 "manufacturer": "Systemair",
 "manufacturer_slug": "systemair",
 "model": "Access controller 5.x (ControllerProgram) BACnet",
 "model_slug": "access-5-controller",
 "aliases": [
  "Systemair Access",
  "Access 5.5",
  "Access 5.5-1-01",
  "Systemair Access controller",
  "Access ControllerProgram",
  "EXOL"
 ],
 "equipment_type": "Air handling unit controller",
 "applies_to": "Systemair air handling units controlled by the Systemair Access controller running application 5.x (published for 5.5-1-01 build 411).",
 "summary": "Systemair's Access controller, fitted to its larger air handling units, is a native BACnet device; Systemair publishes its object list as an EDE file set (objects, state texts, units) rather than a PDF table. The 1,201 objects cover run-mode commands and settings (S_ variables), actual values and I/O (A_ variables), fan and damper data from the Modbus-connected motors (CA_ variables), alarms (AL_), trend logs, schedules, a calendar and notification classes. One application covers many unit types, so most objects only matter when the matching function is configured.",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": "Access 5.5-1-01 build 411",
 "default_device_instance": 114112,
 "access_inferred": true,
 "notes": [
  "The EDE settable column is 'N' for every object, so access is inferred: S_ (setting) objects and the A_BMS_ inputs are shown writable, everything else read-only.",
  "State texts come from the EDE state-text table; multistate values are numbered from 1.",
  "Most temperature, pressure and airflow objects carry BACnet unit NO-UNITS in the EDE, so their units are blank here (temperatures are °C).",
  "Device instance 114112 is the one in the published EDE; set a unique value per unit.",
  "Sequences A-J, zones 1-4, heat pump (HP) and up to 10 supply/extract fan motors are generic slots; only configured ones carry data.",
  "The EDE does not name the data link; Systemair's Access 5 communication manual (472956) describes BACnet/IP on the B-BC profile from 5.0-1-00."
 ],
 "source": {
  "title": "Access 5.x Modbus variables and BACnet objects (Communication document 5.5-1-01 build 411: BACnet_Access_ControllerProgram EDE, state texts, units)",
  "doc_number": "5.5-1-01 build 411",
  "revision_date": "2026-03",
  "url": "https://systemair.canto.global/direct/other/tu4qsjtsu544vba9gqgd0mfv4t/p74ln_6WRy-NkSgEmII-SnQmHFY/original?content-type=application%2Fzip&name=Access+5.x+Modbus+variables+and+BACnet+objects.zip"
 },
 "integration": {
  "summary": "Set MV-12 AirUnitAutoMode to AUTO (3) to let the unit follow its schedule, or to Low/Normal/High speed to force it; MV-31 ExternalControl gives BMS-style extended run and stop commands. Read MV-15 UnitMode and MV-16 UnitModeControl to see what the unit is doing and why, map the supply/extract temperatures and supply setpoint, and watch BV-9..12 sum alarms with BV-8 to acknowledge all alarms. Outdoor temperature and summer/winter or changeover modes can be supplied by the BMS through the BMS_ objects.",
  "minimum_points": [
   {
    "ref": "MV 12",
    "name": "AirUnitAutoMode",
    "why": "Off / manual / auto / forced speed command"
   },
   {
    "ref": "MV 31",
    "name": "ExternalControl",
    "why": "External extended run or stop command"
   },
   {
    "ref": "AV 39",
    "name": "SupplySetpoint",
    "why": "Supply air temperature setpoint"
   },
   {
    "ref": "BV 8",
    "name": "AlaAcknowAll",
    "why": "Acknowledge all alarms"
   },
   {
    "ref": "MV 15",
    "name": "UnitMode",
    "why": "Actual run mode"
   },
   {
    "ref": "MV 16",
    "name": "UnitModeControl",
    "why": "What is driving the current run mode"
   },
   {
    "ref": "AI 3",
    "name": "AI_SupplyAirTemp",
    "why": "Supply air temperature"
   },
   {
    "ref": "AI 5",
    "name": "AI_ExtractAirTemp",
    "why": "Extract air temperature"
   },
   {
    "ref": "AI 1",
    "name": "AI_OutDoorTemp",
    "why": "Outdoor temperature"
   },
   {
    "ref": "BV 9",
    "name": "SumAlarm",
    "why": "Any alarm"
   }
  ],
  "enable": "MV-12 AirUnitAutoMode: 1=OFF, 2=Manual (uses MV-13 AirUnitManual), 3=AUTO, 4=Low speed, 5=Normal speed, 6=High speed. MV-31 ExternalControl adds extended run low/normal/high, external stop, start free cooling and recirculation. MV-32 AirUnitServiceStop stops the unit with top priority.",
  "heartbeat": null,
  "remote_sensors": "AV-466 BMS_OutDoorTemp takes an outdoor temperature from BACnet/Modbus; BV-156 BMS_SummerMode and BV-157/158 BMS_ChangeOver1/2 take summer/winter and cooling/heating changeover modes. BV-51 CommunicationFaultBmsMaster is an alarm for a BMS master communication fault; the files do not state its timeout.",
  "setup": [
   "The published EDE uses device instance 114112 (device name Access); the device ID must be unique on the network.",
   "Per the Access 4.x communication manual, BACnet/IP is disabled on delivery and must be switched on in the controller's communication settings.",
   "Entering a BBMD address (host:port, default port 47808) makes Access a BACnet/IP foreign device that ignores other broadcasts (Access 4.x manual).",
   "Systemair supplies EDE, object-type, state-text and unit files plus a Modbus cross-reference in one zip per Access release; use the one matching the controller's software.",
   "The Modbus cross-reference in the same package shows Modbus TCP enabled with device address 1."
  ],
  "gotchas": [
   "Access is inferred: the EDE marks every object as not settable, so confirm writes on site.",
   "Many temperature and pressure objects report BACnet units NO-UNITS even though values are °C or Pa.",
   "S_ setting objects (PID bands, curves, limits) are configuration settings.",
   "Multistate states start at 1 in BACnet, so 'AUTO' on MV-12 is value 3."
  ]
 },
 "points": [
  {
   "type": "CAL",
   "instance": 1,
   "name": "Calendar",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "SCH",
   "instance": 2,
   "name": "TC_FanSpeed",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "SCH",
   "instance": 3,
   "name": "TC_Extra1",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "SCH",
   "instance": 4,
   "name": "TC_Extra2",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "SCH",
   "instance": 5,
   "name": "TC_Extra3",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "SCH",
   "instance": 6,
   "name": "TC_Extra4",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "DOSelect_SeqPumpA",
   "description": "Run mode pump seq A",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "DOSelect_SeqPumpB",
   "description": "Run mode pump seq B",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "DOSelect_SeqPumpC",
   "description": "Run mode pump seq C",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "DOSelect_SeqPumpD",
   "description": "Run mode pump seq D",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "DOSelect_SeqPumpE",
   "description": "Run mode pump seq E",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "DOSelect_SeqPumpF",
   "description": "Run mode pump seq F",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 7,
   "name": "DOSelect_SeqPumpG",
   "description": "Run mode pump seq G",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 8,
   "name": "DOSelect_SeqPumpH",
   "description": "Run mode pump seq H",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 9,
   "name": "DOSelect_SeqPumpI",
   "description": "Run mode pump seq I",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 10,
   "name": "DOSelect_SeqPumpJ",
   "description": "Run mode pump seq J",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 11,
   "name": "DOSelect_RecircAirDamper",
   "description": "Run mode recirc. damper",
   "units": "",
   "access": "W",
   "states": "1=Close, 2=Open, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 72,
   "name": "DOSelect_OutdoorAirDamper",
   "description": "Run mode outdoor damper",
   "units": "",
   "access": "W",
   "states": "1=Close, 2=Open, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 73,
   "name": "DOSelect_ExhaustAirDamper",
   "description": "Run mode exhaust damper",
   "units": "",
   "access": "W",
   "states": "1=Close, 2=Open, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 74,
   "name": "DOSelect_HumidityStart",
   "description": "Run mode HumidityStart",
   "units": "",
   "access": "W",
   "states": "1=Close, 2=Open, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 75,
   "name": "DOSelect_ChangeOver1",
   "description": "Run mode changeover 1",
   "units": "",
   "access": "W",
   "states": "1=Close, 2=Open, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 76,
   "name": "DOSelect_ChangeOver2",
   "description": "Run mode changeover 2",
   "units": "",
   "access": "W",
   "states": "1=Close, 2=Open, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 12,
   "name": "AirUnitAutoMode",
   "description": "Running mode air unit",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=Manual, 3=AUTO, 4=Low speed, 5=Normal speed, 6=High speed"
  },
  {
   "type": "MV",
   "instance": 13,
   "name": "AirUnitManual",
   "description": "Man. setting for Air unit in Man. mode",
   "units": "",
   "access": "W",
   "states": "1=Stop, 2=Starting up, 3=Low speed, 4=Normal speed, 5=High speed, 6=Support heating, 7=Support cooling, 8=CO2 mode, 9=Free cooling, 10=Cool down mode, 11=Fire mode, 12=Smoke mode, 13=Recirculation mode, 14=Defrosting mode"
  },
  {
   "type": "MV",
   "instance": 14,
   "name": "VentControl",
   "description": "Select temp. cont. mode",
   "units": "",
   "access": "W",
   "states": "1=Const.supply air, 2=Outdoor comp. supply air, 3=Cascade room temp cont., 4=Extract temp cont., 5=Outdoor dep. supply or room temp, 6=Outdoor dep. supply or extract temp, 7=Cascade outdoor comp. room temp cont., 8=Cascade outdoor comp. extract temp cont., 9=Extract air dep. supply air temp."
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "FilterAlarmReset",
   "description": "Resets the filter alarm counter",
   "units": "",
   "access": "W",
   "states": "0=NORMAL, 1=ACKNOWLEDGE"
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "AOManual_SequenceA",
   "description": "Seq.A contr. output if man. on mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "AOManual_SequenceB",
   "description": "Seq.B contr. output if man. on mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "AOManual_SequenceC",
   "description": "Seq.C contr. output if man. on mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "AOManual_SequenceD",
   "description": "Seq.D contr. output if man. on mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "AOManual_SequenceE",
   "description": "Seq.E contr. output if man. on mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "AOManual_SequenceF",
   "description": "Seq.F contr. output if man. on mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "AOManual_SequenceG",
   "description": "Seq.G contr. output if man. on mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "AOManual_SequenceH",
   "description": "Seq.H contr. output if man. on mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "AOManual_SequenceI",
   "description": "Seq.I contr. output if man. on mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "AOManual_SequenceJ",
   "description": "Seq.J contr. output if man. on mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "AOManual_Humidity",
   "description": "Humidification/Dehumidification cont. output if man. mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "AOManual_ExtraController",
   "description": "Manual/Auto Extra contr.",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 17,
   "name": "AOSelect_SequenceA",
   "description": "Seq.A contr. Mode",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 18,
   "name": "AOSelect_SequenceB",
   "description": "Seq.B contr. Mode",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 19,
   "name": "AOSelect_SequenceC",
   "description": "Seq.C contr. Mode",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 20,
   "name": "AOSelect_SequenceD",
   "description": "Seq.D contr. Mode",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 21,
   "name": "AOSelect_SequenceE",
   "description": "Seq.E contr. Mode",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 22,
   "name": "AOSelect_SequenceF",
   "description": "Seq.F contr. Mode",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 23,
   "name": "AOSelect_SequenceG",
   "description": "Seq.G contr. Mode",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 24,
   "name": "AOSelect_SequenceH",
   "description": "Seq.H contr. Mode",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 25,
   "name": "AOSelect_SequenceI",
   "description": "Seq.I contr. Mode",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 26,
   "name": "AOSelect_SequenceJ",
   "description": "Seq.J contr. Mode",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 27,
   "name": "AOSelect_Humidity",
   "description": "Running mode Humidification/Dehumidification",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 28,
   "name": "AOSelect_ExtraController",
   "description": "Manual/Auto Extra contr.",
   "units": "",
   "access": "W",
   "states": "1=Man off, 2=Man on, 3=Auto"
  },
  {
   "type": "MV",
   "instance": 29,
   "name": "SAFAutoMode",
   "description": "Running mode SAF",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=Manual output, 3=AUTO, 4=Manual setpoint, 5=Low speed, 6=Normal speed, 7=High speed"
  },
  {
   "type": "MV",
   "instance": 30,
   "name": "EAFAutoMode",
   "description": "Running mode EAF",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=Manual output, 3=AUTO, 4=Manual setpoint, 5=Low speed, 6=Normal speed, 7=High speed"
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "SAFManualSetpoint",
   "description": "Man. setp. SAF if Man. mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "EAFManualSetpoint",
   "description": "Man. setp. EAF if Man. mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "SAFManualOutput",
   "description": "Man. output SAF if Man. mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "EAFManualOutput",
   "description": "Man. output EAF if Man. mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 31,
   "name": "ExternalControl",
   "description": "External cont.",
   "units": "",
   "access": "W",
   "states": "1=No External control, 2=Extended run low speed, 3=Extended run normal speed, 4=Extended run high speed, 5=External stop, 6=External stop with support control, 7=Start Free cooling, 8=Recirculation"
  },
  {
   "type": "MV",
   "instance": 32,
   "name": "AirUnitServiceStop",
   "description": "Stop the air unit with No 1 prio",
   "units": "",
   "access": "W",
   "states": "1=No, 2=Yes"
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "SeqPumpOutdLimitA",
   "description": "Pump outd. temp. limit seq A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "SeqPumpOutdLimitB",
   "description": "Pump outd. temp. limit seq B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "SeqPumpOutdLimitC",
   "description": "Pump outd. temp. limit seq C",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "SeqPumpOutdLimitD",
   "description": "Pump outd. temp. limit seq D",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "SeqPumpOutdLimitE",
   "description": "Pump outd. temp. limit seq E",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "SeqPumpOutdLimitF",
   "description": "Pump outd. temp. limit seq F",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "SeqPumpOutdLimitG",
   "description": "Pump outd. temp. limit seq G",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "SeqPumpOutdLimitH",
   "description": "Pump outd. temp. limit seq H",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "SeqPumpOutdLimitI",
   "description": "Pump outd. temp. limit seq I",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "SeqPumpOutdLimitJ",
   "description": "Pump outd. temp. limit seq J",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 33,
   "name": "FanType",
   "description": "Select fan cont. mode",
   "units": "",
   "access": "W",
   "states": "1=Freq. cont. pressure, 2=Freq. cont. air flow, 3=Freq. cont. manually, 4=Direct Freq. cont., 5=Freq. cont. with slave cont. EAF, 6=Freq. cont. with slave cont. EAF air flow dep., 7=Freq. cont. with slave cont. SAF, 8=Freq. cont. with slave cont. SAF air flow dep."
