Systemair's Access controller, fitted to its larger air handling units, is a native BACnet device; Systemair publishes its object list as an EDE file set (objects, state texts, units) rather than a PDF table. The 1,201 objects cover run-mode commands and settings (S_ variables), actual values and I/O (A_ variables), fan and damper data from the Modbus-connected motors (CA_ variables), alarms (AL_), trend logs, schedules, a calendar and notification classes. One application covers many unit types, so most objects only matter when the matching function is configured.
This page lists 1201 BACnet objects for the Systemair Access controller 5.x (ControllerProgram) BACnet — 348 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Systemair’s own free documentation, linked below.
- Manufacturer
- Systemair
- Model
- Access controller 5.x (ControllerProgram) BACnet
- Equipment
- Air handling unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 1201 (348 writable)
- Transport
- BACnet IP
- Firmware
- Access 5.5-1-01 build 411
- Default device instance
- 114112
- Also known as
- Systemair Access, Access 5.5, Access 5.5-1-01, Systemair Access controller, Access ControllerProgram, EXOL
BMS integration notes: Systemair Access controller 5.x (ControllerProgram) BACnet
Set MV-12 AirUnitAutoMode to AUTO (3) to let the unit follow its schedule, or to Low/Normal/High speed to force it; MV-31 ExternalControl gives BMS-style extended run and stop commands. Read MV-15 UnitMode and MV-16 UnitModeControl to see what the unit is doing and why, map the supply/extract temperatures and supply setpoint, and watch BV-9..12 sum alarms with BV-8 to acknowledge all alarms. Outdoor temperature and summer/winter or changeover modes can be supplied by the BMS through the BMS_ objects.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 12 | AirUnitAutoMode | Off / manual / auto / forced speed command | Write |
| MV 31 | ExternalControl | External extended run or stop command | Write |
| AV 39 | SupplySetpoint | Supply air temperature setpoint | Write |
| BV 8 | AlaAcknowAll | Acknowledge all alarms | Write |
| MV 15 | UnitMode | Actual run mode | Read |
| MV 16 | UnitModeControl | What is driving the current run mode | Read |
| AI 3 | AI_SupplyAirTemp | Supply air temperature | Read |
| AI 5 | AI_ExtractAirTemp | Extract air temperature | Read |
| AI 1 | AI_OutDoorTemp | Outdoor temperature | Read |
| BV 9 | SumAlarm | Any alarm | Read |
Enable & remote start
MV-12 AirUnitAutoMode: 1=OFF, 2=Manual (uses MV-13 AirUnitManual), 3=AUTO, 4=Low speed, 5=Normal speed, 6=High speed. MV-31 ExternalControl adds extended run low/normal/high, external stop, start free cooling and recirculation. MV-32 AirUnitServiceStop stops the unit with top priority.
Sensors & values from the BMS
AV-466 BMS_OutDoorTemp takes an outdoor temperature from BACnet/Modbus; BV-156 BMS_SummerMode and BV-157/158 BMS_ChangeOver1/2 take summer/winter and cooling/heating changeover modes. BV-51 CommunicationFaultBmsMaster is an alarm for a BMS master communication fault; the files do not state its timeout.
Network setup
- The published EDE uses device instance 114112 (device name Access); the device ID must be unique on the network.
- Per the Access 4.x communication manual, BACnet/IP is disabled on delivery and must be switched on in the controller's communication settings.
- Entering a BBMD address (host:port, default port 47808) makes Access a BACnet/IP foreign device that ignores other broadcasts (Access 4.x manual).
- Systemair supplies EDE, object-type, state-text and unit files plus a Modbus cross-reference in one zip per Access release; use the one matching the controller's software.
- The Modbus cross-reference in the same package shows Modbus TCP enabled with device address 1.
Watch out for
- Access is inferred: the EDE marks every object as not settable, so confirm writes on site.
- Many temperature and pressure objects report BACnet units NO-UNITS even though values are °C or Pa.
- S_ setting objects (PID bands, curves, limits) are configuration settings.
- Multistate states start at 1 in BACnet, so 'AUTO' on MV-12 is value 3.
Systemair Access controller 5.x (ControllerProgram) BACnet BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| CAL | 1 | Calendar | Write | |||
| SCH | 2 | TC_FanSpeed | Write | |||
| SCH | 3 | TC_Extra1 | Write | |||
| SCH | 4 | TC_Extra2 | Write | |||
| SCH | 5 | TC_Extra3 | Write | |||
| SCH | 6 | TC_Extra4 | Write | |||
| MV | 1 | DOSelect_SeqPumpA | Run mode pump seq A | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 2 | DOSelect_SeqPumpB | Run mode pump seq B | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 3 | DOSelect_SeqPumpC | Run mode pump seq C | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 4 | DOSelect_SeqPumpD | Run mode pump seq D | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 5 | DOSelect_SeqPumpE | Run mode pump seq E | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 6 | DOSelect_SeqPumpF | Run mode pump seq F | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 7 | DOSelect_SeqPumpG | Run mode pump seq G | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 8 | DOSelect_SeqPumpH | Run mode pump seq H | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 9 | DOSelect_SeqPumpI | Run mode pump seq I | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 10 | DOSelect_SeqPumpJ | Run mode pump seq J | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 11 | DOSelect_RecircAirDamper | Run mode recirc. damper | Write | 1=Close, 2=Open, 3=Auto | |
| MV | 72 | DOSelect_OutdoorAirDamper | Run mode outdoor damper | Write | 1=Close, 2=Open, 3=Auto | |
| MV | 73 | DOSelect_ExhaustAirDamper | Run mode exhaust damper | Write | 1=Close, 2=Open, 3=Auto | |
| MV | 74 | DOSelect_HumidityStart | Run mode HumidityStart | Write | 1=Close, 2=Open, 3=Auto | |
| MV | 75 | DOSelect_ChangeOver1 | Run mode changeover 1 | Write | 1=Close, 2=Open, 3=Auto | |
| MV | 76 | DOSelect_ChangeOver2 | Run mode changeover 2 | Write | 1=Close, 2=Open, 3=Auto | |
| MVmin | 12 | AirUnitAutoMode | Running mode air unit | Write | 1=OFF, 2=Manual, 3=AUTO, 4=Low speed, 5=Normal speed, 6=High speed | |
| MV | 13 | AirUnitManual | Man. setting for Air unit in Man. mode | Write | 1=Stop, 2=Starting up, 3=Low speed, 4=Normal speed, 5=High speed, 6=Support heating, 7=Support cooling, 8=CO2 mode, 9=Free cooling, 10=Cool down mode, 11=Fire mode, 12=Smoke mode, 13=Recirculation mode, 14=Defrosting mode | |
| MV | 14 | VentControl | Select temp. cont. mode | Write | 1=Const.supply air, 2=Outdoor comp. supply air, 3=Cascade room temp cont., 4=Extract temp cont., 5=Outdoor dep. supply or room temp, 6=Outdoor dep. supply or extract temp, 7=Cascade outdoor comp. room temp cont., 8=Cascade outdoor comp. extract temp cont., 9=Extract air dep. supply air temp. | |
| BV | 6 | FilterAlarmReset | Resets the filter alarm counter | Write | 0=NORMAL, 1=ACKNOWLEDGE | |
| AV | 13 | AOManual_SequenceA | Seq.A contr. output if man. on mode | % | Write | |
| AV | 14 | AOManual_SequenceB | Seq.B contr. output if man. on mode | % | Write | |
| AV | 15 | AOManual_SequenceC | Seq.C contr. output if man. on mode | % | Write | |
| AV | 16 | AOManual_SequenceD | Seq.D contr. output if man. on mode | % | Write | |
| AV | 17 | AOManual_SequenceE | Seq.E contr. output if man. on mode | % | Write | |
| AV | 18 | AOManual_SequenceF | Seq.F contr. output if man. on mode | % | Write | |
| AV | 19 | AOManual_SequenceG | Seq.G contr. output if man. on mode | % | Write | |
| AV | 20 | AOManual_SequenceH | Seq.H contr. output if man. on mode | % | Write | |
| AV | 21 | AOManual_SequenceI | Seq.I contr. output if man. on mode | % | Write | |
| AV | 22 | AOManual_SequenceJ | Seq.J contr. output if man. on mode | % | Write | |
| AV | 23 | AOManual_Humidity | Humidification/Dehumidification cont. output if man. mode | % | Write | |
| AV | 24 | AOManual_ExtraController | Manual/Auto Extra contr. | % | Write | |
| MV | 17 | AOSelect_SequenceA | Seq.A contr. Mode | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 18 | AOSelect_SequenceB | Seq.B contr. Mode | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 19 | AOSelect_SequenceC | Seq.C contr. Mode | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 20 | AOSelect_SequenceD | Seq.D contr. Mode | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 21 | AOSelect_SequenceE | Seq.E contr. Mode | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 22 | AOSelect_SequenceF | Seq.F contr. Mode | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 23 | AOSelect_SequenceG | Seq.G contr. Mode | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 24 | AOSelect_SequenceH | Seq.H contr. Mode | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 25 | AOSelect_SequenceI | Seq.I contr. Mode | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 26 | AOSelect_SequenceJ | Seq.J contr. Mode | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 27 | AOSelect_Humidity | Running mode Humidification/Dehumidification | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 28 | AOSelect_ExtraController | Manual/Auto Extra contr. | Write | 1=Man off, 2=Man on, 3=Auto | |
| MV | 29 | SAFAutoMode | Running mode SAF | Write | 1=OFF, 2=Manual output, 3=AUTO, 4=Manual setpoint, 5=Low speed, 6=Normal speed, 7=High speed | |
| MV | 30 | EAFAutoMode | Running mode EAF | Write | 1=OFF, 2=Manual output, 3=AUTO, 4=Manual setpoint, 5=Low speed, 6=Normal speed, 7=High speed | |
| AV | 25 | SAFManualSetpoint | Man. setp. SAF if Man. mode | Write | ||
| AV | 26 | EAFManualSetpoint | Man. setp. EAF if Man. mode | Write | ||
| AV | 27 | SAFManualOutput | Man. output SAF if Man. mode | % | Write | |
| AV | 28 | EAFManualOutput | Man. output EAF if Man. mode | % | Write | |
| MVmin | 31 | ExternalControl | External cont. | Write | 1=No External control, 2=Extended run low speed, 3=Extended run normal speed, 4=Extended run high speed, 5=External stop, 6=External stop with support control, 7=Start Free cooling, 8=Recirculation | |
| MV | 32 | AirUnitServiceStop | Stop the air unit with No 1 prio | Write | 1=No, 2=Yes | |
| AV | 29 | SeqPumpOutdLimitA | Pump outd. temp. limit seq A | Write | ||
| AV | 30 | SeqPumpOutdLimitB | Pump outd. temp. limit seq B | Write | ||
| AV | 31 | SeqPumpOutdLimitC | Pump outd. temp. limit seq C | Write | ||
| AV | 32 | SeqPumpOutdLimitD | Pump outd. temp. limit seq D | Write | ||
| AV | 33 | SeqPumpOutdLimitE | Pump outd. temp. limit seq E | Write | ||
| AV | 34 | SeqPumpOutdLimitF | Pump outd. temp. limit seq F | Write | ||
| AV | 35 | SeqPumpOutdLimitG | Pump outd. temp. limit seq G | Write | ||
| AV | 36 | SeqPumpOutdLimitH | Pump outd. temp. limit seq H | Write | ||
| AV | 37 | SeqPumpOutdLimitI | Pump outd. temp. limit seq I | Write | ||
| AV | 38 | SeqPumpOutdLimitJ | Pump outd. temp. limit seq J | Write | ||
| MV | 33 | FanType | Select fan cont. mode | Write | 1=Freq. cont. pressure, 2=Freq. cont. air flow, 3=Freq. cont. manually, 4=Direct Freq. cont., 5=Freq. cont. with slave cont. EAF, 6=Freq. cont. with slave cont. EAF air flow dep., 7=Freq. cont. with slave cont. SAF, 8=Freq. cont. with slave cont. SAF air flow dep. | |
| AVmin | 39 | SupplySetpoint | Setp. supply air temp. when constant supply air temp. func. | Write | ||
| AV | 40 | ExtractSetpoint | Setp. extract air temp if extract air temp cont. func. | Write | ||
| AV | 41 | SupplySetpointMax | Max limit of supply setp. when cascade cont. | Write | ||
| AV | 44 | SupplySetpointMin | Min limit of supply setp. when cascade cont. | Write | ||
| AV | 42 | SupplySetpOffsetLow | Temp. setp. Offset in low speed | Write | ||
| AV | 43 | SupplySetpOffsetHigh | Temp. setp. Offset in high speed | Write | ||
| AV | 45 | SummerModeSupplySetpoint | Supply temp setp. at summer time | Write | ||
| AV | 46 | SummerModeOutdoortemp | Outd. temp for switching bet. summer and winter | Write | ||
| AV | 47 | SAFLowSpeedPressure | Setp. low sp. supply air fan press. | Write | ||
| AV | 48 | SAFNormalSpeedPressure | Setp. normal sp. supply air fan press. | Write | ||
| AV | 49 | SAFHighSpeedPressure | Setp. high sp. supply air fan press. | Write | ||
| AV | 50 | EAFLowSpeedPressure | Setp. low sp. Extract air fan press. | Write | ||
| AV | 51 | EAFNormalSpeedPressure | Setp. normal sp. Extract air fan press. | Write | ||
| AV | 52 | EAFHighSpeedPressure | Setp. high sp. Extract air fan press. | Write | ||
| AV | 53 | SAFLowspeedAirFlow | Setp. low sp. SAF air flow. | Write | ||
| AV | 54 | SAFNormalspeedAirFlow | Setp. normal sp. SAF air flow. | Write | ||
| AV | 55 | SAFHighspeedAirFlow | Setp. high sp. SAF air flow. | Write | ||
| AV | 56 | EAFLowspeedAirFlow | Setp. low sp. EAF air flow. | Write | ||
