Watts tekmar Boiler Control 284 BACnet points list
Updated 4 November 2026
The tekmar 284 boiler staging control has BACnet IP built in on an RJ45 port (it can be switched to Modbus over RS-485 instead). In BAS application mode the BMS sends the target temperature, a setpoint call and pump requests; in the other modes the BMS can monitor and adjust a few settings. Per-boiler objects repeat for boilers 1-4.
This page lists 72 BACnet objects for the Watts tekmar Boiler Control 284 — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Watts’s own free documentation, linked below.
- Manufacturer
- Watts
- Model
- tekmar Boiler Control 284
- Equipment
- Multi-boiler plant controller (boiler staging)
- Equipment type
- Boilers & water heaters
- BACnet objects
- 72 (13 writable)
- Transport
- BACnet IP
- Firmware
- Application software J1220x (per the PICS)
- Default device instance
- 0
- Also known as
- tekmar 284, Boiler Control 284, 284, tekmar multi-staging 284
Reference only, provided as-is: verify against Watts’s current documentation and the live device before use. Not official Watts information. Terms of use.
BMS integration notes: Watts tekmar Boiler Control 284
Set the 284 BAS Type to BACnet IP and give it a device ID and IP settings in the BAS menu. For full control put the 284 in BAS application mode, then write AV 0 setpoint and BV 0 setpoint call, plus BV 1 / BO 0 pump requests. In the other application modes, turn BAS Monitor on to read values and adjust the room and outdoor design settings.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 0 | BAS SETP CALL | Setpoint call from the BMS (1 = call for heat) | Write |
| BV 1 | BAS PRIM PMP REQ | Primary pump request (1 = on) | Write |
| AV 0 | SETPOINT | Target supply temperature, 60-225 °F | Write |
| BI 6 | HEAT CALL | Heat call active | Read |
| AI 0 | Boil TARG | Target temperature in use, °F | Read |
| AI 3 | Boil SUP | Boiler plant supply temperature, °F | Read |
| AI 4 | Boil RET | Boiler plant return temperature, °F | Read |
| AI 15 | ERROR | Error code; 0 = no error | Read |
Enable & remote start
BMS control needs Application Mode = BAS on the 284; then AV 0 sets the target temperature and BV 0 makes the setpoint call, BV 1 requests the primary pump(s) and BO 0 the DHW pump. In RSET, SETP, DDHW or EMS mode the BMS gets monitoring and setting adjustment only, and BAS Monitor must be set ON (Advanced access).
Sensors & values from the BMS
AV 5 takes an outdoor air temperature from the BAS; write -85 °F to mean no BAS sensor.
Network setup
- BAS Type = BACn selects BACnet IP over the RJ45 port; MODB switches to Modbus over RS-485.
- Device ID is entered as four number groups (0-4, 0-99, 0-99, 0-99); default 0,0,0,0.
- DHCP is ON by default; with DHCP off the default IP is 192.168.0.200, gateway 192.168.0.1, subnet 255.255.255.0.
- UDP port default 0xBAC0 (47808); BBMD foreign registration is set with BBMD TIME, IP and port.
- The BAS menu items need Advanced access, which requires the lock/unlock switch beside the display set to unlock.
- DeviceCommunicationControl password is tekmar.
Watch out for
- ENABLE B1-B4 (BV 2-5) are 0 = enable, 1 = disable.
- The PICS lists no segmentation support.
- Ethernet cable runs are limited to 150 ft for CAT-5E or 300 ft for CAT-6.
