  4. SPM-4000 Guardian Infinity space pressure monitor / controller (BACnet MS/TP)

Room pressure monitor and controller · BACnet points list

Paragon Controls SPM-4000 Guardian Infinity space pressure monitor / controller (BACnet MS/TP) BACnet points list

Updated 12 November 2026

Short answer

The SPM-4000 Guardian Infinity watches the pressure of two spaces and runs one control loop. On BACnet MS/TP it gives both pressures, temperature, humidity and flow inputs, the air-change rate, per-space modes and alarm limits, and the controller setpoints and tuning.

This page lists 35 BACnet objects for the Paragon Controls SPM-4000 Guardian Infinity space pressure monitor / controller (BACnet MS/TP) — 23 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Paragon Controls’s own free documentation, linked below.

Manufacturer
Paragon Controls
Model
SPM-4000 Guardian Infinity space pressure monitor / controller (BACnet MS/TP)
Equipment
Room pressure monitor and controller
Equipment type
Thermostats, sensors & meters
BACnet objects
35 (23 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
SPM-4000, SPM4000, Guardian Infinity, Paragon Guardian Infinity
Source document
BACnet Communication Operation & Maintenance Manual (MicroTransEQ, MicroTransII, SPM-3000, SPM-4000) · rev. Revision Level 003
Download CSV 35 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Paragon Controls’s current documentation and the live device before use. Not official Paragon Controls information. Terms of use.

BMS integration notes: Paragon Controls SPM-4000 Guardian Infinity space pressure monitor / controller (BACnet MS/TP)

Integration in brief

Set each space's mode (MSV 1 / MSV 3) and the controller setpoint for that mode (AV 11-13). Read the space pressures, the system start status and the two alarm status multistates.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1Sp1 Operating ModeSpace 1 mode: 1 off, 2 positive, 3 negativeWrite
MV 3Sp2 Operating ModeSpace 2 mode: 1 off, 2 positive, 3 negativeWrite
AV 11Cnt Pos SetpointController setpoint in positive modeWrite
AV 12Cnt Neg SetpointController setpoint in negative modeWrite
BI 1Sys Start In StatusSystem start input, 1 = runRead
AI 1Sp1 Process ValueSpace 1 differential pressureRead
AI 2Sp2 Process ValueSpace 2 differential pressureRead
MV 2Sp1 Alarm StatusSpace 1 alarm: 1 none, 2 high, 3 lowRead
MV 4Sp2 Alarm StatusSpace 2 alarm: 1 none, 2 high, 3 lowRead

Enable & remote start

Run/stop comes from the hard-wired system start input; BI 1 only reports it.

Network setup

Watch out for

Paragon Controls SPM-4000 Guardian Infinity space pressure monitor / controller (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

