Chilled water ceiling cassette (fan coil) controller · BACnet points list

Modine Chilled Water Ceiling Cassette Controller, Models SCW / CCW BACnet points list

Updated 6 November 2026

Short answer

The cassette's controller has an RS-485 port that talks native BACnet MS/TP (or Modbus RTU, chosen with DIP switch SW3.8). From the BMS you can switch the unit on and off, set mode, fan speed and cooling and heating setpoints, drive occupancy and lock out the local remote or touchscreen. Every tuning parameter (PID gains, fan delays, valve bands, fan speed percentages, freeze protection) is also exposed, along with the sensors, the valve and fan outputs and the relay outputs.

This page lists 105 BACnet objects for the Modine Chilled Water Ceiling Cassette Controller, Models SCW / CCW — 93 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Modine’s own free documentation, linked below.

Manufacturer
Modine
Model
Chilled Water Ceiling Cassette Controller, Models SCW / CCW
Equipment
Chilled water ceiling cassette (fan coil) controller
Equipment type
VAV boxes & fan coils
BACnet objects
105 (93 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
315000 + MAC address (DIP switches SW1.1-SW1.6)
Also known as
8-510, 8-510.0, 5H1067400000, SCW, CCW, Modine cassette controller
Source document
Microprocessor Controls Manual for Chilled Water Cassettes, Models SCW & CCW (Model Digit 7 = C) · 8-510.0 · rev. 2026-06
Download CSV 105 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Modine’s current documentation and the live device before use. Not official Modine information. Terms of use.

BMS integration notes: Modine Chilled Water Ceiling Cassette Controller, Models SCW / CCW

Integration in brief

Leave SW3.8 on for BACnet MS/TP, give each cassette a unique MAC (0-63) on SW1; the device ID is 315000 + MAC. Switch the unit with BV 0 OnOff, set Mode (AV 4), FanSpeed (AV 6) and the cooling and heating setpoints, and use BV 16 for network occupancy. Read the effective setpoint, return air temperature, effective mode and fan speed, and DI1 for the alarm relay.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0OnOffUnit on/off command (1 = on)Write
BV 16UnoccupiedByNetworkNetwork occupancy: 1 = unoccupiedWrite
AV 4ModeMode: 0 fan, 1 cool, 2 heat, 3 autoWrite
AV 6FanSpeedFan speed: 0 auto, 1 low, 2 medium, 3 highWrite
AV 0SetPoint_SetPointCoolCooling setpoint, 41-95 °FWrite
AV 1SetPointHeatHeating setpoint, 41-95 °FWrite
AV 5ModeEffectiveActive mode (4 = off)Read
AV 3ReturnAirSensorEffectiveControl (return air) temperatureRead
AV 2SetPointEffectiveActive setpointRead
BI 0DI_1Alarm input: 1 = fault, all outputs offRead

Enable & remote start

BV 0 OnOff switches the controller on or off (default off) from the BMS, the remote or the touchscreen. With an occupancy function set (AV 14), BV 16 UnoccupiedByNetwork = 1 puts the space unoccupied; it returns to occupied only when DI2 is open and BV 16 is 0. BV 47 disables the DI2 occupancy input so the BMS has sole control.

Network setup

Watch out for

Modine Chilled Water Ceiling Cassette Controller, Models SCW / CCW BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

