Direct-fired make-up air unit controller · BACnet points list
Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403) BACnet points list
Updated 6 November 2026
These Modine direct-fired make-up air units use a Distech ECB-403 programmable controller that joins a BACnet MS/TP trunk. The BMS can turn the unit fan on, off or auto, write occupied and unoccupied heat and cool setpoints, set the building pressure setpoint and economizer commands, and override space temperature, building pressure and occupancy with network values. Alarms (dirty filter, low temperature, sensor faults, burner lockout, motor not responding) are multistate values.
This page lists 39 BACnet objects for the Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403) — 26 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Modine’s own free documentation, linked below.
- Manufacturer
- Modine
- Model
- Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403)
- Equipment
- Direct-fired make-up air unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 39 (26 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 364000 + MAC address (e.g. MAC 25 = 364025)
- Also known as
- 7-514, 7-514.1, 5H0880010000, MCV, MVV, DCV, DVV, ECB-403, ECL-403, Distech ECB-403, Allure EC Smart-Vue
Reference only, provided as-is: verify against Modine’s current documentation and the live device before use. Not official Modine information. Terms of use.
BMS integration notes: Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403)
Set the MAC address on the controller DIP switches; the device instance follows as 364000 + MAC and the baud rate is auto-detected. Start and stop the unit with network_FanCommand (AV 103), write the occupied heat setpoint (AV 102) and, if fitted, the building pressure setpoint. Monitor discharge and space temperature, the heat command and the alarm multistates.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 103 | network_FanCommand | Unit fan command: 0 = off, 1 = on, 2 = auto | Write |
| AV 134 | network_Occupancy | Occupancy override, 0 = occ, 1 = unocc; null = schedule | Write |
| AV 102 | network_OccHeatSetPoint | Occupied heating setpoint, 55-90 °F | Write |
| AV 107 | network_BuildingPressSetPoint | Building pressure setpoint, -0.1 to 0.1 in. w.c. | Write |
| AV 54 | DischargeTemperature | Discharge air temperature | Read |
| AV 51 | SpaceTemperature | Space temperature | Read |
| AV 57 | HeatCommand | Burner heat output, % | Read |
| MV 37 | BurnerLockoutAlarm | Burner lockout alarm | Read |
| MV 39 | MotorNotRespondingAlarm | Supply fan motor not responding | Read |
| MV 32 | Low_TempAlarm | Low discharge temperature alarm | Read |
Enable & remote start
The unit runs when enabled by the BMS through network_FanCommand (AV 103), by a contact closure on digital input DI-5, or by its internal schedule. network_Occupancy (AV 134) overrides schedule occupancy; write null to give control back.
Sensors & values from the BMS
network_SpaceTemperature (AV 132) and network_BuildingPressure (AV 133) replace the local sensor readings while written; write null to return to the local sensors.
Network setup
- MAC address is set in binary on the 8 controller DIP switches (switch 1 = LSB); each unit ships with a unique MAC.
- Device instance = 364 x 1000 + MAC; change the MAC to clear a duplicate instance.
- Baud rate is auto-detected after a power cycle.
- The manual recommends starting MAC addresses at 3.
Watch out for
- The override points stay in force until the BMS writes null; a left-over value freezes the reading.
- network_ManualEconPercent does nothing on units with the building pressure option.
- Cooling points only apply to units built with cooling.
- A low temperature shutdown is reset by setting the fan command to off and then back on.
Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 51 | SpaceTemperature | Current Space Temperature | °F | Read | |
| AV | 52 | OutsideTemperature | Current Outside Temperature | °F | Read | |
| AVmin | 54 | DischargeTemperature | Current Discharge Temperature | °F | Read | |
| AV | 55 | BuildingPressure | Current Building Pressure | in. w.c. | Read | |
| AV | 56 | EconomizerCommand | Current Economizer Command | % | Read | |
| AVmin | 57 | HeatCommand | Current Heat Command | % | Read | |
| AVmin | 102 | network_OccHeatSetPoint | Occupied Heat Set Point [55 - 90°F] | °F | Write | |
| AVmin | 103 | network_FanCommand | Unit Fan Command [0-Off/1-On/2-Auto] | Write | ||
| AV | 104 | network_UnoccHeatSetPoint | Unoccupied Heat Set Point [55 - 90°F] | °F | Write | |
| AV | 105 | network_OccCoolSetPoint | Occupied Cool Set Point [55 - 90°F] | °F | Write | |
| AV | 106 | network_UnoccCoolSetPoint | Unoccupied Cool Set Point [55 - 90°F] | °F | Write | |
| AVmin | 107 | network_BuildingPressSetPoint | Building Pressure Set Point [-0.1 - 0.1 in/wc] | in. w.c. | Write | |
| AV | 108 | network_EconomizerOverride | Economizer Override Command [0% - 100% / null for auto] | % | Write | |
| AV | 109 | network_ManualEconPercent | Manual Economizer Command [0% - 100% / not available with Building Pressure Option] | % | Write | |
| AV | 110 | network_TwoSpeedEcon | Two Speed Economizer Command [0-Low/1-High] | Write | ||
| AV | 111 | network_HeatCoolMode | Heat Cool Mode [0-Air/1-Heat/2-Cool] (only available with cooling) | Write | ||
| AV | 112 | network_HeatVentMode | Heat Vent Mode [0-Vent/1-Heat] (not available with cooling option) | Write | ||
| AV | 113 | network_HeatLockout | Heat Lockout Set Point [default 65°F] | °F | Write | |
| AV | 114 | network_CoolLockout | Cooling Lockout Set Point [default 75°F] | °F | Write | |
| AV | 115 | network_LowTempLimit | Low Temp Alarm Set Point [default 40°F] | °F | Write | |
| AV | 116 | network_LowTempTime | Low Temp Alarm Delay Time [default 5 minutes] | minutes | Write | |
| AV | 118 | network_MinimumDischarge | Minimum Discharge Temp [default 55°F] | °F | Write | |
| AV | 119 | network_MaximumDischarge | Maximum Discharge Temp [default 90°F] | °F | Write | |
| AV | 122 | network_LowEconomizer | Low Economizer Set Point [default 0%] | % | Write | |
| AV | 123 | network_HighEconomizer | High Economizer Set Point [default 100%] | % | Write | |
| AV | 131 | network_BurnerReset | Burner Reset Command [ON/_ON_ Toggle] | Write | ||
| AV | 132 | network_SpaceTemperature | Network Space Temperature [overrides local space temperature - use ‘null’ value for automatic unit control] | °F | Write | |
| AV | 133 | network_BuildingPressure | Network Building Pressure [overrides local building pressure - use ‘null’ value for automatic unit control] | in. w.c. | Write | |
| AVmin | 134 | network_Occupancy | Network Occupancy Command [overrides schedule occupancy - use ‘null’ value for automatic unit control] | Write | 0 = Occupied / 1 = Unoccupied | |
| BV | 51 | network_ControlType | Unit Control Type [0 = Discharge / 1 = Space] | Write | 0=Discharge, 1=Space | |
| BV | 52 | network_CycleOccupied | Cycle To Space Temp when Occupied [0 = No / 1 = Yes] | Write | 0=No, 1=Yes | |
| BV | 53 | network_CycleUnoccupied | Cycle to Space Temp when Unoccupied [0 - No / 1 = Yes] | Write | 0=No, 1=Yes | |
| MV | 31 | DirtyFilterAlarm | Dirty Filter Alarm (enumeration Filters) | Read | ||
| MVmin | 32 | Low_TempAlarm | Low Temp Alarm | Read | Alarm / Normal | |
| MV | 33 | DischargeSensorAlarm | Discharge Sensor Alarm (enumeration SensorReliability) | Read | ||
| MV | 34 | SpaceSensorAlarm | Space Sensor Alarm (enumeration SensorReliability) | Read | ||
| MV | 35 | OutsideSensorAlarm | Outside Sensor Alarm (enumeration SensorReliability) | Read | ||
| MVmin | 37 | BurnerLockoutAlarm | Burner Lockout Alarm | Read | Alarm / Normal | |
| MVmin | 39 | MotorNotRespondingAlarm | Motor Not Responding Alarm | Read | Alarm / Normal |
No points match these filters.
Object ID lookup: Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV point IDs by name
AV51SpaceTemperatureAV52OutsideTemperatureAV54DischargeTemperatureAV55BuildingPressureAV56EconomizerCommandAV57HeatCommandAV102network_OccHeatSetPointAV103network_FanCommandAV104network_UnoccHeatSetPointAV105network_OccCoolSetPointAV106network_UnoccCoolSetPointAV107network_BuildingPressSetPointAV108network_EconomizerOverrideAV109network_ManualEconPercentAV110network_TwoSpeedEconAV111network_HeatCoolModeAV112network_HeatVentModeAV113network_HeatLockoutAV114network_CoolLockoutAV115network_LowTempLimitAV116network_LowTempTimeAV118network_MinimumDischargeAV119network_MaximumDischargeAV122network_LowEconomizerAV123network_HighEconomizerAV131network_BurnerResetAV132network_SpaceTemperatureAV133network_BuildingPressureAV134network_OccupancyBV51network_ControlTypeBV52network_CycleOccupiedBV53network_CycleUnoccupiedMV31DirtyFilterAlarmMV32Low_TempAlarmMV33DischargeSensorAlarmMV34SpaceSensorAlarmMV35OutsideSensorAlarmMV37BurnerLockoutAlarmMV39MotorNotRespondingAlarm
Integration notes
- The manual calls Table 11.1 'typical' system variables; units with LonTalk (model digit 14 = L) need factory guidance.