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "SupplySetpoint",
   "description": "Setp. supply air temp. when constant supply air temp. func.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "ExtractSetpoint",
   "description": "Setp. extract air temp if extract air temp cont. func.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "SupplySetpointMax",
   "description": "Max limit of supply setp. when cascade cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "SupplySetpointMin",
   "description": "Min limit of supply setp. when cascade cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "SupplySetpOffsetLow",
   "description": "Temp. setp. Offset in low speed",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "SupplySetpOffsetHigh",
   "description": "Temp. setp. Offset in high speed",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "SummerModeSupplySetpoint",
   "description": "Supply temp setp. at summer time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "SummerModeOutdoortemp",
   "description": "Outd. temp for switching bet. summer and winter",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "SAFLowSpeedPressure",
   "description": "Setp. low sp. supply air fan press.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "SAFNormalSpeedPressure",
   "description": "Setp. normal sp. supply air fan press.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "SAFHighSpeedPressure",
   "description": "Setp. high sp. supply air fan press.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "EAFLowSpeedPressure",
   "description": "Setp. low sp. Extract air fan press.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "EAFNormalSpeedPressure",
   "description": "Setp. normal sp. Extract air fan press.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "EAFHighSpeedPressure",
   "description": "Setp. high sp. Extract air fan press.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "SAFLowspeedAirFlow",
   "description": "Setp. low sp. SAF air flow.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "SAFNormalspeedAirFlow",
   "description": "Setp. normal sp. SAF air flow.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "SAFHighspeedAirFlow",
   "description": "Setp. high sp. SAF air flow.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "EAFLowspeedAirFlow",
   "description": "Setp. low sp. EAF air flow.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "EAFNormalspeedAirFlow",
   "description": "Setp. normal sp. EAF air flow.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "EAFHighspeedAirFlow",
   "description": "Setp. high sp. EAF air flow.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "SAFLowSpeedOutput",
   "description": "Output signal low speed SAF if Freq. cont. manually",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "SAFNormalSpeedOutput",
   "description": "Output signal normal speed SAF if Freq. cont. manually",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "SAFHighspeedOutput",
   "description": "Output signal high speed SAF if Freq. cont. manually",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "EAFLowSpeedOutput",
   "description": "Output signal low speed EAF if Freq. cont. manually",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "EAFNormalSpeedOutput",
   "description": "Output signal normal speed EAF if Freq. cont. manually",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "EAFHighspeedOutput",
   "description": "Output signal high speed EAF if Freq. cont. manually",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 34,
   "name": "SAFModeFreeCool",
   "description": "SAF speed in freecool mode",
   "units": "",
   "access": "W",
   "states": "1=Off/Auto, 2=normal setp., 3=Man. setp., 4=Man. output, 5=Low speed setp., 6=Normal speed setp., 7=High speed setp."
  },
  {
   "type": "MV",
   "instance": 35,
   "name": "SAFModeFire",
   "description": "SAF speed in fire mode",
   "units": "",
   "access": "W",
   "states": "1=Off/Auto, 2=normal setp., 3=Man. setp., 4=Man. output, 5=Low speed setp., 6=Normal speed setp., 7=High speed setp."
  },
  {
   "type": "MV",
   "instance": 36,
   "name": "SAFModeSmoke",
   "description": "SAF setp. in smoke mode",
   "units": "",
   "access": "W",
   "states": "1=Off/Auto, 2=normal setp., 3=Man. setp., 4=Man. output, 5=Low speed setp., 6=Normal speed setp., 7=High speed setp."
  },
  {
   "type": "MV",
   "instance": 37,
   "name": "SAFModeRecirculation",
   "description": "SAF speed in recirc. mode",
   "units": "",
   "access": "W",
   "states": "1=Off/Auto, 2=normal setp., 3=Man. setp., 4=Man. output, 5=Low speed setp., 6=Normal speed setp., 7=High speed setp."
  },
  {
   "type": "MV",
   "instance": 38,
   "name": "EAFModeFreeCool",
   "description": "EAF speed in freecool mode",
   "units": "",
   "access": "W",
   "states": "1=Off/Auto, 2=normal setp., 3=Man. setp., 4=Man. output, 5=Low speed setp., 6=Normal speed setp., 7=High speed setp."
  },
  {
   "type": "MV",
   "instance": 39,
   "name": "EAFModeFire",
   "description": "EAF speed in fire mode",
   "units": "",
   "access": "W",
   "states": "1=Off/Auto, 2=normal setp., 3=Man. setp., 4=Man. output, 5=Low speed setp., 6=Normal speed setp., 7=High speed setp."
  },
  {
   "type": "MV",
   "instance": 40,
   "name": "EAFModeSmoke",
   "description": "EAF speed in smoke mode",
   "units": "",
   "access": "W",
   "states": "1=Off/Auto, 2=normal setp., 3=Man. setp., 4=Man. output, 5=Low speed setp., 6=Normal speed setp., 7=High speed setp."
  },
  {
   "type": "MV",
   "instance": 41,
   "name": "EAFModeRecirculation",
   "description": "EAF speed in recirc. mode",
   "units": "",
   "access": "W",
   "states": "1=Off/Auto, 2=normal setp., 3=Man. setp., 4=Man. output, 5=Low speed setp., 6=Normal speed setp., 7=High speed setp."
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "SAFManSetpFreeCool",
   "description": "SAF setp. in freecool mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "SAFManSetpFire",
   "description": "SAF setp. in fire mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "SAFManSetpSmoke",
   "description": "SAF man. output in smoke mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "SAFManSetpRecirculation",
   "description": "SAF setp. in recirc. mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "EAFManSetpFreeCool",
   "description": "EAF setp. in freecool mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "EAFManSetpFire",
   "description": "EAF setp. in fire mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "EAFManSetpSmoke",
   "description": "EAF setp. in smoke mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "EAFManSetpRecirculation",
   "description": "EAF setp. in recirc. mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "SAFManOutFreeCool",
   "description": "SAF man. output in freecool mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "SAFManOutFire",
   "description": "SAF man. output in fire mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "SAFManOutSmoke",
   "description": "SAF man. output in smoke mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 76,
   "name": "SAFManOutRecirculation",
   "description": "SAF man. output in recirc. mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 77,
   "name": "EAFManOutFreeCool",
   "description": "EAF man. output in freecool mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 78,
   "name": "EAFManOutFire",
   "description": "EAF man. output in fire mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "EAFManOutSmoke",
   "description": "EAF man. output in smoke mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "EAFManOutRecirculation",
   "description": "EAF man. output in recirc. mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "EAFFrequencyFact",
   "description": "Factor for controlling EAF if CAV fan cont. is configured",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "Curve1_X1",
   "description": "Outd. temp for 1st curvep. for outd. comp. setp.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 83,
   "name": "Curve1_X2",
   "description": "Outd. temp for 2nd curvep. for outd. comp. setp.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "Curve1_X3",
   "description": "Outd. temp for 3rd curvep. for outd. comp. setp.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "Curve1_X4",
   "description": "Outd. temp for 4th curvep. for outd. comp. setp.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "Curve1_Y1",
   "description": "setp. for 1st curvep. for outd. comp. setp.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 87,
   "name": "Curve1_Y2",
   "description": "Setp. for 2nd curvep. for outd. comp. setp.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 88,
   "name": "Curve1_Y3",
   "description": "Setp. for 3rd curvep. for outd. comp. setp.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "Curve1_Y4",
   "description": "Setp. for 4th curvep. for outd. comp. setp.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 90,
   "name": "ExtractPID_PBand",
   "description": "P-band Extract air cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 93,
   "name": "SAFPID_PBand",
   "description": "P-band press. cont. SAF",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 91,
   "name": "EAFPID_PBand",
   "description": "P-band press. cont. EAF",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 92,
   "name": "FrostPID1_PBand",
   "description": "P-band frost mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 94,
   "name": "FrostPID2_PBand",
   "description": "P-band frost mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 97,
   "name": "FrostPID3_PBand",
   "description": "P-band frost mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 100,
   "name": "CO2PID_PBand",
   "description": "P-band CO2 mode",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "RoomPID_PBand",
   "description": "P-band room air cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 106,
   "name": "DeIcePID_PBand",
   "description": "P-band de-icing",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "HumidityPID_PBand",
   "description": "P-band humidity cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 110,
   "name": "ExtraPID_PBand",
   "description": "P-band extra pid cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "PreHeatPID_PBand",
   "description": "P-band preheater",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 107,
   "name": "Zone1SupplyPID_PBand",
   "description": "P-band Zone 1 supply",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 108,
   "name": "Zone2SupplyPID_PBand",
   "description": "P-band Zone 2 supply",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "Zone3SupplyPID_PBand",
   "description": "P-band Zone 3 supply",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 105,
   "name": "Zone1RoomPID_PBand",
   "description": "P-band Zone 1 room",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "Zone2RoomPID_PBand",
   "description": "P-band Zone 2 room",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "Zone3RoomPID_PBand",
   "description": "P-band Zone 3 room",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 98,
   "name": "Zone1FrostPID_PBand",
   "description": "P-band Zone 1 frost prot.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 99,
   "name": "Zone2FrostPID_PBand",
   "description": "P-band Zone 2 frost prot.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 95,
   "name": "Zone3FrostPID_PBand",
   "description": "P-band Zone 3 frost prot.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 434,
   "name": "FreshAirPID_PBand",
   "description": "P-band fresh air",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 435,
   "name": "EATRPID_PBand",
   "description": "P-band EATR",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 96,
   "name": "Zone1SupplyCoolPID_PBand",
   "description": "P-band Zone 1 cooling",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 112,
   "name": "Zone2SupplyCoolPID_PBand",
   "description": "P-band Zone 2 cooling",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 114,
   "name": "Zone3SupplyCoolPID_PBand",
   "description": "P-band Zone 3 cooling",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 115,
   "name": "SAFAirFlowPID_PBand",
   "description": "P-band flow cont. SAF",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "EAFAirFlowPID_PBand",
   "description": "P-band flow cont. EAF",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 116,
   "name": "DeHumidityPID_PBand",
   "description": "P-band de-humidity cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 438,
   "name": "RHPID_PBand",
   "description": "P-band RH (same PID as CO2)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 117,
   "name": "SeqAPID_PBand",
   "description": "P-band Seq A air cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 118,
   "name": "SeqBPID_PBand",
   "description": "P-band Seq B air cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 119,
   "name": "SeqCPID_PBand",
   "description": "P-band Seq C air cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 120,
   "name": "SeqDPID_PBand",
   "description": "P-band Seq D air cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 121,
   "name": "SeqEPID_PBand",
   "description": "P-band Seq E air cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 122,
   "name": "SeqFPID_PBand",
   "description": "P-band Seq F air cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 123,
   "name": "SeqGPID_PBand",
   "description": "P-band Seq G air cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 124,
   "name": "SeqHPID_PBand",
   "description": "P-band Seq H air cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 125,
   "name": "SeqIPID_PBand",
   "description": "P-band Seq I air cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 126,
   "name": "SeqJPID_PBand",
   "description": "P-band Seq J air cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 127,
   "name": "ExtractPID_ITime",
   "description": "I-time Extract air cont.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 128,
   "name": "SAFPID_ITime",
   "description": "I-time press. cont. SAF",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 129,
   "name": "EAFPID_ITime",
   "description": "I-time press. cont. EAF",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 130,
   "name": "FrostPID1_ITime",
   "description": "I-time frost mode",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 131,
   "name": "FrostPID2_ITime",
   "description": "I-time frost mode",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 132,
   "name": "FrostPID3_ITime",
   "description": "I-time frost mode",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 133,
   "name": "CO2PID_ITime",
   "description": "I-time CO2 mode",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 134,
   "name": "RoomPID_ITime",
   "description": "I-time room air cont.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 135,
   "name": "DeIcePID_ITime",
   "description": "I-time de-icing",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 136,
   "name": "HumidityPID_ITime",
   "description": "I-time humidity cont.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 137,
   "name": "ExtraPID_ITime",
   "description": "I-time extra pid cont.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 138,
   "name": "PreHeatPID_ITime",
   "description": "I-time preheater",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 139,
   "name": "Zone1SupplyPID_ITime",
   "description": "I-time Zone 1 supply",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 140,
   "name": "Zone2SupplyPID_ITime",
   "description": "I-time Zone 2 supply",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 141,
   "name": "Zone3SupplyPID_ITime",
   "description": "I-time Zone 3 supply",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 142,
   "name": "Zone1RoomPID_ITime",
   "description": "I-time Zone 1 room",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 143,
   "name": "Zone2RoomPID_ITime",
   "description": "I-time Zone 2 room",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 144,
   "name": "Zone3RoomPID_ITime",
   "description": "I-time Zone 3 room",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 145,
   "name": "Zone1FrostPID_ITime",
   "description": "I-time Zone 1 frost prot.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 146,
   "name": "Zone2FrostPID_ITime",
   "description": "I-time Zone 2 frost prot.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 147,
   "name": "Zone3FrostPID_ITime",
   "description": "I-time Zone 3 frost prot.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 436,
   "name": "FreshAirPID_ITime",
   "description": "I-time fresh air",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 437,
   "name": "EATRPID_ITime",
   "description": "I-time EATR",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 148,
   "name": "Zone1SupplyCoolPID_ITime",
   "description": "I-time Zone 1 cooling",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 149,
   "name": "Zone2SupplyCoolPID_ITime",
   "description": "I-time Zone 2 cooling",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 150,
   "name": "Zone3SupplyCoolPID_ITime",
   "description": "I-time Zone 3 cooling",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 464,
   "name": "SAFAirFlowPID_ITime",
   "description": "I-time flow cont. SAF",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 465,
   "name": "EAFAirFlowPID_ITime",
   "description": "I-time flow cont. EAF",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 153,
   "name": "DeHumidityPID_ITime",
   "description": "I-time de-humidity cont.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 439,
   "name": "RHPID_ITime",
   "description": "I-time RH (same PID as CO2)",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 154,
   "name": "SeqAPID_ITime",
   "description": "I-time Seq A air cont.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 155,
   "name": "SeqBPID_ITime",
   "description": "I-time Seq B air cont.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 156,
   "name": "SeqCPID_ITime",
   "description": "I-time Seq C air cont.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 157,
   "name": "SeqDPID_ITime",
   "description": "I-time Seq D air cont.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 158,
   "name": "SeqEPID_ITime",
   "description": "I-time Seq E air cont.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 159,
   "name": "SeqFPID_ITime",
   "description": "I-time Seq F air cont.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 160,
   "name": "SeqGPID_ITime",
   "description": "I-time Seq G air cont.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 161,
   "name": "SeqHPID_ITime",
   "description": "I-time Seq H air cont.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 162,
   "name": "SeqIPID_ITime",
   "description": "I-time Seq I air cont.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 163,
   "name": "SeqJPID_ITime",
   "description": "I-time Seq J air cont.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 164,
   "name": "FreeCoolDayLimit",
   "description": "If outdoor temp has been higher on the day free cool is",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 165,
   "name": "FreeCoolHighLimit",
   "description": "If outd. temp is higher at night the free cool is stopped",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 166,
   "name": "FreeCoolLowLimit",
   "description": "If outd. temp is lower at night the free cool is stopped",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 167,
   "name": "FreeCoolRoomLimit",
   "description": "If room temp is lower at night the free cool is stopped",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 73,
   "name": "FreeCoolStartTime",
   "description": "Start time free cool function",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 74,
   "name": "FreeCoolStopTime",
   "description": "Stop time free cool function",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 1,
   "name": "FreeCoolHeatBlockTime",
   "description": "Time in minute to block heat output when start after free cool",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 168,
   "name": "CO2StartLimit",
   "description": "Level to activate CO2 cont. (ppm)",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 169,
   "name": "CO2DemandDiff",
   "description": "Diff. for stop of demand cont.led ventilation (ppm)",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 170,
   "name": "CO2Setpoint",
   "description": "setp. CO2 (ppm)",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 2,
   "name": "CO2MinTime",
   "description": "Min time for CO2 cont. (min)",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 171,
