Easy BACnet
  1. Home
  2. BACnet points lists
  3. Paragon Controls
  4. SPM-4000 Dual Controller space pressure monitor (BACnet MS/TP)

Room pressure dual controller · BACnet points list

Paragon Controls SPM-4000 Dual Controller space pressure monitor (BACnet MS/TP) BACnet points list

Updated 12 November 2026

Short answer

The SPM-4000 Dual Controller monitors two spaces and runs a separate control loop for each. On BACnet MS/TP it gives both pressures, both controller outputs, per-space modes and alarm limits, and setpoints and tuning for each loop. Unlike the single-loop SPM-4000 it has no temperature, humidity, flow or air-change objects.

This page lists 38 BACnet objects for the Paragon Controls SPM-4000 Dual Controller space pressure monitor (BACnet MS/TP) — 28 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Paragon Controls’s own free documentation, linked below.

Manufacturer
Paragon Controls
Model
SPM-4000 Dual Controller space pressure monitor (BACnet MS/TP)
Equipment
Room pressure dual controller
Equipment type
Thermostats, sensors & meters
BACnet objects
38 (28 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
SPM-4000 Dual Controller, SPM4000 Dual, Guardian Infinity Dual Controller
Source document
BACnet Communication Operation & Maintenance Manual (MicroTransEQ, MicroTransII, SPM-3000, SPM-4000) · rev. Revision Level 003
Download CSV 38 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Paragon Controls’s current documentation and the live device before use. Not official Paragon Controls information. Terms of use.

BMS integration notes: Paragon Controls SPM-4000 Dual Controller space pressure monitor (BACnet MS/TP)

Integration in brief

Set each space's mode (MSV 1 / MSV 3) and the loop setpoints for that mode (AV 11-13 for loop 1, AV 17-19 for loop 2). Read both pressures, both controller outputs, the system start status and the alarm multistates.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1Sp1 Operating ModeSpace 1 mode: 1 off, 2 positive, 3 negativeWrite
MV 3Sp2 Operating ModeSpace 2 mode: 1 off, 2 positive, 3 negativeWrite
AV 11Cnt1 Pos SetpointLoop 1 setpoint in positive modeWrite
AV 17Cnt2 Pos SetpointLoop 2 setpoint in positive modeWrite
BI 1Sys Start In StatusSystem start input, 1 = runRead
AI 1Sp1 Process ValueSpace 1 differential pressureRead
AI 2Sp2 Process ValueSpace 2 differential pressureRead
AO 1Controller Output 1Loop 1 outputRead
MV 2Sp1 Alarm StatusSpace 1 alarm: 1 none, 2 high, 3 lowRead
MV 4Sp2 Alarm StatusSpace 2 alarm: 1 none, 2 high, 3 lowRead

Enable & remote start

Run/stop comes from the hard-wired system start input; BI 1 only reports it.

Network setup

Watch out for

Paragon Controls SPM-4000 Dual Controller space pressure monitor (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

