Multi-boiler plant controller (boiler staging) · BACnet points list

Watts tekmar Boiler Control 284 BACnet points list

Updated 4 November 2026

Short answer

The tekmar 284 boiler staging control has BACnet IP built in on an RJ45 port (it can be switched to Modbus over RS-485 instead). In BAS application mode the BMS sends the target temperature, a setpoint call and pump requests; in the other modes the BMS can monitor and adjust a few settings. Per-boiler objects repeat for boilers 1-4.

This page lists 72 BACnet objects for the Watts tekmar Boiler Control 284 — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Watts’s own free documentation, linked below.

Manufacturer
Watts
Model
tekmar Boiler Control 284
Equipment
Multi-boiler plant controller (boiler staging)
Equipment type
Boilers & water heaters
BACnet objects
72 (13 writable)
Transport
BACnet IP
Firmware
Application software J1220x (per the PICS)
Default device instance
0
Also known as
tekmar 284, Boiler Control 284, 284, tekmar multi-staging 284
Source document
Boiler Control 284 BAS Integration Manual · 284_B · rev. 08/14
Download CSV 72 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Watts’s current documentation and the live device before use. Not official Watts information. Terms of use.

BMS integration notes: Watts tekmar Boiler Control 284

Integration in brief

Set the 284 BAS Type to BACnet IP and give it a device ID and IP settings in the BAS menu. For full control put the 284 in BAS application mode, then write AV 0 setpoint and BV 0 setpoint call, plus BV 1 / BO 0 pump requests. In the other application modes, turn BAS Monitor on to read values and adjust the room and outdoor design settings.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0BAS SETP CALLSetpoint call from the BMS (1 = call for heat)Write
BV 1BAS PRIM PMP REQPrimary pump request (1 = on)Write
AV 0SETPOINTTarget supply temperature, 60-225 °FWrite
BI 6HEAT CALLHeat call activeRead
AI 0Boil TARGTarget temperature in use, °FRead
AI 3Boil SUPBoiler plant supply temperature, °FRead
AI 4Boil RETBoiler plant return temperature, °FRead
AI 15ERRORError code; 0 = no errorRead

Enable & remote start

BMS control needs Application Mode = BAS on the 284; then AV 0 sets the target temperature and BV 0 makes the setpoint call, BV 1 requests the primary pump(s) and BO 0 the DHW pump. In RSET, SETP, DDHW or EMS mode the BMS gets monitoring and setting adjustment only, and BAS Monitor must be set ON (Advanced access).

Sensors & values from the BMS

AV 5 takes an outdoor air temperature from the BAS; write -85 °F to mean no BAS sensor.

Network setup

Watch out for

Watts tekmar Boiler Control 284 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

