Write | ||
| AV | 90 | ANALOG_IN1_FUN | Analogue Input 1 Function; menu P05.1.01 | Write | ||
| AV | 91 | ANALOG_IN1_CFG | Analog Input 1 Type; menu P05.1.02 | Write | ||
| AV | 92 | ANALOG_IN2_FUN | Analogue Input 2 Function; menu P05.1.11 | Write | ||
| AV | 93 | ANALOG_IN2_CFG | Analog Input 2 Type; menu P05.1.12 | Write | ||
| AV | 94 | ANALOG_IN3_FUN | Analogue Input 3 Function; menu P05.1.21; HVX+ only | Write | ||
| AV | 95 | ANALOG_IN3_CFG | Analog Input 3 Type; menu P05.1.22; HVX+ only | Write | ||
| AV | 96 | ANALOG_IN4_FUN | Analogue Input 4 Function; menu P05.1.31; HVX+ only | Write | ||
| AV | 97 | ANALOG_IN4_CFG | Analog Input 1 Type; menu P05.1.32; HVX+ only | Write | ||
| AV | 98 | LINEARQUADRATI | Sensor Curve; menu P05.1.40; HVX+ only | Write | ||
| AV | 99 | ANALOGACTUATOR | Analogue Actuator Type; menu P05.1.50; HVX+ only | Write | ||
| AV | 100 | DIG_IN_3_FUN | Digital Input 3 Function; menu P05.2.03 | Write | ||
| AV | 101 | DIG_IN_4_FUN | Digital Input 4 Function; menu P05.2.04; HVX+ only | Write | ||
| AV | 102 | DIG_IN_5_FUN | Digital Input 5 Function; menu P05.2.05; HVX+ only | Write | ||
| AV | 103 | ANALOG_OUT1FUN | Analogue Output Function; menu P05.3.01 | Write | ||
| AV | 104 | ANALOG_OUT1CFG | Analogue Output Type; menu P05.3.02 | Write | ||
| AV | 105 | DIG_OUT_1_FUN | Relay 1 Function; menu P05.4.01 | Write | ||
| AV | 106 | DIG_OUT_2_FUN | Relay 2 Function; menu P05.4.02 | Write | ||
| AV | 107 | AN_IN1_OFFSET | Analogue Input 1 Offset; menu P05.8.01 | Write | ||
| AV | 108 | AN_IN1_GAIN | Analogue Input 1 Gain; menu P05.8.02 | Write | ||
| AV | 109 | AN_IN2_OFFSET | Analogue Input 2 Offset; menu P05.8.11 | Write | ||
| AV | 110 | AN_IN2_GAIN | Analogue Input 2 Gain; menu P05.8.12 | Write | ||
| AV | 111 | AN_IN3_OFFSET | Analogue Input 3 Offset; menu P05.8.21; HVX+ only | Write | ||
| AV | 112 | AN_IN3_GAIN | Analogue Input 3 Gain; menu P05.8.22; HVX+ only | Write | ||
| AV | 113 | AN_IN4_OFFSET | Analogue Input 4 Offset; menu P05.8.31; HVX+ only | Write | ||
| AV | 114 | AN_IN4_GAIN | Analogue Input 4 Gain; menu P05.8.32; HVX+ only | Write | ||
| AV | 115 | MPCONTROLMODE | System Configuration; menu P06.0.01 | Write | ||
| AV | 116 | MAXPUMPNUMBER | Max Units; menu P06.0.02 | Write | ||
| AV | 117 | BACNET_MAC_MP | Multipump Address; menu P06.0.03 | Write | ||
| AV | 118 | ACTVALINCPRESS | Pressure - Inc. value; menu P06.1.11; unit per P04.0.11 | Write | ||
| AV | 119 | ACTVALDECPRESS | Pressure - Dec. value; menu P06.1.12; unit per P04.0.11 | Write | ||
| AV | 120 | ACTVALINCFLOW | Flow - Inc. value; menu P06.1.21; unit per P04.0.12; HVX+ only | Write | ||
| AV | 121 | ACTVALDECFLOW | Flow - Dec. value; menu P06.1.22; unit per P04.0.12; HVX+ only | Write | ||
| AV | 122 | ACTVALINCTEMP | Temperature - Inc. value; menu P06.1.31; unit per P04.0.13; HVX+ only | Write | ||
| AV | 123 | ACTVALDECTEMP | Temperature - Dec. value; menu P06.1.32; unit per P04.0.13; HVX+ only | Write | ||