Watts tekmar Boiler Control 284 BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 0 | Boil TARG | Boiler target temperature | °F | Read | |
| AI | 1 | Boil MIN | Minimum boiler target temperature | °F | Read | |
| AI | 2 | Boil MAX | Maximum boiler target temperature | °F | Read | |
| AImin | 3 | Boil SUP | Boiler supply temperature | °F | Read | |
| AImin | 4 | Boil RET | Boiler return temperature | °F | Read | |
| AI | 5 | OUTDOOR | Outdoor air temperature | °F | Read | |
| AI | 6 | DHW | DHW tank temperature | °F | Read | |
| AI | 7 | VENT | Vent temperature | °F | Read | |
| AI | 8 | Boil INLET | Boiler inlet temperature | °F | Read | |
| AI | 9 | FLOW RATE | Flow rate | GPM | Read | |
| AI | 10 | ENERGY | Energy usage | therms | Read | |
| AI | 11 | PRESSURE | System pressure | psi | Read | |
| AI | 12 | PRIM P1 RT | Primary pump 1 running time | h | Read | |
| AI | 13 | PRIM P2 RT | Primary pump 2 running time | h | Read | |
| AI | 14 | DHW P RT | DHW pump running time | h | Read | |
| AImin | 15 | ERROR | Current error code (see error list) | Read | ||
| AI | 16 | Boil 1 TYPE | Boiler 1 type | Read | 0=MOD, 1=1STG, 2=2STG, 3=EMS | |
| AI | 17 | Boil 1 OUT | Boiler 1 outlet temperature | °F | Read | |
| AI | 18 | Boil 1 MOD | Boiler 1 modulating output | % | Read | |
| AI | 19 | BURNER 1 | Boiler 1 running time | h | Read | |
| AI | 20 | CYCLES 1 | Boiler 1 cycles | Read | ||
| AI | 21 | PUMP 1 RT | Boiler 1 pump running time | h | Read | |
| AI | 22 | Boil 2 TYPE | Boiler 2 type | Read | 0=MOD, 1=1STG, 2=2STG, 3=EMS | |
| AI | 23 | Boil 2 OUT | Boiler 2 outlet temperature | °F | Read | |
| AI | 24 | Boil 2 MOD | Boiler 2 modulating output | % | Read | |
| AI | 25 | BURNER 2 | Boiler 2 running time | h | Read | |
| AI | 26 | CYCLES 2 | Boiler 2 cycles | Read | ||
| AI | 27 | PUMP 2 RT | Boiler 2 pump running time | h | Read | |
| AI | 28 | Boil 3 TYPE | Boiler 3 type | Read | 0=MOD, 1=1STG, 2=2STG, 3=EMS | |
| AI | 29 | Boil 3 OUT | Boiler 3 outlet temperature | °F | Read | |
| AI | 30 | Boil 3 MOD | Boiler 3 modulating output | % | Read | |
| AI | 31 | BURNER 3 | Boiler 3 running time | h | Read | |
| AI | 32 | CYCLES 3 | Boiler 3 cycles | Read | ||
| AI | 33 | PUMP 3 RT | Boiler 3 pump running time | h | Read | |
| AI | 34 | Boil 4 TYPE | Boiler 4 type | Read | 0=MOD, 1=1STG, 2=2STG, 3=EMS | |
| AI | 35 | Boil 4 OUT | Boiler 4 outlet temperature | °F | Read | |
| AI | 36 | Boil 4 MOD | Boiler 4 modulating output | % | Read | |
| AI | 37 | BURNER 4 | Boiler 4 running time | h | Read | |
| AI | 38 | CYCLES 4 | Boiler 4 cycles | Read | ||
| AI | 39 | PUMP 4 RT | Boiler 4 pump running time | h | Read | |
| AVmin | 0 | SETPOINT | BAS setpoint temperature, 60-225 °F | °F | Write | |
| AV | 1 | ROOM Occ | Room occupied temperature | °F | Write | |
| AV | 2 | ROOM UnOcc | Room unoccupied temperature | °F | Write | |
| AV | 3 | OUT DSGN | Outdoor design temperature | °F | Write | |
| AV | 4 | TERMINAL | Terminal unit type | Write | 0=HRF1, 1=HRF2, 2=CONV, 3=COIL, 4=RAD, 5=BASE | |
| AV | 5 | OUTDOOR | Outdoor air temperature from the BAS (-85 = no BAS sensor) | °F | Write | |