72 of 72 shown
Type
Access
Show
Watts tekmar Boiler Control 284 BACnet Points List
DescriptionStates
AImin0Boil TARGBoiler target temperature°FRead
AI1Boil MINMinimum boiler target temperature°FRead
AI2Boil MAXMaximum boiler target temperature°FRead
AImin3Boil SUPBoiler supply temperature°FRead
AImin4Boil RETBoiler return temperature°FRead
AI5OUTDOOROutdoor air temperature°FRead
AI6DHWDHW tank temperature°FRead
AI7VENTVent temperature°FRead
AI8Boil INLETBoiler inlet temperature°FRead
AI9FLOW RATEFlow rateGPMRead
AI10ENERGYEnergy usagethermsRead
AI11PRESSURESystem pressurepsiRead
AI12PRIM P1 RTPrimary pump 1 running timehRead
AI13PRIM P2 RTPrimary pump 2 running timehRead
AI14DHW P RTDHW pump running timehRead
AImin15ERRORCurrent error code (see error list)Read
AI16Boil 1 TYPEBoiler 1 typeRead0=MOD, 1=1STG, 2=2STG, 3=EMS
AI17Boil 1 OUTBoiler 1 outlet temperature°FRead
AI18Boil 1 MODBoiler 1 modulating output%Read
AI19BURNER 1Boiler 1 running timehRead
AI20CYCLES 1Boiler 1 cyclesRead
AI21PUMP 1 RTBoiler 1 pump running timehRead
AI22Boil 2 TYPEBoiler 2 typeRead0=MOD, 1=1STG, 2=2STG, 3=EMS
AI23Boil 2 OUTBoiler 2 outlet temperature°FRead
AI24Boil 2 MODBoiler 2 modulating output%Read
AI25BURNER 2Boiler 2 running timehRead
AI26CYCLES 2Boiler 2 cyclesRead
AI27PUMP 2 RTBoiler 2 pump running timehRead
AI28Boil 3 TYPEBoiler 3 typeRead0=MOD, 1=1STG, 2=2STG, 3=EMS
AI29Boil 3 OUTBoiler 3 outlet temperature°FRead
AI30Boil 3 MODBoiler 3 modulating output%Read
AI31BURNER 3Boiler 3 running timehRead
AI32CYCLES 3Boiler 3 cyclesRead
AI33PUMP 3 RTBoiler 3 pump running timehRead
AI34Boil 4 TYPEBoiler 4 typeRead0=MOD, 1=1STG, 2=2STG, 3=EMS
AI35Boil 4 OUTBoiler 4 outlet temperature°FRead
AI36Boil 4 MODBoiler 4 modulating output%Read
AI37BURNER 4Boiler 4 running timehRead
AI38CYCLES 4Boiler 4 cyclesRead
AI39PUMP 4 RTBoiler 4 pump running timehRead
AVmin0SETPOINTBAS setpoint temperature, 60-225 °F°FWrite
AV1ROOM OccRoom occupied temperature°FWrite
AV2ROOM UnOccRoom unoccupied temperature°FWrite
AV3OUT DSGNOutdoor design temperature°FWrite
AV4TERMINALTerminal unit typeWrite0=HRF1, 1=HRF2, 2=CONV, 3=COIL, 4=RAD, 5=BASE
AV5OUTDOOROutdoor air temperature from the BAS (-85 = no BAS sensor)°FWrite
BI0PRIM P1Primary pump 1 statusRead0=Off, 1=On
BI1PRIM P2Primary pump 2 statusRead0=Off, 1=On
BI2DHW PUMPDHW pump statusRead0=Off, 1=On
BI3SETBACKSetback statusRead0=Off, 1=On
BI4AUX RLYAuxiliary relay statusRead0=Off, 1=On
BI5ALERT RLYAlert relay statusRead0=Off, 1=On
BImin6HEAT CALLHeat call statusRead0=Off, 1=On
BI7DHW CALLDHW call statusRead0=Off, 1=On
BI8SETP CALLSetpoint call statusRead0=Off, 1=On
BI9FLOW PROOFFlow proof call statusRead0=Off, 1=On
BI10CA PROOFCombustion air proof call statusRead0=Off, 1=On
BI11CONDENSE 1Boiler 1 condensingRead0=No, 1=Yes
BI12B1 PUMPBoiler 1 pump statusRead0=Off, 1=On
BI13CONDENSE 2Boiler 2 condensingRead0=No, 1=Yes
BI14B2 PUMPBoiler 2 pump statusRead0=Off, 1=On
BI15CONDENSE 3Boiler 3 condensingRead0=No, 1=Yes
BI16B3 PUMPBoiler 3 pump statusRead0=Off, 1=On
BI17CONDENSE 4Boiler 4 condensingRead0=No, 1=Yes
BI18B4 PUMPBoiler 4 pump statusRead0=Off, 1=On
BO0DHW PUMPDHW pump request from the BASWrite0=Off, 1=On
BVmin0BAS SETP CALLSetpoint call from the BASWrite0=Off, 1=On
BVmin1BAS PRIM PMP REQPrimary pump request from the BASWrite0=Off, 1=On
BV2ENABLE B1Enable / disable boiler 1Write0=Enable, 1=Disable
BV3ENABLE B2Enable / disable boiler 2Write0=Enable, 1=Disable
BV4ENABLE B3Enable / disable boiler 3Write0=Enable, 1=Disable
BV5ENABLE B4Enable / disable boiler 4Write0=Enable, 1=Disable
Object ID lookup: Watts tekmar Boiler Control 284 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the tekmar Boiler Control 284 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Watts tekmar Boiler Control 284

How many BACnet points does the Watts tekmar Boiler Control 284 have?

This list has 72 BACnet objects: 40 analog inputs, 6 analog values, 19 binary inputs, 1 binary output, 6 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Watts tekmar Boiler Control 284 BACnet points are writable?

13 of the 72 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Watts tekmar Boiler Control 284 BACnet documentation?

The source is Boiler Control 284 BAS Integration Manual (284_B), revision 08/14, published free by Watts at https://www.watts.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/42772-source/638820695650000000/284-b-04.pdf.

What are the minimum BACnet points to integrate the Watts tekmar Boiler Control 284?

Start with BV 0 BAS SETP CALL (Setpoint call from the BMS (1 = call for heat)); BV 1 BAS PRIM PMP REQ (Primary pump request (1 = on)); AV 0 SETPOINT (Target supply temperature, 60-225 °F); BI 6 HEAT CALL (Heat call active); AI 0 Boil TARG (Target temperature in use, °F); AI 3 Boil SUP (Boiler plant supply temperature, °F); AI 4 Boil RET (Boiler plant return temperature, °F); AI 15 ERROR (Error code; 0 = no error).

How do I enable BMS control of the Watts tekmar Boiler Control 284?

BMS control needs Application Mode = BAS on the 284; then AV 0 sets the target temperature and BV 0 makes the setpoint call, BV 1 requests the primary pump(s) and BO 0 the DHW pump. In RSET, SETP, DDHW or EMS mode the BMS gets monitoring and setting adjustment only, and BAS Monitor must be set ON (Advanced access).

Can the BMS supply sensor values to the Watts tekmar Boiler Control 284?

AV 5 takes an outdoor air temperature from the BAS; write -85 °F to mean no BAS sensor.

How do I check these points on the real tekmar Boiler Control 284?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.