Air handling unit controller · BACnet points list

Systemair Access controller 4.x (4.7) BACnet BACnet points list

Updated 28 October 2026

Short answer

Older Systemair Access controllers (software 4.x) are native BACnet devices; Systemair publishes their objects as an EDE file set with state texts and units. Unlike 5.x, this release maps nearly everything to analog, binary and multistate values (1,050 objects) in numbered blocks: 10000s for commands, 20000s for alarms, 30000s for settings and 40000s for actual values, plus seven schedules (fan speeds and four extra time channels), a holiday calendar and three notification classes. Physical inputs appear as AVs/BVs named AI_ and DI_.

This page lists 1050 BACnet objects for the Systemair Access controller 4.x (4.7) BACnet — 362 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Systemair’s own free documentation, linked below.

Manufacturer
Systemair
Model
Access controller 4.x (4.7) BACnet
Equipment
Air handling unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
1050 (362 writable)
Transport
BACnet IP
Firmware
Access 4.7-1-02 build 78
Also known as
Systemair Access 4.7, Access 4.7-1-02, Access 4.x, BACnet_Module01_ControllerProgram
Source document
Access 4.x Modbus variables and BACnet objects (BACnet object files Access 4.7-1-02 build 78: EDE, state texts, units) · 4.7-1-02 build 78 · rev. 2022-12-14
Download CSV 1050 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Systemair Access controller 4.x (4.7) BACnet

Integration in brief

Use MV-30565 AirUnitAutoMode (AUTO = 3, or force low/normal/high speed) as the BMS run command, or MV-30573 ExternalControl for extended run / external stop. Read MV-40396 UnitMode and MV-40397 UnitModeControl for the actual mode and its cause, map supply/extract temperatures and AV-30588 SupplySetpoint, and use BV-20007..20010 sum alarms with BV-10000 to acknowledge all alarms. A BMS outdoor temperature can be written to AV-30850.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 30565AirUnitAutoModeOff / manual / auto / forced speed commandWrite
MV 30573ExternalControlExternal extended run or stop commandWrite
AV 30588SupplySetpointSupply air temperature setpointWrite
BV 10000AlaAcknowAllAcknowledge all alarmsWrite
MV 40396UnitModeActual run modeRead
MV 40397UnitModeControlWhat is driving the current run modeRead
AV 40292AI_SupplyAirTempSupply air temperatureRead
AV 40294AI_ExtractAirTempExtract air temperatureRead
AV 40290AI_OutDoorTempOutdoor temperatureRead
BV 20007SumAlarmAny alarmRead

Enable & remote start

MV-30565 AirUnitAutoMode: 1=OFF, 2=Manual (state chosen in MV-30566), 3=AUTO, 4=Low, 5=Normal, 6=High speed. MV-30573 ExternalControl gives extended run speeds 1-3 and external stop; MV-30574 AirUnitServiceStop stops the unit with top priority.

Sensors & values from the BMS

AV-30850 BMS_OutDoorTemp accepts an outdoor temperature from the BMS. BV-20196 CommunicationFaultBMS alarms on a BMS master communication fault; the files give no timeout.

Network setup

Watch out for

Systemair Access controller 4.x (4.7) BACnet BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

