Airflow measuring station (multi-system) · BACnet points list

Paragon Controls MTSE Multi-Trans Smart Ecosystem flow / pressure station (BACnet MS/TP) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The MTSE collects several airflow or pressure sensors into up to three systems plus a sub system and reports them on BACnet MS/TP. Per system it gives total flow, temperature, operating range, alarm limits, units, temperature source and process type; it also has four controller outputs, two digital inputs and outputs, and per-sensor flow, pressure and status objects.

This page lists 56 BACnet objects for the Paragon Controls MTSE Multi-Trans Smart Ecosystem flow / pressure station (BACnet MS/TP) — 37 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Paragon Controls’s documentation hosted by BACnet International, not by Paragon Controls itself, so treat it as unofficial.

Manufacturer
Paragon Controls
Model
MTSE Multi-Trans Smart Ecosystem flow / pressure station (BACnet MS/TP)
Equipment
Airflow measuring station (multi-system)
Equipment type
Thermostats, sensors & meters
BACnet objects
56 (37 writable)
Transport
BACnet MS/TP
Firmware
V5.1.7 (BTL listing)
Also known as
MTSE, Multi-Trans Smart Ecosystem, Paragon MTSE
Source document
MTSE Unit BACnet Protocol Implementation Conformance Statement (MTSE BACnet PIC V5.1.7) · rev. Rev 6, 6/14/2021 (unofficial copy, hosted by BACnet International)
Download CSV 56 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Paragon Controls’s current documentation and the live device before use. Not official Paragon Controls information. Terms of use.

BMS integration notes: Paragon Controls MTSE Multi-Trans Smart Ecosystem flow / pressure station (BACnet MS/TP)

Integration in brief

Read the system total flows (AI 1-4) and the per-sensor status multistates. If temperature compensation should use a BMS value, set the system's temperature source to Network and write the matching temperature AI.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1System 1 Total FlowSystem 1 total flowRead
AI 2System 2 Total FlowSystem 2 total flowRead
AI 3System 3 Total FlowSystem 3 total flowRead
AI 4Sub System FlowSub system flowRead
AI 5System 1 TemperatureSystem 1 temperature; BMS writes it when source = NetworkWrite
MI 11System 1 Sensor 1 StatusSensor status: 1 normal, 2 alarm, 3 failureRead

Sensors & values from the BMS

Each system's temperature can come from the BMS: set its Temperature Source multistate (MSV 5-8) to 3 (Network) and write the matching temperature AI (AI 5-8).

Network setup

Watch out for

Paragon Controls MTSE Multi-Trans Smart Ecosystem flow / pressure station (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

