ECM circulator pump (wet rotor) · BACnet points list

Xylem Lowara ecocirc XL / XLplus circulator BACnet points list

Updated 4 November 2026

Short answer

The ecocirc XL / XLplus drive is a BACnet MS/TP master (Modbus is the alternative). It uses only two object types: Analog Values for settings and commands (on/off, control mode, pressure/speed/temperature setpoints, twin-pump setup) and Analog Inputs for readings, alarm and error bit fields, twin-slave data, an error log and run timers.

This page lists 68 BACnet objects for the Xylem Lowara ecocirc XL / XLplus circulator — 19 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Xylem’s own free documentation, linked below.

Manufacturer
Xylem
Model
Lowara ecocirc XL / XLplus circulator
Equipment
ECM circulator pump (wet rotor)
Equipment type
VFDs & pumps
BACnet objects
68 (19 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
Derived from the serial number: the lower 22 bits of the hex S/N on the drive label
Also known as
ecocirc XLplus, ecocirc XL, Lowara ecocirc, ecocirc XLplus BACnet
Source document
ecocirc XLplus BACnet Objects (Technical Sheet) · ecocirc XLplus BACnet Objects r1.0 · rev. 2014-06-05 (PICS date)
Download CSV 68 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Xylem’s current documentation and the live device before use. Not official Xylem information. Terms of use.

BMS integration notes: Xylem Lowara ecocirc XL / XLplus circulator

Integration in brief

Wire the pump to the MS/TP trunk and set the baud rate (38400 or higher is suggested). Find the device instance from the serial number. Write AV 0 to run or stop the pump, AV 1 for the control mode and the matching setpoint (AV 5, AV 6 or AV 7). Read power, head, flow, speed and the error code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 0ON OFFPump on/off (1 = on)Write
AV 1OP. MODALITYControl mode: 1 const. pressure, 2 prop., 3 curveWrite
AV 6CONST. H S.P.Constant pressure head setpoint, m (mode 1)Write
AV 5PROP. H S.P.Proportional pressure head setpoint, m (mode 2)Write
AV 7RPM S.P.Constant curve speed setpoint, rpm (mode 3)Write
AI 3CURR. RPMPump speed, rpmRead
AI 0POWERInput power, WRead
AI 2CURR. QFlow estimate, m³/hRead
AI 1CURR. HHead, mRead
AI 15CURR. ERRORActive error code; 0 = no errorRead

Enable & remote start

No separate enable: AV 0 ON OFF turns the pump on (1) or off (0) and AV 1 selects the control mode whose setpoint (AV 5, AV 6 or AV 7) applies.

Network setup

Watch out for

Xylem Lowara ecocirc XL / XLplus circulator BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

