Digital water mixing station (DHW tempering valve) · BACnet points list
Watts IntelliStation 2 digital mixing station BACnet points list
Updated 4 November 2026
IntelliStation 2 is a Powers (Watts) electronic DHW mixing station. Its control speaks BACnet MS/TP or BACnet IP (or Modbus RTU), chosen in the BAS menu. The object list is short: temperatures, pressures, flows, valve position, energy, an error code, recirculation pump and isolation valve status, and one writable mixed outlet setpoint.
This page lists 18 BACnet objects for the Watts IntelliStation 2 digital mixing station — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Watts’s own free documentation, linked below.
- Manufacturer
- Watts
- Model
- IntelliStation 2 digital mixing station
- Equipment
- Digital water mixing station (DHW tempering valve)
- Equipment type
- Valves & actuators
- BACnet objects
- 18 (1 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Application software J1314 (per the PICS)
- Also known as
- Powers IntelliStation 2, IntelliStation 2S, IntelliStation2, 116401
Reference only, provided as-is: verify against Watts’s current documentation and the live device before use. Not official Watts information. Terms of use.
BMS integration notes: Watts IntelliStation 2 digital mixing station
Pick BACnet MS/TP or BACnet IP as BAS Type at the control and set the device ID (plus MAC and baud for MS/TP, or port and BBMD for IP). Set Remote Setpoint Max at the control to cap what the BMS may write, then write AV 0 for the outlet temperature. Everything else is read-only monitoring.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 0 | Mixed Outlet Setpoint | Mixed outlet setpoint, °F (capped by AI 10) | Write |
| AI 0 | Mixed Outlet Temperature | Mixed outlet temperature, °F | Read |
| AI 1 | Recirc Return Temperature | Recirculation return temperature, °F | Read |
| AI 11 | Valve Position | Mixing valve position, % | Read |
| BI 0 | Recirc Pump 1 | Recirculation pump 1 running | Read |
| AI 13 | Error Code | Active error or alert code | Read |
Enable & remote start
No separate enable point. Selecting a BAS Type in the BAS menu exposes the Remote Setpoint Max setting, which caps the setpoint the BMS can write to AV 0.
Network setup
- BAS Type: Off, Modbus RTU, BACnet MS/TP or BACnet IP.
- Device ID 0-4194302 (both transports).
- MS/TP: MAC 0-127, baud 9600-115200, plus a user-defined BACnet name.
- IP: UDP port 0-65535; optional BBMD foreign device registration with IP, port and time.
- DeviceCommunicationControl password is Powers1164.
Watch out for
- The manual warns that outlet temperatures above 110 °F need point-of-use mixing valves; set Remote Setpoint Max with that in mind.
- No segmentation support per the PICS.
Watts IntelliStation 2 digital mixing station BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 0 | Mixed Outlet Temperature | Mixed outlet temperature | °F | Read | |
| AImin | 1 | Recirc Return Temperature | Recirculation return temperature | °F | Read | |
| AI | 2 | Hot Inlet Temperature | Hot inlet temperature | °F | Read | |
| AI | 3 | Cold Inlet Temperature | Cold inlet temperature | °F | Read | |
| AI | 4 | Mixed Outlet Pressure | Mixed outlet pressure | psi | Read | |
| AI | 5 | Recirc Return Pressure | Recirculation return pressure | psi | Read | |
| AI | 6 | Hot Inlet Pressure | Hot inlet pressure | psi | Read | |
| AI | 7 | Cold Inlet Pressure | Cold inlet pressure | psi | Read | |
| AI | 8 | Mixed Outlet Flow | Mixed outlet flow | GPM | Read | |
| AI | 9 | Recirc Return Flow | Recirculation return flow | GPM | Read | |
| AI | 10 | Remote Setpoint Max | Highest mixed outlet target the BAS may set | °F | Read | |
| AImin | 11 | Valve Position | Mixing valve position | % | Read | |
| AI | 12 | Energy Usage | Totalized energy | therms | Read | |
| AImin | 13 | Error Code | Error or alert code (see error list) | Read | ||
| AVmin | 0 | Mixed Outlet Setpoint | Mixed outlet setpoint, 60 °F up to Remote Setpoint Max | °F | Write | |
| BImin | 0 | Recirc Pump 1 | Recirculation pump 1 status | Read | 0=Off, 1=On | |
| BI | 1 | Recirc Pump 2 | Recirculation pump 2 status | Read | 0=Off, 1=On | |
| BI | 2 | Isolation Valve | Isolation valve status | Read | 0=Closed, 1=Open |
No points match these filters.
