Digital water mixing station (DHW tempering valve) · BACnet points list

Watts IntelliStation 2 digital mixing station BACnet points list

Updated 4 November 2026

Short answer

IntelliStation 2 is a Powers (Watts) electronic DHW mixing station. Its control speaks BACnet MS/TP or BACnet IP (or Modbus RTU), chosen in the BAS menu. The object list is short: temperatures, pressures, flows, valve position, energy, an error code, recirculation pump and isolation valve status, and one writable mixed outlet setpoint.

This page lists 18 BACnet objects for the Watts IntelliStation 2 digital mixing station — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Watts’s own free documentation, linked below.

Manufacturer
Watts
Model
IntelliStation 2 digital mixing station
Equipment
Digital water mixing station (DHW tempering valve)
Equipment type
Valves & actuators
BACnet objects
18 (1 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Application software J1314 (per the PICS)
Also known as
Powers IntelliStation 2, IntelliStation 2S, IntelliStation2, 116401
Source document
IntelliStation 2 Installation, Operation, and Maintenance Manual · IOM-P-IntelliStation2 · rev. 2526
Download CSV 18 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Watts’s current documentation and the live device before use. Not official Watts information. Terms of use.

BMS integration notes: Watts IntelliStation 2 digital mixing station

Integration in brief

Pick BACnet MS/TP or BACnet IP as BAS Type at the control and set the device ID (plus MAC and baud for MS/TP, or port and BBMD for IP). Set Remote Setpoint Max at the control to cap what the BMS may write, then write AV 0 for the outlet temperature. Everything else is read-only monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 0Mixed Outlet SetpointMixed outlet setpoint, °F (capped by AI 10)Write
AI 0Mixed Outlet TemperatureMixed outlet temperature, °FRead
AI 1Recirc Return TemperatureRecirculation return temperature, °FRead
AI 11Valve PositionMixing valve position, %Read
BI 0Recirc Pump 1Recirculation pump 1 runningRead
AI 13Error CodeActive error or alert codeRead

Enable & remote start

No separate enable point. Selecting a BAS Type in the BAS menu exposes the Remote Setpoint Max setting, which caps the setpoint the BMS can write to AV 0.

Network setup

Watch out for

Watts IntelliStation 2 digital mixing station BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

18 of 18 shown
Type
Binary
Access
Show
Watts IntelliStation 2 digital mixing station BACnet Points List
DescriptionStates
AImin0Mixed Outlet TemperatureMixed outlet temperature°FRead
AImin1Recirc Return TemperatureRecirculation return temperature°FRead
AI2Hot Inlet TemperatureHot inlet temperature°FRead
AI3Cold Inlet TemperatureCold inlet temperature°FRead
AI4Mixed Outlet PressureMixed outlet pressurepsiRead
AI5Recirc Return PressureRecirculation return pressurepsiRead
AI6Hot Inlet PressureHot inlet pressurepsiRead
AI7Cold Inlet PressureCold inlet pressurepsiRead
AI8Mixed Outlet FlowMixed outlet flowGPMRead
AI9Recirc Return FlowRecirculation return flowGPMRead
AI10Remote Setpoint MaxHighest mixed outlet target the BAS may set°FRead
AImin11Valve PositionMixing valve position%Read
AI12Energy UsageTotalized energythermsRead
AImin13Error CodeError or alert code (see error list)Read
AVmin0Mixed Outlet SetpointMixed outlet setpoint, 60 °F up to Remote Setpoint Max°FWrite
BImin0Recirc Pump 1Recirculation pump 1 statusRead0=Off, 1=On
BI1Recirc Pump 2Recirculation pump 2 statusRead0=Off, 1=On
BI2Isolation ValveIsolation valve statusRead0=Closed, 1=Open
Object ID lookup: Watts IntelliStation 2 digital mixing station point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IntelliStation 2 digital mixing station and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Watts IntelliStation 2 digital mixing station

How many BACnet points does the Watts IntelliStation 2 digital mixing station have?

This list has 18 BACnet objects: 14 analog inputs, 1 analog value, 3 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Watts IntelliStation 2 digital mixing station BACnet points are writable?

1 of the 18 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Watts IntelliStation 2 digital mixing station BACnet documentation?

The source is IntelliStation 2 Installation, Operation, and Maintenance Manual (IOM-P-IntelliStation2), revision 2526, published free by Watts at https://www.watts.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/650378-source/638962952400000000/iom-p-intellistation2-2414.pdf.

What are the minimum BACnet points to integrate the Watts IntelliStation 2 digital mixing station?

Start with AV 0 Mixed Outlet Setpoint (Mixed outlet setpoint, °F (capped by AI 10)); AI 0 Mixed Outlet Temperature (Mixed outlet temperature, °F); AI 1 Recirc Return Temperature (Recirculation return temperature, °F); AI 11 Valve Position (Mixing valve position, %); BI 0 Recirc Pump 1 (Recirculation pump 1 running); AI 13 Error Code (Active error or alert code).

How do I enable BMS control of the Watts IntelliStation 2 digital mixing station?

No separate enable point. Selecting a BAS Type in the BAS menu exposes the Remote Setpoint Max setting, which caps the setpoint the BMS can write to AV 0.

How do I check these points on the real IntelliStation 2 digital mixing station?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Watts BACnet points lists

Source: IntelliStation 2 Installation, Operation, and Maintenance Manual · IOM-P-IntelliStation2 · rev. 2526. Object names, instances and units are reproduced as published; descriptions are our own.