- Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3)
Packaged ventilation unit / make-up air controller (DOAS, energy recovery) · BACnet points list
Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3) BACnet points list
Updated 6 November 2026
The Modine Control System is a Carel pCO3 controller in MPR packaged ventilation units, optionally with an ERM energy recovery module. A plug-in card gives BACnet IP/Ethernet or BACnet MS/TP (LonWorks and Modbus are other options). The BMS can switch the unit on and off, send an occupied command, reset alarms and write supply-air, neutral-air, dewpoint, humidity and CO2 setpoints. Readings cover temperatures, humidity, CO2, refrigerant circuit values, demands, damper and fan modulation, switch inputs, relay outputs and alarms.
This page lists 138 BACnet objects for the Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3) — 24 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Modine’s own free documentation, linked below.
- Manufacturer
- Modine
- Model
- Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3)
- Equipment
- Packaged ventilation unit / make-up air controller (DOAS, energy recovery)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 138 (24 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Modine Control System program version series 3 and 4
- Also known as
- MCP15-525, MCP15-525.0, 5H0837230000, Atherion, MPR, ERM, Modine Control System, Carel pCO3
Reference only, provided as-is: verify against Modine’s current documentation and the live device before use. Not official Modine information. Terms of use.
BMS integration notes: Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3)
Select BACnet IP/Ethernet or BACnet MS/TP in the BMS Configuration service menu and set the device instance and address there. Set Enable Unit On/Off to 'By Supervisor' so BV 41 Superv_OnOff starts and stops the unit, then use BV 38 for occupancy and write the supply-air setpoints. Monitor unit status (AV 1023), supply and space temperatures, the general alarm (BV 36) and the alarm codes.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 41 | Superv_OnOff | BMS on/off command (needs On/Off 'By Supervisor') | Write |
| BV 38 | Occupied_Bms | BMS occupied command | Write |
| AV 15 | space_cl_sa_sp_oc | Occupied supply air cooling setpoint | Write |
| AV 16 | space_ht_sa_sp_oc | Occupied supply air heating setpoint | Write |
| BV 39 | BMS_Reset | Alarm reset command | Write |
| AV 1023 | UnitStatus | Unit status code (1 = on, 2 = off by alarm, ...) | Read |
| BV 3 | Supply_fan_sw | Supply fan airflow proving switch | Read |
| AV 10 | supply_temp | Supply air temperature | Read |
| BV 36 | General_Alarm | General alarm | Read |
| AV 1030 | Alarm_Code | Active alarm code (1 of 3) | Read |
Enable & remote start
In Service > Service Settings > Control Settings, enable only one Unit On/Off source. 'By Supervisor' lets a BACnet or Lon network variable (BV 41 Superv_OnOff, on = active) cycle the unit; the other sources are digital input ID14, the pAD wall stat (pLAN) and the clock schedule.
Network setup
- Protocol is chosen in Service > BMS Configuration (password PW1): BACnet IP/Eth or BACnet MSTP, with Enable Plugin = Yes.
- Device instance range 0-99,000, set from the same menu; use Function = Write and Update = Yes to send settings to the card.
- BACnet IP: IP address, subnet, gateway and DNS are set in the menu.
- BACnet MS/TP: baud 9600, 19200, 38400 (default) or 76800; MAC 0-127; Max Masters and Max Info Frames are set in the menu.
Watch out for
- BV 41 only works when Unit On/Off is set to 'By Supervisor' and the other sources are off.
- Integer AVs start at 1001; do not confuse AV 1-39 (analog) with AV 1001+ (integer).
- Option-dependent points (ERM, compressors, heat stages) read 0 when the option is not fitted.
Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | Ret_Air_Hum | Return Air Humidity | Read | ||
| AV | 2 | pAD_Temperature1 | Space Temperature | Read | ||
| AV | 3 | Build_Press | Building Pressure | Read | ||
| AV | 4 | Mixed_temp | Mixed Air Temperature | Read | ||
| AV | 5 | return_temp | Return Air Temperature | Read | ||
| AV | 6 | LL_Press | Liquid Line Pressure | Read | ||
| AV | 7 | OA_hum | Outside Air Humidity | Read | ||
| AV | 8 | LP_sensor | Suction Pressure Sensor | Read | ||
| AV | 9 | OA_Temp | Outside Air Temperature | Read | ||
| AVmin | 10 | supply_temp | Supply Temperature | Read | ||
| AV | 11 | pAD_Setp_Temp | pAD Temperature Setpoint | Write | ||
| AV | 12 | Static_Pressure | Duct Static Pressure | Read | ||
| AV | 13 | na_setpt | Neutral Air Temperature Setpoint | Write | ||
| AV | 14 | OA_Dp_Sp | Outdoor Dewpoint Setpoint | Write | ||
| AVmin | 15 | space_cl_sa_sp_oc | Supply Air Cooling Setpoint | Write | ||
| AVmin | 16 | space_ht_sa_sp_oc | Supply Air Heating Setpoint | Write | ||
| AV | 17 | space_ht_sa_sp_unoc | Unoccupied Heating Setpoint | Write | ||
| AV | 18 | space_cl_sa_sp_unoc | Cooling Unoccupied Setpoint | Write | ||
| AV | 19 | NA_Heating_Lockout | NA Heating Changeover | Write | ||
| AV | 20 | NA_Cooling_Lockout | NA Cooling Changeover | Write | ||
| AV | 21 | LP_Sp | Suction Pressure Setpoint | Write | ||
| AV | 22 | Ent_Hum | ERM Entering (True Outside) Humidity | Read | ||
| AV | 23 | Ent_Temp | ERV Entering (ERM True Outside) Temperature | Read | ||
| AV | 24 | sa_setpt | Actual Supply Air Setpoint | Read | ||
| AV | 25 | space_ht_sp | Space Heating Setpoint | Read | ||
| AV | 26 | Heat_Offset | Heat setpoint = cool setpoint minus this differential | Write | ||
| AV | 27 | Erv_Wheel_econ_lock | OA temperature at which ERM economizer mode is disabled | Write | ||
| AV | 28 | Un_Dehum_DP_SP | Unoccupied Dehum Dew Point Set Point | Write | ||
| AV | 29 | Sup_Fan_Adj | Supply Fan Speed Adjust | Write | ||
| AV | 35 | LL_Press_T | Liquid Line pressure converted to temperature | Read | ||
| AV | 36 | LL_temp | Liquid Line Temperature | Read | ||
| AV | 37 | Subcool | Subcool | Read | ||
| AV | 38 | A10_SH_SH | Superheat | Read | ||
| AV | 39 | Discharge_Temp | Compressor Discharge Temperature | Read | ||
| AV | 1001 | pAD_hum | Space Humidity | Read | ||
| AV | 1002 | pAD_Setp_Humid | Space Humidity Setpoint | Write | ||
| AV | 1003 | CO2 | Space CO2 Level | Read | ||
| AV | 1004 | CO2_SP | Space CO2 Setpoint | Write | ||
| AV | 1005 | Comp_mod_disp | Compressor Modulation | Read | ||
| AV | 1006 | Cond_fan_mod_disp | Condenser Fan Modulation | Read | ||
| AV | 1007 | HGRH_mod_disp | Hot Gas Reheat Modulation | Read | ||
| AV | 1008 | Heat_mod_disp | Gas or Electric Heat Modulation | Read | ||
| AV | 1009 | Supply_Fan_Mod_Disp | Supply Fan Modulation | Read | ||
| AV | 1010 | Ex_Fan_Mod_Disp | Exhaust Fan Modulation | Read | ||
| AV | 1011 | AO1_pCOe_disp | 20kw Supplementary Electric Heat Modulation | Read | ||
| AV | 1012 | ERV_Exh_Fan_Spd_Disp | ERM Exhaust Fan Modulation | Read | ||
| AV | 1013 | Wheel_Spd_Disp | ERM Wheel Modulation | Read | ||