| AV | 57 | EAFNormalspeedAirFlow | Setp. normal sp. EAF air flow. | Write | ||
| AV | 58 | EAFHighspeedAirFlow | Setp. high sp. EAF air flow. | Write | ||
| AV | 59 | SAFLowSpeedOutput | Output signal low speed SAF if Freq. cont. manually | % | Write | |
| AV | 60 | SAFNormalSpeedOutput | Output signal normal speed SAF if Freq. cont. manually | % | Write | |
| AV | 61 | SAFHighspeedOutput | Output signal high speed SAF if Freq. cont. manually | % | Write | |
| AV | 62 | EAFLowSpeedOutput | Output signal low speed EAF if Freq. cont. manually | % | Write | |
| AV | 63 | EAFNormalSpeedOutput | Output signal normal speed EAF if Freq. cont. manually | % | Write | |
| AV | 64 | EAFHighspeedOutput | Output signal high speed EAF if Freq. cont. manually | % | Write | |
| MV | 34 | SAFModeFreeCool | SAF speed in freecool mode | Write | 1=Off/Auto, 2=normal setp., 3=Man. setp., 4=Man. output, 5=Low speed setp., 6=Normal speed setp., 7=High speed setp. | |
| MV | 35 | SAFModeFire | SAF speed in fire mode | Write | 1=Off/Auto, 2=normal setp., 3=Man. setp., 4=Man. output, 5=Low speed setp., 6=Normal speed setp., 7=High speed setp. | |
| MV | 36 | SAFModeSmoke | SAF setp. in smoke mode | Write | 1=Off/Auto, 2=normal setp., 3=Man. setp., 4=Man. output, 5=Low speed setp., 6=Normal speed setp., 7=High speed setp. | |
| MV | 37 | SAFModeRecirculation | SAF speed in recirc. mode | Write | 1=Off/Auto, 2=normal setp., 3=Man. setp., 4=Man. output, 5=Low speed setp., 6=Normal speed setp., 7=High speed setp. | |
| MV | 38 | EAFModeFreeCool | EAF speed in freecool mode | Write | 1=Off/Auto, 2=normal setp., 3=Man. setp., 4=Man. output, 5=Low speed setp., 6=Normal speed setp., 7=High speed setp. | |
| MV | 39 | EAFModeFire | EAF speed in fire mode | Write | 1=Off/Auto, 2=normal setp., 3=Man. setp., 4=Man. output, 5=Low speed setp., 6=Normal speed setp., 7=High speed setp. | |
| MV | 40 | EAFModeSmoke | EAF speed in smoke mode | Write | 1=Off/Auto, 2=normal setp., 3=Man. setp., 4=Man. output, 5=Low speed setp., 6=Normal speed setp., 7=High speed setp. | |
| MV | 41 | EAFModeRecirculation | EAF speed in recirc. mode | Write | 1=Off/Auto, 2=normal setp., 3=Man. setp., 4=Man. output, 5=Low speed setp., 6=Normal speed setp., 7=High speed setp. | |
| AV | 65 | SAFManSetpFreeCool | SAF setp. in freecool mode | Write | ||
| AV | 66 | SAFManSetpFire | SAF setp. in fire mode | Write | ||
| AV | 67 | SAFManSetpSmoke | SAF man. output in smoke mode | Write | ||
| AV | 68 | SAFManSetpRecirculation | SAF setp. in recirc. mode | Write | ||
| AV | 69 | EAFManSetpFreeCool | EAF setp. in freecool mode | Write | ||
| AV | 70 | EAFManSetpFire | EAF setp. in fire mode | Write | ||
| AV | 71 | EAFManSetpSmoke | EAF setp. in smoke mode | Write | ||
| AV | 72 | EAFManSetpRecirculation | EAF setp. in recirc. mode | Write | ||
| AV | 73 | SAFManOutFreeCool | SAF man. output in freecool mode | % | Write | |
| AV | 74 | SAFManOutFire | SAF man. output in fire mode | % | Write | |
| AV | 75 | SAFManOutSmoke | SAF man. output in smoke mode | % | Write | |
| AV | 76 | SAFManOutRecirculation | SAF man. output in recirc. mode | % | Write | |
| AV | 77 | EAFManOutFreeCool | EAF man. output in freecool mode | % | Write | |
| AV | 78 | EAFManOutFire | EAF man. output in fire mode | % | Write | |
| AV | 79 | EAFManOutSmoke | EAF man. output in smoke mode | % | Write | |
| AV | 80 | EAFManOutRecirculation | EAF man. output in recirc. mode | % | Write | |
| AV | 81 | EAFFrequencyFact | Factor for controlling EAF if CAV fan cont. is configured | Write | ||
| AV | 82 | Curve1_X1 | Outd. temp for 1st curvep. for outd. comp. setp. | Write | ||
| AV | 83 | Curve1_X2 | Outd. temp for 2nd curvep. for outd. comp. setp. | Write | ||
| AV | 84 | Curve1_X3 | Outd. temp for 3rd curvep. for outd. comp. setp. | Write | ||
| AV | 85 | Curve1_X4 | Outd. temp for 4th curvep. for outd. comp. setp. | Write | ||
| AV | 86 | Curve1_Y1 | setp. for 1st curvep. for outd. comp. setp. | Write | ||
| AV | 87 | Curve1_Y2 | Setp. for 2nd curvep. for outd. comp. setp. | Write | ||
| AV | 88 | Curve1_Y3 | Setp. for 3rd curvep. for outd. comp. setp. | Write | ||
| AV | 89 | Curve1_Y4 | Setp. for 4th curvep. for outd. comp. setp. | Write | ||
| AV | 90 | ExtractPID_PBand | P-band Extract air cont. | Write | ||
| AV | 93 | SAFPID_PBand | P-band press. cont. SAF | Write | ||
| AV | 91 | EAFPID_PBand | P-band press. cont. EAF | Write | ||
| AV | 92 | FrostPID1_PBand | P-band frost mode | Write | ||
| AV | 94 | FrostPID2_PBand | P-band frost mode | Write | ||
| AV | 97 | FrostPID3_PBand | P-band frost mode | Write | ||
| AV | 100 | CO2PID_PBand | P-band CO2 mode | ppm | Write | |
| AV | 103 | RoomPID_PBand | P-band room air cont. | Write | ||
| AV | 106 | DeIcePID_PBand | P-band de-icing | Write | ||
| AV | 109 | HumidityPID_PBand | P-band humidity cont. | Write | ||
| AV | 110 | ExtraPID_PBand | P-band extra pid cont. | Write | ||
| AV | 111 | PreHeatPID_PBand | P-band preheater | Write | ||
| AV | 107 | Zone1SupplyPID_PBand | P-band Zone 1 supply | Write | ||
| AV | 108 | Zone2SupplyPID_PBand | P-band Zone 2 supply | Write | ||
| AV | 104 | Zone3SupplyPID_PBand | P-band Zone 3 supply | Write | ||
| AV | 105 | Zone1RoomPID_PBand | P-band Zone 1 room | Write | ||
| AV | 101 | Zone2RoomPID_PBand | P-band Zone 2 room | Write | ||
| AV | 102 | Zone3RoomPID_PBand | P-band Zone 3 room | Write | ||
| AV | 98 | Zone1FrostPID_PBand | P-band Zone 1 frost prot. | Write | ||
| AV | 99 | Zone2FrostPID_PBand | P-band Zone 2 frost prot. | Write | ||
| AV | 95 | Zone3FrostPID_PBand | P-band Zone 3 frost prot. | Write | ||
| AV | 434 | FreshAirPID_PBand | P-band fresh air | Write | ||
| AV | 435 | EATRPID_PBand | P-band EATR | Write | ||
| AV | 96 | Zone1SupplyCoolPID_PBand | P-band Zone 1 cooling | Write | ||
| AV | 112 | Zone2SupplyCoolPID_PBand | P-band Zone 2 cooling | Write | ||
| AV | 114 | Zone3SupplyCoolPID_PBand | P-band Zone 3 cooling | Write | ||
| AV | 115 | SAFAirFlowPID_PBand | P-band flow cont. SAF | Write | ||
| AV | 113 | EAFAirFlowPID_PBand | P-band flow cont. EAF | Write | ||
| AV | 116 | DeHumidityPID_PBand | P-band de-humidity cont. | Write | ||
| AV | 438 | RHPID_PBand | P-band RH (same PID as CO2) | Write | ||
| AV | 117 | SeqAPID_PBand | P-band Seq A air cont. | Write | ||
| AV | 118 | SeqBPID_PBand | P-band Seq B air cont. | Write | ||
| AV | 119 | SeqCPID_PBand | P-band Seq C air cont. | Write | ||
| AV | 120 | SeqDPID_PBand | P-band Seq D air cont. | Write | ||
| AV | 121 | SeqEPID_PBand | P-band Seq E air cont. | Write | ||
| AV | 122 | SeqFPID_PBand | P-band Seq F air cont. | Write | ||
| AV | 123 | SeqGPID_PBand | P-band Seq G air cont. | Write | ||
| AV | 124 | SeqHPID_PBand | P-band Seq H air cont. | Write | ||
| AV | 125 | SeqIPID_PBand | P-band Seq I air cont. | Write | ||
| AV | 126 | SeqJPID_PBand | P-band Seq J air cont. | Write | ||
| AV | 127 | ExtractPID_ITime | I-time Extract air cont. | s | Write | |
| AV | 128 | SAFPID_ITime | I-time press. cont. SAF | s | Write | |
| AV | 129 | EAFPID_ITime | I-time press. cont. EAF | s | Write | |
| AV | 130 | FrostPID1_ITime | I-time frost mode | s | Write | |
| AV | 131 | FrostPID2_ITime | I-time frost mode | s | Write | |
| AV | 132 | FrostPID3_ITime | I-time frost mode | s | Write | |
| AV | 133 | CO2PID_ITime | I-time CO2 mode | s | Write | |
| AV | 134 | RoomPID_ITime | I-time room air cont. | s | Write | |
| AV | 135 | DeIcePID_ITime | I-time de-icing | s | Write | |
| AV | 136 | HumidityPID_ITime | I-time humidity cont. | s | Write | |
| AV | 137 | ExtraPID_ITime | I-time extra pid cont. | s | Write | |
| AV | 138 | PreHeatPID_ITime | I-time preheater | s | Write | |
| AV | 139 | Zone1SupplyPID_ITime | I-time Zone 1 supply | s | Write | |
| AV | 140 | Zone2SupplyPID_ITime | I-time Zone 2 supply | s | Write | |
| AV | 141 | Zone3SupplyPID_ITime | I-time Zone 3 supply | s | Write | |
| AV | 142 | Zone1RoomPID_ITime | I-time Zone 1 room | s | Write | |
| AV | 143 | Zone2RoomPID_ITime | I-time Zone 2 room | s | Write | |
| AV | 144 | Zone3RoomPID_ITime | I-time Zone 3 room | s | Write | |
| AV | 145 | Zone1FrostPID_ITime | I-time Zone 1 frost prot. | s | Write | |
| AV | 146 | Zone2FrostPID_ITime | I-time Zone 2 frost prot. | s | Write | |
| AV | 147 | Zone3FrostPID_ITime | I-time Zone 3 frost prot. | s | Write | |
| AV | 436 | FreshAirPID_ITime | I-time fresh air | s | Write | |
| AV | 437 | EATRPID_ITime | I-time EATR | s | Write | |
| AV | 148 | Zone1SupplyCoolPID_ITime | I-time Zone 1 cooling | s | Write | |
| AV | 149 | Zone2SupplyCoolPID_ITime | I-time Zone 2 cooling | s | Write | |
| AV | 150 | Zone3SupplyCoolPID_ITime | I-time Zone 3 cooling | s | Write | |
| AV | 464 | SAFAirFlowPID_ITime | I-time flow cont. SAF | s | Write | |
| AV | 465 | EAFAirFlowPID_ITime | I-time flow cont. EAF | s | Write | |
| AV | 153 | DeHumidityPID_ITime | I-time de-humidity cont. | s | Write | |
| AV | 439 | RHPID_ITime | I-time RH (same PID as CO2) | s | Write | |
| AV | 154 | SeqAPID_ITime | I-time Seq A air cont. | s | Write | |
| AV | 155 | SeqBPID_ITime | I-time Seq B air cont. | s | Write | |
| AV | 156 | SeqCPID_ITime | I-time Seq C air cont. | s | Write | |
| AV | 157 | SeqDPID_ITime | I-time Seq D air cont. | s | Write | |
| AV | 158 | SeqEPID_ITime | I-time Seq E air cont. | s | Write | |
| AV | 159 | SeqFPID_ITime | I-time Seq F air cont. | s | Write | |
| AV | 160 | SeqGPID_ITime | I-time Seq G air cont. | s | Write | |
| AV | 161 | SeqHPID_ITime | I-time Seq H air cont. | s | Write | |
| AV | 162 | SeqIPID_ITime | I-time Seq I air cont. | s | Write | |
| AV | 163 | SeqJPID_ITime | I-time Seq J air cont. | s | Write | |
| AV | 164 | FreeCoolDayLimit | If outdoor temp has been higher on the day free cool is | Write | ||
| AV | 165 | FreeCoolHighLimit | If outd. temp is higher at night the free cool is stopped | Write | ||
| AV | 166 | FreeCoolLowLimit | If outd. temp is lower at night the free cool is stopped | Write | ||
| AV | 167 | FreeCoolRoomLimit | If room temp is lower at night the free cool is stopped | Write | ||
| PIV | 73 | FreeCoolStartTime | Start time free cool function | h | Write | |
| PIV | 74 | FreeCoolStopTime | Stop time free cool function | h | Write | |
| PIV | 1 | FreeCoolHeatBlockTime | Time in minute to block heat output when start after free cool | Write | ||
| AV | 168 | CO2StartLimit | Level to activate CO2 cont. (ppm) | ppm | Write | |
| AV | 169 | CO2DemandDiff | Diff. for stop of demand cont.led ventilation (ppm) | ppm | Write | |
| AV | 170 | CO2Setpoint | setp. CO2 (ppm) | ppm | Write | |
| PIV | 2 | CO2MinTime | Min time for CO2 cont. (min) | min | Write | |
| AV | 171 | NeedHeatStart | Room temperature to start the unit if support heating is active | Write | ||
| AV | 172 | NeedHeatStop | Room temperature to stop the unit if support heating is active | Write | ||
| AV | 173 | NeedCoolStart | Room temperature to start the unit if support cooling is active | Write | ||
| AV | 174 | NeedCoolStop | Room temperature for stop the unit if support cooling is active | Write | ||
| PIV | 3 | NeedMinTime | Min run time support control | min | Write | |
| MV | 57 | FireDampersAutoMode | Run. mode fire damper | Write | 1=Close, 2=Open, 3=Auto | |
| AV | 175 | DeIcingSetpoint | Setp. de-icing temp | Write | ||
| AV | 176 | DeIcingHyst | Hyst. for stop of de-icing | Write | ||
| PIV | 63 | DeIcingMinTime | Min time for de-icing | min | Write | |
| AV | 177 | DeIcingSAFTempStop | If lower outd. temp the SAF will be stopped at de-icing | Write | ||
| AV | 178 | HumiditySetpoint | setp. humidity room | Write | ||
| AV | 179 | HumidityMaxDuct | Max limit humidity duct | Write | ||
| AV | 180 | HumidityHyst | Hyst. to start humidity cont. after stop max limitation | Write | ||
| AV | 181 | HumidityStartLimit | Start limit in % to start DO signal | Write | ||
| AV | 182 | HumidityStopLimit | Stop limit in % to stop DO signal | Write | ||
| AV | 183 | HumidityNeutralZone | Neutral zone humidity room | Write | ||
| AV | 184 | RoomSetP | Room setp. if room temp cont. function | Write | ||
| AV | 188 | FrostProtSPStop1 | Setp. frost prot. if the ventilation unit is stopped | Write | ||
| AV | 203 | FrostProtSPStop2 | Setp. frost prot. if the ventilation unit is stopped | Write | ||
| AV | 204 | FrostProtSPStop3 | Setp. frost prot. if the ventilation unit is stopped | Write | ||
| AV | 185 | FrostProtSPStopZone1 | Setp. frost prot. zone 1 if the ventilation unit is stopped | Write | ||
| AV | 186 | FrostProtSPStopZone2 | Setp. frost prot. zone 2 if the ventilation unit is stopped | Write | ||
| AV | 187 | FrostProtSPStopZone3 | Setp. frost prot. zone 3 if the ventilation unit is stopped | Write | ||
| AV | 206 | FrostProtSPRun1 | Alarm limit frost prot. | Write | ||