1050 of 1050 shown
Type
AnalogBinaryMulti-state
Access
Show
Systemair Access controller 4.x (4.7) BACnet BACnet Points List
DescriptionStates
AV30280MinuteMinuteWrite
AV30281HourHourWrite
AV30282WDayDay of Week (1-7, 1=Monday)Write
AV30283WeekWeek numberWrite
AV30284DateDay of monthWrite
AV30285MonthMonthWrite
AV30286YearYearWrite
AV30537AirFlowK_10K-constant for air flow: SAF press.Write
AV30538AirFlowX_10X-constant for air flow: SAF press.Write
AV30539AirFlowK_11K-constant for air flow: EAF press.Write
AV30540AirFlowX_11X-constant for air flow: EAF press.Write
AV30541AirFlowK_12K-constant for air flow: SAF flowWrite
AV30542AirFlowX_12X-constant for air flow: SAF flowWrite
AV30543AirFlowK_13K-constant for air flow: EAF flowWrite
AV30544AirFlowX_13X-constant for air flow: EAF flowWrite
AV30545AirFlowK_14K-constant for air flow: Exch SAF press.Write
AV30546AirFlowX_14X-constant for air flow: Exch SAF press.Write
AV30547AirFlowK_15K-constant for air flow: Exch EAF press.Write
AV30548AirFlowX_15X-constant for air flow: Exch EAF press.Write
AV30568SAFManualSetpointMan. setp. SAF if Man. modeWrite
AV30569SAFManualOutputMan. output SAF if Man. mode%Write
AV30571EAFManualSetpointMan. setp. EAF if Man. modeWrite
AV30572EAFManualOutputMan. output EAF if Man. mode%Write
AV30575SeqPumpOutdLimitYx_1Pump outd. temp. limit seq AWrite
AV30576SeqPumpOutdLimitYx_2Pump outd. temp. limit seq BWrite
AV30577SeqPumpOutdLimitYx_3Pump outd. temp. limit seq CWrite
AV30578SeqPumpOutdLimitYx_4Pump outd. temp. limit seq DWrite
AV30579SeqPumpOutdLimitYx_5Pump outd. temp. limit seq EWrite
AV30580SeqPumpOutdLimitYx_6Pump outd. temp. limit seq FWrite
AV30581SeqPumpOutdLimitYx_7Pump outd. temp. limit seq GWrite
AV30582SeqPumpOutdLimitYx_8Pump outd. temp. limit seq HWrite
AV30583SeqPumpOutdLimitYx_9Pump outd. temp. limit seq IWrite
AV30584SeqPumpOutdLimitYx_10Pump outd. temp. limit seq jWrite
AVmin30588SupplySetpointSetp. supply air temp. when constant supply air temp. func.Write
AV30589ExtractSetpointSetp. extract air temp if extract air temp cont. func.Write
AV30590SupplySetpointMaxMax limit of supply setp. when cascade cont.Write
AV30591SupplySetpointMinMin limit of supply setp. when cascade cont.Write
AV30592SupplySetpOffsetLowTemp. setp. Offset in low speedWrite
AV30593SupplySetpOffsetHighTemp. setp. Offset in high speedWrite
AV30594Curve1_X1Outd. temp for 1st curvep. for outd. comp. setp.Write
AV30595Curve1_X2Outd. temp for 2nd curvep. for outd. comp. setp.Write
AV30596Curve1_X3Outd. temp for 3rd curvep. for outd. comp. setp.Write
AV30597Curve1_X4Outd. temp for 4th curvep. for outd. comp. setp.Write
AV30602Curve1_Y1setp. for 1st curvep. for outd. comp. setp.Write
AV30603Curve1_Y2Setp. for 2nd curvep. for outd. comp. setp.Write
AV30604Curve1_Y3Setp. for 3rd curvep. for outd. comp. setp.Write
AV30605Curve1_Y4Setp. for 4th curvep. for outd. comp. setp.Write
AV30612SAFLowSpeedPressureSetp. low sp. supply air fan press.Write
AV30613SAFNormalSpeedPressureSetp. normal sp. supply air fan press.Write
AV30614SAFHighSpeedPressureSetp. high sp. supply air fan press.Write
AV30615EAFLowSpeedPressureSetp. low sp. Extract air fan press.Write
AV30616EAFNormalSpeedPressureSetp. normal sp. Extract air fan press.Write
AV30617EAFHighSpeedPressureSetp. high sp. Extract air fan press.Write
AV30618SAFLowspeedAirFlowSetp. low sp. SAF air flow.Write
AV30619SAFNormalspeedAirFlowSetp. normal sp. SAF air flow.Write
AV30620SAFHighspeedAirFlowSetp. high sp. SAF air flow.Write
AV30621EAFLowspeedAirFlowSetp. low sp. EAF air flow.Write
AV30622EAFNormalspeedAirFlowSetp. normal sp. EAF air flow.Write
AV30623EAFHighspeedAirFlowSetp. high sp. EAF air flow.Write
AV30624SAFLowSpeedOutputOutput signal low speed SAF if Freq. cont. manually%Write
AV30625SAFNormalSpeedOutputOutput signal normal speed SAF if Freq. cont. manually%Write
AV30626SAFHighspeedOutputOutput signal high speed SAF if Freq. cont. manually%Write
AV30627EAFLowSpeedOutputOutput signal low speed EAF if Freq. cont. manually%Write
AV30628EAFNormalSpeedOutputOutput signal normal speed EAF if Freq. cont. manually%Write
AV30629EAFHighspeedOutputOutput signal high speed EAF if Freq. cont. manually%Write
AV30630SAFLowSpeedPressOffsetOffset SAF press. low speedWrite
AV30631SAFHighSpeedPressOffsetOffset SAF press. high speedWrite
AV30632SAFLowSpeedAirFlowOffsetOffset SAF air flow low speedWrite
AV30633SAFHighSpeedAirFlowOffsetOffset SAF air flow high speedWrite
AV30634SAFLowSpeedOutputOffsetOffset SAF air flow low speed%Write
AV30635SAFHighSpeedOutputOffsetOffset SAF air flow low speed%Write
AV30636EAFLowSpeedPressOffsetOffset EAF press. low speedWrite
AV30637EAFHighSpeedPressOffsetOffset EAF press. high speedWrite
AV30638EAFLowSpeedAirFlowOffsetOffset EAF air flow low speedWrite
AV30639EAFHighSpeedAirFlowOffsetOffset EAF air flow high speedWrite
AV30640EAFLowSpeedOutputOffsetOffset EAF air flow low speed%Write
AV30641EAFHighSpeedOutputOffsetOffset EAF air flow low speed%Write
AV30643SAFManSetpFreeCoolSAF setp. in freecool modeWrite
AV30644SAFManOutFreeCoolSAF man. output in freecool mode%Write
AV30646SAFManSetpFireSAF setp. in fire modeWrite
AV30647SAFManOutFireSAF man. output in fire mode%Write
AV30649SAFManSetpSmokeSAF setp. in smoke modeWrite
AV30650SAFManOutSmokeSAF man. output in smoke mode%Write
AV30652SAFManSetpRecirculationSAF setp. in recirc. modeWrite
AV30653SAFManOutRecirculationSAF man. output in recirc. mode%Write
AV30655EAFManSetpFreeCoolSAF setp. in freecool modeWrite
AV30656EAFManOutFreeCoolEAF man. output in freecool mode%Write
AV30658EAFManSetpFireEAF setp. in fire modeWrite
AV30659EAFManOutFireEAF man. output in fire mode%Write
AV30661EAFManSetpSmokeEAF setp. in smoke modeWrite
AV30662EAFManOutSmokeEAF man. output in smoke mode%Write
AV30664EAFManSetpRecirculationEAF setp. in recirc. modeWrite
AV30665EAFManOutRecirculationEAF man. output in recirc. mode%Write
AV30666EAFFrequencyFactFactor for controlling EAF if CAV fan cont. is configuredWrite
AV30667ExtractPID_PbandP-band Extract air cont.Write
AV30668ExtractPID_ItimeI-time Extract air cont.Write
AV30669SAFPID_PbandP-band press. cont. SAFWrite
AV30670SAFPID_ItimeI-time press. cont. SAFWrite
AV30671EAFPID_PbandP-band press. cont. EAFWrite
AV30672EAFPID_ItimeI-time press. cont. EAFWrite
AV30673FrostPID1_PBandP-band frost modeWrite
AV30674FrostPID1_ITimeI-time frost modeWrite
AV30675FrostPID2_PbandP-band frost modeWrite
AV30676FrostPID2_ITimeI-time frost modeWrite
AV30677FrostPID3_PbandP-band frost modeWrite
AV30678FrostPID3_ITimeI-time frost modeWrite
AV30679CO2PID_PbandP-band CO2 modeWrite
AV30680CO2PID_ItimeI-time CO2 modeWrite
AV30681RoomPID_PbandP-band room air cont.Write
AV30682RoomPID_ItimeI-time room air cont.Write
AV30683DeIcePID_PbandP-band de-icingWrite
AV30684DeIcePID_ItimeI-time de-icingWrite
AV30685HumidityPID_PbandP-band humidity cont.Write
AV30686HumidityPID_ItimeI-time humidity cont.Write
AV30687ExtraPID_PbandP-band extra pid cont.Write
AV30688ExtraPID_ItimeI-time extra pid cont.Write
AV30689SAFAirFlowPID_PbandP-band flow cont. SAFWrite
AV30690SAFPIDflow_ItimeI-time flow cont. SAFWrite
AV30691EAFAirFlowPID_PbandP-band flow cont. EAFWrite
AV30692EAFPIDflow_ItimeI-time flow cont. EAFWrite
AV30693SeqY1PID_PbandP-band Seq A air cont.Write
AV30694SeqY1PID_ITimeI-time Seq A air cont.Write
AV30695SeqY2PID_PbandP-band Seq B air cont.Write
AV30696SeqY2PID_ITimeI-time Seq B air cont.Write
AV30697SeqY3PID_PbandP-band Seq C air cont.Write
AV30698SeqY3PID_ITimeI-time Seq C air cont.Write
AV30699SeqY4PID_PbandP-band Seq D air cont.Write
AV30700SeqY4PID_ITimeI-time Seq D air cont.Write
AV30701SeqY5PID_PbandP-band Seq E air cont.Write
AV30702SeqY5PID_ITimeI-time Seq E air cont.Write
AV30703SeqY6PID_PbandP-band Seq F air cont.Write
AV30704SeqY6PID_ITimeI-time Seq F air cont.Write
AV30705SeqY7PID_PbandP-band Seq G air cont.Write
AV30706SeqY7PID_ITimeI-time Seq G air cont.Write
AV30707SeqY8PID_PbandP-band Seq H air cont.Write
AV30708SeqY8PID_ITimeI-time Seq H air cont.Write
AV30709SeqY9PID_PbandP-band Seq I air cont.Write
AV30710SeqY9PID_ITimeI-time Seq I air cont.Write
AV30711SeqY10PID_PbandP-band Seq J air cont.Write
AV30712SeqY10PID_ITimeI-time Seq J air cont.Write
AV30714AOManual_HumidityHumidification/Dehumidification cont. output if man. mode%Write
AV30716AOManual_ExtraControllerExtra contr. output if man. mode%Write
AV30718AOManual_SequenceY1Seq.A contr. output if man. on mode%Write
AV30720AOManual_SequenceY2Seq.B contr. output if man. on mode%Write
AV30722AOManual_SequenceY3Seq.C contr. output if man. on mode%Write
AV30724AOManual_SequenceY4Seq.D contr. output if man. on mode%Write
AV30726AOManual_SequenceY5Seq.E contr. output if man. on mode%Write
AV30728AOManual_SequenceY6Seq.F contr. output if man. on mode%Write
AV30730AOManual_SequenceY7Seq.G contr. output if man. on mode%Write
AV30732AOManual_SequenceY8Seq.H contr. output if man. on mode%Write
AV30734AOManual_SequenceY9Seq.I contr. output if man. on mode%Write
AV30736AOManual_SequenceY10Seq.J contr. output if man. on mode%Write
AV30737FreeCoolDayLimitIf outdoor temp has been higher on the day free cool isWrite
AV30738FreeCoolHighLimitIf outd. temp is higher at night the free cool is stoppedWrite
AV30739FreeCoolLowLimitIf outd. temp is lower at night the free cool is stoppedWrite
AV30740FreeCoolRoomLimitIf room temp is lower at night the free cool is stoppedWrite
AV30741FreeCoolStartTimeStart time free cool functionWrite
AV30742FreeCoolStopTimeStop time free cool functionWrite
AV30743FreeCoolHeatBlockTimeTime in minute to block heat output when start after free coolWrite
AV30744CO2StartLimitLevel to activate CO2 cont. (ppm)ppmWrite
AV30745CO2DemandDiffDiff. for stop of demand cont.led ventilation (ppm)ppmWrite
AV30746CO2Setpointsetp. CO2 (ppm)ppmWrite
AV30747CO2MinTimeMin time for CO2 cont. (min)ppmWrite
AV30748NeedControlEnable support control if the unit is shut downWrite
AV30749NeedHeatStartRoom temp for start the unit if intermittent heating cont. is activeWrite
AV30750NeedHeatStopRoom temp for stop the unit if intermittent heating cont. is activeWrite
AV30751NeedCoolStartRoom temp for start the unit if intermittent cooling cont. is activeWrite
AV30752NeedCoolStopRoom temp for stop the unit if intermittent cooling cont. is activeWrite
AV30753NeedMinTimeMin. time (min) for intermittent cont. and demand cont.Write
AV30755DeIcingSetpointSetp. de-icing tempWrite
AV30756DeIcingHystHyst. for stop of de-icingWrite
AV30757DeIcingMinTimeMin time for de-icingWrite
AV30758DeIcingSAFTempStopIf lower outd. temp the SAF will be stopped at de-icingWrite
AV30759HumiditySetpointsetp. humidity roomWrite
AV30760HumidityMaxDuctMax limit humidity ductWrite
AV30761HumidityHystHyst. to start humidity cont. after stop max limitationWrite
