- Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line)
In-line smart circulator pump with integrated drive · BACnet points list
Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line) BACnet points list
Updated 4 November 2026
The Lowara Smart Pump in-line pumps have BACnet MS/TP built into the drive. Analog Values carry start/stop, control mode, speed and pressure setpoints and drive settings; Analog Inputs give speed, pressure, current, power, temperatures, error and alarm codes, an error log and, on twin sets, the follower pump's readings.
This page lists 64 BACnet objects for the Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line) — 21 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Xylem’s own free documentation, linked below.
- Manufacturer
- Xylem
- Model
- Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line)
- Equipment
- In-line smart circulator pump with integrated drive
- Equipment type
- VFDs & pumps
- BACnet objects
- 64 (21 writable)
- Transport
- BACnet MS/TP
- Firmware
- 151.06 or later (e-LNEEE, e-LNESE, e-LNTEE, e-LNTSE)
- Default device instance
- 84002
- Also known as
- e-LNEEE, e-LNESE, e-LNTEE, e-LNTSE, e-LNEE, e-LNES, e-LNTE, e-LNTS, Lowara Smart Pump Range, Smart Pump e-LN
Reference only, provided as-is: verify against Xylem’s current documentation and the live device before use. Not official Xylem information. Terms of use.
BMS integration notes: Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line)
Wire RS-485 to the drive (the twin master needs the RS485 module), set P51 MAC address and P53 device ID offset, and pick a baud rate (38400 suggested). Write AV 1 for the control mode and the matching setpoint (AV 2 speed, AV 4 constant pressure or AV 19 proportional pressure), then AV 0 = 0 to start.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 0 | STOP START | Start/stop (0 = start, 1 = stop) | Write |
| AV 1 | CONTROL MODES | Control mode: 0 ACT, 1 CPP, 2 PPP/MSE, 3 MSY | Write |
| AV 2 | RPM SETPOINT | Speed setpoint in ACT mode, rpm | Write |
| AV 4 | CONST HEAD S.P | Constant pressure setpoint (CPP) | Write |
| AV 19 | PROP HEAD S.P. | Proportional pressure setpoint | Write |
| AI 0 | MEASURED RPM | Motor speed, rpm | Read |
| AI 1 | MEASURED HEAD | Measured pressure, bar/psi per AV 3 | Read |
| AI 4 | INPUT POWER | Input power, W | Read |
| AI 12 | ALARM CODE | Current alarm code | Read |
| AI 9 | ERROR CODE | Current error code | Read |
Enable & remote start
AV 0 STOP START starts (0) or stops (1) the pump; AV 1 picks the control mode whose setpoint applies.
Network setup
- MS/TP master; baud 4800-57600, 38400 suggested (4800 gives frequent timeouts).
- MAC address is parameter P51 Address, factory 1.
- Device instance factory 84002; set with P53 BACnet device ID offset.
- RS-485 on terminals 15 (B1), 16 (A1), 17 (GND) on single-phase drives or 7 (B1), 6 (A1), 5 (GND) on three-phase drives.
Watch out for
- While BACnet communication is active most parameters are locked at the drive keypad.
- Set P69 Avoid frequent parameters saving = yes (AV 13) if the BMS writes setpoints often, to spare the EEPROM.
- AV 9 RESET DEFAULT restores factory values; do not write it routinely.
- On twin sets set P51 and P53 on the master pump only.
Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 0 | STOP START | Start/stop command (0 = start, 1 = stop) | Write | 0=Start, 1=Stop | |
| AVmin | 1 | CONTROL MODES | Control mode (P25) | Write | 0=ACT, 1=CPP, 2=PPP/MSE, 3=MSY | |
| AVmin | 2 | RPM SETPOINT | Speed setpoint in ACT mode, P27-P26 | rpm | Write | |
| AV | 3 | BAR PSI SELECT | Pressure unit (P41) | Write | 0=bar, 1=psi | |
| AVmin | 4 | CONST HEAD S.P | Constant pressure setpoint (CPP) | bar/psi | Write | |
| AV | 5 | 4_20 PROBE FS | Full scale of pressure sensor 1 (P42) | bar/psi | Write | |
| AV | 6 | ABS MAX RPM | Maximum speed (P26) | rpm | Write | |
| AV | 7 | ABS MIN RPM | Minimum speed (P27) | rpm | Write | |
| AV | 8 | LOG IDX SEL. | Error log row selector, 0-7 | Write | ||
| AV | 9 | RESET DEFAULT | Reset to default values (P68) | Write | 0=No, 1=Reset | |
