  4. Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3)

Packaged ventilation unit / make-up air controller (DOAS, energy recovery) · BACnet points list

Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3) BACnet points list

Updated 6 November 2026

Short answer

The Modine Control System is a Carel pCO3 controller in MPR packaged ventilation units, optionally with an ERM energy recovery module. A plug-in card gives BACnet IP/Ethernet or BACnet MS/TP (LonWorks and Modbus are other options). The BMS can switch the unit on and off, send an occupied command, reset alarms and write supply-air, neutral-air, dewpoint, humidity and CO2 setpoints. Readings cover temperatures, humidity, CO2, refrigerant circuit values, demands, damper and fan modulation, switch inputs, relay outputs and alarms.

This page lists 138 BACnet objects for the Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3) — 24 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Modine’s own free documentation, linked below.

Manufacturer
Modine
Model
Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3)
Equipment
Packaged ventilation unit / make-up air controller (DOAS, energy recovery)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
138 (24 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Modine Control System program version series 3 and 4
Also known as
MCP15-525, MCP15-525.0, 5H0837230000, Atherion, MPR, ERM, Modine Control System, Carel pCO3
Source document
Modine Control System Manual - Commercial Packaged Ventilation System, Models MPR and ERM · MCP15-525.0 · rev. 2012-09
Download CSV 138 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Modine’s current documentation and the live device before use. Not official Modine information. Terms of use.

BMS integration notes: Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3)

Integration in brief

Select BACnet IP/Ethernet or BACnet MS/TP in the BMS Configuration service menu and set the device instance and address there. Set Enable Unit On/Off to 'By Supervisor' so BV 41 Superv_OnOff starts and stops the unit, then use BV 38 for occupancy and write the supply-air setpoints. Monitor unit status (AV 1023), supply and space temperatures, the general alarm (BV 36) and the alarm codes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 41Superv_OnOffBMS on/off command (needs On/Off 'By Supervisor')Write
BV 38Occupied_BmsBMS occupied commandWrite
AV 15space_cl_sa_sp_ocOccupied supply air cooling setpointWrite
AV 16space_ht_sa_sp_ocOccupied supply air heating setpointWrite
BV 39BMS_ResetAlarm reset commandWrite
AV 1023UnitStatusUnit status code (1 = on, 2 = off by alarm, ...)Read
BV 3Supply_fan_swSupply fan airflow proving switchRead
AV 10supply_tempSupply air temperatureRead
BV 36General_AlarmGeneral alarmRead
AV 1030Alarm_CodeActive alarm code (1 of 3)Read

Enable & remote start

In Service > Service Settings > Control Settings, enable only one Unit On/Off source. 'By Supervisor' lets a BACnet or Lon network variable (BV 41 Superv_OnOff, on = active) cycle the unit; the other sources are digital input ID14, the pAD wall stat (pLAN) and the clock schedule.

