Gas-fired unit heater BMS board · BACnet points list

Modine BMS Board for Gas-Fired Unit Heaters (PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP) BACnet points list

Updated 28 October 2026

Short answer

Modine's BMS board for gas-fired unit heaters sits beside the ignition control and gives the heater a BACnet MS/TP (or Modbus RTU) connection on RS-485. From the BMS you can turn the heater on and off, switch it between winter heating and summer fan-only, and adjust the heating, fan-only and energy-saver setpoints and bands. It reports the room and intake temperatures, thermostat calls, relay states and four specific alarms plus a general alarm. Setpoints only apply when the board runs on its own room sensor rather than a thermostat.

This page lists 27 BACnet objects for the Modine BMS Board for Gas-Fired Unit Heaters (PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Modine’s own free documentation, linked below.

Manufacturer
Modine
Model
BMS Board for Gas-Fired Unit Heaters (PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP)
Equipment
Gas-fired unit heater BMS board
Equipment type
Other equipment
BACnet objects
27 (10 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
315000 + MAC address (e.g. 315001)
Also known as
6-520, 6-520.3, 5H0827570000, PTP, BTP, PTC, BTC, PTS, BTS, PDP, BDP, BAC_HBB2, Modine BMS board
Source document
BMS Control System Manual - Models PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP · 6-520.3 · rev. 2022-06
Download CSV 27 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Modine BMS Board for Gas-Fired Unit Heaters (PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP)

Integration in brief

Set the board's MAC address with the DIP switches, leave SW4.8 on for BACnet MS/TP, and use Superv_OnOff (BV 0) to enable or disable the heater. Use Summer_winter (BV 9) for fan-only operation. If the board runs on its own room sensor, write the heating setpoint (AV 0). Monitor the fan and gas valve relays, the room temperature and the general alarm (BO 3).

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0Superv_OnOffHeater enable; 0 = off regardless of callsWrite
BV 9Summer_winter0 = winter heating, 1 = summer fan-onlyWrite
AV 0heat_setpt_BMSHeating setpoint (sensor control only)Write
BO 0Supply_fanFan relay status (read-only)Read
BO 1Gas_ht1Low or single stage gas valve relay onRead
AI 3ra_temp_BMSRoom temperature (sensor control)Read
BO 3alarmGeneral alarmRead

Enable & remote start

BV 0 Superv_OnOff (default 1) lets the heater run; when the BMS writes 0 the unit won't energize any output regardless of sensor or thermostat calls. BV 9 Summer_winter = 1 puts the unit in summer (fan-only) mode; 0 (default) is winter heating.

Heartbeat & communication loss

BV 1 heartbeat is listed as a read-only BMS communication heartbeat; the manual gives no timeout or fallback behaviour.

Network setup

Watch out for

Modine BMS Board for Gas-Fired Unit Heaters (PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

27 of 27 shown
Type
Access
Show
Modine BMS Board for Gas-Fired Unit Heaters (PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP) BACnet Points List
DescriptionStates
AImin3ra_temp_BMSRoom (control) temperature, -50 to 200 °F°FRead
AI4intake_air_temp_BMSAir temperature at the unit, -50 to 200 °F°FRead
AVmin0heat_setpt_BMSHeating setpoint; default 70 °F°FWrite
AV1fan_setpt_BMSCooling / fan-only setpoint; default 75 °F°FWrite
AV2Saver_setpt_BMSEnergy saver mode setpoint, 60-80 °F; default 80 °F°FWrite
AV3setpoint_bandHeating/cooling setpoint deadband, 0-4 °F; default 1 °F°FWrite
AV5saver_bandEnergy saver deadband, 0-6 °F; default 3 °F°FWrite
AV10BacnetDeviceInstanceNumberBACnet device ID; default 315000 + MACWrite
BOmin0Supply_fanFan relayRead1=On, 0=Off
BOmin1Gas_ht1Low or single stage gas valve relayRead1=On, 0=Off
BO2Gas_ht2High stage gas valve relayRead1=On, 0=Off
BOmin3alarmGeneral alarmRead1=On, 0=Off
BO12din_supply_fanThermostat G (fan) callRead1=On, 0=Off
BO13din_heat1Thermostat W/W1 call (low or single stage)Read1=On, 0=Off
BO14din_heat2Thermostat W2 call (high stage)Read1=On, 0=Off
BO15Valve_statusGas valve statusRead1=On, 0=Off
BO16Pressure_Switch_statusPowered exhauster pressure switch statusRead1=On, 0=Off
BO17Highlimit_FRO_statusTemperature limit or flame rollout statusRead1=On, 0=Off
BVmin0Superv_OnOffSupervisor on/off control; default 1Write1=On, 0=Off
BV1heartbeatBMS communication heartbeatRead1=On, 0=Off
BV5al_BrokenPrbTempTemperature sensor failure alarmRead1=On, 0=Off
BV6al_highlimit_FRO_alarmTemperature limit or flame rollout alarmRead1=On, 0=Off
BV7al_pressure_switchPowered exhauster pressure switch alarmRead1=On, 0=Off
BV8al_valve_ignition_alarmGas valve ignition alarmRead1=On, 0=Off
BVmin9Summer_winterSummer/winter mode; default 0 (winter)Write1=Summer (fan only), 0=Winter (heating)
BV11RestoreDefaultRestores all values to default; resets to 0Write1=On, 0=Off
BV12C_F_ScaleTemperature units settingWrite1=°C, 0=°F

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BMS Board for Gas-Fired Unit Heaters (PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Modine BMS Board for Gas-Fired Unit Heaters (PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP)

How many BACnet points does the Modine BMS Board for Gas-Fired Unit Heaters (PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP) have?

This list has 27 BACnet objects: 2 analog inputs, 6 analog values, 10 binary outputs, 9 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Modine BMS Board for Gas-Fired Unit Heaters (PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP) BACnet points are writable?

10 of the 27 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Modine BMS Board for Gas-Fired Unit Heaters (PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP) BACnet documentation?

The source is BMS Control System Manual - Models PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP (6-520.3), revision 2022-06, published free by Modine at https://modine.worksmartsuite.com/PORTAL/io_modules/IOGETIMAGE.php?type=stream&filename=6-520.pdf.

What are the minimum BACnet points to integrate the Modine BMS Board for Gas-Fired Unit Heaters (PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP)?

Start with BV 0 Superv_OnOff (Heater enable; 0 = off regardless of calls); BV 9 Summer_winter (0 = winter heating, 1 = summer fan-only); AV 0 heat_setpt_BMS (Heating setpoint (sensor control only)); BO 0 Supply_fan (Fan relay status (read-only)); BO 1 Gas_ht1 (Low or single stage gas valve relay on); AI 3 ra_temp_BMS (Room temperature (sensor control)); BO 3 alarm (General alarm).

How do I enable BMS control of the Modine BMS Board for Gas-Fired Unit Heaters (PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP)?

BV 0 Superv_OnOff (default 1) lets the heater run; when the BMS writes 0 the unit won't energize any output regardless of sensor or thermostat calls. BV 9 Summer_winter = 1 puts the unit in summer (fan-only) mode; 0 (default) is winter heating.

Does the Modine BMS Board for Gas-Fired Unit Heaters (PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP) need a BACnet heartbeat or have a communication timeout?

BV 1 heartbeat is listed as a read-only BMS communication heartbeat; the manual gives no timeout or fallback behaviour.

How do I check these points on the real BMS Board for Gas-Fired Unit Heaters (PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: BMS Control System Manual - Models PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP · 6-520.3 · rev. 2022-06. Object names, instances and units are reproduced as published; descriptions are our own.