105 of 105 shown
Type
Access
Show
Modine Chilled Water Ceiling Cassette Controller, Models SCW / CCW BACnet Points List
DescriptionStates
AI0T1_SensorRange 32...104°F (0...40°C)°FWrite
AI1T2_SensorRange -4...212°F (-20...100°C)°FWrite
AI2T3_SensorRange -4...212°F (-20...100°C)°FWrite
AO0AO_Cool (cool/heat valve)Range 0...100%%Write
AO1AO_HeatRange 0...100%%Write
AO2AO_FanRange 0...100%%Write
AVmin0SetPoint_SetPointCoolRange 41...95°F (5...35°C); default 73°F (23°C)°FWrite
AVmin1SetPointHeatRange 41...95°F (5...35°C); default 72°F (22°C)°FWrite
AVmin2SetPointEffectiveRange 41...95°F (5...35°C)°FRead
AVmin3ReturnAirSensorEffectiveRange 32...212°F (0...100°C)°FRead
AVmin4ModeDefault 3-AutoWrite0-Fan only, 1-Cool,2-Heat, 3-Auto, 6-emergency mode from IRP.
AVmin5ModeEffectiveRead0-Fan only, 1-Cool, 2-Heat, 4-Off, 5-None mode** (2-Pipe)
AVmin6FanSpeedDefault 0-AutoWrite0-Auto, 1-Low, 2-Medium, 3-High
AV7FanEffectiveRead0-Auto, 1-Low, 2-Medium, 3-High, 4-Off
AV8ReturnAirSensorCalibrationRange -9...9°F (-5...5°C); default 0°F (0°C)°FWrite
AV9SetPointLimitCoolRange 41...95°F (5...35°C); default 50°F (10°C)°FWrite
AV10SetPointLimitHeatRange 41...95°F (5...35°C); default 86°F (30°C)°FWrite
AV11EconomySetPointInCoolRange 41...95°F (5...35°C); default 86°F (30°C)°FWrite
AV12EconomySetPointInHeatRange 41...95°F (5...35°C); default 50°F (10°C)°FWrite
AV13OccupancyEffectiveHVACRead0 - Occupied, 2-Unoccupied (AV#14=1), 3-Unoccupied (AV#14=2), 4-Unoccupied (AV#14=3)
AV14OccupancySensorFunctionDefault 0-Not usedWrite0-Not used, 1-On/Off, 2-Start/Stop, 3-Economy
AV15OccupancySensorHVACDelayTimeRange 0...900 min; default 20 minminWrite
AV17T2_EffectiveRange -9.9...210°F (-9.9...99°C)°FRead
AV18T3_EffectiveRange -9.9...210°F (-9.9...99°C)°FRead
AV19CoolFanOnDelayRange 0...120 sec; default 0 secsWrite
AV20CoolFanOffDelayRange 0...120 sec; default 0 secsWrite
AV21HeatFanOnDelayRange 0...120 sec; default 0 secsWrite
AV22HeatFanOffDelayRange 0...120 sec; default 30 secsWrite
AV23FreezeProtectionCutInSetpointRange 46...59°F (8…15°C); default 46°F (8°C)°FWrite
AV24FreezeProtectionCutOutSetpointRange 50...63°F (10…17°C); default 50°F (10°C)°FWrite
AV27CoolDifferentialBandRange 1...9°F (0.5...5°C); default 2°F (1°C)°FWrite
AV28CoolDifferentialBandOffsetRange -9...9°F (-5...5°C); default 0°F (0°C)°FWrite
AV31ShiftBetweenCoolAndHeatRange 0...18°F (0...10°C); default 4°F (2°C)°FWrite
AV33ShiftBetweenHeatStagesRange 0...88°F (0...49°C); default 4°F (2°C)°FWrite
AV36TimeDelayOnNextHeatStageRange 0...600 sec; default 5 secsWrite
AV46FanSoftStartInHeatCutInTemperatureRange 57...99°F (14...37°C); default 97°F (36°C)°FWrite
AV47FanSoftStartInHeatCutOutTemperatureRange 54...95°F (12...35°C); default 90°F (32°C)°FWrite
AV48DifferentialOnOffFanSpeedsRange 0.6...4°F (0.3...2°C); default 1.4°F (0.7°C)°FWrite
AV49OutputsThresholdTimeCoolRange 0...100 sec; default 60 secsWrite
AV50OutputsThresholdTimeHeatRange 0...100 sec; default 60 secsWrite
AV51Kp_PIDCoolRange 0...100; default 100Write
AV52Kp_PIDHeatRange 0...100; default 100Write
AV53Ki_PIDCoolRange 0...100; default 0Write
AV54Ki_PIDHeatRange 0...100; default 0Write
AV55Kd_PIDCoolRange 0...100; default 1Write
AV56Kd_PIDHeatRange 0...100; default 1Write
AV57CoolValveProportionalBandRange 2...18°F (1...10°C); default 4°F (2°C)°FWrite
AV58CoolProportionalLowLimitRange 0...100%; default 0%%Write
AV59CoolProportionalHighLimitRange 0...100%; default 100%%Write
AV60HeatValveProportionalBandRange 2...18°F (1...10°C); default 4°F (2°C)°FWrite