   "name": "NeedHeatStart",
   "description": "Room temperature to start the unit if support heating is active",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 172,
   "name": "NeedHeatStop",
   "description": "Room temperature to stop the unit if support heating is active",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 173,
   "name": "NeedCoolStart",
   "description": "Room temperature to start the unit if support cooling is active",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 174,
   "name": "NeedCoolStop",
   "description": "Room temperature for stop the unit if support cooling is active",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 3,
   "name": "NeedMinTime",
   "description": "Min run time support control",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 57,
   "name": "FireDampersAutoMode",
   "description": "Run. mode fire damper",
   "units": "",
   "access": "W",
   "states": "1=Close, 2=Open, 3=Auto"
  },
  {
   "type": "AV",
   "instance": 175,
   "name": "DeIcingSetpoint",
   "description": "Setp. de-icing temp",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 176,
   "name": "DeIcingHyst",
   "description": "Hyst. for stop of de-icing",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 63,
   "name": "DeIcingMinTime",
   "description": "Min time for de-icing",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 177,
   "name": "DeIcingSAFTempStop",
   "description": "If lower outd. temp the SAF will be stopped at de-icing",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 178,
   "name": "HumiditySetpoint",
   "description": "setp. humidity room",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 179,
   "name": "HumidityMaxDuct",
   "description": "Max limit humidity duct",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 180,
   "name": "HumidityHyst",
   "description": "Hyst. to start humidity cont. after stop max limitation",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 181,
   "name": "HumidityStartLimit",
   "description": "Start limit in % to start DO signal",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 182,
   "name": "HumidityStopLimit",
   "description": "Stop limit in % to stop DO signal",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 183,
   "name": "HumidityNeutralZone",
   "description": "Neutral zone humidity room",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 184,
   "name": "RoomSetP",
   "description": "Room setp. if room temp cont. function",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 188,
   "name": "FrostProtSPStop1",
   "description": "Setp. frost prot. if the ventilation unit is stopped",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 203,
   "name": "FrostProtSPStop2",
   "description": "Setp. frost prot. if the ventilation unit is stopped",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 204,
   "name": "FrostProtSPStop3",
   "description": "Setp. frost prot. if the ventilation unit is stopped",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 185,
   "name": "FrostProtSPStopZone1",
   "description": "Setp. frost prot. zone 1 if the ventilation unit is stopped",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 186,
   "name": "FrostProtSPStopZone2",
   "description": "Setp. frost prot. zone 2 if the ventilation unit is stopped",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 187,
   "name": "FrostProtSPStopZone3",
   "description": "Setp. frost prot. zone 3 if the ventilation unit is stopped",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 206,
   "name": "FrostProtSPRun1",
   "description": "Alarm limit frost prot.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 207,
   "name": "FrostProtSPRun2",
   "description": "Alarm limit frost prot.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 208,
   "name": "FrostProtSPRun3",
   "description": "Alarm limit frost prot.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 189,
   "name": "FrostProtSPRunZone1",
   "description": "Alarm limit frost prot. zone 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 190,
   "name": "FrostProtSPRunZone2",
   "description": "Alarm limit frost prot. zone 2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 191,
   "name": "FrostProtSPRunZone3",
   "description": "Alarm limit frost prot. zone 3",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 194,
   "name": "FrostProtPGain1",
   "description": "P-Gain frost prot. when run (alarm limit+PGain)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 197,
   "name": "FrostProtPGain2",
   "description": "P-Gain frost prot. when run (alarm limit+PGain)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 200,
   "name": "FrostProtPGain3",
   "description": "P-Gain frost prot. when run (alarm limit+PGain)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 201,
   "name": "FrostProtPGainZone1",
   "description": "P-Gain frost prot. zone 1 when run (alarm limit+PGain)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 202,
   "name": "FrostProtPGainZone2",
   "description": "P-Gain frost prot. zone 2 when run (alarm limit+PGain)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 198,
   "name": "FrostProtPGainZone3",
   "description": "P-Gain frost prot. zone 3 when run (alarm limit+PGain)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 205,
   "name": "ExtraControllerSetP",
   "description": "Setp. Extra cont.ler",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 53,
   "name": "ExtraControllerMode",
   "description": "Control mode ex. contr.",
   "units": "",
   "access": "W",
   "states": "1=Heating, 2=Cooling"
  },
  {
   "type": "MV",
   "instance": 58,
   "name": "SumAlarm1",
   "description": "Sum alarm 1 config, defines which alarms that should be on the",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=A+B+C, 3=A+B, 4=B+C, 5=A+C, 6=A, 7=B, 8=C"
  },
  {
   "type": "MV",
   "instance": 59,
   "name": "SumAlarm2",
   "description": "Sum alarm 2 config., defines which alarms that should be on the",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=A+B+C, 3=A+B, 4=B+C, 5=A+C, 6=A, 7=B, 8=C"
  },
  {
   "type": "PIV",
   "instance": 62,
   "name": "AlarmOutput",
   "description": "Alarm output of configured alarm number",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "AlaAcknowAll",
   "description": "Command to acknowledge all alarms",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AV",
   "instance": 211,
   "name": "FilterGuard1Limit_X2",
   "description": "Alarm limt filter guard 1 X2 (m3/h) - Calibration air flow",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 215,
   "name": "FilterGuard2Limit_X2",
   "description": "Alarm limt filter guard 2 X2 (m3/h) - Calibration air flow",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 441,
   "name": "FilterGuard3Limit_X2",
   "description": "Alarm limt filter guard 3 X2 (m3/h) - Calibration air flow",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 442,
   "name": "FilterGuard4Limit_X2",
   "description": "Alarm limt filter guard 4 X2 (m3/h) - Calibration air flow",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 443,
   "name": "FilterGuard5Limit_X2",
   "description": "Alarm limt filter guard 5 X2 (m3/h) - Calibration air flow",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 212,
   "name": "FilterGuard1Limit_Y2",
   "description": "Alarm limt filter guard 1 Y2 (Pa) - Calibration filter alarm limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 216,
   "name": "FilterGuard2Limit_Y2",
   "description": "Alarm limt filter guard 2 Y2 (Pa) - Calibration filter alarm limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 444,
   "name": "FilterGuard3Limit_Y2",
   "description": "Alarm limt filter guard 3 Y2 (Pa) - Calibration filter alarm limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 445,
   "name": "FilterGuard4Limit_Y2",
   "description": "Alarm limt filter guard 4 Y2 (Pa) - Calibration filter alarm limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 446,
   "name": "FilterGuard5Limit_Y2",
   "description": "Alarm limt filter guard 5 Y2 (Pa) - Calibration filter alarm limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 217,
   "name": "RecircSetP",
   "description": "Recirculation setp.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 218,
   "name": "RecircSetPOffset",
   "description": "Offset for recirculation setp.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 51,
   "name": "RecircTempControl",
   "description": "Enable supply air temp cont. when recirc. run",
   "units": "",
   "access": "W",
   "states": "1=No temp control, 2=Heating/cooling, 3=Only heating, 4=Only cooling"
  },
  {
   "type": "AV",
   "instance": 219,
   "name": "RecircMaxRoomTemp",
   "description": "If higher room temp when recirc. run, recirc. damp. is closed and",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 52,
   "name": "RecircFreeCool",
   "description": "Enable the free cool func. when recirc. run",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=On"
  },
  {
   "type": "AV",
   "instance": 220,
   "name": "RecircSAFOffset",
   "description": "Setp. offset if press./flow cont.led SAF",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 221,
   "name": "RecircEAFOffset",
   "description": "Setp. offset if press./flow cont.led EAF (this is not used)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 4,
   "name": "FilterAlarmTime",
   "description": "Time in month between filter exchange (Service Alarm)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 56,
   "name": "SupplyPIDFreeze",
   "description": "Freeze supply PID control",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=On"
  },
  {
   "type": "AV",
   "instance": 222,
   "name": "FanComp1X1",
   "description": "Breakp. 1 (must be lower than breakp. 2)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 223,
   "name": "FanComp2X1",
   "description": "Breakp. 1 (must be lower than breakp. 2)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 224,
   "name": "FanComp3X1",
   "description": "Breakp. 1 (must be lower than breakp. 2)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 225,
   "name": "FanComp1Y1",
   "description": "Comp. breakp. 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 226,
   "name": "FanComp2Y1",
   "description": "Comp. breakp. 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 227,
   "name": "FanComp3Y1",
   "description": "Comp. breakp. 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 228,
   "name": "FanComp1X2",
   "description": "Breakp. 2 (must be higher than breakp. 1)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 229,
   "name": "FanComp2X2",
   "description": "Breakp. 2 (must be higher than breakp. 1)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 230,
   "name": "FanComp3X2",
   "description": "Breakp. 2 (must be higher than breakp. 1)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 234,
   "name": "FanComp1Y2",
   "description": "Comp. breakp. 2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 235,
   "name": "FanComp2Y2",
   "description": "Comp. breakp. 2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 236,
   "name": "FanComp3Y2",
   "description": "Comp. breakp. 2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 231,
   "name": "FanComp1X3",
   "description": "Breakp. 3 (must be higher than breakp. 2)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 232,
   "name": "FanComp2X3",
   "description": "Breakp. 3 (must be higher than breakp. 2)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 233,
   "name": "FanComp3X3",
   "description": "Breakp. 3 (must be higher than breakp. 2)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 237,
   "name": "FanComp1Y3",
   "description": "Comp. breakp. 3",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 238,
   "name": "FanComp2Y3",
   "description": "Comp. breakp. 3",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 239,
   "name": "FanComp3Y3",
   "description": "Comp. breakp. 3",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 240,
   "name": "NeutralZone",
   "description": "Neutral zone supply air.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 575,
   "name": "NeutralZoneCascade",
   "description": "Neutral zone cascade control",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 241,
   "name": "FreeCoolSAFOffset",
   "description": "SAF setp. offset if press./flow controlled SAF when free cool",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 242,
   "name": "FreeCoolEAFOffset",
   "description": "EAF setp. offset if press./flow controlled EAF when free cool",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 243,
   "name": "Zone1SetP",
   "description": "Setpoint zone 1 (room or supply)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 244,
   "name": "Zone2SetP",
   "description": "Setpoint zone 2 (room or supply)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 245,
   "name": "Zone3SetP",
   "description": "Setpoint zone 3 (room or supply)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 246,
   "name": "Zone1NeutralZone",
   "description": "Neutral zone around supply setp. zone 1 before heat/cool",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 249,
   "name": "Zone2NeutralZone",
   "description": "Neutral zone around supply setp. zone 2 before heat/cool",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 252,
   "name": "Zone3NeutralZone",
   "description": "Neutral zone around supply setp. zone 3 before heat/cool",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 253,
   "name": "Zone1SetpointMax",
   "description": "Max limit of zone 1 supply setp. when cascade cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 254,
   "name": "Zone2SetpointMax",
   "description": "Max limit of zone 2 supply setp. when cascade cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 250,
   "name": "Zone3SetpointMax",
   "description": "Max limit of zone 3 supply setp. when cascade cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 251,
   "name": "Zone1SetpointMin",
   "description": "Min limit of zone 1 supply setp. when cascade cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 247,
   "name": "Zone2SetpointMin",
   "description": "Min limit of zone 2 supply setp. when cascade cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 248,
   "name": "Zone3SetpointMin",
   "description": "Min limit of zone 3 supply setp. when cascade cont.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 255,
   "name": "DelayedStartDXCool",
   "description": "Minsetpoint deviation to allow DX-cooling",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 256,
   "name": "DelayedStartDXHeat",
   "description": "Minsetpoint deviation to allow DX-heating",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 78,
   "name": "S_FrostProtFanReduction1",
   "description": "Enable fan reduction when freeze risk freeze protection temperature 1",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 79,
   "name": "S_FrostProtFanReduction2",
   "description": "Enable fan reduction when freeze risk freeze protection temperature 2",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 80,
   "name": "S_FrostProtFanReduction3",
   "description": "Enable fan reduction when freeze risk freeze protection temperature 3",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 81,
   "name": "S_FrostProtFanReductionZone1",
   "description": "Enable fan reduction when freeze risk freeze protection temperature zone 1",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 82,
   "name": "S_FrostProtFanReductionZone2",
   "description": "Enable fan reduction when freeze risk freeze protection temperature zone 2",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 83,
   "name": "S_FrostProtFanReductionZone3",
   "description": "Enable fan reduction when freeze risk freeze protection temperature zone 3",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=On"
  },
  {
   "type": "PIV",
   "instance": 64,
   "name": "FeedbackDXTimeStart",
   "description": "Time that Supply Pid is freezed when DX-machine is started (sec)",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 65,
   "name": "FeedbackDXTimeDefrost",
   "description": "Time that Supply Pid is freezed after DX-machine has been defrosting (sec)",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 66,
   "name": "FeedbackDXMinRunTime",
   "description": "Min run time DX machine, to avoid involuntary shutdown of the DX",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 67,
   "name": "FeedbackDXMaxTime",
   "description": "Max time if DX machine don't give feedback (min)",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 540,
   "name": "PreheatSetp",
   "description": "Setpoint preheater",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 541,
   "name": "SupplySetpointMaxReduction",
   "description": "Offset max limit supply air - if active DX-heating",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 542,
   "name": "SupplySetpointMinReduction",
   "description": "Offset max limit supply air - if active DX-heating",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 543,
   "name": "HPMinSetPDevCool",
   "description": "Min setpoint deviation energy for start cooling (kw)",
   "units": "kW",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 544,
   "name": "HPMinSetPDevHeat",
   "description": "Min setpoint deviation energy for start heating (kw)",
   "units": "kW",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 88,
   "name": "HPPumpMode",
   "description": "Pump run mode (0=Reversible, 1=Only cooling, 2=Only heating)",
   "units": "",
   "access": "W",
   "states": "1=Reversible, 2=Only cooling, 3=Only heating"
  },
  {
   "type": "PIV",
   "instance": 68,
   "name": "HPBlockingTime",
   "description": "Blocking time between heating and cooling (0-360min)",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 545,
   "name": "FrostLimitPrLimitDev",
   "description": "Pressure deviation (%) for start deicing",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 570,
   "name": "ExtDisp_SetpOffset",
   "description": "Actual supply setpoint offset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 571,
   "name": "RHSetpoint",
   "description": "setp. RH (%)",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 69,
   "name": "RHMinTime",
   "description": "Min time for RH cont. (min)",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 70,
   "name": "FireDampersRunTime",
   "description": "Run time fire damper",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 71,
   "name": "FireDampersInterval",
   "description": "Test interval fire damper",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 72,
   "name": "FireDampersExerciseTime",
   "description": "Test hour fire damper",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 574,
   "name": "DXBlockLowOutdoorTemp",
   "description": "Heating mode blocked when exchanger-outdoor temperature is lower",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 576,
   "name": "Zone1NeutralZoneCascade",
   "description": "Neutral zone around cascade setp. zone 1 before heat/cool",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 577,
   "name": "Zone2NeutralZoneCascade",
   "description": "Neutral zone around cascade setp. zone 2 before heat/cool",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 578,
   "name": "Zone3NeutralZoneCascade",
   "description": "Neutral zone around cascade setp. zone 3 before heat/cool",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 75,
   "name": "SummerModeSwitchDelay",
   "description": "Delay outdoor temp for switching between summer and winter mode (in minutes)",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "NeedHeatActive",
   "description": "Is set if ongoing support heating",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "NeedCoolActive",
   "description": "Is set if ongoing support cooling",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "DemandCO2Active",
   "description": "Is set if ongoing support CO2",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "RecirculationRunActive",
   "description": "Is set if ongoing recycle run",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "DeIcingActive",
   "description": "Is set if ongoing de-icing",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 81,
   "name": "FrostProtFanReductionActive",
   "description": "Is set if ongoing fan reduction when freeze risk",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "SAFRunTime",
   "description": "Run. Time supply air fan",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "EAFRunTime",
   "description": "Run. Time extract air fan",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "IV",
   "instance": 1,
   "name": "DeIcingTime",