| AV | 1014 | Damper | Outside Air Damper Position | Read | ||
| AV | 1015 | Cooling_demand_disp | Cooling Demand | Read | ||
| AV | 1016 | Dehum_Demand_disp | Dehumidification Demand | Read | ||
| AV | 1017 | Heat_demand_disp | Heat Demand | Read | ||
| AV | 1018 | Min_damp_open | Outside air damper minimum open position | Write | ||
| AV | 1019 | Mode | Unit mode | Read | 0=Blank, 1=Venting, 2=Heating, 3=Cooling | |
| AV | 1020 | ra_damper | Return Air Damper Position | Read | ||
| AV | 1021 | Occupied_disp | Occupied Display | Read | ||
| AV | 1022 | Enthalpy_Lockout | Compressor enthalpy lockout | Read | 0=None, 1=Comp 1, 2=Comp 2, 3=Comp 1 and 2 | |
| AVmin | 1023 | UnitStatus | Unit status code | Read | 1=Unit on, 2=Off by alarm, 3=Off by pLAN, 4=Off by BMS, 5=Off by clock, 6=Off by digital input, 7=Off by keypad, 10=Off by demand, 12=Off by open door, 15=Waiting for supply fan, 16=Waiting for damper | |
| AV | 1024 | Comp1_Enth_Lock_Out | Compressor 1 Enthalpy Lockout Setpoint | Write | ||
| AV | 1025 | Comp2_Enthalpy_Lock_Out | Compressor 2 Enthalpy Lockout Setpoint | Write | ||
| AV | 1026 | Un_Dehum_Hum_SP | Space Unoccupied Dehum Humidity Setpoint | Write | ||
| AV | 1027 | Heat_Cool_CO_Delay | Loop Delay From Heating to Cooling | Write | ||
| AVmin | 1030 | Alarm_Code | Alarm Code Number variable 1 | Read | ||
| AV | 1031 | Alarm_Code_2 | Alarm Code Number variable 2 | Read | ||
| AV | 1032 | Alarm_Code_3 | Alarm Code Number variable 3 | Read | ||
| AV | 1080 | CURRENT_DAY | Current day | Read | ||
| AV | 1081 | CURRENT_MONTH | Current month | Read | ||
| AV | 1082 | CURRENT_YEAR | Current year | Read | ||
| AV | 1083 | CURRENT_HOUR | Current hour | Read | ||
| AV | 1084 | CURRENT_MINUTE | Current minute | Read | ||
| BV | 1 | HP_sw | High Pressure Switch | Read | ||
| BV | 2 | LP_sw | Low Pressure Switch | Read | ||
| BVmin | 3 | Supply_fan_sw | Supply Fan Status Switch | Read | ||
| BV | 4 | Smoke_detector_sw | Smoke Detector Switch | Read | ||
| BV | 5 | Filter_sw | Main Filter Dirty Switch | Read | ||
| BV | 6 | Damper_end_sw | Damper End Switch | Read | ||
| BV | 7 | Occupied_sw | Occupied Switch (Digital Input) | Read | ||
| BV | 8 | Digital_comp_sw | EC3 Controller Alarm Switch | Read | ||
| BV | 9 | Cond_float_sw | Condensate Pan Float Switch | Read | ||
| BV | 10 | Gas_valve1_sw | Main Gas Valve 1 On Switch | Read | ||
| BV | 11 | Gas_valve2_sw | Main Gas Valve 2 On Switch | Read | ||
| BV | 12 | Freeze_stat_sw | Hot Water Coil Freeze Protection Switch | Read | ||
| BV | 13 | door_sw | Supply Fan Door Switch | Read | ||
| BV | 14 | Dig_In_OnOff | Unit On - Off Control Switch | Read | ||
| BV | 15 | DI_Sup_Fan_Speed2 | Supply Fan Speed 2 Switch | Read | ||
| BV | 16 | DI_Sup_Fan_Speed3 | Supply Fan Speed 3 Switch | Read | ||
| BV | 17 | DX_Cooling_Lockout | Compressor Locked Out | Read | ||
| BV | 18 | Heating_Lockout | Heating Locked Out | Read | ||
| BV | 19 | Heat_3 | Heat 3 Output | Read | ||
| BV | 20 | Heat_4 | Heat 4 Output | Read | ||
| BV | 21 | C1_On | Compressor 1 Output | Read | ||
| BV | 22 | C2_On | Compressor 2 Output | Read | ||
| BV | 23 | oa_damper_open | Outside Air Damper Opening | Read | ||