| AV | 207 | FrostProtSPRun2 | Alarm limit frost prot. | Write | ||
| AV | 208 | FrostProtSPRun3 | Alarm limit frost prot. | Write | ||
| AV | 189 | FrostProtSPRunZone1 | Alarm limit frost prot. zone 1 | Write | ||
| AV | 190 | FrostProtSPRunZone2 | Alarm limit frost prot. zone 2 | Write | ||
| AV | 191 | FrostProtSPRunZone3 | Alarm limit frost prot. zone 3 | Write | ||
| AV | 194 | FrostProtPGain1 | P-Gain frost prot. when run (alarm limit+PGain) | Write | ||
| AV | 197 | FrostProtPGain2 | P-Gain frost prot. when run (alarm limit+PGain) | Write | ||
| AV | 200 | FrostProtPGain3 | P-Gain frost prot. when run (alarm limit+PGain) | Write | ||
| AV | 201 | FrostProtPGainZone1 | P-Gain frost prot. zone 1 when run (alarm limit+PGain) | Write | ||
| AV | 202 | FrostProtPGainZone2 | P-Gain frost prot. zone 2 when run (alarm limit+PGain) | Write | ||
| AV | 198 | FrostProtPGainZone3 | P-Gain frost prot. zone 3 when run (alarm limit+PGain) | Write | ||
| AV | 205 | ExtraControllerSetP | Setp. Extra cont.ler | Write | ||
| MV | 53 | ExtraControllerMode | Control mode ex. contr. | Write | 1=Heating, 2=Cooling | |
| MV | 58 | SumAlarm1 | Sum alarm 1 config, defines which alarms that should be on the | Write | 1=Off, 2=A+B+C, 3=A+B, 4=B+C, 5=A+C, 6=A, 7=B, 8=C | |
| MV | 59 | SumAlarm2 | Sum alarm 2 config., defines which alarms that should be on the | Write | 1=Off, 2=A+B+C, 3=A+B, 4=B+C, 5=A+C, 6=A, 7=B, 8=C | |
| PIV | 62 | AlarmOutput | Alarm output of configured alarm number | Write | ||
| BVmin | 8 | AlaAcknowAll | Command to acknowledge all alarms | Write | 0=Off, 1=On | |
| AV | 211 | FilterGuard1Limit_X2 | Alarm limt filter guard 1 X2 (m3/h) - Calibration air flow | Write | ||
| AV | 215 | FilterGuard2Limit_X2 | Alarm limt filter guard 2 X2 (m3/h) - Calibration air flow | Write | ||
| AV | 441 | FilterGuard3Limit_X2 | Alarm limt filter guard 3 X2 (m3/h) - Calibration air flow | Write | ||
| AV | 442 | FilterGuard4Limit_X2 | Alarm limt filter guard 4 X2 (m3/h) - Calibration air flow | Write | ||
| AV | 443 | FilterGuard5Limit_X2 | Alarm limt filter guard 5 X2 (m3/h) - Calibration air flow | Write | ||
| AV | 212 | FilterGuard1Limit_Y2 | Alarm limt filter guard 1 Y2 (Pa) - Calibration filter alarm limit | Write | ||
| AV | 216 | FilterGuard2Limit_Y2 | Alarm limt filter guard 2 Y2 (Pa) - Calibration filter alarm limit | Write | ||
| AV | 444 | FilterGuard3Limit_Y2 | Alarm limt filter guard 3 Y2 (Pa) - Calibration filter alarm limit | Write | ||
| AV | 445 | FilterGuard4Limit_Y2 | Alarm limt filter guard 4 Y2 (Pa) - Calibration filter alarm limit | Write | ||
| AV | 446 | FilterGuard5Limit_Y2 | Alarm limt filter guard 5 Y2 (Pa) - Calibration filter alarm limit | Write | ||
| AV | 217 | RecircSetP | Recirculation setp. | Write | ||
| AV | 218 | RecircSetPOffset | Offset for recirculation setp. | Write | ||
| MV | 51 | RecircTempControl | Enable supply air temp cont. when recirc. run | Write | 1=No temp control, 2=Heating/cooling, 3=Only heating, 4=Only cooling | |
| AV | 219 | RecircMaxRoomTemp | If higher room temp when recirc. run, recirc. damp. is closed and | Write | ||
| MV | 52 | RecircFreeCool | Enable the free cool func. when recirc. run | Write | 1=Off, 2=On | |
| AV | 220 | RecircSAFOffset | Setp. offset if press./flow cont.led SAF | Write | ||
| AV | 221 | RecircEAFOffset | Setp. offset if press./flow cont.led EAF (this is not used) | Write | ||
| PIV | 4 | FilterAlarmTime | Time in month between filter exchange (Service Alarm) | Write | ||
| MV | 56 | SupplyPIDFreeze | Freeze supply PID control | Write | 1=Off, 2=On | |
| AV | 222 | FanComp1X1 | Breakp. 1 (must be lower than breakp. 2) | Write | ||
| AV | 223 | FanComp2X1 | Breakp. 1 (must be lower than breakp. 2) | Write | ||
| AV | 224 | FanComp3X1 | Breakp. 1 (must be lower than breakp. 2) | Write | ||
| AV | 225 | FanComp1Y1 | Comp. breakp. 1 | Write | ||
| AV | 226 | FanComp2Y1 | Comp. breakp. 1 | Write | ||
| AV | 227 | FanComp3Y1 | Comp. breakp. 1 | Write | ||
| AV | 228 | FanComp1X2 | Breakp. 2 (must be higher than breakp. 1) | Write | ||
| AV | 229 | FanComp2X2 | Breakp. 2 (must be higher than breakp. 1) | Write | ||
| AV | 230 | FanComp3X2 | Breakp. 2 (must be higher than breakp. 1) | Write | ||
| AV | 234 | FanComp1Y2 | Comp. breakp. 2 | Write | ||
| AV | 235 | FanComp2Y2 | Comp. breakp. 2 | Write | ||
| AV | 236 | FanComp3Y2 | Comp. breakp. 2 | Write | ||
| AV | 231 | FanComp1X3 | Breakp. 3 (must be higher than breakp. 2) | Write | ||
| AV | 232 | FanComp2X3 | Breakp. 3 (must be higher than breakp. 2) | Write | ||
| AV | 233 | FanComp3X3 | Breakp. 3 (must be higher than breakp. 2) | Write | ||
| AV | 237 | FanComp1Y3 | Comp. breakp. 3 | Write | ||
| AV | 238 | FanComp2Y3 | Comp. breakp. 3 | Write | ||
| AV | 239 | FanComp3Y3 | Comp. breakp. 3 | Write | ||
| AV | 240 | NeutralZone | Neutral zone supply air. | Write | ||
| AV | 575 | NeutralZoneCascade | Neutral zone cascade control | Write | ||
| AV | 241 | FreeCoolSAFOffset | SAF setp. offset if press./flow controlled SAF when free cool | Write | ||
| AV | 242 | FreeCoolEAFOffset | EAF setp. offset if press./flow controlled EAF when free cool | Write | ||
| AV | 243 | Zone1SetP | Setpoint zone 1 (room or supply) | Write | ||
| AV | 244 | Zone2SetP | Setpoint zone 2 (room or supply) | Write | ||
| AV | 245 | Zone3SetP | Setpoint zone 3 (room or supply) | Write | ||
| AV | 246 | Zone1NeutralZone | Neutral zone around supply setp. zone 1 before heat/cool | Write | ||
| AV | 249 | Zone2NeutralZone | Neutral zone around supply setp. zone 2 before heat/cool | Write | ||
| AV | 252 | Zone3NeutralZone | Neutral zone around supply setp. zone 3 before heat/cool | Write | ||
| AV | 253 | Zone1SetpointMax | Max limit of zone 1 supply setp. when cascade cont. | Write | ||
| AV | 254 | Zone2SetpointMax | Max limit of zone 2 supply setp. when cascade cont. | Write | ||
| AV | 250 | Zone3SetpointMax | Max limit of zone 3 supply setp. when cascade cont. | Write | ||
| AV | 251 | Zone1SetpointMin | Min limit of zone 1 supply setp. when cascade cont. | Write | ||
| AV | 247 | Zone2SetpointMin | Min limit of zone 2 supply setp. when cascade cont. | Write | ||
| AV | 248 | Zone3SetpointMin | Min limit of zone 3 supply setp. when cascade cont. | Write | ||
| AV | 255 | DelayedStartDXCool | Minsetpoint deviation to allow DX-cooling | Write | ||
| AV | 256 | DelayedStartDXHeat | Minsetpoint deviation to allow DX-heating | Write | ||
| MV | 78 | S_FrostProtFanReduction1 | Enable fan reduction when freeze risk freeze protection temperature 1 | Write | 1=Off, 2=On | |
| MV | 79 | S_FrostProtFanReduction2 | Enable fan reduction when freeze risk freeze protection temperature 2 | Write | 1=Off, 2=On | |
| MV | 80 | S_FrostProtFanReduction3 | Enable fan reduction when freeze risk freeze protection temperature 3 | Write | 1=Off, 2=On | |
| MV | 81 | S_FrostProtFanReductionZone1 | Enable fan reduction when freeze risk freeze protection temperature zone 1 | Write | 1=Off, 2=On | |
| MV | 82 | S_FrostProtFanReductionZone2 | Enable fan reduction when freeze risk freeze protection temperature zone 2 | Write | 1=Off, 2=On | |
| MV | 83 | S_FrostProtFanReductionZone3 | Enable fan reduction when freeze risk freeze protection temperature zone 3 | Write | 1=Off, 2=On | |
| PIV | 64 | FeedbackDXTimeStart | Time that Supply Pid is freezed when DX-machine is started (sec) | s | Write | |
| PIV | 65 | FeedbackDXTimeDefrost | Time that Supply Pid is freezed after DX-machine has been defrosting (sec) | s | Write | |
| PIV | 66 | FeedbackDXMinRunTime | Min run time DX machine, to avoid involuntary shutdown of the DX | s | Write | |
| PIV | 67 | FeedbackDXMaxTime | Max time if DX machine don't give feedback (min) | min | Write | |
| AV | 540 | PreheatSetp | Setpoint preheater | Write | ||
| AV | 541 | SupplySetpointMaxReduction | Offset max limit supply air - if active DX-heating | Write | ||
| AV | 542 | SupplySetpointMinReduction | Offset max limit supply air - if active DX-heating | Write | ||
| AV | 543 | HPMinSetPDevCool | Min setpoint deviation energy for start cooling (kw) | kW | Write | |
| AV | 544 | HPMinSetPDevHeat | Min setpoint deviation energy for start heating (kw) | kW | Write | |
| MV | 88 | HPPumpMode | Pump run mode (0=Reversible, 1=Only cooling, 2=Only heating) | Write | 1=Reversible, 2=Only cooling, 3=Only heating | |
| PIV | 68 | HPBlockingTime | Blocking time between heating and cooling (0-360min) | min | Write | |
| AV | 545 | FrostLimitPrLimitDev | Pressure deviation (%) for start deicing | % | Write | |
| AV | 570 | ExtDisp_SetpOffset | Actual supply setpoint offset | Write | ||
| AV | 571 | RHSetpoint | setp. RH (%) | % | Write | |
| PIV | 69 | RHMinTime | Min time for RH cont. (min) | min | Write | |
| PIV | 70 | FireDampersRunTime | Run time fire damper | s | Write | |
| PIV | 71 | FireDampersInterval | Test interval fire damper | Write | ||
| PIV | 72 | FireDampersExerciseTime | Test hour fire damper | h | Write | |
| AV | 574 | DXBlockLowOutdoorTemp | Heating mode blocked when exchanger-outdoor temperature is lower | Write | ||
| AV | 576 | Zone1NeutralZoneCascade | Neutral zone around cascade setp. zone 1 before heat/cool | Write | ||
| AV | 577 | Zone2NeutralZoneCascade | Neutral zone around cascade setp. zone 2 before heat/cool | Write | ||
| AV | 578 | Zone3NeutralZoneCascade | Neutral zone around cascade setp. zone 3 before heat/cool | Write | ||
| PIV | 75 | SummerModeSwitchDelay | Delay outdoor temp for switching between summer and winter mode (in minutes) | min | Write | |
| BV | 1 | NeedHeatActive | Is set if ongoing support heating | Read | 0=Inactive, 1=Active | |
| BV | 2 | NeedCoolActive | Is set if ongoing support cooling | Read | 0=Inactive, 1=Active | |
| BV | 3 | DemandCO2Active | Is set if ongoing support CO2 | Read | 0=Inactive, 1=Active | |
| BV | 4 | RecirculationRunActive | Is set if ongoing recycle run | Read | 0=Inactive, 1=Active | |
| BV | 5 | DeIcingActive | Is set if ongoing de-icing | Read | 0=Inactive, 1=Active | |
| BV | 81 | FrostProtFanReductionActive | Is set if ongoing fan reduction when freeze risk | Read | 0=Inactive, 1=Active | |
| AV | 11 | SAFRunTime | Run. Time supply air fan | h | Read | |
| AV | 12 | EAFRunTime | Run. Time extract air fan | h | Read | |
| IV | 1 | DeIcingTime | Number of min for ongoing de-icing | min | Read | |
| IV | 2 | NeedRunTime | No of min in ongoing support heat/cool | min | Read | |
| BV | 7 | SmokeDetector | Smoke detector | Read | 0=Off, 1=On | |
| AV | 257 | RoomTemp | Room temp. 1-4 | Read | ||
| AV | 258 | ExchPressureSAF | Calculated pressure exchanger SAF | Read | ||
| AV | 259 | ExchAirFlowEAF | Calculated flow exchanger, EAF | Read | ||
| AV | 427 | Efficiency | Efficiency for exchanger | % | Read | |
| MVmin | 15 | UnitMode | Unit run mode | Read | 1=Stop, 2=Starting up, 3=Low speed run, 4=Normal speed run, 5=High speed run, 6=Heating support run, 7=Cooling support run, 8=CO2 Run, 9=Free cool run, 10=Fan stop run, 11=Fire run, 12=Smoke run, 13=Recirculation run, 14=DeIcing run, 15=Filter calibration run, 16=Gas evacuation mode | |
| MVmin | 16 | UnitModeControl | Indicates what is triggering the curr. run mode | Read | 1=Nothing, 2=Time schedule, 3=Manual run, 4=Digital Input, 5=Alarm, 6=External control, 7=Service stop, 8=Support run, 9=Filter calibration, 10=Heat pump exercise | |
| MV | 65 | ActiveSeqType | Active seq. type | Read | 1=Heating, 2=Cooling | |
| MV | 66 | ActiveHeatSeqStep | Curr. heat seq. step that's active | Read | 1=None, 2=1, 3=2, 4=3, 5=4, 6=5, 7=6, 8=7, 9=8, 10=9, 11=10 | |
| MV | 67 | ActiveCoolSeqStep | Curr. cool seq. step that's active | Read | 1=None, 2=1, 3=2, 4=3, 5=4, 6=5, 7=6, 8=7, 9=8, 10=9, 11=10 | |
| MV | 68 | ActiveYSeq | Current sequence that's active and controlling | Read | 1=None, 2=A, 3=B, 4=C, 5=D, 6=E, 7=F, 8=G, 9=H, 10=I, 11=J | |
| IV | 3 | CO2RunTime | Number of min for ongoing de-icing | min | Read | |
| AV | 265 | SAF | Cont. signal supply air fan | % | Read | |
| AV | 266 | EAF | Cont. signal extract air fan | % | Read | |
| MV | 69 | SAFSpeed | SAF speed | Read | 1=Off, 2=Low speed, 3=Normal speed, 4=High speed, 5=Manual setpoint, 6=Manual output | |
| MV | 70 | EAFSpeed | EAF speed | Read | 1=Off, 2=Low speed, 3=Normal speed, 4=High speed, 5=Manual setpoint, 6=Manual output | |
| MV | 71 | HumidityMode | Humidity control mode | Read | 1=Not active, 2=Humidification, 3=Dehumidification | |
| AV | 267 | CompLowSpeedSAF | Total comp. low speed SAF | Read | ||
| AV | 268 | CompNormalSpeedSAF | Total comp. normal speed SAF | Read | ||
| AV | 269 | CompHighSpeedSAF | Total comp. high speed SAF | Read | ||
| AV | 270 | CompLowSpeedEAF | Total comp. low speed EAF | Read | ||