38 of 38 shown
Type
Multi-state
Access
Show
Paragon Controls SPM-4000 Dual Controller space pressure monitor (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1Sp1 Process ValueSpace 1 pressurePer MSV 5Read
AImin2Sp2 Process ValueSpace 2 pressurePer MSV 5Read
AOmin1Controller Output 1Loop 1 outputRead
AO2Controller Output 2Loop 2 outputRead
AV1Sp1 Operating RangeSpace 1 pressure spanRead
AV2Sp1 Pos High AlarmSpace 1 high limit, positive modeWrite
AV3Sp1 Pos Low AlarmSpace 1 low limit, positive modeWrite
AV4Sp1 Neg High AlarmSpace 1 high limit, negative modeWrite
AV5Sp1 Neg Low AlarmSpace 1 low limit, negative modeWrite
AV6Sp2 Operating RangeSpace 2 pressure spanRead
AV7Sp2 Pos High AlarmSpace 2 high limit, positive modeWrite
AV8Sp2 Pos Low AlarmSpace 2 low limit, positive modeWrite
AV9Sp2 Neg High AlarmSpace 2 high limit, negative modeWrite
AV10Sp2 Neg Low AlarmSpace 2 low limit, negative modeWrite
AVmin11Cnt1 Pos SetpointLoop 1 setpoint, positive modeWrite
AV12Cnt1 Neg SetpointLoop 1 setpoint, negative modeWrite
AV13Cnt1 Off SetpointLoop 1 setpoint, off modeWrite
AV14Cnt1 Prop BandLoop 1 proportional bandWrite
AV15Cnt1 Integral TimeLoop 1 integral timeWrite
AV16Cnt1 Derivative TimeLoop 1 derivative timeWrite
AVmin17Cnt2 Pos SetpointLoop 2 setpoint, positive modeWrite
AV18Cnt2 Neg SetpointLoop 2 setpoint, negative modeWrite
AV19Cnt2 Off SetpointLoop 2 setpoint, off modeWrite
AV20Cnt2 Prop BandLoop 2 proportional bandWrite
AV21Cnt2 Integral TimeLoop 2 integral timeWrite
AV22Cnt2 Derivative TimeLoop 2 derivative timeWrite
AV23Sp1 Alarm DelaySpace 1 alarm delayWrite
AV24Sp2 Alarm DelaySpace 2 alarm delayWrite
AV25Field PasswordFront-panel passwordWrite
AV26Decimal PointDisplay decimal placesWrite
BImin1Sys Start In StatusSystem start inputRead0=Off, 1=Run
BI2Sys Hold In StatusSystem hold inputRead0=Off, 1=On
BV1Audible Alarm EnableAudible alarm on/offWrite0=Off, 1=On
MVmin1Sp1 Operating ModeSpace 1 modeWrite1=Off, 2=Pos, 3=Neg
MVmin2Sp1 Alarm StatusSpace 1 alarm stateRead1=No Alarms, 2=High, 3=Low
MVmin3Sp2 Operating ModeSpace 2 modeWrite1=Off, 2=Pos, 3=Neg
MVmin4Sp2 Alarm StatusSpace 2 alarm stateRead1=No Alarms, 2=High, 3=Low
MV5Engineering UnitsPressure unitsWrite1="W.C., 2=Pa, 3=KPa, 4=mmW.C.
Object ID lookup: Paragon Controls SPM-4000 Dual Controller space pressure monitor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SPM-4000 Dual Controller space pressure monitor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Paragon Controls SPM-4000 Dual Controller space pressure monitor (BACnet MS/TP)

How many BACnet points does the Paragon Controls SPM-4000 Dual Controller space pressure monitor (BACnet MS/TP) have?

This list has 38 BACnet objects: 2 analog inputs, 2 analog outputs, 26 analog values, 2 binary inputs, 1 binary value, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Paragon Controls SPM-4000 Dual Controller space pressure monitor (BACnet MS/TP) BACnet points are writable?

28 of the 38 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Paragon Controls SPM-4000 Dual Controller space pressure monitor (BACnet MS/TP) BACnet documentation?

The source is BACnet Communication Operation & Maintenance Manual (MicroTransEQ, MicroTransII, SPM-3000, SPM-4000), revision Revision Level 003, published free by Paragon Controls at https://paragoncontrols.com/wp-content/uploads/2021/03/BACnet-IOM.pdf.

What are the minimum BACnet points to integrate the Paragon Controls SPM-4000 Dual Controller space pressure monitor (BACnet MS/TP)?

Start with MV 1 Sp1 Operating Mode (Space 1 mode: 1 off, 2 positive, 3 negative); MV 3 Sp2 Operating Mode (Space 2 mode: 1 off, 2 positive, 3 negative); AV 11 Cnt1 Pos Setpoint (Loop 1 setpoint in positive mode); AV 17 Cnt2 Pos Setpoint (Loop 2 setpoint in positive mode); BI 1 Sys Start In Status (System start input, 1 = run); AI 1 Sp1 Process Value (Space 1 differential pressure); AI 2 Sp2 Process Value (Space 2 differential pressure); AO 1 Controller Output 1 (Loop 1 output); MV 2 Sp1 Alarm Status (Space 1 alarm: 1 none, 2 high, 3 low); MV 4 Sp2 Alarm Status (Space 2 alarm: 1 none, 2 high, 3 low).

How do I enable BMS control of the Paragon Controls SPM-4000 Dual Controller space pressure monitor (BACnet MS/TP)?

Run/stop comes from the hard-wired system start input; BI 1 only reports it.

How do I check these points on the real SPM-4000 Dual Controller space pressure monitor (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Paragon Controls BACnet points lists

Source: BACnet Communication Operation & Maintenance Manual (MicroTransEQ, MicroTransII, SPM-3000, SPM-4000) · rev. Revision Level 003. Object names, instances and units are reproduced as published; descriptions are our own.