  3. Modine
  4. Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403)

Direct-fired make-up air unit controller · BACnet points list

Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403) BACnet points list

Updated 6 November 2026

Short answer

These Modine direct-fired make-up air units use a Distech ECB-403 programmable controller that joins a BACnet MS/TP trunk. The BMS can turn the unit fan on, off or auto, write occupied and unoccupied heat and cool setpoints, set the building pressure setpoint and economizer commands, and override space temperature, building pressure and occupancy with network values. Alarms (dirty filter, low temperature, sensor faults, burner lockout, motor not responding) are multistate values.

This page lists 39 BACnet objects for the Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403) — 26 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Modine’s own free documentation, linked below.

Manufacturer
Modine
Model
Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403)
Equipment
Direct-fired make-up air unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
39 (26 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
364000 + MAC address (e.g. MAC 25 = 364025)
Also known as
7-514, 7-514.1, 5H0880010000, MCV, MVV, DCV, DVV, ECB-403, ECL-403, Distech ECB-403, Allure EC Smart-Vue
Source document
Programmable Controller User Manual - Direct Fired Makeup Air Units, models MCV/MVV, DCV/DVV (Distech Controls) · 7-514.1 · rev. 2020-04
Download CSV 39 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Modine’s current documentation and the live device before use. Not official Modine information. Terms of use.

BMS integration notes: Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403)

Integration in brief

Set the MAC address on the controller DIP switches; the device instance follows as 364000 + MAC and the baud rate is auto-detected. Start and stop the unit with network_FanCommand (AV 103), write the occupied heat setpoint (AV 102) and, if fitted, the building pressure setpoint. Monitor discharge and space temperature, the heat command and the alarm multistates.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 103network_FanCommandUnit fan command: 0 = off, 1 = on, 2 = autoWrite
AV 134network_OccupancyOccupancy override, 0 = occ, 1 = unocc; null = scheduleWrite
AV 102network_OccHeatSetPointOccupied heating setpoint, 55-90 °FWrite
AV 107network_BuildingPressSetPointBuilding pressure setpoint, -0.1 to 0.1 in. w.c.Write
AV 54DischargeTemperatureDischarge air temperatureRead
AV 51SpaceTemperatureSpace temperatureRead
AV 57HeatCommandBurner heat output, %Read
MV 37BurnerLockoutAlarmBurner lockout alarmRead
MV 39MotorNotRespondingAlarmSupply fan motor not respondingRead
MV 32Low_TempAlarmLow discharge temperature alarmRead

Enable & remote start

The unit runs when enabled by the BMS through network_FanCommand (AV 103), by a contact closure on digital input DI-5, or by its internal schedule. network_Occupancy (AV 134) overrides schedule occupancy; write null to give control back.

Sensors & values from the BMS

network_SpaceTemperature (AV 132) and network_BuildingPressure (AV 133) replace the local sensor readings while written; write null to return to the local sensors.