| AV | 271 | CompNormalSpeedEAF | Total comp. normal speed EAF | Read | ||
| AV | 272 | CompHighSpeedEAF | Total comp. high speed EAF | Read | ||
| BVmin | 9 | SumAlarm | Sumalarm | Read | 0=Inactive, 1=Active | |
| BV | 10 | SumAlarmA | A-alarm | Read | 0=Inactive, 1=Active | |
| BV | 11 | SumAlarmB | B-alarm | Read | 0=Inactive, 1=Active | |
| BV | 12 | SumAlarmC | C-alarm | Read | 0=Inactive, 1=Active | |
| PIV | 5 | AlarmACount | No of A alarms | Read | ||
| PIV | 6 | AlarmBCount | No of B alarms | Read | ||
| PIV | 7 | AlarmCCount | No of C alarms | Read | ||
| PIV | 8 | SumAlarm1Count | No of SumAlarm1 alarms | Read | ||
| PIV | 9 | SumAlarm2Count | No of SumAlarm2 alarms | Read | ||
| AV | 273 | SupplyPID_SetP | Actual setp. supply air temp. | Read | ||
| AV | 274 | SAFPID_SetP | Actual setp. SAF | Read | ||
| AV | 275 | EAFPID_SetP | Actual setp. EAF | Read | ||
| AV | 276 | SupplyPID_Output | % | Read | ||
| AV | 277 | FrostPID1_Output | Frost prot. cont.ler output | % | Read | |
| AV | 278 | FrostPID2_Output | Frost prot. cont.ler output | % | Read | |
| AV | 279 | FrostPID3_Output | Frost prot. cont.ler output | % | Read | |
| AV | 280 | CO2PID_Output | CO2 cont.ler output | % | Read | |
| AV | 281 | DeIcePID_Output | De-icing cont.ler output | % | Read | |
| AV | 282 | HumidityPID_Output | Hum. cont.ler output | % | Read | |
| AV | 283 | SFP | Actual SFP | Read | ||
| AV | 284 | SFPDay | Day aver. SFP | Read | ||
| AV | 285 | SFPMonth | Month aver. (30d aver.) SFP | Read | ||
| AV | 287 | EnergyFanPwr | Power usage fans | kWh | Read | |
| AV | 288 | EnergyHeaterPwr | Power usage heater | kWh | Read | |
| AV | 286 | EnergyExchangerPwr | Power recovery exchanger | kWh | Read | |
| AV | 289 | SupplyPID_SetP_Cool | Cooling setpoint supply air temperature | Read | ||
| AV | 290 | SupplyPID_SetP_Heat | Heating setpoint supply air temperature | Read | ||
| AV | 291 | DeHumidity_SetP | Dehumidification setpoint | Read | ||
| AV | 292 | Humidity_SetP | Humidification setpoint | Read | ||
| AV | 447 | FilterGuard1CalibrationInitPress | Initial pressure when doing the filter calibration | Read | ||
| AV | 448 | FilterGuard2CalibrationInitPress | Initial pressure when doing the filter calibration | Read | ||
| AV | 449 | FilterGuard3CalibrationInitPress | Initial pressure when doing the filter calibration | Read | ||
| AV | 450 | FilterGuard4CalibrationInitPress | Initial pressure when doing the filter calibration | Read | ||
| AV | 451 | FilterGuard5CalibrationInitPress | Initial pressure when doing the filter calibration | Read | ||
| AV | 452 | FilterGuard1Limit_Calc | Calculated alarmlimit filter guard 1 | Read | ||
| AV | 453 | FilterGuard2Limit_Calc | Calculated alarmlimit filter guard 2 | Read | ||
| AV | 454 | FilterGuard3Limit_Calc | Calculated alarmlimit filter guard 3 | Read | ||
| AV | 455 | FilterGuard4Limit_Calc | Calculated alarmlimit filter guard 4 | Read | ||
| AV | 456 | FilterGuard5Limit_Calc | Calculated alarmlimit filter guard 5 | Read | ||
| AV | 466 | BMS_OutDoorTemp | Outdoor temp received from BACnet/Modbus | Write | ||
| AV | 467 | SequenceA | Sequence A output in auto and manual mode (%) | % | Read | |
| AV | 468 | SequenceB | Sequence B output in auto and manual mode (%) | % | Read | |
| AV | 469 | SequenceC | Sequence C output in auto and manual mode (%) | % | Read | |
| AV | 470 | SequenceD | Sequence D output in auto and manual mode (%) | % | Read | |
| AV | 471 | SequenceE | Sequence E output in auto and manual mode (%) | % | Read | |
| AV | 472 | SequenceF | Sequence F output in auto and manual mode (%) | % | Read | |
| AV | 473 | SequenceG | Sequence G output in auto and manual mode (%) | % | Read | |
| AV | 474 | SequenceH | Sequence H output in auto and manual mode (%) | % | Read | |
| AV | 475 | SequenceI | Sequence I output in auto and manual mode (%) | % | Read | |
| AV | 476 | SequenceJ | Sequence J output in auto and manual mode (%) | % | Read | |
| AV | 537 | IndoorEnthalpy | Indoor entalphy | kJ/kg | Read | |
| AV | 538 | OutdoorEnthalpy | Outdoor entalphy | kJ/kg | Read | |
| MV | 77 | EnthalpyDiff | Indicate if enthalpy outdoor > enthalpy indoor | Read | 1=Not active, 2=Outdoor > Enthalpy indoor | |
| AV | 539 | ExtractFilterGuardFlowRef | Extract air flow (calculated) filter calibration | Read | ||
| MV | 84 | ChangeOver1RunMode | Changeover 1 running mode (actual changeover sequence 1-10) | Read | 1=None, 2=1, 3=2, 4=3, 5=4, 6=5, 7=6, 8=7, 9=8, 10=9, 11=10 | |
| MV | 85 | ChangeOver2RunMode | Changeover 2 running mode (actual changeover sequence 1-10) | Read | 1=None, 2=1, 3=2, 4=3, 5=4, 6=5, 7=6, 8=7, 9=8, 10=9, 11=10 | |
| MV | 86 | FeedbackDXWaitStart | Waiting for DX-compressor to start | Read | 1=Off, 2=On | |
| MV | 87 | FeedbackDXWaitDefrost | Waiting for DX-machine to defrost | Read | 1=Off, 2=On | |
| MV | 103 | FrostLimitMode | Ongoing frost limit air flow reduction mode | Read | 1=Off, 2=Reduction mode, 3=Defrosting mode | |
| BV | 93 | HPHeatingModeNotStarted | Heating mode are not allowed to start | Read | 0=Inactive, 1=Active | |
| BV | 94 | HPCoolingModeNotStarted | Cooling mode are not allowed to start | Read | 0=Inactive, 1=Active | |
| BV | 95 | HPExerciseFailed | Exercise of heat pump could not be performed | Read | 0=Inactive, 1=Active | |
| BV | 96 | HPPIDBlocked | Supply air temperature controller is temporary locked | Read | 0=Inactive, 1=Active | |
| BV | 97 | HPSetPDevToSmall | Not allowed to start – Setpoint deviation to small | Read | 0=Inactive, 1=Active | |
| BV | 98 | HPAirflowToLow | Not allowed to start – air flow is to low | Read | 0=Inactive, 1=Active | |
| BV | 99 | HPFlowDiffToBig | Not allowed to start – Flow difference to big | Read | 0=Inactive, 1=Active | |
| BV | 100 | HPReductionMode | Heat pump running in reduction mode | Read | 0=Inactive, 1=Active | |
| BV | 101 | HPAlarm1 | Al02 - Supercap/ Battery fault | Read | 0=Inactive, 1=Active | |
| BV | 102 | HPAlarm2 | Al63 - Oil return fault alarm | Read | 0=Inactive, 1=Active | |
| BV | 103 | HPAlarm3 | Al64 - Watchdog frequency converter | Read | 0=Inactive, 1=Active | |
| BV | 104 | HPAlarm4 | Al59 - Low-pressure alarm digital input (C1-P1) | Read | 0=Inactive, 1=Active | |
| BV | 105 | HPAlarm5 | Al27 - Low-pressure alarm pressure sensor (C1-P1) | Read | 0=Inactive, 1=Active | |
| BV | 106 | HPAlarm6 | Al32 - High-pressure alarm digital input (C1-P2) | Read | 0=Inactive, 1=Active | |
| BV | 107 | HPAlarm7 | Al26 - High-pressure alarm pressure sensor (C1-P2) | Read | 0=Inactive, 1=Active | |
| BV | 108 | HPAlarm8 | Al58 - High temperature on compressor (C1-T3) | Read | 0=Inactive, 1=Active | |
| BV | 109 | HPAlarm9 | Al03 - Low superheating (C1) | Read | 0=Inactive, 1=Active | |
| BV | 110 | HPAlarm10 | Al65 - High superheating (C1) | Read | 0=Inactive, 1=Active | |
| BV | 111 | HPAlarm11 | Al30 - Expansion-valve fault (C1-EEV) | Read | 0=Inactive, 1=Active | |
| BV | 112 | HPAlarm12 | Al53 - Pressure difference “wrong direction” (C1) | Read | 0=Inactive, 1=Active | |
| BV | 113 | HPAlarm13 | Al55 - Pressure difference “EEV no function” (C1) | Read | 0=Inactive, 1=Active | |
| BV | 114 | HPAlarm14 | Al54 - Pressure difference “no function” (C1) | Read | 0=Inactive, 1=Active | |
| BV | 115 | HPAlarm15 | Al25 - Low-pressure-sensor (C1-P1) | Read | 0=Inactive, 1=Active | |
| BV | 116 | HPAlarm16 | Al21 - High-pressure-sensor (C1-P2) | Read | 0=Inactive, 1=Active | |
| BV | 117 | HPAlarm17 | Al67 - Temperature sensor for evaporator in supply air (C1-T1) | Read | 0=Inactive, 1=Active | |
| BV | 118 | HPAlarm18 | Al68 - Temperature sensor for evaporator in exhaust air (C1-T2) | Read | 0=Inactive, 1=Active | |
| BV | 119 | HPAlarm19 | Al24 - Temperature sensor for compressor 1 on outlet side (C1-T3) | Read | 0=Inactive, 1=Active | |
| BV | 120 | HPAlarm20 | Al72 - Temperature sensor for condensing temperature supply (C1-T4) | Read | 0=Inactive, 1=Active | |
| BV | 121 | HPAlarm21 | Al73 - Temperature sensor for condensing temperature extract (C1-T5) | Read | 0=Inactive, 1=Active | |
| BV | 122 | HPAlarm22 | Al77 - Malfunction frequency converter (VSD) | Read | 0=Inactive, 1=Active | |
| BV | 123 | HPAlarm23 | Al61 - Temperature-sensor - supply air outlet coil (T6) | Read | 0=Inactive, 1=Active | |
| BV | 124 | HPAlarm24 | Al80 - Compressor manual off (C1) | Read | 0=Inactive, 1=Active | |
| BV | 125 | HPAlarm25 | Digital input for feedback peak-heater | Read | 0=Inactive, 1=Active | |
| BV | 126 | HPAlarm26 | Phase control C2 | Read | 0=Inactive, 1=Active | |
| BV | 127 | HPAlarm27 | Compressor alarm 2 (C2) | Read | 0=Inactive, 1=Active | |
| BV | 128 | HPAlarm28 | Low-pressure alarm digital input (C2-P1) | Read | 0=Inactive, 1=Active | |
| BV | 129 | HPAlarm29 | Low-pressure alarm pressure sensor (C2-P1) | Read | 0=Inactive, 1=Active | |
| BV | 130 | HPAlarm30 | High-pressure alarm digital input (C2-P2) | Read | 0=Inactive, 1=Active | |
| BV | 131 | HPAlarm31 | High-pressure alarm pressure sensor (C2-P2) | Read | 0=Inactive, 1=Active | |
| BV | 132 | HPAlarm32 | High temperature on compressor (C2-T3) | Read | 0=Inactive, 1=Active | |
| BV | 133 | HPAlarm33 | Low superheating (C2) | Read | 0=Inactive, 1=Active | |
| BV | 134 | HPAlarm34 | High superheating (C2) | Read | 0=Inactive, 1=Active | |
| BV | 135 | HPAlarm35 | Expansion-valve fault (C2-EEV) | Read | 0=Inactive, 1=Active | |
| BV | 136 | HPAlarm36 | Pressure difference “wrong direction” (C2) | Read | 0=Inactive, 1=Active | |
| BV | 137 | HPAlarm37 | Pressure difference “EEV no function” (C2) | Read | 0=Inactive, 1=Active | |
| BV | 138 | HPAlarm38 | Pressure difference “no function” (C2) | Read | 0=Inactive, 1=Active | |
| BV | 139 | HPAlarm39 | Low-pressure-sensor (C2-P1) | Read | 0=Inactive, 1=Active | |
| BV | 140 | HPAlarm40 | High-pressure-sensor (C2-P2) | Read | 0=Inactive, 1=Active | |
| BV | 141 | HPAlarm41 | Temperature-sensor for evaporator in supply-air (C2-T1) | Read | 0=Inactive, 1=Active | |
| BV | 142 | HPAlarm42 | Temperature-sensor for evaporator in exhaust-air (C2-T2) | Read | 0=Inactive, 1=Active | |
| BV | 143 | HPAlarm43 | Temperature-sensor for compressor 2 on outlet-side (C2-T3) | Read | 0=Inactive, 1=Active | |
| BV | 144 | HPAlarm44 | Temperature-sensor for condensing temperature supply (C2-T4) | Read | 0=Inactive, 1=Active | |
| BV | 145 | HPAlarm45 | Temperature-sensor for condensing temperature extract (C2-T5) | Read | 0=Inactive, 1=Active | |
| AV | 546 | HPEnergyDemand | Actual setpoint deviation energy demand (kw) (air volume [m3/s]* temperature-difference “delta T” | kW | Read | |
| AV | 547 | HPOutput | Heat pump output (0-100%) | % | Read | |
| MV | 89 | HPRequest | Heat pump request (0=Off,1=Heating mode,2=Cooling mode,3=Exercise) | Read | 1=Off, 2=Heating mode, 3=Cooling mode, 4=Exercise | |
| AV | 548 | HPPowerConsumption | Actual electric power consumption of heatpump in W | W | Read | |
| AV | 549 | HPTotalCapacity | Actual total heat pump capacity in % | % | Read | |
| AV | 550 | HPC1Capacity | Actual compressor capacity C1 in % | % | Read | |
| AV | 551 | HPC1SuctionTemp | Actual suction temp °C C1 | Read | ||
| AV | 552 | HPC1HighPressure | Actual high pressure in system in bar C1 | bar | Read | |
| AV | 553 | HPC1CondensingTemp | Actual condensing temp °C C1 | Read | ||
| AV | 554 | HPC1LowPressure | Actual low pressure in system in bar C1 | bar | Read | |
| AV | 555 | HPC1EvaporatingTemp | Actual evaporating temp °C C1 | Read | ||
| AV | 556 | HPC1RefrigerantTemp | Actual temp of refrigerant leaving compressor in °C C1 | Read | ||
| AV | 557 | HPC1EEVOpenDegree | Current degree of opening EEV in % and in steps C1 | % | Read | |
| AV | 558 | HPC1SuperheatEvaporator | Current superheating on evaporator C1 | K | Read | |
| MV | 90 | HPC1Status0 | C1 0=Off/1=On/2=Stopped alarm | Read | 1=Off, 2=On, 3=Stopped alarm | |
| MV | 91 | HPActualMode | Actual mode (0=Cooling, 1=Heating) | Read | 1=Cooling, 2=Heating | |
| MV | 92 | HPOilBoostOn | Status oil boost function on | Read | 1=Off, 2=On | |
| MV | 93 | HPOilReturnOn | Status oil return function on | Read | 1=Off, 2=On | |
| MV | 94 | HPC1HighPressReduceMode | Status high pressure reduce mode C1 | Read | 1=Off, 2=On | |
| MV | 95 | HPC1LowPressReduceMode | Status low pressure reduce mode C1 | Read | 1=Off, 2=On | |
| MV | 96 | HPExercise | Status heat pump exercise | Read | 1=Off, 2=On | |
| MV | 97 | HPC1HighTempReduceMode | Status high temp reduce mode C1 | Read | 1=Off, 2=On | |
| MV | 98 | HPIncreaseAirFlow | Increase airflow to avoid high pressure | Read | 1=Off, 2=On | |
| MV | 99 | HPOperationMode | Actual operation mode | Read | 1=Stop, 2=Stopped alarm, 3=Stopped manual keyboard heat pump, 4=Startup, 5=Heating mode, 6=Cooling mode, 7=Pump down | |
