 "manufacturer": "Watts",
 "manufacturer_slug": "watts",
 "model": "tekmar Smart Boiler Control 294BAC",
 "model_slug": "tekmar-smart-boiler-control-294bac",
 "aliases": [
  "tekmar 294BAC",
  "294BAC",
  "tekmar 294",
  "Smart Boiler Control 294",
  "J1308"
 ],
 "equipment_type": "Multi-boiler plant controller",
 "applies_to": "tekmar (Watts) Smart Boiler Control 294BAC, a staging and reset control for plants of up to 16 boilers with DHW, connected natively over BACnet IP or BACnet MS/TP.",
 "summary": "The tekmar 294BAC stages and resets up to 16 boilers and handles domestic hot water. It talks BACnet IP or BACnet MS/TP natively and exposes the plant targets and temperatures, pressure, override state, pump run times, per-boiler firing rate, EMS temperature output, run hours and cycles, per-boiler status and availability, and a large set of writable settings: outdoor temperature from the BAS, room and DHW setpoints, reset curve, boiler limits, staging, alerts and service intervals.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": "J1308, firmware 1.14.0 or later (PICS)",
 "default_device_instance": 1,
 "access_inferred": false,
 "notes": [
  "Native BACnet IP and BACnet MS/TP, vendor ID 585 (tekmar Control Systems), protocol revision 18, device profile B-ASC.",
  "Each boiler uses a block of ten instances: boiler n's objects sit at 100 + 10 x (n - 1) onward (boiler 1 = 100-104 AI, 100-101 AV/BI, 100 BV; boiler 16 = 250-254). All 16 blocks are printed and listed.",
  "Wireless (Nexa) sensors add objects that are not listed here: AI 1000 + 100 x (n - 1) temperature, + 1 humidity, + 2 battery, and BI 1000 + 100 x (n - 1) online status, for sensors n = 1-99 (up to AI/BI 10800).",
  "Most AV and BV objects are installer settings (reset curve, staging, DHW and alert setup) that the control stores; change them deliberately.",
  "Error codes 1-154 are listed in the manual (sensor faults, tN4 and Modbus boiler loss, boiler errors, alerts, wireless and BACnet network errors)."
 ],
 "source": {
  "title": "Smart Boiler Control 294BAC - BAS Integration Manual",
  "doc_number": "IS-T-294BAC 2627",
  "revision_date": "2026",
  "url": "https://www.watts.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/674967-source/is-t-294bac-2627.pdf"
 },
 "integration": {
  "summary": "Set BAS Type to BACnet IP or BACnet MS/TP in the 294BAC BAS menu, give it a Device ID, and discover it. Turn central heating on with BV 0, set occupied/unoccupied room and DHW targets, optionally feed the outdoor temperature from the BAS (AV 0 with AV 33 = BAS), and monitor the boiler target and supply temperatures, plant output, boiler statuses and the error code.",
  "minimum_points": [
   {
    "ref": "BV 0",
    "name": "Central heating",
    "why": "Central heating on/off"
   },
   {
    "ref": "AV 1",
    "name": "Room occupied",
    "why": "Occupied room target, 34.7-100.4 °F"
   },
   {
    "ref": "AV 11",
    "name": "DHW tank occupied",
    "why": "Occupied DHW tank setpoint, 50-230 °F"
   },
   {
    "ref": "AV 0",
    "name": "Outdoor air temperature",
    "why": "Outdoor temperature from the BAS (when AV 33 = BAS)"
   },
   {
    "ref": "AI 1",
    "name": "Boiler target temperature",
    "why": "Plant supply target"
   },
   {
    "ref": "AI 2",
    "name": "Boiler supply temperature",
    "why": "Plant supply temperature"
   },
   {
    "ref": "AI 3",
    "name": "Plant output",
    "why": "Plant output, 0-100 %"
   },
   {
    "ref": "BI 100",
    "name": "Boiler 1 status",
    "why": "Boiler 1 firing (1 = on)"
   },
   {
    "ref": "AI 0",
    "name": "Error code",
    "why": "Active error code"
   }
  ],
  "enable": "BV 0 Central heating turns space heating on or off; BV 100 + 10 x (n - 1) makes boiler n available.",
  "heartbeat": null,
  "remote_sensors": "Set AV 33 Outdoor sensor to 4 (BAS) and write the outdoor temperature to AV 0. Error 153 flags a BAS outdoor sensor problem; the manual does not give a timeout.",
  "setup": [
   "BAS menu: BAS Type None/BACnet MS/TP/BACnet IP (default None). BACnet IP needs Internet Connection Type set to Ethernet.",
   "Device ID 0-4194302 (default 1); device object name default 'Smart Boiler Control'.",
   "MS/TP: MAC 0-127 (default 1), baud 9600-115200 (default 19200), Max Masters default 127, Max Info Frames default 1.",
   "BACnet IP: UDP port default 47808; optional foreign-device registration to a BBMD (TTL default 30 s).",
   "Reinitialize Device and Device Communication Control password: tekmar1150."
