Watts tekmar Smart Boiler Control 294BAC BACnet points list

Updated 7 November 2026

Short answer

The tekmar 294BAC stages and resets up to 16 boilers and handles domestic hot water. It talks BACnet IP or BACnet MS/TP natively and exposes the plant targets and temperatures, pressure, override state, pump run times, per-boiler firing rate, EMS temperature output, run hours and cycles, per-boiler status and availability, and a large set of writable settings: outdoor temperature from the BAS, room and DHW setpoints, reset curve, boiler limits, staging, alerts and service intervals.

This page lists 241 BACnet objects for the Watts tekmar Smart Boiler Control 294BAC — 107 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Watts’s own free documentation, linked below.

Manufacturer
Watts
Model
tekmar Smart Boiler Control 294BAC
Equipment
Multi-boiler plant controller
Equipment type
Boilers & water heaters
BACnet objects
241 (107 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
J1308, firmware 1.14.0 or later (PICS)
Default device instance
1
Also known as
tekmar 294BAC, 294BAC, tekmar 294, Smart Boiler Control 294, J1308
Source document
Smart Boiler Control 294BAC - BAS Integration Manual · IS-T-294BAC 2627 · rev. 2026
Download CSV 241 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Watts’s current documentation and the live device before use. Not official Watts information. Terms of use.

BMS integration notes: Watts tekmar Smart Boiler Control 294BAC

Integration in brief

Set BAS Type to BACnet IP or BACnet MS/TP in the 294BAC BAS menu, give it a Device ID, and discover it. Turn central heating on with BV 0, set occupied/unoccupied room and DHW targets, optionally feed the outdoor temperature from the BAS (AV 0 with AV 33 = BAS), and monitor the boiler target and supply temperatures, plant output, boiler statuses and the error code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0Central heatingCentral heating on/offWrite
AV 1Room occupiedOccupied room target, 34.7-100.4 °FWrite
AV 11DHW tank occupiedOccupied DHW tank setpoint, 50-230 °FWrite
AV 0Outdoor air temperatureOutdoor temperature from the BAS (when AV 33 = BAS)Write
AI 1Boiler target temperaturePlant supply targetRead
AI 2Boiler supply temperaturePlant supply temperatureRead
AI 3Plant outputPlant output, 0-100 %Read
BI 100Boiler 1 statusBoiler 1 firing (1 = on)Read
AI 0Error codeActive error codeRead

Enable & remote start

BV 0 Central heating turns space heating on or off; BV 100 + 10 x (n - 1) makes boiler n available.

Sensors & values from the BMS

Set AV 33 Outdoor sensor to 4 (BAS) and write the outdoor temperature to AV 0. Error 153 flags a BAS outdoor sensor problem; the manual does not give a timeout.

Network setup

Watch out for

Watts tekmar Smart Boiler Control 294BAC BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