AV61HeatProportionalLowLimitRange 0...100%; default 0%%Write
AV62HeatProportionalHighLimitRange 0...100%; default 100%%Write
AV64ProportionalOnPercentRange 0...30%; default 30%%Write
AV65ProportionalOffPercentRange 0...20%; default 10%%Write
AV66CoolVFSProportionalBandRange 2...18°F (1...10°C); default 4°F (2°C)°FWrite
AV67HeatVFSProportionalBandRange 2...18°F (1...10°C); default 4°F (2°C)°FWrite
AV68CoolVFSLowSpeedPercentRange 0...100%; default 41%%Write
AV69CoolVFSMediumSpeedPercentRange 0...100%; default 50%%Write
AV70CoolVFSHighSpeedPercentRange 0...100%; default 55%%Write
AV71HeatVFSLowSpeedPercentRange 0...100%; default 41%%Write
AV72HeatVFSMediumSpeedPercentRange 0...100%; default 50%%Write
AV73HeatVFSHighSpeedPercentRange 0...100%; default 55%%Write
AV75VFSMediumSpeedDiffRange 1...100%; default 10%%Write
AV76VFSHighSpeedDiffRange 1...100%; default 10%%Write
AV77CoolVFSLowLimitRange 0...100%; default 41%%Write
AV78CoolVFSHighLimitRange 0...100%; default 55%%Write
AV79HeatVFSLowLimitRange 0...100%; default 41%%Write
AV80HeatVFSHighLimitRange 0...100%; default 55%%Write
AV113ModbusBaudRate (not in use)Range 0…4Write
AV133DipSwitchesState (SW2, SW3 configuration)Range 0...65535Read
BImin0DI_1Read1-Open: Fault all outputs off, 0-Close: normal work (if BV#39=1)
BI1DI2_OccupancySensorRead1-Open:Occupied, 0-Close: Unoccupied (if BV#40=1)
BI2DI_3Read0-Open, 1-Close (if BV#41=0)
BI3DI_4Read0-Open, 1-Close (if BV#42=0)
BO0Heat1Write1-On, 0-Off
BO1Heat2Write1-On, 0-Off
BO2Heat3Write1-On, 0-Off
BO3Cool1 (cool/heat valve)Write1-On, 0-Off
BO5FanOnOffLowWrite1-On, 0-Off
BO6FanOnOffMediumWrite1-On, 0-Off
BO7FanOnOffHighWrite1-On, 0-Off
BO12PumpOutWrite1-On, 0-Off
BO13SwingOutWrite1-On, 0-Off
BVmin0OnOffdefault 0-OffWrite1-On, 0-Off
BV1AutoFanInCooldefault 0-DisableWrite1-Enable, 0-Disable
BV2C_F_Scaledefault 0-FahrenheitWrite1-Celsius, 0-Fahrenheit
BV3LockFandefault 0-UnlockWrite1-Lock, 0-Unlock
BV4LockModedefault 0-UnlockWrite1-Lock, 0-Unlock
BV5LockOnOffdefault 0-UnlockWrite1-Lock, 0-Unlock
BV6LockSetpointdefault 0-UnlockWrite1-Lock, 0-Unlock
BV7One_TwoSetpointsdefault 0-one setpointWrite0-one setpoint, 1-two setpoints
BV10AutoModeEnabledefault 1-EnableWrite1-Enable, 0-Disable
BV11FreezeProtectionEnabledefault 1-EnableWrite1-Enable, 0-Disable
BV13RestoreDefaultdefault 0-NOPWrite1-Perform Restore, 0-NOP
BVmin16UnoccupiedByNetworkdefault 0-OffWrite1-Unoccupied, 0-Off
BV35TemperatureOverrideEnabledefault 0-DisableWrite1-Enable, 0-Disable
BV38AutoFanInHeatdefault 0-OffWrite1-On, 0-Off
BV39DI1_Polaritydefault 1-N. CloseWrite1-Normally close, 0-Normally open
BV40DI2_Polaritydefault 1-N. OpenWrite1-Normally open, 0-Normally close
BV41DI3_Polaritydefault 0-N. OpenWrite1-Normally close, 0-Normally open
BV42DI4_Polaritydefault 0-N. OpenWrite1-Normally close, 0-Normally open
BV47DisableOccupancySensordefault 0- Enable Occ. SensorWrite0-Enable Occ. sensor, 1-Disable Occ. sensor
BV48SelectModeInFCByDI3Enabledefault 0 - DisableWrite0-Disable DI3 in 2 pipe, 1-Enable DI3 in 2 pipe
BV54DisablePollingdefault 0 - EnableWrite0-Enable Polling after power break, 1-Disable Polling after power break
BV55SwingEnabledefault 0 - DisableWrite0-Swing out disable, 1-Swing out enable (according to controller logic)
Object ID lookup: Modine Chilled Water Ceiling Cassette Controller, Models SCW / CCW point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Chilled Water Ceiling Cassette Controller, Models SCW / CCW and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Modine Chilled Water Ceiling Cassette Controller, Models SCW / CCW

