Snow melting controller (boiler-fed slab) · BACnet points list

Watts tekmar Snow Melting Control 680 BACnet points list

Updated 6 November 2026

Short answer

The tekmar 680 runs an automatic snow melting system: it watches up to two slab and snow/ice sensors, fires a boiler and drives mixing, and talks BACnet IP or BACnet MS/TP natively. The object list gives operation and status codes, melt time remaining, slab, boiler and system temperatures, outputs, flow, pressure, run hours and the error code, plus writable melt/idle/storm setpoints, times, sensitivities and melt/storm requests.

This page lists 52 BACnet objects for the Watts tekmar Snow Melting Control 680 — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Watts’s own free documentation, linked below.

Manufacturer
Watts
Model
tekmar Snow Melting Control 680
Equipment
Snow melting controller (boiler-fed slab)
Equipment type
Boilers & water heaters
BACnet objects
52 (18 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
J1243F (PICS)
Also known as
tekmar 680, Snow Melting Control 680, 680, tekmar snow melt 680, J1243F
Source document
Snow Melting Control 680 BAS Integration Manual · 680_B · rev. 03/20
Download CSV 52 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Watts’s current documentation and the live device before use. Not official Watts information. Terms of use.

BMS integration notes: Watts tekmar Snow Melting Control 680

Integration in brief

Use Melt/Stop Request to start or stop a melt and Storm/Stop Request for storm mode, and adjust the melt, idle and storm setpoints as needed. Read Operation and Operation Status, slab and boiler temperatures, the snow/ice sensor states and the error code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1Melt/Stop RequestStart melting from the BMS (1 = Melt)Write
BV 2Storm/Stop RequestStart storm mode from the BMS (1 = Storm)Write
AV 1Melt SetpointSlab melting setpoint, 32-95 °FWrite
AV 0BAS Outdoor Air TemperatureOutdoor temperature from the BMS (if BV 0 = 1)Write
BV 0Outdoor Sensor Enable1 = use the BMS outdoor temperatureWrite
AI 0Operation0 Off, 1 Idle, 2 Storm, 3 Melt, 4 ManualRead
AI 1Operation StatusNormal, WWSD, CWSD, timed melt, warming upRead
AI 7Coldest Slab TemperatureColdest slab temperatureRead
BI 2Combined Water StatusCombined snow/ice sensor state (1 = wet)Read
AI 26Error CodeError code; see the error listRead

Enable & remote start

BV 1 Melt/Stop Request (1 = Melt) and BV 2 Storm/Stop Request (1 = Storm) start a melt or storm cycle from the BMS. BV 3-6 enable or disable idling, storm mode, warm weather shut down and cold weather cut out.

Sensors & values from the BMS

Set BV 0 Outdoor Sensor Enable = 1 so the 680 uses the BAS outdoor temperature written to AV 0 (-67 to 149 °F); with 0 it measures its own outdoor sensor.

Network setup

Watch out for

Watts tekmar Snow Melting Control 680 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