| AV | 559 | HPC2SuctionTemp | Actual suction temp °C C2 | Read | ||
| AV | 560 | HPC2HighPressure | Actual high pressure in system in bar C2 | bar | Read | |
| AV | 561 | HPC2CondensingTemp | Actual condensing temp °C C2 | Read | ||
| AV | 562 | HPC2LowPressure | Actual low pressure in system in bar C2 | bar | Read | |
| AV | 563 | HPC2EvaporatingTemp | Actual evaporating temp °C C2 | Read | ||
| AV | 564 | HPC2RefrigerantTemp | Actual temp of refrigerant leaving compressor in °C C2 | Read | ||
| AV | 565 | HPC2EEVOpenDegree | Current degree of opening EEV in % and in steps C2 | % | Read | |
| AV | 566 | HPC2SuperheatEvaporator | Current superheating on evaporator C2 | K | Read | |
| MV | 100 | HPC2Status | C2 0=Off/1=On/2=Stopped alarm | Read | 1=Off, 2=On, 3=Stopped alarm | |
| MV | 101 | HPC2StopCompressor | Status stop compressor to avoid high pressure in C2 | Read | 1=Off, 2=On | |
| MV | 102 | HPC2LowPressStopMode | Status low pressure stop mode C2 | Read | 1=Off, 2=On | |
| AV | 567 | HPCOP | Calculated COP value | Read | ||
| AV | 568 | ActualSupplySetpointMax | Actual max limit supply air (Used when Cascade) | Read | ||
| AV | 569 | ActualSupplySetpointMin | Actual min limit supply air (Used when Cascade) | Read | ||
| IV | 4 | GDFRuntime | Actual run time in gas evacuatiuon mode in seconds after gas detection | s | Read | |
| IV | 5 | GDFTimeLeftService | Time left until Service (days) – Heat pump refrigerant system | days | Read | |
| BV | 153 | DHFBlockedDewPoint | Read | 0=Inactive, 1=Active | ||
| BV | 154 | DHFReducedCapacity | Read | 0=Inactive, 1=Active | ||
| BV | 155 | DHFHumidReducedCapacity | Read | 0=Inactive, 1=Active | ||
| AV | 572 | DHFLowestTempCalc | Calculated lowest temperature – cooling capacity | Read | ||
| AV | 573 | DHFDewPoint | The calculated and limited dewpoint value | Read | ||
| BV | 156 | BMS_SummerMode | Summer/Winter mode received from BACnet/Modbus | Write | 0=Inactive, 1=Active | |
| BV | 157 | BMS_ChangeOver1 | Cooling/(Heating) changeover 1 mode received from BACnet/Modbus | Write | 0=Inactive, 1=Active | |
| BV | 158 | BMS_ChangeOver2 | Cooling/(Heating) changeover 2 mode received from BACnet/Modbus | Write | 0=Inactive, 1=Active | |
| AV | 579 | CascadePID_SetP_Cool | Cooling setpoint cascade control | Read | ||
| AV | 580 | CascadePID_SetP_Heat | Heating setpoint cascade control | Read | ||
| BV | 159 | HeatRecoveryNotStarted | Heat recovery mode are not allowed to start | Read | 0=Inactive, 1=Active | |
| BV | 160 | CoolRecoveryNotStarted | Cool recovery mode are not allowed to start | Read | 0=Inactive, 1=Active | |
| BV | 13 | ManualControlSeqA | Manual Control Heating (Seq-A) | Read | 0=Off, 1=On | |
| BV | 14 | ManualControlSeqB | Manual Control Exchanger (Seq-B) | Read | 0=Off, 1=On | |
| BV | 15 | ManualControlSeqC | Manual Control Cooling (Seq-C) | Read | 0=Off, 1=On | |
| BV | 16 | ManualControlSeqD | Manual Control Recirculation 1 (Seq-D) | Read | 0=Off, 1=On | |
| BV | 17 | ManualControlSeqE | Manual Control Recirculation 2 (Seq-E) | Read | 0=Off, 1=On | |
| BV | 18 | ManualControlSeqF | Manual Control Fan Setpoint Comp (Seq-F) | Read | 0=Off, 1=On | |
| BV | 19 | ManualControlSeqG | Manual Control Heating 2 (Seq-G) | Read | 0=Off, 1=On | |
| BV | 20 | ManualControlSeqH | Manual Control Cooling 2 (Seq-H) | Read | 0=Off, 1=On | |
| BV | 21 | ManualControlSeqI | Manual Control Exchanger Extract (Seq-I) | Read | 0=Off, 1=On | |
| BV | 22 | ManualControlSeqJ | Manual Control External Heating/Cooling (Seq-J) | Read | 0=Off, 1=On | |
| BV | 23 | ManualOperationAirHandlingUnit | Manual Operation Air Handling Unit | Read | 0=Off, 1=On | |
| BV | 24 | ManualOperationSAF | Manual Operation Supply Air Fan | Read | 0=Off, 1=On | |
| BV | 25 | ManualOperationEAF | Manual Operation Extract Air Fan | Read | 0=Off, 1=On | |
| BV | 26 | ManualOperationDamperRecirculation | Manual Operation Damper Recirculation | Read | 0=Off, 1=On | |
| BV | 27 | ManualOperationDamperOutdoorAir | Manual Operation Damper Outdoor Air | Read | 0=Off, 1=On | |
| BV | 28 | ManualOperationDamperExhaustAir | Manual Operation Damper Exhaust Air | Read | 0=Off, 1=On | |
| BV | 29 | ManualOperationFireDamper | Manual Operation Fire Damper | Read | 0=Off, 1=On | |
| BV | 30 | OutputInManualOperation | Output In Manual Operation | Read | 0=Off, 1=On | |
| BV | 31 | InputInManualOperation | Input In Manual Operation | Read | 0=Off, 1=On | |
| BV | 32 | ManualOperationExtraController | Manual Operation Extra Controller | Read | 0=Off, 1=On | |
| BV | 33 | ManualOperationExternalFanMotor1 | Manual Operation External Fan Motor 1 | Read | 0=Off, 1=On | |
| BV | 34 | ManualOperationExternalFanMotor2 | Manual Operation External Fan Motor 2 | Read | 0=Off, 1=On | |
| BV | 35 | ManualOperationPretreatment | Manual Operation Pretreatment | Read | 0=Off, 1=On | |
| BV | 36 | ExternalOperationSAF | External Operation Supply Air Fan | Read | 0=Off, 1=On | |
| BV | 37 | ExternalOperationEAF | External Operation Extract Air Fan | Read | 0=Off, 1=On | |
| BV | 38 | ServiceStop | Service Stop | Read | 0=Off, 1=On | |
| BV | 39 | WarningFreezeProtection | Warning Freeze Protection | Read | 0=Off, 1=On | |
| BV | 40 | RestartBlockedAfterPowerOn | Restart Blocked After Power On | Read | 0=Off, 1=On | |
| BV | 41 | TestingFireDamper | Testing Fire Damper | Read | 0=Off, 1=On | |
| BV | 42 | ServiceAlarmSmokeDetector | Service Alarm Smoke Detector | Read | 0=Off, 1=On | |
| BV | 43 | SensorErrorSmokeDetector | Sensor Error Smoke Detector | Read | 0=Off, 1=On | |
| BV | 44 | ExtraFanMotor1Running | Extra Fan Motor 1 Running | Read | 0=Off, 1=On | |
| BV | 45 | ExtraFanMotor2Running | Extra Fan Motor 2 Running | Read | 0=Off, 1=On | |
| BV | 46 | AlarmServiceInterval | Alarm Service Interval | Read | 0=Off, 1=On | |
| AV | 423 | DeviationAlarmHumidityControl | Deviation Alarm Humidity Control | Read | ||
| AV | 424 | DeviationAlarmExtraController | Deviation Alarm Extra Controller | Read | ||
| BV | 47 | RotaryExchangerAlarm | Rotary Exchanger Alarm | Read | 0=Off, 1=On | |
| BV | 48 | InternalBatteryError | Internal Battery Error | Read | 0=Off, 1=On | |
| BV | 49 | CommunicationFaultDevice | Communication Fault Device | Read | 0=Off, 1=On | |
| BV | 50 | InternalError | Internal Error | Read | 0=Off, 1=On | |
| BV | 51 | CommunicationFaultBmsMaster | Communication Fault Bms Master | Read | 0=Off, 1=On | |
| BV | 52 | DeviceWarning | Device Warning | Read | 0=Off, 1=On | |
| BV | 53 | DeviceAlarm | Device Alarm | Read | 0=Off, 1=On | |
| BV | 54 | MalfunctionFireDamper | Malfunction Fire Damper | Read | 0=Off, 1=On | |
| AV | 428 | DeviationAlarmSupplyAirFan | Deviation Alarm Supply Air Fan | Read | ||
| AV | 429 | DeviationAlarmExtractAirFan | Deviation Alarm Extract Air Fan | Read | ||
| AV | 430 | DeviationAlarmSupplyTempZone1 | Deviation Alarm Supply Temp Zone 1 | Read | ||
| AV | 431 | DeviationAlarmSupplyTempZone2 | Deviation Alarm Supply Temp Zone 2 | Read | ||
| AV | 432 | DeviationAlarmSupplyTempZone3 | Deviation Alarm Supply Temp Zone 3 | Read | ||
| BV | 62 | DefrostingAlarm | Defrosting Alarm | Read | 0=Off, 1=On | |
| AV | 425 | DeviationAlarmSupplyAirTemperature | Deviation Alarm Supply Air Temperature | Read | ||
| AV | 426 | LeakageHeaterValve | Leakage Heater Valve | Read | ||
| BV | 63 | FireAlarm | Fire Alarm | Read | 0=Off, 1=On | |
| BV | 64 | SmokeAlarm | Smoke Alarm | Read | 0=Off, 1=On | |
| BV | 65 | MalfunctionPumpHeating | Malfunction Pump Heating (Seq-A) | Read | 0=Off, 1=On | |
| BV | 66 | MalfunctionPumpExchanger | Malfunction Pump Exchanger (Seq-B) | Read | 0=Off, 1=On | |
| BV | 67 | MalfunctionPumpCooling | Malfunction Pump Cooling (Seq-C) | Read | 0=Off, 1=On | |
| BV | 68 | MalfunctionPumpRecirculation1 | Malfunction Pump Recirculation 1 (Seq-D) | Read | 0=Off, 1=On | |
| BV | 69 | MalfunctionPumpRecirculation2 | Malfunction Pump Recirculation 2 (Seq-E) | Read | 0=Off, 1=On | |
| BV | 70 | MalfunctionPumpFanSetpointComp | Malfunction Pump Fan Setpoint Comp (Seq-F) | Read | 0=Off, 1=On | |
| BV | 71 | MalfunctionPumpHeating2 | Malfunction Pump Heating 2 (Seq-G) | Read | 0=Off, 1=On | |
| BV | 72 | MalfunctionPumpCooling2 | Malfunction Pump Cooling 2 (Seq-H) | Read | 0=Off, 1=On | |
| BV | 73 | MalfunctionPumpExchangerExtract | Malfunction Pump Exchanger Extract (Seq-I) | Read | 0=Off, 1=On | |
| BV | 74 | MalfunctionPumpExternalHeatingCooling | Malfunction Pump External Heating/Cooling (Seq-J) | Read | 0=Off, 1=On | |
| BV | 75 | MalfunctionExtraFanMotor1 | Malfunction Extra Fan Motor 1 | Read | 0=Off, 1=On | |
| BV | 76 | MalfunctionExtraFanMotor2 | Malfunction Extra Fan Motor 1 | Read | 0=Off, 1=On | |
| BV | 77 | PreHeaterFaultOverheat | Pre-Heater Fault / Overheat | Read | 0=Off, 1=On | |
| BV | 78 | MalfunctionPreheater | Malfunction Preheater | Read | 0=Off, 1=On | |
| BV | 79 | FailSafe | Fail-safe airflow/temperature | Read | 0=Off, 1=On | |
| BV | 80 | ExternalFrostGuard | External frost guard | Read | 0=Off, 1=On | |
| BV | 82 | MalfunctionSAF | Malfunction SAF | Read | 0=Off, 1=On | |
| BV | 83 | MalfunctionEAF | Malfunction EAF | Read | 0=Off, 1=On | |
| BV | 84 | MalfunctionHeatingZone1 | Malfunction Heating Zone 1 | Read | 0=Off, 1=On | |
| BV | 85 | MalfunctionHeatingZone2 | Malfunction Heating Zone 2 | Read | 0=Off, 1=On | |
| BV | 86 | MalfunctionHeatingZone3 | Malfunction Heating Zone 3 | Read | 0=Off, 1=On | |
| BV | 87 | MalfunctionCoolingZone1 | Malfunction Cooling Zone 1 | Read | 0=Off, 1=On | |
| BV | 88 | MalfunctionCoolingZone2 | Malfunction Cooling Zone 2 | Read | 0=Off, 1=On | |
| BV | 89 | MalfunctionCoolingZone3 | Malfunction Cooling Zone 3 | Read | 0=Off, 1=On | |
| BV | 90 | HPSumAlarmB | Heat pump B-alarm | Read | 0=Off, 1=On | |
| BV | 91 | HPSumAlarmC | Heat pump C-alarm | Read | 0=Off, 1=On | |
| BV | 146 | RotaryExchangerAlarm2 | Rotary Exchanger Alarm 2 | Read | 0=Off, 1=On | |
| BV | 147 | Gasdetectionalarm | Gas detection alarm | Read | 0=Off, 1=On | |
| BV | 148 | GasdetectionConfigError | Refrigerant and gas detection-configuration error | Read | 0=Off, 1=On | |
| BV | 149 | GasdetectionService | Service–Heat pump refrigerant system | Read | 0=Off, 1=On | |
| BV | 151 | ServiceHeatpumpSystemBlocked | Gas evacuation, service test period has expired, heat pump blocked until test | Read | 0=Off, 1=On | |
| BV | 150 | SafetyDamperConfigError | Safety damper module is not complete configured in communication device | Read | 0=Off, 1=On | |
| BV | 152 | DewPointNotReachable | Dewpoint not reachable, because of missing cooling capacity | Read | 0=Off, 1=On | |
| AV | 293 | MotorSpeedHzSAF1 | SAF Mot sp. Hz | Hz | Read | |
| AV | 294 | MotorSpeedHzSAF2 | SAF Mot sp. Hz | Hz | Read | |
| AV | 295 | MotorSpeedHzSAF3 | SAF Mot sp. Hz | Hz | Read | |
| AV | 296 | MotorSpeedHzSAF4 | SAF Mot sp. Hz | Hz | Read | |
| AV | 297 | MotorSpeedHzSAF5 | SAF Mot sp. Hz | Hz | Read | |
| AV | 298 | MotorSpeedHzSAF6 | SAF Mot sp. Hz | Hz | Read | |
| AV | 299 | MotorSpeedHzSAF7 | SAF Mot sp. Hz | Hz | Read | |
| AV | 300 | MotorSpeedHzSAF8 | SAF Mot sp. Hz | Hz | Read | |
| AV | 301 | MotorSpeedHzSAF9 | SAF Mot sp. Hz | Hz | Read | |
| AV | 302 | MotorSpeedHzSAF10 | SAF Mot sp. Hz | Hz | Read | |
| AV | 303 | MotorSpeedHzEAF1 | EAF Mot sp. Hz | Hz | Read | |
| AV | 304 | MotorSpeedHzEAF2 | EAF Mot sp. Hz | Hz | Read | |
| AV | 305 | MotorSpeedHzEAF3 | EAF Mot sp. Hz | Hz | Read | |
| AV | 306 | MotorSpeedHzEAF4 | EAF Mot sp. Hz | Hz | Read | |
| AV | 307 | MotorSpeedHzEAF5 | EAF Mot sp. Hz | Hz | Read | |
| AV | 308 | MotorSpeedHzEAF6 | EAF Mot sp. Hz | Hz | Read | |
| AV | 309 | MotorSpeedHzEAF7 | EAF Mot sp. Hz | Hz | Read | |
| AV | 310 | MotorSpeedHzEAF8 | EAF Mot sp. Hz | Hz | Read | |
| AV | 311 | MotorSpeedHzEAF9 | EAF Mot sp. Hz | Hz | Read | |
| AV | 312 | MotorSpeedHzEAF10 | EAF Mot sp. Hz | Hz | Read | |
| AV | 313 | MotorSpeedRpmSAF1 | SAF Mot sp. RPM | rpm | Read | |
| AV | 314 | MotorSpeedRpmSAF2 | SAF Mot sp. RPM | rpm | Read | |
| AV | 315 | MotorSpeedRpmSAF3 | SAF Mot sp. RPM | rpm | Read | |
| AV | 316 | MotorSpeedRpmSAF4 | SAF Mot sp. RPM | rpm | Read | |
| AV | 317 | MotorSpeedRpmSAF5 | SAF Mot sp. RPM | rpm | Read | |
| AV | 318 | MotorSpeedRpmSAF6 | SAF Mot sp. RPM | rpm | Read | |
| AV | 319 | MotorSpeedRpmSAF7 | SAF Mot sp. RPM | rpm | Read | |
| AV | 320 | MotorSpeedRpmSAF8 | SAF Mot sp. RPM | rpm | Read | |
| AV | 321 | MotorSpeedRpmSAF9 | SAF Mot sp. RPM | rpm | Read | |
| AV | 322 | MotorSpeedRpmSAF10 | SAF Mot sp. RPM | rpm | Read | |
| AV | 323 | MotorSpeedRpmEAF1 | EAF Mot sp. RPM | rpm | Read | |
| AV | 324 | MotorSpeedRpmEAF2 | EAF Mot sp. RPM | rpm | Read | |
| AV | 325 | MotorSpeedRpmEAF3 | EAF Mot sp. RPM | rpm | Read | |
| AV | 326 | MotorSpeedRpmEAF4 | EAF Mot sp. RPM | rpm | Read | |