Network setup

Watch out for

Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

138 of 138 shown
Type
AnalogBinary
Access
Show
Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3) BACnet Points List
DescriptionStates
AV1Ret_Air_HumReturn Air HumidityRead
AV2pAD_Temperature1Space TemperatureRead
AV3Build_PressBuilding PressureRead
AV4Mixed_tempMixed Air TemperatureRead
AV5return_tempReturn Air TemperatureRead
AV6LL_PressLiquid Line PressureRead
AV7OA_humOutside Air HumidityRead
AV8LP_sensorSuction Pressure SensorRead
AV9OA_TempOutside Air TemperatureRead
AVmin10supply_tempSupply TemperatureRead
AV11pAD_Setp_TemppAD Temperature SetpointWrite
AV12Static_PressureDuct Static PressureRead
AV13na_setptNeutral Air Temperature SetpointWrite
AV14OA_Dp_SpOutdoor Dewpoint SetpointWrite
AVmin15space_cl_sa_sp_ocSupply Air Cooling SetpointWrite
AVmin16space_ht_sa_sp_ocSupply Air Heating SetpointWrite
AV17space_ht_sa_sp_unocUnoccupied Heating SetpointWrite
AV18space_cl_sa_sp_unocCooling Unoccupied SetpointWrite
AV19NA_Heating_LockoutNA Heating ChangeoverWrite
AV20NA_Cooling_LockoutNA Cooling ChangeoverWrite
AV21LP_SpSuction Pressure SetpointWrite
AV22Ent_HumERM Entering (True Outside) HumidityRead
AV23Ent_TempERV Entering (ERM True Outside) TemperatureRead
AV24sa_setptActual Supply Air SetpointRead
AV25space_ht_spSpace Heating SetpointRead
AV26Heat_OffsetHeat setpoint = cool setpoint minus this differentialWrite
AV27Erv_Wheel_econ_lockOA temperature at which ERM economizer mode is disabledWrite
AV28Un_Dehum_DP_SPUnoccupied Dehum Dew Point Set PointWrite
AV29Sup_Fan_AdjSupply Fan Speed AdjustWrite
AV35LL_Press_TLiquid Line pressure converted to temperatureRead
AV36LL_tempLiquid Line TemperatureRead
AV37SubcoolSubcoolRead
AV38A10_SH_SHSuperheatRead
AV39Discharge_TempCompressor Discharge TemperatureRead
AV1001pAD_humSpace HumidityRead
AV1002pAD_Setp_HumidSpace Humidity SetpointWrite
AV1003CO2Space CO2 LevelRead
AV1004CO2_SPSpace CO2 SetpointWrite
AV1005Comp_mod_dispCompressor ModulationRead
AV1006Cond_fan_mod_dispCondenser Fan ModulationRead
AV1007HGRH_mod_dispHot Gas Reheat ModulationRead
AV1008Heat_mod_dispGas or Electric Heat ModulationRead
AV1009Supply_Fan_Mod_DispSupply Fan ModulationRead
AV1010Ex_Fan_Mod_DispExhaust Fan ModulationRead
AV1011AO1_pCOe_disp20kw Supplementary Electric Heat ModulationRead
AV1012ERV_Exh_Fan_Spd_DispERM Exhaust Fan ModulationRead
AV1013Wheel_Spd_DispERM Wheel ModulationRead
AV1014DamperOutside Air Damper PositionRead
AV1015Cooling_demand_dispCooling DemandRead
AV1016Dehum_Demand_dispDehumidification DemandRead
AV1017Heat_demand_dispHeat DemandRead
AV1018Min_damp_openOutside air damper minimum open positionWrite
AV1019ModeUnit modeRead0=Blank, 1=Venting, 2=Heating, 3=Cooling
AV1020ra_damperReturn Air Damper PositionRead
AV1021Occupied_dispOccupied DisplayRead
AV1022Enthalpy_LockoutCompressor enthalpy lockoutRead0=None, 1=Comp 1, 2=Comp 2, 3=Comp 1 and 2
AVmin1023UnitStatusUnit status codeRead1=Unit on, 2=Off by alarm, 3=Off by pLAN, 4=Off by BMS, 5=Off by clock, 6=Off by digital input, 7=Off by keypad, 10=Off by demand, 12=Off by open door, 15=Waiting for supply fan, 16=Waiting for damper
AV1024Comp1_Enth_Lock_OutCompressor 1 Enthalpy Lockout SetpointWrite
AV1025Comp2_Enthalpy_Lock_OutCompressor 2 Enthalpy Lockout SetpointWrite
AV1026Un_Dehum_Hum_SPSpace Unoccupied Dehum Humidity SetpointWrite
AV1027Heat_Cool_CO_DelayLoop Delay From Heating to CoolingWrite
AVmin1030Alarm_CodeAlarm Code Number variable 1Read
AV1031Alarm_Code_2Alarm Code Number variable 2Read
AV1032Alarm_Code_3Alarm Code Number variable 3Read
AV1080CURRENT_DAYCurrent dayRead
AV1081CURRENT_MONTHCurrent monthRead
AV1082CURRENT_YEARCurrent yearRead
AV1083CURRENT_HOURCurrent hourRead
AV1084CURRENT_MINUTECurrent minuteRead
BV1HP_swHigh Pressure SwitchRead
BV2LP_swLow Pressure SwitchRead
BVmin3Supply_fan_swSupply Fan Status SwitchRead
BV4Smoke_detector_swSmoke Detector SwitchRead
BV5Filter_swMain Filter Dirty SwitchRead
BV6Damper_end_swDamper End SwitchRead
BV7Occupied_swOccupied Switch (Digital Input)Read
BV8Digital_comp_swEC3 Controller Alarm SwitchRead
BV9Cond_float_swCondensate Pan Float SwitchRead
BV10Gas_valve1_swMain Gas Valve 1 On SwitchRead
BV11Gas_valve2_swMain Gas Valve 2 On SwitchRead
BV12Freeze_stat_swHot Water Coil Freeze Protection SwitchRead
BV13door_swSupply Fan Door SwitchRead
BV14Dig_In_OnOffUnit On - Off Control SwitchRead
BV15DI_Sup_Fan_Speed2Supply Fan Speed 2 SwitchRead
BV16DI_Sup_Fan_Speed3Supply Fan Speed 3 SwitchRead
BV17DX_Cooling_LockoutCompressor Locked OutRead
BV18Heating_LockoutHeating Locked OutRead
BV19Heat_3Heat 3 OutputRead
BV20Heat_4Heat 4 OutputRead
BV21C1_OnCompressor 1 OutputRead
BV22C2_OnCompressor 2 OutputRead
BV23oa_damper_openOutside Air Damper OpeningRead
BV24oa_damper_closeOutside Air Damper ClosingRead
BV25Supply_fan_outSupply Fan OutputRead
BV26Cond_fanCondenser Fan OutputRead
BV27Gas_Heat_1_OnHeat 1 OutputRead
BV28Gas_Heat_2_OnHeat 2 OutputRead
BV29HGRH_S2Hot Gas Reheat Stage 2 OutputRead
BV30ht_exh_fan_1Gas Heat 1 Exhaust Fan Hi Speed OutputRead
BV31ht_exh_fan_2Gas Heat 2 Exhaust Fan Hi Speed OutputRead
BV32HGRH_CVHot Gas Reheat Close Off Valve OutputRead
BV33ra_damper_openReturn Air Damper OpeningRead
BV34ra_damper_closeReturn Air Damper ClosingRead
BV35Ex_FanExhaust Fan OutputRead
BVmin36General_AlarmGeneral Alarm OutputRead
BV37OccupiedOccupied modeRead0=Unoccupied, 1=Occupied
BVmin38Occupied_BmsBMS occupied commandWrite
BVmin39BMS_ResetAlarm reset by BMS commandWrite
BV40Manual_OnOffUnit is in Manual ModeRead
BVmin41Superv_OnOffBMS on-off commandWrite
BV42Wheel_P_SWERM High Wheel Pressure Drop SwitchRead
BV43ERV_Filter_SWERM Filter Switch (Supply or Return)Read
BV44ERV_Exh_Fan_StatERM Exhaust Fan Status SwitchRead
BV45ERV_Door_SWERM Exhaust Fan Door SwitchRead
BV46Wheel_onERM Wheel OutputRead
BV47Bypass_DampERM By-Pass Damper OutputRead
BV48mERV_Filter_ALERM Filter AlarmRead
BV49ERV_Exh_Fan_EnERM Exhaust Fan OutputRead
BV50ERV_Preheater_EnERM Preheater OutputRead
BV51ERV_Wheel_StatusERM Wheel StatusRead
BV52mHP_alarmCompressor High Pressure AlarmRead
BV53mlp_alarmCompressor Low Pressure AlarmRead
BV54mSupply_fan_sw_alSupply Fan AlarmRead
BV55Sup_Fan_DSP_ALSupply Fan Duct Static Pressure AlarmRead
BV56mCFS_ALCondensate Pan Float Switch AlarmRead
BV57mGas_Valve1_alGas Valve 1 AlarmRead
BV58SA_Low_Limit_Temp_ALSupply air low limit: supply air did not rise above 36 °F (adj.) after blower startRead
BV59mGas_Valve2_alGas Valve 2 AlarmRead
BV60mSA_LockoutUnit Shut Down Due to Low Supply Air TemperatureRead
BV61mDCS_ALDigital Compressor Switch AlarmRead
BV62Exhaust_Fan_SwitchExhaust Fan Status SwitchRead
BV63DX_Cooling_Alarm_Unit_ShutdownCompressor Alarm Shuts Down UnitRead
BV64DX_Cooling_Alarm_Unit_SD_SelCompressor Alarm Shuts Down Unit SelectionRead
BV65mExh_Fan_ALExhaust Fan AlarmRead
BV66mExh_Fan_SDExhaust fan shutdown (latched)Read
BV67mWheel_ALWheel AlarmRead
BV68mWheel_SDWheel shutdown (latched)Read
BV69mWheel_Press_ALERM Wheel Pressure Drop AlarmRead
Object ID lookup: Modine Atherion Packaged Ventilation MPR / ERM point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3)