56 of 56 shown
Type
Other
Access
Show
Paragon Controls MTSE Multi-Trans Smart Ecosystem flow / pressure station (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1System 1 Total FlowSystem 1 total flow (or pressure)Per MSV 1Read
AImin2System 2 Total FlowSystem 2 total flow (or pressure)Per MSV 2Read
AImin3System 3 Total FlowSystem 3 total flow (or pressure)Per MSV 3Read
AImin4Sub System FlowSub system flowRead
AImin5System 1 TemperatureSystem 1 temperature; writable when its source is NetworkPer MSV 4Write
AI6System 2 TemperatureSystem 2 temperature; writable when its source is NetworkPer MSV 4Write
AI7System 3 TemperatureSystem 3 temperature; writable when its source is NetworkPer MSV 4Write
AI8Sub System TemperatureSub System temperature; writable when its source is NetworkPer MSV 4Write
AV1System 1 Operating RangeSystem 1 spanWrite
AV2System 2 Operating RangeSystem 2 spanWrite
AV3System 3 Operating RangeSystem 3 spanWrite
AV4Sub System Operating RangeSub System spanWrite
AV5System 1 High Alarm ValueSystem 1 high alarm limitWrite
AV6System 2 High Alarm ValueSystem 2 high alarm limitWrite
AV7System 3 High Alarm ValueSystem 3 high alarm limitWrite
AV8Sub System High Alarm ValueSub System high alarm limitWrite
AV9System 1 Low Alarm ValueSystem 1 low alarm limitWrite
AV10System 2 Low Alarm ValueSystem 2 low alarm limitWrite
AV11System 3 Low Alarm ValueSystem 3 low alarm limitWrite
AV12Sub System Low Alarm ValueSub System low alarm limitWrite
AV13Controller 1 OutputController 1 output, 0-100Write
AV14Controller 2 OutputController 2 output, 0-100Write
AV15Controller 3 OutputController 3 output, 0-100Write
AV16Controller 4 OutputController 4 output, 0-100Write
BI1Digital Input 1Digital input 1Read
BI2Digital Input 2Digital input 2Read
BV1System 1 Alarm EnableSystem 1 alarms on/offWrite1=Off, 2=On
BV2System 2 Alarm EnableSystem 2 alarms on/offWrite1=Off, 2=On
BV3System 3 Alarm EnableSystem 3 alarms on/offWrite1=Off, 2=On
BV4Sub System Alarm EnableSub System alarms on/offWrite1=Off, 2=On
BV5Digital Output 1Digital output 1Write
BV6Digital Output 2Digital output 2Write
MV1System 1 Engineering UnitsSystem 1 unitsWritePer process type (MSV 9-11): Std flow SCFM/SCFH/SL/S/Sm3/S/Sm3/M/Sm3/HR; Act flow ACFM/L/S/Am3/S/Am3/M/Am3/HR; Std vel SFPM/Sm/s; Act vel AFPM/Am/s; Pressure In. W.C./Pa/kPa/mm W.C.
MV2System 2 Engineering UnitsSystem 2 unitsWritePer process type (MSV 9-11): Std flow SCFM/SCFH/SL/S/Sm3/S/Sm3/M/Sm3/HR; Act flow ACFM/L/S/Am3/S/Am3/M/Am3/HR; Std vel SFPM/Sm/s; Act vel AFPM/Am/s; Pressure In. W.C./Pa/kPa/mm W.C.
MV3System 3 Engineering UnitsSystem 3 unitsWritePer process type (MSV 9-11): Std flow SCFM/SCFH/SL/S/Sm3/S/Sm3/M/Sm3/HR; Act flow ACFM/L/S/Am3/S/Am3/M/Am3/HR; Std vel SFPM/Sm/s; Act vel AFPM/Am/s; Pressure In. W.C./Pa/kPa/mm W.C.
MV4Temperature Engineering UnitsTemperature unitsWrite1=F, 2=C
MV5System 1 Temperature SourceSystem 1 temperature sourceWrite1=Fixed, 2=Analog, 3=Network
MV6System 2 Temperature SourceSystem 2 temperature sourceWrite1=Fixed, 2=Analog, 3=Network
MV7System 3 Temperature SourceSystem 3 temperature sourceWrite1=Fixed, 2=Analog, 3=Network
MV8Sub System Temperature SourceSub System temperature sourceWrite1=Fixed, 2=Analog, 3=Network
MV9System 1 Process TypeSystem 1 measurement typeWrite1=Standard Flow, 2=Actual Flow, 3=Standard Velocity, 4=Actual Velocity, 5=Pressure
MV10System 2 Process TypeSystem 2 measurement typeWrite1=Standard Flow, 2=Actual Flow, 3=Standard Velocity, 4=Actual Velocity, 5=Pressure
MV11System 3 Process TypeSystem 3 measurement typeWrite1=Standard Flow, 2=Actual Flow, 3=Standard Velocity, 4=Actual Velocity, 5=Pressure
CSV1System 1 TagSystem 1 tag textRead
CSV2System 2 TagSystem 2 tag textRead
CSV3System 3 TagSystem 3 tag textRead
CSV4Sub System TagSub System tag textRead
AI21System 1 Sensor 1 FlowFlow at system 1 sensor 1Read
AI22System 1 Sensor 1 PressurePressure at system 1 sensor 1Read
MImin11System 1 Sensor 1 StatusSensor statusRead1=Normal, 2=Alarm, 3=Failure
AI23System 1 Sensor 2 FlowFlow at system 1 sensor 2Read
AI24System 1 Sensor 2 PressurePressure at system 1 sensor 2Read
MI12System 1 Sensor 2 StatusSensor statusRead1=Normal, 2=Alarm, 3=Failure
AI39Sub System Sensor 1 FlowFlow at sub system sensor 1 (example position)Read
AI40Sub System Sensor 1 PressurePressure at sub system sensor 1 (example position)Read
MI20Sub System Sensor 1 StatusSensor status (example position)Read1=Normal, 2=Alarm, 3=Failure
Object ID lookup: Paragon Controls MTSE Multi-Trans Smart Ecosystem flow / pressure station point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MTSE Multi-Trans Smart Ecosystem flow / pressure station (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Paragon Controls MTSE Multi-Trans Smart Ecosystem flow / pressure station (BACnet MS/TP)

How many BACnet points does the Paragon Controls MTSE Multi-Trans Smart Ecosystem flow / pressure station (BACnet MS/TP) have?

This list has 56 BACnet objects: 14 analog inputs, 16 analog values, 2 binary inputs, 6 binary values, 3 multi-state inputs, 11 multi-state values, 4 characterstring values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Paragon Controls MTSE Multi-Trans Smart Ecosystem flow / pressure station (BACnet MS/TP) BACnet points are writable?

37 of the 56 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Paragon Controls MTSE Multi-Trans Smart Ecosystem flow / pressure station (BACnet MS/TP) BACnet documentation?

Paragon Controls does not publish it on its own website. This list comes from MTSE Unit BACnet Protocol Implementation Conformance Statement (MTSE BACnet PIC V5.1.7), revision Rev 6, 6/14/2021, a copy hosted by BACnet International at https://www.bacnetinternational.net/catalog/manu/paragon%20controls%20inc./MTSE%20BACnet%20PIC%20V5.1.7%20BTL%20Cert.pdf. Ask Paragon Controls or its representative for the current revision.

What are the minimum BACnet points to integrate the Paragon Controls MTSE Multi-Trans Smart Ecosystem flow / pressure station (BACnet MS/TP)?

Start with AI 1 System 1 Total Flow (System 1 total flow); AI 2 System 2 Total Flow (System 2 total flow); AI 3 System 3 Total Flow (System 3 total flow); AI 4 Sub System Flow (Sub system flow); AI 5 System 1 Temperature (System 1 temperature; BMS writes it when source = Network); MI 11 System 1 Sensor 1 Status (Sensor status: 1 normal, 2 alarm, 3 failure).

Can the BMS supply sensor values to the Paragon Controls MTSE Multi-Trans Smart Ecosystem flow / pressure station (BACnet MS/TP)?

Each system's temperature can come from the BMS: set its Temperature Source multistate (MSV 5-8) to 3 (Network) and write the matching temperature AI (AI 5-8).

How do I check these points on the real MTSE Multi-Trans Smart Ecosystem flow / pressure station (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Paragon Controls BACnet points lists

Source: MTSE Unit BACnet Protocol Implementation Conformance Statement (MTSE BACnet PIC V5.1.7) · rev. Rev 6, 6/14/2021. Object names, instances and units are reproduced as published; descriptions are our own.