Object ID lookup: Watts IntelliStation 2 digital mixing station point IDs by name
AI0Mixed Outlet TemperatureAI1Recirc Return TemperatureAI2Hot Inlet TemperatureAI3Cold Inlet TemperatureAI4Mixed Outlet PressureAI5Recirc Return PressureAI6Hot Inlet PressureAI7Cold Inlet PressureAI8Mixed Outlet FlowAI9Recirc Return FlowAI10Remote Setpoint MaxAI11Valve PositionAI12Energy UsageAI13Error CodeAV0Mixed Outlet SetpointBI0Recirc Pump 1BI1Recirc Pump 2BI2Isolation Valve
Integration notes
- Published under the Powers brand (Watts); the PICS lists vendor Powers Control Systems Ltd., vendor ID 834.
- Pressure, flow and some temperature points need the matching sensor options fitted.
- AV 0 is limited to 60 °F up to the Remote Setpoint Max set at the control (read back on AI 10).
- AI 13 returns a numeric error/alert code; the manual lists codes for sensor, pressure, flow, network and Wi-Fi faults.
- Temperatures are in °F.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IntelliStation 2 digital mixing station and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Watts IntelliStation 2 digital mixing station
How many BACnet points does the Watts IntelliStation 2 digital mixing station have?
This list has 18 BACnet objects: 14 analog inputs, 1 analog value, 3 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Watts IntelliStation 2 digital mixing station BACnet points are writable?
1 of the 18 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Watts IntelliStation 2 digital mixing station BACnet documentation?
The source is IntelliStation 2 Installation, Operation, and Maintenance Manual (IOM-P-IntelliStation2), revision 2526, published free by Watts at https://www.watts.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/650378-source/638962952400000000/iom-p-intellistation2-2414.pdf.
What are the minimum BACnet points to integrate the Watts IntelliStation 2 digital mixing station?
Start with AV 0 Mixed Outlet Setpoint (Mixed outlet setpoint, °F (capped by AI 10)); AI 0 Mixed Outlet Temperature (Mixed outlet temperature, °F); AI 1 Recirc Return Temperature (Recirculation return temperature, °F); AI 11 Valve Position (Mixing valve position, %); BI 0 Recirc Pump 1 (Recirculation pump 1 running); AI 13 Error Code (Active error or alert code).
How do I enable BMS control of the Watts IntelliStation 2 digital mixing station?
No separate enable point. Selecting a BAS Type in the BAS menu exposes the Remote Setpoint Max setting, which caps the setpoint the BMS can write to AV 0.
How do I check these points on the real IntelliStation 2 digital mixing station?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Watts BACnet points lists
- Snow/ice sensor interface (BAS-run snow melting)
Watts tekmar BACnet Snow/Ice Sensor Interface 681
tekmar (Watts) 681 interface that connects a snow/ice sensor and slab and outdoor sensors to a building automation system for snow melting.
Also known as: tekmar 681, 681, BACnet Snow/Ice Sensor Interface, tekmar snow ice sensor interface, J1297 - Multi-boiler plant controller (boiler staging)
Watts tekmar Boiler Control 284
tekmar Boiler Control 284, which stages and modulates up to four boilers for heating and DHW loads.
Also known as: tekmar 284, Boiler Control 284, 284, tekmar multi-staging 284 - Multi-boiler plant controller
Watts tekmar Smart Boiler Control 294BAC
tekmar (Watts) Smart Boiler Control 294BAC, a staging and reset control for plants of up to 16 boilers with DHW, connected natively over BACnet IP or BACnet MS/TP.
Also known as: tekmar 294BAC, 294BAC, tekmar 294, Smart Boiler Control 294, J1308 - Snow melting controller (boiler-fed slab)
Watts tekmar Snow Melting Control 680
tekmar (Watts) Snow Melting Control 680 for hydronic or electric snow melting slabs, with boiler and mixing outputs.
Also known as: tekmar 680, Snow Melting Control 680, 680, tekmar snow melt 680, J1243F
Source: IntelliStation 2 Installation, Operation, and Maintenance Manual · IOM-P-IntelliStation2 · rev. 2526. Object names, instances and units are reproduced as published; descriptions are our own.