How many BACnet points does the Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3) have?

This list has 138 BACnet objects: 69 analog values, 69 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3) BACnet points are writable?

24 of the 138 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3) BACnet documentation?

The source is Modine Control System Manual - Commercial Packaged Ventilation System, Models MPR and ERM (MCP15-525.0), revision 2012-09, published free by Modine at https://modine.worksmartsuite.com/PORTAL/io_modules/IOGETIMAGE.php?type=stream&filename=MCP15-525.pdf.

What are the minimum BACnet points to integrate the Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3)?

Start with BV 41 Superv_OnOff (BMS on/off command (needs On/Off 'By Supervisor')); BV 38 Occupied_Bms (BMS occupied command); AV 15 space_cl_sa_sp_oc (Occupied supply air cooling setpoint); AV 16 space_ht_sa_sp_oc (Occupied supply air heating setpoint); BV 39 BMS_Reset (Alarm reset command); AV 1023 UnitStatus (Unit status code (1 = on, 2 = off by alarm, ...)); BV 3 Supply_fan_sw (Supply fan airflow proving switch); AV 10 supply_temp (Supply air temperature); BV 36 General_Alarm (General alarm); AV 1030 Alarm_Code (Active alarm code (1 of 3)).

How do I enable BMS control of the Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3)?

In Service > Service Settings > Control Settings, enable only one Unit On/Off source. 'By Supervisor' lets a BACnet or Lon network variable (BV 41 Superv_OnOff, on = active) cycle the unit; the other sources are digital input ID14, the pAD wall stat (pLAN) and the clock schedule.

How do I check these points on the real Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Modine BACnet points lists

Source: Modine Control System Manual - Commercial Packaged Ventilation System, Models MPR and ERM · MCP15-525.0 · rev. 2012-09. Object names, instances and units are reproduced as published; descriptions are our own.