Systemair SYS GW IMS BAC(A) VRF BACnet gateway BACnet points list

Updated 28 October 2026

Short answer

The SYS GW IMS BAC(A) gateway (IMMP-BAC(A) in the manual) links Systemair VRF systems to a BMS over BACnet IP. It has four RS-485 ports to the outdoor units' X/Y/E bus (up to 64 indoor units per port, 384 indoor and outdoor units in total) and one Ethernet port. Each indoor unit, outdoor unit and HTHM appears as its own BACnet device with fixed object instances, so one template per unit type covers the site. Indoor units take on/off, mode, fan speed, setpoint and swing commands; outdoor units are monitoring only.

This page lists 85 BACnet objects for the Systemair SYS GW IMS BAC(A) VRF BACnet gateway — 21 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Systemair’s own free documentation, linked below.

Manufacturer
Systemair
Model
SYS GW IMS BAC(A) VRF BACnet gateway
Equipment
VRF BACnet IP gateway
Equipment type
VRF & split air conditioners
BACnet objects
85 (21 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
SYS GW IMS BAC(A), SYS GW IMS BAC, IMMP-BAC(A), IMMP-BAC, Systemair VRF BACnet gateway, SYS GW gateway
Source document
Operation and Installation Manual - IMMP-BAC(A) Manual
Download CSV 85 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Systemair SYS GW IMS BAC(A) VRF BACnet gateway

Integration in brief

Wire each RS-485 port to an outdoor unit's X/Y/E bus, set the gateway's IP address and a unique BACnet network number on its web page, restart it, then discover the per-unit BACnet devices. Map each indoor unit's on/off, mode, fan speed and setpoint commands plus room temperature and alarm. Outdoor unit devices are for monitoring; HTHM devices have their own heating and water-heating on/off commands and setpoints (BV 90/91, AV 50/51).

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1On/Off SettingStart/stop indoor unitWrite
MV 1Mode SettingMode command (3 = cool, 4 = heat, 5 = auto)Write
AV 1Temperature SettingSetpoint command, 10-30 °CWrite
MV 2Fan Speed SettingFan speed command (8 = auto)Write
AI 1Room TemperatureIndoor unit room temperatureRead
BI 2Alarm IndicationIndoor unit has an error codeRead
AI 7Malfunction CodeIndoor unit error code; 0 = no errorRead

Enable & remote start

No enable point is documented. Writing BV 1 on starts the indoor unit with its last-used mode, fan speed and setpoint; if the unit was off when the gateway first came online it defaults to cooling at 24 °C, low fan. Locks (BV 4, BV 5, MV 3, MV 5) restrict local changes.

Network setup

Watch out for

Systemair SYS GW IMS BAC(A) VRF BACnet gateway BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