AV30762HumidityMaxDiffMax allowed diff. between setp. and hum. in room before alarm%Write
AV30763HumidityStartLimitStart limit in % to start DO signal%Write
AV30764HumidityStopLimitStop limit in % to stop DO signal%Write
AV30765RoomSetPRoom setp. if room temp cont. functionWrite
AV30766FrostProtSPRun_1Alarm limit frost prot.Write
AV30767FrostProtSPStop_1Setp. frost prot. if the ventilation unit is stoppedWrite
AV30768FrostProtPGain_1P-Gain frost prot. when run (alarm limit+PGain)Write
AV30769FrostProtSPRun_2Alarm limit frost prot.Write
AV30770FrostProtSPStop_2Setp. frost prot. if the ventilation unit is stoppedWrite
AV30771FrostProtPGain_2P-Gain frost prot. when run (alarm limit+PGain)Write
AV30772FrostProtSPRun_3Alarm limit frost prot.Write
AV30773FrostProtSPStop_3Setp. frost prot. if the vent. unit is stoppedWrite
AV30774FrostProtPGain_3P-Gain frost prot. when run (alarm limit+PGain)Write
AV30775ExtraControllerSetPSetp. Extra cont.lerWrite
AV30779AlarmOutputAlarm output of configured alarm numberWrite
AV30780SupplyMaxDiffMax cont. deviation supply air tempWrite
AV30781SupplyHighAlarmLimitHigh alarm limit supply air tempWrite
AV30782SupplyLowAlarmLimitLow alarm limit supply air tempWrite
AV30783EfficiencyLowLimitLow efficiency%Write
AV30784RoomHighLimitHigh alarm limit room air tempWrite
AV30785RoomLowLimitLow alarm limit room air tempWrite
AV30786ExtractAirTempHighHigh alarm limit Extract air tempWrite
AV30787ExtractAirTempLowLow alarm limit Extract air tempWrite
AV30788SAFMaxDiffPressureMax cont. dev. press. SAFWrite
AV30789EAFMaxDiffPressureMax cont. dev. press. EAFWrite
AV30790RecircSetPRecirculation setp.Write
AV30792RecircMaxRoomTempIf higher room temp when recirc. run, recirc. damp. is closed andWrite
AV30793RecircFreeCoolEnable the free cool func. when recirc. runWrite
AV30794RecircSAFOffsetSetp. offset if press./flow cont.led SAFWrite
AV30795RecircEAFOffsetSetp. offset if press./flow cont.led EAF (this is not used)Write
AV30796RecircSetPOffsetOffset for recirculation setp.Write
AV30797FilterAlarmTimeTime in month between filter exchange (Service Alarm)Write
AV30798ExtraSensor1HighLimitAl. limit high temp ex. sensor 1Write
AV30799ExtraSensor2HighLimitAl. limit high temp ex. sensor 2Write
AV30800ExtraSensor3HighLimitAl. limit high temp ex. sensor 3Write
AV30801ExtraSensor4HighLimitAl. limit high temp ex. sensor 4Write
AV30802ExtraSensor5HighLimitAl. limit high temp ex. sensor 5Write
AV30803ExtraSensor1LowLimitAl. limit low temp ex. sensor 1Write
AV30804ExtraSensor2LowLimitAl. limit low temp ex. sensor 2Write
AV30805ExtraSensor3LowLimitAl. limit low temp ex. sensor 3Write
AV30806ExtraSensor4LowLimitAl. limit low temp ex. sensor 4Write
AV30807ExtraSensor5LowLimitAl. limit low temp ex. sensor 5Write
AV30808SelectedSensor1Select sensor 1 for high low alarmWrite
AV30809SelectedSensor1HighLimitAl. limit high temp sel. sensor 1Write
AV30810SelectedSensor1LowLimitAl. limit low temp sel. sensor 1Write
AV30811SelectedSensor2Select sensor 2 for high low Al.Write
AV30812SelectedSensor2HighLimitAl. limit high temp sel. sensor 1Write
AV30813SelectedSensor2LowLimitAl. limit low temp sel. sensor 1Write
AV30815FanComp1X1Breakp. 1 (must be lower than breakp. 2)Write
AV30816FanComp1Y1Comp. breakp. 1Write
AV30817FanComp1X2Breakp. 2 (must be higher than breakp. 1)Write
AV30818FanComp1Y2Comp. breakp. 2Write
AV30819FanComp1X3Breakp. 3 (must be higher than breakp. 2)Write
AV30820FanComp1Y3Comp. breakp. 3Write
AV30821FanComp2X1Breakp. 1 (must be lower than breakp. 2)Write
AV30822FanComp2Y1Comp. breakp. 1Write
AV30823FanComp2X2Breakp. 2 (must be higher than breakp. 1)Write
AV30824FanComp2Y2Comp. breakp. 2Write
AV30825FanComp2X3Breakp. 3 (must be higher than breakp. 2)Write
AV30826FanComp2Y3Comp. breakp. 3Write
AV30827FanComp3X1Breakp. 1 (must be lower than breakp. 2)Write
AV30828FanComp3Y1Comp. breakp. 1Write
AV30829FanComp3X2Breakp. 2 (must be higher than breakp. 1)Write
AV30830FanComp3Y2Comp. breakp. 2Write
AV30831FanComp3X3Breakp. 3 (must be higher than breakp. 2)Write
AV30832FanComp3Y3Comp. breakp. 3Write
AV30833NeutralZoneNeutral zone supply air.Write
AV30834FreeCoolSAFOffsetSAF setp. offset if press./flow controlled SAF when free coolWrite
AV30835FreeCoolEAFOffsetEAF setp. offset if press./flow controlled EAF when free coolWrite
AV30838FilterGuard1Limit_X2Filter guard 1 calibration air flowWrite
AV30839FilterGuard1Limit_Y2Filter guard 1 calibration filter alarm limit pressure at air flowWrite
AV30842FilterGuard2Limit_X2Filter guard 2 calibration air flowWrite
AV30843FilterGuard2Limit_Y2Filter guard 2 calibration filter alarm limit pressure at air flowWrite
AV30844SummerModeSupplySetpointSupply temp setp. at summer timeWrite
AV30845SummerModeOutdoortempOutd. temp for switching bet. summer and winterWrite
AV30850BMS_OutDoorTempOutdoor temperature from BMS systemWrite
AV30851EnergyHeaterLeakagedTHeater valve leakage delta TWrite
AV30852Zone1SetPSetpoint zone 1 (room or supply)Write
AV30853Zone2SetPSetpoint zone 2 (room or supply)Write
AV30854Zone3SetPSetpoint zone 3 (room or supply)Write
AV30855Zone1SetpointMaxMax limit of zone 1 supply setp. when cascade cont.Write
AV30856Zone1SetpointMinMin limit of zone 1 supply setp. when cascade cont.Write
AV30857Zone2SetpointMaxMax limit of zone 2 supply setp. when cascade cont.Write
AV30858Zone2SetpointMinMin limit of zone 2 supply setp. when cascade cont.Write
AV30859Zone3SetpointMaxMax limit of zone 3 supply setp. when cascade cont.Write
AV30860Zone3SetpointMinMin limit of zone 3 supply setp. when cascade cont.Write
AV30861Zone1NeutralZoneNeutral zone around supply setp. zone 1 before heat/coolWrite
AV30862Zone2NeutralZoneNeutral zone around supply setp. zone 2 before heat/coolWrite
AV30863Zone3NeutralZoneNeutral zone around supply setp. zone 3 before heat/coolWrite
AV30864FrostProtSPRunZone1Alarm limit frost prot. zone 1Write
AV30865FrostProtSPStopZone1Setp. frost prot. zone 1 if the ventilation unit is stoppedWrite
AV30866FrostProtPGainZone1P-Gain frost prot. zone 1 when run (alarm limit+PGain)Write
AV30867FrostProtSPRunZone2Alarm limit frost prot. zone 2Write
AV30868FrostProtSPStopZone2Setp. frost prot. zone 2 if the ventilation unit is stoppedWrite
AV30869FrostProtPGainZone2P-Gain frost prot. zone 2 when run (alarm limit+PGain)Write
AV30870FrostProtSPRunZone3Alarm limit frost prot. zone 3Write
AV30871FrostProtSPStopZone3Setp. frost prot. zone 3 if the ventilation unit is stoppedWrite
AV30872FrostProtPGainZone3P-Gain frost prot. zone 3 when run (alarm limit+PGain)Write
AV30885DelayedStartDXCoolMinsetpoint deviation to allow DX-coolingWrite
AV30886DelayedStartDXHeatMinsetpoint deviation to allow DX-heatingWrite
AV30887HumidityNeutralZoneNeutral zone humidity roomWrite
AV30914FilterGuard3Limit_X2Filter guard 3 calibration air flowWrite
AV30915FilterGuard3Limit_Y2Filter guard 3 calibration filter alarm limit pressure at air flowWrite
AV30916FilterGuard4Limit_X2Filter guard 4 calibration air flowWrite
AV30917FilterGuard4Limit_Y2Filter guard 4 calibration filter alarm limit pressure at air flowWrite
AV30918FilterGuard5Limit_X2Filter guard 5 calibration air flowWrite
AV30919FilterGuard5Limit_Y2Filter guard 5 calibration filter alarm limit pressure at air flowWrite
AV30920FeedbackDXTimeStartTime that Supply Pid is freezed when DX-machine is started (sec)sWrite
AV30921FeedbackDXTimeDefrostTime that Supply Pid is freezed after DX-machine has been defrosting (sec)sWrite
AV30922FeedbackDXMinRunTimeMin run time DX machine, to avoid involuntary shutdown of the DXsWrite
AV30923FeedbackDXMaxTimeMax time if DX machine don't give feedback (min)minWrite
AV40250AI_1AI1Read
AV40251AI_2AI2Read
AV40252AI_3AI3Read
AV40253AI_4AI4Read
AV40254AI_5AI5 (UI1 on CU283)Read
AV40255AI_6AI6 (UI2 on CU283)Read
AV40256AI_7AI7 (UI3 on CU283)Read
AV40257AI_8AI8 (UI4 on CU283)Read
AV40258AIExp1_1AI1 Exp. Unit 1Read
AV40259AIExp1_2AI2 Exp. Unit 1Read
AV40260AIExp1_3AI3 Exp. Unit 1Read
AV40261AIExp1_4AI4 Exp. Unit 1Read
AV40262AIExp1_5UI1 Exp. Unit 1Read
AV40263AIExp1_6UI2 Exp. Unit 1Read
AV40264AIExp1_7UI3 Exp. Unit 1Read
AV40265AIExp1_8UI4 Exp. Unit 1Read
AV40266AIExp2_1AI1 Exp. Unit 2Read
AV40267AIExp2_2AI2 Exp. Unit 2Read
AV40268AIExp2_3AI3 Exp. Unit 2Read
AV40269AIExp2_4AI4 Exp. Unit 2Read
AV40270AIExp2_5UI1 Exp. Unit 2Read
AV40271AIExp2_6UI2 Exp. Unit 2Read
AV40272AIExp2_7UI3 Exp. Unit 2Read
AV40273AIExp2_8UI4 Exp. Unit 2Read
AV40274AI_9AI9Read
AV40275AI_10AI SmokeRead
AV40276AI_11UI1Read
AV40277AI_12UI2Read
AV40278AI_13UI3Read
AV40279AI_14UI4Read
AVmin40290AI_OutDoorTempOutdoor temp.Read
AV40291AI_IntakeAirTempIntake air temp.Read
AVmin40292AI_SupplyAirTempSupply air temp.Read
AV40293AI_ExhaustAirTempExhaust air tempRead
AVmin40294AI_ExtractAirTempExtract air tempRead
AV40295AI_RoomTemp1Room temp. 1Read
AV40296AI_RoomTemp2Room temp. 2Read
AV40297AI_RoomTemp3Room temp. 3Read
AV40298AI_RoomTemp4Room temp. 4Read
AV40299AI_SAFPressureSupply air fan press.Read
AV40300AI_EAFPressureExtract air fan press.Read
AV40301AI_SAFFlowSupply air fan flowRead
AV40302AI_EAFFlowExtract air fan flowRead
AV40303ExchPressureSAFExch. SAF press. sensorRead
AV40304AI_ExchPressureEAFExch. EAF press. sensorRead
AV40305AI_DeIcingTempDe-icing temp exchangerRead
AV40306AI_FrostprotTemp1Frost prot. temp 1Read
AV40307AI_FrostprotTemp2Frost prot. temp 2Read
AV40308AI_FrostprotTemp3Frost prot. temp 3Read
AV40309AI_CO2CO2 (ppm)ppmRead
AV40310AI_HumidityRoomHumidity roomRead
AV40311AI_HumidityDuctHumidity ductRead
AV40312AI_HumidityOutDoorHumidity outdoorRead
AV40313AI_ExtraControllerTempExtra cont.ler tempRead
AV40314AI_ExtSAFControlExt. SAF signal cont.%Read
AV40315AI_ExtEAFControlExt. EAF signal cont.%Read
AV40316AI_ExtraSensor1Extra sensor 1Read
AV40317AI_ExtraSensor2Extra sensor 2Read
AV40318AI_ExtraSensor3Extra sensor 3Read
AV40319AI_ExtraSensor4Extra sensor 4Read
AV40320AI_ExtraSensor5Extra sensor 5Read
AV40321AI_ExternalSupplySetPExt. setp.Read
AV40322AI_ExternalFlowSetPExt. setp. SAF airflowRead
AV40323AI_FilterGuard1Supply air filterRead
AV40324AI_FilterGuard2Extract air filterRead
AV40325AI_EfficiencyTemptemp. efficiency sensorRead
AV40326AI_PreHeatTempPreheater tempRead
AV40327AI_Zone1SupplyTempZone1 supply tempRead
AV40328AI_Zone2SupplyTempZone2 supply tempRead
AV40329AI_Zone3SupplyTempZone3 supply tempRead
AV40330AI_Zone1ExtractTempZone1 extract tempRead
AV40331AI_Zone2ExtractTempZone2 sxtract tempRead
AV40332AI_Zone3ExtractTempZone3 extract tempRead
AV40333AI_Zone1RoomTempZone1 room tempRead
AV40334AI_Zone2RoomTempZone2 room tempRead
AV40335AI_Zone3RoomTempZone3 room tempRead
AV40336RoomTempRoom temp. 1-4Read
AV40339AI_ExchAirFlowSAFCalculated flow over Exchanger, SAFRead
AV40340ExchAirFlowEAFCalculated flow over Exchanger, EAFRead
AV40341AO_SeqY1Seq A output%Read
AV40342AO_SeqY2Seq B output%Read
AV40343AO_SeqY3Seq C output%Read