| AV | 124 | ACTVALINCLVL | Level - Inc. value; menu P06.1.41; unit per P04.0.14; HVX+ only | Write | ||
| AV | 125 | ACTVALDECLVL | Level - Dec. value; menu P06.1.42; unit per P04.0.14; HVX+ only | Write | ||
| AV | 128 | MULTIPUMPENABL | Multipump Enable Speed; menu P06.1.61 | rpm | Write | |
| AV | 129 | SYNCHLIMSPEED | Synchronous Limit; menu P06.1.71 | rpm | Write | |
| AV | 130 | SYNCHSPEEDWIND | Synchronous Window; menu P06.1.72 | rpm | Write | |
| AV | 131 | SWITCHOVERINT | Automatic Switchover Interval; menu P06.1.81 | h | Write | |
| AV | 132 | MAXSWITCHFREQ | Switching Frequency; menu P07.0.01 | Write | ||
| AV | 133 | MINSWITCHFREQ | Min Switching Frequency; menu P07.0.02 | Write | ||
| AV | 134 | SKIPSPEEDCENTR | Skip Speed Center; menu P07.1.01 | rpm | Write | |
| AV | 135 | SKIPSPEEDBAND | Skip Speed Range; menu P07.1.02 | rpm | Write | |
| AV | 136 | MOTORPREHEATHI | Motor heating function; menu P07.2.01 | Write | ||
| AV | 137 | COM_1_FUNC | Com 1 Function; menu P08.0.01 | Write | ||
| AV | 138 | COM_2_FUNC | Com 2 Function; menu P08.0.02 | Write | ||
| AV | 139 | MODBUSRTU_ADDR | Modbus RTU Address; menu P08.1.01 | Write | ||
| AV | 140 | MODBUSRTU_BAUD | Modbus RTU Baudrate; menu P08.1.02 | Write | ||
| AV | 141 | MODBUSRTU_FORM | Modbus RTU Format; menu P08.1.08 | Write | ||
| AV | 142 | BACNET_MAC | Bacnet MS/TP Mac Address; menu P08.2.01 | Write | ||
| AV | 143 | BACNET_BAUD | Bacnet MS/TP Baudrate; menu P08.2.02 | Write | ||
| AV | 144 | BACNET_FORMAT | Bacnet MS/TP Format; menu P08.2.03 | Write | ||
| AV | 145 | BACNET_DEVID | Bacnet MS/TP Device Id; menu P08.2.04 | Write | ||
| AV | 146 | BACNET_MAXMAS | Bacnet MS/TP Max Master; menu P08.2.05 | Write | ||
| AV | 147 | BACNET_INFOFRM | Frame info BACnet | Write | ||
| AV | 148 | BACNET_REINIT | BACnet Reinit | Write | ||
| AV | 149 | BLUETOOTHEN | Enable Wireless Communication; menu P08.3.01 | Write | ||
| AV | 150 | LANGUAGE | Language; menu P09.0.01; HVX+ only | Write | ||
| AV | 151 | CALENDARTIME | Hour; menu P09.0.12; HVX+ only | Write | ||
| AV | 152 | CALENDARDATE | Date; menu P09.0.11; HVX+ only | Write | ||
| AV | 153 | EN_SAVING_EN | Display Energy Saving; menu P09.1.01 | Write | ||
| AV | 154 | EN_SAVING_TIME | Energy Saving Time; menu P09.1.02 | s | Write | |
| AV | 155 | DISPLAYORIENTA | Display Orientation; menu P09.1.10 | Write | ||
| AV | 156 | ERRORLOGRESET | Error Log Reset; menu P09.3.01 | Write | ||
| AV | 157 | OPERATINGTIMEC | Operating Time Couter Reset; menu P09.3.02 | Write | ||
| AV | 158 | MOTORRUNCOUNTE | Motor Running Counter Reset; menu P09.3.03 | Write | ||
| AV | 159 | KWHCOUNTERRESE | Energy Counter Reset; menu P09.3.04 | Write | ||
| AV | 160 | FACTORYRESTORE | Factory Restore; menu P09.3.05 | Write | ||
| AV | 161 | FIRSTCOMMISSIO | Commissioning Completed; menu P09.3.06 | Write | ||
| AV | 162 | UNBONDDEVICE | Bonded Device List Reset; menu P09.3.07 | Write | ||
| AV | 163 | SKIPSPSAVING | Limit setpoint saving; menu P04.1.60 | Write |
No points match these filters.