68 of 68 shown
Type
Access
Show
Xylem Lowara ecocirc XL / XLplus circulator BACnet Points List
DescriptionStates
AVmin0ON OFFOperating mode (pump on/off), default 1Write0=Off, 1=On
AVmin1OP. MODALITYControl mode, default 2Write1=Constant pressure, 2=Proportional pressure, 3=Constant curve
AV2NIGHT MODENight mode activationWrite0=Not active, 1=Active
AV3AIR VENTINGAir venting procedureWrite0=Not active, 1=Active
AV4A. VEN. PWR ONAir venting at power onWrite0=Not active, 1=Active
AVmin5PROP. H S.P.Proportional pressure setpoint (control mode 2)mWrite
AVmin6CONST. H S.P.Constant pressure setpoint (control mode 1)mWrite
AVmin7RPM S.P.Constant curve speed setpoint (control mode 3)rpmWrite
AV8T REG. TYPETemperature control modeWrite0=Not active, 1=Prop. temperature to head, 2=Constant temperature
AV9ABS T S.P.Absolute temperature setpoint°CWrite
AV10DIFF T S.P.Differential temperature setpoint, 5-30°CWrite
AV11T ACQ. TYPETemperature probe sourceWrite0=Internal, 1=External, 2=Differential
AV12T SLOPETemperature slopeWrite0=Increasing, 1=Decreasing
AV13KP CONST. TProportional constant for temperature controlWrite
AV14KI CONST. TIntegral constant for temperature controlWrite
AV15T PI PERIODTemperature control sampling timemsWrite
AV16CIRC. CONFCirculator configurationWrite0=Twin master, 1=Twin slave, 2=Single
AV17TWIN MOD.Twin pump control modeWrite0=Backup, 1=Alternate, 2=Parallel, 3=Forced parallel
AV18LOG IDX SEL.Error log row selector (0-7) for AI 28-43Write
AImin0POWERInput powerWRead
AImin1CURR. HHeadmRead
AImin2CURR. QFlowm³/hRead
AImin3CURR. RPMSpeedrpmRead
AI4CAN TEMPWater temperature°CRead
AI5EXT. TEMPExternal water temperature°CRead
AI6WIND 1 TEMPWinding 1 temperature°CRead
AI7WIND 2 TEMPWinding 2 temperature°CRead
AI8WIND 3 TEMPWinding 3 temperature°CRead
AI9MODULE TEMPPower module temperature°CRead
AI10IQQuadrature currentARead
AI11IO B.F. STSI/O status bit field (0-10 V, 4-20 mA, start/stop, probe, relay)Read
AI12ALARM 1 B.F.Alarm bit field 1 (A1-A7, A12)Read
AI13ALARM 2 B.F.Alarm bit field 2 (internal alarms A20)Read
AI14ERROR 1 B.F.Error bit field (E1-E10)Read
AImin15CURR. ERRORActive error code, 0 = no errorRead
AI16SLAVE PWRTwin slave input powerWRead
AI17SLAVE HTwin slave headmRead
AI18SLAVE QTwin slave flowm³/hRead
AI19SLAVE RPMTwin slave speedrpmRead
AI20SLAVE W.1 TTwin slave winding 1 temperature°CRead
AI21SLAVE W.2 TTwin slave winding 2 temperature°CRead
AI22SLAVE W.3 TTwin slave winding 3 temperature°CRead
AI23SLAVE MOD. TTwin slave power module temperature°CRead
AI24SLAVE IQTwin slave quadrature currentARead
AI25SLAVE B.F. A1Twin slave alarm bit field 1Read
AI26SLAVE B.F. A2Twin slave alarm bit field 2Read
AI27SLAVE B.F. E2Twin slave error bit fieldRead
AI28LOG ACT ERRLogged error X: error codeRead
AI29LOG ERR STA TLogged error X: start timesRead
AI30LOG ERR END TLogged error X: end timesRead
AI31LOG ERR B.F.Logged error X: error bit fieldRead
AI32LOG ERR COUNTLogged error X: occurrence counterRead
AI33LOG RPM SETLogged error X: speed setpointrpmRead
AI34LOG RPM VALUELogged error X: speedrpmRead
AI35LOG IQLogged error X: quadrature currentARead
AI36LOG AL 1 B.F.Logged error X: alarm bit field 1Read
AI37LOG AL 2 B.F.Logged error X: alarm bit field 2Read
AI38LOG B.F. IOLogged error X: I/O status bit fieldRead
AI39LOG PWRLogged error X: input powerWRead
AI40LOG QLogged error X: flowm³/hRead
AI41LOG HLogged error X: headmRead
AI42LOG PWR M TLogged error X: power module temperature°CRead
AI43LOG ON-OFFLogged error X: operating modeRead
AI48LIFE TMRLife timersRead
AI49TMR P 0-25Time at 0-25 % powersRead
AI50TMR P 25-50Time at 25-50 % powersRead
AI51TMR P 50-75Time at 50-75 % powersRead
AI52TMR P 75-100Time at 75-100 % powersRead
Object ID lookup: Xylem Lowara ecocirc XL / XLplus circulator point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Lowara ecocirc XL / XLplus circulator and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Xylem Lowara ecocirc XL / XLplus circulator

How many BACnet points does the Xylem Lowara ecocirc XL / XLplus circulator have?

This list has 68 BACnet objects: 49 analog inputs, 19 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Xylem Lowara ecocirc XL / XLplus circulator BACnet points are writable?

19 of the 68 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Xylem Lowara ecocirc XL / XLplus circulator BACnet documentation?

The source is ecocirc XLplus BACnet Objects (Technical Sheet) (ecocirc XLplus BACnet Objects r1.0), revision 2014-06-05 (PICS date), published free by Xylem at https://www.xylem.com/siteassets/brand/lowara/resources/manual/2014-08-29_ecocircxlplus_bacnet_objects_r1.0.pdf.

What are the minimum BACnet points to integrate the Xylem Lowara ecocirc XL / XLplus circulator?

Start with AV 0 ON OFF (Pump on/off (1 = on)); AV 1 OP. MODALITY (Control mode: 1 const. pressure, 2 prop., 3 curve); AV 6 CONST. H S.P. (Constant pressure head setpoint, m (mode 1)); AV 5 PROP. H S.P. (Proportional pressure head setpoint, m (mode 2)); AV 7 RPM S.P. (Constant curve speed setpoint, rpm (mode 3)); AI 3 CURR. RPM (Pump speed, rpm); AI 0 POWER (Input power, W); AI 2 CURR. Q (Flow estimate, m³/h); AI 1 CURR. H (Head, m); AI 15 CURR. ERROR (Active error code; 0 = no error).

How do I enable BMS control of the Xylem Lowara ecocirc XL / XLplus circulator?

No separate enable: AV 0 ON OFF turns the pump on (1) or off (0) and AV 1 selects the control mode whose setpoint (AV 5, AV 6 or AV 7) applies.

How do I check these points on the real Lowara ecocirc XL / XLplus circulator?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Xylem BACnet points lists

Source: ecocirc XLplus BACnet Objects (Technical Sheet) · ecocirc XLplus BACnet Objects r1.0 · rev. 2014-06-05 (PICS date). Object names, instances and units are reproduced as published; descriptions are our own.