AV40344AO_SeqY4Seq D output%Read
AV40345AO_SeqY5Seq E output%Read
AV40346AO_SeqY6Seq F output%Read
AV40347AO_SeqY7Seq G output%Read
AV40348AO_SeqY8Seq H output%Read
AV40349AO_SeqY9Seq I output%Read
AV40350AO_SeqY10Seq J output%Read
AV40351AO_ChangeOver1Cont. signal heat. or cool. controlled by changeover%Read
AV40352AO_ChangeOver2Cont. signal heat. or cool. controlled by changeover%Read
AV40353AO_SAFSupply air fan cont.%Read
AV40354AO_EAFExtract air fan cont.%Read
AV40355AO_HumidityCont. valve humidity%Read
AV40356AO_StepController1Step cont. 1%Read
AV40357AO_StepController2Step cont. 2%Read
AV40358AO_ExtraControllerExtra cont.ler%Read
AV40359AO_AISignalOutputAI Signal output%Read
AV40360AO_Auto_PreHeatPreheater output%Read
AV40361AO_Auto_Zone1HeatZone 1 heating%Read
AV40362AO_Auto_Zone2HeatZone 2 heating%Read
AV40363AO_Auto_Zone3HeatZone 3 heating%Read
AV40364AO_Auto_Zone1CoolZone 1 cooling%Read
AV40365AO_Auto_Zone2CoolZone 2 cooling%Read
AV40366AO_Auto_Zone3CoolZone 3 cooling%Read
AV40367AO_Auto_EATRControlEATR control function output (%)%Read
AV40370AO_1AO1%Read
AV40371AO_2AO2%Read
AV40372AO_3AO3%Read
AV40373AO_4AO4%Read
AV40374AO_5AO5%Read
AV40375AOExp1_1AO1 Exp. Unit 1%Read
AV40376AOExp1_2AO2 Exp. Unit 1%Read
AV40377AOExp1_3AO3 Exp. Unit 1%Read
AV40378AOExp1_4AO4 Exp. Unit 1%Read
AV40379AOExp1_5AO5 Exp. Unit 1%Read
AV40380AOExp2_1AO1 Exp. Unit 2%Read
AV40381AOExp2_2AO2 Exp. Unit 2%Read
AV40382AOExp2_3AO3 Exp. Unit 2%Read
AV40383AOExp2_4AO4 Exp. Unit 2%Read
AV40384AOExp2_5AO5 Exp. Unit 2%Read
AV40385AO_6AO6%Read
AV40395EfficiencyEfficiency for exchanger%Read
AV40399ActiveHeatSeqStepCurr. heat seq. step that's activeRead
AV40400ActiveCoolSeqStepCurr. cool seq. step that's activeRead
AV40401ActiveYSeqCurr. Y seq. that's active and controllingRead
AV40402SAFRunTimeRun. Time supply air fanhRead
AV40403EAFRunTimeRun. Time extract air fanhRead
AV40404DeIcingTimeNumber of min for ongoing de-icingminRead
AV40405NeedRunTimeNo of min in ongoing support heat/coolminRead
AV40406CO2RunTimeNo of min support run time CO2minRead
AV40408Y1SeqCont. signal Y1%Read
AV40409Y2SeqCont. signal Y2%Read
AV40410Y3SeqCont. signal Y3%Read
AV40411Y4SeqCont. signal Y4%Read
AV40412Y5SeqCont. signal Y5%Read
AV40413Y6SeqCont. signal Y6%Read
AV40414Y7SeqCont. signal Y7%Read
AV40415Y8SeqCont. signal Y8%Read
AV40416Y9SeqCont. signal Y9%Read
AV40417Y10SeqCont. signal Y10%Read
AV40418SAFCont. signal supply air fan%Read
AV40419EAFCont. signal extract air fan%Read
AV40422CompLowSpeedSAFTotal comp. low speed SAFRead
AV40423CompNormalSpeedSAFTotal comp. normal speed SAFRead
AV40424CompHighSpeedSAFTotal comp. high speed SAFRead
AV40425CompLowSpeedEAFTotal comp. low speed EAFRead
AV40426CompNormalSpeedEAFTotal comp. normal speed EAFRead
AV40427CompHighSpeedEAFTotal comp. high speed EAFRead
AV40428AlarmACountNo of A alarmsRead
AV40429AlarmBCountNo of B alarmsRead
AV40430AlarmCCountNo of C alarmsRead
AV40431SumAlarm1CountNo of SumAlarm1 alarmsRead
AV40432SumAlarm2CountNo of SumAlarm2 alarmsRead
AV40433SupplyPID_SetPCalc. setp. supply air temp. when outd. comp. control func.Read
AV40434SAFPID_SetPActual setp. SAFRead
AV40435EAFPID_SetPActual setp. EAFRead
AV40436FrostPID1_OutputFrost prot. cont.ler output%Read
AV40437FrostPID2_OutputFrost prot. cont.ler output%Read
AV40438FrostPID3_OutputFrost prot. cont.ler output%Read
AV40439CO2PID_OutputCO2 cont.ler output%Read
AV40440DeIcePID_OutputDe-icing cont.ler output%Read
AV40441HumidityPID_OutputHum. cont.ler output%Read
AV40443SFPActual SFPRead
AV40444SFPDayDay aver. SFPRead
AV40445SFPMonthMonth aver. (30d aver.) SFPRead
AV40446MotSpHzSAF_1SAF Mot sp. HzHzRead
AV40447MotSpHzSAF_2SAF Mot sp. HzHzRead
AV40448MotSpHzSAF_3SAF Mot sp. HzHzRead
AV40449MotSpHzSAF_4SAF Mot sp. HzHzRead
AV40450MotSpHzSAF_5SAF Mot sp. HzHzRead
AV40451MotSpHzEAF_1EAF Mot sp. HzHzRead
AV40452MotSpHzEAF_2EAF Mot sp. HzHzRead
AV40453MotSpHzEAF_3EAF Mot sp. HzHzRead
AV40454MotSpHzEAF_4EAF Mot sp. HzHzRead
AV40455MotSpHzEAF_5EAF Mot sp. HzHzRead
AV40456MotSpRpmSAF_1SAF Mot sp. RPMrpmRead
AV40457MotSpRpmSAF_2SAF Mot sp. RPMrpmRead
AV40458MotSpRpmSAF_3SAF Mot sp. RPMrpmRead
AV40459MotSpRpmSAF_4SAF Mot sp. RPMrpmRead
AV40460MotSpRpmSAF_5SAF Mot sp. RPMrpmRead
AV40461MotSpRpmEAF_1EAF Mot sp. RPMrpmRead
AV40462MotSpRpmEAF_2EAF Mot sp. RPMrpmRead
AV40463MotSpRpmEAF_3EAF Mot sp. RPMrpmRead
AV40464MotSpRpmEAF_4EAF Mot sp. RPMrpmRead
AV40465MotSpRpmEAF_5EAF Mot sp. RPMrpmRead
AV40466MotCurrSAF_1SAF Mot curr.ARead
AV40467MotCurrSAF_2SAF Mot curr.ARead
AV40468MotCurrSAF_3SAF Mot curr.ARead
AV40469MotCurrSAF_4SAF Mot curr.ARead
AV40470MotCurrSAF_5SAF Mot curr.ARead
AV40471MotCurrEAF_1EAF Mot curr.ARead
AV40472MotCurrEAF_2EAF Mot curr.ARead
AV40473MotCurrEAF_3EAF Mot curr.ARead
AV40474MotCurrEAF_4EAF Mot curr.ARead
AV40475MotCurrEAF_5EAF Mot curr.ARead
AV40476MotPowSAF_1SAF Mot power%Read
AV40477MotPowSAF_2SAF Mot power%Read
AV40478MotPowSAF_3SAF Mot power%Read
AV40479MotPowSAF_4SAF Mot power%Read
AV40480MotPowSAF_5SAF Mot power%Read
AV40481MotPowEAF_1EAF Mot power%Read
AV40482MotPowEAF_2EAF Mot power%Read
AV40483MotPowEAF_3EAF Mot power%Read
AV40484MotPowEAF_4EAF Mot power%Read
AV40485MotPowEAF_5EAF Mot power%Read
AV40486ActFaultSAF_1SAF fault (bit masked)Read
AV40487ActFaultSAF_2SAF fault (bit masked)Read
AV40488ActFaultSAF_3SAF fault (bit masked)Read
AV40489ActFaultSAF_4SAF fault (bit masked)Read
AV40490ActFaultSAF_5SAF fault (bit masked)Read
AV40491ActFaultEAF_1EAF fault (bit masked)Read
AV40492ActFaultEAF_2EAF fault (bit masked)Read
AV40493ActFaultEAF_3EAF fault (bit masked)Read
AV40494ActFaultEAF_4EAF fault (bit masked)Read
AV40495ActFaultEAF_5EAF fault (bit masked)Read
AV40496ActualSpeedSAF_1SAF Act. speedRead
AV40497ActualSpeedSAF_2SAF Act. speedRead
AV40498ActualSpeedSAF_3SAF Act. speedRead
AV40499ActualSpeedSAF_4SAF Act. speedRead
AV40500ActualSpeedSAF_5SAF Act. speedRead
AV40501ActualSpeedEAF_1EAF Act. speedRead
AV40502ActualSpeedEAF_2EAF Act. speedRead
AV40503ActualSpeedEAF_3EAF Act. speedRead
AV40504ActualSpeedEAF_4EAF Act. speedRead
AV40505ActualSpeedEAF_5EAF Act. speedRead
AV40506AccumPowSAF_1SAF Accum. powerRead
AV40507AccumPowSAF_2SAF Accum. powerRead
AV40508AccumPowSAF_3SAF Accum. powerRead
AV40509AccumPowSAF_4SAF Accum. powerRead
AV40510AccumPowSAF_5SAF Accum. powerRead
AV40511AccumPowEAF_1EAF Accum. powerRead
AV40512AccumPowEAF_2EAF Accum. powerRead
AV40513AccumPowEAF_3EAF Accum. powerRead
AV40514AccumPowEAF_4EAF Accum. powerRead
AV40515AccumPowEAF_5EAF Accum. powerRead
AV40516VVXFaultVVX Fault (bit masked)Read
AV40517DampActPos_1Damper act. pos.%Read
AV40518DampActPos_2Damper act. pos.%Read
AV40519DampActPos_3Damper act. pos.%Read
AV40520DampActPos_4Damper act. pos.%Read
AV40521DampActPos_5Damper act. pos.%Read
AV40522DampFault_1Damper fault (bit masked)Read
AV40523DampFault_2Damper fault (bit masked)Read
AV40524DampFault_3Damper fault (bit masked)Read
AV40525DampFault_4Damper fault (bit masked)Read
AV40526DampFault_5Damper fault (bit masked)Read
AV40527EnergyFanPwrPower usage fanskWhRead
AV40528EnergyHeaterPwrPower usage heaterkWhRead
AV40529EnergyExchangerPwrPower recovery exchangerkWhRead
AV40530AI_Zone1FrostprotTempFrost protection temperature zone 1Read
AV40531AI_Zone2FrostprotTempFrost protection temperature zone 2Read
AV40532AI_Zone3FrostprotTempFrost protection temperature zone 3Read
AV40539MotSpHzSAF_6SAF Mot sp. HzHzRead
AV40540MotSpHzSAF_7SAF Mot sp. HzHzRead
AV40541MotSpHzSAF_8SAF Mot sp. HzHzRead
AV40542MotSpHzEAF_6EAF Mot sp. HzHzRead
AV40543MotSpHzEAF_7EAF Mot sp. HzHzRead
AV40544MotSpHzEAF_8EAF Mot sp. HzHzRead
AV40545MotSpRpmSAF_6SAF Mot sp. RPMrpmRead
AV40546MotSpRpmSAF_7SAF Mot sp. RPMrpmRead
AV40547MotSpRpmSAF_8SAF Mot sp. RPMrpmRead
AV40548MotSpRpmEAF_6EAF Mot sp. RPMrpmRead
AV40549MotSpRpmEAF_7EAF Mot sp. RPMrpmRead
AV40550MotSpRpmEAF_8EAF Mot sp. RPMrpmRead
AV40551MotCurrSAF_6SAF Mot curr.ARead
AV40552MotCurrSAF_7SAF Mot curr.ARead
AV40553MotCurrSAF_8SAF Mot curr.ARead
AV40554MotCurrEAF_6EAF Mot curr.ARead
AV40555MotCurrEAF_7EAF Mot curr.ARead
AV40556MotCurrEAF_8EAF Mot curr.ARead
AV40557MotPowSAF_6SAF Mot power%Read
AV40558MotPowSAF_7SAF Mot power%Read
AV40559MotPowSAF_8SAF Mot power%Read
AV40560MotPowEAF_6EAF Mot power%Read
AV40561MotPowEAF_7EAF Mot power%Read
AV40562MotPowEAF_8EAF Mot power%Read
AV40563ActFaultSAF_6SAF fault (bit masked)Read
AV40564ActFaultSAF_7SAF fault (bit masked)Read
AV40565ActFaultSAF_8SAF fault (bit masked)Read
AV40566ActFaultEAF_6EAF fault (bit masked)Read
AV40567ActFaultEAF_7EAF fault (bit masked)Read
AV40568ActFaultEAF_8EAF fault (bit masked)Read
AV40569ActualSpeedSAF_6SAF Act. speedRead
AV40570ActualSpeedSAF_7SAF Act. speedRead
AV40571ActualSpeedSAF_8SAF Act. speedRead
AV40572ActualSpeedEAF_6EAF Act. speedRead
AV40573ActualSpeedEAF_7EAF Act. speedRead
AV40574ActualSpeedEAF_8EAF Act. speedRead
AV40575AccumPowSAF_6SAF Accum. powerRead
AV40576AccumPowSAF_7SAF Accum. powerRead
AV40577AccumPowSAF_8SAF Accum. powerRead
AV40578AccumPowEAF_6EAF Accum. powerRead
AV40579AccumPowEAF_7EAF Accum. powerRead
AV40580AccumPowEAF_8EAF Accum. powerRead
AV40581SupplyPID_SetP_CoolCooling setpoint supply air temperatureRead
AV40582SupplyPID_SetP_HeatHeating setpoint supply air temperatureRead
AV40583DeHumidity_SetPDehumidification setpointRead
AV40584Humidity_SetPHumidification setpointRead
AV40586AI_FeedbackCoolerValveFeedback cooler valve. (Not valid in version 4.4)%Read
AV40587AI_FeedbackOutdoorAirDamperFeedback outdoor air damper. (Not valid in version 4.4)%Read
AV40588AI_FeedbackRecircAirDamperFeedback recirculation air damper. (Not valid in version 4.4)%Read
AV40590DCVoltageSAF_1SAF DC link voltage (V)VRead
AV40591DCVoltageSAF_2SAF DC link voltage (V)VRead
AV40592DCVoltageSAF_3SAF DC link voltage (V)VRead
AV40593DCVoltageSAF_4SAF DC link voltage (V)VRead
AV40594DCVoltageSAF_5SAF DC link voltage (V)VRead
AV40595DCVoltageSAF_6SAF DC link voltage (V)VRead
AV40596DCVoltageSAF_7SAF DC link voltage (V)VRead
AV40597DCVoltageSAF_8SAF DC link voltage (V)VRead
AV40598DCVoltageEAF_1EAF DC link voltage (V)VRead
AV40599DCVoltageEAF_2EAF DC link voltage (V)VRead
AV40600DCVoltageEAF_3EAF DC link voltage (V)VRead
AV40601DCVoltageEAF_4EAF DC link voltage (V)VRead
AV40602DCVoltageEAF_5EAF DC link voltage (V)VRead
AV40603DCVoltageEAF_6EAF DC link voltage (V)VRead
AV40604DCVoltageEAF_7EAF DC link voltage (V)VRead
AV40605DCVoltageEAF_8EAF DC link voltage (V)VRead
AV40606MotorTemperatureSAF_1SAF Motor temperature°CRead
AV40607MotorTemperatureSAF_2SAF Motor temperature°CRead
AV40608MotorTemperatureSAF_3SAF Motor temperature°CRead
AV40609MotorTemperatureSAF_4SAF Motor temperature°CRead
AV40610MotorTemperatureSAF_5SAF Motor temperature°CRead
AV40611MotorTemperatureSAF_6SAF Motor temperature°CRead
AV40612MotorTemperatureSAF_7SAF Motor temperature°CRead
AV40613MotorTemperatureSAF_8SAF Motor temperature°CRead