Object ID lookup: Xylem Lowara hydrovar X HVX / HVX+ pump drive point IDs by name
CSV0PARTNUMBERCSV1SERIALFINISHEDCSV2SERIAL_DRIVEAI0ERROR1CODEAI1ERROR1DATEAI2ERROR1TIMEAI3ERROR1ENDDATEAI4ERROR1ENDTIMEAI5LOGERRORCOUN 1AI6LOGERROR1BF 1AI7LOGERROR2BF 1AI8LOGALARM1BF 1AI9LOGSYSSTATUS 1AI10LOGINTERNALC 1AI11LOGFLOW 1AI12LOGHEAD 1AI13LOGIGBTTEMP 1AI14LOG_I_MOT 1AI15LOG_V_MOT 1AI16LOGINNERTEMP 1AI17LOGTORQUE 1AI18LOG_DC_BUSVO 1AI19LOGGRIDVOLTA 1AI20ERROR2CODEAI21ERROR2DATEAI22ERROR2TIMEAI23ERROR2ENDDATEAI24ERROR2ENDTIMEAI25LOGERRORCOUN 2AI26LOGERROR1BF 2AI27LOGERROR2BF 2AI28LOGALARM1BF 2AI29LOGSYSSTATUS 2AI30LOGINTERNALC 2AI31LOGFLOW 2AI32LOGHEAD 2AI33LOGIGBTTEMP 2AI34LOG_I_MOT 2AI35LOG_V_MOT 2AI36LOGINNERTEMP 2AI37LOGTORQUE 2AI38LOG_DC_BUSVO 2AI39LOGGRIDVOLTA 2AI40ERROR3CODEAI41ERROR3DATEAI42ERROR3TIMEAI43ERROR3ENDDATEAI44ERROR3ENDTIMEAI45LOGERRORCOUN 3AI46LOGERROR1BF 3AI47LOGERROR2BF 3AI48LOGALARM1BF 3AI49LOGSYSSTATUS 3AI50LOGINTERNALC 3AI51LOGFLOW 3AI52LOGHEAD 3AI53LOGIGBTTEMP 3AI54LOG_I_MOT 3AI55LOG_V_MOT 3AI56LOGINNERTEMP 3AI57LOGTORQUE 3AI58LOG_DC_BUSVO 3AI59LOGGRIDVOLTA 3AI60ERROR4CODEAI61ERROR4DATEAI62ERROR4TIMEAI63ERROR4ENDDATEAI64ERROR4ENDTIMEAI65LOGERRORCOUN 4AI66LOGERROR1BF 4AI67LOGERROR2BF 4AI68LOGALARM1BF 4AI69LOGSYSSTATUS 4AI70LOGINTERNALC 4AI71LOGFLOW 4AI72LOGHEAD 4AI73LOGIGBTTEMP 4AI74LOG_I_MOT 4AI75LOG_V_MOT 4AI76LOGINNERTEMP 4AI77LOGTORQUE 4AI78LOG_DC_BUSVO 4AI79LOGGRIDVOLTA 4AI80ERROR5CODEAI81ERROR5DATEAI82ERROR5TIMEAI83ERROR5ENDDATEAI84ERROR5ENDTIMEAI85LOGERRORCOUN 5AI86LOGERROR1BF 5AI87LOGERROR2BF 5AI88LOGALARM1BF 5AI89LOGSYSSTATUS 5AI90LOGINTERNALC 5AI91LOGFLOW 5AI92LOGHEAD 5AI93LOGIGBTTEMP 5AI94LOG_I_MOT 5AI95LOG_V_MOT 5AI96LOGINNERTEMP 5AI97LOGTORQUE 5AI98LOG_DC_BUSVO 5AI99LOGGRIDVOLTA 5AI100ERROR6CODEAI101ERROR6DATEAI102ERROR6TIMEAI103ERROR6ENDDATEAI104ERROR6ENDTIMEAI105LOGERRORCOUN 6AI106LOGERROR1BF 6AI107LOGERROR2BF 