85 of 85 shown
Type
Access
Show
Systemair SYS GW IMS BAC(A) VRF BACnet gateway BACnet Points List
DescriptionStates
AImin1Room Temperature[Indoor unit] Room temperature°CRead
AImin7Malfunction Code[Indoor unit] Error code numberRead0=No error; 1-260=error code, see notes
AI8Outlet Air Temperature[Indoor unit] Outlet (discharge) air temperature°CRead
AI9EXV Opening[Indoor unit] Electronic expansion valve openingRead
AI10Software Version[Indoor unit] Software versionRead
AI11Indoor type[Indoor unit] Indoor unit type codeRead0=4-way cassette; 1=4-way cassette; 2=Wall-mounted; 3=Medium static duct; 4=Low static duct; 5=AHU; 6=High static duct; 7=Compact 4-way cassette; 8=Ceiling & floor; 9=Floor standing; 10=Floor standing; 11=Fresh air processing unit; 12=Inverter split AC; 13=HRV; 14=1-way cassette; 15=2-way cassette; 16=Console; 17=HTHM; 18=Fresh air processing unit; 20=Fresh air processing unit; 21=AHU kit (return air control); 22=Floor standing; 24=AHU kit (discharge air control)
AI12Indoor Horses[Indoor unit] Indoor unit capacity (horsepower)Read
AI13T2A[Indoor unit] T2A temperature°CRead
AI14T2B[Indoor unit] T2B temperature°CRead
BImin2Alarm Indication[Indoor unit] Error presentRead0=No error; 1=Error
BVmin1On/Off Setting[Indoor unit] On/off commandWrite0=Off; 1=On
BV4Remote Control Lock Setting[Indoor unit] Wireless remote control lockWrite0=Unlocked; 1=Locked
BV5Controller Lock Setting[Indoor unit] Wired controller lockWrite0=Unlocked; 1=Locked
MVmin1Mode Setting[Indoor unit] Mode command (HRV units use the second state set)WriteVRF indoor unit: 1=Off; 2=Fan; 3=Cool; 4=Heat; 5=Auto; 6=Dry. HRV: 1=Off; 2=Free cool; 3=Heat exchange; 4=Bypass; 5=Auto
MVmin2Fan Speed Setting[Indoor unit] Fan speed command; 9 (off) is status onlyWrite1-7=Fan speed 1-7 (3-speed models: 1-2=Low; 3-4=Mid; 5-7=High); 8=Auto; 9=Fan off (read only)
MV3Mode Limit Setting[Indoor unit] Mode lockWrite1=Unlocked; 2=Cooling locked; 3=Heating locked
MV5Fan Lock/Unlock Setting[Indoor unit] Fan speed lockWrite1-7=Locked at speed 1-7 (3-speed models: 1-2=Low; 3-4=Mid; 5-7=High); 8=Unlocked
AVmin1Temperature Setting[Indoor unit] Setpoint, 10-30 °C°CWrite
AV2Dual Point (Cooling) Setting[Indoor unit] Auto mode cooling setpoint, 10-30 °C°CWrite
AV3Dual Point (Heating) Setting[Indoor unit] Auto mode heating setpoint, 10-30 °C°CWrite
AV4Cooling Temperature Limit Setting[Indoor unit] Lowest allowed cooling setpoint, 0 = unlocked°CWrite0=Unlocked; 17-30=Lower limit, °C
AV5Heating Temperature Limit Setting[Indoor unit] Highest allowed heating setpoint, 0 = unlocked°CWrite0=Unlocked; 17-30=Upper limit, °C
AV6Swing Setting[Indoor unit] Louver swing angle commandWrite0=Keep current angle; 1-5=Swing angle 1-5; 6=Auto swing off; 7=Auto swing on
MI1Mode Status[Outdoor unit] Operating modeRead1=Off; 2=Reserved; 3=Cooling; 4=Heating; 5=Forced cooling; 6=Master cooling; 7=Master heat; 8=Forced heat
BI1On/Off Status[Outdoor unit] Running statusRead0=Off; 1=On
BI2Alarm Indication[Outdoor unit] Error presentRead0=No error; 1=Error
BI3SV1[Outdoor unit] Solenoid valve SV1 stateRead
BI4SV2[Outdoor unit] Solenoid valve SV2 stateRead
BI5SV3[Outdoor unit] Solenoid valve SV3 stateRead
BI6SV4[Outdoor unit] Solenoid valve SV4 stateRead
BI7SV5[Outdoor unit] Solenoid valve SV5 stateRead
BI8SV6[Outdoor unit] Solenoid valve SV6 stateRead
BI9SV7[Outdoor unit] Solenoid valve SV7 stateRead
BI10SV8[Outdoor unit] Solenoid valve SV8 stateRead
BI11ST1[Outdoor unit] ST1 valve stateRead
BI12ST2[Outdoor unit] ST2 valve stateRead
BI13ST3[Outdoor unit] ST3 valve stateRead
BI14SV8B[Outdoor unit] Solenoid valve SV8B stateRead
BI15SV9[Outdoor unit] Solenoid valve SV9 stateRead
BI17HEATER 1[Outdoor unit] Heater 1 stateRead
BI18HEATER 2[Outdoor unit] Heater 2 stateRead
AI1Ambient Temperatue[Outdoor unit] Outdoor ambient temperature°CRead
AI2Compressor 1 Freq[Outdoor unit] Compressor 1 frequencyHzRead
AI3Compressor 2 Freq[Outdoor unit] Compressor 2 frequencyHzRead
AI4Compressor 1 Discharge Temp[Outdoor unit] Compressor 1 discharge temperature°CRead
AI5Compressor 2 Discharge Temp[Outdoor unit] Compressor 2 discharge temperature°CRead
AI6High Pressure[Outdoor unit] Compressor high pressurebarRead
AI7Low Pressure[Outdoor unit] Compressor low pressurebarRead
AI8Malfunction Code[Outdoor unit] Error code numberRead0=No error; 1-260=error code, see notes
AI9Fan 1 Speed[Outdoor unit] Fan 1 speedRead
AI10Fan 2 Speed[Outdoor unit] Fan 2 speedRead
AI11T3[Outdoor unit] T3 temperature°CRead
AI12T3B[Outdoor unit] T3B temperature (reserved)°CRead
AI13Version[Outdoor unit] Software versionRead
AI14Outdoor type[Outdoor unit] Outdoor unit type codeRead
AI15Outdoor Horses[Outdoor unit] Outdoor unit capacity (horsepower)Read
AI16Exv1 opening[Outdoor unit] Expansion valve 1 openingRead
AI17Exv2 opening[Outdoor unit] Expansion valve 2 openingRead
AI18Exv3 opening[Outdoor unit] Expansion valve 3 opening (reserved)Read
BV1Emergency Stop[Outdoor unit] Emergency stop status (read only)Read0=Emergency stop off; 1=Emergency stop on
AV50Water Heating Temperature Setting[HTHM unit] Water heating setpoint, 25-80 °C°CWrite
AV51Heating Temperature Setting[HTHM unit] Heating setpoint, 25-80 °C°CWrite
AV52Heating Temperature Lock[HTHM unit] Heating setpoint upper limit lock°CWrite0=Unlocked; 25-80=Upper limit, °C; 254=Not adjustable
AV53Water Heating Temperature Lock[HTHM unit] Water heating setpoint upper limit lock°CWrite0=Unlocked; 25-80=Upper limit, °C; 254=Not adjustable
AV60Water Inlet Temperature[HTHM unit] Water inlet temperature°CRead
AV61Water outlet Temperature[HTHM unit] Water outlet temperature°CRead
AV62Water Tank Temperature[HTHM unit] Water tank temperature°CRead
AV63Error Code[HTHM unit] Error code numberRead0=No error; 1-260=error code, see notes
AV64Tf[HTHM unit] Tf temperature°CRead
AV65T2A[HTHM unit] T2A temperature°CRead
AV66T7[HTHM unit] T7 temperature°CRead
AV67T7C[HTHM unit] T7C temperature°CRead
AV68Pe[HTHM unit] Pe pressurebarRead
AV69Pc[HTHM unit] Pc pressurebarRead
AV70EXV 1[HTHM unit] Expansion valve 1 openingRead
AV71EXV 2[HTHM unit] Expansion valve 2 openingRead
AV72Need[HTHM unit] HTHM demandRead
AV73Power[HTHM unit] PowerRead
AV75Compressor Frequency[HTHM unit] Compressor frequencyHzRead
AV76Software Version[HTHM unit] Software versionRead
MV78Heating Lock[HTHM unit] Heating lockWrite1=Lock on; 2=Lock off; 3=Unlock
MV79Heating-water Lock[HTHM unit] Water heating lockWrite1=Lock on; 2=Lock off; 3=Unlock
MI56Current Mode[HTHM unit] Current modeRead1=Off; 4=Heating; 6=Water heating
BV90Heating On/Off[HTHM unit] Heating on/off commandWrite0=Off; 1=On
BV91Water Heating On/Off[HTHM unit] Water heating on/off commandWrite0=Off; 1=On

