Multistage smart pump with integrated drive (booster) · BACnet points list

Xylem Lowara Smart Pump e-HME / e-SVE / VME / e-SVIE (booster / multistage) BACnet points list

Updated 4 November 2026

Short answer

The Lowara Smart Pump multistage models have BACnet MS/TP built into the drive. Analog Values cover start/stop, control mode, speed and pressure setpoints, ramps, minimum-pressure protection and multi-pump settings; Analog Inputs give speed, pressure, current, power, temperatures, error and alarm codes and an error log.

This page lists 73 BACnet objects for the Xylem Lowara Smart Pump e-HME / e-SVE / VME / e-SVIE (booster / multistage) — 41 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Xylem’s own free documentation, linked below.

Manufacturer
Xylem
Model
Lowara Smart Pump e-HME / e-SVE / VME / e-SVIE (booster / multistage)
Equipment
Multistage smart pump with integrated drive (booster)
Equipment type
VFDs & pumps
BACnet objects
73 (41 writable)
Transport
BACnet MS/TP
Firmware
101.10 or later (e-HME, e-SVE, VME, e-SVIE)
Default device instance
84002
Also known as
e-HME, e-SVE, VME, e-SVIE, Lowara Smart Pump Range, Lowara e-SV smart
Source document
Smart Pump Range BACnet Protocol Parameter List · 001086068 EN rev. C · rev. 04/2021
Download CSV 73 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Xylem’s current documentation and the live device before use. Not official Xylem information. Terms of use.

BMS integration notes: Xylem Lowara Smart Pump e-HME / e-SVE / VME / e-SVIE (booster / multistage)

Integration in brief

Wire RS-485 to each drive, set a unique P51 MAC address and P53 device ID offset per pump, and pick a baud rate (38400 suggested). Write AV 1 for the control mode and AV 4 (pressure) or AV 2 (speed in ACT mode), then AV 0 = 0 to start.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 0STOP STARTStart/stop (0 = start, 1 = stop)Write
AV 1CONTROL MODESControl mode: 0 ACT, 1 HCS, 2 MSE, 3 MSYWrite
AV 4HEAD S.PPressure setpoint for HCS / MSE / MSYWrite
AV 2RPM SETPOINTSpeed setpoint in ACT mode, rpmWrite
AI 0MEASURED RPMMotor speed, rpmRead
AI 1MEASURED HEADMeasured pressure, bar/psi per AV 3Read
AI 4INPUT POWERInput power, WRead
AI 12ALARM CODECurrent alarm codeRead
AI 9ERROR CODECurrent error codeRead

Enable & remote start

AV 0 STOP START starts (0) or stops (1) the pump; AV 1 picks the control mode. AV 17 AUTOSTART sets whether the pump restarts by itself after power-up.

Network setup

Watch out for

Xylem Lowara Smart Pump e-HME / e-SVE / VME / e-SVIE (booster / multistage) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