   "description": "Number of min for ongoing de-icing",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "IV",
   "instance": 2,
   "name": "NeedRunTime",
   "description": "No of min in ongoing support heat/cool",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "SmokeDetector",
   "description": "Smoke detector",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AV",
   "instance": 257,
   "name": "RoomTemp",
   "description": "Room temp. 1-4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 258,
   "name": "ExchPressureSAF",
   "description": "Calculated pressure exchanger SAF",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 259,
   "name": "ExchAirFlowEAF",
   "description": "Calculated flow exchanger, EAF",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 427,
   "name": "Efficiency",
   "description": "Efficiency for exchanger",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 15,
   "name": "UnitMode",
   "description": "Unit run mode",
   "units": "",
   "access": "R",
   "states": "1=Stop, 2=Starting up, 3=Low speed run, 4=Normal speed run, 5=High speed run, 6=Heating support run, 7=Cooling support run, 8=CO2 Run, 9=Free cool run, 10=Fan stop run, 11=Fire run, 12=Smoke run, 13=Recirculation run, 14=DeIcing run, 15=Filter calibration run, 16=Gas evacuation mode"
  },
  {
   "type": "MV",
   "instance": 16,
   "name": "UnitModeControl",
   "description": "Indicates what is triggering the curr. run mode",
   "units": "",
   "access": "R",
   "states": "1=Nothing, 2=Time schedule, 3=Manual run, 4=Digital Input, 5=Alarm, 6=External control, 7=Service stop, 8=Support run, 9=Filter calibration, 10=Heat pump exercise"
  },
  {
   "type": "MV",
   "instance": 65,
   "name": "ActiveSeqType",
   "description": "Active seq. type",
   "units": "",
   "access": "R",
   "states": "1=Heating, 2=Cooling"
  },
  {
   "type": "MV",
   "instance": 66,
   "name": "ActiveHeatSeqStep",
   "description": "Curr. heat seq. step that's active",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1, 3=2, 4=3, 5=4, 6=5, 7=6, 8=7, 9=8, 10=9, 11=10"
  },
  {
   "type": "MV",
   "instance": 67,
   "name": "ActiveCoolSeqStep",
   "description": "Curr. cool seq. step that's active",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1, 3=2, 4=3, 5=4, 6=5, 7=6, 8=7, 9=8, 10=9, 11=10"
  },
  {
   "type": "MV",
   "instance": 68,
   "name": "ActiveYSeq",
   "description": "Current sequence that's active and controlling",
   "units": "",
   "access": "R",
   "states": "1=None, 2=A, 3=B, 4=C, 5=D, 6=E, 7=F, 8=G, 9=H, 10=I, 11=J"
  },
  {
   "type": "IV",
   "instance": 3,
   "name": "CO2RunTime",
   "description": "Number of min for ongoing de-icing",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 265,
   "name": "SAF",
   "description": "Cont. signal supply air fan",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 266,
   "name": "EAF",
   "description": "Cont. signal extract air fan",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 69,
   "name": "SAFSpeed",
   "description": "SAF speed",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=Low speed, 3=Normal speed, 4=High speed, 5=Manual setpoint, 6=Manual output"
  },
  {
   "type": "MV",
   "instance": 70,
   "name": "EAFSpeed",
   "description": "EAF speed",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=Low speed, 3=Normal speed, 4=High speed, 5=Manual setpoint, 6=Manual output"
  },
  {
   "type": "MV",
   "instance": 71,
   "name": "HumidityMode",
   "description": "Humidity control mode",
   "units": "",
   "access": "R",
   "states": "1=Not active, 2=Humidification, 3=Dehumidification"
  },
  {
   "type": "AV",
   "instance": 267,
   "name": "CompLowSpeedSAF",
   "description": "Total comp. low speed SAF",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 268,
   "name": "CompNormalSpeedSAF",
   "description": "Total comp. normal speed SAF",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 269,
   "name": "CompHighSpeedSAF",
   "description": "Total comp. high speed SAF",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 270,
   "name": "CompLowSpeedEAF",
   "description": "Total comp. low speed EAF",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 271,
   "name": "CompNormalSpeedEAF",
   "description": "Total comp. normal speed EAF",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 272,
   "name": "CompHighSpeedEAF",
   "description": "Total comp. high speed EAF",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "SumAlarm",
   "description": "Sumalarm",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "SumAlarmA",
   "description": "A-alarm",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "SumAlarmB",
   "description": "B-alarm",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "SumAlarmC",
   "description": "C-alarm",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "PIV",
   "instance": 5,
   "name": "AlarmACount",
   "description": "No of A alarms",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 6,
   "name": "AlarmBCount",
   "description": "No of B alarms",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 7,
   "name": "AlarmCCount",
   "description": "No of C alarms",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 8,
   "name": "SumAlarm1Count",
   "description": "No of SumAlarm1 alarms",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 9,
   "name": "SumAlarm2Count",
   "description": "No of SumAlarm2 alarms",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 273,
   "name": "SupplyPID_SetP",
   "description": "Actual setp. supply air temp.",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 274,
   "name": "SAFPID_SetP",
   "description": "Actual setp. SAF",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 275,
   "name": "EAFPID_SetP",
   "description": "Actual setp. EAF",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 276,
   "name": "SupplyPID_Output",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 277,
   "name": "FrostPID1_Output",
   "description": "Frost prot. cont.ler output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 278,
   "name": "FrostPID2_Output",
   "description": "Frost prot. cont.ler output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 279,
   "name": "FrostPID3_Output",
   "description": "Frost prot. cont.ler output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 280,
   "name": "CO2PID_Output",
   "description": "CO2 cont.ler output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 281,
   "name": "DeIcePID_Output",
   "description": "De-icing cont.ler output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 282,
   "name": "HumidityPID_Output",
   "description": "Hum. cont.ler output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 283,
   "name": "SFP",
   "description": "Actual SFP",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 284,
   "name": "SFPDay",
   "description": "Day aver. SFP",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 285,
   "name": "SFPMonth",
   "description": "Month aver. (30d aver.) SFP",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 287,
   "name": "EnergyFanPwr",
   "description": "Power usage fans",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 288,
   "name": "EnergyHeaterPwr",
   "description": "Power usage heater",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 286,
   "name": "EnergyExchangerPwr",
   "description": "Power recovery exchanger",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 289,
   "name": "SupplyPID_SetP_Cool",
   "description": "Cooling setpoint supply air temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 290,
   "name": "SupplyPID_SetP_Heat",
   "description": "Heating setpoint supply air temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 291,
   "name": "DeHumidity_SetP",
   "description": "Dehumidification setpoint",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 292,
   "name": "Humidity_SetP",
   "description": "Humidification setpoint",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 447,
   "name": "FilterGuard1CalibrationInitPress",
   "description": "Initial pressure when doing the filter calibration",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 448,
   "name": "FilterGuard2CalibrationInitPress",
   "description": "Initial pressure when doing the filter calibration",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 449,
   "name": "FilterGuard3CalibrationInitPress",
   "description": "Initial pressure when doing the filter calibration",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 450,
   "name": "FilterGuard4CalibrationInitPress",
   "description": "Initial pressure when doing the filter calibration",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 451,
   "name": "FilterGuard5CalibrationInitPress",
   "description": "Initial pressure when doing the filter calibration",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 452,
   "name": "FilterGuard1Limit_Calc",
   "description": "Calculated alarmlimit filter guard 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 453,
   "name": "FilterGuard2Limit_Calc",
   "description": "Calculated alarmlimit filter guard 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 454,
   "name": "FilterGuard3Limit_Calc",
   "description": "Calculated alarmlimit filter guard 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 455,
   "name": "FilterGuard4Limit_Calc",
   "description": "Calculated alarmlimit filter guard 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 456,
   "name": "FilterGuard5Limit_Calc",
   "description": "Calculated alarmlimit filter guard 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 466,
   "name": "BMS_OutDoorTemp",
   "description": "Outdoor temp received from BACnet/Modbus",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 467,
   "name": "SequenceA",
   "description": "Sequence A output in auto and manual mode (%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 468,
   "name": "SequenceB",
   "description": "Sequence B output in auto and manual mode (%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 469,
   "name": "SequenceC",
   "description": "Sequence C output in auto and manual mode (%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 470,
   "name": "SequenceD",
   "description": "Sequence D output in auto and manual mode (%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 471,
   "name": "SequenceE",
   "description": "Sequence E output in auto and manual mode (%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 472,
   "name": "SequenceF",
   "description": "Sequence F output in auto and manual mode (%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 473,
   "name": "SequenceG",
   "description": "Sequence G output in auto and manual mode (%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 474,
   "name": "SequenceH",
   "description": "Sequence H output in auto and manual mode (%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 475,
   "name": "SequenceI",
   "description": "Sequence I output in auto and manual mode (%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 476,
   "name": "SequenceJ",
   "description": "Sequence J output in auto and manual mode (%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 537,
   "name": "IndoorEnthalpy",
   "description": "Indoor entalphy",
   "units": "kJ/kg",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 538,
   "name": "OutdoorEnthalpy",
   "description": "Outdoor entalphy",
   "units": "kJ/kg",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 77,
   "name": "EnthalpyDiff",
   "description": "Indicate if enthalpy outdoor > enthalpy indoor",
   "units": "",
   "access": "R",
   "states": "1=Not active, 2=Outdoor > Enthalpy indoor"
  },
  {
   "type": "AV",
   "instance": 539,
   "name": "ExtractFilterGuardFlowRef",
   "description": "Extract air flow (calculated) filter calibration",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 84,
   "name": "ChangeOver1RunMode",
   "description": "Changeover 1 running mode (actual changeover sequence 1-10)",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1, 3=2, 4=3, 5=4, 6=5, 7=6, 8=7, 9=8, 10=9, 11=10"
  },
  {
   "type": "MV",
   "instance": 85,
   "name": "ChangeOver2RunMode",
   "description": "Changeover 2 running mode (actual changeover sequence 1-10)",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1, 3=2, 4=3, 5=4, 6=5, 7=6, 8=7, 9=8, 10=9, 11=10"
  },
  {
   "type": "MV",
   "instance": 86,
   "name": "FeedbackDXWaitStart",
   "description": "Waiting for DX-compressor to start",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 87,
   "name": "FeedbackDXWaitDefrost",
   "description": "Waiting for DX-machine to defrost",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 103,
   "name": "FrostLimitMode",
   "description": "Ongoing frost limit air flow reduction mode",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=Reduction mode, 3=Defrosting mode"
  },
  {
   "type": "BV",
   "instance": 93,
   "name": "HPHeatingModeNotStarted",
   "description": "Heating mode are not allowed to start",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 94,
   "name": "HPCoolingModeNotStarted",
   "description": "Cooling mode are not allowed to start",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 95,
   "name": "HPExerciseFailed",
   "description": "Exercise of heat pump could not be performed",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 96,
   "name": "HPPIDBlocked",
   "description": "Supply air temperature controller is temporary locked",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 97,
   "name": "HPSetPDevToSmall",
   "description": "Not allowed to start – Setpoint deviation to small",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 98,
   "name": "HPAirflowToLow",
   "description": "Not allowed to start – air flow is to low",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 99,
   "name": "HPFlowDiffToBig",
   "description": "Not allowed to start – Flow difference to big",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 100,
   "name": "HPReductionMode",
   "description": "Heat pump running in reduction mode",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 101,
   "name": "HPAlarm1",
   "description": "Al02 - Supercap/ Battery fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 102,
   "name": "HPAlarm2",
   "description": "Al63 - Oil return fault alarm",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 103,
   "name": "HPAlarm3",
   "description": "Al64 - Watchdog frequency converter",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 104,
   "name": "HPAlarm4",
   "description": "Al59 - Low-pressure alarm digital input (C1-P1)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 105,
   "name": "HPAlarm5",
   "description": "Al27 - Low-pressure alarm pressure sensor (C1-P1)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 106,
   "name": "HPAlarm6",
   "description": "Al32 - High-pressure alarm digital input (C1-P2)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 107,
   "name": "HPAlarm7",
   "description": "Al26 - High-pressure alarm pressure sensor (C1-P2)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 108,
   "name": "HPAlarm8",
   "description": "Al58 - High temperature on compressor (C1-T3)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 109,
   "name": "HPAlarm9",
   "description": "Al03 - Low superheating (C1)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 110,
   "name": "HPAlarm10",
   "description": "Al65 - High superheating (C1)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 111,
   "name": "HPAlarm11",
   "description": "Al30 - Expansion-valve fault (C1-EEV)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 112,
   "name": "HPAlarm12",
   "description": "Al53 - Pressure difference “wrong direction” (C1)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 113,
   "name": "HPAlarm13",
   "description": "Al55 - Pressure difference “EEV no function” (C1)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 114,
   "name": "HPAlarm14",
   "description": "Al54 - Pressure difference “no function” (C1)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 115,
   "name": "HPAlarm15",
   "description": "Al25 - Low-pressure-sensor (C1-P1)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 116,
   "name": "HPAlarm16",
   "description": "Al21 - High-pressure-sensor (C1-P2)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 117,
   "name": "HPAlarm17",
   "description": "Al67 - Temperature sensor for evaporator in supply air (C1-T1)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 118,
   "name": "HPAlarm18",
   "description": "Al68 - Temperature sensor for evaporator in exhaust air (C1-T2)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 119,
   "name": "HPAlarm19",
   "description": "Al24 - Temperature sensor for compressor 1 on outlet side (C1-T3)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 120,
   "name": "HPAlarm20",
   "description": "Al72 - Temperature sensor for condensing temperature supply (C1-T4)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 121,
   "name": "HPAlarm21",
   "description": "Al73 - Temperature sensor for condensing temperature extract (C1-T5)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 122,
   "name": "HPAlarm22",
   "description": "Al77 - Malfunction frequency converter (VSD)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 123,
   "name": "HPAlarm23",
   "description": "Al61 - Temperature-sensor - supply air outlet coil (T6)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 124,
   "name": "HPAlarm24",
   "description": "Al80 - Compressor manual off (C1)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 125,
   "name": "HPAlarm25",
   "description": "Digital input for feedback peak-heater",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 126,
   "name": "HPAlarm26",
   "description": "Phase control C2",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 127,
   "name": "HPAlarm27",
   "description": "Compressor alarm 2 (C2)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 128,
   "name": "HPAlarm28",
   "description": "Low-pressure alarm digital input (C2-P1)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 129,
   "name": "HPAlarm29",
   "description": "Low-pressure alarm pressure sensor (C2-P1)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 130,
   "name": "HPAlarm30",
   "description": "High-pressure alarm digital input (C2-P2)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 131,
   "name": "HPAlarm31",
   "description": "High-pressure alarm pressure sensor (C2-P2)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 132,
   "name": "HPAlarm32",
   "description": "High temperature on compressor (C2-T3)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 133,
   "name": "HPAlarm33",
   "description": "Low superheating (C2)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 134,
   "name": "HPAlarm34",
   "description": "High superheating (C2)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 135,
   "name": "HPAlarm35",
   "description": "Expansion-valve fault (C2-EEV)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 136,
   "name": "HPAlarm36",
   "description": "Pressure difference “wrong direction” (C2)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 137,
   "name": "HPAlarm37",
   "description": "Pressure difference “EEV no function” (C2)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 138,
   "name": "HPAlarm38",
   "description": "Pressure difference “no function” (C2)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 139,
   "name": "HPAlarm39",
   "description": "Low-pressure-sensor (C2-P1)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 140,
   "name": "HPAlarm40",
   "description": "High-pressure-sensor (C2-P2)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 141,
   "name": "HPAlarm41",
   "description": "Temperature-sensor for evaporator in supply-air (C2-T1)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 142,
   "name": "HPAlarm42",
   "description": "Temperature-sensor for evaporator in exhaust-air (C2-T2)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 143,
   "name": "HPAlarm43",
   "description": "Temperature-sensor for compressor 2 on outlet-side (C2-T3)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 144,
   "name": "HPAlarm44",
   "description": "Temperature-sensor for condensing temperature supply (C2-T4)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 145,
   "name": "HPAlarm45",
   "description": "Temperature-sensor for condensing temperature extract (C2-T5)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "AV",
   "instance": 546,
   "name": "HPEnergyDemand",
   "description": "Actual setpoint deviation energy demand (kw) (air volume [m3/s]* temperature-difference “delta T”",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 547,