241 of 241 shown
Type
Access
Show
Watts tekmar Smart Boiler Control 294BAC BACnet Points List
DescriptionStates
AImin0Error codeActive error code (see error list)Read
AImin1Boiler target temperatureRange 50-230 °F°FRead
AImin2Boiler supply temperatureRange 32.0-266.0 °F°FRead
AImin3Plant outputRange 0-100 %%Read
AI4Domestic hot water tank targetRange 32.0-266.0 °F°FRead
AI5Domestic hot water tank temperatureRange 32.0-266.0 °F°FRead
AI6Setpoint target temperatureRange 32.0-266.0 °F°FRead
AI7Central heating targetRange 32.0-266.0 °F°FRead
AI8Room targetRange 32.0-266.0 °F°FRead
AI9PressureRange 0.0-150.0 psipsiRead
AI10IndoorRange 32.0-266.0 °F°FRead
AI11OverrideRead0=Auto, 1=Hand, 2=Max Heat, 3=Purge, 4=Off, 5=Exercise
AI12System pump run time hoursRange 0-999999hRead
AI13System cyclesRange 0-999999Read
AI14DHW pump run time hoursRange 0-999999hRead
AI15DHW cyclesRange 0-999999Read
AI100Boiler 1 firing rateRange 0-100 %%Read
AI101Boiler 1 EMS temperature outputRange 50.0-210.2 °F°FRead
AI102Boiler 1 run time hoursRange 0-999999hRead
AI103Boiler 1 cyclesRange 0-999999Read
AI104Boiler 1 pump or valve run time hoursRange 0-999999hRead
AI110Boiler 2 firing rateRange 0-100 %%Read
AI111Boiler 2 EMS temperature outputRange 50.0-210.2 °F°FRead
AI112Boiler 2 run time hoursRange 0-999999hRead
AI113Boiler 2 cyclesRange 0-999999Read
AI114Boiler 2 pump or valve run time hoursRange 0-999999hRead
AI120Boiler 3 firing rateRange 0-100 %%Read
AI121Boiler 3 EMS temperature outputRange 50.0-210.2 °F°FRead
AI122Boiler 3 run time hoursRange 0-999999hRead
AI123Boiler 3 cyclesRange 0-999999Read
AI124Boiler 3 pump or valve run time hoursRange 0-999999hRead
AI130Boiler 4 firing rateRange 0-100 %%Read
AI131Boiler 4 EMS temperature outputRange 50.0-210.2 °F°FRead
AI132Boiler 4 run time hoursRange 0-999999hRead
AI133Boiler 4 cyclesRange 0-999999Read
AI134Boiler 4 pump or valve run time hoursRange 0-999999hRead
AI140Boiler 5 firing rateRange 0-100 %%Read
AI141Boiler 5 EMS temperature outputRange 50.0-210.2 °F°FRead
AI142Boiler 5 run time hoursRange 0-999999hRead
AI143Boiler 5 cyclesRange 0-999999Read
AI144Boiler 5 pump or valve run time hoursRange 0-999999hRead
AI150Boiler 6 firing rateRange 0-100 %%Read
AI151Boiler 6 EMS temperature outputRange 50.0-210.2 °F°FRead
AI152Boiler 6 run time hoursRange 0-999999hRead
AI153Boiler 6 cyclesRange 0-999999Read
AI154Boiler 6 pump or valve run time hoursRange 0-999999hRead
AI160Boiler 7 firing rateRange 0-100 %%Read
AI161Boiler 7 EMS temperature outputRange 50.0-210.2 °F°FRead
AI162Boiler 7 run time hoursRange 0-999999hRead
AI163Boiler 7 cyclesRange 0-999999Read
AI164Boiler 7 pump or valve run time hoursRange 0-999999hRead
AI170Boiler 8 firing rateRange 0-100 %%Read
AI171Boiler 8 EMS temperature outputRange 50.0-210.2 °F°FRead
AI172Boiler 8 run time hoursRange 0-999999hRead
AI173Boiler 8 cyclesRange 0-999999Read
AI174Boiler 8 pump or valve run time hoursRange 0-999999hRead
AI180Boiler 9 firing rateRange 0-100 %%Read
AI181Boiler 9 EMS temperature outputRange 50.0-210.2 °F°FRead
AI182Boiler 9 run time hoursRange 0-999999hRead
AI183Boiler 9 cyclesRange 0-999999Read
AI184Boiler 9 pump or valve run time hoursRange 0-999999hRead
AI190Boiler 10 firing rateRange 0-100 %%Read
AI191Boiler 10 EMS temperature outputRange 50.0-210.2 °F°FRead
AI192Boiler 10 run time hoursRange 0-999999hRead
AI193Boiler 10 cyclesRange 0-999999Read
AI194Boiler 10 pump or valve run time hoursRange 0-999999hRead
AI200Boiler 11 firing rateRange 0-100 %%Read
AI201Boiler 11 EMS temperature outputRange 50.0-210.2 °F°FRead
AI202Boiler 11 run time hoursRange 0-999999hRead
AI203Boiler 11 cyclesRange 0-999999Read
AI204Boiler 11 pump or valve run time hoursRange 0-999999hRead
AI210Boiler 12 firing rateRange 0-100 %%Read
AI211Boiler 12 EMS temperature outputRange 50.0-210.2 °F°FRead
AI212Boiler 12 run time hoursRange 0-999999hRead
AI213Boiler 12 cyclesRange 0-999999Read
AI214Boiler 12 pump or valve run time hoursRange 0-999999hRead