Network setup

Watch out for

Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

39 of 39 shown
Type
AnalogBinaryMulti-state
Access
Show
Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403) BACnet Points List
DescriptionStates
AVmin51SpaceTemperatureCurrent Space Temperature°FRead
AV52OutsideTemperatureCurrent Outside Temperature°FRead
AVmin54DischargeTemperatureCurrent Discharge Temperature°FRead
AV55BuildingPressureCurrent Building Pressurein. w.c.Read
AV56EconomizerCommandCurrent Economizer Command%Read
AVmin57HeatCommandCurrent Heat Command%Read
AVmin102network_OccHeatSetPointOccupied Heat Set Point [55 - 90°F]°FWrite
AVmin103network_FanCommandUnit Fan Command [0-Off/1-On/2-Auto]Write
AV104network_UnoccHeatSetPointUnoccupied Heat Set Point [55 - 90°F]°FWrite
AV105network_OccCoolSetPointOccupied Cool Set Point [55 - 90°F]°FWrite
AV106network_UnoccCoolSetPointUnoccupied Cool Set Point [55 - 90°F]°FWrite
AVmin107network_BuildingPressSetPointBuilding Pressure Set Point [-0.1 - 0.1 in/wc]in. w.c.Write
AV108network_EconomizerOverrideEconomizer Override Command [0% - 100% / null for auto]%Write
AV109network_ManualEconPercentManual Economizer Command [0% - 100% / not available with Building Pressure Option]%Write
AV110network_TwoSpeedEconTwo Speed Economizer Command [0-Low/1-High]Write
AV111network_HeatCoolModeHeat Cool Mode [0-Air/1-Heat/2-Cool] (only available with cooling)Write
AV112network_HeatVentModeHeat Vent Mode [0-Vent/1-Heat] (not available with cooling option)Write
AV113network_HeatLockoutHeat Lockout Set Point [default 65°F]°FWrite
AV114network_CoolLockoutCooling Lockout Set Point [default 75°F]°FWrite
AV115network_LowTempLimitLow Temp Alarm Set Point [default 40°F]°FWrite
AV116network_LowTempTimeLow Temp Alarm Delay Time [default 5 minutes]minutesWrite
AV118network_MinimumDischargeMinimum Discharge Temp [default 55°F]°FWrite
AV119network_MaximumDischargeMaximum Discharge Temp [default 90°F]°FWrite
AV122network_LowEconomizerLow Economizer Set Point [default 0%]%Write
AV123network_HighEconomizerHigh Economizer Set Point [default 100%]%Write
AV131network_BurnerResetBurner Reset Command [ON/_ON_ Toggle]Write
AV132network_SpaceTemperatureNetwork Space Temperature [overrides local space temperature - use ‘null’ value for automatic unit control]°FWrite
AV133network_BuildingPressureNetwork Building Pressure [overrides local building pressure - use ‘null’ value for automatic unit control]in. w.c.Write
AVmin134network_OccupancyNetwork Occupancy Command [overrides schedule occupancy - use ‘null’ value for automatic unit control]Write0 = Occupied / 1 = Unoccupied
BV51network_ControlTypeUnit Control Type [0 = Discharge / 1 = Space]Write0=Discharge, 1=Space
BV52network_CycleOccupiedCycle To Space Temp when Occupied [0 = No / 1 = Yes]Write0=No, 1=Yes
BV53network_CycleUnoccupiedCycle to Space Temp when Unoccupied [0 - No / 1 = Yes]Write0=No, 1=Yes
MV31DirtyFilterAlarmDirty Filter Alarm (enumeration Filters)Read
MVmin32Low_TempAlarmLow Temp AlarmReadAlarm / Normal
MV33DischargeSensorAlarmDischarge Sensor Alarm (enumeration SensorReliability)Read
MV34SpaceSensorAlarmSpace Sensor Alarm (enumeration SensorReliability)Read
MV35OutsideSensorAlarmOutside Sensor Alarm (enumeration SensorReliability)Read
MVmin37BurnerLockoutAlarmBurner Lockout AlarmReadAlarm / Normal
MVmin39MotorNotRespondingAlarmMotor Not Responding AlarmReadAlarm / Normal
Object ID lookup: Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403)

How many BACnet points does the Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403) have?

This list has 39 BACnet objects: 29 analog values, 3 binary values, 7 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403) BACnet points are writable?

26 of the 39 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403) BACnet documentation?

The source is Programmable Controller User Manual - Direct Fired Makeup Air Units, models MCV/MVV, DCV/DVV (Distech Controls) (7-514.1), revision 2020-04, published free by Modine at https://modine.worksmartsuite.com/PORTAL/io_modules/IOGETIMAGE.php?type=stream&filename=7-514.pdf.

What are the minimum BACnet points to integrate the Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403)?

Start with AV 103 network_FanCommand (Unit fan command: 0 = off, 1 = on, 2 = auto); AV 134 network_Occupancy (Occupancy override, 0 = occ, 1 = unocc; null = schedule); AV 102 network_OccHeatSetPoint (Occupied heating setpoint, 55-90 °F); AV 107 network_BuildingPressSetPoint (Building pressure setpoint, -0.1 to 0.1 in. w.c); AV 54 DischargeTemperature (Discharge air temperature); AV 51 SpaceTemperature (Space temperature); AV 57 HeatCommand (Burner heat output, %); MV 37 BurnerLockoutAlarm (Burner lockout alarm); MV 39 MotorNotRespondingAlarm (Supply fan motor not responding); MV 32 Low_TempAlarm (Low discharge temperature alarm).

How do I enable BMS control of the Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403)?

The unit runs when enabled by the BMS through network_FanCommand (AV 103), by a contact closure on digital input DI-5, or by its internal schedule. network_Occupancy (AV 134) overrides schedule occupancy; write null to give control back.

Can the BMS supply sensor values to the Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403)?

network_SpaceTemperature (AV 132) and network_BuildingPressure (AV 133) replace the local sensor readings while written; write null to return to the local sensors.

How do I check these points on the real Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Modine BACnet points lists

Source: Programmable Controller User Manual - Direct Fired Makeup Air Units, models MCV/MVV, DCV/DVV (Distech Controls) · 7-514.1 · rev. 2020-04. Object names, instances and units are reproduced as published; descriptions are our own.