| BI | 0 | PRIM P1 | Primary pump 1 status | Read | 0=Off, 1=On | |
| BI | 1 | PRIM P2 | Primary pump 2 status | Read | 0=Off, 1=On | |
| BI | 2 | DHW PUMP | DHW pump status | Read | 0=Off, 1=On | |
| BI | 3 | SETBACK | Setback status | Read | 0=Off, 1=On | |
| BI | 4 | AUX RLY | Auxiliary relay status | Read | 0=Off, 1=On | |
| BI | 5 | ALERT RLY | Alert relay status | Read | 0=Off, 1=On | |
| BImin | 6 | HEAT CALL | Heat call status | Read | 0=Off, 1=On | |
| BI | 7 | DHW CALL | DHW call status | Read | 0=Off, 1=On | |
| BI | 8 | SETP CALL | Setpoint call status | Read | 0=Off, 1=On | |
| BI | 9 | FLOW PROOF | Flow proof call status | Read | 0=Off, 1=On | |
| BI | 10 | CA PROOF | Combustion air proof call status | Read | 0=Off, 1=On | |
| BI | 11 | CONDENSE 1 | Boiler 1 condensing | Read | 0=No, 1=Yes | |
| BI | 12 | B1 PUMP | Boiler 1 pump status | Read | 0=Off, 1=On | |
| BI | 13 | CONDENSE 2 | Boiler 2 condensing | Read | 0=No, 1=Yes | |
| BI | 14 | B2 PUMP | Boiler 2 pump status | Read | 0=Off, 1=On | |
| BI | 15 | CONDENSE 3 | Boiler 3 condensing | Read | 0=No, 1=Yes | |
| BI | 16 | B3 PUMP | Boiler 3 pump status | Read | 0=Off, 1=On | |
| BI | 17 | CONDENSE 4 | Boiler 4 condensing | Read | 0=No, 1=Yes | |
| BI | 18 | B4 PUMP | Boiler 4 pump status | Read | 0=Off, 1=On | |
| BO | 0 | DHW PUMP | DHW pump request from the BAS | Write | 0=Off, 1=On | |
| BVmin | 0 | BAS SETP CALL | Setpoint call from the BAS | Write | 0=Off, 1=On | |
| BVmin | 1 | BAS PRIM PMP REQ | Primary pump request from the BAS | Write | 0=Off, 1=On | |
| BV | 2 | ENABLE B1 | Enable / disable boiler 1 | Write | 0=Enable, 1=Disable | |
| BV | 3 | ENABLE B2 | Enable / disable boiler 2 | Write | 0=Enable, 1=Disable | |
| BV | 4 | ENABLE B3 | Enable / disable boiler 3 | Write | 0=Enable, 1=Disable | |
| BV | 5 | ENABLE B4 | Enable / disable boiler 4 | Write | 0=Enable, 1=Disable |
No points match these filters.
Object ID lookup: Watts tekmar Boiler Control 284 point IDs by name
AI0Boil TARGAI1Boil MINAI2Boil MAXAI3Boil SUPAI4Boil RETAI5OUTDOORAI6DHWAI7VENTAI8Boil INLETAI9FLOW RATEAI10ENERGYAI11PRESSUREAI12PRIM P1 RTAI13PRIM P2 RTAI14DHW P RTAI15ERRORAI16Boil 1 TYPEAI17Boil 1 OUTAI18Boil 1 MODAI19BURNER 1AI20CYCLES 1AI21PUMP 1 RTAI22Boil 2 TYPEAI23Boil 2 OUTAI24Boil 2 MODAI25BURNER 2AI26CYCLES 2AI27PUMP 2 RTAI28Boil 3 TYPEAI29Boil 3 OUTAI30Boil 3 MODAI31BURNER 3AI32CYCLES 3AI33PUMP 3 RTAI34Boil 4 TYPEAI35Boil 4 OUTAI36Boil 4 MODAI37BURNER 4AI38CYCLES 4AI39PUMP 4 RTAV0SETPOINTAV1ROOM OccAV2ROOM UnOccAV3OUT DSGNAV4TERMINALAV5OUTDOORBI0PRIM P1BI1PRIM P2BI2DHW PUMPBI3SETBACKBI4AUX RLYBI5ALERT RLYBI6HEAT CALLBI7DHW CALLBI8SETP CALLBI9FLOW PROOFBI10CA PROOFBI11CONDENSE 1BI12B1 PUMPBI13CONDENSE 2BI14B2 PUMPBI15CONDENSE 3BI16B3 PUMPBI17CONDENSE 4BI18B4 PUMPBO0DHW PUMPBV0BAS SETP CALLBV1BAS PRIM PMP REQBV2ENABLE B1BV3ENABLE B2BV4ENABLE B3BV5ENABLE B4
Integration notes
- The manual prints the per-boiler objects once with an (n) placeholder (e.g. "Boil (n) TYPE", "B(n) PUMP", "ENABLE B(n)") and lists the instance for each of boilers 1-4; names here are written with (n) replaced by the boiler number.