AV40614MotorTemperatureEAF_1EAF Motor temperature°CRead
AV40615MotorTemperatureEAF_2EAF Motor temperature°CRead
AV40616MotorTemperatureEAF_3EAF Motor temperature°CRead
AV40617MotorTemperatureEAF_4EAF Motor temperature°CRead
AV40618MotorTemperatureEAF_5EAF Motor temperature°CRead
AV40619MotorTemperatureEAF_6EAF Motor temperature°CRead
AV40620MotorTemperatureEAF_7EAF Motor temperature°CRead
AV40621MotorTemperatureEAF_8EAF Motor temperature°CRead
AV40622MotorRunHourSAF_1SAF Running time (h)hRead
AV40623MotorRunHourSAF_2SAF Running time (h)hRead
AV40624MotorRunHourSAF_3SAF Running time (h)hRead
AV40625MotorRunHourSAF_4SAF Running time (h)hRead
AV40626MotorRunHourSAF_5SAF Running time (h)hRead
AV40627MotorRunHourSAF_6SAF Running time (h)hRead
AV40628MotorRunHourSAF_7SAF Running time (h)hRead
AV40629MotorRunHourSAF_8SAF Running time (h)hRead
AV40630MotorRunHourEAF_1EAF Running time (h)hRead
AV40631MotorRunHourEAF_2EAF Running time (h)hRead
AV40632MotorRunHourEAF_3EAF Running time (h)hRead
AV40633MotorRunHourEAF_4EAF Running time (h)hRead
AV40634MotorRunHourEAF_5EAF Running time (h)hRead
AV40635MotorRunHourEAF_6EAF Running time (h)hRead
AV40636MotorRunHourEAF_7EAF Running time (h)hRead
AV40637MotorRunHourEAF_8EAF Running time (h)hRead
AV40638IndoorEnthalpyIndoor entalphykJ/kgRead
AV40639OutdoorEnthalpyOutdoor entalphykJ/kgRead
AV40640A_EnthalpyDiffIs set when enthalpy outdoor > enthalpy indoorRead
AV40651FilterGuard1CalibrationInitPressFilter guard 1 calibration initial pressurem³/hRead
AV40652FilterGuard1CalibrationMadeTimeFilter guard 1 calibration made (time)Read
AV40653FilterGuard1CalibrationMadeDateFilter guard 1 calibration made (date)Read
AV40654FilterGuard1CalibrationMadeYearFilter guard 1 calibration made (year)Read
AV40655FilterGuard1Limit_CalcFilter guard 1 calibration calculated alarmm³/hRead
AV40656FilterGuard2CalibrationInitPressFilter guard 2 calibration initial pressurem³/hRead
AV40657FilterGuard2CalibrationMadeTimeFilter guard 2 calibration made (time)Read
AV40658FilterGuard2CalibrationMadeDateFilter guard 2 calibration made (date)Read
AV40659FilterGuard2CalibrationMadeYearFilter guard 2 calibration made (year)Read
AV40660FilterGuard2Limit_CalcFilter guard 2 calibration calculated alarmm³/hRead
AV40661FilterGuard3CalibrationInitPressFilter guard 3 calibration initial pressurem³/hRead
AV40662FilterGuard3CalibrationMadeTimeFilter guard 3 calibration made (time)Read
AV40663FilterGuard3CalibrationMadeDateFilter guard 3 calibration made (date)Read
AV40664FilterGuard3CalibrationMadeYearFilter guard 3 calibration made (year)Read
AV40665FilterGuard3Limit_CalcFilter guard 3 calibration calculated alarmm³/hRead
AV40666FilterGuard4CalibrationInitPressFilter guard 4 calibration initial pressurem³/hRead
AV40667FilterGuard4CalibrationMadeTimeFilter guard 4 calibration made (time)Read
AV40668FilterGuard4CalibrationMadeDateFilter guard 4 calibration made (date)Read
AV40669FilterGuard4CalibrationMadeYearFilter guard 4 calibration made (year)Read
AV40670FilterGuard4Limit_CalcFilter guard 4 calibration calculated alarmm³/hRead
AV40671FilterGuard5CalibrationInitPressFilter guard 5 calibration initial pressurem³/hRead
AV40672FilterGuard5CalibrationMadeTimeFilter guard 5 calibration made (time)Read
AV40673FilterGuard5CalibrationMadeDateFilter guard 5 calibration made (date)Read
AV40674FilterGuard5CalibrationMadeYearFilter guard 5 calibration made (year)Read
AV40675FilterGuard5Limit_CalcFilter guard 5 calibration calculated alarmm³/hRead
AV40676AI_FilterGuard3Supply air pre filterRead
AV40677AI_FilterGuard4Supply air end filterRead
AV40678AI_FilterGuard5Extract air pre filterRead
AV40679ExtractFilterGuardFlowRefExtract air flow (calculated) filter calibrationRead
AV40680ChangeOver1RunModeChangeover 1 running mode (actual changeover sequence 1-10)Read
AV40681ChangeOver2RunModeChangeover 2 running mode (actual changeover sequence 1-10)Read
AV40682FeedbackDXWaitStartWaiting for DX-compressor to startRead
AV40683FeedbackDXWaitDefrostWaiting for DX-machine to defrostRead
BVmin10000AlaAcknowAllCommand to acknowledge all alarmsWrite0=NORMAL, 1=ACKNOWLEDGE
BV10001FilterAlarmResetResets the filter alarm counterWrite0=Inactive, 1=Active
BV20000TC_FanLowSpeedActualTC low speedRead0=INACTIVE, 1=ACTIVE
BV20001TC_FanNormalSpeedActualTC normal speedRead0=INACTIVE, 1=ACTIVE
BV20002TC_FanHighSpeedActualTC high speedRead0=INACTIVE, 1=ACTIVE
BV20003TC_Extra1ActualTC timer 1Read0=INACTIVE, 1=ACTIVE
BV20004TC_Extra2ActualTC timer 2Read0=INACTIVE, 1=ACTIVE
BV20005TC_Extra3ActualTC timer 3Read0=INACTIVE, 1=ACTIVE
BV20006TC_Extra4ActualTC timer 4Read0=INACTIVE, 1=ACTIVE
BVmin20007SumAlarmSumalarmRead0=NORMAL, 1=ALARM
BV20008SumAlarmAA-alarmRead0=NORMAL, 1=ALARM
BV20009SumAlarmBB-alarmRead0=NORMAL, 1=ALARM
BV20010SumAlarmCC-alarmRead0=NORMAL, 1=ALARM
BV20011MalfunctionSAF1Malfunction SAF 1Read0=NORMAL, 1=ALARM
BV20012MalfunctionSAF2Malfunction SAF 2Read0=NORMAL, 1=ALARM
BV20013MalfunctionSAF3Malfunction SAF 3Read0=NORMAL, 1=ALARM
BV20014MalfunctionSAF4Malfunction SAF 4Read0=NORMAL, 1=ALARM
BV20015MalfunctionSAF5Malfunction SAF 5Read0=NORMAL, 1=ALARM
BV20016MalfunctionEAF1Malfunction EAF 1Read0=NORMAL, 1=ALARM
BV20017MalfunctionEAF2Malfunction EAF 2Read0=NORMAL, 1=ALARM
BV20018MalfunctionEAF3Malfunction EAF 3Read0=NORMAL, 1=ALARM
BV20019MalfunctionEAF4Malfunction EAF 4Read0=NORMAL, 1=ALARM
BV20020MalfunctionEAF5Malfunction EAF 5Read0=NORMAL, 1=ALARM
BV20021AlarmfrequencyconverterSAF1Alarm frequency converter SAF 1Read0=NORMAL, 1=ALARM
BV20022AlarmfrequencyconverterSAF2Alarm frequency converter SAF 2Read0=NORMAL, 1=ALARM
BV20023AlarmfrequencyconverterSAF3Alarm frequency converter SAF 3Read0=NORMAL, 1=ALARM
BV20024AlarmfrequencyconverterSAF4Alarm frequency converter SAF 4Read0=NORMAL, 1=ALARM
BV20025AlarmfrequencyconverterSAF5Alarm frequency converter SAF 5Read0=NORMAL, 1=ALARM
BV20026AlarmfrequencyconverterEAF1Alarm frequency converter EAF 1Read0=NORMAL, 1=ALARM
BV20027AlarmfrequencyconverterEAF2Alarm frequency converter EAF 2Read0=NORMAL, 1=ALARM
BV20028AlarmfrequencyconverterEAF3Alarm frequency converter EAF 3Read0=NORMAL, 1=ALARM
BV20029AlarmfrequencyconverterEAF4Alarm frequency converter EAF 4Read0=NORMAL, 1=ALARM
BV20030AlarmfrequencyconverterEAF5Alarm frequency converter EAF 5Read0=NORMAL, 1=ALARM
BV20031WarningfrequencyconverterSAF1Warning frequency converter SAF 1Read0=NORMAL, 1=ALARM
BV20032WarningfrequencyconverterSAF2Warning frequency converter SAF 2Read0=NORMAL, 1=ALARM
BV20033WarningfrequencyconverterSAF3Warning frequency converter SAF 3Read0=NORMAL, 1=ALARM
BV20034WarningfrequencyconverterSAF4Warning frequency converter SAF 4Read0=NORMAL, 1=ALARM
BV20035WarningfrequencyconverterSAF5Warning frequency converter SAF 5Read0=NORMAL, 1=ALARM
BV20036WarningfrequencyconverterEAF1Warning frequency converter EAF 1Read0=NORMAL, 1=ALARM
BV20037WarningfrequencyconverterEAF2Warning frequency converter EAF 2Read0=NORMAL, 1=ALARM
BV20038WarningfrequencyconverterEAF3Warning frequency converter EAF 3Read0=NORMAL, 1=ALARM
BV20039WarningfrequencyconverterEAF4Warning frequency converter EAF 4Read0=NORMAL, 1=ALARM
BV20040WarningfrequencyconverterEAF5Warning frequency converter EAF 5Read0=NORMAL, 1=ALARM
BV20041ExternaloperationSAFExternal operation SAFRead0=NORMAL, 1=ALARM
BV20042ExternaloperationEAFExternal operation EAFRead0=NORMAL, 1=ALARM
BV20043MotorCont1extOperationMotor cont. 1 external oper.Read0=NORMAL, 1=ALARM
BV20044MotorCont2extOperationMotor cont. 2 external oper.Read0=NORMAL, 1=ALARM
BV20045Malf_pumpheaterMalf. pump heaterRead0=NORMAL, 1=ALARM
BV20046Malf_pumpcoolerMalf. pump coolerRead0=NORMAL, 1=ALARM
BV20047Malf_pumpexchangerMalf. pump exchangerRead0=NORMAL, 1=ALARM
BV20048Malf_firedamperMalf. fire damperRead0=NORMAL, 1=ALARM
BV20049Malf_damperMalf. damperRead0=NORMAL, 1=ALARM
BV20050Malf_motorcont_1Malf. motor cont. 1Read0=NORMAL, 1=ALARM
BV20051Malf_motorcont_2Malf. motor cont. 2Read0=NORMAL, 1=ALARM
BV20052FireDamperExStopFire damper exercise stopRead0=NORMAL, 1=ALARM
BV20053Malf_pumpseq_1Malf. pump seq. ARead0=NORMAL, 1=ALARM
BV20054Malf_pumpseq_2Malf. pump seq. BRead0=NORMAL, 1=ALARM
BV20055Malf_pumpseq_3Malf. pump seq. CRead0=NORMAL, 1=ALARM
BV20056Malf_pumpseq_4Malf. pump seq. DRead0=NORMAL, 1=ALARM
BV20057Malf_pumpseq_5Malf. pump seq. ERead0=NORMAL, 1=ALARM
BV20058Malf_pumpseq_6Malf. pump seq. FRead0=NORMAL, 1=ALARM
BV20059Malf_pumpseq_7Malf. pump seq. GRead0=NORMAL, 1=ALARM
BV20060Malf_pumpseq_8Malf. pump seq. HRead0=NORMAL, 1=ALARM
BV20061Malf_pumpseq_9Malf. pump seq. IRead0=NORMAL, 1=ALARM
BV20062Malf_pumpseq_10Malf. pump seq. JRead0=NORMAL, 1=ALARM
BV20063Filterguard1Filter guard 1Read0=NORMAL, 1=ALARM
BV20064Filterguard2Filter guard 2Read0=NORMAL, 1=ALARM
BV20065FlowguardFlow guardRead0=NORMAL, 1=ALARM
BV20066ExternalfrostguardExternal frost guardRead0=NORMAL, 1=ALARM
BV20067DeicingpressGuardDeicing press. guardRead0=NORMAL, 1=ALARM
BV20068FirealarmFire alarmRead0=NORMAL, 1=ALARM
BV20069SmokedetectoralarmSmoke detector alarmRead0=NORMAL, 1=ALARM
BV20070Ext_switchExt. switchRead0=NORMAL, 1=ALARM
BV20071Ext_alarmExt. alarmRead0=NORMAL, 1=ALARM
BV20072ServicestopService stopRead0=NORMAL, 1=ALARM
BV20073Elec_heatingisoverheatedElec. heating is overheatedRead0=NORMAL, 1=ALARM
BV20074FrostriskFrost riskRead0=NORMAL, 1=ALARM
BV20075LowefficiencyLow efficiencyRead0=NORMAL, 1=ALARM
BV20076AnaloguedeicingAnalogue deicingRead0=NORMAL, 1=ALARM
BV20077RotationguardexchangerRotation guard exchangerRead0=NORMAL, 1=ALARM
BV20078Ex_alarm1Extra alarm 1Read0=NORMAL, 1=ALARM
BV20079Ex_alarm2Extra alarm 2Read0=NORMAL, 1=ALARM
BV20080Ex_alarm3Extra alarm 3Read0=NORMAL, 1=ALARM
BV20081Ex_alarm4Extra alarm 4Read0=NORMAL, 1=ALARM
BV20082Ex_alarm5Extra alarm 5Read0=NORMAL, 1=ALARM
BV20083Ex_alarm6Extra alarm 6Read0=NORMAL, 1=ALARM
BV20084Ex_alarm7Extra alarm 7Read0=NORMAL, 1=ALARM
BV20085Ex_alarm8Extra alarm 8Read0=NORMAL, 1=ALARM
BV20086Ex_alarm9Extra alarm 9Read0=NORMAL, 1=ALARM
BV20087Ex_alarm10Extra alarm 10Read0=NORMAL, 1=ALARM
BV20088InternalbatteryerrorInternal battery errorRead0=NORMAL, 1=ALARM
BV20089TimeforserviceTime for serviceRead0=NORMAL, 1=ALARM
BV20090RestartblockedafterpoweronRestart blocked after power onRead0=NORMAL, 1=ALARM
BV20091SupplyairtempcontErrorSupply air temp cont. errorRead0=NORMAL, 1=ALARM
BV20092SAFcontErrorSAF cont. errorRead0=NORMAL, 1=ALARM
BV20093EAFcontErrorEAF cont. errorRead0=NORMAL, 1=ALARM
BV20094HumiditycontErrorHumidity cont. errorRead0=NORMAL, 1=ALARM
BV20095ExtraControllercontollErrorExtra cont.ler cont. errorRead0=NORMAL, 1=ALARM
BV20096HighsupplyairtempHigh supply air tempRead0=NORMAL, 1=ALARM
BV20097LowsupplyairtempLow supply air tempRead0=NORMAL, 1=ALARM
BV20098SupplyairtempmaxlimitSupply air temp max limitRead0=NORMAL, 1=ALARM
BV20099SupplyairtempminlimitSupply air temp min limitRead0=NORMAL, 1=ALARM