   "name": "HPOutput",
   "description": "Heat pump output (0-100%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 89,
   "name": "HPRequest",
   "description": "Heat pump request (0=Off,1=Heating mode,2=Cooling mode,3=Exercise)",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=Heating mode, 3=Cooling mode, 4=Exercise"
  },
  {
   "type": "AV",
   "instance": 548,
   "name": "HPPowerConsumption",
   "description": "Actual electric power consumption of heatpump in W",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 549,
   "name": "HPTotalCapacity",
   "description": "Actual total heat pump capacity in %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 550,
   "name": "HPC1Capacity",
   "description": "Actual compressor capacity C1 in %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 551,
   "name": "HPC1SuctionTemp",
   "description": "Actual suction temp °C C1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 552,
   "name": "HPC1HighPressure",
   "description": "Actual high pressure in system in bar C1",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 553,
   "name": "HPC1CondensingTemp",
   "description": "Actual condensing temp °C C1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 554,
   "name": "HPC1LowPressure",
   "description": "Actual low pressure in system in bar C1",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 555,
   "name": "HPC1EvaporatingTemp",
   "description": "Actual evaporating temp °C C1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 556,
   "name": "HPC1RefrigerantTemp",
   "description": "Actual temp of refrigerant leaving compressor in °C C1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 557,
   "name": "HPC1EEVOpenDegree",
   "description": "Current degree of opening EEV in % and in steps C1",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 558,
   "name": "HPC1SuperheatEvaporator",
   "description": "Current superheating on evaporator C1",
   "units": "K",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 90,
   "name": "HPC1Status0",
   "description": "C1 0=Off/1=On/2=Stopped alarm",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=On, 3=Stopped alarm"
  },
  {
   "type": "MV",
   "instance": 91,
   "name": "HPActualMode",
   "description": "Actual mode (0=Cooling, 1=Heating)",
   "units": "",
   "access": "R",
   "states": "1=Cooling, 2=Heating"
  },
  {
   "type": "MV",
   "instance": 92,
   "name": "HPOilBoostOn",
   "description": "Status oil boost function on",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 93,
   "name": "HPOilReturnOn",
   "description": "Status oil return function on",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 94,
   "name": "HPC1HighPressReduceMode",
   "description": "Status high pressure reduce mode C1",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 95,
   "name": "HPC1LowPressReduceMode",
   "description": "Status low pressure reduce mode C1",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 96,
   "name": "HPExercise",
   "description": "Status heat pump exercise",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 97,
   "name": "HPC1HighTempReduceMode",
   "description": "Status high temp reduce mode C1",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 98,
   "name": "HPIncreaseAirFlow",
   "description": "Increase airflow to avoid high pressure",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 99,
   "name": "HPOperationMode",
   "description": "Actual operation mode",
   "units": "",
   "access": "R",
   "states": "1=Stop, 2=Stopped alarm, 3=Stopped manual keyboard heat pump, 4=Startup, 5=Heating mode, 6=Cooling mode, 7=Pump down"
  },
  {
   "type": "AV",
   "instance": 559,
   "name": "HPC2SuctionTemp",
   "description": "Actual suction temp °C C2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 560,
   "name": "HPC2HighPressure",
   "description": "Actual high pressure in system in bar C2",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 561,
   "name": "HPC2CondensingTemp",
   "description": "Actual condensing temp °C C2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 562,
   "name": "HPC2LowPressure",
   "description": "Actual low pressure in system in bar C2",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 563,
   "name": "HPC2EvaporatingTemp",
   "description": "Actual evaporating temp °C C2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 564,
   "name": "HPC2RefrigerantTemp",
   "description": "Actual temp of refrigerant leaving compressor in °C C2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 565,
   "name": "HPC2EEVOpenDegree",
   "description": "Current degree of opening EEV in % and in steps C2",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 566,
   "name": "HPC2SuperheatEvaporator",
   "description": "Current superheating on evaporator C2",
   "units": "K",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 100,
   "name": "HPC2Status",
   "description": "C2 0=Off/1=On/2=Stopped alarm",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=On, 3=Stopped alarm"
  },
  {
   "type": "MV",
   "instance": 101,
   "name": "HPC2StopCompressor",
   "description": "Status stop compressor to avoid high pressure in C2",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 102,
   "name": "HPC2LowPressStopMode",
   "description": "Status low pressure stop mode C2",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=On"
  },
  {
   "type": "AV",
   "instance": 567,
   "name": "HPCOP",
   "description": "Calculated COP value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 568,
   "name": "ActualSupplySetpointMax",
   "description": "Actual max limit supply air (Used when Cascade)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 569,
   "name": "ActualSupplySetpointMin",
   "description": "Actual min limit supply air (Used when Cascade)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "IV",
   "instance": 4,
   "name": "GDFRuntime",
   "description": "Actual run time in gas evacuatiuon mode in seconds after gas detection",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "IV",
   "instance": 5,
   "name": "GDFTimeLeftService",
   "description": "Time left until Service (days) – Heat pump refrigerant system",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 153,
   "name": "DHFBlockedDewPoint",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 154,
   "name": "DHFReducedCapacity",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 155,
   "name": "DHFHumidReducedCapacity",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "AV",
   "instance": 572,
   "name": "DHFLowestTempCalc",
   "description": "Calculated lowest temperature – cooling capacity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 573,
   "name": "DHFDewPoint",
   "description": "The calculated and limited dewpoint value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 156,
   "name": "BMS_SummerMode",
   "description": "Summer/Winter mode received from BACnet/Modbus",
   "units": "",
   "access": "W",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 157,
   "name": "BMS_ChangeOver1",
   "description": "Cooling/(Heating) changeover 1 mode received from BACnet/Modbus",
   "units": "",
   "access": "W",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 158,
   "name": "BMS_ChangeOver2",
   "description": "Cooling/(Heating) changeover 2 mode received from BACnet/Modbus",
   "units": "",
   "access": "W",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "AV",
   "instance": 579,
   "name": "CascadePID_SetP_Cool",
   "description": "Cooling setpoint cascade control",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 580,
   "name": "CascadePID_SetP_Heat",
   "description": "Heating setpoint cascade control",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 159,
   "name": "HeatRecoveryNotStarted",
   "description": "Heat recovery mode are not allowed to start",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 160,
   "name": "CoolRecoveryNotStarted",
   "description": "Cool recovery mode are not allowed to start",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "ManualControlSeqA",
   "description": "Manual Control Heating (Seq-A)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "ManualControlSeqB",
   "description": "Manual Control Exchanger (Seq-B)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "ManualControlSeqC",
   "description": "Manual Control Cooling (Seq-C)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "ManualControlSeqD",
   "description": "Manual Control Recirculation 1 (Seq-D)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "ManualControlSeqE",
   "description": "Manual Control Recirculation 2 (Seq-E)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "ManualControlSeqF",
   "description": "Manual Control Fan Setpoint Comp (Seq-F)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "ManualControlSeqG",
   "description": "Manual Control Heating 2 (Seq-G)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "ManualControlSeqH",
   "description": "Manual Control Cooling 2 (Seq-H)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "ManualControlSeqI",
   "description": "Manual Control Exchanger Extract (Seq-I)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "ManualControlSeqJ",
   "description": "Manual Control External Heating/Cooling (Seq-J)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "ManualOperationAirHandlingUnit",
   "description": "Manual Operation Air Handling Unit",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "ManualOperationSAF",
   "description": "Manual Operation Supply Air Fan",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "ManualOperationEAF",
   "description": "Manual Operation Extract Air Fan",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "ManualOperationDamperRecirculation",
   "description": "Manual Operation Damper Recirculation",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "ManualOperationDamperOutdoorAir",
   "description": "Manual Operation Damper Outdoor Air",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 28,
   "name": "ManualOperationDamperExhaustAir",
   "description": "Manual Operation Damper Exhaust Air",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "ManualOperationFireDamper",
   "description": "Manual Operation Fire Damper",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "OutputInManualOperation",
   "description": "Output In Manual Operation",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "InputInManualOperation",
   "description": "Input In Manual Operation",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "ManualOperationExtraController",
   "description": "Manual Operation Extra Controller",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "ManualOperationExternalFanMotor1",
   "description": "Manual Operation External Fan Motor 1",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 34,
   "name": "ManualOperationExternalFanMotor2",
   "description": "Manual Operation External Fan Motor 2",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 35,
   "name": "ManualOperationPretreatment",
   "description": "Manual Operation Pretreatment",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 36,
   "name": "ExternalOperationSAF",
   "description": "External Operation Supply Air Fan",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 37,
   "name": "ExternalOperationEAF",
   "description": "External Operation Extract Air Fan",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "ServiceStop",
   "description": "Service Stop",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 39,
   "name": "WarningFreezeProtection",
   "description": "Warning Freeze Protection",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "RestartBlockedAfterPowerOn",
   "description": "Restart Blocked After Power On",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 41,
   "name": "TestingFireDamper",
   "description": "Testing Fire Damper",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 42,
   "name": "ServiceAlarmSmokeDetector",
   "description": "Service Alarm Smoke Detector",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 43,
   "name": "SensorErrorSmokeDetector",
   "description": "Sensor Error Smoke Detector",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 44,
   "name": "ExtraFanMotor1Running",
   "description": "Extra Fan Motor 1 Running",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 45,
   "name": "ExtraFanMotor2Running",
   "description": "Extra Fan Motor 2 Running",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 46,
   "name": "AlarmServiceInterval",
   "description": "Alarm Service Interval",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AV",
   "instance": 423,
   "name": "DeviationAlarmHumidityControl",
   "description": "Deviation Alarm Humidity Control",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 424,
   "name": "DeviationAlarmExtraController",
   "description": "Deviation Alarm Extra Controller",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 47,
   "name": "RotaryExchangerAlarm",
   "description": "Rotary Exchanger Alarm",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 48,
   "name": "InternalBatteryError",
   "description": "Internal Battery Error",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 49,
   "name": "CommunicationFaultDevice",
   "description": "Communication Fault Device",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 50,
   "name": "InternalError",
   "description": "Internal Error",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 51,
   "name": "CommunicationFaultBmsMaster",
   "description": "Communication Fault Bms Master",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 52,
   "name": "DeviceWarning",
   "description": "Device Warning",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 53,
   "name": "DeviceAlarm",
   "description": "Device Alarm",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 54,
   "name": "MalfunctionFireDamper",
   "description": "Malfunction Fire Damper",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AV",
   "instance": 428,
   "name": "DeviationAlarmSupplyAirFan",
   "description": "Deviation Alarm Supply Air Fan",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 429,
   "name": "DeviationAlarmExtractAirFan",
   "description": "Deviation Alarm Extract Air Fan",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 430,
   "name": "DeviationAlarmSupplyTempZone1",
   "description": "Deviation Alarm Supply Temp Zone 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 431,
   "name": "DeviationAlarmSupplyTempZone2",
   "description": "Deviation Alarm Supply Temp Zone 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 432,
   "name": "DeviationAlarmSupplyTempZone3",
   "description": "Deviation Alarm Supply Temp Zone 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 62,
   "name": "DefrostingAlarm",
   "description": "Defrosting Alarm",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AV",
   "instance": 425,
   "name": "DeviationAlarmSupplyAirTemperature",
   "description": "Deviation Alarm Supply Air Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 426,
   "name": "LeakageHeaterValve",
   "description": "Leakage Heater Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 63,
   "name": "FireAlarm",
   "description": "Fire Alarm",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 64,
   "name": "SmokeAlarm",
   "description": "Smoke Alarm",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 65,
   "name": "MalfunctionPumpHeating",
   "description": "Malfunction Pump Heating (Seq-A)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 66,
   "name": "MalfunctionPumpExchanger",
   "description": "Malfunction Pump Exchanger (Seq-B)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 67,
   "name": "MalfunctionPumpCooling",
   "description": "Malfunction Pump Cooling (Seq-C)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 68,
   "name": "MalfunctionPumpRecirculation1",
   "description": "Malfunction Pump Recirculation 1 (Seq-D)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 69,
   "name": "MalfunctionPumpRecirculation2",
   "description": "Malfunction Pump Recirculation 2 (Seq-E)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 70,
   "name": "MalfunctionPumpFanSetpointComp",
   "description": "Malfunction Pump Fan Setpoint Comp (Seq-F)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 71,
   "name": "MalfunctionPumpHeating2",
   "description": "Malfunction Pump Heating 2 (Seq-G)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 72,
   "name": "MalfunctionPumpCooling2",
   "description": "Malfunction Pump Cooling 2 (Seq-H)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 73,
   "name": "MalfunctionPumpExchangerExtract",
   "description": "Malfunction Pump Exchanger Extract (Seq-I)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 74,
   "name": "MalfunctionPumpExternalHeatingCooling",
   "description": "Malfunction Pump External Heating/Cooling (Seq-J)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 75,
   "name": "MalfunctionExtraFanMotor1",
   "description": "Malfunction Extra Fan Motor 1",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 76,
   "name": "MalfunctionExtraFanMotor2",
   "description": "Malfunction Extra Fan Motor 1",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 77,
   "name": "PreHeaterFaultOverheat",
   "description": "Pre-Heater Fault / Overheat",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 78,
   "name": "MalfunctionPreheater",
   "description": "Malfunction Preheater",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 79,
   "name": "FailSafe",
   "description": "Fail-safe airflow/temperature",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 80,
   "name": "ExternalFrostGuard",
   "description": "External frost guard",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 82,
   "name": "MalfunctionSAF",
   "description": "Malfunction SAF",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 83,
   "name": "MalfunctionEAF",
   "description": "Malfunction EAF",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 84,
   "name": "MalfunctionHeatingZone1",
   "description": "Malfunction Heating Zone 1",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 85,
   "name": "MalfunctionHeatingZone2",
   "description": "Malfunction Heating Zone 2",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 86,
   "name": "MalfunctionHeatingZone3",
   "description": "Malfunction Heating Zone 3",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 87,
   "name": "MalfunctionCoolingZone1",
   "description": "Malfunction Cooling Zone 1",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 88,
   "name": "MalfunctionCoolingZone2",
   "description": "Malfunction Cooling Zone 2",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 89,
   "name": "MalfunctionCoolingZone3",
   "description": "Malfunction Cooling Zone 3",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 90,
   "name": "HPSumAlarmB",
   "description": "Heat pump B-alarm",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 91,
   "name": "HPSumAlarmC",
   "description": "Heat pump C-alarm",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 146,
   "name": "RotaryExchangerAlarm2",
   "description": "Rotary Exchanger Alarm 2",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 147,
   "name": "Gasdetectionalarm",
   "description": "Gas detection alarm",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 148,
   "name": "GasdetectionConfigError",
   "description": "Refrigerant and gas detection-configuration error",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 149,
   "name": "GasdetectionService",
   "description": "Service–Heat pump refrigerant system",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 151,
   "name": "ServiceHeatpumpSystemBlocked",
   "description": "Gas evacuation, service test period has expired, heat pump blocked until test",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 150,
   "name": "SafetyDamperConfigError",
   "description": "Safety damper module is not complete configured in communication device",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 152,
   "name": "DewPointNotReachable",
   "description": "Dewpoint not reachable, because of missing cooling capacity",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AV",
   "instance": 293,
   "name": "MotorSpeedHzSAF1",
   "description": "SAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 294,
   "name": "MotorSpeedHzSAF2",
   "description": "SAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 295,
   "name": "MotorSpeedHzSAF3",
   "description": "SAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 296,
   "name": "MotorSpeedHzSAF4",