| AV | 327 | MotorSpeedRpmEAF5 | EAF Mot sp. RPM | rpm | Read | |
| AV | 328 | MotorSpeedRpmEAF6 | EAF Mot sp. RPM | rpm | Read | |
| AV | 329 | MotorSpeedRpmEAF7 | EAF Mot sp. RPM | rpm | Read | |
| AV | 330 | MotorSpeedRpmEAF8 | EAF Mot sp. RPM | rpm | Read | |
| AV | 331 | MotorSpeedRpmEAF9 | EAF Mot sp. RPM | rpm | Read | |
| AV | 332 | MotorSpeedRpmEAF10 | EAF Mot sp. RPM | rpm | Read | |
| AV | 333 | MotorCurrentSAF1 | SAF Motor current | A | Read | |
| AV | 334 | MotorCurrentSAF2 | SAF Motor current | A | Read | |
| AV | 335 | MotorCurrentSAF3 | SAF Motor current | A | Read | |
| AV | 336 | MotorCurrentSAF4 | SAF Motor current | A | Read | |
| AV | 337 | MotorCurrentSAF5 | SAF Motor current | A | Read | |
| AV | 338 | MotorCurrentSAF6 | SAF Motor current | A | Read | |
| AV | 339 | MotorCurrentSAF7 | SAF Motor current | A | Read | |
| AV | 340 | MotorCurrentSAF8 | SAF Motor current | A | Read | |
| AV | 341 | MotorCurrentSAF9 | SAF Motor current | A | Read | |
| AV | 342 | MotorCurrentSAF10 | SAF Motor current | A | Read | |
| AV | 343 | MotorCurrentEAF1 | EAF Motor current | A | Read | |
| AV | 344 | MotorCurrentEAF2 | EAF Motor current | A | Read | |
| AV | 345 | MotorCurrentEAF3 | EAF Motor current | A | Read | |
| AV | 346 | MotorCurrentEAF4 | EAF Motor current | A | Read | |
| AV | 347 | MotorCurrentEAF5 | EAF Motor current | A | Read | |
| AV | 348 | MotorCurrentEAF6 | EAF Motor current | A | Read | |
| AV | 349 | MotorCurrentEAF7 | EAF Motor current | A | Read | |
| AV | 350 | MotorCurrentEAF8 | EAF Motor current | A | Read | |
| AV | 351 | MotorCurrentEAF9 | EAF Motor current | A | Read | |
| AV | 352 | MotorCurrentEAF10 | EAF Motor current | A | Read | |
| AV | 353 | MotorPowerSAF1 | SAF Mot power | % | Read | |
| AV | 354 | MotorPowerSAF2 | SAF Mot power | % | Read | |
| AV | 355 | MotorPowerSAF3 | SAF Mot power | % | Read | |
| AV | 356 | MotorPowerSAF4 | SAF Mot power | % | Read | |
| AV | 357 | MotorPowerSAF5 | SAF Mot power | % | Read | |
| AV | 358 | MotorPowerSAF6 | SAF Mot power | % | Read | |
| AV | 359 | MotorPowerSAF7 | SAF Mot power | % | Read | |
| AV | 360 | MotorPowerSAF8 | SAF Mot power | % | Read | |
| AV | 361 | MotorPowerSAF9 | SAF Mot power | % | Read | |
| AV | 362 | MotorPowerSAF10 | SAF Mot power | % | Read | |
| AV | 363 | MotorPowerEAF1 | EAF Mot power | % | Read | |
| AV | 364 | MotorPowerEAF2 | EAF Mot power | % | Read | |
| AV | 365 | MotorPowerEAF3 | EAF Mot power | % | Read | |
| AV | 366 | MotorPowerEAF4 | EAF Mot power | % | Read | |
| AV | 367 | MotorPowerEAF5 | EAF Mot power | % | Read | |
| AV | 368 | MotorPowerEAF6 | EAF Mot power | % | Read | |
| AV | 369 | MotorPowerEAF7 | EAF Mot power | % | Read | |
| AV | 370 | MotorPowerEAF8 | EAF Mot power | % | Read | |
| AV | 371 | MotorPowerEAF9 | EAF Mot power | % | Read | |
| AV | 372 | MotorPowerEAF10 | EAF Mot power | % | Read | |
| PIV | 10 | ActiveFaultSAF1 | SAF fault (bit masked) | Read | ||
| PIV | 11 | ActiveFaultSAF2 | SAF fault (bit masked) | Read | ||
| PIV | 12 | ActiveFaultSAF3 | SAF fault (bit masked) | Read | ||
| PIV | 13 | ActiveFaultSAF4 | SAF fault (bit masked) | Read | ||
| PIV | 14 | ActiveFaultSAF5 | SAF fault (bit masked) | Read | ||
| PIV | 15 | ActiveFaultSAF6 | SAF fault (bit masked) | Read | ||
| PIV | 16 | ActiveFaultSAF7 | SAF fault (bit masked) | Read | ||
| PIV | 17 | ActiveFaultSAF8 | SAF fault (bit masked) | Read | ||
| PIV | 18 | ActiveFaultSAF9 | SAF fault (bit masked) | Read | ||
| PIV | 19 | ActiveFaultSAF10 | SAF fault (bit masked) | Read | ||
| PIV | 20 | ActiveFaultEAF1 | EAF fault (bit masked) | Read | ||
| PIV | 21 | ActiveFaultEAF2 | EAF fault (bit masked) | Read | ||
| PIV | 22 | ActiveFaultEAF3 | EAF fault (bit masked) | Read | ||
| PIV | 23 | ActiveFaultEAF4 | EAF fault (bit masked) | Read | ||
| PIV | 24 | ActiveFaultEAF5 | EAF fault (bit masked) | Read | ||
| PIV | 25 | ActiveFaultEAF6 | EAF fault (bit masked) | Read | ||
| PIV | 26 | ActiveFaultEAF7 | EAF fault (bit masked) | Read | ||
| PIV | 27 | ActiveFaultEAF8 | EAF fault (bit masked) | Read | ||
| PIV | 28 | ActiveFaultEAF9 | EAF fault (bit masked) | Read | ||
| PIV | 29 | ActiveFaultEAF10 | EAF fault (bit masked) | Read | ||
| AV | 373 | ActualSpeedSAF1 | SAF Act. speed | Read | ||
| AV | 374 | ActualSpeedSAF2 | SAF Act. speed | Read | ||
| AV | 375 | ActualSpeedSAF3 | SAF Act. speed | Read | ||
| AV | 376 | ActualSpeedSAF4 | SAF Act. speed | Read | ||
| AV | 377 | ActualSpeedSAF5 | SAF Act. speed | Read | ||
| AV | 378 | ActualSpeedSAF6 | SAF Act. speed | Read | ||
| AV | 379 | ActualSpeedSAF7 | SAF Act. speed | Read | ||
| AV | 380 | ActualSpeedSAF8 | SAF Act. speed | Read | ||
| AV | 381 | ActualSpeedSAF9 | SAF Act. speed | Read | ||
| AV | 382 | ActualSpeedSAF10 | SAF Act. speed | Read | ||
| AV | 383 | ActualSpeedEAF1 | EAF Act. speed | Read | ||
| AV | 384 | ActualSpeedEAF2 | EAF Act. speed | Read | ||
| AV | 385 | ActualSpeedEAF3 | EAF Act. speed | Read | ||
| AV | 386 | ActualSpeedEAF4 | EAF Act. speed | Read | ||
| AV | 387 | ActualSpeedEAF5 | EAF Act. speed | Read | ||
| AV | 388 | ActualSpeedEAF6 | EAF Act. speed | Read | ||
| AV | 389 | ActualSpeedEAF7 | EAF Act. speed | Read | ||
| AV | 390 | ActualSpeedEAF8 | EAF Act. speed | Read | ||
| AV | 391 | ActualSpeedEAF9 | EAF Act. speed | Read | ||
| AV | 392 | ActualSpeedEAF10 | EAF Act. speed | Read | ||
| AV | 393 | AccumPowerSAF1 | SAF Accum. power | Read | ||
| AV | 394 | AccumPowerSAF2 | SAF Accum. power | Read | ||
| AV | 395 | AccumPowerSAF3 | SAF Accum. power | Read | ||
| AV | 396 | AccumPowerSAF4 | SAF Accum. power | Read | ||
| AV | 397 | AccumPowerSAF5 | SAF Accum. power | Read | ||
| AV | 398 | AccumPowerSAF6 | SAF Accum. power | Read | ||
| AV | 399 | AccumPowerSAF7 | SAF Accum. power | Read | ||
| AV | 400 | AccumPowerSAF8 | SAF Accum. power | Read | ||
| AV | 401 | AccumPowerSAF9 | SAF Accum. power | Read | ||
| AV | 402 | AccumPowerSAF10 | SAF Accum. power | Read | ||
| AV | 403 | AccumPowerEAF1 | EAF Accum. power | Read | ||
| AV | 404 | AccumPowerEAF2 | EAF Accum. power | Read | ||
| AV | 405 | AccumPowerEAF3 | EAF Accum. power | Read | ||
| AV | 406 | AccumPowerEAF4 | EAF Accum. power | Read | ||
| AV | 407 | AccumPowerEAF5 | EAF Accum. power | Read | ||
| AV | 408 | AccumPowerEAF6 | EAF Accum. power | Read | ||
| AV | 409 | AccumPowerEAF7 | EAF Accum. power | Read | ||
| AV | 410 | AccumPowerEAF8 | EAF Accum. power | Read | ||
| AV | 411 | AccumPowerEAF9 | EAF Accum. power | Read | ||
| AV | 412 | AccumPowerEAF10 | EAF Accum. power | Read | ||
| PIV | 30 | VVXFault | VVX Fault (bit masked) | Read | ||
| AV | 413 | DamperActPos1 | Damper act. pos. | % | Read | |
| AV | 414 | DamperActPos2 | Damper act. pos. | % | Read | |
| AV | 415 | DamperActPos3 | Damper act. pos. | % | Read | |
| AV | 416 | DamperActPos4 | Damper act. pos. | % | Read | |
| AV | 417 | DamperActPos5 | Damper act. pos. | % | Read | |
| AV | 418 | DamperActPos6 | Damper act. pos. | % | Read | |
| AV | 419 | DamperActPos7 | Damper act. pos. | % | Read | |
| AV | 420 | DamperActPos8 | Damper act. pos. | % | Read | |
| AV | 421 | DamperActPos9 | Damper act. pos. | % | Read | |
| AV | 422 | DamperActPos10 | Damper act. pos. | % | Read | |
| PIV | 31 | DamperFault1 | Damper fault (bit masked) | Read | ||
| PIV | 32 | DamperFault2 | Damper fault (bit masked) | Read | ||
| PIV | 33 | DamperFault3 | Damper fault (bit masked) | Read | ||
| PIV | 34 | DamperFault4 | Damper fault (bit masked) | Read | ||
| PIV | 35 | DamperFault5 | Damper fault (bit masked) | Read | ||
| PIV | 36 | DamperFault6 | Damper fault (bit masked) | Read | ||
| PIV | 37 | DamperFault7 | Damper fault (bit masked) | Read | ||
| PIV | 38 | DamperFault8 | Damper fault (bit masked) | Read | ||
| PIV | 39 | DamperFault9 | Damper fault (bit masked) | Read | ||
| PIV | 40 | DamperFault10 | Damper fault (bit masked) | Read | ||
| AV | 477 | DCVoltageSAF1 | SAF1 DC link voltage | V | Read | |
| AV | 478 | DCVoltageSAF2 | SAF2 DC link voltage | V | Read | |
| AV | 479 | DCVoltageSAF3 | SAF3 DC link voltage | V | Read | |
| AV | 480 | DCVoltageSAF4 | SAF4 DC link voltage | V | Read | |
| AV | 481 | DCVoltageSAF5 | SAF5 DC link voltage | V | Read | |
| AV | 482 | DCVoltageSAF6 | SAF6 DC link voltage | V | Read | |
| AV | 483 | DCVoltageSAF7 | SAF7 DC link voltage | V | Read | |
| AV | 484 | DCVoltageSAF8 | SAF8 DC link voltage | V | Read | |
| AV | 485 | DCVoltageSAF9 | SAF9 DC link voltage | V | Read | |
| AV | 486 | DCVoltageSAF10 | SAF10 DC link voltage | V | Read | |
| AV | 487 | DCVoltageEAF1 | EAF1 DC link voltage | V | Read | |
| AV | 488 | DCVoltageEAF2 | EAF2 DC link voltage | V | Read | |
| AV | 489 | DCVoltageEAF3 | EAF3 DC link voltage | V | Read | |
| AV | 490 | DCVoltageEAF4 | EAF4 DC link voltage | V | Read | |
| AV | 491 | DCVoltageEAF5 | EAF5 DC link voltage | V | Read | |
| AV | 492 | DCVoltageEAF6 | EAF6 DC link voltage | V | Read | |
| AV | 493 | DCVoltageEAF7 | EAF7 DC link voltage | V | Read | |
| AV | 494 | DCVoltageEAF8 | EAF8 DC link voltage | V | Read | |
| AV | 495 | DCVoltageEAF9 | EAF9 DC link voltage | V | Read | |
| AV | 496 | DCVoltageEAF10 | EAF10 DC link voltage | V | Read | |
| AV | 497 | MotorTemperatureSAF1 | Motor temperature SAF1 | °C | Read | |
| AV | 498 | MotorTemperatureSAF2 | Motor temperature SAF2 | °C | Read | |
| AV | 499 | MotorTemperatureSAF3 | Motor temperature SAF3 | °C | Read | |
| AV | 500 | MotorTemperatureSAF4 | Motor temperature SAF4 | °C | Read | |
| AV | 501 | MotorTemperatureSAF5 | Motor temperature SAF5 | °C | Read | |
| AV | 502 | MotorTemperatureSAF6 | Motor temperature SAF6 | °C | Read | |
| AV | 503 | MotorTemperatureSAF7 | Motor temperature SAF7 | °C | Read | |
| AV | 504 | MotorTemperatureSAF8 | Motor temperature SAF8 | °C | Read | |
| AV | 505 | MotorTemperatureSAF9 | Motor temperature SAF9 | °C | Read | |
| AV | 506 | MotorTemperatureSAF10 | Motor temperature SAF10 | °C | Read | |
| AV | 507 | MotorTemperatureEAF1 | Motor temperature EAF1 | °C | Read | |
| AV | 508 | MotorTemperatureEAF2 | Motor temperature EAF2 | °C | Read | |
| AV | 509 | MotorTemperatureEAF3 | Motor temperature EAF3 | °C | Read | |
| AV | 510 | MotorTemperatureEAF4 | Motor temperature EAF4 | °C | Read | |
| AV | 511 | MotorTemperatureEAF5 | Motor temperature EAF5 | °C | Read | |
| AV | 512 | MotorTemperatureEAF6 | Motor temperature EAF6 | °C | Read | |
| AV | 513 | MotorTemperatureEAF7 | Motor temperature EAF7 | °C | Read | |
| AV | 514 | MotorTemperatureEAF8 | Motor temperature EAF8 | °C | Read | |
| AV | 515 | MotorTemperatureEAF9 | Motor temperature EAF9 | °C | Read | |
| AV | 516 | MotorTemperatureEAF10 | Motor temperature EAF10 | °C | Read | |
| AV | 517 | MotorRunHourSAF1 | Running time SAF1 | h | Read | |
| AV | 518 | MotorRunHourSAF2 | Running time SAF2 | h | Read | |
| AV | 519 | MotorRunHourSAF3 | Running time SAF3 | h | Read | |
| AV | 520 | MotorRunHourSAF4 | Running time SAF4 | h | Read | |
| AV | 521 | MotorRunHourSAF5 | Running time SAF5 | h | Read | |
| AV | 522 | MotorRunHourSAF6 | Running time SAF6 | h | Read | |
| AV | 523 | MotorRunHourSAF7 | Running time SAF7 | h | Read | |
| AV | 524 | MotorRunHourSAF8 | Running time SAF8 | h | Read | |
| AV | 525 | MotorRunHourSAF9 | Running time SAF9 | h | Read | |
| AV | 526 | MotorRunHourSAF10 | Running time SAF10 | h | Read | |
| AV | 527 | MotorRunHourEAF1 | Running time EAF1 | h | Read | |
| AV | 528 | MotorRunHourEAF2 | Running time EAF2 | h | Read | |
| AV | 529 | MotorRunHourEAF3 | Running time EAF3 | h | Read | |
| AV | 530 | MotorRunHourEAF4 | Running time EAF4 | h | Read | |
| AV | 531 | MotorRunHourEAF5 | Running time EAF5 | h | Read | |
| AV | 532 | MotorRunHourEAF6 | Running time EAF6 | h | Read | |
| AV | 533 | MotorRunHourEAF7 | Running time EAF7 | h | Read | |
| AV | 534 | MotorRunHourEAF8 | Running time EAF8 | h | Read | |
| AV | 535 | MotorRunHourEAF9 | Running time EAF9 | h | Read | |
| AV | 536 | MotorRunHourEAF10 | Running time EAF10 | h | Read | |
| BI | 1 | DI_SAF | Feedback supply air fan | Read | 0=Off, 1=On | |
| BI | 2 | DI_EAF | Feedback extract air fan | Read | 0=Off, 1=On | |
| BI | 3 | DI_ExtendedRunLowSpeed | Extended operation low speed | Read | 0=Off, 1=On | |
| BI | 4 | DI_ExtendedRunNormalSpeed | Extended operation normal speed | Read | 0=Off, 1=On | |
| BI | 5 | DI_ExtendedRunHighSpeed | Extended operation high speed | Read | 0=Off, 1=On | |
| BI | 6 | DI_FireAlarm | Fire alarm | Read | 0=Off, 1=On | |
| BI | 7 | DI_SmokeAlarm | Smoke alarm | Read | 0=Off, 1=On | |
| BI | 8 | DI_ExternalAlarm | External alarm | Read | 0=Off, 1=On | |
| BI | 9 | DI_FireDamperIndication | Feedback fire damper | Read | 0=Off, 1=On | |
| BI | 10 | DI_SeqIndicationA | Feedback heating (SEQ-A) | Read | 0=Off, 1=On | |