  ],
  "gotchas": [
   "Most writable objects are configuration settings stored by the control; avoid writing them cyclically."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 0,
   "name": "Error code",
   "description": "Active error code (see error list)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "Boiler target temperature",
   "description": "Range 50-230 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Boiler supply temperature",
   "description": "Range 32.0-266.0 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Plant output",
   "description": "Range 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Domestic hot water tank target",
   "description": "Range 32.0-266.0 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "Domestic hot water tank temperature",
   "description": "Range 32.0-266.0 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "Setpoint target temperature",
   "description": "Range 32.0-266.0 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "Central heating target",
   "description": "Range 32.0-266.0 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "Room target",
   "description": "Range 32.0-266.0 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "Pressure",
   "description": "Range 0.0-150.0 psi",
   "units": "psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "Indoor",
   "description": "Range 32.0-266.0 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "Override",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Auto, 1=Hand, 2=Max Heat, 3=Purge, 4=Off, 5=Exercise"
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "System pump run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "System cycles",
   "description": "Range 0-999999",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "DHW pump run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "DHW cycles",
   "description": "Range 0-999999",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 100,
   "name": "Boiler 1 firing rate",
   "description": "Range 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 101,
   "name": "Boiler 1 EMS temperature output",
   "description": "Range 50.0-210.2 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 102,
   "name": "Boiler 1 run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 103,
   "name": "Boiler 1 cycles",
   "description": "Range 0-999999",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 104,
   "name": "Boiler 1 pump or valve run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 110,
   "name": "Boiler 2 firing rate",
   "description": "Range 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 111,
   "name": "Boiler 2 EMS temperature output",
   "description": "Range 50.0-210.2 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 112,
   "name": "Boiler 2 run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 113,
   "name": "Boiler 2 cycles",
   "description": "Range 0-999999",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 114,
   "name": "Boiler 2 pump or valve run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 120,
   "name": "Boiler 3 firing rate",
   "description": "Range 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 121,
   "name": "Boiler 3 EMS temperature output",
   "description": "Range 50.0-210.2 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 122,
   "name": "Boiler 3 run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 123,
   "name": "Boiler 3 cycles",
   "description": "Range 0-999999",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 124,
   "name": "Boiler 3 pump or valve run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 130,
   "name": "Boiler 4 firing rate",
   "description": "Range 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 131,
   "name": "Boiler 4 EMS temperature output",
   "description": "Range 50.0-210.2 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 132,
   "name": "Boiler 4 run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 133,
   "name": "Boiler 4 cycles",
   "description": "Range 0-999999",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 134,
   "name": "Boiler 4 pump or valve run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 140,
   "name": "Boiler 5 firing rate",
   "description": "Range 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 141,
   "name": "Boiler 5 EMS temperature output",
   "description": "Range 50.0-210.2 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 142,
   "name": "Boiler 5 run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 143,
   "name": "Boiler 5 cycles",
   "description": "Range 0-999999",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 144,
   "name": "Boiler 5 pump or valve run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 150,
   "name": "Boiler 6 firing rate",
   "description": "Range 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 151,
   "name": "Boiler 6 EMS temperature output",
   "description": "Range 50.0-210.2 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 152,
   "name": "Boiler 6 run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 153,
   "name": "Boiler 6 cycles",
   "description": "Range 0-999999",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 154,
   "name": "Boiler 6 pump or valve run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 160,
   "name": "Boiler 7 firing rate",
   "description": "Range 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 161,
   "name": "Boiler 7 EMS temperature output",
   "description": "Range 50.0-210.2 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 162,
   "name": "Boiler 7 run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 163,
   "name": "Boiler 7 cycles",
   "description": "Range 0-999999",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 164,
   "name": "Boiler 7 pump or valve run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 170,
   "name": "Boiler 8 firing rate",
   "description": "Range 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 171,
   "name": "Boiler 8 EMS temperature output",
   "description": "Range 50.0-210.2 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 172,
   "name": "Boiler 8 run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 173,
   "name": "Boiler 8 cycles",
   "description": "Range 0-999999",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 174,
   "name": "Boiler 8 pump or valve run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 180,
   "name": "Boiler 9 firing rate",
   "description": "Range 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 181,
   "name": "Boiler 9 EMS temperature output",