BV20100HighroomtempHigh room tempRead0=NORMAL, 1=ALARM
BV20101LowroomtempLow room tempRead0=NORMAL, 1=ALARM
BV20102HighextractairtempHigh extract air tempRead0=NORMAL, 1=ALARM
BV20103LowextractairtempLow extract air tempRead0=NORMAL, 1=ALARM
BV20104HighoutdoorairtempHigh outdoor air tempRead0=NORMAL, 1=ALARM
BV20105LowoutdoorairtempLow outdoor air tempRead0=NORMAL, 1=ALARM
BV20106Lowfrostguardtemp1Low frost guard temp 1Read0=NORMAL, 1=ALARM
BV20107Lowfrostguardtemp2Low frost guard temp 2Read0=NORMAL, 1=ALARM
BV20108Lowfrostguardtemp3Low frost guard temp 3Read0=NORMAL, 1=ALARM
BV20109Hightempextrasensor1High temp extra sensor 1Read0=NORMAL, 1=ALARM
BV20110Lowtempextrasensor1Low temp extra sensor 1Read0=NORMAL, 1=ALARM
BV20111Hightempextrasensor2High temp extra sensor 2Read0=NORMAL, 1=ALARM
BV20112Lowtempextrasensor2Low temp extra sensor 2Read0=NORMAL, 1=ALARM
BV20113Hightempextrasensor3High temp extra sensor 3Read0=NORMAL, 1=ALARM
BV20114Lowtempextrasensor3Low temp extra sensor 3Read0=NORMAL, 1=ALARM
BV20115Hightempextrasensor4High temp extra sensor 4Read0=NORMAL, 1=ALARM
BV20116Lowtempextrasensor4Low temp extra sensor 4Read0=NORMAL, 1=ALARM
BV20117Hightempextrasensor5High temp extra sensor 5Read0=NORMAL, 1=ALARM
BV20118Lowtempextrasensor5Low temp extra sensor 5Read0=NORMAL, 1=ALARM
BV20119Hightempsel_sensor1High temp sel. sensor 1Read0=NORMAL, 1=ALARM
BV20120Lowtempsel_sensor1Low temp sel. sensor 1Read0=NORMAL, 1=ALARM
BV20121Hightempsel_sensor2High temp sel. sensor 2Read0=NORMAL, 1=ALARM
BV20122Lowtempsel_sensor2Low temp sel. sensor 2Read0=NORMAL, 1=ALARM
BV20123ManCont_airunitMan. cont. air unitRead0=NORMAL, 1=ALARM
BV20124ManCont_supplyairMan. cont. supply airRead0=NORMAL, 1=ALARM
BV20125ManCont_SAFMan. cont. SAFRead0=NORMAL, 1=ALARM
BV20126ManCont_EAFMan. cont. EAFRead0=NORMAL, 1=ALARM
BV20127ManCont_heaterMan. cont. heaterRead0=NORMAL, 1=ALARM
BV20128ManCont_exchangerMan. cont. exchangerRead0=NORMAL, 1=ALARM
BV20129ManCont_coolerMan. cont. coolerRead0=NORMAL, 1=ALARM
BV20130ManCont_damperMan. cont. damperRead0=NORMAL, 1=ALARM
BV20131ManCont_heaterpumpMan. cont. heater pumpRead0=NORMAL, 1=ALARM
BV20132ManCont_exchangerpumpMan. cont. exchanger pumpRead0=NORMAL, 1=ALARM
BV20133ManCont_coolerpumpMan. cont. cooler pumpRead0=NORMAL, 1=ALARM
BV20134ManCont_recirculationairdamperMan. cont. recirculation air damperRead0=NORMAL, 1=ALARM
BV20135ManCont_freshairdamperMan. cont. fresh air damperRead0=NORMAL, 1=ALARM
BV20136ManCont_exhaustairdamperMan. cont. exhaust air damperRead0=NORMAL, 1=ALARM
BV20137ManCont_firedamperMan. cont. fire damperRead0=NORMAL, 1=ALARM
BV20138ManCont_seq_1Man. cont. seq. ARead0=NORMAL, 1=ALARM
BV20139ManCont_seq_2Man. cont. seq. BRead0=NORMAL, 1=ALARM
BV20140ManCont_seq_3Man. cont. seq. CRead0=NORMAL, 1=ALARM
BV20141ManCont_seq_4Man. cont. seq. DRead0=NORMAL, 1=ALARM
BV20142ManCont_seq_5Man. cont. seq. ERead0=NORMAL, 1=ALARM
BV20143ManCont_seq_6Man. cont. seq. FRead0=NORMAL, 1=ALARM
BV20144ManCont_seq_7Man. cont. seq. GRead0=NORMAL, 1=ALARM
BV20145ManCont_seq_8Man. cont. seq. HRead0=NORMAL, 1=ALARM
BV20146ManCont_seq_9Man. cont. seq. IRead0=NORMAL, 1=ALARM
BV20147ManCont_seq_10Man. cont. seq. JRead0=NORMAL, 1=ALARM
BV20148OutputinManCont_Output in Man. cont.Read0=NORMAL, 1=ALARM
BV20149InputinManCont_Input in Man. cont.Read0=NORMAL, 1=ALARM
BV20150ManCont_extracont_lerMan. cont. extra cont.lerRead0=NORMAL, 1=ALARM
BV20151ManCont_motorcont_1Man. cont. motor cont. 1Read0=NORMAL, 1=ALARM
BV20152ManCont_motorcont_2Man. cont. motor cont. 2Read0=NORMAL, 1=ALARM
BV20153ManCont_pretreatmentMan. cont. pretreatmentRead0=NORMAL, 1=ALARM
BV20190CommErrorDeviceFault communication deviceRead0=NORMAL, 1=ALARM
BV20191MalfunctionExtraControllerMalfunction Extra ControllerRead0=NORMAL, 1=ALARM
BV20192InternalErrorInternal errorRead0=NORMAL, 1=ALARM
BV20193SmokeDetectorServiceSmoke detector serviceRead0=NORMAL, 1=ALARM
BV20194SmokeDetectorErrorSmoke detector connection errorRead0=NORMAL, 1=ALARM
BV20195MalfunctionPreheaterMalfunction preheaterRead0=NORMAL, 1=ALARM
BV20196CommunicationFaultBMSCommunication fault BMS masterRead0=NORMAL, 1=ALARM
BV20197LeakageHeaterValveLeakage heater valveRead0=NORMAL, 1=ALARM
BV20198SensorerrorpreheatertempSensor error preheater tempRead0=NORMAL, 1=ALARM
BV20199Malfunctionsupplyairfan6Malfunction supply air fan 6Read0=NORMAL, 1=ALARM
BV20200Malfunctionsupplyairfan7Malfunction supply air fan 7Read0=NORMAL, 1=ALARM
BV20201Malfunctionsupplyairfan8Malfunction supply air fan 8Read0=NORMAL, 1=ALARM
BV20202Malfunctionextractairfan6Malfunction extract air fan 6Read0=NORMAL, 1=ALARM
BV20203Malfunctionextractairfan7Malfunction extract air fan 7Read0=NORMAL, 1=ALARM
BV20204Malfunctionextractairfan8Malfunction extract air fan 8Read0=NORMAL, 1=ALARM
BV20205Alarmsupplyairfan6Alarm supply air fan 6Read0=NORMAL, 1=ALARM
BV20206Alarmsupplyairfan7Alarm supply air fan 7Read0=NORMAL, 1=ALARM
BV20207Alarmsupplyairfan8Alarm supply air fan 8Read0=NORMAL, 1=ALARM
BV20208Alarmextractairfan6Alarm extract air fan 6Read0=NORMAL, 1=ALARM
BV20209Alarmextractairfan7Alarm extract air fan 7Read0=NORMAL, 1=ALARM
BV20210Alarmextractairfan8Alarm extract air fan 8Read0=NORMAL, 1=ALARM
BV20211Warningsupplyairfan6Warning supply air fan 6Read0=NORMAL, 1=ALARM
BV20212Warningsupplyairfan7Warning supply air fan 7Read0=NORMAL, 1=ALARM
BV20213Warningsupplyairfan8Warning supply air fan 8Read0=NORMAL, 1=ALARM
BV20214Warningextractairfan6Warning extract air fan 6Read0=NORMAL, 1=ALARM
BV20215Warningextractairfan7Warning extract air fan 7Read0=NORMAL, 1=ALARM
BV20216Warningextractairfan8Warning extract air fan 8Read0=NORMAL, 1=ALARM
BV20217Malfunctionheatingzone1Malfunction heating zone 1Read0=NORMAL, 1=ALARM
BV20218Malfunctionheatingzone2Malfunction heating zone 2Read0=NORMAL, 1=ALARM
BV20219Malfunctionheatingzone3Malfunction heating zone 3Read0=NORMAL, 1=ALARM
BV20220Malfunctioncoolingzone1Malfunction cooling zone 1Read0=NORMAL, 1=ALARM
BV20221Malfunctioncoolingzone2Malfunction cooling zone 2Read0=NORMAL, 1=ALARM
BV20222Malfunctioncoolingzone3Malfunction cooling zone 3Read0=NORMAL, 1=ALARM
BV20223Deviationalarmsupplytempzone1Deviation alarm supply temp zone 1Read0=NORMAL, 1=ALARM
BV20224Deviationalarmsupplytempzone2Deviation alarm supply temp zone 2Read0=NORMAL, 1=ALARM
BV20225Deviationalarmsupplytempzone3Deviation alarm supply temp zone 3Read0=NORMAL, 1=ALARM
BV20226Freezeprotectionalarmzone1Freeze protection alarm zone 1Read0=NORMAL, 1=ALARM
BV20227Freezeprotectionalarmzone2Freeze protection alarm zone 2Read0=NORMAL, 1=ALARM
BV20228Freezeprotectionalarmzone3Freeze protection alarm zone 3Read0=NORMAL, 1=ALARM
BV20229Electricheaterisoverheatedzone1Electric heater is overheated zone 1Read0=NORMAL, 1=ALARM
BV20230Electricheaterisoverheatedzone2Electric heater is overheated zone 2Read0=NORMAL, 1=ALARM
BV20231Electricheaterisoverheatedzone3Electric heater is overheated zone 3Read0=NORMAL, 1=ALARM
BV20247DevicewarningDevice warningRead0=NORMAL, 1=ALARM
BV20248DevicealarmDevice alarmRead0=NORMAL, 1=ALARM
BV20249EATROverpressureEATR OverpressureRead0=NORMAL, 1=ALARM
BV20251FailsafeairflowtemperatureFail-safe airflow/temperatureRead0=NORMAL, 1=ALARM
BV20252FilteralarmpresupplyairFilter alarm pre supply airRead0=NORMAL, 1=ALARM
BV20253FilteralarmsupplyairendFilter alarm supply air endRead0=NORMAL, 1=ALARM
BV20254FilteralarmpreextractairFilter alarm pre extract airRead0=NORMAL, 1=ALARM
BV20261DI_1DI1Read0=Inactive, 1=Active
BV20262DI_2DI2Read0=Inactive, 1=Active
BV20263DI_3DI3Read0=Inactive, 1=Active
BV20264DI_4DI4Read0=Inactive, 1=Active
BV20265DI_5DI5Read0=Inactive, 1=Active
BV20266DI_6DI6Read0=Inactive, 1=Active
BV20267DI_7DI7Read0=Inactive, 1=Active
BV20268DI_8DI8Read0=Inactive, 1=Active
BV20269DI_9DI9 (UI1 on CU283)Read0=Inactive, 1=Active
BV20270DI_10DI10 (UI2 on CU283)Read0=Inactive, 1=Active
BV20271DI_11DI11 (UI3 on CU283)Read0=Inactive, 1=Active
BV20272DI_12DI12 (UI4 on CU283)Read0=Inactive, 1=Active
BV20273DIExp1_1DI1 exp. unit 1Read0=Inactive, 1=Active
BV20274DIExp1_2DI2 exp. unit 1Read0=Inactive, 1=Active
BV20275DIExp1_3DI3 exp. unit 1Read0=Inactive, 1=Active
BV20276DIExp1_4DI4 exp. unit 1Read0=Inactive, 1=Active
BV20277DIExp1_5DI5 exp. unit 1Read0=Inactive, 1=Active
BV20278DIExp1_6DI6 exp. unit 1Read0=Inactive, 1=Active
BV20279DIExp1_7DI7 exp. unit 1Read0=Inactive, 1=Active
BV20280DIExp1_8DI8 exp. unit 1Read0=Inactive, 1=Active
BV20281DIExp1_9UI1 exp. unit 1Read0=Inactive, 1=Active
BV20282DIExp1_10UI2 exp. unit 1Read0=Inactive, 1=Active
BV20283DIExp1_11UI3 exp. unit 1Read0=Inactive, 1=Active
BV20284DIExp1_12UI4 exp. unit 1Read0=Inactive, 1=Active
BV20285DIExp2_1DI1 exp. unit 2Read0=Inactive, 1=Active
BV20286DIExp2_2DI2 exp. unit 2Read0=Inactive, 1=Active
BV20287DIExp2_3DI3 exp. unit 2Read0=Inactive, 1=Active
BV20288DIExp2_4DI4 exp. unit 2Read0=Inactive, 1=Active
BV20289DIExp2_5DI5 exp. unit 2Read0=Inactive, 1=Active
BV20290DIExp2_6DI6 exp. unit 2Read0=Inactive, 1=Active
BV20291DIExp2_7DI7 exp. unit 2Read0=Inactive, 1=Active
BV20292DIExp2_8DI8 exp. unit 2Read0=Inactive, 1=Active
BV20293DIExp2_9UI1 exp. unit 2Read0=Inactive, 1=Active
BV20294DIExp2_10UI2 exp. unit 2Read0=Inactive, 1=Active
BV20295DIExp2_11UI3 exp. unit 2Read0=Inactive, 1=Active
BV20296DIExp2_12UI4 exp. unit 2Read0=Inactive, 1=Active
BV20297DI_13UI1Read0=Inactive, 1=Active
BV20298DI_14UI2Read0=Inactive, 1=Active
BV20299DI_15UI3Read0=Inactive, 1=Active
BV20300DI_16UI4Read0=Inactive, 1=Active
BV20321DO_SeqPumpY1Start sig. pump seq ARead0=Inactive, 1=Active
BV20322DO_SeqPumpY2Start sig. pump seq BRead0=Inactive, 1=Active
BV20323DO_SeqPumpY3Start sig. pump seq CRead0=Inactive, 1=Active
BV20324DO_SeqPumpY4Start sig. pump seq DRead0=Inactive, 1=Active
BV20325DO_SeqPumpY5Start sig. pump seq ERead0=Inactive, 1=Active
BV20326DO_SeqPumpY6Start sig. pump seq FRead0=Inactive, 1=Active
BV20327DO_SeqPumpY7Start sig. pump seq GRead0=Inactive, 1=Active
BV20328DO_SeqPumpY8Start sig. pump seq HRead0=Inactive, 1=Active
BV20329DO_SeqPumpY9Start sig. pump seq IRead0=Inactive, 1=Active
BV20330DO_SeqPumpY10Start sig. pump seq JRead0=Inactive, 1=Active
BV20331DO_SAFStartStart sig. Supply air fanRead0=Inactive, 1=Active
BV20332DO_EAFStartStart sig. Extract air fanRead0=Inactive, 1=Active
BV20333DO_1DO1Read0=Inactive, 1=Active
BV20334DO_2DO2Read0=Inactive, 1=Active
BV20335DO_3DO3Read0=Inactive, 1=Active
BV20336DO_4DO4Read0=Inactive, 1=Active
BV20337DO_5DO5Read0=Inactive, 1=Active
BV20338DO_6DO6Read0=Inactive, 1=Active
BV20339DO_7DO7Read0=Inactive, 1=Active
BV20340DOExp1_1DO1 Exp. unit 1Read0=Inactive, 1=Active
BV20341DOExp1_2DO2 Exp. unit 1Read0=Inactive, 1=Active
BV20342DOExp1_3DO3 Exp. unit 1Read0=Inactive, 1=Active
BV20343DOExp1_4DO4 Exp. unit 1Read0=Inactive, 1=Active
BV20344DOExp1_5DO5 Exp. unit 1Read0=Inactive, 1=Active
