In-line smart circulator pump with integrated drive · BACnet points list

Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line) BACnet points list

Updated 4 November 2026

Short answer

The Lowara Smart Pump in-line pumps have BACnet MS/TP built into the drive. Analog Values carry start/stop, control mode, speed and pressure setpoints and drive settings; Analog Inputs give speed, pressure, current, power, temperatures, error and alarm codes, an error log and, on twin sets, the follower pump's readings.

This page lists 64 BACnet objects for the Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line) — 21 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Xylem’s own free documentation, linked below.

Manufacturer
Xylem
Model
Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line)
Equipment
In-line smart circulator pump with integrated drive
Equipment type
VFDs & pumps
BACnet objects
64 (21 writable)
Transport
BACnet MS/TP
Firmware
151.06 or later (e-LNEEE, e-LNESE, e-LNTEE, e-LNTSE)
Default device instance
84002
Also known as
e-LNEEE, e-LNESE, e-LNTEE, e-LNTSE, e-LNEE, e-LNES, e-LNTE, e-LNTS, Lowara Smart Pump Range, Smart Pump e-LN
Source document
Smart Pump Range BACnet Protocol Parameter List · 001086068 EN rev. C · rev. 04/2021
Download CSV 64 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Xylem’s current documentation and the live device before use. Not official Xylem information. Terms of use.

BMS integration notes: Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line)

Integration in brief

Wire RS-485 to the drive (the twin master needs the RS485 module), set P51 MAC address and P53 device ID offset, and pick a baud rate (38400 suggested). Write AV 1 for the control mode and the matching setpoint (AV 2 speed, AV 4 constant pressure or AV 19 proportional pressure), then AV 0 = 0 to start.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 0STOP STARTStart/stop (0 = start, 1 = stop)Write
AV 1CONTROL MODESControl mode: 0 ACT, 1 CPP, 2 PPP/MSE, 3 MSYWrite
AV 2RPM SETPOINTSpeed setpoint in ACT mode, rpmWrite
AV 4CONST HEAD S.PConstant pressure setpoint (CPP)Write
AV 19PROP HEAD S.P.Proportional pressure setpointWrite
AI 0MEASURED RPMMotor speed, rpmRead
AI 1MEASURED HEADMeasured pressure, bar/psi per AV 3Read
AI 4INPUT POWERInput power, WRead
AI 12ALARM CODECurrent alarm codeRead
AI 9ERROR CODECurrent error codeRead

Enable & remote start

AV 0 STOP START starts (0) or stops (1) the pump; AV 1 picks the control mode whose setpoint applies.