   "description": "Range 50.0-210.2 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 182,
   "name": "Boiler 9 run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 183,
   "name": "Boiler 9 cycles",
   "description": "Range 0-999999",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 184,
   "name": "Boiler 9 pump or valve run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 190,
   "name": "Boiler 10 firing rate",
   "description": "Range 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 191,
   "name": "Boiler 10 EMS temperature output",
   "description": "Range 50.0-210.2 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 192,
   "name": "Boiler 10 run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 193,
   "name": "Boiler 10 cycles",
   "description": "Range 0-999999",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 194,
   "name": "Boiler 10 pump or valve run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 200,
   "name": "Boiler 11 firing rate",
   "description": "Range 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 201,
   "name": "Boiler 11 EMS temperature output",
   "description": "Range 50.0-210.2 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 202,
   "name": "Boiler 11 run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 203,
   "name": "Boiler 11 cycles",
   "description": "Range 0-999999",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 204,
   "name": "Boiler 11 pump or valve run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 210,
   "name": "Boiler 12 firing rate",
   "description": "Range 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 211,
   "name": "Boiler 12 EMS temperature output",
   "description": "Range 50.0-210.2 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 212,
   "name": "Boiler 12 run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 213,
   "name": "Boiler 12 cycles",
   "description": "Range 0-999999",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 214,
   "name": "Boiler 12 pump or valve run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 220,
   "name": "Boiler 13 firing rate",
   "description": "Range 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 221,
   "name": "Boiler 13 EMS temperature output",
   "description": "Range 50.0-210.2 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 222,
   "name": "Boiler 13 run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 223,
   "name": "Boiler 13 cycles",
   "description": "Range 0-999999",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 224,
   "name": "Boiler 13 pump or valve run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 230,
   "name": "Boiler 14 firing rate",
   "description": "Range 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 231,
   "name": "Boiler 14 EMS temperature output",
   "description": "Range 50.0-210.2 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 232,
   "name": "Boiler 14 run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 233,
   "name": "Boiler 14 cycles",
   "description": "Range 0-999999",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 234,
   "name": "Boiler 14 pump or valve run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 240,
   "name": "Boiler 15 firing rate",
   "description": "Range 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 241,
   "name": "Boiler 15 EMS temperature output",
   "description": "Range 50.0-210.2 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 242,
   "name": "Boiler 15 run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 243,
   "name": "Boiler 15 cycles",
   "description": "Range 0-999999",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 244,
   "name": "Boiler 15 pump or valve run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 250,
   "name": "Boiler 16 firing rate",
   "description": "Range 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 251,
   "name": "Boiler 16 EMS temperature output",
   "description": "Range 50.0-210.2 °F",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 252,
   "name": "Boiler 16 run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 253,
   "name": "Boiler 16 cycles",
   "description": "Range 0-999999",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 254,
   "name": "Boiler 16 pump or valve run time hours",
   "description": "Range 0-999999",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "Outdoor air temperature",
   "description": "Range -85-149 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Room occupied",
   "description": "Range 34.7-100.4 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Room unoccupied",
   "description": "Range 34.7-100.4 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Terminal unit",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Radiant Floor, 1=Baseboard, 2=Radiator, 3=Fancoil"
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "Outdoor design temperature",
   "description": "Range -60-45 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Outdoor start temperature",
   "description": "Range 34.7-100.4 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Boiler start temperature",
   "description": "Range 34.7-100.4 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Boiler design temperature",
   "description": "Range 50-230 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Warm weather shut down occupied",
   "description": "Range 34.7-100.4 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Warm weather shut down unoccupied",
   "description": "Range 34.7-100.4 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "DHW Type",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=System, 1=Side, 2=Dedicated"
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "DHW tank occupied",
   "description": "Range 50-230 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "DHW tank unoccupied",
   "description": "Range 50-230 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "DHW tank differential",
   "description": "Range 0.9-42.4 Δ°F",
   "units": "Δ°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "DHW exchange occupied",
   "description": "Range 50-230 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "Indirect DHW priority override",
   "description": "Range 20-240 min",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "Indirect DHW boiler limiting",
   "description": "Range 1-16",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "Constant setpoint occupied",
   "description": "Range 50-230 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "Boiler minimum",
