- MicroTransII flow / pressure transmitter-controller (BACnet MS/TP)
Airflow / pressure transmitter with controller · BACnet points list
Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP) BACnet points list
Updated 12 November 2026
The MicroTransII is a flow or pressure transmitter with a built-in loop controller, on BACnet MS/TP through an add-on communication board. Besides the measurements and alarm settings it exposes the controller setpoints, tuning, output and the system start / hold input status.
This page lists 31 BACnet objects for the Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP) — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Paragon Controls’s own free documentation, linked below.
- Manufacturer
- Paragon Controls
- Model
- MicroTransII flow / pressure transmitter-controller (BACnet MS/TP)
- Equipment
- Airflow / pressure transmitter with controller
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 31 (20 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- MicroTransII, MicroTrans II, MT2 device, Paragon MicroTrans II
Reference only, provided as-is: verify against Paragon Controls’s current documentation and the live device before use. Not official Paragon Controls information. Terms of use.
BMS integration notes: Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP)
Write the controller setpoint (AV 8 for flow, AV 7 for pressure) and read the measurement, the controller output AO 1, the system start status and the alarm status multistates. Set MSV 8 to Network to feed temperature from the BMS through AI 3.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 8 | Flow Controller Setpoint | Controller setpoint in flow mode | Write |
| AV 7 | Pressure Controller Setpoint | Controller setpoint in pressure mode | Write |
| AI 3 | Temperature | Temperature; BMS writes it when MSV 8 = Network | Write |
| BI 1 | Sys Start In Status | System start input, 1 = run | Read |
| AI 2 | Flow | Flow or velocity reading | Read |
| AI 1 | Pressure | Pressure reading | Read |
| AO 1 | Controller Output | Controller output | Read |
| MV 2 | Hi Alarm Status | High alarm, 2 = alarm | Read |
| MV 4 | Lo Alarm Status | Low alarm, 2 = alarm | Read |
Enable & remote start
Run/stop comes from the hard-wired system start input; BI 1 only reports it.
Sensors & values from the BMS
Temperature can come from the BMS: set MSV 8 Temperature Source to 3 (Network) and write AI 3.
Network setup
- MS/TP MAC address 2-127, unique on each trunk; set at the device (see the device O&M).
- Baud 9600, 19200, 38400 or 76800.
- Device instance 1,002 to 4,194,302.
- Turn the BACnet terminator switch ON only on the two end devices of the trunk.
Watch out for
- MSV 6 state meanings change with the process type (flow, velocity or pressure).
- The controller output AO 1 is read-only.
Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Pressure | Measured pressure | Per MSV 6 | Read | |
| AImin | 2 | Flow | Measured flow or velocity | Per MSV 6 | Read | |
| AImin | 3 | Temperature | Temperature in use; writable for a network value | Per MSV 7 | Write | |
| AOmin | 1 | Controller Output | Built-in controller output | Read | ||
| AV | 1 | Pressure Operating Range | Pressure span | Write | ||
| AV | 2 | Pressure Hi Alarm | High pressure alarm limit | Write | ||
| AV | 3 | Pressure Lo Alarm | Low pressure alarm limit | Write | ||
| AV | 4 | Flow Operating Range | Flow span | Write | ||
| AV | 5 | Flow Hi Alarm | High flow alarm limit | Write | ||
| AV | 6 | Flow Lo Alarm | Low flow alarm limit | Write | ||
| AVmin | 7 | Pressure Controller Setpoint | Controller setpoint, pressure mode | Write | ||
| AVmin | 8 | Flow Controller Setpoint | Controller setpoint, flow mode | Write | ||
| AV | 9 | Controller Prop Band | Controller proportional band | Write | ||
| AV | 10 | Controller Integrator Time | Controller integral time | Write | ||
| AV | 11 | Cnt. Inverse Derivative Time | Controller derivative setting | Write | ||
| AV | 12 | Economizer Value | Economizer override value | Write | ||
| AV | 13 | Hi Alarm Delay | High alarm delay | Write | ||
| AV | 14 | Lo Alarm Delay | Low alarm delay | Write | ||
| BImin | 1 | Sys Start In Status | System start input | Read | 0=Off, 1=Run | |
| BI | 2 | Sys Hold Out Status | System hold input | Read | 0=Off, 1=On | |
| MV | 1 | Hi Alarm Enable | High alarm on/off | Write | 1=Disable, 2=Enable | |
| MVmin | 2 | Hi Alarm Status | High alarm state | Read | 1=No Alarm, 2=Alarm | |
| MV | 3 | Lo Alarm Enable | Low alarm on/off | Write | 1=Disable, 2=Enable | |
| MVmin | 4 | Lo Alarm Status | Low alarm state | Read | 1=No Alarm, 2=Alarm | |
| MV | 5 | Controller Action | Controller direct or reverse | Read | 1=Direct, 2=Reverse | |
| MV | 6 | Engineering Units | Display/process units | Write | Flow: 1=CFM, 2=L/S, 3=m3/S, 4=m3/M, 5=m3/HR, 6=%; Velocity: 1=FPM, 2=m/s, 3=%; Pressure: 1=Inch W.C., 2=Pa, 3=KPa, 4=mm W.C., 5=% | |
| MV | 7 | Temperature Units | Temperature units | Write | 1=Fahrenheit, 2=Celsius | |
| MV | 8 | Temperature Source | Where the temperature comes from | Write | 1=Temp. Input, 2=Fixed Temp., 3=Network | |
| MV | 9 | Process Type | Configured as flow or pressure | Read | 1=Flow, 2=Pressure | |
| MV | 10 | Process Unit | Flow or velocity output | Read | 1=Flow, 2=Velocity | |
| MV | 11 | Flow Type | Actual or standard flow | Read | 1=Actual, 2=Standard |
No points match these filters.