| BV | 24 | oa_damper_close | Outside Air Damper Closing | Read | ||
| BV | 25 | Supply_fan_out | Supply Fan Output | Read | ||
| BV | 26 | Cond_fan | Condenser Fan Output | Read | ||
| BV | 27 | Gas_Heat_1_On | Heat 1 Output | Read | ||
| BV | 28 | Gas_Heat_2_On | Heat 2 Output | Read | ||
| BV | 29 | HGRH_S2 | Hot Gas Reheat Stage 2 Output | Read | ||
| BV | 30 | ht_exh_fan_1 | Gas Heat 1 Exhaust Fan Hi Speed Output | Read | ||
| BV | 31 | ht_exh_fan_2 | Gas Heat 2 Exhaust Fan Hi Speed Output | Read | ||
| BV | 32 | HGRH_CV | Hot Gas Reheat Close Off Valve Output | Read | ||
| BV | 33 | ra_damper_open | Return Air Damper Opening | Read | ||
| BV | 34 | ra_damper_close | Return Air Damper Closing | Read | ||
| BV | 35 | Ex_Fan | Exhaust Fan Output | Read | ||
| BVmin | 36 | General_Alarm | General Alarm Output | Read | ||
| BV | 37 | Occupied | Occupied mode | Read | 0=Unoccupied, 1=Occupied | |
| BVmin | 38 | Occupied_Bms | BMS occupied command | Write | ||
| BVmin | 39 | BMS_Reset | Alarm reset by BMS command | Write | ||
| BV | 40 | Manual_OnOff | Unit is in Manual Mode | Read | ||
| BVmin | 41 | Superv_OnOff | BMS on-off command | Write | ||
| BV | 42 | Wheel_P_SW | ERM High Wheel Pressure Drop Switch | Read | ||
| BV | 43 | ERV_Filter_SW | ERM Filter Switch (Supply or Return) | Read | ||
| BV | 44 | ERV_Exh_Fan_Stat | ERM Exhaust Fan Status Switch | Read | ||
| BV | 45 | ERV_Door_SW | ERM Exhaust Fan Door Switch | Read | ||
| BV | 46 | Wheel_on | ERM Wheel Output | Read | ||
| BV | 47 | Bypass_Damp | ERM By-Pass Damper Output | Read | ||
| BV | 48 | mERV_Filter_AL | ERM Filter Alarm | Read | ||
| BV | 49 | ERV_Exh_Fan_En | ERM Exhaust Fan Output | Read | ||
| BV | 50 | ERV_Preheater_En | ERM Preheater Output | Read | ||
| BV | 51 | ERV_Wheel_Status | ERM Wheel Status | Read | ||
| BV | 52 | mHP_alarm | Compressor High Pressure Alarm | Read | ||
| BV | 53 | mlp_alarm | Compressor Low Pressure Alarm | Read | ||
| BV | 54 | mSupply_fan_sw_al | Supply Fan Alarm | Read | ||
| BV | 55 | Sup_Fan_DSP_AL | Supply Fan Duct Static Pressure Alarm | Read | ||
| BV | 56 | mCFS_AL | Condensate Pan Float Switch Alarm | Read | ||
| BV | 57 | mGas_Valve1_al | Gas Valve 1 Alarm | Read | ||
| BV | 58 | SA_Low_Limit_Temp_AL | Supply air low limit: supply air did not rise above 36 °F (adj.) after blower start | Read | ||
| BV | 59 | mGas_Valve2_al | Gas Valve 2 Alarm | Read | ||
| BV | 60 | mSA_Lockout | Unit Shut Down Due to Low Supply Air Temperature | Read | ||
| BV | 61 | mDCS_AL | Digital Compressor Switch Alarm | Read | ||
| BV | 62 | Exhaust_Fan_Switch | Exhaust Fan Status Switch | Read | ||
| BV | 63 | DX_Cooling_Alarm_Unit_Shutdown | Compressor Alarm Shuts Down Unit | Read | ||
| BV | 64 | DX_Cooling_Alarm_Unit_SD_Sel | Compressor Alarm Shuts Down Unit Selection | Read | ||
| BV | 65 | mExh_Fan_AL | Exhaust Fan Alarm | Read | ||
| BV | 66 | mExh_Fan_SD | Exhaust fan shutdown (latched) | Read | ||
| BV | 67 | mWheel_AL | Wheel Alarm | Read | ||
| BV | 68 | mWheel_SD | Wheel shutdown (latched) | Read | ||
| BV | 69 | mWheel_Press_AL | ERM Wheel Pressure Drop Alarm | Read |
No points match these filters.