   "description": "Range 50-230 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "Boiler maximum",
   "description": "Range 50-230 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "Staging",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=PID, 1=Proportional"
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "PID manual boiler differential",
   "description": "Range 1.8-42.4 Δ°F",
   "units": "Δ°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "Proportional interstage differential",
   "description": "Range 0.9-10.0 Δ°F",
   "units": "Δ°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "Proportional interstage manual",
   "description": "Range 0.5-40.0 min",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "Proportional interstage on delay",
   "description": "Range 0.5-10.0 min",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "Proportional interstage off delay",
   "description": "Range 0.5-10.0 min",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "Minimum stage run time",
   "description": "Range 0.5-10.0 min",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "Minimum stage off time",
   "description": "Range 0.5-10.0 min",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "Condensing group sequencing",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Sequential, 1=Parallel"
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "Non-Condensing group sequencing",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Sequential, 1=Parallel"
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "Feature lead type",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=First On First Off, 1=First On Last Off"
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "Combustion air delay",
   "description": "Range 0-360 s",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "Variable primary flow",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Pump, 1=Valve"
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "Outdoor sensor",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Control, 1=tN4, 2=Cloud, 3=Wireless, 4=BAS"
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "Alert Boiler High temperature",
   "description": "Range 50-230 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "Alert Boiler Low temperature",
   "description": "Range 50-230 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "Alert High Pressure",
   "description": "Range 0-150 psi",
   "units": "psi",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "Alert Low Pressure",
   "description": "Range 0-150 psi",
   "units": "psi",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "Alert No Heat",
   "description": "Range 0.5-80",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 100,
   "name": "Alert Boiler 1 hours",
   "description": "Range 1000-15000",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "Alert Boiler 1 cycles",
   "description": "Range 1-25000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 110,
   "name": "Alert Boiler 2 hours",
   "description": "Range 1000-15000",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "Alert Boiler 2 cycles",
   "description": "Range 1-25000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 120,
   "name": "Alert Boiler 3 hours",
   "description": "Range 1000-15000",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 121,
   "name": "Alert Boiler 3 cycles",
   "description": "Range 1-25000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 130,
   "name": "Alert Boiler 4 hours",
   "description": "Range 1000-15000",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 131,
   "name": "Alert Boiler 4 cycles",
   "description": "Range 1-25000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 140,
   "name": "Alert Boiler 5 hours",
   "description": "Range 1000-15000",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 141,
   "name": "Alert Boiler 5 cycles",
   "description": "Range 1-25000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 150,
   "name": "Alert Boiler 6 hours",
   "description": "Range 1000-15000",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 151,
   "name": "Alert Boiler 6 cycles",
   "description": "Range 1-25000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 160,
   "name": "Alert Boiler 7 hours",
   "description": "Range 1000-15000",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 161,
   "name": "Alert Boiler 7 cycles",
   "description": "Range 1-25000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 170,
   "name": "Alert Boiler 8 hours",
   "description": "Range 1000-15000",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 171,
   "name": "Alert Boiler 8 cycles",
   "description": "Range 1-25000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 180,
   "name": "Alert Boiler 9 hours",
   "description": "Range 1000-15000",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 181,
   "name": "Alert Boiler 9 cycles",
   "description": "Range 1-25000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 190,
   "name": "Alert Boiler 10 hours",
   "description": "Range 1000-15000",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 191,
   "name": "Alert Boiler 10 cycles",
   "description": "Range 1-25000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 200,
   "name": "Alert Boiler 11 hours",
   "description": "Range 1000-15000",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 201,
   "name": "Alert Boiler 11 cycles",
   "description": "Range 1-25000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 210,
   "name": "Alert Boiler 12 hours",
   "description": "Range 1000-15000",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 211,
   "name": "Alert Boiler 12 cycles",
   "description": "Range 1-25000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 220,
   "name": "Alert Boiler 13 hours",
   "description": "Range 1000-15000",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 221,
   "name": "Alert Boiler 13 cycles",
   "description": "Range 1-25000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 230,
   "name": "Alert Boiler 14 hours",
   "description": "Range 1000-15000",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 231,
   "name": "Alert Boiler 14 cycles",
   "description": "Range 1-25000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 240,
   "name": "Alert Boiler 15 hours",
   "description": "Range 1000-15000",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 241,
   "name": "Alert Boiler 15 cycles",
   "description": "Range 1-25000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 250,
   "name": "Alert Boiler 16 hours",