52 of 52 shown
Type
Access
Show
Watts tekmar Snow Melting Control 680 BACnet Points List
DescriptionStates
AImin0OperationRead0=Off, 1=Idle, 2=Storm, 3=Melt, 4=Manual Override
AImin1Operation StatusRead0=Normal, 1=WWSD, 2=CWSD, 3=Timed Melting, 4=Warming Up, 5=Pending
AI2Melt Time RemainingRange 0 to 24:00 hourshRead
AI3Additional Melt Time RemainingRange 0 to 6:00 hourshRead
AI4Outdoor Air TemperatureRange -67 to 149°F°FRead
AI5Slab 1 TemperatureRange -58 to 167°F°FRead
AI6Slab 2 TemperatureRange -58 to 167°F°FRead
AImin7Coldest Slab TemperatureRange -58 to 167°F°FRead
AI8Slab Target TemperatureRange 20 to 120°F°FRead
AI9Boiler Supply TemperatureRange -31 to 266°F°FRead
AI10Boiler Return TemperatureRange -31 to 266°F°FRead
AI11Boiler Target TemperatureRange 50 to 230°F°FRead
AI12Boiler OutputRange 0 to 100%%Read
AI13System Supply TemperatureRange -31 to 266°F°FRead
AI14System Return TemperatureRange -31 to 266°F°FRead
AI15Mix System Target TemperatureRange 50 to 230°F°FRead
AI16Mix System OutputRange 0 to 100%%Read
AI17PWM and Electric Heat OutputRange 0 to 100%%Read
AI18System Flow RateRange 0 to 1000 GPMgpmRead
AI19System PressureRange 0 to 300 psipsiRead
AI21Melting HoursRange 0 to 65535 HourshRead
AI22Heat CyclesRange 0 to 65535 CyclesRead
AI23System Pump Run TimeRange 0 to 65535 HourshRead
AI24Primary Pump Run TimeRange 0 to 65535 HourshRead
AI25Boiler Pump Run TimeRange 0 to 65535 HourshRead
AImin26Error CodeCode from the error code list in the manualRead
AVmin0BAS Outdoor Air TemperatureRange -67 to 149°F°FWrite
AVmin1Melt SetpointRange 32 to 95°F°FWrite
AV2Idle SetpointRange 20 to 95°F, 0 = off°FWrite
AV3Storm SetpointRange 20 to 95°F, 0 = off°FWrite
AV4Manual Melt TimeRange 0:30 to 24:00 HourshWrite
AV5Add Melt TimeRange 0:00 to 6:00 HourshWrite
AV6Storm Run TimeRange 0:30 to 24:00 HourshWrite
AV7Snow/Ice Sensitivity 1Write0=Auto, 1=Min, 2=-2, 3=-1, 4=Mid, 5=+1, 6=+2, 7=Max
AV8Snow/Ice Sensitivity 2Write0=Auto, 1=Min, 2=-2, 3=-1, 4=Mid, 5=+1, 6=+2, 7=Max
AV9Warm Weather Shut DownRange 32 to 95°F°FWrite
AV10Cold Weather Cut OutRange -30 to 50°F°FWrite
BI0Slab 1 WaterRead0=Dry, 1=Wet
BI1Slab 2 WaterRead0=Dry, 1=Wet
BImin2Combined Water StatusRead0=Dry, 1=Wet
BI3System PumpRead0=Off, 1=On
BI4Primary PumpRead0=Off, 1=On
BI5Boiler PumpRead0=Off, 1=On
BI6Boiler Stage 1Read0=Off, 1=On
BI7Boiler Stage 2Read0=Off, 1=On
BVmin0Outdoor Sensor EnableWrite0=Control measures outdoor air temperature, 1=BAS sends outdoor air temperature
BVmin1Melt/Stop RequestWrite0=Off, 1=Melt
BVmin2Storm/Stop RequestWrite0=Off, 1=Storm
BV3Idle EnableWrite0=Idling disabled, 1=Idling enabled
BV4Storm EnableWrite0=Storm disabled, 1=Storm enabled
BV5WWSD EnableWrite0=WWSD disabled, 1=WWSD enabled
BV6CWCO EnableWrite0=CWCO disabled, 1=CWCO enabled
Object ID lookup: Watts tekmar Snow Melting Control 680 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the tekmar Snow Melting Control 680 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Watts tekmar Snow Melting Control 680

How many BACnet points does the Watts tekmar Snow Melting Control 680 have?

This list has 52 BACnet objects: 26 analog inputs, 11 analog values, 8 binary inputs, 7 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Watts tekmar Snow Melting Control 680 BACnet points are writable?

18 of the 52 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Watts tekmar Snow Melting Control 680 BACnet documentation?

The source is Snow Melting Control 680 BAS Integration Manual (680_B), revision 03/20, published free by Watts at https://www.watts.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/43041-source/680_b_02.pdf.

What are the minimum BACnet points to integrate the Watts tekmar Snow Melting Control 680?

Start with BV 1 Melt/Stop Request (Start melting from the BMS (1 = Melt)); BV 2 Storm/Stop Request (Start storm mode from the BMS (1 = Storm)); AV 1 Melt Setpoint (Slab melting setpoint, 32-95 °F); AV 0 BAS Outdoor Air Temperature (Outdoor temperature from the BMS (if BV 0 = 1)); BV 0 Outdoor Sensor Enable (1 = use the BMS outdoor temperature); AI 0 Operation (0 Off, 1 Idle, 2 Storm, 3 Melt, 4 Manual); AI 1 Operation Status (Normal, WWSD, CWSD, timed melt, warming up); AI 7 Coldest Slab Temperature (Coldest slab temperature); BI 2 Combined Water Status (Combined snow/ice sensor state (1 = wet)); AI 26 Error Code (Error code; see the error list).

How do I enable BMS control of the Watts tekmar Snow Melting Control 680?

BV 1 Melt/Stop Request (1 = Melt) and BV 2 Storm/Stop Request (1 = Storm) start a melt or storm cycle from the BMS. BV 3-6 enable or disable idling, storm mode, warm weather shut down and cold weather cut out.

Can the BMS supply sensor values to the Watts tekmar Snow Melting Control 680?

Set BV 0 Outdoor Sensor Enable = 1 so the 680 uses the BAS outdoor temperature written to AV 0 (-67 to 149 °F); with 0 it measures its own outdoor sensor.

How do I check these points on the real tekmar Snow Melting Control 680?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Watts BACnet points lists

Source: Snow Melting Control 680 BAS Integration Manual · 680_B · rev. 03/20. Object names, instances and units are reproduced as published; descriptions are our own.