AI220Boiler 13 firing rateRange 0-100 %%Read
AI221Boiler 13 EMS temperature outputRange 50.0-210.2 °F°FRead
AI222Boiler 13 run time hoursRange 0-999999hRead
AI223Boiler 13 cyclesRange 0-999999Read
AI224Boiler 13 pump or valve run time hoursRange 0-999999hRead
AI230Boiler 14 firing rateRange 0-100 %%Read
AI231Boiler 14 EMS temperature outputRange 50.0-210.2 °F°FRead
AI232Boiler 14 run time hoursRange 0-999999hRead
AI233Boiler 14 cyclesRange 0-999999Read
AI234Boiler 14 pump or valve run time hoursRange 0-999999hRead
AI240Boiler 15 firing rateRange 0-100 %%Read
AI241Boiler 15 EMS temperature outputRange 50.0-210.2 °F°FRead
AI242Boiler 15 run time hoursRange 0-999999hRead
AI243Boiler 15 cyclesRange 0-999999Read
AI244Boiler 15 pump or valve run time hoursRange 0-999999hRead
AI250Boiler 16 firing rateRange 0-100 %%Read
AI251Boiler 16 EMS temperature outputRange 50.0-210.2 °F°FRead
AI252Boiler 16 run time hoursRange 0-999999hRead
AI253Boiler 16 cyclesRange 0-999999Read
AI254Boiler 16 pump or valve run time hoursRange 0-999999hRead
AVmin0Outdoor air temperatureRange -85-149 °F°FWrite
AVmin1Room occupiedRange 34.7-100.4 °F°FWrite
AV2Room unoccupiedRange 34.7-100.4 °F°FWrite
AV3Terminal unitWrite0=Radiant Floor, 1=Baseboard, 2=Radiator, 3=Fancoil
AV4Outdoor design temperatureRange -60-45 °F°FWrite
AV5Outdoor start temperatureRange 34.7-100.4 °F°FWrite
AV6Boiler start temperatureRange 34.7-100.4 °F°FWrite
AV7Boiler design temperatureRange 50-230 °F°FWrite
AV8Warm weather shut down occupiedRange 34.7-100.4 °F°FWrite
AV9Warm weather shut down unoccupiedRange 34.7-100.4 °F°FWrite
AV10DHW TypeWrite0=System, 1=Side, 2=Dedicated
AVmin11DHW tank occupiedRange 50-230 °F°FWrite
AV12DHW tank unoccupiedRange 50-230 °F°FWrite
AV13DHW tank differentialRange 0.9-42.4 Δ°FΔ°FWrite
AV14DHW exchange occupiedRange 50-230 °F°FWrite
AV15Indirect DHW priority overrideRange 20-240 minminWrite
AV16Indirect DHW boiler limitingRange 1-16Write
AV17Constant setpoint occupiedRange 50-230 °F°FWrite
AV18Boiler minimumRange 50-230 °F°FWrite
AV19Boiler maximumRange 50-230 °F°FWrite
AV20StagingWrite0=PID, 1=Proportional
AV21PID manual boiler differentialRange 1.8-42.4 Δ°FΔ°FWrite
AV22Proportional interstage differentialRange 0.9-10.0 Δ°FΔ°FWrite
AV23Proportional interstage manualRange 0.5-40.0 minminWrite
AV24Proportional interstage on delayRange 0.5-10.0 minminWrite
AV25Proportional interstage off delayRange 0.5-10.0 minminWrite
AV26Minimum stage run timeRange 0.5-10.0 minminWrite
AV27Minimum stage off timeRange 0.5-10.0 minminWrite
AV28Condensing group sequencingWrite0=Sequential, 1=Parallel
AV29Non-Condensing group sequencingWrite0=Sequential, 1=Parallel
AV30Feature lead typeWrite0=First On First Off, 1=First On Last Off
AV31Combustion air delayRange 0-360 ssWrite
AV32Variable primary flowWrite0=Pump, 1=Valve
AV33Outdoor sensorWrite0=Control, 1=tN4, 2=Cloud, 3=Wireless, 4=BAS
AV34Alert Boiler High temperatureRange 50-230 °F°FWrite
AV35Alert Boiler Low temperatureRange 50-230 °F°FWrite
AV36Alert High PressureRange 0-150 psipsiWrite
AV37Alert Low PressureRange 0-150 psipsiWrite
AV38Alert No HeatRange 0.5-80hWrite
AV100Alert Boiler 1 hoursRange 1000-15000hWrite
AV101Alert Boiler 1 cyclesRange 1-25000Write
AV110Alert Boiler 2 hoursRange 1000-15000hWrite
AV111Alert Boiler 2 cyclesRange 1-25000Write
AV120Alert Boiler 3 hoursRange 1000-15000hWrite
AV121Alert Boiler 3 cyclesRange 1-25000Write
AV130Alert Boiler 4 hoursRange 1000-15000hWrite
AV131Alert Boiler 4 cyclesRange 1-25000Write
AV140Alert Boiler 5 hoursRange 1000-15000hWrite
AV141Alert Boiler 5 cyclesRange 1-25000Write
AV150Alert Boiler 6 hoursRange 1000-15000hWrite
AV151Alert Boiler 6 cyclesRange 1-25000Write
AV160Alert Boiler 7 hoursRange 1000-15000hWrite
AV161Alert Boiler 7 cyclesRange 1-25000Write
AV170Alert Boiler 8 hoursRange 1000-15000hWrite
AV171Alert Boiler 8 cyclesRange 1-25000Write
AV180Alert Boiler 9 hoursRange 1000-15000hWrite
AV181Alert Boiler 9 cyclesRange 1-25000Write
AV190Alert Boiler 10 hoursRange 1000-15000hWrite