| AV | 10 | LOW BEHAV | Lack-of-water input behaviour (P48) | Write | 0=Disabled, 1=Alarm, 2=Error | |
| AV | 11 | HMI PASSWORD | System password (P22), default 66 | Write | ||
| AV | 12 | HMI PAR LOCK | Parameter lock (P23) | Write | 0=Off, 1=On | |
| AV | 13 | AVOID EEP SAV | Avoid frequent parameter saving (P69) | Write | 0=No, 1=Yes | |
| AV | 14 | TST RUN START | Test run start interval (P65) | h | Write | |
| AV | 15 | TST RUN RPM | Test run speed (P66) | rpm | Write | |
| AV | 16 | TST RUN TIME | Test run duration (P67) | s | Write | |
| AV | 17 | SENSOR CONFIG. | Pressure sensor selection (P40) | Write | 0=No sensor, 1=Two individual sensors, 2=One differential sensor | |
| AV | 18 | 0_10 PROBE FS | Full scale of pressure sensor 2 (P43) | bar/psi | Write | |
| AVmin | 19 | PROP HEAD S.P. | Proportional pressure setpoint | bar/psi | Write | |
| AV | 20 | TWIN CTRL MODE | Twin pump mode | Write | 0=Backup, 1=Alternate, 2=Parallel, 3=Force parallel | |
| AImin | 0 | MEASURED RPM | Motor speed (P16) | rpm | Read | |
| AImin | 1 | MEASURED HEAD | Current pressure | bar/psi | Read | |
| AI | 2 | QUAD CURRENT | Inverter current (P14) | A | Read | |
| AI | 3 | GRID VOLTAGE | Inverter voltage (P15) | V | Read | |
| AImin | 4 | INPUT POWER | Input power | W | Read | |
| AI | 5 | W1 TEMP | Winding 1 temperature | °C | Read | |
| AI | 6 | W2 TEMP | Winding 2 temperature | °C | Read | |
| AI | 7 | W3 TEMP | Winding 3 temperature | °C | Read | |
| AI | 8 | POWER MOD TEMP | Power module temperature (P13) | °C | Read | |
| AImin | 9 | ERROR CODE | Current error code | Read | ||
| AI | 10 | ERROR B.F. MSW | Error bit field, high word | Read | ||
| AI | 11 | ERROR B.F. LSW | Error bit field, low word (E01-E11) | Read | ||
| AImin | 12 | ALARM CODE | Current alarm code | Read | ||
| AI | 13 | ALARM 1 B.F. | Alarm bit field, low word | Read | ||
| AI | 14 | ALARM 2 B.F. | Alarm bit field, high word (A20 internal) | Read | ||
| AI | 15 | LIFE TIMER | Time of use (P05-P06) | s | Read | |
| AI | 16 | RUNNING TIMER | Motor running time (P07-P08) | s | Read | |
| AI | 17 | LOG ACT ERR | Logged error (row from AV 8): error code | Read | ||
| AI | 18 | LOG ERR STA T | Logged error: start time | s | Read | |
| AI | 19 | LOG ERR END T | Logged error: end time | s | Read | |
| AI | 20 | LOG ERR B.F. | Logged error: error bit field | Read | ||
| AI | 21 | LOG ERR COUNT | Logged error: occurrence count | Read | ||
| AI | 22 | LOG RPM SET | Logged error: speed setpoint | rpm | Read | |
| AI | 23 | LOG RPM VALUE | Logged error: measured speed | rpm | Read | |
| AI | 24 | LOG IQ | Logged error: phase current | A | Read | |
| AI | 25 | LOG AL 1 B.F. | Logged error: alarm bit field 1 | Read | ||
| AI | 26 | LOG AL 2 B.F | Logged error: alarm bit field 2 | Read | ||
| AI | 27 | LOG B.F. IO | Logged error: I/O status bit field | Read | ||
| AI | 28 | LOG PWR | Logged error: power | W | Read | |
| AI | 30 | LOG H | Logged error: pressure | bar/psi | Read | |
| AI | 31 | LOG PWR.M. T. | Logged error: power module temperature | °C | Read | |
| AI | 32 | LOG STOP START | Logged error: AV 0 value | Read | ||
| AI | 38 | FOLL INPUT PWR | Twin follower: input power | W | Read | |
| AI | 39 | FOLL MEAS HEAD | Twin follower: pressure | bar/psi | Read | |
| AI | 41 | FOLL MEAS RPM | Twin follower: motor speed | rpm | Read | |
| AI | 42 | FOLL W1 TEMP | Twin follower: winding 1 temperature | °C | Read | |
| AI | 43 | FOLL W2 TEMP | Twin follower: winding 2 temperature | °C | Read | |
| AI | 44 | FOLL W3 TEMP | Twin follower: winding 3 temperature | °C | Read | |
| AI | 45 | FOLL MOD TEMP | Twin follower: power module temperature | °C | Read | |
| AI | 46 | FOLL QUAD CURR | Twin follower: inverter current | A | Read | |
| AI | 47 | FOLL ALR1 B.F. | Twin follower: alarm bit field, low word | Read | ||
| AI | 48 | FOLL ALR2 B.F. | Twin follower: alarm bit field, high word | Read | ||
| AI | 49 | FOLL ERR CODE | Twin follower: current error code | Read |
No points match these filters.