35 of 35 shown
Type
Multi-state
Access
Show
Paragon Controls SPM-4000 Guardian Infinity space pressure monitor / controller (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1Sp1 Process ValueSpace 1 pressurePer MSV 5Read
AImin2Sp2 Process ValueSpace 2 pressurePer MSV 5Read
AI3Temperature InputTemperature inputPer MSV 6Read
AI4Humidity InputHumidity inputRead
AI5Flow InputFlow inputRead
AV1Sp1 Operating RangeSpace 1 pressure spanRead
AV2Sp1 Pos High AlarmSpace 1 high limit, positive modeWrite
AV3Sp1 Pos Low AlarmSpace 1 low limit, positive modeWrite
AV4Sp1 Neg High AlarmSpace 1 high limit, negative modeWrite
AV5Sp1 Neg Low AlarmSpace 1 low limit, negative modeWrite
AV6Sp2 Operating RangeSpace 2 pressure spanRead
AV7Sp2 Pos High AlarmSpace 2 high limit, positive modeWrite
AV8Sp2 Pos Low AlarmSpace 2 low limit, positive modeWrite
AV9Sp2 Neg High AlarmSpace 2 high limit, negative modeWrite
AV10Sp2 Neg Low AlarmSpace 2 low limit, negative modeWrite
AVmin11Cnt Pos SetpointController setpoint, positive modeWrite
AVmin12Cnt Neg SetpointController setpoint, negative modeWrite
AV13Cnt Off SetpointController setpoint, off modeWrite
AV14Cnt Prop BandController proportional bandWrite
AV15Cnt Integral TimeController integral timeWrite
AV16Cnt Derivative TimeController derivative timeWrite
AV17ACH ValueAir changes per hourRead
AV18Sp1 Alarm DelaySpace 1 alarm delayWrite
AV19Sp2 Alarm DelaySpace 2 alarm delayWrite
AV20Field PasswordFront-panel passwordWrite
AV21Decimal PointDisplay decimal placesWrite
BImin1Sys Start In StatusSystem start inputRead0=Off, 1=Run
BI2Sys Hold In StatusSystem hold inputRead0=Off, 1=On
BV1Audible Alarm EnableAudible alarm on/offWrite0=Off, 1=On
MVmin1Sp1 Operating ModeSpace 1 modeWrite1=Off, 2=Pos, 3=Neg
MVmin2Sp1 Alarm StatusSpace 1 alarm stateRead1=No Alarms, 2=High, 3=Low
MVmin3Sp2 Operating ModeSpace 2 modeWrite1=Off, 2=Pos, 3=Neg
MVmin4Sp2 Alarm StatusSpace 2 alarm stateRead1=No Alarms, 2=High, 3=Low
MV5Engineering UnitsPressure unitsWrite1="W.C., 2=Pa, 3=KPa, 4=mmW.C.
MV6Temp Eng UnitsTemperature unitsWrite1=F, 2=C
Object ID lookup: Paragon Controls SPM-4000 Guardian Infinity space pressure monitor / controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SPM-4000 Guardian Infinity space pressure monitor / controller (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Paragon Controls SPM-4000 Guardian Infinity space pressure monitor / controller (BACnet MS/TP)

How many BACnet points does the Paragon Controls SPM-4000 Guardian Infinity space pressure monitor / controller (BACnet MS/TP) have?

This list has 35 BACnet objects: 5 analog inputs, 21 analog values, 2 binary inputs, 1 binary value, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Paragon Controls SPM-4000 Guardian Infinity space pressure monitor / controller (BACnet MS/TP) BACnet points are writable?

23 of the 35 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Paragon Controls SPM-4000 Guardian Infinity space pressure monitor / controller (BACnet MS/TP) BACnet documentation?

The source is BACnet Communication Operation & Maintenance Manual (MicroTransEQ, MicroTransII, SPM-3000, SPM-4000), revision Revision Level 003, published free by Paragon Controls at https://paragoncontrols.com/wp-content/uploads/2021/03/BACnet-IOM.pdf.

What are the minimum BACnet points to integrate the Paragon Controls SPM-4000 Guardian Infinity space pressure monitor / controller (BACnet MS/TP)?

Start with MV 1 Sp1 Operating Mode (Space 1 mode: 1 off, 2 positive, 3 negative); MV 3 Sp2 Operating Mode (Space 2 mode: 1 off, 2 positive, 3 negative); AV 11 Cnt Pos Setpoint (Controller setpoint in positive mode); AV 12 Cnt Neg Setpoint (Controller setpoint in negative mode); BI 1 Sys Start In Status (System start input, 1 = run); AI 1 Sp1 Process Value (Space 1 differential pressure); AI 2 Sp2 Process Value (Space 2 differential pressure); MV 2 Sp1 Alarm Status (Space 1 alarm: 1 none, 2 high, 3 low); MV 4 Sp2 Alarm Status (Space 2 alarm: 1 none, 2 high, 3 low).

How do I enable BMS control of the Paragon Controls SPM-4000 Guardian Infinity space pressure monitor / controller (BACnet MS/TP)?

Run/stop comes from the hard-wired system start input; BI 1 only reports it.

How do I check these points on the real SPM-4000 Guardian Infinity space pressure monitor / controller (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Paragon Controls BACnet points lists

Source: BACnet Communication Operation & Maintenance Manual (MicroTransEQ, MicroTransII, SPM-3000, SPM-4000) · rev. Revision Level 003. Object names, instances and units are reproduced as published; descriptions are our own.