   "description": "Range 1000-15000",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 251,
   "name": "Alert Boiler 16 cycles",
   "description": "Range 1-25000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 0,
   "name": "tekmarNet call status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "System pump status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "DHW pump status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "Combustion air damper status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "Domestic Hot Water Priority",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "Warm Weather Shut Down",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 100,
   "name": "Boiler 1 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 101,
   "name": "Boiler 1 pump or valve status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 110,
   "name": "Boiler 2 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 111,
   "name": "Boiler 2 pump or valve status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 120,
   "name": "Boiler 3 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 121,
   "name": "Boiler 3 pump or valve status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 130,
   "name": "Boiler 4 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 131,
   "name": "Boiler 4 pump or valve status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 140,
   "name": "Boiler 5 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 141,
   "name": "Boiler 5 pump or valve status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 150,
   "name": "Boiler 6 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 151,
   "name": "Boiler 6 pump or valve status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 160,
   "name": "Boiler 7 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 161,
   "name": "Boiler 7 pump or valve status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 170,
   "name": "Boiler 8 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 171,
   "name": "Boiler 8 pump or valve status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 180,
   "name": "Boiler 9 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 181,
   "name": "Boiler 9 pump or valve status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 190,
   "name": "Boiler 10 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 191,
   "name": "Boiler 10 pump or valve status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 200,
   "name": "Boiler 11 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 201,
   "name": "Boiler 11 pump or valve status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 210,
   "name": "Boiler 12 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 211,
   "name": "Boiler 12 pump or valve status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 220,
   "name": "Boiler 13 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 221,
   "name": "Boiler 13 pump or valve status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 230,
   "name": "Boiler 14 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 231,
   "name": "Boiler 14 pump or valve status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 240,
   "name": "Boiler 15 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 241,
   "name": "Boiler 15 pump or valve status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 250,
   "name": "Boiler 16 status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 251,
   "name": "Boiler 16 pump or valve status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 0,
   "name": "Central heating",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "Warm weather shut down",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "DHW available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "DHW sensor available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "DHW exchange unoccupied",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "Indirect DHW priority",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "Indirect DHW system pump",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "Constant setpoint",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "Constant setpoint unoccupied",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "Constant setpoint priority",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "Constant setpoint system pump",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "Remote setpoint",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "Boiler Auto Diff",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "Interstage Auto",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "Condensing Boiler Rotation",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "Non-Condensing Boiler Rotation",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "Staging Fixed Lead",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "Staging Fixed Last",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "Pressure sensor available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "Exercise available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 100,
   "name": "Boiler 1 available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 110,
   "name": "Boiler 2 available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 120,
   "name": "Boiler 3 available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 130,
   "name": "Boiler 4 available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 140,
   "name": "Boiler 5 available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 150,
   "name": "Boiler 6 available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 160,
   "name": "Boiler 7 available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 170,
   "name": "Boiler 8 available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 180,
   "name": "Boiler 9 available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 190,
   "name": "Boiler 10 available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 200,
   "name": "Boiler 11 available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 210,
   "name": "Boiler 12 available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 220,
   "name": "Boiler 13 available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 230,
   "name": "Boiler 14 available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 240,
   "name": "Boiler 15 available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 250,
   "name": "Boiler 16 available",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/watts/tekmar-smart-boiler-control-294bac",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}