Object ID lookup: Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS point IDs by name
AV0STOP STARTAV1CONTROL MODESAV2RPM SETPOINTAV3BAR PSI SELECTAV4CONST HEAD S.PAV54_20 PROBE FSAV6ABS MAX RPMAV7ABS MIN RPMAV8LOG IDX SEL.AV9RESET DEFAULTAV10LOW BEHAVAV11HMI PASSWORDAV12HMI PAR LOCKAV13AVOID EEP SAVAV14TST RUN STARTAV15TST RUN RPMAV16TST RUN TIMEAV17SENSOR CONFIG.AV180_10 PROBE FSAV19PROP HEAD S.P.AV20TWIN CTRL MODEAI0MEASURED RPMAI1MEASURED HEADAI2QUAD CURRENTAI3GRID VOLTAGEAI4INPUT POWERAI5W1 TEMPAI6W2 TEMPAI7W3 TEMPAI8POWER MOD TEMPAI9ERROR CODEAI10ERROR B.F. MSWAI11ERROR B.F. LSWAI12ALARM CODEAI13ALARM 1 B.F.AI14ALARM 2 B.F.AI15LIFE TIMERAI16RUNNING TIMERAI17LOG ACT ERRAI18LOG ERR STA TAI19LOG ERR END TAI20LOG ERR B.F.AI21LOG ERR COUNTAI22LOG RPM SETAI23LOG RPM VALUEAI24LOG IQAI25LOG AL 1 B.F.AI26LOG AL 2 B.FAI27LOG B.F. IOAI28LOG PWRAI30LOG HAI31LOG PWR.M. T.AI32LOG STOP STARTAI38FOLL INPUT PWRAI39FOLL MEAS HEADAI41FOLL MEAS RPMAI42FOLL W1 TEMPAI43FOLL W2 TEMPAI44FOLL W3 TEMPAI45FOLL MOD TEMPAI46FOLL QUAD CURRAI47FOLL ALR1 B.F.AI48FOLL ALR2 B.F.AI49FOLL ERR CODE
Integration notes
- The device instance is 84002 from the factory; change it with parameter P53 (BACnet device ID offset) or by writing the Device object's Object_Identifier.
- AV 0 uses inverted logic: 0 = start, 1 = stop.
- Setpoint limits and defaults depend on the pump model; speed limits come from P26/P27.
- Bit-field AIs (10, 11, 13, 14 and the log/follower fields) must be split into bits; the manual lists each bit.
- AI 17-32 show one row of the 8-row error log, chosen with AV 8.
- Objects the manual marks "N. A." (not used) or "RESERVED" are left out.
- Twin (dual pump) sets: only the master is wired to the BMS (it needs the RS485 Module Smart Pump); follower data appears on AI 38-49.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line)
How many BACnet points does the Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line) have?
This list has 64 BACnet objects: 43 analog inputs, 21 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line) BACnet points are writable?
21 of the 64 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line) BACnet documentation?
The source is Smart Pump Range BACnet Protocol Parameter List (001086068 EN rev. C), revision 04/2021, published free by Xylem at https://www.xylem.com/siteassets/brand/lowara/resources/manual/001086068en_c_04_2021_bacnet.pdf.
What are the minimum BACnet points to integrate the Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line)?
Start with AV 0 STOP START (Start/stop (0 = start, 1 = stop)); AV 1 CONTROL MODES (Control mode: 0 ACT, 1 CPP, 2 PPP/MSE, 3 MSY); AV 2 RPM SETPOINT (Speed setpoint in ACT mode, rpm); AV 4 CONST HEAD S.P (Constant pressure setpoint (CPP)); AV 19 PROP HEAD S.P. (Proportional pressure setpoint); AI 0 MEASURED RPM (Motor speed, rpm); AI 1 MEASURED HEAD (Measured pressure, bar/psi per AV 3); AI 4 INPUT POWER (Input power, W); AI 12 ALARM CODE (Current alarm code); AI 9 ERROR CODE (Current error code).
How do I enable BMS control of the Xylem Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line)?
AV 0 STOP START starts (0) or stops (1) the pump; AV 1 picks the control mode whose setpoint applies.
How do I check these points on the real Lowara Smart Pump e-LNEE / e-LNES / e-LNTE / e-LNTS (in-line)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Xylem BACnet points lists
- ECM circulator pump (wet rotor)
Xylem Lowara ecocirc XL / XLplus circulator
Lowara ecocirc XL and ecocirc XLplus single and twin wet-rotor circulators with the communication-capable drive.
Also known as: ecocirc XLplus, ecocirc XL, Lowara ecocirc, ecocirc XLplus BACnet - Multistage smart pump with integrated drive (booster)
Xylem Lowara Smart Pump e-HME / e-SVE / VME / e-SVIE (booster / multistage)
Lowara Smart Pump Range multistage pumps e-HME, e-SVE, VME and e-SVIE (firmware 101.10 and later), alone or in a 2-3 pump multi-pump set.
Also known as: e-HME, e-SVE, VME, e-SVIE, Lowara Smart Pump Range, Lowara e-SV smart
Source: Smart Pump Range BACnet Protocol Parameter List · 001086068 EN rev. C · rev. 04/2021. Object names, instances and units are reproduced as published; descriptions are our own.