- Cooling-related points (cool setpoints, HeatCoolMode, CoolLockout) only apply to units with the cooling option; HeatVentMode applies to units without it.
- network_SpaceTemperature, network_BuildingPressure and network_Occupancy override local values; write null (relinquish) to return to automatic control.
- network_ManualEconPercent is not available with the building pressure option.
- The enumeration texts for the Filters and SensorReliability state sets are not printed in the BACnet table; the display menu shows the sensor alarms as no-fault / open / short.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403)
How many BACnet points does the Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403) have?
This list has 39 BACnet objects: 29 analog values, 3 binary values, 7 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403) BACnet points are writable?
26 of the 39 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403) BACnet documentation?
The source is Programmable Controller User Manual - Direct Fired Makeup Air Units, models MCV/MVV, DCV/DVV (Distech Controls) (7-514.1), revision 2020-04, published free by Modine at https://modine.worksmartsuite.com/PORTAL/io_modules/IOGETIMAGE.php?type=stream&filename=7-514.pdf.
What are the minimum BACnet points to integrate the Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403)?
Start with AV 103 network_FanCommand (Unit fan command: 0 = off, 1 = on, 2 = auto); AV 134 network_Occupancy (Occupancy override, 0 = occ, 1 = unocc; null = schedule); AV 102 network_OccHeatSetPoint (Occupied heating setpoint, 55-90 °F); AV 107 network_BuildingPressSetPoint (Building pressure setpoint, -0.1 to 0.1 in. w.c); AV 54 DischargeTemperature (Discharge air temperature); AV 51 SpaceTemperature (Space temperature); AV 57 HeatCommand (Burner heat output, %); MV 37 BurnerLockoutAlarm (Burner lockout alarm); MV 39 MotorNotRespondingAlarm (Supply fan motor not responding); MV 32 Low_TempAlarm (Low discharge temperature alarm).
How do I enable BMS control of the Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403)?
The unit runs when enabled by the BMS through network_FanCommand (AV 103), by a contact closure on digital input DI-5, or by its internal schedule. network_Occupancy (AV 134) overrides schedule occupancy; write null to give control back.
Can the BMS supply sensor values to the Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403)?
network_SpaceTemperature (AV 132) and network_BuildingPressure (AV 133) replace the local sensor readings while written; write null to return to the local sensors.
How do I check these points on the real Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Modine BACnet points lists
- Packaged ventilation unit / make-up air controller (DOAS, energy recovery)
Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3)
Modine Atherion MPR commercial packaged ventilation units and ERM energy recovery modules running Modine Control System program series 3 and 4.
Also known as: MCP15-525, MCP15-525.0, 5H0837230000, Atherion, MPR, ERM, Modine Control System, Carel pCO3 - Gas-fired unit heater BMS board
Modine BMS Board for Gas-Fired Unit Heaters (PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP)
Modine PTP/BTP, PTC/BTC, PTS/BTS and PDP/BDP gas-fired unit heaters fitted with the factory BMS board.
Also known as: 6-520, 6-520.3, 5H0827570000, PTP, BTP, PTC, BTC, PTS, BTS, PDP, BDP, BAC_HBB2, Modine BMS board - Chilled water ceiling cassette (fan coil) controller
Modine Chilled Water Ceiling Cassette Controller, Models SCW / CCW
Modine SCW and CCW ductless chilled water ceiling cassettes, model digit 7 = C, with the factory microprocessor controller.
Also known as: 8-510, 8-510.0, 5H1067400000, SCW, CCW, Modine cassette controller - Self-contained vertical unit ventilator controller (classroom)
Modine ClassMate / SchoolMate Vertical Unit Ventilators (Modine Controls System, pCOOEM+)
Modine ClassMate (CMD/CMP/CMS) and SchoolMate (SMG/SMW) vertical classroom units running Modine Controls System program series 1.
Also known as: AIR74-525, AIR74-525.1, 5H1046210000, ClassMate, SchoolMate, CMD, CMP, CMS, SMG, SMW, Carel pCOOEM+ - Indirect gas-fired heating and make-up air unit controller
Modine Indirect Gas-Fired Heating & Make-Up Air, Series D/H/I/O (Modine Controls System, pCOOEM+)
Modine indirect gas-fired heating and make-up air units, model series D, H, I and O, with the Modine Controls System (Carel pCOOEM+ medium controller).
Also known as: 74-510, 74-510.1, 5H0880420000, Modine Controls System, Carel pCOOEM+, Series D, Series H, Series I, Series O
Source: Programmable Controller User Manual - Direct Fired Makeup Air Units, models MCV/MVV, DCV/DVV (Distech Controls) · 7-514.1 · rev. 2020-04. Object names, instances and units are reproduced as published; descriptions are our own.