   "description": "SAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 297,
   "name": "MotorSpeedHzSAF5",
   "description": "SAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 298,
   "name": "MotorSpeedHzSAF6",
   "description": "SAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 299,
   "name": "MotorSpeedHzSAF7",
   "description": "SAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 300,
   "name": "MotorSpeedHzSAF8",
   "description": "SAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 301,
   "name": "MotorSpeedHzSAF9",
   "description": "SAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 302,
   "name": "MotorSpeedHzSAF10",
   "description": "SAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 303,
   "name": "MotorSpeedHzEAF1",
   "description": "EAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 304,
   "name": "MotorSpeedHzEAF2",
   "description": "EAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 305,
   "name": "MotorSpeedHzEAF3",
   "description": "EAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 306,
   "name": "MotorSpeedHzEAF4",
   "description": "EAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 307,
   "name": "MotorSpeedHzEAF5",
   "description": "EAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 308,
   "name": "MotorSpeedHzEAF6",
   "description": "EAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 309,
   "name": "MotorSpeedHzEAF7",
   "description": "EAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 310,
   "name": "MotorSpeedHzEAF8",
   "description": "EAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 311,
   "name": "MotorSpeedHzEAF9",
   "description": "EAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 312,
   "name": "MotorSpeedHzEAF10",
   "description": "EAF Mot sp. Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 313,
   "name": "MotorSpeedRpmSAF1",
   "description": "SAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 314,
   "name": "MotorSpeedRpmSAF2",
   "description": "SAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 315,
   "name": "MotorSpeedRpmSAF3",
   "description": "SAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 316,
   "name": "MotorSpeedRpmSAF4",
   "description": "SAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 317,
   "name": "MotorSpeedRpmSAF5",
   "description": "SAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 318,
   "name": "MotorSpeedRpmSAF6",
   "description": "SAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 319,
   "name": "MotorSpeedRpmSAF7",
   "description": "SAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 320,
   "name": "MotorSpeedRpmSAF8",
   "description": "SAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 321,
   "name": "MotorSpeedRpmSAF9",
   "description": "SAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 322,
   "name": "MotorSpeedRpmSAF10",
   "description": "SAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 323,
   "name": "MotorSpeedRpmEAF1",
   "description": "EAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 324,
   "name": "MotorSpeedRpmEAF2",
   "description": "EAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 325,
   "name": "MotorSpeedRpmEAF3",
   "description": "EAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 326,
   "name": "MotorSpeedRpmEAF4",
   "description": "EAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 327,
   "name": "MotorSpeedRpmEAF5",
   "description": "EAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 328,
   "name": "MotorSpeedRpmEAF6",
   "description": "EAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 329,
   "name": "MotorSpeedRpmEAF7",
   "description": "EAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 330,
   "name": "MotorSpeedRpmEAF8",
   "description": "EAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 331,
   "name": "MotorSpeedRpmEAF9",
   "description": "EAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 332,
   "name": "MotorSpeedRpmEAF10",
   "description": "EAF Mot sp. RPM",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 333,
   "name": "MotorCurrentSAF1",
   "description": "SAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 334,
   "name": "MotorCurrentSAF2",
   "description": "SAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 335,
   "name": "MotorCurrentSAF3",
   "description": "SAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 336,
   "name": "MotorCurrentSAF4",
   "description": "SAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 337,
   "name": "MotorCurrentSAF5",
   "description": "SAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 338,
   "name": "MotorCurrentSAF6",
   "description": "SAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 339,
   "name": "MotorCurrentSAF7",
   "description": "SAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 340,
   "name": "MotorCurrentSAF8",
   "description": "SAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 341,
   "name": "MotorCurrentSAF9",
   "description": "SAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 342,
   "name": "MotorCurrentSAF10",
   "description": "SAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 343,
   "name": "MotorCurrentEAF1",
   "description": "EAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 344,
   "name": "MotorCurrentEAF2",
   "description": "EAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 345,
   "name": "MotorCurrentEAF3",
   "description": "EAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 346,
   "name": "MotorCurrentEAF4",
   "description": "EAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 347,
   "name": "MotorCurrentEAF5",
   "description": "EAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 348,
   "name": "MotorCurrentEAF6",
   "description": "EAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 349,
   "name": "MotorCurrentEAF7",
   "description": "EAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 350,
   "name": "MotorCurrentEAF8",
   "description": "EAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 351,
   "name": "MotorCurrentEAF9",
   "description": "EAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 352,
   "name": "MotorCurrentEAF10",
   "description": "EAF Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 353,
   "name": "MotorPowerSAF1",
   "description": "SAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 354,
   "name": "MotorPowerSAF2",
   "description": "SAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 355,
   "name": "MotorPowerSAF3",
   "description": "SAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 356,
   "name": "MotorPowerSAF4",
   "description": "SAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 357,
   "name": "MotorPowerSAF5",
   "description": "SAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 358,
   "name": "MotorPowerSAF6",
   "description": "SAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 359,
   "name": "MotorPowerSAF7",
   "description": "SAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 360,
   "name": "MotorPowerSAF8",
   "description": "SAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 361,
   "name": "MotorPowerSAF9",
   "description": "SAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 362,
   "name": "MotorPowerSAF10",
   "description": "SAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 363,
   "name": "MotorPowerEAF1",
   "description": "EAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 364,
   "name": "MotorPowerEAF2",
   "description": "EAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 365,
   "name": "MotorPowerEAF3",
   "description": "EAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 366,
   "name": "MotorPowerEAF4",
   "description": "EAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 367,
   "name": "MotorPowerEAF5",
   "description": "EAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 368,
   "name": "MotorPowerEAF6",
   "description": "EAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 369,
   "name": "MotorPowerEAF7",
   "description": "EAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 370,
   "name": "MotorPowerEAF8",
   "description": "EAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 371,
   "name": "MotorPowerEAF9",
   "description": "EAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 372,
   "name": "MotorPowerEAF10",
   "description": "EAF Mot power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 10,
   "name": "ActiveFaultSAF1",
   "description": "SAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 11,
   "name": "ActiveFaultSAF2",
   "description": "SAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 12,
   "name": "ActiveFaultSAF3",
   "description": "SAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 13,
   "name": "ActiveFaultSAF4",
   "description": "SAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 14,
   "name": "ActiveFaultSAF5",
   "description": "SAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 15,
   "name": "ActiveFaultSAF6",
   "description": "SAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 16,
   "name": "ActiveFaultSAF7",
   "description": "SAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 17,
   "name": "ActiveFaultSAF8",
   "description": "SAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 18,
   "name": "ActiveFaultSAF9",
   "description": "SAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 19,
   "name": "ActiveFaultSAF10",
   "description": "SAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 20,
   "name": "ActiveFaultEAF1",
   "description": "EAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 21,
   "name": "ActiveFaultEAF2",
   "description": "EAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 22,
   "name": "ActiveFaultEAF3",
   "description": "EAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 23,
   "name": "ActiveFaultEAF4",
   "description": "EAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 24,
   "name": "ActiveFaultEAF5",
   "description": "EAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 25,
   "name": "ActiveFaultEAF6",
   "description": "EAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 26,
   "name": "ActiveFaultEAF7",
   "description": "EAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 27,
   "name": "ActiveFaultEAF8",
   "description": "EAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 28,
   "name": "ActiveFaultEAF9",
   "description": "EAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 29,
   "name": "ActiveFaultEAF10",
   "description": "EAF fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 373,
   "name": "ActualSpeedSAF1",
   "description": "SAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 374,
   "name": "ActualSpeedSAF2",
   "description": "SAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 375,
   "name": "ActualSpeedSAF3",
   "description": "SAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 376,
   "name": "ActualSpeedSAF4",
   "description": "SAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 377,
   "name": "ActualSpeedSAF5",
   "description": "SAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 378,
   "name": "ActualSpeedSAF6",
   "description": "SAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 379,
   "name": "ActualSpeedSAF7",
   "description": "SAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 380,
   "name": "ActualSpeedSAF8",
   "description": "SAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 381,
   "name": "ActualSpeedSAF9",
   "description": "SAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 382,
   "name": "ActualSpeedSAF10",
   "description": "SAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 383,
   "name": "ActualSpeedEAF1",
   "description": "EAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 384,
   "name": "ActualSpeedEAF2",
   "description": "EAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 385,
   "name": "ActualSpeedEAF3",
   "description": "EAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 386,
   "name": "ActualSpeedEAF4",
   "description": "EAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 387,
   "name": "ActualSpeedEAF5",
   "description": "EAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 388,
   "name": "ActualSpeedEAF6",
   "description": "EAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 389,
   "name": "ActualSpeedEAF7",
   "description": "EAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 390,
   "name": "ActualSpeedEAF8",
   "description": "EAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 391,
   "name": "ActualSpeedEAF9",
   "description": "EAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 392,
   "name": "ActualSpeedEAF10",
   "description": "EAF Act. speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 393,
   "name": "AccumPowerSAF1",
   "description": "SAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 394,
   "name": "AccumPowerSAF2",
   "description": "SAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 395,
   "name": "AccumPowerSAF3",
   "description": "SAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 396,
   "name": "AccumPowerSAF4",
   "description": "SAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 397,
   "name": "AccumPowerSAF5",
   "description": "SAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 398,
   "name": "AccumPowerSAF6",
   "description": "SAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 399,
   "name": "AccumPowerSAF7",
   "description": "SAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 400,
   "name": "AccumPowerSAF8",
   "description": "SAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 401,
   "name": "AccumPowerSAF9",
   "description": "SAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 402,
   "name": "AccumPowerSAF10",
   "description": "SAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 403,
   "name": "AccumPowerEAF1",
   "description": "EAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 404,
   "name": "AccumPowerEAF2",
   "description": "EAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 405,
   "name": "AccumPowerEAF3",
   "description": "EAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 406,
   "name": "AccumPowerEAF4",
   "description": "EAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 407,
   "name": "AccumPowerEAF5",
   "description": "EAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 408,
   "name": "AccumPowerEAF6",
   "description": "EAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 409,
   "name": "AccumPowerEAF7",
   "description": "EAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 410,
   "name": "AccumPowerEAF8",
   "description": "EAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 411,
   "name": "AccumPowerEAF9",
   "description": "EAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 412,
   "name": "AccumPowerEAF10",
   "description": "EAF Accum. power",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 30,
   "name": "VVXFault",
   "description": "VVX Fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 413,
   "name": "DamperActPos1",
   "description": "Damper act. pos.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 414,
   "name": "DamperActPos2",
   "description": "Damper act. pos.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 415,
   "name": "DamperActPos3",
   "description": "Damper act. pos.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 416,
   "name": "DamperActPos4",
   "description": "Damper act. pos.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 417,
   "name": "DamperActPos5",
   "description": "Damper act. pos.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 418,
   "name": "DamperActPos6",
   "description": "Damper act. pos.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 419,
   "name": "DamperActPos7",
   "description": "Damper act. pos.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 420,
   "name": "DamperActPos8",
   "description": "Damper act. pos.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 421,
   "name": "DamperActPos9",
   "description": "Damper act. pos.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 422,
   "name": "DamperActPos10",
   "description": "Damper act. pos.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 31,
   "name": "DamperFault1",
   "description": "Damper fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 32,
   "name": "DamperFault2",
   "description": "Damper fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 33,
   "name": "DamperFault3",
   "description": "Damper fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 34,
   "name": "DamperFault4",
   "description": "Damper fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 35,
   "name": "DamperFault5",
   "description": "Damper fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 36,
   "name": "DamperFault6",
   "description": "Damper fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 37,
   "name": "DamperFault7",
   "description": "Damper fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 38,
   "name": "DamperFault8",
   "description": "Damper fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 39,
   "name": "DamperFault9",
   "description": "Damper fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 40,
   "name": "DamperFault10",
   "description": "Damper fault (bit masked)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 477,
   "name": "DCVoltageSAF1",
   "description": "SAF1 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 478,
   "name": "DCVoltageSAF2",
   "description": "SAF2 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 479,
   "name": "DCVoltageSAF3",
   "description": "SAF3 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 480,
   "name": "DCVoltageSAF4",
   "description": "SAF4 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 481,
   "name": "DCVoltageSAF5",
   "description": "SAF5 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 482,
   "name": "DCVoltageSAF6",
   "description": "SAF6 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 483,
   "name": "DCVoltageSAF7",
   "description": "SAF7 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 484,
   "name": "DCVoltageSAF8",
   "description": "SAF8 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 485,
   "name": "DCVoltageSAF9",
   "description": "SAF9 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 486,
   "name": "DCVoltageSAF10",
   "description": "SAF10 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 487,
   "name": "DCVoltageEAF1",
   "description": "EAF1 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 488,
   "name": "DCVoltageEAF2",
   "description": "EAF2 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 489,
   "name": "DCVoltageEAF3",
   "description": "EAF3 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 490,
   "name": "DCVoltageEAF4",
   "description": "EAF4 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 491,
   "name": "DCVoltageEAF5",
   "description": "EAF5 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 492,
   "name": "DCVoltageEAF6",
   "description": "EAF6 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 493,
   "name": "DCVoltageEAF7",
   "description": "EAF7 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 494,
   "name": "DCVoltageEAF8",
   "description": "EAF8 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 495,
   "name": "DCVoltageEAF9",
   "description": "EAF9 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 496,
   "name": "DCVoltageEAF10",
   "description": "EAF10 DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 497,
   "name": "MotorTemperatureSAF1",
   "description": "Motor temperature SAF1",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 498,
   "name": "MotorTemperatureSAF2",
   "description": "Motor temperature SAF2",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 499,
   "name": "MotorTemperatureSAF3",
   "description": "Motor temperature SAF3",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 500,
   "name": "MotorTemperatureSAF4",
   "description": "Motor temperature SAF4",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 501,
   "name": "MotorTemperatureSAF5",
   "description": "Motor temperature SAF5",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 502,
   "name": "MotorTemperatureSAF6",
   "description": "Motor temperature SAF6",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 503,
   "name": "MotorTemperatureSAF7",
   "description": "Motor temperature SAF7",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 504,
   "name": "MotorTemperatureSAF8",
   "description": "Motor temperature SAF8",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 505,
   "name": "MotorTemperatureSAF9",