| BI | 11 | DI_SeqIndicationB | Feedback exchanger (SEQ-B) | Read | 0=Off, 1=On | |
| BI | 12 | DI_SeqIndicationC | Feedback cooling (SEQ-C) | Read | 0=Off, 1=On | |
| BI | 13 | DI_SeqIndicationD | Feedback recirculation 1 (SEQ-D) | Read | 0=Off, 1=On | |
| BI | 14 | DI_SeqIndicationE | Feedback recirculation 2 (SEQ-E) | Read | 0=Off, 1=On | |
| BI | 15 | DI_SeqIndicationF | Feedback fan setpoint comp (SEQ-F) | Read | 0=Off, 1=On | |
| BI | 16 | DI_SeqIndicationG | Feedback heating 2 (SEQ-G) | Read | 0=Off, 1=On | |
| BI | 17 | DI_SeqIndicationH | Feedback cooling 2 (SEQ-H) | Read | 0=Off, 1=On | |
| BI | 18 | DI_SeqIndicationI | Feedback exchanger extract (SEQ-I) | Read | 0=Off, 1=On | |
| BI | 19 | DI_SeqIndicationJ | Feedback external heating/cooling (SEQ-J) | Read | 0=Off, 1=On | |
| BI | 20 | DI_Overheating | Overheated electric heater | Read | 0=Off, 1=On | |
| BI | 21 | DI_ExternalStop | External stop | Read | 0=Off, 1=On | |
| BI | 22 | DI_AlarmAcknowledgement | Alarm acknowledgement | Read | 0=Off, 1=On | |
| BI | 23 | DI_Flowswitch | Flow guard | Read | 0=Off, 1=On | |
| BI | 24 | DI_DeIcing | Defrosting guard exhanger | Read | 0=Off, 1=On | |
| BI | 60 | DI_ExchRotation | Rotary exchanger alarm | Read | 0=Off, 1=On | |
| BI | 26 | DI_Frostprotection | Freeze protection guard | Read | 0=Off, 1=On | |
| BI | 27 | DI_RecirculationRun | Start/(Stop) recirculation | Read | 0=Off, 1=On | |
| BI | 28 | DI_ChangeOver1 | Cooling/(Heating) changeover 1 | Read | 0=Off, 1=On | |
| BI | 29 | DI_ChangeOver2 | Cooling/(Heating) changeover 2 | Read | 0=Off, 1=On | |
| BI | 30 | DI_FilterGuard1 | Filter guard 1 supply air | Read | 0=Off, 1=On | |
| BI | 31 | DI_FilterGuard2 | Filter guard 2 extract air | Read | 0=Off, 1=On | |
| BI | 32 | DI_MotorControl1Start | Start/(Stop) extra fan motor 1 | Read | 0=Off, 1=On | |
| BI | 33 | DI_MotorControl2Start | Start/(Stop) extra fan motor 2 | Read | 0=Off, 1=On | |
| BI | 34 | DI_MotorControl1 | Feedback extra fan motor 1 | Read | 0=Off, 1=On | |
| BI | 35 | DI_MotorControl2 | Feedback extra fan motor 2 | Read | 0=Off, 1=On | |
| BI | 36 | DI_ExtraAlarm1 | Extra alarm 1 | Read | 0=Off, 1=On | |
| BI | 37 | DI_ExtraAlarm2 | Extra alarm 2 | Read | 0=Off, 1=On | |
| BI | 38 | DI_ExtraAlarm3 | Extra alarm 3 | Read | 0=Off, 1=On | |
| BI | 39 | DI_ExtraAlarm4 | Extra alarm 4 | Read | 0=Off, 1=On | |
| BI | 40 | DI_ExtraAlarm5 | Extra alarm 5 | Read | 0=Off, 1=On | |
| BI | 41 | DI_ExtraAlarm6 | Extra alarm 6 | Read | 0=Off, 1=On | |
| BI | 42 | DI_ExtraAlarm7 | Extra alarm 7 | Read | 0=Off, 1=On | |
| BI | 43 | DI_ExtraAlarm8 | Extra alarm 8 | Read | 0=Off, 1=On | |
| BI | 44 | DI_ExtraAlarm9 | Extra alarm 9 | Read | 0=Off, 1=On | |
| BI | 45 | DI_ExtraAlarm10 | Extra alarm 10 | Read | 0=Off, 1=On | |
| BI | 46 | DI_SupplyPIDFreeze | Lock PID controller supply | Read | 0=Off, 1=On | |
| BI | 47 | DI_SummerMode | Summer/(Winter) mode | Read | 0=Off, 1=On | |
| BI | 48 | DI_ExtraController | Feedback extra controller | Read | 0=Off, 1=On | |
| BI | 49 | DI_PreHeat | Feedback preheater | Read | 0=Off, 1=On | |
| BI | 50 | DI_Zone1HeatIndication | Feedback heating zone 1 | Read | 0=Off, 1=On | |
| BI | 51 | DI_Zone2HeatIndication | Feedback heating zone 2 | Read | 0=Off, 1=On | |
| BI | 52 | DI_Zone3HeatIndication | Feedback heating zone 3 | Read | 0=Off, 1=On | |
| BI | 53 | DI_Zone1CoolIndication | Feedback cooling zone 1 | Read | 0=Off, 1=On | |
| BI | 54 | DI_Zone2CoolIndication | Feedback cooling zone 2 | Read | 0=Off, 1=On | |
| BI | 55 | DI_Zone3CoolIndication | Feedback cooling zone 3 | Read | 0=Off, 1=On | |
| BI | 56 | DI_Zone1Overheating | Overheated electric heater zone 1 | Read | 0=Off, 1=On | |
| BI | 57 | DI_Zone2Overheating | Overheated electric heater zone 2 | Read | 0=Off, 1=On | |
| BI | 58 | DI_Zone3Overheating | Overheated electric heater zone 3 | Read | 0=Off, 1=On | |
| BI | 61 | DI_FeedbackDXRunIndSeqA | DX-machine run indication Seq A | Read | 0=Off, 1=On | |
| BI | 62 | DI_FeedbackDXRunIndSeqB | DX-machine run indication Seq B | Read | 0=Off, 1=On | |
| BI | 63 | DI_FeedbackDXRunIndSeqC | DX-machine run indication Seq C | Read | 0=Off, 1=On | |
| BI | 64 | DI_FeedbackDXRunIndSeqD | DX-machine run indication Seq D | Read | 0=Off, 1=On | |
| BI | 65 | DI_FeedbackDXRunIndSeqE | DX-machine run indication Seq E | Read | 0=Off, 1=On | |
| BI | 66 | DI_FeedbackDXRunIndSeqF | DX-machine run indication Seq F | Read | 0=Off, 1=On | |
| BI | 67 | DI_FeedbackDXRunIndSeqG | DX-machine run indication Seq G | Read | 0=Off, 1=On | |
| BI | 68 | DI_FeedbackDXRunIndSeqH | DX-machine run indication Seq H | Read | 0=Off, 1=On | |
| BI | 69 | DI_FeedbackDXRunIndSeqI | DX-machine run indication Seq I | Read | 0=Off, 1=On | |
| BI | 70 | DI_FeedbackDXRunIndSeqJ | DX-machine run indication Seq I | Read | 0=Off, 1=On | |
| BI | 71 | DI_FeedbackDXDefSeqA | DX-machine defrost indication Seq A | Read | 0=Off, 1=On | |
| BI | 72 | DI_FeedbackDXDefSeqB | DX-machine defrost indication Seq B | Read | 0=Off, 1=On | |
| BI | 73 | DI_FeedbackDXDefSeqC | DX-machine defrost indication Seq C | Read | 0=Off, 1=On | |
| BI | 74 | DI_FeedbackDXDefSeqD | DX-machine defrost indication Seq D | Read | 0=Off, 1=On | |
| BI | 75 | DI_FeedbackDXDefSeqE | DX-machine defrost indication Seq E | Read | 0=Off, 1=On | |
| BI | 76 | DI_FeedbackDXDefSeqF | DX-machine defrost indication Seq F | Read | 0=Off, 1=On | |
| BI | 77 | DI_FeedbackDXDefSeqG | DX-machine defrost indication Seq G | Read | 0=Off, 1=On | |
| BI | 78 | DI_FeedbackDXDefSeqH | DX-machine defrost indication Seq H | Read | 0=Off, 1=On | |
| BI | 79 | DI_FeedbackDXDefSeqI | DX-machine defrost indication Seq I | Read | 0=Off, 1=On | |
| BI | 80 | DI_FeedbackDXDefSeqJ | DX-machine defrost indication Seq J | Read | 0=Off, 1=On | |
| BI | 81 | DI_FeedbackDXRunIndChangeOver1 | DX-machine run indication change over 1 | Read | 0=Off, 1=On | |
| BI | 82 | DI_FeedbackDXRunIndChangeOver2 | DX-machine run indication change over 2 | Read | 0=Off, 1=On | |
| BI | 83 | DI_FeedbackDXDefChangeOver1 | DX-machine defrost indication change over 1 | Read | 0=Off, 1=On | |
| BI | 84 | DI_FeedbackDXDefChangeOver2 | DX-machine defrost indication change over 2 | Read | 0=Off, 1=On | |
| BI | 85 | DI_FilterGuard3 | Filter guard 3 supply air pre filter | Read | 0=Off, 1=On | |
| BI | 86 | DI_FilterGuard4 | Filter guard 4 supply air end filter | Read | 0=Off, 1=On | |
| BI | 87 | DI_FilterGuard5 | Filter guard 5 extract air pre filter | Read | 0=Off, 1=On | |
| BI | 88 | DI_ExchRotation2 | Rotary exchanger alarm 2 | Read | 0=Off, 1=On | |
| BI | 89 | DI_GasDetectionAcknowledgement | Gas detection alarm acknowledgement | Read | 0=Off, 1=On | |
| AImin | 1 | AI_OutDoorTemp | Outdoor temperature | Read | ||
| AI | 2 | AI_IntakeAirTemp | Intake air temperature | Read | ||
| AImin | 3 | AI_SupplyAirTemp | Supply air temperature | Read | ||
| AI | 4 | AI_ExhaustAirTemp | Exhaust air temp | Read | ||
| AImin | 5 | AI_ExtractAirTemp | Extract air temp | Read | ||
| AI | 6 | AI_RoomTemp1 | Room temperature 1 | Read | ||
| AI | 7 | AI_RoomTemp2 | Room temperature 2 | Read | ||
| AI | 8 | AI_RoomTemp3 | Room temperature 3 | Read | ||
| AI | 9 | AI_RoomTemp4 | Room temperature 4 | Read | ||
| AI | 10 | AI_SAFPressure | Supply air fan pressure | Read | ||
| AI | 11 | AI_EAFPressure | Extract air fan pressure | Read | ||
| AI | 12 | AI_SAFFlow | Supply air fan flow | Read | ||
| AI | 13 | AI_EAFFlow | Extract air fan flow | Read | ||
| AI | 14 | AI_ExchAirFlowSAF | Exchanger SAF pressure sensor | Read | ||
| AI | 15 | AI_ExchPressureEAF | Exchanger EAF pressure sensor | Read | ||
| AI | 16 | AI_DeIcingTemp | De-icing temp exchanger | Read | ||
| AI | 17 | AI_FrostprotTemp1 | Frost protection temp 1 | Read | ||
| AI | 18 | AI_FrostprotTemp2 | Frost protection temp 2 | Read | ||
| AI | 19 | AI_FrostprotTemp3 | Frost protection temp 3 | Read | ||
| AI | 20 | AI_CO2 | CO2 (ppm) | ppm | Read | |
| AI | 21 | AI_HumidityRoom | Humidity room | Read | ||
| AI | 22 | AI_HumidityDuct | Humidity duct | Read | ||
| AI | 23 | AI_HumidityOutDoor | Humidity outdoor | Read | ||
| AI | 24 | AI_ExtraControllerTemp | Extra controller temp | Read | ||
| AI | 25 | AI_ExtSAFControl | External SAF signal control | % | Read | |
| AI | 26 | AI_ExtEAFControl | External EAF signal control | % | Read | |
| AI | 27 | AI_ExtraSensor1 | Extra sensor 1 | Read | ||
| AI | 28 | AI_ExtraSensor2 | Extra sensor 2 | Read | ||
| AI | 29 | AI_ExtraSensor3 | Extra sensor 3 | Read | ||
| AI | 30 | AI_ExtraSensor4 | Extra sensor 4 | Read | ||
| AI | 31 | AI_ExtraSensor5 | Extra sensor 5 | Read | ||
| AI | 32 | AI_ExternalSupplySetP | External Setpoint | Read | ||
| AI | 33 | AI_ExternalFlowSetP | External Setpoint SAF airflow | Read | ||
| AI | 34 | AI_FilterGuard1 | Supply air filter | Read | ||
| AI | 35 | AI_FilterGuard2 | Extract air filter | Read | ||
| AI | 36 | AI_EfficiencyTemp | Temperature efficiency sensor | Read | ||
| AI | 37 | AI_PreHeatTemp | Preheater temp | Read | ||
| AI | 38 | AI_Zone1SupplyTemp | Zone1 supply temp | Read | ||
| AI | 39 | AI_Zone2SupplyTemp | Zone2 supply temp | Read | ||
| AI | 40 | AI_Zone3SupplyTemp | Zone3 supply temp | Read | ||
| AI | 41 | AI_Zone1ExtractTemp | Zone1 extract temp | Read | ||
| AI | 42 | AI_Zone2ExtractTemp | Zone2 sxtract temp | Read | ||
| AI | 43 | AI_Zone3ExtractTemp | Zone3 extract temp | Read | ||
| AI | 44 | AI_Zone1RoomTemp | Zone1 room temp | Read | ||
| AI | 45 | AI_Zone2RoomTemp | Zone2 room temp | Read | ||
| AI | 46 | AI_Zone3RoomTemp | Zone3 room temp | Read | ||
| AI | 47 | AI_Zone1FrostprotTemp | Zone1 frost protection temp | Read | ||
| AI | 48 | AI_Zone2FrostprotTemp | Zone2 frost protection temp | Read | ||
| AI | 49 | AI_Zone3FrostprotTemp | Zone3 frost protection temp | Read | ||
| AI | 50 | AI_FeedbackCoolerValve | Feedback cooler valve | % | Read | |
| AI | 51 | AI_FeedbackOutdoorAirDamper | Feedback outdoor air damper | % | Read | |
| AI | 52 | AI_FeedbackRecircAirDamper | Feedback recirculation damper | % | Read | |
| AI | 53 | AI_EATRDPT | Difference pressure between SAF and EAF (Pa) | Read | ||
| AI | 54 | AI_FilterGuard3 | Supply air pre filter | Read | ||
| AI | 55 | AI_FilterGuard4 | Supply air end filter | Read | ||
| AI | 56 | AI_FilterGuard5 | Extract air pre filter | Read | ||
| AI | 57 | AI_CoolerInletTemp | Temperature entering the cooling coil | Read | ||
| AI | 58 | AI_CoolerInletHumidity | Humidity entering the cooling coil | Read | ||
| AI | 59 | AI_ExchExtractTemp | Exchanger extract air temperature | Read | ||
| BO | 1 | DO_SeqStartA | Read | 0=Off, 1=On | ||
| BO | 2 | DO_SeqStartB | Read | 0=Off, 1=On | ||
| BO | 3 | DO_SeqStartC | Read | 0=Off, 1=On | ||
| BO | 4 | DO_SeqStartD | Read | 0=Off, 1=On | ||
| BO | 5 | DO_SeqStartE | Read | 0=Off, 1=On | ||
| BO | 6 | DO_SeqStartF | Read | 0=Off, 1=On | ||
| BO | 7 | DO_SeqStartG | Read | 0=Off, 1=On | ||
| BO | 8 | DO_SeqStartH | Read | 0=Off, 1=On | ||
| BO | 9 | DO_SeqStartI | Read | 0=Off, 1=On | ||
| BO | 10 | DO_SeqStartJ | Read | 0=Off, 1=On | ||
| BO | 11 | DO_SeqPumpA | Read | 0=Off, 1=On | ||
| BO | 12 | DO_SeqPumpB | Read | 0=Off, 1=On | ||
| BO | 13 | DO_SeqPumpC | Read | 0=Off, 1=On | ||
| BO | 14 | DO_SeqPumpD | Read | 0=Off, 1=On | ||
| BO | 15 | DO_SeqPumpE | Read | 0=Off, 1=On | ||
| BO | 16 | DO_SeqPumpF | Read | 0=Off, 1=On | ||
| BO | 17 | DO_SeqPumpG | Read | 0=Off, 1=On | ||
| BO | 18 | DO_SeqPumpH | Read | 0=Off, 1=On | ||
| BO | 19 | DO_SeqPumpI | Read | 0=Off, 1=On | ||
| BO | 20 | DO_SeqPumpJ | Read | 0=Off, 1=On | ||
| BO | 21 | DO_SAFStart | Read | 0=Off, 1=On | ||
| BO | 22 | DO_EAFStart | Read | 0=Off, 1=On | ||
| BO | 23 | DO_RecirculationAirDamper | Read | 0=Off, 1=On | ||
| BO | 24 | DO_OutdoorAirDamper | Read | 0=Off, 1=On | ||
| BO | 25 | DO_ExhaustAirDamper | Read | 0=Off, 1=On | ||
| BO | 26 | DO_FireDamper | Read | 0=Off, 1=On | ||
| BO | 27 | DO_SumAlarm1 | Read | 0=Off, 1=On | ||
| BO | 28 | DO_SumAlarm2 | Read | 0=Off, 1=On | ||
| BO | 29 | DO_AlarmOutput | Read | 0=Off, 1=On | ||
| BO | 30 | DO_MotorControl1Start | Read | 0=Off, 1=On | ||
| BO | 31 | DO_MotorControl2Start | Read | 0=Off, 1=On | ||
| BO | 32 | DO_TimeChannel1 | Read | 0=Off, 1=On | ||
| BO | 33 | DO_TimeChannel2 | Read | 0=Off, 1=On | ||
| BO | 34 | DO_TimeChannel3 | Read | 0=Off, 1=On | ||
| BO | 35 | DO_TimeChannel4 | Read | 0=Off, 1=On | ||
| BO | 36 | DO_FreeCoolRun | Read | 0=Off, 1=On | ||
| BO | 37 | DO_PreTreatment | Read | 0=Off, 1=On | ||
| BO | 38 | DO_RunIndication | Read | 0=Off, 1=On | ||
| BO | 39 | DO_StepController1Step1 | Read | 0=Off, 1=On | ||
| BO | 40 | DO_StepController1Step2 | Read | 0=Off, 1=On | ||
| BO | 41 | DO_StepController1Step3 | Read | 0=Off, 1=On | ||