Object ID lookup: Modine Atherion Packaged Ventilation MPR / ERM point IDs by name
AV1Ret_Air_HumAV2pAD_Temperature1AV3Build_PressAV4Mixed_tempAV5return_tempAV6LL_PressAV7OA_humAV8LP_sensorAV9OA_TempAV10supply_tempAV11pAD_Setp_TempAV12Static_PressureAV13na_setptAV14OA_Dp_SpAV15space_cl_sa_sp_ocAV16space_ht_sa_sp_ocAV17space_ht_sa_sp_unocAV18space_cl_sa_sp_unocAV19NA_Heating_LockoutAV20NA_Cooling_LockoutAV21LP_SpAV22Ent_HumAV23Ent_TempAV24sa_setptAV25space_ht_spAV26Heat_OffsetAV27Erv_Wheel_econ_lockAV28Un_Dehum_DP_SPAV29Sup_Fan_AdjAV35LL_Press_TAV36LL_tempAV37SubcoolAV38A10_SH_SHAV39Discharge_TempAV1001pAD_humAV1002pAD_Setp_HumidAV1003CO2AV1004CO2_SPAV1005Comp_mod_dispAV1006Cond_fan_mod_dispAV1007HGRH_mod_dispAV1008Heat_mod_dispAV1009Supply_Fan_Mod_DispAV1010Ex_Fan_Mod_DispAV1011AO1_pCOe_dispAV1012ERV_Exh_Fan_Spd_DispAV1013Wheel_Spd_DispAV1014DamperAV1015Cooling_demand_dispAV1016Dehum_Demand_dispAV1017Heat_demand_dispAV1018Min_damp_openAV1019ModeAV1020ra_damperAV1021Occupied_dispAV1022Enthalpy_LockoutAV1023UnitStatusAV1024Comp1_Enth_Lock_OutAV1025Comp2_Enthalpy_Lock_OutAV1026Un_Dehum_Hum_SPAV1027Heat_Cool_CO_DelayAV1030Alarm_CodeAV1031Alarm_Code_2AV1032Alarm_Code_3AV1080CURRENT_DAYAV1081CURRENT_MONTHAV1082CURRENT_YEARAV1083CURRENT_HOURAV1084CURRENT_MINUTEBV1HP_swBV2LP_swBV3Supply_fan_swBV4Smoke_detector_swBV5Filter_swBV6Damper_end_swBV7Occupied_swBV8Digital_comp_swBV9Cond_float_swBV10Gas_valve1_swBV11Gas_valve2_swBV12Freeze_stat_swBV13door_swBV14Dig_In_OnOffBV15DI_Sup_Fan_Speed2BV16DI_Sup_Fan_Speed3BV17DX_Cooling_LockoutBV18Heating_LockoutBV19Heat_3BV20Heat_4BV21C1_OnBV22C2_OnBV23oa_damper_openBV24oa_damper_closeBV25Supply_fan_outBV26Cond_fanBV27Gas_Heat_1_OnBV28Gas_Heat_2_OnBV29HGRH_S2BV30ht_exh_fan_1BV31ht_exh_fan_2BV32HGRH_CVBV33ra_damper_openBV34ra_damper_closeBV35Ex_FanBV36General_AlarmBV37OccupiedBV38Occupied_BmsBV39BMS_ResetBV40Manual_OnOffBV41Superv_OnOffBV42Wheel_P_SWBV43ERV_Filter_SWBV44ERV_Exh_Fan_StatBV45ERV_Door_SWBV46Wheel_onBV47Bypass_DampBV48mERV_Filter_ALBV49ERV_Exh_Fan_EnBV50ERV_Preheater_EnBV51ERV_Wheel_StatusBV52mHP_alarmBV53mlp_alarmBV54mSupply_fan_sw_alBV55Sup_Fan_DSP_ALBV56mCFS_ALBV57mGas_Valve1_alBV58SA_Low_Limit_Temp_ALBV59mGas_Valve2_alBV60mSA_LockoutBV61mDCS_ALBV62Exhaust_Fan_SwitchBV63DX_Cooling_Alarm_Unit_ShutdownBV64DX_Cooling_Alarm_Unit_SD_SelBV65mExh_Fan_ALBV66mExh_Fan_SDBV67mWheel_ALBV68mWheel_SDBV69mWheel_Press_AL
Integration notes
- Object names here are the Carel variable names printed in the manual; the BACnet column gives only the object address (AVn / BVn). Check the names your BACnet card reports.
- Carel analog variables are AV 1-39, Carel integer variables are AV 1001-1084 and digital variables are BV 1-69.
- The manual titles the table 'Typical BMS / EMS / BAS System Variables'; ERM, compressor, gas and electric heat points only carry data when those options are fitted.
- Engineering units are not printed in the table.