Object ID lookup: Paragon Controls MicroTransII flow / pressure transmitter-controller point IDs by name
AI1PressureAI2FlowAI3TemperatureAO1Controller OutputAV1Pressure Operating RangeAV2Pressure Hi AlarmAV3Pressure Lo AlarmAV4Flow Operating RangeAV5Flow Hi AlarmAV6Flow Lo AlarmAV7Pressure Controller SetpointAV8Flow Controller SetpointAV9Controller Prop BandAV10Controller Integrator TimeAV11Cnt. Inverse Derivative TimeAV12Economizer ValueAV13Hi Alarm DelayAV14Lo Alarm DelayBI1Sys Start In StatusBI2Sys Hold Out StatusMV1Hi Alarm EnableMV2Hi Alarm StatusMV3Lo Alarm EnableMV4Lo Alarm StatusMV5Controller ActionMV6Engineering UnitsMV7Temperature UnitsMV8Temperature SourceMV9Process TypeMV10Process UnitMV11Flow Type
Integration notes
- The manual gives each object as '<object type> <number> - <label>'; the label is used here as the object name.
- Units of the process values follow the engineering-units multistate; they are not printed per object.
- MSV 6 state text depends on MSV 9 / MSV 10 (flow, velocity or pressure); all three sets are given in the states field.
- AV 7 and AV 11 labels are cut off in the printed table; the full names were read from the PDF text layer.
- Device instance range 1,002 to 4,194,302 per the manual.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTransII flow / pressure transmitter-controller (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP)
How many BACnet points does the Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP) have?
This list has 31 BACnet objects: 3 analog inputs, 1 analog output, 14 analog values, 2 binary inputs, 11 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP) BACnet points are writable?
20 of the 31 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP) BACnet documentation?
The source is BACnet Communication Operation & Maintenance Manual (MicroTransEQ, MicroTransII, SPM-3000, SPM-4000), revision Revision Level 003, published free by Paragon Controls at https://paragoncontrols.com/wp-content/uploads/2021/03/BACnet-IOM.pdf.
What are the minimum BACnet points to integrate the Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP)?
Start with AV 8 Flow Controller Setpoint (Controller setpoint in flow mode); AV 7 Pressure Controller Setpoint (Controller setpoint in pressure mode); AI 3 Temperature (Temperature; BMS writes it when MSV 8 = Network); BI 1 Sys Start In Status (System start input, 1 = run); AI 2 Flow (Flow or velocity reading); AI 1 Pressure (Pressure reading); AO 1 Controller Output (Controller output); MV 2 Hi Alarm Status (High alarm, 2 = alarm); MV 4 Lo Alarm Status (Low alarm, 2 = alarm).
How do I enable BMS control of the Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP)?
Run/stop comes from the hard-wired system start input; BI 1 only reports it.
Can the BMS supply sensor values to the Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP)?
Temperature can come from the BMS: set MSV 8 Temperature Source to 3 (Network) and write AI 3.
How do I check these points on the real MicroTransII flow / pressure transmitter-controller (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Paragon Controls BACnet points lists
- Airflow / pressure transmitter
Paragon Controls MicroTransEQ airflow / pressure transmitter (BACnet MS/TP)
Paragon Controls MicroTransEQ flow, velocity and pressure transmitters fitted with the BACnet communication board.
Also known as: MicroTransEQ, MicroTrans EQ, EQ device, Paragon MicroTransEQ - Airflow measuring station (multi-system)
Paragon Controls MTSE Multi-Trans Smart Ecosystem flow / pressure station (BACnet MS/TP)
Paragon Controls MTSE multi-sensor flow and pressure stations with up to three systems plus a sub system.
Also known as: MTSE, Multi-Trans Smart Ecosystem, Paragon MTSE - Room pressure monitor
Paragon Controls SPM-3000 Micro Guardian space pressure monitor (BACnet MS/TP)
Paragon Controls SPM-3000 (Micro Guardian) single-space pressure monitors with the BACnet communication board.
Also known as: SPM-3000, SPM3000, Micro Guardian, Paragon Micro Guardian - Room pressure dual controller
Paragon Controls SPM-4000 Dual Controller space pressure monitor (BACnet MS/TP)
Paragon Controls SPM-4000 Dual Controller two-space pressure monitors with two control loops, fitted with the BACnet communication board.
Also known as: SPM-4000 Dual Controller, SPM4000 Dual, Guardian Infinity Dual Controller - Room pressure monitor and controller
Paragon Controls SPM-4000 Guardian Infinity space pressure monitor / controller (BACnet MS/TP)
Paragon Controls SPM-4000 (Guardian Infinity) two-space pressure monitors with one control loop, fitted with the BACnet communication board.
Also known as: SPM-4000, SPM4000, Guardian Infinity, Paragon Guardian Infinity
Source: BACnet Communication Operation & Maintenance Manual (MicroTransEQ, MicroTransII, SPM-3000, SPM-4000) · rev. Revision Level 003. Object names, instances and units are reproduced as published; descriptions are our own.