| BO | 42 | DO_StepController1Step4 | Read | 0=Off, 1=On | ||
| BO | 43 | DO_StepController2Step1 | Read | 0=Off, 1=On | ||
| BO | 44 | DO_StepController2Step2 | Read | 0=Off, 1=On | ||
| BO | 45 | DO_StepController2Step3 | Read | 0=Off, 1=On | ||
| BO | 46 | DO_StepController2Step4 | Read | 0=Off, 1=On | ||
| BO | 47 | DO_HumidityStart | Read | 0=Off, 1=On | ||
| BO | 48 | DO_ChangeOver1 | Read | 0=Off, 1=On | ||
| BO | 49 | DO_ChangeOver2 | Read | 0=Off, 1=On | ||
| BO | 50 | DO_ExchControl | Read | 0=Off, 1=On | ||
| BO | 51 | DO_Deicing3Start | Read | 0=Off, 1=On | ||
| BO | 52 | DO_ExtraControllerStart | Read | 0=Off, 1=On | ||
| BO | 53 | DO_ExtraControllerPump | Read | 0=Off, 1=On | ||
| BO | 54 | DO_Auxiliary1 | Read | 0=Off, 1=On | ||
| BO | 55 | DO_Auxiliary2 | Read | 0=Off, 1=On | ||
| BO | 56 | DO_Auxiliary3 | Read | 0=Off, 1=On | ||
| BO | 57 | DO_PreHeatStart | Read | 0=Off, 1=On | ||
| BO | 58 | DO_PreHeatPump | Read | 0=Off, 1=On | ||
| BO | 59 | DO_Zone1HeatPump | Read | 0=Off, 1=On | ||
| BO | 60 | DO_Zone2HeatPump | Read | 0=Off, 1=On | ||
| BO | 61 | DO_Zone3HeatPump | Read | 0=Off, 1=On | ||
| BO | 62 | DO_Zone1CoolPump | Read | 0=Off, 1=On | ||
| BO | 63 | DO_Zone2CoolPump | Read | 0=Off, 1=On | ||
| BO | 64 | DO_Zone3CoolPump | Read | 0=Off, 1=On | ||
| BO | 65 | DO_Zone1Step1 | Read | 0=Off, 1=On | ||
| BO | 66 | DO_Zone1Step2 | Read | 0=Off, 1=On | ||
| BO | 67 | DO_Zone2Step1 | Read | 0=Off, 1=On | ||
| BO | 68 | DO_Zone2Step2 | Read | 0=Off, 1=On | ||
| BO | 69 | DO_Zone3Step1 | Read | 0=Off, 1=On | ||
| BO | 70 | DO_Zone3Step2 | Read | 0=Off, 1=On | ||
| BO | 71 | DO_Zone1HeatStart | Read | 0=Off, 1=On | ||
| BO | 72 | DO_Zone2HeatStart | Read | 0=Off, 1=On | ||
| BO | 73 | DO_Zone3HeatStart | Read | 0=Off, 1=On | ||
| BO | 74 | DO_Zone1CoolStart | Read | 0=Off, 1=On | ||
| BO | 75 | DO_Zone2CoolStart | Read | 0=Off, 1=On | ||
| BO | 76 | DO_Zone3CoolStart | Read | 0=Off, 1=On | ||
| BO | 77 | DO_Zone4CoolStart | Read | 0=Off, 1=On | ||
| BO | 78 | DO_GasDetectionAlarm | Read | 0=Off, 1=On | ||
| AO | 1 | AO_SequenceA | Y1 sequence output | % | Read | |
| AO | 2 | AO_SequenceB | Y2 sequence output | % | Read | |
| AO | 3 | AO_SequenceC | Y3 sequence output | % | Read | |
| AO | 4 | AO_SequenceD | Y4 sequence output | % | Read | |
| AO | 5 | AO_SequenceE | Y5 sequence output | % | Read | |
| AO | 6 | AO_SequenceF | Y6 sequence output | % | Read | |
| AO | 7 | AO_SequenceG | Y7 sequence output | % | Read | |
| AO | 8 | AO_SequenceH | Y8 sequence output | % | Read | |
| AO | 9 | AO_SequenceI | Y9 sequence output | % | Read | |
| AO | 10 | AO_SequenceJ | Y10 sequence output | % | Read | |
| AO | 11 | AO_ChangeOver1 | Change over 1 | % | Read | |
| AO | 12 | AO_ChangeOver2 | Change over 2 | % | Read | |
| AO | 13 | AO_SAF | Control valve Supply air fan in | % | Read | |
| AO | 14 | AO_EAF | Control valve Extract air fan | % | Read | |
| AO | 15 | AO_Humidity | Control valve Humidity | % | Read | |
| AO | 16 | AO_StepController1 | Step Controller 1 | % | Read | |
| AO | 17 | AO_StepController2 | Step Controller 2 | % | Read | |
| AO | 18 | AO_ExtraController | Extra Controller | % | Read | |
| AO | 19 | AO_AISignalOutput | AI Signal output | % | Read | |
| AO | 20 | AO_PreHeat | PreHeat output | % | Read | |
| AO | 21 | AO_Zone1Heat | Zone1 Heating | % | Read | |
| AO | 22 | AO_Zone2Heat | Zone2 Heating | % | Read | |
| AO | 23 | AO_Zone3Heat | Zone3 Heating | % | Read | |
| AO | 24 | AO_Zone1Cool | Zone1 Cooling | % | Read | |
| AO | 25 | AO_Zone2Cool | Zone2 Cooling | % | Read | |
| AO | 26 | AO_Zone3Cool | Zone3 Cooling | % | Read | |
| AO | 27 | AO_EATRControl | EATR control function output | % | Read | |
| TL | 1 | TL_IntakeAirTemp | Read | |||
| TL | 2 | TL_IntakeAirTemp_Avg2min | Read | |||
| TL | 3 | TL_SupplyAirTemp | Read | |||
| TL | 4 | TL_SupplyAirTemp_Avg2min | Read | |||
| TL | 5 | TL_ExhaustAirTemp | Read | |||
| TL | 6 | TL_ExhaustAirTemp_Avg2min | Read | |||
| TL | 7 | TL_ExtractAirTemp | Read | |||
| TL | 8 | TL_ExtractAirTemp_Avg2min | Read | |||
| TL | 9 | TL_DeIcingTemp | Read | |||
| TL | 10 | TL_DeIcingTemp_Avg2min | Read | |||
| TL | 11 | TL_FrostprotTemp1 | Read | |||
| TL | 12 | TL_FrostprotTemp1_Avg2min | Read | |||
| TL | 13 | TL_CO2 | Read | |||
| TL | 14 | TL_CO2_Avg2min | Read | |||
| TL | 15 | TL_HumidityRoom | Read | |||
| TL | 16 | TL_HumidityRoom_Avg2min | Read | |||
| TL | 17 | TL_EAFPressure | Read | |||
| TL | 18 | TL_EAFPressure_Avg2min | Read | |||
| TL | 19 | TL_SAFFlow | Read | |||
| TL | 20 | TL_SAFFlow_Avg2min | Read | |||
| TL | 21 | TL_EAFFlow | Read | |||
| TL | 22 | TL_EAFFlow_Avg2min | Read | |||
| TL | 23 | TL_RoomTemp1 | Read | |||
| TL | 24 | TL_RoomTemp1_Avg2min | Read | |||
| TL | 25 | TL_FlowExchSA | Read | |||
| TL | 26 | TL_FlowExchSA_Avg2min | Read | |||
| TL | 27 | TL_FrostprotTemp3 | Read | |||
| TL | 28 | TL_FrostprotTemp3_Avg2min | Read | |||
| TL | 29 | TL_HumiditySupplyAir | Read | |||
| TL | 30 | TL_HumiditySupplyAir_Avg2min | Read | |||
| TL | 31 | TL_EfficiencyTempExch | Read | |||
| TL | 32 | TL_EfficiencyTempExch_Avg2min | Read | |||
| TL | 33 | TLPreHeatTemp | Read | |||
| TL | 34 | TL_PreHeatTemp_Avg2min | Read | |||
| TL | 35 | TL_EATRPressure | Read | |||
| TL | 36 | TL_EATRPressure_Avg2min | Read | |||
| TL | 37 | TL_SeqPumpA | Read | |||
| TL | 38 | TL_SeqPumpA_Avg2min | Read | |||
| TL | 39 | TL_Auxiliary1 | Read | |||
| TL | 40 | TL_Auxiliary1_Avg2min | Read | |||
| TL | 41 | TL_HeatingSeqA | Read | |||
| TL | 42 | TL_HeatingSeqA_Avg2min | Read | |||
| TL | 43 | TL_CoolingSeqC | Read | |||
| TL | 44 | TL_CoolingSeqC_Avg2min | Read | |||
| TL | 45 | TL_ExcSeqB | Read | |||
| TL | 46 | TL_ExcSeqB_Avg2min | Read | |||
| TL | 47 | TL_Recirculation1SeqD | Read | |||
| TL | 48 | TL_Recirculation1SeqD_Avg2min | Read | |||
| TL | 49 | TL_Recirculation2SeqE | Read | |||
| TL | 50 | TL_Recirculation2SeqE_Avg2min | Read | |||
| TL | 51 | TL_Heating2SeqG | Read | |||
| TL | 52 | TL_Heating2SeqG_Avg2min | Read | |||
| TL | 53 | TL_SeqPumpC | Read | |||
| TL | 54 | TL_SeqPumpC_Avg2min | Read | |||
| TL | 55 | TL_Cooling2SeqH | Read | |||
| TL | 56 | TL_Cooling2SeqH_Avg2min | Read | |||
| TL | 57 | TL_ExternalHCSeqJ | Read | |||
| TL | 58 | TL_ExternalHCSeqJ_Avg2min | Read | |||
| TL | 59 | TL_SAFanAO | Read | |||
| TL | 60 | TL_SAFanAO_Avg2min | Read | |||
| TL | 61 | TL_EAFanAO | Read | |||
| TL | 62 | TL_EAFanAO_Avg2min | Read | |||
| TL | 63 | TL_PreHeatAO | Read | |||
| TL | 64 | TL_PreHeatAO_Avg2min | Read | |||
| TL | 65 | TL_EATRControlAO | Read | |||
| TL | 66 | TL_EATRControlAO_Avg2min | Read | |||
| TL | 67 | TL_SAFPressure | Read | |||
| TL | 68 | TL_SAFPressure_Avg2min | Read | |||
| TL | 71 | TL_UnitModeM | Read | |||
| TL | 72 | TL_UnitModeM_Avg2min | Read | |||
| TL | 73 | TL_DefrostIndDxChangover1 | Read | |||
| TL | 74 | TL_DefrostIndDxChangover1_Avg2min | Read | |||
| TL | 75 | TL_DefrostIndDxChangover2 | Read | |||
| TL | 76 | TL_DefrostIndDxChangover2_Avg2min | Read | |||
| TL | 77 | TL_HumidityStartDO | Read | |||
| TL | 78 | TL_HumidityStartDO_Avg2min | Read | |||
| TL | 79 | TL_ChangeOver1DO | Read | |||
| TL | 80 | TL_ChangeOver1DO_Avg2min | Read | |||
| TL | 81 | TL_ChangeOver2DO | Read | |||
| TL | 82 | TL_ChangeOver2DO_Avg2min | Read | |||
| TL | 83 | TL_PreHeatPumpDO | Read | |||
| TL | 84 | TL_PreHeatPumpDO_Avg2min | Read | |||
| TL | 85 | TL_AEfficiency | Read | |||
| TL | 86 | TL_AEfficiency_Avg2min | Read | |||
| TL | 87 | TL_FreeCoolActiveDO | Read | |||
| TL | 88 | TL_FreeCoolActiveDO_Avg2min | Read | |||
| TL | 89 | TL_SupprtConHeatDO | Read | |||
| TL | 90 | TL_SupprtConHeatDO_Avg2min | Read | |||
| TL | 91 | TL_SupprtConCoolDO | Read | |||
| TL | 92 | TL_SupprtConCoolDO_Avg2min | Read | |||
| TL | 93 | TL_SectionDefrostActiveDO | Read | |||
| TL | 94 | TL_SectionDefrostActiveDO_Avg2min | Read | |||
| TL | 95 | TL_BMSOverride | Read | |||
| TL | 96 | TL_BMSOverride_Avg2min | Read | |||
| TL | 97 | TL_ExchExtractTemp | Read | |||
| TL | 98 | TL_ExchExtractTemp_Avg2min | Read | |||
| NC | 1 | AlarmsClassA | Read | |||
| NC | 2 | AlarmsClassB | Read | |||
| NC | 3 | AlarmsClassC | Read | |||
| NC | 4 | EventPoints | Read | |||
| DEV | 1 | Access | Read |
No points match these filters.
Integration notes
- The EDE settable column is 'N' for every object, so access is inferred: S_ (setting) objects and the A_BMS_ inputs are shown writable, everything else read-only.
- State texts come from the EDE state-text table; multistate values are numbered from 1.
- Most temperature, pressure and airflow objects carry BACnet unit NO-UNITS in the EDE, so their units are blank here (temperatures are °C).
- Device instance 114112 is the one in the published EDE; set a unique value per unit.
- Sequences A-J, zones 1-4, heat pump (HP) and up to 10 supply/extract fan motors are generic slots; only configured ones carry data.
- The EDE does not name the data link; Systemair's Access 5 communication manual (472956) describes BACnet/IP on the B-BC profile from 5.0-1-00.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Access controller 5.x (ControllerProgram) BACnet and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Systemair Access controller 5.x (ControllerProgram) BACnet
How many BACnet points does the Systemair Access controller 5.x (ControllerProgram) BACnet have?
This list has 1201 BACnet objects: 59 analog inputs, 27 analog outputs, 545 analog values, 87 binary inputs, 78 binary outputs, 152 binary values, 1 calendar, 1 device, 4 notification classs, 5 schedules, 87 multi-state values, 96 trend logs, 5 integer values, 54 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Systemair Access controller 5.x (ControllerProgram) BACnet BACnet points are writable?
348 of the 1201 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Systemair Access controller 5.x (ControllerProgram) BACnet BACnet documentation?
The source is Access 5.x Modbus variables and BACnet objects (Communication document 5.5-1-01 build 411: BACnet_Access_ControllerProgram EDE, state texts, units) (5.5-1-01 build 411), revision 2026-03, published free by Systemair at https://systemair.canto.global/direct/other/tu4qsjtsu544vba9gqgd0mfv4t/p74ln_6WRy-NkSgEmII-SnQmHFY/original?content-type=application%2Fzip&name=Access+5.x+Modbus+variables+and+BACnet+objects.zip.
What are the minimum BACnet points to integrate the Systemair Access controller 5.x (ControllerProgram) BACnet?
Start with MV 12 AirUnitAutoMode (Off / manual / auto / forced speed command); MV 31 ExternalControl (External extended run or stop command); AV 39 SupplySetpoint (Supply air temperature setpoint); BV 8 AlaAcknowAll (Acknowledge all alarms); MV 15 UnitMode (Actual run mode); MV 16 UnitModeControl (What is driving the current run mode); AI 3 AI_SupplyAirTemp (Supply air temperature); AI 5 AI_ExtractAirTemp (Extract air temperature); AI 1 AI_OutDoorTemp (Outdoor temperature); BV 9 SumAlarm (Any alarm).
How do I enable BMS control of the Systemair Access controller 5.x (ControllerProgram) BACnet?
MV-12 AirUnitAutoMode: 1=OFF, 2=Manual (uses MV-13 AirUnitManual), 3=AUTO, 4=Low speed, 5=Normal speed, 6=High speed. MV-31 ExternalControl adds extended run low/normal/high, external stop, start free cooling and recirculation. MV-32 AirUnitServiceStop stops the unit with top priority.
Can the BMS supply sensor values to the Systemair Access controller 5.x (ControllerProgram) BACnet?
AV-466 BMS_OutDoorTemp takes an outdoor temperature from BACnet/Modbus; BV-156 BMS_SummerMode and BV-157/158 BMS_ChangeOver1/2 take summer/winter and cooling/heating changeover modes. BV-51 CommunicationFaultBmsMaster is an alarm for a BMS master communication fault; the files do not state its timeout.
How do I check these points on the real Access controller 5.x (ControllerProgram) BACnet?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Systemair BACnet points lists
- Air handling unit controller
Systemair Access controller 4.x (4.7) BACnet
Systemair air handling units with the Access controller on software 4.x (object files published for 4.7-1-02 build 78).
Also known as: Systemair Access 4.7, Access 4.7-1-02, Access 4.x, BACnet_Module01_ControllerProgram - VRF BACnet IP gateway
Systemair SYS GW IMS BAC(A) VRF BACnet gateway
Systemair SYSVRF indoor units, outdoor units and high-temperature hydro modules (HTHM) on the outdoor unit X/Y/E bus.
Also known as: SYS GW IMS BAC(A), SYS GW IMS BAC, IMMP-BAC(A), IMMP-BAC, Systemair VRF BACnet gateway, SYS GW gateway
Source: Access 5.x Modbus variables and BACnet objects (Communication document 5.5-1-01 build 411: BACnet_Access_ControllerProgram EDE, state texts, units) · 5.5-1-01 build 411 · rev. 2026-03. Object names, instances and units are reproduced as published; descriptions are our own.