- The manual swaps the LonWorks variables on BV 4 (smoke) and BV 5 (filter); the BACnet descriptions are shown as printed.
- Source table: manual pages 87-94 (138 objects).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3)
How many BACnet points does the Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3) have?
This list has 138 BACnet objects: 69 analog values, 69 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3) BACnet points are writable?
24 of the 138 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3) BACnet documentation?
The source is Modine Control System Manual - Commercial Packaged Ventilation System, Models MPR and ERM (MCP15-525.0), revision 2012-09, published free by Modine at https://modine.worksmartsuite.com/PORTAL/io_modules/IOGETIMAGE.php?type=stream&filename=MCP15-525.pdf.
What are the minimum BACnet points to integrate the Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3)?
Start with BV 41 Superv_OnOff (BMS on/off command (needs On/Off 'By Supervisor')); BV 38 Occupied_Bms (BMS occupied command); AV 15 space_cl_sa_sp_oc (Occupied supply air cooling setpoint); AV 16 space_ht_sa_sp_oc (Occupied supply air heating setpoint); BV 39 BMS_Reset (Alarm reset command); AV 1023 UnitStatus (Unit status code (1 = on, 2 = off by alarm, ...)); BV 3 Supply_fan_sw (Supply fan airflow proving switch); AV 10 supply_temp (Supply air temperature); BV 36 General_Alarm (General alarm); AV 1030 Alarm_Code (Active alarm code (1 of 3)).
How do I enable BMS control of the Modine Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3)?
In Service > Service Settings > Control Settings, enable only one Unit On/Off source. 'By Supervisor' lets a BACnet or Lon network variable (BV 41 Superv_OnOff, on = active) cycle the unit; the other sources are digital input ID14, the pAD wall stat (pLAN) and the clock schedule.
How do I check these points on the real Atherion Packaged Ventilation MPR / ERM (Modine Control System, pCO3)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Modine BACnet points lists
- Gas-fired unit heater BMS board
Modine BMS Board for Gas-Fired Unit Heaters (PTP/BTP, PTC/BTC, PTS/BTS, PDP/BDP)
Modine PTP/BTP, PTC/BTC, PTS/BTS and PDP/BDP gas-fired unit heaters fitted with the factory BMS board.
Also known as: 6-520, 6-520.3, 5H0827570000, PTP, BTP, PTC, BTC, PTS, BTS, PDP, BDP, BAC_HBB2, Modine BMS board - Chilled water ceiling cassette (fan coil) controller
Modine Chilled Water Ceiling Cassette Controller, Models SCW / CCW
Modine SCW and CCW ductless chilled water ceiling cassettes, model digit 7 = C, with the factory microprocessor controller.
Also known as: 8-510, 8-510.0, 5H1067400000, SCW, CCW, Modine cassette controller - Self-contained vertical unit ventilator controller (classroom)
Modine ClassMate / SchoolMate Vertical Unit Ventilators (Modine Controls System, pCOOEM+)
Modine ClassMate (CMD/CMP/CMS) and SchoolMate (SMG/SMW) vertical classroom units running Modine Controls System program series 1.
Also known as: AIR74-525, AIR74-525.1, 5H1046210000, ClassMate, SchoolMate, CMD, CMP, CMS, SMG, SMW, Carel pCOOEM+ - Direct-fired make-up air unit controller
Modine Direct-Fired Make-Up Air MCV/MVV, DCV/DVV (Distech ECB/ECL-403)
Modine MCV/MVV and DCV/DVV direct-fired make-up air units with model digit 14 = L or M and the Distech ECB/ECL-403 controller.
Also known as: 7-514, 7-514.1, 5H0880010000, MCV, MVV, DCV, DVV, ECB-403, ECL-403, Distech ECB-403, Allure EC Smart-Vue - Indirect gas-fired heating and make-up air unit controller
Modine Indirect Gas-Fired Heating & Make-Up Air, Series D/H/I/O (Modine Controls System, pCOOEM+)
Modine indirect gas-fired heating and make-up air units, model series D, H, I and O, with the Modine Controls System (Carel pCOOEM+ medium controller).
Also known as: 74-510, 74-510.1, 5H0880420000, Modine Controls System, Carel pCOOEM+, Series D, Series H, Series I, Series O
Source: Modine Control System Manual - Commercial Packaged Ventilation System, Models MPR and ERM · MCP15-525.0 · rev. 2012-09. Object names, instances and units are reproduced as published; descriptions are our own.