- AI 15 ERROR returns a numeric code; the manual lists 0 = no error and codes for EEPROM, sensor, flow/combustion-air proof and tN4 bus faults.
- BV 2-5 use inverted logic: 0 = enable, 1 = disable.
- AV 5 accepts -85 °F to mean no BAS outdoor sensor.
- Temperatures are in °F.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the tekmar Boiler Control 284 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Watts tekmar Boiler Control 284
How many BACnet points does the Watts tekmar Boiler Control 284 have?
This list has 72 BACnet objects: 40 analog inputs, 6 analog values, 19 binary inputs, 1 binary output, 6 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Watts tekmar Boiler Control 284 BACnet points are writable?
13 of the 72 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Watts tekmar Boiler Control 284 BACnet documentation?
The source is Boiler Control 284 BAS Integration Manual (284_B), revision 08/14, published free by Watts at https://www.watts.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/42772-source/638820695650000000/284-b-04.pdf.
What are the minimum BACnet points to integrate the Watts tekmar Boiler Control 284?
Start with BV 0 BAS SETP CALL (Setpoint call from the BMS (1 = call for heat)); BV 1 BAS PRIM PMP REQ (Primary pump request (1 = on)); AV 0 SETPOINT (Target supply temperature, 60-225 °F); BI 6 HEAT CALL (Heat call active); AI 0 Boil TARG (Target temperature in use, °F); AI 3 Boil SUP (Boiler plant supply temperature, °F); AI 4 Boil RET (Boiler plant return temperature, °F); AI 15 ERROR (Error code; 0 = no error).
How do I enable BMS control of the Watts tekmar Boiler Control 284?
BMS control needs Application Mode = BAS on the 284; then AV 0 sets the target temperature and BV 0 makes the setpoint call, BV 1 requests the primary pump(s) and BO 0 the DHW pump. In RSET, SETP, DDHW or EMS mode the BMS gets monitoring and setting adjustment only, and BAS Monitor must be set ON (Advanced access).
Can the BMS supply sensor values to the Watts tekmar Boiler Control 284?
AV 5 takes an outdoor air temperature from the BAS; write -85 °F to mean no BAS sensor.
How do I check these points on the real tekmar Boiler Control 284?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Watts BACnet points lists
- Digital water mixing station (DHW tempering valve)
Watts IntelliStation 2 digital mixing station
Powers IntelliStation 2 and 2S digital hot-water mixing stations for building domestic hot water systems.
Also known as: Powers IntelliStation 2, IntelliStation 2S, IntelliStation2, 116401 - Snow/ice sensor interface (BAS-run snow melting)
Watts tekmar BACnet Snow/Ice Sensor Interface 681
tekmar (Watts) 681 interface that connects a snow/ice sensor and slab and outdoor sensors to a building automation system for snow melting.
Also known as: tekmar 681, 681, BACnet Snow/Ice Sensor Interface, tekmar snow ice sensor interface, J1297 - Multi-boiler plant controller
Watts tekmar Smart Boiler Control 294BAC
tekmar (Watts) Smart Boiler Control 294BAC, a staging and reset control for plants of up to 16 boilers with DHW, connected natively over BACnet IP or BACnet MS/TP.
Also known as: tekmar 294BAC, 294BAC, tekmar 294, Smart Boiler Control 294, J1308 - Snow melting controller (boiler-fed slab)
Watts tekmar Snow Melting Control 680
tekmar (Watts) Snow Melting Control 680 for hydronic or electric snow melting slabs, with boiler and mixing outputs.
Also known as: tekmar 680, Snow Melting Control 680, 680, tekmar snow melt 680, J1243F
Source: Boiler Control 284 BAS Integration Manual · 284_B · rev. 08/14. Object names, instances and units are reproduced as published; descriptions are our own.