   "description": "Motor temperature SAF9",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 506,
   "name": "MotorTemperatureSAF10",
   "description": "Motor temperature SAF10",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 507,
   "name": "MotorTemperatureEAF1",
   "description": "Motor temperature EAF1",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 508,
   "name": "MotorTemperatureEAF2",
   "description": "Motor temperature EAF2",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 509,
   "name": "MotorTemperatureEAF3",
   "description": "Motor temperature EAF3",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 510,
   "name": "MotorTemperatureEAF4",
   "description": "Motor temperature EAF4",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 511,
   "name": "MotorTemperatureEAF5",
   "description": "Motor temperature EAF5",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 512,
   "name": "MotorTemperatureEAF6",
   "description": "Motor temperature EAF6",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 513,
   "name": "MotorTemperatureEAF7",
   "description": "Motor temperature EAF7",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 514,
   "name": "MotorTemperatureEAF8",
   "description": "Motor temperature EAF8",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 515,
   "name": "MotorTemperatureEAF9",
   "description": "Motor temperature EAF9",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 516,
   "name": "MotorTemperatureEAF10",
   "description": "Motor temperature EAF10",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 517,
   "name": "MotorRunHourSAF1",
   "description": "Running time SAF1",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 518,
   "name": "MotorRunHourSAF2",
   "description": "Running time SAF2",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 519,
   "name": "MotorRunHourSAF3",
   "description": "Running time SAF3",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 520,
   "name": "MotorRunHourSAF4",
   "description": "Running time SAF4",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 521,
   "name": "MotorRunHourSAF5",
   "description": "Running time SAF5",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 522,
   "name": "MotorRunHourSAF6",
   "description": "Running time SAF6",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 523,
   "name": "MotorRunHourSAF7",
   "description": "Running time SAF7",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 524,
   "name": "MotorRunHourSAF8",
   "description": "Running time SAF8",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 525,
   "name": "MotorRunHourSAF9",
   "description": "Running time SAF9",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 526,
   "name": "MotorRunHourSAF10",
   "description": "Running time SAF10",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 527,
   "name": "MotorRunHourEAF1",
   "description": "Running time EAF1",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 528,
   "name": "MotorRunHourEAF2",
   "description": "Running time EAF2",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 529,
   "name": "MotorRunHourEAF3",
   "description": "Running time EAF3",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 530,
   "name": "MotorRunHourEAF4",
   "description": "Running time EAF4",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 531,
   "name": "MotorRunHourEAF5",
   "description": "Running time EAF5",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 532,
   "name": "MotorRunHourEAF6",
   "description": "Running time EAF6",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 533,
   "name": "MotorRunHourEAF7",
   "description": "Running time EAF7",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 534,
   "name": "MotorRunHourEAF8",
   "description": "Running time EAF8",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 535,
   "name": "MotorRunHourEAF9",
   "description": "Running time EAF9",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 536,
   "name": "MotorRunHourEAF10",
   "description": "Running time EAF10",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "DI_SAF",
   "description": "Feedback supply air fan",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "DI_EAF",
   "description": "Feedback extract air fan",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "DI_ExtendedRunLowSpeed",
   "description": "Extended operation low speed",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "DI_ExtendedRunNormalSpeed",
   "description": "Extended operation normal speed",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "DI_ExtendedRunHighSpeed",
   "description": "Extended operation high speed",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "DI_FireAlarm",
   "description": "Fire alarm",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "DI_SmokeAlarm",
   "description": "Smoke alarm",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "DI_ExternalAlarm",
   "description": "External alarm",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "DI_FireDamperIndication",
   "description": "Feedback fire damper",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "DI_SeqIndicationA",
   "description": "Feedback heating (SEQ-A)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "DI_SeqIndicationB",
   "description": "Feedback exchanger (SEQ-B)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 12,
   "name": "DI_SeqIndicationC",
   "description": "Feedback cooling (SEQ-C)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 13,
   "name": "DI_SeqIndicationD",
   "description": "Feedback recirculation 1 (SEQ-D)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "DI_SeqIndicationE",
   "description": "Feedback recirculation 2 (SEQ-E)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 15,
   "name": "DI_SeqIndicationF",
   "description": "Feedback fan setpoint comp (SEQ-F)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 16,
   "name": "DI_SeqIndicationG",
   "description": "Feedback heating 2 (SEQ-G)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 17,
   "name": "DI_SeqIndicationH",
   "description": "Feedback cooling 2 (SEQ-H)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 18,
   "name": "DI_SeqIndicationI",
   "description": "Feedback exchanger extract (SEQ-I)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 19,
   "name": "DI_SeqIndicationJ",
   "description": "Feedback external heating/cooling (SEQ-J)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 20,
   "name": "DI_Overheating",
   "description": "Overheated electric heater",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 21,
   "name": "DI_ExternalStop",
   "description": "External stop",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 22,
   "name": "DI_AlarmAcknowledgement",
   "description": "Alarm acknowledgement",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 23,
   "name": "DI_Flowswitch",
   "description": "Flow guard",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 24,
   "name": "DI_DeIcing",
   "description": "Defrosting guard exhanger",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 60,
   "name": "DI_ExchRotation",
   "description": "Rotary exchanger alarm",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 26,
   "name": "DI_Frostprotection",
   "description": "Freeze protection guard",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 27,
   "name": "DI_RecirculationRun",
   "description": "Start/(Stop) recirculation",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 28,
   "name": "DI_ChangeOver1",
   "description": "Cooling/(Heating) changeover 1",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 29,
   "name": "DI_ChangeOver2",
   "description": "Cooling/(Heating) changeover 2",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 30,
   "name": "DI_FilterGuard1",
   "description": "Filter guard 1 supply air",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 31,
   "name": "DI_FilterGuard2",
   "description": "Filter guard 2 extract air",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 32,
   "name": "DI_MotorControl1Start",
   "description": "Start/(Stop) extra fan motor 1",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 33,
   "name": "DI_MotorControl2Start",
   "description": "Start/(Stop) extra fan motor 2",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 34,
   "name": "DI_MotorControl1",
   "description": "Feedback extra fan motor 1",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 35,
   "name": "DI_MotorControl2",
   "description": "Feedback extra fan motor 2",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 36,
   "name": "DI_ExtraAlarm1",
   "description": "Extra alarm 1",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 37,
   "name": "DI_ExtraAlarm2",
   "description": "Extra alarm 2",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 38,
   "name": "DI_ExtraAlarm3",
   "description": "Extra alarm 3",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 39,
   "name": "DI_ExtraAlarm4",
   "description": "Extra alarm 4",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 40,
   "name": "DI_ExtraAlarm5",
   "description": "Extra alarm 5",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 41,
   "name": "DI_ExtraAlarm6",
   "description": "Extra alarm 6",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 42,
   "name": "DI_ExtraAlarm7",
   "description": "Extra alarm 7",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 43,
   "name": "DI_ExtraAlarm8",
   "description": "Extra alarm 8",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 44,
   "name": "DI_ExtraAlarm9",
   "description": "Extra alarm 9",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 45,
   "name": "DI_ExtraAlarm10",
   "description": "Extra alarm 10",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 46,
   "name": "DI_SupplyPIDFreeze",
   "description": "Lock PID controller supply",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 47,
   "name": "DI_SummerMode",
   "description": "Summer/(Winter) mode",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 48,
   "name": "DI_ExtraController",
   "description": "Feedback extra controller",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 49,
   "name": "DI_PreHeat",
   "description": "Feedback preheater",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 50,
   "name": "DI_Zone1HeatIndication",
   "description": "Feedback heating zone 1",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 51,
   "name": "DI_Zone2HeatIndication",
   "description": "Feedback heating zone 2",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 52,
   "name": "DI_Zone3HeatIndication",
   "description": "Feedback heating zone 3",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 53,
   "name": "DI_Zone1CoolIndication",
   "description": "Feedback cooling zone 1",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 54,
   "name": "DI_Zone2CoolIndication",
   "description": "Feedback cooling zone 2",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 55,
   "name": "DI_Zone3CoolIndication",
   "description": "Feedback cooling zone 3",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 56,
   "name": "DI_Zone1Overheating",
   "description": "Overheated electric heater zone 1",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 57,
   "name": "DI_Zone2Overheating",
   "description": "Overheated electric heater zone 2",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 58,
   "name": "DI_Zone3Overheating",
   "description": "Overheated electric heater zone 3",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 61,
   "name": "DI_FeedbackDXRunIndSeqA",
   "description": "DX-machine run indication Seq A",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 62,
   "name": "DI_FeedbackDXRunIndSeqB",
   "description": "DX-machine run indication Seq B",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 63,
   "name": "DI_FeedbackDXRunIndSeqC",
   "description": "DX-machine run indication Seq C",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 64,
   "name": "DI_FeedbackDXRunIndSeqD",
   "description": "DX-machine run indication Seq D",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 65,
   "name": "DI_FeedbackDXRunIndSeqE",
   "description": "DX-machine run indication Seq E",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 66,
   "name": "DI_FeedbackDXRunIndSeqF",
   "description": "DX-machine run indication Seq F",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 67,
   "name": "DI_FeedbackDXRunIndSeqG",
   "description": "DX-machine run indication Seq G",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 68,
   "name": "DI_FeedbackDXRunIndSeqH",
   "description": "DX-machine run indication Seq H",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 69,
   "name": "DI_FeedbackDXRunIndSeqI",
   "description": "DX-machine run indication Seq I",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 70,
   "name": "DI_FeedbackDXRunIndSeqJ",
   "description": "DX-machine run indication Seq I",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 71,
   "name": "DI_FeedbackDXDefSeqA",
   "description": "DX-machine defrost indication Seq A",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 72,
   "name": "DI_FeedbackDXDefSeqB",
   "description": "DX-machine defrost indication Seq B",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 73,
   "name": "DI_FeedbackDXDefSeqC",
   "description": "DX-machine defrost indication Seq C",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 74,
   "name": "DI_FeedbackDXDefSeqD",
   "description": "DX-machine defrost indication Seq D",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 75,
   "name": "DI_FeedbackDXDefSeqE",
   "description": "DX-machine defrost indication Seq E",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 76,
   "name": "DI_FeedbackDXDefSeqF",
   "description": "DX-machine defrost indication Seq F",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 77,
   "name": "DI_FeedbackDXDefSeqG",
   "description": "DX-machine defrost indication Seq G",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 78,
   "name": "DI_FeedbackDXDefSeqH",
   "description": "DX-machine defrost indication Seq H",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 79,
   "name": "DI_FeedbackDXDefSeqI",
   "description": "DX-machine defrost indication Seq I",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 80,
   "name": "DI_FeedbackDXDefSeqJ",
   "description": "DX-machine defrost indication Seq J",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 81,
   "name": "DI_FeedbackDXRunIndChangeOver1",
   "description": "DX-machine run indication change over 1",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 82,
   "name": "DI_FeedbackDXRunIndChangeOver2",
   "description": "DX-machine run indication change over 2",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 83,
   "name": "DI_FeedbackDXDefChangeOver1",
   "description": "DX-machine defrost indication change over 1",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 84,
   "name": "DI_FeedbackDXDefChangeOver2",
   "description": "DX-machine defrost indication change over 2",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 85,
   "name": "DI_FilterGuard3",
   "description": "Filter guard 3 supply air pre filter",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 86,
   "name": "DI_FilterGuard4",
   "description": "Filter guard 4 supply air end filter",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 87,
   "name": "DI_FilterGuard5",
   "description": "Filter guard 5 extract air pre filter",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 88,
   "name": "DI_ExchRotation2",
   "description": "Rotary exchanger alarm 2",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 89,
   "name": "DI_GasDetectionAcknowledgement",
   "description": "Gas detection alarm acknowledgement",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "AI_OutDoorTemp",
   "description": "Outdoor temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "AI_IntakeAirTemp",
   "description": "Intake air temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "AI_SupplyAirTemp",
   "description": "Supply air temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "AI_ExhaustAirTemp",
   "description": "Exhaust air temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "AI_ExtractAirTemp",
   "description": "Extract air temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "AI_RoomTemp1",
   "description": "Room temperature 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "AI_RoomTemp2",
   "description": "Room temperature 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "AI_RoomTemp3",
   "description": "Room temperature 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "AI_RoomTemp4",
   "description": "Room temperature 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "AI_SAFPressure",
   "description": "Supply air fan pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "AI_EAFPressure",
   "description": "Extract air fan pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "AI_SAFFlow",
   "description": "Supply air fan flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "AI_EAFFlow",
   "description": "Extract air fan flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "AI_ExchAirFlowSAF",
   "description": "Exchanger SAF pressure sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "AI_ExchPressureEAF",
   "description": "Exchanger EAF pressure sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "AI_DeIcingTemp",
   "description": "De-icing temp exchanger",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "AI_FrostprotTemp1",
   "description": "Frost protection temp 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "AI_FrostprotTemp2",
   "description": "Frost protection temp 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "AI_FrostprotTemp3",
   "description": "Frost protection temp 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "AI_CO2",
   "description": "CO2 (ppm)",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "AI_HumidityRoom",
   "description": "Humidity room",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "AI_HumidityDuct",
   "description": "Humidity duct",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "AI_HumidityOutDoor",
   "description": "Humidity outdoor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "AI_ExtraControllerTemp",
   "description": "Extra controller temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "AI_ExtSAFControl",
   "description": "External SAF signal control",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "AI_ExtEAFControl",
   "description": "External EAF signal control",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "AI_ExtraSensor1",
   "description": "Extra sensor 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "AI_ExtraSensor2",
   "description": "Extra sensor 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "AI_ExtraSensor3",
   "description": "Extra sensor 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "AI_ExtraSensor4",
   "description": "Extra sensor 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "AI_ExtraSensor5",
   "description": "Extra sensor 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "AI_ExternalSupplySetP",
   "description": "External Setpoint",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "AI_ExternalFlowSetP",
   "description": "External Setpoint SAF airflow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "AI_FilterGuard1",
   "description": "Supply air filter",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "AI_FilterGuard2",
   "description": "Extract air filter",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "AI_EfficiencyTemp",
   "description": "Temperature efficiency sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "AI_PreHeatTemp",
   "description": "Preheater temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "AI_Zone1SupplyTemp",
   "description": "Zone1 supply temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "AI_Zone2SupplyTemp",
   "description": "Zone2 supply temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "AI_Zone3SupplyTemp",
   "description": "Zone3 supply temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "AI_Zone1ExtractTemp",
   "description": "Zone1 extract temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "AI_Zone2ExtractTemp",
   "description": "Zone2 sxtract temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "AI_Zone3ExtractTemp",
   "description": "Zone3 extract temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "AI_Zone1RoomTemp",
   "description": "Zone1 room temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "AI_Zone2RoomTemp",