BV20345DOExp1_6DO6 Exp. unit 1Read0=Inactive, 1=Active
BV20346DOExp1_7DO7 Exp. unit 1Read0=Inactive, 1=Active
BV20347DOExp2_1DO1 Exp. unit 2Read0=Inactive, 1=Active
BV20348DOExp2_2DO2 Exp. unit 2Read0=Inactive, 1=Active
BV20349DOExp2_3DO3 Exp. unit 2Read0=Inactive, 1=Active
BV20350DOExp2_4DO4 Exp. unit 2Read0=Inactive, 1=Active
BV20351DOExp2_5DO5 Exp. unit 2Read0=Inactive, 1=Active
BV20352DOExp2_6DO6 Exp. unit 2Read0=Inactive, 1=Active
BV20353DOExp2_7DO7 Exp. unit 2Read0=Inactive, 1=Active
BV20354DO_8DO8Read0=Inactive, 1=Active
BV20368NeedHeatActiveSupport heatingRead0=INACTIVE, 1=ACTIVE
BV20369NeedCoolActiveSupport coolingRead0=INACTIVE, 1=ACTIVE
BV20370DemandCO2ActiveSupport CO2Read0=INACTIVE, 1=ACTIVE
BV20371RecirculationRunActiveRecycle runRead0=INACTIVE, 1=ACTIVE
BV20372DeIcingActiveDe-icingRead0=INACTIVE, 1=ACTIVE
BV20373DO_Auxiliary1Actual status of auxiliary output 1Read0=INACTIVE, 1=ACTIVE
BV20374DO_Auxiliary2Actual status of auxiliary output 2Read0=INACTIVE, 1=ACTIVE
BV20375DO_Auxiliary3Actual status of auxiliary output 3Read0=INACTIVE, 1=ACTIVE
BV20376DO_Zone1HeatPumpActual status of zone 1 heat pumpRead0=INACTIVE, 1=ACTIVE
BV20377DO_Zone2HeatPumpActual status of zone 2 heat pumpRead0=INACTIVE, 1=ACTIVE
BV20378DO_Zone3HeatPumpActual status of zone 3 heat pumpRead0=INACTIVE, 1=ACTIVE
BV20379DO_Zone1CoolPumpActual status of zone 1 cool pumpRead0=INACTIVE, 1=ACTIVE
BV20380DO_Zone2CoolPumpActual status of zone 2 cool pumpRead0=INACTIVE, 1=ACTIVE
BV20381DO_Zone3CoolPumpActual status of zone 3 cool pumpRead0=INACTIVE, 1=ACTIVE
BV20382FrostProtFanReductionActiveIs set if ongoing fan reduction when freeze riskRead0=INACTIVE, 1=ACTIVE
BV20383FeedbackDXAOFreezeFreeze AO when DX-compressor is defrostingRead0=INACTIVE, 1=ACTIVE
CAL1HolidayPlanThe holiday plan for time channelsWrite
NC1AlarmClassANotification class for alarms of class ARead
NC2AlarmClassBNotification class for alarms of class BRead
NC3AlarmClassCNotification class for events of class CRead
SCH1TC_FanLowSpeedThe start/stop times for Fan low speedWrite
SCH2TC_FanNormalSpeedThe start/stop times for Fan normal speedWrite
SCH3TC_FanHighSpeedThe start/stop times for Fan high speedWrite
SCH4TC_Extra1The start/stop times for extra time channel 1Write
SCH5TC_Extra2The start/stop times for extra time channel 2Write
SCH6TC_Extra3The start/stop times for extra time channel 3Write
SCH7TC_Extra4The start/stop times for extra time channel 4Write
MV30272TC_FanLowSpeed_StatusManual/Auto Low Speed time channelWrite1=Man Off, 2=Man On, 3=Forced Off, 4=Forced On, 5=Auto
MV30273TC_FanNormalSpeed_StatusMan/Auto Normal Speed time channelWrite1=Man Off, 2=Man On, 3=Forced Off, 4=Forced On, 5=Auto
MV30274TC_FanHighSpeed_StatusMan/Auto High Speed time channelWrite1=Man Off, 2=Man On, 3=Forced Off, 4=Forced On, 5=Auto
MV30275TC_Extra1_StatusMan/Auto Timer 1Write1=Man Off, 2=Man On, 3=Forced Off, 4=Forced On, 5=Auto
MV30276TC_Extra2_StatusMan/Auto Timer 2Write1=Man Off, 2=Man On, 3=Forced Off, 4=Forced On, 5=Auto
MV30277TC_Extra3_StatusMan/Auto Timer 3Write1=Man Off, 2=Man On, 3=Forced Off, 4=Forced On, 5=Auto
MV30278TC_Extra4_StatusMan/Auto Timer 4Write1=Man Off, 2=Man On, 3=Forced Off, 4=Forced On, 5=Auto
MV30549DOSelect_SeqPumpY1Run mode pump seq AWrite1=Man off, 2=Man on, 3=Auto
MV30550DOSelect_SeqPumpY2Run mode pump seq BWrite1=Man off, 2=Man on, 3=Auto
MV30551DOSelect_SeqPumpY3Run mode pump seq CWrite1=Man off, 2=Man on, 3=Auto
MV30552DOSelect_SeqPumpY4Run mode pump seq DWrite1=Man off, 2=Man on, 3=Auto
MV30553DOSelect_SeqPumpY5Run mode pump seq EWrite1=Man off, 2=Man on, 3=Auto
MV30554DOSelect_SeqPumpY6Run mode pump seq FWrite1=Man off, 2=Man on, 3=Auto
MV30555DOSelect_SeqPumpY7Run mode pump seq GWrite1=Man off, 2=Man on, 3=Auto
MV30556DOSelect_SeqPumpY8Run mode pump seq HWrite1=Man off, 2=Man on, 3=Auto
MV30557DOSelect_SeqPumpY9Run mode pump seq IWrite1=Man off, 2=Man on, 3=Auto
MV30558DOSelect_SeqPumpY10Run mode pump seq JWrite1=Man off, 2=Man on, 3=Auto
MV30559DOSelect_RecirculationAirDamperRun mode recirc. damperWrite1=Close, 2=Open, 3=Auto
MV30560DOSelect_OutdoorAirDamperRun mode fresh air damperWrite1=Close, 2=Open, 3=Auto
MV30561DOSelect_ExhaustAirDamperRun mode exhaust airWrite1=Close, 2=Open, 3=Auto
MV30562DOSelect_HumidityStartRun mode humidity start signalWrite1=Off, 2=On, 3=Auto
MV30563DOSelect_ChangeOver1Select changeOver ExternalWrite1=Heating, 2=Cooling, 3=Auto
MV30564DOSelect_ChangeOver2Select changeOver ExternalWrite1=Heating, 2=Cooling, 3=Auto
MVmin30565AirUnitAutoModeRunning mode air unitWrite1=OFF, 2=Manual, 3=AUTO, 4=Low speed, 5=Normal speed, 6=High speed
MV30566AirUnitManualMan. setting for Air unit in Man. modeWrite1=Stop, 2=Starting up, 3=Low speed run, 4=Normal speed run, 5=High speed run, 6=Heat support run, 7=Cool support run, 8=CO2 Run, 9=Free cool run, 10=Fan stop run, 11=Fire run, 12=Smoke run, 13=Recirculation run, 14=DeIcing run
MV30567SAFAutoModeRunning mode SAFWrite1=OFF, 2=Manual output, 3=AUTO, 4=Manual setpoint, 5=Low speed, 6=Normal speed, 7=High speed
MV30570EAFAutoModeRunning mode EAFWrite1=OFF, 2=Manual output, 3=AUTO, 4=Manual setpoint, 5=Low speed, 6=Normal speed, 7=High speed
MVmin30573ExternalControlExternal cont.Write1=No External control, 2=Extended run speed 1, 3=Extended run speed 2, 4=Extended run speed 3, 5=External stop, 6=External stop with support control, 7=Start Free cooling, 8=Recirculation
MV30574AirUnitServiceStopStop the air unit with No 1 prioWrite1=No, 2=Yes
MV30585VentControlSelect temp. cont. modeWrite1=Const.supply air, 2=Outdoor comp. supply air, 3=Cascade room temp cont., 4=Extract temp cont., 5=Outdoor dep. supply or room temp, 6=Outdoor dep. supply or extract temp, 7=Cascade outdoor comp. room temp cont., 8=Cascade outdoor comp. extract temp cont., 9=Extract air dep. supply air temp.
MV30586FanTypeSelect fan cont. modeWrite1=Freq. cont. pressure, 2=Freq. cont. air flow, 3=Freq. cont. manually, 4=Direct Freq. cont., 5=Freq. cont. with slave cont. EAF, 6=Freq. cont. with slave cont. EAF air flow dep., 7=Freq. cont. with slave cont. SAF, 8=Freq. cont. with slave cont. SAF air flow dep.
MV30610SAFSetpointSelectSAF setp. selectWrite1=Constant setpoints, 2=Offset of normal speed setpoint
MV30611EAFSetpointSelectEAF setp. selectWrite1=Constant setpoints, 2=Offset of normal speed setpoint
MV30642SAFModeFreeCoolSAF speed in freecool modeWrite1=Off/Auto, normal setp., 2=Man. setp., 3=Man. output, 4=Low speed setp., 5=Normal speed setp., 6=High speed setp.
MV30645SAFModeFireSAF speed in fire modeWrite1=Off/Auto, normal setp., 2=Man. setp., 3=Man. output, 4=Low speed setp., 5=Normal speed setp., 6=High speed setp.
MV30648SAFModeSmokeSAF speed in smoke modeWrite1=Off/Auto, normal setp., 2=Man. setp., 3=Man. output, 4=Low speed setp., 5=Normal speed setp., 6=High speed setp.
MV30651SAFModeRecirculationSAF speed in recirc. modeWrite1=Off/Auto, normal setp., 2=Man. setp., 3=Man. output, 4=Low speed setp., 5=Normal speed setp., 6=High speed setp.
MV30654EAFModeFreeCoolEAF speed in freecool modeWrite1=Off/Auto, normal setp., 2=Man. setp., 3=Man. output, 4=Low speed setp., 5=Normal speed setp., 6=High speed setp.
MV30657EAFModeFireEAF speed in fire modeWrite1=Off/Auto, normal setp., 2=Man. setp., 3=Man. output, 4=Low speed setp., 5=Normal speed setp., 6=High speed setp.
MV30660EAFModeSmokeEAF speed in smoke modeWrite1=Off/Auto, normal setp., 2=Man. setp., 3=Man. output, 4=Low speed setp., 5=Normal speed setp., 6=High speed setp.
MV30663EAFModeRecirculationEAF speed in recirc. modeWrite1=Off/Auto, normal setp., 2=Man. setp., 3=Man. output, 4=Low speed setp., 5=Normal speed setp., 6=High speed setp.
MV30713AOSelect_HumidityRunning mode Humidification/DehumidificationWrite1=Manual off, 2=Manual on, 3=Auto
MV30715AOSelect_ExtraControllerManual/Auto Extra contr.Write1=Manual off, 2=Manual on, 3=Auto
MV30717AOSelect_SequenceY1Seq.A contr. ModeWrite1=Manual off, 2=Manual on, 3=Auto
MV30719AOSelect_SequenceY2Seq.B contr. modeWrite1=Manual off, 2=Manual on, 3=Auto
MV30721AOSelect_SequenceY3Seq.C contr. modeWrite1=Manual off, 2=Manual on, 3=Auto
MV30723AOSelect_SequenceY4Seq.D contr. modeWrite1=Manual off, 2=Manual on, 3=Auto
MV30725AOSelect_SequenceY5Seq.E contr. modeWrite1=Manual off, 2=Manual on, 3=Auto
MV30727AOSelect_SequenceY6Seq.F contr. modeWrite1=Manual off, 2=Manual on, 3=Auto
MV30729AOSelect_SequenceY7Seq.G contr. modeWrite1=Manual off, 2=Manual on, 3=Auto
MV30731AOSelect_SequenceY8Seq.H contr. modeWrite1=Manual off, 2=Manual on, 3=Auto
MV30733AOSelect_SequenceY9Seq.I contr. modeWrite1=Manual off, 2=Manual on, 3=Auto
MV30735AOSelect_SequenceY10Seq.J contr. modeWrite1=Manual off, 2=Manual on, 3=Auto
MV30754FireDampersAutoModeRun. mode fire damperWrite1=Close, 2=Open, 3=Auto
MV30776ExtraControllerModeControl mode ex. contr.Write1=Heating, 2=Cooling
MV30777SumAlarm1Sum alarm 1 config, defines which alarms that should be on theWrite1=Off, 2=A+B+C, 3=A+B, 4=B+C, 5=A+C, 6=A, 7=B, 8=C
MV30778SumAlarm2Sum alarm 2 config., defines which alarms that should be on theWrite1=Off, 2=A+B+C, 3=A+B, 4=B+C, 5=A+C, 6=A, 7=B, 8=C
MV30791RecircTempControlEnable supply air temp cont. when recirc. runWrite1=No temp control, 2=Heating/cooling, 3=Only heating, 4=Only cooling
MV30814SupplyPIDFreezeFreeze supply PID controlWrite1=Off, 2=On
MV30888FrostProtFanReduction1Enable fan reduction when freeze risk freeze protection temperature 1Write1=Off, 2=On
MV30889FrostProtFanReduction2Enable fan reduction when freeze risk freeze protection temperature 2Write1=Off, 2=On
MV30890FrostProtFanReduction3Enable fan reduction when freeze risk freeze protection temperature 3Write1=Off, 2=On
MV30891FrostProtFanReductionZone1Enable fan reduction when freeze risk freeze protection temperature zone 1Write1=Off, 2=On
MV30892FrostProtFanReductionZone2Enable fan reduction when freeze risk freeze protection temperature zone 2Write1=Off, 2=On
MV30893FrostProtFanReductionZone3Enable fan reduction when freeze risk freeze protection temperature zone 3Write1=Off, 2=On
MVmin40396UnitModeRun mode.Read1=Stop, 2=Starting up, 3=Low speed run, 4=Normal speed run, 5=High speed run, 6=Heating support run, 7=Cooling support run, 8=CO2 Run, 9=Free cool run, 10=Fan stop run, 11=Fire run, 12=Smoke run, 13=Recirculation run, 14=DeIcing run
MVmin40397UnitModeControlIndicates what is triggering the curr. run modeRead1=Nothing, 2=Time schedule, 3=Manual run, 4=Digital Input, 5=Alarm, 6=External control, 7=Service stop
MV40398ActiveSeqTypeActive seq. typeRead1=Heating, 2=Cooling
MV40420SAFSpeedSAF speedRead1=Off, 2=Low speed, 3=Normal speed, 4=High speed, 5=Special
MV40421EAFSpeedEAF speedRead1=Off, 2=Low speed, 3=Normal speed, 4=High speed, 5=Special
MV40585HumidityModeHumidity control modeRead1=Not active, 2=Humidification, 3=Dehumidificaiton