How many BACnet points does the Modine Chilled Water Ceiling Cassette Controller, Models SCW / CCW have?

This list has 105 BACnet objects: 3 analog inputs, 3 analog outputs, 64 analog values, 4 binary inputs, 9 binary outputs, 22 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Modine Chilled Water Ceiling Cassette Controller, Models SCW / CCW BACnet points are writable?

93 of the 105 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Modine Chilled Water Ceiling Cassette Controller, Models SCW / CCW BACnet documentation?

The source is Microprocessor Controls Manual for Chilled Water Cassettes, Models SCW & CCW (Model Digit 7 = C) (8-510.0), revision 2026-06, published free by Modine at https://modine.worksmartsuite.com/PORTAL/io_modules/IOGETIMAGE.php?type=stream&filename=8-510.pdf.

What are the minimum BACnet points to integrate the Modine Chilled Water Ceiling Cassette Controller, Models SCW / CCW?

Start with BV 0 OnOff (Unit on/off command (1 = on)); BV 16 UnoccupiedByNetwork (Network occupancy: 1 = unoccupied); AV 4 Mode (Mode: 0 fan, 1 cool, 2 heat, 3 auto); AV 6 FanSpeed (Fan speed: 0 auto, 1 low, 2 medium, 3 high); AV 0 SetPoint_SetPointCool (Cooling setpoint, 41-95 °F); AV 1 SetPointHeat (Heating setpoint, 41-95 °F); AV 5 ModeEffective (Active mode (4 = off)); AV 3 ReturnAirSensorEffective (Control (return air) temperature); AV 2 SetPointEffective (Active setpoint); BI 0 DI_1 (Alarm input: 1 = fault, all outputs off).

How do I enable BMS control of the Modine Chilled Water Ceiling Cassette Controller, Models SCW / CCW?

BV 0 OnOff switches the controller on or off (default off) from the BMS, the remote or the touchscreen. With an occupancy function set (AV 14), BV 16 UnoccupiedByNetwork = 1 puts the space unoccupied; it returns to occupied only when DI2 is open and BV 16 is 0. BV 47 disables the DI2 occupancy input so the BMS has sole control.

How do I check these points on the real Chilled Water Ceiling Cassette Controller, Models SCW / CCW?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Modine BACnet points lists

Source: Microprocessor Controls Manual for Chilled Water Cassettes, Models SCW & CCW (Model Digit 7 = C) · 8-510.0 · rev. 2026-06. Object names, instances and units are reproduced as published; descriptions are our own.