6AI108LOGALARM1BF 6AI109LOGSYSSTATUS 6AI110LOGINTERNALC 6AI111LOGFLOW 6AI112LOGHEAD 6AI113LOGIGBTTEMP 6AI114LOG_I_MOT 6AI115LOG_V_MOT 6AI116LOGINNERTEMP 6AI117LOGTORQUE 6AI118LOG_DC_BUSVO 6AI119LOGGRIDVOLTA 6AI120ERROR7CODEAI121ERROR7DATEAI122ERROR7TIMEAI123ERROR7ENDDATEAI124ERROR7ENDTIMEAI125LOGERRORCOUN 7AI126LOGERROR1BF 7AI127LOGERROR2BF 7AI128LOGALARM1BF 7AI129LOGSYSSTATUS 7AI130LOGINTERNALC 7AI131LOGFLOW 7AI132LOGHEAD 7AI133LOGIGBTTEMP 7AI134LOG_I_MOT 7AI135LOG_V_MOT 7AI136LOGINNERTEMP 7AI137LOGTORQUE 7AI138LOG_DC_BUSVO 7AI139LOGGRIDVOLTA 7AI140ERROR8CODEAI141ERROR8DATEAI142ERROR8TIMEAI143ERROR8ENDDATEAI144ERROR8ENDTIMEAI145LOGERRORCOUN 8AI146LOGERROR1BF 8AI147LOGERROR2BF 8AI148LOGALARM1BF 8AI149LOGSYSSTATUS 8AI150LOGINTERNALC 8AI151LOGFLOW 8AI152LOGHEAD 8AI153LOGIGBTTEMP 8AI154LOG_I_MOT 8AI155LOG_V_MOT 8AI156LOGINNERTEMP 8AI157LOGTORQUE 8AI158LOG_DC_BUSVO 8AI159LOGGRIDVOLTA 8AI160ERROR9CODEAI161ERROR9DATEAI162ERROR9TIMEAI163ERROR9ENDDATEAI164ERROR9ENDTIMEAI165LOGERRORCOUN 9AI166LOGERROR1BF 9AI167LOGERROR2BF 9AI168LOGALARM1BF 9AI169LOGSYSSTATUS 9AI170LOGINTERNALC 9AI171LOGFLOW 9AI172LOGHEAD 9AI173LOGIGBTTEMP 9AI174LOG_I_MOT 9AI175LOG_V_MOT 9AI176LOGINNERTEMP 9AI177LOGTORQUE 9AI178LOG_DC_BUSVO 9AI179LOGGRIDVOLTA 9AI180ERROR10CODEAI181ERROR10DATEAI182ERROR10TIMEAI183ERROR10ENDDATEAI184ERROR10ENDTIMEAI185LOGERRORCOU 10AI186LOGERROR1BF 10AI187LOGERROR2BF 10AI188LOGALARM1BF 10AI189LOGSYSSTATU 10AI190LOGINTERNAL 10AI191LOGFLOW 10AI192LOGHEAD 10AI193LOGIGBTTEMP 10AI194LOG_I_MOT 10AI195LOG_V_MOT 10AI196LOGINNERTEM 10AI197LOGTORQUE 10AI198LOG_DC_BUSV 10AI199LOGGRIDVOLT 