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Access controller 4.x (4.7) BACnet and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Systemair Access controller 4.x (4.7) BACnet

How many BACnet points does the Systemair Access controller 4.x (4.7) BACnet have?

This list has 1050 BACnet objects: 673 analog values, 295 binary values, 1 calendar, 3 notification classs, 7 schedules, 71 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Systemair Access controller 4.x (4.7) BACnet BACnet points are writable?

362 of the 1050 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Systemair Access controller 4.x (4.7) BACnet BACnet documentation?

The source is Access 4.x Modbus variables and BACnet objects (BACnet object files Access 4.7-1-02 build 78: EDE, state texts, units) (4.7-1-02 build 78), revision 2022-12-14, published free by Systemair at https://systemair.canto.global/direct/other/092hjedtn543je5ivo9m2njh4m/CM9llsIhUF7VaB-6eOjGXK_g-y8/original?content-type=application%2Fzip&name=Access+4.x+Modbus+variables+and+BACnet+objects.zip.

What are the minimum BACnet points to integrate the Systemair Access controller 4.x (4.7) BACnet?

Start with MV 30565 AirUnitAutoMode (Off / manual / auto / forced speed command); MV 30573 ExternalControl (External extended run or stop command); AV 30588 SupplySetpoint (Supply air temperature setpoint); BV 10000 AlaAcknowAll (Acknowledge all alarms); MV 40396 UnitMode (Actual run mode); MV 40397 UnitModeControl (What is driving the current run mode); AV 40292 AI_SupplyAirTemp (Supply air temperature); AV 40294 AI_ExtractAirTemp (Extract air temperature); AV 40290 AI_OutDoorTemp (Outdoor temperature); BV 20007 SumAlarm (Any alarm).

How do I enable BMS control of the Systemair Access controller 4.x (4.7) BACnet?

MV-30565 AirUnitAutoMode: 1=OFF, 2=Manual (state chosen in MV-30566), 3=AUTO, 4=Low, 5=Normal, 6=High speed. MV-30573 ExternalControl gives extended run speeds 1-3 and external stop; MV-30574 AirUnitServiceStop stops the unit with top priority.

Can the BMS supply sensor values to the Systemair Access controller 4.x (4.7) BACnet?

AV-30850 BMS_OutDoorTemp accepts an outdoor temperature from the BMS. BV-20196 CommunicationFaultBMS alarms on a BMS master communication fault; the files give no timeout.

How do I check these points on the real Access controller 4.x (4.7) BACnet?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Systemair BACnet points lists

Source: Access 4.x Modbus variables and BACnet objects (BACnet object files Access 4.7-1-02 build 78: EDE, state texts, units) · 4.7-1-02 build 78 · rev. 2022-12-14. Object names, instances and units are reproduced as published; descriptions are our own.