Room pressure monitor · BACnet points list

Paragon Controls SPM-3000 Micro Guardian space pressure monitor (BACnet MS/TP) BACnet points list

Updated 12 November 2026

Short answer

The SPM-3000 Micro Guardian monitors one room's differential pressure and alarms on it. On BACnet MS/TP it gives the pressure reading, the room mode (off, positive, negative), separate alarm limits for each mode and the alarm status.

This page lists 14 BACnet objects for the Paragon Controls SPM-3000 Micro Guardian space pressure monitor (BACnet MS/TP) — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Paragon Controls’s own free documentation, linked below.

Manufacturer
Paragon Controls
Model
SPM-3000 Micro Guardian space pressure monitor (BACnet MS/TP)
Equipment
Room pressure monitor
Equipment type
Thermostats, sensors & meters
BACnet objects
14 (11 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
SPM-3000, SPM3000, Micro Guardian, Paragon Micro Guardian
Source document
BACnet Communication Operation & Maintenance Manual (MicroTransEQ, MicroTransII, SPM-3000, SPM-4000) · rev. Revision Level 003
Download CSV 14 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Paragon Controls’s current documentation and the live device before use. Not official Paragon Controls information. Terms of use.

BMS integration notes: Paragon Controls SPM-3000 Micro Guardian space pressure monitor (BACnet MS/TP)

Integration in brief

Set the room mode with MSV 1 (positive or negative) and read the pressure AI 1 and the alarm status MSV 2.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1Operating ModeRoom mode: 1 off, 2 positive, 3 negativeWrite
AI 1Process ValueRoom differential pressureRead
MV 2Alarm StatusAlarm: 1 none, 2 high, 3 lowRead

Network setup

Watch out for

Paragon Controls SPM-3000 Micro Guardian space pressure monitor (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

14 of 14 shown
Type
BinaryMulti-state
Access
Show
Paragon Controls SPM-3000 Micro Guardian space pressure monitor (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1Process ValueMeasured room pressurePer MSV 3Read
AV1Operating RangePressure spanRead
AV2Pos Lo AlarmLow alarm limit, positive modeWrite
AV3Pos Hi AlarmHigh alarm limit, positive modeWrite
AV4Neg Lo AlarmLow alarm limit, negative modeWrite
AV5Neg Hi AlarmHigh alarm limit, negative modeWrite
AV6Alarm DelayAlarm delayWrite
AV7Field PasswordFront-panel passwordWrite
AV8Process FilterReading filterWrite
AV9Decimal PointDisplay decimal placesWrite
BV1Audible Alarm EnableAudible alarm on/offWrite0=Off, 1=On
MVmin1Operating ModeRoom mode: off, positive or negativeWrite1=Off, 2=Pos, 3=Neg
MVmin2Alarm StatusAlarm stateRead1=No Alarms, 2=High, 3=Low
MV3Engineering UnitsPressure unitsWrite1="W.C., 2=Pa, 3=KPa, 4=mmW.C.
Object ID lookup: Paragon Controls SPM-3000 Micro Guardian space pressure monitor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SPM-3000 Micro Guardian space pressure monitor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Paragon Controls SPM-3000 Micro Guardian space pressure monitor (BACnet MS/TP)

How many BACnet points does the Paragon Controls SPM-3000 Micro Guardian space pressure monitor (BACnet MS/TP) have?

This list has 14 BACnet objects: 1 analog input, 9 analog values, 1 binary value, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Paragon Controls SPM-3000 Micro Guardian space pressure monitor (BACnet MS/TP) BACnet points are writable?

11 of the 14 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Paragon Controls SPM-3000 Micro Guardian space pressure monitor (BACnet MS/TP) BACnet documentation?

The source is BACnet Communication Operation & Maintenance Manual (MicroTransEQ, MicroTransII, SPM-3000, SPM-4000), revision Revision Level 003, published free by Paragon Controls at https://paragoncontrols.com/wp-content/uploads/2021/03/BACnet-IOM.pdf.

What are the minimum BACnet points to integrate the Paragon Controls SPM-3000 Micro Guardian space pressure monitor (BACnet MS/TP)?

Start with MV 1 Operating Mode (Room mode: 1 off, 2 positive, 3 negative); AI 1 Process Value (Room differential pressure); MV 2 Alarm Status (Alarm: 1 none, 2 high, 3 low).

How do I check these points on the real SPM-3000 Micro Guardian space pressure monitor (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Paragon Controls BACnet points lists

Source: BACnet Communication Operation & Maintenance Manual (MicroTransEQ, MicroTransII, SPM-3000, SPM-4000) · rev. Revision Level 003. Object names, instances and units are reproduced as published; descriptions are our own.