10AI200TOTAL_ERRORS_CAI201TOTAL_ALARMS_CAI202ERROR1_BFAI203ERROR2_BFAI204ALARM1_BFAI205HEADAI206FLOWAI207FLUIDTEMPAI208ACTUALLEVELAI209EFFREQVALAI210INITIALREQVALAI211PUMPDEVICESTATAI212POWERUPTIMEAI213MOTORRUNNINGTIAI214ENERGYCOUNTERAI215MOTOR_SPEEDAI216MOTOR_SPEED_PEAI217OUTPUTCURRENTAI218OUTPUTPOWERAI219OUTPUTVOLTAGEAI220GRIDVOLTAGEAI221DCLINKVOLTAGEAI222INVERTERPOWERMAI223INVERTERCARDTEAI224MOTORPTCVALUEAI225DIGITAL_IO_STAAI226ANALOGVALUE1AI227ANALOGVALUE2AI228ANALOGVALUE3AI229ANALOGVALUE4AI230ANALOGOUTVALUEAI231DATE_SERIALFINAI232PRODUCTIONDATEAI233DRIVETYPEAI234MULTIPUMPSMAPAI235MPO_MYPUMPPRIOAI236AOC_VERSIONAI237MOC_VERSIONAI238UI_VERSIONAI239BTLE_VERSIONAI240MAPS_VERSIONAI241DEFAULT_VERSIOAI242LUT_PAR_VERSIOAI243UI_LANGUAGES_VAV0SET_STARTSTOPAV1ERRORRESTCMDAV2SYSTEMTYPEAV3SET_CONTROLMODAV4DIRECTION_OF_RAV5SET_RESTARTVALAV6AUTOSTARTAV7SET_MINSPEEDCOAV8UNITSELECTIONAV9PRESSUREUNITSEAV10FLOWUNITSELAV11TEMPUNITSELAV12LEVELUNITSELAV13POWERUNITSELAV14ENERGYUNITSELAV15SPENUNITSELAV16MAXDECIMALSAV17CONFSETP 1AV18CONFSETP 2AV19CONFSETP 3AV20CONFSETP 4AV21SETPOINTSPEED1AV22SETPOINTSPEED2AV23SETPOINTSPEED3AV24SETPOINTSPEED4AV25SETPOINTPRESS1AV26SETPOINTPRESS2AV27SETPOINTPRESS3AV28SETPOINTPRESS4AV29SETPOINTFLOW1AV30SETPOINTFLOW2AV31SETPOINTFLOW3AV32SETPOINTFLOW4AV33SETPOINTTEMP1AV34SETPOINTTEMP2AV35SETPOINTTEMP3AV36SETPOINTTEMP4AV37SETPOINTLEVEL1AV38SETPOINTLEVEL2AV39SETPOINTLEVEL3AV40SETPOINTLEVEL4AV45SET_RPMWINDOW_AV46SET_RPMHYST_PEAV47SPEEDLIFTKNEEAV48SPEEDLIFTAMOUNAV49QUADRATICLIFTAAV50RAMP1_SECAV51RAMP2_SECAV52RAMP3_SECAV53RAMP4_SECAV54RAMPSPEEDMIN_AAV55RAMPSPEEDMIN_DAV56SET_MINRPM_RPMAV57SET_MAXRPM_RPMAV58MINSPEEDTIMEAV59AUTOMATICERRORAV60MINTHRESHPRESSAV61MINTHRESHTEMPAV62MINTHRESHFLVLAV63MINTHRESHFLOWAV65MINTHRESHDELAYAV66LOW_DELAYAV67TESTRUNSPEEDAV68TESTRUNTIMEOUTAV69TESTRUNTIMEAV70TESTRUNCOMMANDAV71SET_PIPEFILLINAV72PIPE_FILL_THREAV73SET_RAMP_PF_SEAV74MAXPIPEFILLINGAV75SET_STEADYTIMEAV76SET_RPMSTEPPFAV77ACT_VAL_SOURCEAV78ACTUATOR_ZEROAV79ACTUATOR_FULLAV80PRESS_ZERO_VALAV81PRESS_FULLAV82FLOW_ZERO_VALAV83FLOW_FULLAV84TEMPE_ZERO_VALAV85TEMP_FULLAV86LEVEL_ZERO_VALAV87LEVEL_FULLAV90ANALOG_IN1_FUNAV91ANALOG_IN1_CFGAV92ANALOG_IN2_FUNAV93ANALOG_IN2_CFGAV94ANALOG_IN3_FUNAV95ANALOG_IN3_CFGAV96ANALOG_IN4_FUNAV97ANALOG_IN4_CFGAV98LINEARQUADRATIAV99ANALOGACTUATORAV100DIG_IN_3_FUNAV101DIG_IN_4_FUNAV102DIG_IN_5_FUNAV103ANALOG_OUT1FUNAV104ANALOG_OUT1CFGAV105DIG_OUT_1_FUNAV106DIG_OUT_2_FUNAV107AN_IN1_OFFSETAV108AN_IN1_GAINAV109AN_IN2_OFFSETAV110AN_IN2_GAINAV111AN_IN3_OFFSETAV112AN_IN3_GAINAV113AN_IN4_OFFSETAV114AN_IN4_GAINAV115MPCONTROLMODEAV116MAXPUMPNUMBERAV117BACNET_MAC_MPAV118ACTVALINCPRESSAV119ACTVALDECPRESSAV120ACTVALINCFLOWAV121ACTVALDECFLOWAV122ACTVALINCTEMPAV123ACTVALDECTEMPAV124ACTVALINCLVLAV125ACTVALDECLVLAV128MULTIPUMPENABLAV129SYNCHLIMSPEEDAV130SYNCHSPEEDWINDAV131SWITCHOVERINTAV132MAXSWITCHFREQAV133MINSWITCHFREQAV134SKIPSPEEDCENTRAV135SKIPSPEEDBANDAV136MOTORPREHEATHIAV137COM_1_FUNCAV138COM_2_FUNCAV139MODBUSRTU_ADDRAV140MODBUSRTU_BAUDAV141MODBUSRTU_FORMAV142BACNET_MACAV143BACNET_BAUDAV144BACNET_FORMATAV145BACNET_DEVIDAV146BACNET_MAXMASAV147BACNET_INFOFRMAV148BACNET_REINITAV149BLUETOOTHENAV150LANGUAGEAV151CALENDARTIMEAV152CALENDARDATEAV153EN_SAVING_ENAV154EN_SAVING_TIMEAV155DISPLAYORIENTAAV156ERRORLOGRESETAV157OPERATINGTIMECAV158MOTORRUNCOUNTEAV159KWHCOUNTERRESEAV160FACTORYRESTOREAV161FIRSTCOMMISSIOAV162UNBONDDEVICEAV163SKIPSPSAVING
Integration notes
- The tables have no read/write column; Analog Values (parameters and commands) are taken as writable and Analog Inputs as read-only.
- Many units follow unit-selection parameters (P04.0.11 pressure, P04.0.12 flow, P04.0.13 temperature, P04.0.14 level, P04.0.15 power, P04.0.16 energy); the description names the parameter.
- Objects marked "HVX+ only" (menu index flagged [X+]) exist only on the HVX+.
- The manual prints AI 73-90 twice around the page 75/76 break (the repeat names AI 77 "Log: Motor load"); each is listed once. AV 41-44, 64, 88-89 and 126-127 are not in the table.