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SYS GW IMS BAC(A) VRF BACnet gateway and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Systemair SYS GW IMS BAC(A) VRF BACnet gateway

How many BACnet points does the Systemair SYS GW IMS BAC(A) VRF BACnet gateway have?

This list has 85 BACnet objects: 27 analog inputs, 26 analog values, 18 binary inputs, 6 binary values, 2 multi-state inputs, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Systemair SYS GW IMS BAC(A) VRF BACnet gateway BACnet points are writable?

21 of the 85 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Systemair SYS GW IMS BAC(A) VRF BACnet gateway BACnet documentation?

The source is Operation and Installation Manual - IMMP-BAC(A) Manual, published free by Systemair at https://stepimassets.blob.core.windows.net/dsassetsprod/IOM_BACNET_GATEWAY_GB.PDF.

What are the minimum BACnet points to integrate the Systemair SYS GW IMS BAC(A) VRF BACnet gateway?

Start with BV 1 On/Off Setting (Start/stop indoor unit); MV 1 Mode Setting (Mode command (3 = cool, 4 = heat, 5 = auto)); AV 1 Temperature Setting (Setpoint command, 10-30 °C); MV 2 Fan Speed Setting (Fan speed command (8 = auto)); AI 1 Room Temperature (Indoor unit room temperature); BI 2 Alarm Indication (Indoor unit has an error code); AI 7 Malfunction Code (Indoor unit error code; 0 = no error).

How do I enable BMS control of the Systemair SYS GW IMS BAC(A) VRF BACnet gateway?

No enable point is documented. Writing BV 1 on starts the indoor unit with its last-used mode, fan speed and setpoint; if the unit was off when the gateway first came online it defaults to cooling at 24 °C, low fan. Locks (BV 4, BV 5, MV 3, MV 5) restrict local changes.

How do I check these points on the real SYS GW IMS BAC(A) VRF BACnet gateway?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Systemair BACnet points lists

Source: Operation and Installation Manual - IMMP-BAC(A) Manual. Object names, instances and units are reproduced as published; descriptions are our own.