73 of 73 shown
Type
Access
Show
Xylem Lowara Smart Pump e-HME / e-SVE / VME / e-SVIE (booster / multistage) BACnet Points List
DescriptionStates
AVmin0STOP STARTStart/stop command (0 = start, 1 = stop)Write0=Start, 1=Stop
AVmin1CONTROL MODESControl mode (P25)Write0=ACT, 1=HCS, 2=MSE, 3=MSY
AVmin2RPM SETPOINTSpeed setpoint in ACT mode, P27-P26rpmWrite
AV3BAR PSI SELECTPressure unit (P41)Write0=bar, 1=psi
AVmin4HEAD S.PPressure setpoint for HCS / MSE / MSYbar/psiWrite
AV54_20 PROBE FSFull scale of pressure sensor 1 (P42)bar/psiWrite
AV6ABS MAX RPMMaximum speed (P26)rpmWrite
AV7ABS MIN RPMMinimum speed (P27)rpmWrite
AV8LOG IDX SEL.Error log row selector, 0-7Write
AV9RESET DEFAULTReset to default values (P68)Write0=No, 1=Reset
AV10LOW BEHAVLack-of-water input behaviour (P48)Write0=Disabled, 1=Alarm, 2=Error
AV11HMI PASSWORDSystem password (P22), default 66Write
AV12HMI PAR LOCKParameter lock (P23)Write0=Off, 1=On
AV13AVOID EEP SAVAvoid frequent parameter saving (P69)Write0=No, 1=Yes
AV14TST RUN STARTTest run start interval (P65)hWrite
AV15TST RUN RPMTest run speed (P66)rpmWrite
AV16TST RUN TIMETest run duration (P67)sWrite
AV17AUTOSTARTAutomatic start (P04)Write0=Off, 1=On
AV18RAMP 1Ramp 1 (P28)sWrite
AV19RAMP 2Ramp 2 (P29)sWrite
AV20RAMP 3Ramp 3 (P30)sWrite
AV21RAMP 4Ramp 4 (P31)sWrite
AV22RAMP SMIN AAcceleration ramp at startup (P32)sWrite
AV23RAMP SMIN DDeceleration ramp at shutdown (P33)sWrite
AV24CONF SMINMinimum speed configuration (P34)Write0=STP, 1=SMI
AV25SMIN TIMEMinimum speed duration (P35)sWrite
AV26% RPM WINDOWAdjustment window (P36)%Write
AV27% RPM HYSTERAdjustment hysteresis (P37)%Write
AV28% RESTART VALRestart adjustment value (P03)%Write
AV29MIN THRESH LIMPressure minimum threshold (P45)bar/psiWrite
AV30TH LIM DELAYPressure minimum threshold delay (P46)sWrite
AV31TH LIM ERR RESMinimum threshold automatic error reset (P47)Write0=Disabled, 1=Enabled
AV32SWC OVER INTERMultipump switch interval (P57)hWrite
AV33SYNC RPM LIMMultipump synchronous shutdown speed (P61)rpmWrite
AV34SYNC WINDOWMultipump synchronous window (P62)rpmWrite
AV35ACT VAL INCMultipump actual value increase (P58)bar/psiWrite
AV36ACT VAL DECMultipump actual value decrease (P59)bar/psiWrite
AV37ENABLE SPEEDMultipump enable speed (P60)rpmWrite
AV38MP MAX UNITMultipump maximum units, 1-3 (P56)Write
AV39SPEED LIFTSpeed lift (P38)rpmWrite
AV40LIFT AMOUNTLift amount (P39)%Write
AImin0MEASURED RPMMotor speed (P16)rpmRead
AImin1MEASURED HEADCurrent pressurebar/psiRead
AI2QUAD CURRENTInverter current (P14)ARead
AI3GRID VOLTAGEInverter voltage (P15)VRead
AImin4INPUT POWERInput powerWRead
AI5W1 TEMPWinding 1 temperature°CRead
AI6W2 TEMPWinding 2 temperature°CRead
AI7W3 TEMPWinding 3 temperature°CRead
AI8POWER MOD TEMPPower module temperature (P13)°CRead
AImin9ERROR CODECurrent error codeRead
AI10ERROR B.F. MSWError bit field, high wordRead
AI11ERROR B.F. LSWError bit field, low word (E01-E11)Read
AImin12ALARM CODECurrent alarm codeRead
AI13ALARM 1 B.F.Alarm bit field, low wordRead
AI14ALARM 2 B.F.Alarm bit field, high word (A20 internal)Read
AI15LIFE TIMERTime of use (P05-P06)sRead
AI16RUNNING TIMERMotor running time (P07-P08)sRead
AI17LOG ACT ERRLogged error (row from AV 8): error codeRead
AI18LOG ERR STA TLogged error: start timesRead
AI19LOG ERR END TLogged error: end timesRead
AI20LOG ERR B.F.Logged error: error bit fieldRead
AI21LOG ERR COUNTLogged error: occurrence countRead
AI22LOG RPM SETLogged error: speed setpointrpmRead
AI23LOG RPM VALUELogged error: measured speedrpmRead
AI24LOG PHASE CURRLogged error: phase currentARead
AI25LOG AL 1 B.F.Logged error: alarm bit field 1Read
AI26LOG AL 2 B.FLogged error: alarm bit field 2Read
AI27LOG B.F. IOLogged error: I/O status bit fieldRead
AI28LOG PWRLogged error: powerWRead
AI30LOG HLogged error: pressurebar/psiRead
AI31LOG PWR.M. T.Logged error: power module temperature°CRead
AI32LOG STOP STARTLogged error: AV 0 valueRead
Object ID lookup: Xylem Lowara Smart Pump e-HME / e-SVE / VME / e-SVIE point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Lowara Smart Pump e-HME / e-SVE / VME / e-SVIE (booster / multistage) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Xylem Lowara Smart Pump e-HME / e-SVE / VME / e-SVIE (booster / multistage)

How many BACnet points does the Xylem Lowara Smart Pump e-HME / e-SVE / VME / e-SVIE (booster / multistage) have?

This list has 73 BACnet objects: 32 analog inputs, 41 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Xylem Lowara Smart Pump e-HME / e-SVE / VME / e-SVIE (booster / multistage) BACnet points are writable?

41 of the 73 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Xylem Lowara Smart Pump e-HME / e-SVE / VME / e-SVIE (booster / multistage) BACnet documentation?

The source is Smart Pump Range BACnet Protocol Parameter List (001086068 EN rev. C), revision 04/2021, published free by Xylem at https://www.xylem.com/siteassets/brand/lowara/resources/manual/001086068en_c_04_2021_bacnet.pdf.

What are the minimum BACnet points to integrate the Xylem Lowara Smart Pump e-HME / e-SVE / VME / e-SVIE (booster / multistage)?

Start with AV 0 STOP START (Start/stop (0 = start, 1 = stop)); AV 1 CONTROL MODES (Control mode: 0 ACT, 1 HCS, 2 MSE, 3 MSY); AV 4 HEAD S.P (Pressure setpoint for HCS / MSE / MSY); AV 2 RPM SETPOINT (Speed setpoint in ACT mode, rpm); AI 0 MEASURED RPM (Motor speed, rpm); AI 1 MEASURED HEAD (Measured pressure, bar/psi per AV 3); AI 4 INPUT POWER (Input power, W); AI 12 ALARM CODE (Current alarm code); AI 9 ERROR CODE (Current error code).

How do I enable BMS control of the Xylem Lowara Smart Pump e-HME / e-SVE / VME / e-SVIE (booster / multistage)?

AV 0 STOP START starts (0) or stops (1) the pump; AV 1 picks the control mode. AV 17 AUTOSTART sets whether the pump restarts by itself after power-up.

How do I check these points on the real Lowara Smart Pump e-HME / e-SVE / VME / e-SVIE (booster / multistage)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Xylem BACnet points lists

Source: Smart Pump Range BACnet Protocol Parameter List · 001086068 EN rev. C · rev. 04/2021. Object names, instances and units are reproduced as published; descriptions are our own.