Network setup

Watch out for

Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

64 of 64 shown
Type
Access
Show
Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line) BACnet Points List
DescriptionStates
AVmin0STOP STARTStart/stop command (0 = start, 1 = stop)Write0=Start, 1=Stop
AVmin1CONTROL MODESControl mode (P25)Write0=ACT, 1=CPP, 2=PPP/MSE, 3=MSY
AVmin2RPM SETPOINTSpeed setpoint in ACT mode, P27-P26rpmWrite
AV3BAR PSI SELECTPressure unit (P41)Write0=bar, 1=psi
AVmin4CONST HEAD S.PConstant pressure setpoint (CPP)bar/psiWrite
AV54_20 PROBE FSFull scale of pressure sensor 1 (P42)bar/psiWrite
AV6ABS MAX RPMMaximum speed (P26)rpmWrite
AV7ABS MIN RPMMinimum speed (P27)rpmWrite
AV8LOG IDX SEL.Error log row selector, 0-7Write
AV9RESET DEFAULTReset to default values (P68)Write0=No, 1=Reset
AV10LOW BEHAVLack-of-water input behaviour (P48)Write0=Disabled, 1=Alarm, 2=Error
AV11HMI PASSWORDSystem password (P22), default 66Write
AV12HMI PAR LOCKParameter lock (P23)Write0=Off, 1=On
AV13AVOID EEP SAVAvoid frequent parameter saving (P69)Write0=No, 1=Yes
AV14TST RUN STARTTest run start interval (P65)hWrite
AV15TST RUN RPMTest run speed (P66)rpmWrite
AV16TST RUN TIMETest run duration (P67)sWrite
AV17SENSOR CONFIG.Pressure sensor selection (P40)Write0=No sensor, 1=Two individual sensors, 2=One differential sensor
AV180_10 PROBE FSFull scale of pressure sensor 2 (P43)bar/psiWrite
AVmin19PROP HEAD S.P.Proportional pressure setpointbar/psiWrite
AV20TWIN CTRL MODETwin pump modeWrite0=Backup, 1=Alternate, 2=Parallel, 3=Force parallel
AImin0MEASURED RPMMotor speed (P16)rpmRead
AImin1MEASURED HEADCurrent pressurebar/psiRead
AI2QUAD CURRENTInverter current (P14)ARead
AI3GRID VOLTAGEInverter voltage (P15)VRead
AImin4INPUT POWERInput powerWRead
AI5W1 TEMPWinding 1 temperature°CRead
AI6W2 TEMPWinding 2 temperature°CRead
AI7W3 TEMPWinding 3 temperature°CRead
AI8POWER MOD TEMPPower module temperature (P13)°CRead
AImin9ERROR CODECurrent error codeRead
AI10ERROR B.F. MSWError bit field, high wordRead
AI11ERROR B.F. LSWError bit field, low word (E01-E11)Read
AImin12ALARM CODECurrent alarm codeRead
AI13ALARM 1 B.F.Alarm bit field, low wordRead
AI14ALARM 2 B.F.Alarm bit field, high word (A20 internal)Read
AI15LIFE TIMERTime of use (P05-P06)sRead
AI16RUNNING TIMERMotor running time (P07-P08)sRead
AI17LOG ACT ERRLogged error (row from AV 8): error codeRead
AI18LOG ERR STA TLogged error: start timesRead
AI19LOG ERR END TLogged error: end timesRead
AI20LOG ERR B.F.Logged error: error bit fieldRead
AI21LOG ERR COUNTLogged error: occurrence countRead
AI22LOG RPM SETLogged error: speed setpointrpmRead
AI23LOG RPM VALUELogged error: measured speedrpmRead
AI24LOG IQLogged error: phase currentARead
AI25LOG AL 1 B.F.Logged error: alarm bit field 1Read
AI26LOG AL 2 B.FLogged error: alarm bit field 2Read
AI27LOG B.F. IOLogged error: I/O status bit fieldRead
AI28LOG PWRLogged error: powerWRead
AI30LOG HLogged error: pressurebar/psiRead
AI31LOG PWR.M. T.Logged error: power module temperature°CRead
AI32LOG STOP STARTLogged error: AV 0 valueRead
AI38FOLL INPUT PWRTwin follower: input powerWRead
AI39FOLL MEAS HEADTwin follower: pressurebar/psiRead
AI41FOLL MEAS RPMTwin follower: motor speedrpmRead
AI42FOLL W1 TEMPTwin follower: winding 1 temperature°CRead
AI43FOLL W2 TEMPTwin follower: winding 2 temperature°CRead
AI44FOLL W3 TEMPTwin follower: winding 3 temperature°CRead
AI45FOLL MOD TEMPTwin follower: power module temperature°CRead
AI46FOLL QUAD CURRTwin follower: inverter currentARead
AI47FOLL ALR1 B.F.Twin follower: alarm bit field, low wordRead
AI48FOLL ALR2 B.F.Twin follower: alarm bit field, high wordRead
AI49FOLL ERR CODETwin follower: current error codeRead
Object ID lookup: Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line)

How many BACnet points does the Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line) have?

This list has 64 BACnet objects: 43 analog inputs, 21 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line) BACnet points are writable?

21 of the 64 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line) BACnet documentation?

The source is Smart Pump Range BACnet Protocol Parameter List (001086068 EN rev. C), revision 04/2021, published free by Xylem at https://www.xylem.com/siteassets/brand/lowara/resources/manual/001086068en_c_04_2021_bacnet.pdf.

What are the minimum BACnet points to integrate the Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line)?

Start with AV 0 STOP START (Start/stop (0 = start, 1 = stop)); AV 1 CONTROL MODES (Control mode: 0 ACT, 1 CPP, 2 PPP/MSE, 3 MSY); AV 2 RPM SETPOINT (Speed setpoint in ACT mode, rpm); AV 4 CONST HEAD S.P (Constant pressure setpoint (CPP)); AV 19 PROP HEAD S.P. (Proportional pressure setpoint); AI 0 MEASURED RPM (Motor speed, rpm); AI 1 MEASURED HEAD (Measured pressure, bar/psi per AV 3); AI 4 INPUT POWER (Input power, W); AI 12 ALARM CODE (Current alarm code); AI 9 ERROR CODE (Current error code).

How do I enable BMS control of the Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line)?

AV 0 STOP START starts (0) or stops (1) the pump; AV 1 picks the control mode whose setpoint applies.

How do I check these points on the real Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Xylem BACnet points lists

Source: Smart Pump Range BACnet Protocol Parameter List · 001086068 EN rev. C · rev. 04/2021. Object names, instances and units are reproduced as published; descriptions are our own.