- Error log objects (AI 0-199) repeat in blocks of 20 for errors 1-10; names carry the error number.
- Set P04.1.60 Limit Setpoint Saving to Yes when setpoints are written often, to spare the EEPROM.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Lowara hydrovar X HVX / HVX+ pump drive (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Xylem Lowara hydrovar X HVX / HVX+ pump drive (BACnet MS/TP)
How many BACnet points does the Xylem Lowara hydrovar X HVX / HVX+ pump drive (BACnet MS/TP) have?
This list has 402 BACnet objects: 244 analog inputs, 155 analog values, 3 characterstring values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Xylem Lowara hydrovar X HVX / HVX+ pump drive (BACnet MS/TP) BACnet points are writable?
155 of the 402 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Xylem Lowara hydrovar X HVX / HVX+ pump drive (BACnet MS/TP) BACnet documentation?
The source is HVX, HVX+ Installation, Operation and Programming Manual, ch. 7.4-7.6 BACnet objects (001088108 EN rev C), revision 08/2023, published free by Xylem at https://prod.xylem.com/siteassets/brand/lowara/resources/manual/001088108en_c_08_2023_hvx_hvx.pdf.
What are the minimum BACnet points to integrate the Xylem Lowara hydrovar X HVX / HVX+ pump drive (BACnet MS/TP)?
Start with AV 0 SET_STARTSTOP (Start/stop: 0 = stop, 1 = start); AV 3 SET_CONTROLMOD (Control mode); AV 1 ERRORRESTCMD (Error reset command); AI 211 PUMPDEVICESTAT (Pump status); AI 205 HEAD (Actual pressure (head)); AI 215 MOTOR_SPEED (Motor speed, rpm); AI 218 OUTPUTPOWER (Motor power); AI 0 ERROR1CODE (Most recent error code).
How do I enable BMS control of the Xylem Lowara hydrovar X HVX / HVX+ pump drive (BACnet MS/TP)?
AV 0 SET_STARTSTOP starts (1) and stops (0) the pump.
How do I check these points on the real Lowara hydrovar X HVX / HVX+ pump drive (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Xylem BACnet points lists
- ECM circulator pump (wet rotor)
Xylem Lowara ecocirc XL / XLplus circulator
Lowara ecocirc XL and ecocirc XLplus single and twin wet-rotor circulators with the communication-capable drive.
Also known as: ecocirc XLplus, ecocirc XL, Lowara ecocirc, ecocirc XLplus BACnet - Multi-pump controller for pump frequency drives
Xylem Lowara hydrovar X HVX+ Smart Controller (BACnet MS/TP)
Xylem Lowara HVX+ Smart Controller, the multi-pump control unit for hydrovar X frequency converters.
Also known as: HVX+ Smart Controller, hydrovar X Smart Controller, HVX Smart Controller, 001080187 - Multistage smart pump with integrated drive (booster)
Xylem Lowara Smart Pump e-HME / e-SVE / VME / e-SVIE (booster / multistage)
Lowara Smart Pump Range multistage pumps e-HME, e-SVE, VME and e-SVIE (firmware 101.10 and later), alone or in a 2-3 pump multi-pump set.
Also known as: e-HME, e-SVE, VME, e-SVIE, Lowara Smart Pump Range, Lowara e-SV smart - In-line smart circulator pump with integrated drive
Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line)
Lowara Smart Pump Range in-line pumps e-LNEEE, e-LNESE, e-LNTEE and e-LNTSE (firmware 151.06 and later), single or dual (twin) units.
Also known as: e-LNEEE, e-LNESE, e-LNTEE, e-LNTSE, e-LNEE, e-LNES, e-LNTE, e-LNTS, Lowara Smart Pump Range, Smart Pump e-LN
Source: HVX, HVX+ Installation, Operation and Programming Manual, ch. 7.4-7.6 BACnet objects · 001088108 EN rev C · rev. 08/2023. Object names, instances and units are reproduced as published; descriptions are our own.