Airflow / pressure transmitter with controller · BACnet points list

Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP) BACnet points list

Updated 12 November 2026

Short answer

The MicroTransII is a flow or pressure transmitter with a built-in loop controller, on BACnet MS/TP through an add-on communication board. Besides the measurements and alarm settings it exposes the controller setpoints, tuning, output and the system start / hold input status.

This page lists 31 BACnet objects for the Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP) — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Paragon Controls’s own free documentation, linked below.

Manufacturer
Paragon Controls
Model
MicroTransII flow / pressure transmitter-controller (BACnet MS/TP)
Equipment
Airflow / pressure transmitter with controller
Equipment type
Thermostats, sensors & meters
BACnet objects
31 (20 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
MicroTransII, MicroTrans II, MT2 device, Paragon MicroTrans II
Source document
BACnet Communication Operation & Maintenance Manual (MicroTransEQ, MicroTransII, SPM-3000, SPM-4000) · rev. Revision Level 003
Download CSV 31 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Paragon Controls’s current documentation and the live device before use. Not official Paragon Controls information. Terms of use.

BMS integration notes: Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP)

Integration in brief

Write the controller setpoint (AV 8 for flow, AV 7 for pressure) and read the measurement, the controller output AO 1, the system start status and the alarm status multistates. Set MSV 8 to Network to feed temperature from the BMS through AI 3.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 8Flow Controller SetpointController setpoint in flow modeWrite
AV 7Pressure Controller SetpointController setpoint in pressure modeWrite
AI 3TemperatureTemperature; BMS writes it when MSV 8 = NetworkWrite
BI 1Sys Start In StatusSystem start input, 1 = runRead
AI 2FlowFlow or velocity readingRead
AI 1PressurePressure readingRead
AO 1Controller OutputController outputRead
MV 2Hi Alarm StatusHigh alarm, 2 = alarmRead
MV 4Lo Alarm StatusLow alarm, 2 = alarmRead

Enable & remote start

Run/stop comes from the hard-wired system start input; BI 1 only reports it.

Sensors & values from the BMS

Temperature can come from the BMS: set MSV 8 Temperature Source to 3 (Network) and write AI 3.

Network setup

Watch out for

Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

31 of 31 shown
Type
BinaryMulti-state
Access
Show
Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1PressureMeasured pressurePer MSV 6Read
AImin2FlowMeasured flow or velocityPer MSV 6Read
AImin3TemperatureTemperature in use; writable for a network valuePer MSV 7Write
AOmin1Controller OutputBuilt-in controller outputRead
AV1Pressure Operating RangePressure spanWrite
AV2Pressure Hi AlarmHigh pressure alarm limitWrite
AV3Pressure Lo AlarmLow pressure alarm limitWrite
AV4Flow Operating RangeFlow spanWrite
AV5Flow Hi AlarmHigh flow alarm limitWrite
AV6Flow Lo AlarmLow flow alarm limitWrite
AVmin7Pressure Controller SetpointController setpoint, pressure modeWrite
AVmin8Flow Controller SetpointController setpoint, flow modeWrite
AV9Controller Prop BandController proportional bandWrite
AV10Controller Integrator TimeController integral timeWrite
AV11Cnt. Inverse Derivative TimeController derivative settingWrite
AV12Economizer ValueEconomizer override valueWrite
AV13Hi Alarm DelayHigh alarm delayWrite
AV14Lo Alarm DelayLow alarm delayWrite
BImin1Sys Start In StatusSystem start inputRead0=Off, 1=Run
BI2Sys Hold Out StatusSystem hold inputRead0=Off, 1=On
MV1Hi Alarm EnableHigh alarm on/offWrite1=Disable, 2=Enable
MVmin2Hi Alarm StatusHigh alarm stateRead1=No Alarm, 2=Alarm
MV3Lo Alarm EnableLow alarm on/offWrite1=Disable, 2=Enable
MVmin4Lo Alarm StatusLow alarm stateRead1=No Alarm, 2=Alarm
MV5Controller ActionController direct or reverseRead1=Direct, 2=Reverse
MV6Engineering UnitsDisplay/process unitsWriteFlow: 1=CFM, 2=L/S, 3=m3/S, 4=m3/M, 5=m3/HR, 6=%; Velocity: 1=FPM, 2=m/s, 3=%; Pressure: 1=Inch W.C., 2=Pa, 3=KPa, 4=mm W.C., 5=%
MV7Temperature UnitsTemperature unitsWrite1=Fahrenheit, 2=Celsius
MV8Temperature SourceWhere the temperature comes fromWrite1=Temp. Input, 2=Fixed Temp., 3=Network
MV9Process TypeConfigured as flow or pressureRead1=Flow, 2=Pressure
MV10Process UnitFlow or velocity outputRead1=Flow, 2=Velocity
MV11Flow TypeActual or standard flowRead1=Actual, 2=Standard
Object ID lookup: Paragon Controls MicroTransII flow / pressure transmitter-controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTransII flow / pressure transmitter-controller (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP)

How many BACnet points does the Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP) have?

This list has 31 BACnet objects: 3 analog inputs, 1 analog output, 14 analog values, 2 binary inputs, 11 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP) BACnet points are writable?

20 of the 31 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP) BACnet documentation?

The source is BACnet Communication Operation & Maintenance Manual (MicroTransEQ, MicroTransII, SPM-3000, SPM-4000), revision Revision Level 003, published free by Paragon Controls at https://paragoncontrols.com/wp-content/uploads/2021/03/BACnet-IOM.pdf.

What are the minimum BACnet points to integrate the Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP)?

Start with AV 8 Flow Controller Setpoint (Controller setpoint in flow mode); AV 7 Pressure Controller Setpoint (Controller setpoint in pressure mode); AI 3 Temperature (Temperature; BMS writes it when MSV 8 = Network); BI 1 Sys Start In Status (System start input, 1 = run); AI 2 Flow (Flow or velocity reading); AI 1 Pressure (Pressure reading); AO 1 Controller Output (Controller output); MV 2 Hi Alarm Status (High alarm, 2 = alarm); MV 4 Lo Alarm Status (Low alarm, 2 = alarm).

How do I enable BMS control of the Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP)?

Run/stop comes from the hard-wired system start input; BI 1 only reports it.

Can the BMS supply sensor values to the Paragon Controls MicroTransII flow / pressure transmitter-controller (BACnet MS/TP)?

Temperature can come from the BMS: set MSV 8 Temperature Source to 3 (Network) and write AI 3.

How do I check these points on the real MicroTransII flow / pressure transmitter-controller (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Paragon Controls BACnet points lists

Source: BACnet Communication Operation & Maintenance Manual (MicroTransEQ, MicroTransII, SPM-3000, SPM-4000) · rev. Revision Level 003. Object names, instances and units are reproduced as published; descriptions are our own.