AV191Alert Boiler 10 cyclesRange 1-25000Write
AV200Alert Boiler 11 hoursRange 1000-15000hWrite
AV201Alert Boiler 11 cyclesRange 1-25000Write
AV210Alert Boiler 12 hoursRange 1000-15000hWrite
AV211Alert Boiler 12 cyclesRange 1-25000Write
AV220Alert Boiler 13 hoursRange 1000-15000hWrite
AV221Alert Boiler 13 cyclesRange 1-25000Write
AV230Alert Boiler 14 hoursRange 1000-15000hWrite
AV231Alert Boiler 14 cyclesRange 1-25000Write
AV240Alert Boiler 15 hoursRange 1000-15000hWrite
AV241Alert Boiler 15 cyclesRange 1-25000Write
AV250Alert Boiler 16 hoursRange 1000-15000hWrite
AV251Alert Boiler 16 cyclesRange 1-25000Write
BI0tekmarNet call statusRead0=Off, 1=On
BI1System pump statusRead0=Off, 1=On
BI2DHW pump statusRead0=Off, 1=On
BI3Combustion air damper statusRead0=Off, 1=On
BI4Domestic Hot Water PriorityRead0=Off, 1=On
BI5Warm Weather Shut DownRead0=Off, 1=On
BImin100Boiler 1 statusRead0=Off, 1=On
BI101Boiler 1 pump or valve statusRead0=Off, 1=On
BI110Boiler 2 statusRead0=Off, 1=On
BI111Boiler 2 pump or valve statusRead0=Off, 1=On
BI120Boiler 3 statusRead0=Off, 1=On
BI121Boiler 3 pump or valve statusRead0=Off, 1=On
BI130Boiler 4 statusRead0=Off, 1=On
BI131Boiler 4 pump or valve statusRead0=Off, 1=On
BI140Boiler 5 statusRead0=Off, 1=On
BI141Boiler 5 pump or valve statusRead0=Off, 1=On
BI150Boiler 6 statusRead0=Off, 1=On
BI151Boiler 6 pump or valve statusRead0=Off, 1=On
BI160Boiler 7 statusRead0=Off, 1=On
BI161Boiler 7 pump or valve statusRead0=Off, 1=On
BI170Boiler 8 statusRead0=Off, 1=On
BI171Boiler 8 pump or valve statusRead0=Off, 1=On
BI180Boiler 9 statusRead0=Off, 1=On
BI181Boiler 9 pump or valve statusRead0=Off, 1=On
BI190Boiler 10 statusRead0=Off, 1=On
BI191Boiler 10 pump or valve statusRead0=Off, 1=On
BI200Boiler 11 statusRead0=Off, 1=On
BI201Boiler 11 pump or valve statusRead0=Off, 1=On
BI210Boiler 12 statusRead0=Off, 1=On
BI211Boiler 12 pump or valve statusRead0=Off, 1=On
BI220Boiler 13 statusRead0=Off, 1=On
BI221Boiler 13 pump or valve statusRead0=Off, 1=On
BI230Boiler 14 statusRead0=Off, 1=On
BI231Boiler 14 pump or valve statusRead0=Off, 1=On
BI240Boiler 15 statusRead0=Off, 1=On
BI241Boiler 15 pump or valve statusRead0=Off, 1=On
BI250Boiler 16 statusRead0=Off, 1=On
BI251Boiler 16 pump or valve statusRead0=Off, 1=On
BVmin0Central heatingWrite0=Off, 1=On
BV1Warm weather shut downWrite0=Off, 1=On
BV2DHW availableWrite0=Off, 1=On
BV3DHW sensor availableWrite0=Off, 1=On
BV4DHW exchange unoccupiedWrite0=Off, 1=On
BV5Indirect DHW priorityWrite0=Off, 1=On
BV6Indirect DHW system pumpWrite0=Off, 1=On
BV7Constant setpointWrite0=Off, 1=On
BV8Constant setpoint unoccupiedWrite0=Off, 1=On
BV9Constant setpoint priorityWrite0=Off, 1=On
BV10Constant setpoint system pumpWrite0=Off, 1=On
BV11Remote setpointWrite0=Off, 1=On
BV12Boiler Auto DiffWrite0=Off, 1=On
BV13Interstage AutoWrite0=Off, 1=On
BV14Condensing Boiler RotationWrite0=Off, 1=On
BV15Non-Condensing Boiler RotationWrite0=Off, 1=On
BV16Staging Fixed LeadWrite0=Off, 1=On
BV17Staging Fixed LastWrite0=Off, 1=On
BV18Pressure sensor availableWrite0=Off, 1=On
BV19Exercise availableWrite0=Off, 1=On
BV100Boiler 1 availableWrite0=Off, 1=On
BV110Boiler 2 availableWrite0=Off, 1=On
BV120Boiler 3 availableWrite0=Off, 1=On
BV130Boiler 4 availableWrite0=Off, 1=On
BV140Boiler 5 availableWrite0=Off, 1=On
BV150Boiler 6 availableWrite0=Off, 1=On
BV160Boiler 7 availableWrite0=Off, 1=On
BV170Boiler 8 availableWrite0=Off, 1=On
BV180Boiler 9 availableWrite0=Off, 1=On
BV190Boiler 10 availableWrite0=Off, 1=On
BV200Boiler 11 availableWrite0=Off, 1=On
BV210Boiler 12 availableWrite0=Off, 1=On
BV220Boiler 13 availableWrite0=Off, 1=On
BV230Boiler 14 availableWrite0=Off, 1=On
BV240Boiler 15 availableWrite0=Off, 1=On
BV250Boiler 16 availableWrite0=Off, 1=On
Object ID lookup: Watts tekmar Smart Boiler Control 294BAC point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the tekmar Smart Boiler Control 294BAC and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Watts tekmar Smart Boiler Control 294BAC