   "description": "Zone2 room temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "AI_Zone3RoomTemp",
   "description": "Zone3 room temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "AI_Zone1FrostprotTemp",
   "description": "Zone1 frost protection temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "AI_Zone2FrostprotTemp",
   "description": "Zone2 frost protection temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 49,
   "name": "AI_Zone3FrostprotTemp",
   "description": "Zone3 frost protection temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 50,
   "name": "AI_FeedbackCoolerValve",
   "description": "Feedback cooler valve",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 51,
   "name": "AI_FeedbackOutdoorAirDamper",
   "description": "Feedback outdoor air damper",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 52,
   "name": "AI_FeedbackRecircAirDamper",
   "description": "Feedback recirculation damper",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 53,
   "name": "AI_EATRDPT",
   "description": "Difference pressure between SAF and EAF (Pa)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 54,
   "name": "AI_FilterGuard3",
   "description": "Supply air pre filter",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "AI_FilterGuard4",
   "description": "Supply air end filter",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 56,
   "name": "AI_FilterGuard5",
   "description": "Extract air pre filter",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 57,
   "name": "AI_CoolerInletTemp",
   "description": "Temperature entering the cooling coil",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 58,
   "name": "AI_CoolerInletHumidity",
   "description": "Humidity entering the cooling coil",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 59,
   "name": "AI_ExchExtractTemp",
   "description": "Exchanger extract air temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "DO_SeqStartA",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 2,
   "name": "DO_SeqStartB",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 3,
   "name": "DO_SeqStartC",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "DO_SeqStartD",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 5,
   "name": "DO_SeqStartE",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 6,
   "name": "DO_SeqStartF",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 7,
   "name": "DO_SeqStartG",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 8,
   "name": "DO_SeqStartH",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 9,
   "name": "DO_SeqStartI",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 10,
   "name": "DO_SeqStartJ",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 11,
   "name": "DO_SeqPumpA",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 12,
   "name": "DO_SeqPumpB",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 13,
   "name": "DO_SeqPumpC",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 14,
   "name": "DO_SeqPumpD",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 15,
   "name": "DO_SeqPumpE",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 16,
   "name": "DO_SeqPumpF",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 17,
   "name": "DO_SeqPumpG",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 18,
   "name": "DO_SeqPumpH",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 19,
   "name": "DO_SeqPumpI",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 20,
   "name": "DO_SeqPumpJ",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 21,
   "name": "DO_SAFStart",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 22,
   "name": "DO_EAFStart",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 23,
   "name": "DO_RecirculationAirDamper",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 24,
   "name": "DO_OutdoorAirDamper",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 25,
   "name": "DO_ExhaustAirDamper",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 26,
   "name": "DO_FireDamper",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 27,
   "name": "DO_SumAlarm1",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 28,
   "name": "DO_SumAlarm2",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 29,
   "name": "DO_AlarmOutput",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 30,
   "name": "DO_MotorControl1Start",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 31,
   "name": "DO_MotorControl2Start",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 32,
   "name": "DO_TimeChannel1",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 33,
   "name": "DO_TimeChannel2",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 34,
   "name": "DO_TimeChannel3",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 35,
   "name": "DO_TimeChannel4",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 36,
   "name": "DO_FreeCoolRun",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 37,
   "name": "DO_PreTreatment",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 38,
   "name": "DO_RunIndication",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 39,
   "name": "DO_StepController1Step1",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 40,
   "name": "DO_StepController1Step2",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 41,
   "name": "DO_StepController1Step3",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 42,
   "name": "DO_StepController1Step4",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 43,
   "name": "DO_StepController2Step1",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 44,
   "name": "DO_StepController2Step2",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 45,
   "name": "DO_StepController2Step3",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 46,
   "name": "DO_StepController2Step4",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 47,
   "name": "DO_HumidityStart",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 48,
   "name": "DO_ChangeOver1",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 49,
   "name": "DO_ChangeOver2",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 50,
   "name": "DO_ExchControl",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 51,
   "name": "DO_Deicing3Start",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 52,
   "name": "DO_ExtraControllerStart",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 53,
   "name": "DO_ExtraControllerPump",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 54,
   "name": "DO_Auxiliary1",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 55,
   "name": "DO_Auxiliary2",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 56,
   "name": "DO_Auxiliary3",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 57,
   "name": "DO_PreHeatStart",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 58,
   "name": "DO_PreHeatPump",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 59,
   "name": "DO_Zone1HeatPump",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 60,
   "name": "DO_Zone2HeatPump",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 61,
   "name": "DO_Zone3HeatPump",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 62,
   "name": "DO_Zone1CoolPump",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 63,
   "name": "DO_Zone2CoolPump",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 64,
   "name": "DO_Zone3CoolPump",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 65,
   "name": "DO_Zone1Step1",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 66,
   "name": "DO_Zone1Step2",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 67,
   "name": "DO_Zone2Step1",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 68,
   "name": "DO_Zone2Step2",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 69,
   "name": "DO_Zone3Step1",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 70,
   "name": "DO_Zone3Step2",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 71,
   "name": "DO_Zone1HeatStart",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 72,
   "name": "DO_Zone2HeatStart",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 73,
   "name": "DO_Zone3HeatStart",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 74,
   "name": "DO_Zone1CoolStart",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 75,
   "name": "DO_Zone2CoolStart",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 76,
   "name": "DO_Zone3CoolStart",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 77,
   "name": "DO_Zone4CoolStart",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 78,
   "name": "DO_GasDetectionAlarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "AO_SequenceA",
   "description": "Y1 sequence output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 2,
   "name": "AO_SequenceB",
   "description": "Y2 sequence output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 3,
   "name": "AO_SequenceC",
   "description": "Y3 sequence output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 4,
   "name": "AO_SequenceD",
   "description": "Y4 sequence output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 5,
   "name": "AO_SequenceE",
   "description": "Y5 sequence output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 6,
   "name": "AO_SequenceF",
   "description": "Y6 sequence output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 7,
   "name": "AO_SequenceG",
   "description": "Y7 sequence output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 8,
   "name": "AO_SequenceH",
   "description": "Y8 sequence output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 9,
   "name": "AO_SequenceI",
   "description": "Y9 sequence output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 10,
   "name": "AO_SequenceJ",
   "description": "Y10 sequence output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 11,
   "name": "AO_ChangeOver1",
   "description": "Change over 1",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 12,
   "name": "AO_ChangeOver2",
   "description": "Change over 2",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 13,
   "name": "AO_SAF",
   "description": "Control valve Supply air fan in",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 14,
   "name": "AO_EAF",
   "description": "Control valve Extract air fan",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 15,
   "name": "AO_Humidity",
   "description": "Control valve Humidity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 16,
   "name": "AO_StepController1",
   "description": "Step Controller 1",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 17,
   "name": "AO_StepController2",
   "description": "Step Controller 2",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 18,
   "name": "AO_ExtraController",
   "description": "Extra Controller",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 19,
   "name": "AO_AISignalOutput",
   "description": "AI Signal output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 20,
   "name": "AO_PreHeat",
   "description": "PreHeat output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 21,
   "name": "AO_Zone1Heat",
   "description": "Zone1 Heating",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 22,
   "name": "AO_Zone2Heat",
   "description": "Zone2 Heating",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 23,
   "name": "AO_Zone3Heat",
   "description": "Zone3 Heating",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 24,
   "name": "AO_Zone1Cool",
   "description": "Zone1 Cooling",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 25,
   "name": "AO_Zone2Cool",
   "description": "Zone2 Cooling",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 26,
   "name": "AO_Zone3Cool",
   "description": "Zone3 Cooling",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 27,
   "name": "AO_EATRControl",
   "description": "EATR control function output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 1,
   "name": "TL_IntakeAirTemp",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 2,
   "name": "TL_IntakeAirTemp_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 3,
   "name": "TL_SupplyAirTemp",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 4,
   "name": "TL_SupplyAirTemp_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 5,
   "name": "TL_ExhaustAirTemp",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 6,
   "name": "TL_ExhaustAirTemp_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 7,
   "name": "TL_ExtractAirTemp",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 8,
   "name": "TL_ExtractAirTemp_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 9,
   "name": "TL_DeIcingTemp",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 10,
   "name": "TL_DeIcingTemp_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 11,
   "name": "TL_FrostprotTemp1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 12,
   "name": "TL_FrostprotTemp1_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 13,
   "name": "TL_CO2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 14,
   "name": "TL_CO2_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 15,
   "name": "TL_HumidityRoom",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 16,
   "name": "TL_HumidityRoom_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 17,
   "name": "TL_EAFPressure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 18,
   "name": "TL_EAFPressure_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 19,
   "name": "TL_SAFFlow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 20,
   "name": "TL_SAFFlow_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 21,
   "name": "TL_EAFFlow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 22,
   "name": "TL_EAFFlow_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 23,
   "name": "TL_RoomTemp1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 24,
   "name": "TL_RoomTemp1_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 25,
   "name": "TL_FlowExchSA",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 26,
   "name": "TL_FlowExchSA_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 27,
   "name": "TL_FrostprotTemp3",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 28,
   "name": "TL_FrostprotTemp3_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 29,
   "name": "TL_HumiditySupplyAir",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 30,
   "name": "TL_HumiditySupplyAir_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 31,
   "name": "TL_EfficiencyTempExch",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 32,
   "name": "TL_EfficiencyTempExch_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 33,
   "name": "TLPreHeatTemp",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 34,
   "name": "TL_PreHeatTemp_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 35,
   "name": "TL_EATRPressure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 36,
   "name": "TL_EATRPressure_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 37,
   "name": "TL_SeqPumpA",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 38,
   "name": "TL_SeqPumpA_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 39,
   "name": "TL_Auxiliary1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 40,
   "name": "TL_Auxiliary1_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 41,
   "name": "TL_HeatingSeqA",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 42,
   "name": "TL_HeatingSeqA_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 43,
   "name": "TL_CoolingSeqC",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 44,
   "name": "TL_CoolingSeqC_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 45,
   "name": "TL_ExcSeqB",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 46,
   "name": "TL_ExcSeqB_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 47,
   "name": "TL_Recirculation1SeqD",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 48,
   "name": "TL_Recirculation1SeqD_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 49,
   "name": "TL_Recirculation2SeqE",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 50,
   "name": "TL_Recirculation2SeqE_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 51,
   "name": "TL_Heating2SeqG",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 52,
   "name": "TL_Heating2SeqG_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 53,
   "name": "TL_SeqPumpC",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 54,
   "name": "TL_SeqPumpC_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 55,
   "name": "TL_Cooling2SeqH",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 56,
   "name": "TL_Cooling2SeqH_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 57,
   "name": "TL_ExternalHCSeqJ",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 58,
   "name": "TL_ExternalHCSeqJ_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 59,
   "name": "TL_SAFanAO",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 60,
   "name": "TL_SAFanAO_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 61,
   "name": "TL_EAFanAO",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 62,
   "name": "TL_EAFanAO_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 63,
   "name": "TL_PreHeatAO",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 64,
   "name": "TL_PreHeatAO_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 65,
   "name": "TL_EATRControlAO",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 66,
   "name": "TL_EATRControlAO_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 67,
   "name": "TL_SAFPressure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 68,
   "name": "TL_SAFPressure_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 71,
   "name": "TL_UnitModeM",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 72,
   "name": "TL_UnitModeM_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 73,
   "name": "TL_DefrostIndDxChangover1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 74,
   "name": "TL_DefrostIndDxChangover1_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 75,
   "name": "TL_DefrostIndDxChangover2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 76,
   "name": "TL_DefrostIndDxChangover2_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 77,
   "name": "TL_HumidityStartDO",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 78,
   "name": "TL_HumidityStartDO_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 79,
   "name": "TL_ChangeOver1DO",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 80,
   "name": "TL_ChangeOver1DO_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 81,
   "name": "TL_ChangeOver2DO",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 82,
   "name": "TL_ChangeOver2DO_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 83,
   "name": "TL_PreHeatPumpDO",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 84,
   "name": "TL_PreHeatPumpDO_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 85,
   "name": "TL_AEfficiency",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 86,
   "name": "TL_AEfficiency_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 87,
   "name": "TL_FreeCoolActiveDO",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 88,
   "name": "TL_FreeCoolActiveDO_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 89,
   "name": "TL_SupprtConHeatDO",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 90,
   "name": "TL_SupprtConHeatDO_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 91,
   "name": "TL_SupprtConCoolDO",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 92,
   "name": "TL_SupprtConCoolDO_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 93,
   "name": "TL_SectionDefrostActiveDO",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 94,
   "name": "TL_SectionDefrostActiveDO_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 95,
   "name": "TL_BMSOverride",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 96,
   "name": "TL_BMSOverride_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 97,
   "name": "TL_ExchExtractTemp",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "TL",
   "instance": 98,
   "name": "TL_ExchExtractTemp_Avg2min",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 1,
   "name": "AlarmsClassA",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 2,
   "name": "AlarmsClassB",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 3,
   "name": "AlarmsClassC",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 4,
   "name": "EventPoints",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "DEV",
   "instance": 1,
   "name": "Access",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/systemair/access-5-controller",
 "note": "Re-typed from the manufacturer's public documentation (see source). Point availability varies by firmware and options; verify against the live device."
}