How many BACnet points does the Watts tekmar Smart Boiler Control 294BAC have?

This list has 241 BACnet objects: 96 analog inputs, 71 analog values, 38 binary inputs, 36 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Watts tekmar Smart Boiler Control 294BAC BACnet points are writable?

107 of the 241 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Watts tekmar Smart Boiler Control 294BAC BACnet documentation?

The source is Smart Boiler Control 294BAC - BAS Integration Manual (IS-T-294BAC 2627), revision 2026, published free by Watts at https://www.watts.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/674967-source/is-t-294bac-2627.pdf.

What are the minimum BACnet points to integrate the Watts tekmar Smart Boiler Control 294BAC?

Start with BV 0 Central heating (Central heating on/off); AV 1 Room occupied (Occupied room target, 34.7-100.4 °F); AV 11 DHW tank occupied (Occupied DHW tank setpoint, 50-230 °F); AV 0 Outdoor air temperature (Outdoor temperature from the BAS (when AV 33 = BAS)); AI 1 Boiler target temperature (Plant supply target); AI 2 Boiler supply temperature (Plant supply temperature); AI 3 Plant output (Plant output, 0-100 %); BI 100 Boiler 1 status (Boiler 1 firing (1 = on)); AI 0 Error code (Active error code).

How do I enable BMS control of the Watts tekmar Smart Boiler Control 294BAC?

BV 0 Central heating turns space heating on or off; BV 100 + 10 x (n - 1) makes boiler n available.

Can the BMS supply sensor values to the Watts tekmar Smart Boiler Control 294BAC?

Set AV 33 Outdoor sensor to 4 (BAS) and write the outdoor temperature to AV 0. Error 153 flags a BAS outdoor sensor problem; the manual does not give a timeout.

How do I check these points on the real tekmar Smart Boiler Control 294BAC?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.